Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2020-06-03 19:11:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1876.29 | 817.91 | 817.91 |
Net Site Energy | 1876.29 | 817.91 | 817.91 |
Total Source Energy | 5768.15 | 2514.46 | 2514.46 |
Net Source Energy | 5768.15 | 2514.46 | 2514.46 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 795.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 338.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 390.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 83.32 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1792.73 | 83.56 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 795.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 338.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 73.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 390.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 83.32 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 179.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 516.88 | 36.42 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 781.49 | 36.42 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 179.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 516.88 | 36.42 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 781.49 | 36.42 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1792.728 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1792.728 | 100.00 |
Total On-Site and Utility Electric Sources | 1792.728 | 100.00 |
Total Electricity End Uses | 1792.728 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 271.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.7888 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 16.5511 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 12.6567 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | 20-FEB-16:10 | - | - | - | 28-APR-11:09 |
Heating | 0.00 | 5312.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89803.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 22936.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20530.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4659.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 144041.76 | 9972.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 5312.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 89803.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 22936.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 20530.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4659.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.25 | 0.00 | 0.00 | 0.00 |
Cooling | 2518.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1072.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 231.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1236.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.32 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5677.57 | 90.58 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.11 | 0.00 | 0.00 | 0.00 |
Cooling | 1097.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 467.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 539.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.37 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2474.97 | 39.48 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.11 | 0.00 | 0.00 | 0.00 |
Cooling | 1097.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 467.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 539.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.37 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2474.97 | 39.48 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.39 |
CORE_RETAIL DIRECT AIR | 8.22 |
POINT_OF_SALE DIRECT AIR | 1.37 |
FRONT_RETAIL DIRECT AIR | 1.13 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.787410 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.787410 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 18245.88 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 57981.88 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 209797.03 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 33658.70 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 28028.57 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 2.39 | 1.00 | 1.00 | 2.39 |
PSZ-AC:2 | 8.22 | 8.22 | 8.22 | 8.22 | 8.33 | 8.33 | 1.00 | 0.986693 | 8.33 |
PSZ-AC:3 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.37 | 1.00 | 1.000000 | 1.37 |
PSZ-AC:4 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.00 | 1.00 | 1.13 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.39 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.33 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.37 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.13 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.39 | 2.39 | 2.39 | 2.39 | 48830.73 | 57981.88 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.33 | 8.33 | 8.33 | 8.33 | 206910.14 | 209797.03 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.37 | 1.37 | 1.37 | 1.37 | 32217.28 | 33658.70 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.13 | 1.13 | 1.13 | 1.13 | 27559.05 | 28028.57 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.39 | 1.19 | 2.39 | 45661.43 | 48830.73 | 24415.37 | 48830.73 | 0.728503 | 0.728500 | 0.728500 | 0.728500 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.33 | 4.17 | 8.33 | 206910.11 | 206910.14 | 103455.07 | 206910.14 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.37 | 0.685100 | 1.37 | 30336.97 | 32217.28 | 16108.64 | 32217.28 | 0.689837 | 0.689840 | 0.689840 | 0.689840 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.13 | 0.564290 | 1.13 | 26035.46 | 27559.05 | 13779.52 | 27559.05 | 0.680230 | 0.680230 | 0.680230 | 0.680230 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.39 | 2554.21 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.33 | 15209.27 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.37 | 1517.03 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.13 | 1249.52 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.789 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.859 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 38.071 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 12.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.657 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2958.869 | 7.789 | 48.236 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2958.869 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 26489.747 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26489.747 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 151.881 | 12.657 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 151.881 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.9170 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9232 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.27584055E-14 | 0.34322882E-16 | -0.15031138E-09 | 0.48455878E-16 |
25 | 8 | 0.21957962E-07 | 0.12358672E-12 | 0.37866961E-03 | -0.24966959E-09 |
26 | 7 | -0.12267734E-01 | 0.64103010E-08 | -0.23123512E-01 | 0.13948861E-03 |
27 | 6 | 0.40606172 | 0.22327916E-05 | 0.47269724 | -0.47561475E-02 |
28 | 5 | -5.1975060 | 0.83457246E-04 | -4.4459193 | 0.63269931E-01 |
29 | 4 | 33.033567 | 0.68336110E-03 | 21.458556 | -0.42253064 |
30 | 3 | -111.29159 | 0.14906214E-02 | -55.660041 | 1.5161389 |
31 | 2 | 197.19602 | 0.83912566E-03 | 77.907859 | -2.9017470 |
32 | 1 | -171.18851 | 0.89643828E-04 | -55.264270 | 2.7460078 |
33 | 0 | 57.057407 | 0.51076119E-06 | 15.557052 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 30 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 31 | 1 | VerySmooth | 5.108 | 0.600 | 0.461 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 27887.93044 | 33465.51652 | 1.98917 | 2.38700 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07356E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 12249.35446 | 14699.22535 | 0.50660 | 0.60792 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 96664.91593 | 115997.89912 | 6.85116 | 8.22140 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07356E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 38544.95535 | 46253.94642 | 1.58898 | 1.90677 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 15880.41002 | 19056.49202 | 1.14183 | 1.37020 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07356E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 5761.09795 | 6913.31754 | 0.23980 | 0.28776 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 13128.04901 | 15753.65881 | 0.94048 | 1.12858 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07356E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 5761.09795 | 6913.31754 | 0.23980 | 0.28776 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80000 | 1.07356E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 15205.87052 | 18247.04462 | 0.65617 | 0.78741 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 35418.82 | 2.38700 | 2.38700 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 16434.87 | 0.60792 | 0.60792 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 146517.24 | 8.33227 | 8.33227 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 62796.15 | 1.90677 | 1.90677 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 22059.92 | 1.37020 | 1.37020 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 8435.87 | 0.28776 | 0.28776 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 19162.34 | 1.12858 | 1.12858 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 8435.87 | 0.28776 | 0.28776 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.38700 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.22140 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.37020 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12858 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.78741 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.78741 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 18245.87764 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38700 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.38700 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.38700 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.38700 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.38700 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.38700 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.22140 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.22140 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.22140 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.22140 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.33227 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.33227 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98669 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.37020 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37020 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.37020 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.37020 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.37020 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.37020 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12858 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12858 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12858 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12858 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12858 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12858 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.38700 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.33227 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.37020 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.12858 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.38700 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.38700 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.38700 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.38700 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.38700 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.38700 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19350 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.38700 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 45661.42663 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 48830.73000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 24415.36500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 48830.73000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72850 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72850 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72850 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72850 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 48830.73000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 57981.87846 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.38700 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2554.20516 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 57981.87846 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.33227 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.33227 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.33227 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.33227 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 8.33227 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.33227 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.16614 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 8.33227 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 206910.10678 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 206910.14000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 103455.07000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 206910.14000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 206910.14000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 209797.02878 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.33227 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 15209.27128 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 209797.02878 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.37020 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.37020 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.37020 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.37020 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.37020 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.37020 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68510 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.37020 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30336.96672 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32217.28000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16108.64000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 32217.28000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68984 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68984 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68984 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68984 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32217.28000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33658.70018 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.37020 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1517.02591 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33658.70018 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12858 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12858 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12858 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12858 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12858 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12858 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56429 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.12858 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 26035.45853 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27559.05000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13779.52500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27559.05000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68023 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68023 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68023 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68023 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27559.05000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28028.56606 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12858 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1249.51757 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28028.56606 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 46954.2 | 10.94 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 200336.7 | 12.75 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 31137.4 | 101.27 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 26669.0 | 130.18 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 1.9073728490E-002 | 2.8734670465E-002 | Pass | Pass | 7.1881923328E-002 | 0.2055339482 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 1.7082406959E-002 | 3.1998933835E-002 | Pass | Pass | 0.1038421466 | 0.5777808989 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 2.2080963175E-002 | 4.1968806058E-002 | Pass | Pass | 3.3595185743E-002 | 0.1105775366 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 2.4187347457E-002 | 3.4957431302E-002 | Pass | Pass | 6.0148992575E-002 | 0.1652746119 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1159482828 | 0.2294115235 | Pass | Pass | 2.5640898233E-002 | 0.1373473318 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.843 | 0.252 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.343 | 0.329 | 0.328 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.343 | 0.329 | 0.328 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.7888 | 379.89 | 2958.87 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 34.59 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 16.5511 | 1600.48 | 26489.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 47.92 | 0.0000 | Y | 238.26 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 12.6567 | 12.00 | 151.88 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.95 |
Interior Lighting Total | 15.0797 | 2293.99 | 34592.64 | 338.75 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4644.36 | AstronomicalClock | - | 83.85 | 83.85 | 73.10 | |
Exterior Lighting Total | 4644.36 | 73.10 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 48830.73 | 35573.19 | 13257.54 | 0.73 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 206910.14 | 139887.81 | 67022.33 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32217.28 | 22224.77 | 9992.51 | 0.69 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27559.05 | 18746.49 | 8812.56 | 0.68 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 46954.2 | 10.94 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 200336.7 | 12.75 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 31137.4 | 101.27 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 26669.0 | 130.18 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 18245.88 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 57981.88 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 209797.03 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33658.70 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28028.57 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.79 | 871.79 | 1107.16 | 1.00 | 1.46 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.39 | 2554.21 | 1070.05 | 1.00 | 1.29 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.61 | 1110.54 | 8.33 | 15209.27 | 1825.35 | 1.00 | 1.15 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.37 | 1517.03 | 1107.16 | 1.00 | 1.33 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.13 | 1249.52 | 1107.16 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 27887.93 | 33465.52 | 88.09 | 1.989 | 2.387 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00767 | 35.62 | 0.01074 | 0.232 | 0.00 |
CORE_RETAIL | 96664.92 | 115997.90 | 72.48 | 6.851 | 8.221 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00793 | 35.62 | 0.01074 | 1.890 | 0.00 |
POINT_OF_SALE | 15880.41 | 19056.49 | 126.36 | 1.142 | 1.370 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00741 | 35.62 | 0.01074 | 0.178 | 0.00 |
FRONT_RETAIL | 13128.05 | 15753.66 | 104.46 | 0.940 | 1.129 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00753 | 35.62 | 0.01074 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 41.75 | 100.00 | 0.00001 | 42.80 | 0.01074 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 12249.35 | 14699.23 | 38.69 | 0.507 | 0.608 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00842 | 12.70 | 0.00915 | 0.232 | 0.00 |
CORE_RETAIL | 38544.96 | 46253.95 | 28.90 | 1.589 | 1.907 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00814 | 12.70 | 0.00915 | 1.890 | 0.00 |
POINT_OF_SALE | 5761.10 | 6913.32 | 45.84 | 0.240 | 0.288 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00836 | 12.70 | 0.00915 | 0.178 | 0.00 |
FRONT_RETAIL | 5761.10 | 6913.32 | 45.84 | 0.240 | 0.288 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00836 | 12.70 | 0.00915 | 0.178 | 0.00 |
FRONT_ENTRY | 15205.87 | 18247.04 | 1520.59 | 0.656 | 0.787 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.12 | 0.00879 | 12.70 | 0.00915 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.39 | 2.39 | 0.61 | 0.61 | 2.3870 | 2.3870 | 2.3870 | 1.0000 | 1.0000 |
PSZ-AC:2 | 8.33 | 8.33 | 1.91 | 1.91 | 8.3323 | 8.2214 | 8.3323 | 0.9867 | 1.0000 |
PSZ-AC:3 | 1.37 | 1.37 | 0.29 | 0.29 | 1.3702 | 1.3702 | 1.3702 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.13 | 1.13 | 0.29 | 0.29 | 1.1286 | 1.1286 | 1.1286 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 18245.878 | 18245.878 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 18245.88 | 18245.88 | 0.787410 | 20.97 | 15.54 | 0.00879801 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.12 | 0.00879149 | 56.3197 | 18247.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 48830.730 | 0.000 | 2.387000 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 48830.73 | 42511.43 | 2.387000 | 25.07 | 16.29 | 0.00797065 | 12.80 | 10.55 | 0.00700000 | 35.62 | 0.01073558 | 21.81 | 9.7012 | 23.89 | 0.00767361 | 41.6236 | 27887.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 57981.878 | 57981.878 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 57981.88 | 57981.88 | 2.387002 | 17.65 | 14.21 | 0.00870124 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 9.7011 | 21.11 | 0.00842300 | 54.0215 | 12249.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 206910.140 | 0.000 | 8.332270 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 206910.14 | 175320.56 | 8.332270 | 28.53 | 17.86 | 0.00842211 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01073558 | 23.80 | 22.6854 | 23.89 | 0.00792856 | 42.9914 | 87181.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 209797.029 | 209797.029 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 209797.03 | 209797.03 | 8.332271 | 12.77 | 12.72 | 0.00914461 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 22.6854 | 21.11 | 0.00813654 | 52.2092 | 38544.96 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 32217.280 | 0.000 | 1.370200 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 32217.28 | 28778.44 | 1.370200 | 26.40 | 16.65 | 0.00784299 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01073558 | 23.80 | 12.9989 | 23.89 | 0.00740827 | 40.1996 | 15182.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 33658.700 | 33658.700 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33658.70 | 33658.70 | 1.370197 | 15.76 | 13.62 | 0.00885210 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.9989 | 21.11 | 0.00836260 | 53.6390 | 5761.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 27559.050 | 0.000 | 1.128580 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 27559.05 | 24240.72 | 1.128580 | 26.88 | 16.94 | 0.00799173 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01073558 | 23.80 | 15.7818 | 23.89 | 0.00752804 | 40.8425 | 12736.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 28028.566 | 28028.566 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28028.57 | 28028.57 | 1.128580 | 15.76 | 13.62 | 0.00885210 | 40.00 | 21.14 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 15.7818 | 21.11 | 0.00836260 | 53.6390 | 5761.10 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 18245.878 | 18245.878 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.787410 | 0.94772232 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 18245.88 | 18245.88 | 1.0000 | 0.94772232 | 0.787410 | 20.97 | 15.54 | 0.00879801 | 43416.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18245.88 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.12 | 0.00879149 | 21.12 | 0.00879149 | 56.3197 | 18247.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 48830.730 | 0.000 | 2.387000 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6570 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 48830.73 | 42511.43 | 1.0000 | 2.87298122 | 2.387000 | 25.07 | 16.29 | 0.00797065 | 45495.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48830.73 | 35.62 | 0.01073558 | 21.81 | 0.23156651 | 9.7012 | 23.93 | 0.00767361 | 23.89 | 0.00767361 | 41.6236 | 27887.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 57981.878 | 57981.878 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.387002 | 2.87298384 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 57981.88 | 57981.88 | 1.0000 | 2.87298384 | 2.387002 | 17.65 | 14.21 | 0.00870124 | 39779.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57981.88 | 12.70 | 0.00915345 | 12.70 | 0.23156651 | 9.7011 | 20.69 | 0.00842300 | 21.11 | 0.00842300 | 54.0215 | 12249.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 206910.140 | 0.000 | 8.332270 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4963 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 206910.14 | 175320.56 | 1.0000 | 10.02867836 | 8.332270 | 28.53 | 17.86 | 0.00842211 | 50177.4 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 206910.14 | 42.80 | 0.01073558 | 23.80 | 1.89021192 | 22.6854 | 23.89 | 0.00766965 | 23.89 | 0.00792856 | 42.9914 | 87181.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 209797.029 | 209797.029 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.332271 | 10.02868000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 209797.03 | 209797.03 | 1.0000 | 10.02868000 | 8.332271 | 12.77 | 12.72 | 0.00914461 | 35919.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 209797.03 | 12.70 | 0.00915345 | 12.70 | 1.89021192 | 22.6854 | 20.75 | 0.00813654 | 21.11 | 0.00813654 | 52.2092 | 38544.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32217.280 | 0.000 | 1.370200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4197 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 32217.28 | 28778.44 | 1.0000 | 1.64916584 | 1.370200 | 26.40 | 16.65 | 0.00784299 | 46527.0 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32217.28 | 42.80 | 0.01073558 | 23.80 | 0.17811053 | 12.9989 | 23.89 | 0.00740004 | 23.89 | 0.00740827 | 40.1996 | 15182.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33658.700 | 33658.700 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.370197 | 1.64916259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33658.70 | 33658.70 | 1.0000 | 1.64916259 | 1.370197 | 15.76 | 13.62 | 0.00885210 | 38235.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33658.70 | 12.70 | 0.00915345 | 12.70 | 0.17811053 | 12.9989 | 20.73 | 0.00836260 | 21.11 | 0.00836260 | 53.6390 | 5761.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27559.050 | 0.000 | 1.128580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6962 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 27559.05 | 24240.72 | 1.0000 | 1.35835322 | 1.128580 | 26.88 | 16.94 | 0.00799173 | 47398.1 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27559.05 | 42.80 | 0.01073558 | 23.80 | 0.17811053 | 15.7818 | 23.89 | 0.00747568 | 23.89 | 0.00752804 | 40.8425 | 12736.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28028.566 | 28028.566 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.128580 | 1.35835362 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 28028.57 | 28028.57 | 1.0000 | 1.35835362 | 1.128580 | 15.76 | 13.62 | 0.00885210 | 38235.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28028.57 | 12.70 | 0.00915345 | 12.70 | 0.17811053 | 15.7818 | 20.73 | 0.00836260 | 21.11 | 0.00836260 | 53.6390 | 5761.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3872.50 | 222.83 | 107.67 |
CORE_RETAIL | 4298.17 | 287.33 | 250.67 |
POINT_OF_SALE | 4624.50 | 75.17 | 57.17 |
FRONT_RETAIL | 4444.67 | 145.17 | 91.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4625.67 | 389.00 | 271.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 10.33 | 0.00 | 1.33 |
CORE_RETAIL | 0.00 | 0.33 | 0.00 | 0.33 |
POINT_OF_SALE | 0.00 | 3.33 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 3.67 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 13.33 | 0.00 | 1.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.371 | 0.049 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.720 | 0.009 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.719 | 0.053 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.719 | 0.053 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.362 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.701 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.701 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.701 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1792.73 | 3304.06 | 26-FEB-08:00 | 144041.76 | 10-AUG-16:00 |
Electricity:Building | 533.91 | 3083.31 | 26-FEB-09:00 | 41654.89 | 02-JAN-16:30 |
Electricity:Zone:BACK_SPACE | 84.58 | 607.80 | 01-JAN-00:10 | 5172.60 | 02-JAN-09:10 |
InteriorLights:Electricity | 338.75 | 1288.14 | 26-FEB-09:00 | 30883.85 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BACK_SPACE | 34.59 | 147.94 | 01-JAN-00:10 | 2413.46 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 338.75 | 1288.14 | 26-FEB-09:00 | 30883.85 | 02-JAN-16:30 |
Electricity:Zone:CORE_RETAIL | 322.56 | 1658.43 | 26-FEB-09:00 | 28493.38 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 238.26 | 882.99 | 26-FEB-09:00 | 23840.77 | 02-JAN-16:30 |
Electricity:Zone:POINT_OF_SALE | 84.90 | 611.62 | 01-JAN-00:10 | 5167.35 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 39.92 | 197.87 | 01-JAN-00:10 | 2684.87 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1792.73 | 3304.06 | 26-FEB-08:00 | 144041.76 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 1792.73 | 3304.06 | 26-FEB-08:00 | 144041.76 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1792.73 | 3304.06 | 26-FEB-08:00 | 144041.76 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1792.73 | 3304.06 | 26-FEB-08:00 | 144041.76 | 10-AUG-16:00 |
ElectricityNet:Plant | 1792.73 | 3304.06 | 26-FEB-08:00 | 144041.76 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 1792.73 | 3304.06 | 26-FEB-08:00 | 144041.76 | 10-AUG-16:00 |
Electricity:HVAC | 1185.72 | 0.00 | 01-JAN-00:10 | 110333.80 | 10-AUG-16:00 |
Fans:Electricity | 390.54 | 0.00 | 01-JAN-00:10 | 21401.81 | 01-JAN-10:40 |
General:Fans:Electricity | 390.54 | 0.00 | 01-JAN-00:10 | 21401.81 | 01-JAN-10:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 795.18 | 0.00 | 01-JAN-00:10 | 89803.78 | 10-AUG-16:00 |
ExteriorLights:Electricity | 73.10 | 0.00 | 01-JAN-07:10 | 4644.36 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 73.10 | 0.00 | 01-JAN-07:10 | 4644.36 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 83.56 | 1862.00 | 23-JAN-08:10 | 9972.42 | 20-FEB-16:10 |
Gas:Plant | 83.32 | 1862.00 | 23-JAN-08:10 | 4862.75 | 13-JAN-12:30 |
WaterSystems:Gas | 83.32 | 1862.00 | 23-JAN-08:10 | 4862.75 | 13-JAN-12:30 |
Water Heater:WaterSystems:Gas | 83.32 | 1862.00 | 23-JAN-08:10 | 4862.75 | 13-JAN-12:30 |
Gas:HVAC | 0.23 | 0.00 | 01-JAN-00:10 | 5377.79 | 20-FEB-16:00 |
Heating:Gas | 0.23 | 0.00 | 01-JAN-00:10 | 5377.79 | 20-FEB-16:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3745.95 | 0.00 | 01-JAN-00:10 | 417279.45 | 08-AUG-06:10 |
EnergyTransfer:Building | 1156.31 | 0.00 | 01-JAN-00:10 | 121738.35 | 04-JUL-08:10 |
EnergyTransfer:Zone:BACK_SPACE | 201.16 | 0.00 | 01-JAN-00:10 | 22082.84 | 04-JUL-08:10 |
Heating:EnergyTransfer | 4.19 | 0.00 | 01-JAN-00:10 | 22623.58 | 05-MAY-05:20 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.56 | 0.00 | 01-JAN-00:10 | 3723.61 | 02-MAR-06:20 |
Cooling:EnergyTransfer | 1152.12 | 0.00 | 01-JAN-00:10 | 113479.17 | 04-JUL-08:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 200.60 | 0.00 | 01-JAN-00:10 | 22028.65 | 06-AUG-08:10 |
EnergyTransfer:Zone:CORE_RETAIL | 697.92 | 0.00 | 01-JAN-00:10 | 80414.93 | 04-JUL-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 2.84 | 0.00 | 01-JAN-00:10 | 17312.76 | 12-MAY-05:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 695.08 | 0.00 | 01-JAN-00:10 | 73086.20 | 04-JUL-08:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 145.60 | 0.00 | 01-JAN-00:10 | 12988.07 | 05-SEP-14:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.14 | 0.00 | 01-JAN-00:10 | 1755.73 | 28-MAR-05:20 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 145.45 | 0.00 | 01-JAN-00:10 | 12988.07 | 05-SEP-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 111.14 | 0.00 | 01-JAN-00:10 | 10919.48 | 05-SEP-14:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.15 | 0.00 | 01-JAN-00:10 | 2025.69 | 02-MAR-06:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 110.99 | 0.00 | 01-JAN-00:10 | 10919.48 | 05-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.49 | 0.00 | 01-JAN-00:10 | 5174.02 | 20-FEB-16:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.49 | 0.00 | 01-JAN-00:10 | 5174.02 | 20-FEB-16:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 2589.64 | 0.00 | 01-JAN-00:10 | 319617.85 | 08-AUG-06:10 |
HeatingCoils:EnergyTransfer | 0.19 | 0.00 | 01-JAN-00:10 | 4302.23 | 20-FEB-16:00 |
CoolingCoils:EnergyTransfer | 2589.46 | 0.00 | 01-JAN-00:10 | 319617.85 | 08-AUG-06:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.559 | -200.592 | 0.000 | 0.000 | 36.663 | 34.587 | 49.992 | 0.000 | 0.000 | 6.880 | 74.555 | 0.000 | 0.000 | 0.000 | -2.643 | -0.001 |
CORE_RETAIL | 0.000 | 0.000 | 2.842 | -695.074 | 0.000 | 0.000 | 154.464 | 238.261 | 84.299 | 87.145 | 0.000 | 5.921 | 134.809 | 0.000 | -10.415 | 0.000 | -2.252 | -0.003 |
POINT_OF_SALE | 0.000 | 0.000 | 0.143 | -145.449 | 0.000 | 0.000 | 14.554 | 31.980 | 52.922 | 33.576 | 0.000 | 2.801 | 16.666 | 0.000 | -5.814 | 0.000 | -1.380 | -0.000 |
FRONT_RETAIL | 0.000 | 0.000 | 0.153 | -110.987 | 0.000 | 0.000 | 14.556 | 31.980 | 7.943 | 33.588 | 0.000 | 2.903 | 26.554 | 0.000 | -5.470 | 0.000 | -1.220 | -0.001 |
FRONT_ENTRY | 0.488 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.946 | 0.000 | 5.645 | 0.000 | 5.513 | 0.000 | 0.000 | -1.273 | 0.000 | -3.302 | -9.017 |
Total Facility | 0.488 | 0.000 | 3.697 | -1152.103 | 0.000 | 0.000 | 220.236 | 338.755 | 195.156 | 159.955 | 0.000 | 24.018 | 252.585 | 0.000 | -22.972 | 0.000 | -10.798 | -9.021 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | -43418.87 | 0.00 | 0.00 | 383.94 | 536.32 | 1226.28 | 0.00 | 0.00 | 0.00 | 41328.03 | 0.00 | -0.00 | 0.00 | -55.71 | 0.00 |
CORE_RETAIL | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | -180712.93 | 0.00 | 0.00 | 1595.70 | 5297.95 | 2067.82 | 0.00 | 0.00 | 0.00 | 172854.09 | 0.00 | -1062.41 | 0.00 | -40.23 | 0.00 |
POINT_OF_SALE | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | -27835.51 | 0.00 | 0.00 | 0.00 | 124.80 | 649.09 | 0.00 | 0.00 | 0.00 | 27444.14 | 0.00 | -382.42 | 0.00 | -0.10 | 0.00 |
FRONT_RETAIL | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | -23971.78 | 0.00 | 0.00 | 150.36 | 499.21 | 194.85 | 0.00 | 0.00 | 0.00 | 23647.10 | 0.00 | -502.97 | 0.00 | -16.77 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | -275461.65 | 0.00 | 0.00 | 2275.18 | 6863.08 | 4787.13 | 0.00 | 0.00 | 0.00 | 263851.41 | 0.00 | -2188.73 | 0.00 | -126.41 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 05-AUG-05:07 | 0.00 | 0.00 | 5432.94 | 0.00 | 0.00 | 0.00 | 0.00 | 147.94 | 459.86 | 0.00 | 0.00 | 170.83 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6211.56 |
CORE_RETAIL | 04-JUL-08:06 | 0.00 | 0.00 | 36643.05 | 0.00 | 0.00 | 0.00 | 1595.71 | 1765.98 | 1550.87 | 4798.94 | 0.00 | 116.66 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -46471.21 |
POINT_OF_SALE | 05-AUG-05:05 | 0.00 | 0.00 | 3883.28 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 486.81 | 320.77 | 0.00 | 74.19 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4889.86 |
FRONT_RETAIL | 04-JUL-07:04 | 0.00 | 0.00 | 3094.53 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 73.07 | 634.88 | 0.00 | 34.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3961.76 |
FRONT_ENTRY | 20-FEB-16:00 | 5173.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 | 0.00 | 58.91 | 0.00 | 0.00 | 467.92 | 0.00 | -0.00 | 0.00 | -5791.52 | 0.00 |
Total Facility | 04-JUL-08:06 | -6800.93 | 6800.93 | 41295.11 | -6800.93 | 0.00 | 0.00 | 2275.19 | 2548.55 | 3590.35 | 7565.56 | 0.00 | 690.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -51164.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.3870 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.3870 | 0.0970 | 1.0000 | 0.2316 | 0.0970 | ||
PSZ-AC:2 | 8.2214 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.3323 | 0.2269 | 1.0000 | 1.8902 | 0.2269 | ||
PSZ-AC:3 | 1.3702 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3702 | 0.1300 | 1.0000 | 0.1781 | 0.1300 | ||
PSZ-AC:4 | 1.1286 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1286 | 0.1578 | 1.0000 | 0.1781 | 0.1578 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.3870 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.3870 | 1.0000 | 1.0000 | 0.2316 | 0.0970 | ||
PSZ-AC:2 | 8.2214 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.2214 | 1.0000 | 1.0000 | 1.8902 | 0.2299 | ||
PSZ-AC:3 | 1.3702 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3702 | 1.0000 | 1.0000 | 0.1781 | 0.1300 | ||
PSZ-AC:4 | 1.1286 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1286 | 1.0000 | 1.0000 | 0.1781 | 0.1578 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.3870 | 2.3870 | 2.3870 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.2214 | 8.2214 | 8.2214 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3702 | 1.3702 | 1.3702 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.1286 | 1.1286 | 1.1286 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.3870 | 2.3870 | 2.3870 | 2.3870 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.2214 | 8.3323 | 8.2214 | 8.2214 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3702 | 1.3702 | 1.3702 | 1.3702 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.1286 | 1.1286 | 1.1286 | 1.1286 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.3870 | 2.3870 | 2.3870 | 0.2316 | 0.3809 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.2214 | 8.2214 | 8.2214 | 1.8902 | 0.9913 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3702 | 1.3702 | 1.3702 | 0.1781 | 0.6190 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.1286 | 1.1286 | 1.1286 | 0.1781 | 0.6190 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.3870 | 2.3870 | 2.3870 | 2.3870 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.2214 | 8.2214 | 8.2214 | 8.2214 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3702 | 1.3702 | 1.3702 | 1.3702 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.1286 | 1.1286 | 1.1286 | 1.1286 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1.33 |
Number of hours not met | 1.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.23 | 5377.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 795.18 | 89803.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 338.75 | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 73.10 | 4644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 390.54 | 21401.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 83.32 | 4862.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1792.73 |
Natural Gas | 0.00 | 83.56 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1876.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 147.67 |
Space Heating | 0.00 |
Space Cooling | 346.64 |
Fans (All) | 170.24 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 781.49 |
Subtotal | 781.49 |
Natural Gas [MJ/m2] | |
Space Heating | 0.10 |
Service Water Heating | 36.32 |
Miscellaneous (All) | 36.42 |
Subtotal | 36.42 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.05 |
Space Heating | 0.01 |
Space Cooling | 42.38 |
Fans (All) | 20.81 |
Service Water Heating | 4.44 |
Receptacle Equipment | 10.40 |
Miscellaneous | 3.90 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.461914E+08 |
February | 0.000 | 0.108009E+09 |
March | 0.000 | 0.235975E+08 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.550993E+08 |
Annual Sum or Average | 0.232897E+09 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.108009E+09 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.778972E+10 | 32967.85 | 29-JAN-09:02 | 23.22 | 19.02 | 0.218352E+10 | 2451.29 | 21-JAN-12:09 | 23.10 | 12.86 |
February | 0.830843E+10 | 41659.61 | 10-FEB-07:02 | 19.92 | 12.96 | 0.199441E+10 | 2451.32 | 04-FEB-14:09 | 30.67 | 16.66 |
March | 0.113339E+11 | 43419.80 | 22-MAR-06:02 | 20.17 | 10.96 | 0.228160E+10 | 2451.37 | 27-MAR-14:09 | 35.00 | 19.28 |
April | 0.139302E+11 | 42905.03 | 26-APR-06:02 | 23.97 | 12.26 | 0.215728E+10 | 2451.45 | 27-APR-14:39 | 36.60 | 21.53 |
May | 0.201496E+11 | 43046.43 | 11-MAY-05:01 | 28.00 | 16.04 | 0.223346E+10 | 2451.46 | 20-MAY-15:20 | 37.00 | 22.35 |
June | 0.222363E+11 | 36725.60 | 02-JUN-05:01 | 27.00 | 17.59 | 0.220250E+10 | 2451.47 | 21-JUN-14:00 | 39.00 | 23.71 |
July | 0.249814E+11 | 41596.29 | 04-JUL-07:01 | 31.33 | 17.53 | 0.218818E+10 | 2451.39 | 12-JUL-14:20 | 40.33 | 24.44 |
August | 0.263657E+11 | 35527.68 | 06-AUG-06:02 | 34.98 | 22.46 | 0.228192E+10 | 2451.46 | 17-AUG-14:09 | 41.67 | 26.41 |
September | 0.220709E+11 | 33433.25 | 26-SEP-06:02 | 26.10 | 17.85 | 0.215727E+10 | 2451.22 | 02-SEP-11:20 | 38.67 | 24.26 |
October | 0.191684E+11 | 38957.50 | 21-OCT-06:02 | 22.00 | 15.42 | 0.218490E+10 | 2451.43 | 14-OCT-13:50 | 35.20 | 21.16 |
November | 0.142197E+11 | 38057.41 | 05-NOV-08:62 | 24.50 | 17.34 | 0.210214E+10 | 2451.36 | 13-NOV-15:09 | 32.53 | 19.07 |
December | 0.100451E+11 | 40258.91 | 01-DEC-07:02 | 18.17 | 12.77 | 0.218772E+10 | 2451.23 | 16-DEC-12:20 | 22.03 | 14.23 |
Annual Sum or Average | 0.200599E+12 | 0.261549E+11 | ||||||||
Minimum of Months | 0.778972E+10 | 32967.85 | 18.17 | 10.96 | 0.199441E+10 | 2451.22 | 22.03 | 12.86 | ||
Maximum of Months | 0.263657E+11 | 43419.80 | 34.98 | 22.46 | 0.228192E+10 | 2451.47 | 41.67 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361398E+11 | 149852.53 | 22-JAN-09:02 | 20.15 | 15.67 | 0.919636E+10 | 10327.53 | 28-JAN-15:20 | 25.50 | 18.06 |
February | 0.368123E+11 | 163542.59 | 10-FEB-07:02 | 19.92 | 12.96 | 0.840197E+10 | 10327.49 | 09-FEB-15:09 | 22.85 | 20.18 |
March | 0.469191E+11 | 180714.13 | 23-MAR-06:02 | 22.83 | 12.03 | 0.961222E+10 | 10327.16 | 13-MAR-14:30 | 32.00 | 17.05 |
April | 0.529148E+11 | 174756.57 | 26-APR-06:02 | 23.97 | 12.26 | 0.908846E+10 | 10327.67 | 29-APR-10:39 | 35.90 | 19.57 |
May | 0.680441E+11 | 164878.86 | 11-MAY-05:01 | 28.00 | 16.04 | 0.940959E+10 | 10328.22 | 20-MAY-14:50 | 37.75 | 21.24 |
June | 0.714998E+11 | 146170.57 | 01-JUN-05:01 | 28.67 | 21.40 | 0.927926E+10 | 10328.11 | 16-JUN-14:50 | 37.83 | 21.11 |
July | 0.776976E+11 | 158024.78 | 04-JUL-07:01 | 31.33 | 17.53 | 0.921894E+10 | 10327.59 | 13-JUL-14:09 | 38.00 | 27.89 |
August | 0.807107E+11 | 131297.83 | 06-AUG-07:02 | 35.08 | 22.67 | 0.961395E+10 | 10327.17 | 16-AUG-14:00 | 40.00 | 29.78 |
September | 0.697534E+11 | 135450.09 | 26-SEP-06:02 | 26.10 | 17.85 | 0.908876E+10 | 10327.51 | 09-SEP-14:09 | 35.83 | 30.24 |
October | 0.626748E+11 | 155504.28 | 20-OCT-06:02 | 23.82 | 15.95 | 0.920505E+10 | 10328.09 | 21-OCT-15:09 | 33.77 | 19.12 |
November | 0.503788E+11 | 154919.97 | 19-NOV-09:02 | 25.40 | 16.07 | 0.885616E+10 | 10327.36 | 18-NOV-16:40 | 29.67 | 16.97 |
December | 0.415337E+11 | 158194.92 | 01-DEC-07:02 | 18.17 | 12.77 | 0.921626E+10 | 10327.30 | 09-DEC-14:09 | 28.83 | 21.36 |
Annual Sum or Average | 0.695079E+12 | 0.110187E+12 | ||||||||
Minimum of Months | 0.361398E+11 | 131297.83 | 18.17 | 12.03 | 0.840197E+10 | 10327.16 | 22.85 | 16.97 | ||
Maximum of Months | 0.807107E+11 | 180714.13 | 35.08 | 22.67 | 0.961395E+10 | 10328.22 | 40.00 | 30.24 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.837268E+10 | 20859.31 | 30-JAN-07:02 | 20.17 | 17.38 | 0.867081E+09 | 973.20 | 28-JAN-14:50 | 26.33 | 17.63 |
February | 0.801253E+10 | 26044.29 | 10-FEB-07:02 | 19.92 | 12.96 | 0.791833E+09 | 973.17 | 06-FEB-15:00 | 31.40 | 17.53 |
March | 0.949321E+10 | 27835.62 | 28-MAR-05:02 | 25.67 | 14.72 | 0.905799E+09 | 973.19 | 27-MAR-14:09 | 35.00 | 19.28 |
April | 0.100623E+11 | 27056.73 | 26-APR-06:02 | 23.97 | 12.26 | 0.856405E+09 | 973.26 | 27-APR-14:30 | 36.70 | 21.32 |
May | 0.129193E+11 | 27309.15 | 11-MAY-05:01 | 28.00 | 16.04 | 0.886643E+09 | 973.27 | 20-MAY-15:09 | 37.25 | 21.97 |
June | 0.136707E+11 | 23358.51 | 02-JUN-05:01 | 27.00 | 17.59 | 0.874351E+09 | 973.26 | 21-JUN-14:39 | 39.33 | 22.95 |
July | 0.153496E+11 | 25365.06 | 04-JUL-07:01 | 31.33 | 17.53 | 0.868661E+09 | 973.17 | 15-JUL-11:00 | 45.00 | 25.09 |
August | 0.165855E+11 | 22552.47 | 06-AUG-06:02 | 34.98 | 22.46 | 0.905875E+09 | 973.23 | 05-AUG-13:20 | 43.27 | 26.29 |
September | 0.149218E+11 | 21980.06 | 26-SEP-05:01 | 26.25 | 18.46 | 0.856390E+09 | 973.11 | 09-SEP-14:09 | 35.83 | 30.24 |
October | 0.143748E+11 | 25128.22 | 21-OCT-05:02 | 22.83 | 15.32 | 0.867362E+09 | 973.27 | 14-OCT-13:00 | 35.00 | 21.49 |
November | 0.120450E+11 | 25911.13 | 05-NOV-07:01 | 21.17 | 15.80 | 0.834510E+09 | 973.19 | 13-NOV-15:20 | 32.07 | 19.49 |
December | 0.964583E+10 | 25535.89 | 01-DEC-07:02 | 18.17 | 12.77 | 0.868573E+09 | 973.16 | 30-DEC-14:50 | 25.00 | 14.17 |
Annual Sum or Average | 0.145453E+12 | 0.103835E+11 | ||||||||
Minimum of Months | 0.801253E+10 | 20859.31 | 18.17 | 12.26 | 0.791833E+09 | 973.11 | 25.00 | 14.17 | ||
Maximum of Months | 0.165855E+11 | 27835.62 | 34.98 | 22.46 | 0.905875E+09 | 973.27 | 45.00 | 30.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.557914E+10 | 17447.99 | 29-JAN-09:02 | 23.22 | 19.02 | 0.866142E+09 | 973.17 | 28-JAN-14:39 | 26.67 | 16.85 |
February | 0.544874E+10 | 20028.48 | 05-FEB-09:02 | 23.55 | 16.77 | 0.791389E+09 | 973.17 | 06-FEB-15:50 | 31.58 | 17.49 |
March | 0.655731E+10 | 23971.85 | 23-MAR-06:02 | 22.83 | 12.03 | 0.905613E+09 | 973.19 | 22-MAR-14:20 | 30.00 | 16.81 |
April | 0.727102E+10 | 23131.49 | 26-APR-06:02 | 23.97 | 12.26 | 0.856366E+09 | 973.23 | 27-APR-14:09 | 36.90 | 20.89 |
May | 0.998975E+10 | 22701.48 | 11-MAY-05:01 | 28.00 | 16.04 | 0.886642E+09 | 973.25 | 20-MAY-14:00 | 37.50 | 21.56 |
June | 0.107629E+11 | 19170.71 | 02-JUN-05:01 | 27.00 | 17.59 | 0.874352E+09 | 973.23 | 16-JUN-14:00 | 38.00 | 21.57 |
July | 0.123899E+11 | 21775.87 | 04-JUL-07:01 | 31.33 | 17.53 | 0.868659E+09 | 973.12 | 29-JUL-15:00 | 40.70 | 21.32 |
August | 0.135057E+11 | 18655.29 | 06-AUG-06:02 | 34.98 | 22.46 | 0.905873E+09 | 973.19 | 05-AUG-12:00 | 43.90 | 25.82 |
September | 0.120310E+11 | 18248.48 | 26-SEP-06:02 | 26.10 | 17.85 | 0.856390E+09 | 973.10 | 09-SEP-14:09 | 35.83 | 30.24 |
October | 0.114434E+11 | 20861.17 | 21-OCT-06:02 | 22.00 | 15.42 | 0.867359E+09 | 973.22 | 21-OCT-15:30 | 33.30 | 19.31 |
November | 0.922348E+10 | 20939.11 | 05-NOV-07:01 | 21.17 | 15.80 | 0.834497E+09 | 973.19 | 13-NOV-15:09 | 32.53 | 19.07 |
December | 0.678808E+10 | 20334.06 | 01-DEC-07:02 | 18.17 | 12.77 | 0.868422E+09 | 973.11 | 09-DEC-14:09 | 28.83 | 21.36 |
Annual Sum or Average | 0.110990E+12 | 0.103817E+11 | ||||||||
Minimum of Months | 0.544874E+10 | 17447.99 | 18.17 | 12.03 | 0.791389E+09 | 973.10 | 26.67 | 16.81 | ||
Maximum of Months | 0.135057E+11 | 23971.85 | 34.98 | 22.46 | 0.905873E+09 | 973.25 | 43.90 | 30.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 | 12.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 14.58 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 | 18.45 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 | 0.00 | 0.00 | 01-APR-00:10 | 22.05 | 20.11 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 | 23.55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 | 23.23 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 | 27.01 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 | 28.28 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 | 25.03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 | 26.77 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 | 21.16 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 | 15.62 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 15.70 | 12.83 | 0.00 | 0.00 | 15.70 | 12.83 | ||
Maximum of Months | 0.00 | 0.00 | 33.23 | 28.28 | 0.00 | 0.00 | 33.23 | 28.28 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36402718.72 | 2612.94 | 29-JAN-09:06 | 23.22 |
February | 51564133.60 | 3510.54 | 05-FEB-09:04 | 23.55 |
March | 80219413.18 | 4516.20 | 02-MAR-06:04 | 28.80 |
April | 77289414.50 | 3841.85 | 28-APR-05:04 | 25.83 |
May | 61415408.06 | 5117.03 | 21-MAY-08:06 | 31.67 |
June | 33184388.39 | 4585.71 | 11-JUN-07:17 | 32.33 |
July | 14274926.56 | 4797.83 | 30-JUL-07:06 | 31.25 |
August | 9217744.10 | 5433.71 | 05-AUG-05:07 | 35.00 |
September | 31566755.47 | 4442.79 | 04-SEP-07:07 | 31.55 |
October | 51564381.60 | 4181.60 | 15-OCT-08:06 | 27.67 |
November | 57373116.15 | 3707.15 | 11-NOV-09:06 | 25.52 |
December | 54951452.65 | 3201.90 | 12-DEC-07:06 | 23.17 |
Annual Sum or Average | 0.559024E+09 | |||
Minimum of Months | 9217744.10 | 2612.94 | 23.17 | |
Maximum of Months | 80219413.18 | 5433.71 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82068404.01 | 16433.16 | 29-JAN-09:06 | 23.22 |
February | 0.141245E+09 | 16191.55 | 05-FEB-09:06 | 23.55 |
March | 0.239266E+09 | 25323.71 | 02-MAR-07:06 | 27.67 |
April | 0.305760E+09 | 21900.02 | 02-APR-08:06 | 26.00 |
May | 0.387597E+09 | 34416.29 | 21-MAY-08:06 | 31.67 |
June | 0.264526E+09 | 32046.96 | 11-JUN-07:05 | 31.92 |
July | 0.229036E+09 | 36643.68 | 04-JUL-08:06 | 32.82 |
August | 0.231292E+09 | 34736.79 | 20-AUG-07:06 | 33.33 |
September | 0.212538E+09 | 27607.55 | 05-SEP-05:06 | 30.17 |
October | 0.322599E+09 | 26208.87 | 15-OCT-08:06 | 27.67 |
November | 0.291345E+09 | 21481.46 | 11-NOV-09:06 | 25.52 |
December | 0.134598E+09 | 17398.33 | 10-DEC-09:06 | 23.60 |
Annual Sum or Average | 0.284187E+10 | |||
Minimum of Months | 82068404.01 | 16191.55 | 23.22 | |
Maximum of Months | 0.387597E+09 | 36643.68 | 33.33 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3737326.58 | 1664.82 | 22-JAN-09:05 | 20.15 |
February | 6992799.12 | 2293.79 | 05-FEB-09:04 | 23.55 |
March | 16682199.76 | 3173.00 | 02-MAR-06:04 | 28.80 |
April | 21007529.23 | 2787.14 | 02-APR-08:04 | 26.00 |
May | 25177371.38 | 2784.14 | 13-MAY-05:04 | 28.00 |
June | 15319933.22 | 3405.69 | 11-JUN-07:05 | 31.92 |
July | 6647034.22 | 3274.50 | 21-JUL-05:05 | 32.08 |
August | 4047089.52 | 3884.22 | 05-AUG-05:05 | 35.00 |
September | 7424470.64 | 3034.92 | 02-SEP-05:04 | 30.50 |
October | 15368603.59 | 2491.42 | 11-OCT-05:05 | 26.83 |
November | 17096675.82 | 2388.58 | 20-NOV-06:04 | 25.85 |
December | 3926347.33 | 1675.40 | 27-DEC-07:04 | 20.92 |
Annual Sum or Average | 0.143427E+09 | |||
Minimum of Months | 3737326.58 | 1664.82 | 20.15 | |
Maximum of Months | 25177371.38 | 3884.22 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2910322.91 | 1210.06 | 29-JAN-09:06 | 23.22 |
February | 5532730.14 | 1788.08 | 05-FEB-09:04 | 23.55 |
March | 18730866.71 | 2684.57 | 02-MAR-06:04 | 28.80 |
April | 24604133.35 | 2340.50 | 02-APR-08:04 | 26.00 |
May | 27318713.87 | 2426.00 | 23-MAY-05:06 | 30.40 |
June | 17439407.69 | 3023.42 | 11-JUN-07:05 | 31.92 |
July | 7518890.14 | 3094.89 | 04-JUL-07:04 | 31.33 |
August | 3614425.40 | 3030.91 | 20-AUG-07:06 | 33.33 |
September | 11235943.63 | 2472.98 | 01-SEP-05:06 | 29.75 |
October | 17637942.57 | 2054.80 | 11-OCT-05:05 | 26.83 |
November | 11832796.13 | 1932.52 | 20-NOV-06:04 | 25.85 |
December | 4427539.74 | 1270.97 | 10-DEC-09:06 | 23.60 |
Annual Sum or Average | 0.152804E+09 | |||
Minimum of Months | 2910322.91 | 1210.06 | 23.22 | |
Maximum of Months | 27318713.87 | 3094.89 | 33.33 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181053E+09 | 2960.46 | 18-JAN-18:00 | 19.00 |
February | 0.164056E+09 | 5174.02 | 20-FEB-16:00 | 17.80 |
March | 54768631.99 | 4832.49 | 05-MAR-18:00 | 18.00 |
April | 270342.27 | 847.72 | 01-APR-07:07 | 17.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 45948.73 | 765.81 | 22-NOV-08:10 | 18.33 |
December | 88030833.04 | 4501.53 | 15-DEC-12:10 | 18.10 |
Annual Sum or Average | 0.488225E+09 | |||
Minimum of Months | 0.00 | 0.00 | 17.67 | |
Maximum of Months | 0.181053E+09 | 5174.02 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.290080E+10 | 2413.46 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.263912E+10 | 2413.46 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.300979E+10 | 2413.46 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.284005E+10 | 2413.46 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.295530E+10 | 2413.46 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.290440E+10 | 2413.46 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.289095E+10 | 2413.46 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.300979E+10 | 2413.46 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.284005E+10 | 2413.46 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.290080E+10 | 2413.46 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.280526E+10 | 2413.46 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.289095E+10 | 2413.46 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.345872E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.263912E+10 | 2413.46 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.300979E+10 | 2413.46 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220689E+11 | 23840.77 | 02-JAN-16:30 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.190902E+11 | 23840.77 | 01-FEB-16:00 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.204964E+11 | 23840.77 | 01-MAR-17:19 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.187099E+11 | 21854.04 | 01-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.191522E+11 | 19867.31 | 01-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.185836E+11 | 19867.31 | 05-JUN-16:00 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.184350E+11 | 19867.31 | 14-JUL-08:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.193549E+11 | 19867.31 | 12-AUG-16:00 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.187416E+11 | 21854.04 | 05-SEP-16:00 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.200895E+11 | 23840.77 | 03-OCT-16:00 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.209537E+11 | 23840.77 | 01-NOV-16:40 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.225854E+11 | 23840.77 | 01-DEC-16:19 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.238261E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.184350E+11 | 19867.31 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.225854E+11 | 23840.77 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.163184E+09 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.148475E+09 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.169362E+09 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.159794E+09 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.166273E+09 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.163430E+09 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.162637E+09 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.169362E+09 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.159794E+09 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.163184E+09 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.157798E+09 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.162637E+09 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194593E+10 | ||||
Minimum of Months | 0.148475E+09 | 136.69 | 0.00 | 0.00 | |
Maximum of Months | 0.169362E+09 | 136.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6954726.01 | 0.659480E+09 |
February | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47762705.41 | 0.637564E+09 |
March | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159854E+09 | 0.350458E+09 |
April | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345599E+09 | 0.185741E+09 |
May | 0.536353E+10 | 0.295530E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790219E+09 | 28819518.63 |
June | 0.528933E+10 | 0.290440E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103502E+10 | 7937463.27 |
July | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136772E+10 | 0.00 |
August | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138686E+10 | 0.00 |
September | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921193E+09 | 7097473.58 |
October | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547349E+09 | 49235486.72 |
November | 0.504819E+10 | 0.280526E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234232E+09 | 0.210356E+09 |
December | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37399560.14 | 0.506643E+09 |
Annual Sum or Average | 0.628175E+11 | 0.345872E+11 | 0.499918E+11 | 0.688016E+10 | 0.264333E+10 | ||||
Minimum of Months | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6954726.01 | 0.00 |
Maximum of Months | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138686E+10 | 0.659480E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.220689E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5692947.43 | 0.573671E+09 |
February | 0.201852E+11 | 0.190902E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39177509.16 | 0.560992E+09 |
March | 0.230879E+11 | 0.204964E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131866E+09 | 0.307518E+09 |
April | 0.218263E+11 | 0.187099E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285098E+09 | 0.155565E+09 |
May | 0.225967E+11 | 0.191522E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670761E+09 | 18874654.04 |
June | 0.222841E+11 | 0.185836E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897304E+09 | 3557608.62 |
July | 0.221389E+11 | 0.184350E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119217E+10 | 0.00 |
August | 0.230879E+11 | 0.193549E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120299E+10 | 0.00 |
September | 0.218263E+11 | 0.187416E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799999E+09 | 3228360.57 |
October | 0.221054E+11 | 0.200895E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469068E+09 | 30142396.69 |
November | 0.212681E+11 | 0.209537E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195770E+09 | 0.165882E+09 |
December | 0.221389E+11 | 0.225854E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30673018.65 | 0.432899E+09 |
Annual Sum or Average | 0.264651E+12 | 0.238261E+12 | 0.842987E+11 | 0.592057E+10 | 0.225233E+10 | ||||
Minimum of Months | 0.201852E+11 | 0.184350E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5692947.43 | 0.00 |
Maximum of Months | 0.230879E+11 | 0.225854E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120299E+10 | 0.573671E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3014257.24 | 0.321543E+09 |
February | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20327635.71 | 0.318227E+09 |
March | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65397434.28 | 0.183161E+09 |
April | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144881E+09 | 0.100303E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325256E+09 | 18521687.90 |
June | 0.209978E+10 | 0.268587E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424320E+09 | 6165840.83 |
July | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558773E+09 | 0.00 |
August | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565058E+09 | 18169.90 |
September | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366961E+09 | 7830829.06 |
October | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216070E+09 | 42493201.16 |
November | 0.200405E+10 | 0.259332E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95004428.64 | 0.126208E+09 |
December | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16090353.81 | 0.255569E+09 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.529224E+11 | 0.280115E+10 | 0.138004E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3014257.24 | 0.00 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565058E+09 | 0.321543E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3014122.72 | 0.298727E+09 |
February | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20408140.54 | 0.290017E+09 |
March | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67129223.29 | 0.158965E+09 |
April | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147453E+09 | 81735713.72 |
May | 0.212923E+10 | 0.273260E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337126E+09 | 12296621.83 |
June | 0.209978E+10 | 0.268587E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443945E+09 | 3144363.16 |
July | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580830E+09 | 0.00 |
August | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584606E+09 | 0.00 |
September | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382127E+09 | 4552686.64 |
October | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223686E+09 | 30557815.05 |
November | 0.200405E+10 | 0.259332E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96935920.86 | 0.107007E+09 |
December | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16131067.39 | 0.232738E+09 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.794328E+10 | 0.290339E+10 | 0.121974E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3014122.72 | 0.00 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584606E+09 | 0.298727E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170647.44 | 0.992674E+09 |
February | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16536536.07 | 0.751189E+09 |
March | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98169613.01 | 0.433177E+09 |
April | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311105E+09 | 91804614.15 |
May | 0.00 | 0.166273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821017E+09 | 10051620.60 |
June | 0.00 | 0.163430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957433E+09 | 7264985.54 |
July | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116390E+10 | 148755.34 |
August | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109760E+10 | 288868.91 |
September | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704525E+09 | 8152491.09 |
October | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310283E+09 | 43217890.39 |
November | 0.00 | 0.157798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28838751.50 | 0.220097E+09 |
December | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3122198.03 | 0.744184E+09 |
Annual Sum or Average | 0.00 | 0.194593E+10 | 0.551270E+10 | 0.330225E+10 | |||||
Minimum of Months | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170647.44 | 148755.34 |
Maximum of Months | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116390E+10 | 0.992674E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2413.46 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.14 | 29-JAN-12:00 | 1731.53 | 18-JAN-04:00 |
February | 5888.82 | 01-FEB-15:09 | 2413.46 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 740.10 | 05-FEB-19:03 | 1523.70 | 10-FEB-23:00 |
March | 5888.82 | 01-MAR-15:09 | 2413.46 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 967.62 | 01-MAR-13:00 | 1297.38 | 06-MAR-06:00 |
April | 5888.82 | 01-APR-10:09 | 2413.46 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.58 | 28-APR-13:20 | 1039.77 | 05-APR-01:00 |
May | 5888.82 | 01-MAY-14:09 | 2413.46 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3315.07 | 21-MAY-13:00 | 342.10 | 01-MAY-05:00 |
June | 5888.82 | 01-JUN-14:09 | 2413.46 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2041.35 | 09-JUN-20:02 | 396.35 | 07-JUN-05:00 |
July | 5888.82 | 01-JUL-10:09 | 2413.46 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2554.61 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 5888.82 | 01-AUG-14:09 | 2413.46 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3987.72 | 16-AUG-20:02 | 0.00 | 01-AUG-00:10 |
September | 5888.82 | 01-SEP-14:09 | 2413.46 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2611.40 | 04-SEP-18:02 | 309.10 | 25-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 2413.46 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1755.38 | 09-OCT-18:02 | 656.14 | 20-OCT-05:00 |
November | 5888.82 | 01-NOV-14:09 | 2413.46 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1069.18 | 19-NOV-19:03 | 927.25 | 22-NOV-06:00 |
December | 5888.82 | 01-DEC-15:09 | 2413.46 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 231.99 | 10-DEC-13:00 | 1260.81 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 201.14 | 0.00 | |||||
Maximum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3987.72 | 1731.53 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 23840.77 | 02-JAN-16:30 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.64 | 29-JAN-12:00 | 1651.56 | 18-JAN-04:00 |
February | 24809.68 | 01-FEB-15:09 | 23840.77 | 01-FEB-16:00 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 609.72 | 05-FEB-19:03 | 1429.09 | 10-FEB-23:00 |
March | 24809.68 | 01-MAR-15:09 | 23840.77 | 01-MAR-17:19 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 844.24 | 02-MAR-04:00 | 1166.68 | 06-MAR-06:00 |
April | 24809.68 | 01-APR-10:09 | 21854.04 | 01-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 985.12 | 28-APR-13:20 | 913.25 | 05-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 19867.31 | 01-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2713.44 | 21-MAY-13:00 | 271.41 | 01-MAY-05:00 |
June | 24809.68 | 01-JUN-14:09 | 19867.31 | 05-JUN-16:00 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1683.46 | 09-JUN-20:02 | 278.86 | 07-JUN-05:00 |
July | 24809.68 | 01-JUL-10:09 | 19867.31 | 14-JUL-08:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2111.11 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 24809.68 | 01-AUG-14:09 | 19867.31 | 12-AUG-16:00 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3293.46 | 16-AUG-20:02 | 0.00 | 01-AUG-00:10 |
September | 24809.68 | 01-SEP-14:09 | 21854.04 | 05-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.43 | 04-SEP-18:02 | 219.06 | 25-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 23840.77 | 03-OCT-16:00 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1449.78 | 09-OCT-18:02 | 505.42 | 20-OCT-05:00 |
November | 24809.68 | 01-NOV-14:09 | 23840.77 | 01-NOV-16:40 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 883.97 | 19-NOV-19:03 | 779.50 | 22-NOV-06:00 |
December | 24809.68 | 01-DEC-15:09 | 23840.77 | 01-DEC-16:19 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.89 | 10-DEC-13:00 | 1118.30 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 19867.31 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 164.64 | 0.00 | |||||
Maximum of Months | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3293.46 | 1651.56 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 29-JAN-12:00 | 896.54 | 18-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 303.25 | 05-FEB-19:03 | 771.12 | 10-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 419.30 | 01-MAR-13:00 | 628.47 | 17-MAR-21:20 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 521.54 | 28-APR-13:20 | 494.77 | 05-APR-01:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1436.53 | 21-MAY-13:00 | 166.60 | 01-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 876.36 | 09-JUN-20:02 | 199.51 | 07-JUN-05:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.98 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.23 | 16-AUG-20:02 | 6.93 | 31-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.17 | 04-SEP-18:02 | 162.97 | 25-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 748.80 | 09-OCT-18:02 | 371.82 | 20-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 448.68 | 19-NOV-19:03 | 441.04 | 22-NOV-06:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.53 | 10-DEC-13:00 | 569.48 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 0.00 | |||||
Maximum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.23 | 896.54 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 29-JAN-12:00 | 812.59 | 18-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 308.39 | 05-FEB-19:03 | 699.01 | 10-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 419.29 | 01-MAR-13:00 | 551.75 | 17-MAR-21:10 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 521.54 | 28-APR-13:20 | 446.43 | 05-APR-01:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1436.53 | 21-MAY-13:00 | 145.67 | 01-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 880.14 | 09-JUN-20:02 | 158.90 | 07-JUN-05:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.42 | 30-JUL-18:02 | 0.00 | 01-JUL-00:10 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1717.90 | 16-AUG-20:02 | 0.00 | 01-AUG-00:10 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.88 | 04-SEP-18:02 | 139.57 | 25-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 751.81 | 09-OCT-18:02 | 316.63 | 20-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.99 | 19-NOV-19:03 | 406.68 | 22-NOV-06:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.53 | 10-DEC-13:00 | 530.83 | 16-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 0.00 | |||||
Maximum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1717.90 | 812.59 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.86 | 23-JAN-12:53 | 3685.85 | 19-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754.45 | 05-FEB-12:03 | 5791.52 | 20-FEB-16:00 |
March | 0.00 | 01-MAR-00:10 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4137.33 | 27-MAR-11:01 | 5389.61 | 05-MAR-18:00 |
April | 0.00 | 01-APR-00:10 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5309.70 | 28-APR-11:01 | 1629.10 | 01-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5220.80 | 09-MAY-11:01 | 1193.13 | 01-MAY-07:01 |
June | 0.00 | 01-JUN-00:10 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5910.66 | 12-JUN-11:01 | 895.23 | 22-JUN-07:53 |
July | 0.00 | 01-JUL-00:10 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7009.36 | 21-JUL-11:01 | 206.80 | 20-JUL-10:53 |
August | 0.00 | 01-AUG-00:10 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6794.43 | 16-AUG-11:01 | 925.81 | 04-AUG-13:52 |
September | 0.00 | 01-SEP-00:10 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4435.09 | 26-SEP-11:01 | 689.24 | 25-SEP-07:02 |
October | 0.00 | 01-OCT-00:10 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.07 | 09-OCT-11:01 | 1385.05 | 29-OCT-07:01 |
November | 0.00 | 01-NOV-00:10 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1130.92 | 05-NOV-11:02 | 1703.95 | 22-NOV-08:61 |
December | 0.00 | 01-DEC-00:10 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.34 | 10-DEC-12:05 | 5292.63 | 15-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.86 | 206.80 | ||||
Maximum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7009.36 | 5791.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32967.85 | 29-JAN-09:02 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.21 |
February | 41659.61 | 10-FEB-07:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.19 |
March | 43419.80 | 22-MAR-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.71 |
April | 42905.03 | 26-APR-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 |
May | 43046.43 | 11-MAY-05:01 | 0.00 | 1035.60 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.49 | 0.00 |
June | 36725.60 | 02-JUN-05:01 | 0.00 | 1035.60 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 41596.29 | 04-JUL-07:01 | 0.00 | 1035.60 | 3219.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.95 | 0.00 |
August | 35527.68 | 06-AUG-06:02 | 0.00 | 887.66 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 336.20 | 0.00 |
September | 33433.25 | 26-SEP-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 | 0.00 |
October | 38957.50 | 21-OCT-06:02 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 |
November | 38057.41 | 05-NOV-08:62 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 |
December | 40258.91 | 01-DEC-07:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 32967.85 | 0.00 | 887.66 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43419.80 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 336.20 | 286.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 149852.53 | 22-JAN-09:02 | 12404.84 | 8829.92 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.99 |
February | 163542.59 | 10-FEB-07:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.07 |
March | 180714.13 | 23-MAR-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.23 |
April | 174756.57 | 26-APR-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
May | 164878.86 | 11-MAY-05:01 | 0.00 | 9271.41 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 0.00 |
June | 146170.57 | 01-JUN-05:01 | 0.00 | 9271.41 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 0.00 |
July | 158024.78 | 04-JUL-07:01 | 0.00 | 7726.18 | 5428.04 | 0.00 | 0.00 | 0.00 | 0.00 | 51.97 | 0.00 |
August | 131297.83 | 06-AUG-07:02 | 0.00 | 6622.44 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 60.83 | 0.00 |
September | 135450.09 | 26-SEP-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 0.00 |
October | 155504.28 | 20-OCT-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 |
November | 154919.97 | 19-NOV-09:02 | 15506.05 | 8829.92 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 0.00 |
December | 158194.92 | 01-DEC-07:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 131297.83 | 0.00 | 6622.44 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 180714.13 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 60.83 | 251.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20859.31 | 30-JAN-07:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 |
February | 26044.29 | 10-FEB-07:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.33 |
March | 27835.62 | 28-MAR-05:02 | 0.00 | 624.02 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
April | 27056.73 | 26-APR-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
May | 27309.15 | 11-MAY-05:01 | 0.00 | 873.62 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 0.00 |
June | 23358.51 | 02-JUN-05:01 | 0.00 | 873.62 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
July | 25365.06 | 04-JUL-07:01 | 0.00 | 873.62 | 3407.70 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 0.00 |
August | 22552.47 | 06-AUG-06:02 | 0.00 | 748.82 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 133.05 | 0.00 |
September | 21980.06 | 26-SEP-05:01 | 0.00 | 873.62 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 |
October | 25128.22 | 21-OCT-05:02 | 0.00 | 624.02 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 |
November | 25911.13 | 05-NOV-07:01 | 0.00 | 998.43 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 |
December | 25535.89 | 01-DEC-07:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20859.31 | 0.00 | 624.02 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27835.62 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 133.05 | 120.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17447.99 | 29-JAN-09:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.55 |
February | 20028.48 | 05-FEB-09:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
March | 23971.85 | 23-MAR-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.77 |
April | 23131.49 | 26-APR-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 22701.48 | 11-MAY-05:01 | 0.00 | 873.62 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 0.00 |
June | 19170.71 | 02-JUN-05:01 | 0.00 | 873.62 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 0.00 |
July | 21775.87 | 04-JUL-07:01 | 0.00 | 873.62 | 511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 23.55 | 0.00 |
August | 18655.29 | 06-AUG-06:02 | 0.00 | 748.82 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 140.34 | 0.00 |
September | 18248.48 | 26-SEP-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
October | 20861.17 | 21-OCT-06:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 |
November | 20939.11 | 05-NOV-07:01 | 0.00 | 998.43 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
December | 20334.06 | 01-DEC-07:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17447.99 | 0.00 | 748.82 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23971.85 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 140.34 | 61.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 31.57 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.114399E+12 | 93778.93 | 23-JAN-17:00 | 0.747233E+10 | 7352.21 | 19-JAN-17:00 |
February | 0.108212E+12 | 103664.36 | 07-FEB-16:30 | 0.677919E+10 | 9972.42 | 20-FEB-16:10 |
March | 0.127178E+12 | 105816.39 | 01-MAR-17:00 | 0.731527E+10 | 9584.00 | 05-MAR-17:00 |
April | 0.134539E+12 | 114233.36 | 29-APR-15:00 | 0.684246E+10 | 4787.34 | 03-APR-11:09 |
May | 0.161205E+12 | 126198.69 | 30-MAY-15:00 | 0.688781E+10 | 4746.31 | 01-MAY-11:39 |
June | 0.171651E+12 | 132715.67 | 09-JUN-14:09 | 0.655664E+10 | 4708.43 | 01-JUN-11:20 |
July | 0.187562E+12 | 140287.18 | 20-JUL-13:30 | 0.669090E+10 | 4690.27 | 31-JUL-11:50 |
August | 0.195604E+12 | 144041.76 | 10-AUG-15:00 | 0.679158E+10 | 4714.51 | 31-AUG-11:30 |
September | 0.173103E+12 | 133272.57 | 07-SEP-15:00 | 0.668973E+10 | 4751.45 | 29-SEP-11:20 |
October | 0.158721E+12 | 127876.82 | 07-OCT-16:00 | 0.707485E+10 | 4799.28 | 31-OCT-11:39 |
November | 0.136607E+12 | 117632.52 | 01-NOV-16:40 | 0.701288E+10 | 4838.18 | 30-NOV-12:09 |
December | 0.123949E+12 | 105047.62 | 05-DEC-17:30 | 0.744383E+10 | 9330.69 | 15-DEC-12:09 |
Annual Sum or Average | 0.179273E+13 | 0.835575E+11 | ||||
Minimum of Months | 0.108212E+12 | 93778.93 | 0.655664E+10 | 4690.27 | ||
Maximum of Months | 0.195604E+12 | 144041.76 | 0.747233E+10 | 9972.42 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.304966E+11 | 0.692474E+10 | 0.164409E+11 | 0.00 | 0.330395E+11 | 0.00 | 0.00 | 0.274969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267580E+11 | 0.600794E+10 | 0.149157E+11 | 0.00 | 0.299416E+11 | 0.00 | 0.00 | 0.305890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292423E+11 | 0.629218E+10 | 0.168545E+11 | 0.00 | 0.335215E+11 | 0.00 | 0.00 | 0.412672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269620E+11 | 0.570699E+10 | 0.160165E+11 | 0.00 | 0.321503E+11 | 0.00 | 0.00 | 0.537029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277389E+11 | 0.558995E+10 | 0.166477E+11 | 0.00 | 0.331854E+11 | 0.00 | 0.00 | 0.780430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.270231E+11 | 0.526670E+10 | 0.162772E+11 | 0.00 | 0.323766E+11 | 0.00 | 0.00 | 0.907069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268343E+11 | 0.549520E+10 | 0.163871E+11 | 0.00 | 0.330017E+11 | 0.00 | 0.00 | 0.105844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.281008E+11 | 0.575993E+10 | 0.168545E+11 | 0.00 | 0.335439E+11 | 0.00 | 0.00 | 0.111345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269936E+11 | 0.592156E+10 | 0.160165E+11 | 0.00 | 0.321661E+11 | 0.00 | 0.00 | 0.920047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285171E+11 | 0.649839E+10 | 0.164409E+11 | 0.00 | 0.328907E+11 | 0.00 | 0.00 | 0.743735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291034E+11 | 0.661542E+10 | 0.159174E+11 | 0.00 | 0.317066E+11 | 0.00 | 0.00 | 0.532639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309847E+11 | 0.702227E+10 | 0.163871E+11 | 0.00 | 0.330118E+11 | 0.00 | 0.00 | 0.365432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338755E+12 | 0.731013E+11 | 0.195156E+12 | 0.390536E+12 | 0.00 | 0.795180E+12 | |||||||
Minimum of Months | 0.267580E+11 | 0.526670E+10 | 0.149157E+11 | 0.00 | 0.299416E+11 | 0.00 | 0.00 | 0.274969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.309847E+11 | 0.702227E+10 | 0.168545E+11 | 0.00 | 0.335439E+11 | 0.00 | 0.00 | 0.111345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 46191359.74 | 0.00 | 0.742614E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108009E+09 | 0.00 | 0.667118E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 23597511.43 | 0.00 | 0.729168E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.684246E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.688781E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.655664E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.669090E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.679158E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.668973E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.707485E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.701288E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 55099290.69 | 0.00 | 0.738873E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.232897E+09 | 0.833246E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.655664E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.108009E+09 | 0.00 | 0.742614E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30883.85 | 02-JAN-16:30 | 4644.36 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 21401.81 | 01-JAN-10:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30883.85 | 01-FEB-16:00 | 4644.36 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 21401.81 | 01-FEB-08:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30883.85 | 01-MAR-17:19 | 4644.36 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 21401.81 | 04-MAR-08:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28897.12 | 01-APR-16:00 | 4644.36 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 20747.97 | 05-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 26910.39 | 01-MAY-16:49 | 4644.36 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 20530.02 | 01-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26910.39 | 05-JUN-16:00 | 4644.36 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 20530.02 | 22-JUN-05:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 26910.39 | 14-JUL-08:09 | 4644.36 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 20530.02 | 06-JUL-05:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 26910.39 | 12-AUG-16:00 | 4644.36 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 20530.02 | 01-AUG-05:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28897.12 | 05-SEP-16:00 | 4644.36 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 20530.02 | 05-SEP-05:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30883.85 | 03-OCT-16:00 | 4644.36 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 20530.02 | 08-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30883.85 | 01-NOV-16:40 | 4644.36 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 20617.20 | 22-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30883.85 | 01-DEC-16:19 | 4644.36 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 21401.81 | 15-DEC-13:39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 26910.39 | 4644.36 | 10771.04 | 0.00 | 20530.02 | 0.00 | 0.00 | |||||
Maximum of Months | 30883.85 | 4644.36 | 10771.04 | 0.00 | 21401.81 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 32131.90 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44644.50 | 07-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50234.24 | 27-MAR-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63501.44 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73635.44 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80464.42 | 09-JUN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86049.19 | 20-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89803.78 | 10-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80082.52 | 07-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72126.66 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61385.86 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43064.46 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 32131.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89803.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 93778.93 | 23-JAN-17:00 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 20530.02 | 0.00 | 0.00 | 26949.66 | 0.00 |
February | 103664.36 | 07-FEB-16:30 | 28897.12 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 43466.18 | 0.00 |
March | 105816.39 | 01-MAR-17:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 43631.48 | 0.00 |
April | 114233.36 | 29-APR-15:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 58008.64 | 0.00 |
May | 126198.69 | 30-MAY-15:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 69973.97 | 0.00 |
June | 132715.67 | 09-JUN-14:09 | 20950.20 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 80464.42 | 0.00 |
July | 140287.18 | 20-JUL-13:30 | 22936.93 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 86049.19 | 0.00 |
August | 144041.76 | 10-AUG-15:00 | 22936.93 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 89803.78 | 0.00 |
September | 133272.57 | 07-SEP-15:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 77047.85 | 0.00 |
October | 127876.82 | 07-OCT-16:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 65691.91 | 0.00 |
November | 117632.52 | 01-NOV-16:40 | 30883.85 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 55447.61 | 0.00 |
December | 105047.62 | 05-DEC-17:30 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 20530.02 | 0.00 | 0.00 | 38218.35 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 93778.93 | 20950.20 | 10771.04 | 0.00 | 0.00 | 20530.02 | 0.00 | 0.00 | 26949.66 | 0.00 | |
Maximum of Months | 144041.76 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 20530.02 | 0.00 | 0.00 | 89803.78 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 2610.84 | 18-JAN-17:00 | 0.00 | 4862.75 | 13-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 5377.79 | 20-FEB-15:00 | 0.00 | 4857.32 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 4950.88 | 05-MAR-17:00 | 0.00 | 4833.06 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4787.34 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4746.31 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4708.43 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4690.27 | 31-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4714.51 | 31-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4751.45 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4799.28 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4838.18 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 4479.12 | 15-DEC-12:09 | 0.00 | 4859.88 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4690.27 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 5377.79 | 0.00 | 4862.75 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.27 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.16 | 0.50 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.00 | 0.83 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.26 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.33 | 26.11 | 1.33 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 26.27 | 0.83 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.45 | 0.33 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.45 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.66 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.80 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.97 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.39 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 27.86 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.45 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.22 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.22 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.23 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 26.22 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 26.23 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.50 | 23.83 | 70.00 | 23.89 | 0.00 | 0.00 |
February | 19.17 | 23.84 | 134.00 | 23.89 | 0.67 | 23.99 |
March | 11.00 | 23.89 | 206.83 | 23.89 | 0.50 | 23.97 |
April | 2.00 | 23.95 | 360.17 | 23.89 | 2.00 | 23.95 |
May | 6.50 | 23.99 | 418.00 | 23.89 | 6.50 | 23.99 |
June | 17.83 | 23.97 | 408.00 | 23.89 | 17.83 | 23.97 |
July | 24.17 | 23.99 | 415.00 | 23.90 | 24.17 | 23.99 |
August | 19.50 | 24.02 | 422.00 | 23.90 | 19.50 | 24.02 |
September | 20.00 | 23.99 | 405.00 | 23.89 | 20.00 | 23.99 |
October | 14.00 | 23.97 | 412.83 | 23.89 | 14.00 | 23.97 |
November | 2.33 | 23.99 | 380.83 | 23.89 | 2.33 | 23.99 |
December | 13.83 | 23.89 | 239.83 | 23.89 | 0.17 | 24.02 |
Annual Sum or Average | 222.83 | 23.91 | 3872.50 | 23.89 | 107.67 | 23.99 |
Minimum of Months | 2.00 | 23.83 | 70.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 72.50 | 24.02 | 422.00 | 23.90 | 24.17 | 24.02 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.33 | 23.60 | 187.83 | 23.89 | 0.00 | 0.00 |
February | 5.83 | 23.61 | 262.50 | 23.89 | 0.00 | 0.00 |
March | 1.83 | 23.87 | 305.67 | 23.89 | 0.00 | 0.00 |
April | 0.67 | 23.96 | 374.67 | 23.89 | 0.67 | 23.96 |
May | 3.50 | 23.99 | 416.00 | 23.89 | 3.50 | 23.99 |
June | 33.17 | 23.92 | 408.00 | 23.89 | 33.17 | 23.92 |
July | 68.50 | 23.92 | 415.00 | 23.90 | 68.50 | 23.92 |
August | 68.83 | 23.92 | 422.00 | 23.90 | 68.83 | 23.92 |
September | 49.50 | 23.92 | 405.00 | 23.89 | 49.50 | 23.92 |
October | 25.33 | 23.92 | 408.67 | 23.89 | 25.33 | 23.92 |
November | 1.17 | 24.04 | 387.67 | 23.89 | 1.17 | 24.04 |
December | 3.67 | 23.76 | 305.17 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 287.33 | 23.88 | 4298.17 | 23.89 | 250.67 | 23.92 |
Minimum of Months | 0.67 | 23.60 | 187.83 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 68.83 | 24.04 | 422.00 | 23.90 | 68.83 | 24.04 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.33 | 23.81 | 297.00 | 23.89 | 0.00 | 0.00 |
February | 3.33 | 23.76 | 318.83 | 23.89 | 0.00 | 0.00 |
March | 3.17 | 23.90 | 354.50 | 23.89 | 0.17 | 24.05 |
April | 1.17 | 23.99 | 393.67 | 23.89 | 1.17 | 23.99 |
May | 3.50 | 23.98 | 418.00 | 23.89 | 3.50 | 23.98 |
June | 11.50 | 23.96 | 408.00 | 23.89 | 11.50 | 23.96 |
July | 13.67 | 23.98 | 415.00 | 23.89 | 13.67 | 23.98 |
August | 11.17 | 23.99 | 422.00 | 23.89 | 11.17 | 23.99 |
September | 8.83 | 23.99 | 405.00 | 23.89 | 8.83 | 23.99 |
October | 6.33 | 23.99 | 414.00 | 23.89 | 6.33 | 23.99 |
November | 0.83 | 24.07 | 399.00 | 23.89 | 0.83 | 24.07 |
December | 0.33 | 23.90 | 379.50 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 75.17 | 23.94 | 4624.50 | 23.89 | 57.17 | 23.98 |
Minimum of Months | 0.33 | 23.76 | 297.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 13.67 | 24.07 | 422.00 | 23.89 | 13.67 | 24.07 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.17 | 23.45 | 242.17 | 23.89 | 0.00 | 0.00 |
February | 11.83 | 23.40 | 284.50 | 23.89 | 0.50 | 24.04 |
March | 8.33 | 23.68 | 310.83 | 23.89 | 0.50 | 23.98 |
April | 2.50 | 23.96 | 376.00 | 23.89 | 2.50 | 23.96 |
May | 6.50 | 23.96 | 417.67 | 23.89 | 6.50 | 23.96 |
June | 18.67 | 23.94 | 408.00 | 23.89 | 18.67 | 23.94 |
July | 20.50 | 23.96 | 415.00 | 23.89 | 20.50 | 23.96 |
August | 16.33 | 23.98 | 422.00 | 23.89 | 16.33 | 23.98 |
September | 14.33 | 23.98 | 405.00 | 23.89 | 14.33 | 23.98 |
October | 9.33 | 23.97 | 414.00 | 23.89 | 9.33 | 23.97 |
November | 2.00 | 23.99 | 397.33 | 23.89 | 2.00 | 23.99 |
December | 3.67 | 23.70 | 352.17 | 23.89 | 0.50 | 23.96 |
Annual Sum or Average | 145.17 | 23.78 | 4444.67 | 23.89 | 91.67 | 23.97 |
Minimum of Months | 2.00 | 23.40 | 242.17 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 31.17 | 23.99 | 422.00 | 23.89 | 20.50 | 24.04 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88051 | 46.17263 | 0.36743 | 7.91345 |
February | 376.00000 | 23.89334 | 48.35211 | 0.40852 | 8.54858 |
March | 422.00000 | 23.90233 | 46.22230 | 0.42496 | 8.84409 |
April | 405.00000 | 23.91118 | 48.38397 | 0.48685 | 10.01065 |
May | 418.00000 | 23.91394 | 49.22235 | -0.2836 | 6.76951 |
June | 408.00000 | 23.91498 | 53.77572 | -0.2135 | 6.04003 |
July | 415.00000 | 23.91729 | 55.52158 | -0.1665 | 5.68042 |
August | 422.00000 | 23.91691 | 56.21135 | -0.1509 | 5.56328 |
September | 405.00000 | 23.91565 | 55.39114 | -0.2037 | 5.95767 |
October | 414.00000 | 23.91471 | 51.72131 | 0.56992 | 11.89018 |
November | 399.00000 | 23.91264 | 50.08478 | 0.50543 | 10.40169 |
December | 415.00000 | 23.89965 | 49.06444 | 0.42880 | 8.90415 |
Annual Sum or Average | 4913.00000 | 23.90784 | 50.85831 | 0.17847 | 8.03112 |
Minimum of Months | 376.00000 | 23.88051 | 46.17263 | -0.2836 | 5.56328 |
Maximum of Months | 422.00000 | 23.91729 | 56.21135 | 0.56992 | 11.89018 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.86980 | 44.41887 | 0.40969 | 8.61451 |
February | 376.00000 | 23.89093 | 46.73735 | 0.45190 | 9.33141 |
March | 422.00000 | 23.90166 | 44.61417 | 0.46443 | 9.59153 |
April | 405.00000 | 23.91022 | 47.14588 | 0.52031 | 10.73820 |
May | 418.00000 | 23.91372 | 49.00164 | -0.2526 | 6.43741 |
June | 408.00000 | 23.91459 | 55.21442 | -0.1858 | 5.81403 |
July | 415.00000 | 23.91643 | 57.99233 | -0.1423 | 5.52096 |
August | 422.00000 | 23.91627 | 59.27522 | -0.1283 | 5.42043 |
September | 405.00000 | 23.91536 | 57.80438 | -0.1768 | 5.73217 |
October | 414.00000 | 23.91447 | 52.71348 | 0.58931 | 12.37664 |
November | 399.00000 | 23.91120 | 50.18610 | 0.53103 | 10.97180 |
December | 415.00000 | 23.89628 | 48.16708 | 0.46627 | 9.61789 |
Annual Sum or Average | 4913.00000 | 23.90599 | 51.13430 | 0.20953 | 8.33052 |
Minimum of Months | 376.00000 | 23.86980 | 44.41887 | -0.2526 | 5.42043 |
Maximum of Months | 422.00000 | 23.91643 | 59.27522 | 0.58931 | 12.37664 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.89398 | 40.72251 | 0.46814 | 9.70069 |
February | 376.00000 | 23.89913 | 43.05459 | 0.49883 | 10.30431 |
March | 422.00000 | 23.90428 | 41.67347 | 0.50333 | 10.41533 |
April | 405.00000 | 23.91083 | 44.22984 | 0.55087 | 11.43387 |
May | 418.00000 | 23.91275 | 45.60182 | -0.1879 | 5.85787 |
June | 408.00000 | 23.91303 | 50.64505 | -0.1206 | 5.40629 |
July | 415.00000 | 23.91401 | 52.48431 | -0.0625 | 5.19230 |
August | 422.00000 | 23.91365 | 53.01251 | -0.0320 | 5.12139 |
September | 405.00000 | 23.91339 | 51.51379 | -0.0687 | 5.21554 |
October | 414.00000 | 23.91330 | 47.04096 | 0.67150 | 14.56601 |
November | 399.00000 | 23.91264 | 44.82017 | 0.61274 | 12.96338 |
December | 415.00000 | 23.90506 | 43.52665 | 0.52673 | 10.90634 |
Annual Sum or Average | 4913.00000 | 23.90889 | 46.55176 | 0.27742 | 8.90047 |
Minimum of Months | 376.00000 | 23.89398 | 40.72251 | -0.1879 | 5.12139 |
Maximum of Months | 422.00000 | 23.91401 | 53.01251 | 0.67150 | 14.56601 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.85319 | 42.67790 | 0.43327 | 9.10919 |
February | 376.00000 | 23.87564 | 45.25359 | 0.46969 | 9.74165 |
March | 422.00000 | 23.89412 | 43.42085 | 0.47371 | 9.81934 |
April | 405.00000 | 23.90848 | 45.91658 | 0.52544 | 10.85960 |
May | 418.00000 | 23.91301 | 46.81154 | -0.2275 | 6.20198 |
June | 408.00000 | 23.91357 | 52.22202 | -0.1573 | 5.62185 |
July | 415.00000 | 23.91477 | 53.95958 | -0.0981 | 5.31345 |
August | 422.00000 | 23.91449 | 54.47013 | -0.0676 | 5.19495 |
September | 405.00000 | 23.91399 | 53.09563 | -0.1040 | 5.33883 |
October | 414.00000 | 23.91365 | 48.41785 | 0.64786 | 13.90973 |
November | 399.00000 | 23.91187 | 46.40078 | 0.58832 | 12.34299 |
December | 415.00000 | 23.89594 | 45.63988 | 0.50073 | 10.35060 |
Annual Sum or Average | 4913.00000 | 23.90204 | 48.21096 | 0.24605 | 8.63030 |
Minimum of Months | 376.00000 | 23.85319 | 42.67790 | -0.2275 | 5.19495 |
Maximum of Months | 422.00000 | 23.91477 | 54.47013 | 0.64786 | 13.90973 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.128303E+11 | 0.352350E+10 | 399.14 | 0.104095E+11 | 0.242086E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 51851.16 | 30-JAN-07:02 | 37501.75 | 29-JAN-09:02 | 15705.82 | 30-JAN-07:02 | 11294.93 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.142398E+11 | 0.395228E+10 | 370.96 | 0.113241E+11 | 0.291566E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:10 | 52979.25 | 09-FEB-07:02 | 45543.46 | 10-FEB-07:02 | 19750.01 | 09-FEB-07:04 | 11355.85 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.190450E+11 | 0.542701E+10 | 424.62 | 0.157522E+11 | 0.329289E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 52926.53 | 29-MAR-06:02 | 47954.74 | 28-MAR-06:02 | 19854.37 | 29-MAR-06:02 | 11549.99 | 02-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.244053E+11 | 0.719097E+10 | 421.01 | 0.198943E+11 | 0.451095E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:10 | 53839.18 | 30-APR-07:01 | 47746.30 | 26-APR-06:02 | 22431.78 | 30-APR-07:01 | 11524.25 | 16-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.352258E+11 | 0.108443E+11 | 444.77 | 0.286892E+11 | 0.653659E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 56217.19 | 30-MAY-05:01 | 48054.27 | 10-MAY-05:02 | 29374.22 | 30-MAY-05:04 | 12808.96 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.420411E+11 | 0.127408E+11 | 436.75 | 0.314483E+11 | 0.105928E+11 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 56307.37 | 08-JUN-05:02 | 41412.21 | 01-JUN-05:01 | 33760.24 | 19-JUN-05:06 | 13069.16 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.490504E+11 | 0.149321E+11 | 450.13 | 0.354057E+11 | 0.136447E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 55986.23 | 06-JUL-05:01 | 47139.36 | 04-JUL-07:01 | 33958.16 | 05-JUL-04:03 | 13353.73 | 23-JUL-08:15 | 0.00 | 01-JUL-00:10 |
August | 0.520074E+11 | 0.157352E+11 | 461.15 | 0.370589E+11 | 0.149485E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 55986.23 | 31-AUG-05:01 | 41796.99 | 06-AUG-06:02 | 34773.47 | 08-AUG-05:07 | 13299.30 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.433246E+11 | 0.128116E+11 | 434.39 | 0.309977E+11 | 0.123269E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 56294.10 | 23-SEP-05:02 | 38337.81 | 26-SEP-06:02 | 32904.80 | 11-SEP-05:07 | 12949.25 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.351819E+11 | 0.102805E+11 | 441.52 | 0.267454E+11 | 0.843656E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 56277.28 | 01-OCT-07:01 | 43044.07 | 21-OCT-06:02 | 32743.99 | 08-OCT-07:04 | 12234.26 | 08-OCT-08:15 | 0.00 | 01-OCT-00:10 |
November | 0.252964E+11 | 0.719216E+10 | 417.78 | 0.197077E+11 | 0.558874E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 54536.32 | 03-NOV-05:02 | 42870.90 | 05-NOV-08:62 | 23427.84 | 03-NOV-05:02 | 11606.74 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.173922E+11 | 0.479396E+10 | 411.25 | 0.135892E+11 | 0.380302E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 52754.15 | 11-DEC-07:02 | 43519.20 | 01-DEC-07:02 | 18932.04 | 06-DEC-07:02 | 11350.55 | 12-DEC-07:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.370040E+12 | 0.109424E+12 | 5113.47 | 0.281022E+12 | 0.890182E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.128303E+11 | 0.352350E+10 | 370.96 | 0.104095E+11 | 0.242086E+10 | 0.00 | 1.00 | 0.00 | 51851.16 | 37501.75 | 15705.82 | 11294.93 | 0.00 | |||||||
Maximum of Months | 0.520074E+11 | 0.157352E+11 | 461.15 | 0.370589E+11 | 0.149485E+11 | 0.00 | 1.00 | 0.00 | 56307.37 | 48054.27 | 34773.47 | 13353.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.626517E+11 | 0.186945E+11 | 390.83 | 0.486066E+11 | 0.140450E+11 | 0.00 | 1.00 | 22-JAN-09:02 | 0.00 | 01-JAN-00:10 | 218623.75 | 30-JAN-07:02 | 164893.31 | 22-JAN-09:02 | 72467.48 | 30-JAN-07:02 | 52514.66 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.699785E+11 | 0.210620E+11 | 369.59 | 0.532954E+11 | 0.166831E+11 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:10 | 222508.98 | 07-FEB-07:02 | 175493.95 | 10-FEB-07:02 | 84030.70 | 07-FEB-07:02 | 52624.94 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.931086E+11 | 0.287093E+11 | 424.36 | 0.739308E+11 | 0.191777E+11 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 222738.33 | 29-MAR-06:02 | 199492.71 | 23-MAR-06:02 | 87550.10 | 29-MAR-06:02 | 53973.18 | 02-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.118660E+12 | 0.375998E+11 | 422.55 | 0.926565E+11 | 0.260035E+11 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:10 | 227575.63 | 30-APR-08:62 | 195588.60 | 26-APR-06:02 | 101024.88 | 30-APR-08:04 | 53663.15 | 03-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.164615E+12 | 0.542140E+11 | 444.80 | 0.128008E+12 | 0.366075E+11 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 230315.29 | 24-MAY-05:02 | 192557.98 | 10-MAY-06:02 | 103606.18 | 01-MAY-06:04 | 59730.57 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.195783E+12 | 0.628658E+11 | 436.88 | 0.136662E+12 | 0.591208E+11 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 235206.01 | 19-JUN-05:01 | 172159.58 | 01-JUN-05:01 | 121704.74 | 25-JUN-08:06 | 60879.32 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.228459E+12 | 0.730220E+11 | 445.24 | 0.152043E+12 | 0.764159E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 236577.29 | 05-JUL-05:02 | 189376.32 | 04-JUL-07:01 | 124673.64 | 20-JUL-06:06 | 61827.79 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.241451E+12 | 0.764836E+11 | 452.42 | 0.156894E+12 | 0.845566E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 236635.85 | 09-AUG-05:02 | 171068.04 | 06-AUG-07:02 | 128819.95 | 08-AUG-06:06 | 62110.79 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.202483E+12 | 0.631664E+11 | 434.17 | 0.132539E+12 | 0.699441E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 237031.38 | 11-SEP-05:01 | 161595.93 | 04-SEP-08:62 | 127777.62 | 11-SEP-06:06 | 60109.54 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.162042E+12 | 0.506468E+11 | 441.40 | 0.114677E+12 | 0.473651E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 235888.31 | 08-OCT-07:01 | 175316.08 | 20-OCT-06:02 | 121979.39 | 08-OCT-08:06 | 56831.97 | 08-OCT-08:15 | 0.00 | 01-OCT-00:10 |
November | 0.118010E+12 | 0.361515E+11 | 415.67 | 0.860881E+11 | 0.319224E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 227528.35 | 03-NOV-06:02 | 178564.96 | 19-NOV-09:02 | 100049.84 | 03-NOV-06:04 | 53933.54 | 11-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.833152E+11 | 0.248909E+11 | 409.18 | 0.614409E+11 | 0.218742E+11 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 221980.86 | 06-DEC-07:02 | 166559.50 | 01-DEC-07:02 | 90378.38 | 06-DEC-07:02 | 52737.52 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.174056E+13 | 0.547507E+12 | 5087.09 | 0.123684E+13 | 0.503716E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.626517E+11 | 0.186945E+11 | 369.59 | 0.486066E+11 | 0.140450E+11 | 0.00 | 1.00 | 0.00 | 218623.75 | 161595.93 | 72467.48 | 52514.66 | 0.00 | |||||||
Maximum of Months | 0.241451E+12 | 0.764836E+11 | 452.42 | 0.156894E+12 | 0.845566E+11 | 0.00 | 1.00 | 0.00 | 237031.38 | 199492.71 | 128819.95 | 62110.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.117071E+11 | 0.309749E+10 | 409.79 | 0.970075E+10 | 0.200639E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 34073.52 | 30-JAN-07:02 | 23811.30 | 29-JAN-09:02 | 10756.04 | 30-JAN-07:02 | 7325.80 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.119921E+11 | 0.321988E+10 | 377.14 | 0.971644E+10 | 0.227570E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:10 | 34690.70 | 09-FEB-07:02 | 28820.09 | 10-FEB-07:02 | 12920.86 | 07-FEB-07:02 | 7337.63 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.146513E+11 | 0.406284E+10 | 430.76 | 0.122075E+11 | 0.244387E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 34756.93 | 29-MAR-06:02 | 31648.62 | 28-MAR-05:02 | 13645.61 | 29-MAR-06:02 | 7692.03 | 02-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.171589E+11 | 0.495707E+10 | 426.72 | 0.139801E+11 | 0.317885E+10 | 0.00 | 1.00 | 01-APR-06:03 | 0.00 | 01-APR-00:10 | 35676.65 | 30-APR-07:01 | 30615.80 | 26-APR-06:02 | 15780.43 | 30-APR-07:01 | 7453.12 | 16-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.232010E+11 | 0.705132E+10 | 446.60 | 0.187628E+11 | 0.443822E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 37141.40 | 24-MAY-05:02 | 30873.82 | 10-MAY-05:02 | 19911.73 | 30-MAY-05:04 | 8304.75 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.271232E+11 | 0.813384E+10 | 439.46 | 0.200215E+11 | 0.710162E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 37160.41 | 25-JUN-07:02 | 26578.61 | 01-JUN-05:01 | 22332.43 | 19-JUN-05:04 | 8467.29 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.317855E+11 | 0.956879E+10 | 457.29 | 0.226064E+11 | 0.917904E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 36938.28 | 06-JUL-05:01 | 29348.59 | 04-JUL-07:01 | 22559.27 | 05-JUL-04:03 | 8604.89 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.342105E+11 | 0.102131E+11 | 470.75 | 0.240382E+11 | 0.101722E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 36953.57 | 31-AUG-04:03 | 26995.55 | 06-AUG-06:02 | 22691.83 | 08-AUG-04:02 | 8603.40 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.295677E+11 | 0.858950E+10 | 441.00 | 0.210667E+11 | 0.850097E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 37141.40 | 23-SEP-05:02 | 25318.64 | 26-SEP-06:02 | 20859.06 | 11-SEP-04:03 | 8353.03 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.254528E+11 | 0.726220E+10 | 444.74 | 0.194860E+11 | 0.596681E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 37130.55 | 07-OCT-05:01 | 28147.17 | 21-OCT-05:02 | 21621.49 | 08-OCT-07:04 | 7884.55 | 08-OCT-08:04 | 0.00 | 01-OCT-00:10 |
November | 0.197509E+11 | 0.544394E+10 | 422.46 | 0.155947E+11 | 0.415621E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 36190.08 | 03-NOV-05:02 | 27842.16 | 05-NOV-07:01 | 15581.42 | 03-NOV-05:02 | 7594.09 | 20-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.146715E+11 | 0.390617E+10 | 423.16 | 0.116936E+11 | 0.297792E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 34657.99 | 11-DEC-07:02 | 27790.21 | 01-DEC-07:02 | 13093.67 | 15-DEC-07:02 | 7336.76 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.261273E+12 | 0.755061E+11 | 5189.87 | 0.198875E+12 | 0.623978E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.117071E+11 | 0.309749E+10 | 377.14 | 0.970075E+10 | 0.200639E+10 | 0.00 | 1.00 | 0.00 | 34073.52 | 23811.30 | 10756.04 | 7325.80 | 0.00 | |||||||
Maximum of Months | 0.342105E+11 | 0.102131E+11 | 470.75 | 0.240382E+11 | 0.101722E+11 | 0.00 | 1.00 | 0.00 | 37160.41 | 31648.62 | 22691.83 | 8604.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.815167E+10 | 0.218143E+10 | 385.62 | 0.648398E+10 | 0.166769E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 29210.24 | 30-JAN-07:02 | 19737.21 | 29-JAN-09:02 | 10184.64 | 30-JAN-07:02 | 6277.87 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.867183E+10 | 0.235485E+10 | 363.97 | 0.676238E+10 | 0.190945E+10 | 0.00 | 1.00 | 05-FEB-09:02 | 0.00 | 01-FEB-00:10 | 29831.72 | 09-FEB-07:02 | 22553.96 | 05-FEB-09:02 | 12132.67 | 07-FEB-07:02 | 6290.85 | 09-FEB-07:02 | 0.00 | 01-FEB-00:10 |
March | 0.109444E+11 | 0.306804E+10 | 419.65 | 0.882673E+10 | 0.211763E+10 | 0.00 | 1.00 | 01-MAR-07:02 | 0.00 | 01-MAR-00:10 | 29932.59 | 29-MAR-06:02 | 26497.23 | 23-MAR-06:02 | 12861.96 | 29-MAR-06:02 | 6557.18 | 02-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.136123E+11 | 0.395503E+10 | 416.80 | 0.107518E+11 | 0.286051E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:10 | 30436.44 | 30-APR-08:62 | 25790.85 | 26-APR-06:02 | 14329.22 | 30-APR-08:62 | 6389.18 | 03-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.195673E+11 | 0.593330E+10 | 445.56 | 0.153828E+11 | 0.418451E+10 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 31771.22 | 24-MAY-05:02 | 25464.74 | 10-MAY-05:02 | 17616.24 | 24-MAY-05:02 | 7112.48 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.234249E+11 | 0.696653E+10 | 437.82 | 0.166678E+11 | 0.675711E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:10 | 31787.48 | 25-JUN-07:02 | 21882.01 | 02-JUN-06:02 | 19615.06 | 19-JUN-05:03 | 7249.91 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.280257E+11 | 0.832088E+10 | 452.07 | 0.191863E+11 | 0.883933E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 31597.46 | 06-JUL-05:01 | 25018.15 | 04-JUL-07:01 | 19565.25 | 05-JUL-05:07 | 7366.06 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.303112E+11 | 0.891314E+10 | 464.91 | 0.204885E+11 | 0.982272E+10 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 31597.46 | 31-AUG-05:01 | 22359.84 | 06-AUG-06:02 | 20148.43 | 08-AUG-04:02 | 7370.51 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.258915E+11 | 0.743725E+10 | 437.54 | 0.177279E+11 | 0.816357E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 31771.22 | 23-SEP-05:02 | 20987.00 | 26-SEP-06:02 | 18631.09 | 11-SEP-05:06 | 7154.89 | 04-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.217822E+11 | 0.618398E+10 | 442.75 | 0.161055E+11 | 0.567672E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 31779.26 | 07-OCT-05:01 | 22905.69 | 21-OCT-06:02 | 19127.77 | 08-OCT-07:04 | 6739.46 | 08-OCT-08:04 | 0.00 | 01-OCT-00:10 |
November | 0.162110E+11 | 0.447623E+10 | 417.98 | 0.123508E+11 | 0.386028E+10 | 0.00 | 1.00 | 01-NOV-05:02 | 0.00 | 01-NOV-00:10 | 30911.38 | 03-NOV-05:02 | 22661.35 | 05-NOV-08:62 | 14271.90 | 03-NOV-05:02 | 6474.68 | 20-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.109929E+11 | 0.295215E+10 | 411.67 | 0.839892E+10 | 0.259398E+10 | 0.00 | 1.00 | 02-DEC-07:02 | 0.00 | 01-DEC-00:10 | 29780.43 | 11-DEC-07:02 | 21665.53 | 01-DEC-07:02 | 12204.32 | 15-DEC-07:02 | 6291.49 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.217587E+12 | 0.627428E+11 | 5096.34 | 0.159133E+12 | 0.584535E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.815167E+10 | 0.218143E+10 | 363.97 | 0.648398E+10 | 0.166769E+10 | 0.00 | 1.00 | 0.00 | 29210.24 | 19737.21 | 10184.64 | 6277.87 | 0.00 | |||||||
Maximum of Months | 0.303112E+11 | 0.891314E+10 | 464.91 | 0.204885E+11 | 0.982272E+10 | 0.00 | 1.00 | 0.00 | 31787.48 | 26497.23 | 20148.43 | 7370.51 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.66 | 30.56 | 49.10 | 96.85 | 40.42 | 0.00 | 0.00 | 744.00 |
February | 96.91 | 39.82 | 57.09 | 122.54 | 34.65 | 0.00 | 0.00 | 672.00 |
March | 116.14 | 48.40 | 67.75 | 153.04 | 29.87 | 0.00 | 0.00 | 744.00 |
April | 138.11 | 61.48 | 76.62 | 190.83 | 23.39 | 0.00 | 0.00 | 720.00 |
May | 156.17 | 75.93 | 80.24 | 226.15 | 12.38 | 0.00 | 0.00 | 744.00 |
June | 162.88 | 82.87 | 80.01 | 238.19 | 9.22 | 0.00 | 0.00 | 720.00 |
July | 157.97 | 80.17 | 77.80 | 238.96 | 3.84 | 0.00 | 0.00 | 744.00 |
August | 150.29 | 73.77 | 76.51 | 228.61 | 3.37 | 0.00 | 0.00 | 744.00 |
September | 135.25 | 65.02 | 70.23 | 199.12 | 9.95 | 0.00 | 0.00 | 720.00 |
October | 113.45 | 53.21 | 60.24 | 161.13 | 17.79 | 0.00 | 0.00 | 744.00 |
November | 90.54 | 39.77 | 50.77 | 121.70 | 27.82 | 0.00 | 0.00 | 720.00 |
December | 73.86 | 28.62 | 45.24 | 92.44 | 35.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 122.71 | 56.71 | 66.00 | 172.71 | 20.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.86 | 28.62 | 45.24 | 92.44 | 3.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 162.88 | 82.87 | 80.24 | 238.96 | 40.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.39 | 345.34 | 389.05 | 1028.90 | 444.79 | 0.00 | 0.00 | 744.00 |
February | 689.50 | 282.03 | 407.47 | 1000.12 | 382.61 | 0.00 | 0.00 | 672.00 |
March | 567.38 | 153.96 | 413.42 | 863.79 | 303.45 | 0.00 | 0.00 | 744.00 |
April | 445.96 | 47.17 | 398.80 | 782.01 | 200.39 | 0.00 | 0.00 | 720.00 |
May | 377.79 | 5.70 | 372.09 | 909.85 | 68.75 | 0.00 | 0.00 | 744.00 |
June | 355.86 | 0.43 | 355.43 | 962.47 | 29.77 | 0.00 | 0.00 | 720.00 |
July | 355.81 | 2.97 | 352.84 | 1103.36 | 3.26 | 0.00 | 0.00 | 744.00 |
August | 412.63 | 29.10 | 383.53 | 1182.69 | 2.20 | 0.00 | 0.00 | 744.00 |
September | 544.12 | 124.60 | 419.52 | 1195.49 | 43.79 | 0.00 | 0.00 | 720.00 |
October | 712.44 | 283.19 | 429.26 | 1339.01 | 121.64 | 0.00 | 0.00 | 744.00 |
November | 786.16 | 379.04 | 407.12 | 1311.41 | 241.43 | 0.00 | 0.00 | 720.00 |
December | 729.86 | 360.61 | 369.25 | 1090.67 | 382.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 558.54 | 167.24 | 391.31 | 1064.69 | 184.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 355.81 | 0.43 | 352.84 | 782.01 | 2.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 786.16 | 379.04 | 429.26 | 1339.01 | 444.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.39 | 345.34 | 389.05 | 1028.80 | 427.98 | 0.00 | 0.00 | 744.00 |
February | 689.50 | 282.03 | 407.47 | 999.13 | 366.31 | 0.00 | 0.00 | 672.00 |
March | 567.38 | 153.96 | 413.42 | 862.06 | 287.02 | 0.00 | 0.00 | 744.00 |
April | 445.96 | 47.17 | 398.80 | 779.43 | 185.55 | 0.00 | 0.00 | 720.00 |
May | 377.79 | 5.70 | 372.09 | 910.09 | 59.06 | 0.00 | 0.00 | 744.00 |
June | 355.86 | 0.43 | 355.43 | 965.24 | 23.21 | 0.00 | 0.00 | 720.00 |
July | 355.81 | 2.97 | 352.84 | 1110.00 | 2.09 | 0.00 | 0.00 | 744.00 |
August | 412.63 | 29.10 | 383.53 | 1189.03 | 1.33 | 0.00 | 0.00 | 744.00 |
September | 544.12 | 124.60 | 419.52 | 1196.14 | 36.53 | 0.00 | 0.00 | 720.00 |
October | 712.44 | 283.19 | 429.26 | 1335.94 | 109.32 | 0.00 | 0.00 | 744.00 |
November | 786.16 | 379.04 | 407.12 | 1308.75 | 227.73 | 0.00 | 0.00 | 720.00 |
December | 729.86 | 360.61 | 369.25 | 1089.41 | 366.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 558.54 | 167.24 | 391.31 | 1065.06 | 173.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 355.81 | 0.43 | 352.84 | 779.43 | 1.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 786.16 | 379.04 | 429.26 | 1335.94 | 427.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.11 | 71.06 | 80.05 | 210.33 | 83.59 | 0.00 | 0.00 | 744.00 |
February | 141.87 | 58.03 | 83.84 | 199.43 | 73.52 | 0.00 | 0.00 | 672.00 |
March | 116.75 | 31.68 | 85.07 | 164.23 | 61.27 | 0.00 | 0.00 | 744.00 |
April | 91.76 | 9.70 | 82.06 | 133.27 | 45.20 | 0.00 | 0.00 | 720.00 |
May | 77.74 | 1.17 | 76.56 | 131.82 | 19.68 | 0.00 | 0.00 | 744.00 |
June | 73.22 | 0.09 | 73.14 | 132.03 | 11.50 | 0.00 | 0.00 | 720.00 |
July | 73.21 | 0.61 | 72.60 | 146.47 | 2.92 | 0.00 | 0.00 | 744.00 |
August | 84.90 | 5.99 | 78.92 | 159.56 | 2.95 | 0.00 | 0.00 | 744.00 |
September | 111.96 | 25.64 | 86.32 | 182.25 | 16.86 | 0.00 | 0.00 | 720.00 |
October | 146.60 | 58.27 | 88.33 | 229.67 | 35.72 | 0.00 | 0.00 | 744.00 |
November | 161.76 | 77.99 | 83.77 | 243.79 | 57.51 | 0.00 | 0.00 | 720.00 |
December | 150.18 | 74.20 | 75.98 | 216.49 | 75.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 114.93 | 34.41 | 80.52 | 179.01 | 40.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.21 | 0.09 | 72.60 | 131.82 | 2.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 161.76 | 77.99 | 88.33 | 243.79 | 83.59 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213368E+09 | 81859244.11 | 0.131509E+09 | 0.259405E+09 | 0.108255E+09 |
February | 0.234454E+09 | 96342990.54 | 0.138111E+09 | 0.296448E+09 | 83829507.44 |
March | 0.311081E+09 | 0.129628E+09 | 0.181453E+09 | 0.409904E+09 | 79991401.71 |
April | 0.357973E+09 | 0.159367E+09 | 0.198606E+09 | 0.494642E+09 | 60619632.31 |
May | 0.418280E+09 | 0.203359E+09 | 0.214921E+09 | 0.605730E+09 | 33171058.73 |
June | 0.422183E+09 | 0.214793E+09 | 0.207390E+09 | 0.617397E+09 | 23885537.44 |
July | 0.423095E+09 | 0.214717E+09 | 0.208378E+09 | 0.640020E+09 | 10272755.33 |
August | 0.402524E+09 | 0.197593E+09 | 0.204930E+09 | 0.612322E+09 | 9015791.51 |
September | 0.350560E+09 | 0.168520E+09 | 0.182040E+09 | 0.516120E+09 | 25794719.78 |
October | 0.303863E+09 | 0.142515E+09 | 0.161348E+09 | 0.431574E+09 | 47654771.28 |
November | 0.234693E+09 | 0.103085E+09 | 0.131607E+09 | 0.315435E+09 | 72111647.74 |
December | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 96360529.31 |
Annual Sum or Average | 0.386990E+10 | 0.178845E+10 | 0.208146E+10 | 0.544659E+10 | 0.650963E+09 |
Minimum of Months | 0.197830E+09 | 76665826.48 | 0.121164E+09 | 0.247591E+09 | 9015791.51 |
Maximum of Months | 0.423095E+09 | 0.214793E+09 | 0.214921E+09 | 0.640020E+09 | 0.108255E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196699E+10 | 0.924960E+09 | 0.104204E+10 | 0.275582E+10 | 0.119134E+10 |
February | 0.166803E+10 | 0.682292E+09 | 0.985740E+09 | 0.241949E+10 | 0.925607E+09 |
March | 0.151968E+10 | 0.412379E+09 | 0.110730E+10 | 0.231358E+10 | 0.812753E+09 |
April | 0.115593E+10 | 0.122253E+09 | 0.103368E+10 | 0.202696E+10 | 0.519406E+09 |
May | 0.101187E+10 | 15259018.28 | 0.996607E+09 | 0.243693E+10 | 0.184137E+09 |
June | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.249471E+10 | 77162196.48 |
July | 0.953013E+09 | 7966282.29 | 0.945047E+09 | 0.295524E+10 | 8727969.69 |
August | 0.110518E+10 | 77940244.08 | 0.102724E+10 | 0.316772E+10 | 5903920.35 |
September | 0.141035E+10 | 0.322963E+09 | 0.108739E+10 | 0.309870E+10 | 0.113496E+09 |
October | 0.190820E+10 | 0.758484E+09 | 0.114972E+10 | 0.358640E+10 | 0.325800E+09 |
November | 0.203772E+10 | 0.982466E+09 | 0.105526E+10 | 0.339918E+10 | 0.625790E+09 |
December | 0.195487E+10 | 0.965865E+09 | 0.989004E+09 | 0.292124E+10 | 0.102400E+10 |
Annual Sum or Average | 0.176142E+11 | 0.527393E+10 | 0.123403E+11 | 0.335760E+11 | 0.581412E+10 |
Minimum of Months | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.202696E+10 | 5903920.35 |
Maximum of Months | 0.203772E+10 | 0.982466E+09 | 0.114972E+10 | 0.358640E+10 | 0.119134E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196699E+10 | 0.924960E+09 | 0.104204E+10 | 0.275554E+10 | 0.114630E+10 |
February | 0.166803E+10 | 0.682292E+09 | 0.985740E+09 | 0.241710E+10 | 0.886173E+09 |
March | 0.151968E+10 | 0.412379E+09 | 0.110730E+10 | 0.230895E+10 | 0.768766E+09 |
April | 0.115593E+10 | 0.122253E+09 | 0.103368E+10 | 0.202029E+10 | 0.480947E+09 |
May | 0.101187E+10 | 15259018.28 | 0.996607E+09 | 0.243759E+10 | 0.158193E+09 |
June | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.250190E+10 | 60153841.17 |
July | 0.953013E+09 | 7966282.29 | 0.945047E+09 | 0.297303E+10 | 5589187.02 |
August | 0.110518E+10 | 77940244.08 | 0.102724E+10 | 0.318469E+10 | 3575483.39 |
September | 0.141035E+10 | 0.322963E+09 | 0.108739E+10 | 0.310040E+10 | 94674173.91 |
October | 0.190820E+10 | 0.758484E+09 | 0.114972E+10 | 0.357819E+10 | 0.292790E+09 |
November | 0.203772E+10 | 0.982466E+09 | 0.105526E+10 | 0.339229E+10 | 0.590275E+09 |
December | 0.195487E+10 | 0.965865E+09 | 0.989004E+09 | 0.291789E+10 | 0.982576E+09 |
Annual Sum or Average | 0.176142E+11 | 0.527393E+10 | 0.123403E+11 | 0.335879E+11 | 0.547002E+10 |
Minimum of Months | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.202029E+10 | 3575483.39 |
Maximum of Months | 0.203772E+10 | 0.982466E+09 | 0.114972E+10 | 0.357819E+10 | 0.114630E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.404738E+09 | 0.190324E+09 | 0.214414E+09 | 0.563343E+09 | 0.223889E+09 |
February | 0.343222E+09 | 0.140392E+09 | 0.202830E+09 | 0.482458E+09 | 0.177854E+09 |
March | 0.312697E+09 | 84853044.88 | 0.227844E+09 | 0.439884E+09 | 0.164094E+09 |
April | 0.237850E+09 | 25155270.67 | 0.212695E+09 | 0.345438E+09 | 0.117159E+09 |
May | 0.208206E+09 | 3139765.20 | 0.205066E+09 | 0.353067E+09 | 52704117.72 |
June | 0.189794E+09 | 227038.30 | 0.189567E+09 | 0.342229E+09 | 29801860.79 |
July | 0.196096E+09 | 1639178.58 | 0.194457E+09 | 0.392299E+09 | 7808431.78 |
August | 0.227407E+09 | 16037340.12 | 0.211369E+09 | 0.427363E+09 | 7893017.19 |
September | 0.290200E+09 | 66454397.07 | 0.223746E+09 | 0.472385E+09 | 43693860.39 |
October | 0.392641E+09 | 0.156069E+09 | 0.236572E+09 | 0.615156E+09 | 95661950.04 |
November | 0.419291E+09 | 0.202157E+09 | 0.217135E+09 | 0.631898E+09 | 0.149053E+09 |
December | 0.402243E+09 | 0.198741E+09 | 0.203502E+09 | 0.579846E+09 | 0.203060E+09 |
Annual Sum or Average | 0.362439E+10 | 0.108519E+10 | 0.253920E+10 | 0.564537E+10 | 0.127267E+10 |
Minimum of Months | 0.189794E+09 | 227038.30 | 0.189567E+09 | 0.342229E+09 | 7808431.78 |
Maximum of Months | 0.419291E+09 | 0.202157E+09 | 0.236572E+09 | 0.631898E+09 | 0.223889E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1549.61 | 646.69 | 1274.60 | 489.00 | 785.60 | 0.00 | 0.00 |
February | 1960.63 | 554.43 | 1550.62 | 637.19 | 913.43 | 0.00 | 0.00 |
March | 2448.65 | 477.85 | 1858.31 | 774.36 | 1083.95 | 0.00 | 0.00 |
April | 3053.35 | 374.20 | 2209.71 | 983.75 | 1225.96 | 0.00 | 0.00 |
May | 3618.46 | 198.15 | 2498.69 | 1214.81 | 1283.88 | 0.00 | 0.00 |
June | 3811.09 | 147.44 | 2606.07 | 1325.88 | 1280.19 | 0.00 | 0.00 |
July | 3823.30 | 61.37 | 2527.45 | 1282.66 | 1244.79 | 0.00 | 0.00 |
August | 3657.84 | 53.86 | 2404.56 | 1180.37 | 1224.20 | 0.00 | 0.00 |
September | 3185.93 | 159.23 | 2163.95 | 1040.25 | 1123.70 | 0.00 | 0.00 |
October | 2578.10 | 284.68 | 1815.19 | 851.34 | 963.85 | 0.00 | 0.00 |
November | 1947.13 | 445.13 | 1448.72 | 636.33 | 812.39 | 0.00 | 0.00 |
December | 1479.04 | 575.63 | 1181.78 | 457.98 | 723.80 | 0.00 | 0.00 |
Annual Sum or Average | 2763.36 | 330.27 | 1963.42 | 907.38 | 1056.04 | 0.00 | 0.00 |
Minimum of Months | 1479.04 | 53.86 | 1181.78 | 457.98 | 723.80 | 0.00 | 0.00 |
Maximum of Months | 3823.30 | 646.69 | 2606.07 | 1325.88 | 1283.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1028.90 | 444.79 | 734.39 | 345.34 | 389.05 | 0.00 | 0.00 |
February | 1000.12 | 382.61 | 689.50 | 282.03 | 407.47 | 0.00 | 0.00 |
March | 863.79 | 303.45 | 567.38 | 153.96 | 413.42 | 0.00 | 0.00 |
April | 782.01 | 200.39 | 445.96 | 47.17 | 398.80 | 0.00 | 0.00 |
May | 909.85 | 68.75 | 377.79 | 5.70 | 372.09 | 0.00 | 0.00 |
June | 962.47 | 29.77 | 355.86 | 0.43 | 355.43 | 0.00 | 0.00 |
July | 1103.36 | 3.26 | 355.81 | 2.97 | 352.84 | 0.00 | 0.00 |
August | 1182.69 | 2.20 | 412.63 | 29.10 | 383.53 | 0.00 | 0.00 |
September | 1195.49 | 43.79 | 544.12 | 124.60 | 419.52 | 0.00 | 0.00 |
October | 1339.01 | 121.64 | 712.44 | 283.19 | 429.26 | 0.00 | 0.00 |
November | 1311.41 | 241.43 | 786.16 | 379.04 | 407.12 | 0.00 | 0.00 |
December | 1090.67 | 382.32 | 729.86 | 360.61 | 369.25 | 0.00 | 0.00 |
Annual Sum or Average | 1064.69 | 184.36 | 558.54 | 167.24 | 391.31 | 0.00 | 0.00 |
Minimum of Months | 782.01 | 2.20 | 355.81 | 0.43 | 352.84 | 0.00 | 0.00 |
Maximum of Months | 1339.01 | 444.79 | 786.16 | 379.04 | 429.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1028.80 | 427.98 | 734.39 | 345.34 | 389.05 | 0.00 | 0.00 |
February | 999.13 | 366.31 | 689.50 | 282.03 | 407.47 | 0.00 | 0.00 |
March | 862.06 | 287.02 | 567.38 | 153.96 | 413.42 | 0.00 | 0.00 |
April | 779.43 | 185.55 | 445.96 | 47.17 | 398.80 | 0.00 | 0.00 |
May | 910.09 | 59.06 | 377.79 | 5.70 | 372.09 | 0.00 | 0.00 |
June | 965.24 | 23.21 | 355.86 | 0.43 | 355.43 | 0.00 | 0.00 |
July | 1110.00 | 2.09 | 355.81 | 2.97 | 352.84 | 0.00 | 0.00 |
August | 1189.03 | 1.33 | 412.63 | 29.10 | 383.53 | 0.00 | 0.00 |
September | 1196.14 | 36.53 | 544.12 | 124.60 | 419.52 | 0.00 | 0.00 |
October | 1335.94 | 109.32 | 712.44 | 283.19 | 429.26 | 0.00 | 0.00 |
November | 1308.75 | 227.73 | 786.16 | 379.04 | 407.12 | 0.00 | 0.00 |
December | 1089.41 | 366.85 | 729.86 | 360.61 | 369.25 | 0.00 | 0.00 |
Annual Sum or Average | 1065.06 | 173.45 | 558.54 | 167.24 | 391.31 | 0.00 | 0.00 |
Minimum of Months | 779.43 | 1.33 | 355.81 | 0.43 | 352.84 | 0.00 | 0.00 |
Maximum of Months | 1335.94 | 427.98 | 786.16 | 379.04 | 429.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.33 | 83.59 | 151.11 | 71.06 | 80.05 | 0.00 | 0.00 |
February | 199.43 | 73.52 | 141.87 | 58.03 | 83.84 | 0.00 | 0.00 |
March | 164.23 | 61.27 | 116.75 | 31.68 | 85.07 | 0.00 | 0.00 |
April | 133.27 | 45.20 | 91.76 | 9.70 | 82.06 | 0.00 | 0.00 |
May | 131.82 | 19.68 | 77.74 | 1.17 | 76.56 | 0.00 | 0.00 |
June | 132.03 | 11.50 | 73.22 | 0.09 | 73.14 | 0.00 | 0.00 |
July | 146.47 | 2.92 | 73.21 | 0.61 | 72.60 | 0.00 | 0.00 |
August | 159.56 | 2.95 | 84.90 | 5.99 | 78.92 | 0.00 | 0.00 |
September | 182.25 | 16.86 | 111.96 | 25.64 | 86.32 | 0.00 | 0.00 |
October | 229.67 | 35.72 | 146.60 | 58.27 | 88.33 | 0.00 | 0.00 |
November | 243.79 | 57.51 | 161.76 | 77.99 | 83.77 | 0.00 | 0.00 |
December | 216.49 | 75.81 | 150.18 | 74.20 | 75.98 | 0.00 | 0.00 |
Annual Sum or Average | 179.01 | 40.36 | 114.93 | 34.41 | 80.52 | 0.00 | 0.00 |
Minimum of Months | 131.82 | 2.92 | 73.21 | 0.09 | 72.60 | 0.00 | 0.00 |
Maximum of Months | 243.79 | 83.59 | 161.76 | 77.99 | 88.33 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.415048E+10 | 0.173209E+10 | 0.341389E+10 | 0.130975E+10 | 0.210414E+10 | 0.00 | 0.00 |
February | 0.474317E+10 | 0.134127E+10 | 0.375127E+10 | 0.154149E+10 | 0.220978E+10 | 0.00 | 0.00 |
March | 0.655847E+10 | 0.127986E+10 | 0.497730E+10 | 0.207405E+10 | 0.290325E+10 | 0.00 | 0.00 |
April | 0.791427E+10 | 0.969914E+09 | 0.572756E+10 | 0.254987E+10 | 0.317769E+10 | 0.00 | 0.00 |
May | 0.969168E+10 | 0.530737E+09 | 0.669249E+10 | 0.325375E+10 | 0.343874E+10 | 0.00 | 0.00 |
June | 0.987836E+10 | 0.382169E+09 | 0.675494E+10 | 0.343669E+10 | 0.331824E+10 | 0.00 | 0.00 |
July | 0.102403E+11 | 0.164364E+09 | 0.676951E+10 | 0.343547E+10 | 0.333405E+10 | 0.00 | 0.00 |
August | 0.979716E+10 | 0.144253E+09 | 0.644038E+10 | 0.316150E+10 | 0.327888E+10 | 0.00 | 0.00 |
September | 0.825792E+10 | 0.412716E+09 | 0.560896E+10 | 0.269632E+10 | 0.291264E+10 | 0.00 | 0.00 |
October | 0.690518E+10 | 0.762476E+09 | 0.486180E+10 | 0.228024E+10 | 0.258157E+10 | 0.00 | 0.00 |
November | 0.504696E+10 | 0.115379E+10 | 0.375508E+10 | 0.164936E+10 | 0.210572E+10 | 0.00 | 0.00 |
December | 0.396145E+10 | 0.154177E+10 | 0.316527E+10 | 0.122665E+10 | 0.193862E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.871454E+11 | 0.104154E+11 | 0.619184E+11 | 0.286151E+11 | 0.333033E+11 | 0.00 | 0.00 |
Minimum of Months | 0.396145E+10 | 0.144253E+09 | 0.316527E+10 | 0.122665E+10 | 0.193862E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102403E+11 | 0.173209E+10 | 0.676951E+10 | 0.343669E+10 | 0.343874E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.275582E+10 | 0.119134E+10 | 0.196699E+10 | 0.924960E+09 | 0.104204E+10 | 0.00 | 0.00 |
February | 0.241949E+10 | 0.925607E+09 | 0.166803E+10 | 0.682292E+09 | 0.985740E+09 | 0.00 | 0.00 |
March | 0.231358E+10 | 0.812753E+09 | 0.151968E+10 | 0.412379E+09 | 0.110730E+10 | 0.00 | 0.00 |
April | 0.202696E+10 | 0.519406E+09 | 0.115593E+10 | 0.122253E+09 | 0.103368E+10 | 0.00 | 0.00 |
May | 0.243693E+10 | 0.184137E+09 | 0.101187E+10 | 15259018.28 | 0.996607E+09 | 0.00 | 0.00 |
June | 0.249471E+10 | 77162196.48 | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.00 | 0.00 |
July | 0.295524E+10 | 8727969.69 | 0.953013E+09 | 7966282.29 | 0.945047E+09 | 0.00 | 0.00 |
August | 0.316772E+10 | 5903920.35 | 0.110518E+10 | 77940244.08 | 0.102724E+10 | 0.00 | 0.00 |
September | 0.309870E+10 | 0.113496E+09 | 0.141035E+10 | 0.322963E+09 | 0.108739E+10 | 0.00 | 0.00 |
October | 0.358640E+10 | 0.325800E+09 | 0.190820E+10 | 0.758484E+09 | 0.114972E+10 | 0.00 | 0.00 |
November | 0.339918E+10 | 0.625790E+09 | 0.203772E+10 | 0.982466E+09 | 0.105526E+10 | 0.00 | 0.00 |
December | 0.292124E+10 | 0.102400E+10 | 0.195487E+10 | 0.965865E+09 | 0.989004E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335760E+11 | 0.581412E+10 | 0.176142E+11 | 0.527393E+10 | 0.123403E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202696E+10 | 5903920.35 | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.00 | 0.00 |
Maximum of Months | 0.358640E+10 | 0.119134E+10 | 0.203772E+10 | 0.982466E+09 | 0.114972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.275554E+10 | 0.114630E+10 | 0.196699E+10 | 0.924960E+09 | 0.104204E+10 | 0.00 | 0.00 |
February | 0.241710E+10 | 0.886173E+09 | 0.166803E+10 | 0.682292E+09 | 0.985740E+09 | 0.00 | 0.00 |
March | 0.230895E+10 | 0.768766E+09 | 0.151968E+10 | 0.412379E+09 | 0.110730E+10 | 0.00 | 0.00 |
April | 0.202029E+10 | 0.480947E+09 | 0.115593E+10 | 0.122253E+09 | 0.103368E+10 | 0.00 | 0.00 |
May | 0.243759E+10 | 0.158193E+09 | 0.101187E+10 | 15259018.28 | 0.996607E+09 | 0.00 | 0.00 |
June | 0.250190E+10 | 60153841.17 | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.00 | 0.00 |
July | 0.297303E+10 | 5589187.02 | 0.953013E+09 | 7966282.29 | 0.945047E+09 | 0.00 | 0.00 |
August | 0.318469E+10 | 3575483.39 | 0.110518E+10 | 77940244.08 | 0.102724E+10 | 0.00 | 0.00 |
September | 0.310040E+10 | 94674173.91 | 0.141035E+10 | 0.322963E+09 | 0.108739E+10 | 0.00 | 0.00 |
October | 0.357819E+10 | 0.292790E+09 | 0.190820E+10 | 0.758484E+09 | 0.114972E+10 | 0.00 | 0.00 |
November | 0.339229E+10 | 0.590275E+09 | 0.203772E+10 | 0.982466E+09 | 0.105526E+10 | 0.00 | 0.00 |
December | 0.291789E+10 | 0.982576E+09 | 0.195487E+10 | 0.965865E+09 | 0.989004E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335879E+11 | 0.547002E+10 | 0.176142E+11 | 0.527393E+10 | 0.123403E+11 | 0.00 | 0.00 |
Minimum of Months | 0.202029E+10 | 3575483.39 | 0.922386E+09 | 1103388.75 | 0.921282E+09 | 0.00 | 0.00 |
Maximum of Months | 0.357819E+10 | 0.114630E+10 | 0.203772E+10 | 0.982466E+09 | 0.114972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.563343E+09 | 0.223889E+09 | 0.404738E+09 | 0.190324E+09 | 0.214414E+09 | 0.00 | 0.00 |
February | 0.482458E+09 | 0.177854E+09 | 0.343222E+09 | 0.140392E+09 | 0.202830E+09 | 0.00 | 0.00 |
March | 0.439884E+09 | 0.164094E+09 | 0.312697E+09 | 84853044.88 | 0.227844E+09 | 0.00 | 0.00 |
April | 0.345438E+09 | 0.117159E+09 | 0.237850E+09 | 25155270.67 | 0.212695E+09 | 0.00 | 0.00 |
May | 0.353067E+09 | 52704117.72 | 0.208206E+09 | 3139765.20 | 0.205066E+09 | 0.00 | 0.00 |
June | 0.342229E+09 | 29801860.79 | 0.189794E+09 | 227038.30 | 0.189567E+09 | 0.00 | 0.00 |
July | 0.392299E+09 | 7808431.78 | 0.196096E+09 | 1639178.58 | 0.194457E+09 | 0.00 | 0.00 |
August | 0.427363E+09 | 7893017.19 | 0.227407E+09 | 16037340.12 | 0.211369E+09 | 0.00 | 0.00 |
September | 0.472385E+09 | 43693860.39 | 0.290200E+09 | 66454397.07 | 0.223746E+09 | 0.00 | 0.00 |
October | 0.615156E+09 | 95661950.04 | 0.392641E+09 | 0.156069E+09 | 0.236572E+09 | 0.00 | 0.00 |
November | 0.631898E+09 | 0.149053E+09 | 0.419291E+09 | 0.202157E+09 | 0.217135E+09 | 0.00 | 0.00 |
December | 0.579846E+09 | 0.203060E+09 | 0.402243E+09 | 0.198741E+09 | 0.203502E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.564537E+10 | 0.127267E+10 | 0.362439E+10 | 0.108519E+10 | 0.253920E+10 | 0.00 | 0.00 |
Minimum of Months | 0.342229E+09 | 7808431.78 | 0.189794E+09 | 227038.30 | 0.189567E+09 | 0.00 | 0.00 |
Maximum of Months | 0.631898E+09 | 0.223889E+09 | 0.419291E+09 | 0.202157E+09 | 0.236572E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.73 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.25 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.73 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.16 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.89 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.77 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.47 | 23.16 | 3.85 | 24.13 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.01 | 24.10 | 3.89 | 24.32 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.67 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.65 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.61 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.83 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.01 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.73 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.01 | 24.10 | 3.95 | 24.32 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.53 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.25 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.80 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.14 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.72 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.53 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 21.97 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.35 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.39 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.78 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.12 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.02 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.53 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.35 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.44 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.73 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.73 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.04 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.94 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.23 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.43 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.81 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.81 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.94 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.20 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.04 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.10 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.85 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.13 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.23 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.13 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.20 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.10 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.85 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.09 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.85 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.200029E+10 | -.161534E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -384952342.5 | 58.99 | 0.00 | 0.00 |
February | 0.177582E+10 | -.142942E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -346406341.8 | 58.99 | 0.00 | 0.00 |
March | 0.188916E+10 | -.150827E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -380885902.6 | 58.99 | 0.00 | 0.00 |
April | 0.165360E+10 | -.128836E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -365239592.9 | 58.99 | 0.00 | 0.00 |
May | 0.155834E+10 | -.118621E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -372135096.1 | 58.99 | 0.00 | 0.00 |
June | 0.141775E+10 | -.105949E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -358251041.6 | 58.99 | 0.00 | 0.00 |
July | 0.139726E+10 | -.102962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -367631656.0 | 58.99 | 0.00 | 0.00 |
August | 0.147883E+10 | -.111116E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -367676035.3 | 58.99 | 0.00 | 0.00 |
September | 0.152726E+10 | -.116923E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -358024989.2 | 58.99 | 0.00 | 0.00 |
October | 0.171160E+10 | -.133894E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -372662004.1 | 58.99 | 0.00 | 0.00 |
November | 0.179338E+10 | -.142861E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -364775471.2 | 58.99 | 0.00 | 0.00 |
December | 0.196787E+10 | -.158582E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382053882.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.201712E+11 | -.157505E+11 | 8760.00 | -.442069E+10 | 58.99 | |||||
Minimum of Months | 0.139726E+10 | -.161534E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -384952342.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.200029E+10 | -.102962E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -346406341.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.74 | 0.50 | 01-JAN-11:50 | 398.01 | 9.40 | 0.00 | 118.00 | 327.17 | 7.88 | 0.00 | 56.50 |
February | 308.33 | 0.71 | 0.50 | 01-FEB-10:30 | 461.57 | 10.26 | 0.00 | 144.67 | 382.27 | 8.66 | 0.00 | 91.00 |
March | 357.50 | 0.68 | 0.50 | 01-MAR-10:09 | 2081.89 | 11.34 | 0.00 | 224.67 | 1838.05 | 9.69 | 0.00 | 133.50 |
April | 375.00 | 0.68 | 0.50 | 01-APR-09:30 | 530.14 | 12.07 | 0.00 | 205.50 | 444.22 | 10.43 | 0.00 | 147.00 |
May | 405.33 | 0.68 | 0.50 | 01-MAY-08:50 | 515.95 | 13.08 | 0.00 | 225.50 | 431.12 | 11.44 | 0.00 | 155.83 |
June | 403.50 | 0.68 | 0.50 | 01-JUN-08:00 | 519.62 | 13.62 | 0.00 | 229.83 | 430.58 | 11.90 | 0.00 | 161.17 |
July | 405.00 | 0.67 | 0.50 | 01-JUL-08:30 | 530.42 | 13.40 | 0.00 | 236.17 | 439.14 | 11.73 | 0.00 | 165.33 |
August | 395.83 | 0.67 | 0.50 | 01-AUG-08:00 | 557.02 | 12.85 | 0.00 | 233.50 | 463.16 | 11.20 | 0.00 | 170.17 |
September | 358.83 | 0.67 | 0.50 | 01-SEP-08:50 | 578.99 | 12.06 | 0.00 | 210.50 | 482.87 | 10.39 | 0.00 | 153.33 |
October | 351.17 | 0.69 | 0.50 | 01-OCT-08:00 | 514.90 | 10.70 | 0.00 | 185.50 | 428.99 | 9.14 | 0.00 | 129.83 |
November | 318.83 | 0.72 | 0.50 | 01-NOV-09:39 | 432.18 | 9.90 | 0.00 | 134.67 | 356.23 | 8.33 | 0.00 | 76.67 |
December | 319.00 | 0.76 | 0.50 | 01-DEC-11:09 | 379.31 | 9.24 | 0.00 | 97.00 | 310.67 | 7.71 | 0.00 | 32.00 |
Annual Sum or Average | 4323.33 | 0.69 | 628.27 | 11.63 | 0.00 | 2245.50 | 530.64 | 10.01 | 0.00 | 1472.33 | ||
Minimum of Months | 308.33 | 0.67 | 0.50 | 379.31 | 9.24 | 0.00 | 97.00 | 310.67 | 7.71 | 0.00 | 32.00 | |
Maximum of Months | 405.33 | 0.76 | 0.50 | 2081.89 | 13.62 | 0.00 | 236.17 | 1838.05 | 11.90 | 0.00 | 170.17 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 36953087.79 | 2088.67 | 18-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86406835.69 | 4302.23 | 20-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18878009.14 | 3960.70 | 05-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44079432.55 | 3583.30 | 15-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186317E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86406835.69 | 4302.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128303E+11 | 0.104095E+11 | 51851.16 | 30-JAN-07:02 | 36145.35 | 0.00 |
February | 0.00 | 0.00 | 0.142398E+11 | 0.113241E+11 | 52979.25 | 09-FEB-07:02 | 33578.13 | 0.00 |
March | 0.00 | 0.00 | 0.190450E+11 | 0.157522E+11 | 52926.53 | 29-MAR-06:02 | 33072.16 | 0.00 |
April | 0.00 | 0.00 | 0.244053E+11 | 0.198943E+11 | 53839.18 | 30-APR-07:01 | 31407.40 | 0.00 |
May | 0.00 | 0.00 | 0.352258E+11 | 0.286892E+11 | 56217.19 | 30-MAY-05:01 | 27245.39 | 0.00 |
June | 0.00 | 0.00 | 0.420411E+11 | 0.314483E+11 | 56307.37 | 08-JUN-05:02 | 26817.46 | 0.00 |
July | 0.00 | 0.00 | 0.490504E+11 | 0.354057E+11 | 55986.23 | 06-JUL-05:01 | 24394.99 | 0.00 |
August | 0.00 | 0.00 | 0.520074E+11 | 0.370589E+11 | 55986.23 | 31-AUG-05:01 | 29498.30 | 0.00 |
September | 0.00 | 0.00 | 0.433246E+11 | 0.309977E+11 | 56294.10 | 23-SEP-05:02 | 26060.58 | 0.00 |
October | 0.00 | 0.00 | 0.351819E+11 | 0.267454E+11 | 56277.28 | 01-OCT-07:01 | 25656.83 | 0.00 |
November | 0.00 | 0.00 | 0.252964E+11 | 0.197077E+11 | 54536.32 | 03-NOV-05:02 | 31108.48 | 0.00 |
December | 0.00 | 0.00 | 0.173922E+11 | 0.135892E+11 | 52754.15 | 11-DEC-07:02 | 34109.81 | 0.00 |
Annual Sum or Average | 0.370040E+12 | 0.281022E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.128303E+11 | 0.104095E+11 | 51851.16 | 24394.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.520074E+11 | 0.370589E+11 | 56307.37 | 36145.35 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.626517E+11 | 0.486066E+11 | 218623.75 | 30-JAN-07:02 | 146156.27 | 0.00 |
February | 0.00 | 0.00 | 0.699785E+11 | 0.532954E+11 | 222508.98 | 07-FEB-07:02 | 138478.27 | 0.00 |
March | 0.00 | 0.00 | 0.931086E+11 | 0.739308E+11 | 222738.33 | 29-MAR-06:02 | 135188.24 | 0.00 |
April | 0.00 | 0.00 | 0.118660E+12 | 0.926565E+11 | 227575.63 | 30-APR-08:62 | 127031.10 | 0.00 |
May | 0.00 | 0.00 | 0.164615E+12 | 0.128008E+12 | 230315.29 | 24-MAY-05:02 | 130928.00 | 0.00 |
June | 0.00 | 0.00 | 0.195783E+12 | 0.136662E+12 | 235206.01 | 19-JUN-05:01 | 122200.40 | 0.00 |
July | 0.00 | 0.00 | 0.228459E+12 | 0.152043E+12 | 236577.29 | 05-JUL-05:02 | 121001.72 | 0.00 |
August | 0.00 | 0.00 | 0.241451E+12 | 0.156894E+12 | 236635.85 | 09-AUG-05:02 | 121025.04 | 0.00 |
September | 0.00 | 0.00 | 0.202483E+12 | 0.132539E+12 | 237031.38 | 11-SEP-05:01 | 120139.65 | 0.00 |
October | 0.00 | 0.00 | 0.162042E+12 | 0.114677E+12 | 235888.31 | 08-OCT-07:01 | 116703.92 | 0.00 |
November | 0.00 | 0.00 | 0.118010E+12 | 0.860881E+11 | 227528.35 | 03-NOV-06:02 | 127995.59 | 0.00 |
December | 0.00 | 0.00 | 0.833152E+11 | 0.614409E+11 | 221980.86 | 06-DEC-07:02 | 131602.48 | 0.00 |
Annual Sum or Average | 0.174056E+13 | 0.123684E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.626517E+11 | 0.486066E+11 | 218623.75 | 116703.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.241451E+12 | 0.156894E+12 | 237031.38 | 146156.27 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.117071E+11 | 0.970075E+10 | 34073.52 | 30-JAN-07:02 | 23317.48 | 0.00 |
February | 0.00 | 0.00 | 0.119921E+11 | 0.971644E+10 | 34690.70 | 09-FEB-07:02 | 21801.92 | 0.00 |
March | 0.00 | 0.00 | 0.146513E+11 | 0.122075E+11 | 34756.93 | 29-MAR-06:02 | 21111.31 | 0.00 |
April | 0.00 | 0.00 | 0.171589E+11 | 0.139801E+11 | 35676.65 | 30-APR-07:01 | 19896.22 | 0.00 |
May | 0.00 | 0.00 | 0.232010E+11 | 0.187628E+11 | 37141.40 | 24-MAY-05:02 | 17545.55 | 0.00 |
June | 0.00 | 0.00 | 0.271232E+11 | 0.200215E+11 | 37160.41 | 25-JUN-07:02 | 17365.16 | 0.00 |
July | 0.00 | 0.00 | 0.317855E+11 | 0.226064E+11 | 36938.28 | 06-JUL-05:01 | 16567.26 | 0.00 |
August | 0.00 | 0.00 | 0.342105E+11 | 0.240382E+11 | 36953.57 | 31-AUG-04:03 | 19260.20 | 0.00 |
September | 0.00 | 0.00 | 0.295677E+11 | 0.210667E+11 | 37141.40 | 23-SEP-05:02 | 17057.56 | 0.00 |
October | 0.00 | 0.00 | 0.254528E+11 | 0.194860E+11 | 37130.55 | 07-OCT-05:01 | 18676.91 | 0.00 |
November | 0.00 | 0.00 | 0.197509E+11 | 0.155947E+11 | 36190.08 | 03-NOV-05:02 | 20608.66 | 0.00 |
December | 0.00 | 0.00 | 0.146715E+11 | 0.116936E+11 | 34657.99 | 11-DEC-07:02 | 21752.09 | 0.00 |
Annual Sum or Average | 0.261273E+12 | 0.198875E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.117071E+11 | 0.970075E+10 | 34073.52 | 16567.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.342105E+11 | 0.240382E+11 | 37160.41 | 23317.48 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.815167E+10 | 0.648398E+10 | 29210.24 | 30-JAN-07:02 | 19025.59 | 0.00 |
February | 0.00 | 0.00 | 0.867183E+10 | 0.676238E+10 | 29831.72 | 09-FEB-07:02 | 17874.44 | 0.00 |
March | 0.00 | 0.00 | 0.109444E+11 | 0.882673E+10 | 29932.59 | 29-MAR-06:02 | 17070.63 | 0.00 |
April | 0.00 | 0.00 | 0.136123E+11 | 0.107518E+11 | 30436.44 | 30-APR-08:62 | 16107.21 | 0.00 |
May | 0.00 | 0.00 | 0.195673E+11 | 0.153828E+11 | 31771.22 | 24-MAY-05:02 | 14154.98 | 0.00 |
June | 0.00 | 0.00 | 0.234249E+11 | 0.166678E+11 | 31787.48 | 25-JUN-07:02 | 13971.67 | 0.00 |
July | 0.00 | 0.00 | 0.280257E+11 | 0.191863E+11 | 31597.46 | 06-JUL-05:01 | 12619.17 | 0.00 |
August | 0.00 | 0.00 | 0.303112E+11 | 0.204885E+11 | 31597.46 | 31-AUG-05:01 | 15828.00 | 0.00 |
September | 0.00 | 0.00 | 0.258915E+11 | 0.177279E+11 | 31771.22 | 23-SEP-05:02 | 13786.69 | 0.00 |
October | 0.00 | 0.00 | 0.217822E+11 | 0.161055E+11 | 31779.26 | 07-OCT-05:01 | 14653.28 | 0.00 |
November | 0.00 | 0.00 | 0.162110E+11 | 0.123508E+11 | 30911.38 | 03-NOV-05:02 | 16639.48 | 0.00 |
December | 0.00 | 0.00 | 0.109929E+11 | 0.839892E+10 | 29780.43 | 11-DEC-07:02 | 17857.07 | 0.00 |
Annual Sum or Average | 0.217587E+12 | 0.159133E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.815167E+10 | 0.648398E+10 | 29210.24 | 12619.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.303112E+11 | 0.204885E+11 | 31787.48 | 19025.59 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150383E+09 | 0.06 | 871.79 | 01-JAN-08:07 | 0.91 |
February | 82705025.87 | 0.04 | 871.79 | 01-FEB-08:05 | 0.90 |
March | 41130933.61 | 0.02 | 871.79 | 03-MAR-08:08 | 0.90 |
April | 300766.68 | 0.00 | 871.79 | 01-APR-07:07 | 0.90 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 52307.25 | 0.00 | 871.79 | 22-NOV-08:10 | 0.90 |
December | 48756168.16 | 0.02 | 871.79 | 08-DEC-08:10 | 0.90 |
Annual Sum or Average | 0.323328E+09 | 0.01 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150383E+09 | 0.06 | 871.79 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.409184E+10 | 0.52 | 2554.21 | 18-JAN-14:30 | 0.87 |
February | 0.371484E+10 | 0.52 | 2554.21 | 01-FEB-07:20 | 0.87 |
March | 0.416540E+10 | 0.53 | 2554.21 | 17-MAR-19:30 | 0.87 |
April | 0.399989E+10 | 0.53 | 2554.21 | 01-APR-07:10 | 0.87 |
May | 0.412862E+10 | 0.52 | 2554.21 | 01-MAY-06:00 | 0.86 |
June | 0.402804E+10 | 0.53 | 2554.21 | 01-JUN-06:40 | 0.87 |
July | 0.411367E+10 | 0.53 | 2554.21 | 01-JUL-05:20 | 0.86 |
August | 0.418720E+10 | 0.54 | 2554.21 | 01-AUG-05:50 | 0.86 |
September | 0.400231E+10 | 0.53 | 2554.21 | 02-SEP-12:30 | 0.87 |
October | 0.409184E+10 | 0.52 | 2554.21 | 01-OCT-07:50 | 0.86 |
November | 0.394471E+10 | 0.52 | 2554.21 | 01-NOV-06:08 | 0.86 |
December | 0.410103E+10 | 0.52 | 2554.21 | 01-DEC-08:04 | 0.87 |
Annual Sum or Average | 0.485694E+11 | 0.53 | |||
Minimum of Months | 0.371484E+10 | 0.52 | 2554.21 | 0.86 | |
Maximum of Months | 0.418720E+10 | 0.54 | 2554.21 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.243653E+11 | 0.89 | 15209.27 | 27-JAN-20:40 | 1.49 |
February | 0.221204E+11 | 0.89 | 15209.27 | 01-FEB-08:05 | 1.49 |
March | 0.248033E+11 | 0.90 | 15209.27 | 12-MAR-08:13 | 1.48 |
April | 0.238177E+11 | 0.90 | 15209.27 | 01-APR-07:15 | 1.48 |
May | 0.245843E+11 | 0.89 | 15209.27 | 01-MAY-07:03 | 1.47 |
June | 0.239820E+11 | 0.90 | 15209.27 | 01-JUN-06:08 | 1.48 |
July | 0.244200E+11 | 0.88 | 15209.27 | 01-JUL-05:10 | 1.47 |
August | 0.248033E+11 | 0.90 | 15209.27 | 01-AUG-05:20 | 1.47 |
September | 0.238177E+11 | 0.89 | 15209.27 | 01-SEP-05:10 | 1.47 |
October | 0.243653E+11 | 0.89 | 15209.27 | 12-OCT-05:06 | 1.48 |
November | 0.234892E+11 | 0.88 | 15209.27 | 01-NOV-05:50 | 1.48 |
December | 0.244200E+11 | 0.89 | 15209.27 | 01-DEC-07:30 | 1.49 |
Annual Sum or Average | 0.288988E+12 | 0.89 | |||
Minimum of Months | 0.221204E+11 | 0.88 | 15209.27 | 1.47 | |
Maximum of Months | 0.248033E+11 | 0.90 | 15209.27 | 1.49 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.243028E+10 | 0.54 | 1517.03 | 08-JAN-13:50 | 0.90 |
February | 0.220636E+10 | 0.54 | 1517.03 | 01-FEB-11:10 | 0.90 |
March | 0.247397E+10 | 0.55 | 1517.03 | 08-MAR-14:30 | 0.90 |
April | 0.237566E+10 | 0.54 | 1517.03 | 12-APR-18:30 | 0.90 |
May | 0.245278E+10 | 0.54 | 1517.03 | 01-MAY-08:20 | 0.90 |
June | 0.239570E+10 | 0.55 | 1517.03 | 20-JUN-05:50 | 0.89 |
July | 0.245373E+10 | 0.55 | 1517.03 | 01-JUL-05:07 | 0.89 |
August | 0.250109E+10 | 0.57 | 1517.03 | 01-AUG-05:07 | 0.89 |
September | 0.238581E+10 | 0.55 | 1517.03 | 15-SEP-05:09 | 0.89 |
October | 0.243190E+10 | 0.54 | 1517.03 | 01-OCT-07:20 | 0.89 |
November | 0.234289E+10 | 0.54 | 1517.03 | 09-NOV-07:30 | 0.90 |
December | 0.243574E+10 | 0.54 | 1517.03 | 01-DEC-20:00 | 0.90 |
Annual Sum or Average | 0.288859E+11 | 0.55 | |||
Minimum of Months | 0.220636E+10 | 0.54 | 1517.03 | 0.89 | |
Maximum of Months | 0.250109E+10 | 0.57 | 1517.03 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.200173E+10 | 0.54 | 1249.52 | 01-JAN-17:40 | 0.90 |
February | 0.181730E+10 | 0.54 | 1249.52 | 01-FEB-20:20 | 0.90 |
March | 0.203771E+10 | 0.55 | 1249.52 | 03-MAR-08:00 | 0.90 |
April | 0.195674E+10 | 0.54 | 1249.52 | 01-APR-06:30 | 0.90 |
May | 0.201972E+10 | 0.54 | 1249.52 | 05-MAY-05:10 | 0.90 |
June | 0.197092E+10 | 0.55 | 1249.52 | 01-JUN-05:20 | 0.90 |
July | 0.201429E+10 | 0.55 | 1249.52 | 06-JUL-06:08 | 0.89 |
August | 0.205231E+10 | 0.56 | 1249.52 | 02-AUG-11:20 | 0.90 |
September | 0.196031E+10 | 0.55 | 1249.52 | 01-SEP-05:07 | 0.89 |
October | 0.200173E+10 | 0.54 | 1249.52 | 03-OCT-06:04 | 0.90 |
November | 0.192975E+10 | 0.54 | 1249.52 | 01-NOV-05:20 | 0.89 |
December | 0.200623E+10 | 0.54 | 1249.52 | 02-DEC-07:50 | 0.90 |
Annual Sum or Average | 0.237687E+11 | 0.54 | |||
Minimum of Months | 0.181730E+10 | 0.54 | 1249.52 | 0.89 | |
Maximum of Months | 0.205231E+10 | 0.56 | 1249.52 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 6.13 |
February | 0.00 | 0.00 |
March | 0.25 | 4.09 |
April | 0.38 | 0.00 |
May | 1.24 | 0.00 |
June | 2.24 | 0.00 |
July | 0.74 | 0.46 |
August | 1.45 | 0.47 |
September | 0.94 | 0.00 |
October | 0.37 | 0.00 |
November | 0.07 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.84 | 0.39 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.24 | 6.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 25.84 |
February | 0.08 | 25.84 |
March | 0.33 | 19.38 |
April | 0.21 | 0.00 |
May | 0.41 | 0.00 |
June | 0.43 | 0.00 |
July | 0.17 | 0.00 |
August | 0.31 | 0.00 |
September | 0.28 | 0.00 |
October | 0.13 | 0.00 |
November | 0.03 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.47 | 4.35 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.43 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.97 | 0.00 |
February | 1.01 | 0.40 |
March | 1.15 | 0.00 |
April | 1.51 | 0.00 |
May | 1.85 | 0.00 |
June | 2.48 | 0.00 |
July | 1.19 | 0.00 |
August | 1.50 | 0.00 |
September | 1.65 | 0.00 |
October | 1.39 | 0.00 |
November | 1.82 | 0.00 |
December | 0.96 | 0.00 |
Annual Sum or Average | 17.49 | 0.02 |
Minimum of Months | 0.96 | 0.00 |
Maximum of Months | 2.48 | 0.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.12 | 0.00 |
March | 0.79 | 1.28 |
April | 1.29 | 0.94 |
May | 1.41 | 0.00 |
June | 2.24 | 0.00 |
July | 0.67 | 0.00 |
August | 1.49 | 0.00 |
September | 1.19 | 0.00 |
October | 1.20 | 0.00 |
November | 0.76 | 0.00 |
December | 0.29 | 1.39 |
Annual Sum or Average | 11.46 | 0.23 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.24 | 1.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 7.58 | 0.00 |
February | 6.19 | 0.00 |
March | 4.26 | 0.00 |
April | 3.64 | 0.00 |
May | 1.87 | 0.00 |
June | 2.17 | 0.00 |
July | 2.74 | 0.00 |
August | 3.34 | 0.00 |
September | 2.33 | 0.00 |
October | 3.69 | 0.00 |
November | 2.36 | 0.00 |
December | 6.28 | 0.00 |
Annual Sum or Average | 46.46 | 0.00 |
Minimum of Months | 1.87 | 0.00 |
Maximum of Months | 7.58 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.761534E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.766711E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.959241E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111909E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.149729E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.167688E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.190458E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.199224E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.168139E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.143724E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111369E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.889500E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.157994E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.761534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.199224E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.430597E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.431823E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.535126E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.614176E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.787983E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.868478E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.974421E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.101287E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.869841E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.750120E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.596407E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.493109E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.836495E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.430597E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.101287E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.552777E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.542625E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.653680E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.733273E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.950410E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.105295E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.120225E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.127142E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.109753E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.969410E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.778683E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.634191E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104392E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.542625E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.127142E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.418315E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.417215E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.510576E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.591178E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.795302E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.893745E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.103352E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.109655E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.939755E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.818570E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.640599E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.495838E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.865116E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.417215E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.109655E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.409184E+10 | 0.128303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371484E+10 | 0.142398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416540E+10 | 0.190450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399989E+10 | 0.244053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.412862E+10 | 0.352258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402804E+10 | 0.420411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.411367E+10 | 0.490504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418720E+10 | 0.520074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400231E+10 | 0.433246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.409184E+10 | 0.351819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394471E+10 | 0.252964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410103E+10 | 0.173922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485694E+11 | 0.370040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371484E+10 | 0.128303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418720E+10 | 0.520074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.243653E+11 | 0.626517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221204E+11 | 0.699785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248033E+11 | 0.931086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.238177E+11 | 0.118660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245843E+11 | 0.164615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239820E+11 | 0.195783E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.244200E+11 | 0.228459E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.248033E+11 | 0.241451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238177E+11 | 0.202483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243653E+11 | 0.162042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234892E+11 | 0.118010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244200E+11 | 0.833152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288988E+12 | 0.174056E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.221204E+11 | 0.626517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.248033E+11 | 0.241451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.243028E+10 | 0.117071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220636E+10 | 0.119921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247397E+10 | 0.146513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237566E+10 | 0.171589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245278E+10 | 0.232010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239570E+10 | 0.271232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245373E+10 | 0.317855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250109E+10 | 0.342105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238581E+10 | 0.295677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243190E+10 | 0.254528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234289E+10 | 0.197509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243574E+10 | 0.146715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288859E+11 | 0.261273E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.220636E+10 | 0.117071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250109E+10 | 0.342105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.200173E+10 | 0.815167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181730E+10 | 0.867183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203771E+10 | 0.109444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195674E+10 | 0.136123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201972E+10 | 0.195673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197092E+10 | 0.234249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201429E+10 | 0.280257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205231E+10 | 0.303112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196031E+10 | 0.258915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200173E+10 | 0.217822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192975E+10 | 0.162110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200623E+10 | 0.109929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237687E+11 | 0.217587E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.181730E+10 | 0.815167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205231E+10 | 0.303112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.409184E+10 | 0.00 | 0.00 | 0.00 | 0.352350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371484E+10 | 0.00 | 0.00 | 0.00 | 0.395228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416540E+10 | 0.00 | 0.00 | 0.00 | 0.542701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399989E+10 | 0.00 | 0.00 | 0.00 | 0.719097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.412862E+10 | 0.00 | 0.00 | 0.00 | 0.108443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402804E+10 | 0.00 | 0.00 | 0.00 | 0.127408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.411367E+10 | 0.00 | 0.00 | 0.00 | 0.149321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.418720E+10 | 0.00 | 0.00 | 0.00 | 0.157352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400231E+10 | 0.00 | 0.00 | 0.00 | 0.128116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.409184E+10 | 0.00 | 0.00 | 0.00 | 0.102805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394471E+10 | 0.00 | 0.00 | 0.00 | 0.719216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410103E+10 | 0.00 | 0.00 | 0.00 | 0.479396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.485694E+11 | 0.00 | 0.00 | 0.00 | 0.109424E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.371484E+10 | 0.00 | 0.00 | 0.00 | 0.352350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.418720E+10 | 0.00 | 0.00 | 0.00 | 0.157352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.243653E+11 | 0.00 | 0.00 | 0.00 | 0.186945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221204E+11 | 0.00 | 0.00 | 0.00 | 0.210620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248033E+11 | 0.00 | 0.00 | 0.00 | 0.287093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.238177E+11 | 0.00 | 0.00 | 0.00 | 0.375998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245843E+11 | 0.00 | 0.00 | 0.00 | 0.542140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239820E+11 | 0.00 | 0.00 | 0.00 | 0.628658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.244200E+11 | 0.00 | 0.00 | 0.00 | 0.730220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.248033E+11 | 0.00 | 0.00 | 0.00 | 0.764836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238177E+11 | 0.00 | 0.00 | 0.00 | 0.631664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243653E+11 | 0.00 | 0.00 | 0.00 | 0.506468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234892E+11 | 0.00 | 0.00 | 0.00 | 0.361515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244200E+11 | 0.00 | 0.00 | 0.00 | 0.248909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288988E+12 | 0.00 | 0.00 | 0.00 | 0.547507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.221204E+11 | 0.00 | 0.00 | 0.00 | 0.186945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.248033E+11 | 0.00 | 0.00 | 0.00 | 0.764836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.243028E+10 | 0.00 | 0.00 | 0.00 | 0.309749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220636E+10 | 0.00 | 0.00 | 0.00 | 0.321988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247397E+10 | 0.00 | 0.00 | 0.00 | 0.406284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237566E+10 | 0.00 | 0.00 | 0.00 | 0.495707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245278E+10 | 0.00 | 0.00 | 0.00 | 0.705132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.239570E+10 | 0.00 | 0.00 | 0.00 | 0.813384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.245373E+10 | 0.00 | 0.00 | 0.00 | 0.956879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.250109E+10 | 0.00 | 0.00 | 0.00 | 0.102131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238581E+10 | 0.00 | 0.00 | 0.00 | 0.858950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243190E+10 | 0.00 | 0.00 | 0.00 | 0.726220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234289E+10 | 0.00 | 0.00 | 0.00 | 0.544394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243574E+10 | 0.00 | 0.00 | 0.00 | 0.390617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288859E+11 | 0.00 | 0.00 | 0.00 | 0.755061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.220636E+10 | 0.00 | 0.00 | 0.00 | 0.309749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.250109E+10 | 0.00 | 0.00 | 0.00 | 0.102131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.200173E+10 | 0.00 | 0.00 | 0.00 | 0.218143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181730E+10 | 0.00 | 0.00 | 0.00 | 0.235485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203771E+10 | 0.00 | 0.00 | 0.00 | 0.306804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195674E+10 | 0.00 | 0.00 | 0.00 | 0.395503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201972E+10 | 0.00 | 0.00 | 0.00 | 0.593330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.197092E+10 | 0.00 | 0.00 | 0.00 | 0.696653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201429E+10 | 0.00 | 0.00 | 0.00 | 0.832088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205231E+10 | 0.00 | 0.00 | 0.00 | 0.891314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196031E+10 | 0.00 | 0.00 | 0.00 | 0.743725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200173E+10 | 0.00 | 0.00 | 0.00 | 0.618398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192975E+10 | 0.00 | 0.00 | 0.00 | 0.447623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200623E+10 | 0.00 | 0.00 | 0.00 | 0.295215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237687E+11 | 0.00 | 0.00 | 0.00 | 0.627428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.181730E+10 | 0.00 | 0.00 | 0.00 | 0.218143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205231E+10 | 0.00 | 0.00 | 0.00 | 0.891314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458926E+09 | 0.385453E+09 | 0.00 | 9636051.08 | 2630909.36 | 0.00 | 0.116712E+10 | 0.00 | 0.22 |
February | 0.295907E+09 | 0.854799E+09 | 0.00 | 7349833.72 | 573389.58 | 0.00 | 0.589004E+09 | 0.00 | 0.22 |
March | 0.237384E+09 | 0.171086E+10 | 0.00 | 6802450.33 | 1623474.79 | 0.00 | 0.395346E+09 | 0.00 | 0.23 |
April | 0.123760E+09 | 0.395832E+10 | 0.00 | 4514469.40 | 11154787.40 | 0.00 | 0.157208E+09 | 0.00 | 0.22 |
May | 8671592.73 | 0.741596E+10 | 0.00 | 2353053.01 | 21511507.71 | 0.00 | 38819651.84 | 0.00 | 0.22 |
June | 2220844.66 | 0.110071E+11 | 0.00 | 1191639.75 | 24195667.21 | 0.00 | 9145143.60 | 0.00 | 0.23 |
July | 721920.86 | 0.142447E+11 | 0.00 | 960984.57 | 15573090.92 | 0.00 | 4907952.89 | 0.00 | 0.23 |
August | 0.00 | 0.155424E+11 | 0.00 | 72934.99 | 16550815.55 | 0.00 | 11779.71 | 0.00 | 0.23 |
September | 1163773.63 | 0.122189E+11 | 0.00 | 891297.39 | 24410080.49 | 0.00 | 4054710.92 | 0.00 | 0.23 |
October | 5435670.76 | 0.796503E+10 | 0.00 | 1640744.14 | 40157277.88 | 0.00 | 31975300.61 | 0.00 | 0.22 |
November | 43865635.68 | 0.431100E+10 | 0.00 | 2221499.43 | 10210939.81 | 0.00 | 52797282.53 | 0.00 | 0.22 |
December | 0.263440E+09 | 0.149867E+10 | 0.00 | 7919482.54 | 3084925.26 | 0.00 | 0.484877E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.144150E+10 | 0.811132E+11 | 0.00 | 45554440.36 | 0.171677E+09 | 0.00 | 0.293526E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.385453E+09 | 0.00 | 72934.99 | 573389.58 | 0.00 | 11779.71 | 0.00 | 0.22 |
Maximum of Months | 0.458926E+09 | 0.155424E+11 | 0.00 | 9636051.08 | 40157277.88 | 0.00 | 0.116712E+10 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.383274E+10 | 0.380596E+10 | 0.00 | 39357063.19 | 43490708.13 | 0.00 | 0.717056E+10 | 0.00 | 0.43 |
February | 0.215590E+10 | 0.806688E+10 | 0.00 | 28226161.90 | 28336607.83 | 0.00 | 0.364161E+10 | 0.00 | 0.43 |
March | 0.170946E+10 | 0.156081E+11 | 0.00 | 22981268.57 | 51763078.01 | 0.00 | 0.228865E+10 | 0.00 | 0.44 |
April | 0.784056E+09 | 0.339423E+11 | 0.00 | 12837493.04 | 0.173893E+09 | 0.00 | 0.862619E+09 | 0.00 | 0.43 |
May | 28747591.31 | 0.611741E+11 | 0.00 | 4794183.63 | 0.411205E+09 | 0.00 | 0.127853E+09 | 0.00 | 0.43 |
June | 7024043.46 | 0.881920E+11 | 0.00 | 1451968.52 | 0.579303E+09 | 0.00 | 17175977.48 | 0.00 | 0.44 |
July | 3398788.20 | 0.112938E+12 | 0.00 | 1704203.96 | 0.584950E+09 | 0.00 | 18508235.42 | 0.00 | 0.44 |
August | 0.00 | 0.122200E+12 | 0.00 | 0.00 | 0.610742E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 4728857.50 | 0.965981E+11 | 0.00 | 837594.65 | 0.549438E+09 | 0.00 | 15424167.75 | 0.00 | 0.44 |
October | 30027015.44 | 0.637011E+11 | 0.00 | 3809645.91 | 0.774158E+09 | 0.00 | 0.133680E+09 | 0.00 | 0.43 |
November | 0.252340E+09 | 0.350298E+11 | 0.00 | 6288049.35 | 0.268236E+09 | 0.00 | 0.251338E+09 | 0.00 | 0.43 |
December | 0.207654E+10 | 0.126243E+11 | 0.00 | 28464033.04 | 55061609.53 | 0.00 | 0.282062E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.108850E+11 | 0.653880E+12 | 0.00 | 0.150752E+09 | 0.413058E+10 | 0.00 | 0.173480E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.380596E+10 | 0.00 | 0.00 | 28336607.83 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.383274E+10 | 0.122200E+12 | 0.00 | 39357063.19 | 0.774158E+09 | 0.00 | 0.717056E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250571E+09 | 0.707634E+09 | 0.00 | 6923298.63 | 7259.57 | 0.00 | 0.587537E+09 | 0.00 | 0.43 |
February | 0.180895E+09 | 0.115293E+10 | 0.00 | 3631054.79 | 110616.29 | 0.00 | 0.265683E+09 | 0.00 | 0.43 |
March | 0.132323E+09 | 0.187973E+10 | 0.00 | 2964233.89 | 138616.77 | 0.00 | 0.202099E+09 | 0.00 | 0.44 |
April | 37753461.97 | 0.363318E+10 | 0.00 | 1806653.93 | 3901314.79 | 0.00 | 0.128919E+09 | 0.00 | 0.43 |
May | 4554757.13 | 0.627386E+10 | 0.00 | 1009395.53 | 18075164.42 | 0.00 | 19451006.50 | 0.00 | 0.43 |
June | 1519065.10 | 0.897098E+10 | 0.00 | 542256.55 | 24937376.67 | 0.00 | 4166379.46 | 0.00 | 0.44 |
July | 165217.90 | 0.114995E+11 | 0.00 | 384865.83 | 16862008.54 | 0.00 | 2833325.03 | 0.00 | 0.44 |
August | 0.00 | 0.125548E+11 | 0.00 | 59337.32 | 11274007.61 | 0.00 | 39350.45 | 0.00 | 0.45 |
September | 351499.69 | 0.100473E+11 | 0.00 | 401977.05 | 16761324.49 | 0.00 | 1355058.00 | 0.00 | 0.44 |
October | 2548410.67 | 0.686311E+10 | 0.00 | 710978.86 | 29628023.47 | 0.00 | 12042763.14 | 0.00 | 0.43 |
November | 8821858.09 | 0.409123E+10 | 0.00 | 1265109.56 | 5967640.90 | 0.00 | 42635843.80 | 0.00 | 0.43 |
December | 0.141312E+09 | 0.179292E+10 | 0.00 | 3720979.40 | 70605.96 | 0.00 | 0.228272E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.760815E+09 | 0.694672E+11 | 0.00 | 23420141.35 | 0.127734E+09 | 0.00 | 0.149503E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.707634E+09 | 0.00 | 59337.32 | 7259.57 | 0.00 | 39350.45 | 0.00 | 0.43 |
Maximum of Months | 0.250571E+09 | 0.125548E+11 | 0.00 | 6923298.63 | 29628023.47 | 0.00 | 0.587537E+09 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.397602E+09 | 0.541082E+09 | 0.00 | 4796852.81 | 353361.34 | 0.00 | 0.536386E+09 | 0.00 | 0.43 |
February | 0.245936E+09 | 0.951773E+09 | 0.00 | 2826339.07 | 110793.64 | 0.00 | 0.285036E+09 | 0.00 | 0.43 |
March | 0.182158E+09 | 0.166913E+10 | 0.00 | 2257803.41 | 1169884.35 | 0.00 | 0.206809E+09 | 0.00 | 0.44 |
April | 99174577.30 | 0.339741E+10 | 0.00 | 1367701.27 | 4814543.06 | 0.00 | 93959689.57 | 0.00 | 0.43 |
May | 6189619.76 | 0.607144E+10 | 0.00 | 819803.95 | 20505450.54 | 0.00 | 23845557.67 | 0.00 | 0.43 |
June | 2093062.11 | 0.870038E+10 | 0.00 | 464310.54 | 25477090.77 | 0.00 | 4980047.95 | 0.00 | 0.44 |
July | 573982.64 | 0.112211E+11 | 0.00 | 382337.20 | 15267096.75 | 0.00 | 2817920.57 | 0.00 | 0.44 |
August | 0.00 | 0.122706E+11 | 0.00 | 36905.52 | 10024674.11 | 0.00 | 45936.54 | 0.00 | 0.45 |
September | 642440.61 | 0.976431E+10 | 0.00 | 353285.12 | 21404975.05 | 0.00 | 2139527.59 | 0.00 | 0.44 |
October | 3112727.70 | 0.662917E+10 | 0.00 | 616378.32 | 32875921.08 | 0.00 | 14021017.88 | 0.00 | 0.43 |
November | 28282821.73 | 0.385706E+10 | 0.00 | 1034187.63 | 6307699.09 | 0.00 | 36223548.46 | 0.00 | 0.43 |
December | 0.192509E+09 | 0.153867E+10 | 0.00 | 3022255.61 | 671804.98 | 0.00 | 0.239958E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.115827E+10 | 0.666121E+11 | 0.00 | 17978160.46 | 0.138983E+09 | 0.00 | 0.144622E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.541082E+09 | 0.00 | 36905.52 | 110793.64 | 0.00 | 45936.54 | 0.00 | 0.43 |
Maximum of Months | 0.397602E+09 | 0.122706E+11 | 0.00 | 4796852.81 | 32875921.08 | 0.00 | 0.536386E+09 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |