Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:11:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1036.98 | 452.04 | 452.04 |
Net Site Energy | 1036.98 | 452.04 | 452.04 |
Total Source Energy | 2588.81 | 1128.52 | 1128.52 |
Net Source Energy | 2588.81 | 1128.52 | 1128.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 239.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 270.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 94.76 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 703.18 | 333.81 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 239.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 43.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 270.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 150.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 94.76 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 136.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 84.75 | 145.51 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 306.53 | 145.51 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 136.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 84.75 | 145.51 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 306.53 | 145.51 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 703.178 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 703.178 | 100.00 |
Total On-Site and Utility Electric Sources | 703.178 | 100.00 |
Total Electricity End Uses | 703.178 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1058.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 5.1793 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.8188 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:50 | 19-FEB-09:09 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 156727.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28155.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 20461.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8604.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4551.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 67992.05 | 161278.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 156727.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28155.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 20461.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8604.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4551.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 259.12 | 0.00 | 0.00 | 0.00 |
Cooling | 139.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 857.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 135.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 476.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 102.72 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2226.96 | 361.85 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 112.96 | 0.00 | 0.00 | 0.00 |
Cooling | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 373.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.78 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 970.78 | 157.74 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 112.96 | 0.00 | 0.00 | 0.00 |
Cooling | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 373.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.78 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 970.78 | 157.74 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.50 |
CORE_RETAIL DIRECT AIR | 6.51 |
POINT_OF_SALE DIRECT AIR | 1.13 |
FRONT_RETAIL DIRECT AIR | 0.892935 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.02 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.02 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 29778.96 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 41114.33 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 205704.52 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 30947.42 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 25653.28 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.50 | 1.50 | 1.50 | 1.50 | 1.56 | 1.56 | 1.00 | 0.959786 | 1.56 |
PSZ-AC:2 | 6.51 | 6.51 | 6.51 | 6.51 | 6.75 | 6.75 | 1.00 | 0.963884 | 6.75 |
PSZ-AC:3 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.13 | 1.00 | 1.00 | 1.13 |
PSZ-AC:4 | 0.892935 | 0.892935 | 0.892935 | 0.892935 | 0.892935 | 0.892935 | 1.00 | 1.00 | 0.892935 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.56 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 6.75 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.13 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.892935 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.56 | 1.56 | 1.56 | 1.03 | 27650.46 | 41114.33 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 6.75 | 6.75 | 6.75 | 4.46 | 123579.28 | 205704.52 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.13 | 1.13 | 1.13 | 1.13 | 18960.69 | 30947.42 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.892935 | 0.892935 | 0.892935 | 0.892935 | 15429.35 | 25653.28 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.56 | 0.780715 | 1.04 | 25847.21 | 27650.46 | 13825.23 | 13825.23 | 0.774678 | 0.774680 | 0.774680 | 0.774680 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 6.75 | 3.38 | 4.50 | 114943.17 | 123579.28 | 61789.64 | 61789.64 | 0.763555 | 0.763550 | 0.763550 | 0.763550 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.13 | 0.562815 | 0.750420 | 18633.17 | 18960.69 | 9480.34 | 9480.34 | 0.792305 | 0.792300 | 0.792300 | 0.792300 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.892930 | 0.446465 | 0.595287 | 14781.16 | 15429.35 | 7714.68 | 7714.68 | 0.783210 | 0.783210 | 0.783210 | 0.783210 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.56 | 1670.81 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 6.75 | 11376.36 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.13 | 1246.25 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.892935 | 988.62 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 5.179 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.249 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 33.339 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 1967.547 | 5.179 | 32.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1967.547 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 18915.745 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18915.745 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1725 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3437E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3274 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.721 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 29.02 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.978 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
25 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
26 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
27 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
28 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
29 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
30 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
31 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
32 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
33 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
34 | 7 | -0.24541788E-08 | -0.10674912E-14 | 0.56595312E-14 | -0.88347803E-16 |
35 | 6 | 0.48874313E-05 | 0.32994277E-08 | 0.31919810E-02 | -0.26777012E-04 |
36 | 5 | -0.34768456E-03 | 0.19525666E-05 | -0.22384457 | 0.19572094E-02 |
37 | 4 | 0.79733842E-02 | 0.88847046E-04 | 4.8315443 | -0.45284193E-01 |
38 | 3 | -0.69943606E-01 | 0.70626596E-03 | -38.032707 | 0.39877855 |
39 | 2 | 0.24825401 | 0.11745943E-02 | 116.50592 | -1.4182332 |
40 | 1 | -0.35825340 | 0.35768630E-03 | -143.92024 | 2.0492525 |
41 | 0 | 0.17465044 | 0.86763216E-05 | 60.838472 | |
42 | 7 | -0.12489162E-07 | 0.28466235E-14 | -0.17145271E-13 | 0.26119495E-15 |
43 | 6 | 0.18517441E-05 | 0.69460444E-09 | 0.32027219E-02 | -0.26867115E-04 |
44 | 5 | -0.89695516E-04 | 0.39969105E-06 | -0.22445454 | 0.19625936E-02 |
45 | 4 | 0.17714562E-02 | 0.17921615E-04 | 4.8416944 | -0.45381772E-01 |
46 | 3 | -0.14613545E-01 | 0.14074818E-03 | -38.089997 | 0.39941188 |
47 | 2 | 0.50542763E-01 | 0.23137019E-03 | 116.61736 | -1.4197240 |
48 | 1 | -0.72070041E-01 | 0.69440628E-04 | -143.98582 | 2.0503304 |
49 | 0 | 0.34918756E-01 | 0.16519960E-05 | 60.838472 | |
50 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
51 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
52 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
53 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
54 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
55 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
56 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
57 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
58 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
59 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
60 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
61 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
62 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
63 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
64 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
65 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
66 | 7 | -0.12723796E-08 | -0.15085021E-15 | 0.80954726E-14 | -0.10933793E-15 |
67 | 6 | 0.91456241E-05 | 0.63025983E-08 | 0.31797574E-02 | -0.26674470E-04 |
68 | 5 | -0.66211654E-03 | 0.37378006E-05 | -0.22314974 | 0.19510765E-02 |
69 | 4 | 0.15256371E-01 | 0.17022008E-03 | 4.8199703 | -0.45172938E-01 |
70 | 3 | -0.13404479 | 0.13543778E-02 | -37.967318 | 0.39805580 |
71 | 2 | 0.47605416 | 0.22539081E-02 | 116.37865 | -1.4165309 |
72 | 1 | -0.68716389 | 0.68732095E-03 | -143.84532 | 2.0480210 |
73 | 0 | 0.33503722 | 0.16534103E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.36 | 30 | 1 | VerySmooth | 2.159 | 0.355 | 0.274 | 0.361 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 31 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1928 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 17594.18976 | 21113.02771 | 1.24887 | 1.49864 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 21306.65091 | 25567.98109 | 0.90915 | 1.09098 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 76311.25293 | 91573.50352 | 5.42401 | 6.50881 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 55062.15101 | 66074.58121 | 2.31715 | 2.78058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12600.69314 | 15120.83177 | 0.93802 | 1.12563 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10176.38518 | 12211.66222 | 0.43594 | 0.52313 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 9995.78678 | 11994.94414 | 0.74411 | 0.89293 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10171.72258 | 12206.06709 | 0.43574 | 0.52288 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 24810.46039 | 29772.55247 | 0.85147 | 1.02176 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:10:00 | -4.20000 | 2.69032E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 20224.10 | 1.56143 | 1.56143 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 31814.18 | 1.09098 | 1.09098 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 95615.08 | 6.75270 | 6.75270 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 120096.46 | 2.78058 | 2.78058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 15994.61 | 1.12563 | 1.12563 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 17239.63 | 0.52313 | 0.52313 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 12925.19 | 0.89293 | 0.89293 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 17234.07 | 0.52288 | 0.52288 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49864 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.50881 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12563 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.89293 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.02176 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.02176 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 29778.96232 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49864 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49864 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49864 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49864 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.56143 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.56143 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.95979 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.50881 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.50881 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.50881 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.50881 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.75270 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 6.75270 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96388 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12563 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12563 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12563 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12563 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.12563 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.12563 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.89293 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.89293 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.89293 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.89293 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.89293 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.89293 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.56143 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 6.75270 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.12563 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.89293 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.56143 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.56143 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.56143 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.56143 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.03054 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.56143 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.78072 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.04095 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 25847.21073 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27650.46000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13825.23000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13825.23000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77468 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77468 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77468 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77468 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27650.46000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41114.32893 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.56143 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1670.80528 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 41114.32893 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.75270 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.75270 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.75270 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.75270 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.45678 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.75270 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.37635 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.50180 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 114943.17438 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 123579.28000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 61789.64000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 61789.64000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76356 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76355 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76355 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76355 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 123579.28000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 205704.52005 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.75270 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11376.36480 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 205704.52005 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.12563 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.12563 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.12563 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.12563 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12563 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.12563 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.56282 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.75042 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18633.17332 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18960.69000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9480.34500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9480.34500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79230 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79230 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79230 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79230 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18960.69000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30947.42079 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.12563 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1246.24862 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30947.42079 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.89293 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.89293 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.89293 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.89293 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89293 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.89293 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44647 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.59529 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14781.16206 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15429.35000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7714.67500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7714.67500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78321 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78321 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78321 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78321 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15429.35000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25653.28452 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.89293 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 988.62067 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25653.28452 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 26425.6 | 11.26 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 118279.7 | 12.66 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 18078.3 | 106.97 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14729.1 | 143.99 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.172 | 0.166 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.437E-002 | 3.409E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.327 | 0.303 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 6.6810108323E-002 | 0.2382458373 | Pass | Pass | 0.1531359474 | 1.3140153833 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.5956119146E-002 | 0.1531666265 | Pass | Pass | 0.2048012129 | 0.8326587089 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 6.9441021694E-002 | 0.2751700128 | Pass | Pass | 0.1547624250 | 0.5648306081 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 7.8141128431E-002 | 0.2571256798 | Pass | Pass | 5.5161530140E-002 | 0.2711307944 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1400960740 | 0.6260285703 | Pass | Pass | 6.9900828264E-002 | 0.6288117377 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.172 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.034 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.327 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.355 | 0.361 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.355 | 0.361 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.36 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.159 | 0.355 | 0.361 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.623 | 0.410 | 0.414 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.623 | 0.410 | 0.414 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 5.1793 | 379.89 | 1967.55 | LightsWired | BLDG_LIGHT_BACK_SCH | 60.89 | 168.00 | 60.06 | 0.0000 | Y | 22.18 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 11.8188 | 1600.48 | 18915.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 56.75 | 0.0000 | Y | 201.50 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.49 |
Interior Lighting Total | 10.7081 | 2293.99 | 24564.32 | 270.84 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 238.00 | AstronomicalClock | - | 42.59 | 42.59 | 1.90 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.55 | 71.26 | 40.86 | |
Exterior Lighting Total | 3292.90 | 42.77 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27650.46 | 21420.26 | 6230.20 | 0.77 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 123579.28 | 94358.96 | 29220.32 | 0.76 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18960.69 | 15022.55 | 3938.14 | 0.79 | 4.12 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 15429.35 | 12084.42 | 3344.93 | 0.78 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 26425.6 | 11.26 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 118279.7 | 12.66 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 18078.3 | 106.97 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14729.1 | 143.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 29778.96 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 41114.33 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 205704.52 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30947.42 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25653.28 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 1.02 | 1131.25 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.56 | 1670.81 | 1070.05 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 6.75 | 11376.36 | 1684.71 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.13 | 1246.25 | 1107.16 | 1.00 | 1.37 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.89 | 988.62 | 1107.16 | 1.00 | 1.43 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 17594.19 | 21113.03 | 55.58 | 1.249 | 1.499 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.88 | 0.01046 | 21.70 | 0.00879 | 0.232 | 0.00 |
CORE_RETAIL | 76311.25 | 91573.50 | 57.22 | 5.424 | 6.509 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.88 | 0.01044 | 21.70 | 0.00879 | 1.890 | 0.00 |
POINT_OF_SALE | 12600.69 | 15120.83 | 100.26 | 0.938 | 1.126 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00893 | 29.05 | 0.00879 | 0.178 | 0.00 |
FRONT_RETAIL | 9995.79 | 11994.94 | 79.54 | 0.744 | 0.893 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.89 | 0.00904 | 29.14 | 0.00879 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.49 | 100.00 | 0.00001 | 29.40 | 0.00879 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 21306.65 | 25567.98 | 67.30 | 0.909 | 1.091 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00719 | -4.20 | 0.00269 | 0.232 | 0.00 |
CORE_RETAIL | 55062.15 | 66074.58 | 41.28 | 2.317 | 2.781 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00750 | -4.20 | 0.00269 | 1.890 | 0.00 |
POINT_OF_SALE | 10176.39 | 12211.66 | 80.97 | 0.436 | 0.523 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_RETAIL | 10171.72 | 12206.07 | 80.94 | 0.436 | 0.523 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_ENTRY | 24810.46 | 29772.55 | 2481.05 | 0.851 | 1.022 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:10:00 | 16.00 | 15.92 | 0.00511 | -4.20 | 0.00269 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.56 | 1.56 | 1.09 | 1.09 | 1.5614 | 1.4986 | 1.5614 | 0.9598 | 1.0000 |
PSZ-AC:2 | 6.75 | 6.75 | 2.78 | 2.78 | 6.7527 | 6.5088 | 6.7527 | 0.9639 | 1.0000 |
PSZ-AC:3 | 1.13 | 1.13 | 0.52 | 0.52 | 1.1256 | 1.1256 | 1.1256 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.89 | 0.89 | 0.52 | 0.52 | 0.8929 | 0.8929 | 0.8929 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 29778.962 | 29778.962 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:10:00 | 29778.96 | 29778.96 | 1.021763 | 15.64 | 9.60 | 0.00507433 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 15.92 | 0.00510786 | 44.9599 | 29772.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 13825.230 | 0.000 | 1.561430 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 13825.23 | 10881.95 | 1.561430 | 23.66 | 17.23 | 0.00983180 | 12.80 | 11.97 | 0.00850000 | 22.36 | 0.00879438 | 15.90 | 14.8304 | 23.88 | 0.01046259 | 55.7333 | 17594.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 41114.329 | 41114.329 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 41114.33 | 41114.33 | 1.561431 | 15.55 | 10.80 | 0.00623621 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 14.8304 | 21.11 | 0.00719164 | 45.5847 | 21306.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 61789.640 | 0.000 | 6.752700 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 61789.64 | 55369.57 | 6.752700 | 25.51 | 17.30 | 0.00915632 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 27.9919 | 23.88 | 0.01043906 | 55.6116 | 76311.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 205704.520 | 205704.520 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 205704.52 | 205704.52 | 6.752695 | 3.79 | 2.72 | 0.00422962 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 27.9920 | 21.11 | 0.00749751 | 47.4959 | 55062.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 9480.345 | 0.000 | 1.125630 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 9480.34 | 8809.56 | 1.125630 | 24.72 | 16.82 | 0.00890699 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 15.8232 | 23.89 | 0.00892799 | 47.6617 | 12593.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 30947.421 | 30947.421 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30947.42 | 30947.42 | 1.125628 | 12.37 | 9.02 | 0.00587337 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 15.8232 | 21.11 | 0.00751657 | 47.6179 | 10176.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 7714.675 | 0.000 | 0.892930 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 7714.68 | 7075.94 | 0.892930 | 24.94 | 16.97 | 0.00899024 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 19.9468 | 23.89 | 0.00903904 | 48.2461 | 9995.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 25653.285 | 25653.285 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25653.28 | 25653.28 | 0.892935 | 12.37 | 9.01 | 0.00587203 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.9466 | 21.11 | 0.00751571 | 47.6126 | 10171.72 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 29778.962 | 29778.962 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.021763 | 1.21282312 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:10:00 | 29778.96 | 29778.96 | 1.0000 | 1.21282312 | 1.021763 | 15.64 | 9.60 | 0.00507433 | 28556.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29778.96 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 15.93 | 0.00510786 | 15.92 | 0.00510786 | 44.9599 | 29772.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13825.230 | 0.000 | 1.561430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1168 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 13825.23 | 10881.95 | 1.0000 | 1.85340302 | 1.561430 | 23.66 | 17.23 | 0.00983180 | 48794.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13825.23 | 22.36 | 0.00879438 | 15.90 | 0.23156651 | 14.8304 | 23.88 | 0.01001244 | 23.88 | 0.01046259 | 55.7333 | 17594.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41114.329 | 41114.329 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.561431 | 1.85340453 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 41114.33 | 41114.33 | 1.0000 | 1.85340453 | 1.561431 | 15.55 | 10.80 | 0.00623621 | 31403.4 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41114.33 | -4.20 | 0.00269032 | -4.20 | 0.23156651 | 14.8304 | 20.87 | 0.00719164 | 21.11 | 0.00719164 | 45.5847 | 21306.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 61789.640 | 0.000 | 6.752700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8611 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 61789.64 | 55369.57 | 1.0000 | 8.01539266 | 6.752700 | 25.51 | 17.30 | 0.00915632 | 48971.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61789.64 | 29.31 | 0.00879438 | 18.27 | 1.89021192 | 27.9919 | 23.89 | 0.00931128 | 23.88 | 0.01043906 | 55.6116 | 76311.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 205704.520 | 205704.520 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.752695 | 8.01538721 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 205704.52 | 205704.52 | 1.0000 | 8.01538721 | 6.752695 | 3.79 | 2.72 | 0.00422962 | 14415.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 205704.52 | -4.20 | 0.00269032 | -4.20 | 1.89021192 | 27.9920 | 20.75 | 0.00749751 | 21.11 | 0.00749751 | 47.4959 | 55062.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9480.345 | 0.000 | 1.125630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3977 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 9480.34 | 8809.56 | 1.0000 | 1.33611244 | 1.125630 | 24.72 | 16.82 | 0.00890699 | 47524.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9480.34 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 15.8232 | 23.89 | 0.00892817 | 23.89 | 0.00892799 | 47.6617 | 12593.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30947.421 | 30947.421 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.125628 | 1.33610979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30947.42 | 30947.42 | 1.0000 | 1.33610979 | 1.125628 | 12.37 | 9.02 | 0.00587337 | 27254.7 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30947.42 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 15.8232 | 20.93 | 0.00751657 | 21.11 | 0.00751657 | 47.6179 | 10176.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7714.675 | 0.000 | 0.892930 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5524 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 7714.68 | 7075.94 | 1.0000 | 1.05989968 | 0.892930 | 24.94 | 16.97 | 0.00899024 | 47957.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7714.68 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 19.9468 | 23.89 | 0.00903904 | 23.89 | 0.00903904 | 48.2461 | 9995.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25653.285 | 25653.285 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.892935 | 1.05990549 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25653.28 | 25653.28 | 1.0000 | 1.05990549 | 0.892935 | 12.37 | 9.01 | 0.00587203 | 27247.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25653.28 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 19.9466 | 20.93 | 0.00751571 | 21.11 | 0.00751571 | 47.6126 | 10171.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.56 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 6.75 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.13 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 1272.00 | 3786.50 | 989.67 |
CORE_RETAIL | 1158.17 | 3217.17 | 279.33 |
POINT_OF_SALE | 1463.67 | 2797.50 | 384.83 |
FRONT_RETAIL | 1551.83 | 3331.67 | 774.50 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 2163.00 | 3804.00 | 1058.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.33 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1096.17 | 0.00 | 0.00 | 0.00 |
Facility | 1096.83 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.525 | 0.027 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.815 | 0.005 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 1.411 | 0.029 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.709 | 0.029 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.354 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.686 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.686 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.686 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 703.18 | 2865.76 | 07-MAY-06:40 | 67992.05 | 10-AUG-15:50 |
Electricity:Building | 466.00 | 2708.13 | 07-MAY-07:20 | 32651.56 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 72.17 | 558.23 | 01-JAN-00:10 | 4302.56 | 02-JAN-09:10 |
InteriorLights:Electricity | 270.84 | 912.95 | 07-MAY-07:20 | 21880.52 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 22.18 | 98.38 | 01-JAN-00:10 | 1543.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 270.84 | 912.95 | 07-MAY-07:20 | 21880.52 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 285.80 | 1405.96 | 07-MAY-07:20 | 21676.77 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 201.50 | 630.52 | 07-MAY-07:20 | 17024.17 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 75.76 | 575.93 | 01-JAN-00:10 | 4525.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 30.78 | 162.19 | 01-JAN-00:10 | 2042.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 703.18 | 2865.76 | 07-MAY-06:40 | 67992.05 | 10-AUG-15:50 |
ElectricityPurchased:Plant | 703.18 | 2865.76 | 07-MAY-06:40 | 67992.05 | 10-AUG-15:50 |
Cogeneration:ElectricityPurchased | 703.18 | 2865.76 | 07-MAY-06:40 | 67992.05 | 10-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 703.18 | 2865.76 | 07-MAY-06:40 | 67992.05 | 10-AUG-15:50 |
ElectricityNet:Plant | 703.18 | 2865.76 | 07-MAY-06:40 | 67992.05 | 10-AUG-15:50 |
Cogeneration:ElectricityNet | 703.18 | 2865.76 | 07-MAY-06:40 | 67992.05 | 10-AUG-15:50 |
Electricity:HVAC | 194.42 | 0.00 | 01-JAN-00:10 | 37338.08 | 10-AUG-15:00 |
Fans:Electricity | 150.50 | 0.00 | 01-JAN-00:10 | 11880.65 | 19-FEB-09:10 |
General:Fans:Electricity | 150.50 | 0.00 | 01-JAN-00:10 | 11880.65 | 19-FEB-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 43.92 | 0.00 | 01-JAN-00:10 | 28542.29 | 10-AUG-15:00 |
ExteriorLights:Electricity | 42.77 | 0.00 | 01-JAN-08:10 | 3292.90 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.77 | 0.00 | 01-JAN-08:10 | 3292.90 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 333.81 | 1862.00 | 05-MAY-07:10 | 161278.66 | 19-FEB-09:10 |
Gas:Plant | 94.76 | 1862.00 | 01-JAN-08:30 | 5081.10 | 13-FEB-12:30 |
WaterSystems:Gas | 94.76 | 1862.00 | 01-JAN-08:30 | 5081.10 | 13-FEB-12:30 |
Water Heater:WaterSystems:Gas | 94.76 | 1862.00 | 01-JAN-08:30 | 5081.10 | 13-FEB-12:30 |
Gas:HVAC | 239.04 | 0.00 | 01-JAN-00:10 | 158723.17 | 16-JAN-09:10 |
Heating:Gas | 239.04 | 0.00 | 01-JAN-00:10 | 158723.17 | 16-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 854.31 | 0.00 | 01-JAN-00:10 | 224934.40 | 16-JAN-09:10 |
EnergyTransfer:Building | 491.82 | 0.00 | 01-JAN-00:10 | 97955.87 | 16-JAN-09:10 |
EnergyTransfer:Zone:BACK_SPACE | 54.92 | 0.00 | 01-JAN-00:10 | 19804.01 | 09-JAN-06:10 |
Heating:EnergyTransfer | 52.84 | 0.00 | 01-JAN-00:10 | 85090.23 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 11.91 | 0.00 | 01-JAN-00:10 | 19804.01 | 09-JAN-06:10 |
Cooling:EnergyTransfer | 438.98 | 0.00 | 01-JAN-00:10 | 73446.95 | 01-AUG-06:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 43.01 | 0.00 | 01-JAN-00:10 | 9972.52 | 10-AUG-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 327.32 | 0.00 | 01-JAN-00:10 | 67448.15 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 11.49 | 0.00 | 01-JAN-00:10 | 53172.55 | 01-JAN-09:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 315.83 | 0.00 | 01-JAN-00:10 | 59707.11 | 01-AUG-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 54.54 | 0.00 | 01-JAN-00:10 | 9704.69 | 04-OCT-13:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 2.72 | 0.00 | 01-JAN-00:10 | 7876.11 | 16-JAN-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 51.82 | 0.00 | 01-JAN-00:10 | 9704.69 | 04-OCT-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 33.77 | 0.00 | 01-JAN-00:10 | 9235.82 | 17-JAN-06:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 5.45 | 0.00 | 01-JAN-00:10 | 8431.22 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 28.32 | 0.00 | 01-JAN-00:10 | 7443.44 | 14-SEP-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 21.26 | 0.00 | 01-JAN-00:10 | 19509.72 | 18-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 21.26 | 0.00 | 01-JAN-00:10 | 19509.72 | 18-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 362.50 | 0.00 | 01-JAN-00:10 | 126978.53 | 16-JAN-09:10 |
HeatingCoils:EnergyTransfer | 191.24 | 0.00 | 01-JAN-00:10 | 126978.53 | 16-JAN-09:10 |
CoolingCoils:EnergyTransfer | 171.26 | 0.00 | 01-JAN-00:10 | 111227.49 | 10-AUG-14:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 11.914 | -43.010 | 0.000 | 0.000 | 39.780 | 22.181 | 49.992 | 0.000 | 0.000 | 0.041 | 0.006 | 0.000 | 0.000 | 0.000 | -14.453 | -66.443 |
CORE_RETAIL | 0.000 | 0.000 | 11.489 | -315.829 | 0.000 | 0.000 | 167.783 | 201.497 | 84.299 | 46.090 | 0.000 | 0.033 | 0.001 | 0.000 | -23.599 | 0.000 | -12.827 | -158.935 |
POINT_OF_SALE | 0.000 | 0.000 | 2.724 | -51.820 | 0.000 | 0.000 | 15.197 | 22.836 | 52.922 | 25.883 | 0.000 | 0.017 | 0.002 | 0.000 | -18.025 | 0.000 | -6.799 | -42.937 |
FRONT_RETAIL | 0.000 | 0.000 | 5.448 | -28.321 | 0.000 | 0.000 | 15.724 | 22.836 | 7.943 | 26.089 | 0.000 | 0.017 | 0.002 | 0.000 | -17.083 | 0.000 | -6.318 | -26.337 |
FRONT_ENTRY | 21.262 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.489 | 0.000 | 5.704 | 0.000 | 0.018 | 9.737 | 0.000 | -3.012 | 0.000 | -35.197 | 0.000 |
Total Facility | 21.262 | 0.000 | 31.575 | -438.980 | 0.000 | 0.000 | 238.483 | 270.840 | 195.156 | 103.766 | 0.000 | 0.126 | 9.748 | 0.000 | -61.719 | 0.000 | -75.595 | -294.652 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-AUG-06:02 | 0.00 | 0.00 | 0.00 | -30709.69 | 0.00 | 0.00 | 407.66 | 342.98 | 1226.28 | 0.00 | 0.00 | 0.00 | 28950.02 | 0.00 | -0.00 | 0.00 | -217.26 | 0.00 |
CORE_RETAIL | 16-MAY-06:03 | 0.00 | 0.00 | 0.00 | -142166.90 | 0.00 | 0.00 | 1679.06 | 3783.15 | 2067.82 | 0.00 | 0.00 | 0.00 | 135576.85 | 0.00 | -725.70 | 0.00 | -214.28 | 0.00 |
POINT_OF_SALE | 05-OCT-06:02 | 0.00 | 0.00 | 0.00 | -27281.86 | 0.00 | 0.00 | 150.45 | 356.48 | 1298.17 | 0.00 | 0.00 | 0.00 | 26830.58 | 0.00 | -1274.21 | 0.00 | -79.62 | 0.00 |
FRONT_RETAIL | 13-AUG-08:62 | 0.00 | 0.00 | 0.00 | -12897.12 | 0.00 | 0.00 | 161.80 | 178.24 | 146.13 | 643.62 | 0.00 | 0.00 | 11806.98 | 0.00 | -0.00 | 0.00 | -39.65 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-AUG-06:02 | 0.00 | 0.00 | 0.00 | -192889.01 | 0.00 | 0.00 | 2330.06 | 4547.08 | 4787.13 | 115.51 | 0.00 | 0.00 | 182713.55 | 0.00 | -996.43 | 0.00 | -607.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 09-JAN-06:01 | 0.00 | 0.00 | 41786.19 | 0.00 | 0.00 | 0.00 | 0.00 | 98.38 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -319.09 | -42178.61 |
CORE_RETAIL | 09-JAN-06:01 | 0.00 | 0.00 | 211923.15 | 0.00 | 0.00 | 0.00 | 0.00 | 945.79 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2072.26 | 0.00 | -287.42 | -211543.17 |
POINT_OF_SALE | 09-JAN-06:01 | 0.00 | 0.00 | 30872.11 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1497.79 | 0.00 | -149.96 | -29962.56 |
FRONT_RETAIL | 28-DEC-06:01 | 0.00 | 0.00 | 23846.66 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -629.43 | 0.00 | -175.28 | -23228.50 |
FRONT_ENTRY | 27-DEC-16:31 | 24109.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -92.74 | 0.00 | -8554.96 | -15566.12 |
Total Facility | 15-JAN-08:61 | 3821.33 | 0.00 | 305150.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1228.22 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4199.19 | 0.00 | -4075.04 | -303721.10 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.4986 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.5614 | 0.1483 | 1.0000 | 0.2316 | 0.1483 | ||
PSZ-AC:2 | 6.5088 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.7527 | 0.2799 | 1.0000 | 1.8902 | 0.2799 | ||
PSZ-AC:3 | 1.1256 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1256 | 0.1582 | 1.0000 | 0.1781 | 0.1582 | ||
PSZ-AC:4 | 0.8929 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8929 | 0.1995 | 1.0000 | 0.1781 | 0.1995 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.4986 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.4986 | 1.0000 | 1.0000 | 0.2316 | 0.1545 | ||
PSZ-AC:2 | 6.5088 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.5088 | 1.0000 | 1.0000 | 1.8902 | 0.2904 | ||
PSZ-AC:3 | 1.1256 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1256 | 1.0000 | 1.0000 | 0.1781 | 0.1582 | ||
PSZ-AC:4 | 0.8929 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8929 | 1.0000 | 1.0000 | 0.1781 | 0.1995 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.4986 | 1.4986 | 1.4986 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.5088 | 6.5088 | 6.5088 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1256 | 1.1256 | 1.1256 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8929 | 0.8929 | 0.8929 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.4986 | 1.5614 | 1.4986 | 1.4986 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.5088 | 6.7527 | 6.5088 | 6.5088 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1256 | 1.1256 | 1.1256 | 1.1256 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8929 | 0.8929 | 0.8929 | 0.8929 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.4986 | 1.4986 | 1.4986 | 0.2316 | 0.2123 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.5088 | 6.5088 | 6.5088 | 1.8902 | 0.6798 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1256 | 1.1256 | 1.1256 | 0.1781 | 0.3405 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8929 | 0.8929 | 0.8929 | 0.1781 | 0.3406 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.4986 | 1.4986 | 1.4986 | 1.4986 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.5088 | 6.5088 | 6.5088 | 6.5088 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1256 | 1.1256 | 1.1256 | 1.1256 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8929 | 0.8929 | 0.8929 | 0.8929 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 239.04 | 158723.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 43.92 | 28542.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 270.84 | 21880.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.77 | 3292.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 150.50 | 11880.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 94.76 | 5081.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 703.18 |
Natural Gas | 0.00 | 333.81 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1036.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 118.07 |
Space Heating | 0.00 |
Space Cooling | 19.14 |
Fans (All) | 65.61 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 306.53 |
Subtotal | 306.53 |
Natural Gas [MJ/m2] | |
Space Heating | 104.20 |
Service Water Heating | 41.31 |
Miscellaneous (All) | 145.51 |
Subtotal | 145.51 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 26.12 |
Space Heating | 23.05 |
Space Cooling | 4.24 |
Fans (All) | 14.51 |
Service Water Heating | 9.14 |
Receptacle Equipment | 18.82 |
Miscellaneous | 4.12 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3175. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.702759E+11 |
February | 0.000 | 0.463281E+11 |
March | 0.000 | 0.209346E+11 |
April | 0.000 | 0.722339E+10 |
May | 0.000 | 0.414105E+09 |
June | 0.000 | 7484245.207 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.237548E+08 |
October | 0.000 | 0.426987E+10 |
November | 0.000 | 0.313816E+11 |
December | 0.000 | 0.581852E+11 |
Annual Sum or Average | 0.239044E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.702759E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.599817E+09 | 4692.37 | 13-JAN-07:05 | 2.80 | 1.90 | 0.165292E+10 | 1974.88 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.968928E+09 | 4639.24 | 16-FEB-07:05 | 2.80 | 1.84 | 0.153710E+10 | 2328.80 | 27-FEB-15:00 | 19.40 | 12.41 |
March | 0.223718E+10 | 5672.84 | 01-MAR-07:05 | -0.1 | -1.6 | 0.180677E+10 | 2398.32 | 18-MAR-15:00 | 20.60 | 10.40 |
April | 0.276353E+10 | 5255.88 | 29-APR-15:00 | 22.20 | 15.22 | 0.186774E+10 | 2451.89 | 01-APR-14:39 | 25.37 | 14.15 |
May | 0.425515E+10 | 6540.53 | 06-MAY-14:00 | 23.90 | 16.62 | 0.214542E+10 | 2451.24 | 05-MAY-14:00 | 24.40 | 17.03 |
June | 0.575316E+10 | 18711.85 | 29-JUN-06:02 | 12.70 | 11.22 | 0.218347E+10 | 2451.28 | 10-JUN-10:09 | 19.60 | 14.75 |
July | 0.744878E+10 | 28313.95 | 28-JUL-06:02 | 15.10 | 12.80 | 0.218390E+10 | 2451.28 | 22-JUL-10:09 | 20.78 | 14.77 |
August | 0.787259E+10 | 30715.02 | 01-AUG-06:02 | 11.32 | 11.32 | 0.227732E+10 | 2451.24 | 26-AUG-10:09 | 18.45 | 15.91 |
September | 0.516580E+10 | 17351.23 | 14-SEP-06:02 | 12.07 | 11.66 | 0.212803E+10 | 2451.24 | 09-SEP-11:20 | 19.27 | 13.68 |
October | 0.312096E+10 | 4611.20 | 04-OCT-15:00 | 21.70 | 11.47 | 0.193686E+10 | 2451.24 | 07-OCT-11:20 | 15.37 | 11.27 |
November | 0.192102E+10 | 5315.65 | 11-NOV-09:05 | 0.78 | 0.55 | 0.166255E+10 | 2451.21 | 04-NOV-15:20 | 20.73 | 15.93 |
December | 0.902967E+09 | 5372.82 | 06-DEC-07:05 | 0.18 | -0.1 | 0.165572E+10 | 1910.09 | 02-DEC-14:00 | 11.70 | 5.51 |
Annual Sum or Average | 0.430099E+11 | 0.230378E+11 | ||||||||
Minimum of Months | 0.599817E+09 | 4611.20 | -0.1 | -1.6 | 0.153710E+10 | 1910.09 | 11.70 | 5.51 | ||
Maximum of Months | 0.787259E+10 | 30715.02 | 23.90 | 16.62 | 0.227732E+10 | 2451.89 | 25.37 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134829E+11 | 49964.94 | 07-JAN-07:05 | -2.5 | -2.6 | 0.696819E+10 | 8740.82 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.150197E+11 | 51153.79 | 19-FEB-09:05 | -3.1 | -4.2 | 0.648390E+10 | 10326.89 | 27-FEB-15:00 | 19.40 | 12.41 |
March | 0.229089E+11 | 43346.07 | 01-MAR-07:03 | -0.1 | -1.6 | 0.766099E+10 | 10326.83 | 18-MAR-13:39 | 19.07 | 10.71 |
April | 0.248257E+11 | 123245.12 | 28-APR-06:02 | 11.10 | 10.22 | 0.788068E+10 | 10327.08 | 29-APR-11:20 | 16.50 | 13.36 |
May | 0.313168E+11 | 142176.02 | 16-MAY-06:03 | 11.70 | 10.49 | 0.899847E+10 | 10327.10 | 20-MAY-11:20 | 15.37 | 10.33 |
June | 0.351250E+11 | 140797.75 | 22-JUN-06:02 | 11.70 | 10.71 | 0.918968E+10 | 10327.08 | 10-JUN-10:20 | 19.80 | 14.77 |
July | 0.404153E+11 | 141447.28 | 02-JUL-08:62 | 14.50 | 10.32 | 0.919789E+10 | 10327.22 | 22-JUL-10:09 | 20.78 | 14.77 |
August | 0.408405E+11 | 138401.10 | 01-AUG-06:02 | 11.32 | 11.32 | 0.958876E+10 | 10327.18 | 19-AUG-12:09 | 19.18 | 14.29 |
September | 0.317742E+11 | 139424.49 | 11-SEP-06:02 | 12.07 | 10.69 | 0.890792E+10 | 10327.23 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.260213E+11 | 65395.25 | 05-OCT-06:02 | 8.48 | 5.35 | 0.807164E+10 | 10327.09 | 07-OCT-11:20 | 15.37 | 11.27 |
November | 0.188865E+11 | 41698.55 | 24-NOV-07:05 | 1.20 | 0.92 | 0.694105E+10 | 10327.03 | 04-NOV-12:50 | 20.32 | 15.90 |
December | 0.152118E+11 | 47744.76 | 26-DEC-07:05 | -1.6 | -1.6 | 0.697917E+10 | 8403.32 | 02-DEC-14:20 | 12.03 | 5.69 |
Annual Sum or Average | 0.315829E+12 | 0.968683E+11 | ||||||||
Minimum of Months | 0.134829E+11 | 41698.55 | -3.1 | -4.2 | 0.648390E+10 | 8403.32 | 12.03 | 5.69 | ||
Maximum of Months | 0.408405E+11 | 142176.02 | 14.50 | 11.32 | 0.958876E+10 | 10327.23 | 20.78 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199636E+10 | 3989.01 | 07-JAN-07:05 | -2.5 | -2.6 | 0.693317E+09 | 973.10 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.224329E+10 | 5166.77 | 27-FEB-15:10 | 19.90 | 12.20 | 0.686100E+09 | 973.10 | 25-FEB-12:20 | 15.00 | 12.12 |
March | 0.300641E+10 | 5599.44 | 18-MAR-13:50 | 19.53 | 10.60 | 0.844079E+09 | 973.10 | 04-MAR-12:20 | 10.97 | 7.74 |
April | 0.363198E+10 | 23284.04 | 28-APR-06:02 | 11.10 | 10.22 | 0.826038E+09 | 973.11 | 22-APR-11:20 | 11.13 | 8.44 |
May | 0.482370E+10 | 22159.08 | 05-MAY-06:02 | 13.90 | 11.48 | 0.877534E+09 | 973.13 | 06-MAY-10:09 | 20.68 | 16.06 |
June | 0.567535E+10 | 22704.04 | 22-JUN-06:02 | 11.70 | 10.71 | 0.872963E+09 | 973.12 | 03-JUN-15:00 | 20.60 | 13.78 |
July | 0.695296E+10 | 22862.00 | 19-JUL-06:02 | 14.08 | 10.93 | 0.868563E+09 | 973.14 | 22-JUL-10:09 | 20.78 | 14.77 |
August | 0.782728E+10 | 22171.77 | 01-AUG-06:02 | 11.32 | 11.32 | 0.905725E+09 | 973.17 | 16-AUG-14:00 | 19.40 | 16.00 |
September | 0.654015E+10 | 22859.50 | 11-SEP-06:02 | 12.07 | 10.69 | 0.854639E+09 | 973.13 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.441563E+10 | 27285.67 | 05-OCT-06:02 | 8.48 | 5.35 | 0.848280E+09 | 973.10 | 28-OCT-11:20 | 11.10 | 8.28 |
November | 0.251151E+10 | 7355.38 | 04-NOV-14:00 | 21.10 | 15.93 | 0.742243E+09 | 973.15 | 04-NOV-15:00 | 20.00 | 15.90 |
December | 0.219500E+10 | 4402.41 | 05-DEC-12:30 | 10.30 | 6.12 | 0.721225E+09 | 973.10 | 05-DEC-15:00 | 6.10 | 4.53 |
Annual Sum or Average | 0.518196E+11 | 0.974071E+10 | ||||||||
Minimum of Months | 0.199636E+10 | 3989.01 | -2.5 | -2.6 | 0.686100E+09 | 973.10 | 6.10 | 4.53 | ||
Maximum of Months | 0.782728E+10 | 27285.67 | 21.10 | 15.93 | 0.905725E+09 | 973.17 | 20.78 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.561946E+09 | 4135.06 | 07-JAN-06:04 | -2.2 | -2.2 | 0.658428E+09 | 830.96 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.993924E+09 | 4530.95 | 19-FEB-08:04 | -4.7 | -5.5 | 0.625383E+09 | 973.09 | 27-FEB-15:00 | 19.40 | 12.41 |
March | 0.159296E+10 | 3819.76 | 01-MAR-07:05 | -0.1 | -1.6 | 0.751902E+09 | 973.10 | 18-MAR-12:09 | 16.78 | 11.23 |
April | 0.194391E+10 | 5456.68 | 27-APR-14:10 | 26.28 | 16.89 | 0.758529E+09 | 973.11 | 29-APR-11:09 | 16.05 | 13.18 |
May | 0.258568E+10 | 4482.83 | 15-MAY-14:10 | 23.30 | 13.33 | 0.841166E+09 | 973.14 | 06-MAY-10:09 | 20.68 | 16.06 |
June | 0.309325E+10 | 4684.76 | 28-JUN-15:00 | 26.10 | 15.52 | 0.859897E+09 | 973.13 | 10-JUN-10:09 | 19.60 | 14.75 |
July | 0.410172E+10 | 6971.83 | 31-JUL-06:02 | 18.07 | 14.93 | 0.864707E+09 | 973.13 | 15-JUL-10:50 | 18.22 | 15.41 |
August | 0.491680E+10 | 12897.91 | 13-AUG-08:62 | 19.73 | 15.21 | 0.902101E+09 | 973.13 | 26-AUG-10:39 | 18.90 | 16.15 |
September | 0.398843E+10 | 7443.44 | 14-SEP-13:30 | 23.35 | 17.42 | 0.838108E+09 | 973.12 | 23-SEP-10:09 | 18.90 | 15.99 |
October | 0.259599E+10 | 7299.20 | 04-OCT-14:10 | 21.20 | 11.40 | 0.781078E+09 | 973.10 | 07-OCT-11:20 | 15.37 | 11.27 |
November | 0.115091E+10 | 4569.27 | 04-NOV-14:10 | 21.10 | 15.93 | 0.660771E+09 | 973.13 | 04-NOV-11:09 | 17.98 | 14.86 |
December | 0.795048E+09 | 3723.26 | 06-DEC-07:05 | 0.18 | -0.1 | 0.671318E+09 | 973.09 | 02-DEC-14:39 | 11.87 | 5.60 |
Annual Sum or Average | 0.283206E+11 | 0.921339E+10 | ||||||||
Minimum of Months | 0.561946E+09 | 3723.26 | -4.7 | -5.5 | 0.625383E+09 | 830.96 | 11.87 | 5.60 | ||
Maximum of Months | 0.491680E+10 | 12897.91 | 26.28 | 17.42 | 0.902101E+09 | 973.14 | 20.68 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357246E+10 | 41786.15 | 09-JAN-06:01 | -1.5 |
February | 0.253382E+10 | 41782.78 | 21-FEB-06:01 | 1.70 |
March | 0.112106E+10 | 41515.74 | 06-MAR-06:01 | 6.70 |
April | 0.410896E+09 | 41026.56 | 18-APR-05:02 | 3.30 |
May | 67193459.60 | 658.87 | 28-MAY-07:12 | 8.30 |
June | 64018938.11 | 655.58 | 04-JUN-07:12 | 11.87 |
July | 66502436.95 | 655.69 | 04-JUL-07:12 | 12.07 |
August | 66933620.21 | 656.25 | 20-AUG-07:12 | 14.17 |
September | 67352166.55 | 659.94 | 17-SEP-07:12 | 11.10 |
October | 0.191296E+09 | 37434.45 | 31-OCT-06:03 | 10.18 |
November | 0.115627E+10 | 41534.22 | 24-NOV-06:01 | 2.02 |
December | 0.259592E+10 | 41770.86 | 03-DEC-08:61 | 7.80 |
Annual Sum or Average | 0.119137E+11 | |||
Minimum of Months | 64018938.11 | 655.58 | -1.5 | |
Maximum of Months | 0.357246E+10 | 41786.15 | 14.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296587E+10 | 211923.10 | 09-JAN-06:01 | -1.5 |
February | 0.176355E+10 | 211873.50 | 21-FEB-06:01 | 1.70 |
March | 0.646648E+09 | 96081.75 | 06-MAR-07:03 | 6.70 |
April | 0.491979E+09 | 18099.17 | 17-APR-06:08 | 6.10 |
May | 0.467581E+09 | 4495.70 | 28-MAY-07:12 | 8.30 |
June | 0.448945E+09 | 4477.37 | 04-JUN-07:12 | 11.87 |
July | 0.452992E+09 | 4478.82 | 04-JUL-07:12 | 12.07 |
August | 0.438896E+09 | 4477.22 | 20-AUG-07:12 | 14.17 |
September | 0.457504E+09 | 4496.22 | 17-SEP-07:12 | 11.10 |
October | 0.496101E+09 | 13842.48 | 29-OCT-08:10 | 6.88 |
November | 0.932038E+09 | 137557.21 | 13-NOV-07:03 | 1.52 |
December | 0.192693E+10 | 211330.78 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.114890E+11 | |||
Minimum of Months | 0.438896E+09 | 4477.22 | -1.5 | |
Maximum of Months | 0.296587E+10 | 211923.10 | 14.17 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.712661E+09 | 30872.09 | 09-JAN-06:01 | -1.5 |
February | 0.373017E+09 | 30866.68 | 21-FEB-06:01 | 1.70 |
March | 0.168126E+09 | 30513.70 | 06-MAR-06:01 | 6.70 |
April | 0.127189E+09 | 8132.78 | 18-APR-05:02 | 3.30 |
May | 0.118732E+09 | 1209.71 | 28-MAY-07:12 | 8.30 |
June | 0.112069E+09 | 1198.15 | 04-JUN-07:12 | 11.87 |
July | 0.100552E+09 | 1199.18 | 04-JUL-07:12 | 12.07 |
August | 68189843.36 | 1329.58 | 10-AUG-05:04 | 17.33 |
September | 99836035.93 | 1264.27 | 14-SEP-05:03 | 12.62 |
October | 0.121036E+09 | 1213.87 | 15-OCT-07:12 | 8.30 |
November | 0.215127E+09 | 30539.22 | 24-NOV-06:01 | 2.02 |
December | 0.507892E+09 | 30739.65 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.272443E+10 | |||
Minimum of Months | 68189843.36 | 1198.15 | -1.5 | |
Maximum of Months | 0.712661E+09 | 30872.09 | 17.33 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172971E+10 | 23509.25 | 03-JAN-06:01 | 7.80 |
February | 0.939204E+09 | 23438.40 | 22-FEB-06:01 | 7.62 |
March | 0.461668E+09 | 23380.65 | 12-MAR-07:01 | 7.38 |
April | 0.206427E+09 | 22520.17 | 11-APR-05:02 | 5.60 |
May | 31617084.95 | 13760.78 | 20-MAY-06:03 | 8.40 |
June | 1342917.47 | 2484.10 | 15-JUN-06:05 | 9.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 72444.30 | 444.63 | 13-AUG-08:04 | 19.73 |
September | 3646061.72 | 8877.52 | 28-SEP-06:03 | 8.40 |
October | 97423902.62 | 14698.41 | 31-OCT-06:03 | 10.18 |
November | 0.596873E+09 | 23768.77 | 27-NOV-06:02 | 11.70 |
December | 0.137976E+10 | 23846.55 | 28-DEC-06:01 | 9.40 |
Annual Sum or Average | 0.544774E+10 | |||
Minimum of Months | 0.00 | 0.00 | 5.60 | |
Maximum of Months | 0.172971E+10 | 23846.55 | 19.73 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.676196E+10 | 24020.98 | 22-JAN-16:31 | 7.07 |
February | 0.421453E+10 | 23743.42 | 20-FEB-17:51 | 7.20 |
March | 0.895114E+09 | 22608.46 | 04-MAR-16:41 | 6.97 |
April | 89971641.92 | 22830.22 | 18-APR-16:51 | 7.20 |
May | 7726598.16 | 1873.31 | 18-MAY-07:10 | 6.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 17454958.81 | 1897.88 | 16-OCT-07:10 | 6.38 |
November | 0.328949E+10 | 23807.08 | 25-NOV-16:51 | 7.20 |
December | 0.598535E+10 | 24108.75 | 27-DEC-16:31 | 7.07 |
Annual Sum or Average | 0.212616E+11 | |||
Minimum of Months | 0.00 | 0.00 | 6.10 | |
Maximum of Months | 0.676196E+10 | 24108.75 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.186041E+10 | 1543.42 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.169252E+10 | 1543.42 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.193008E+10 | 1543.42 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.182131E+10 | 1543.42 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.189524E+10 | 1543.42 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.186250E+10 | 1543.42 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.185405E+10 | 1543.42 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.193008E+10 | 1543.42 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.182131E+10 | 1543.42 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.186041E+10 | 1543.42 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.179919E+10 | 1543.42 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.185405E+10 | 1543.42 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.221812E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.169252E+10 | 1543.42 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.193008E+10 | 1543.42 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.194157E+11 | 17024.17 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.168939E+11 | 17024.17 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.178503E+11 | 17024.17 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.147306E+11 | 17024.17 | 01-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.145812E+11 | 17024.17 | 01-MAY-16:00 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.144914E+11 | 15605.49 | 01-JUN-16:19 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.147968E+11 | 17024.17 | 12-JUL-08:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.159107E+11 | 17024.17 | 08-AUG-16:00 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.163177E+11 | 17024.17 | 07-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.181602E+11 | 17024.17 | 02-OCT-15:39 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.186180E+11 | 17024.17 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.197304E+11 | 17024.17 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.201497E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.144914E+11 | 15605.49 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.197304E+11 | 17024.17 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.124902E+09 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.113644E+09 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.129631E+09 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.122307E+09 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.127266E+09 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.125090E+09 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.124483E+09 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.129631E+09 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.122307E+09 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.124902E+09 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.120779E+09 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.124483E+09 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148942E+10 | ||||
Minimum of Months | 0.113644E+09 | 104.63 | 0.00 | 0.00 | |
Maximum of Months | 0.129631E+09 | 104.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175507E+10 |
February | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148081E+10 |
March | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146610E+10 |
April | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2221523.09 | 0.138657E+10 |
May | 0.536353E+10 | 0.189524E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142615.32 | 0.118893E+10 |
June | 0.528933E+10 | 0.186250E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1225956.70 | 0.998731E+09 |
July | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12671792.50 | 0.806501E+09 |
August | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24109803.50 | 0.713018E+09 |
September | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135366.97 | 0.566133E+09 |
October | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122695E+10 |
November | 0.504819E+10 | 0.179919E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140031E+10 |
December | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146419E+10 |
Annual Sum or Average | 0.628175E+11 | 0.221812E+11 | 0.499918E+11 | 40507058.08 | 0.144533E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566133E+09 |
Maximum of Months | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24109803.50 | 0.175507E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.194157E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155106E+10 |
February | 0.201852E+11 | 0.168939E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130854E+10 |
March | 0.230879E+11 | 0.178503E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131665E+10 |
April | 0.218263E+11 | 0.147306E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1798567.32 | 0.124343E+10 |
May | 0.225967E+11 | 0.145812E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116851.44 | 0.105419E+10 |
June | 0.222841E+11 | 0.144914E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1003876.20 | 0.888451E+09 |
July | 0.221389E+11 | 0.147968E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10284965.58 | 0.715624E+09 |
August | 0.230879E+11 | 0.159107E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19696183.58 | 0.632666E+09 |
September | 0.218263E+11 | 0.163177E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110885.90 | 0.497214E+09 |
October | 0.221054E+11 | 0.181602E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108343E+10 |
November | 0.212681E+11 | 0.186180E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124105E+10 |
December | 0.221389E+11 | 0.197304E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129462E+10 |
Annual Sum or Average | 0.264651E+12 | 0.201497E+12 | 0.842987E+11 | 33011330.03 | 0.128269E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.144914E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497214E+09 |
Maximum of Months | 0.230879E+11 | 0.197304E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19696183.58 | 0.155106E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788205E+09 |
February | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688960E+09 |
March | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715459E+09 |
April | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 952164.45 | 0.671705E+09 |
May | 0.212923E+10 | 0.195129E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61824.85 | 0.553483E+09 |
June | 0.209978E+10 | 0.191792E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531248.50 | 0.460426E+09 |
July | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5365948.98 | 0.377332E+09 |
August | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10375094.45 | 0.342958E+09 |
September | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58733.09 | 0.270097E+09 |
October | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602231E+09 |
November | 0.200405E+10 | 0.185183E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660265E+09 |
December | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668052E+09 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.529224E+11 | 17345014.33 | 0.679917E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270097E+09 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10375094.45 | 0.788205E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753192E+09 |
February | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648934E+09 |
March | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656714E+09 |
April | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 952134.57 | 0.614858E+09 |
May | 0.212923E+10 | 0.195129E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61789.09 | 0.511428E+09 |
June | 0.209978E+10 | 0.191792E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 531252.54 | 0.428052E+09 |
July | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5406837.80 | 0.350321E+09 |
August | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10391123.80 | 0.317315E+09 |
September | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58699.05 | 0.251191E+09 |
October | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548270E+09 |
November | 0.200405E+10 | 0.185183E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604458E+09 |
December | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632990E+09 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.794328E+10 | 17401836.85 | 0.631772E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251191E+09 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10391123.80 | 0.753192E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774503E+10 |
February | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535365E+10 |
March | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250501E+10 |
April | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2901690.42 | 0.147547E+10 |
May | 0.00 | 0.127266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127129E+10 |
June | 0.00 | 0.125090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1444.71 | 0.963005E+09 |
July | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4166057.10 | 0.766681E+09 |
August | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10616236.39 | 0.682411E+09 |
September | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122064E+10 |
October | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163257E+10 |
November | 0.00 | 0.120779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452945E+10 |
December | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705217E+10 |
Annual Sum or Average | 0.00 | 0.148942E+10 | 17685428.62 | 0.351974E+11 | |||||
Minimum of Months | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682411E+09 |
Maximum of Months | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10616236.39 | 0.774503E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 1543.42 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2964.47 | 12-JAN-24:00 |
February | 5888.82 | 01-FEB-15:09 | 1543.42 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2922.52 | 16-FEB-21:03 |
March | 5888.82 | 01-MAR-15:09 | 1543.42 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2595.56 | 04-MAR-22:05 |
April | 5888.82 | 01-APR-10:09 | 1543.42 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.83 | 01-APR-16:00 | 2703.70 | 07-APR-24:00 |
May | 5888.82 | 01-MAY-14:09 | 1543.42 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 05-MAY-16:00 | 2627.98 | 17-MAY-20:05 |
June | 5888.82 | 01-JUN-14:09 | 1543.42 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 | 28-JUN-16:00 | 2835.90 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 1543.42 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 239.07 | 30-JUL-18:03 | 1493.62 | 02-JUL-04:00 |
August | 5888.82 | 01-AUG-14:09 | 1543.42 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 219.11 | 13-AUG-18:03 | 2099.41 | 11-AUG-04:00 |
September | 5888.82 | 01-SEP-14:09 | 1543.42 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 14-SEP-17:00 | 1392.94 | 18-SEP-23:00 |
October | 5888.82 | 02-OCT-14:09 | 1543.42 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2792.47 | 31-OCT-20:05 |
November | 5888.82 | 01-NOV-14:09 | 1543.42 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3455.81 | 29-NOV-21:05 |
December | 5888.82 | 01-DEC-15:09 | 1543.42 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2932.74 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1392.94 | |||||
Maximum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 239.07 | 3455.81 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 17024.17 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2774.93 | 12-JAN-24:00 |
February | 24809.68 | 01-FEB-15:09 | 17024.17 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2538.90 | 16-FEB-04:00 |
March | 24809.68 | 01-MAR-15:09 | 17024.17 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2336.75 | 28-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 17024.17 | 01-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.65 | 01-APR-16:00 | 2535.75 | 07-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 17024.17 | 01-MAY-16:00 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 | 05-MAY-16:00 | 2178.55 | 17-MAY-20:10 |
June | 24809.68 | 01-JUN-14:09 | 15605.49 | 01-JUN-16:19 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.13 | 28-JUN-15:00 | 2678.99 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 17024.17 | 12-JUL-08:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 192.66 | 30-JUL-18:03 | 1368.96 | 02-JUL-04:00 |
August | 24809.68 | 01-AUG-14:09 | 17024.17 | 08-AUG-16:00 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.58 | 13-AUG-18:03 | 1893.36 | 11-AUG-04:00 |
September | 24809.68 | 01-SEP-14:09 | 17024.17 | 07-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | 14-SEP-17:00 | 1254.04 | 18-SEP-23:00 |
October | 24809.68 | 02-OCT-14:09 | 17024.17 | 02-OCT-15:39 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2333.38 | 31-OCT-20:10 |
November | 24809.68 | 01-NOV-14:09 | 17024.17 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2875.18 | 29-NOV-21:05 |
December | 24809.68 | 01-DEC-15:09 | 17024.17 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2427.82 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 15605.49 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.04 | |||||
Maximum of Months | 24809.68 | 17024.17 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 192.66 | 2875.18 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1351.52 | 12-JAN-24:00 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1268.77 | 16-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1244.50 | 28-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-APR-16:00 | 1295.95 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 05-MAY-16:00 | 1199.41 | 17-MAY-20:05 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 28-JUN-16:00 | 1277.24 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.52 | 30-JUL-18:03 | 675.58 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.41 | 13-AUG-18:03 | 1003.16 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 14-SEP-17:00 | 642.40 | 18-SEP-23:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1273.23 | 31-OCT-20:05 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1503.17 | 29-NOV-21:05 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1275.19 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.40 | |||||
Maximum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 95.52 | 1503.17 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1255.47 | 12-JAN-24:00 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1262.89 | 16-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1141.58 | 28-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-APR-16:00 | 1196.11 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 05-MAY-16:00 | 1070.44 | 17-MAY-20:10 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 28-JUN-16:00 | 1199.66 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.47 | 30-JUL-18:03 | 634.45 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.33 | 13-AUG-18:03 | 947.26 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 14-SEP-17:00 | 589.19 | 30-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1206.59 | 31-OCT-20:05 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1491.51 | 29-NOV-21:05 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1268.59 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.19 | |||||
Maximum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 98.47 | 1491.51 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 19964.59 | 07-JAN-12:10 |
February | 0.00 | 01-FEB-00:10 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 19883.25 | 18-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 12827.98 | 05-MAR-12:10 |
April | 0.00 | 01-APR-00:10 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.13 | 01-APR-16:00 | 10369.05 | 18-APR-17:00 |
May | 0.00 | 01-MAY-00:10 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 4964.02 | 18-MAY-11:01 |
June | 0.00 | 01-JUN-00:10 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 28-JUN-17:00 | 5238.46 | 13-JUN-11:01 |
July | 0.00 | 01-JUL-00:10 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.31 | 24-JUL-15:00 | 4239.47 | 12-JUL-11:01 |
August | 0.00 | 01-AUG-00:10 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.68 | 10-AUG-17:00 | 5171.29 | 01-AUG-11:01 |
September | 0.00 | 01-SEP-00:10 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 5736.95 | 16-SEP-11:01 |
October | 0.00 | 01-OCT-00:10 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6263.36 | 29-OCT-11:01 |
November | 0.00 | 01-NOV-00:10 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 15265.30 | 12-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 19119.38 | 26-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4239.47 | ||||
Maximum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.68 | 19964.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4692.37 | 13-JAN-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.71 |
February | 4639.24 | 16-FEB-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.04 |
March | 5672.84 | 01-MAR-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.40 |
April | 5255.88 | 29-APR-15:00 | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 |
May | 6540.53 | 06-MAY-14:00 | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
June | 18711.85 | 29-JUN-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.14 |
July | 28313.95 | 28-JUL-06:02 | 4416.61 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.87 |
August | 30715.02 | 01-AUG-06:02 | 4416.61 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.26 |
September | 17351.23 | 14-SEP-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4611.20 | 04-OCT-15:00 | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 |
November | 5315.65 | 11-NOV-09:05 | 2944.41 | 685.97 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.31 |
December | 5372.82 | 06-DEC-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4611.20 | 2944.41 | 685.97 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30715.02 | 5888.82 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 668.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49964.94 | 07-JAN-07:05 | 12404.84 | 7566.30 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.91 |
February | 51153.79 | 19-FEB-09:05 | 12404.84 | 7566.30 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.66 |
March | 43346.07 | 01-MAR-07:03 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.91 |
April | 123245.12 | 28-APR-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.80 |
May | 142176.02 | 16-MAY-06:03 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.28 |
June | 140797.75 | 22-JUN-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.78 |
July | 141447.28 | 02-JUL-08:62 | 12404.84 | 5044.20 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.43 |
August | 138401.10 | 01-AUG-06:02 | 18607.26 | 20807.32 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.35 |
September | 139424.49 | 11-SEP-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.79 |
October | 65395.25 | 05-OCT-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.35 |
November | 41698.55 | 24-NOV-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.24 |
December | 47744.76 | 26-DEC-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.83 |
Annual Sum or Average | |||||||||||
Minimum of Months | 41698.55 | 12404.84 | 5044.20 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.79 | |
Maximum of Months | 142176.02 | 18607.26 | 20807.32 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3989.01 | 07-JAN-07:05 | 1168.88 | 712.96 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.68 |
February | 5166.77 | 27-FEB-15:10 | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 |
March | 5599.44 | 18-MAR-13:50 | 4675.52 | 3208.30 | 5841.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.74 |
April | 23284.04 | 28-APR-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 |
May | 22159.08 | 05-MAY-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 |
June | 22704.04 | 22-JUN-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.60 |
July | 22862.00 | 19-JUL-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.85 |
August | 22171.77 | 01-AUG-06:02 | 1753.32 | 2138.87 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.77 |
September | 22859.50 | 11-SEP-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.34 |
October | 27285.67 | 05-OCT-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.62 |
November | 7355.38 | 04-NOV-14:00 | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4402.41 | 05-DEC-12:30 | 2045.54 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3989.01 | 1168.88 | 712.96 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27285.67 | 4675.52 | 3208.30 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4135.06 | 07-JAN-06:04 | 0.00 | 623.84 | 511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.22 |
February | 4530.95 | 19-FEB-08:04 | 0.00 | 623.84 | 511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.50 |
March | 3819.76 | 01-MAR-07:05 | 1168.88 | 1425.91 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.52 |
April | 5456.68 | 27-APR-14:10 | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 |
May | 4482.83 | 15-MAY-14:10 | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
June | 4684.76 | 28-JUN-15:00 | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 0.00 |
July | 6971.83 | 31-JUL-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 |
August | 12897.91 | 13-AUG-08:62 | 1461.10 | 891.19 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 |
September | 7443.44 | 14-SEP-13:30 | 2045.54 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
October | 7299.20 | 04-OCT-14:10 | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 |
November | 4569.27 | 04-NOV-14:10 | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 |
December | 3723.26 | 06-DEC-07:05 | 1168.88 | 1425.91 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3723.26 | 0.00 | 623.84 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12897.91 | 2337.76 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 306.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.35 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.98 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.26 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.43 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.18 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | |
Maximum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.609663E+11 | 45612.18 | 06-JAN-17:00 | 0.784931E+11 | 160585.17 | 16-JAN-09:09 |
February | 0.535639E+11 | 45702.86 | 18-FEB-17:00 | 0.537857E+11 | 161278.66 | 19-FEB-09:09 |
March | 0.574320E+11 | 44814.05 | 04-MAR-17:00 | 0.292233E+11 | 97462.22 | 06-MAR-07:10 |
April | 0.525518E+11 | 54692.22 | 27-APR-14:00 | 0.151118E+11 | 81034.83 | 19-APR-06:10 |
May | 0.547486E+11 | 54233.05 | 04-MAY-15:50 | 0.845217E+10 | 32009.10 | 18-MAY-06:49 |
June | 0.567818E+11 | 57901.64 | 28-JUN-16:00 | 0.771588E+10 | 7297.27 | 15-JUN-06:10 |
July | 0.638950E+11 | 64918.72 | 31-JUL-15:00 | 0.782009E+10 | 4976.60 | 03-JUL-11:39 |
August | 0.691489E+11 | 67992.05 | 10-AUG-15:50 | 0.787350E+10 | 4966.45 | 31-AUG-11:30 |
September | 0.584135E+11 | 58532.91 | 14-SEP-15:30 | 0.763904E+10 | 8603.79 | 28-SEP-06:10 |
October | 0.570883E+11 | 50931.84 | 04-OCT-14:00 | 0.121995E+11 | 49654.41 | 30-OCT-06:10 |
November | 0.575447E+11 | 47331.37 | 04-NOV-14:30 | 0.391562E+11 | 128906.69 | 24-NOV-07:10 |
December | 0.610433E+11 | 45501.95 | 06-DEC-17:00 | 0.663359E+11 | 159859.20 | 26-DEC-07:10 |
Annual Sum or Average | 0.703178E+12 | 0.333806E+12 | ||||
Minimum of Months | 0.525518E+11 | 44814.05 | 0.763904E+10 | 4966.45 | ||
Maximum of Months | 0.691489E+11 | 67992.05 | 0.784931E+11 | 161278.66 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.252311E+11 | 0.484202E+10 | 0.164409E+11 | 0.00 | 0.144523E+11 | 0.00 | 0.00 | 11.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221850E+11 | 0.393094E+10 | 0.149157E+11 | 0.00 | 0.125190E+11 | 0.00 | 0.00 | 13258358.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238851E+11 | 0.374548E+10 | 0.168545E+11 | 0.00 | 0.129039E+11 | 0.00 | 0.00 | 43014442.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204248E+11 | 0.301569E+10 | 0.160165E+11 | 0.00 | 0.119044E+11 | 0.00 | 0.00 | 0.119033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205063E+11 | 0.262672E+10 | 0.166477E+11 | 0.00 | 0.120652E+11 | 0.00 | 0.00 | 0.290267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.203148E+11 | 0.229283E+10 | 0.162772E+11 | 0.00 | 0.117667E+11 | 0.00 | 0.00 | 0.613022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.205926E+11 | 0.246779E+10 | 0.163871E+11 | 0.00 | 0.120073E+11 | 0.00 | 0.00 | 0.124402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.219455E+11 | 0.287706E+10 | 0.168545E+11 | 0.00 | 0.122333E+11 | 0.00 | 0.00 | 0.152384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220118E+11 | 0.335947E+10 | 0.160165E+11 | 0.00 | 0.116848E+11 | 0.00 | 0.00 | 0.534082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239756E+11 | 0.410112E+10 | 0.164409E+11 | 0.00 | 0.120534E+11 | 0.00 | 0.00 | 0.517222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242416E+11 | 0.452120E+10 | 0.159174E+11 | 0.00 | 0.127646E+11 | 0.00 | 0.00 | 99810608.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255261E+11 | 0.498625E+10 | 0.163871E+11 | 0.00 | 0.141436E+11 | 0.00 | 0.00 | 315585.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270840E+12 | 0.427666E+11 | 0.195156E+12 | 0.150499E+12 | 0.00 | 0.439163E+11 | |||||||
Minimum of Months | 0.203148E+11 | 0.229283E+10 | 0.149157E+11 | 0.00 | 0.116848E+11 | 0.00 | 0.00 | 11.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.255261E+11 | 0.498625E+10 | 0.168545E+11 | 0.00 | 0.144523E+11 | 0.00 | 0.00 | 0.152384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.702759E+11 | 0.00 | 0.821716E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.463281E+11 | 0.00 | 0.745755E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.209346E+11 | 0.00 | 0.828871E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.722339E+10 | 0.00 | 0.788845E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.414105E+09 | 0.00 | 0.803807E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7484245.21 | 0.00 | 0.770839E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.782009E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.787350E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 23754845.32 | 0.00 | 0.761529E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.426987E+10 | 0.00 | 0.792966E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.313816E+11 | 0.00 | 0.777457E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.581852E+11 | 0.00 | 0.815077E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.239044E+12 | 0.947622E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.745755E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.702759E+11 | 0.00 | 0.828871E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21880.52 | 02-JAN-09:09 | 3292.90 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 11856.66 | 16-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 21880.52 | 01-FEB-09:09 | 3292.90 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 11880.65 | 19-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 21880.52 | 01-MAR-09:09 | 3292.90 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 10312.66 | 05-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 21880.52 | 01-APR-16:00 | 3292.90 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 9723.71 | 18-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 21880.52 | 01-MAY-16:00 | 3292.90 | 01-MAY-19:19 | 10771.04 | 01-MAY-08:09 | 0.00 | 9160.19 | 16-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 20461.84 | 01-JUN-16:19 | 3292.90 | 01-JUN-19:00 | 10771.04 | 01-JUN-08:09 | 0.00 | 9160.19 | 10-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 21880.52 | 12-JUL-08:09 | 3292.90 | 01-JUL-20:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 10384.56 | 30-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 21880.52 | 08-AUG-16:00 | 3292.90 | 01-AUG-19:40 | 10771.04 | 01-AUG-08:09 | 0.00 | 10384.56 | 13-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 21880.52 | 07-SEP-08:09 | 3292.90 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 9160.19 | 02-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21880.52 | 02-OCT-15:39 | 3292.90 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 9415.42 | 30-OCT-07:19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 21880.52 | 01-NOV-08:09 | 3292.90 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 10640.10 | 26-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 21880.52 | 01-DEC-09:09 | 3292.90 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 11645.23 | 25-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 20461.84 | 3292.90 | 10771.04 | 0.00 | 9160.19 | 0.00 | 0.00 | |||||
Maximum of Months | 21880.52 | 3292.90 | 10771.04 | 0.00 | 11880.65 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.01 | 11-JAN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1242.78 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2975.40 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18842.97 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17945.26 | 06-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19911.36 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26561.75 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28542.29 | 10-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20983.01 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10826.55 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7226.07 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 77.47 | 02-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28542.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 45612.18 | 06-JAN-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 9667.73 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45702.86 | 18-FEB-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 9758.41 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44814.05 | 04-MAR-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 8869.59 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 54692.22 | 27-APR-14:00 | 17624.48 | 10771.04 | 0.00 | 0.00 | 7453.74 | 0.00 | 0.00 | 18842.97 | 0.00 |
May | 54233.05 | 04-MAY-15:50 | 20461.84 | 10771.04 | 0.00 | 0.00 | 7453.74 | 0.00 | 0.00 | 15546.44 | 0.00 |
June | 57901.64 | 28-JUN-16:00 | 20461.84 | 10771.04 | 0.00 | 0.00 | 7453.74 | 0.00 | 0.00 | 19215.03 | 0.00 |
July | 64918.72 | 31-JUL-15:00 | 20461.84 | 10771.04 | 0.00 | 0.00 | 8092.79 | 0.00 | 0.00 | 25593.05 | 0.00 |
August | 67992.05 | 10-AUG-15:50 | 20461.84 | 10771.04 | 0.00 | 0.00 | 8604.03 | 0.00 | 0.00 | 28155.14 | 0.00 |
September | 58532.91 | 14-SEP-15:30 | 20461.84 | 10771.04 | 0.00 | 0.00 | 7453.74 | 0.00 | 0.00 | 19846.30 | 0.00 |
October | 50931.84 | 04-OCT-14:00 | 21880.52 | 10771.04 | 0.00 | 0.00 | 7453.74 | 0.00 | 0.00 | 10826.55 | 0.00 |
November | 47331.37 | 04-NOV-14:30 | 21880.52 | 10771.04 | 0.00 | 0.00 | 7453.74 | 0.00 | 0.00 | 7226.07 | 0.00 |
December | 45501.95 | 06-DEC-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 9557.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 44814.05 | 17624.48 | 10771.04 | 0.00 | 0.00 | 7453.74 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67992.05 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 9758.41 | 0.00 | 0.00 | 28155.14 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 158723.17 | 16-JAN-09:09 | 0.00 | 5080.12 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 156727.00 | 19-FEB-09:09 | 0.00 | 5081.10 | 13-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 95600.22 | 06-MAR-07:10 | 0.00 | 5077.53 | 03-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 79172.83 | 19-APR-06:10 | 0.00 | 5058.58 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 30147.10 | 18-MAY-06:49 | 0.00 | 5032.12 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 2753.59 | 15-JUN-06:10 | 0.00 | 5001.48 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4976.60 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4966.45 | 31-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 4751.05 | 28-SEP-06:10 | 0.00 | 4980.92 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 46296.29 | 16-OCT-06:30 | 0.00 | 5011.23 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 127044.69 | 24-NOV-07:10 | 0.00 | 5041.07 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 157997.20 | 26-DEC-07:10 | 0.00 | 5064.70 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4966.45 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 158723.17 | 0.00 | 5081.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.17 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.22 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 93.00 | 11.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 120.00 | 12.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 224.17 | 13.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 153.67 | 13.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71.50 | 14.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15.50 | 14.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25.50 | 14.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 148.33 | 13.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 138.67 | 12.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 105.83 | 12.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1096.17 | 13.07 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 224.17 | 14.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 285.00 | 21.11 | 285.00 | 21.11 |
February | 376.00 | 21.24 | 221.67 | 21.11 | 221.67 | 21.11 |
March | 422.00 | 21.44 | 112.67 | 21.12 | 112.67 | 21.12 |
April | 391.00 | 22.15 | 27.00 | 21.12 | 27.00 | 21.12 |
May | 359.83 | 23.13 | 1.67 | 23.89 | 0.00 | 0.00 |
June | 232.67 | 23.58 | 5.83 | 23.89 | 0.00 | 0.00 |
July | 94.67 | 23.69 | 92.33 | 23.89 | 0.00 | 0.00 |
August | 53.33 | 23.55 | 150.17 | 23.89 | 0.00 | 0.00 |
September | 215.33 | 23.42 | 32.33 | 23.89 | 0.00 | 0.00 |
October | 413.67 | 22.42 | 3.33 | 21.15 | 3.33 | 21.15 |
November | 399.00 | 21.45 | 102.67 | 21.11 | 102.67 | 21.11 |
December | 415.00 | 21.11 | 237.33 | 21.11 | 237.33 | 21.11 |
Annual Sum or Average | 3786.50 | 22.02 | 1272.00 | 21.73 | 989.67 | 21.11 |
Minimum of Months | 53.33 | 21.11 | 1.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.69 | 285.00 | 23.89 | 285.00 | 21.15 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.12 | 117.17 | 21.11 | 117.17 | 21.11 |
February | 376.00 | 21.24 | 73.67 | 21.11 | 73.67 | 21.11 |
March | 422.00 | 21.48 | 9.67 | 21.11 | 9.67 | 21.11 |
April | 367.33 | 22.06 | 14.17 | 23.89 | 0.00 | 0.00 |
May | 227.67 | 22.67 | 50.50 | 23.89 | 0.00 | 0.00 |
June | 76.50 | 23.05 | 110.50 | 23.89 | 0.00 | 0.00 |
July | 26.83 | 23.30 | 254.00 | 23.89 | 0.00 | 0.00 |
August | 23.17 | 23.10 | 302.17 | 23.89 | 0.00 | 0.00 |
September | 115.50 | 22.87 | 146.17 | 23.88 | 0.00 | 0.00 |
October | 359.50 | 22.10 | 1.33 | 23.89 | 0.00 | 0.00 |
November | 393.67 | 21.34 | 14.83 | 21.11 | 14.83 | 21.11 |
December | 415.00 | 21.12 | 64.00 | 21.11 | 64.00 | 21.11 |
Annual Sum or Average | 3217.17 | 21.68 | 1158.17 | 23.22 | 279.33 | 21.11 |
Minimum of Months | 23.17 | 21.12 | 1.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.30 | 302.17 | 23.89 | 117.17 | 21.11 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.48 | 148.33 | 21.11 | 148.33 | 21.11 |
February | 360.17 | 22.06 | 79.00 | 21.11 | 79.00 | 21.11 |
March | 389.50 | 22.74 | 21.50 | 21.11 | 21.50 | 21.11 |
April | 298.33 | 23.06 | 35.33 | 23.53 | 4.50 | 21.11 |
May | 164.33 | 23.33 | 63.67 | 23.89 | 0.00 | 0.00 |
June | 58.17 | 23.62 | 107.67 | 23.89 | 0.00 | 0.00 |
July | 20.17 | 23.83 | 269.67 | 23.89 | 0.00 | 0.00 |
August | 12.50 | 23.72 | 335.00 | 23.89 | 0.00 | 0.00 |
September | 49.50 | 23.50 | 216.00 | 23.89 | 0.00 | 0.00 |
October | 247.50 | 23.18 | 45.33 | 23.89 | 0.00 | 0.00 |
November | 372.17 | 22.31 | 38.83 | 21.87 | 28.17 | 21.11 |
December | 411.17 | 21.74 | 103.33 | 21.11 | 103.33 | 21.11 |
Annual Sum or Average | 2797.50 | 22.41 | 1463.67 | 23.16 | 384.83 | 21.11 |
Minimum of Months | 12.50 | 21.48 | 21.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 414.00 | 23.83 | 335.00 | 23.89 | 148.33 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.13 | 240.33 | 21.11 | 240.33 | 21.11 |
February | 373.17 | 21.38 | 153.00 | 21.11 | 153.00 | 21.11 |
March | 411.00 | 21.73 | 68.50 | 21.11 | 68.50 | 21.11 |
April | 357.50 | 22.20 | 40.67 | 22.39 | 22.00 | 21.12 |
May | 272.17 | 22.65 | 39.83 | 23.81 | 1.17 | 21.25 |
June | 145.17 | 23.00 | 65.67 | 23.89 | 0.00 | 0.00 |
July | 72.83 | 23.27 | 202.17 | 23.89 | 0.00 | 0.00 |
August | 43.17 | 23.03 | 268.00 | 23.89 | 0.00 | 0.00 |
September | 136.50 | 22.84 | 146.33 | 23.89 | 0.00 | 0.00 |
October | 304.50 | 22.09 | 37.17 | 23.53 | 4.83 | 21.16 |
November | 386.67 | 21.38 | 81.83 | 21.30 | 76.33 | 21.11 |
December | 415.00 | 21.25 | 208.33 | 21.11 | 208.33 | 21.11 |
Annual Sum or Average | 3331.67 | 21.83 | 1551.83 | 22.50 | 774.50 | 21.11 |
Minimum of Months | 43.17 | 21.13 | 37.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.27 | 268.00 | 23.89 | 240.33 | 21.25 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09976 | 36.34903 | -0.5752 | 12.09572 |
February | 376.00000 | 21.22488 | 38.00831 | -0.5173 | 11.17747 |
March | 422.00000 | 21.42532 | 39.09051 | -0.4230 | 9.30085 |
April | 405.00000 | 22.19870 | 41.95620 | -0.1904 | 7.13041 |
May | 418.00000 | 23.22883 | 43.65998 | -0.8985 | 23.64335 |
June | 408.00000 | 23.70868 | 42.99923 | -0.6836 | 15.37026 |
July | 415.00000 | 23.84646 | 46.13229 | -0.5674 | 12.00017 |
August | 422.00000 | 23.84896 | 49.38943 | -0.5407 | 11.35497 |
September | 405.00000 | 23.63587 | 49.55691 | -0.6863 | 15.64578 |
October | 414.00000 | 22.41072 | 45.55578 | -0.1058 | 6.41346 |
November | 399.00000 | 21.43307 | 44.60221 | -0.3896 | 9.08160 |
December | 415.00000 | 21.10065 | 38.56897 | -0.5459 | 11.35695 |
Annual Sum or Average | 4913.00000 | 22.44052 | 43.01688 | -0.5109 | 12.06542 |
Minimum of Months | 376.00000 | 21.09976 | 36.34903 | -0.8985 | 6.41346 |
Maximum of Months | 422.00000 | 23.84896 | 49.55691 | -0.1058 | 23.64335 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10726 | 33.41527 | -0.4870 | 10.10802 |
February | 376.00000 | 21.23676 | 34.96347 | -0.4187 | 9.18884 |
March | 422.00000 | 21.48204 | 35.61217 | -0.3098 | 7.56472 |
April | 405.00000 | 22.23727 | 38.97405 | -0.0841 | 6.48021 |
May | 418.00000 | 23.22980 | 41.76735 | -0.7561 | 18.60844 |
June | 408.00000 | 23.72701 | 41.97663 | -0.5504 | 11.81171 |
July | 415.00000 | 23.85226 | 45.36709 | -0.4518 | 9.53507 |
August | 422.00000 | 23.84973 | 48.67287 | -0.4358 | 9.22870 |
September | 405.00000 | 23.58093 | 48.12966 | -0.5860 | 13.03712 |
October | 414.00000 | 22.34022 | 42.90323 | -0.0336 | 6.20277 |
November | 399.00000 | 21.37748 | 41.88538 | -0.3174 | 7.85102 |
December | 415.00000 | 21.10875 | 35.46235 | -0.4573 | 9.46974 |
Annual Sum or Average | 4913.00000 | 22.43797 | 40.79567 | -0.4078 | 9.93610 |
Minimum of Months | 376.00000 | 21.10726 | 33.41527 | -0.7561 | 6.20277 |
Maximum of Months | 422.00000 | 23.85226 | 48.67287 | -0.0336 | 18.60844 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.46295 | 32.27658 | -0.4423 | 9.85851 |
February | 376.00000 | 22.13085 | 32.51740 | -0.2454 | 8.33746 |
March | 422.00000 | 22.81710 | 32.21308 | -0.0546 | 6.71552 |
April | 405.00000 | 23.27260 | 35.18710 | 0.11432 | 6.79954 |
May | 418.00000 | 23.67070 | 38.59206 | -0.6516 | 15.10102 |
June | 408.00000 | 23.86033 | 40.01826 | -0.5265 | 11.14393 |
July | 415.00000 | 23.90397 | 44.34299 | -0.4240 | 9.02576 |
August | 422.00000 | 23.90209 | 47.52367 | -0.3739 | 8.23362 |
September | 405.00000 | 23.85435 | 45.38858 | -0.4562 | 10.04778 |
October | 414.00000 | 23.46583 | 38.33469 | 0.20556 | 6.94861 |
November | 399.00000 | 22.40641 | 38.77921 | -0.1301 | 7.30758 |
December | 415.00000 | 21.74697 | 33.85542 | -0.3507 | 8.85832 |
Annual Sum or Average | 4913.00000 | 23.04870 | 38.29144 | -0.2789 | 9.04158 |
Minimum of Months | 376.00000 | 21.46295 | 32.21308 | -0.6516 | 6.71552 |
Maximum of Months | 422.00000 | 23.90397 | 47.52367 | 0.20556 | 15.10102 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.12042 | 32.77396 | -0.5542 | 11.68747 |
February | 376.00000 | 21.38564 | 34.14286 | -0.4328 | 10.00014 |
March | 422.00000 | 21.77051 | 34.73718 | -0.2974 | 8.22792 |
April | 405.00000 | 22.37973 | 38.32478 | -0.0958 | 7.24007 |
May | 418.00000 | 23.06064 | 42.03720 | -0.8745 | 23.70335 |
June | 408.00000 | 23.55513 | 43.20147 | -0.6608 | 15.43715 |
July | 415.00000 | 23.76928 | 45.89164 | -0.5185 | 11.27109 |
August | 422.00000 | 23.79181 | 48.60653 | -0.4616 | 10.13490 |
September | 405.00000 | 23.51721 | 47.40738 | -0.6075 | 14.57256 |
October | 414.00000 | 22.54385 | 41.96411 | -0.0072 | 7.01937 |
November | 399.00000 | 21.44645 | 40.90586 | -0.3616 | 8.94512 |
December | 415.00000 | 21.23457 | 34.67843 | -0.4954 | 10.69923 |
Annual Sum or Average | 4913.00000 | 22.47448 | 40.42899 | -0.4479 | 11.59801 |
Minimum of Months | 376.00000 | 21.12042 | 32.77396 | -0.8745 | 7.01937 |
Maximum of Months | 422.00000 | 23.79181 | 48.60653 | -0.0072 | 23.70335 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.316103E+09 | 84932719.37 | 29.96 | 0.279449E+09 | 36653771.14 | 0.00 | 0.64 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7901.51 | 27-APR-15:00 | 6780.33 | 27-APR-15:00 | 1121.19 | 27-APR-15:00 | 2064.46 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.964454E+09 | 0.248258E+09 | 128.38 | 0.818720E+09 | 0.145734E+09 | 0.00 | 0.72 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 | 9321.69 | 06-MAY-13:50 | 7273.11 | 06-MAY-14:00 | 2104.41 | 06-MAY-13:20 | 2245.23 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 |
June | 0.228927E+10 | 0.584248E+09 | 235.41 | 0.204752E+10 | 0.241748E+09 | 0.00 | 0.81 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 14135.05 | 29-JUN-06:02 | 9499.88 | 29-JUN-06:02 | 4635.17 | 29-JUN-06:02 | 2999.36 | 29-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.563242E+10 | 0.139660E+10 | 301.34 | 0.460461E+10 | 0.102781E+10 | 0.00 | 1.00 | 23-JUL-08:62 | 0.00 | 01-JUL-00:10 | 27691.24 | 31-JUL-06:02 | 21372.33 | 23-JUL-08:62 | 10420.74 | 25-JUL-06:02 | 5895.04 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.712351E+10 | 0.176412E+10 | 319.51 | 0.577036E+10 | 0.135315E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27974.37 | 25-AUG-06:02 | 21578.27 | 13-AUG-08:62 | 11272.75 | 26-AUG-06:02 | 5950.28 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.190859E+10 | 0.477168E+09 | 187.25 | 0.148332E+10 | 0.425267E+09 | 0.00 | 0.82 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 | 13263.41 | 14-SEP-06:02 | 8538.72 | 14-SEP-15:00 | 5382.20 | 14-SEP-06:02 | 2821.26 | 14-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 42959217.32 | 11499229.26 | 39.78 | 42953250.76 | 5966.56 | 0.00 | 0.32 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3373.35 | 04-OCT-15:00 | 3373.35 | 04-OCT-15:00 | 0.25 | 02-OCT-14:10 | 886.90 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 5713838.34 | 1591203.30 | 4.50 | 4092674.21 | 1621164.13 | 0.00 | 0.09 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 | 996.56 | 04-NOV-15:00 | 720.53 | 04-NOV-15:00 | 276.03 | 04-NOV-15:00 | 276.28 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.182830E+11 | 0.456842E+10 | 1246.13 | 0.150510E+11 | 0.323199E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.712351E+10 | 0.176412E+10 | 319.51 | 0.577036E+10 | 0.135315E+10 | 0.00 | 1.00 | 0.00 | 27974.37 | 21578.27 | 11272.75 | 5950.28 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 3545.86 | 1123.84 | 0.50 | 3390.83 | 155.03 | 0.00 | 0.00 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 | 4.61 | 27-FEB-14:50 | 4.41 | 27-FEB-14:50 | 0.20 | 27-FEB-14:50 | 1.46 | 27-FEB-14:50 | 0.00 | 01-FEB-00:10 |
March | 32048719.04 | 9913072.09 | 3.75 | 32048596.59 | 122.45 | 0.00 | 0.13 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 5742.78 | 18-MAR-16:00 | 5742.78 | 18-MAR-16:00 | 0.35 | 18-MAR-13:20 | 1756.15 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.275052E+10 | 0.794653E+09 | 45.56 | 0.250748E+10 | 0.243043E+09 | 0.00 | 0.82 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 99675.93 | 28-APR-06:02 | 68350.19 | 28-APR-06:02 | 31325.74 | 28-APR-06:02 | 23588.46 | 28-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.737570E+10 | 0.206332E+10 | 137.73 | 0.629212E+10 | 0.108358E+10 | 0.00 | 1.00 | 05-MAY-06:02 | 0.00 | 01-MAY-00:10 | 123780.65 | 07-MAY-08:62 | 89724.58 | 05-MAY-06:02 | 36455.58 | 07-MAY-08:62 | 29447.96 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.161126E+11 | 0.448464E+10 | 254.80 | 0.143278E+11 | 0.178478E+10 | 0.00 | 1.00 | 10-JUN-06:03 | 0.00 | 01-JUN-00:10 | 121489.85 | 12-JUN-06:02 | 101156.81 | 25-JUN-08:62 | 41169.15 | 12-JUN-06:02 | 28909.38 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.332248E+11 | 0.897576E+10 | 323.01 | 0.273753E+11 | 0.584948E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 124233.35 | 31-JUL-06:02 | 101422.35 | 02-JUL-08:62 | 44656.75 | 16-JUL-08:62 | 29548.41 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.396578E+11 | 0.107381E+11 | 338.46 | 0.324466E+11 | 0.721122E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 125414.94 | 30-AUG-06:02 | 98591.46 | 13-AUG-08:62 | 47868.12 | 26-AUG-06:03 | 29800.93 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.129074E+11 | 0.352280E+10 | 191.29 | 0.100331E+11 | 0.287430E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 122148.53 | 24-SEP-08:62 | 88929.37 | 04-SEP-08:62 | 51236.13 | 24-SEP-08:62 | 29069.31 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.679284E+09 | 0.199437E+09 | 45.16 | 0.655106E+09 | 24178114.91 | 0.00 | 0.49 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 24686.70 | 04-OCT-15:00 | 24686.70 | 04-OCT-15:00 | 2002.06 | 05-OCT-06:02 | 6904.91 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.163432E+09 | 48699526.20 | 5.58 | 0.116931E+09 | 46501422.70 | 0.00 | 0.29 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 14577.18 | 04-NOV-14:40 | 10657.27 | 04-NOV-14:40 | 3924.22 | 04-NOV-14:30 | 4290.72 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.112904E+12 | 0.308373E+11 | 1345.85 | 0.937866E+11 | 0.191171E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.396578E+11 | 0.107381E+11 | 338.46 | 0.324466E+11 | 0.721122E+10 | 0.00 | 1.00 | 0.00 | 125414.94 | 101422.35 | 51236.13 | 29800.93 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 46.99 | 11.64 | 0.42 | 46.53 | 0.46 | 0.00 | 0.00 | 11-JAN-13:45 | 0.00 | 01-JAN-00:10 | 0.07 | 11-JAN-13:45 | 0.07 | 11-JAN-13:45 | 0.00 | 11-JAN-16:25 | 0.02 | 11-JAN-13:45 | 0.00 | 01-JAN-00:10 |
February | 18617052.17 | 4326974.37 | 33.43 | 18614757.90 | 2294.28 | 0.00 | 0.33 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 2625.78 | 27-FEB-15:00 | 2625.78 | 27-FEB-15:00 | 0.65 | 27-FEB-16:50 | 595.18 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 33798647.52 | 7659747.85 | 76.40 | 33797129.85 | 1517.67 | 0.00 | 0.39 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3146.28 | 18-MAR-14:00 | 3146.28 | 18-MAR-14:00 | 0.55 | 18-MAR-13:00 | 700.01 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.704167E+09 | 0.151476E+09 | 139.64 | 0.676040E+09 | 28126873.73 | 0.00 | 1.00 | 28-APR-06:02 | 0.00 | 01-APR-00:10 | 17843.58 | 28-APR-06:02 | 12669.50 | 28-APR-06:02 | 5174.08 | 28-APR-06:02 | 3485.68 | 28-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.125879E+10 | 0.268969E+09 | 196.78 | 0.114049E+10 | 0.118302E+09 | 0.00 | 1.00 | 05-MAY-06:02 | 0.00 | 01-MAY-00:10 | 18910.72 | 07-MAY-08:62 | 14064.86 | 05-MAY-06:02 | 5284.42 | 07-MAY-08:62 | 3715.28 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.223351E+10 | 0.483188E+09 | 266.34 | 0.213748E+10 | 96031249.09 | 0.00 | 1.00 | 11-JUN-08:62 | 0.00 | 01-JUN-00:10 | 18638.76 | 12-JUN-06:02 | 14332.02 | 28-JUN-06:02 | 6453.67 | 12-JUN-06:02 | 3661.91 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.499577E+10 | 0.105514E+10 | 318.66 | 0.441329E+10 | 0.582483E+09 | 0.00 | 1.00 | 08-JUL-06:02 | 0.00 | 01-JUL-00:10 | 19033.69 | 31-JUL-06:02 | 15160.83 | 23-JUL-08:62 | 6872.17 | 25-JUL-06:02 | 3738.16 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.684774E+10 | 0.143337E+10 | 336.37 | 0.602794E+10 | 0.819797E+09 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 19217.01 | 25-AUG-06:02 | 15219.16 | 13-AUG-08:62 | 7473.10 | 26-AUG-06:02 | 3770.77 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.299659E+10 | 0.608115E+09 | 245.02 | 0.251673E+10 | 0.479856E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 18686.01 | 01-SEP-06:02 | 13060.63 | 10-SEP-08:62 | 7712.93 | 24-SEP-08:62 | 3671.45 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.390278E+09 | 83385971.65 | 146.50 | 0.377383E+09 | 12894895.43 | 0.00 | 0.89 | 04-OCT-14:30 | 0.00 | 01-OCT-00:10 | 15863.06 | 05-OCT-06:02 | 14444.56 | 05-OCT-06:02 | 1418.50 | 05-OCT-06:02 | 3073.83 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.114634E+09 | 23891626.49 | 33.86 | 88543584.64 | 26090765.87 | 0.00 | 0.77 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 7491.26 | 04-NOV-14:00 | 5983.37 | 04-NOV-14:00 | 1603.10 | 04-NOV-13:20 | 1497.79 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 3679.28 | 906.92 | 7.99 | 3679.28 | 0.00 | 0.00 | 0.00 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 | 0.35 | 02-DEC-13:00 | 0.35 | 02-DEC-13:00 | 0.00 | 02-DEC-13:30 | 0.09 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.195939E+11 | 0.411952E+10 | 1801.40 | 0.174303E+11 | 0.216359E+10 | 0.00 | ||||||||||||||
Minimum of Months | 46.99 | 11.64 | 0.42 | 46.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 0.07 | 0.00 | 0.02 | 0.00 | |||||||
Maximum of Months | 0.684774E+10 | 0.143337E+10 | 336.37 | 0.602794E+10 | 0.819797E+09 | 0.00 | 1.00 | 0.00 | 19217.01 | 15219.16 | 7712.93 | 3770.77 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 39110573.42 | 8930260.58 | 6.36 | 38949405.49 | 161167.93 | 0.00 | 0.42 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 2922.97 | 27-FEB-15:10 | 2922.97 | 27-FEB-15:10 | 23.42 | 27-FEB-17:00 | 648.04 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.110369E+09 | 25441622.35 | 25.39 | 0.110105E+09 | 263645.55 | 0.00 | 0.46 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 3196.27 | 18-MAR-14:00 | 3196.27 | 18-MAR-14:00 | 40.93 | 10-MAR-13:20 | 700.88 | 18-MAR-13:55 | 0.00 | 01-MAR-00:10 |
April | 0.718854E+09 | 0.159272E+09 | 84.83 | 0.679905E+09 | 38949103.29 | 0.00 | 0.91 | 27-APR-14:10 | 0.00 | 01-APR-00:10 | 7412.59 | 27-APR-14:20 | 6975.31 | 27-APR-14:10 | 846.76 | 28-APR-12:55 | 1542.20 | 27-APR-14:40 | 0.00 | 01-APR-00:10 |
May | 0.145180E+10 | 0.322128E+09 | 189.56 | 0.132594E+10 | 0.125858E+09 | 0.00 | 0.80 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6469.56 | 06-MAY-13:30 | 5435.80 | 06-MAY-13:40 | 1053.03 | 06-MAY-13:10 | 1325.91 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.261229E+10 | 0.578145E+09 | 286.12 | 0.243952E+10 | 0.172773E+09 | 0.00 | 0.81 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 6353.30 | 28-JUN-16:00 | 6152.62 | 28-JUN-15:00 | 752.39 | 12-JUN-15:00 | 1355.77 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.471062E+10 | 0.101272E+10 | 350.06 | 0.417188E+10 | 0.538747E+09 | 0.00 | 1.00 | 24-JUL-13:30 | 0.00 | 01-JUL-00:10 | 9315.04 | 31-JUL-14:10 | 8263.74 | 24-JUL-15:00 | 1492.43 | 31-JUL-06:02 | 1942.94 | 31-JUL-14:10 | 0.00 | 01-JUL-00:10 |
August | 0.614190E+10 | 0.130286E+10 | 372.78 | 0.535712E+10 | 0.784786E+09 | 0.00 | 1.00 | 10-AUG-06:02 | 0.00 | 01-AUG-00:10 | 15913.50 | 25-AUG-06:02 | 13637.31 | 13-AUG-08:62 | 3411.30 | 25-AUG-06:02 | 3113.50 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.353970E+10 | 0.732736E+09 | 264.48 | 0.308531E+10 | 0.454395E+09 | 0.00 | 1.00 | 15-SEP-11:55 | 0.00 | 01-SEP-00:10 | 9930.07 | 14-SEP-13:30 | 8465.47 | 14-SEP-14:10 | 1726.31 | 14-SEP-11:40 | 1927.03 | 14-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 0.103299E+10 | 0.222900E+09 | 118.28 | 0.991660E+09 | 41331739.31 | 0.00 | 0.95 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 | 7707.04 | 04-OCT-14:10 | 7707.04 | 04-OCT-14:10 | 615.29 | 01-OCT-13:30 | 1455.10 | 04-OCT-14:10 | 0.00 | 01-OCT-00:10 |
November | 0.121489E+09 | 25628252.93 | 11.25 | 99067187.89 | 22421352.23 | 0.00 | 0.76 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6035.20 | 04-NOV-14:00 | 4989.46 | 04-NOV-14:10 | 1076.22 | 04-NOV-13:30 | 1209.54 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 1290065.33 | 314679.02 | 1.67 | 1290065.33 | 0.00 | 0.00 | 0.05 | 02-DEC-13:30 | 0.00 | 01-DEC-00:10 | 318.24 | 02-DEC-13:30 | 318.24 | 02-DEC-13:30 | 0.00 | 01-DEC-00:10 | 77.40 | 02-DEC-13:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.204804E+11 | 0.439107E+10 | 1710.79 | 0.183007E+11 | 0.217969E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.614190E+10 | 0.130286E+10 | 372.78 | 0.535712E+10 | 0.784786E+09 | 0.00 | 1.00 | 0.00 | 15913.50 | 13637.31 | 3411.30 | 3113.50 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 9.07 | 68.15 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.54 | 60.64 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 64.10 | 50.42 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.96 | 41.50 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.80 | 36.81 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.58 | 30.76 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 195.07 | 29.13 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.82 | 29.88 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 102.28 | 39.54 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 50.18 | 48.97 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 16.29 | 55.50 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.33 | 70.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 91.34 | 46.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.33 | 29.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 195.07 | 70.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 617.57 | 366.63 | 250.93 | 518.72 | 805.39 | 0.00 | 0.00 | 744.00 |
February | 950.05 | 588.11 | 361.95 | 884.86 | 733.64 | 0.00 | 0.00 | 672.00 |
March | 1022.36 | 545.40 | 476.95 | 930.78 | 653.20 | 0.00 | 0.00 | 744.00 |
April | 1079.07 | 468.58 | 610.50 | 913.93 | 544.06 | 0.00 | 0.00 | 720.00 |
May | 986.46 | 293.78 | 692.68 | 754.27 | 469.21 | 0.00 | 0.00 | 744.00 |
June | 902.50 | 242.21 | 660.29 | 660.94 | 378.18 | 0.00 | 0.00 | 720.00 |
July | 984.19 | 360.36 | 623.84 | 805.30 | 346.97 | 0.00 | 0.00 | 744.00 |
August | 1057.49 | 493.08 | 564.41 | 998.15 | 342.25 | 0.00 | 0.00 | 744.00 |
September | 1172.12 | 647.45 | 524.67 | 1152.55 | 471.02 | 0.00 | 0.00 | 720.00 |
October | 1061.69 | 655.62 | 406.07 | 1065.41 | 604.79 | 0.00 | 0.00 | 744.00 |
November | 627.41 | 359.51 | 267.91 | 554.15 | 691.03 | 0.00 | 0.00 | 720.00 |
December | 656.37 | 424.68 | 231.68 | 616.15 | 828.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 926.04 | 452.95 | 473.09 | 820.76 | 571.57 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 617.57 | 242.21 | 231.68 | 518.72 | 342.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1172.12 | 655.62 | 692.68 | 1152.55 | 828.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 617.57 | 366.63 | 250.93 | 521.75 | 783.87 | 0.00 | 0.00 | 744.00 |
February | 950.05 | 588.11 | 361.95 | 893.43 | 700.35 | 0.00 | 0.00 | 672.00 |
March | 1022.36 | 545.40 | 476.95 | 943.34 | 608.90 | 0.00 | 0.00 | 744.00 |
April | 1079.07 | 468.58 | 610.50 | 927.50 | 506.21 | 0.00 | 0.00 | 720.00 |
May | 986.46 | 293.78 | 692.68 | 764.90 | 439.00 | 0.00 | 0.00 | 744.00 |
June | 902.50 | 242.21 | 660.29 | 665.39 | 356.94 | 0.00 | 0.00 | 720.00 |
July | 984.19 | 360.36 | 623.84 | 805.51 | 328.52 | 0.00 | 0.00 | 744.00 |
August | 1057.49 | 493.08 | 564.41 | 996.69 | 325.43 | 0.00 | 0.00 | 744.00 |
September | 1172.12 | 647.45 | 524.67 | 1154.77 | 447.27 | 0.00 | 0.00 | 720.00 |
October | 1061.69 | 655.62 | 406.07 | 1075.31 | 563.09 | 0.00 | 0.00 | 744.00 |
November | 627.41 | 359.51 | 267.91 | 564.13 | 648.68 | 0.00 | 0.00 | 720.00 |
December | 656.37 | 424.68 | 231.68 | 621.07 | 800.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 926.04 | 452.95 | 473.09 | 827.27 | 541.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 617.57 | 242.21 | 231.68 | 521.75 | 325.43 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1172.12 | 655.62 | 692.68 | 1154.77 | 800.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.07 | 75.44 | 51.63 | 115.47 | 135.08 | 0.00 | 0.00 | 744.00 |
February | 195.49 | 121.01 | 74.48 | 195.70 | 121.71 | 0.00 | 0.00 | 672.00 |
March | 210.36 | 112.22 | 98.14 | 211.13 | 102.29 | 0.00 | 0.00 | 744.00 |
April | 222.03 | 96.42 | 125.62 | 208.37 | 88.93 | 0.00 | 0.00 | 720.00 |
May | 202.98 | 60.45 | 142.53 | 173.08 | 79.00 | 0.00 | 0.00 | 744.00 |
June | 185.70 | 49.84 | 135.86 | 148.35 | 66.48 | 0.00 | 0.00 | 720.00 |
July | 202.51 | 74.15 | 128.36 | 170.59 | 63.85 | 0.00 | 0.00 | 744.00 |
August | 217.59 | 101.46 | 116.14 | 205.19 | 65.50 | 0.00 | 0.00 | 744.00 |
September | 241.18 | 133.22 | 107.96 | 247.25 | 82.53 | 0.00 | 0.00 | 720.00 |
October | 218.46 | 134.90 | 83.55 | 235.24 | 95.77 | 0.00 | 0.00 | 744.00 |
November | 129.10 | 73.97 | 55.13 | 126.11 | 108.69 | 0.00 | 0.00 | 720.00 |
December | 135.06 | 87.38 | 47.67 | 135.60 | 137.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 190.55 | 93.20 | 97.35 | 180.87 | 95.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 127.07 | 49.84 | 47.67 | 115.47 | 63.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 241.18 | 134.90 | 142.53 | 247.25 | 137.85 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 24296661.36 | 0.182539E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 76307997.58 | 0.146690E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.171682E+09 | 0.135050E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.308352E+09 | 0.107566E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.433354E+09 | 98596190.67 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.465462E+09 | 79735269.76 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.522481E+09 | 78031865.07 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.417337E+09 | 80020049.40 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.265099E+09 | 0.102484E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.134399E+09 | 0.131167E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 42211139.01 | 0.143861E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 0.189173E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.288060E+10 | 0.147491E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19620774.57 | 78031865.07 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.522481E+09 | 0.189173E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165409E+10 | 0.981990E+09 | 0.672096E+09 | 0.138935E+10 | 0.215716E+10 |
February | 0.229837E+10 | 0.142275E+10 | 0.875618E+09 | 0.214065E+10 | 0.177483E+10 |
March | 0.273828E+10 | 0.146080E+10 | 0.127748E+10 | 0.249300E+10 | 0.174954E+10 |
April | 0.279696E+10 | 0.121455E+10 | 0.158240E+10 | 0.236890E+10 | 0.141020E+10 |
May | 0.264212E+10 | 0.786857E+09 | 0.185527E+10 | 0.202023E+10 | 0.125674E+10 |
June | 0.233929E+10 | 0.627820E+09 | 0.171147E+10 | 0.171317E+10 | 0.980231E+09 |
July | 0.263606E+10 | 0.965177E+09 | 0.167089E+10 | 0.215691E+10 | 0.929322E+09 |
August | 0.283239E+10 | 0.132068E+10 | 0.151172E+10 | 0.267345E+10 | 0.916685E+09 |
September | 0.303814E+10 | 0.167819E+10 | 0.135995E+10 | 0.298741E+10 | 0.122088E+10 |
October | 0.284363E+10 | 0.175602E+10 | 0.108761E+10 | 0.285360E+10 | 0.161986E+10 |
November | 0.162625E+10 | 0.931842E+09 | 0.694413E+09 | 0.143637E+10 | 0.179115E+10 |
December | 0.175801E+10 | 0.113747E+10 | 0.620540E+09 | 0.165028E+10 | 0.221859E+10 |
Annual Sum or Average | 0.292036E+11 | 0.142842E+11 | 0.149194E+11 | 0.258833E+11 | 0.180252E+11 |
Minimum of Months | 0.162625E+10 | 0.627820E+09 | 0.620540E+09 | 0.138935E+10 | 0.916685E+09 |
Maximum of Months | 0.303814E+10 | 0.175602E+10 | 0.185527E+10 | 0.298741E+10 | 0.221859E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.165409E+10 | 0.981990E+09 | 0.672096E+09 | 0.139745E+10 | 0.209951E+10 |
February | 0.229837E+10 | 0.142275E+10 | 0.875618E+09 | 0.216137E+10 | 0.169428E+10 |
March | 0.273828E+10 | 0.146080E+10 | 0.127748E+10 | 0.252664E+10 | 0.163087E+10 |
April | 0.279696E+10 | 0.121455E+10 | 0.158240E+10 | 0.240407E+10 | 0.131210E+10 |
May | 0.264212E+10 | 0.786857E+09 | 0.185527E+10 | 0.204872E+10 | 0.117582E+10 |
June | 0.233929E+10 | 0.627820E+09 | 0.171147E+10 | 0.172468E+10 | 0.925192E+09 |
July | 0.263606E+10 | 0.965177E+09 | 0.167089E+10 | 0.215749E+10 | 0.879919E+09 |
August | 0.283239E+10 | 0.132068E+10 | 0.151172E+10 | 0.266953E+10 | 0.871623E+09 |
September | 0.303814E+10 | 0.167819E+10 | 0.135995E+10 | 0.299315E+10 | 0.115932E+10 |
October | 0.284363E+10 | 0.175602E+10 | 0.108761E+10 | 0.288012E+10 | 0.150817E+10 |
November | 0.162625E+10 | 0.931842E+09 | 0.694413E+09 | 0.146222E+10 | 0.168138E+10 |
December | 0.175801E+10 | 0.113747E+10 | 0.620540E+09 | 0.166348E+10 | 0.214467E+10 |
Annual Sum or Average | 0.292036E+11 | 0.142842E+11 | 0.149194E+11 | 0.260889E+11 | 0.170829E+11 |
Minimum of Months | 0.162625E+10 | 0.627820E+09 | 0.620540E+09 | 0.139745E+10 | 0.871623E+09 |
Maximum of Months | 0.303814E+10 | 0.175602E+10 | 0.185527E+10 | 0.299315E+10 | 0.214467E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340352E+09 | 0.202059E+09 | 0.138294E+09 | 0.309287E+09 | 0.361788E+09 |
February | 0.472923E+09 | 0.292752E+09 | 0.180171E+09 | 0.473438E+09 | 0.294448E+09 |
March | 0.563440E+09 | 0.300581E+09 | 0.262859E+09 | 0.565497E+09 | 0.273982E+09 |
April | 0.575515E+09 | 0.249912E+09 | 0.325603E+09 | 0.540084E+09 | 0.230506E+09 |
May | 0.543655E+09 | 0.161907E+09 | 0.381748E+09 | 0.463571E+09 | 0.211581E+09 |
June | 0.481343E+09 | 0.129183E+09 | 0.352160E+09 | 0.384526E+09 | 0.172315E+09 |
July | 0.542408E+09 | 0.198599E+09 | 0.343809E+09 | 0.456904E+09 | 0.171021E+09 |
August | 0.582806E+09 | 0.271748E+09 | 0.311058E+09 | 0.549574E+09 | 0.175442E+09 |
September | 0.625141E+09 | 0.345312E+09 | 0.279829E+09 | 0.640881E+09 | 0.213906E+09 |
October | 0.585118E+09 | 0.361327E+09 | 0.223791E+09 | 0.630054E+09 | 0.256506E+09 |
November | 0.334626E+09 | 0.191740E+09 | 0.142886E+09 | 0.326871E+09 | 0.281724E+09 |
December | 0.361736E+09 | 0.234051E+09 | 0.127685E+09 | 0.363195E+09 | 0.369220E+09 |
Annual Sum or Average | 0.600906E+10 | 0.293917E+10 | 0.306989E+10 | 0.570388E+10 | 0.301244E+10 |
Minimum of Months | 0.334626E+09 | 0.129183E+09 | 0.127685E+09 | 0.309287E+09 | 0.171021E+09 |
Maximum of Months | 0.625141E+09 | 0.361327E+09 | 0.381748E+09 | 0.640881E+09 | 0.369220E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 145.14 | 1090.44 | 373.27 | 86.35 | 286.92 | 0.00 | 0.00 |
February | 504.68 | 970.17 | 685.68 | 259.72 | 425.95 | 0.00 | 0.00 |
March | 1025.58 | 806.75 | 1108.16 | 470.70 | 637.46 | 0.00 | 0.00 |
April | 1903.41 | 663.99 | 1776.99 | 904.23 | 872.76 | 0.00 | 0.00 |
May | 2588.73 | 588.99 | 2295.61 | 1177.15 | 1118.46 | 0.00 | 0.00 |
June | 2873.22 | 492.19 | 2500.32 | 1454.40 | 1045.92 | 0.00 | 0.00 |
July | 3121.15 | 466.14 | 2612.91 | 1715.65 | 897.26 | 0.00 | 0.00 |
August | 2493.05 | 478.02 | 2091.89 | 1321.60 | 770.29 | 0.00 | 0.00 |
September | 1636.41 | 632.62 | 1485.92 | 823.94 | 661.98 | 0.00 | 0.00 |
October | 802.86 | 783.56 | 866.06 | 397.52 | 468.54 | 0.00 | 0.00 |
November | 260.56 | 888.03 | 438.01 | 114.54 | 323.47 | 0.00 | 0.00 |
December | 117.21 | 1130.07 | 315.18 | 81.42 | 233.76 | 0.00 | 0.00 |
Annual Sum or Average | 1461.49 | 748.31 | 1382.99 | 736.84 | 646.15 | 0.00 | 0.00 |
Minimum of Months | 117.21 | 466.14 | 315.18 | 81.42 | 233.76 | 0.00 | 0.00 |
Maximum of Months | 3121.15 | 1130.07 | 2612.91 | 1715.65 | 1118.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 518.72 | 805.39 | 617.57 | 366.63 | 250.93 | 0.00 | 0.00 |
February | 884.86 | 733.64 | 950.05 | 588.11 | 361.95 | 0.00 | 0.00 |
March | 930.78 | 653.20 | 1022.36 | 545.40 | 476.95 | 0.00 | 0.00 |
April | 913.93 | 544.06 | 1079.07 | 468.58 | 610.50 | 0.00 | 0.00 |
May | 754.27 | 469.21 | 986.46 | 293.78 | 692.68 | 0.00 | 0.00 |
June | 660.94 | 378.18 | 902.50 | 242.21 | 660.29 | 0.00 | 0.00 |
July | 805.30 | 346.97 | 984.19 | 360.36 | 623.84 | 0.00 | 0.00 |
August | 998.15 | 342.25 | 1057.49 | 493.08 | 564.41 | 0.00 | 0.00 |
September | 1152.55 | 471.02 | 1172.12 | 647.45 | 524.67 | 0.00 | 0.00 |
October | 1065.41 | 604.79 | 1061.69 | 655.62 | 406.07 | 0.00 | 0.00 |
November | 554.15 | 691.03 | 627.41 | 359.51 | 267.91 | 0.00 | 0.00 |
December | 616.15 | 828.32 | 656.37 | 424.68 | 231.68 | 0.00 | 0.00 |
Annual Sum or Average | 820.76 | 571.57 | 926.04 | 452.95 | 473.09 | 0.00 | 0.00 |
Minimum of Months | 518.72 | 342.25 | 617.57 | 242.21 | 231.68 | 0.00 | 0.00 |
Maximum of Months | 1152.55 | 828.32 | 1172.12 | 655.62 | 692.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 521.75 | 783.87 | 617.57 | 366.63 | 250.93 | 0.00 | 0.00 |
February | 893.43 | 700.35 | 950.05 | 588.11 | 361.95 | 0.00 | 0.00 |
March | 943.34 | 608.90 | 1022.36 | 545.40 | 476.95 | 0.00 | 0.00 |
April | 927.50 | 506.21 | 1079.07 | 468.58 | 610.50 | 0.00 | 0.00 |
May | 764.90 | 439.00 | 986.46 | 293.78 | 692.68 | 0.00 | 0.00 |
June | 665.39 | 356.94 | 902.50 | 242.21 | 660.29 | 0.00 | 0.00 |
July | 805.51 | 328.52 | 984.19 | 360.36 | 623.84 | 0.00 | 0.00 |
August | 996.69 | 325.43 | 1057.49 | 493.08 | 564.41 | 0.00 | 0.00 |
September | 1154.77 | 447.27 | 1172.12 | 647.45 | 524.67 | 0.00 | 0.00 |
October | 1075.31 | 563.09 | 1061.69 | 655.62 | 406.07 | 0.00 | 0.00 |
November | 564.13 | 648.68 | 627.41 | 359.51 | 267.91 | 0.00 | 0.00 |
December | 621.07 | 800.73 | 656.37 | 424.68 | 231.68 | 0.00 | 0.00 |
Annual Sum or Average | 827.27 | 541.69 | 926.04 | 452.95 | 473.09 | 0.00 | 0.00 |
Minimum of Months | 521.75 | 325.43 | 617.57 | 242.21 | 231.68 | 0.00 | 0.00 |
Maximum of Months | 1154.77 | 800.73 | 1172.12 | 655.62 | 692.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 115.47 | 135.08 | 127.07 | 75.44 | 51.63 | 0.00 | 0.00 |
February | 195.70 | 121.71 | 195.49 | 121.01 | 74.48 | 0.00 | 0.00 |
March | 211.13 | 102.29 | 210.36 | 112.22 | 98.14 | 0.00 | 0.00 |
April | 208.37 | 88.93 | 222.03 | 96.42 | 125.62 | 0.00 | 0.00 |
May | 173.08 | 79.00 | 202.98 | 60.45 | 142.53 | 0.00 | 0.00 |
June | 148.35 | 66.48 | 185.70 | 49.84 | 135.86 | 0.00 | 0.00 |
July | 170.59 | 63.85 | 202.51 | 74.15 | 128.36 | 0.00 | 0.00 |
August | 205.19 | 65.50 | 217.59 | 101.46 | 116.14 | 0.00 | 0.00 |
September | 247.25 | 82.53 | 241.18 | 133.22 | 107.96 | 0.00 | 0.00 |
October | 235.24 | 95.77 | 218.46 | 134.90 | 83.55 | 0.00 | 0.00 |
November | 126.11 | 108.69 | 129.10 | 73.97 | 55.13 | 0.00 | 0.00 |
December | 135.60 | 137.85 | 135.06 | 87.38 | 47.67 | 0.00 | 0.00 |
Annual Sum or Average | 180.87 | 95.52 | 190.55 | 93.20 | 97.35 | 0.00 | 0.00 |
Minimum of Months | 115.47 | 63.85 | 127.07 | 49.84 | 47.67 | 0.00 | 0.00 |
Maximum of Months | 247.25 | 137.85 | 241.18 | 134.90 | 142.53 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.388747E+09 | 0.292062E+10 | 0.999755E+09 | 0.231279E+09 | 0.768477E+09 | 0.00 | 0.00 |
February | 0.122093E+10 | 0.234704E+10 | 0.165879E+10 | 0.628323E+09 | 0.103046E+10 | 0.00 | 0.00 |
March | 0.274691E+10 | 0.216081E+10 | 0.296808E+10 | 0.126071E+10 | 0.170737E+10 | 0.00 | 0.00 |
April | 0.493363E+10 | 0.172105E+10 | 0.460597E+10 | 0.234377E+10 | 0.226220E+10 | 0.00 | 0.00 |
May | 0.693366E+10 | 0.157754E+10 | 0.614856E+10 | 0.315289E+10 | 0.299567E+10 | 0.00 | 0.00 |
June | 0.744739E+10 | 0.127576E+10 | 0.648083E+10 | 0.376980E+10 | 0.271104E+10 | 0.00 | 0.00 |
July | 0.835969E+10 | 0.124851E+10 | 0.699841E+10 | 0.459520E+10 | 0.240321E+10 | 0.00 | 0.00 |
August | 0.667740E+10 | 0.128032E+10 | 0.560292E+10 | 0.353978E+10 | 0.206315E+10 | 0.00 | 0.00 |
September | 0.424159E+10 | 0.163975E+10 | 0.385150E+10 | 0.213565E+10 | 0.171585E+10 | 0.00 | 0.00 |
October | 0.215038E+10 | 0.209868E+10 | 0.231966E+10 | 0.106472E+10 | 0.125494E+10 | 0.00 | 0.00 |
November | 0.675378E+09 | 0.230177E+10 | 0.113532E+10 | 0.296899E+09 | 0.838424E+09 | 0.00 | 0.00 |
December | 0.313932E+09 | 0.302677E+10 | 0.844175E+09 | 0.218065E+09 | 0.626110E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.460896E+11 | 0.235986E+11 | 0.436140E+11 | 0.232371E+11 | 0.203769E+11 | 0.00 | 0.00 |
Minimum of Months | 0.313932E+09 | 0.124851E+10 | 0.844175E+09 | 0.218065E+09 | 0.626110E+09 | 0.00 | 0.00 |
Maximum of Months | 0.835969E+10 | 0.302677E+10 | 0.699841E+10 | 0.459520E+10 | 0.299567E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138935E+10 | 0.215716E+10 | 0.165409E+10 | 0.981990E+09 | 0.672096E+09 | 0.00 | 0.00 |
February | 0.214065E+10 | 0.177483E+10 | 0.229837E+10 | 0.142275E+10 | 0.875618E+09 | 0.00 | 0.00 |
March | 0.249300E+10 | 0.174954E+10 | 0.273828E+10 | 0.146080E+10 | 0.127748E+10 | 0.00 | 0.00 |
April | 0.236890E+10 | 0.141020E+10 | 0.279696E+10 | 0.121455E+10 | 0.158240E+10 | 0.00 | 0.00 |
May | 0.202023E+10 | 0.125674E+10 | 0.264212E+10 | 0.786857E+09 | 0.185527E+10 | 0.00 | 0.00 |
June | 0.171317E+10 | 0.980231E+09 | 0.233929E+10 | 0.627820E+09 | 0.171147E+10 | 0.00 | 0.00 |
July | 0.215691E+10 | 0.929322E+09 | 0.263606E+10 | 0.965177E+09 | 0.167089E+10 | 0.00 | 0.00 |
August | 0.267345E+10 | 0.916685E+09 | 0.283239E+10 | 0.132068E+10 | 0.151172E+10 | 0.00 | 0.00 |
September | 0.298741E+10 | 0.122088E+10 | 0.303814E+10 | 0.167819E+10 | 0.135995E+10 | 0.00 | 0.00 |
October | 0.285360E+10 | 0.161986E+10 | 0.284363E+10 | 0.175602E+10 | 0.108761E+10 | 0.00 | 0.00 |
November | 0.143637E+10 | 0.179115E+10 | 0.162625E+10 | 0.931842E+09 | 0.694413E+09 | 0.00 | 0.00 |
December | 0.165028E+10 | 0.221859E+10 | 0.175801E+10 | 0.113747E+10 | 0.620540E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.258833E+11 | 0.180252E+11 | 0.292036E+11 | 0.142842E+11 | 0.149194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.138935E+10 | 0.916685E+09 | 0.162625E+10 | 0.627820E+09 | 0.620540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.298741E+10 | 0.221859E+10 | 0.303814E+10 | 0.175602E+10 | 0.185527E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139745E+10 | 0.209951E+10 | 0.165409E+10 | 0.981990E+09 | 0.672096E+09 | 0.00 | 0.00 |
February | 0.216137E+10 | 0.169428E+10 | 0.229837E+10 | 0.142275E+10 | 0.875618E+09 | 0.00 | 0.00 |
March | 0.252664E+10 | 0.163087E+10 | 0.273828E+10 | 0.146080E+10 | 0.127748E+10 | 0.00 | 0.00 |
April | 0.240407E+10 | 0.131210E+10 | 0.279696E+10 | 0.121455E+10 | 0.158240E+10 | 0.00 | 0.00 |
May | 0.204872E+10 | 0.117582E+10 | 0.264212E+10 | 0.786857E+09 | 0.185527E+10 | 0.00 | 0.00 |
June | 0.172468E+10 | 0.925192E+09 | 0.233929E+10 | 0.627820E+09 | 0.171147E+10 | 0.00 | 0.00 |
July | 0.215749E+10 | 0.879919E+09 | 0.263606E+10 | 0.965177E+09 | 0.167089E+10 | 0.00 | 0.00 |
August | 0.266953E+10 | 0.871623E+09 | 0.283239E+10 | 0.132068E+10 | 0.151172E+10 | 0.00 | 0.00 |
September | 0.299315E+10 | 0.115932E+10 | 0.303814E+10 | 0.167819E+10 | 0.135995E+10 | 0.00 | 0.00 |
October | 0.288012E+10 | 0.150817E+10 | 0.284363E+10 | 0.175602E+10 | 0.108761E+10 | 0.00 | 0.00 |
November | 0.146222E+10 | 0.168138E+10 | 0.162625E+10 | 0.931842E+09 | 0.694413E+09 | 0.00 | 0.00 |
December | 0.166348E+10 | 0.214467E+10 | 0.175801E+10 | 0.113747E+10 | 0.620540E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.260889E+11 | 0.170829E+11 | 0.292036E+11 | 0.142842E+11 | 0.149194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139745E+10 | 0.871623E+09 | 0.162625E+10 | 0.627820E+09 | 0.620540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.299315E+10 | 0.214467E+10 | 0.303814E+10 | 0.175602E+10 | 0.185527E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.309287E+09 | 0.361788E+09 | 0.340352E+09 | 0.202059E+09 | 0.138294E+09 | 0.00 | 0.00 |
February | 0.473438E+09 | 0.294448E+09 | 0.472923E+09 | 0.292752E+09 | 0.180171E+09 | 0.00 | 0.00 |
March | 0.565497E+09 | 0.273982E+09 | 0.563440E+09 | 0.300581E+09 | 0.262859E+09 | 0.00 | 0.00 |
April | 0.540084E+09 | 0.230506E+09 | 0.575515E+09 | 0.249912E+09 | 0.325603E+09 | 0.00 | 0.00 |
May | 0.463571E+09 | 0.211581E+09 | 0.543655E+09 | 0.161907E+09 | 0.381748E+09 | 0.00 | 0.00 |
June | 0.384526E+09 | 0.172315E+09 | 0.481343E+09 | 0.129183E+09 | 0.352160E+09 | 0.00 | 0.00 |
July | 0.456904E+09 | 0.171021E+09 | 0.542408E+09 | 0.198599E+09 | 0.343809E+09 | 0.00 | 0.00 |
August | 0.549574E+09 | 0.175442E+09 | 0.582806E+09 | 0.271748E+09 | 0.311058E+09 | 0.00 | 0.00 |
September | 0.640881E+09 | 0.213906E+09 | 0.625141E+09 | 0.345312E+09 | 0.279829E+09 | 0.00 | 0.00 |
October | 0.630054E+09 | 0.256506E+09 | 0.585118E+09 | 0.361327E+09 | 0.223791E+09 | 0.00 | 0.00 |
November | 0.326871E+09 | 0.281724E+09 | 0.334626E+09 | 0.191740E+09 | 0.142886E+09 | 0.00 | 0.00 |
December | 0.363195E+09 | 0.369220E+09 | 0.361736E+09 | 0.234051E+09 | 0.127685E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.570388E+10 | 0.301244E+10 | 0.600906E+10 | 0.293917E+10 | 0.306989E+10 | 0.00 | 0.00 |
Minimum of Months | 0.309287E+09 | 0.171021E+09 | 0.334626E+09 | 0.129183E+09 | 0.127685E+09 | 0.00 | 0.00 |
Maximum of Months | 0.640881E+09 | 0.369220E+09 | 0.625141E+09 | 0.361327E+09 | 0.381748E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.264893E+10 | -.225148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -397444566.4 | 58.99 | 0.00 | 0.00 |
February | 0.242144E+10 | -.206449E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -356955426.4 | 58.99 | 0.00 | 0.00 |
March | 0.270644E+10 | -.231594E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -390500790.3 | 58.99 | 0.00 | 0.00 |
April | 0.251054E+10 | -.214136E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -369173998.0 | 58.99 | 0.00 | 0.00 |
May | 0.250191E+10 | -.213336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -368545507.1 | 58.99 | 0.00 | 0.00 |
June | 0.236317E+10 | -.201361E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -349557762.4 | 58.99 | 0.00 | 0.00 |
July | 0.232161E+10 | -.196379E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -357826115.5 | 59.00 | 0.00 | 0.00 |
August | 0.236654E+10 | -.200936E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -357178543.1 | 59.00 | 0.00 | 0.00 |
September | 0.228719E+10 | -.193716E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -350030414.2 | 58.99 | 0.00 | 0.00 |
October | 0.241241E+10 | -.203476E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -377649244.1 | 58.99 | 0.00 | 0.00 |
November | 0.241674E+10 | -.203901E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -377725525.8 | 59.00 | 0.00 | 0.00 |
December | 0.259351E+10 | -.219754E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -395971402.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.295504E+11 | -.251019E+11 | 8760.00 | -.444856E+10 | 58.99 | |||||
Minimum of Months | 0.228719E+10 | -.231594E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -397444566.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.270644E+10 | -.193716E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -349557762.4 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.93 | 0.75 | 17-JAN-12:30 | 171.70 | 5.76 | 0.00 | 0.00 | 139.87 | 4.38 | 0.00 | 0.00 |
February | 259.50 | 0.89 | 0.67 | 15-FEB-11:20 | 224.47 | 6.82 | 0.00 | 0.00 | 182.93 | 5.38 | 0.00 | 0.00 |
March | 247.00 | 0.81 | 0.50 | 06-MAR-11:39 | 317.60 | 8.26 | 0.00 | 32.33 | 258.90 | 6.72 | 0.00 | 10.17 |
April | 379.50 | 0.75 | 0.50 | 01-APR-11:30 | 839.74 | 9.46 | 0.00 | 147.17 | 310.50 | 7.87 | 0.00 | 58.50 |
May | 427.83 | 0.73 | 0.50 | 01-MAY-09:50 | 1676.03 | 10.72 | 0.00 | 176.00 | 1864.34 | 8.99 | 0.00 | 111.33 |
June | 375.17 | 0.75 | 0.50 | 01-JUN-10:30 | 445.47 | 10.42 | 0.00 | 135.83 | 2457.64 | 8.75 | 0.00 | 88.33 |
July | 471.00 | 0.78 | 0.50 | 01-JUL-11:20 | 2254.77 | 8.81 | 0.00 | 142.83 | 2281.88 | 7.12 | 0.00 | 101.17 |
August | 366.67 | 0.78 | 0.50 | 01-AUG-08:09 | 1953.89 | 8.38 | 0.00 | 104.50 | 1375.72 | 6.74 | 0.00 | 80.33 |
September | 301.17 | 0.80 | 0.50 | 01-SEP-12:09 | 334.90 | 8.70 | 0.00 | 35.67 | 266.89 | 7.06 | 0.00 | 10.00 |
October | 245.33 | 0.87 | 0.50 | 02-OCT-09:30 | 245.31 | 6.82 | 0.00 | 5.17 | 198.74 | 5.34 | 0.00 | 0.83 |
November | 242.67 | 0.92 | 0.75 | 01-NOV-12:20 | 187.78 | 6.26 | 0.00 | 0.00 | 153.04 | 4.83 | 0.00 | 0.00 |
December | 160.33 | 0.95 | 0.75 | 10-DEC-12:20 | 150.94 | 4.82 | 0.00 | 0.00 | 122.53 | 3.55 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.81 | 912.66 | 8.37 | 0.00 | 779.50 | 1008.96 | 6.79 | 0.00 | 460.67 | ||
Minimum of Months | 160.33 | 0.73 | 0.50 | 150.94 | 4.82 | 0.00 | 0.00 | 122.53 | 3.55 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.95 | 0.75 | 2254.77 | 10.72 | 0.00 | 176.00 | 2457.64 | 8.99 | 0.00 | 111.33 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.834558E+10 | 41114.33 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587279E+10 | 41114.33 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277611E+10 | 41114.33 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.962409E+09 | 41114.33 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41390821.69 | 2868.36 | 18-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.509800E+09 | 41114.33 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329744E+10 | 41114.33 | 11-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.669298E+10 | 41114.33 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284985E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.834558E+10 | 41114.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351888E+11 | 205704.52 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235608E+11 | 205704.52 | 19-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113260E+11 | 123209.13 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389114E+10 | 46114.34 | 17-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135160E+09 | 18427.28 | 18-MAY-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 946360.02 | 1577.27 | 28-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245990E+10 | 40245.48 | 29-OCT-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163750E+11 | 176398.00 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292657E+11 | 205704.52 | 25-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122203E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.351888E+11 | 205704.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195499E+10 | 30947.42 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105538E+10 | 30947.42 | 12-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.347412E+09 | 30947.42 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111411E+09 | 8827.79 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1276130.44 | 1005.22 | 18-MAY-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20913593.15 | 1918.72 | 28-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496833E+09 | 30947.42 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143118E+10 | 30947.42 | 09-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541939E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195499E+10 | 30947.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.510410E+10 | 25653.28 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310591E+10 | 25653.28 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170714E+10 | 25653.28 | 05-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.801477E+09 | 25653.28 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153341E+09 | 16722.94 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5987396.17 | 4405.75 | 15-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18057516.24 | 11402.52 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.424937E+09 | 17427.73 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227641E+10 | 25653.28 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.421169E+10 | 25653.28 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178090E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.510410E+10 | 25653.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.562727E+10 | 29778.96 | 22-JAN-16:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.346760E+10 | 29460.99 | 20-FEB-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591067E+09 | 28013.61 | 04-MAR-16:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12277787.62 | 28186.79 | 18-APR-16:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 115727.98 | 385.76 | 18-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 343024.43 | 666.28 | 16-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265964E+10 | 29387.68 | 25-NOV-16:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.494658E+10 | 29778.96 | 27-DEC-16:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173049E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.562727E+10 | 29778.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.316103E+09 | 0.279449E+09 | 7901.51 | 27-APR-15:00 | 6780.33 | 0.00 |
May | 0.00 | 0.00 | 0.964454E+09 | 0.818720E+09 | 9321.69 | 06-MAY-13:50 | 7265.98 | 0.00 |
June | 0.00 | 0.00 | 0.228927E+10 | 0.204752E+10 | 14135.05 | 29-JUN-06:02 | 9499.88 | 0.00 |
July | 0.00 | 0.00 | 0.563242E+10 | 0.460461E+10 | 27691.24 | 31-JUL-06:02 | 19299.36 | 0.00 |
August | 0.00 | 0.00 | 0.712351E+10 | 0.577036E+10 | 27974.37 | 25-AUG-06:02 | 18765.58 | 0.00 |
September | 0.00 | 0.00 | 0.190859E+10 | 0.148332E+10 | 13263.41 | 14-SEP-06:02 | 7881.20 | 0.00 |
October | 0.00 | 0.00 | 42959217.32 | 42953250.76 | 3373.35 | 04-OCT-15:00 | 3373.35 | 0.00 |
November | 0.00 | 0.00 | 5713838.34 | 4092674.21 | 996.56 | 04-NOV-15:00 | 720.53 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.182830E+11 | 0.150510E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.712351E+10 | 0.577036E+10 | 27974.37 | 19299.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 3545.86 | 3390.83 | 4.61 | 27-FEB-14:50 | 4.41 | 0.00 |
March | 0.00 | 0.00 | 32048719.04 | 32048596.59 | 5742.78 | 18-MAR-16:00 | 5742.78 | 0.00 |
April | 0.00 | 0.00 | 0.275052E+10 | 0.250748E+10 | 99675.93 | 28-APR-06:02 | 68350.19 | 0.00 |
May | 0.00 | 0.00 | 0.737570E+10 | 0.629212E+10 | 123780.65 | 07-MAY-08:62 | 87325.07 | 0.00 |
June | 0.00 | 0.00 | 0.161126E+11 | 0.143278E+11 | 121489.85 | 12-JUN-06:02 | 80320.70 | 0.00 |
July | 0.00 | 0.00 | 0.332248E+11 | 0.273753E+11 | 124233.35 | 31-JUL-06:02 | 89373.26 | 0.00 |
August | 0.00 | 0.00 | 0.396578E+11 | 0.324466E+11 | 125414.94 | 30-AUG-06:02 | 80487.02 | 0.00 |
September | 0.00 | 0.00 | 0.129074E+11 | 0.100331E+11 | 122148.53 | 24-SEP-08:62 | 70912.39 | 0.00 |
October | 0.00 | 0.00 | 0.679284E+09 | 0.655106E+09 | 24686.70 | 04-OCT-15:00 | 24686.70 | 0.00 |
November | 0.00 | 0.00 | 0.163432E+09 | 0.116931E+09 | 14577.18 | 04-NOV-14:40 | 10657.27 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112904E+12 | 0.937866E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.396578E+11 | 0.324466E+11 | 125414.94 | 89373.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 46.99 | 46.53 | 0.07 | 11-JAN-13:45 | 0.07 | 0.00 |
February | 0.00 | 0.00 | 18617052.17 | 18614757.90 | 2625.78 | 27-FEB-15:00 | 2625.78 | 0.00 |
March | 0.00 | 0.00 | 33798647.52 | 33797129.85 | 3146.28 | 18-MAR-14:00 | 3146.28 | 0.00 |
April | 0.00 | 0.00 | 0.704167E+09 | 0.676040E+09 | 17843.58 | 28-APR-06:02 | 12669.50 | 0.00 |
May | 0.00 | 0.00 | 0.125879E+10 | 0.114049E+10 | 18910.72 | 07-MAY-08:62 | 13626.30 | 0.00 |
June | 0.00 | 0.00 | 0.223351E+10 | 0.213748E+10 | 18638.76 | 12-JUN-06:02 | 12185.08 | 0.00 |
July | 0.00 | 0.00 | 0.499577E+10 | 0.441329E+10 | 19033.69 | 31-JUL-06:02 | 13647.96 | 0.00 |
August | 0.00 | 0.00 | 0.684774E+10 | 0.602794E+10 | 19217.01 | 25-AUG-06:02 | 13215.89 | 0.00 |
September | 0.00 | 0.00 | 0.299659E+10 | 0.251673E+10 | 18686.01 | 01-SEP-06:02 | 12382.59 | 0.00 |
October | 0.00 | 0.00 | 0.390278E+09 | 0.377383E+09 | 15863.06 | 05-OCT-06:02 | 14444.56 | 0.00 |
November | 0.00 | 0.00 | 0.114634E+09 | 88543584.64 | 7491.26 | 04-NOV-14:00 | 5983.37 | 0.00 |
December | 0.00 | 0.00 | 3679.28 | 3679.28 | 0.35 | 02-DEC-13:00 | 0.35 | 0.00 |
Annual Sum or Average | 0.195939E+11 | 0.174303E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.99 | 46.53 | 0.07 | 0.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.684774E+10 | 0.602794E+10 | 19217.01 | 14444.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 39110573.42 | 38949405.49 | 2922.97 | 27-FEB-15:10 | 2922.97 | 0.00 |
March | 0.00 | 0.00 | 0.110369E+09 | 0.110105E+09 | 3196.27 | 18-MAR-14:00 | 3196.27 | 0.00 |
April | 0.00 | 0.00 | 0.718854E+09 | 0.679905E+09 | 7412.59 | 27-APR-14:20 | 6962.37 | 0.00 |
May | 0.00 | 0.00 | 0.145180E+10 | 0.132594E+10 | 6469.56 | 06-MAY-13:30 | 5427.87 | 0.00 |
June | 0.00 | 0.00 | 0.261229E+10 | 0.243952E+10 | 6353.30 | 28-JUN-16:00 | 6090.26 | 0.00 |
July | 0.00 | 0.00 | 0.471062E+10 | 0.417188E+10 | 9315.04 | 31-JUL-14:10 | 8185.73 | 0.00 |
August | 0.00 | 0.00 | 0.614190E+10 | 0.535712E+10 | 15913.50 | 25-AUG-06:02 | 12502.20 | 0.00 |
September | 0.00 | 0.00 | 0.353970E+10 | 0.308531E+10 | 9930.07 | 14-SEP-13:30 | 8363.23 | 0.00 |
October | 0.00 | 0.00 | 0.103299E+10 | 0.991660E+09 | 7707.04 | 04-OCT-14:10 | 7707.04 | 0.00 |
November | 0.00 | 0.00 | 0.121489E+09 | 99067187.89 | 6035.20 | 04-NOV-14:00 | 4988.00 | 0.00 |
December | 0.00 | 0.00 | 1290065.33 | 1290065.33 | 318.24 | 02-DEC-13:30 | 318.24 | 0.00 |
Annual Sum or Average | 0.204804E+11 | 0.183007E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.614190E+10 | 0.535712E+10 | 15913.50 | 12502.20 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113803E+10 | 0.35 | 1131.25 | 01-JAN-01:53 | 0.92 |
February | 0.751360E+09 | 0.25 | 1131.25 | 01-FEB-10:53 | 0.92 |
March | 0.304816E+09 | 0.09 | 1131.25 | 01-MAR-08:07 | 0.92 |
April | 78339318.77 | 0.02 | 1131.25 | 08-APR-07:10 | 0.92 |
May | 7805650.53 | 0.00 | 1131.25 | 18-MAY-07:10 | 0.92 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 18473372.93 | 0.01 | 1131.25 | 12-OCT-07:06 | 0.92 |
November | 0.629305E+09 | 0.20 | 1131.25 | 09-NOV-08:10 | 0.92 |
December | 0.104117E+10 | 0.32 | 1131.25 | 01-DEC-08:65 | 0.92 |
Annual Sum or Average | 0.396930E+10 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113803E+10 | 0.35 | 1131.25 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127475E+10 | 0.36 | 1670.81 | 01-JAN-08:61 | 0.89 |
February | 0.111585E+10 | 0.35 | 1670.81 | 01-FEB-06:02 | 0.89 |
March | 0.115759E+10 | 0.34 | 1670.81 | 01-MAR-07:03 | 0.89 |
April | 0.107006E+10 | 0.33 | 1670.81 | 01-APR-06:03 | 0.89 |
May | 0.108129E+10 | 0.32 | 738.26 | 18-MAY-06:15 | 0.57 |
June | 0.105382E+10 | 0.33 | 751.17 | 29-JUN-06:02 | 0.58 |
July | 0.107400E+10 | 0.32 | 1670.81 | 23-JUL-08:62 | 0.88 |
August | 0.109200E+10 | 0.33 | 1670.81 | 01-AUG-06:02 | 0.88 |
September | 0.104659E+10 | 0.32 | 671.70 | 14-SEP-06:02 | 0.54 |
October | 0.108308E+10 | 0.32 | 1670.81 | 30-OCT-06:03 | 0.89 |
November | 0.111256E+10 | 0.34 | 1670.81 | 11-NOV-08:62 | 0.89 |
December | 0.123625E+10 | 0.35 | 1670.81 | 01-DEC-06:02 | 0.89 |
Annual Sum or Average | 0.133978E+11 | 0.33 | |||
Minimum of Months | 0.104659E+10 | 0.32 | 671.70 | 0.54 | |
Maximum of Months | 0.127475E+10 | 0.36 | 1670.81 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.845763E+10 | 0.56 | 11376.36 | 01-JAN-08:61 | 1.40 |
February | 0.740012E+10 | 0.55 | 11376.36 | 19-FEB-08:61 | 1.40 |
March | 0.779686E+10 | 0.53 | 8638.95 | 06-MAR-07:03 | 1.23 |
April | 0.725624E+10 | 0.52 | 9429.17 | 28-APR-06:02 | 1.28 |
May | 0.736367E+10 | 0.51 | 11376.36 | 05-MAY-06:02 | 1.39 |
June | 0.718897E+10 | 0.51 | 11376.36 | 10-JUN-06:03 | 1.39 |
July | 0.734502E+10 | 0.51 | 11376.36 | 01-JUL-06:03 | 1.39 |
August | 0.749668E+10 | 0.52 | 11376.36 | 01-AUG-06:02 | 1.39 |
September | 0.713845E+10 | 0.51 | 11376.36 | 01-SEP-06:02 | 1.39 |
October | 0.737160E+10 | 0.51 | 5886.00 | 29-OCT-08:10 | 1.00 |
November | 0.757123E+10 | 0.53 | 10403.90 | 13-NOV-07:03 | 1.35 |
December | 0.827747E+10 | 0.55 | 11376.36 | 25-DEC-08:61 | 1.40 |
Annual Sum or Average | 0.906639E+11 | 0.52 | |||
Minimum of Months | 0.713845E+10 | 0.51 | 5886.00 | 1.00 | |
Maximum of Months | 0.845763E+10 | 0.56 | 11376.36 | 1.40 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199684E+10 | 0.55 | 1246.25 | 24-JAN-11:20 | 0.92 |
February | 0.181279E+10 | 0.55 | 1246.25 | 01-FEB-16:50 | 0.92 |
March | 0.203238E+10 | 0.56 | 1246.25 | 08-MAR-06:03 | 0.92 |
April | 0.195163E+10 | 0.55 | 1246.25 | 01-APR-06:08 | 0.92 |
May | 0.201444E+10 | 0.55 | 1246.25 | 02-MAY-18:50 | 0.92 |
June | 0.196508E+10 | 0.56 | 1246.25 | 22-JUN-11:08 | 0.91 |
July | 0.200098E+10 | 0.55 | 1246.25 | 01-JUL-06:03 | 0.92 |
August | 0.203238E+10 | 0.56 | 1246.25 | 27-AUG-12:40 | 0.91 |
September | 0.195163E+10 | 0.55 | 1246.25 | 01-SEP-07:01 | 0.91 |
October | 0.199649E+10 | 0.55 | 1246.25 | 05-OCT-07:30 | 0.92 |
November | 0.192471E+10 | 0.55 | 1246.25 | 01-NOV-11:20 | 0.91 |
December | 0.200098E+10 | 0.55 | 1246.25 | 01-DEC-08:20 | 0.92 |
Annual Sum or Average | 0.236803E+11 | 0.55 | |||
Minimum of Months | 0.181279E+10 | 0.55 | 1246.25 | 0.91 | |
Maximum of Months | 0.203238E+10 | 0.56 | 1246.25 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158509E+10 | 0.55 | 988.62 | 08-JAN-15:50 | 0.92 |
February | 0.143885E+10 | 0.56 | 988.62 | 01-FEB-10:10 | 0.92 |
March | 0.161224E+10 | 0.56 | 988.62 | 23-MAR-11:40 | 0.92 |
April | 0.154818E+10 | 0.55 | 988.62 | 10-APR-10:10 | 0.92 |
May | 0.159801E+10 | 0.55 | 988.62 | 01-MAY-15:30 | 0.91 |
June | 0.155886E+10 | 0.56 | 988.62 | 01-JUN-11:10 | 0.92 |
July | 0.158733E+10 | 0.55 | 988.62 | 17-JUL-10:00 | 0.91 |
August | 0.161224E+10 | 0.56 | 988.62 | 02-AUG-18:30 | 0.91 |
September | 0.154818E+10 | 0.55 | 988.62 | 21-SEP-10:50 | 0.91 |
October | 0.158377E+10 | 0.55 | 988.62 | 05-OCT-19:16 | 0.92 |
November | 0.152683E+10 | 0.55 | 988.62 | 16-NOV-18:50 | 0.92 |
December | 0.158773E+10 | 0.55 | 988.62 | 12-DEC-16:20 | 0.92 |
Annual Sum or Average | 0.187873E+11 | 0.55 | |||
Minimum of Months | 0.143885E+10 | 0.55 | 988.62 | 0.91 | |
Maximum of Months | 0.161224E+10 | 0.56 | 988.62 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.28 | 0.00 |
February | 0.11 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.08 | 0.00 |
Annual Sum or Average | 0.47 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.28 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.08 | 25.84 |
March | 0.14 | 25.84 |
April | 1.03 | 25.84 |
May | 1.93 | 25.84 |
June | 1.36 | 25.84 |
July | 0.33 | 25.84 |
August | 0.06 | 25.84 |
September | 0.83 | 25.84 |
October | 1.58 | 25.84 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.35 | 25.84 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.93 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.00 |
February | 0.17 | 0.00 |
March | 0.94 | 1.58 |
April | 0.31 | 1.77 |
May | 0.32 | 2.44 |
June | 0.11 | 1.22 |
July | 0.28 | 0.00 |
August | 0.53 | 0.00 |
September | 0.11 | 2.44 |
October | 0.39 | 2.44 |
November | 0.00 | 0.00 |
December | 0.17 | 0.00 |
Annual Sum or Average | 3.49 | 1.19 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.94 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.05 | 0.00 |
February | 0.44 | 0.00 |
March | 0.08 | 0.00 |
April | 0.17 | 2.44 |
May | 0.08 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 0.00 |
October | 0.08 | 0.00 |
November | 0.31 | 1.33 |
December | 0.56 | 0.00 |
Annual Sum or Average | 2.86 | 0.28 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.05 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.84 | 0.00 |
February | 5.20 | 0.00 |
March | 7.87 | 0.00 |
April | 5.30 | 0.00 |
May | 4.24 | 0.00 |
June | 3.65 | 0.00 |
July | 3.72 | 0.00 |
August | 3.73 | 0.00 |
September | 6.61 | 0.00 |
October | 7.25 | 0.00 |
November | 5.83 | 0.00 |
December | 2.39 | 0.00 |
Annual Sum or Average | 57.62 | 0.00 |
Minimum of Months | 1.84 | 0.00 |
Maximum of Months | 7.87 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.127475E+10 | 0.104320E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111585E+10 | 0.734099E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.115759E+10 | 0.347013E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.115499E+10 | 0.120301E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.132954E+10 | 51738527.12 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.163807E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.247060E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.285612E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.152376E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.109458E+10 | 0.637250E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111415E+10 | 0.412179E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.123625E+10 | 0.836622E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179663E+11 | 0.356231E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.109458E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.285612E+10 | 0.104320E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.845763E+10 | 0.439860E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.740013E+10 | 0.294510E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.780677E+10 | 0.141575E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.805089E+10 | 0.486393E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.942699E+10 | 0.168950E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.116736E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.163208E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.182348E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.106612E+11 | 1182950.02 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.757104E+10 | 0.307488E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.761993E+10 | 0.204687E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.827747E+10 | 0.365821E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.121501E+12 | 0.152754E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.740013E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.182348E+11 | 0.439860E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.199684E+10 | 0.244374E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.181712E+10 | 0.131922E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.204004E+10 | 0.434265E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.210310E+10 | 0.139263E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.228340E+10 | 1595163.05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.244827E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.305611E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.346575E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.255974E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.207988E+10 | 26141991.44 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.194860E+10 | 0.621041E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.200098E+10 | 0.178897E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.277998E+11 | 0.677424E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181712E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.346575E+10 | 0.244374E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158509E+10 | 0.638012E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144778E+10 | 0.388239E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.163768E+10 | 0.213392E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.170745E+10 | 0.100185E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.192013E+10 | 0.191676E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.213700E+10 | 7484245.21 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.260005E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291510E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.228092E+10 | 22571895.30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.180667E+10 | 0.531171E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.155245E+10 | 0.284551E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158804E+10 | 0.526461E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.231784E+11 | 0.222613E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144778E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.291510E+10 | 0.638012E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.127475E+10 | 0.00 | 0.834558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111585E+10 | 0.00 | 0.587279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115759E+10 | 0.00 | 0.277611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107006E+10 | 0.316103E+09 | 0.962409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108129E+10 | 0.964454E+09 | 41390821.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105382E+10 | 0.228927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107400E+10 | 0.563242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109200E+10 | 0.712351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104659E+10 | 0.190859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108308E+10 | 42959217.32 | 0.509800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111256E+10 | 5713838.34 | 0.329744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123625E+10 | 0.00 | 0.669298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133978E+11 | 0.182830E+11 | 0.284985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127475E+10 | 0.712351E+10 | 0.834558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.845763E+10 | 0.00 | 0.351888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740012E+10 | 3545.86 | 0.235608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779686E+10 | 32048719.04 | 0.113260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725624E+10 | 0.275052E+10 | 0.389114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736367E+10 | 0.737570E+10 | 0.135160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718897E+10 | 0.161126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.734502E+10 | 0.332248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749668E+10 | 0.396578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.713845E+10 | 0.129074E+11 | 946360.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737160E+10 | 0.679284E+09 | 0.245990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757123E+10 | 0.163432E+09 | 0.163750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827747E+10 | 0.00 | 0.292657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906639E+11 | 0.112904E+12 | 0.122203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.713845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.845763E+10 | 0.396578E+11 | 0.351888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199684E+10 | 46.99 | 0.195499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181279E+10 | 18617052.17 | 0.105538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203238E+10 | 33798647.52 | 0.347412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195163E+10 | 0.704167E+09 | 0.111411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201444E+10 | 0.125879E+10 | 1276130.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196508E+10 | 0.223351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.200098E+10 | 0.499577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203238E+10 | 0.684774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195163E+10 | 0.299659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199649E+10 | 0.390278E+09 | 20913593.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192471E+10 | 0.114634E+09 | 0.496833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200098E+10 | 3679.28 | 0.143118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236803E+11 | 0.195939E+11 | 0.541939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.181279E+10 | 46.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203238E+10 | 0.684774E+10 | 0.195499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158509E+10 | 0.00 | 0.510410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143885E+10 | 39110573.42 | 0.310591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161224E+10 | 0.110369E+09 | 0.170714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154818E+10 | 0.718854E+09 | 0.801477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159801E+10 | 0.145180E+10 | 0.153341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155886E+10 | 0.261229E+10 | 5987396.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158733E+10 | 0.471062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161224E+10 | 0.614190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154818E+10 | 0.353970E+10 | 18057516.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158377E+10 | 0.103299E+10 | 0.424937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152683E+10 | 0.121489E+09 | 0.227641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158773E+10 | 1290065.33 | 0.421169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187873E+11 | 0.204804E+11 | 0.178090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161224E+10 | 0.614190E+10 | 0.510410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.127475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107006E+10 | 0.00 | 0.00 | 0.00 | 84932719.37 | 0.00 | 0.120301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108129E+10 | 0.00 | 0.00 | 0.00 | 0.248258E+09 | 0.00 | 51738527.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105382E+10 | 0.00 | 0.00 | 0.00 | 0.584248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107400E+10 | 0.00 | 0.00 | 0.00 | 0.139660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109200E+10 | 0.00 | 0.00 | 0.00 | 0.176412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104659E+10 | 0.00 | 0.00 | 0.00 | 0.477168E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108308E+10 | 0.00 | 0.00 | 0.00 | 11499229.26 | 0.00 | 0.637250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111256E+10 | 0.00 | 0.00 | 0.00 | 1591203.30 | 0.00 | 0.412179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133978E+11 | 0.00 | 0.00 | 0.00 | 0.456842E+10 | 0.00 | 0.356231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.104659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127475E+10 | 0.00 | 0.00 | 0.00 | 0.176412E+10 | 0.00 | 0.104320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.845763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740012E+10 | 0.00 | 0.00 | 0.00 | 1123.84 | 0.00 | 0.294510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779686E+10 | 0.00 | 0.00 | 0.00 | 9913072.09 | 0.00 | 0.141575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.725624E+10 | 0.00 | 0.00 | 0.00 | 0.794653E+09 | 0.00 | 0.486393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736367E+10 | 0.00 | 0.00 | 0.00 | 0.206332E+10 | 0.00 | 0.168950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718897E+10 | 0.00 | 0.00 | 0.00 | 0.448464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.734502E+10 | 0.00 | 0.00 | 0.00 | 0.897576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.749668E+10 | 0.00 | 0.00 | 0.00 | 0.107381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.713845E+10 | 0.00 | 0.00 | 0.00 | 0.352280E+10 | 0.00 | 1182950.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737160E+10 | 0.00 | 0.00 | 0.00 | 0.199437E+09 | 0.00 | 0.307488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757123E+10 | 0.00 | 0.00 | 0.00 | 48699526.20 | 0.00 | 0.204687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.906639E+11 | 0.00 | 0.00 | 0.00 | 0.308373E+11 | 0.00 | 0.152754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.713845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.845763E+10 | 0.00 | 0.00 | 0.00 | 0.107381E+11 | 0.00 | 0.439860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.199684E+10 | 0.00 | 0.00 | 0.00 | 11.64 | 0.00 | 0.244374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181279E+10 | 0.00 | 0.00 | 0.00 | 4326974.37 | 0.00 | 0.131922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203238E+10 | 0.00 | 0.00 | 0.00 | 7659747.85 | 0.00 | 0.434265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195163E+10 | 0.00 | 0.00 | 0.00 | 0.151476E+09 | 0.00 | 0.139263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201444E+10 | 0.00 | 0.00 | 0.00 | 0.268969E+09 | 0.00 | 1595163.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196508E+10 | 0.00 | 0.00 | 0.00 | 0.483188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.200098E+10 | 0.00 | 0.00 | 0.00 | 0.105514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203238E+10 | 0.00 | 0.00 | 0.00 | 0.143337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.195163E+10 | 0.00 | 0.00 | 0.00 | 0.608115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.199649E+10 | 0.00 | 0.00 | 0.00 | 83385971.65 | 0.00 | 26141991.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192471E+10 | 0.00 | 0.00 | 0.00 | 23891626.49 | 0.00 | 0.621041E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200098E+10 | 0.00 | 0.00 | 0.00 | 906.92 | 0.00 | 0.178897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236803E+11 | 0.00 | 0.00 | 0.00 | 0.411952E+10 | 0.00 | 0.677424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.181279E+10 | 0.00 | 0.00 | 0.00 | 11.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.203238E+10 | 0.00 | 0.00 | 0.00 | 0.143337E+10 | 0.00 | 0.244374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.158509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143885E+10 | 0.00 | 0.00 | 0.00 | 8930260.58 | 0.00 | 0.388239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161224E+10 | 0.00 | 0.00 | 0.00 | 25441622.35 | 0.00 | 0.213392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154818E+10 | 0.00 | 0.00 | 0.00 | 0.159272E+09 | 0.00 | 0.100185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159801E+10 | 0.00 | 0.00 | 0.00 | 0.322128E+09 | 0.00 | 0.191676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155886E+10 | 0.00 | 0.00 | 0.00 | 0.578145E+09 | 0.00 | 7484245.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.158733E+10 | 0.00 | 0.00 | 0.00 | 0.101272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161224E+10 | 0.00 | 0.00 | 0.00 | 0.130286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154818E+10 | 0.00 | 0.00 | 0.00 | 0.732736E+09 | 0.00 | 22571895.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158377E+10 | 0.00 | 0.00 | 0.00 | 0.222900E+09 | 0.00 | 0.531171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152683E+10 | 0.00 | 0.00 | 0.00 | 25628252.93 | 0.00 | 0.284551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158773E+10 | 0.00 | 0.00 | 0.00 | 314679.02 | 0.00 | 0.526461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187873E+11 | 0.00 | 0.00 | 0.00 | 0.439107E+10 | 0.00 | 0.222613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161224E+10 | 0.00 | 0.00 | 0.00 | 0.130286E+10 | 0.00 | 0.638012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502636E+10 | 0.00 | 0.00 | 0.20 |
February | 0.320383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342945E+10 | 0.00 | 0.00 | 0.20 |
March | 0.515731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137086E+10 | 0.00 | 0.00 | 0.21 |
April | 0.464248E+10 | 2303437.53 | 0.00 | 866841.65 | 0.00 | 0.411713E+09 | 0.510425E+09 | 0.00 | 0.22 |
May | 0.268751E+10 | 537000.99 | 0.00 | 4803347.45 | 0.00 | 940973.69 | 0.345364E+10 | 0.00 | 0.31 |
June | 0.947386E+09 | 2172184.91 | 0.00 | 9860196.62 | 0.00 | 0.00 | 0.549286E+10 | 0.00 | 0.44 |
July | 0.394701E+09 | 0.148748E+09 | 0.00 | 12153900.23 | 0.00 | 0.00 | 0.460548E+10 | 0.00 | 0.47 |
August | 0.317062E+09 | 0.332397E+09 | 0.00 | 10950797.68 | 0.00 | 0.00 | 0.398255E+10 | 0.00 | 0.44 |
September | 0.135572E+10 | 1312921.03 | 0.00 | 8777540.15 | 0.00 | 0.00 | 0.482984E+10 | 0.00 | 0.39 |
October | 0.452158E+10 | 0.00 | 0.00 | 1390297.96 | 0.00 | 0.220214E+09 | 0.134274E+10 | 0.00 | 0.23 |
November | 0.461950E+10 | 0.00 | 0.00 | 62329.03 | 0.00 | 0.176287E+10 | 90180857.99 | 0.00 | 0.21 |
December | 0.358336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397874E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.343421E+11 | 0.487471E+09 | 0.00 | 48865250.77 | 0.00 | 0.162011E+11 | 0.243077E+11 | 0.00 | 0.29 |
Minimum of Months | 0.317062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.515731E+10 | 0.332397E+09 | 0.00 | 12153900.23 | 0.00 | 0.502636E+10 | 0.549286E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.508123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100764E+11 | 0.00 | 0.00 | 0.39 |
February | 0.440761E+11 | 0.00 | 0.00 | 142704.25 | 0.00 | 0.613561E+10 | 0.238443E+09 | 0.00 | 0.40 |
March | 0.464511E+11 | 0.00 | 0.00 | 393160.59 | 0.00 | 0.171147E+10 | 0.676074E+09 | 0.00 | 0.40 |
April | 0.350267E+11 | 50577972.35 | 0.00 | 7588797.88 | 0.00 | 0.418874E+09 | 0.492171E+10 | 0.00 | 0.42 |
May | 0.203337E+11 | 29486379.16 | 0.00 | 30312389.02 | 0.00 | 0.00 | 0.194140E+11 | 0.00 | 0.47 |
June | 0.687092E+10 | 45294001.59 | 0.00 | 59562688.16 | 0.00 | 0.00 | 0.279162E+11 | 0.00 | 0.56 |
July | 0.271460E+10 | 0.135650E+10 | 0.00 | 69008866.65 | 0.00 | 0.00 | 0.217055E+11 | 0.00 | 0.56 |
August | 0.241182E+10 | 0.290138E+10 | 0.00 | 59636113.41 | 0.00 | 0.00 | 0.181970E+11 | 0.00 | 0.55 |
September | 0.115662E+11 | 45300805.15 | 0.00 | 46703550.63 | 0.00 | 0.00 | 0.227623E+11 | 0.00 | 0.52 |
October | 0.342321E+11 | 0.00 | 0.00 | 9805347.78 | 0.00 | 0.118519E+09 | 0.829419E+10 | 0.00 | 0.42 |
November | 0.450858E+11 | 0.00 | 0.00 | 538873.36 | 0.00 | 0.294006E+10 | 0.473493E+09 | 0.00 | 0.39 |
December | 0.501539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741413E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.349735E+12 | 0.442853E+10 | 0.00 | 0.283692E+09 | 0.00 | 0.288151E+11 | 0.124599E+12 | 0.00 | 0.46 |
Minimum of Months | 0.241182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.508123E+11 | 0.290138E+10 | 0.00 | 69008866.65 | 0.00 | 0.100764E+11 | 0.279162E+11 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.467140E+10 | 0.00 | 0.00 | 105712.55 | 0.00 | 0.102456E+10 | 0.121346E+09 | 0.00 | 0.39 |
February | 0.349413E+10 | 0.00 | 0.00 | 1418939.44 | 0.00 | 0.529368E+09 | 0.126732E+10 | 0.00 | 0.44 |
March | 0.278461E+10 | 0.00 | 0.00 | 3449108.34 | 0.00 | 0.206670E+09 | 0.291520E+10 | 0.00 | 0.51 |
April | 0.154157E+10 | 6895118.10 | 0.00 | 5869396.72 | 0.00 | 57233452.94 | 0.397573E+10 | 0.00 | 0.67 |
May | 0.756029E+09 | 8527816.80 | 0.00 | 9143280.81 | 0.00 | 0.00 | 0.549084E+10 | 0.00 | 0.95 |
June | 0.244544E+09 | 5721629.27 | 0.00 | 11407570.87 | 0.00 | 0.00 | 0.587243E+10 | 0.00 | 1.23 |
July | 76152643.64 | 0.151075E+09 | 0.00 | 12328543.23 | 0.00 | 0.00 | 0.474192E+10 | 0.00 | 1.29 |
August | 87735502.32 | 0.348108E+09 | 0.00 | 10955087.97 | 0.00 | 0.00 | 0.410318E+10 | 0.00 | 1.21 |
September | 0.289925E+09 | 34875160.62 | 0.00 | 13213171.15 | 0.00 | 0.00 | 0.594311E+10 | 0.00 | 1.20 |
October | 0.134259E+10 | 0.00 | 0.00 | 8194333.32 | 0.00 | 997015.52 | 0.532915E+10 | 0.00 | 0.76 |
November | 0.352378E+10 | 0.00 | 0.00 | 1844315.48 | 0.00 | 0.282310E+09 | 0.141166E+10 | 0.00 | 0.45 |
December | 0.422471E+10 | 0.00 | 0.00 | 759582.88 | 0.00 | 0.828277E+09 | 0.677702E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.230372E+11 | 0.555202E+09 | 0.00 | 78689042.76 | 0.00 | 0.292941E+10 | 0.418496E+11 | 0.00 | 0.79 |
Minimum of Months | 76152643.64 | 0.00 | 0.00 | 105712.55 | 0.00 | 0.00 | 0.121346E+09 | 0.00 | 0.39 |
Maximum of Months | 0.467140E+10 | 0.348108E+09 | 0.00 | 13213171.15 | 0.00 | 0.102456E+10 | 0.594311E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373954E+10 | 0.00 | 0.00 | 0.42 |
February | 0.291052E+10 | 0.00 | 0.00 | 91813.18 | 0.00 | 0.210273E+10 | 80748729.21 | 0.00 | 0.43 |
March | 0.346307E+10 | 0.00 | 0.00 | 395834.95 | 0.00 | 0.116506E+10 | 0.381549E+09 | 0.00 | 0.43 |
April | 0.289666E+10 | 5313594.95 | 0.00 | 1339551.65 | 0.00 | 0.483678E+09 | 0.642684E+09 | 0.00 | 0.43 |
May | 0.210129E+10 | 2835396.07 | 0.00 | 2875494.86 | 0.00 | 56458848.92 | 0.141696E+10 | 0.00 | 0.43 |
June | 0.106783E+10 | 2507627.11 | 0.00 | 4862142.33 | 0.00 | 2699861.24 | 0.174349E+10 | 0.00 | 0.43 |
July | 0.623823E+09 | 0.119768E+09 | 0.00 | 5896000.95 | 0.00 | 0.00 | 0.127158E+10 | 0.00 | 0.43 |
August | 0.497639E+09 | 0.297093E+09 | 0.00 | 5493775.39 | 0.00 | 0.00 | 0.106804E+10 | 0.00 | 0.43 |
September | 0.130232E+10 | 18674421.32 | 0.00 | 5984047.99 | 0.00 | 4080264.46 | 0.150790E+10 | 0.00 | 0.43 |
October | 0.278490E+10 | 0.00 | 0.00 | 2869220.22 | 0.00 | 0.257437E+09 | 0.112196E+10 | 0.00 | 0.42 |
November | 0.312608E+10 | 0.00 | 0.00 | 237076.67 | 0.00 | 0.158245E+10 | 89269852.52 | 0.00 | 0.42 |
December | 0.252292E+10 | 0.00 | 0.00 | 41776.92 | 0.00 | 0.319393E+10 | 73440084.14 | 0.00 | 0.42 |
Annual Sum or Average | 0.256371E+11 | 0.446192E+09 | 0.00 | 30086735.11 | 0.00 | 0.125881E+11 | 0.939761E+10 | 0.00 | 0.43 |
Minimum of Months | 0.497639E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.346307E+10 | 0.297093E+09 | 0.00 | 5984047.99 | 0.00 | 0.373954E+10 | 0.174349E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |