Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:12:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2969.83 | 1294.61 | 1294.61 |
Net Site Energy | 2969.83 | 1294.61 | 1294.61 |
Total Source Energy | 6157.39 | 2684.14 | 2684.14 |
Net Source Energy | 6157.39 | 2684.14 | 2684.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1458.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 121.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 475.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 114.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 503.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 100.78 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1410.51 | 1559.31 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1458.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 121.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 475.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 114.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 503.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 100.78 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 257.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 272.60 | 679.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 614.87 | 679.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 257.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 272.60 | 679.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 614.87 | 679.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1410.513 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1410.513 | 100.00 |
Total On-Site and Utility Electric Sources | 1410.513 | 100.00 |
Total Electricity End Uses | 1410.513 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2606.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 6.69 |
Skylight-Roof Ratio [%] | 0.29 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 8.3451 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 17.7333 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 17.7333 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 17.7333 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 13.5608 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.1568 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.1568 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:00 | 06-JAN-05:10 | - | - | - | 19-JAN-12:09 |
Heating | 0.00 | 461129.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 61123.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19069.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 124349.17 | 462991.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 461129.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 61123.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 19069.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1581.05 | 0.00 | 0.00 | 0.00 |
Cooling | 384.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1505.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 363.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1595.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 109.24 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4467.09 | 1690.30 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 689.21 | 0.00 | 0.00 | 0.00 |
Cooling | 167.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 656.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 695.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.62 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1947.30 | 736.84 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 689.21 | 0.00 | 0.00 | 0.00 |
Cooling | 167.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 656.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 695.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.62 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1947.30 | 736.84 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.72 |
CORE_RETAIL DIRECT AIR | 7.77 |
POINT_OF_SALE DIRECT AIR | 1.20 |
FRONT_RETAIL DIRECT AIR | 0.958331 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 5.88 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 5.88 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 131696.21 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 56121.05 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 323663.63 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 40741.14 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 35477.71 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.72 | 1.72 | 1.72 | 1.72 | 1.72 | 1.72 | 1.00 | 1.00 | 1.72 |
PSZ-AC:2 | 7.77 | 7.77 | 7.77 | 7.77 | 7.96 | 7.96 | 1.00 | 0.975225 | 7.96 |
PSZ-AC:3 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.20 | 1.00 | 1.00 | 1.20 |
PSZ-AC:4 | 0.958331 | 0.958331 | 0.958331 | 0.958331 | 0.958331 | 0.958331 | 1.00 | 1.00 | 0.958331 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.72 | 0.289458 |
PSZ-AC:2_OA_CONTROLLER | 7.96 | 2.44 |
PSZ-AC:3_OA_CONTROLLER | 1.20 | 0.229820 |
PSZ-AC:4_OA_CONTROLLER | 0.958331 | 0.229820 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.72 | 1.72 | 1.72 | 1.72 | 34024.91 | 56121.05 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.96 | 7.96 | 7.96 | 7.96 | 170865.06 | 323663.63 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.20 | 1.20 | 1.20 | 1.20 | 22648.67 | 40741.14 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.958331 | 0.958331 | 0.958331 | 0.958331 | 19073.41 | 35477.71 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.72 | 0.862450 | 1.72 | 31846.94 | 34024.91 | 17012.46 | 34024.91 | 0.739531 | 0.739530 | 0.739530 | 0.739530 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.96 | 3.98 | 7.96 | 161032.38 | 170865.06 | 85432.53 | 170865.06 | 0.714658 | 0.714660 | 0.714660 | 0.714660 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.20 | 0.598215 | 1.20 | 21122.93 | 22648.67 | 11324.33 | 22648.67 | 0.752497 | 0.752500 | 0.752500 | 0.752500 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.958330 | 0.479165 | 0.958330 | 17866.25 | 19073.41 | 9536.70 | 19073.41 | 0.736787 | 0.736790 | 0.736790 | 0.736790 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.72 | 1887.91 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.96 | 14725.37 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.20 | 1364.06 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.958331 | 1092.60 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 8.345 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.415 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 17.733 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.963 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 17.733 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.253 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 17.733 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.963 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 13.561 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.561 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 3170.217 | 8.345 | 51.681 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3170.217 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 28381.872 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28381.872 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2674.362 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2674.362 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2674.362 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2674.362 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 162.729 | 13.561 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 162.729 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
25 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
26 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
27 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
28 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
29 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
30 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
31 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
32 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
33 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.46_SHGC_0.45 | 30 | 1 | VerySmooth | 2.615 | 0.446 | 0.367 | 0.451 |
2 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 31 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.53892E-002 | 0.36619 | 0.42302 | 0.42302 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 18576.89888 | 22292.27865 | 1.36154 | 1.63385 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 379.89000 | 61.34184 | 0.28946 | 0.00000 |
2 | BACK_SPACE | Heating | 32517.53979 | 39021.04775 | 1.43741 | 1.72490 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 379.89000 | 61.34184 | 0.28946 | 0.00000 |
3 | CORE_RETAIL | Cooling | 87915.72455 | 105498.86946 | 6.47203 | 7.76644 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 1600.48290 | 258.43418 | 2.43898 | 0.00000 |
4 | CORE_RETAIL | Heating | 73765.78823 | 88518.94587 | 3.21733 | 3.86080 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1600.48290 | 258.43418 | 2.43898 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13019.84935 | 15623.81922 | 0.99703 | 1.19643 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
6 | POINT_OF_SALE | Heating | 16079.31154 | 19295.17385 | 0.71262 | 0.85514 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 10428.74967 | 12514.49960 | 0.79861 | 0.95833 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
8 | FRONT_RETAIL | Heating | 16075.87692 | 19291.05230 | 0.71246 | 0.85495 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.82869E-002 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 12.00000 | 0.00000 | 1.82869E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 109627.12367 | 131552.54840 | 4.89861 | 5.87834 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -32.70000 | 1.83376E-004 | 12.00000 | 0.00000 | 1.82869E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 22022.47 | 1.69069 | 1.69069 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 56121.05 | 1.72490 | 1.72490 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 112122.44 | 7.96374 | 7.96374 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 237110.37 | 3.86080 | 3.86080 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 16980.23 | 1.19643 | 1.19643 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 33196.54 | 0.85514 | 0.85514 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 13937.19 | 0.95833 | 0.95833 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 33192.46 | 0.85495 | 0.85495 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.72490 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.76644 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19643 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95833 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.87834 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 5.87834 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 131696.21019 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.72490 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.72490 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.72490 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.72490 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.72490 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.72490 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.76644 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.76644 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.76644 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.76644 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.96374 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.96374 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97522 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19643 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19643 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19643 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19643 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19643 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.19643 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95833 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95833 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95833 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95833 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95833 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95833 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.72490 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.96374 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.19643 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.95833 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.72490 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.28946 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.72490 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.72490 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.72490 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.72490 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.72490 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86245 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.72490 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 31846.93666 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 34024.91000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 17012.45500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 34024.91000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73953 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73953 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73953 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73953 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34024.91000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56121.05088 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.72490 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1887.90902 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 56121.05088 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.96374 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.43898 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.96374 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.96374 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.96374 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.96374 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.96374 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.98187 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.96374 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 161032.38136 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 170865.06000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 85432.53000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 170865.06000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71466 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71466 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71466 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71466 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 170865.06000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 323663.63443 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.96374 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14725.36505 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 323663.63443 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19643 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.22982 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19643 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19643 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19643 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.19643 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19643 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59822 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.19643 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21122.92593 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22648.67000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11324.33500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 22648.67000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75250 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75250 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75250 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75250 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22648.67000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 40741.13715 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19643 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1364.06433 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 40741.13715 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95833 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.22982 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95833 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95833 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95833 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95833 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95833 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47917 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95833 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17866.25443 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19073.41000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9536.70500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19073.41000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73679 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73679 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73679 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73679 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19073.41000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35477.71119 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95833 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1092.60322 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 35477.71119 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32669.7 | 10.30 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 164599.3 | 11.64 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21709.2 | 103.26 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18320.3 | 133.55 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1593.79 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.45 | N/A | 2.615 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.3761862028 | 0.6053770718 | Pass | Pass | 0.2831688623 | 0.4331998093 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1345022533 | 0.4240996434 | Pass | Pass | 6.4885284843E-002 | 0.2218487726 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.3754218394 | 0.6890577171 | Pass | Pass | 0.4214953030 | 0.6054155318 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.3844835308 | 0.6824198318 | Pass | Pass | 0.3071812719 | 0.4439254442 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.2502028805 | 0.4787653586 | Pass | Pass | 0.1018743304 | 0.5038005656 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 1600.48 | 1593.79 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.615 | 0.446 | 0.451 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.615 | 0.446 | 0.451 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.45 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.615 | 0.446 | 0.451 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 90.63 | 2.674 | 0.442 | 0.447 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 90.63 | 2.674 | 0.442 | 0.447 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 8.3451 | 379.89 | 3170.22 | LightsWired | BLDG_LIGHT_BACK_SCH | 69.84 | 168.00 | 68.87 | 0.0000 | Y | 40.98 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 17.7333 | 1600.48 | 28381.87 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 363.63 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 17.7333 | 150.81 | 2674.36 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.26 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 17.7333 | 150.81 | 2674.36 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.26 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 13.5608 | 12.00 | 162.73 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 2.08 |
Interior Lighting Total | 16.1568 | 2293.99 | 37063.54 | 475.23 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7322.00 | AstronomicalClock | - | 83.52 | 83.52 | 114.79 | |
Exterior Lighting Total | 7322.00 | 114.79 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 34024.91 | 25162.44 | 8862.47 | 0.74 | 3.50 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 170865.06 | 122110.42 | 48754.64 | 0.71 | 3.23 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22648.67 | 17043.12 | 5605.55 | 0.75 | 3.50 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19073.41 | 14053.10 | 5020.31 | 0.74 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32669.7 | 10.30 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 164599.3 | 11.64 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21709.2 | 103.26 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18320.3 | 133.55 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 131696.21 | 0.79 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 56121.05 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 323663.63 | 0.79 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 40741.14 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 35477.71 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.59 | 1110.54 | 5.88 | 11036.57 | 1877.50 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.72 | 1887.91 | 1094.51 | 1.00 | 1.31 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1110.54 | 7.96 | 14725.37 | 1849.05 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.20 | 1364.06 | 1140.11 | 1.00 | 1.32 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 0.96 | 1092.60 | 1140.11 | 1.00 | 1.37 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 18576.90 | 22292.28 | 58.68 | 1.362 | 1.634 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01022 | 20.92 | 0.01270 | 0.289 | 0.00 |
CORE_RETAIL | 87915.72 | 105498.87 | 65.92 | 6.472 | 7.766 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00972 | 20.92 | 0.01270 | 2.439 | 0.00 |
POINT_OF_SALE | 13019.85 | 15623.82 | 103.60 | 0.997 | 1.196 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00897 | 29.79 | 0.01270 | 0.230 | 0.00 |
FRONT_RETAIL | 10428.75 | 12514.50 | 82.98 | 0.799 | 0.958 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00909 | 29.79 | 0.01270 | 0.230 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.018 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.05 | 100.00 | 0.00001 | 30.10 | 0.01270 | 0.018 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 32517.54 | 39021.05 | 102.72 | 1.437 | 1.725 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00783 | -32.70 | 0.00018 | 0.289 | 0.00 |
CORE_RETAIL | 73765.79 | 88518.95 | 55.31 | 3.217 | 3.861 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00778 | -32.70 | 0.00018 | 2.439 | 0.00 |
POINT_OF_SALE | 16079.31 | 19295.17 | 127.94 | 0.713 | 0.855 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00787 | -32.70 | 0.00018 | 0.230 | 0.00 |
FRONT_RETAIL | 16075.88 | 19291.05 | 127.92 | 0.712 | 0.855 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00787 | -32.70 | 0.00018 | 0.230 | 0.00 |
FRONT_ENTRY | 109627.12 | 131552.55 | 10962.71 | 4.899 | 5.878 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 20.96 | 0.00596 | -32.70 | 0.00018 | 0.018 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.69 | 1.69 | 1.72 | 1.72 | 1.7249 | 1.7249 | 1.7249 | 1.0000 | 1.0000 |
PSZ-AC:2 | 7.96 | 7.96 | 3.86 | 3.86 | 7.9637 | 7.7664 | 7.9637 | 0.9752 | 1.0000 |
PSZ-AC:3 | 1.20 | 1.20 | 0.86 | 0.86 | 1.1964 | 1.1964 | 1.1964 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.96 | 0.96 | 0.85 | 0.85 | 0.9583 | 0.9583 | 0.9583 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 131696.210 | 131696.210 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 131696.21 | 131696.21 | 5.878338 | 20.79 | 12.41 | 0.00594032 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 20.96 | 0.00595828 | 37.1221 | 131552.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 34024.910 | 0.000 | 1.724900 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 34024.91 | 26837.06 | 1.724900 | 25.05 | 17.54 | 0.01001209 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 16.7811 | 23.88 | 0.01022429 | 52.9654 | 18576.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 56121.051 | 56121.051 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56121.05 | 56121.05 | 1.724897 | 11.94 | 9.33 | 0.00654328 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 16.7812 | 21.11 | 0.00782576 | 48.1694 | 32517.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 170865.060 | 0.000 | 7.963740 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 170865.06 | 130063.93 | 7.963740 | 25.95 | 18.13 | 0.01038301 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 30.6261 | 23.89 | 0.00972007 | 50.3906 | 80032.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 323663.634 | 323663.634 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 323663.63 | 323663.63 | 7.963742 | -12.97 | -12.97 | 0.00297979 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 30.6261 | 21.11 | 0.00777676 | 47.8710 | 73765.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 22648.670 | 0.000 | 1.196430 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 22648.67 | 18710.88 | 1.196430 | 25.06 | 17.29 | 0.00968951 | 12.80 | 11.72 | 0.00850000 | 30.00 | 0.01270324 | 21.07 | 19.2088 | 23.89 | 0.00897016 | 46.5505 | 12994.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 40741.137 | 40741.137 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40741.14 | 40741.14 | 1.196432 | 6.52 | 5.96 | 0.00580632 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.2088 | 21.11 | 0.00787289 | 48.4554 | 16079.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 19073.410 | 0.000 | 0.958330 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 19073.41 | 15233.04 | 0.958330 | 25.38 | 17.61 | 0.00995680 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 23.9813 | 23.89 | 0.00908547 | 47.1404 | 10395.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 35477.711 | 35477.711 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35477.71 | 35477.71 | 0.958331 | 6.52 | 5.96 | 0.00580584 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 23.9813 | 21.11 | 0.00787284 | 48.4552 | 16075.88 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 131696.210 | 131696.210 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 5.878338 | 6.78316022 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 131696.21 | 131696.21 | 1.0000 | 6.78316022 | 5.878338 | 20.79 | 12.41 | 0.00594032 | 35979.8 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 131696.21 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.98 | 0.00595828 | 20.96 | 0.00595828 | 37.1221 | 131552.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34024.910 | 0.000 | 1.724900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4520 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 34024.91 | 26837.06 | 1.0000 | 1.99040499 | 1.724900 | 25.05 | 17.54 | 0.01001209 | 50674.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34024.91 | 30.10 | 0.01270324 | 21.10 | 0.28945795 | 16.7811 | 23.89 | 0.00939449 | 23.88 | 0.01022429 | 52.9654 | 18576.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56121.051 | 56121.051 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.724897 | 1.99040128 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56121.05 | 56121.05 | 1.0000 | 1.99040128 | 1.724897 | 11.94 | 9.33 | 0.00654328 | 28507.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56121.05 | -32.70 | 0.00018338 | -32.70 | 0.28945795 | 16.7812 | 20.94 | 0.00782576 | 21.11 | 0.00782576 | 48.1694 | 32517.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 170865.060 | 0.000 | 7.963740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1415 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 170865.06 | 130063.93 | 1.0000 | 9.18955754 | 7.963740 | 25.95 | 18.13 | 0.01038301 | 52541.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 170865.06 | 30.10 | 0.01270324 | 21.10 | 2.43898389 | 30.6261 | 23.89 | 0.00923174 | 23.89 | 0.00972007 | 50.3906 | 80032.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 323663.634 | 323663.634 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.963742 | 9.18956006 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 323663.63 | 323663.63 | 1.0000 | 9.18956006 | 7.963742 | -12.97 | -12.97 | 0.00297979 | -5647.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 323663.63 | -32.70 | 0.00018338 | -32.70 | 2.43898389 | 30.6261 | 20.89 | 0.00777676 | 21.11 | 0.00777676 | 47.8710 | 73765.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22648.670 | 0.000 | 1.196430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8523 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 22648.67 | 18710.88 | 1.0000 | 1.38059032 | 1.196430 | 25.06 | 17.29 | 0.00968951 | 49869.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22648.67 | 30.00 | 0.01270324 | 21.07 | 0.22982011 | 19.2088 | 23.89 | 0.00897125 | 23.89 | 0.00897016 | 46.5505 | 12994.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40741.137 | 40741.137 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.196432 | 1.38059301 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40741.14 | 40741.14 | 1.0000 | 1.38059301 | 1.196432 | 6.52 | 5.96 | 0.00580632 | 21144.1 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40741.14 | -32.70 | 0.00018338 | -32.70 | 0.22982011 | 19.2088 | 20.94 | 0.00787289 | 21.11 | 0.00787289 | 48.4554 | 16079.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19073.410 | 0.000 | 0.958330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3492 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 19073.41 | 15233.04 | 1.0000 | 1.10584081 | 0.958330 | 25.38 | 17.61 | 0.00995680 | 50876.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19073.41 | 30.10 | 0.01270324 | 21.10 | 0.22982011 | 23.9813 | 23.89 | 0.00908675 | 23.89 | 0.00908547 | 47.1404 | 10395.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35477.711 | 35477.711 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.958331 | 1.10584254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35477.71 | 35477.71 | 1.0000 | 1.10584254 | 0.958331 | 6.52 | 5.96 | 0.00580584 | 21139.7 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35477.71 | -32.70 | 0.00018338 | -32.70 | 0.22982011 | 23.9813 | 20.94 | 0.00787284 | 21.11 | 0.00787284 | 48.4552 | 16075.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3108.67 | 3886.33 | 2578.67 |
CORE_RETAIL | 2942.00 | 3357.00 | 1835.00 |
POINT_OF_SALE | 3103.33 | 3215.00 | 1887.83 |
FRONT_RETAIL | 3133.17 | 3580.33 | 2188.50 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3799.67 | 3927.50 | 2606.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 154.83 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 27.17 | 2.33 | 0.00 | 0.00 |
POINT_OF_SALE | 121.67 | 0.83 | 0.00 | 0.00 |
FRONT_RETAIL | 149.33 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 264.33 | 2.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.456 | 0.054 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.912 | 0.011 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.912 | 0.059 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.911 | 0.059 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.440 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.880 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.880 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.880 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1410.51 | 3648.35 | 09-APR-05:50 | 124349.17 | 29-JUN-16:00 |
Electricity:Building | 670.39 | 3648.35 | 01-JAN-00:10 | 44155.79 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 90.98 | 618.37 | 01-JAN-00:10 | 5639.90 | 02-JAN-09:10 |
InteriorLights:Electricity | 475.23 | 1853.18 | 01-JAN-00:10 | 33384.75 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 40.98 | 158.51 | 01-JAN-00:10 | 2880.76 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 475.23 | 1853.18 | 01-JAN-00:10 | 33384.75 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 447.93 | 2194.53 | 01-JAN-00:10 | 30196.29 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 363.63 | 1419.09 | 01-JAN-00:10 | 25543.68 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 87.19 | 620.53 | 01-JAN-00:10 | 5327.81 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.26 | 133.72 | 01-JAN-00:10 | 2406.93 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 42.21 | 206.79 | 01-JAN-00:10 | 2845.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.26 | 133.72 | 01-JAN-00:10 | 2406.93 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 2.08 | 8.14 | 01-JAN-00:10 | 146.46 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 2.08 | 8.14 | 01-JAN-00:10 | 146.46 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1410.51 | 3648.35 | 29-MAY-18:10 | 124349.17 | 29-JUN-16:00 |
ElectricityPurchased:Plant | 1410.51 | 3648.35 | 29-MAY-18:10 | 124349.17 | 29-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1410.51 | 3648.35 | 29-MAY-18:10 | 124349.17 | 29-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1410.51 | 3648.35 | 29-MAY-18:10 | 124349.17 | 29-JUN-16:00 |
ElectricityNet:Plant | 1410.51 | 3648.35 | 29-MAY-18:10 | 124349.17 | 29-JUN-16:00 |
Cogeneration:ElectricityNet | 1410.51 | 3648.35 | 29-MAY-18:10 | 124349.17 | 29-JUN-16:00 |
Electricity:HVAC | 625.33 | 0.00 | 02-JAN-21:10 | 80193.38 | 29-JUN-16:00 |
Fans:Electricity | 503.85 | 0.00 | 02-JAN-21:10 | 30106.51 | 04-JAN-09:40 |
General:Fans:Electricity | 503.85 | 0.00 | 02-JAN-21:10 | 30106.51 | 04-JAN-09:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 121.48 | 0.00 | 01-JAN-00:10 | 61123.44 | 29-JUN-16:00 |
ExteriorLights:Electricity | 114.79 | 0.00 | 01-JAN-08:20 | 7322.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 114.79 | 0.00 | 01-JAN-08:20 | 7322.00 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1559.31 | 1862.00 | 04-JAN-21:20 | 462991.21 | 06-JAN-05:10 |
Gas:Plant | 100.78 | 1862.00 | 02-JAN-05:50 | 6347.25 | 27-FEB-12:40 |
WaterSystems:Gas | 100.78 | 1862.00 | 02-JAN-05:50 | 6347.25 | 27-FEB-12:40 |
Water Heater:WaterSystems:Gas | 100.78 | 1862.00 | 02-JAN-05:50 | 6347.25 | 27-FEB-12:40 |
Gas:HVAC | 1458.54 | 0.00 | 01-JAN-00:40 | 461129.21 | 06-JAN-05:10 |
Heating:Gas | 1458.54 | 0.00 | 01-JAN-00:40 | 461129.21 | 06-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 19-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2470.53 | 0.00 | 02-JAN-21:10 | 595030.25 | 01-JAN-07:10 |
EnergyTransfer:Building | 907.26 | 0.00 | 02-JAN-21:10 | 237488.83 | 01-JAN-07:10 |
EnergyTransfer:Zone:BACK_SPACE | 134.12 | 0.00 | 01-JAN-00:40 | 47463.31 | 03-JAN-05:20 |
Heating:EnergyTransfer | 497.05 | 0.00 | 02-JAN-21:10 | 237488.83 | 01-JAN-07:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 101.25 | 0.00 | 01-JAN-00:40 | 47463.31 | 03-JAN-05:20 |
Cooling:EnergyTransfer | 410.21 | 0.00 | 01-JAN-00:10 | 81861.63 | 30-JUN-14:50 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 32.87 | 0.00 | 01-JAN-00:10 | 11838.13 | 30-JUN-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 371.61 | 0.00 | 01-JAN-00:10 | 158329.47 | 25-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 71.34 | 0.00 | 01-JAN-00:10 | 158329.47 | 25-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 300.27 | 0.00 | 01-JAN-00:10 | 52511.48 | 30-JUN-14:50 |
EnergyTransfer:Zone:POINT_OF_SALE | 73.58 | 0.00 | 01-JAN-00:40 | 24979.76 | 16-DEC-05:20 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 24.99 | 0.00 | 01-JAN-00:40 | 24979.76 | 16-DEC-05:20 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 48.59 | 0.00 | 01-JAN-00:10 | 11457.70 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 65.24 | 0.00 | 01-JAN-00:40 | 24984.07 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 36.77 | 0.00 | 01-JAN-00:40 | 24984.07 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 28.47 | 0.00 | 01-JAN-00:10 | 9318.43 | 01-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 262.71 | 0.00 | 01-JAN-20:10 | 99846.23 | 05-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 262.71 | 0.00 | 01-JAN-20:10 | 99846.23 | 05-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1563.27 | 0.00 | 01-JAN-00:40 | 366616.36 | 06-JAN-05:10 |
HeatingCoils:EnergyTransfer | 1159.27 | 0.00 | 01-JAN-00:40 | 366616.36 | 06-JAN-05:10 |
CoolingCoils:EnergyTransfer | 404.00 | 0.00 | 01-JAN-00:10 | 201240.60 | 30-JUN-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 101.249 | -32.874 | 0.000 | 0.000 | 40.430 | 40.985 | 49.992 | 0.000 | 0.000 | 0.168 | 0.001 | 0.000 | 0.000 | 0.000 | -42.257 | -157.693 |
CORE_RETAIL | 0.000 | 0.000 | 71.337 | -300.274 | 0.000 | 0.000 | 169.491 | 363.635 | 84.299 | 6.198 | 0.000 | 0.134 | 0.012 | 0.000 | -9.892 | 0.000 | -37.277 | -347.652 |
POINT_OF_SALE | 0.000 | 0.000 | 24.990 | -48.587 | 0.000 | 0.000 | 15.834 | 34.265 | 52.922 | 37.658 | 0.000 | 0.069 | 0.001 | 0.000 | -32.442 | 0.000 | -18.869 | -65.840 |
FRONT_RETAIL | 0.000 | 0.000 | 36.766 | -28.469 | 0.000 | 0.000 | 16.043 | 34.265 | 7.943 | 37.771 | 0.000 | 0.071 | 0.000 | 0.000 | -31.886 | 0.000 | -18.470 | -54.033 |
FRONT_ENTRY | 262.710 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.085 | 0.000 | 7.542 | 0.000 | 0.042 | 0.000 | 0.000 | -6.697 | 0.000 | -259.774 | -5.907 |
Total Facility | 262.710 | 0.000 | 234.341 | -410.204 | 0.000 | 0.000 | 241.798 | 475.233 | 195.156 | 89.170 | 0.000 | 0.484 | 0.014 | 0.000 | -80.916 | 0.000 | -376.646 | -631.125 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 10-AUG-04:02 | 0.00 | 0.00 | 0.00 | -22236.78 | 0.00 | 0.00 | 0.00 | 158.51 | 613.14 | 0.00 | 0.00 | 0.00 | 21913.08 | 0.00 | -0.00 | 0.00 | -447.95 | 0.00 |
CORE_RETAIL | 01-JUL-04:02 | 0.00 | 0.00 | 0.00 | -146869.41 | 0.00 | 0.00 | 0.00 | 1419.09 | 775.43 | 0.00 | 0.00 | 0.00 | 145746.81 | 0.00 | -378.17 | 0.00 | -693.75 | 0.00 |
POINT_OF_SALE | 26-AUG-04:02 | 0.00 | 0.00 | 0.00 | -18217.41 | 0.00 | 0.00 | 0.00 | 133.72 | 486.81 | 0.00 | 0.00 | 0.00 | 18770.53 | 0.00 | -1078.88 | 0.00 | -94.77 | 0.00 |
FRONT_RETAIL | 26-AUG-04:02 | 0.00 | 0.00 | 0.00 | -14768.40 | 0.00 | 0.00 | 0.00 | 133.72 | 73.07 | 0.00 | 0.00 | 0.00 | 15691.10 | 0.00 | -1038.66 | 0.00 | -90.82 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-04:02 | 0.00 | 0.00 | 0.00 | -174661.62 | 0.00 | 0.00 | 0.00 | 1853.18 | 2393.56 | 0.00 | 0.00 | 0.00 | 173615.94 | 0.00 | -1922.04 | 0.00 | -1279.02 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 18-APR-04:01 | 0.00 | 0.00 | 54336.42 | 0.00 | 0.00 | 0.00 | 0.00 | 158.51 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1259.62 | -53848.46 |
CORE_RETAIL | 31-OCT-04:01 | 0.00 | 0.00 | 301305.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1419.09 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -219.13 | 0.00 | -3535.91 | -300003.23 |
POINT_OF_SALE | 31-OCT-04:01 | 0.00 | 0.00 | 38337.14 | 0.00 | 0.00 | 0.00 | 0.00 | 133.72 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -736.52 | 0.00 | -1573.04 | -36810.38 |
FRONT_RETAIL | 31-OCT-04:01 | 0.00 | 0.00 | 33461.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.72 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -694.36 | 0.00 | -1434.07 | -31563.71 |
FRONT_ENTRY | 05-JAN-18:00 | 99846.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 67.06 | 0.00 | -793.40 | 0.00 | -99266.29 | 0.00 |
Total Facility | 31-OCT-04:01 | 3167.82 | 0.00 | 427269.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.18 | 2393.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1793.08 | 0.00 | -9940.79 | -422950.56 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7249 | 0.0000 | 61.3418 | 1.0000 | 0.2895 | 1.7249 | 0.1712 | 1.0000 | 0.2895 | 0.1678 | ||
PSZ-AC:2 | 7.7664 | 0.0000 | 258.4342 | 1.0000 | 2.4390 | 7.9637 | 0.3063 | 1.0000 | 2.4390 | 0.3063 | ||
PSZ-AC:3 | 1.1964 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 1.1964 | 0.1921 | 1.0000 | 0.2298 | 0.1921 | ||
PSZ-AC:4 | 0.9583 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 0.9583 | 0.2398 | 1.0000 | 0.2298 | 0.2398 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7249 | 0.0000 | 61.3418 | 1.0000 | 0.2895 | 1.7249 | 1.0000 | 1.0000 | 0.2895 | 0.1678 | ||
PSZ-AC:2 | 7.7664 | 0.0000 | 258.4342 | 1.0000 | 2.4390 | 7.7664 | 1.0000 | 1.0000 | 2.4390 | 0.3140 | ||
PSZ-AC:3 | 1.1964 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 1.1964 | 1.0000 | 1.0000 | 0.2298 | 0.1921 | ||
PSZ-AC:4 | 0.9583 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 0.9583 | 1.0000 | 1.0000 | 0.2298 | 0.2398 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000762 | 379.89 | 0.2895 | 1.0000 | 0.2895 | 1.000 | 0.2895 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001524 | 1600.48 | 2.4390 | 1.0000 | 2.4390 | 1.000 | 2.4390 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001524 | 150.81 | 0.2298 | 1.0000 | 0.2298 | 1.000 | 0.2298 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001524 | 150.81 | 0.2298 | 1.0000 | 0.2298 | 1.000 | 0.2298 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000762 | 379.8900 | 0.2895 | 0.2895 | 0.2895 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001524 | 1600.4829 | 2.4390 | 2.4390 | 2.4390 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001524 | 150.8100 | 0.2298 | 0.2298 | 0.2298 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001524 | 150.8100 | 0.2298 | 0.2298 | 0.2298 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7249 | 1.7249 | 1.7249 | 0.2895 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.7664 | 7.7664 | 7.7664 | 2.4390 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1964 | 1.1964 | 1.1964 | 0.2298 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9583 | 0.9583 | 0.9583 | 0.2298 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7249 | 1.7249 | 1.7249 | 1.7249 | 0.2895 | 1.0000 |
PSZ-AC:2 | 7.7664 | 7.9637 | 7.7664 | 7.7664 | 2.4390 | 1.0000 |
PSZ-AC:3 | 1.1964 | 1.1964 | 1.1964 | 1.1964 | 0.2298 | 1.0000 |
PSZ-AC:4 | 0.9583 | 0.9583 | 0.9583 | 0.9583 | 0.2298 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7249 | 1.7249 | 1.7249 | 0.2895 | 0.1678 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.7664 | 7.7664 | 7.7664 | 2.4390 | 0.6317 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1964 | 1.1964 | 1.1964 | 0.2298 | 0.2688 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9583 | 0.9583 | 0.9583 | 0.2298 | 0.2688 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7249 | 1.7249 | 1.7249 | 1.7249 | 0.2895 | 1.0000 |
PSZ-AC:2 | 7.7664 | 7.7664 | 7.7664 | 7.7664 | 2.4390 | 1.0000 |
PSZ-AC:3 | 1.1964 | 1.1964 | 1.1964 | 1.1964 | 0.2298 | 1.0000 |
PSZ-AC:4 | 0.9583 | 0.9583 | 0.9583 | 0.9583 | 0.2298 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:29
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 1458.54 | 461129.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 121.48 | 61123.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 475.23 | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 114.79 | 7322.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 503.85 | 30106.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 100.78 | 6347.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1410.51 |
Natural Gas | 0.00 | 1559.31 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 2969.83 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 207.16 |
Space Heating | 0.00 |
Space Cooling | 52.96 |
Fans (All) | 219.64 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 614.87 |
Subtotal | 614.87 |
Natural Gas [MJ/m2] | |
Space Heating | 635.81 |
Service Water Heating | 43.93 |
Miscellaneous (All) | 679.74 |
Subtotal | 679.74 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.00 |
Space Heating | 49.11 |
Space Cooling | 4.09 |
Fans (All) | 16.97 |
Service Water Heating | 3.39 |
Receptacle Equipment | 6.57 |
Miscellaneous | 3.87 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3641. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.369812E+12 |
February | 0.000 | 0.254571E+12 |
March | 0.000 | 0.207763E+12 |
April | 0.000 | 0.773353E+11 |
May | 0.000 | 0.852937E+10 |
June | 0.000 | 0.261058E+09 |
July | 0.000 | 0.261898E+08 |
August | 0.000 | 0.176550E+09 |
September | 0.000 | 0.313842E+10 |
October | 0.000 | 0.500382E+11 |
November | 0.000 | 0.148405E+12 |
December | 0.000 | 0.338481E+12 |
Annual Sum or Average | 0.145854E+13 | |
Minimum of Months | 0.000 | 0.261898E+08 |
Maximum of Months | 0.000 | 0.369812E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1103160.83 | 8823.79 | 12-JAN-06:06 | -17.4 | -17.9 | 0.165228E+10 | 1854.44 | 19-JAN-15:00 | -2.8 | -3.5 |
February | 22402.82 | 224.03 | 11-FEB-06:07 | -16.6 | -16.9 | 0.150875E+10 | 1854.45 | 04-FEB-11:09 | 0.37 | -1.8 |
March | 31010874.16 | 1412.63 | 31-MAR-15:00 | 8.30 | 2.61 | 0.172573E+10 | 1854.44 | 18-MAR-14:00 | -0.6 | -4.6 |
April | 0.521180E+09 | 3121.28 | 24-APR-12:20 | 6.30 | 3.57 | 0.169196E+10 | 2417.63 | 13-APR-14:00 | 20.00 | 8.07 |
May | 0.314147E+10 | 7749.58 | 25-MAY-15:00 | 28.90 | 19.65 | 0.207604E+10 | 2451.26 | 10-MAY-14:50 | 24.85 | 13.55 |
June | 0.576977E+10 | 20900.05 | 29-JUN-04:02 | 22.20 | 19.58 | 0.217795E+10 | 2451.30 | 17-JUN-10:30 | 21.95 | 12.98 |
July | 0.864652E+10 | 22225.41 | 21-JUL-04:02 | 18.22 | 18.14 | 0.218382E+10 | 2451.25 | 08-JUL-10:09 | 13.30 | 12.39 |
August | 0.788630E+10 | 22241.25 | 10-AUG-04:02 | 15.60 | 15.14 | 0.227496E+10 | 2451.27 | 17-AUG-14:39 | 10.93 | 10.04 |
September | 0.444343E+10 | 9764.86 | 01-SEP-15:00 | 26.10 | 17.80 | 0.206415E+10 | 2451.28 | 14-SEP-14:20 | 20.03 | 11.70 |
October | 0.207432E+10 | 4151.13 | 24-OCT-18:51 | 3.30 | 1.89 | 0.177726E+10 | 2451.27 | 21-OCT-13:09 | 19.50 | 11.33 |
November | 0.358684E+09 | 5801.23 | 04-NOV-11:03 | -2.2 | -3.7 | 0.159983E+10 | 2287.31 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 55251.25 | 552.51 | 16-DEC-06:07 | -15.5 | -15.8 | 0.165478E+10 | 1854.44 | 06-DEC-15:09 | -6.7 | -6.9 |
Annual Sum or Average | 0.328739E+11 | 0.223875E+11 | ||||||||
Minimum of Months | 22402.82 | 224.03 | -17.4 | -17.9 | 0.150875E+10 | 1854.44 | -6.7 | -6.9 | ||
Maximum of Months | 0.864652E+10 | 22241.25 | 28.90 | 19.65 | 0.227496E+10 | 2451.30 | 24.85 | 13.55 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386110E+10 | 86089.82 | 10-JAN-11:42 | -15.8 | -16.4 | 0.696116E+10 | 7812.80 | 02-JAN-15:09 | -11.8 | -12.5 |
February | 0.713557E+10 | 93033.46 | 10-FEB-20:01 | -18.2 | -18.6 | 0.635635E+10 | 7812.82 | 04-FEB-11:09 | 0.37 | -1.8 |
March | 0.136704E+11 | 26891.35 | 29-MAR-15:00 | 4.40 | 1.35 | 0.727411E+10 | 8247.36 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.215621E+11 | 55214.04 | 13-APR-05:03 | -4.2 | -5.4 | 0.745390E+10 | 10327.14 | 18-APR-14:09 | 17.33 | 10.20 |
May | 0.340158E+11 | 129884.30 | 27-MAY-04:03 | 14.35 | 12.96 | 0.900980E+10 | 10327.22 | 18-MAY-14:00 | 28.90 | 16.58 |
June | 0.414506E+11 | 125184.60 | 27-JUN-04:03 | 15.60 | 14.89 | 0.923895E+10 | 10327.42 | 15-JUN-14:50 | 21.60 | 13.12 |
July | 0.492661E+11 | 146904.05 | 01-JUL-04:02 | 9.90 | 9.57 | 0.920806E+10 | 10327.13 | 08-JUL-10:09 | 13.30 | 12.39 |
August | 0.468995E+11 | 146006.73 | 25-AUG-04:03 | 8.72 | 8.66 | 0.959437E+10 | 10327.28 | 17-AUG-14:39 | 10.93 | 10.04 |
September | 0.358541E+11 | 136215.45 | 02-SEP-04:03 | 14.82 | 11.36 | 0.874157E+10 | 10327.24 | 22-SEP-14:09 | 13.30 | 11.04 |
October | 0.267963E+11 | 54245.37 | 25-OCT-05:02 | -3.5 | -3.8 | 0.756214E+10 | 10327.23 | 21-OCT-12:39 | 18.87 | 11.19 |
November | 0.144435E+11 | 45638.18 | 03-NOV-05:03 | 0.00 | -1.8 | 0.678790E+10 | 10327.07 | 01-NOV-14:09 | 17.88 | 13.28 |
December | 0.531947E+10 | 62673.28 | 27-DEC-11:02 | -7.3 | -7.8 | 0.697153E+10 | 7812.79 | 23-DEC-11:09 | -15.4 | -16.0 |
Annual Sum or Average | 0.300275E+12 | 0.951598E+11 | ||||||||
Minimum of Months | 0.386110E+10 | 26891.35 | -18.2 | -18.6 | 0.635635E+10 | 7812.79 | -15.4 | -16.0 | ||
Maximum of Months | 0.492661E+11 | 146904.05 | 15.60 | 14.89 | 0.959437E+10 | 10327.42 | 28.90 | 16.58 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.683824E+09 | 8573.51 | 31-JAN-06:04 | -14.3 | -14.6 | 0.655929E+09 | 736.18 | 14-JAN-16:49 | -12.3 | -12.8 |
February | 0.134308E+10 | 9972.19 | 13-FEB-06:04 | -24.0 | -24.3 | 0.607886E+09 | 953.76 | 28-FEB-15:50 | 6.10 | 1.53 |
March | 0.191342E+10 | 6706.65 | 02-MAR-06:04 | -8.3 | -8.8 | 0.699050E+09 | 973.07 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.284688E+10 | 6073.43 | 13-APR-14:10 | 19.08 | 7.51 | 0.727425E+09 | 973.10 | 22-APR-10:00 | 15.00 | 5.64 |
May | 0.500666E+10 | 13624.36 | 26-MAY-04:03 | 19.40 | 15.70 | 0.858548E+09 | 973.17 | 27-MAY-15:00 | 21.70 | 14.15 |
June | 0.637246E+10 | 14965.32 | 28-JUN-04:03 | 15.40 | 14.76 | 0.869829E+09 | 973.17 | 07-JUN-14:09 | 22.20 | 14.32 |
July | 0.829363E+10 | 17281.46 | 25-JUL-04:02 | 16.02 | 14.98 | 0.867608E+09 | 973.20 | 31-JUL-14:20 | 20.40 | 14.42 |
August | 0.854832E+10 | 18221.81 | 26-AUG-04:02 | 12.85 | 12.65 | 0.904334E+09 | 973.20 | 25-AUG-14:30 | 28.30 | 19.00 |
September | 0.654289E+10 | 16073.19 | 02-SEP-04:03 | 14.82 | 11.36 | 0.839588E+09 | 973.18 | 01-SEP-14:09 | 25.68 | 18.04 |
October | 0.432901E+10 | 9429.73 | 20-OCT-14:10 | 18.90 | 10.05 | 0.757373E+09 | 973.15 | 02-OCT-14:30 | 10.00 | 9.40 |
November | 0.213441E+10 | 7245.77 | 25-NOV-13:52 | -13.3 | -14.1 | 0.659232E+09 | 973.09 | 01-NOV-14:09 | 17.88 | 13.28 |
December | 0.573062E+09 | 5913.02 | 15-DEC-14:13 | -8.3 | -8.7 | 0.656924E+09 | 736.18 | 23-DEC-12:30 | -15.5 | -16.1 |
Annual Sum or Average | 0.485877E+11 | 0.910373E+10 | ||||||||
Minimum of Months | 0.573062E+09 | 5913.02 | -24.0 | -24.3 | 0.607886E+09 | 736.18 | -15.5 | -16.1 | ||
Maximum of Months | 0.854832E+10 | 18221.81 | 19.40 | 15.70 | 0.904334E+09 | 973.20 | 28.30 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179858E+09 | 4104.37 | 28-JAN-06:05 | -26.4 | -26.6 | 0.655926E+09 | 736.18 | 30-JAN-15:20 | -6.5 | -7.4 |
February | 0.517799E+09 | 9435.28 | 14-FEB-11:51 | -20.0 | -20.7 | 0.599928E+09 | 822.12 | 28-FEB-15:50 | 6.10 | 1.53 |
March | 0.758750E+09 | 7112.52 | 12-MAR-11:12 | -11.3 | -13.1 | 0.686603E+09 | 858.85 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.136589E+10 | 3873.54 | 13-APR-14:10 | 19.08 | 7.51 | 0.698495E+09 | 973.10 | 13-APR-14:00 | 20.00 | 8.07 |
May | 0.285482E+10 | 6230.72 | 18-MAY-14:10 | 28.57 | 16.70 | 0.820979E+09 | 973.13 | 18-MAY-14:09 | 28.57 | 16.70 |
June | 0.382207E+10 | 11678.61 | 29-JUN-04:02 | 22.20 | 19.58 | 0.857890E+09 | 973.13 | 15-JUN-14:00 | 21.70 | 13.19 |
July | 0.549394E+10 | 12868.23 | 25-JUL-04:02 | 16.02 | 14.98 | 0.864940E+09 | 973.16 | 07-JUL-14:30 | 21.95 | 14.12 |
August | 0.568213E+10 | 14772.45 | 26-AUG-04:02 | 12.85 | 12.65 | 0.898300E+09 | 973.10 | 19-AUG-10:20 | 17.93 | 13.27 |
September | 0.433289E+10 | 10196.01 | 01-SEP-04:02 | 16.02 | 16.02 | 0.804427E+09 | 973.15 | 07-SEP-14:00 | 23.90 | 14.99 |
October | 0.250433E+10 | 7076.59 | 20-OCT-14:10 | 18.90 | 10.05 | 0.710924E+09 | 973.14 | 18-OCT-14:09 | 16.78 | 11.26 |
November | 0.825997E+09 | 4571.38 | 10-NOV-14:00 | -1.7 | -4.3 | 0.639453E+09 | 945.22 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 0.131186E+09 | 9206.53 | 01-DEC-11:22 | -19.4 | -19.8 | 0.656897E+09 | 736.18 | 23-DEC-12:30 | -15.5 | -16.1 |
Annual Sum or Average | 0.284697E+11 | 0.889476E+10 | ||||||||
Minimum of Months | 0.131186E+09 | 3873.54 | -26.4 | -26.6 | 0.599928E+09 | 736.18 | -15.5 | -16.1 | ||
Maximum of Months | 0.568213E+10 | 14772.45 | 28.57 | 19.58 | 0.898300E+09 | 973.16 | 28.57 | 16.70 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.256491E+11 | 51080.48 | 16-JAN-07:01 | -1.6 |
February | 0.190905E+11 | 52414.00 | 21-FEB-05:01 | 2.30 |
March | 0.153167E+11 | 52100.94 | 28-MAR-04:01 | 2.12 |
April | 0.668508E+10 | 54336.37 | 18-APR-04:01 | 11.70 |
May | 0.834091E+09 | 52229.94 | 09-MAY-04:01 | 4.63 |
June | 22348916.59 | 35141.59 | 01-JUN-04:02 | 14.82 |
July | 2930776.19 | 1703.04 | 04-JUL-07:07 | 22.70 |
August | 1874426.29 | 609.45 | 20-AUG-08:35 | 19.83 |
September | 58013997.68 | 46051.04 | 28-SEP-04:02 | 6.20 |
October | 0.218358E+10 | 54166.01 | 31-OCT-04:01 | 10.00 |
November | 0.893199E+10 | 54117.41 | 01-NOV-04:01 | 10.60 |
December | 0.224718E+11 | 52035.49 | 05-DEC-05:41 | -1.1 |
Annual Sum or Average | 0.101248E+12 | |||
Minimum of Months | 1874426.29 | 609.45 | -1.6 | |
Maximum of Months | 0.256491E+11 | 54336.37 | 22.70 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209040E+11 | 277023.53 | 16-JAN-07:01 | -1.6 |
February | 0.131766E+11 | 287021.30 | 21-FEB-05:01 | 2.30 |
March | 0.939090E+10 | 281307.85 | 28-MAR-04:01 | 2.12 |
April | 0.281544E+10 | 286639.27 | 08-APR-04:01 | 4.22 |
May | 0.179377E+09 | 268177.07 | 01-MAY-04:01 | -2.9 |
June | 4103063.96 | 9026.89 | 25-JUN-07:10 | 22.98 |
July | 2748775.77 | 3207.30 | 05-JUL-05:10 | 19.60 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.103001E+10 | 301296.13 | 31-OCT-04:01 | 10.00 |
November | 0.620857E+10 | 293921.43 | 01-NOV-04:01 | 10.60 |
December | 0.176256E+11 | 276567.15 | 17-DEC-07:01 | -0.9 |
Annual Sum or Average | 0.713373E+11 | |||
Minimum of Months | 0.00 | 0.00 | -2.9 | |
Maximum of Months | 0.209040E+11 | 301296.13 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.691416E+10 | 36109.85 | 16-JAN-07:01 | -1.6 |
February | 0.435157E+10 | 36846.32 | 21-FEB-05:01 | 2.30 |
March | 0.324503E+10 | 36467.52 | 28-MAR-04:01 | 2.12 |
April | 0.132220E+10 | 37093.50 | 08-APR-04:01 | 4.22 |
May | 0.143239E+09 | 36764.45 | 09-MAY-04:01 | 4.63 |
June | 242300.81 | 498.26 | 25-JUN-07:10 | 22.98 |
July | 156269.24 | 253.66 | 05-JUL-05:10 | 19.60 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 568347.89 | 1783.71 | 28-SEP-05:03 | 6.70 |
October | 0.475209E+09 | 38336.53 | 31-OCT-04:01 | 10.00 |
November | 0.217291E+10 | 38304.79 | 01-NOV-04:01 | 10.60 |
December | 0.636443E+10 | 36465.50 | 17-DEC-07:41 | -0.8 |
Annual Sum or Average | 0.249897E+11 | |||
Minimum of Months | 0.00 | 0.00 | -1.6 | |
Maximum of Months | 0.691416E+10 | 38336.53 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.956554E+10 | 31020.63 | 16-JAN-07:01 | -1.6 |
February | 0.617608E+10 | 31941.85 | 21-FEB-05:01 | 2.30 |
March | 0.496073E+10 | 31617.96 | 28-MAR-04:01 | 2.12 |
April | 0.223492E+10 | 33192.98 | 18-APR-04:01 | 11.70 |
May | 0.333098E+09 | 31961.98 | 09-MAY-04:01 | 4.63 |
June | 11903082.73 | 19281.53 | 01-JUN-04:02 | 14.82 |
July | 544047.61 | 635.81 | 30-JUL-07:05 | 21.65 |
August | 266787.00 | 1200.68 | 19-AUG-05:06 | 4.60 |
September | 50574949.75 | 26117.48 | 28-SEP-04:02 | 6.20 |
October | 0.929343E+09 | 33460.47 | 31-OCT-04:01 | 10.00 |
November | 0.345354E+10 | 33450.51 | 01-NOV-04:01 | 10.60 |
December | 0.904895E+10 | 31431.02 | 17-DEC-07:11 | -0.9 |
Annual Sum or Average | 0.367655E+11 | |||
Minimum of Months | 266787.00 | 635.81 | -1.6 | |
Maximum of Months | 0.956554E+10 | 33460.47 | 21.65 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.534535E+11 | 99846.23 | 05-JAN-18:00 | -28.3 |
February | 0.378027E+11 | 87083.94 | 01-FEB-18:00 | -23.3 |
March | 0.346336E+11 | 69883.72 | 15-MAR-11:10 | -15.3 |
April | 0.185475E+11 | 51864.62 | 04-APR-11:03 | -4.9 |
May | 0.659574E+10 | 26742.51 | 08-MAY-11:05 | 6.53 |
June | 0.248813E+10 | 16807.74 | 09-JUN-11:05 | 12.38 |
July | 0.122410E+10 | 15144.84 | 08-JUL-11:05 | 13.30 |
August | 0.201289E+10 | 18253.70 | 17-AUG-11:02 | 11.93 |
September | 0.786460E+10 | 27606.43 | 27-SEP-11:10 | 7.38 |
October | 0.177977E+11 | 43466.48 | 29-OCT-11:02 | 0.68 |
November | 0.289926E+11 | 69451.75 | 25-NOV-17:00 | -15.6 |
December | 0.512963E+11 | 96378.30 | 24-DEC-12:10 | -26.9 |
Annual Sum or Average | 0.262709E+12 | |||
Minimum of Months | 0.122410E+10 | 15144.84 | -28.3 | |
Maximum of Months | 0.534535E+11 | 99846.23 | 13.30 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.343688E+10 | 2880.76 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.312713E+10 | 2880.76 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.356711E+10 | 2880.76 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.336554E+10 | 2880.76 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.350199E+10 | 2880.76 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.344215E+10 | 2880.76 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.342538E+10 | 2880.76 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.356711E+10 | 2880.76 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.336554E+10 | 2880.76 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.343688E+10 | 2880.76 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.332343E+10 | 2880.76 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.342538E+10 | 2880.76 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.409845E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.312713E+10 | 2880.76 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.356711E+10 | 2880.76 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.304941E+11 | 25543.68 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.277456E+11 | 25543.68 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.316486E+11 | 25543.68 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.298606E+11 | 25543.68 | 01-APR-09:09 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.310713E+11 | 25543.68 | 01-MAY-08:09 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.305400E+11 | 25543.68 | 01-JUN-08:09 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.303919E+11 | 25543.68 | 01-JUL-09:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.316486E+11 | 25543.68 | 01-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.298606E+11 | 25543.68 | 01-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.304941E+11 | 25543.68 | 02-OCT-08:09 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.294876E+11 | 25543.68 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.303919E+11 | 25543.68 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.363635E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.277456E+11 | 25543.68 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.316486E+11 | 25543.68 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.287339E+10 | 2406.93 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.261440E+10 | 2406.93 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.298218E+10 | 2406.93 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.281370E+10 | 2406.93 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.292778E+10 | 2406.93 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.287772E+10 | 2406.93 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.286376E+10 | 2406.93 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.298218E+10 | 2406.93 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.281370E+10 | 2406.93 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.287339E+10 | 2406.93 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.277855E+10 | 2406.93 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.286376E+10 | 2406.93 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.342645E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.261440E+10 | 2406.93 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.298218E+10 | 2406.93 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.287339E+10 | 2406.93 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.261440E+10 | 2406.93 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.298218E+10 | 2406.93 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.281370E+10 | 2406.93 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.292778E+10 | 2406.93 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.287772E+10 | 2406.93 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.286376E+10 | 2406.93 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.298218E+10 | 2406.93 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.281370E+10 | 2406.93 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.287339E+10 | 2406.93 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.277855E+10 | 2406.93 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.286376E+10 | 2406.93 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.342645E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.261440E+10 | 2406.93 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.298218E+10 | 2406.93 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.174840E+09 | 146.46 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.159081E+09 | 146.46 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.181459E+09 | 146.46 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.171207E+09 | 146.46 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.178149E+09 | 146.46 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.175103E+09 | 146.46 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.174254E+09 | 146.46 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.181459E+09 | 146.46 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.171207E+09 | 146.46 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.174840E+09 | 146.46 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.169069E+09 | 146.46 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.174254E+09 | 146.46 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208492E+10 | ||||
Minimum of Months | 0.159081E+09 | 146.46 | 0.00 | 0.00 | |
Maximum of Months | 0.181459E+09 | 146.46 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.343688E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718628E+10 |
February | 0.479114E+10 | 0.312713E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619190E+10 |
March | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435525E+10 |
April | 0.518069E+10 | 0.336554E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4934893.30 | 0.346524E+10 |
May | 0.536353E+10 | 0.350199E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14965957.63 | 0.168675E+10 |
June | 0.528933E+10 | 0.344215E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61553271.58 | 0.960435E+09 |
July | 0.525489E+10 | 0.342538E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61997062.11 | 0.675069E+09 |
August | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23946077.26 | 0.105414E+10 |
September | 0.518069E+10 | 0.336554E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 780129.38 | 0.181388E+10 |
October | 0.524694E+10 | 0.343688E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260992E+10 |
November | 0.504819E+10 | 0.332343E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483519E+10 |
December | 0.525489E+10 | 0.342538E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742274E+10 |
Annual Sum or Average | 0.628175E+11 | 0.409845E+11 | 0.499918E+11 | 0.168177E+09 | 0.422568E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.312713E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675069E+09 |
Maximum of Months | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61997062.11 | 0.742274E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.304941E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614278E+10 |
February | 0.201852E+11 | 0.277456E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535607E+10 |
March | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383137E+10 |
April | 0.218263E+11 | 0.298606E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2486142.68 | 0.318080E+10 |
May | 0.225967E+11 | 0.310713E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12240350.95 | 0.160681E+10 |
June | 0.222841E+11 | 0.305400E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48229835.40 | 0.929134E+09 |
July | 0.221389E+11 | 0.303919E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50587153.70 | 0.621232E+09 |
August | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19591515.46 | 0.962564E+09 |
September | 0.218263E+11 | 0.298606E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 638624.34 | 0.164082E+10 |
October | 0.221054E+11 | 0.304941E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232033E+10 |
November | 0.212681E+11 | 0.294876E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429785E+10 |
December | 0.221389E+11 | 0.303919E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638711E+10 |
Annual Sum or Average | 0.264651E+12 | 0.363635E+12 | 0.842987E+11 | 0.133774E+09 | 0.372769E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.277456E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621232E+09 |
Maximum of Months | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50587153.70 | 0.638711E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.287339E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312326E+10 |
February | 0.190200E+10 | 0.261440E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271465E+10 |
March | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193694E+10 |
April | 0.205665E+10 | 0.281370E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1185817.67 | 0.159078E+10 |
May | 0.212923E+10 | 0.292778E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6475428.86 | 0.795010E+09 |
June | 0.209978E+10 | 0.287772E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24512194.39 | 0.456995E+09 |
July | 0.208610E+10 | 0.286376E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26527402.57 | 0.321603E+09 |
August | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10365545.53 | 0.503232E+09 |
September | 0.205665E+10 | 0.281370E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337804.81 | 0.849307E+09 |
October | 0.208295E+10 | 0.287339E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120605E+10 |
November | 0.200405E+10 | 0.277855E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214703E+10 |
December | 0.208610E+10 | 0.286376E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322418E+10 |
Annual Sum or Average | 0.249375E+11 | 0.342645E+11 | 0.529224E+11 | 69404193.83 | 0.188690E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.261440E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321603E+09 |
Maximum of Months | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26527402.57 | 0.322418E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.287339E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311453E+10 |
February | 0.190200E+10 | 0.261440E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269781E+10 |
March | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190957E+10 |
April | 0.205665E+10 | 0.281370E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1249426.77 | 0.154166E+10 |
May | 0.212923E+10 | 0.292778E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6479307.87 | 0.742700E+09 |
June | 0.209978E+10 | 0.287772E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25489698.94 | 0.418441E+09 |
July | 0.208610E+10 | 0.286376E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26645728.96 | 0.298433E+09 |
August | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10368003.37 | 0.470844E+09 |
September | 0.205665E+10 | 0.281370E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 338074.03 | 0.800161E+09 |
October | 0.208295E+10 | 0.287339E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115767E+10 |
November | 0.200405E+10 | 0.277855E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210609E+10 |
December | 0.208610E+10 | 0.286376E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321196E+10 |
Annual Sum or Average | 0.249375E+11 | 0.342645E+11 | 0.794328E+10 | 70570239.95 | 0.184699E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.261440E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298433E+09 |
Maximum of Months | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26645728.96 | 0.321196E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.174840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520501E+11 |
February | 0.00 | 0.159081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369362E+11 |
March | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337181E+11 |
April | 0.00 | 0.171207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26391.63 | 0.182733E+11 |
May | 0.00 | 0.178149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2057754.39 | 0.686621E+10 |
June | 0.00 | 0.175103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29052602.70 | 0.284657E+10 |
July | 0.00 | 0.174254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10274376.98 | 0.168835E+10 |
August | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618314.79 | 0.270377E+10 |
September | 0.00 | 0.171207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852910E+10 |
October | 0.00 | 0.174840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179206E+11 |
November | 0.00 | 0.169069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283611E+11 |
December | 0.00 | 0.174254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498804E+11 |
Annual Sum or Average | 0.00 | 0.208492E+10 | 42029440.48 | 0.259774E+12 | |||||
Minimum of Months | 0.00 | 0.159081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168835E+10 |
Maximum of Months | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29052602.70 | 0.520501E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2880.76 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 15209.92 | 04-JAN-05:53 |
February | 5888.82 | 01-FEB-15:09 | 2880.76 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 17001.17 | 12-FEB-22:59 |
March | 5888.82 | 01-MAR-15:09 | 2880.76 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9263.51 | 15-MAR-04:51 |
April | 5888.82 | 01-APR-10:09 | 2880.76 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 694.46 | 23-APR-18:10 | 7165.01 | 01-APR-21:01 |
May | 5888.82 | 01-MAY-14:09 | 2880.76 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.09 | 24-MAY-15:00 | 3481.31 | 09-MAY-04:43 |
June | 5888.82 | 01-JUN-14:09 | 2880.76 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 761.02 | 29-JUN-20:03 | 2351.68 | 09-JUN-20:10 |
July | 5888.82 | 01-JUL-10:09 | 2880.76 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 820.58 | 23-JUL-18:03 | 2120.47 | 06-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 2880.76 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.83 | 08-AUG-16:00 | 3061.33 | 27-AUG-06:00 |
September | 5888.82 | 01-SEP-14:09 | 2880.76 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 01-SEP-15:00 | 4143.26 | 20-SEP-01:00 |
October | 5888.82 | 02-OCT-14:09 | 2880.76 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5887.74 | 31-OCT-20:01 |
November | 5888.82 | 01-NOV-14:09 | 2880.76 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 9287.99 | 23-NOV-08:00 |
December | 5888.82 | 01-DEC-15:09 | 2880.76 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 15013.30 | 16-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2120.47 | |||||
Maximum of Months | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 820.58 | 17001.17 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 25543.68 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 12538.17 | 04-JAN-06:00 |
February | 24809.68 | 01-FEB-15:09 | 25543.68 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14623.23 | 12-FEB-22:51 |
March | 24809.68 | 01-MAR-15:09 | 25543.68 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7664.76 | 15-MAR-05:00 |
April | 24809.68 | 01-APR-10:09 | 25543.68 | 01-APR-09:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 372.87 | 23-APR-18:05 | 5917.37 | 02-APR-00:55 |
May | 24809.68 | 01-MAY-14:09 | 25543.68 | 01-MAY-08:09 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.42 | 24-MAY-15:00 | 3199.87 | 20-MAY-04:53 |
June | 24809.68 | 01-JUN-14:09 | 25543.68 | 01-JUN-08:09 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 618.85 | 29-JUN-20:03 | 2194.97 | 10-JUN-22:00 |
July | 24809.68 | 01-JUL-10:09 | 25543.68 | 01-JUL-09:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.65 | 23-JUL-18:03 | 2142.08 | 06-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 25543.68 | 01-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.54 | 08-AUG-16:00 | 2941.18 | 27-AUG-06:00 |
September | 24809.68 | 01-SEP-14:09 | 25543.68 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.07 | 01-SEP-15:00 | 3941.14 | 20-SEP-01:00 |
October | 24809.68 | 02-OCT-14:09 | 25543.68 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4872.92 | 31-OCT-20:55 |
November | 24809.68 | 01-NOV-14:09 | 25543.68 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8506.58 | 22-NOV-01:53 |
December | 24809.68 | 01-DEC-15:09 | 25543.68 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 12489.31 | 16-DEC-05:57 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2142.08 | |||||
Maximum of Months | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 670.65 | 14623.23 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2406.93 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6637.70 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2406.93 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 7367.11 | 12-FEB-22:59 |
March | 2337.76 | 01-MAR-15:09 | 2406.93 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4057.72 | 15-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 2406.93 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.48 | 23-APR-18:05 | 3109.98 | 01-APR-21:01 |
May | 2337.76 | 01-MAY-14:09 | 2406.93 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 | 24-MAY-15:00 | 1532.17 | 09-MAY-04:03 |
June | 2337.76 | 01-JUN-14:09 | 2406.93 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.55 | 29-JUN-20:03 | 1080.58 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2406.93 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.58 | 23-JUL-18:03 | 1073.09 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2406.93 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.76 | 08-AUG-16:00 | 1444.86 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2406.93 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 01-SEP-15:00 | 1853.68 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2406.93 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2553.14 | 31-OCT-20:01 |
November | 2337.76 | 01-NOV-14:09 | 2406.93 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4024.76 | 23-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 2406.93 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6611.84 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1073.09 | |||||
Maximum of Months | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 339.58 | 7367.11 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2406.93 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6637.70 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2406.93 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 7367.11 | 12-FEB-22:57 |
March | 2337.76 | 01-MAR-15:09 | 2406.93 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4057.72 | 15-MAR-05:00 |
April | 2337.76 | 01-APR-10:09 | 2406.93 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 186.49 | 23-APR-18:05 | 3105.05 | 01-APR-21:01 |
May | 2337.76 | 01-MAY-14:09 | 2406.93 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.81 | 24-MAY-15:00 | 1512.69 | 09-MAY-04:43 |
June | 2337.76 | 01-JUN-14:09 | 2406.93 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.75 | 29-JUN-20:03 | 938.94 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2406.93 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 344.28 | 23-JUL-18:03 | 974.56 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2406.93 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.76 | 08-AUG-16:00 | 1378.24 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2406.93 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.69 | 01-SEP-15:00 | 1793.87 | 20-SEP-04:04 |
October | 2337.76 | 02-OCT-14:09 | 2406.93 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2549.13 | 31-OCT-20:01 |
November | 2337.76 | 01-NOV-14:09 | 2406.93 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4024.76 | 23-NOV-08:00 |
December | 2337.76 | 01-DEC-15:09 | 2406.93 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6611.84 | 16-DEC-05:59 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.94 | |||||
Maximum of Months | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 344.28 | 7367.11 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 146.46 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 99266.29 | 05-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 146.46 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 86726.83 | 01-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 146.46 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 70016.50 | 15-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 146.46 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.61 | 23-APR-16:00 | 54638.24 | 04-APR-11:02 |
May | 0.00 | 01-MAY-00:10 | 146.46 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.35 | 25-MAY-17:00 | 27043.15 | 01-MAY-11:02 |
June | 0.00 | 01-JUN-00:10 | 146.46 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.42 | 29-JUN-16:00 | 17128.53 | 09-JUN-11:05 |
July | 0.00 | 01-JUL-00:10 | 146.46 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.16 | 15-JUL-13:55 | 15480.42 | 08-JUL-11:05 |
August | 0.00 | 01-AUG-00:10 | 146.46 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.33 | 08-AUG-16:00 | 17922.64 | 17-AUG-12:00 |
September | 0.00 | 01-SEP-00:10 | 146.46 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 27867.80 | 27-SEP-11:10 |
October | 0.00 | 01-OCT-00:10 | 146.46 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 47613.13 | 29-OCT-11:01 |
November | 0.00 | 01-NOV-00:10 | 146.46 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 68963.83 | 25-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 146.46 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 96618.13 | 24-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15480.42 | ||||
Maximum of Months | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.42 | 99266.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8823.79 | 12-JAN-06:06 | 0.00 | 1109.58 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2662.78 |
February | 224.03 | 11-FEB-06:07 | 0.00 | 951.06 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1412.63 | 31-MAR-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.36 |
April | 3121.28 | 24-APR-12:20 | 5152.71 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.30 |
May | 7749.58 | 25-MAY-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 132.82 | 0.00 |
June | 20900.05 | 29-JUN-04:02 | 0.00 | 951.06 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.85 |
July | 22225.41 | 21-JUL-04:02 | 0.00 | 792.55 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.44 |
August | 22241.25 | 10-AUG-04:02 | 0.00 | 792.55 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.95 |
September | 9764.86 | 01-SEP-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 0.00 |
October | 4151.13 | 24-OCT-18:51 | 17666.45 | 12803.38 | 17167.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.39 |
November | 5801.23 | 04-NOV-11:03 | 47110.53 | 23046.08 | 22073.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.36 |
December | 552.51 | 16-DEC-06:07 | 0.00 | 951.06 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3632.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 224.03 | 0.00 | 792.55 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22241.25 | 47110.53 | 23046.08 | 22073.13 | 0.00 | 0.00 | 0.00 | 0.00 | 132.82 | 3632.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 86089.82 | 10-JAN-11:42 | 130250.83 | 153262.11 | 27915.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.20 |
February | 93033.46 | 10-FEB-20:01 | 65125.41 | 99336.55 | 25330.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.62 |
March | 26891.35 | 29-MAR-15:00 | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.87 |
April | 55214.04 | 13-APR-05:03 | 0.00 | 5676.37 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.11 |
May | 129884.30 | 27-MAY-04:03 | 0.00 | 5676.37 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.06 |
June | 125184.60 | 27-JUN-04:03 | 0.00 | 5676.37 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.77 |
July | 146904.05 | 01-JUL-04:02 | 0.00 | 7095.47 | 3877.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.75 |
August | 146006.73 | 25-AUG-04:03 | 0.00 | 5676.37 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 136215.45 | 02-SEP-04:03 | 0.00 | 5676.37 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.02 |
October | 54245.37 | 25-OCT-05:02 | 0.00 | 8514.56 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45638.18 | 03-NOV-05:03 | 0.00 | 9933.66 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.69 |
December | 62673.28 | 27-DEC-11:02 | 108542.36 | 127718.42 | 23263.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1739.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 26891.35 | 0.00 | 5676.37 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 146904.05 | 130250.83 | 153262.11 | 27915.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1739.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8573.51 | 31-JAN-06:04 | 0.00 | 936.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 720.10 |
February | 9972.19 | 13-FEB-06:04 | 0.00 | 936.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1175.87 |
March | 6706.65 | 02-MAR-06:04 | 0.00 | 668.59 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.02 |
April | 6073.43 | 13-APR-14:10 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.42 |
May | 13624.36 | 26-MAY-04:03 | 0.00 | 534.87 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.38 |
June | 14965.32 | 28-JUN-04:03 | 0.00 | 534.87 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17281.46 | 25-JUL-04:02 | 0.00 | 668.59 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.34 |
August | 18221.81 | 26-AUG-04:02 | 0.00 | 668.59 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.77 |
September | 16073.19 | 02-SEP-04:03 | 0.00 | 534.87 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 537.65 |
October | 9429.73 | 20-OCT-14:10 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.94 |
November | 7245.77 | 25-NOV-13:52 | 11688.81 | 12034.63 | 14604.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.09 |
December | 5913.02 | 15-DEC-14:13 | 8182.17 | 9627.70 | 11683.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5913.02 | 0.00 | 534.87 | 1947.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18221.81 | 11688.81 | 12034.63 | 14604.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1175.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4104.37 | 28-JAN-06:05 | 0.00 | 802.31 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.17 |
February | 9435.28 | 14-FEB-11:51 | 14318.79 | 16848.48 | 3068.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.54 |
March | 7112.52 | 12-MAR-11:12 | 5844.40 | 8023.08 | 1948.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.99 |
April | 3873.54 | 13-APR-14:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.42 |
May | 6230.72 | 18-MAY-14:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 58.41 | 0.00 |
June | 11678.61 | 29-JUN-04:02 | 0.00 | 802.31 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.84 |
July | 12868.23 | 25-JUL-04:02 | 0.00 | 668.59 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 |
August | 14772.45 | 26-AUG-04:02 | 0.00 | 668.59 | 365.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.82 |
September | 10196.01 | 01-SEP-04:02 | 0.00 | 668.59 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.76 |
October | 7076.59 | 20-OCT-14:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.94 |
November | 4571.38 | 10-NOV-14:00 | 2045.54 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.64 |
December | 9206.53 | 01-DEC-11:22 | 12273.25 | 14441.55 | 2630.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 838.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3873.54 | 0.00 | 668.59 | 365.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14772.45 | 14318.79 | 16848.48 | 3068.83 | 0.00 | 0.00 | 0.00 | 0.00 | 58.41 | 838.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.10 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.13 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.08 |
April | 0.00 | 01-APR-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.47 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.91 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.77 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.09 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | |
Maximum of Months | 0.00 | 0.00 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.13 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.118917E+12 | 81584.30 | 02-JAN-16:30 | 0.378633E+12 | 462991.21 | 06-JAN-05:10 |
February | 0.105908E+12 | 81584.30 | 01-FEB-17:10 | 0.262631E+12 | 426761.30 | 14-FEB-05:10 |
March | 0.116577E+12 | 81584.30 | 01-MAR-17:00 | 0.216755E+12 | 346585.17 | 07-MAR-05:10 |
April | 0.108270E+12 | 84777.76 | 13-APR-14:39 | 0.858697E+11 | 234398.11 | 04-APR-04:10 |
May | 0.115761E+12 | 103874.57 | 25-MAY-14:00 | 0.171586E+11 | 148395.01 | 01-MAY-04:10 |
June | 0.123477E+12 | 124349.17 | 29-JUN-15:00 | 0.845553E+10 | 13554.42 | 01-JUN-04:10 |
July | 0.133989E+12 | 120352.16 | 15-JUL-14:09 | 0.824571E+10 | 7030.56 | 08-JUL-11:00 |
August | 0.131446E+12 | 115815.80 | 08-AUG-14:00 | 0.840380E+10 | 19874.23 | 19-AUG-05:00 |
September | 0.113269E+12 | 101311.87 | 01-SEP-14:20 | 0.110805E+11 | 40837.78 | 23-SEP-06:40 |
October | 0.112571E+12 | 87915.34 | 21-OCT-12:00 | 0.583334E+11 | 173274.59 | 30-OCT-04:10 |
November | 0.111493E+12 | 82927.76 | 01-NOV-16:00 | 0.156597E+12 | 312365.32 | 25-NOV-05:10 |
December | 0.118835E+12 | 81584.30 | 01-DEC-16:19 | 0.347150E+12 | 446186.30 | 24-DEC-07:10 |
Annual Sum or Average | 0.141051E+13 | 0.155931E+13 | ||||
Minimum of Months | 0.105908E+12 | 81584.30 | 0.824571E+10 | 7030.56 | ||
Maximum of Months | 0.133989E+12 | 124349.17 | 0.378633E+12 | 462991.21 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.398525E+11 | 0.125953E+11 | 0.164409E+11 | 0.00 | 0.500280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362606E+11 | 0.103460E+11 | 0.149157E+11 | 0.00 | 0.443853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413616E+11 | 0.100560E+11 | 0.168545E+11 | 0.00 | 0.483036E+11 | 0.00 | 0.00 | 914723.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390247E+11 | 0.832511E+10 | 0.160165E+11 | 0.00 | 0.437899E+11 | 0.00 | 0.00 | 0.111326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406071E+11 | 0.733664E+10 | 0.166477E+11 | 0.00 | 0.387397E+11 | 0.00 | 0.00 | 0.124301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399127E+11 | 0.641407E+10 | 0.162772E+11 | 0.00 | 0.336119E+11 | 0.00 | 0.00 | 0.272610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.397190E+11 | 0.695004E+10 | 0.163871E+11 | 0.00 | 0.325949E+11 | 0.00 | 0.00 | 0.383381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413616E+11 | 0.803516E+10 | 0.168545E+11 | 0.00 | 0.342274E+11 | 0.00 | 0.00 | 0.309677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.390247E+11 | 0.911589E+10 | 0.160165E+11 | 0.00 | 0.391257E+11 | 0.00 | 0.00 | 0.998615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398525E+11 | 0.108776E+11 | 0.164409E+11 | 0.00 | 0.440772E+11 | 0.00 | 0.00 | 0.132318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385372E+11 | 0.118045E+11 | 0.159174E+11 | 0.00 | 0.451746E+11 | 0.00 | 0.00 | 59388827.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397190E+11 | 0.129336E+11 | 0.163871E+11 | 0.00 | 0.497953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475233E+12 | 0.114790E+12 | 0.195156E+12 | 0.503854E+12 | 0.00 | 0.121480E+12 | |||||||
Minimum of Months | 0.362606E+11 | 0.641407E+10 | 0.149157E+11 | 0.00 | 0.325949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413616E+11 | 0.129336E+11 | 0.168545E+11 | 0.00 | 0.500280E+11 | 0.00 | 0.00 | 0.383381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.369812E+12 | 0.00 | 0.882137E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.254571E+12 | 0.00 | 0.806052E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.207763E+12 | 0.00 | 0.899157E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.773353E+11 | 0.00 | 0.853446E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.852937E+10 | 0.00 | 0.862927E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.261058E+09 | 0.00 | 0.819447E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 26189826.01 | 0.00 | 0.821952E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.176550E+09 | 0.00 | 0.822725E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.313842E+10 | 0.00 | 0.794203E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.500382E+11 | 0.00 | 0.829521E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.148405E+12 | 0.00 | 0.819221E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.338481E+12 | 0.00 | 0.866950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.145854E+13 | 0.100777E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 26189826.01 | 0.00 | 0.794203E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.369812E+12 | 0.00 | 0.899157E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33384.75 | 02-JAN-09:09 | 7322.00 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 30106.51 | 04-JAN-09:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33384.75 | 01-FEB-09:09 | 7322.00 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 30106.51 | 07-FEB-17:19 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33384.75 | 01-MAR-09:09 | 7322.00 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 30106.51 | 09-MAR-13:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33384.75 | 01-APR-09:09 | 7322.00 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 30106.51 | 13-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33384.75 | 01-MAY-08:09 | 7322.00 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 30106.51 | 20-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33384.75 | 01-JUN-08:09 | 7322.00 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 30106.51 | 02-JUN-07:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33384.75 | 01-JUL-09:09 | 7322.00 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 30106.51 | 01-JUL-07:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33384.75 | 01-AUG-08:09 | 7322.00 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 30106.51 | 01-AUG-11:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33384.75 | 01-SEP-08:09 | 7322.00 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 30106.51 | 10-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33384.75 | 02-OCT-08:09 | 7322.00 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 30106.51 | 05-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33384.75 | 01-NOV-08:09 | 7322.00 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 30106.51 | 01-NOV-07:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33384.75 | 01-DEC-09:09 | 7322.00 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 30106.51 | 25-DEC-12:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 33384.75 | 7322.00 | 10771.04 | 0.00 | 30106.51 | 0.00 | 0.00 | |||||
Maximum of Months | 33384.75 | 7322.00 | 10771.04 | 0.00 | 30106.51 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 198.23 | 31-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18608.91 | 23-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40648.84 | 25-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 61123.44 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57126.43 | 15-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 52590.07 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38086.14 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17142.47 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4790.86 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61123.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 81584.30 | 02-JAN-16:30 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81584.30 | 01-FEB-17:10 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81584.30 | 01-MAR-17:00 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84777.76 | 13-APR-14:39 | 33384.75 | 10771.04 | 0.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 10515.46 | 0.00 |
May | 103874.57 | 25-MAY-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 19069.94 | 0.00 | 0.00 | 40648.84 | 0.00 |
June | 124349.17 | 29-JUN-15:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 19069.94 | 0.00 | 0.00 | 61123.44 | 0.00 |
July | 120352.16 | 15-JUL-14:09 | 33384.75 | 10771.04 | 0.00 | 0.00 | 19069.94 | 0.00 | 0.00 | 57126.43 | 0.00 |
August | 115815.80 | 08-AUG-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 19069.94 | 0.00 | 0.00 | 52590.07 | 0.00 |
September | 101311.87 | 01-SEP-14:20 | 33384.75 | 10771.04 | 0.00 | 0.00 | 19069.94 | 0.00 | 0.00 | 38086.14 | 0.00 |
October | 87915.34 | 21-OCT-12:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 13653.04 | 0.00 |
November | 82927.76 | 01-NOV-16:00 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 1343.46 | 0.00 |
December | 81584.30 | 01-DEC-16:19 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 81584.30 | 33384.75 | 10771.04 | 0.00 | 0.00 | 19069.94 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 124349.17 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 30106.51 | 0.00 | 0.00 | 61123.44 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 461129.21 | 06-JAN-05:10 | 0.00 | 6246.07 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 424899.30 | 14-FEB-05:10 | 0.00 | 6347.25 | 27-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 344723.17 | 07-MAR-05:10 | 0.00 | 6345.16 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 232536.11 | 04-APR-04:10 | 0.00 | 6149.40 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 146533.01 | 01-MAY-04:10 | 0.00 | 5678.13 | 04-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 11692.42 | 01-JUN-04:10 | 0.00 | 5150.76 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 1982.71 | 08-JUL-11:00 | 0.00 | 5095.24 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 18012.23 | 19-AUG-05:00 | 0.00 | 5061.70 | 01-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 37503.50 | 23-SEP-06:00 | 0.00 | 5069.99 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 171412.59 | 30-OCT-04:10 | 0.00 | 5116.16 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 310503.32 | 25-NOV-05:10 | 0.00 | 5317.07 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 444324.30 | 24-DEC-07:10 | 0.00 | 5836.87 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 1982.71 | 0.00 | 5061.70 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 461129.21 | 0.00 | 6347.25 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 16.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33.33 | 16.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17.33 | 18.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8.67 | 19.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.00 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.17 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38.83 | 16.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 154.83 | 17.14 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.17 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.83 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.17 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.60 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.55 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.50 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.17 | 20.21 | 0.00 | 2.33 | 24.50 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 20.55 | 0.00 | 0.00 | 1.50 | 24.60 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.00 | 16.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24.67 | 16.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13.17 | 18.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4.83 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.29 | 0.00 | 0.00 | 0.17 | 24.55 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.50 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33.17 | 16.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.67 | 17.05 | 0.00 | 0.83 | 24.54 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.00 | 20.31 | 0.00 | 0.00 | 0.50 | 24.55 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 41.33 | 16.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30.50 | 16.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16.67 | 17.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6.67 | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1.17 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.83 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.83 | 19.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39.33 | 16.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.33 | 16.84 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 41.33 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.11 | 422.00 | 21.11 | 422.00 | 21.11 |
April | 405.00 | 21.39 | 310.00 | 21.12 | 310.00 | 21.12 |
May | 348.67 | 22.75 | 57.33 | 21.74 | 44.83 | 21.14 |
June | 233.00 | 23.45 | 133.67 | 23.87 | 46.33 | 23.82 |
July | 74.33 | 23.62 | 240.50 | 23.89 | 35.00 | 23.89 |
August | 67.17 | 23.41 | 200.50 | 23.89 | 3.00 | 23.89 |
September | 318.17 | 23.04 | 29.67 | 23.89 | 2.50 | 23.89 |
October | 414.00 | 21.66 | 154.00 | 21.11 | 154.00 | 21.11 |
November | 399.00 | 21.15 | 356.00 | 21.11 | 356.00 | 21.11 |
December | 415.00 | 21.11 | 415.00 | 21.11 | 415.00 | 21.11 |
Annual Sum or Average | 3886.33 | 21.74 | 3108.67 | 21.66 | 2578.67 | 21.20 |
Minimum of Months | 67.17 | 21.11 | 29.67 | 21.11 | 2.50 | 21.11 |
Maximum of Months | 422.00 | 23.62 | 422.00 | 23.89 | 422.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 411.33 | 21.11 | 411.33 | 21.11 |
February | 376.00 | 21.11 | 347.17 | 21.11 | 347.17 | 21.11 |
March | 422.00 | 21.11 | 290.50 | 21.11 | 290.50 | 21.11 |
April | 401.50 | 21.71 | 85.00 | 21.11 | 85.00 | 21.11 |
May | 234.17 | 22.77 | 86.83 | 23.73 | 4.83 | 21.11 |
June | 63.67 | 23.20 | 252.00 | 23.89 | 8.83 | 23.89 |
July | 43.67 | 23.67 | 378.83 | 23.89 | 30.83 | 23.89 |
August | 19.33 | 22.95 | 352.17 | 23.89 | 0.50 | 23.89 |
September | 172.17 | 22.51 | 82.17 | 23.89 | 0.00 | 0.00 |
October | 396.50 | 21.65 | 24.17 | 21.11 | 24.17 | 21.11 |
November | 399.00 | 21.20 | 223.33 | 21.11 | 223.33 | 21.11 |
December | 415.00 | 21.11 | 408.50 | 21.11 | 408.50 | 21.11 |
Annual Sum or Average | 3357.00 | 21.53 | 2942.00 | 22.19 | 1835.00 | 21.17 |
Minimum of Months | 19.33 | 21.11 | 24.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.67 | 411.33 | 23.89 | 411.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 401.33 | 21.11 | 401.33 | 21.11 |
February | 376.00 | 21.20 | 302.17 | 21.11 | 302.17 | 21.11 |
March | 422.00 | 21.26 | 311.17 | 21.11 | 311.17 | 21.11 |
April | 376.00 | 21.87 | 158.33 | 21.17 | 154.83 | 21.11 |
May | 224.67 | 22.89 | 100.17 | 23.53 | 12.83 | 21.11 |
June | 88.00 | 23.21 | 226.33 | 23.89 | 8.67 | 23.88 |
July | 26.83 | 23.46 | 363.17 | 23.89 | 10.67 | 23.89 |
August | 19.83 | 23.05 | 350.83 | 23.89 | 0.00 | 0.00 |
September | 126.33 | 22.68 | 167.67 | 23.89 | 0.00 | 0.00 |
October | 328.50 | 21.82 | 94.00 | 22.17 | 58.00 | 21.11 |
November | 397.83 | 21.38 | 221.67 | 21.11 | 221.67 | 21.11 |
December | 415.00 | 21.11 | 406.50 | 21.11 | 406.50 | 21.11 |
Annual Sum or Average | 3215.00 | 21.61 | 3103.33 | 22.22 | 1887.83 | 21.14 |
Minimum of Months | 19.83 | 21.11 | 94.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.46 | 406.50 | 23.89 | 406.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 406.83 | 21.11 | 406.83 | 21.11 |
February | 376.00 | 21.12 | 327.67 | 21.11 | 327.67 | 21.11 |
March | 422.00 | 21.13 | 340.50 | 21.11 | 340.50 | 21.11 |
April | 391.50 | 21.60 | 203.33 | 21.11 | 203.33 | 21.11 |
May | 290.50 | 22.44 | 88.00 | 23.06 | 26.33 | 21.11 |
June | 176.33 | 23.03 | 184.00 | 23.86 | 49.83 | 23.79 |
July | 78.67 | 23.35 | 335.00 | 23.89 | 39.67 | 23.89 |
August | 67.67 | 22.92 | 318.33 | 23.89 | 5.50 | 23.89 |
September | 191.83 | 22.10 | 121.00 | 23.89 | 4.83 | 23.84 |
October | 357.83 | 21.40 | 123.00 | 21.66 | 98.50 | 21.11 |
November | 399.00 | 21.19 | 276.17 | 21.11 | 276.17 | 21.11 |
December | 415.00 | 21.11 | 409.33 | 21.11 | 409.33 | 21.11 |
Annual Sum or Average | 3580.33 | 21.54 | 3133.17 | 22.03 | 2188.50 | 21.23 |
Minimum of Months | 67.67 | 21.11 | 88.00 | 21.11 | 4.83 | 21.11 |
Maximum of Months | 422.00 | 23.35 | 409.33 | 23.89 | 409.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10985 | 12.25993 | -0.8713 | 21.17295 |
February | 376.00000 | 21.10988 | 14.17440 | -0.8282 | 19.62623 |
March | 422.00000 | 21.10992 | 18.29865 | -0.7735 | 17.80202 |
April | 405.00000 | 21.38777 | 23.26880 | -0.5940 | 13.21090 |
May | 418.00000 | 22.91858 | 35.77784 | -1.0991 | 33.09430 |
June | 408.00000 | 23.62149 | 48.85865 | -0.6912 | 16.52379 |
July | 415.00000 | 23.83422 | 52.60099 | -0.5065 | 10.74182 |
August | 422.00000 | 23.80405 | 51.41979 | -0.5454 | 11.69190 |
September | 405.00000 | 23.20479 | 42.95953 | -0.8954 | 23.96710 |
October | 414.00000 | 21.66143 | 33.53806 | -0.3905 | 9.48421 |
November | 399.00000 | 21.15271 | 22.42649 | -0.6723 | 14.94063 |
December | 415.00000 | 21.10986 | 13.81837 | -0.8377 | 19.97567 |
Annual Sum or Average | 4913.00000 | 22.17943 | 30.92515 | -0.7248 | 17.67947 |
Minimum of Months | 376.00000 | 21.10985 | 12.25993 | -1.0991 | 9.48421 |
Maximum of Months | 422.00000 | 23.83422 | 52.60099 | -0.3905 | 33.09430 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10991 | 9.74887 | -0.7278 | 16.29099 |
February | 376.00000 | 21.10986 | 11.89563 | -0.6716 | 14.63859 |
March | 422.00000 | 21.11336 | 15.83343 | -0.5999 | 12.76523 |
April | 405.00000 | 21.72537 | 20.74326 | -0.3513 | 8.96404 |
May | 418.00000 | 23.24180 | 33.12150 | -0.8012 | 21.26192 |
June | 408.00000 | 23.76720 | 46.28720 | -0.4781 | 10.60072 |
July | 415.00000 | 23.85916 | 51.46932 | -0.3686 | 8.09578 |
August | 422.00000 | 23.83274 | 50.11042 | -0.4082 | 8.83161 |
September | 405.00000 | 23.27849 | 40.52108 | -0.7224 | 17.95316 |
October | 414.00000 | 21.73617 | 30.97537 | -0.2571 | 7.78621 |
November | 399.00000 | 21.19655 | 20.04395 | -0.5348 | 11.53436 |
December | 415.00000 | 21.10979 | 11.33493 | -0.7004 | 15.47487 |
Annual Sum or Average | 4913.00000 | 22.26766 | 28.65138 | -0.5511 | 12.84022 |
Minimum of Months | 376.00000 | 21.10979 | 9.74887 | -0.8012 | 7.78621 |
Maximum of Months | 422.00000 | 23.85916 | 51.46932 | -0.2571 | 21.26192 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10970 | 9.47483 | -0.7732 | 17.91636 |
February | 376.00000 | 21.20066 | 11.48799 | -0.6657 | 15.10803 |
March | 422.00000 | 21.25714 | 15.38273 | -0.6089 | 13.72715 |
April | 405.00000 | 22.00564 | 20.18555 | -0.3284 | 9.89682 |
May | 418.00000 | 23.33107 | 32.44132 | -0.8022 | 21.80241 |
June | 408.00000 | 23.72533 | 45.39608 | -0.5111 | 11.93771 |
July | 415.00000 | 23.85525 | 49.57529 | -0.3510 | 8.04873 |
August | 422.00000 | 23.84230 | 47.70857 | -0.3667 | 8.44817 |
September | 405.00000 | 23.49147 | 38.94610 | -0.6170 | 15.49338 |
October | 414.00000 | 22.24107 | 29.67430 | -0.1465 | 8.35801 |
November | 399.00000 | 21.38611 | 19.60621 | -0.5197 | 11.97105 |
December | 415.00000 | 21.10976 | 11.06230 | -0.7628 | 17.52803 |
Annual Sum or Average | 4913.00000 | 22.39015 | 27.71619 | -0.5372 | 13.34704 |
Minimum of Months | 376.00000 | 21.10970 | 9.47483 | -0.8022 | 8.04873 |
Maximum of Months | 422.00000 | 23.85525 | 49.57529 | -0.1465 | 21.80241 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10983 | 9.50962 | -0.8058 | 18.97921 |
February | 376.00000 | 21.11948 | 11.57343 | -0.7175 | 16.34391 |
March | 422.00000 | 21.12599 | 15.53282 | -0.6732 | 15.06062 |
April | 405.00000 | 21.66852 | 20.47561 | -0.4345 | 11.07903 |
May | 418.00000 | 22.86440 | 33.60412 | -0.9868 | 29.28697 |
June | 408.00000 | 23.49642 | 47.76523 | -0.6229 | 15.50825 |
July | 415.00000 | 23.77380 | 52.03982 | -0.4134 | 9.42031 |
August | 422.00000 | 23.71660 | 50.27228 | -0.4431 | 10.23130 |
September | 405.00000 | 23.02046 | 40.86685 | -0.7963 | 22.06284 |
October | 414.00000 | 21.73180 | 30.56333 | -0.2875 | 9.24346 |
November | 399.00000 | 21.19104 | 19.90647 | -0.5985 | 13.26174 |
December | 415.00000 | 21.10966 | 11.09803 | -0.7958 | 18.59295 |
Annual Sum or Average | 4913.00000 | 22.17091 | 28.74718 | -0.6308 | 15.75644 |
Minimum of Months | 376.00000 | 21.10966 | 9.50962 | -0.9868 | 9.24346 |
Maximum of Months | 422.00000 | 23.77380 | 52.03982 | -0.2875 | 29.28697 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 6350064.81 | 2093415.61 | 2.17 | 5356423.28 | 993641.53 | 0.00 | 0.07 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 1885.67 | 23-APR-16:00 | 1587.57 | 23-APR-16:00 | 298.10 | 23-APR-16:00 | 621.15 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.341873E+10 | 0.102453E+10 | 168.97 | 0.284718E+10 | 0.571557E+09 | 0.00 | 0.50 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 | 14872.47 | 25-MAY-15:00 | 11472.74 | 25-MAY-15:00 | 3827.97 | 26-MAY-12:00 | 4479.21 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.946122E+10 | 0.276529E+10 | 318.68 | 0.703353E+10 | 0.242769E+10 | 0.00 | 1.00 | 29-JUN-04:02 | 0.00 | 01-JUN-00:10 | 38498.76 | 30-JUN-04:01 | 22732.99 | 29-JUN-04:02 | 20728.28 | 30-JUN-04:04 | 8807.47 | 30-JUN-04:13 | 0.00 | 01-JUN-00:10 |
July | 0.149444E+11 | 0.429296E+10 | 395.00 | 0.107893E+11 | 0.415506E+10 | 0.00 | 1.00 | 04-JUL-06:02 | 0.00 | 01-JUL-00:10 | 37594.94 | 04-JUL-06:02 | 22919.23 | 21-JUL-04:02 | 19199.48 | 04-JUL-06:02 | 8452.36 | 04-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.120555E+11 | 0.344097E+10 | 378.95 | 0.880721E+10 | 0.324826E+10 | 0.00 | 1.00 | 09-AUG-04:02 | 0.00 | 01-AUG-00:10 | 36257.53 | 09-AUG-04:02 | 22102.34 | 10-AUG-04:02 | 14158.74 | 09-AUG-04:02 | 8262.04 | 09-AUG-04:02 | 0.00 | 01-AUG-00:10 |
September | 0.331514E+10 | 0.966387E+09 | 203.41 | 0.269230E+10 | 0.622841E+09 | 0.00 | 0.53 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 | 15720.56 | 01-SEP-14:50 | 12513.69 | 01-SEP-15:00 | 5472.84 | 01-SEP-05:05 | 4507.85 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.173653E+09 | 52083205.39 | 19.78 | 0.159091E+09 | 14561814.40 | 0.00 | 0.16 | 21-OCT-15:58 | 0.00 | 01-OCT-00:10 | 4157.57 | 21-OCT-15:58 | 3880.35 | 21-OCT-15:58 | 524.91 | 19-OCT-15:00 | 1229.88 | 21-OCT-15:58 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.433750E+11 | 0.125443E+11 | 1486.96 | 0.323340E+11 | 0.110410E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.149444E+11 | 0.429296E+10 | 395.00 | 0.107893E+11 | 0.415506E+10 | 0.00 | 1.00 | 0.00 | 38498.76 | 22919.23 | 20728.28 | 8807.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.232047E+10 | 0.754872E+09 | 47.49 | 0.220696E+10 | 0.113516E+09 | 0.00 | 0.31 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 42670.72 | 23-APR-16:00 | 36808.61 | 23-APR-16:00 | 5862.11 | 23-APR-16:00 | 14299.17 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.293843E+11 | 0.929632E+10 | 246.71 | 0.253856E+11 | 0.399867E+10 | 0.00 | 1.00 | 26-MAY-04:03 | 0.00 | 01-MAY-00:10 | 175157.20 | 26-MAY-04:03 | 132524.99 | 26-MAY-04:03 | 45780.60 | 27-MAY-04:03 | 43696.55 | 26-MAY-04:03 | 0.00 | 01-MAY-00:10 |
June | 0.659622E+11 | 0.203037E+11 | 367.69 | 0.493436E+11 | 0.166186E+11 | 0.00 | 1.00 | 25-JUN-06:03 | 0.00 | 01-JUN-00:10 | 189072.18 | 30-JUN-04:01 | 121061.09 | 29-JUN-04:02 | 81924.11 | 30-JUN-04:13 | 47849.71 | 30-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.917500E+11 | 0.278944E+11 | 417.02 | 0.650140E+11 | 0.267361E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 186609.46 | 04-JUL-06:02 | 131065.64 | 07-JUL-04:03 | 81492.55 | 04-JUL-06:02 | 45766.05 | 04-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.728581E+11 | 0.221564E+11 | 401.91 | 0.523003E+11 | 0.205578E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 181139.47 | 09-AUG-04:02 | 127490.58 | 01-AUG-04:03 | 69897.76 | 29-AUG-04:03 | 44768.97 | 09-AUG-04:02 | 0.00 | 01-AUG-00:10 |
September | 0.214737E+11 | 0.671203E+10 | 222.38 | 0.175677E+11 | 0.390604E+10 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 180486.79 | 01-SEP-04:02 | 130123.36 | 02-SEP-04:03 | 72080.33 | 01-SEP-04:02 | 44667.11 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 |
October | 0.206801E+10 | 0.661269E+09 | 38.08 | 0.190818E+10 | 0.159826E+09 | 0.00 | 0.26 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 34848.69 | 19-OCT-15:00 | 31244.61 | 19-OCT-15:00 | 3756.52 | 19-OCT-14:10 | 11055.99 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.118635E+09 | 38920418.35 | 4.50 | 92449991.29 | 26184849.44 | 0.00 | 0.09 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 12283.47 | 01-NOV-15:00 | 9564.09 | 01-NOV-15:00 | 2719.39 | 01-NOV-15:00 | 4001.11 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.285935E+12 | 0.878179E+11 | 1745.79 | 0.213819E+12 | 0.721168E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.917500E+11 | 0.278944E+11 | 417.02 | 0.650140E+11 | 0.267361E+11 | 0.00 | 1.00 | 0.00 | 189072.18 | 132524.99 | 81924.11 | 47849.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 3009268.89 | 914723.25 | 2.00 | 3009268.89 | 0.00 | 0.00 | 0.04 | 31-MAR-14:30 | 0.00 | 01-MAR-00:10 | 653.45 | 31-MAR-14:30 | 653.45 | 31-MAR-14:30 | 0.00 | 31-MAR-14:00 | 198.23 | 31-MAR-14:30 | 0.00 | 01-MAR-00:10 |
April | 0.900043E+09 | 0.262133E+09 | 83.69 | 0.886041E+09 | 14002055.04 | 0.00 | 0.40 | 23-APR-14:30 | 0.00 | 01-APR-00:10 | 7406.05 | 23-APR-14:30 | 6678.86 | 23-APR-14:30 | 727.20 | 23-APR-14:30 | 2189.60 | 23-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 0.469963E+10 | 0.136365E+10 | 278.24 | 0.426675E+10 | 0.432873E+09 | 0.00 | 0.87 | 26-MAY-04:03 | 0.00 | 01-MAY-00:10 | 18707.31 | 26-MAY-04:03 | 14688.48 | 26-MAY-04:03 | 4018.83 | 26-MAY-04:03 | 4603.79 | 26-MAY-04:03 | 0.00 | 01-MAY-00:10 |
June | 0.893198E+10 | 0.255017E+10 | 364.96 | 0.712063E+10 | 0.181134E+10 | 0.00 | 1.00 | 29-JUN-04:02 | 0.00 | 01-JUN-00:10 | 25789.13 | 30-JUN-04:01 | 16021.26 | 29-JUN-04:02 | 13210.04 | 30-JUN-04:06 | 5862.75 | 30-JUN-04:06 | 0.00 | 01-JUN-00:10 |
July | 0.127843E+11 | 0.358977E+10 | 418.21 | 0.976239E+10 | 0.302194E+10 | 0.00 | 1.00 | 04-JUL-06:02 | 0.00 | 01-JUL-00:10 | 25117.31 | 04-JUL-06:02 | 17497.30 | 25-JUL-04:02 | 12129.70 | 04-JUL-06:02 | 5631.98 | 04-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.115486E+11 | 0.319954E+10 | 414.86 | 0.904034E+10 | 0.250828E+10 | 0.00 | 1.00 | 09-AUG-04:02 | 0.00 | 01-AUG-00:10 | 24249.55 | 09-AUG-04:02 | 17614.78 | 26-AUG-04:02 | 8727.48 | 09-AUG-04:03 | 5514.52 | 09-AUG-04:02 | 0.00 | 01-AUG-00:10 |
September | 0.531429E+10 | 0.148879E+10 | 291.93 | 0.474746E+10 | 0.566832E+09 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 24150.28 | 01-SEP-04:02 | 16256.45 | 02-SEP-04:03 | 9373.22 | 01-SEP-04:02 | 5501.68 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 |
October | 0.143654E+10 | 0.403768E+09 | 94.99 | 0.138296E+10 | 53584324.53 | 0.00 | 0.54 | 19-OCT-14:20 | 0.00 | 01-OCT-00:10 | 10445.35 | 19-OCT-14:20 | 9871.28 | 19-OCT-14:20 | 827.87 | 22-OCT-12:30 | 2815.51 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 68555447.06 | 20468409.06 | 11.10 | 61940681.29 | 6614765.77 | 0.00 | 0.15 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 2663.11 | 01-NOV-15:00 | 2353.29 | 17-NOV-13:40 | 455.66 | 01-NOV-15:00 | 789.75 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.456870E+11 | 0.128792E+11 | 1959.98 | 0.372715E+11 | 0.841547E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.127843E+11 | 0.358977E+10 | 418.21 | 0.976239E+10 | 0.302194E+10 | 0.00 | 1.00 | 0.00 | 25789.13 | 17614.78 | 13210.04 | 5862.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.316908E+09 | 94163845.11 | 44.69 | 0.304842E+09 | 12065783.05 | 0.00 | 0.33 | 23-APR-14:40 | 0.00 | 01-APR-00:10 | 5040.35 | 23-APR-14:40 | 4406.76 | 23-APR-14:40 | 636.63 | 23-APR-14:30 | 1519.62 | 23-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 0.252670E+10 | 0.745646E+09 | 191.91 | 0.219658E+10 | 0.330129E+09 | 0.00 | 0.59 | 25-MAY-14:10 | 0.00 | 01-MAY-00:10 | 10022.26 | 25-MAY-14:10 | 8605.27 | 18-MAY-14:10 | 2426.12 | 26-MAY-12:00 | 2933.44 | 25-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.569696E+10 | 0.164187E+10 | 294.74 | 0.429918E+10 | 0.139778E+10 | 0.00 | 1.00 | 29-JUN-04:02 | 0.00 | 01-JUN-00:10 | 21664.51 | 30-JUN-04:01 | 12631.61 | 29-JUN-04:02 | 11555.96 | 30-JUN-04:04 | 4937.27 | 30-JUN-04:13 | 0.00 | 01-JUN-00:10 |
July | 0.904972E+10 | 0.256094E+10 | 377.65 | 0.655306E+10 | 0.249666E+10 | 0.00 | 1.00 | 04-JUL-06:02 | 0.00 | 01-JUL-00:10 | 21121.74 | 04-JUL-06:02 | 12466.26 | 25-JUL-04:02 | 10974.19 | 04-JUL-06:02 | 4741.11 | 04-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.777609E+10 | 0.217086E+10 | 350.43 | 0.579414E+10 | 0.198196E+10 | 0.00 | 1.00 | 09-AUG-04:02 | 0.00 | 01-AUG-00:10 | 20346.75 | 09-AUG-04:02 | 13536.77 | 26-AUG-04:02 | 7982.54 | 09-AUG-04:02 | 4634.36 | 09-AUG-04:02 | 0.00 | 01-AUG-00:10 |
September | 0.290454E+10 | 0.818937E+09 | 201.97 | 0.254567E+10 | 0.358871E+09 | 0.00 | 0.89 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 | 16955.35 | 01-SEP-04:02 | 10965.15 | 01-SEP-14:10 | 7248.01 | 01-SEP-04:02 | 4084.02 | 01-SEP-04:02 | 0.00 | 01-SEP-00:10 |
October | 0.730097E+09 | 0.206061E+09 | 55.66 | 0.691727E+09 | 38370523.58 | 0.00 | 0.49 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 | 7857.75 | 19-OCT-14:20 | 7264.86 | 19-OCT-14:30 | 818.61 | 22-OCT-12:50 | 2151.17 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.290010E+11 | 0.823848E+10 | 1517.04 | 0.223852E+11 | 0.661583E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.904972E+10 | 0.256094E+10 | 377.65 | 0.655306E+10 | 0.249666E+10 | 0.00 | 1.00 | 0.00 | 21664.51 | 13536.77 | 11555.96 | 4937.27 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.23 | 3.12 | 7.11 | 0.03 | 80.88 | 0.00 | 0.00 | 744.00 |
February | 18.49 | 8.03 | 10.46 | 2.44 | 63.31 | 0.00 | 0.00 | 672.00 |
March | 27.08 | 14.96 | 12.12 | 12.99 | 49.13 | 0.00 | 0.00 | 744.00 |
April | 40.81 | 25.75 | 15.06 | 32.68 | 32.02 | 0.00 | 0.00 | 720.00 |
May | 50.44 | 28.56 | 21.88 | 49.81 | 19.74 | 0.00 | 0.00 | 744.00 |
June | 53.19 | 30.86 | 22.33 | 56.58 | 14.79 | 0.00 | 0.00 | 720.00 |
July | 54.61 | 32.86 | 21.75 | 59.72 | 14.21 | 0.00 | 0.00 | 744.00 |
August | 42.82 | 24.13 | 18.70 | 44.21 | 15.45 | 0.00 | 0.00 | 744.00 |
September | 30.65 | 15.62 | 15.03 | 25.84 | 22.39 | 0.00 | 0.00 | 720.00 |
October | 17.89 | 6.82 | 11.07 | 8.33 | 32.64 | 0.00 | 0.00 | 744.00 |
November | 10.14 | 2.72 | 7.42 | 0.60 | 49.43 | 0.00 | 0.00 | 720.00 |
December | 8.06 | 1.73 | 6.33 | 0.00 | 77.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.30 | 14.12 | 24.57 | 39.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.06 | 1.73 | 6.33 | 0.00 | 14.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 54.61 | 32.86 | 22.33 | 59.72 | 80.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1542.81 | 1073.16 | 469.65 | 1113.89 | 1980.53 | 0.00 | 0.00 | 744.00 |
February | 1954.07 | 1319.82 | 634.25 | 1618.63 | 1657.77 | 0.00 | 0.00 | 672.00 |
March | 1722.64 | 1090.48 | 632.16 | 1394.74 | 1384.02 | 0.00 | 0.00 | 744.00 |
April | 1560.16 | 846.91 | 713.25 | 1295.66 | 904.91 | 0.00 | 0.00 | 720.00 |
May | 1311.30 | 448.16 | 863.13 | 1120.91 | 519.32 | 0.00 | 0.00 | 744.00 |
June | 1176.59 | 313.47 | 863.12 | 1067.11 | 368.95 | 0.00 | 0.00 | 720.00 |
July | 1286.39 | 407.38 | 879.02 | 1235.75 | 353.41 | 0.00 | 0.00 | 744.00 |
August | 1373.97 | 574.69 | 799.28 | 1351.24 | 422.29 | 0.00 | 0.00 | 744.00 |
September | 1472.28 | 784.33 | 687.95 | 1405.11 | 647.59 | 0.00 | 0.00 | 720.00 |
October | 1257.16 | 739.54 | 517.61 | 1096.38 | 922.82 | 0.00 | 0.00 | 744.00 |
November | 1119.24 | 702.32 | 416.91 | 884.96 | 1283.13 | 0.00 | 0.00 | 720.00 |
December | 1191.25 | 780.99 | 410.25 | 782.32 | 1931.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1410.45 | 753.18 | 657.26 | 1194.13 | 1028.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1119.24 | 313.47 | 410.25 | 782.32 | 353.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1954.07 | 1319.82 | 879.02 | 1618.63 | 1980.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1542.81 | 1073.16 | 469.65 | 1112.06 | 1977.48 | 0.00 | 0.00 | 744.00 |
February | 1954.07 | 1319.82 | 634.25 | 1618.90 | 1648.78 | 0.00 | 0.00 | 672.00 |
March | 1722.64 | 1090.48 | 632.16 | 1396.63 | 1370.18 | 0.00 | 0.00 | 744.00 |
April | 1560.16 | 846.91 | 713.25 | 1301.60 | 881.21 | 0.00 | 0.00 | 720.00 |
May | 1311.30 | 448.16 | 863.13 | 1131.77 | 493.22 | 0.00 | 0.00 | 744.00 |
June | 1176.59 | 313.47 | 863.12 | 1073.36 | 347.59 | 0.00 | 0.00 | 720.00 |
July | 1286.39 | 407.38 | 879.02 | 1236.35 | 337.08 | 0.00 | 0.00 | 744.00 |
August | 1373.97 | 574.69 | 799.28 | 1352.01 | 403.85 | 0.00 | 0.00 | 744.00 |
September | 1472.28 | 784.33 | 687.95 | 1413.21 | 619.50 | 0.00 | 0.00 | 720.00 |
October | 1257.16 | 739.54 | 517.61 | 1104.73 | 892.11 | 0.00 | 0.00 | 744.00 |
November | 1119.24 | 702.32 | 416.91 | 888.03 | 1265.68 | 0.00 | 0.00 | 720.00 |
December | 1191.25 | 780.99 | 410.25 | 781.04 | 1928.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1410.45 | 753.18 | 657.26 | 1197.72 | 1011.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1119.24 | 313.47 | 410.25 | 781.04 | 337.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1954.07 | 1319.82 | 879.02 | 1618.90 | 1977.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 317.46 | 220.82 | 96.64 | 220.19 | 417.51 | 0.00 | 0.00 | 744.00 |
February | 402.08 | 271.57 | 130.51 | 320.03 | 347.81 | 0.00 | 0.00 | 672.00 |
March | 354.46 | 224.38 | 130.08 | 276.68 | 293.05 | 0.00 | 0.00 | 744.00 |
April | 321.03 | 174.26 | 146.76 | 259.47 | 186.21 | 0.00 | 0.00 | 720.00 |
May | 269.82 | 92.22 | 177.60 | 228.01 | 100.25 | 0.00 | 0.00 | 744.00 |
June | 242.10 | 64.50 | 177.60 | 215.68 | 69.67 | 0.00 | 0.00 | 720.00 |
July | 264.69 | 83.82 | 180.87 | 247.64 | 69.04 | 0.00 | 0.00 | 744.00 |
August | 282.71 | 118.25 | 164.46 | 274.75 | 81.38 | 0.00 | 0.00 | 744.00 |
September | 302.94 | 161.39 | 141.56 | 287.00 | 125.11 | 0.00 | 0.00 | 720.00 |
October | 258.68 | 152.17 | 106.51 | 221.08 | 185.93 | 0.00 | 0.00 | 744.00 |
November | 230.30 | 144.51 | 85.79 | 172.85 | 269.71 | 0.00 | 0.00 | 720.00 |
December | 245.12 | 160.70 | 84.42 | 153.68 | 409.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 290.22 | 154.98 | 135.24 | 239.16 | 212.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 230.30 | 64.50 | 84.42 | 153.68 | 69.04 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 402.08 | 271.57 | 180.87 | 320.03 | 417.51 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27388968.73 | 8345530.45 | 19043438.28 | 83027.16 | 0.216618E+09 |
February | 44734636.40 | 19434402.45 | 25300233.95 | 5912818.44 | 0.153165E+09 |
March | 72541354.00 | 40070568.85 | 32470785.15 | 34799413.62 | 0.131598E+09 |
April | 0.105775E+09 | 66731534.12 | 39043224.75 | 84717002.23 | 83002027.90 |
May | 0.135100E+09 | 76499656.28 | 58599984.38 | 0.133404E+09 | 52872732.74 |
June | 0.137866E+09 | 79997476.06 | 57868532.10 | 0.146659E+09 | 38335419.42 |
July | 0.146260E+09 | 87999815.14 | 58259731.22 | 0.159966E+09 | 38051273.36 |
August | 0.114699E+09 | 64625426.36 | 50073296.68 | 0.118401E+09 | 41373839.01 |
September | 79447906.33 | 40492126.77 | 38955779.56 | 66972813.34 | 58024489.82 |
October | 47916515.53 | 18279134.41 | 29637381.12 | 22314709.22 | 87432128.01 |
November | 26270969.90 | 7049349.83 | 19221620.08 | 1553398.49 | 0.128113E+09 |
December | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 0.207867E+09 |
Annual Sum or Average | 0.959575E+09 | 0.514155E+09 | 0.445421E+09 | 0.774784E+09 | 0.123645E+10 |
Minimum of Months | 21576440.51 | 4629622.04 | 16946818.47 | 0.00 | 38051273.36 |
Maximum of Months | 0.146260E+09 | 87999815.14 | 58599984.38 | 0.159966E+09 | 0.216618E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.298344E+10 | 0.530464E+10 |
February | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.391578E+10 | 0.401049E+10 |
March | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.373568E+10 | 0.370695E+10 |
April | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.335835E+10 | 0.234553E+10 |
May | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.300224E+10 | 0.139096E+10 |
June | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.276594E+10 | 0.956321E+09 |
July | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.330982E+10 | 0.946585E+09 |
August | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.361916E+10 | 0.113106E+10 |
September | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.364204E+10 | 0.167856E+10 |
October | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.293654E+10 | 0.247169E+10 |
November | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.229383E+10 | 0.332586E+10 |
December | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.209538E+10 | 0.517320E+10 |
Annual Sum or Average | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.376582E+11 | 0.324418E+11 |
Minimum of Months | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.209538E+10 | 0.946585E+09 |
Maximum of Months | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.391578E+10 | 0.530464E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.297854E+10 | 0.529649E+10 |
February | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.391644E+10 | 0.398872E+10 |
March | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.374074E+10 | 0.366988E+10 |
April | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.337376E+10 | 0.228410E+10 |
May | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.303133E+10 | 0.132105E+10 |
June | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.278215E+10 | 0.900959E+09 |
July | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.331145E+10 | 0.902831E+09 |
August | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.362122E+10 | 0.108168E+10 |
September | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.366305E+10 | 0.160574E+10 |
October | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.295892E+10 | 0.238943E+10 |
November | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.230176E+10 | 0.328065E+10 |
December | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.209193E+10 | 0.516420E+10 |
Annual Sum or Average | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.377713E+11 | 0.318857E+11 |
Minimum of Months | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.209193E+10 | 0.900959E+09 |
Maximum of Months | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.391644E+10 | 0.529649E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.850274E+09 | 0.591437E+09 | 0.258836E+09 | 0.589761E+09 | 0.111825E+10 |
February | 0.972707E+09 | 0.656985E+09 | 0.315722E+09 | 0.774220E+09 | 0.841415E+09 |
March | 0.949382E+09 | 0.600986E+09 | 0.348396E+09 | 0.741054E+09 | 0.784905E+09 |
April | 0.832101E+09 | 0.451694E+09 | 0.380406E+09 | 0.672542E+09 | 0.482651E+09 |
May | 0.722681E+09 | 0.246992E+09 | 0.475689E+09 | 0.610691E+09 | 0.268517E+09 |
June | 0.627525E+09 | 0.167186E+09 | 0.460339E+09 | 0.559044E+09 | 0.180572E+09 |
July | 0.708958E+09 | 0.224513E+09 | 0.484444E+09 | 0.663279E+09 | 0.184911E+09 |
August | 0.757222E+09 | 0.316722E+09 | 0.440500E+09 | 0.735895E+09 | 0.217955E+09 |
September | 0.785229E+09 | 0.418316E+09 | 0.366912E+09 | 0.743891E+09 | 0.324281E+09 |
October | 0.692844E+09 | 0.407576E+09 | 0.285267E+09 | 0.592133E+09 | 0.497990E+09 |
November | 0.596936E+09 | 0.374579E+09 | 0.222357E+09 | 0.448023E+09 | 0.699082E+09 |
December | 0.656519E+09 | 0.430420E+09 | 0.226098E+09 | 0.411628E+09 | 0.109678E+10 |
Annual Sum or Average | 0.915238E+10 | 0.488741E+10 | 0.426497E+10 | 0.754216E+10 | 0.669730E+10 |
Minimum of Months | 0.596936E+09 | 0.167186E+09 | 0.222357E+09 | 0.411628E+09 | 0.180572E+09 |
Maximum of Months | 0.972707E+09 | 0.656985E+09 | 0.484444E+09 | 0.774220E+09 | 0.111825E+10 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.25 | 647.01 | 81.81 | 24.93 | 56.88 | 0.00 | 0.00 |
February | 19.55 | 506.50 | 147.93 | 64.27 | 83.66 | 0.00 | 0.00 |
March | 103.94 | 393.06 | 216.67 | 119.69 | 96.99 | 0.00 | 0.00 |
April | 261.47 | 256.18 | 326.47 | 205.96 | 120.50 | 0.00 | 0.00 |
May | 398.46 | 157.92 | 403.52 | 228.49 | 175.03 | 0.00 | 0.00 |
June | 452.65 | 118.32 | 425.51 | 246.91 | 178.61 | 0.00 | 0.00 |
July | 477.80 | 113.65 | 436.86 | 262.84 | 174.01 | 0.00 | 0.00 |
August | 353.65 | 123.58 | 342.59 | 193.03 | 149.56 | 0.00 | 0.00 |
September | 206.71 | 179.09 | 245.21 | 124.98 | 120.23 | 0.00 | 0.00 |
October | 66.65 | 261.15 | 143.12 | 54.60 | 88.52 | 0.00 | 0.00 |
November | 4.79 | 395.41 | 81.08 | 21.76 | 59.33 | 0.00 | 0.00 |
December | 0.00 | 620.87 | 64.45 | 13.83 | 50.62 | 0.00 | 0.00 |
Annual Sum or Average | 196.55 | 313.66 | 243.42 | 130.43 | 112.99 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 113.65 | 64.45 | 13.83 | 50.62 | 0.00 | 0.00 |
Maximum of Months | 477.80 | 647.01 | 436.86 | 262.84 | 178.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1113.89 | 1980.53 | 1542.81 | 1073.16 | 469.65 | 0.00 | 0.00 |
February | 1618.63 | 1657.77 | 1954.07 | 1319.82 | 634.25 | 0.00 | 0.00 |
March | 1394.74 | 1384.02 | 1722.64 | 1090.48 | 632.16 | 0.00 | 0.00 |
April | 1295.66 | 904.91 | 1560.16 | 846.91 | 713.25 | 0.00 | 0.00 |
May | 1120.91 | 519.32 | 1311.30 | 448.16 | 863.13 | 0.00 | 0.00 |
June | 1067.11 | 368.95 | 1176.59 | 313.47 | 863.12 | 0.00 | 0.00 |
July | 1235.75 | 353.41 | 1286.39 | 407.38 | 879.02 | 0.00 | 0.00 |
August | 1351.24 | 422.29 | 1373.97 | 574.69 | 799.28 | 0.00 | 0.00 |
September | 1405.11 | 647.59 | 1472.28 | 784.33 | 687.95 | 0.00 | 0.00 |
October | 1096.38 | 922.82 | 1257.16 | 739.54 | 517.61 | 0.00 | 0.00 |
November | 884.96 | 1283.13 | 1119.24 | 702.32 | 416.91 | 0.00 | 0.00 |
December | 782.32 | 1931.45 | 1191.25 | 780.99 | 410.25 | 0.00 | 0.00 |
Annual Sum or Average | 1194.13 | 1028.72 | 1410.45 | 753.18 | 657.26 | 0.00 | 0.00 |
Minimum of Months | 782.32 | 353.41 | 1119.24 | 313.47 | 410.25 | 0.00 | 0.00 |
Maximum of Months | 1618.63 | 1980.53 | 1954.07 | 1319.82 | 879.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1112.06 | 1977.48 | 1542.81 | 1073.16 | 469.65 | 0.00 | 0.00 |
February | 1618.90 | 1648.78 | 1954.07 | 1319.82 | 634.25 | 0.00 | 0.00 |
March | 1396.63 | 1370.18 | 1722.64 | 1090.48 | 632.16 | 0.00 | 0.00 |
April | 1301.60 | 881.21 | 1560.16 | 846.91 | 713.25 | 0.00 | 0.00 |
May | 1131.77 | 493.22 | 1311.30 | 448.16 | 863.13 | 0.00 | 0.00 |
June | 1073.36 | 347.59 | 1176.59 | 313.47 | 863.12 | 0.00 | 0.00 |
July | 1236.35 | 337.08 | 1286.39 | 407.38 | 879.02 | 0.00 | 0.00 |
August | 1352.01 | 403.85 | 1373.97 | 574.69 | 799.28 | 0.00 | 0.00 |
September | 1413.21 | 619.50 | 1472.28 | 784.33 | 687.95 | 0.00 | 0.00 |
October | 1104.73 | 892.11 | 1257.16 | 739.54 | 517.61 | 0.00 | 0.00 |
November | 888.03 | 1265.68 | 1119.24 | 702.32 | 416.91 | 0.00 | 0.00 |
December | 781.04 | 1928.09 | 1191.25 | 780.99 | 410.25 | 0.00 | 0.00 |
Annual Sum or Average | 1197.72 | 1011.09 | 1410.45 | 753.18 | 657.26 | 0.00 | 0.00 |
Minimum of Months | 781.04 | 337.08 | 1119.24 | 313.47 | 410.25 | 0.00 | 0.00 |
Maximum of Months | 1618.90 | 1977.48 | 1954.07 | 1319.82 | 879.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.19 | 417.51 | 317.46 | 220.82 | 96.64 | 0.00 | 0.00 |
February | 320.03 | 347.81 | 402.08 | 271.57 | 130.51 | 0.00 | 0.00 |
March | 276.68 | 293.05 | 354.46 | 224.38 | 130.08 | 0.00 | 0.00 |
April | 259.47 | 186.21 | 321.03 | 174.26 | 146.76 | 0.00 | 0.00 |
May | 228.01 | 100.25 | 269.82 | 92.22 | 177.60 | 0.00 | 0.00 |
June | 215.68 | 69.67 | 242.10 | 64.50 | 177.60 | 0.00 | 0.00 |
July | 247.64 | 69.04 | 264.69 | 83.82 | 180.87 | 0.00 | 0.00 |
August | 274.75 | 81.38 | 282.71 | 118.25 | 164.46 | 0.00 | 0.00 |
September | 287.00 | 125.11 | 302.94 | 161.39 | 141.56 | 0.00 | 0.00 |
October | 221.08 | 185.93 | 258.68 | 152.17 | 106.51 | 0.00 | 0.00 |
November | 172.85 | 269.71 | 230.30 | 144.51 | 85.79 | 0.00 | 0.00 |
December | 153.68 | 409.49 | 245.12 | 160.70 | 84.42 | 0.00 | 0.00 |
Annual Sum or Average | 239.16 | 212.37 | 290.22 | 154.98 | 135.24 | 0.00 | 0.00 |
Minimum of Months | 153.68 | 69.04 | 230.30 | 64.50 | 84.42 | 0.00 | 0.00 |
Maximum of Months | 320.03 | 417.51 | 402.08 | 271.57 | 180.87 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 664217.31 | 0.173295E+10 | 0.219112E+09 | 66764243.62 | 0.152348E+09 | 0.00 | 0.00 |
February | 47302547.49 | 0.122532E+10 | 0.357877E+09 | 0.155475E+09 | 0.202402E+09 | 0.00 | 0.00 |
March | 0.278395E+09 | 0.105278E+10 | 0.580331E+09 | 0.320565E+09 | 0.259766E+09 | 0.00 | 0.00 |
April | 0.677736E+09 | 0.664016E+09 | 0.846198E+09 | 0.533852E+09 | 0.312346E+09 | 0.00 | 0.00 |
May | 0.106723E+10 | 0.422982E+09 | 0.108080E+10 | 0.611997E+09 | 0.468800E+09 | 0.00 | 0.00 |
June | 0.117327E+10 | 0.306683E+09 | 0.110293E+10 | 0.639980E+09 | 0.462948E+09 | 0.00 | 0.00 |
July | 0.127973E+10 | 0.304410E+09 | 0.117008E+10 | 0.703999E+09 | 0.466078E+09 | 0.00 | 0.00 |
August | 0.947211E+09 | 0.330991E+09 | 0.917590E+09 | 0.517003E+09 | 0.400586E+09 | 0.00 | 0.00 |
September | 0.535783E+09 | 0.464196E+09 | 0.635583E+09 | 0.323937E+09 | 0.311646E+09 | 0.00 | 0.00 |
October | 0.178518E+09 | 0.699457E+09 | 0.383332E+09 | 0.146233E+09 | 0.237099E+09 | 0.00 | 0.00 |
November | 12427187.94 | 0.102490E+10 | 0.210168E+09 | 56394798.63 | 0.153773E+09 | 0.00 | 0.00 |
December | 0.00 | 0.166294E+10 | 0.172612E+09 | 37036976.35 | 0.135575E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.619827E+10 | 0.989162E+10 | 0.767660E+10 | 0.411324E+10 | 0.356337E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.304410E+09 | 0.172612E+09 | 37036976.35 | 0.135575E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127973E+10 | 0.173295E+10 | 0.117008E+10 | 0.703999E+09 | 0.468800E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.298344E+10 | 0.530464E+10 | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.00 | 0.00 |
February | 0.391578E+10 | 0.401049E+10 | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.00 | 0.00 |
March | 0.373568E+10 | 0.370695E+10 | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.00 | 0.00 |
April | 0.335835E+10 | 0.234553E+10 | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.00 | 0.00 |
May | 0.300224E+10 | 0.139096E+10 | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.00 | 0.00 |
June | 0.276594E+10 | 0.956321E+09 | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.00 | 0.00 |
July | 0.330982E+10 | 0.946585E+09 | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.00 | 0.00 |
August | 0.361916E+10 | 0.113106E+10 | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.00 | 0.00 |
September | 0.364204E+10 | 0.167856E+10 | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.00 | 0.00 |
October | 0.293654E+10 | 0.247169E+10 | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.00 | 0.00 |
November | 0.229383E+10 | 0.332586E+10 | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.00 | 0.00 |
December | 0.209538E+10 | 0.517320E+10 | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.376582E+11 | 0.324418E+11 | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209538E+10 | 0.946585E+09 | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.00 | 0.00 |
Maximum of Months | 0.391578E+10 | 0.530464E+10 | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297854E+10 | 0.529649E+10 | 0.413226E+10 | 0.287434E+10 | 0.125792E+10 | 0.00 | 0.00 |
February | 0.391644E+10 | 0.398872E+10 | 0.472728E+10 | 0.319290E+10 | 0.153439E+10 | 0.00 | 0.00 |
March | 0.374074E+10 | 0.366988E+10 | 0.461392E+10 | 0.292075E+10 | 0.169318E+10 | 0.00 | 0.00 |
April | 0.337376E+10 | 0.228410E+10 | 0.404395E+10 | 0.219520E+10 | 0.184875E+10 | 0.00 | 0.00 |
May | 0.303133E+10 | 0.132105E+10 | 0.351217E+10 | 0.120036E+10 | 0.231181E+10 | 0.00 | 0.00 |
June | 0.278215E+10 | 0.900959E+09 | 0.304972E+10 | 0.812512E+09 | 0.223721E+10 | 0.00 | 0.00 |
July | 0.331145E+10 | 0.902831E+09 | 0.344548E+10 | 0.109112E+10 | 0.235436E+10 | 0.00 | 0.00 |
August | 0.362122E+10 | 0.108168E+10 | 0.368004E+10 | 0.153925E+10 | 0.214079E+10 | 0.00 | 0.00 |
September | 0.366305E+10 | 0.160574E+10 | 0.381615E+10 | 0.203299E+10 | 0.178317E+10 | 0.00 | 0.00 |
October | 0.295892E+10 | 0.238943E+10 | 0.336717E+10 | 0.198079E+10 | 0.138638E+10 | 0.00 | 0.00 |
November | 0.230176E+10 | 0.328065E+10 | 0.290106E+10 | 0.182043E+10 | 0.108064E+10 | 0.00 | 0.00 |
December | 0.209193E+10 | 0.516420E+10 | 0.319063E+10 | 0.209181E+10 | 0.109882E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.377713E+11 | 0.318857E+11 | 0.444798E+11 | 0.237524E+11 | 0.207274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209193E+10 | 0.900959E+09 | 0.290106E+10 | 0.812512E+09 | 0.108064E+10 | 0.00 | 0.00 |
Maximum of Months | 0.391644E+10 | 0.529649E+10 | 0.472728E+10 | 0.319290E+10 | 0.235436E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.589761E+09 | 0.111825E+10 | 0.850274E+09 | 0.591437E+09 | 0.258836E+09 | 0.00 | 0.00 |
February | 0.774220E+09 | 0.841415E+09 | 0.972707E+09 | 0.656985E+09 | 0.315722E+09 | 0.00 | 0.00 |
March | 0.741054E+09 | 0.784905E+09 | 0.949382E+09 | 0.600986E+09 | 0.348396E+09 | 0.00 | 0.00 |
April | 0.672542E+09 | 0.482651E+09 | 0.832101E+09 | 0.451694E+09 | 0.380406E+09 | 0.00 | 0.00 |
May | 0.610691E+09 | 0.268517E+09 | 0.722681E+09 | 0.246992E+09 | 0.475689E+09 | 0.00 | 0.00 |
June | 0.559044E+09 | 0.180572E+09 | 0.627525E+09 | 0.167186E+09 | 0.460339E+09 | 0.00 | 0.00 |
July | 0.663279E+09 | 0.184911E+09 | 0.708958E+09 | 0.224513E+09 | 0.484444E+09 | 0.00 | 0.00 |
August | 0.735895E+09 | 0.217955E+09 | 0.757222E+09 | 0.316722E+09 | 0.440500E+09 | 0.00 | 0.00 |
September | 0.743891E+09 | 0.324281E+09 | 0.785229E+09 | 0.418316E+09 | 0.366912E+09 | 0.00 | 0.00 |
October | 0.592133E+09 | 0.497990E+09 | 0.692844E+09 | 0.407576E+09 | 0.285267E+09 | 0.00 | 0.00 |
November | 0.448023E+09 | 0.699082E+09 | 0.596936E+09 | 0.374579E+09 | 0.222357E+09 | 0.00 | 0.00 |
December | 0.411628E+09 | 0.109678E+10 | 0.656519E+09 | 0.430420E+09 | 0.226098E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.754216E+10 | 0.669730E+10 | 0.915238E+10 | 0.488741E+10 | 0.426497E+10 | 0.00 | 0.00 |
Minimum of Months | 0.411628E+09 | 0.180572E+09 | 0.596936E+09 | 0.167186E+09 | 0.222357E+09 | 0.00 | 0.00 |
Maximum of Months | 0.774220E+09 | 0.111825E+10 | 0.972707E+09 | 0.656985E+09 | 0.484444E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.314438E+10 | -.270575E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -438627004.2 | 58.99 | 0.00 | 0.00 |
February | 0.291555E+10 | -.252022E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -395328718.4 | 59.00 | 0.00 | 0.00 |
March | 0.328361E+10 | -.284827E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -435335296.1 | 58.99 | 0.00 | 0.00 |
April | 0.304045E+10 | -.262635E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -414108189.7 | 59.00 | 0.00 | 0.00 |
May | 0.298547E+10 | -.258140E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -404072244.1 | 58.99 | 0.00 | 0.00 |
June | 0.276199E+10 | -.238190E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -380085581.0 | 58.99 | 0.00 | 0.00 |
July | 0.265005E+10 | -.226382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386234558.6 | 58.99 | 0.00 | 0.00 |
August | 0.265609E+10 | -.226848E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -387610968.9 | 58.99 | 0.00 | 0.00 |
September | 0.255420E+10 | -.216888E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -385311807.2 | 59.00 | 0.00 | 0.00 |
October | 0.271301E+10 | -.229379E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -419218084.8 | 58.99 | 0.00 | 0.00 |
November | 0.275899E+10 | -.234050E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -418485641.6 | 58.99 | 0.00 | 0.00 |
December | 0.301961E+10 | -.258157E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -438039788.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344834E+11 | -.295809E+11 | 8760.00 | -.490246E+10 | 58.99 | |||||
Minimum of Months | 0.255420E+10 | -.284827E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -438627004.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.328361E+10 | -.216888E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -380085581.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | ||||||||||
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.446020E+11 | 56121.05 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.327428E+11 | 56121.05 | 01-FEB-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271330E+11 | 56121.05 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116842E+11 | 56121.05 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149972E+10 | 56121.05 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32175918.23 | 36044.70 | 01-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2054261.43 | 1329.44 | 19-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.289170E+09 | 50172.24 | 28-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540678E+10 | 56121.05 | 03-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174766E+11 | 56121.05 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399330E+11 | 56121.05 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180801E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.446020E+11 | 56121.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165885E+12 | 323663.63 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114704E+12 | 323663.63 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.926346E+11 | 323663.63 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.314857E+11 | 323663.63 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266572E+10 | 323663.63 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5337836.85 | 8554.66 | 19-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.606446E+09 | 27303.67 | 23-SEP-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210080E+11 | 323663.63 | 09-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.665183E+11 | 323663.63 | 04-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150698E+12 | 323663.63 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646212E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165885E+12 | 323663.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208722E+11 | 40741.14 | 01-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136456E+11 | 40741.14 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107409E+11 | 40741.14 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.409443E+10 | 40741.14 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.532542E+09 | 40741.14 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9485204.47 | 1785.20 | 03-JUN-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5359710.07 | 1846.94 | 19-AUG-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105691E+09 | 4547.90 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202449E+10 | 40741.14 | 06-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733731E+10 | 40741.14 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193858E+11 | 40741.14 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.787538E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208722E+11 | 40741.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248277E+11 | 35477.71 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168740E+11 | 35477.71 | 01-FEB-01:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141257E+11 | 35477.71 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.623841E+10 | 35477.71 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105827E+10 | 35477.71 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89560240.53 | 20078.90 | 01-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3222522.00 | 1717.10 | 10-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20604833.99 | 4537.73 | 19-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.396761E+09 | 29393.48 | 28-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.385731E+10 | 35477.71 | 05-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102868E+11 | 35477.71 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232639E+11 | 35477.71 | 01-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101042E+12 | |||||||
Minimum of Months | 3222522.00 | 1717.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248277E+11 | 35477.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.377351E+11 | 88809.66 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243734E+11 | 76047.37 | 01-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205059E+11 | 57568.69 | 15-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.799191E+10 | 35004.22 | 04-APR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103225E+10 | 13468.68 | 01-MAY-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76897081.01 | 3573.90 | 02-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17563126.25 | 1571.30 | 08-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106822E+09 | 6271.66 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109655E+10 | 11696.20 | 27-SEP-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746448E+10 | 29106.76 | 29-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163211E+11 | 58415.11 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357392E+11 | 85303.86 | 24-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152461E+12 | |||||||
Minimum of Months | 17563126.25 | 1571.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.377351E+11 | 88809.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6350064.81 | 5356423.28 | 1885.67 | 23-APR-16:00 | 1587.57 | 0.00 |
May | 0.00 | 0.00 | 0.341873E+10 | 0.284718E+10 | 14872.47 | 25-MAY-15:00 | 11472.74 | 0.00 |
June | 0.00 | 0.00 | 0.946122E+10 | 0.703353E+10 | 38498.76 | 30-JUN-04:01 | 17812.70 | 0.00 |
July | 0.00 | 0.00 | 0.149444E+11 | 0.107893E+11 | 37594.94 | 04-JUL-06:02 | 18395.45 | 0.00 |
August | 0.00 | 0.00 | 0.120555E+11 | 0.880721E+10 | 36257.53 | 09-AUG-04:02 | 22098.79 | 0.00 |
September | 0.00 | 0.00 | 0.331514E+10 | 0.269230E+10 | 15720.56 | 01-SEP-14:50 | 12468.18 | 0.00 |
October | 0.00 | 0.00 | 0.173653E+09 | 0.159091E+09 | 4157.57 | 21-OCT-15:58 | 3880.35 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.433750E+11 | 0.323340E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.149444E+11 | 0.107893E+11 | 38498.76 | 22098.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.232047E+10 | 0.220696E+10 | 42670.72 | 23-APR-16:00 | 36808.61 | 0.00 |
May | 0.00 | 0.00 | 0.293843E+11 | 0.253856E+11 | 175157.20 | 26-MAY-04:03 | 132524.99 | 0.00 |
June | 0.00 | 0.00 | 0.659622E+11 | 0.493436E+11 | 189072.18 | 30-JUN-04:01 | 109648.93 | 0.00 |
July | 0.00 | 0.00 | 0.917500E+11 | 0.650140E+11 | 186609.46 | 04-JUL-06:02 | 105116.91 | 0.00 |
August | 0.00 | 0.00 | 0.728581E+11 | 0.523003E+11 | 181139.47 | 09-AUG-04:02 | 115455.69 | 0.00 |
September | 0.00 | 0.00 | 0.214737E+11 | 0.175677E+11 | 180486.79 | 01-SEP-04:02 | 108406.46 | 0.00 |
October | 0.00 | 0.00 | 0.206801E+10 | 0.190818E+10 | 34848.69 | 19-OCT-15:00 | 31244.61 | 0.00 |
November | 0.00 | 0.00 | 0.118635E+09 | 92449991.29 | 12283.47 | 01-NOV-15:00 | 9564.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.285935E+12 | 0.213819E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.917500E+11 | 0.650140E+11 | 189072.18 | 132524.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 3009268.89 | 3009268.89 | 653.45 | 31-MAR-14:30 | 653.45 | 0.00 |
April | 0.00 | 0.00 | 0.900043E+09 | 0.886041E+09 | 7406.05 | 23-APR-14:30 | 6678.86 | 0.00 |
May | 0.00 | 0.00 | 0.469963E+10 | 0.426675E+10 | 18707.31 | 26-MAY-04:03 | 14688.48 | 0.00 |
June | 0.00 | 0.00 | 0.893198E+10 | 0.712063E+10 | 25789.13 | 30-JUN-04:01 | 12794.29 | 0.00 |
July | 0.00 | 0.00 | 0.127843E+11 | 0.976239E+10 | 25117.31 | 04-JUL-06:02 | 12987.61 | 0.00 |
August | 0.00 | 0.00 | 0.115486E+11 | 0.904034E+10 | 24249.55 | 09-AUG-04:02 | 15766.16 | 0.00 |
September | 0.00 | 0.00 | 0.531429E+10 | 0.474746E+10 | 24150.28 | 01-SEP-04:02 | 14777.06 | 0.00 |
October | 0.00 | 0.00 | 0.143654E+10 | 0.138296E+10 | 10445.35 | 19-OCT-14:20 | 9871.28 | 0.00 |
November | 0.00 | 0.00 | 68555447.06 | 61940681.29 | 2663.11 | 01-NOV-15:00 | 2207.45 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.456870E+11 | 0.372715E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127843E+11 | 0.976239E+10 | 25789.13 | 15766.16 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.316908E+09 | 0.304842E+09 | 5040.35 | 23-APR-14:40 | 4406.76 | 0.00 |
May | 0.00 | 0.00 | 0.252670E+10 | 0.219658E+10 | 10022.26 | 25-MAY-14:10 | 7974.14 | 0.00 |
June | 0.00 | 0.00 | 0.569696E+10 | 0.429918E+10 | 21664.51 | 30-JUN-04:01 | 10151.38 | 0.00 |
July | 0.00 | 0.00 | 0.904972E+10 | 0.655306E+10 | 21121.74 | 04-JUL-06:02 | 10147.56 | 0.00 |
August | 0.00 | 0.00 | 0.777609E+10 | 0.579414E+10 | 20346.75 | 09-AUG-04:02 | 12364.22 | 0.00 |
September | 0.00 | 0.00 | 0.290454E+10 | 0.254567E+10 | 16955.35 | 01-SEP-04:02 | 9707.34 | 0.00 |
October | 0.00 | 0.00 | 0.730097E+09 | 0.691727E+09 | 7857.75 | 19-OCT-14:20 | 7255.54 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290010E+11 | 0.223852E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.904972E+10 | 0.655306E+10 | 21664.51 | 12364.22 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.185037E+11 | 1.01 | 11036.57 | 01-JAN-00:04 | 1.62 |
February | 0.159634E+11 | 0.97 | 11036.57 | 01-FEB-00:05 | 1.62 |
March | 0.167203E+11 | 0.91 | 11036.57 | 01-MAR-05:01 | 1.61 |
April | 0.137354E+11 | 0.77 | 11036.57 | 01-APR-04:01 | 1.61 |
May | 0.786966E+10 | 0.43 | 11036.57 | 01-MAY-04:01 | 1.61 |
June | 0.346762E+10 | 0.19 | 11036.57 | 01-JUN-04:02 | 1.60 |
July | 0.179908E+10 | 0.10 | 11036.57 | 01-JUL-07:05 | 1.59 |
August | 0.299154E+10 | 0.16 | 11036.57 | 01-AUG-07:04 | 1.58 |
September | 0.923747E+10 | 0.52 | 11036.57 | 01-SEP-07:05 | 1.58 |
October | 0.134523E+11 | 0.73 | 11036.57 | 01-OCT-06:02 | 1.60 |
November | 0.154094E+11 | 0.87 | 11036.57 | 01-NOV-04:01 | 1.61 |
December | 0.183178E+11 | 1.00 | 11036.57 | 01-DEC-00:55 | 1.61 |
Annual Sum or Average | 0.137468E+12 | 0.64 | |||
Minimum of Months | 0.179908E+10 | 0.10 | 11036.57 | 1.58 | |
Maximum of Months | 0.185037E+11 | 1.01 | 11036.57 | 1.62 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.332657E+10 | 0.74 | 1887.91 | 09-JAN-15:50 | 0.94 |
February | 0.296424E+10 | 0.71 | 1887.91 | 18-FEB-07:45 | 0.94 |
March | 0.322634E+10 | 0.66 | 1887.91 | 07-MAR-18:45 | 0.94 |
April | 0.302620E+10 | 0.60 | 1887.91 | 01-APR-08:25 | 0.94 |
May | 0.306526E+10 | 0.57 | 1887.91 | 01-MAY-06:17 | 0.94 |
June | 0.297956E+10 | 0.57 | 1887.91 | 01-JUN-11:00 | 0.93 |
July | 0.303381E+10 | 0.56 | 1887.91 | 05-JUL-12:20 | 0.92 |
August | 0.308012E+10 | 0.57 | 1887.91 | 21-AUG-14:20 | 0.92 |
September | 0.295748E+10 | 0.56 | 1887.91 | 01-SEP-07:38 | 0.92 |
October | 0.305351E+10 | 0.58 | 1887.91 | 01-OCT-07:03 | 0.93 |
November | 0.300608E+10 | 0.61 | 1887.91 | 02-NOV-19:27 | 0.94 |
December | 0.329438E+10 | 0.72 | 1887.91 | 02-DEC-20:56 | 0.94 |
Annual Sum or Average | 0.370136E+11 | 0.62 | |||
Minimum of Months | 0.295748E+10 | 0.56 | 1887.91 | 0.92 | |
Maximum of Months | 0.332657E+10 | 0.74 | 1887.91 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.240023E+11 | 1.00 | 14725.37 | 02-JAN-07:42 | 1.59 |
February | 0.217133E+11 | 1.00 | 14725.37 | 04-FEB-11:46 | 1.59 |
March | 0.242415E+11 | 1.01 | 14725.37 | 09-MAR-13:40 | 1.59 |
April | 0.231347E+11 | 0.98 | 14725.37 | 03-APR-07:08 | 1.59 |
May | 0.238251E+11 | 0.96 | 14725.37 | 01-MAY-07:43 | 1.59 |
June | 0.232849E+11 | 0.96 | 14725.37 | 02-JUN-10:32 | 1.58 |
July | 0.238052E+11 | 0.96 | 14725.37 | 06-JUL-07:10 | 1.57 |
August | 0.241390E+11 | 0.97 | 14725.37 | 15-AUG-18:28 | 1.56 |
September | 0.230807E+11 | 0.95 | 14725.37 | 06-SEP-10:16 | 1.58 |
October | 0.236153E+11 | 0.96 | 14725.37 | 01-OCT-08:47 | 1.58 |
November | 0.228904E+11 | 0.98 | 14725.37 | 03-NOV-08:43 | 1.59 |
December | 0.240029E+11 | 1.00 | 14725.37 | 01-DEC-20:45 | 1.59 |
Annual Sum or Average | 0.281735E+12 | 0.98 | |||
Minimum of Months | 0.217133E+11 | 0.95 | 14725.37 | 1.56 | |
Maximum of Months | 0.242415E+11 | 1.01 | 14725.37 | 1.59 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230654E+10 | 0.74 | 1364.06 | 01-JAN-11:10 | 0.98 |
February | 0.206436E+10 | 0.71 | 1364.06 | 01-FEB-09:10 | 0.98 |
March | 0.227499E+10 | 0.66 | 1364.06 | 01-MAR-06:02 | 0.98 |
April | 0.215684E+10 | 0.62 | 1364.06 | 01-APR-05:30 | 0.98 |
May | 0.220828E+10 | 0.59 | 1364.06 | 01-MAY-09:58 | 0.98 |
June | 0.215498E+10 | 0.59 | 1364.06 | 01-JUN-16:20 | 0.97 |
July | 0.219973E+10 | 0.59 | 1364.06 | 01-JUL-07:28 | 0.97 |
August | 0.223243E+10 | 0.60 | 1364.06 | 01-AUG-07:51 | 0.96 |
September | 0.213766E+10 | 0.59 | 1364.06 | 01-SEP-06:40 | 0.96 |
October | 0.219398E+10 | 0.60 | 1364.06 | 01-OCT-11:40 | 0.97 |
November | 0.214078E+10 | 0.63 | 1364.06 | 01-NOV-05:51 | 0.97 |
December | 0.230043E+10 | 0.74 | 1364.06 | 01-DEC-15:10 | 0.98 |
Annual Sum or Average | 0.263710E+11 | 0.64 | |||
Minimum of Months | 0.206436E+10 | 0.59 | 1364.06 | 0.96 | |
Maximum of Months | 0.230654E+10 | 0.74 | 1364.06 | 0.98 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.188893E+10 | 0.78 | 1092.60 | 01-JAN-08:06 | 0.98 |
February | 0.168000E+10 | 0.73 | 1092.60 | 21-FEB-14:50 | 0.98 |
March | 0.184048E+10 | 0.68 | 1092.60 | 01-MAR-06:02 | 0.98 |
April | 0.173673E+10 | 0.63 | 1092.60 | 14-APR-14:10 | 0.98 |
May | 0.177144E+10 | 0.60 | 1092.60 | 02-MAY-08:23 | 0.98 |
June | 0.172490E+10 | 0.59 | 1092.60 | 10-JUN-13:10 | 0.96 |
July | 0.175709E+10 | 0.58 | 1092.60 | 01-JUL-07:53 | 0.97 |
August | 0.178432E+10 | 0.59 | 1092.60 | 10-AUG-07:33 | 0.96 |
September | 0.171236E+10 | 0.59 | 1092.60 | 01-SEP-07:42 | 0.96 |
October | 0.176211E+10 | 0.60 | 1092.60 | 03-OCT-18:53 | 0.98 |
November | 0.172795E+10 | 0.65 | 1092.60 | 14-NOV-11:20 | 0.98 |
December | 0.187985E+10 | 0.76 | 1092.60 | 01-DEC-06:03 | 0.98 |
Annual Sum or Average | 0.212662E+11 | 0.65 | |||
Minimum of Months | 0.168000E+10 | 0.58 | 1092.60 | 0.96 | |
Maximum of Months | 0.188893E+10 | 0.78 | 1092.60 | 0.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.99 | 0.00 |
February | 3.47 | 0.00 |
March | 2.94 | 0.00 |
April | 1.18 | 0.00 |
May | 0.00 | 0.00 |
June | 0.04 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.54 | 0.00 |
November | 2.53 | 0.00 |
December | 3.75 | 0.00 |
Annual Sum or Average | 18.43 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.99 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.07 | 0.00 |
May | 0.50 | 0.00 |
June | 0.69 | 0.00 |
July | 0.24 | 0.00 |
August | 0.10 | 0.00 |
September | 1.42 | 0.00 |
October | 0.28 | 0.00 |
November | 0.00 | 0.00 |
December | 0.14 | 0.00 |
Annual Sum or Average | 3.55 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.42 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.12 | 0.00 |
February | 1.97 | 0.00 |
March | 1.38 | 0.00 |
April | 0.43 | 0.00 |
May | 0.00 | 0.00 |
June | 0.21 | 0.00 |
July | 0.32 | 0.00 |
August | 0.60 | 0.00 |
September | 0.38 | 0.00 |
October | 0.20 | 0.00 |
November | 0.80 | 0.00 |
December | 2.99 | 0.00 |
Annual Sum or Average | 12.38 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.12 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.50 | 0.00 |
February | 2.58 | 0.00 |
March | 2.34 | 0.00 |
April | 1.02 | 0.00 |
May | 0.07 | 0.00 |
June | 0.12 | 0.00 |
July | 0.18 | 0.00 |
August | 0.00 | 0.00 |
September | 0.26 | 0.00 |
October | 0.89 | 0.00 |
November | 2.02 | 0.00 |
December | 3.65 | 0.00 |
Annual Sum or Average | 16.64 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.65 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 54.65 | 0.00 |
February | 40.29 | 0.00 |
March | 38.95 | 0.00 |
April | 61.83 | 0.00 |
May | 74.06 | 0.00 |
June | 42.73 | 0.00 |
July | 26.84 | 0.00 |
August | 44.49 | 0.00 |
September | 88.71 | 0.00 |
October | 67.84 | 0.00 |
November | 41.92 | 0.00 |
December | 46.64 | 0.00 |
Annual Sum or Average | 628.94 | 0.00 |
Minimum of Months | 26.84 | 0.00 |
Maximum of Months | 88.71 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.332657E+10 | 0.557525E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.296424E+10 | 0.409285E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.322634E+10 | 0.339162E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.302829E+10 | 0.146052E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.408979E+10 | 0.187464E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.574485E+10 | 40219897.78 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.732677E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.652110E+10 | 2567826.79 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.392386E+10 | 0.361462E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.310559E+10 | 0.675848E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.300608E+10 | 0.218457E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.329438E+10 | 0.499163E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.495579E+11 | 0.226002E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.296424E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.732677E+10 | 0.557525E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.240023E+11 | 0.209319E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.217133E+11 | 0.144737E+12 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.242415E+11 | 0.116889E+12 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.238896E+11 | 0.397296E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.331214E+11 | 0.336368E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.435885E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.516996E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.462953E+11 | 6735440.82 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.297928E+11 | 0.765231E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.242766E+11 | 0.265085E+11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.229293E+11 | 0.839348E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.240029E+11 | 0.190156E+12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.369553E+12 | 0.815410E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.217133E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.516996E+11 | 0.209319E+12 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.230654E+10 | 0.260903E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.206436E+10 | 0.170570E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.227591E+10 | 0.134261E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.241898E+10 | 0.511803E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.357193E+10 | 0.665677E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.470514E+10 | 11856505.59 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.578949E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.543197E+10 | 6699637.59 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.362645E+10 | 0.132114E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.259775E+10 | 0.253061E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.216125E+10 | 0.917164E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.230043E+10 | 0.242323E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.392502E+11 | 0.984423E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.578949E+10 | 0.260903E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.188893E+10 | 0.310347E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.168000E+10 | 0.210925E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.184048E+10 | 0.176571E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.183090E+10 | 0.779801E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.251709E+10 | 0.132284E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.336676E+10 | 0.111950E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.431803E+10 | 4028152.50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.395518E+10 | 25756042.49 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.253130E+10 | 0.495951E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.196817E+10 | 0.482164E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172795E+10 | 0.128585E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.187985E+10 | 0.290798E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.295046E+11 | 0.126303E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.168000E+10 | 4028152.50 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.431803E+10 | 0.310347E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.332657E+10 | 0.00 | 0.446020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296424E+10 | 0.00 | 0.327428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322634E+10 | 0.00 | 0.271330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302620E+10 | 6350064.81 | 0.116842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306526E+10 | 0.341873E+10 | 0.149972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.297956E+10 | 0.946122E+10 | 32175918.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.303381E+10 | 0.149444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.308012E+10 | 0.120555E+11 | 2054261.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295748E+10 | 0.331514E+10 | 0.289170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.305351E+10 | 0.173653E+09 | 0.540678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300608E+10 | 0.00 | 0.174766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329438E+10 | 0.00 | 0.399330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370136E+11 | 0.433750E+11 | 0.180801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.295748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.332657E+10 | 0.149444E+11 | 0.446020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.240023E+11 | 0.00 | 0.165885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217133E+11 | 0.00 | 0.114704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242415E+11 | 0.00 | 0.926346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231347E+11 | 0.232047E+10 | 0.314857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238251E+11 | 0.293843E+11 | 0.266572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.232849E+11 | 0.659622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.238052E+11 | 0.917500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.241390E+11 | 0.728581E+11 | 5337836.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230807E+11 | 0.214737E+11 | 0.606446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236153E+11 | 0.206801E+10 | 0.210080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228904E+11 | 0.118635E+09 | 0.665183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240029E+11 | 0.00 | 0.150698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281735E+12 | 0.285935E+12 | 0.646212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.217133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242415E+11 | 0.917500E+11 | 0.165885E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.230654E+10 | 0.00 | 0.208722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206436E+10 | 0.00 | 0.136456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227499E+10 | 3009268.89 | 0.107409E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215684E+10 | 0.900043E+09 | 0.409443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220828E+10 | 0.469963E+10 | 0.532542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.215498E+10 | 0.893198E+10 | 9485204.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219973E+10 | 0.127843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223243E+10 | 0.115486E+11 | 5359710.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213766E+10 | 0.531429E+10 | 0.105691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219398E+10 | 0.143654E+10 | 0.202449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214078E+10 | 68555447.06 | 0.733731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230043E+10 | 0.00 | 0.193858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263710E+11 | 0.456870E+11 | 0.787538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.206436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230654E+10 | 0.127843E+11 | 0.208722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.188893E+10 | 0.00 | 0.248277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168000E+10 | 0.00 | 0.168740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184048E+10 | 0.00 | 0.141257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173673E+10 | 0.316908E+09 | 0.623841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177144E+10 | 0.252670E+10 | 0.105827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172490E+10 | 0.569696E+10 | 89560240.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175709E+10 | 0.904972E+10 | 3222522.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178432E+10 | 0.777609E+10 | 20604833.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171236E+10 | 0.290454E+10 | 0.396761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176211E+10 | 0.730097E+09 | 0.385731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172795E+10 | 0.00 | 0.102868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187985E+10 | 0.00 | 0.232639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212662E+11 | 0.290010E+11 | 0.101042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168000E+10 | 0.00 | 3222522.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188893E+10 | 0.904972E+10 | 0.248277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.332657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302620E+10 | 0.00 | 0.00 | 0.00 | 2093415.61 | 0.00 | 0.146052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.306526E+10 | 0.00 | 0.00 | 0.00 | 0.102453E+10 | 0.00 | 0.187464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.297956E+10 | 0.00 | 0.00 | 0.00 | 0.276529E+10 | 0.00 | 40219897.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.303381E+10 | 0.00 | 0.00 | 0.00 | 0.429296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.308012E+10 | 0.00 | 0.00 | 0.00 | 0.344097E+10 | 0.00 | 2567826.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.295748E+10 | 0.00 | 0.00 | 0.00 | 0.966387E+09 | 0.00 | 0.361462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.305351E+10 | 0.00 | 0.00 | 0.00 | 52083205.39 | 0.00 | 0.675848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.329438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370136E+11 | 0.00 | 0.00 | 0.00 | 0.125443E+11 | 0.00 | 0.226002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.295748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.332657E+10 | 0.00 | 0.00 | 0.00 | 0.429296E+10 | 0.00 | 0.557525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.240023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231347E+11 | 0.00 | 0.00 | 0.00 | 0.754872E+09 | 0.00 | 0.397296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238251E+11 | 0.00 | 0.00 | 0.00 | 0.929632E+10 | 0.00 | 0.336368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.232849E+11 | 0.00 | 0.00 | 0.00 | 0.203037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.238052E+11 | 0.00 | 0.00 | 0.00 | 0.278944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.241390E+11 | 0.00 | 0.00 | 0.00 | 0.221564E+11 | 0.00 | 6735440.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230807E+11 | 0.00 | 0.00 | 0.00 | 0.671203E+10 | 0.00 | 0.765231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236153E+11 | 0.00 | 0.00 | 0.00 | 0.661269E+09 | 0.00 | 0.265085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228904E+11 | 0.00 | 0.00 | 0.00 | 38920418.35 | 0.00 | 0.839348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.240029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281735E+12 | 0.00 | 0.00 | 0.00 | 0.878179E+11 | 0.00 | 0.815410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.217133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242415E+11 | 0.00 | 0.00 | 0.00 | 0.278944E+11 | 0.00 | 0.209319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.230654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227499E+10 | 0.00 | 0.00 | 0.00 | 914723.25 | 0.00 | 0.134261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.215684E+10 | 0.00 | 0.00 | 0.00 | 0.262133E+09 | 0.00 | 0.511803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220828E+10 | 0.00 | 0.00 | 0.00 | 0.136365E+10 | 0.00 | 0.665677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.215498E+10 | 0.00 | 0.00 | 0.00 | 0.255017E+10 | 0.00 | 11856505.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219973E+10 | 0.00 | 0.00 | 0.00 | 0.358977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.223243E+10 | 0.00 | 0.00 | 0.00 | 0.319954E+10 | 0.00 | 6699637.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213766E+10 | 0.00 | 0.00 | 0.00 | 0.148879E+10 | 0.00 | 0.132114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.219398E+10 | 0.00 | 0.00 | 0.00 | 0.403768E+09 | 0.00 | 0.253061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214078E+10 | 0.00 | 0.00 | 0.00 | 20468409.06 | 0.00 | 0.917164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263710E+11 | 0.00 | 0.00 | 0.00 | 0.128792E+11 | 0.00 | 0.984423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.206436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.230654E+10 | 0.00 | 0.00 | 0.00 | 0.358977E+10 | 0.00 | 0.260903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.188893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.184048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173673E+10 | 0.00 | 0.00 | 0.00 | 94163845.11 | 0.00 | 0.779801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177144E+10 | 0.00 | 0.00 | 0.00 | 0.745646E+09 | 0.00 | 0.132284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172490E+10 | 0.00 | 0.00 | 0.00 | 0.164187E+10 | 0.00 | 0.111950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175709E+10 | 0.00 | 0.00 | 0.00 | 0.256094E+10 | 0.00 | 4028152.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178432E+10 | 0.00 | 0.00 | 0.00 | 0.217086E+10 | 0.00 | 25756042.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171236E+10 | 0.00 | 0.00 | 0.00 | 0.818937E+09 | 0.00 | 0.495951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176211E+10 | 0.00 | 0.00 | 0.00 | 0.206061E+09 | 0.00 | 0.482164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212662E+11 | 0.00 | 0.00 | 0.00 | 0.823848E+10 | 0.00 | 0.126303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.168000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4028152.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188893E+10 | 0.00 | 0.00 | 0.00 | 0.256094E+10 | 0.00 | 0.310347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4677900.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235599E+11 | 0.00 | 0.00 | 0.30 |
February | 1326125.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177291E+11 | 0.00 | 0.00 | 0.29 |
March | 0.362978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160434E+11 | 0.00 | 0.00 | 0.29 |
April | 0.244321E+10 | 0.00 | 281322.40 | 0.00 | 16007969.83 | 0.733529E+10 | 0.00 | 18773.70 | 0.28 |
May | 0.334154E+10 | 0.140365E+09 | 0.00 | 2929219.16 | 0.00 | 0.942369E+09 | 0.893018E+09 | 0.00 | 0.28 |
June | 0.129313E+10 | 0.135166E+10 | 0.00 | 6246770.58 | 3943484.59 | 9473219.65 | 0.147501E+10 | 0.00 | 0.28 |
July | 0.521170E+09 | 0.220008E+10 | 0.00 | 7923042.71 | 2763167.40 | 0.00 | 0.907369E+09 | 0.00 | 0.28 |
August | 0.820050E+09 | 0.104736E+10 | 0.00 | 12386130.63 | 23985.55 | 0.00 | 0.146399E+10 | 0.00 | 0.28 |
September | 0.362572E+10 | 33346638.28 | 0.00 | 8456770.05 | 0.00 | 0.157913E+09 | 0.225900E+10 | 0.00 | 0.28 |
October | 0.578319E+10 | 0.00 | 0.00 | 514184.31 | 0.00 | 0.355124E+10 | 0.235443E+09 | 0.00 | 0.27 |
November | 0.193164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111605E+11 | 0.00 | 0.00 | 0.28 |
December | 1265213.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220259E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.201299E+11 | 0.477281E+10 | 281322.40 | 38456117.44 | 22738607.37 | 0.102515E+12 | 0.723383E+10 | 18773.70 | 0.28 |
Minimum of Months | 1265213.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.578319E+10 | 0.220008E+10 | 281322.40 | 12386130.63 | 16007969.83 | 0.235599E+11 | 0.225900E+10 | 18773.70 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.635960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115829E+12 | 0.00 | 0.00 | 0.55 |
February | 0.705789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657500E+11 | 0.00 | 0.00 | 0.55 |
March | 0.832308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448694E+11 | 0.00 | 0.00 | 0.56 |
April | 0.606237E+11 | 0.116808E+09 | 0.00 | 6985525.94 | 0.00 | 0.127118E+11 | 0.481923E+10 | 0.00 | 0.55 |
May | 0.245027E+11 | 0.181368E+10 | 0.00 | 43059478.38 | 0.00 | 0.948965E+09 | 0.158173E+11 | 0.00 | 0.55 |
June | 0.691027E+10 | 0.121015E+11 | 0.00 | 63438735.54 | 17642457.41 | 0.00 | 0.134066E+11 | 0.00 | 0.56 |
July | 0.293505E+10 | 0.192003E+11 | 0.00 | 52089722.09 | 11250858.97 | 0.00 | 0.742044E+10 | 0.00 | 0.56 |
August | 0.477025E+10 | 0.911426E+10 | 0.00 | 85811497.09 | 9725576.64 | 0.00 | 0.123187E+11 | 0.00 | 0.56 |
September | 0.274507E+11 | 0.330221E+09 | 0.00 | 67441562.81 | 0.00 | 0.00 | 0.195464E+11 | 0.00 | 0.56 |
October | 0.653099E+11 | 0.00 | 0.00 | 7735575.94 | 0.00 | 0.638557E+10 | 0.416021E+10 | 0.00 | 0.54 |
November | 0.731930E+11 | 0.00 | 0.00 | 247205.35 | 0.00 | 0.302229E+11 | 0.447331E+09 | 99218.12 | 0.55 |
December | 0.729193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960938E+11 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.556020E+12 | 0.426768E+11 | 0.00 | 0.326809E+09 | 38618893.03 | 0.372811E+12 | 0.779362E+11 | 99218.12 | 0.55 |
Minimum of Months | 0.293505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.832308E+11 | 0.192003E+11 | 0.00 | 85811497.09 | 17642457.41 | 0.115829E+12 | 0.195464E+11 | 99218.12 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.412949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133547E+11 | 0.00 | 0.00 | 0.57 |
February | 0.511090E+10 | 0.00 | 0.00 | 21853.47 | 0.00 | 0.800873E+10 | 64181588.50 | 0.00 | 0.56 |
March | 0.600789E+10 | 0.00 | 0.00 | 55076.41 | 0.00 | 0.618410E+10 | 69216851.53 | 0.00 | 0.56 |
April | 0.408595E+10 | 14116581.35 | 0.00 | 3429439.29 | 0.00 | 0.230986E+10 | 0.108841E+10 | 0.00 | 0.55 |
May | 0.176176E+10 | 0.201391E+09 | 0.00 | 7995541.05 | 0.00 | 0.296143E+09 | 0.176780E+10 | 0.00 | 0.55 |
June | 0.619267E+09 | 0.128667E+10 | 0.00 | 8972031.08 | 347666.00 | 0.00 | 0.120637E+10 | 0.00 | 0.56 |
July | 0.275519E+09 | 0.211268E+10 | 0.00 | 7341620.13 | 0.00 | 0.00 | 0.625561E+09 | 0.00 | 0.56 |
August | 0.367030E+09 | 0.116350E+10 | 0.00 | 13144117.97 | 78570.79 | 0.00 | 0.105853E+10 | 0.00 | 0.56 |
September | 0.167349E+10 | 60676983.35 | 0.00 | 17963624.08 | 0.00 | 3045401.59 | 0.262124E+10 | 0.00 | 0.56 |
October | 0.483191E+10 | 0.00 | 0.00 | 6321710.11 | 0.00 | 0.976115E+09 | 0.149340E+10 | 0.00 | 0.55 |
November | 0.553616E+10 | 0.00 | 0.00 | 296736.48 | 0.00 | 0.415390E+10 | 0.239147E+09 | 0.00 | 0.55 |
December | 0.386161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125726E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.382610E+11 | 0.483903E+10 | 0.00 | 65541750.06 | 426236.79 | 0.478592E+11 | 0.102339E+11 | 0.00 | 0.56 |
Minimum of Months | 0.275519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.600789E+10 | 0.211268E+10 | 0.00 | 17963624.08 | 347666.00 | 0.133547E+11 | 0.262124E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163401E+11 | 0.00 | 0.00 | 0.58 |
February | 0.257856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108014E+11 | 0.00 | 0.00 | 0.57 |
March | 0.294668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939836E+10 | 0.00 | 0.00 | 0.57 |
April | 0.298908E+10 | 12211906.75 | 0.00 | 901397.00 | 0.00 | 0.393653E+10 | 0.454647E+09 | 0.00 | 0.56 |
May | 0.217844E+10 | 0.170515E+09 | 0.00 | 2700077.99 | 0.00 | 0.668071E+09 | 0.831519E+09 | 0.00 | 0.55 |
June | 0.101397E+10 | 0.110594E+10 | 0.00 | 3553146.89 | 396525.81 | 35251981.31 | 0.848936E+09 | 0.00 | 0.56 |
July | 0.486776E+09 | 0.181116E+10 | 0.00 | 4212198.10 | 1852821.72 | 0.00 | 0.536667E+09 | 0.00 | 0.56 |
August | 0.854882E+09 | 0.962889E+09 | 0.00 | 6906014.47 | 0.00 | 1653587.02 | 0.766299E+09 | 0.00 | 0.56 |
September | 0.246787E+10 | 46282387.67 | 0.00 | 8773281.50 | 0.00 | 0.208981E+09 | 0.157498E+10 | 0.00 | 0.55 |
October | 0.429860E+10 | 0.00 | 0.00 | 2951211.79 | 0.00 | 0.220298E+10 | 0.592569E+09 | 0.00 | 0.55 |
November | 0.315599E+10 | 0.00 | 0.00 | 13338.09 | 0.00 | 0.672662E+10 | 45738433.60 | 0.00 | 0.55 |
December | 0.121390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155614E+11 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.257225E+11 | 0.410900E+10 | 0.00 | 30010665.84 | 2249347.53 | 0.658814E+11 | 0.565136E+10 | 0.00 | 0.56 |
Minimum of Months | 0.486776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.429860E+10 | 0.181116E+10 | 0.00 | 8773281.50 | 1852821.72 | 0.163401E+11 | 0.157498E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |