Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:13:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1364.47 | 594.80 | 594.80 |
Net Site Energy | 1364.47 | 594.80 | 594.80 |
Total Source Energy | 4127.07 | 1799.08 | 1799.08 |
Net Source Energy | 4127.07 | 1799.08 | 1799.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 7.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 531.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 325.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 159.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.40 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1271.23 | 93.24 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 7.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 531.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 325.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 59.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 159.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 85.40 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 167.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 301.14 | 40.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 554.16 | 40.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 167.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 301.14 | 40.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 554.16 | 40.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1271.234 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1271.234 | 100.00 |
Total On-Site and Utility Electric Sources | 1271.234 | 100.00 |
Total Electricity End Uses | 1271.234 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 505.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 6.8133 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 15.4032 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.4032 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.4032 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 8.7188 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 13.9457 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 13.9457 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-15:00 | 02-JAN-07:10 | - | - | - | 01-MAY-11:09 |
Heating | 0.00 | 101679.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 75401.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 22946.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14085.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 123204.38 | 103541.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 101679.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 75401.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 22946.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14085.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 8.50 | 0.00 | 0.00 | 0.00 |
Cooling | 1682.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1031.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 188.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 505.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.57 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4026.00 | 101.07 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.71 | 0.00 | 0.00 | 0.00 |
Cooling | 733.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 449.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.35 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1755.02 | 44.06 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.71 | 0.00 | 0.00 | 0.00 |
Cooling | 733.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 449.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 82.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.35 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1755.02 | 44.06 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.28 |
CORE_RETAIL DIRECT AIR | 8.00 |
POINT_OF_SALE DIRECT AIR | 1.31 |
FRONT_RETAIL DIRECT AIR | 1.06 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.41 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.41 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 32011.49 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 55620.81 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 214175.49 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 32637.28 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 27069.96 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.28 | 2.28 | 2.28 | 2.28 | 2.28 | 2.28 | 1.00 | 1.00 | 2.28 |
PSZ-AC:2 | 8.00 | 8.00 | 8.00 | 8.00 | 8.14 | 8.14 | 1.00 | 0.983279 | 8.14 |
PSZ-AC:3 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
PSZ-AC:4 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.28 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.14 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.31 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.06 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.28 | 2.28 | 2.28 | 1.51 | 44873.78 | 55620.81 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.14 | 8.14 | 8.14 | 5.37 | 202018.46 | 214175.49 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 0.865427 | 29352.91 | 32637.28 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 0.702513 | 24762.78 | 27069.96 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.28 | 1.14 | 1.52 | 41817.81 | 44873.78 | 22436.89 | 22436.89 | 0.740899 | 0.740900 | 0.740900 | 0.740900 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.14 | 4.07 | 5.42 | 195817.80 | 202018.46 | 101009.23 | 101009.23 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.31 | 0.655625 | 0.874167 | 27534.97 | 29352.91 | 14676.45 | 14676.45 | 0.702873 | 0.702870 | 0.702870 | 0.702870 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.06 | 0.532205 | 0.709607 | 23310.59 | 24762.78 | 12381.39 | 12381.39 | 0.692602 | 0.692600 | 0.692600 | 0.692600 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.28 | 2445.03 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.14 | 13705.63 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1451.76 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1178.47 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 6.813 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.883 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 36.923 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 8.719 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.719 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2588.290 | 6.813 | 42.195 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2588.290 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 24652.487 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24652.487 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2322.950 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.950 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2322.950 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.950 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 104.625 | 8.719 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 104.625 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.9837 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8493 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | 0.31844121E-15 | 0.33891907E-16 | -0.14717764E-09 | -0.34085343E-17 |
25 | 8 | 0.21517510E-07 | 0.13210865E-12 | 0.37403321E-03 | -0.24466149E-09 |
26 | 7 | -0.12129356E-01 | 0.68855956E-08 | -0.22924263E-01 | 0.13791520E-03 |
27 | 6 | 0.40230169 | 0.24029480E-05 | 0.46949424 | -0.47118258E-02 |
28 | 5 | -5.1608121 | 0.89965799E-04 | -4.4213154 | 0.62814943E-01 |
29 | 4 | 32.871256 | 0.73775273E-03 | 21.362378 | -0.42037561 |
30 | 3 | -110.94624 | 0.16114037E-02 | -55.469893 | 1.5111496 |
31 | 2 | 196.85374 | 0.90819125E-03 | 77.733479 | -2.8963115 |
32 | 1 | -171.06207 | 0.97128343E-04 | -55.213590 | 2.7437919 |
33 | 0 | 57.057407 | 0.55402955E-06 | 15.565444 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 30 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 31 | 1 | VerySmooth | 5.108 | 0.600 | 0.461 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 26068.14000 | 31281.76800 | 1.90414 | 2.28497 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 16987.44552 | 20384.93462 | 0.72941 | 0.87529 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 91792.58915 | 110151.10698 | 6.66605 | 7.99925 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 49229.77115 | 59075.72538 | 2.08614 | 2.50337 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 14834.86077 | 17801.83293 | 1.09271 | 1.31125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 8314.91662 | 9977.89994 | 0.35884 | 0.43061 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 12090.22959 | 14508.27551 | 0.88701 | 1.06441 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 8319.53132 | 9983.43758 | 0.35904 | 0.43085 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00000 | 9.11023E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 26671.37100 | 32005.64519 | 1.17841 | 1.41409 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 32978.19 | 2.28497 | 2.28497 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 23755.65 | 0.87529 | 0.87529 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 138636.34 | 8.13528 | 8.13528 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 89088.98 | 2.50337 | 2.50337 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 20259.87 | 1.31125 | 1.31125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 12774.69 | 0.43061 | 0.43061 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 17387.54 | 1.06441 | 1.06441 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 12780.20 | 0.43085 | 0.43085 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.28497 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.99925 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.31125 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06441 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.41409 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.41409 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 32011.48819 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.28497 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28497 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.28497 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28497 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.28497 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.28497 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.99925 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.99925 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.99925 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.99925 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.13528 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.13528 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98328 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.31125 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.31125 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.31125 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.31125 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.31125 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.31125 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06441 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06441 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06441 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06441 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06441 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06441 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.28497 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.13528 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.31125 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.06441 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.28497 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.28497 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.28497 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.28497 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.50808 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.28497 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.14249 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.52331 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 41817.80686 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 44873.78000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 22436.89000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22436.89000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74090 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74090 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74090 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74090 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 44873.78000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55620.80669 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.28497 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2445.02869 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 55620.80669 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.13528 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.13528 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.13528 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.13528 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.36929 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.13528 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.06764 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.42352 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 195817.80182 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 202018.46000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 101009.23000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 101009.23000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 202018.46000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 214175.48633 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.13528 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13705.63114 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 214175.48633 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.31125 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.31125 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.31125 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.31125 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.86543 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.31125 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65563 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.87417 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27534.96605 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29352.91000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14676.45500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14676.45500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70287 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70287 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70287 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70287 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29352.91000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32637.28431 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.31125 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1451.76455 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32637.28431 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06441 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06441 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06441 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06441 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70251 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06441 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53221 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.70961 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23310.59202 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 24762.78000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12381.39000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12381.39000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69260 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69260 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69260 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69260 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24762.78000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27069.96411 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06441 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1178.47442 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27069.96411 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 43078.6 | 11.33 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 195600.4 | 13.25 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 28320.5 | 110.84 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 23924.1 | 143.85 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 4.4732879886E-002 | 0.1556490003 | Pass | Pass | 9.0446297002E-002 | 0.2279543192 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.3055181572E-002 | 0.1092185318 | Pass | Pass | 0.1529647038 | 0.5459037071 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 6.1366600860E-002 | 0.1181982271 | Pass | Pass | 0.3868668604 | 3.0095669295 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 5.0085171963E-002 | 0.1195452070 | Pass | Pass | 0.1551598369 | 0.5959206778 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 9.0160622549E-002 | 0.3885506179 | Pass | Pass | 6.7767090913E-002 | 0.4794478610 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.843 | 0.252 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.343 | 0.329 | 0.328 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.343 | 0.329 | 0.328 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 6.8133 | 379.89 | 2588.29 | LightsWired | BLDG_LIGHT_BACK_SCH | 60.89 | 168.00 | 60.06 | 0.0000 | Y | 29.18 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 15.4032 | 1600.48 | 24652.49 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 50.90 | 0.0000 | Y | 235.54 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 15.4032 | 150.81 | 2322.95 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 15.4032 | 150.81 | 2322.95 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 8.7188 | 12.00 | 104.63 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.34 |
Interior Lighting Total | 13.9457 | 2293.99 | 31991.30 | 325.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.49 | 6163.12 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.49 | 6163.12 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 238.00 | AstronomicalClock | - | 41.75 | 41.75 | 1.87 | |
EXTERIOR_LIGHTS_B | 4328.05 | AstronomicalClock | - | 83.75 | 71.15 | 57.81 | |
Exterior Lighting Total | 4566.05 | 59.67 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 44873.78 | 33246.98 | 11626.80 | 0.74 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 202018.46 | 136580.64 | 65437.82 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29352.91 | 20631.28 | 8721.63 | 0.70 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 24762.78 | 17150.70 | 7612.08 | 0.69 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 43078.6 | 11.33 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 195600.4 | 13.25 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 28320.5 | 110.84 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 23924.1 | 143.85 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 32011.49 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 55620.81 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 214175.49 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32637.28 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27069.96 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 1.41 | 1565.63 | 1107.16 | 1.00 | 1.31 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.28 | 2445.03 | 1070.05 | 1.00 | 1.30 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.14 | 13705.63 | 1684.71 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1451.76 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1178.47 | 1107.16 | 1.00 | 1.39 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 26068.14 | 31281.77 | 82.34 | 1.904 | 2.285 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00772 | 34.82 | 0.00911 | 0.232 | 0.00 |
CORE_RETAIL | 91792.59 | 110151.11 | 68.82 | 6.666 | 7.999 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00803 | 34.82 | 0.00911 | 1.890 | 0.00 |
POINT_OF_SALE | 14834.86 | 17801.83 | 118.04 | 1.093 | 1.311 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00740 | 34.82 | 0.00911 | 0.178 | 0.00 |
FRONT_RETAIL | 12090.23 | 14508.28 | 96.20 | 0.887 | 1.064 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00756 | 34.82 | 0.00911 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 40.91 | 100.00 | 0.00001 | 42.00 | 0.00911 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 16987.45 | 20384.93 | 53.66 | 0.729 | 0.875 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00792 | 6.30 | 0.00607 | 0.232 | 0.00 |
CORE_RETAIL | 49229.77 | 59075.73 | 36.91 | 2.086 | 2.503 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00797 | 6.30 | 0.00607 | 1.890 | 0.00 |
POINT_OF_SALE | 8314.92 | 9977.90 | 66.16 | 0.359 | 0.431 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00793 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_RETAIL | 8319.53 | 9983.44 | 66.20 | 0.359 | 0.431 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00793 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_ENTRY | 26671.37 | 32005.65 | 2667.14 | 1.178 | 1.414 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.09 | 0.00693 | 6.30 | 0.00607 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.28 | 2.28 | 0.88 | 0.88 | 2.2850 | 2.2850 | 2.2850 | 1.0000 | 1.0000 |
PSZ-AC:2 | 8.14 | 8.14 | 2.50 | 2.50 | 8.1353 | 7.9993 | 8.1353 | 0.9833 | 1.0000 |
PSZ-AC:3 | 1.31 | 1.31 | 0.43 | 0.43 | 1.3113 | 1.3113 | 1.3113 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.06 | 1.06 | 0.43 | 0.43 | 1.0644 | 1.0644 | 1.0644 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 32011.488 | 32011.488 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32011.49 | 32011.49 | 1.414094 | 20.94 | 13.56 | 0.00692002 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.09 | 0.00692861 | 43.5024 | 32005.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 22436.890 | 0.000 | 2.284970 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 22436.89 | 19869.81 | 2.284970 | 25.04 | 15.93 | 0.00786107 | 12.80 | 10.33 | 0.00700000 | 34.82 | 0.00911022 | 20.12 | 10.1343 | 23.89 | 0.00772021 | 40.8367 | 26068.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 55620.807 | 55620.807 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 55620.81 | 55620.81 | 2.284973 | 16.99 | 12.50 | 0.00742884 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 10.1343 | 21.11 | 0.00791680 | 49.5593 | 16987.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 101009.230 | 0.000 | 8.135280 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 101009.23 | 89315.54 | 8.135280 | 28.42 | 17.25 | 0.00804683 | 12.80 | 10.33 | 0.00700000 | 41.92 | 0.00911022 | 22.18 | 23.2347 | 23.89 | 0.00803019 | 42.4581 | 83090.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 214175.486 | 214175.486 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 214175.49 | 214175.49 | 8.135283 | 9.83 | 8.51 | 0.00653818 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 23.2347 | 21.11 | 0.00797424 | 49.9139 | 49229.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 14676.455 | 0.000 | 1.311250 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 14676.45 | 13482.77 | 1.311250 | 26.45 | 16.23 | 0.00763949 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 13.5833 | 23.89 | 0.00740188 | 39.1704 | 13889.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 32637.284 | 32637.284 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32637.28 | 32637.28 | 1.311252 | 14.85 | 11.37 | 0.00716435 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.5832 | 21.11 | 0.00793464 | 49.6696 | 8314.92 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 12381.390 | 0.000 | 1.064410 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 12381.39 | 11233.47 | 1.064410 | 26.99 | 16.52 | 0.00775992 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 16.7333 | 23.89 | 0.00755557 | 39.9751 | 11465.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 27069.964 | 27069.964 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27069.96 | 27069.96 | 1.064413 | 14.85 | 11.37 | 0.00716482 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.7332 | 21.11 | 0.00793471 | 49.6700 | 8319.53 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 32011.488 | 32011.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.414094 | 1.65984353 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32011.49 | 32011.49 | 1.0000 | 1.65984353 | 1.414094 | 20.94 | 13.56 | 0.00692002 | 38616.0 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32011.49 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.09 | 0.00692861 | 21.09 | 0.00692861 | 43.5024 | 32005.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22436.890 | 0.000 | 2.284970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4533 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 22436.89 | 19869.81 | 1.0000 | 2.68206456 | 2.284970 | 25.04 | 15.93 | 0.00786107 | 45183.5 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22436.89 | 34.82 | 0.00911022 | 20.12 | 0.23156651 | 10.1343 | 23.93 | 0.00772021 | 23.89 | 0.00772021 | 40.8367 | 26068.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55620.807 | 55620.807 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.284973 | 2.68206761 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 55620.81 | 55620.81 | 1.0000 | 2.68206761 | 2.284973 | 16.99 | 12.50 | 0.00742884 | 35885.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55620.81 | 6.30 | 0.00607234 | 6.30 | 0.23156651 | 10.1343 | 20.84 | 0.00791680 | 21.11 | 0.00791680 | 49.5593 | 16987.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 101009.230 | 0.000 | 8.135280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7986 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 101009.23 | 89315.54 | 1.0000 | 9.54907338 | 8.135280 | 28.42 | 17.25 | 0.00804683 | 49103.3 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101009.23 | 41.92 | 0.00911022 | 22.18 | 1.89021192 | 23.2347 | 23.89 | 0.00769022 | 23.89 | 0.00803019 | 42.4581 | 83090.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 214175.486 | 214175.486 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.135283 | 9.54907744 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 214175.49 | 214175.49 | 1.0000 | 9.54907744 | 8.135283 | 9.83 | 8.51 | 0.00653818 | 26346.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 214175.49 | 6.30 | 0.00607234 | 6.30 | 1.89021192 | 23.2347 | 20.70 | 0.00797424 | 21.11 | 0.00797424 | 49.9139 | 49229.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14676.455 | 0.000 | 1.311250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0414 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 14676.45 | 13482.77 | 1.0000 | 1.53912618 | 1.311250 | 26.45 | 16.23 | 0.00763949 | 46061.7 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14676.45 | 42.00 | 0.00911023 | 22.20 | 0.17811053 | 13.5833 | 23.89 | 0.00739696 | 23.89 | 0.00740188 | 39.1704 | 13889.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32637.284 | 32637.284 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.311252 | 1.53912900 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32637.28 | 32637.28 | 1.0000 | 1.53912900 | 1.311252 | 14.85 | 11.37 | 0.00716435 | 33035.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32637.28 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 13.5832 | 20.88 | 0.00793464 | 21.11 | 0.00793464 | 49.6696 | 8314.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12381.390 | 0.000 | 1.064410 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2653 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 12381.39 | 11233.47 | 1.0000 | 1.24938898 | 1.064410 | 26.99 | 16.52 | 0.00775992 | 46921.4 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12381.39 | 42.00 | 0.00911023 | 22.20 | 0.17811053 | 16.7333 | 23.89 | 0.00748041 | 23.89 | 0.00755557 | 39.9751 | 11465.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27069.964 | 27069.964 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.064413 | 1.24939279 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27069.96 | 27069.96 | 1.0000 | 1.24939279 | 1.064413 | 14.85 | 11.37 | 0.00716482 | 33039.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27069.96 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 16.7332 | 20.88 | 0.00793471 | 21.11 | 0.00793471 | 49.6700 | 8319.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3035.83 | 1136.67 | 91.50 |
CORE_RETAIL | 3408.00 | 1114.67 | 504.00 |
POINT_OF_SALE | 4022.00 | 308.33 | 63.50 |
FRONT_RETAIL | 3749.83 | 575.00 | 147.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4041.83 | 1556.17 | 505.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 3.17 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.17 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 3.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.32 | 61.34 | 2317.33 | 0.372 | 0.013 | 0.000 | 0.000 |
CORE_RETAIL | 127.72 | 258.43 | 9762.95 | 0.720 | 0.002 | 0.000 | 0.000 |
POINT_OF_SALE | 12.04 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
FRONT_RETAIL | 12.04 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.32 | 61.34 | 2317.33 | 0.339 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.72 | 258.43 | 9762.95 | 0.658 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.04 | 24.35 | 919.94 | 0.661 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.04 | 24.35 | 919.94 | 0.659 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1271.23 | 3189.30 | 05-MAR-08:00 | 123204.38 | 10-JUN-16:00 |
Electricity:Building | 520.74 | 2983.86 | 14-MAY-08:00 | 39264.11 | 02-JAN-16:20 |
Electricity:Zone:BACK_SPACE | 79.17 | 589.27 | 01-JAN-00:10 | 4789.50 | 02-JAN-09:10 |
InteriorLights:Electricity | 325.59 | 1188.69 | 14-MAY-08:00 | 28493.07 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:BACK_SPACE | 29.18 | 129.41 | 01-JAN-00:10 | 2030.36 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 325.59 | 1188.69 | 14-MAY-08:00 | 28493.07 | 02-JAN-16:20 |
Electricity:Zone:CORE_RETAIL | 319.84 | 1597.18 | 14-MAY-08:00 | 26839.84 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 235.54 | 821.75 | 14-MAY-08:00 | 22187.24 | 02-JAN-16:20 |
Electricity:Zone:POINT_OF_SALE | 82.68 | 602.96 | 01-JAN-00:10 | 5011.54 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 37.71 | 189.21 | 01-JAN-00:10 | 2529.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.34 | 5.23 | 01-JAN-00:10 | 94.16 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.34 | 5.23 | 01-JAN-00:10 | 94.16 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1271.23 | 3189.30 | 05-MAR-08:00 | 123204.38 | 10-JUN-16:00 |
ElectricityPurchased:Plant | 1271.23 | 3189.30 | 05-MAR-08:00 | 123204.38 | 10-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1271.23 | 3189.30 | 05-MAR-08:00 | 123204.38 | 10-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1271.23 | 3189.30 | 05-MAR-08:00 | 123204.38 | 10-JUN-16:00 |
ElectricityNet:Plant | 1271.23 | 3189.30 | 05-MAR-08:00 | 123204.38 | 10-JUN-16:00 |
Cogeneration:ElectricityNet | 1271.23 | 3189.30 | 05-MAR-08:00 | 123204.38 | 10-JUN-16:00 |
Electricity:HVAC | 690.82 | 0.00 | 01-JAN-00:10 | 89487.08 | 10-JUN-16:00 |
Fans:Electricity | 159.60 | 0.00 | 01-JAN-00:10 | 14776.27 | 04-JUL-08:10 |
General:Fans:Electricity | 159.60 | 0.00 | 01-JAN-00:10 | 14776.27 | 04-JUL-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 531.22 | 0.00 | 01-JAN-00:10 | 75401.59 | 10-JUN-16:00 |
ExteriorLights:Electricity | 59.67 | 0.00 | 01-JAN-07:20 | 4566.05 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 59.67 | 0.00 | 01-JAN-07:20 | 4566.05 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 93.24 | 1862.00 | 15-JAN-19:10 | 103541.68 | 02-JAN-07:10 |
Gas:Plant | 85.40 | 1862.00 | 15-JAN-19:10 | 4922.89 | 23-JAN-12:40 |
WaterSystems:Gas | 85.40 | 1862.00 | 15-JAN-19:10 | 4922.89 | 23-JAN-12:40 |
Water Heater:WaterSystems:Gas | 85.40 | 1862.00 | 15-JAN-19:10 | 4922.89 | 23-JAN-12:40 |
Gas:HVAC | 7.84 | 0.00 | 01-JAN-00:10 | 101679.68 | 02-JAN-07:10 |
Heating:Gas | 7.84 | 0.00 | 01-JAN-00:10 | 101679.68 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2946.91 | 0.00 | 01-JAN-00:10 | 357309.27 | 08-JUL-06:10 |
EnergyTransfer:Building | 1022.82 | 0.00 | 01-JAN-00:10 | 117316.19 | 12-JUN-06:10 |
EnergyTransfer:Zone:BACK_SPACE | 161.10 | 0.00 | 01-JAN-00:10 | 21520.57 | 05-JUL-06:10 |
Heating:EnergyTransfer | 9.25 | 0.00 | 01-JAN-00:10 | 64254.30 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.39 | 0.00 | 01-JAN-00:10 | 11873.58 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1013.57 | 0.00 | 01-JAN-00:10 | 113223.68 | 12-JUN-06:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 160.71 | 0.00 | 01-JAN-00:10 | 21520.57 | 05-JUL-06:10 |
EnergyTransfer:Zone:CORE_RETAIL | 625.95 | 0.00 | 01-JAN-00:10 | 76978.30 | 07-JUN-06:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 1.83 | 0.00 | 01-JAN-00:10 | 43045.92 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 624.12 | 0.00 | 01-JAN-00:10 | 71842.90 | 12-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 131.21 | 0.00 | 01-JAN-00:10 | 12872.44 | 02-OCT-14:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.09 | 0.00 | 01-JAN-00:10 | 3749.29 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 131.12 | 0.00 | 01-JAN-00:10 | 12872.44 | 02-OCT-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 97.77 | 0.00 | 01-JAN-00:10 | 10820.56 | 02-OCT-14:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.14 | 0.00 | 01-JAN-00:10 | 4956.78 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 97.63 | 0.00 | 01-JAN-00:10 | 10820.56 | 02-OCT-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 6.79 | 0.00 | 01-JAN-00:10 | 15108.77 | 31-DEC-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 6.79 | 0.00 | 01-JAN-00:10 | 15108.77 | 31-DEC-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1924.09 | 0.00 | 01-JAN-00:10 | 258347.91 | 18-JUL-06:10 |
HeatingCoils:EnergyTransfer | 6.27 | 0.00 | 01-JAN-00:10 | 81343.75 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 1917.81 | 0.00 | 01-JAN-00:10 | 258347.91 | 18-JUL-06:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.393 | -160.707 | 0.000 | 0.000 | 36.833 | 29.179 | 49.992 | 0.000 | 0.000 | 1.346 | 43.839 | 0.000 | 0.000 | 0.000 | -0.875 | -0.005 |
CORE_RETAIL | 0.000 | 0.000 | 1.834 | -624.106 | 0.000 | 0.000 | 155.203 | 235.542 | 84.299 | 86.255 | 0.000 | 1.145 | 74.626 | 0.000 | -14.042 | 0.000 | -0.755 | -0.001 |
POINT_OF_SALE | 0.000 | 0.000 | 0.092 | -131.116 | 0.000 | 0.000 | 14.574 | 29.762 | 52.922 | 35.829 | 0.000 | 0.545 | 7.143 | 0.000 | -9.312 | 0.000 | -0.441 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.140 | -97.624 | 0.000 | 0.000 | 14.610 | 29.762 | 7.943 | 35.871 | 0.000 | 0.569 | 18.001 | 0.000 | -8.869 | 0.000 | -0.403 | -0.000 |
FRONT_ENTRY | 6.790 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.340 | 0.000 | 6.401 | 0.000 | 4.169 | 0.000 | 0.000 | -1.930 | 0.000 | -10.376 | -6.394 |
Total Facility | 6.790 | 0.000 | 2.459 | -1013.553 | 0.000 | 0.000 | 221.220 | 325.586 | 195.156 | 164.356 | 0.000 | 7.774 | 143.610 | 0.000 | -34.153 | 0.000 | -12.850 | -6.400 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -40245.22 | 0.00 | 0.00 | 0.00 | 129.41 | 613.14 | 0.00 | 0.00 | 0.47 | 39502.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 08-APR-06:02 | 0.00 | 0.00 | 0.00 | -167336.81 | 0.00 | 0.00 | 1595.74 | 2465.25 | 1550.87 | 0.00 | 0.00 | 0.00 | 162278.92 | 0.00 | -543.46 | 0.00 | -10.51 | 0.00 |
POINT_OF_SALE | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -25957.84 | 0.00 | 0.00 | 0.00 | 116.15 | 649.09 | 0.00 | 0.00 | 0.05 | 25519.11 | 0.00 | -326.56 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -21791.77 | 0.00 | 0.00 | 0.00 | 116.15 | 97.42 | 0.00 | 0.00 | 0.14 | 21872.87 | 0.00 | -294.81 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -254694.77 | 0.00 | 0.00 | 0.00 | 1599.57 | 2393.56 | 0.00 | 0.00 | 1.17 | 252187.19 | 0.00 | -1486.65 | 0.00 | -0.06 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-JAN-08:62 | 0.00 | 0.00 | 41210.32 | 0.00 | 0.00 | 0.00 | 0.00 | 129.41 | 459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2.06 | -41797.53 |
CORE_RETAIL | 02-JAN-07:03 | 0.00 | 0.00 | 155935.19 | 0.00 | 0.00 | 0.00 | 2238.13 | 4930.50 | 2067.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1661.55 | 0.00 | 0.00 | -163510.09 |
POINT_OF_SALE | 02-JAN-07:03 | 0.00 | 0.00 | 13954.84 | 0.00 | 0.00 | 0.00 | 210.89 | 464.59 | 1298.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1243.88 | 0.00 | 0.00 | -14684.62 |
FRONT_RETAIL | 02-JAN-07:03 | 0.00 | 0.00 | 15701.53 | 0.00 | 0.00 | 0.00 | 210.89 | 464.59 | 194.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1225.11 | 0.00 | 0.00 | -15346.75 |
FRONT_ENTRY | 31-DEC-18:00 | 15110.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.85 | 0.00 | 0.00 | 0.00 | 0.00 | 624.64 | 0.00 | -222.29 | 0.00 | -15554.56 | 0.00 |
Total Facility | 02-JAN-07:03 | 818.19 | 0.00 | 225483.40 | 0.00 | 0.00 | 0.00 | 3191.16 | 6331.79 | 4787.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4382.48 | 0.00 | 0.00 | -236229.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.2850 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.2850 | 0.1013 | 1.0000 | 0.2316 | 0.1013 | ||
PSZ-AC:2 | 7.9993 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.1353 | 0.2323 | 1.0000 | 1.8902 | 0.2323 | ||
PSZ-AC:3 | 1.3113 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3113 | 0.1358 | 1.0000 | 0.1781 | 0.1358 | ||
PSZ-AC:4 | 1.0644 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0644 | 0.1673 | 1.0000 | 0.1781 | 0.1673 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.2850 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.2850 | 1.0000 | 1.0000 | 0.2316 | 0.1013 | ||
PSZ-AC:2 | 7.9993 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.9993 | 1.0000 | 1.0000 | 1.8902 | 0.2363 | ||
PSZ-AC:3 | 1.3113 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3113 | 1.0000 | 1.0000 | 0.1781 | 0.1358 | ||
PSZ-AC:4 | 1.0644 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0644 | 1.0000 | 1.0000 | 0.1781 | 0.1673 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.2850 | 2.2850 | 2.2850 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.9993 | 7.9993 | 7.9993 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3113 | 1.3113 | 1.3113 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0644 | 1.0644 | 1.0644 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.2850 | 2.2850 | 2.2850 | 2.2850 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.9993 | 8.1353 | 7.9993 | 7.9993 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3113 | 1.3113 | 1.3113 | 1.3113 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0644 | 1.0644 | 1.0644 | 1.0644 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.2850 | 2.2850 | 2.2850 | 0.2316 | 0.2646 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.9993 | 7.9993 | 7.9993 | 1.8902 | 0.7551 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3113 | 1.3113 | 1.3113 | 0.1781 | 0.4136 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0644 | 1.0644 | 1.0644 | 0.1781 | 0.4134 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.2850 | 2.2850 | 2.2850 | 2.2850 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.9993 | 7.9993 | 7.9993 | 7.9993 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3113 | 1.3113 | 1.3113 | 1.3113 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0644 | 1.0644 | 1.0644 | 1.0644 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 7.84 | 101679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 531.22 | 75401.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 325.59 | 28493.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 59.67 | 4566.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 159.60 | 14776.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.40 | 4922.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1271.23 |
Natural Gas | 0.00 | 93.24 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1364.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 141.93 |
Space Heating | 0.00 |
Space Cooling | 231.57 |
Fans (All) | 69.57 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 554.16 |
Subtotal | 554.16 |
Natural Gas [MJ/m2] | |
Space Heating | 3.42 |
Service Water Heating | 37.23 |
Miscellaneous (All) | 40.64 |
Subtotal | 40.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.86 |
Space Heating | 0.57 |
Space Cooling | 38.93 |
Fans (All) | 11.70 |
Service Water Heating | 6.26 |
Receptacle Equipment | 14.30 |
Miscellaneous | 4.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3175. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.551700E+10 |
February | 0.000 | 0.528268E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2168871.282 |
December | 0.000 | 0.179438E+10 |
Annual Sum or Average | 0.784182E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.551700E+10 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312921E+10 | 5354.24 | 14-JAN-16:10 | 21.20 | 15.00 | 0.208506E+10 | 2451.26 | 24-JAN-15:00 | 20.30 | 11.57 |
February | 0.472601E+10 | 7864.05 | 24-FEB-16:00 | 26.30 | 17.46 | 0.196850E+10 | 2451.28 | 21-FEB-15:50 | 26.13 | 15.60 |
March | 0.955712E+10 | 34880.78 | 29-MAR-06:02 | 21.15 | 17.30 | 0.228000E+10 | 2451.31 | 04-MAR-11:09 | 24.52 | 15.14 |
April | 0.151932E+11 | 40244.85 | 28-APR-05:01 | 27.22 | 17.14 | 0.215722E+10 | 2451.32 | 28-APR-14:30 | 38.90 | 21.10 |
May | 0.206084E+11 | 40155.59 | 06-MAY-05:01 | 29.55 | 17.33 | 0.223343E+10 | 2451.35 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.211330E+11 | 37749.15 | 07-JUN-05:01 | 33.20 | 19.47 | 0.220249E+10 | 2451.32 | 03-JUN-10:09 | 36.82 | 23.31 |
July | 0.212601E+11 | 33766.20 | 07-JUL-05:01 | 31.52 | 25.90 | 0.218816E+10 | 2451.24 | 28-JUL-14:00 | 30.30 | 26.39 |
August | 0.206575E+11 | 31859.44 | 09-AUG-05:01 | 29.90 | 25.20 | 0.228192E+10 | 2451.27 | 19-AUG-10:09 | 30.20 | 27.07 |
September | 0.174334E+11 | 35469.73 | 27-SEP-05:01 | 23.08 | 20.68 | 0.215730E+10 | 2451.27 | 02-SEP-10:09 | 29.75 | 26.54 |
October | 0.143160E+11 | 38242.58 | 02-OCT-05:01 | 21.60 | 17.46 | 0.218474E+10 | 2451.28 | 21-OCT-10:09 | 26.07 | 16.99 |
November | 0.832780E+10 | 27035.23 | 09-NOV-07:02 | 18.42 | 16.26 | 0.209890E+10 | 2451.28 | 22-NOV-15:20 | 24.80 | 15.43 |
December | 0.436838E+10 | 6569.33 | 01-DEC-15:20 | 23.03 | 13.47 | 0.214647E+10 | 2451.27 | 01-DEC-15:00 | 22.30 | 13.70 |
Annual Sum or Average | 0.160710E+12 | 0.259842E+11 | ||||||||
Minimum of Months | 0.312921E+10 | 5354.24 | 18.42 | 13.47 | 0.196850E+10 | 2451.24 | 20.30 | 11.57 | ||
Maximum of Months | 0.212601E+11 | 40244.85 | 33.20 | 25.90 | 0.228192E+10 | 2451.35 | 38.90 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254343E+11 | 33759.18 | 05-JAN-07:05 | 4.93 | 4.82 | 0.879504E+10 | 10327.10 | 21-JAN-11:39 | 16.90 | 9.78 |
February | 0.295026E+11 | 36595.24 | 23-FEB-15:20 | 25.47 | 14.17 | 0.829536E+10 | 10327.13 | 23-FEB-15:00 | 24.80 | 14.33 |
March | 0.461298E+11 | 144169.53 | 13-MAR-06:02 | 20.65 | 15.51 | 0.960405E+10 | 10327.26 | 10-MAR-15:09 | 32.45 | 20.62 |
April | 0.610848E+11 | 167344.21 | 08-APR-06:02 | 23.28 | 14.20 | 0.908810E+10 | 10327.14 | 22-APR-14:50 | 30.72 | 18.74 |
May | 0.737946E+11 | 163081.24 | 29-MAY-07:01 | 30.38 | 18.50 | 0.940934E+10 | 10327.41 | 06-MAY-10:30 | 37.35 | 19.52 |
June | 0.724563E+11 | 147138.49 | 07-JUN-05:01 | 33.20 | 19.47 | 0.927906E+10 | 10326.97 | 03-JUN-11:20 | 38.23 | 23.38 |
July | 0.678907E+11 | 128571.77 | 01-JUL-05:01 | 29.33 | 23.52 | 0.921879E+10 | 10327.14 | 12-JUL-14:09 | 27.52 | 25.06 |
August | 0.657234E+11 | 119486.48 | 03-AUG-05:01 | 28.40 | 23.49 | 0.961378E+10 | 10326.90 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.583801E+11 | 134459.74 | 27-SEP-05:01 | 23.08 | 20.68 | 0.908858E+10 | 10327.15 | 29-SEP-14:00 | 31.30 | 22.59 |
October | 0.541074E+11 | 150449.91 | 23-OCT-06:02 | 19.08 | 14.20 | 0.920337E+10 | 10327.19 | 25-OCT-14:00 | 29.10 | 18.46 |
November | 0.400990E+11 | 103782.25 | 11-NOV-09:02 | 20.20 | 15.91 | 0.883336E+10 | 10327.34 | 08-NOV-15:20 | 29.67 | 18.18 |
December | 0.295129E+11 | 33790.02 | 01-DEC-15:30 | 22.85 | 13.53 | 0.901928E+10 | 10327.25 | 01-DEC-15:30 | 22.85 | 13.53 |
Annual Sum or Average | 0.624116E+12 | 0.109448E+12 | ||||||||
Minimum of Months | 0.254343E+11 | 33759.18 | 4.93 | 4.82 | 0.829536E+10 | 10326.90 | 16.90 | 9.78 | ||
Maximum of Months | 0.737946E+11 | 167344.21 | 33.20 | 23.52 | 0.961378E+10 | 10327.41 | 38.23 | 26.11 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.620483E+10 | 7989.47 | 12-JAN-15:10 | 23.55 | 14.23 | 0.855499E+09 | 973.15 | 07-JAN-16:00 | 18.40 | 12.94 |
February | 0.686673E+10 | 9137.84 | 22-FEB-14:20 | 27.03 | 16.26 | 0.788088E+09 | 973.16 | 15-FEB-15:09 | 22.98 | 16.79 |
March | 0.965289E+10 | 24138.44 | 29-MAR-05:02 | 21.18 | 17.33 | 0.905621E+09 | 973.15 | 21-MAR-14:09 | 23.05 | 15.20 |
April | 0.114780E+11 | 25956.99 | 28-APR-05:01 | 27.22 | 17.14 | 0.856400E+09 | 973.20 | 15-APR-12:00 | 39.40 | 19.77 |
May | 0.134591E+11 | 25689.30 | 06-MAY-05:01 | 29.55 | 17.33 | 0.886635E+09 | 973.19 | 06-MAY-11:39 | 39.60 | 19.75 |
June | 0.134154E+11 | 23756.37 | 12-JUN-04:02 | 33.75 | 20.80 | 0.874351E+09 | 973.17 | 02-JUN-14:39 | 38.53 | 20.87 |
July | 0.134178E+11 | 20980.77 | 07-JUL-04:02 | 31.73 | 26.03 | 0.868659E+09 | 973.13 | 12-JUL-14:00 | 28.10 | 25.12 |
August | 0.133442E+11 | 19834.79 | 15-AUG-05:01 | 26.82 | 25.45 | 0.905879E+09 | 973.14 | 16-AUG-14:09 | 27.82 | 26.54 |
September | 0.123845E+11 | 23133.87 | 27-SEP-05:01 | 23.08 | 20.68 | 0.856396E+09 | 973.15 | 30-SEP-10:09 | 30.97 | 23.64 |
October | 0.128592E+11 | 25226.20 | 02-OCT-05:01 | 21.60 | 17.46 | 0.867364E+09 | 973.19 | 18-OCT-14:30 | 33.00 | 20.08 |
November | 0.105672E+11 | 22465.39 | 12-NOV-09:02 | 20.32 | 15.27 | 0.834159E+09 | 973.12 | 18-NOV-16:00 | 24.80 | 17.32 |
December | 0.746814E+10 | 9164.07 | 02-DEC-14:00 | 24.10 | 13.12 | 0.864325E+09 | 973.16 | 11-DEC-15:50 | 21.78 | 14.91 |
Annual Sum or Average | 0.131118E+12 | 0.103634E+11 | ||||||||
Minimum of Months | 0.620483E+10 | 7989.47 | 20.32 | 13.12 | 0.788088E+09 | 973.12 | 18.40 | 12.94 | ||
Maximum of Months | 0.134591E+11 | 25956.99 | 33.75 | 26.03 | 0.905879E+09 | 973.20 | 39.60 | 26.54 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382869E+10 | 5755.14 | 12-JAN-15:10 | 23.55 | 14.23 | 0.836954E+09 | 973.13 | 06-JAN-15:20 | 20.57 | 13.01 |
February | 0.449553E+10 | 7008.50 | 22-FEB-15:10 | 27.00 | 16.13 | 0.780691E+09 | 973.14 | 24-FEB-15:09 | 26.38 | 17.38 |
March | 0.677275E+10 | 18045.60 | 29-MAR-06:02 | 21.15 | 17.30 | 0.904652E+09 | 973.13 | 04-MAR-11:00 | 25.60 | 15.48 |
April | 0.866089E+10 | 21791.19 | 28-APR-05:01 | 27.22 | 17.14 | 0.856357E+09 | 973.16 | 15-APR-12:50 | 39.17 | 19.69 |
May | 0.105001E+11 | 21157.00 | 06-MAY-05:01 | 29.55 | 17.33 | 0.886627E+09 | 973.14 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.104530E+11 | 19224.45 | 12-JUN-04:02 | 33.75 | 20.80 | 0.874347E+09 | 973.13 | 02-JUN-14:20 | 38.37 | 20.77 |
July | 0.104636E+11 | 16496.80 | 07-JUL-05:01 | 31.52 | 25.90 | 0.868662E+09 | 973.09 | 12-JUL-14:00 | 28.10 | 25.12 |
August | 0.103061E+11 | 15683.67 | 09-AUG-05:01 | 29.90 | 25.20 | 0.905881E+09 | 973.12 | 16-AUG-14:09 | 27.82 | 26.54 |
September | 0.950568E+10 | 18414.02 | 27-SEP-05:01 | 23.08 | 20.68 | 0.856391E+09 | 973.08 | 07-SEP-14:09 | 27.02 | 25.39 |
October | 0.995317E+10 | 20576.33 | 02-OCT-05:01 | 21.60 | 17.46 | 0.867305E+09 | 973.14 | 16-OCT-14:39 | 33.47 | 19.01 |
November | 0.781775E+10 | 18503.93 | 12-NOV-09:02 | 20.32 | 15.27 | 0.833484E+09 | 973.15 | 18-NOV-16:00 | 24.80 | 17.32 |
December | 0.486893E+10 | 7002.74 | 02-DEC-14:00 | 24.10 | 13.12 | 0.856393E+09 | 973.14 | 07-DEC-15:00 | 19.20 | 12.65 |
Annual Sum or Average | 0.976261E+11 | 0.103277E+11 | ||||||||
Minimum of Months | 0.382869E+10 | 5755.14 | 20.32 | 13.12 | 0.780691E+09 | 973.08 | 19.20 | 12.65 | ||
Maximum of Months | 0.105001E+11 | 21791.19 | 33.75 | 25.90 | 0.905881E+09 | 973.16 | 39.17 | 26.54 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178015E+09 | 41211.69 | 01-JAN-08:62 | 8.17 |
February | 1292649.88 | 4186.06 | 02-FEB-07:03 | 7.12 |
March | 4738774.41 | 1529.32 | 11-MAR-07:06 | 23.87 |
April | 34351758.25 | 3230.53 | 16-APR-08:06 | 30.70 |
May | 40162680.44 | 3693.98 | 01-MAY-06:06 | 32.80 |
June | 33232572.24 | 3575.43 | 04-JUN-08:06 | 31.72 |
July | 29201682.89 | 3297.77 | 02-JUL-07:07 | 33.57 |
August | 26608273.54 | 2525.73 | 08-AUG-05:06 | 30.10 |
September | 27755466.26 | 2035.58 | 17-SEP-07:04 | 27.33 |
October | 11015243.34 | 1888.99 | 04-OCT-06:06 | 25.52 |
November | 622992.92 | 483.98 | 11-NOV-09:04 | 20.20 |
December | 6497196.08 | 12800.39 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.393494E+09 | |||
Minimum of Months | 622992.92 | 483.98 | 6.25 | |
Maximum of Months | 0.178015E+09 | 41211.69 | 33.57 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349265E+09 | 155934.64 | 02-JAN-07:03 | 6.78 |
February | 5295076.68 | 26475.38 | 02-FEB-07:03 | 7.12 |
March | 9900334.22 | 7515.49 | 11-MAR-07:06 | 23.87 |
April | 0.171981E+09 | 22147.64 | 16-APR-08:06 | 30.70 |
May | 0.263532E+09 | 26469.53 | 01-MAY-06:06 | 32.80 |
June | 0.280137E+09 | 28548.44 | 07-JUN-06:06 | 33.87 |
July | 0.244531E+09 | 24219.80 | 02-JUL-07:06 | 33.57 |
August | 0.228337E+09 | 17088.19 | 08-AUG-05:05 | 30.10 |
September | 0.211766E+09 | 13223.54 | 12-SEP-06:08 | 27.02 |
October | 52972050.66 | 10623.11 | 04-OCT-06:06 | 25.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 15760796.98 | 65425.18 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.183348E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 0.349265E+09 | 155934.64 | 33.87 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10059231.55 | 13954.85 | 02-JAN-07:03 | 6.78 |
February | 499176.79 | 3327.85 | 11-FEB-07:03 | 9.97 |
March | 746075.01 | 638.83 | 12-MAR-08:04 | 21.93 |
April | 12598896.21 | 2145.05 | 27-APR-05:04 | 30.50 |
May | 14895758.28 | 2490.99 | 01-MAY-05:04 | 32.45 |
June | 14137759.69 | 2681.08 | 12-JUN-05:04 | 34.12 |
July | 10883904.44 | 2181.46 | 04-JUL-07:05 | 31.77 |
August | 12454116.57 | 1782.43 | 09-AUG-05:04 | 29.90 |
September | 14050774.67 | 1423.62 | 24-SEP-07:04 | 27.28 |
October | 1760988.95 | 1045.21 | 04-OCT-05:04 | 25.07 |
November | 32619.31 | 261.23 | 12-NOV-09:04 | 20.32 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 92119301.47 | |||
Minimum of Months | 0.00 | 0.00 | 6.78 | |
Maximum of Months | 14895758.28 | 13954.85 | 34.12 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48491563.67 | 15701.52 | 02-JAN-07:03 | 6.78 |
February | 3737707.26 | 13500.88 | 11-FEB-07:03 | 9.97 |
March | 417712.86 | 567.47 | 11-MAR-07:06 | 23.87 |
April | 10669823.93 | 1763.97 | 27-APR-05:04 | 30.50 |
May | 18005242.66 | 2272.72 | 01-MAY-05:04 | 32.45 |
June | 16196160.02 | 2508.73 | 12-JUN-05:04 | 34.12 |
July | 12054752.97 | 2319.91 | 02-JUL-07:06 | 33.57 |
August | 12992530.84 | 1542.39 | 09-AUG-05:06 | 29.90 |
September | 13881822.94 | 1333.26 | 22-SEP-06:06 | 27.53 |
October | 1388231.38 | 884.58 | 04-OCT-06:06 | 25.52 |
November | 3979.51 | 33.16 | 12-NOV-09:04 | 20.32 |
December | 1707995.42 | 7471.02 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.139548E+09 | |||
Minimum of Months | 3979.51 | 33.16 | 6.25 | |
Maximum of Months | 48491563.67 | 15701.52 | 34.12 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334829E+10 | 13806.94 | 01-JAN-18:00 | 13.10 |
February | 0.835569E+09 | 11099.28 | 10-FEB-18:00 | 14.50 |
March | 62694857.64 | 1959.32 | 16-MAR-07:10 | 15.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 303555.39 | 1330.18 | 31-OCT-07:07 | 16.90 |
November | 77467049.03 | 2564.34 | 30-NOV-18:00 | 19.10 |
December | 0.246578E+10 | 15108.77 | 31-DEC-18:00 | 12.10 |
Annual Sum or Average | 0.679010E+10 | |||
Minimum of Months | 0.00 | 0.00 | 12.10 | |
Maximum of Months | 0.334829E+10 | 15108.77 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.244735E+10 | 2030.36 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.222649E+10 | 2030.36 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.253900E+10 | 2030.36 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.239592E+10 | 2030.36 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.249318E+10 | 2030.36 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.245011E+10 | 2030.36 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.243899E+10 | 2030.36 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.253900E+10 | 2030.36 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.239592E+10 | 2030.36 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.244735E+10 | 2030.36 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.236682E+10 | 2030.36 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.243899E+10 | 2030.36 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.291791E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.222649E+10 | 2030.36 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.253900E+10 | 2030.36 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.219603E+11 | 22187.24 | 02-JAN-16:19 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.188508E+11 | 22187.24 | 01-FEB-16:40 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.197026E+11 | 22187.24 | 01-MAR-17:10 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.186412E+11 | 22187.24 | 22-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.193141E+11 | 22187.24 | 31-MAY-16:30 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.185392E+11 | 18489.37 | 01-JUN-16:00 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.177648E+11 | 22187.24 | 18-JUL-08:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.188819E+11 | 22187.24 | 14-AUG-16:40 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.182152E+11 | 22187.24 | 05-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.200477E+11 | 22187.24 | 02-OCT-16:00 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.213827E+11 | 22187.24 | 01-NOV-16:30 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.222414E+11 | 22187.24 | 01-DEC-16:10 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.235542E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.177648E+11 | 18489.37 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.222414E+11 | 22187.24 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.244398E+10 | 2090.65 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.249959E+10 | 2090.65 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.244398E+10 | 2090.65 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.244398E+10 | 2090.65 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.249959E+10 | 2090.65 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.244398E+10 | 2090.65 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112411E+09 | 94.16 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102280E+09 | 94.16 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.116668E+09 | 94.16 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.110076E+09 | 94.16 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.114539E+09 | 94.16 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.112581E+09 | 94.16 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112035E+09 | 94.16 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.116668E+09 | 94.16 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.110076E+09 | 94.16 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112411E+09 | 94.16 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108701E+09 | 94.16 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112035E+09 | 94.16 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134048E+10 | ||||
Minimum of Months | 0.102280E+09 | 94.16 | 0.00 | 0.00 | |
Maximum of Months | 0.116668E+09 | 94.16 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.244735E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196246E+09 |
February | 0.479114E+10 | 0.222649E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3245161.05 | 0.225714E+09 |
March | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41905723.19 | 0.155284E+09 |
April | 0.518069E+10 | 0.239592E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161367E+09 | 12983801.53 |
May | 0.536353E+10 | 0.249318E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313055E+09 | 7285679.21 |
June | 0.528933E+10 | 0.245011E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236003E+09 | 3632696.79 |
July | 0.525489E+10 | 0.243899E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274510E+09 | 2701988.50 |
August | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158292E+09 | 4296616.69 |
September | 0.518069E+10 | 0.239592E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97297816.04 | 7119611.30 |
October | 0.524694E+10 | 0.244735E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48404545.93 | 15027554.78 |
November | 0.504819E+10 | 0.236682E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11483578.67 | 52432571.19 |
December | 0.525489E+10 | 0.243899E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109486.09 | 0.192244E+09 |
Annual Sum or Average | 0.628175E+11 | 0.291791E+11 | 0.499918E+11 | 0.134567E+10 | 0.874968E+09 | ||||
Minimum of Months | 0.479114E+10 | 0.222649E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2701988.50 |
Maximum of Months | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313055E+09 | 0.225714E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.219603E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169975E+09 |
February | 0.201852E+11 | 0.188508E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2656772.40 | 0.197223E+09 |
March | 0.230879E+11 | 0.197026E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34141339.99 | 0.138484E+09 |
April | 0.218263E+11 | 0.186412E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132350E+09 | 11140386.06 |
May | 0.225967E+11 | 0.193141E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265461E+09 | 5246734.15 |
June | 0.222841E+11 | 0.185392E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199853E+09 | 2601598.97 |
July | 0.221389E+11 | 0.177648E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240529E+09 | 1428916.50 |
August | 0.230879E+11 | 0.188819E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139106E+09 | 2216458.84 |
September | 0.218263E+11 | 0.182152E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81956928.43 | 4063466.08 |
October | 0.221054E+11 | 0.200477E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39709643.48 | 11920210.90 |
November | 0.212681E+11 | 0.213827E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9400739.19 | 44580495.99 |
December | 0.221389E+11 | 0.222414E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89657.64 | 0.166370E+09 |
Annual Sum or Average | 0.264651E+12 | 0.235542E+12 | 0.842987E+11 | 0.114525E+10 | 0.755251E+09 | ||||
Minimum of Months | 0.201852E+11 | 0.177648E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1428916.50 |
Maximum of Months | 0.230879E+11 | 0.222414E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265461E+09 | 0.197223E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94433511.42 |
February | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1406161.21 | 0.108341E+09 |
March | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17579138.70 | 82806563.42 |
April | 0.205665E+10 | 0.244398E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67061003.72 | 8855505.82 |
May | 0.212923E+10 | 0.254307E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125765E+09 | 5365963.60 |
June | 0.209978E+10 | 0.249959E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95973320.89 | 2008513.06 |
July | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108613E+09 | 2307905.29 |
August | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62520358.94 | 3444166.32 |
September | 0.205665E+10 | 0.244398E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40458135.98 | 6228707.75 |
October | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20615794.09 | 8423840.73 |
November | 0.200405E+10 | 0.241345E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4976964.79 | 26011422.41 |
December | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47434.33 | 92566772.62 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.529224E+11 | 0.545016E+09 | 0.440794E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2008513.06 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125765E+09 | 0.108341E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88899933.04 |
February | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1406182.36 | 0.101836E+09 |
March | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17729408.61 | 73951638.01 |
April | 0.205665E+10 | 0.244398E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68193338.55 | 6629150.72 |
May | 0.212923E+10 | 0.254307E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131953E+09 | 3307011.09 |
June | 0.209978E+10 | 0.249959E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100496E+09 | 1494559.28 |
July | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115989E+09 | 1150635.80 |
August | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66569576.70 | 1977869.25 |
September | 0.205665E+10 | 0.244398E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41284753.90 | 3571377.01 |
October | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20705036.02 | 7339146.87 |
November | 0.200405E+10 | 0.241345E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4976903.65 | 24591849.25 |
December | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47415.82 | 87832907.65 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.794328E+10 | 0.569351E+09 | 0.402582E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1150635.80 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131953E+09 | 0.101836E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410225E+10 |
February | 0.00 | 0.102280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145445E+10 |
March | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67894278.26 | 0.370677E+09 |
April | 0.00 | 0.110076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622711E+09 | 32989231.92 |
May | 0.00 | 0.114539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113984E+10 | 8910840.53 |
June | 0.00 | 0.112581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103026E+10 | 15766482.94 |
July | 0.00 | 0.112035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593675E+09 | 11019555.92 |
August | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383665E+09 | 23346224.79 |
September | 0.00 | 0.110076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252623E+09 | 27139832.26 |
October | 0.00 | 0.112411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77846538.69 | 0.203872E+09 |
November | 0.00 | 0.108701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748593E+09 |
December | 0.00 | 0.112035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337722E+10 |
Annual Sum or Average | 0.00 | 0.134048E+10 | 0.416851E+10 | 0.103762E+11 | |||||
Minimum of Months | 0.00 | 0.102280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8910840.53 |
Maximum of Months | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113984E+10 | 0.410225E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2030.36 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 559.19 | 15-JAN-19:10 |
February | 5888.82 | 01-FEB-15:09 | 2030.36 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.09 | 19-FEB-15:00 | 1045.16 | 09-FEB-21:10 |
March | 5888.82 | 01-MAR-15:09 | 2030.36 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.42 | 26-MAR-18:03 | 1646.13 | 24-MAR-24:00 |
April | 5888.82 | 01-APR-10:09 | 2030.36 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 650.45 | 02-APR-18:03 | 181.42 | 10-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 2030.36 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.20 | 28-MAY-18:02 | 165.60 | 15-MAY-03:00 |
June | 5888.82 | 01-JUN-14:09 | 2030.36 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 925.14 | 17-JUN-21:03 | 169.24 | 18-JUN-04:00 |
July | 5888.82 | 01-JUL-10:09 | 2030.36 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 620.82 | 20-JUL-20:03 | 140.43 | 19-JUL-03:00 |
August | 5888.82 | 01-AUG-14:09 | 2030.36 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 405.34 | 15-AUG-20:03 | 177.67 | 15-AUG-24:00 |
September | 5888.82 | 01-SEP-14:09 | 2030.36 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 269.55 | 02-SEP-21:03 | 101.33 | 19-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 2030.36 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 255.56 | 03-OCT-15:00 | 269.86 | 12-OCT-03:00 |
November | 5888.82 | 01-NOV-14:09 | 2030.36 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.03 | 13-NOV-14:00 | 412.83 | 28-NOV-05:00 |
December | 5888.82 | 01-DEC-15:09 | 2030.36 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | 28-DEC-14:00 | 943.29 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.33 | |||||
Maximum of Months | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1118.20 | 1646.13 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 22187.24 | 02-JAN-16:19 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 458.33 | 15-JAN-19:10 |
February | 24809.68 | 01-FEB-15:09 | 22187.24 | 01-FEB-16:40 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 19-FEB-15:00 | 882.09 | 09-FEB-21:20 |
March | 24809.68 | 01-MAR-15:09 | 22187.24 | 01-MAR-17:10 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 275.97 | 26-MAR-18:03 | 1629.59 | 24-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 22187.24 | 22-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 533.73 | 02-APR-18:03 | 151.16 | 10-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 22187.24 | 31-MAY-16:30 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 918.94 | 28-MAY-18:02 | 119.52 | 15-MAY-03:10 |
June | 24809.68 | 01-JUN-14:09 | 18489.37 | 01-JUN-16:00 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 763.55 | 17-JUN-21:03 | 135.61 | 18-JUN-05:00 |
July | 24809.68 | 01-JUL-10:09 | 22187.24 | 18-JUL-08:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.10 | 20-JUL-20:03 | 107.62 | 19-JUL-03:00 |
August | 24809.68 | 01-AUG-14:09 | 22187.24 | 14-AUG-16:40 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 336.19 | 15-AUG-20:03 | 125.68 | 15-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 22187.24 | 05-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.54 | 02-SEP-21:03 | 68.48 | 19-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 22187.24 | 02-OCT-16:00 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 209.20 | 03-OCT-15:00 | 220.08 | 12-OCT-03:00 |
November | 24809.68 | 01-NOV-14:09 | 22187.24 | 01-NOV-16:30 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.97 | 13-NOV-14:00 | 366.58 | 28-NOV-05:00 |
December | 24809.68 | 01-DEC-15:09 | 22187.24 | 01-DEC-16:10 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 28-DEC-14:00 | 858.49 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 18489.37 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.48 | |||||
Maximum of Months | 24809.68 | 22187.24 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 918.94 | 1629.59 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 253.97 | 15-JAN-19:10 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 463.17 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.66 | 26-MAR-18:03 | 895.70 | 24-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 276.43 | 02-APR-18:03 | 89.51 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 480.52 | 28-MAY-18:02 | 95.43 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 397.10 | 17-JUN-21:03 | 82.06 | 18-JUN-04:00 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 264.48 | 20-JUL-20:03 | 71.67 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.55 | 15-AUG-20:03 | 92.55 | 15-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.47 | 02-SEP-21:03 | 58.95 | 19-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 135.17 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 217.08 | 29-NOV-24:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 445.93 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.95 | |||||
Maximum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 480.52 | 895.70 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 230.21 | 15-JAN-19:10 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 433.96 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.25 | 26-MAR-18:03 | 802.28 | 24-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.17 | 02-APR-18:03 | 75.93 | 10-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 481.77 | 28-MAY-18:02 | 71.35 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.21 | 17-JUN-21:03 | 67.11 | 18-JUN-04:00 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 266.74 | 20-JUL-20:03 | 56.66 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.55 | 15-AUG-20:03 | 79.07 | 15-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.55 | 02-SEP-21:03 | 47.29 | 19-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 117.46 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 201.41 | 28-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 414.72 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.29 | |||||
Maximum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 481.77 | 802.28 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 94.16 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13888.78 | 01-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 94.16 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 11356.27 | 10-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 94.16 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090.54 | 28-MAR-11:02 | 2063.24 | 16-MAR-07:10 |
April | 0.00 | 01-APR-00:10 | 94.16 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3398.55 | 16-APR-11:01 | 1155.01 | 05-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 94.16 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5030.78 | 01-MAY-11:01 | 690.54 | 31-MAY-16:53 |
June | 0.00 | 01-JUN-00:10 | 94.16 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4978.76 | 12-JUN-11:01 | 1214.57 | 27-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 94.16 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3295.99 | 06-JUL-11:01 | 796.43 | 18-JUL-11:03 |
August | 0.00 | 01-AUG-00:10 | 94.16 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1746.13 | 05-AUG-11:02 | 668.24 | 16-AUG-07:02 |
September | 0.00 | 01-SEP-00:10 | 94.16 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.77 | 11-SEP-11:02 | 665.66 | 19-SEP-07:02 |
October | 0.00 | 01-OCT-00:10 | 94.16 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.90 | 02-OCT-11:02 | 1971.60 | 31-OCT-07:01 |
November | 0.00 | 01-NOV-00:10 | 94.16 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3415.33 | 30-NOV-18:00 |
December | 0.00 | 01-DEC-00:10 | 94.16 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 15581.01 | 21-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.66 | ||||
Maximum of Months | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5030.78 | 15581.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5354.24 | 14-JAN-16:10 | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 |
February | 7864.05 | 24-FEB-16:00 | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 0.00 |
March | 34880.78 | 29-MAR-06:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
April | 40244.85 | 28-APR-05:01 | 0.00 | 905.90 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 0.00 |
May | 40155.59 | 06-MAY-05:01 | 0.00 | 1035.32 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 15.79 | 0.00 |
June | 37749.15 | 07-JUN-05:01 | 0.00 | 1035.32 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 | 0.00 |
July | 33766.20 | 07-JUL-05:01 | 0.00 | 1035.32 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 |
August | 31859.44 | 09-AUG-05:01 | 0.00 | 905.90 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
September | 35469.73 | 27-SEP-05:01 | 0.00 | 905.90 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 |
October | 38242.58 | 02-OCT-05:01 | 0.00 | 905.90 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 27035.23 | 09-NOV-07:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 |
December | 6569.33 | 01-DEC-15:20 | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5354.24 | 0.00 | 905.90 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40244.85 | 5888.82 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 | 42.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33759.18 | 05-JAN-07:05 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36595.24 | 23-FEB-15:20 | 24809.68 | 16640.43 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 | 0.00 |
March | 144169.53 | 13-MAR-06:02 | 15506.05 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.05 |
April | 167344.21 | 08-APR-06:02 | 15506.05 | 12326.24 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
May | 163081.24 | 29-MAY-07:01 | 0.00 | 8217.50 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 104.19 | 0.00 |
June | 147138.49 | 07-JUN-05:01 | 0.00 | 9860.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 | 0.00 |
July | 128571.77 | 01-JUL-05:01 | 0.00 | 9860.99 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 0.00 |
August | 119486.48 | 03-AUG-05:01 | 0.00 | 9860.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 | 0.00 |
September | 134459.74 | 27-SEP-05:01 | 0.00 | 8628.37 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
October | 150449.91 | 23-OCT-06:02 | 15506.05 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 |
November | 103782.25 | 11-NOV-09:02 | 15506.05 | 9244.68 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33790.02 | 01-DEC-15:30 | 24809.68 | 20338.30 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 33759.18 | 0.00 | 8217.50 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 167344.21 | 24809.68 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 104.19 | 45.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7989.47 | 12-JAN-15:10 | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
February | 9137.84 | 22-FEB-14:20 | 2045.54 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 | 0.00 |
March | 24138.44 | 29-MAR-05:02 | 0.00 | 580.74 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
April | 25956.99 | 28-APR-05:01 | 0.00 | 813.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
May | 25689.30 | 06-MAY-05:01 | 0.00 | 929.18 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
June | 23756.37 | 12-JUN-04:02 | 0.00 | 696.88 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 51.99 | 0.00 |
July | 20980.77 | 07-JUL-04:02 | 0.00 | 580.74 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19834.79 | 15-AUG-05:01 | 0.00 | 813.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
September | 23133.87 | 27-SEP-05:01 | 0.00 | 813.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 25226.20 | 02-OCT-05:01 | 0.00 | 813.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
November | 22465.39 | 12-NOV-09:02 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 |
December | 9164.07 | 02-DEC-14:00 | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7989.47 | 0.00 | 580.74 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25956.99 | 2337.76 | 2090.65 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 51.99 | 15.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5755.14 | 12-JAN-15:10 | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
February | 7008.50 | 22-FEB-15:10 | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 | 0.00 |
March | 18045.60 | 29-MAR-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
April | 21791.19 | 28-APR-05:01 | 0.00 | 813.03 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
May | 21157.00 | 06-MAY-05:01 | 0.00 | 929.18 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 7.03 | 0.00 |
June | 19224.45 | 12-JUN-04:02 | 0.00 | 696.88 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 | 0.00 |
July | 16496.80 | 07-JUL-05:01 | 0.00 | 929.18 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 | 0.00 |
August | 15683.67 | 09-AUG-05:01 | 0.00 | 813.03 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 | 0.00 |
September | 18414.02 | 27-SEP-05:01 | 0.00 | 813.03 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
October | 20576.33 | 02-OCT-05:01 | 0.00 | 813.03 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
November | 18503.93 | 12-NOV-09:02 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
December | 7002.74 | 02-DEC-14:00 | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5755.14 | 0.00 | 696.88 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21791.19 | 2337.76 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 | 14.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 | 0.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 5.58 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.712863E+11 | 65607.01 | 14-JAN-17:49 | 0.131911E+11 | 103541.68 | 02-JAN-07:10 |
February | 0.700689E+11 | 69063.64 | 24-FEB-17:10 | 0.742564E+10 | 31506.84 | 02-FEB-07:10 |
March | 0.916602E+11 | 81969.78 | 28-MAR-16:40 | 0.753036E+10 | 4893.84 | 01-MAR-12:39 |
April | 0.107168E+12 | 97044.63 | 28-APR-14:00 | 0.704255E+10 | 4841.59 | 03-APR-11:09 |
May | 0.132392E+12 | 112374.44 | 30-MAY-14:00 | 0.705748E+10 | 4790.73 | 01-MAY-11:30 |
June | 0.137416E+12 | 123204.38 | 10-JUN-15:00 | 0.669026E+10 | 4743.38 | 01-JUN-11:20 |
July | 0.138121E+12 | 116778.36 | 01-JUL-16:40 | 0.680255E+10 | 4715.16 | 03-JUL-11:39 |
August | 0.137317E+12 | 107618.45 | 28-AUG-15:50 | 0.689701E+10 | 4737.74 | 31-AUG-11:20 |
September | 0.120354E+12 | 103084.71 | 14-SEP-16:00 | 0.679877E+10 | 4779.60 | 29-SEP-11:30 |
October | 0.104709E+12 | 92450.30 | 03-OCT-14:39 | 0.721437E+10 | 4836.91 | 31-OCT-11:20 |
November | 0.860268E+11 | 77906.70 | 08-NOV-17:30 | 0.718664E+10 | 5753.10 | 30-NOV-17:00 |
December | 0.747145E+11 | 66562.50 | 01-DEC-17:30 | 0.940176E+10 | 56117.05 | 23-DEC-07:10 |
Annual Sum or Average | 0.127123E+13 | 0.932385E+11 | ||||
Minimum of Months | 0.700689E+11 | 65607.01 | 0.669026E+10 | 4715.16 | ||
Maximum of Months | 0.138121E+12 | 123204.38 | 0.131911E+11 | 103541.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.295117E+11 | 0.586960E+10 | 0.164409E+11 | 0.00 | 0.137776E+11 | 0.00 | 0.00 | 0.568644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257213E+11 | 0.504043E+10 | 0.149157E+11 | 0.00 | 0.114899E+11 | 0.00 | 0.00 | 0.129016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275389E+11 | 0.515730E+10 | 0.168545E+11 | 0.00 | 0.123401E+11 | 0.00 | 0.00 | 0.297694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260351E+11 | 0.457681E+10 | 0.160165E+11 | 0.00 | 0.120723E+11 | 0.00 | 0.00 | 0.484673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270080E+11 | 0.436554E+10 | 0.166477E+11 | 0.00 | 0.140706E+11 | 0.00 | 0.00 | 0.702997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.261011E+11 | 0.402888E+10 | 0.162772E+11 | 0.00 | 0.150101E+11 | 0.00 | 0.00 | 0.759990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.252908E+11 | 0.426966E+10 | 0.163871E+11 | 0.00 | 0.154014E+11 | 0.00 | 0.00 | 0.767716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.267182E+11 | 0.456280E+10 | 0.168545E+11 | 0.00 | 0.152105E+11 | 0.00 | 0.00 | 0.739710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.256092E+11 | 0.481241E+10 | 0.160165E+11 | 0.00 | 0.129990E+11 | 0.00 | 0.00 | 0.609167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275991E+11 | 0.540386E+10 | 0.164409E+11 | 0.00 | 0.121885E+11 | 0.00 | 0.00 | 0.430770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286851E+11 | 0.558773E+10 | 0.159174E+11 | 0.00 | 0.116941E+11 | 0.00 | 0.00 | 0.241424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297673E+11 | 0.599836E+10 | 0.163871E+11 | 0.00 | 0.133423E+11 | 0.00 | 0.00 | 0.921943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.325586E+12 | 0.596734E+11 | 0.195156E+12 | 0.159597E+12 | 0.00 | 0.531222E+12 | |||||||
Minimum of Months | 0.252908E+11 | 0.402888E+10 | 0.149157E+11 | 0.00 | 0.114899E+11 | 0.00 | 0.00 | 0.568644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.297673E+11 | 0.599836E+10 | 0.168545E+11 | 0.00 | 0.154014E+11 | 0.00 | 0.00 | 0.767716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.551700E+10 | 0.00 | 0.767410E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.528268E+09 | 0.00 | 0.689737E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.753036E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.704255E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.705748E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.669026E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.680255E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.689701E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.679877E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.721437E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2168871.28 | 0.00 | 0.718447E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.179438E+10 | 0.00 | 0.760738E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.784182E+10 | 0.853967E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.669026E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.551700E+10 | 0.00 | 0.767410E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28493.07 | 02-JAN-16:19 | 4566.05 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 11503.96 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28493.07 | 01-FEB-16:40 | 4566.05 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 9234.04 | 02-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28493.07 | 01-MAR-17:10 | 4566.05 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 10477.68 | 11-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28493.07 | 22-APR-16:00 | 4566.05 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 11680.59 | 16-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28493.07 | 31-MAY-16:30 | 4566.05 | 01-MAY-05:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 12434.55 | 30-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 24795.20 | 01-JUN-16:00 | 4566.05 | 01-JUN-05:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 14211.95 | 27-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28493.07 | 18-JUL-08:09 | 4566.05 | 01-JUL-05:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 14776.27 | 04-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28493.07 | 14-AUG-16:40 | 4566.05 | 01-AUG-05:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 14495.29 | 10-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28493.07 | 05-SEP-08:09 | 4566.05 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 13341.56 | 03-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28493.07 | 02-OCT-16:00 | 4566.05 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 11784.05 | 04-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28493.07 | 01-NOV-16:30 | 4566.05 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 9077.99 | 25-NOV-17:49 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28493.07 | 01-DEC-16:10 | 4566.05 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 9566.15 | 31-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 24795.20 | 4566.05 | 10771.04 | 0.00 | 9077.99 | 0.00 | 0.00 | |||||
Maximum of Months | 28493.07 | 4566.05 | 10771.04 | 0.00 | 14776.27 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 16499.52 | 12-JAN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25244.58 | 24-FEB-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39399.52 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53633.28 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66222.59 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75401.59 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72122.08 | 01-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 64763.13 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58028.68 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49567.78 | 03-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31927.08 | 09-NOV-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19205.34 | 28-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 16499.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75401.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 65607.01 | 14-JAN-17:49 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 9077.99 | 0.00 | 0.00 | 12698.87 | 0.00 |
February | 69063.64 | 24-FEB-17:10 | 28493.07 | 10771.04 | 0.00 | 0.00 | 7512.36 | 0.00 | 0.00 | 22287.17 | 0.00 |
March | 81969.78 | 28-MAR-16:40 | 26644.13 | 10771.04 | 0.00 | 0.00 | 7512.36 | 0.00 | 0.00 | 37042.25 | 0.00 |
April | 97044.63 | 28-APR-14:00 | 22946.26 | 10771.04 | 0.00 | 0.00 | 9751.07 | 0.00 | 0.00 | 53576.26 | 0.00 |
May | 112374.44 | 30-MAY-14:00 | 22946.26 | 10771.04 | 0.00 | 0.00 | 12434.55 | 0.00 | 0.00 | 66222.59 | 0.00 |
June | 123204.38 | 10-JUN-15:00 | 22946.26 | 10771.04 | 0.00 | 0.00 | 14085.49 | 0.00 | 0.00 | 75401.59 | 0.00 |
July | 116778.36 | 01-JUL-16:40 | 22946.26 | 10771.04 | 0.00 | 0.00 | 13806.46 | 0.00 | 0.00 | 69254.60 | 0.00 |
August | 107618.45 | 28-AUG-15:50 | 22946.26 | 10771.04 | 0.00 | 0.00 | 12329.72 | 0.00 | 0.00 | 61571.44 | 0.00 |
September | 103084.71 | 14-SEP-16:00 | 26644.13 | 10771.04 | 0.00 | 0.00 | 10820.97 | 0.00 | 0.00 | 54848.57 | 0.00 |
October | 92450.30 | 03-OCT-14:39 | 22946.26 | 10771.04 | 0.00 | 0.00 | 9165.86 | 0.00 | 0.00 | 49567.14 | 0.00 |
November | 77906.70 | 08-NOV-17:30 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 7512.36 | 0.00 | 0.00 | 26564.19 | 0.00 |
December | 66562.50 | 01-DEC-17:30 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 9077.99 | 0.00 | 0.00 | 13654.36 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 65607.01 | 22946.26 | 10771.04 | 0.00 | 0.00 | 7512.36 | 0.00 | 0.00 | 12698.87 | 0.00 | |
Maximum of Months | 123204.38 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 14085.49 | 0.00 | 0.00 | 75401.59 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 101679.68 | 02-JAN-07:10 | 0.00 | 4922.89 | 23-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 29338.12 | 02-FEB-07:10 | 0.00 | 4919.02 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4893.84 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4841.59 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4790.73 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4743.38 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4715.16 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4737.74 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4779.60 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4836.91 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 1241.70 | 30-NOV-17:00 | 0.00 | 4886.16 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 51547.45 | 23-DEC-07:10 | 0.00 | 4916.65 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4715.16 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 101679.68 | 0.00 | 4922.89 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 26.16 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.41 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.45 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.43 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.41 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 28.42 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.45 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 381.83 | 23.06 | 1.17 | 21.24 | 1.17 | 21.24 |
February | 221.50 | 23.41 | 10.00 | 23.89 | 0.00 | 0.00 |
March | 45.83 | 23.73 | 154.33 | 23.89 | 0.00 | 0.00 |
April | 0.33 | 23.85 | 342.33 | 23.89 | 0.00 | 0.00 |
May | 2.17 | 24.00 | 418.00 | 23.89 | 2.17 | 24.00 |
June | 12.50 | 23.95 | 408.00 | 23.89 | 12.50 | 23.95 |
July | 25.00 | 23.96 | 415.00 | 23.89 | 25.00 | 23.96 |
August | 22.00 | 23.97 | 422.00 | 23.89 | 22.00 | 23.97 |
September | 28.17 | 23.93 | 405.00 | 23.89 | 28.17 | 23.93 |
October | 0.50 | 23.95 | 372.67 | 23.89 | 0.50 | 23.95 |
November | 59.67 | 23.65 | 87.33 | 23.89 | 0.00 | 0.00 |
December | 337.17 | 23.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1136.67 | 23.36 | 3035.83 | 23.89 | 91.50 | 23.92 |
Minimum of Months | 0.33 | 23.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 381.83 | 24.00 | 422.00 | 23.89 | 28.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 287.83 | 22.77 | 10.17 | 23.74 | 0.50 | 21.23 |
February | 95.17 | 22.77 | 76.33 | 23.89 | 0.00 | 0.00 |
March | 17.17 | 23.38 | 270.83 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 370.83 | 23.89 | 0.00 | 0.00 |
May | 6.17 | 23.93 | 418.00 | 23.89 | 6.17 | 23.93 |
June | 42.83 | 23.91 | 408.00 | 23.89 | 42.83 | 23.91 |
July | 120.00 | 23.91 | 415.00 | 23.89 | 120.00 | 23.91 |
August | 193.33 | 23.90 | 422.00 | 23.89 | 193.33 | 23.90 |
September | 135.67 | 23.90 | 405.00 | 23.89 | 135.67 | 23.90 |
October | 5.50 | 23.89 | 399.00 | 23.89 | 5.50 | 23.89 |
November | 32.50 | 23.12 | 203.00 | 23.89 | 0.00 | 0.00 |
December | 178.50 | 22.85 | 9.83 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 1114.67 | 23.31 | 3408.00 | 23.89 | 504.00 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 9.83 | 23.74 | 0.00 | 0.00 |
Maximum of Months | 287.83 | 23.93 | 422.00 | 23.89 | 193.33 | 23.93 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.33 | 22.69 | 95.00 | 23.88 | 0.50 | 21.22 |
February | 47.00 | 22.85 | 201.00 | 23.89 | 0.00 | 0.00 |
March | 8.83 | 23.76 | 336.17 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 393.67 | 23.89 | 0.00 | 0.00 |
May | 1.17 | 24.00 | 418.00 | 23.89 | 1.17 | 24.00 |
June | 8.33 | 23.94 | 408.00 | 23.89 | 8.33 | 23.94 |
July | 17.67 | 23.95 | 415.00 | 23.89 | 17.67 | 23.95 |
August | 17.33 | 23.95 | 422.00 | 23.89 | 17.33 | 23.95 |
September | 18.17 | 23.92 | 405.00 | 23.89 | 18.17 | 23.92 |
October | 0.33 | 23.97 | 414.00 | 23.89 | 0.33 | 23.97 |
November | 4.67 | 23.38 | 345.50 | 23.89 | 0.00 | 0.00 |
December | 70.50 | 23.07 | 168.67 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 308.33 | 23.10 | 4022.00 | 23.89 | 63.50 | 23.92 |
Minimum of Months | 0.00 | 0.00 | 95.00 | 23.88 | 0.00 | 0.00 |
Maximum of Months | 114.33 | 24.00 | 422.00 | 23.89 | 18.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 190.67 | 22.46 | 33.67 | 23.84 | 0.67 | 21.17 |
February | 85.50 | 22.60 | 146.17 | 23.89 | 0.00 | 0.00 |
March | 26.50 | 23.37 | 296.33 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 372.67 | 23.89 | 0.00 | 0.00 |
May | 4.17 | 23.93 | 418.00 | 23.89 | 4.17 | 23.93 |
June | 19.00 | 23.92 | 408.00 | 23.89 | 19.00 | 23.92 |
July | 34.33 | 23.94 | 415.00 | 23.89 | 34.33 | 23.94 |
August | 37.17 | 23.93 | 422.00 | 23.89 | 37.17 | 23.93 |
September | 48.83 | 23.91 | 405.00 | 23.89 | 48.83 | 23.91 |
October | 3.50 | 23.90 | 406.67 | 23.89 | 3.50 | 23.90 |
November | 14.50 | 23.14 | 318.17 | 23.89 | 0.00 | 0.00 |
December | 110.83 | 22.68 | 108.17 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 575.00 | 22.96 | 3749.83 | 23.89 | 147.67 | 23.91 |
Minimum of Months | 0.00 | 0.00 | 33.67 | 23.84 | 0.00 | 0.00 |
Maximum of Months | 190.67 | 23.94 | 422.00 | 23.89 | 48.83 | 23.94 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.09859 | 46.55875 | 0.06516 | 6.33276 |
February | 376.00000 | 23.58627 | 46.13429 | 0.23637 | 6.79597 |
March | 422.00000 | 23.87316 | 44.97286 | 0.38223 | 8.16485 |
April | 405.00000 | 23.91002 | 44.58887 | 0.48116 | 9.91763 |
May | 418.00000 | 23.91381 | 49.84890 | -0.2649 | 6.54536 |
June | 408.00000 | 23.91448 | 53.15290 | -0.2274 | 6.18193 |
July | 415.00000 | 23.91597 | 56.49800 | -0.2100 | 6.01567 |
August | 422.00000 | 23.91511 | 56.94772 | -0.2223 | 6.09911 |
September | 405.00000 | 23.91472 | 55.95729 | -0.2690 | 6.57621 |
October | 414.00000 | 23.90776 | 47.66148 | 0.48513 | 9.97717 |
November | 399.00000 | 23.85032 | 44.75459 | 0.36223 | 7.85890 |
December | 415.00000 | 23.46963 | 44.17724 | 0.17507 | 6.34371 |
Annual Sum or Average | 4913.00000 | 23.77348 | 49.30712 | 0.08073 | 7.23184 |
Minimum of Months | 376.00000 | 23.09859 | 44.17724 | -0.2690 | 6.01567 |
Maximum of Months | 422.00000 | 23.91597 | 56.94772 | 0.48513 | 9.97717 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.08300 | 42.41632 | 0.13357 | 6.60924 |
February | 376.00000 | 23.58364 | 42.71554 | 0.30702 | 7.54894 |
March | 422.00000 | 23.86766 | 42.11715 | 0.43546 | 9.07868 |
April | 405.00000 | 23.90934 | 42.24143 | 0.52099 | 10.77642 |
May | 418.00000 | 23.91361 | 49.67761 | -0.2163 | 6.07769 |
June | 408.00000 | 23.91443 | 54.87041 | -0.1808 | 5.78573 |
July | 415.00000 | 23.91579 | 60.49885 | -0.1743 | 5.71038 |
August | 422.00000 | 23.91522 | 61.82915 | -0.1836 | 5.76247 |
September | 405.00000 | 23.91479 | 59.82039 | -0.2219 | 6.09097 |
October | 414.00000 | 23.90287 | 47.46877 | 0.51957 | 10.71267 |
November | 399.00000 | 23.81516 | 42.13751 | 0.40360 | 8.55835 |
December | 415.00000 | 23.41857 | 40.36241 | 0.23132 | 6.85754 |
Annual Sum or Average | 4913.00000 | 23.76384 | 48.91034 | 0.12900 | 7.45684 |
Minimum of Months | 376.00000 | 23.08300 | 40.36241 | -0.2219 | 5.71038 |
Maximum of Months | 422.00000 | 23.91579 | 61.82915 | 0.52099 | 10.77642 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.52982 | 38.47286 | 0.28508 | 7.70366 |
February | 376.00000 | 23.74562 | 39.17351 | 0.39133 | 8.69249 |
March | 422.00000 | 23.89456 | 39.40557 | 0.49002 | 10.17288 |
April | 405.00000 | 23.91114 | 40.32443 | 0.56548 | 11.82179 |
May | 418.00000 | 23.91287 | 46.44336 | -0.1579 | 5.64554 |
June | 408.00000 | 23.91301 | 50.24516 | -0.1246 | 5.46486 |
July | 415.00000 | 23.91393 | 53.87794 | -0.1092 | 5.36402 |
August | 422.00000 | 23.91329 | 54.32067 | -0.1168 | 5.38196 |
September | 405.00000 | 23.91315 | 52.30710 | -0.1434 | 5.56088 |
October | 414.00000 | 23.91119 | 42.27911 | 0.60614 | 12.81606 |
November | 399.00000 | 23.89038 | 37.83943 | 0.51834 | 10.77807 |
December | 415.00000 | 23.73430 | 36.23990 | 0.36391 | 8.25611 |
Annual Sum or Average | 4913.00000 | 23.84918 | 44.29859 | 0.21174 | 8.12334 |
Minimum of Months | 376.00000 | 23.52982 | 36.23990 | -0.1579 | 5.36402 |
Maximum of Months | 422.00000 | 23.91393 | 54.32067 | 0.60614 | 12.81606 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.20072 | 41.06606 | 0.19205 | 7.19266 |
February | 376.00000 | 23.57277 | 41.50973 | 0.33099 | 8.10594 |
March | 422.00000 | 23.85632 | 40.96370 | 0.45449 | 9.53010 |
April | 405.00000 | 23.90892 | 41.14909 | 0.53579 | 11.13406 |
May | 418.00000 | 23.91303 | 47.77148 | -0.1964 | 5.92329 |
June | 408.00000 | 23.91350 | 52.07094 | -0.1614 | 5.67458 |
July | 415.00000 | 23.91487 | 56.23087 | -0.1410 | 5.52425 |
August | 422.00000 | 23.91417 | 56.89727 | -0.1479 | 5.54718 |
September | 405.00000 | 23.91371 | 54.94178 | -0.1748 | 5.75481 |
October | 414.00000 | 23.90846 | 43.66199 | 0.58062 | 12.16985 |
November | 399.00000 | 23.85966 | 39.11715 | 0.48324 | 10.08367 |
December | 415.00000 | 23.54276 | 38.27531 | 0.29810 | 7.69361 |
Annual Sum or Average | 4913.00000 | 23.78611 | 46.19182 | 0.16893 | 7.84988 |
Minimum of Months | 376.00000 | 23.20072 | 38.27531 | -0.1964 | 5.52425 |
Maximum of Months | 422.00000 | 23.91487 | 56.89727 | 0.58062 | 12.16985 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.190622E+10 | 0.522949E+09 | 179.97 | 0.155572E+10 | 0.350505E+09 | 0.00 | 0.39 | 14-JAN-15:30 | 0.00 | 01-JAN-00:10 | 7401.03 | 14-JAN-15:30 | 5696.18 | 14-JAN-15:30 | 1704.85 | 14-JAN-15:30 | 1940.46 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.532213E+10 | 0.144288E+10 | 281.17 | 0.439024E+10 | 0.931891E+09 | 0.00 | 0.60 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 11807.06 | 24-FEB-16:00 | 9587.89 | 24-FEB-15:50 | 3432.51 | 25-FEB-17:00 | 3137.04 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.134883E+11 | 0.367884E+10 | 401.85 | 0.114185E+11 | 0.206986E+10 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 46861.69 | 11-MAR-07:02 | 38489.54 | 29-MAR-06:02 | 10572.64 | 11-MAR-07:02 | 10412.54 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.223261E+11 | 0.634695E+10 | 417.05 | 0.198976E+11 | 0.242859E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 47013.33 | 17-APR-05:01 | 44589.68 | 28-APR-05:01 | 10655.67 | 24-APR-06:02 | 11272.16 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.331218E+11 | 0.947410E+10 | 443.18 | 0.274695E+11 | 0.565230E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 49683.88 | 24-MAY-05:02 | 44694.40 | 06-MAY-05:01 | 20598.17 | 24-MAY-06:04 | 11546.20 | 31-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.367870E+11 | 0.102780E+11 | 437.22 | 0.281455E+11 | 0.864150E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 51035.49 | 26-JUN-05:02 | 43415.55 | 12-JUN-04:02 | 25247.89 | 26-JUN-05:03 | 11832.36 | 12-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.407101E+11 | 0.105120E+11 | 444.33 | 0.274910E+11 | 0.132191E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 51378.75 | 20-JUL-05:01 | 38829.36 | 07-JUL-05:01 | 26016.43 | 20-JUL-05:04 | 11956.11 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.401947E+11 | 0.100472E+11 | 448.71 | 0.262252E+11 | 0.139695E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 50545.41 | 10-AUG-05:01 | 36656.56 | 09-AUG-05:01 | 22116.48 | 17-AUG-06:04 | 11389.88 | 08-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.325475E+11 | 0.818279E+10 | 428.70 | 0.220111E+11 | 0.105364E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 50663.82 | 03-SEP-07:01 | 38736.14 | 27-SEP-05:01 | 24944.00 | 10-SEP-08:04 | 11129.51 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.216314E+11 | 0.573348E+10 | 418.35 | 0.175056E+11 | 0.412589E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 48647.17 | 12-OCT-06:02 | 41204.33 | 02-OCT-05:01 | 18445.23 | 12-OCT-06:04 | 10653.60 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.109660E+11 | 0.295412E+10 | 370.14 | 0.925119E+10 | 0.171486E+10 | 0.00 | 0.95 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 38708.55 | 09-NOV-07:02 | 28957.47 | 09-NOV-07:02 | 9751.08 | 09-NOV-07:02 | 8353.87 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.365562E+10 | 0.994046E+09 | 259.79 | 0.302790E+10 | 0.627721E+09 | 0.00 | 0.44 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 8068.88 | 01-DEC-15:10 | 7376.16 | 01-DEC-15:10 | 1762.50 | 16-DEC-16:00 | 2157.40 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.262657E+12 | 0.701673E+11 | 4530.46 | 0.198389E+12 | 0.642681E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.190622E+10 | 0.522949E+09 | 179.97 | 0.155572E+10 | 0.350505E+09 | 0.00 | 0.39 | 0.00 | 7401.03 | 5696.18 | 1704.85 | 1940.46 | 0.00 | |||||||
Maximum of Months | 0.407101E+11 | 0.105120E+11 | 448.71 | 0.281455E+11 | 0.139695E+11 | 0.00 | 1.00 | 0.00 | 51378.75 | 44694.40 | 26016.43 | 11956.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.108324E+11 | 0.322732E+10 | 188.43 | 0.879012E+10 | 0.204229E+10 | 0.00 | 0.45 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 38404.29 | 14-JAN-15:00 | 31388.70 | 12-JAN-15:10 | 9753.88 | 14-JAN-15:00 | 10913.92 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.288784E+11 | 0.846444E+10 | 283.73 | 0.231981E+11 | 0.568027E+10 | 0.00 | 0.67 | 24-FEB-15:40 | 0.00 | 01-FEB-00:10 | 60793.49 | 24-FEB-15:40 | 49245.56 | 22-FEB-15:10 | 20507.07 | 25-FEB-17:00 | 17378.44 | 24-FEB-15:40 | 0.00 | 01-FEB-00:10 |
March | 0.700259E+11 | 0.205209E+11 | 398.71 | 0.571291E+11 | 0.128968E+11 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 210075.49 | 11-MAR-07:02 | 156486.73 | 13-MAR-06:02 | 56211.01 | 29-MAR-06:02 | 51345.55 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.110659E+12 | 0.338274E+11 | 415.14 | 0.955519E+11 | 0.151074E+11 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 213960.88 | 26-APR-06:02 | 189072.89 | 09-APR-08:62 | 71514.53 | 24-APR-06:02 | 55956.36 | 16-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.160404E+12 | 0.491881E+11 | 443.17 | 0.125285E+12 | 0.351184E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 221927.64 | 24-MAY-06:02 | 192593.74 | 01-MAY-05:01 | 98737.97 | 24-MAY-06:04 | 57430.09 | 04-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.179918E+12 | 0.532316E+11 | 434.47 | 0.124652E+12 | 0.552660E+11 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 228336.21 | 25-JUN-08:62 | 180805.64 | 12-JUN-05:01 | 118525.12 | 25-JUN-08:62 | 58659.22 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.196623E+12 | 0.534380E+11 | 442.74 | 0.113159E+12 | 0.834639E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 228561.99 | 25-JUL-06:02 | 158122.68 | 05-JUL-05:01 | 119570.42 | 28-JUL-06:02 | 59199.49 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.195785E+12 | 0.514817E+11 | 448.12 | 0.105913E+12 | 0.898722E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 230594.72 | 27-AUG-08:62 | 143085.64 | 07-AUG-05:01 | 126262.25 | 20-AUG-08:62 | 56349.15 | 08-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.158440E+12 | 0.421226E+11 | 427.65 | 0.911603E+11 | 0.672797E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 230624.32 | 10-SEP-08:62 | 148054.65 | 26-SEP-05:01 | 127948.76 | 10-SEP-08:62 | 55215.54 | 24-SEP-08:04 | 0.00 | 01-SEP-00:10 |
October | 0.100910E+12 | 0.289694E+11 | 410.98 | 0.758667E+11 | 0.250429E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 220391.18 | 12-OCT-06:02 | 164431.14 | 15-OCT-08:62 | 99577.88 | 12-OCT-06:02 | 53128.76 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.539836E+11 | 0.157440E+11 | 357.50 | 0.437902E+11 | 0.101934E+11 | 0.00 | 0.79 | 09-NOV-13:40 | 0.00 | 01-NOV-00:10 | 150806.31 | 11-NOV-09:02 | 108486.16 | 11-NOV-09:02 | 42320.15 | 11-NOV-09:02 | 35822.44 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.185599E+11 | 0.548009E+10 | 250.37 | 0.149275E+11 | 0.363234E+10 | 0.00 | 0.51 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 | 43365.43 | 28-DEC-15:30 | 37747.05 | 02-DEC-14:40 | 10269.31 | 16-DEC-16:10 | 12648.87 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.128502E+13 | 0.365695E+12 | 4501.01 | 0.879424E+12 | 0.405595E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.108324E+11 | 0.322732E+10 | 188.43 | 0.879012E+10 | 0.204229E+10 | 0.00 | 0.45 | 0.00 | 38404.29 | 31388.70 | 9753.88 | 10913.92 | 0.00 | |||||||
Maximum of Months | 0.196623E+12 | 0.534380E+11 | 448.12 | 0.125285E+12 | 0.898722E+11 | 0.00 | 1.00 | 0.00 | 230624.32 | 192593.74 | 127948.76 | 59199.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.512363E+10 | 0.129050E+10 | 321.58 | 0.447126E+10 | 0.652366E+09 | 0.00 | 0.72 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 9309.49 | 12-JAN-15:10 | 8519.66 | 12-JAN-15:10 | 1553.22 | 13-JAN-13:40 | 2258.19 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.732486E+10 | 0.182936E+10 | 333.47 | 0.631802E+10 | 0.100684E+10 | 0.00 | 0.85 | 22-FEB-14:20 | 0.00 | 01-FEB-00:10 | 11479.71 | 22-FEB-14:20 | 10417.13 | 22-FEB-14:20 | 2584.08 | 25-FEB-16:00 | 2841.60 | 22-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 0.124788E+11 | 0.318826E+10 | 420.12 | 0.107986E+11 | 0.168023E+10 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 30334.76 | 11-MAR-07:02 | 26608.03 | 29-MAR-05:02 | 6979.27 | 11-MAR-07:02 | 6651.38 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.166135E+11 | 0.456846E+10 | 423.72 | 0.148595E+11 | 0.175402E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 30832.29 | 17-APR-05:01 | 28975.82 | 28-APR-05:01 | 8435.40 | 24-APR-06:02 | 7243.42 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.224565E+11 | 0.631189E+10 | 449.57 | 0.184617E+11 | 0.399474E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 32648.75 | 24-MAY-05:02 | 28907.01 | 06-MAY-05:01 | 13890.32 | 24-MAY-06:02 | 7493.46 | 04-MAY-04:02 | 0.00 | 01-MAY-00:10 |
June | 0.246387E+11 | 0.674991E+10 | 441.99 | 0.184889E+11 | 0.614984E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 33616.77 | 26-JUN-05:02 | 27943.18 | 12-JUN-04:02 | 17038.29 | 26-JUN-05:03 | 7622.40 | 14-JUN-04:02 | 0.00 | 01-JUN-00:10 |
July | 0.272812E+11 | 0.690236E+10 | 449.44 | 0.178715E+11 | 0.940969E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 33715.94 | 20-JUL-05:01 | 24905.63 | 07-JUL-04:02 | 17324.49 | 20-JUL-05:03 | 7681.82 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.273835E+11 | 0.671353E+10 | 453.44 | 0.173222E+11 | 0.100614E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 33135.17 | 19-AUG-05:01 | 22907.65 | 08-AUG-04:02 | 15848.34 | 12-AUG-06:04 | 7344.42 | 08-AUG-04:02 | 0.00 | 01-AUG-00:10 |
September | 0.234152E+11 | 0.575858E+10 | 430.93 | 0.156828E+11 | 0.773244E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 33401.18 | 03-SEP-07:01 | 25230.02 | 27-SEP-05:01 | 17244.16 | 10-SEP-08:62 | 7160.57 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.183004E+11 | 0.459971E+10 | 431.66 | 0.150769E+11 | 0.322356E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 31835.50 | 12-OCT-06:02 | 27065.43 | 02-OCT-05:01 | 12921.41 | 12-OCT-06:02 | 6836.48 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.125942E+11 | 0.308786E+10 | 394.11 | 0.109976E+11 | 0.159654E+10 | 0.00 | 1.00 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 | 30209.44 | 09-NOV-07:02 | 24760.76 | 12-NOV-09:02 | 7026.86 | 09-NOV-07:02 | 6408.61 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.696344E+10 | 0.173126E+10 | 358.64 | 0.608128E+10 | 0.882152E+09 | 0.00 | 0.79 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 10235.96 | 02-DEC-14:00 | 9797.06 | 02-DEC-14:00 | 1519.83 | 16-DEC-14:20 | 2482.19 | 28-DEC-14:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.204574E+12 | 0.527317E+11 | 4908.66 | 0.156430E+12 | 0.481438E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.512363E+10 | 0.129050E+10 | 321.58 | 0.447126E+10 | 0.652366E+09 | 0.00 | 0.72 | 0.00 | 9309.49 | 8519.66 | 1519.83 | 2258.19 | 0.00 | |||||||
Maximum of Months | 0.273835E+11 | 0.690236E+10 | 453.44 | 0.184889E+11 | 0.100614E+11 | 0.00 | 1.00 | 0.00 | 33715.94 | 28975.82 | 17324.49 | 7681.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.250839E+10 | 0.645674E+09 | 231.88 | 0.214698E+10 | 0.361411E+09 | 0.00 | 0.65 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 6915.80 | 12-JAN-15:10 | 6175.35 | 12-JAN-15:10 | 1357.30 | 13-JAN-14:00 | 1714.70 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.456961E+10 | 0.116490E+10 | 285.55 | 0.385544E+10 | 0.714177E+09 | 0.00 | 0.82 | 22-FEB-14:20 | 0.00 | 01-FEB-00:10 | 9195.70 | 22-FEB-14:20 | 8172.11 | 22-FEB-14:30 | 2228.01 | 25-FEB-15:40 | 2300.49 | 22-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 0.918052E+10 | 0.238143E+10 | 394.53 | 0.774878E+10 | 0.143174E+10 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 25700.80 | 11-MAR-07:02 | 19668.73 | 29-MAR-06:02 | 6653.76 | 11-MAR-07:02 | 5625.55 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.134798E+11 | 0.372451E+10 | 417.29 | 0.118593E+11 | 0.162052E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 25993.96 | 24-APR-06:02 | 24084.42 | 28-APR-05:01 | 8180.08 | 24-APR-06:02 | 6110.41 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.190395E+11 | 0.532568E+10 | 446.69 | 0.152859E+11 | 0.375363E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 27531.37 | 24-MAY-05:02 | 23693.51 | 01-MAY-05:01 | 12843.34 | 24-MAY-06:04 | 6267.59 | 04-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.211326E+11 | 0.573954E+10 | 439.45 | 0.153034E+11 | 0.582924E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 28373.06 | 26-JUN-05:02 | 22643.10 | 12-JUN-04:02 | 15204.64 | 26-JUN-05:02 | 6431.03 | 14-JUN-04:02 | 0.00 | 01-JUN-00:10 |
July | 0.236634E+11 | 0.591930E+10 | 447.50 | 0.146929E+11 | 0.897045E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 28443.54 | 20-JUL-05:01 | 19407.30 | 07-JUL-05:01 | 15496.57 | 20-JUL-05:03 | 6487.31 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.236475E+11 | 0.572864E+10 | 451.33 | 0.140561E+11 | 0.959146E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 28181.49 | 10-AUG-05:01 | 18371.33 | 09-AUG-05:01 | 14606.93 | 12-AUG-06:04 | 6177.38 | 08-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.198822E+11 | 0.485269E+10 | 428.98 | 0.125964E+11 | 0.728585E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 28247.91 | 10-SEP-08:62 | 19862.36 | 27-SEP-05:01 | 16009.81 | 10-SEP-08:62 | 6049.09 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.149724E+11 | 0.377447E+10 | 425.11 | 0.119801E+11 | 0.299235E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 27073.47 | 12-OCT-06:02 | 21725.54 | 02-OCT-05:01 | 12289.94 | 12-OCT-06:02 | 5784.49 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.949328E+10 | 0.235639E+10 | 378.03 | 0.808797E+10 | 0.140531E+10 | 0.00 | 1.00 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 | 25526.66 | 09-NOV-07:02 | 20010.78 | 12-NOV-09:02 | 7235.97 | 09-NOV-07:02 | 5413.39 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.399338E+10 | 0.101402E+10 | 305.45 | 0.338338E+10 | 0.610001E+09 | 0.00 | 0.74 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7984.64 | 02-DEC-14:00 | 7527.35 | 02-DEC-14:00 | 1356.83 | 16-DEC-14:10 | 1946.87 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.165563E+12 | 0.426272E+11 | 4651.79 | 0.120997E+12 | 0.445661E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.250839E+10 | 0.645674E+09 | 231.88 | 0.214698E+10 | 0.361411E+09 | 0.00 | 0.65 | 0.00 | 6915.80 | 6175.35 | 1356.83 | 1714.70 | 0.00 | |||||||
Maximum of Months | 0.236634E+11 | 0.591930E+10 | 451.33 | 0.153034E+11 | 0.959146E+10 | 0.00 | 1.00 | 0.00 | 28443.54 | 24084.42 | 16009.81 | 6487.31 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 92.01 | 57.86 | 9.33 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.76 | 47.94 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.75 | 33.79 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.57 | 20.28 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.83 | 10.26 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.63 | 6.21 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.09 | 3.76 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.15 | 5.80 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.57 | 12.30 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.21 | 30.63 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 130.01 | 47.14 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.72 | 59.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.94 | 27.83 | 9.33 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.72 | 3.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.83 | 59.10 | 9.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1207.63 | 703.49 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1213.58 | 571.67 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1128.30 | 362.66 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 969.87 | 151.08 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 947.41 | 42.18 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 966.00 | 24.42 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 901.24 | 13.06 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 839.85 | 33.94 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 953.28 | 92.93 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1479.32 | 315.46 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1690.79 | 542.53 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1345.09 | 704.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1136.14 | 295.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 839.85 | 13.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1690.79 | 704.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1214.27 | 675.90 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1216.24 | 550.52 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1126.42 | 345.49 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 967.84 | 137.55 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 949.57 | 33.97 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 971.82 | 19.27 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 906.47 | 8.87 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 840.58 | 26.11 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 951.09 | 79.53 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1475.58 | 301.44 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1689.22 | 526.53 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1348.99 | 684.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1137.46 | 281.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 840.58 | 8.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1689.22 | 684.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.13 | 113.12 | 73.01 | 250.82 | 131.38 | 0.00 | 0.00 | 744.00 |
February | 176.96 | 98.29 | 78.66 | 247.69 | 108.40 | 0.00 | 0.00 | 672.00 |
March | 151.25 | 66.79 | 84.47 | 217.09 | 74.72 | 0.00 | 0.00 | 744.00 |
April | 106.22 | 29.94 | 76.27 | 156.44 | 37.88 | 0.00 | 0.00 | 720.00 |
May | 76.37 | 5.61 | 70.76 | 128.57 | 15.35 | 0.00 | 0.00 | 744.00 |
June | 69.88 | 1.17 | 68.71 | 130.60 | 9.43 | 0.00 | 0.00 | 720.00 |
July | 72.90 | 0.99 | 71.91 | 130.88 | 5.19 | 4.50 | 0.00 | 744.00 |
August | 77.34 | 4.12 | 73.22 | 129.07 | 11.75 | 0.00 | 0.00 | 744.00 |
September | 103.67 | 26.89 | 76.78 | 159.21 | 26.74 | 9.67 | 0.00 | 720.00 |
October | 178.38 | 99.61 | 78.78 | 275.74 | 73.81 | 0.00 | 0.00 | 744.00 |
November | 222.88 | 147.34 | 75.54 | 334.71 | 110.10 | 0.00 | 0.00 | 720.00 |
December | 198.92 | 124.67 | 74.25 | 278.27 | 132.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 134.83 | 59.66 | 75.18 | 202.98 | 61.20 | 14.17 | 0.00 | 8760.00 |
Minimum of Months | 69.88 | 0.99 | 68.71 | 128.57 | 5.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 222.88 | 147.34 | 84.47 | 334.71 | 132.28 | 9.67 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.246435E+09 | 0.154979E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.304250E+09 | 0.115983E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478762E+09 | 90512984.66 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641701E+09 | 52559786.54 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.720046E+09 | 27484687.15 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662606E+09 | 16100949.05 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490400E+09 | 10067716.43 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420914E+09 | 15539347.61 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400635E+09 | 31872488.92 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.445181E+09 | 82046936.92 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336999E+09 | 0.122175E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.242977E+09 | 0.158289E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.539091E+10 | 0.877610E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.242977E+09 | 10067716.43 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.720046E+09 | 0.158289E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.323452E+10 | 0.188422E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.293589E+10 | 0.138298E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.302205E+10 | 0.971346E+09 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.251390E+10 | 0.391587E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.253754E+10 | 0.112982E+09 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.250387E+10 | 63298768.05 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.241387E+10 | 34973856.94 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.224946E+10 | 90900741.13 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.247090E+10 | 0.240872E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.396221E+10 | 0.844919E+09 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.438252E+10 | 0.140624E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.360269E+10 | 0.188792E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.358294E+11 | 0.931224E+10 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.224946E+10 | 34973856.94 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.438252E+10 | 0.188792E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.325230E+10 | 0.181034E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.294232E+10 | 0.133182E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.301701E+10 | 0.925361E+09 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.250864E+10 | 0.356542E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.254333E+10 | 90994465.57 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.251897E+10 | 49947457.46 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.242788E+10 | 23766235.52 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.225140E+10 | 69923133.88 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.246523E+10 | 0.206133E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.395220E+10 | 0.807389E+09 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.437845E+10 | 0.136476E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.361313E+10 | 0.183214E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.358709E+11 | 0.886913E+10 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.225140E+10 | 23766235.52 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.437845E+10 | 0.183214E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.671806E+09 | 0.351889E+09 |
February | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.599206E+09 | 0.262233E+09 |
March | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.581460E+09 | 0.200118E+09 |
April | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.405489E+09 | 98195585.23 |
May | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.344360E+09 | 41100569.87 |
June | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.338526E+09 | 24434973.33 |
July | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.350560E+09 | 13902919.50 |
August | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.345699E+09 | 31468148.13 |
September | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.412670E+09 | 69316251.97 |
October | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.738549E+09 | 0.197701E+09 |
November | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.867581E+09 | 0.285387E+09 |
December | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.745328E+09 | 0.354288E+09 |
Annual Sum or Average | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.640123E+10 | 0.193003E+10 |
Minimum of Months | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.338526E+09 | 13902919.50 |
Maximum of Months | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.867581E+09 | 0.354288E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1472.13 | 925.80 | 1280.29 | 680.77 | 599.52 | 0.00 | 0.00 |
February | 2012.24 | 767.08 | 1632.41 | 913.67 | 718.74 | 0.00 | 0.00 |
March | 2859.99 | 540.70 | 2160.06 | 1282.60 | 877.47 | 0.00 | 0.00 |
April | 3961.11 | 324.44 | 2808.25 | 1963.99 | 844.26 | 0.00 | 0.00 |
May | 4301.35 | 164.19 | 2963.58 | 2042.37 | 921.21 | 0.00 | 0.00 |
June | 4090.16 | 99.39 | 2777.51 | 1762.44 | 1015.07 | 0.00 | 0.00 |
July | 2929.51 | 60.14 | 1947.01 | 694.09 | 1252.92 | 0.00 | 0.00 |
August | 2514.42 | 92.83 | 1678.90 | 472.52 | 1206.38 | 0.00 | 0.00 |
September | 2473.06 | 196.74 | 1743.29 | 743.43 | 999.86 | 0.00 | 0.00 |
October | 2659.39 | 490.13 | 1932.49 | 1221.65 | 710.85 | 0.00 | 0.00 |
November | 2080.24 | 754.17 | 1622.76 | 1068.61 | 554.15 | 0.00 | 0.00 |
December | 1451.48 | 945.57 | 1246.60 | 670.01 | 576.59 | 0.00 | 0.00 |
Annual Sum or Average | 2735.11 | 445.26 | 1982.85 | 1125.26 | 857.58 | 0.00 | 0.00 |
Minimum of Months | 1451.48 | 60.14 | 1246.60 | 472.52 | 554.15 | 0.00 | 0.00 |
Maximum of Months | 4301.35 | 945.57 | 2963.58 | 2042.37 | 1252.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1207.63 | 703.49 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1213.58 | 571.67 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1128.30 | 362.66 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 969.87 | 151.08 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 947.41 | 42.18 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 966.00 | 24.42 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 901.24 | 13.06 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 839.85 | 33.94 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 953.28 | 92.93 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1479.32 | 315.46 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1690.79 | 542.53 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1345.09 | 704.87 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1136.14 | 295.29 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 839.85 | 13.06 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1690.79 | 704.87 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1214.27 | 675.90 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1216.24 | 550.52 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1126.42 | 345.49 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 967.84 | 137.55 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 949.57 | 33.97 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 971.82 | 19.27 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 906.47 | 8.87 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 840.58 | 26.11 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 951.09 | 79.53 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1475.58 | 301.44 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1689.22 | 526.53 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1348.99 | 684.04 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1137.46 | 281.24 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 840.58 | 8.87 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1689.22 | 684.04 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 250.82 | 131.38 | 186.13 | 113.12 | 73.01 | 0.00 | 0.00 |
February | 247.69 | 108.40 | 176.96 | 98.29 | 78.66 | 0.00 | 0.00 |
March | 217.09 | 74.72 | 151.25 | 66.79 | 84.47 | 0.00 | 0.00 |
April | 156.44 | 37.88 | 106.22 | 29.94 | 76.27 | 0.00 | 0.00 |
May | 128.57 | 15.35 | 76.37 | 5.61 | 70.76 | 0.00 | 0.00 |
June | 130.60 | 9.43 | 69.88 | 1.17 | 68.71 | 0.00 | 0.00 |
July | 130.88 | 5.19 | 72.90 | 0.99 | 71.91 | 0.00 | 0.00 |
August | 129.07 | 11.75 | 77.34 | 4.12 | 73.22 | 0.00 | 0.00 |
September | 159.21 | 26.74 | 103.67 | 26.89 | 76.78 | 0.00 | 0.00 |
October | 275.74 | 73.81 | 178.38 | 99.61 | 78.78 | 0.00 | 0.00 |
November | 334.71 | 110.10 | 222.88 | 147.34 | 75.54 | 0.00 | 0.00 |
December | 278.27 | 132.28 | 198.92 | 124.67 | 74.25 | 0.00 | 0.00 |
Annual Sum or Average | 202.98 | 61.20 | 134.83 | 59.66 | 75.18 | 0.00 | 0.00 |
Minimum of Months | 128.57 | 5.19 | 69.88 | 0.99 | 68.71 | 0.00 | 0.00 |
Maximum of Months | 334.71 | 132.28 | 222.88 | 147.34 | 84.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.394296E+10 | 0.247966E+10 | 0.342912E+10 | 0.182338E+10 | 0.160574E+10 | 0.00 | 0.00 |
February | 0.486801E+10 | 0.185572E+10 | 0.394912E+10 | 0.221035E+10 | 0.173877E+10 | 0.00 | 0.00 |
March | 0.766019E+10 | 0.144821E+10 | 0.578551E+10 | 0.343531E+10 | 0.235021E+10 | 0.00 | 0.00 |
April | 0.102672E+11 | 0.840957E+09 | 0.727900E+10 | 0.509067E+10 | 0.218833E+10 | 0.00 | 0.00 |
May | 0.115207E+11 | 0.439755E+09 | 0.793764E+10 | 0.547029E+10 | 0.246736E+10 | 0.00 | 0.00 |
June | 0.106017E+11 | 0.257615E+09 | 0.719930E+10 | 0.456825E+10 | 0.263105E+10 | 0.00 | 0.00 |
July | 0.784641E+10 | 0.161083E+09 | 0.521487E+10 | 0.185906E+10 | 0.335581E+10 | 0.00 | 0.00 |
August | 0.673463E+10 | 0.248630E+09 | 0.449676E+10 | 0.126559E+10 | 0.323117E+10 | 0.00 | 0.00 |
September | 0.641016E+10 | 0.509960E+09 | 0.451861E+10 | 0.192697E+10 | 0.259163E+10 | 0.00 | 0.00 |
October | 0.712290E+10 | 0.131275E+10 | 0.517598E+10 | 0.327206E+10 | 0.190393E+10 | 0.00 | 0.00 |
November | 0.539198E+10 | 0.195480E+10 | 0.420620E+10 | 0.276983E+10 | 0.143636E+10 | 0.00 | 0.00 |
December | 0.388764E+10 | 0.253262E+10 | 0.333889E+10 | 0.179456E+10 | 0.154433E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.862545E+11 | 0.140418E+11 | 0.625310E+11 | 0.354863E+11 | 0.270447E+11 | 0.00 | 0.00 |
Minimum of Months | 0.388764E+10 | 0.161083E+09 | 0.333889E+10 | 0.126559E+10 | 0.143636E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115207E+11 | 0.253262E+10 | 0.793764E+10 | 0.547029E+10 | 0.335581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323452E+10 | 0.188422E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.293589E+10 | 0.138298E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.302205E+10 | 0.971346E+09 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.251390E+10 | 0.391587E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.253754E+10 | 0.112982E+09 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.250387E+10 | 63298768.05 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.241387E+10 | 34973856.94 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.224946E+10 | 90900741.13 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.247090E+10 | 0.240872E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.396221E+10 | 0.844919E+09 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.438252E+10 | 0.140624E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.360269E+10 | 0.188792E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.358294E+11 | 0.931224E+10 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224946E+10 | 34973856.94 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.438252E+10 | 0.188792E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325230E+10 | 0.181034E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.294232E+10 | 0.133182E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.301701E+10 | 0.925361E+09 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.250864E+10 | 0.356542E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.254333E+10 | 90994465.57 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.251897E+10 | 49947457.46 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.242788E+10 | 23766235.52 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.225140E+10 | 69923133.88 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.246523E+10 | 0.206133E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.395220E+10 | 0.807389E+09 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.437845E+10 | 0.136476E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.361313E+10 | 0.183214E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.358709E+11 | 0.886913E+10 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225140E+10 | 23766235.52 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.437845E+10 | 0.183214E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.671806E+09 | 0.351889E+09 | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.00 | 0.00 |
February | 0.599206E+09 | 0.262233E+09 | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.00 | 0.00 |
March | 0.581460E+09 | 0.200118E+09 | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.00 | 0.00 |
April | 0.405489E+09 | 98195585.23 | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.00 | 0.00 |
May | 0.344360E+09 | 41100569.87 | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.00 | 0.00 |
June | 0.338526E+09 | 24434973.33 | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.00 | 0.00 |
July | 0.350560E+09 | 13902919.50 | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.00 | 0.00 |
August | 0.345699E+09 | 31468148.13 | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.00 | 0.00 |
September | 0.412670E+09 | 69316251.97 | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.00 | 0.00 |
October | 0.738549E+09 | 0.197701E+09 | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.00 | 0.00 |
November | 0.867581E+09 | 0.285387E+09 | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.00 | 0.00 |
December | 0.745328E+09 | 0.354288E+09 | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.640123E+10 | 0.193003E+10 | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.00 | 0.00 |
Minimum of Months | 0.338526E+09 | 13902919.50 | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.00 | 0.00 |
Maximum of Months | 0.867581E+09 | 0.354288E+09 | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.220405E+10 | -.180378E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -400271527.4 | 59.00 | 0.00 | 0.00 |
February | 0.196101E+10 | -.160755E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -353461482.9 | 58.99 | 0.00 | 0.00 |
March | 0.208530E+10 | -.170245E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382842243.9 | 58.99 | 0.00 | 0.00 |
April | 0.181624E+10 | -.145247E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -363768482.1 | 58.99 | 0.00 | 0.00 |
May | 0.169845E+10 | -.132688E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -371569240.4 | 58.99 | 0.00 | 0.00 |
June | 0.152749E+10 | -.116832E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -359168933.8 | 58.99 | 0.00 | 0.00 |
July | 0.148789E+10 | -.111752E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -370361965.7 | 58.99 | 0.00 | 0.00 |
August | 0.156577E+10 | -.119402E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -371747964.1 | 58.99 | 0.00 | 0.00 |
September | 0.161755E+10 | -.125598E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -361572992.7 | 58.99 | 0.00 | 0.00 |
October | 0.182574E+10 | -.144865E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -377084649.0 | 58.99 | 0.00 | 0.00 |
November | 0.193379E+10 | -.156203E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -371752917.4 | 58.99 | 0.00 | 0.00 |
December | 0.214716E+10 | -.175316E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -394003354.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.218704E+11 | -.173928E+11 | 8760.00 | -.447761E+10 | 58.99 | |||||
Minimum of Months | 0.148789E+10 | -.180378E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -400271527.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.220405E+10 | -.111752E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -353461482.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.80 | 0.50 | 14-JAN-11:39 | 323.38 | 8.09 | 0.00 | 30.00 | 266.49 | 6.65 | 0.00 | 4.67 |
February | 303.83 | 0.76 | 0.50 | 01-FEB-10:00 | 385.45 | 8.99 | 0.00 | 78.83 | 319.10 | 7.43 | 0.00 | 44.33 |
March | 364.50 | 0.71 | 0.50 | 01-MAR-10:00 | 2499.35 | 10.09 | 0.00 | 174.00 | 2685.86 | 8.50 | 0.00 | 103.17 |
April | 379.83 | 0.73 | 0.50 | 01-APR-10:20 | 421.38 | 10.32 | 0.00 | 128.67 | 350.10 | 8.69 | 0.00 | 72.50 |
May | 406.00 | 0.73 | 0.50 | 04-MAY-11:00 | 423.67 | 11.57 | 0.00 | 117.33 | 352.46 | 9.88 | 0.00 | 65.00 |
June | 386.67 | 0.71 | 0.50 | 01-JUN-09:09 | 454.45 | 12.32 | 0.00 | 143.83 | 376.83 | 10.55 | 0.00 | 91.67 |
July | 379.83 | 0.68 | 0.50 | 01-JUL-10:09 | 530.31 | 13.18 | 0.00 | 207.83 | 447.27 | 11.53 | 0.00 | 145.50 |
August | 372.50 | 0.68 | 0.50 | 01-AUG-08:50 | 596.27 | 12.53 | 0.00 | 194.50 | 520.02 | 10.94 | 0.00 | 142.33 |
September | 344.33 | 0.69 | 0.50 | 01-SEP-09:09 | 1385.39 | 11.43 | 0.00 | 173.50 | 1375.41 | 9.80 | 0.00 | 119.17 |
October | 347.33 | 0.74 | 0.50 | 01-OCT-10:00 | 404.52 | 9.13 | 0.00 | 100.83 | 336.04 | 7.64 | 0.00 | 59.67 |
November | 317.83 | 0.81 | 0.58 | 28-NOV-10:50 | 322.92 | 7.92 | 0.00 | 1.33 | 267.36 | 6.43 | 0.00 | 0.00 |
December | 315.50 | 0.81 | 0.58 | 08-DEC-11:39 | 315.35 | 7.96 | 0.00 | 8.33 | 259.31 | 6.48 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.73 | 680.21 | 10.42 | 0.00 | 1359.00 | 638.00 | 8.84 | 0.00 | 848.00 | ||
Minimum of Months | 303.83 | 0.68 | 0.50 | 315.35 | 7.92 | 0.00 | 1.33 | 259.31 | 6.43 | 0.00 | 0.00 | |
Maximum of Months | 406.00 | 0.81 | 0.58 | 2499.35 | 13.18 | 0.00 | 207.83 | 2685.86 | 11.53 | 0.00 | 145.50 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.382059E+09 | 44868.92 | 01-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7285687.71 | 7325.67 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13198167.64 | 16503.74 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402543E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382059E+09 | 44868.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201282E+10 | 182769.75 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73657043.34 | 52767.84 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147859E+09 | 94087.27 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223433E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201282E+10 | 182769.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 56684247.80 | 17055.32 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1218527.97 | 5311.31 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 748798.03 | 2568.81 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58651573.81 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56684247.80 | 17055.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204658E+09 | 18712.34 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21380278.17 | 15876.17 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14173506.79 | 10554.07 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240212E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204658E+09 | 18712.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175738E+10 | 12241.31 | 01-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319073E+09 | 9533.65 | 10-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1735097.03 | 993.36 | 30-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125952E+10 | 13543.14 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333771E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175738E+10 | 13543.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.190622E+10 | 0.155572E+10 | 7401.03 | 14-JAN-15:30 | 5696.18 | 0.00 |
February | 0.00 | 0.00 | 0.532213E+10 | 0.439024E+10 | 11807.06 | 24-FEB-16:00 | 9585.90 | 0.00 |
March | 0.00 | 0.00 | 0.134883E+11 | 0.114185E+11 | 46861.69 | 11-MAR-07:02 | 36289.05 | 0.00 |
April | 0.00 | 0.00 | 0.223261E+11 | 0.198976E+11 | 47013.33 | 17-APR-05:01 | 38624.69 | 0.00 |
May | 0.00 | 0.00 | 0.331218E+11 | 0.274695E+11 | 49683.88 | 24-MAY-05:02 | 29904.51 | 0.00 |
June | 0.00 | 0.00 | 0.367870E+11 | 0.281455E+11 | 51035.49 | 26-JUN-05:02 | 25957.35 | 0.00 |
July | 0.00 | 0.00 | 0.407101E+11 | 0.274910E+11 | 51378.75 | 20-JUL-05:01 | 25678.14 | 0.00 |
August | 0.00 | 0.00 | 0.401947E+11 | 0.262252E+11 | 50545.41 | 10-AUG-05:01 | 29818.29 | 0.00 |
September | 0.00 | 0.00 | 0.325475E+11 | 0.220111E+11 | 50663.82 | 03-SEP-07:01 | 27942.87 | 0.00 |
October | 0.00 | 0.00 | 0.216314E+11 | 0.175056E+11 | 48647.17 | 12-OCT-06:02 | 30559.87 | 0.00 |
November | 0.00 | 0.00 | 0.109660E+11 | 0.925119E+10 | 38708.55 | 09-NOV-07:02 | 28957.47 | 0.00 |
December | 0.00 | 0.00 | 0.365562E+10 | 0.302790E+10 | 8068.88 | 01-DEC-15:10 | 7376.16 | 0.00 |
Annual Sum or Average | 0.262657E+12 | 0.198389E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.190622E+10 | 0.155572E+10 | 7401.03 | 5696.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.407101E+11 | 0.281455E+11 | 51378.75 | 38624.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.108324E+11 | 0.879012E+10 | 38404.29 | 14-JAN-15:00 | 28650.40 | 0.00 |
February | 0.00 | 0.00 | 0.288784E+11 | 0.231981E+11 | 60793.49 | 24-FEB-15:40 | 47563.18 | 0.00 |
March | 0.00 | 0.00 | 0.700259E+11 | 0.571291E+11 | 210075.49 | 11-MAR-07:02 | 153946.51 | 0.00 |
April | 0.00 | 0.00 | 0.110659E+12 | 0.955519E+11 | 213960.88 | 26-APR-06:02 | 144179.02 | 0.00 |
May | 0.00 | 0.00 | 0.160404E+12 | 0.125285E+12 | 221927.64 | 24-MAY-06:02 | 123580.30 | 0.00 |
June | 0.00 | 0.00 | 0.179918E+12 | 0.124652E+12 | 228336.21 | 25-JUN-08:62 | 109811.09 | 0.00 |
July | 0.00 | 0.00 | 0.196623E+12 | 0.113159E+12 | 228561.99 | 25-JUL-06:02 | 109527.19 | 0.00 |
August | 0.00 | 0.00 | 0.195785E+12 | 0.105913E+12 | 230594.72 | 27-AUG-08:62 | 105618.47 | 0.00 |
September | 0.00 | 0.00 | 0.158440E+12 | 0.911603E+11 | 230624.32 | 10-SEP-08:62 | 102675.56 | 0.00 |
October | 0.00 | 0.00 | 0.100910E+12 | 0.758667E+11 | 220391.18 | 12-OCT-06:02 | 120813.30 | 0.00 |
November | 0.00 | 0.00 | 0.539836E+11 | 0.437902E+11 | 150806.31 | 11-NOV-09:02 | 108486.16 | 0.00 |
December | 0.00 | 0.00 | 0.185599E+11 | 0.149275E+11 | 43365.43 | 28-DEC-15:30 | 35635.06 | 0.00 |
Annual Sum or Average | 0.128502E+13 | 0.879424E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.108324E+11 | 0.879012E+10 | 38404.29 | 28650.40 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196623E+12 | 0.125285E+12 | 230624.32 | 153946.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.512363E+10 | 0.447126E+10 | 9309.49 | 12-JAN-15:10 | 8519.66 | 0.00 |
February | 0.00 | 0.00 | 0.732486E+10 | 0.631802E+10 | 11479.71 | 22-FEB-14:20 | 10417.13 | 0.00 |
March | 0.00 | 0.00 | 0.124788E+11 | 0.107986E+11 | 30334.76 | 11-MAR-07:02 | 23355.49 | 0.00 |
April | 0.00 | 0.00 | 0.166135E+11 | 0.148595E+11 | 30832.29 | 17-APR-05:01 | 24911.03 | 0.00 |
May | 0.00 | 0.00 | 0.224565E+11 | 0.184617E+11 | 32648.75 | 24-MAY-05:02 | 19148.63 | 0.00 |
June | 0.00 | 0.00 | 0.246387E+11 | 0.184889E+11 | 33616.77 | 26-JUN-05:02 | 16702.03 | 0.00 |
July | 0.00 | 0.00 | 0.272812E+11 | 0.178715E+11 | 33715.94 | 20-JUL-05:01 | 16575.95 | 0.00 |
August | 0.00 | 0.00 | 0.273835E+11 | 0.173222E+11 | 33135.17 | 19-AUG-05:01 | 18666.72 | 0.00 |
September | 0.00 | 0.00 | 0.234152E+11 | 0.156828E+11 | 33401.18 | 03-SEP-07:01 | 17764.31 | 0.00 |
October | 0.00 | 0.00 | 0.183004E+11 | 0.150769E+11 | 31835.50 | 12-OCT-06:02 | 18914.09 | 0.00 |
November | 0.00 | 0.00 | 0.125942E+11 | 0.109976E+11 | 30209.44 | 09-NOV-07:02 | 23182.58 | 0.00 |
December | 0.00 | 0.00 | 0.696344E+10 | 0.608128E+10 | 10235.96 | 02-DEC-14:00 | 9797.06 | 0.00 |
Annual Sum or Average | 0.204574E+12 | 0.156430E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.512363E+10 | 0.447126E+10 | 9309.49 | 8519.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.273835E+11 | 0.184889E+11 | 33715.94 | 24911.03 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.250839E+10 | 0.214698E+10 | 6915.80 | 12-JAN-15:10 | 6175.35 | 0.00 |
February | 0.00 | 0.00 | 0.456961E+10 | 0.385544E+10 | 9195.70 | 22-FEB-14:20 | 8169.97 | 0.00 |
March | 0.00 | 0.00 | 0.918052E+10 | 0.774878E+10 | 25700.80 | 11-MAR-07:02 | 19047.04 | 0.00 |
April | 0.00 | 0.00 | 0.134798E+11 | 0.118593E+11 | 25993.96 | 24-APR-06:02 | 17813.89 | 0.00 |
May | 0.00 | 0.00 | 0.190395E+11 | 0.152859E+11 | 27531.37 | 24-MAY-05:02 | 15219.96 | 0.00 |
June | 0.00 | 0.00 | 0.211326E+11 | 0.153034E+11 | 28373.06 | 26-JUN-05:02 | 13168.43 | 0.00 |
July | 0.00 | 0.00 | 0.236634E+11 | 0.146929E+11 | 28443.54 | 20-JUL-05:01 | 13053.01 | 0.00 |
August | 0.00 | 0.00 | 0.236475E+11 | 0.140561E+11 | 28181.49 | 10-AUG-05:01 | 15021.83 | 0.00 |
September | 0.00 | 0.00 | 0.198822E+11 | 0.125964E+11 | 28247.91 | 10-SEP-08:62 | 12238.10 | 0.00 |
October | 0.00 | 0.00 | 0.149724E+11 | 0.119801E+11 | 27073.47 | 12-OCT-06:02 | 14783.53 | 0.00 |
November | 0.00 | 0.00 | 0.949328E+10 | 0.808797E+10 | 25526.66 | 09-NOV-07:02 | 18290.70 | 0.00 |
December | 0.00 | 0.00 | 0.399338E+10 | 0.338338E+10 | 7984.64 | 02-DEC-14:00 | 7527.35 | 0.00 |
Annual Sum or Average | 0.165563E+12 | 0.120997E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.250839E+10 | 0.214698E+10 | 6915.80 | 6175.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236634E+11 | 0.153034E+11 | 28443.54 | 19047.04 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164862E+10 | 0.36 | 1565.63 | 01-JAN-08:62 | 0.93 |
February | 0.560277E+09 | 0.14 | 1565.63 | 01-FEB-08:70 | 0.93 |
March | 76783569.13 | 0.02 | 1565.63 | 01-MAR-08:70 | 0.92 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 375750.49 | 0.00 | 1565.63 | 28-OCT-07:09 | 0.92 |
November | 89694773.50 | 0.02 | 1565.63 | 01-NOV-07:08 | 0.92 |
December | 0.127408E+10 | 0.28 | 1565.63 | 01-DEC-08:70 | 0.93 |
Annual Sum or Average | 0.364983E+10 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164862E+10 | 0.36 | 1565.63 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157685E+10 | 0.33 | 2161.44 | 01-JAN-08:62 | 0.84 |
February | 0.142261E+10 | 0.33 | 1171.23 | 02-FEB-07:03 | 0.61 |
March | 0.159641E+10 | 0.33 | 2445.03 | 11-MAR-07:02 | 0.89 |
April | 0.154862E+10 | 0.33 | 2445.03 | 01-APR-06:02 | 0.89 |
May | 0.176935E+10 | 0.35 | 2445.03 | 01-MAY-05:01 | 0.90 |
June | 0.188976E+10 | 0.37 | 2445.03 | 01-JUN-05:02 | 0.89 |
July | 0.195163E+10 | 0.37 | 2445.03 | 01-JUL-05:01 | 0.89 |
August | 0.190027E+10 | 0.36 | 2445.03 | 01-AUG-05:01 | 0.88 |
September | 0.163481E+10 | 0.34 | 2445.03 | 01-SEP-05:01 | 0.88 |
October | 0.157602E+10 | 0.32 | 2445.03 | 01-OCT-07:02 | 0.89 |
November | 0.151075E+10 | 0.32 | 1962.24 | 09-NOV-07:02 | 0.81 |
December | 0.157064E+10 | 0.32 | 1413.30 | 23-DEC-07:03 | 0.68 |
Annual Sum or Average | 0.199477E+11 | 0.34 | |||
Minimum of Months | 0.142261E+10 | 0.32 | 1171.23 | 0.61 | |
Maximum of Months | 0.195163E+10 | 0.37 | 2445.03 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.885985E+10 | 0.51 | 12499.79 | 02-JAN-07:03 | 1.35 |
February | 0.797622E+10 | 0.51 | 7508.30 | 02-FEB-07:03 | 1.04 |
March | 0.894784E+10 | 0.52 | 13705.63 | 11-MAR-07:02 | 1.40 |
April | 0.881271E+10 | 0.52 | 13705.63 | 01-APR-06:02 | 1.41 |
May | 0.103345E+11 | 0.56 | 13705.63 | 01-MAY-05:01 | 1.41 |
June | 0.110411E+11 | 0.59 | 13705.63 | 01-JUN-05:02 | 1.40 |
July | 0.112879E+11 | 0.58 | 13705.63 | 01-JUL-05:01 | 1.40 |
August | 0.111598E+11 | 0.58 | 13705.63 | 01-AUG-05:01 | 1.39 |
September | 0.945848E+10 | 0.54 | 13705.63 | 01-SEP-05:01 | 1.39 |
October | 0.884096E+10 | 0.51 | 13705.63 | 01-OCT-08:62 | 1.40 |
November | 0.846732E+10 | 0.51 | 9295.37 | 11-NOV-09:02 | 1.16 |
December | 0.880798E+10 | 0.51 | 9094.78 | 23-DEC-07:03 | 1.16 |
Annual Sum or Average | 0.113995E+12 | 0.54 | |||
Minimum of Months | 0.797622E+10 | 0.51 | 7508.30 | 1.04 | |
Maximum of Months | 0.112879E+11 | 0.59 | 13705.63 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.931804E+09 | 0.34 | 1035.90 | 02-JAN-07:03 | 0.79 |
February | 0.844611E+09 | 0.34 | 722.46 | 11-FEB-07:03 | 0.64 |
March | 0.949115E+09 | 0.34 | 1451.76 | 11-MAR-07:02 | 0.92 |
April | 0.944678E+09 | 0.35 | 1451.76 | 01-APR-06:02 | 0.92 |
May | 0.108341E+10 | 0.37 | 1451.76 | 01-MAY-05:01 | 0.93 |
June | 0.114201E+10 | 0.39 | 1451.76 | 01-JUN-05:02 | 0.92 |
July | 0.118284E+10 | 0.39 | 1451.76 | 01-JUL-05:01 | 0.92 |
August | 0.117952E+10 | 0.39 | 1451.76 | 01-AUG-05:01 | 0.91 |
September | 0.104810E+10 | 0.37 | 1451.76 | 01-SEP-05:01 | 0.92 |
October | 0.976832E+09 | 0.34 | 1451.76 | 01-OCT-07:02 | 0.92 |
November | 0.897795E+09 | 0.33 | 1451.76 | 09-NOV-07:02 | 0.92 |
December | 0.932401E+09 | 0.34 | 649.26 | 23-DEC-07:03 | 0.60 |
Annual Sum or Average | 0.121131E+11 | 0.36 | |||
Minimum of Months | 0.844611E+09 | 0.33 | 649.26 | 0.60 | |
Maximum of Months | 0.118284E+10 | 0.39 | 1451.76 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.760512E+09 | 0.34 | 960.17 | 02-JAN-07:03 | 0.84 |
February | 0.686148E+09 | 0.34 | 886.09 | 11-FEB-07:03 | 0.81 |
March | 0.769936E+09 | 0.34 | 1178.47 | 11-MAR-07:02 | 0.92 |
April | 0.766311E+09 | 0.35 | 1178.47 | 01-APR-06:02 | 0.92 |
May | 0.883384E+09 | 0.37 | 1178.47 | 01-MAY-05:01 | 0.93 |
June | 0.937234E+09 | 0.39 | 1178.47 | 01-JUN-06:02 | 0.92 |
July | 0.979037E+09 | 0.39 | 1178.47 | 01-JUL-05:01 | 0.92 |
August | 0.970918E+09 | 0.39 | 1178.47 | 01-AUG-05:01 | 0.91 |
September | 0.857646E+09 | 0.37 | 1178.47 | 01-SEP-05:01 | 0.91 |
October | 0.794322E+09 | 0.34 | 1178.47 | 01-OCT-07:02 | 0.92 |
November | 0.728536E+09 | 0.33 | 1178.47 | 09-NOV-07:02 | 0.92 |
December | 0.757234E+09 | 0.34 | 747.07 | 23-DEC-07:03 | 0.74 |
Annual Sum or Average | 0.989122E+10 | 0.36 | |||
Minimum of Months | 0.686148E+09 | 0.33 | 747.07 | 0.74 | |
Maximum of Months | 0.979037E+09 | 0.39 | 1178.47 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 3.97 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.18 | 0.00 |
May | 0.39 | 0.00 |
June | 0.82 | 0.00 |
July | 1.16 | 0.00 |
August | 1.29 | 0.00 |
September | 0.62 | 0.00 |
October | 0.11 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 5.04 | 0.37 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.29 | 3.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.83 | 3.52 |
February | 0.61 | 0.00 |
March | 0.12 | 0.00 |
April | 0.18 | 0.00 |
May | 0.19 | 0.00 |
June | 0.24 | 0.00 |
July | 0.27 | 0.00 |
August | 0.34 | 0.00 |
September | 0.46 | 0.00 |
October | 0.07 | 0.00 |
November | 0.14 | 0.00 |
December | 0.92 | 0.00 |
Annual Sum or Average | 5.38 | 1.20 |
Minimum of Months | 0.07 | 0.00 |
Maximum of Months | 1.83 | 3.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.28 | 0.00 |
March | 1.35 | 0.00 |
April | 2.02 | 0.00 |
May | 0.93 | 0.00 |
June | 1.59 | 0.00 |
July | 1.66 | 0.00 |
August | 1.90 | 0.00 |
September | 2.96 | 0.00 |
October | 1.30 | 0.00 |
November | 1.26 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 15.38 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.96 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.28 | 1.95 |
February | 0.06 | 2.44 |
March | 0.46 | 0.44 |
April | 1.27 | 0.64 |
May | 0.64 | 0.00 |
June | 1.33 | 0.00 |
July | 1.24 | 0.00 |
August | 1.84 | 0.00 |
September | 2.26 | 0.00 |
October | 0.64 | 0.00 |
November | 0.38 | 0.00 |
December | 0.06 | 0.00 |
Annual Sum or Average | 10.43 | 0.16 |
Minimum of Months | 0.06 | 0.00 |
Maximum of Months | 2.26 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 13.92 | 0.00 |
February | 14.28 | 0.00 |
March | 4.76 | 0.00 |
April | 3.36 | 0.00 |
May | 3.52 | 0.00 |
June | 3.08 | 0.00 |
July | 2.02 | 0.00 |
August | 1.53 | 0.00 |
September | 1.54 | 0.00 |
October | 2.14 | 0.00 |
November | 7.43 | 0.00 |
December | 23.54 | 0.00 |
Annual Sum or Average | 81.13 | 0.00 |
Minimum of Months | 1.53 | 0.00 |
Maximum of Months | 23.54 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.209980E+10 | 0.477574E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.286549E+10 | 9107109.64 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.527525E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.789556E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.112434E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.121677E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.124636E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.119475E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.981759E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.730950E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.446487E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.256469E+10 | 16497709.55 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.901150E+11 | 0.503179E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.209980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.124636E+11 | 0.477574E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120872E+11 | 0.251602E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.164407E+11 | 92071304.18 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.294687E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.426401E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.595226E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.642727E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.647259E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.626415E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.515811E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.378103E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.242113E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.142881E+11 | 0.184824E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.479690E+12 | 0.279292E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120872E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.647259E+11 | 0.251602E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.222231E+10 | 70855309.76 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.267397E+10 | 1523159.97 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.413738E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.551314E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.739530E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.789192E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.808520E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.789305E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.680668E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.557654E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.398565E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.266367E+10 | 935997.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.648448E+11 | 73314467.26 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.222231E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.808520E+10 | 70855309.76 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.140619E+10 | 0.255822E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.185105E+10 | 26725347.71 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.315136E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.449082E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.620906E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.667678E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.689834E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.669956E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.571034E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.456879E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.308493E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.177126E+10 | 17716883.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.525185E+11 | 0.300264E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.140619E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.689834E+10 | 0.255822E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157685E+10 | 0.190622E+10 | 0.382059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142261E+10 | 0.532213E+10 | 7285687.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159641E+10 | 0.134883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154862E+10 | 0.223261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176935E+10 | 0.331218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188976E+10 | 0.367870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195163E+10 | 0.407101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190027E+10 | 0.401947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163481E+10 | 0.325475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157602E+10 | 0.216314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151075E+10 | 0.109660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157064E+10 | 0.365562E+10 | 13198167.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199477E+11 | 0.262657E+12 | 0.402543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142261E+10 | 0.190622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195163E+10 | 0.407101E+11 | 0.382059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.885985E+10 | 0.108324E+11 | 0.201282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797622E+10 | 0.288784E+11 | 73657043.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894784E+10 | 0.700259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.881271E+10 | 0.110659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103345E+11 | 0.160404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110411E+11 | 0.179918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112879E+11 | 0.196623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111598E+11 | 0.195785E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945848E+10 | 0.158440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.884096E+10 | 0.100910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.846732E+10 | 0.539836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880798E+10 | 0.185599E+11 | 0.147859E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113995E+12 | 0.128502E+13 | 0.223433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.797622E+10 | 0.108324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112879E+11 | 0.196623E+12 | 0.201282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.931804E+09 | 0.512363E+10 | 56684247.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844611E+09 | 0.732486E+10 | 1218527.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949115E+09 | 0.124788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.944678E+09 | 0.166135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108341E+10 | 0.224565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114201E+10 | 0.246387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118284E+10 | 0.272812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117952E+10 | 0.273835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104810E+10 | 0.234152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.976832E+09 | 0.183004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897795E+09 | 0.125942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.932401E+09 | 0.696344E+10 | 748798.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121131E+11 | 0.204574E+12 | 58651573.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.844611E+09 | 0.512363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118284E+10 | 0.273835E+11 | 56684247.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.760512E+09 | 0.250839E+10 | 0.204658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686148E+09 | 0.456961E+10 | 21380278.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769936E+09 | 0.918052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766311E+09 | 0.134798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.883384E+09 | 0.190395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.937234E+09 | 0.211326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.979037E+09 | 0.236634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.970918E+09 | 0.236475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857646E+09 | 0.198822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.794322E+09 | 0.149724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728536E+09 | 0.949328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.757234E+09 | 0.399338E+10 | 14173506.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.989122E+10 | 0.165563E+12 | 0.240212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.686148E+09 | 0.250839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.979037E+09 | 0.236634E+11 | 0.204658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157685E+10 | 0.00 | 0.00 | 0.00 | 0.522949E+09 | 0.00 | 0.477574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142261E+10 | 0.00 | 0.00 | 0.00 | 0.144288E+10 | 0.00 | 9107109.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159641E+10 | 0.00 | 0.00 | 0.00 | 0.367884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154862E+10 | 0.00 | 0.00 | 0.00 | 0.634695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176935E+10 | 0.00 | 0.00 | 0.00 | 0.947410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188976E+10 | 0.00 | 0.00 | 0.00 | 0.102780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195163E+10 | 0.00 | 0.00 | 0.00 | 0.105120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190027E+10 | 0.00 | 0.00 | 0.00 | 0.100472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.818279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157602E+10 | 0.00 | 0.00 | 0.00 | 0.573348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151075E+10 | 0.00 | 0.00 | 0.00 | 0.295412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157064E+10 | 0.00 | 0.00 | 0.00 | 0.994046E+09 | 0.00 | 16497709.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199477E+11 | 0.00 | 0.00 | 0.00 | 0.701673E+11 | 0.00 | 0.503179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.142261E+10 | 0.00 | 0.00 | 0.00 | 0.522949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195163E+10 | 0.00 | 0.00 | 0.00 | 0.105120E+11 | 0.00 | 0.477574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.885985E+10 | 0.00 | 0.00 | 0.00 | 0.322732E+10 | 0.00 | 0.251602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797622E+10 | 0.00 | 0.00 | 0.00 | 0.846444E+10 | 0.00 | 92071304.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.894784E+10 | 0.00 | 0.00 | 0.00 | 0.205209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.881271E+10 | 0.00 | 0.00 | 0.00 | 0.338274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103345E+11 | 0.00 | 0.00 | 0.00 | 0.491881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110411E+11 | 0.00 | 0.00 | 0.00 | 0.532316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112879E+11 | 0.00 | 0.00 | 0.00 | 0.534380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111598E+11 | 0.00 | 0.00 | 0.00 | 0.514817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.945848E+10 | 0.00 | 0.00 | 0.00 | 0.421226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.884096E+10 | 0.00 | 0.00 | 0.00 | 0.289694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.846732E+10 | 0.00 | 0.00 | 0.00 | 0.157440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880798E+10 | 0.00 | 0.00 | 0.00 | 0.548009E+10 | 0.00 | 0.184824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113995E+12 | 0.00 | 0.00 | 0.00 | 0.365695E+12 | 0.00 | 0.279292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.797622E+10 | 0.00 | 0.00 | 0.00 | 0.322732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112879E+11 | 0.00 | 0.00 | 0.00 | 0.534380E+11 | 0.00 | 0.251602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.931804E+09 | 0.00 | 0.00 | 0.00 | 0.129050E+10 | 0.00 | 70855309.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844611E+09 | 0.00 | 0.00 | 0.00 | 0.182936E+10 | 0.00 | 1523159.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.949115E+09 | 0.00 | 0.00 | 0.00 | 0.318826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.944678E+09 | 0.00 | 0.00 | 0.00 | 0.456846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108341E+10 | 0.00 | 0.00 | 0.00 | 0.631189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114201E+10 | 0.00 | 0.00 | 0.00 | 0.674991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118284E+10 | 0.00 | 0.00 | 0.00 | 0.690236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117952E+10 | 0.00 | 0.00 | 0.00 | 0.671353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104810E+10 | 0.00 | 0.00 | 0.00 | 0.575858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.976832E+09 | 0.00 | 0.00 | 0.00 | 0.459971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897795E+09 | 0.00 | 0.00 | 0.00 | 0.308786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.932401E+09 | 0.00 | 0.00 | 0.00 | 0.173126E+10 | 0.00 | 935997.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121131E+11 | 0.00 | 0.00 | 0.00 | 0.527317E+11 | 0.00 | 73314467.26 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.844611E+09 | 0.00 | 0.00 | 0.00 | 0.129050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118284E+10 | 0.00 | 0.00 | 0.00 | 0.690236E+10 | 0.00 | 70855309.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.760512E+09 | 0.00 | 0.00 | 0.00 | 0.645674E+09 | 0.00 | 0.255822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.686148E+09 | 0.00 | 0.00 | 0.00 | 0.116490E+10 | 0.00 | 26725347.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769936E+09 | 0.00 | 0.00 | 0.00 | 0.238143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766311E+09 | 0.00 | 0.00 | 0.00 | 0.372451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.883384E+09 | 0.00 | 0.00 | 0.00 | 0.532568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.937234E+09 | 0.00 | 0.00 | 0.00 | 0.573954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.979037E+09 | 0.00 | 0.00 | 0.00 | 0.591930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.970918E+09 | 0.00 | 0.00 | 0.00 | 0.572864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.857646E+09 | 0.00 | 0.00 | 0.00 | 0.485269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.794322E+09 | 0.00 | 0.00 | 0.00 | 0.377447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.728536E+09 | 0.00 | 0.00 | 0.00 | 0.235639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.757234E+09 | 0.00 | 0.00 | 0.00 | 0.101402E+10 | 0.00 | 17716883.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.989122E+10 | 0.00 | 0.00 | 0.00 | 0.426272E+11 | 0.00 | 0.300264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.686148E+09 | 0.00 | 0.00 | 0.00 | 0.645674E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.979037E+09 | 0.00 | 0.00 | 0.00 | 0.591930E+10 | 0.00 | 0.255822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.290835E+10 | 0.00 | 0.00 | 3383885.67 | 0.00 | 0.244026E+09 | 0.185393E+10 | 0.00 | 0.22 |
February | 0.121621E+10 | 19509455.22 | 0.00 | 7297382.43 | 0.00 | 956279.49 | 0.147666E+10 | 0.00 | 0.22 |
March | 0.303333E+09 | 0.101684E+10 | 0.00 | 7651673.70 | 2576023.65 | 0.00 | 0.655107E+09 | 0.00 | 0.23 |
April | 24251234.79 | 0.344671E+10 | 0.00 | 1490346.50 | 49259491.40 | 0.00 | 29579132.70 | 0.00 | 0.22 |
May | 0.00 | 0.809824E+10 | 0.00 | 86224.90 | 64140569.40 | 0.00 | 0.00 | 0.00 | 0.23 |
June | 0.00 | 0.109316E+11 | 0.00 | 0.00 | 89524424.18 | 0.00 | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.138983E+11 | 0.00 | 0.00 | 96748115.57 | 0.00 | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.142943E+11 | 0.00 | 0.00 | 0.103329E+09 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.106840E+11 | 0.00 | 0.00 | 0.124666E+09 | 0.00 | 0.00 | 0.00 | 0.23 |
October | 66679100.46 | 0.360925E+10 | 0.00 | 1947773.90 | 49067417.15 | 0.00 | 51256854.94 | 0.00 | 0.22 |
November | 0.503888E+09 | 0.411005E+09 | 0.00 | 8779882.02 | 0.00 | 0.00 | 0.857731E+09 | 0.00 | 0.22 |
December | 0.211103E+10 | 0.00 | 0.00 | 6422257.14 | 0.00 | 2858099.32 | 0.223279E+10 | 0.00 | 0.22 |
Annual Sum or Average | 0.713374E+10 | 0.664098E+11 | 0.00 | 37059426.24 | 0.579311E+09 | 0.247840E+09 | 0.715706E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.290835E+10 | 0.142943E+11 | 0.00 | 8779882.02 | 0.124666E+09 | 0.244026E+09 | 0.223279E+10 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200956E+11 | 0.00 | 0.00 | 24097215.49 | 0.00 | 0.842214E+09 | 0.130820E+11 | 0.00 | 0.42 |
February | 0.860054E+10 | 0.552416E+09 | 0.00 | 36807742.74 | 0.00 | 6658936.99 | 0.869304E+10 | 0.00 | 0.43 |
March | 0.216127E+10 | 0.107477E+11 | 0.00 | 31512403.14 | 35730380.65 | 0.00 | 0.320874E+10 | 0.00 | 0.44 |
April | 0.113493E+09 | 0.317325E+11 | 0.00 | 3811921.83 | 0.543764E+09 | 0.00 | 0.112825E+09 | 0.00 | 0.44 |
May | 0.00 | 0.664871E+11 | 0.00 | 118070.59 | 0.701077E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.862326E+11 | 0.00 | 0.00 | 0.967456E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.106613E+12 | 0.00 | 0.00 | 0.124224E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.107746E+12 | 0.00 | 0.00 | 0.139443E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.801749E+11 | 0.00 | 0.00 | 0.147904E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.535070E+09 | 0.296834E+11 | 0.00 | 7556982.45 | 0.568763E+09 | 0.00 | 0.589501E+09 | 0.00 | 0.43 |
November | 0.444066E+10 | 0.553526E+10 | 0.00 | 31746446.49 | 0.00 | 0.00 | 0.448063E+10 | 0.00 | 0.43 |
December | 0.156085E+11 | 3082222.52 | 0.00 | 36754276.11 | 0.00 | 27907225.25 | 0.132793E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.515551E+11 | 0.525508E+12 | 0.00 | 0.172405E+09 | 0.693249E+10 | 0.876781E+09 | 0.434459E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.200956E+11 | 0.107746E+12 | 0.00 | 36807742.74 | 0.147904E+10 | 0.842214E+09 | 0.132793E+11 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109689E+10 | 459230.59 | 0.00 | 10310946.89 | 0.00 | 20810308.89 | 0.179406E+10 | 0.00 | 0.42 |
February | 0.507054E+09 | 0.155734E+09 | 0.00 | 8970448.45 | 0.00 | 412625.20 | 0.824933E+09 | 0.00 | 0.43 |
March | 0.119792E+09 | 0.131764E+10 | 0.00 | 5004282.55 | 784640.78 | 0.00 | 0.282584E+09 | 0.00 | 0.44 |
April | 6709767.81 | 0.330618E+10 | 0.00 | 602634.67 | 27829052.09 | 0.00 | 14136590.41 | 0.00 | 0.43 |
May | 0.00 | 0.679145E+10 | 0.00 | 25506.44 | 43452950.06 | 0.00 | 8651.53 | 0.00 | 0.44 |
June | 0.00 | 0.889191E+10 | 0.00 | 0.00 | 56928092.68 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.111434E+11 | 0.00 | 0.00 | 60725489.08 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.114307E+11 | 0.00 | 0.00 | 80277724.74 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.878934E+10 | 0.00 | 0.00 | 91663311.20 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 10685302.64 | 0.360780E+10 | 0.00 | 1357891.70 | 21521418.81 | 0.00 | 40733152.64 | 0.00 | 0.43 |
November | 0.191056E+09 | 0.885500E+09 | 0.00 | 6809102.00 | 0.00 | 0.00 | 0.408695E+09 | 0.00 | 0.43 |
December | 0.756582E+09 | 13868867.64 | 0.00 | 12550814.28 | 0.00 | 705636.59 | 0.153758E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.268877E+10 | 0.563339E+11 | 0.00 | 45631626.98 | 0.383183E+09 | 21928570.68 | 0.490273E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 459230.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.109689E+10 | 0.114307E+11 | 0.00 | 12550814.28 | 91663311.20 | 20810308.89 | 0.179406E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161640E+10 | 0.00 | 0.00 | 5226354.79 | 0.00 | 99123572.59 | 0.134887E+10 | 0.00 | 0.42 |
February | 0.764146E+09 | 0.107409E+09 | 0.00 | 5383980.79 | 0.00 | 3817581.97 | 0.725077E+09 | 0.00 | 0.43 |
March | 0.229598E+09 | 0.117403E+10 | 0.00 | 3443353.57 | 1077092.12 | 0.00 | 0.245873E+09 | 0.00 | 0.44 |
April | 10628640.47 | 0.317071E+10 | 0.00 | 388344.26 | 37980130.82 | 0.00 | 12109246.59 | 0.00 | 0.43 |
May | 0.00 | 0.655640E+10 | 0.00 | 38598.96 | 53167508.51 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.857560E+10 | 0.00 | 0.00 | 63345560.39 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.107340E+11 | 0.00 | 0.00 | 60869690.90 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.109807E+11 | 0.00 | 0.00 | 79244624.28 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.835405E+10 | 0.00 | 0.00 | 92859067.72 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 28650918.77 | 0.339535E+10 | 0.00 | 971394.85 | 24227667.27 | 0.00 | 39101449.88 | 0.00 | 0.43 |
November | 0.275071E+09 | 0.796069E+09 | 0.00 | 4900181.00 | 0.00 | 0.00 | 0.406950E+09 | 0.00 | 0.43 |
December | 0.110268E+10 | 5330500.88 | 0.00 | 7563210.24 | 0.00 | 2623874.23 | 0.136951E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.402717E+10 | 0.538497E+11 | 0.00 | 27915418.46 | 0.412771E+09 | 0.105565E+09 | 0.414750E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.161640E+10 | 0.109807E+11 | 0.00 | 7563210.24 | 92859067.72 | 99123572.59 | 0.136951E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |