Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2020-06-03 19:11:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1908.75 | 832.07 | 832.07 |
Net Site Energy | 1908.75 | 832.07 | 832.07 |
Total Source Energy | 5565.43 | 2426.09 | 2426.09 |
Net Source Energy | 5565.43 | 2426.09 | 2426.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 139.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 399.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 475.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 115.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.41 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1678.51 | 230.24 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 139.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 399.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 475.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 115.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 90.41 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 257.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 389.27 | 100.37 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 731.70 | 100.37 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 257.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 389.27 | 100.37 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 731.70 | 100.37 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1678.511 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1678.511 | 100.00 |
Total On-Site and Utility Electric Sources | 1678.511 | 100.00 |
Total Electricity End Uses | 1678.511 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1373.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 6.69 |
Skylight-Roof Ratio [%] | 0.29 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 8.3451 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 17.7333 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 17.7333 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 17.7333 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 13.5608 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.1568 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.1568 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:00 | 28-DEC-05:10 | - | - | - | 10-NOV-12:09 |
Heating | 0.00 | 195251.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 78875.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24635.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 147666.48 | 197113.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 195251.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 78875.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 24635.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 151.58 | 0.00 | 0.00 | 0.00 |
Cooling | 1266.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1505.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 364.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1561.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 98.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5315.84 | 249.58 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 66.08 | 0.00 | 0.00 | 0.00 |
Cooling | 552.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 656.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 680.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 42.72 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2317.29 | 108.80 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 66.08 | 0.00 | 0.00 | 0.00 |
Cooling | 552.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 656.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 680.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 42.72 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2317.29 | 108.80 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 3.02 |
CORE_RETAIL DIRECT AIR | 10.57 |
POINT_OF_SALE DIRECT AIR | 1.66 |
FRONT_RETAIL DIRECT AIR | 1.46 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 2.65 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 2.65 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 53572.08 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 68157.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 278797.90 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 39333.82 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 35365.97 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 3.02 | 3.02 | 3.02 | 3.02 | 3.02 | 3.02 | 1.00 | 1.00 | 3.02 |
PSZ-AC:2 | 10.57 | 10.57 | 10.57 | 10.57 | 10.57 | 10.57 | 1.00 | 1.00 | 10.57 |
PSZ-AC:3 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.66 | 1.00 | 1.00 | 1.66 |
PSZ-AC:4 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 3.02 | 0.289458 |
PSZ-AC:2_OA_CONTROLLER | 10.57 | 2.44 |
PSZ-AC:3_OA_CONTROLLER | 1.66 | 0.229820 |
PSZ-AC:4_OA_CONTROLLER | 1.46 | 0.229820 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 3.02 | 3.02 | 3.02 | 3.02 | 54214.19 | 68157.00 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 10.57 | 10.57 | 10.57 | 10.57 | 209082.31 | 278797.90 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.66 | 1.66 | 1.66 | 1.66 | 29977.35 | 39333.82 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 1.46 | 27067.11 | 35365.97 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 3.02 | 1.51 | 3.02 | 49987.75 | 54214.19 | 27107.10 | 54214.19 | 0.769994 | 0.769990 | 0.769990 | 0.769990 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 10.57 | 5.28 | 10.57 | 194376.90 | 209082.31 | 104541.15 | 209082.31 | 0.738668 | 0.738670 | 0.738670 | 0.738670 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.66 | 0.828010 | 1.66 | 27611.50 | 29977.35 | 14988.67 | 29977.35 | 0.767205 | 0.767210 | 0.767210 | 0.767210 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.46 | 0.728495 | 1.46 | 24993.80 | 27067.11 | 13533.56 | 27067.11 | 0.758602 | 0.758600 | 0.758600 | 0.758600 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 3.02 | 3305.14 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 10.57 | 17922.77 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.66 | 1812.53 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1594.68 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 8.345 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.415 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 17.733 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.963 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 17.733 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.253 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 17.733 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.963 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 13.561 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.561 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 3170.217 | 8.345 | 51.681 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3170.217 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 28381.872 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28381.872 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2674.362 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2674.362 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2674.362 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2674.362 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 162.729 | 13.561 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 162.729 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.233 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1215 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2334905 | 8.2334905 | 8.2334905 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
21 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
22 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
23 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.61_SHGC_0.25 | 30 | 1 | VerySmooth | 3.468 | 0.253 | 0.159 | 0.251 |
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 31 | 1 | VerySmooth | 5.108 | 0.400 | 0.232 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.15839 | 0.59143 | 0.59143 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 1.67629E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.23173 | 0.24680 | 0.24680 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 29659.70718 | 35591.64861 | 2.51646 | 3.01976 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 37.58000 | 6.82375E-003 | 379.89000 | 61.34184 | 0.28946 | 0.00000 |
2 | BACK_SPACE | Heating | 38850.79774 | 46620.95728 | 1.90408 | 2.28489 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 379.89000 | 61.34184 | 0.28946 | 0.00000 |
3 | CORE_RETAIL | Cooling | 103813.65362 | 124576.38434 | 8.80819 | 10.56982 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.82376E-003 | 1600.48290 | 258.43418 | 2.43898 | 0.00000 |
4 | CORE_RETAIL | Heating | 78886.54445 | 94663.85334 | 3.81950 | 4.58340 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 1600.48290 | 258.43418 | 2.43898 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 16265.43344 | 19518.52013 | 1.38002 | 1.65602 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.82374E-003 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
6 | POINT_OF_SALE | Heating | 16956.61259 | 20347.93510 | 0.83200 | 0.99840 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 14310.52660 | 17172.63192 | 1.21416 | 1.45699 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.82375E-003 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
8 | FRONT_RETAIL | Heating | 17002.76735 | 20403.32082 | 0.83429 | 1.00115 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 150.81000 | 24.35169 | 0.22982 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.82869E-002 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10000 | 6.82375E-003 | 12.00000 | 0.00000 | 1.82869E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 44608.42037 | 53530.10444 | 2.21006 | 2.65207 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 12.00000 | 0.00000 | 1.82869E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 39354.02 | 3.01976 | 3.01976 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 53507.90 | 2.28489 | 2.28489 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 159281.33 | 10.56982 | 10.56982 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 158706.87 | 4.58340 | 4.58340 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 22537.80 | 1.65602 | 1.65602 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 26223.57 | 0.99840 | 0.99840 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 20329.25 | 1.45699 | 1.45699 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 26278.39 | 1.00115 | 1.00115 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.01976 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 10.56982 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.65602 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45699 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.65207 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.65207 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 53572.07534 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.01976 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.01976 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.01976 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.01976 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.01976 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.01976 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 10.56982 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.56982 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.56982 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 10.56982 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.56982 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 10.56982 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.65602 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.65602 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.65602 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.65602 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.65602 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.65602 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45699 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45699 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45699 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45699 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.45699 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.45699 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 3.01976 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 10.56982 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.65602 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.45699 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.01976 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.28946 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.01976 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.01976 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.01976 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.01976 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.01976 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.50988 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.01976 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 49987.75037 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 54214.19000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 27107.09500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 54214.19000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76999 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76999 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76999 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76999 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54214.19000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68157.00201 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.01976 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3305.14071 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 68157.00201 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.56982 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.43898 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 10.56982 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 10.56982 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 10.56982 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 10.56982 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 10.56982 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 5.28491 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 10.56982 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 194376.89831 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 209082.31000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 104541.15500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 209082.31000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73867 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73867 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73867 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73867 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 209082.31000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 278797.89891 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 10.56982 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 17922.76861 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 278797.89891 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.65602 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.22982 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.65602 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.65602 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.65602 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.65602 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.65602 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.82801 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.65602 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27611.50019 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29977.35000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14988.67500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29977.35000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76721 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76721 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76721 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76721 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29977.35000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 39333.81591 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.65602 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1812.52647 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 39333.81591 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.45699 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.22982 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.45699 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45699 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45699 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.45699 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.45699 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72850 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.45699 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24993.80443 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 27067.11000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13533.55500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 27067.11000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75860 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75860 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75860 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75860 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27067.11000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35365.96868 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.45699 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1594.68451 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 35365.96868 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 51844.9 | 9.66 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 200777.2 | 12.10 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 28677.9 | 99.75 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 25923.4 | 120.98 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.233 | 8.233 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 1593.79 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | N/A | 5.108 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.61_SHGC_0.25 | N/A | 3.468 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.61_SHGC_0.25 | N/A | 3.468 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.61_SHGC_0.25 | N/A | 3.468 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 6 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 9.0762882122E-002 | 0.3896445449 | Pass | Pass | 5.2384968146E-002 | 0.1567270993 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 6.8793484786E-002 | 0.1279888516 | Pass | Pass | 0.1270495376 | 0.4569003285 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 7.6591738466E-002 | 0.1428334644 | Pass | Pass | 7.6188758511E-002 | 0.2550055959 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 7.6807480833E-002 | 0.1689913583 | Pass | Pass | 0.1955809191 | 1.3471374489 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.2044430517 | 0.5699080810 | Pass | Pass | 6.2506153624E-002 | 0.4181456070 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 1600.48 | 1593.79 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.358 | 0.376 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 5.108 | 0.400 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.61_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.468 | 0.253 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.61_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.468 | 0.253 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.61_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 3.468 | 0.253 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 90.63 | 3.589 | 0.264 | 0.262 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 90.63 | 3.589 | 0.264 | 0.262 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 3.688 | 8.233 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 8.3451 | 379.89 | 3170.22 | LightsWired | BLDG_LIGHT_BACK_SCH | 69.84 | 168.00 | 68.87 | 0.0000 | Y | 40.98 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 17.7333 | 1600.48 | 28381.87 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 363.63 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 17.7333 | 150.81 | 2674.36 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.26 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 17.7333 | 150.81 | 2674.36 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.26 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 13.5608 | 12.00 | 162.73 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 2.08 |
Interior Lighting Total | 16.1568 | 2293.99 | 37063.54 | 475.23 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7322.00 | AstronomicalClock | - | 83.77 | 83.77 | 115.13 | |
Exterior Lighting Total | 7322.00 | 115.13 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 54214.19 | 41744.38 | 12469.81 | 0.77 | 3.30 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 209082.31 | 154442.83 | 54639.48 | 0.74 | 3.23 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29977.35 | 22998.92 | 6978.43 | 0.77 | 3.50 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 27067.11 | 20533.11 | 6534.00 | 0.76 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 51844.9 | 9.66 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 200777.2 | 12.10 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 28677.9 | 99.75 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 25923.4 | 120.98 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 53572.08 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 68157.00 | 0.79 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 278797.90 | 0.79 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 39333.82 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 35365.97 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.57 | 622.50 | 2.65 | 2902.71 | 1094.51 | 1.00 | 1.24 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 3.02 | 3305.14 | 1094.51 | 1.00 | 1.24 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 10.57 | 17922.77 | 1695.65 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.66 | 1812.53 | 1094.51 | 1.00 | 1.31 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.46 | 1594.68 | 1094.51 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 29659.71 | 35591.65 | 93.69 | 2.516 | 3.020 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 23.89 | 23.89 | 0.00745 | 37.58 | 0.00682 | 0.289 | 0.00 |
CORE_RETAIL | 103813.65 | 124576.38 | 77.84 | 8.808 | 10.570 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00755 | 37.88 | 0.00682 | 2.439 | 0.00 |
POINT_OF_SALE | 16265.43 | 19518.52 | 129.42 | 1.380 | 1.656 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 23.89 | 23.89 | 0.00733 | 37.15 | 0.00682 | 0.230 | 0.00 |
FRONT_RETAIL | 14310.53 | 17172.63 | 113.87 | 1.214 | 1.457 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 23.89 | 23.89 | 0.00737 | 37.71 | 0.00682 | 0.230 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.018 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 37.33 | 100.00 | 0.00001 | 38.10 | 0.00682 | 0.018 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 38850.80 | 46620.96 | 122.72 | 1.904 | 2.285 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00794 | -5.20 | 0.00281 | 0.289 | 0.00 |
CORE_RETAIL | 78886.54 | 94663.85 | 59.15 | 3.820 | 4.583 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00790 | -5.20 | 0.00281 | 2.439 | 0.00 |
POINT_OF_SALE | 16956.61 | 20347.94 | 134.92 | 0.832 | 0.998 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00794 | -5.20 | 0.00281 | 0.230 | 0.00 |
FRONT_RETAIL | 17002.77 | 20403.32 | 135.29 | 0.834 | 1.001 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00794 | -5.20 | 0.00281 | 0.230 | 0.00 |
FRONT_ENTRY | 44608.42 | 53530.10 | 4460.84 | 2.210 | 2.652 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.03 | 0.00586 | -5.20 | 0.00281 | 0.018 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 3.02 | 3.02 | 2.28 | 2.28 | 3.0198 | 3.0198 | 3.0198 | 1.0000 | 1.0000 |
PSZ-AC:2 | 10.57 | 10.57 | 4.58 | 4.58 | 10.5698 | 10.5698 | 10.5698 | 1.0000 | 1.0000 |
PSZ-AC:3 | 1.66 | 1.66 | 1.00 | 1.00 | 1.6560 | 1.6560 | 1.6560 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.46 | 1.46 | 1.00 | 1.00 | 1.4570 | 1.4570 | 1.4570 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 53572.075 | 53572.075 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 53572.08 | 53572.08 | 2.652075 | 20.85 | 11.41 | 0.00584092 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.03 | 0.00586197 | 32.9141 | 53530.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 54214.190 | 0.000 | 3.019760 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 54214.19 | 51500.10 | 3.019760 | 25.24 | 14.41 | 0.00739148 | 12.80 | 9.32 | 0.00700000 | 37.97 | 0.00682374 | 18.06 | 9.5855 | 23.89 | 0.00745099 | 35.0787 | 29608.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 68157.002 | 68157.002 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 68157.00 | 68157.00 | 3.019757 | 17.68 | 11.56 | 0.00728684 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 9.5855 | 21.11 | 0.00793648 | 44.2024 | 38850.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 209082.310 | 0.000 | 10.569820 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 209082.31 | 199760.70 | 10.569820 | 27.17 | 15.06 | 0.00738206 | 12.80 | 9.32 | 0.00700000 | 38.10 | 0.00682375 | 18.10 | 23.0750 | 23.89 | 0.00754943 | 35.5370 | 103745.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 278797.899 | 278797.899 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 278797.90 | 278797.90 | 10.569824 | 7.00 | 4.72 | 0.00519228 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 23.0750 | 21.11 | 0.00790363 | 44.0215 | 78886.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 29977.350 | 0.000 | 1.656020 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 29977.35 | 29000.99 | 1.656020 | 25.81 | 14.49 | 0.00725768 | 12.80 | 9.32 | 0.00700000 | 37.71 | 0.00682375 | 17.98 | 13.8779 | 23.89 | 0.00732707 | 34.5019 | 16210.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 39333.816 | 39333.816 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39333.82 | 39333.82 | 1.656023 | 14.97 | 9.98 | 0.00675970 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 13.8778 | 21.11 | 0.00794120 | 44.2283 | 16956.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 27067.110 | 0.000 | 1.456990 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 27067.11 | 26109.15 | 1.456990 | 26.14 | 14.63 | 0.00728550 | 12.80 | 9.32 | 0.00700000 | 38.10 | 0.00682375 | 18.10 | 15.7736 | 23.89 | 0.00737119 | 34.7072 | 14266.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 35365.969 | 35365.969 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35365.97 | 35365.97 | 1.456991 | 14.99 | 9.99 | 0.00676315 | 40.00 | 19.50 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.7736 | 21.11 | 0.00794148 | 44.2298 | 17002.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 53572.075 | 53572.075 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 2.652075 | 2.76964576 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 53572.08 | 53572.08 | 1.0000 | 2.76964576 | 2.652075 | 20.85 | 11.41 | 0.00584092 | 35785.5 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53572.08 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.05 | 0.00586197 | 21.03 | 0.00586197 | 32.9141 | 53530.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 54214.190 | 0.000 | 3.019760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5804 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 54214.19 | 51500.10 | 1.0000 | 3.15363119 | 3.019760 | 25.24 | 14.41 | 0.00739148 | 44194.8 | 12.80 | 9.32 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54214.19 | 37.97 | 0.00682374 | 18.06 | 0.28945795 | 9.5855 | 23.89 | 0.00745178 | 23.89 | 0.00745099 | 35.0787 | 29608.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68157.002 | 68157.002 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.019757 | 3.15362813 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 68157.00 | 68157.00 | 1.0000 | 3.15362813 | 3.019757 | 17.68 | 11.56 | 0.00728684 | 36233.5 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68157.00 | -5.20 | 0.00280840 | -5.20 | 0.28945795 | 9.5855 | 21.00 | 0.00793648 | 21.11 | 0.00793648 | 44.2024 | 38850.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 209082.310 | 0.000 | 10.569820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5629 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 209082.31 | 199760.70 | 1.0000 | 11.03839842 | 10.569820 | 27.17 | 15.06 | 0.00738206 | 46135.8 | 12.80 | 9.32 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 209082.31 | 38.10 | 0.00682375 | 18.10 | 2.43898389 | 23.0750 | 23.89 | 0.00754968 | 23.89 | 0.00754943 | 35.5370 | 103745.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 278797.899 | 278797.899 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 10.569824 | 11.03840298 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 278797.90 | 278797.90 | 1.0000 | 11.03840298 | 10.569824 | 7.00 | 4.72 | 0.00519228 | 20090.8 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 278797.90 | -5.20 | 0.00280840 | -5.20 | 2.43898389 | 23.0750 | 20.88 | 0.00790363 | 21.11 | 0.00790363 | 44.0215 | 78886.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29977.350 | 0.000 | 1.656020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3317 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 29977.35 | 29000.99 | 1.0000 | 1.72943423 | 1.656020 | 25.81 | 14.49 | 0.00725768 | 44437.0 | 12.80 | 9.32 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29977.35 | 37.71 | 0.00682375 | 17.98 | 0.22982011 | 13.8779 | 23.89 | 0.00732788 | 23.89 | 0.00732707 | 34.5019 | 16210.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39333.816 | 39333.816 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.656023 | 1.72943756 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39333.82 | 39333.82 | 1.0000 | 1.72943756 | 1.656023 | 14.97 | 9.98 | 0.00675970 | 32137.3 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39333.82 | -5.20 | 0.00280840 | -5.20 | 0.22982011 | 13.8778 | 21.00 | 0.00794120 | 21.11 | 0.00794120 | 44.2283 | 16956.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27067.110 | 0.000 | 1.456990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3834 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 27067.11 | 26109.15 | 1.0000 | 1.52158089 | 1.456990 | 26.14 | 14.63 | 0.00728550 | 44837.8 | 12.80 | 9.32 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27067.11 | 38.10 | 0.00682375 | 18.10 | 0.22982011 | 15.7736 | 23.89 | 0.00737229 | 23.89 | 0.00737119 | 34.7072 | 14266.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35365.969 | 35365.969 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.456991 | 1.52158180 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35365.97 | 35365.97 | 1.0000 | 1.52158180 | 1.456991 | 14.99 | 9.99 | 0.00676315 | 32162.8 | 40.00 | 19.50 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35365.97 | -5.20 | 0.00280840 | -5.20 | 0.22982011 | 15.7736 | 21.00 | 0.00794148 | 21.11 | 0.00794148 | 44.2298 | 17002.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.29 | 3.02 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 2.44 | 10.57 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.66 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.46 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3142.33 | 2766.17 | 1364.33 |
CORE_RETAIL | 2418.67 | 2169.17 | 318.17 |
POINT_OF_SALE | 2626.00 | 1850.67 | 360.17 |
FRONT_RETAIL | 2626.50 | 2064.00 | 486.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3659.50 | 2779.50 | 1373.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 36.33 | 11.00 | 0.00 | 0.00 |
CORE_RETAIL | 2.00 | 8.33 | 0.00 | 0.00 |
POINT_OF_SALE | 11.00 | 17.00 | 0.00 | 0.00 |
FRONT_RETAIL | 15.33 | 11.50 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 38.33 | 20.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.50 | 61.34 | 2317.33 | 0.856 | 0.048 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 1.347 | 0.009 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 1.902 | 0.053 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 1.612 | 0.053 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.50 | 61.34 | 2317.33 | 0.444 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.48 | 258.43 | 9762.95 | 0.888 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.11 | 24.35 | 919.94 | 0.891 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.11 | 24.35 | 919.94 | 0.889 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1678.51 | 3648.35 | 12-FEB-07:00 | 147666.48 | 15-JUN-15:00 |
Electricity:Building | 670.39 | 3648.35 | 01-JAN-00:10 | 44155.79 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 90.98 | 618.37 | 01-JAN-00:10 | 5639.90 | 02-JAN-09:10 |
InteriorLights:Electricity | 475.23 | 1853.18 | 01-JAN-00:10 | 33384.75 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 40.98 | 158.51 | 01-JAN-00:10 | 2880.76 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 475.23 | 1853.18 | 01-JAN-00:10 | 33384.75 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 447.93 | 2194.53 | 01-JAN-00:10 | 30196.29 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 363.63 | 1419.09 | 01-JAN-00:10 | 25543.68 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 87.19 | 620.53 | 01-JAN-00:10 | 5327.81 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.26 | 133.72 | 01-JAN-00:10 | 2406.93 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 42.21 | 206.79 | 01-JAN-00:10 | 2845.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.26 | 133.72 | 01-JAN-00:10 | 2406.93 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 2.08 | 8.14 | 01-JAN-00:10 | 146.46 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 2.08 | 8.14 | 01-JAN-00:10 | 146.46 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1678.51 | 3648.35 | 19-MAR-18:10 | 147666.48 | 15-JUN-15:00 |
ElectricityPurchased:Plant | 1678.51 | 3648.35 | 19-MAR-18:10 | 147666.48 | 15-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1678.51 | 3648.35 | 19-MAR-18:10 | 147666.48 | 15-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1678.51 | 3648.35 | 19-MAR-18:10 | 147666.48 | 15-JUN-15:00 |
ElectricityNet:Plant | 1678.51 | 3648.35 | 19-MAR-18:10 | 147666.48 | 15-JUN-15:00 |
Cogeneration:ElectricityNet | 1678.51 | 3648.35 | 19-MAR-18:10 | 147666.48 | 15-JUN-15:00 |
Electricity:HVAC | 892.99 | 0.00 | 01-JAN-00:10 | 103510.69 | 15-JUN-15:00 |
Fans:Electricity | 493.01 | 0.00 | 01-JAN-00:10 | 27537.83 | 15-JAN-14:20 |
General:Fans:Electricity | 493.01 | 0.00 | 01-JAN-00:10 | 27537.83 | 15-JAN-14:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 399.98 | 0.00 | 01-JAN-00:10 | 78875.57 | 15-JUN-15:00 |
ExteriorLights:Electricity | 115.13 | 0.00 | 01-JAN-07:20 | 7322.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 115.13 | 0.00 | 01-JAN-07:20 | 7322.00 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 230.24 | 1862.00 | 01-JAN-20:10 | 197113.58 | 28-DEC-05:10 |
Gas:Plant | 90.41 | 1862.00 | 01-JAN-20:10 | 5020.90 | 31-JAN-12:10 |
WaterSystems:Gas | 90.41 | 1862.00 | 01-JAN-20:10 | 5020.90 | 31-JAN-12:10 |
Water Heater:WaterSystems:Gas | 90.41 | 1862.00 | 01-JAN-20:10 | 5020.90 | 31-JAN-12:10 |
Gas:HVAC | 139.84 | 0.00 | 01-JAN-00:10 | 195251.58 | 28-DEC-05:10 |
Heating:Gas | 139.84 | 0.00 | 01-JAN-00:10 | 195251.58 | 28-DEC-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 10-NOV-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2388.77 | 0.00 | 01-JAN-00:10 | 354551.80 | 26-JUL-14:30 |
EnergyTransfer:Building | 1046.53 | 0.00 | 01-JAN-00:10 | 158998.11 | 13-JUN-04:20 |
EnergyTransfer:Zone:BACK_SPACE | 172.92 | 0.00 | 01-JAN-00:10 | 45700.38 | 27-DEC-05:20 |
Heating:EnergyTransfer | 114.39 | 0.00 | 01-JAN-00:10 | 158341.95 | 28-DEC-05:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 44.58 | 0.00 | 01-JAN-00:10 | 45700.38 | 27-DEC-05:20 |
Cooling:EnergyTransfer | 932.14 | 0.00 | 01-JAN-00:10 | 154841.34 | 13-JUN-04:20 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 128.34 | 0.00 | 01-JAN-00:10 | 32586.11 | 03-JUL-04:10 |
EnergyTransfer:Zone:CORE_RETAIL | 628.72 | 0.00 | 01-JAN-00:10 | 130518.90 | 03-APR-05:00 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 18.99 | 0.00 | 01-JAN-00:10 | 90483.40 | 27-DEC-05:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 609.73 | 0.00 | 01-JAN-00:10 | 112149.41 | 01-MAY-04:50 |
EnergyTransfer:Zone:POINT_OF_SALE | 113.84 | 0.00 | 01-JAN-00:10 | 17755.95 | 13-JUN-04:20 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 3.88 | 0.00 | 01-JAN-00:10 | 17514.87 | 27-DEC-05:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 109.97 | 0.00 | 01-JAN-00:10 | 15296.81 | 13-JUN-04:20 |
EnergyTransfer:Zone:FRONT_RETAIL | 90.16 | 0.00 | 01-JAN-00:10 | 18044.61 | 27-DEC-05:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 6.05 | 0.00 | 01-JAN-00:10 | 18044.61 | 27-DEC-05:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 84.11 | 0.00 | 01-JAN-00:10 | 13424.55 | 05-OCT-14:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 40.90 | 0.00 | 01-JAN-00:10 | 32358.70 | 26-DEC-12:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 40.90 | 0.00 | 01-JAN-00:10 | 32358.70 | 26-DEC-12:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 2.49 | 29-NOV-05:10 |
EnergyTransfer:HVAC | 1342.24 | 0.00 | 01-JAN-00:10 | 222526.90 | 26-JUL-14:20 |
HeatingCoils:EnergyTransfer | 111.16 | 0.00 | 01-JAN-00:10 | 155002.79 | 28-DEC-05:10 |
CoolingCoils:EnergyTransfer | 1231.08 | 0.00 | 01-JAN-00:10 | 222526.90 | 26-JUL-14:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 44.577 | -128.337 | 0.000 | 0.000 | 38.581 | 40.985 | 49.992 | 0.000 | 0.000 | 1.501 | 0.001 | 0.000 | 0.000 | 0.000 | -12.431 | -34.867 |
CORE_RETAIL | 0.000 | 0.000 | 18.988 | -609.721 | 0.000 | 0.000 | 158.344 | 363.635 | 84.299 | 16.784 | 0.000 | 1.284 | 0.007 | 0.000 | -6.765 | 0.000 | -12.052 | -14.795 |
POINT_OF_SALE | 0.000 | 0.000 | 3.875 | -109.965 | 0.000 | 0.000 | 14.771 | 34.265 | 52.922 | 34.103 | 0.000 | 0.625 | 0.006 | 0.000 | -19.910 | 0.000 | -6.537 | -4.150 |
FRONT_RETAIL | 0.000 | 0.000 | 6.051 | -84.104 | 0.000 | 0.000 | 14.920 | 34.265 | 7.943 | 34.139 | 0.000 | 0.641 | 11.412 | 0.000 | -19.114 | 0.000 | -6.153 | -0.000 |
FRONT_ENTRY | 40.897 | -0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.085 | 0.000 | 6.564 | 0.000 | 1.210 | 0.000 | 0.000 | -3.981 | 0.000 | -45.386 | -1.388 |
Total Facility | 40.897 | -0.000 | 73.492 | -932.126 | 0.000 | 0.000 | 226.616 | 475.233 | 195.156 | 91.589 | 0.000 | 5.261 | 11.427 | 0.000 | -49.772 | 0.000 | -82.559 | -55.201 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 21-MAY-06:02 | 0.00 | 0.00 | 0.00 | -68718.97 | 0.00 | 0.00 | 0.00 | 158.51 | 459.86 | 0.00 | 0.00 | 0.00 | 68960.61 | 0.00 | -0.00 | 0.00 | -860.01 | 0.00 |
CORE_RETAIL | 22-APR-04:03 | 0.00 | 0.00 | 0.00 | -268255.34 | 0.00 | 0.00 | 0.00 | 1419.09 | 775.43 | 0.00 | 0.00 | 0.00 | 269287.54 | 0.00 | -557.43 | 0.00 | -2669.30 | 0.00 |
POINT_OF_SALE | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | -39118.55 | 0.00 | 0.00 | 0.00 | 133.72 | 486.81 | 0.00 | 0.00 | 0.00 | 40306.09 | 0.00 | -1758.19 | 0.00 | -49.89 | 0.00 |
FRONT_RETAIL | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | -34356.87 | 0.00 | 0.00 | 0.00 | 133.72 | 73.07 | 0.00 | 0.00 | 0.00 | 35907.77 | 0.00 | -1709.18 | 0.00 | -48.50 | 0.00 |
FRONT_ENTRY | 29-NOV-05:02 | 0.00 | -24.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 242.18 | 0.00 | -190.52 | 0.00 | -34.94 | 0.00 |
Total Facility | 13-JUN-04:01 | 0.00 | 0.00 | 0.00 | -386465.48 | 0.00 | 0.00 | 0.00 | 1853.18 | 2393.56 | 0.00 | 0.00 | 0.00 | 387295.90 | 0.00 | -3382.64 | 0.00 | -1694.52 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 27-DEC-05:11 | 0.00 | 0.00 | 69882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 158.51 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -587.72 | -70066.73 |
CORE_RETAIL | 27-DEC-05:41 | 0.00 | 0.00 | 292536.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1419.09 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -697.22 | 0.00 | -1491.50 | -292800.86 |
POINT_OF_SALE | 27-DEC-05:41 | 0.00 | 0.00 | 41001.81 | 0.00 | 0.00 | 0.00 | 0.00 | 133.72 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2183.40 | 0.00 | -737.13 | -38864.09 |
FRONT_RETAIL | 27-DEC-05:41 | 0.00 | 0.00 | 37243.82 | 0.00 | 0.00 | 0.00 | 0.00 | 133.72 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2160.90 | 0.00 | -722.30 | -34591.76 |
FRONT_ENTRY | 26-DEC-12:10 | 32355.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.46 | 0.00 | 391.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -31968.47 | -925.03 |
Total Facility | 04-DEC-05:01 | 6598.68 | 0.00 | 430164.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.18 | 2393.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4525.16 | 0.00 | -434.89 | -436049.88 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 3.0198 | 0.0000 | 61.3418 | 1.0000 | 0.2895 | 3.0198 | 0.0959 | 1.0000 | 0.2895 | 0.0959 | ||
PSZ-AC:2 | 10.5698 | 0.0000 | 258.4342 | 1.0000 | 2.4390 | 10.5698 | 0.2307 | 1.0000 | 2.4390 | 0.2307 | ||
PSZ-AC:3 | 1.6560 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 1.6560 | 0.1388 | 1.0000 | 0.2298 | 0.1388 | ||
PSZ-AC:4 | 1.4570 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 1.4570 | 0.1577 | 1.0000 | 0.2298 | 0.1577 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 3.0198 | 0.0000 | 61.3418 | 1.0000 | 0.2895 | 3.0198 | 1.0000 | 1.0000 | 0.2895 | 0.0959 | ||
PSZ-AC:2 | 10.5698 | 0.0000 | 258.4342 | 1.0000 | 2.4390 | 10.5698 | 1.0000 | 1.0000 | 2.4390 | 0.2307 | ||
PSZ-AC:3 | 1.6560 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 1.6560 | 1.0000 | 1.0000 | 0.2298 | 0.1388 | ||
PSZ-AC:4 | 1.4570 | 0.0000 | 24.3517 | 1.0000 | 0.2298 | 1.4570 | 1.0000 | 1.0000 | 0.2298 | 0.1577 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000762 | 379.89 | 0.2895 | 1.0000 | 0.2895 | 1.000 | 0.2895 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001524 | 1600.48 | 2.4390 | 1.0000 | 2.4390 | 1.000 | 2.4390 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001524 | 150.81 | 0.2298 | 1.0000 | 0.2298 | 1.000 | 0.2298 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001524 | 150.81 | 0.2298 | 1.0000 | 0.2298 | 1.000 | 0.2298 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000762 | 379.8900 | 0.2895 | 0.2895 | 0.2895 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001524 | 1600.4829 | 2.4390 | 2.4390 | 2.4390 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001524 | 150.8100 | 0.2298 | 0.2298 | 0.2298 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001524 | 150.8100 | 0.2298 | 0.2298 | 0.2298 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 3.0198 | 3.0198 | 3.0198 | 0.2895 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 10.5698 | 10.5698 | 10.5698 | 2.4390 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.6560 | 1.6560 | 1.6560 | 0.2298 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.4570 | 1.4570 | 1.4570 | 0.2298 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 3.0198 | 3.0198 | 3.0198 | 3.0198 | 0.2895 | 1.0000 |
PSZ-AC:2 | 10.5698 | 10.5698 | 10.5698 | 10.5698 | 2.4390 | 1.0000 |
PSZ-AC:3 | 1.6560 | 1.6560 | 1.6560 | 1.6560 | 0.2298 | 1.0000 |
PSZ-AC:4 | 1.4570 | 1.4570 | 1.4570 | 1.4570 | 0.2298 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 3.0198 | 3.0198 | 3.0198 | 0.2895 | 0.1267 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 10.5698 | 10.5698 | 10.5698 | 2.4390 | 0.5321 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.6560 | 1.6560 | 1.6560 | 0.2298 | 0.2302 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.4570 | 1.4570 | 1.4570 | 0.2298 | 0.2296 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 3.0198 | 3.0198 | 3.0198 | 3.0198 | 0.2895 | 1.0000 |
PSZ-AC:2 | 10.5698 | 10.5698 | 10.5698 | 10.5698 | 2.4390 | 1.0000 |
PSZ-AC:3 | 1.6560 | 1.6560 | 1.6560 | 1.6560 | 0.2298 | 1.0000 |
PSZ-AC:4 | 1.4570 | 1.4570 | 1.4570 | 1.4570 | 0.2298 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:31
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 139.84 | 195251.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 399.98 | 78875.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 475.23 | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 115.13 | 7322.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 493.01 | 27537.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 90.41 | 5020.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1678.51 |
Natural Gas | 0.00 | 230.24 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1908.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 207.16 |
Space Heating | 0.00 |
Space Cooling | 174.36 |
Fans (All) | 214.91 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 731.70 |
Subtotal | 731.70 |
Natural Gas [MJ/m2] | |
Space Heating | 60.96 |
Service Water Heating | 39.41 |
Miscellaneous (All) | 100.37 |
Subtotal | 100.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.90 |
Space Heating | 7.33 |
Space Cooling | 20.96 |
Fans (All) | 25.83 |
Service Water Heating | 4.74 |
Receptacle Equipment | 10.22 |
Miscellaneous | 6.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3641. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.400220E+11 |
February | 0.000 | 0.211468E+11 |
March | 0.000 | 0.103947E+11 |
April | 0.000 | 0.848681E+09 |
May | 0.000 | 0.341506E+08 |
June | 0.000 | 5606169.043 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 3367494.819 |
October | 0.000 | 0.452813E+09 |
November | 0.000 | 0.144014E+11 |
December | 0.000 | 0.525262E+11 |
Annual Sum or Average | 0.139836E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.525262E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60542.47 | 117.34 | 04-JAN-18:05 | 9.82 | 2.03 | 0.168166E+10 | 2285.22 | 12-JAN-15:00 | 18.90 | 10.15 |
February | 18208907.68 | 1392.62 | 08-FEB-19:00 | 5.00 | 0.51 | 0.163886E+10 | 2451.27 | 22-FEB-15:20 | 22.40 | 8.14 |
March | 0.435965E+09 | 5204.16 | 16-MAR-15:00 | 22.80 | 8.68 | 0.205886E+10 | 2451.27 | 04-MAR-15:00 | 18.90 | 8.32 |
April | 0.713928E+10 | 55929.54 | 20-APR-04:01 | 20.00 | 9.58 | 0.213301E+10 | 2451.35 | 29-APR-13:09 | 28.17 | 15.27 |
May | 0.177499E+11 | 68732.76 | 21-MAY-06:02 | 13.13 | 4.10 | 0.223216E+10 | 2451.39 | 27-MAY-10:39 | 27.07 | 15.24 |
June | 0.274456E+11 | 67606.32 | 13-JUN-04:01 | 16.83 | 5.66 | 0.220164E+10 | 2451.48 | 03-JUN-10:09 | 30.28 | 18.19 |
July | 0.276770E+11 | 51638.94 | 11-JUL-04:01 | 23.03 | 15.41 | 0.218730E+10 | 2451.70 | 08-JUL-14:39 | 22.80 | 19.37 |
August | 0.238981E+11 | 59083.74 | 23-AUG-04:01 | 20.00 | 11.86 | 0.228105E+10 | 2451.42 | 09-AUG-14:09 | 32.30 | 18.79 |
September | 0.172353E+11 | 58741.37 | 12-SEP-04:01 | 16.52 | 10.93 | 0.215612E+10 | 2451.43 | 23-SEP-15:39 | 22.37 | 18.91 |
October | 0.637863E+10 | 51119.20 | 06-OCT-04:01 | 13.80 | 12.43 | 0.216099E+10 | 2451.35 | 28-OCT-15:20 | 23.90 | 13.82 |
November | 0.361419E+09 | 5107.93 | 10-NOV-15:10 | 15.50 | 10.15 | 0.182845E+10 | 2451.26 | 03-NOV-14:30 | 23.05 | 13.54 |
December | 29938.45 | 49.90 | 01-DEC-17:50 | 9.60 | 4.15 | 0.167654E+10 | 2190.74 | 09-DEC-16:10 | 16.42 | 6.47 |
Annual Sum or Average | 0.128340E+12 | 0.242366E+11 | ||||||||
Minimum of Months | 29938.45 | 49.90 | 5.00 | 0.51 | 0.163886E+10 | 2190.74 | 16.42 | 6.47 | ||
Maximum of Months | 0.276770E+11 | 68732.76 | 23.03 | 15.41 | 0.228105E+10 | 2451.70 | 32.30 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137003E+11 | 33458.31 | 05-JAN-07:05 | -0.9 | -5.2 | 0.805176E+10 | 10327.06 | 10-JAN-15:09 | 16.70 | 5.80 |
February | 0.162006E+11 | 37579.20 | 16-FEB-07:03 | -1.5 | -2.5 | 0.781667E+10 | 10327.10 | 23-FEB-15:00 | 18.90 | 7.08 |
March | 0.281309E+11 | 41468.03 | 16-MAR-15:00 | 22.80 | 8.68 | 0.929877E+10 | 10327.14 | 04-MAR-11:39 | 16.27 | 7.74 |
April | 0.519434E+11 | 268253.11 | 22-APR-04:03 | 9.82 | 4.28 | 0.905794E+10 | 10327.45 | 29-APR-11:50 | 26.93 | 15.11 |
May | 0.749889E+11 | 259746.67 | 21-MAY-06:02 | 13.13 | 4.10 | 0.940500E+10 | 10327.48 | 27-MAY-10:50 | 27.43 | 15.32 |
June | 0.917440E+11 | 249440.90 | 13-JUN-04:01 | 16.83 | 5.66 | 0.927527E+10 | 10327.34 | 20-JUN-14:09 | 33.68 | 18.26 |
July | 0.907054E+11 | 184921.91 | 11-JUL-04:01 | 23.03 | 15.41 | 0.921491E+10 | 10328.27 | 08-JUL-14:39 | 22.80 | 19.37 |
August | 0.864793E+11 | 217674.12 | 23-AUG-04:01 | 20.00 | 11.86 | 0.960989E+10 | 10327.62 | 25-AUG-14:09 | 30.78 | 16.97 |
September | 0.734172E+11 | 253123.39 | 30-SEP-04:01 | 10.50 | 6.64 | 0.908424E+10 | 10327.72 | 12-SEP-14:00 | 32.20 | 17.93 |
October | 0.475411E+11 | 232840.65 | 20-OCT-04:02 | 13.95 | 8.17 | 0.917902E+10 | 10327.40 | 14-OCT-13:39 | 19.03 | 15.22 |
November | 0.224450E+11 | 41310.17 | 10-NOV-15:10 | 15.50 | 10.15 | 0.841137E+10 | 10327.06 | 18-NOV-11:09 | 17.38 | 5.73 |
December | 0.124331E+11 | 30153.17 | 12-DEC-07:03 | 1.10 | -2.3 | 0.790252E+10 | 10327.12 | 09-DEC-11:00 | 16.10 | 6.91 |
Annual Sum or Average | 0.609729E+12 | 0.106307E+12 | ||||||||
Minimum of Months | 0.124331E+11 | 30153.17 | -1.5 | -5.2 | 0.781667E+10 | 10327.06 | 16.10 | 5.73 | ||
Maximum of Months | 0.917440E+11 | 268253.11 | 23.03 | 15.41 | 0.960989E+10 | 10328.27 | 33.68 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354159E+10 | 8273.82 | 12-JAN-15:30 | 18.90 | 10.07 | 0.811150E+09 | 973.08 | 28-JAN-15:20 | 12.57 | 5.17 |
February | 0.369020E+10 | 8403.53 | 21-FEB-16:00 | 22.80 | 8.13 | 0.757125E+09 | 973.11 | 23-FEB-15:00 | 18.90 | 7.08 |
March | 0.469240E+10 | 8455.73 | 16-MAR-15:00 | 22.80 | 8.68 | 0.877937E+09 | 973.10 | 04-MAR-11:39 | 16.27 | 7.74 |
April | 0.769209E+10 | 35808.28 | 04-APR-04:03 | 13.40 | 4.44 | 0.851332E+09 | 973.18 | 29-APR-10:39 | 25.03 | 14.58 |
May | 0.108341E+11 | 37100.00 | 21-MAY-06:02 | 13.13 | 4.10 | 0.886134E+09 | 973.20 | 18-MAY-14:09 | 30.78 | 17.60 |
June | 0.141910E+11 | 36989.97 | 13-JUN-04:01 | 16.83 | 5.66 | 0.874009E+09 | 973.23 | 03-JUN-11:09 | 31.88 | 18.70 |
July | 0.147568E+11 | 28672.88 | 11-JUL-04:01 | 23.03 | 15.41 | 0.868323E+09 | 973.32 | 08-JUL-14:39 | 22.80 | 19.37 |
August | 0.150385E+11 | 33542.13 | 23-AUG-04:01 | 20.00 | 11.86 | 0.905544E+09 | 973.23 | 31-AUG-14:09 | 28.30 | 17.66 |
September | 0.146489E+11 | 39121.54 | 30-SEP-04:01 | 10.50 | 6.64 | 0.856045E+09 | 973.24 | 23-SEP-14:39 | 28.30 | 18.21 |
October | 0.111314E+11 | 35662.08 | 20-OCT-04:02 | 13.95 | 8.17 | 0.865556E+09 | 973.23 | 02-OCT-14:09 | 26.70 | 16.67 |
November | 0.656202E+10 | 12082.91 | 09-NOV-15:10 | 23.30 | 12.68 | 0.805716E+09 | 973.16 | 10-NOV-15:09 | 15.50 | 10.15 |
December | 0.318778E+10 | 7041.29 | 16-DEC-15:30 | 15.00 | 4.15 | 0.807879E+09 | 973.10 | 23-DEC-12:20 | 13.87 | 5.00 |
Annual Sum or Average | 0.109967E+12 | 0.101667E+11 | ||||||||
Minimum of Months | 0.318778E+10 | 7041.29 | 10.50 | 4.10 | 0.757125E+09 | 973.08 | 12.57 | 5.00 | ||
Maximum of Months | 0.150385E+11 | 39121.54 | 23.30 | 15.41 | 0.905544E+09 | 973.32 | 31.88 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207678E+10 | 6224.59 | 12-JAN-15:30 | 18.90 | 10.07 | 0.776909E+09 | 973.10 | 09-JAN-15:09 | 15.78 | 5.77 |
February | 0.231280E+10 | 6618.63 | 21-FEB-16:00 | 22.80 | 8.13 | 0.728614E+09 | 973.10 | 23-FEB-15:50 | 19.27 | 7.10 |
March | 0.283071E+10 | 6671.94 | 16-MAR-15:00 | 22.80 | 8.68 | 0.854286E+09 | 973.10 | 03-MAR-15:09 | 22.30 | 9.41 |
April | 0.549360E+10 | 30002.92 | 28-APR-04:01 | 15.82 | 10.02 | 0.846147E+09 | 973.16 | 29-APR-11:30 | 26.40 | 14.94 |
May | 0.834137E+10 | 32522.04 | 01-MAY-04:01 | 15.40 | 5.53 | 0.885612E+09 | 973.17 | 18-MAY-14:00 | 31.70 | 17.61 |
June | 0.116571E+11 | 32491.36 | 13-JUN-04:01 | 16.83 | 5.66 | 0.874005E+09 | 973.20 | 03-JUN-12:50 | 34.13 | 19.65 |
July | 0.121350E+11 | 24702.84 | 11-JUL-04:01 | 23.03 | 15.41 | 0.868319E+09 | 973.27 | 08-JUL-14:39 | 22.80 | 19.37 |
August | 0.123370E+11 | 29152.22 | 23-AUG-04:01 | 20.00 | 11.86 | 0.905524E+09 | 973.20 | 09-AUG-14:09 | 32.30 | 18.79 |
September | 0.120251E+11 | 34359.75 | 30-SEP-04:01 | 10.50 | 6.64 | 0.855921E+09 | 973.20 | 16-SEP-14:09 | 31.28 | 18.98 |
October | 0.850207E+10 | 31304.21 | 20-OCT-04:02 | 13.95 | 8.17 | 0.861162E+09 | 973.19 | 03-OCT-14:30 | 32.25 | 19.35 |
November | 0.453617E+10 | 10403.44 | 09-NOV-15:10 | 23.30 | 12.68 | 0.789939E+09 | 973.15 | 10-NOV-15:09 | 15.50 | 10.15 |
December | 0.185779E+10 | 5035.84 | 16-DEC-15:30 | 15.00 | 4.15 | 0.770673E+09 | 973.10 | 09-DEC-11:00 | 16.10 | 6.91 |
Annual Sum or Average | 0.841056E+11 | 0.100171E+11 | ||||||||
Minimum of Months | 0.185779E+10 | 5035.84 | 10.50 | 4.15 | 0.728614E+09 | 973.10 | 15.50 | 5.77 | ||
Maximum of Months | 0.123370E+11 | 34359.75 | 23.30 | 15.41 | 0.905524E+09 | 973.27 | 34.13 | 19.65 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1134.79 | 17.03 | 17-JAN-05:02 | 5.40 | 3.70 | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 | 3.91 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 | 1.83 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 | 2.39 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 | 0.00 | 0.00 | 01-APR-00:10 | 11.18 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 | 8.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 | 11.53 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 | 17.05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 | 18.10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 | 17.17 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 | 8.65 |
November | 1491.33 | 24.86 | 29-NOV-05:02 | 8.30 | 3.94 | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 | 5.63 |
December | 1269.54 | 21.16 | 03-DEC-07:02 | 2.80 | 1.35 | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 | 5.45 |
Annual Sum or Average | 3895.66 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 2.80 | 1.35 | 0.00 | 0.00 | 6.42 | 1.83 | ||
Maximum of Months | 1491.33 | 24.86 | 27.63 | 18.10 | 0.00 | 0.00 | 27.63 | 18.10 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118901E+11 | 69295.46 | 10-JAN-05:12 | 1.13 |
February | 0.761690E+10 | 69691.56 | 02-FEB-05:11 | -2.6 |
March | 0.451185E+10 | 69412.11 | 02-MAR-05:11 | -3.9 |
April | 0.549554E+09 | 67040.54 | 11-APR-04:02 | 5.50 |
May | 67770216.16 | 3796.13 | 14-MAY-06:20 | 20.17 |
June | 7031670.38 | 5610.59 | 23-JUN-05:05 | 19.60 |
July | 1710130.22 | 2319.96 | 23-JUL-07:02 | 23.40 |
August | 15396867.14 | 6879.56 | 14-AUG-05:05 | 17.30 |
September | 32488235.44 | 3551.85 | 29-SEP-05:05 | 16.73 |
October | 0.441661E+09 | 11685.32 | 14-OCT-05:02 | 13.30 |
November | 0.538385E+10 | 69438.37 | 28-NOV-05:12 | -0.0 |
December | 0.140588E+11 | 69882.47 | 27-DEC-05:11 | -3.7 |
Annual Sum or Average | 0.445771E+11 | |||
Minimum of Months | 1710130.22 | 2319.96 | -3.9 | |
Maximum of Months | 0.140588E+11 | 69882.47 | 23.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505584E+10 | 286987.99 | 10-JAN-05:01 | 0.87 |
February | 0.268271E+10 | 287028.02 | 02-FEB-05:01 | -2.4 |
March | 0.184842E+10 | 287011.25 | 02-MAR-05:01 | -3.9 |
April | 0.318939E+09 | 57427.06 | 03-APR-05:00 | 17.20 |
May | 0.101447E+09 | 33134.85 | 12-MAY-04:50 | 14.32 |
June | 57574035.54 | 25942.18 | 23-JUN-05:05 | 19.60 |
July | 15288266.75 | 21809.10 | 19-JUL-05:05 | 20.10 |
August | 55704613.06 | 27226.10 | 26-AUG-05:05 | 19.78 |
September | 95594632.96 | 34282.26 | 12-SEP-05:05 | 15.13 |
October | 0.171447E+09 | 19426.28 | 01-OCT-07:02 | 15.05 |
November | 0.209845E+10 | 287006.57 | 28-NOV-05:01 | -0.3 |
December | 0.648715E+10 | 292535.99 | 27-DEC-05:41 | -3.4 |
Annual Sum or Average | 0.189886E+11 | |||
Minimum of Months | 15288266.75 | 19426.28 | -3.9 | |
Maximum of Months | 0.648715E+10 | 292535.99 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.987930E+09 | 38996.59 | 10-JAN-05:01 | 0.87 |
February | 0.672761E+09 | 39009.82 | 02-FEB-05:01 | -2.4 |
March | 0.416360E+09 | 39006.28 | 02-MAR-05:01 | -3.9 |
April | 84521606.82 | 20280.86 | 11-APR-04:02 | 5.50 |
May | 18583446.33 | 6182.98 | 16-MAY-04:20 | 18.87 |
June | 5475411.95 | 6727.21 | 11-JUN-06:20 | 19.83 |
July | 1066998.53 | 1296.70 | 21-JUL-05:25 | 20.60 |
August | 2674635.70 | 3177.09 | 12-AUG-05:05 | 19.82 |
September | 4500070.81 | 6114.53 | 26-SEP-04:50 | 17.80 |
October | 37934543.89 | 2186.91 | 30-OCT-05:02 | 11.05 |
November | 0.398430E+09 | 39013.08 | 28-NOV-05:01 | -0.3 |
December | 0.124519E+10 | 41001.57 | 27-DEC-05:41 | -3.4 |
Annual Sum or Average | 0.387543E+10 | |||
Minimum of Months | 1066998.53 | 1296.70 | -3.9 | |
Maximum of Months | 0.124519E+10 | 41001.57 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157198E+10 | 35456.77 | 28-JAN-05:42 | -3.2 |
February | 0.101332E+10 | 35267.47 | 02-FEB-05:01 | -2.4 |
March | 0.686485E+09 | 35265.86 | 02-MAR-05:01 | -3.9 |
April | 0.132931E+09 | 28032.78 | 11-APR-04:02 | 5.50 |
May | 35535981.29 | 6654.73 | 14-MAY-06:20 | 20.17 |
June | 1454182.47 | 1342.30 | 04-JUN-07:13 | 22.43 |
July | 260601.68 | 1109.40 | 23-JUL-07:02 | 23.40 |
August | 8128718.31 | 3043.29 | 26-AUG-05:05 | 19.78 |
September | 3786177.34 | 1776.38 | 27-SEP-05:03 | 12.02 |
October | 62144494.67 | 1805.04 | 01-OCT-07:02 | 15.05 |
November | 0.631666E+09 | 35269.67 | 28-NOV-05:01 | -0.3 |
December | 0.190324E+10 | 37243.61 | 27-DEC-05:41 | -3.4 |
Annual Sum or Average | 0.605093E+10 | |||
Minimum of Months | 260601.68 | 1109.40 | -3.9 | |
Maximum of Months | 0.190324E+10 | 37243.61 | 23.40 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102739E+11 | 26829.24 | 26-JAN-12:10 | 3.98 |
February | 0.631737E+10 | 22253.85 | 02-FEB-12:10 | 6.88 |
March | 0.451264E+10 | 23454.33 | 01-MAR-18:00 | 6.10 |
April | 0.116865E+10 | 14645.55 | 11-APR-11:05 | 12.07 |
May | 73976493.84 | 3282.52 | 01-MAY-11:10 | 19.40 |
June | 1122183.54 | 1712.26 | 29-JUN-07:06 | 17.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 2651941.51 | 1940.86 | 17-AUG-07:04 | 17.88 |
September | 34955930.56 | 3685.53 | 23-SEP-17:00 | 17.80 |
October | 0.117960E+10 | 13385.97 | 24-OCT-11:04 | 13.07 |
November | 0.585003E+10 | 23999.90 | 27-NOV-12:10 | 6.20 |
December | 0.114819E+11 | 32358.70 | 26-DEC-12:10 | 1.20 |
Annual Sum or Average | 0.408968E+11 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 0.114819E+11 | 32358.70 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.343688E+10 | 2880.76 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.312713E+10 | 2880.76 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.356711E+10 | 2880.76 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.336554E+10 | 2880.76 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.350199E+10 | 2880.76 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.344215E+10 | 2880.76 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.342538E+10 | 2880.76 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.356711E+10 | 2880.76 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.336554E+10 | 2880.76 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.343688E+10 | 2880.76 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.332343E+10 | 2880.76 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.342538E+10 | 2880.76 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.409845E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.312713E+10 | 2880.76 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.356711E+10 | 2880.76 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.304941E+11 | 25543.68 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.277456E+11 | 25543.68 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.316486E+11 | 25543.68 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.298606E+11 | 25543.68 | 01-APR-09:09 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.310713E+11 | 25543.68 | 01-MAY-08:09 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.305400E+11 | 25543.68 | 01-JUN-08:09 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.303919E+11 | 25543.68 | 01-JUL-09:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.316486E+11 | 25543.68 | 01-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.298606E+11 | 25543.68 | 01-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.304941E+11 | 25543.68 | 02-OCT-08:09 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.294876E+11 | 25543.68 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.303919E+11 | 25543.68 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.363635E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.277456E+11 | 25543.68 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.316486E+11 | 25543.68 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.287339E+10 | 2406.93 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.261440E+10 | 2406.93 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.298218E+10 | 2406.93 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.281370E+10 | 2406.93 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.292778E+10 | 2406.93 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.287772E+10 | 2406.93 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.286376E+10 | 2406.93 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.298218E+10 | 2406.93 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.281370E+10 | 2406.93 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.287339E+10 | 2406.93 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.277855E+10 | 2406.93 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.286376E+10 | 2406.93 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.342645E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.261440E+10 | 2406.93 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.298218E+10 | 2406.93 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.287339E+10 | 2406.93 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.261440E+10 | 2406.93 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.298218E+10 | 2406.93 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.281370E+10 | 2406.93 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.292778E+10 | 2406.93 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.287772E+10 | 2406.93 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.286376E+10 | 2406.93 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.298218E+10 | 2406.93 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.281370E+10 | 2406.93 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.287339E+10 | 2406.93 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.277855E+10 | 2406.93 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.286376E+10 | 2406.93 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.342645E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.261440E+10 | 2406.93 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.298218E+10 | 2406.93 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.174840E+09 | 146.46 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.159081E+09 | 146.46 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.181459E+09 | 146.46 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.171207E+09 | 146.46 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.178149E+09 | 146.46 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.175103E+09 | 146.46 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.174254E+09 | 146.46 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.181459E+09 | 146.46 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.171207E+09 | 146.46 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.174840E+09 | 146.46 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.169069E+09 | 146.46 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.174254E+09 | 146.46 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208492E+10 | ||||
Minimum of Months | 0.159081E+09 | 146.46 | 0.00 | 0.00 | |
Maximum of Months | 0.181459E+09 | 146.46 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.343688E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182621E+10 |
February | 0.479114E+10 | 0.312713E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168731E+10 |
March | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 866255.26 | 0.177252E+10 |
April | 0.518069E+10 | 0.336554E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104827E+09 | 0.108328E+10 |
May | 0.536353E+10 | 0.350199E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264085E+09 | 0.701828E+09 |
June | 0.528933E+10 | 0.344215E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426665E+09 | 0.339883E+09 |
July | 0.525489E+10 | 0.342538E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322044E+09 | 0.290753E+09 |
August | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257322E+09 | 0.314633E+09 |
September | 0.518069E+10 | 0.336554E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93269238.72 | 0.334186E+09 |
October | 0.524694E+10 | 0.343688E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32115799.44 | 0.928213E+09 |
November | 0.504819E+10 | 0.332343E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 0.152439E+10 |
December | 0.525489E+10 | 0.342538E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162803E+10 |
Annual Sum or Average | 0.628175E+11 | 0.409845E+11 | 0.499918E+11 | 0.150119E+10 | 0.124312E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.312713E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290753E+09 |
Maximum of Months | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426665E+09 | 0.182621E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.304941E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181345E+10 |
February | 0.201852E+11 | 0.277456E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171196E+10 |
March | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 712516.08 | 0.179228E+10 |
April | 0.218263E+11 | 0.298606E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84819795.71 | 0.105644E+10 |
May | 0.225967E+11 | 0.310713E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221820E+09 | 0.632763E+09 |
June | 0.222841E+11 | 0.305400E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370671E+09 | 0.259803E+09 |
July | 0.221389E+11 | 0.303919E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283977E+09 | 0.215127E+09 |
August | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220241E+09 | 0.262840E+09 |
September | 0.218263E+11 | 0.298606E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76813077.99 | 0.292623E+09 |
October | 0.221054E+11 | 0.304941E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25014980.18 | 0.888390E+09 |
November | 0.212681E+11 | 0.294876E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.153061E+10 |
December | 0.221389E+11 | 0.303919E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159583E+10 |
Annual Sum or Average | 0.264651E+12 | 0.363635E+12 | 0.842987E+11 | 0.128407E+10 | 0.120521E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.277456E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215127E+09 |
Maximum of Months | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370671E+09 | 0.181345E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.287339E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967987E+09 |
February | 0.190200E+10 | 0.261440E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892932E+09 |
March | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 377118.19 | 0.913508E+09 |
April | 0.205665E+10 | 0.281370E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43579544.90 | 0.548037E+09 |
May | 0.212923E+10 | 0.292778E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110591E+09 | 0.344028E+09 |
June | 0.209978E+10 | 0.287772E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179358E+09 | 0.162143E+09 |
July | 0.208610E+10 | 0.286376E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135311E+09 | 0.146487E+09 |
August | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105305E+09 | 0.175960E+09 |
September | 0.205665E+10 | 0.281370E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39561142.88 | 0.190435E+09 |
October | 0.208295E+10 | 0.287339E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11214836.88 | 0.509865E+09 |
November | 0.200405E+10 | 0.277855E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 0.831171E+09 |
December | 0.208610E+10 | 0.286376E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854513E+09 |
Annual Sum or Average | 0.249375E+11 | 0.342645E+11 | 0.529224E+11 | 0.625297E+09 | 0.653707E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.261440E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146487E+09 |
Maximum of Months | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179358E+09 | 0.967987E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.287339E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925985E+09 |
February | 0.190200E+10 | 0.261440E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.852968E+09 |
March | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 377091.44 | 0.871419E+09 |
April | 0.205665E+10 | 0.281370E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43934029.16 | 0.512607E+09 |
May | 0.212923E+10 | 0.292778E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113200E+09 | 0.305145E+09 |
June | 0.209978E+10 | 0.287772E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186185E+09 | 0.136485E+09 |
July | 0.208610E+10 | 0.286376E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139085E+09 | 0.120447E+09 |
August | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107258E+09 | 0.152740E+09 |
September | 0.205665E+10 | 0.281370E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39673601.85 | 0.174503E+09 |
October | 0.208295E+10 | 0.287339E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11250070.64 | 0.482271E+09 |
November | 0.200405E+10 | 0.277855E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.798296E+09 |
December | 0.208610E+10 | 0.286376E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819704E+09 |
Annual Sum or Average | 0.249375E+11 | 0.342645E+11 | 0.794328E+10 | 0.640962E+09 | 0.615257E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.261440E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120447E+09 |
Maximum of Months | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186185E+09 | 0.925985E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.174840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106249E+11 |
February | 0.00 | 0.159081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.671281E+10 |
March | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494391E+10 |
April | 0.00 | 0.171207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34369456.73 | 0.149327E+10 |
May | 0.00 | 0.178149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179834E+09 | 0.259608E+09 |
June | 0.00 | 0.175103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470140E+09 | 0.101235E+09 |
July | 0.00 | 0.174254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322054E+09 | 0.104488E+09 |
August | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180490E+09 | 0.202347E+09 |
September | 0.00 | 0.171207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22286729.75 | 0.398683E+09 |
October | 0.00 | 0.174840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494888.77 | 0.208356E+10 |
November | 0.00 | 0.169069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672007E+10 |
December | 0.00 | 0.174254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117407E+11 |
Annual Sum or Average | 0.00 | 0.208492E+10 | 0.120967E+10 | 0.453856E+11 | |||||
Minimum of Months | 0.00 | 0.159081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101235E+09 |
Maximum of Months | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470140E+09 | 0.117407E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2880.76 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4784.23 | 25-JAN-23:00 |
February | 5888.82 | 01-FEB-15:09 | 2880.76 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8008.50 | 08-FEB-21:03 |
March | 5888.82 | 01-MAR-15:09 | 2880.76 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.23 | 22-MAR-13:00 | 4665.47 | 19-MAR-24:00 |
April | 5888.82 | 01-APR-10:09 | 2880.76 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 946.37 | 21-APR-15:00 | 5847.14 | 10-APR-24:00 |
May | 5888.82 | 01-MAY-14:09 | 2880.76 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2055.90 | 14-MAY-18:02 | 2613.67 | 04-MAY-02:00 |
June | 5888.82 | 01-JUN-14:09 | 2880.76 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2981.46 | 21-JUN-20:02 | 2770.76 | 28-JUN-02:00 |
July | 5888.82 | 01-JUL-10:09 | 2880.76 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2217.30 | 02-JUL-18:01 | 1696.09 | 18-JUL-21:00 |
August | 5888.82 | 01-AUG-14:09 | 2880.76 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.91 | 06-AUG-18:01 | 2197.72 | 14-AUG-01:00 |
September | 5888.82 | 01-SEP-14:09 | 2880.76 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 741.47 | 10-SEP-18:02 | 1093.49 | 24-SEP-06:55 |
October | 5888.82 | 02-OCT-14:09 | 2880.76 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 605.38 | 01-OCT-18:01 | 3001.29 | 23-OCT-21:00 |
November | 5888.82 | 01-NOV-14:09 | 2880.76 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 08-NOV-15:00 | 3384.08 | 28-NOV-05:06 |
December | 5888.82 | 01-DEC-15:09 | 2880.76 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5685.79 | 18-DEC-05:44 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.49 | |||||
Maximum of Months | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 2981.46 | 8008.50 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 25543.68 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5205.22 | 25-JAN-23:00 |
February | 24809.68 | 01-FEB-15:09 | 25543.68 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7096.52 | 09-FEB-01:00 |
March | 24809.68 | 01-MAR-15:09 | 25543.68 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.51 | 22-MAR-13:00 | 5436.68 | 19-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 25543.68 | 01-APR-09:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 774.66 | 21-APR-15:00 | 5933.95 | 10-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 25543.68 | 01-MAY-08:09 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1713.84 | 14-MAY-18:02 | 2841.64 | 04-MAY-02:00 |
June | 24809.68 | 01-JUN-14:09 | 25543.68 | 01-JUN-08:09 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2494.53 | 21-JUN-20:02 | 2455.65 | 28-JUN-02:00 |
July | 24809.68 | 01-JUL-10:09 | 25543.68 | 01-JUL-09:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1838.31 | 02-JUL-18:01 | 1397.58 | 18-JUL-21:00 |
August | 24809.68 | 01-AUG-14:09 | 25543.68 | 01-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.14 | 06-AUG-18:01 | 1924.74 | 14-AUG-01:00 |
September | 24809.68 | 01-SEP-14:09 | 25543.68 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 615.00 | 10-SEP-18:02 | 951.57 | 25-SEP-03:00 |
October | 24809.68 | 02-OCT-14:09 | 25543.68 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 495.10 | 01-OCT-18:01 | 2891.53 | 23-OCT-21:00 |
November | 24809.68 | 01-NOV-14:09 | 25543.68 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 08-NOV-15:00 | 3106.14 | 04-NOV-04:00 |
December | 24809.68 | 01-DEC-15:09 | 25543.68 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4658.96 | 18-DEC-05:44 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.57 | |||||
Maximum of Months | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 2494.53 | 7096.52 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2406.93 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2352.91 | 25-JAN-23:00 |
February | 2337.76 | 01-FEB-15:09 | 2406.93 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3764.27 | 08-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 2406.93 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 22-MAR-13:00 | 2553.05 | 19-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2406.93 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 410.09 | 21-APR-15:00 | 2711.77 | 10-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2406.93 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 876.53 | 14-MAY-18:02 | 1267.62 | 04-MAY-02:00 |
June | 2337.76 | 01-JUN-14:09 | 2406.93 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.99 | 21-JUN-20:02 | 1220.45 | 28-JUN-02:00 |
July | 2337.76 | 01-JUL-10:09 | 2406.93 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 953.60 | 02-JUL-18:01 | 816.45 | 18-JUL-21:00 |
August | 2337.76 | 01-AUG-14:09 | 2406.93 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 568.09 | 06-AUG-18:01 | 1061.90 | 30-AUG-23:00 |
September | 2337.76 | 01-SEP-14:09 | 2406.93 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 308.23 | 10-SEP-18:02 | 619.95 | 04-SEP-20:00 |
October | 2337.76 | 02-OCT-14:09 | 2406.93 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 248.78 | 01-OCT-18:01 | 1606.01 | 23-OCT-21:00 |
November | 2337.76 | 01-NOV-14:09 | 2406.93 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-NOV-16:00 | 1614.19 | 04-NOV-04:00 |
December | 2337.76 | 01-DEC-15:09 | 2406.93 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2473.52 | 18-DEC-05:44 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.95 | |||||
Maximum of Months | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.99 | 3764.27 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2406.93 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2219.06 | 25-JAN-23:00 |
February | 2337.76 | 01-FEB-15:09 | 2406.93 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3538.80 | 08-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 2406.93 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 22-MAR-13:00 | 2460.75 | 19-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2406.93 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 410.09 | 21-APR-15:00 | 2630.19 | 10-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2406.93 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 883.20 | 14-MAY-18:02 | 1139.54 | 04-MAY-02:00 |
June | 2337.76 | 01-JUN-14:09 | 2406.93 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1283.67 | 21-JUN-20:02 | 1122.16 | 28-JUN-02:00 |
July | 2337.76 | 01-JUL-10:09 | 2406.93 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 956.20 | 02-JUL-18:01 | 738.05 | 18-JUL-21:00 |
August | 2337.76 | 01-AUG-14:09 | 2406.93 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 570.08 | 06-AUG-18:01 | 988.94 | 14-AUG-01:00 |
September | 2337.76 | 01-SEP-14:09 | 2406.93 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 311.06 | 10-SEP-18:02 | 584.88 | 04-SEP-20:00 |
October | 2337.76 | 02-OCT-14:09 | 2406.93 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 250.29 | 01-OCT-18:01 | 1541.26 | 23-OCT-21:00 |
November | 2337.76 | 01-NOV-14:09 | 2406.93 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 08-NOV-15:00 | 1540.56 | 04-NOV-04:00 |
December | 2337.76 | 01-DEC-15:09 | 2406.93 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2496.83 | 18-DEC-05:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 584.88 | |||||
Maximum of Months | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1283.67 | 3538.80 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 146.46 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 27150.19 | 26-JAN-12:10 |
February | 0.00 | 01-FEB-00:10 | 146.46 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 22526.41 | 02-FEB-12:10 |
March | 0.00 | 01-MAR-00:10 | 146.46 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 23832.61 | 01-MAR-18:00 |
April | 0.00 | 01-APR-00:10 | 146.46 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.49 | 19-APR-11:03 | 14932.11 | 11-APR-11:05 |
May | 0.00 | 01-MAY-00:10 | 146.46 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1808.34 | 19-MAY-11:02 | 4001.87 | 01-MAY-11:10 |
June | 0.00 | 01-JUN-00:10 | 146.46 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2338.75 | 02-JUN-11:01 | 1264.25 | 28-JUN-07:01 |
July | 0.00 | 01-JUL-00:10 | 146.46 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1964.89 | 01-JUL-11:02 | 1287.28 | 08-JUL-14:55 |
August | 0.00 | 01-AUG-00:10 | 146.46 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.98 | 27-AUG-11:02 | 1813.95 | 14-AUG-11:02 |
September | 0.00 | 01-SEP-00:10 | 146.46 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.11 | 17-SEP-11:03 | 5358.47 | 23-SEP-17:00 |
October | 0.00 | 01-OCT-00:10 | 146.46 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.06 | 03-OCT-13:55 | 14717.49 | 24-OCT-11:02 |
November | 0.00 | 01-NOV-00:10 | 146.46 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 23764.20 | 26-NOV-18:00 |
December | 0.00 | 01-DEC-00:10 | 146.46 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 31968.47 | 26-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1264.25 | ||||
Maximum of Months | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2338.75 | 31968.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 117.34 | 04-JAN-18:05 | 7361.02 | 3200.84 | 5518.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.97 |
February | 1392.62 | 08-FEB-19:00 | 3680.51 | 1600.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1690.40 |
March | 5204.16 | 16-MAR-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.57 |
April | 55929.54 | 20-APR-04:01 | 0.00 | 1585.11 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.49 |
May | 68732.76 | 21-MAY-06:02 | 0.00 | 792.55 | 2299.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.01 |
June | 67606.32 | 13-JUN-04:01 | 0.00 | 1585.11 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.86 |
July | 51638.94 | 11-JUL-04:01 | 0.00 | 1585.11 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.84 |
August | 59083.74 | 23-AUG-04:01 | 0.00 | 1585.11 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.89 |
September | 58741.37 | 12-SEP-04:01 | 0.00 | 1585.11 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 |
October | 51119.20 | 06-OCT-04:01 | 0.00 | 1585.11 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.63 |
November | 5107.93 | 10-NOV-15:10 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.43 |
December | 49.90 | 01-DEC-17:50 | 3680.51 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 49.90 | 0.00 | 792.55 | 2299.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | |
Maximum of Months | 68732.76 | 7361.02 | 3200.84 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1926.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33458.31 | 05-JAN-07:05 | 6202.42 | 11352.75 | 4135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.57 |
February | 37579.20 | 16-FEB-07:03 | 12404.84 | 22705.50 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41468.03 | 16-MAR-15:00 | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.54 |
April | 268253.11 | 22-APR-04:03 | 0.00 | 5676.37 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2669.30 |
May | 259746.67 | 21-MAY-06:02 | 0.00 | 7095.47 | 3877.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.91 |
June | 249440.90 | 13-JUN-04:01 | 0.00 | 14190.94 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.41 |
July | 184921.91 | 11-JUL-04:01 | 0.00 | 14190.94 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.58 |
August | 217674.12 | 23-AUG-04:01 | 0.00 | 14190.94 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.41 |
September | 253123.39 | 30-SEP-04:01 | 0.00 | 9933.66 | 5428.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.41 |
October | 232840.65 | 20-OCT-04:02 | 0.00 | 8514.56 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.52 |
November | 41310.17 | 10-NOV-15:10 | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.98 |
December | 30153.17 | 12-DEC-07:03 | 9303.63 | 17029.12 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 30153.17 | 0.00 | 5676.37 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 268253.11 | 24809.68 | 25543.68 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2669.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8273.82 | 12-JAN-15:30 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
February | 8403.53 | 21-FEB-16:00 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 |
March | 8455.73 | 16-MAR-15:00 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 |
April | 35808.28 | 04-APR-04:03 | 0.00 | 534.87 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 |
May | 37100.00 | 21-MAY-06:02 | 0.00 | 668.59 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.03 |
June | 36989.97 | 13-JUN-04:01 | 0.00 | 1337.18 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.63 |
July | 28672.88 | 11-JUL-04:01 | 0.00 | 1337.18 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.76 |
August | 33542.13 | 23-AUG-04:01 | 0.00 | 1337.18 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.72 |
September | 39121.54 | 30-SEP-04:01 | 0.00 | 936.03 | 3407.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 |
October | 35662.08 | 20-OCT-04:02 | 0.00 | 802.31 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.80 |
November | 12082.91 | 09-NOV-15:10 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
December | 7041.29 | 16-DEC-15:30 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7041.29 | 0.00 | 534.87 | 2434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | |
Maximum of Months | 39121.54 | 2337.76 | 2406.93 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6224.59 | 12-JAN-15:30 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
February | 6618.63 | 21-FEB-16:00 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 |
March | 6671.94 | 16-MAR-15:00 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 |
April | 30002.92 | 28-APR-04:01 | 0.00 | 1337.18 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.23 |
May | 32522.04 | 01-MAY-04:01 | 0.00 | 1337.18 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.11 |
June | 32491.36 | 13-JUN-04:01 | 0.00 | 1337.18 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.30 |
July | 24702.84 | 11-JUL-04:01 | 0.00 | 1337.18 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.43 |
August | 29152.22 | 23-AUG-04:01 | 0.00 | 1337.18 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.26 |
September | 34359.75 | 30-SEP-04:01 | 0.00 | 936.03 | 511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 |
October | 31304.21 | 20-OCT-04:02 | 0.00 | 802.31 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.59 |
November | 10403.44 | 09-NOV-15:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
December | 5035.84 | 16-DEC-15:30 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5035.84 | 0.00 | 802.31 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | |
Maximum of Months | 34359.75 | 2337.76 | 2406.93 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17.03 | 17-JAN-05:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.12 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.12 |
April | 0.00 | 01-APR-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.61 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 |
November | 24.86 | 29-NOV-05:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 |
December | 21.16 | 03-DEC-07:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | |
Maximum of Months | 24.86 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.12 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.111615E+12 | 80068.48 | 03-JAN-17:19 | 0.480674E+11 | 166547.31 | 28-JAN-05:10 |
February | 0.101331E+12 | 85482.30 | 21-FEB-15:00 | 0.284229E+11 | 158781.70 | 03-FEB-05:10 |
March | 0.115724E+12 | 93876.00 | 22-MAR-14:09 | 0.184022E+11 | 122328.88 | 02-MAR-07:30 |
April | 0.129616E+12 | 119775.77 | 21-APR-14:00 | 0.837125E+10 | 35342.11 | 03-APR-04:00 |
May | 0.157893E+12 | 131075.76 | 30-MAY-14:00 | 0.760819E+10 | 21076.16 | 12-MAY-04:49 |
June | 0.179329E+12 | 147666.48 | 15-JUN-14:00 | 0.718963E+10 | 9335.29 | 13-JUN-04:19 |
July | 0.189285E+12 | 146511.60 | 26-JUL-14:20 | 0.727091E+10 | 4831.86 | 03-JUL-11:20 |
August | 0.180326E+12 | 141481.81 | 07-AUG-15:00 | 0.733420E+10 | 4833.95 | 31-AUG-11:00 |
September | 0.161175E+12 | 131846.35 | 01-SEP-14:00 | 0.717009E+10 | 5482.65 | 26-SEP-04:49 |
October | 0.131564E+12 | 129024.93 | 03-OCT-14:09 | 0.800698E+10 | 15111.76 | 24-OCT-11:20 |
November | 0.108843E+12 | 96076.71 | 09-NOV-17:10 | 0.219156E+11 | 187559.74 | 28-NOV-05:10 |
December | 0.111809E+12 | 79016.23 | 15-DEC-17:30 | 0.604830E+11 | 197113.58 | 28-DEC-05:10 |
Annual Sum or Average | 0.167851E+13 | 0.230242E+12 | ||||
Minimum of Months | 0.101331E+12 | 79016.23 | 0.717009E+10 | 4831.86 | ||
Maximum of Months | 0.189285E+12 | 147666.48 | 0.604830E+11 | 197113.58 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.398525E+11 | 0.113081E+11 | 0.164409E+11 | 0.00 | 0.439577E+11 | 0.00 | 0.00 | 55867992.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362606E+11 | 0.967383E+10 | 0.149157E+11 | 0.00 | 0.391314E+11 | 0.00 | 0.00 | 0.134986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413616E+11 | 0.994181E+10 | 0.168545E+11 | 0.00 | 0.431638E+11 | 0.00 | 0.00 | 0.440226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390247E+11 | 0.884790E+10 | 0.160165E+11 | 0.00 | 0.397281E+11 | 0.00 | 0.00 | 0.259988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406071E+11 | 0.847888E+10 | 0.166477E+11 | 0.00 | 0.404235E+11 | 0.00 | 0.00 | 0.517361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399127E+11 | 0.787261E+10 | 0.162772E+11 | 0.00 | 0.395948E+11 | 0.00 | 0.00 | 0.756721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.397190E+11 | 0.828118E+10 | 0.163871E+11 | 0.00 | 0.403976E+11 | 0.00 | 0.00 | 0.845001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413616E+11 | 0.884790E+10 | 0.168545E+11 | 0.00 | 0.410303E+11 | 0.00 | 0.00 | 0.722313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.390247E+11 | 0.927844E+10 | 0.160165E+11 | 0.00 | 0.394311E+11 | 0.00 | 0.00 | 0.574238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398525E+11 | 0.103943E+11 | 0.164409E+11 | 0.00 | 0.406557E+11 | 0.00 | 0.00 | 0.242205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385372E+11 | 0.107326E+11 | 0.159174E+11 | 0.00 | 0.412650E+11 | 0.00 | 0.00 | 0.239079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397190E+11 | 0.114750E+11 | 0.163871E+11 | 0.00 | 0.442280E+11 | 0.00 | 0.00 | 86392.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475233E+12 | 0.115133E+12 | 0.195156E+12 | 0.493007E+12 | 0.00 | 0.399982E+12 | |||||||
Minimum of Months | 0.362606E+11 | 0.787261E+10 | 0.149157E+11 | 0.00 | 0.391314E+11 | 0.00 | 0.00 | 86392.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413616E+11 | 0.114750E+11 | 0.168545E+11 | 0.00 | 0.442280E+11 | 0.00 | 0.00 | 0.845001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.400220E+11 | 0.00 | 0.804546E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.211468E+11 | 0.00 | 0.727604E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.103947E+11 | 0.00 | 0.800750E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.848681E+09 | 0.00 | 0.752257E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 34150614.82 | 0.00 | 0.757404E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5606169.04 | 0.00 | 0.718403E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.727091E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.733420E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 3367494.82 | 0.00 | 0.716673E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.452813E+09 | 0.00 | 0.755416E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.144014E+11 | 0.00 | 0.751419E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.525262E+11 | 0.00 | 0.795674E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.139836E+12 | 0.904066E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.716673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.525262E+11 | 0.00 | 0.804546E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33384.75 | 02-JAN-09:09 | 7322.00 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 27537.83 | 15-JAN-14:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33384.75 | 01-FEB-09:09 | 7322.00 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 27537.83 | 01-FEB-06:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33384.75 | 01-MAR-09:09 | 7322.00 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 27537.83 | 13-MAR-11:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33384.75 | 01-APR-09:09 | 7322.00 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 27537.83 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33384.75 | 01-MAY-08:09 | 7322.00 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 27537.83 | 01-MAY-07:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33384.75 | 01-JUN-08:09 | 7322.00 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 27537.83 | 29-JUN-07:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33384.75 | 01-JUL-09:09 | 7322.00 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 24635.12 | 02-JUL-11:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33384.75 | 01-AUG-08:09 | 7322.00 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 26086.48 | 17-AUG-07:19 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33384.75 | 01-SEP-08:09 | 7322.00 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 27537.83 | 23-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33384.75 | 02-OCT-08:09 | 7322.00 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 27537.83 | 06-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33384.75 | 01-NOV-08:09 | 7322.00 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 27537.83 | 11-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33384.75 | 01-DEC-09:09 | 7322.00 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 27537.83 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 33384.75 | 7322.00 | 10771.04 | 0.00 | 24635.12 | 0.00 | 0.00 | |||||
Maximum of Months | 33384.75 | 7322.00 | 10771.04 | 0.00 | 27537.83 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 3923.24 | 03-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16691.39 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25085.09 | 22-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50984.86 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62284.85 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78875.57 | 15-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77720.69 | 26-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72690.90 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63055.44 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60234.02 | 03-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25751.77 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.36 | 23-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 13.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78875.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 80068.48 | 03-JAN-17:19 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 27537.83 | 0.00 | 0.00 | 1052.86 | 0.00 |
February | 85482.30 | 21-FEB-15:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 16691.39 | 0.00 |
March | 93876.00 | 22-MAR-14:09 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 25085.09 | 0.00 |
April | 119775.77 | 21-APR-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 50984.86 | 0.00 |
May | 131075.76 | 30-MAY-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 62284.85 | 0.00 |
June | 147666.48 | 15-JUN-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 78875.57 | 0.00 |
July | 146511.60 | 26-JUL-14:20 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 77720.69 | 0.00 |
August | 141481.81 | 07-AUG-15:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 72690.90 | 0.00 |
September | 131846.35 | 01-SEP-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 63055.44 | 0.00 |
October | 129024.93 | 03-OCT-14:09 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 60234.02 | 0.00 |
November | 96076.71 | 09-NOV-17:10 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 19963.80 | 0.00 |
December | 79016.23 | 15-DEC-17:30 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 27537.83 | 0.00 | 0.00 | 0.61 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 79016.23 | 33384.75 | 10771.04 | 0.00 | 0.00 | 24635.12 | 0.00 | 0.00 | 0.61 | 0.00 | |
Maximum of Months | 147666.48 | 33384.75 | 10771.04 | 7322.00 | 0.00 | 27537.83 | 0.00 | 0.00 | 78875.57 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 164685.31 | 28-JAN-05:10 | 0.00 | 5020.90 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 154351.00 | 03-FEB-05:10 | 0.00 | 5020.87 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 119641.77 | 02-MAR-07:10 | 0.00 | 5006.96 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 33480.11 | 03-APR-04:00 | 0.00 | 4962.08 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 19214.16 | 12-MAY-04:49 | 0.00 | 4916.15 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 4906.92 | 13-JUN-04:19 | 0.00 | 4866.90 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4831.86 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4833.95 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 3620.65 | 26-SEP-04:49 | 0.00 | 4865.99 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 10206.68 | 24-OCT-11:20 | 0.00 | 4916.44 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 185697.74 | 28-NOV-05:10 | 0.00 | 4969.31 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 195251.58 | 28-DEC-05:10 | 0.00 | 5005.88 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4831.86 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 195251.58 | 0.00 | 5020.90 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.67 | 19.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.33 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.64 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.88 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.95 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.88 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.00 | 0.00 |
October | 0.17 | 20.53 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 0.00 |
November | 4.67 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.50 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.33 | 19.69 | 0.00 | 11.00 | 24.90 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.50 | 20.53 | 0.00 | 0.00 | 5.67 | 24.95 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.67 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.66 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.67 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 0.00 |
November | 0.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 20.44 | 0.00 | 8.33 | 24.65 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.51 | 0.00 | 0.00 | 3.33 | 24.67 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.81 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.96 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.40 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.87 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.74 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.78 | 0.00 | 0.00 |
November | 0.67 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11.00 | 20.12 | 0.00 | 17.00 | 25.27 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 20.26 | 0.00 | 0.00 | 5.17 | 25.87 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.83 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.72 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.84 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.81 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.25 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.62 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.81 | 0.00 | 0.00 |
November | 1.17 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.33 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.33 | 20.04 | 0.00 | 11.50 | 24.88 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 20.50 | 0.00 | 0.00 | 4.00 | 25.25 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.23 | 360.00 | 21.13 | 360.00 | 21.13 |
February | 376.00 | 21.76 | 221.50 | 21.15 | 221.50 | 21.15 |
March | 422.00 | 22.61 | 121.67 | 21.15 | 121.67 | 21.15 |
April | 280.00 | 23.60 | 36.67 | 23.07 | 11.00 | 21.16 |
May | 63.17 | 23.85 | 244.33 | 23.89 | 0.00 | 0.00 |
June | 2.00 | 23.89 | 382.17 | 23.89 | 1.17 | 23.89 |
July | 44.50 | 23.89 | 415.00 | 23.89 | 44.50 | 23.89 |
August | 33.00 | 23.89 | 419.00 | 23.89 | 33.00 | 23.89 |
September | 57.33 | 23.86 | 335.00 | 23.89 | 35.83 | 23.89 |
October | 260.17 | 23.54 | 86.67 | 23.89 | 15.33 | 23.89 |
November | 399.00 | 22.22 | 137.83 | 21.14 | 137.83 | 21.14 |
December | 415.00 | 21.19 | 382.50 | 21.13 | 382.50 | 21.13 |
Annual Sum or Average | 2766.17 | 22.30 | 3142.33 | 22.81 | 1364.33 | 21.40 |
Minimum of Months | 2.00 | 21.19 | 36.67 | 21.13 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.89 | 419.00 | 23.89 | 382.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 22.20 | 60.00 | 21.11 | 60.00 | 21.11 |
February | 372.83 | 22.86 | 24.67 | 21.11 | 24.67 | 21.11 |
March | 362.67 | 23.26 | 6.50 | 21.11 | 6.50 | 21.11 |
April | 96.67 | 23.60 | 94.17 | 23.89 | 0.00 | 0.00 |
May | 16.50 | 23.83 | 296.50 | 23.89 | 0.00 | 0.00 |
June | 0.33 | 23.89 | 382.67 | 23.89 | 0.00 | 0.00 |
July | 40.83 | 23.89 | 414.67 | 23.89 | 40.83 | 23.89 |
August | 25.83 | 23.89 | 420.17 | 23.89 | 25.83 | 23.89 |
September | 35.83 | 23.86 | 373.33 | 23.89 | 32.50 | 23.89 |
October | 58.50 | 23.44 | 209.50 | 23.89 | 9.00 | 23.89 |
November | 330.17 | 22.96 | 31.00 | 22.69 | 13.33 | 21.11 |
December | 415.00 | 22.03 | 105.50 | 21.11 | 105.50 | 21.11 |
Annual Sum or Average | 2169.17 | 22.76 | 2418.67 | 23.65 | 318.17 | 22.06 |
Minimum of Months | 0.33 | 22.03 | 6.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.89 | 420.17 | 23.89 | 105.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 348.83 | 22.72 | 65.17 | 21.25 | 62.00 | 21.11 |
February | 301.50 | 23.01 | 42.67 | 21.19 | 41.50 | 21.11 |
March | 305.83 | 23.14 | 33.00 | 21.13 | 33.00 | 21.13 |
April | 136.00 | 23.55 | 115.83 | 23.77 | 5.17 | 21.14 |
May | 34.33 | 23.82 | 279.33 | 23.89 | 0.00 | 0.00 |
June | 2.17 | 23.89 | 383.67 | 23.89 | 0.83 | 23.89 |
July | 42.50 | 23.89 | 415.00 | 23.89 | 42.50 | 23.89 |
August | 27.50 | 23.89 | 421.67 | 23.89 | 27.50 | 23.89 |
September | 34.33 | 23.88 | 385.50 | 23.89 | 31.17 | 23.89 |
October | 51.50 | 23.52 | 311.17 | 23.89 | 7.83 | 23.89 |
November | 176.83 | 22.69 | 88.83 | 23.12 | 24.50 | 21.12 |
December | 389.33 | 22.76 | 84.17 | 21.11 | 84.17 | 21.11 |
Annual Sum or Average | 1850.67 | 23.01 | 2626.00 | 23.63 | 360.17 | 21.96 |
Minimum of Months | 2.17 | 22.69 | 33.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 389.33 | 23.89 | 421.67 | 23.89 | 84.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 376.50 | 22.32 | 89.50 | 21.16 | 88.00 | 21.11 |
February | 325.00 | 22.59 | 56.17 | 21.11 | 56.17 | 21.11 |
March | 347.50 | 22.86 | 53.67 | 21.11 | 53.67 | 21.11 |
April | 157.17 | 23.34 | 95.00 | 23.65 | 8.17 | 21.12 |
May | 49.17 | 23.71 | 258.83 | 23.89 | 0.00 | 0.00 |
June | 4.00 | 23.89 | 378.83 | 23.89 | 1.33 | 23.89 |
July | 49.50 | 23.89 | 414.83 | 23.89 | 49.50 | 23.89 |
August | 33.00 | 23.88 | 420.17 | 23.89 | 33.00 | 23.88 |
September | 40.00 | 23.84 | 379.83 | 23.89 | 33.33 | 23.89 |
October | 69.00 | 23.07 | 276.67 | 23.89 | 10.17 | 23.89 |
November | 209.83 | 22.42 | 92.33 | 22.61 | 42.67 | 21.11 |
December | 403.33 | 22.31 | 110.67 | 21.11 | 110.67 | 21.11 |
Annual Sum or Average | 2064.00 | 22.69 | 2626.50 | 23.51 | 486.67 | 21.84 |
Minimum of Months | 4.00 | 22.31 | 53.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 403.33 | 23.89 | 420.17 | 23.89 | 110.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.22963 | 26.70132 | -0.6704 | 14.85242 |
February | 376.00000 | 21.74985 | 23.17378 | -0.5336 | 12.26180 |
March | 422.00000 | 22.59602 | 20.58965 | -0.3033 | 8.67046 |
April | 405.00000 | 23.68279 | 22.65694 | 0.13531 | 6.43872 |
May | 418.00000 | 23.88401 | 31.21414 | -0.4668 | 10.18258 |
June | 408.00000 | 23.88968 | 36.10069 | -0.2695 | 6.72595 |
July | 415.00000 | 23.88968 | 46.87298 | -0.1985 | 5.91573 |
August | 422.00000 | 23.88968 | 44.79795 | -0.2799 | 6.82462 |
September | 405.00000 | 23.88500 | 43.69923 | -0.3799 | 8.42493 |
October | 414.00000 | 23.66225 | 37.72058 | 0.21590 | 6.88113 |
November | 399.00000 | 22.21308 | 27.35940 | -0.3596 | 9.65340 |
December | 415.00000 | 21.19088 | 23.88857 | -0.7149 | 16.07848 |
Annual Sum or Average | 4913.00000 | 22.98943 | 32.14143 | -0.3179 | 9.39276 |
Minimum of Months | 376.00000 | 21.19088 | 20.58965 | -0.7149 | 5.91573 |
Maximum of Months | 422.00000 | 23.88968 | 46.87298 | 0.21590 | 16.07848 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.20495 | 23.28717 | -0.2788 | 7.88965 |
February | 376.00000 | 22.87131 | 19.07017 | -0.1147 | 6.65525 |
March | 422.00000 | 23.35000 | 17.50086 | 0.05094 | 6.23047 |
April | 405.00000 | 23.82042 | 21.18628 | 0.30791 | 7.43273 |
May | 418.00000 | 23.88731 | 30.15149 | -0.3716 | 8.27380 |
June | 408.00000 | 23.88944 | 34.68556 | -0.2544 | 6.56415 |
July | 415.00000 | 23.88951 | 47.97445 | -0.1751 | 5.75263 |
August | 422.00000 | 23.88949 | 44.50677 | -0.2293 | 6.27222 |
September | 405.00000 | 23.88705 | 42.97746 | -0.2852 | 6.98676 |
October | 414.00000 | 23.82558 | 36.47451 | 0.38722 | 8.50571 |
November | 399.00000 | 23.12202 | 23.63847 | 0.00996 | 6.68472 |
December | 415.00000 | 22.02758 | 20.54954 | -0.3497 | 8.78626 |
Annual Sum or Average | 4913.00000 | 23.39221 | 30.26450 | -0.1094 | 7.17353 |
Minimum of Months | 376.00000 | 22.02758 | 17.50086 | -0.3716 | 5.75263 |
Maximum of Months | 422.00000 | 23.88951 | 47.97445 | 0.38722 | 8.78626 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.88141 | 21.17856 | -0.0923 | 7.63790 |
February | 376.00000 | 23.16914 | 17.82530 | -0.0235 | 7.05002 |
March | 422.00000 | 23.32673 | 16.79547 | 0.03365 | 6.87008 |
April | 405.00000 | 23.77095 | 20.84282 | 0.28023 | 7.60517 |
May | 418.00000 | 23.88413 | 29.71884 | -0.3903 | 8.86819 |
June | 408.00000 | 23.88964 | 34.43643 | -0.2309 | 6.38965 |
July | 415.00000 | 23.88971 | 46.91033 | -0.1337 | 5.52488 |
August | 422.00000 | 23.88972 | 43.76243 | -0.1588 | 5.82917 |
September | 405.00000 | 23.88889 | 41.83703 | -0.1572 | 6.00156 |
October | 414.00000 | 23.84405 | 35.56628 | 0.48288 | 10.51650 |
November | 399.00000 | 23.34856 | 22.15333 | 0.14254 | 7.94670 |
December | 415.00000 | 22.81466 | 18.48691 | -0.1427 | 7.91382 |
Annual Sum or Average | 4913.00000 | 23.55230 | 29.22594 | -0.0336 | 7.34749 |
Minimum of Months | 376.00000 | 22.81466 | 16.79547 | -0.3903 | 5.52488 |
Maximum of Months | 422.00000 | 23.88972 | 46.91033 | 0.48288 | 10.51650 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.45419 | 22.15052 | -0.1995 | 8.42529 |
February | 376.00000 | 22.75518 | 18.85042 | -0.1227 | 7.65580 |
March | 422.00000 | 23.02083 | 17.49834 | -0.0489 | 7.31961 |
April | 405.00000 | 23.66817 | 21.09759 | 0.23734 | 7.42677 |
May | 418.00000 | 23.86794 | 29.87273 | -0.4263 | 9.61646 |
June | 408.00000 | 23.88961 | 34.57618 | -0.2612 | 6.73644 |
July | 415.00000 | 23.88969 | 47.59328 | -0.1621 | 5.71736 |
August | 422.00000 | 23.88907 | 44.13053 | -0.1904 | 6.09916 |
September | 405.00000 | 23.88437 | 42.12339 | -0.1918 | 6.33009 |
October | 414.00000 | 23.75050 | 36.09411 | 0.43585 | 9.92254 |
November | 399.00000 | 23.10580 | 22.83160 | 0.06833 | 8.08312 |
December | 415.00000 | 22.34483 | 19.47385 | -0.2565 | 8.80978 |
Annual Sum or Average | 4913.00000 | 23.38077 | 29.78821 | -0.0941 | 7.67981 |
Minimum of Months | 376.00000 | 22.34483 | 17.49834 | -0.4263 | 5.71736 |
Maximum of Months | 422.00000 | 23.88969 | 47.59328 | 0.43585 | 9.92254 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 7386293.81 | 2456726.60 | 9.50 | 7386293.81 | 0.00 | 0.00 | 0.04 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 1378.33 | 21-FEB-16:00 | 1378.33 | 21-FEB-16:00 | 0.00 | 21-FEB-16:00 | 457.79 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.401829E+09 | 0.132867E+09 | 64.32 | 0.401829E+09 | 0.00 | 0.00 | 0.17 | 22-MAR-14:20 | 0.00 | 01-MAR-00:10 | 6686.27 | 22-MAR-14:20 | 6686.27 | 22-MAR-14:20 | 0.00 | 22-MAR-15:20 | 2206.29 | 22-MAR-14:20 | 0.00 | 01-MAR-00:10 |
April | 0.873269E+10 | 0.293998E+10 | 288.25 | 0.866194E+10 | 70755838.39 | 0.00 | 1.00 | 20-APR-04:01 | 0.00 | 01-APR-00:10 | 51358.38 | 29-APR-04:01 | 51020.04 | 20-APR-04:01 | 8138.48 | 29-APR-04:01 | 12536.65 | 29-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.228408E+11 | 0.761725E+10 | 402.04 | 0.219988E+11 | 0.842016E+09 | 0.00 | 1.00 | 09-MAY-04:01 | 0.00 | 01-MAY-00:10 | 54693.28 | 28-MAY-06:43 | 51483.70 | 31-MAY-04:01 | 19873.17 | 25-MAY-04:01 | 13884.40 | 31-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.363697E+11 | 0.123740E+11 | 440.43 | 0.345443E+11 | 0.182533E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 55193.65 | 28-JUN-04:01 | 52661.34 | 22-JUN-04:01 | 24173.68 | 28-JUN-04:02 | 14802.79 | 15-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.425814E+11 | 0.137933E+11 | 456.97 | 0.352484E+11 | 0.733300E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 59155.50 | 21-JUL-04:01 | 53829.50 | 03-JUL-04:01 | 35003.69 | 21-JUL-04:15 | 14976.52 | 03-JUL-04:01 | 0.00 | 01-JUL-00:10 |
August | 0.343077E+11 | 0.112116E+11 | 441.21 | 0.297028E+11 | 0.460493E+10 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 58300.39 | 02-AUG-04:01 | 51447.46 | 24-AUG-04:01 | 28990.80 | 02-AUG-04:53 | 14435.52 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.249168E+11 | 0.808262E+10 | 388.85 | 0.212307E+11 | 0.368606E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 57603.11 | 22-SEP-04:01 | 45315.98 | 12-SEP-04:01 | 29114.99 | 22-SEP-04:30 | 13989.03 | 13-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.771410E+10 | 0.250365E+10 | 266.08 | 0.678218E+10 | 0.931924E+09 | 0.00 | 1.00 | 02-OCT-04:01 | 0.00 | 01-OCT-00:10 | 55896.03 | 04-OCT-04:01 | 51639.80 | 02-OCT-04:01 | 26033.03 | 04-OCT-04:01 | 13741.16 | 02-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.216044E+09 | 70614535.29 | 28.79 | 0.214178E+09 | 1866198.53 | 0.00 | 0.17 | 09-NOV-15:30 | 0.00 | 01-NOV-00:10 | 6968.94 | 09-NOV-15:30 | 6968.94 | 09-NOV-15:30 | 213.73 | 03-NOV-14:10 | 2257.53 | 09-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.178088E+12 | 0.587284E+11 | 2786.44 | 0.158792E+12 | 0.192959E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.425814E+11 | 0.137933E+11 | 456.97 | 0.352484E+11 | 0.733300E+10 | 0.00 | 1.00 | 0.00 | 59155.50 | 53829.50 | 35003.69 | 14976.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 38748950.54 | 12765793.19 | 29.23 | 38748437.42 | 513.12 | 0.00 | 0.04 | 03-JAN-15:10 | 0.00 | 01-JAN-00:10 | 6102.13 | 03-JAN-15:10 | 6102.13 | 03-JAN-15:10 | 0.12 | 02-JAN-14:40 | 2003.43 | 03-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.277621E+10 | 0.900973E+09 | 115.18 | 0.277621E+10 | 2626.66 | 0.00 | 0.23 | 21-FEB-15:20 | 0.00 | 01-FEB-00:10 | 36254.59 | 21-FEB-15:20 | 36254.59 | 21-FEB-15:20 | 0.30 | 27-FEB-14:00 | 11678.10 | 21-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 0.105709E+11 | 0.340183E+10 | 212.15 | 0.105709E+11 | 17590.52 | 0.00 | 0.35 | 22-MAR-13:10 | 0.00 | 01-MAR-00:10 | 55905.51 | 22-MAR-14:10 | 55905.51 | 22-MAR-14:10 | 1.43 | 11-MAR-16:10 | 18155.04 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.573200E+11 | 0.188511E+11 | 343.12 | 0.567658E+11 | 0.554252E+09 | 0.00 | 1.00 | 03-APR-04:01 | 0.00 | 01-APR-00:10 | 198762.12 | 29-APR-04:01 | 196763.83 | 03-APR-04:01 | 45691.78 | 30-APR-06:03 | 49550.36 | 29-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.109159E+12 | 0.362216E+11 | 423.83 | 0.104965E+12 | 0.419425E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 209262.34 | 28-MAY-06:01 | 199115.42 | 31-MAY-04:01 | 75592.06 | 25-MAY-04:50 | 54747.77 | 31-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.149641E+12 | 0.514521E+11 | 442.08 | 0.141248E+12 | 0.839328E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 212649.43 | 04-JUN-06:01 | 201386.91 | 17-JUN-04:01 | 83407.36 | 28-JUN-04:15 | 57761.58 | 15-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.176273E+12 | 0.572544E+11 | 457.29 | 0.141425E+12 | 0.348485E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 227327.56 | 21-JUL-04:01 | 205359.00 | 03-JUL-04:01 | 126511.69 | 21-JUL-04:30 | 58257.39 | 03-JUL-04:01 | 0.00 | 01-JUL-00:10 |
August | 0.149786E+12 | 0.489646E+11 | 450.71 | 0.127557E+12 | 0.222294E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 224099.03 | 03-AUG-04:01 | 197833.52 | 27-AUG-06:41 | 104969.24 | 02-AUG-04:59 | 56612.77 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.120819E+12 | 0.388508E+11 | 404.72 | 0.101926E+12 | 0.188933E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 221223.53 | 22-SEP-04:01 | 189565.98 | 26-SEP-04:21 | 106621.81 | 22-SEP-04:46 | 54971.95 | 13-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.514351E+11 | 0.164230E+11 | 330.79 | 0.453237E+11 | 0.611139E+10 | 0.00 | 1.00 | 01-OCT-06:03 | 0.00 | 01-OCT-00:10 | 215946.66 | 04-OCT-04:01 | 196089.37 | 02-OCT-04:01 | 96281.85 | 04-OCT-04:15 | 54185.02 | 02-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.436446E+10 | 0.139902E+10 | 141.25 | 0.424744E+10 | 0.117013E+09 | 0.00 | 0.33 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 53357.72 | 03-NOV-16:00 | 52587.10 | 09-NOV-15:10 | 5030.59 | 03-NOV-12:50 | 17124.24 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 119653.43 | 39690.01 | 22.33 | 119653.43 | 0.00 | 0.00 | 0.00 | 22-DEC-16:20 | 0.00 | 01-DEC-00:10 | 16.54 | 22-DEC-16:20 | 16.54 | 22-DEC-16:20 | 0.00 | 11-DEC-16:00 | 5.49 | 22-DEC-16:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.832185E+12 | 0.273732E+12 | 3372.69 | 0.736843E+12 | 0.953414E+11 | 0.00 | ||||||||||||||
Minimum of Months | 119653.43 | 39690.01 | 22.33 | 119653.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 16.54 | 0.00 | 5.49 | 0.00 | |||||||
Maximum of Months | 0.176273E+12 | 0.572544E+11 | 457.29 | 0.141425E+12 | 0.348485E+11 | 0.00 | 1.00 | 0.00 | 227327.56 | 205359.00 | 126511.69 | 58257.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 99693220.46 | 29488609.77 | 116.94 | 99614023.33 | 79197.13 | 0.00 | 0.18 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 4103.97 | 03-JAN-15:00 | 4103.97 | 03-JAN-15:00 | 30.85 | 12-JAN-17:00 | 1199.54 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.928046E+09 | 0.270618E+09 | 171.59 | 0.928045E+09 | 127.58 | 0.00 | 0.38 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 | 8883.32 | 21-FEB-16:00 | 8883.32 | 21-FEB-16:00 | 0.03 | 27-FEB-13:30 | 2538.71 | 21-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.179013E+10 | 0.527008E+09 | 229.28 | 0.179013E+10 | 1189.34 | 0.00 | 0.41 | 22-MAR-13:30 | 0.00 | 01-MAR-00:10 | 9512.78 | 22-MAR-13:40 | 9512.78 | 22-MAR-13:40 | 0.09 | 11-MAR-16:10 | 2799.28 | 22-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.767549E+10 | 0.234680E+10 | 329.79 | 0.763452E+10 | 40972262.36 | 0.00 | 1.00 | 03-APR-04:01 | 0.00 | 01-APR-00:10 | 28459.24 | 29-APR-04:01 | 28211.19 | 20-APR-04:01 | 4362.05 | 29-APR-04:02 | 6553.04 | 29-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.138543E+11 | 0.431876E+10 | 404.37 | 0.134273E+11 | 0.427040E+09 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 30246.93 | 28-MAY-06:43 | 28508.04 | 31-MAY-04:01 | 10947.10 | 25-MAY-04:01 | 7248.90 | 31-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.197304E+11 | 0.636260E+10 | 440.13 | 0.188317E+11 | 0.898688E+09 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 30541.90 | 28-JUN-04:01 | 29113.61 | 22-JUN-04:01 | 13424.44 | 28-JUN-04:02 | 7723.15 | 15-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.236482E+11 | 0.721414E+10 | 459.01 | 0.195907E+11 | 0.405750E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 32761.67 | 21-JUL-04:01 | 30000.79 | 03-JUL-03:31 | 19427.72 | 21-JUL-04:15 | 7836.11 | 03-JUL-02:31 | 0.00 | 01-JUL-00:10 |
August | 0.213477E+11 | 0.648354E+10 | 449.23 | 0.186983E+11 | 0.264939E+10 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 32299.61 | 02-AUG-04:01 | 30156.95 | 06-AUG-21:50 | 16004.81 | 02-AUG-04:15 | 7987.37 | 04-AUG-23:01 | 0.00 | 01-AUG-00:10 |
September | 0.191853E+11 | 0.564648E+10 | 404.00 | 0.167682E+11 | 0.241711E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 31945.11 | 22-SEP-04:01 | 26075.50 | 19-SEP-04:03 | 16353.54 | 22-SEP-04:46 | 7309.48 | 13-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.101860E+11 | 0.291557E+10 | 336.58 | 0.929863E+10 | 0.887337E+09 | 0.00 | 1.00 | 01-OCT-06:03 | 0.00 | 01-OCT-00:10 | 30980.72 | 04-OCT-04:01 | 29289.83 | 02-OCT-04:01 | 14168.93 | 04-OCT-04:15 | 7198.10 | 02-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.187712E+10 | 0.537481E+09 | 196.03 | 0.184394E+10 | 33182074.31 | 0.00 | 0.54 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 13167.83 | 09-NOV-15:10 | 13167.83 | 09-NOV-15:10 | 1093.49 | 03-NOV-12:25 | 3638.76 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 109898.16 | 33675.68 | 96.52 | 109885.36 | 12.79 | 0.00 | 0.00 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 | 40.19 | 23-DEC-15:00 | 40.19 | 23-DEC-15:00 | 0.00 | 04-DEC-14:40 | 12.31 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.120322E+12 | 0.366525E+11 | 3633.47 | 0.108911E+12 | 0.114113E+11 | 0.00 | ||||||||||||||
Minimum of Months | 109898.16 | 33675.68 | 96.52 | 109885.36 | 12.79 | 0.00 | 0.00 | 0.00 | 40.19 | 40.19 | 0.00 | 12.31 | 0.00 | |||||||
Maximum of Months | 0.236482E+11 | 0.721414E+10 | 459.01 | 0.195907E+11 | 0.405750E+10 | 0.00 | 1.00 | 0.00 | 32761.67 | 30156.95 | 19427.72 | 7987.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 45517076.06 | 13613589.13 | 71.09 | 45455806.67 | 61269.39 | 0.00 | 0.13 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 2473.33 | 03-JAN-15:00 | 2473.33 | 03-JAN-15:00 | 18.13 | 12-JAN-16:30 | 734.21 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.597480E+09 | 0.175810E+09 | 115.63 | 0.597480E+09 | 0.07 | 0.00 | 0.34 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 7112.47 | 20-FEB-15:30 | 7112.47 | 20-FEB-15:30 | 0.00 | 14-FEB-11:50 | 2074.12 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.114312E+10 | 0.340555E+09 | 187.21 | 0.114312E+10 | 341.03 | 0.00 | 0.35 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 7271.26 | 22-MAR-13:40 | 7271.26 | 22-MAR-13:40 | 0.05 | 11-MAR-16:30 | 2182.36 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.601029E+10 | 0.186091E+10 | 300.75 | 0.597489E+10 | 35400357.21 | 0.00 | 1.00 | 03-APR-04:01 | 0.00 | 01-APR-00:10 | 26022.02 | 29-APR-04:02 | 25472.40 | 03-APR-04:01 | 4118.25 | 29-APR-04:01 | 6004.04 | 29-APR-04:02 | 0.00 | 01-APR-00:10 |
May | 0.113551E+11 | 0.357847E+10 | 393.05 | 0.109797E+11 | 0.375390E+09 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 27038.78 | 28-MAY-06:01 | 25647.05 | 31-MAY-04:01 | 10094.60 | 28-MAY-06:01 | 6522.29 | 31-MAY-04:01 | 0.00 | 01-MAY-00:10 |
June | 0.168671E+11 | 0.548338E+10 | 437.55 | 0.160708E+11 | 0.796270E+09 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 27542.80 | 28-JUN-04:01 | 26111.38 | 17-JUN-04:01 | 12263.55 | 28-JUN-04:01 | 6899.75 | 15-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.203165E+11 | 0.623820E+10 | 454.01 | 0.166716E+11 | 0.364491E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:10 | 29572.59 | 21-JUL-04:01 | 26585.03 | 03-JUL-04:02 | 17610.35 | 21-JUL-04:15 | 7049.90 | 03-JUL-04:01 | 0.00 | 01-JUL-00:10 |
August | 0.182248E+11 | 0.557156E+10 | 440.55 | 0.158653E+11 | 0.235952E+10 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 29138.03 | 02-AUG-04:01 | 25586.77 | 27-AUG-06:41 | 14599.43 | 02-AUG-04:15 | 6798.88 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.163460E+11 | 0.484387E+10 | 397.85 | 0.141768E+11 | 0.216915E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 28810.00 | 22-SEP-04:01 | 22599.42 | 12-SEP-04:01 | 14683.94 | 22-SEP-04:47 | 6594.42 | 13-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.824331E+10 | 0.237831E+10 | 315.01 | 0.749814E+10 | 0.745171E+09 | 0.00 | 1.00 | 01-OCT-06:03 | 0.00 | 01-OCT-00:10 | 27948.13 | 04-OCT-04:01 | 25953.91 | 02-OCT-04:01 | 12955.78 | 04-OCT-04:02 | 6492.92 | 02-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.133262E+10 | 0.383678E+09 | 169.25 | 0.130568E+10 | 26940105.62 | 0.00 | 0.52 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 11357.62 | 09-NOV-15:10 | 11357.62 | 09-NOV-15:10 | 907.93 | 03-NOV-12:50 | 3156.86 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 |
December | 42507.04 | 13026.63 | 54.36 | 42496.54 | 10.49 | 0.00 | 0.00 | 16-DEC-12:50 | 0.00 | 01-DEC-00:10 | 0.91 | 16-DEC-12:50 | 0.91 | 16-DEC-12:50 | 0.00 | 04-DEC-15:10 | 0.28 | 16-DEC-12:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.100482E+12 | 0.308684E+11 | 3336.31 | 0.903291E+11 | 0.101528E+11 | 0.00 | ||||||||||||||
Minimum of Months | 42507.04 | 13026.63 | 54.36 | 42496.54 | 0.07 | 0.00 | 0.00 | 0.00 | 0.91 | 0.91 | 0.00 | 0.28 | 0.00 | |||||||
Maximum of Months | 0.203165E+11 | 0.623820E+10 | 454.01 | 0.166716E+11 | 0.364491E+10 | 0.00 | 1.00 | 0.00 | 29572.59 | 26585.03 | 17610.35 | 7049.90 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.93 | 16.01 | 6.91 | 27.78 | 40.16 | 0.00 | 0.00 | 744.00 |
February | 30.26 | 21.59 | 8.68 | 40.61 | 38.48 | 0.00 | 0.00 | 672.00 |
March | 40.97 | 28.79 | 12.17 | 60.16 | 34.88 | 0.00 | 0.00 | 744.00 |
April | 51.65 | 38.33 | 13.32 | 84.15 | 25.44 | 0.00 | 0.00 | 720.00 |
May | 56.68 | 42.08 | 14.60 | 98.22 | 19.46 | 0.00 | 0.00 | 744.00 |
June | 59.89 | 46.41 | 13.48 | 110.20 | 13.29 | 0.00 | 0.00 | 720.00 |
July | 51.88 | 37.38 | 14.50 | 96.67 | 10.36 | 0.00 | 0.00 | 744.00 |
August | 48.28 | 34.74 | 13.54 | 88.23 | 12.70 | 0.00 | 0.00 | 744.00 |
September | 44.55 | 33.34 | 11.21 | 79.07 | 19.06 | 0.00 | 0.00 | 720.00 |
October | 33.59 | 24.41 | 9.18 | 53.04 | 25.95 | 0.00 | 0.00 | 744.00 |
November | 26.62 | 19.86 | 6.76 | 34.97 | 38.09 | 0.00 | 0.00 | 720.00 |
December | 21.48 | 14.31 | 7.17 | 24.06 | 44.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.76 | 29.79 | 10.98 | 66.53 | 26.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.48 | 14.31 | 6.76 | 24.06 | 10.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.89 | 46.41 | 14.60 | 110.20 | 44.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1131.89 | 857.31 | 274.58 | 1489.04 | 1020.34 | 0.00 | 0.00 | 744.00 |
February | 1050.83 | 740.84 | 309.99 | 1362.00 | 939.15 | 0.00 | 0.00 | 672.00 |
March | 855.36 | 493.79 | 361.57 | 1051.52 | 851.66 | 0.00 | 0.00 | 744.00 |
April | 581.16 | 218.21 | 362.95 | 716.37 | 573.63 | 0.00 | 0.00 | 720.00 |
May | 410.30 | 58.40 | 351.89 | 570.08 | 377.23 | 0.00 | 0.00 | 744.00 |
June | 353.54 | 22.94 | 330.60 | 674.93 | 236.27 | 0.00 | 0.00 | 720.00 |
July | 360.55 | 34.06 | 326.49 | 679.56 | 204.73 | 0.00 | 0.00 | 744.00 |
August | 460.26 | 122.98 | 337.28 | 773.32 | 267.59 | 0.00 | 0.00 | 744.00 |
September | 717.91 | 373.90 | 344.01 | 1160.08 | 459.14 | 0.00 | 0.00 | 720.00 |
October | 973.43 | 658.30 | 315.13 | 1438.80 | 642.18 | 0.00 | 0.00 | 744.00 |
November | 1170.22 | 892.04 | 278.18 | 1586.92 | 927.97 | 0.00 | 0.00 | 720.00 |
December | 1159.13 | 869.83 | 289.30 | 1495.43 | 1095.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 767.09 | 443.54 | 323.55 | 1081.41 | 631.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 353.54 | 22.94 | 274.58 | 570.08 | 204.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1170.22 | 892.04 | 362.95 | 1586.92 | 1095.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1131.89 | 857.31 | 274.58 | 1497.54 | 985.31 | 0.00 | 0.00 | 744.00 |
February | 1050.83 | 740.84 | 309.99 | 1368.17 | 906.23 | 0.00 | 0.00 | 672.00 |
March | 855.36 | 493.79 | 361.57 | 1057.49 | 822.49 | 0.00 | 0.00 | 744.00 |
April | 581.16 | 218.21 | 362.95 | 714.98 | 550.02 | 0.00 | 0.00 | 720.00 |
May | 410.30 | 58.40 | 351.89 | 566.10 | 356.64 | 0.00 | 0.00 | 744.00 |
June | 353.54 | 22.94 | 330.60 | 671.06 | 218.15 | 0.00 | 0.00 | 720.00 |
July | 360.55 | 34.06 | 326.49 | 676.19 | 187.25 | 0.00 | 0.00 | 744.00 |
August | 460.26 | 122.98 | 337.28 | 769.21 | 250.49 | 0.00 | 0.00 | 744.00 |
September | 717.91 | 373.90 | 344.01 | 1155.71 | 439.32 | 0.00 | 0.00 | 720.00 |
October | 973.43 | 658.30 | 315.13 | 1439.25 | 617.20 | 0.00 | 0.00 | 744.00 |
November | 1170.22 | 892.04 | 278.18 | 1591.65 | 899.67 | 0.00 | 0.00 | 720.00 |
December | 1159.13 | 869.83 | 289.30 | 1504.25 | 1059.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 767.09 | 443.54 | 323.55 | 1082.53 | 606.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 353.54 | 22.94 | 274.58 | 566.10 | 187.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1170.22 | 892.04 | 362.95 | 1591.65 | 1059.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.90 | 176.40 | 56.50 | 302.93 | 198.83 | 0.00 | 0.00 | 744.00 |
February | 216.22 | 152.44 | 63.79 | 277.89 | 181.16 | 0.00 | 0.00 | 672.00 |
March | 176.00 | 101.60 | 74.40 | 216.24 | 163.41 | 0.00 | 0.00 | 744.00 |
April | 119.58 | 44.90 | 74.68 | 141.41 | 111.52 | 0.00 | 0.00 | 720.00 |
May | 84.42 | 12.02 | 72.41 | 99.93 | 76.81 | 0.00 | 0.00 | 744.00 |
June | 72.75 | 4.72 | 68.03 | 100.18 | 54.03 | 0.00 | 0.00 | 720.00 |
July | 74.19 | 7.01 | 67.18 | 104.00 | 47.54 | 0.00 | 0.00 | 744.00 |
August | 94.71 | 25.31 | 69.40 | 129.35 | 62.16 | 0.00 | 0.00 | 744.00 |
September | 147.72 | 76.94 | 70.78 | 214.36 | 101.80 | 0.00 | 0.00 | 720.00 |
October | 200.30 | 135.46 | 64.84 | 288.16 | 128.33 | 0.00 | 0.00 | 744.00 |
November | 240.79 | 183.55 | 57.24 | 324.71 | 178.80 | 0.00 | 0.00 | 720.00 |
December | 238.51 | 178.98 | 59.53 | 303.57 | 214.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 157.84 | 91.26 | 66.58 | 208.14 | 126.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.75 | 4.72 | 56.50 | 99.93 | 47.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 240.79 | 183.55 | 74.68 | 324.71 | 214.02 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61405475.60 | 42889533.81 | 18515941.79 | 74404246.13 | 0.107559E+09 |
February | 73210819.59 | 52220214.19 | 20990605.40 | 98250558.38 | 93095970.85 |
March | 0.109722E+09 | 77120267.70 | 32602052.38 | 0.161146E+09 | 93410373.09 |
April | 0.133878E+09 | 99360956.74 | 34516811.15 | 0.218110E+09 | 65937779.75 |
May | 0.151824E+09 | 0.112720E+09 | 39104848.61 | 0.263085E+09 | 52124252.04 |
June | 0.155236E+09 | 0.120289E+09 | 34946365.91 | 0.285643E+09 | 34456615.08 |
July | 0.138952E+09 | 0.100116E+09 | 38836053.26 | 0.258934E+09 | 27759491.69 |
August | 0.129309E+09 | 93037667.49 | 36271372.59 | 0.236303E+09 | 34013639.28 |
September | 0.115476E+09 | 86412953.22 | 29062712.12 | 0.204950E+09 | 49407319.50 |
October | 89972996.01 | 65389661.22 | 24583334.79 | 0.142067E+09 | 69509509.08 |
November | 69003360.28 | 51471393.07 | 17531967.21 | 90632277.84 | 98718442.56 |
December | 57544201.40 | 38337215.41 | 19206986.00 | 64442461.60 | 0.119690E+09 |
Annual Sum or Average | 0.128553E+10 | 0.939365E+09 | 0.346169E+09 | 0.209797E+10 | 0.845682E+09 |
Minimum of Months | 57544201.40 | 38337215.41 | 17531967.21 | 64442461.60 | 27759491.69 |
Maximum of Months | 0.155236E+09 | 0.120289E+09 | 39104848.61 | 0.285643E+09 | 0.119690E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303164E+10 | 0.229622E+10 | 0.735426E+09 | 0.398825E+10 | 0.273288E+10 |
February | 0.254216E+10 | 0.179223E+10 | 0.749931E+09 | 0.329495E+10 | 0.227200E+10 |
March | 0.229100E+10 | 0.132257E+10 | 0.968430E+09 | 0.281639E+10 | 0.228109E+10 |
April | 0.150636E+10 | 0.565598E+09 | 0.940767E+09 | 0.185684E+10 | 0.148685E+10 |
May | 0.109893E+10 | 0.156427E+09 | 0.942508E+09 | 0.152691E+10 | 0.101036E+10 |
June | 0.916388E+09 | 59459973.85 | 0.856928E+09 | 0.174943E+10 | 0.612414E+09 |
July | 0.965696E+09 | 91226655.22 | 0.874469E+09 | 0.182014E+10 | 0.548360E+09 |
August | 0.123277E+10 | 0.329391E+09 | 0.903382E+09 | 0.207126E+10 | 0.716710E+09 |
September | 0.186083E+10 | 0.969162E+09 | 0.891669E+09 | 0.300693E+10 | 0.119009E+10 |
October | 0.260724E+10 | 0.176320E+10 | 0.844040E+09 | 0.385367E+10 | 0.172001E+10 |
November | 0.303322E+10 | 0.231217E+10 | 0.721054E+09 | 0.411331E+10 | 0.240531E+10 |
December | 0.310462E+10 | 0.232976E+10 | 0.774869E+09 | 0.400535E+10 | 0.293409E+10 |
Annual Sum or Average | 0.241909E+11 | 0.139874E+11 | 0.102035E+11 | 0.341034E+11 | 0.199102E+11 |
Minimum of Months | 0.916388E+09 | 59459973.85 | 0.721054E+09 | 0.152691E+10 | 0.548360E+09 |
Maximum of Months | 0.310462E+10 | 0.232976E+10 | 0.968430E+09 | 0.411331E+10 | 0.293409E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303164E+10 | 0.229622E+10 | 0.735426E+09 | 0.401102E+10 | 0.263904E+10 |
February | 0.254216E+10 | 0.179223E+10 | 0.749931E+09 | 0.330988E+10 | 0.219234E+10 |
March | 0.229100E+10 | 0.132257E+10 | 0.968430E+09 | 0.283238E+10 | 0.220295E+10 |
April | 0.150636E+10 | 0.565598E+09 | 0.940767E+09 | 0.185323E+10 | 0.142565E+10 |
May | 0.109893E+10 | 0.156427E+09 | 0.942508E+09 | 0.151624E+10 | 0.955227E+09 |
June | 0.916388E+09 | 59459973.85 | 0.856928E+09 | 0.173940E+10 | 0.565454E+09 |
July | 0.965696E+09 | 91226655.22 | 0.874469E+09 | 0.181110E+10 | 0.501517E+09 |
August | 0.123277E+10 | 0.329391E+09 | 0.903382E+09 | 0.206026E+10 | 0.670913E+09 |
September | 0.186083E+10 | 0.969162E+09 | 0.891669E+09 | 0.299560E+10 | 0.113871E+10 |
October | 0.260724E+10 | 0.176320E+10 | 0.844040E+09 | 0.385488E+10 | 0.165311E+10 |
November | 0.303322E+10 | 0.231217E+10 | 0.721054E+09 | 0.412556E+10 | 0.233194E+10 |
December | 0.310462E+10 | 0.232976E+10 | 0.774869E+09 | 0.402898E+10 | 0.283764E+10 |
Annual Sum or Average | 0.241909E+11 | 0.139874E+11 | 0.102035E+11 | 0.341385E+11 | 0.191145E+11 |
Minimum of Months | 0.916388E+09 | 59459973.85 | 0.721054E+09 | 0.151624E+10 | 0.501517E+09 |
Maximum of Months | 0.310462E+10 | 0.232976E+10 | 0.968430E+09 | 0.412556E+10 | 0.283764E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623804E+09 | 0.472480E+09 | 0.151325E+09 | 0.811365E+09 | 0.532541E+09 |
February | 0.523087E+09 | 0.368778E+09 | 0.154309E+09 | 0.672260E+09 | 0.438262E+09 |
March | 0.471406E+09 | 0.272137E+09 | 0.199269E+09 | 0.579169E+09 | 0.437677E+09 |
April | 0.309956E+09 | 0.116380E+09 | 0.193576E+09 | 0.366531E+09 | 0.289052E+09 |
May | 0.226122E+09 | 32187156.39 | 0.193935E+09 | 0.267663E+09 | 0.205732E+09 |
June | 0.188560E+09 | 12234755.43 | 0.176325E+09 | 0.259657E+09 | 0.140047E+09 |
July | 0.198706E+09 | 18771212.68 | 0.179935E+09 | 0.278553E+09 | 0.127319E+09 |
August | 0.253661E+09 | 67776969.32 | 0.185884E+09 | 0.346447E+09 | 0.166501E+09 |
September | 0.382893E+09 | 0.199419E+09 | 0.183474E+09 | 0.555618E+09 | 0.263863E+09 |
October | 0.536477E+09 | 0.362804E+09 | 0.173673E+09 | 0.771802E+09 | 0.343718E+09 |
November | 0.624130E+09 | 0.475762E+09 | 0.148367E+09 | 0.841639E+09 | 0.463447E+09 |
December | 0.638822E+09 | 0.479381E+09 | 0.159441E+09 | 0.813069E+09 | 0.573227E+09 |
Annual Sum or Average | 0.497762E+10 | 0.287811E+10 | 0.209951E+10 | 0.656377E+10 | 0.398139E+10 |
Minimum of Months | 0.188560E+09 | 12234755.43 | 0.148367E+09 | 0.259657E+09 | 0.127319E+09 |
Maximum of Months | 0.638822E+09 | 0.479381E+09 | 0.199269E+09 | 0.841639E+09 | 0.573227E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.23 | 321.26 | 183.41 | 128.10 | 55.30 | 0.00 | 0.00 |
February | 324.90 | 307.86 | 242.10 | 172.69 | 69.41 | 0.00 | 0.00 |
March | 481.32 | 279.00 | 327.72 | 230.35 | 97.38 | 0.00 | 0.00 |
April | 673.18 | 203.51 | 413.20 | 306.67 | 106.53 | 0.00 | 0.00 |
May | 785.80 | 155.69 | 453.48 | 336.68 | 116.80 | 0.00 | 0.00 |
June | 881.61 | 106.35 | 479.12 | 371.26 | 107.86 | 0.00 | 0.00 |
July | 773.40 | 82.91 | 415.03 | 299.03 | 116.00 | 0.00 | 0.00 |
August | 705.80 | 101.59 | 386.23 | 277.89 | 108.34 | 0.00 | 0.00 |
September | 632.56 | 152.49 | 356.41 | 266.71 | 89.70 | 0.00 | 0.00 |
October | 424.33 | 207.62 | 268.74 | 195.31 | 73.43 | 0.00 | 0.00 |
November | 279.73 | 304.69 | 212.97 | 158.86 | 54.11 | 0.00 | 0.00 |
December | 192.48 | 357.50 | 171.88 | 114.51 | 57.37 | 0.00 | 0.00 |
Annual Sum or Average | 532.21 | 214.53 | 326.11 | 238.30 | 87.82 | 0.00 | 0.00 |
Minimum of Months | 192.48 | 82.91 | 171.88 | 114.51 | 54.11 | 0.00 | 0.00 |
Maximum of Months | 881.61 | 357.50 | 479.12 | 371.26 | 116.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1489.04 | 1020.34 | 1131.89 | 857.31 | 274.58 | 0.00 | 0.00 |
February | 1362.00 | 939.15 | 1050.83 | 740.84 | 309.99 | 0.00 | 0.00 |
March | 1051.52 | 851.66 | 855.36 | 493.79 | 361.57 | 0.00 | 0.00 |
April | 716.37 | 573.63 | 581.16 | 218.21 | 362.95 | 0.00 | 0.00 |
May | 570.08 | 377.23 | 410.30 | 58.40 | 351.89 | 0.00 | 0.00 |
June | 674.93 | 236.27 | 353.54 | 22.94 | 330.60 | 0.00 | 0.00 |
July | 679.56 | 204.73 | 360.55 | 34.06 | 326.49 | 0.00 | 0.00 |
August | 773.32 | 267.59 | 460.26 | 122.98 | 337.28 | 0.00 | 0.00 |
September | 1160.08 | 459.14 | 717.91 | 373.90 | 344.01 | 0.00 | 0.00 |
October | 1438.80 | 642.18 | 973.43 | 658.30 | 315.13 | 0.00 | 0.00 |
November | 1586.92 | 927.97 | 1170.22 | 892.04 | 278.18 | 0.00 | 0.00 |
December | 1495.43 | 1095.46 | 1159.13 | 869.83 | 289.30 | 0.00 | 0.00 |
Annual Sum or Average | 1081.41 | 631.35 | 767.09 | 443.54 | 323.55 | 0.00 | 0.00 |
Minimum of Months | 570.08 | 204.73 | 353.54 | 22.94 | 274.58 | 0.00 | 0.00 |
Maximum of Months | 1586.92 | 1095.46 | 1170.22 | 892.04 | 362.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1497.54 | 985.31 | 1131.89 | 857.31 | 274.58 | 0.00 | 0.00 |
February | 1368.17 | 906.23 | 1050.83 | 740.84 | 309.99 | 0.00 | 0.00 |
March | 1057.49 | 822.49 | 855.36 | 493.79 | 361.57 | 0.00 | 0.00 |
April | 714.98 | 550.02 | 581.16 | 218.21 | 362.95 | 0.00 | 0.00 |
May | 566.10 | 356.64 | 410.30 | 58.40 | 351.89 | 0.00 | 0.00 |
June | 671.06 | 218.15 | 353.54 | 22.94 | 330.60 | 0.00 | 0.00 |
July | 676.19 | 187.25 | 360.55 | 34.06 | 326.49 | 0.00 | 0.00 |
August | 769.21 | 250.49 | 460.26 | 122.98 | 337.28 | 0.00 | 0.00 |
September | 1155.71 | 439.32 | 717.91 | 373.90 | 344.01 | 0.00 | 0.00 |
October | 1439.25 | 617.20 | 973.43 | 658.30 | 315.13 | 0.00 | 0.00 |
November | 1591.65 | 899.67 | 1170.22 | 892.04 | 278.18 | 0.00 | 0.00 |
December | 1504.25 | 1059.45 | 1159.13 | 869.83 | 289.30 | 0.00 | 0.00 |
Annual Sum or Average | 1082.53 | 606.12 | 767.09 | 443.54 | 323.55 | 0.00 | 0.00 |
Minimum of Months | 566.10 | 187.25 | 353.54 | 22.94 | 274.58 | 0.00 | 0.00 |
Maximum of Months | 1591.65 | 1059.45 | 1170.22 | 892.04 | 362.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.93 | 198.83 | 232.90 | 176.40 | 56.50 | 0.00 | 0.00 |
February | 277.89 | 181.16 | 216.22 | 152.44 | 63.79 | 0.00 | 0.00 |
March | 216.24 | 163.41 | 176.00 | 101.60 | 74.40 | 0.00 | 0.00 |
April | 141.41 | 111.52 | 119.58 | 44.90 | 74.68 | 0.00 | 0.00 |
May | 99.93 | 76.81 | 84.42 | 12.02 | 72.41 | 0.00 | 0.00 |
June | 100.18 | 54.03 | 72.75 | 4.72 | 68.03 | 0.00 | 0.00 |
July | 104.00 | 47.54 | 74.19 | 7.01 | 67.18 | 0.00 | 0.00 |
August | 129.35 | 62.16 | 94.71 | 25.31 | 69.40 | 0.00 | 0.00 |
September | 214.36 | 101.80 | 147.72 | 76.94 | 70.78 | 0.00 | 0.00 |
October | 288.16 | 128.33 | 200.30 | 135.46 | 64.84 | 0.00 | 0.00 |
November | 324.71 | 178.80 | 240.79 | 183.55 | 57.24 | 0.00 | 0.00 |
December | 303.57 | 214.02 | 238.51 | 178.98 | 59.53 | 0.00 | 0.00 |
Annual Sum or Average | 208.14 | 126.25 | 157.84 | 91.26 | 66.58 | 0.00 | 0.00 |
Minimum of Months | 99.93 | 47.54 | 72.75 | 4.72 | 56.50 | 0.00 | 0.00 |
Maximum of Months | 324.71 | 214.02 | 240.79 | 183.55 | 74.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595234E+09 | 0.860469E+09 | 0.491244E+09 | 0.343116E+09 | 0.148128E+09 | 0.00 | 0.00 |
February | 0.786004E+09 | 0.744768E+09 | 0.585687E+09 | 0.417762E+09 | 0.167925E+09 | 0.00 | 0.00 |
March | 0.128916E+10 | 0.747283E+09 | 0.877779E+09 | 0.616962E+09 | 0.260816E+09 | 0.00 | 0.00 |
April | 0.174488E+10 | 0.527502E+09 | 0.107102E+10 | 0.794888E+09 | 0.276134E+09 | 0.00 | 0.00 |
May | 0.210468E+10 | 0.416994E+09 | 0.121459E+10 | 0.901756E+09 | 0.312839E+09 | 0.00 | 0.00 |
June | 0.228514E+10 | 0.275653E+09 | 0.124189E+10 | 0.962315E+09 | 0.279571E+09 | 0.00 | 0.00 |
July | 0.207147E+10 | 0.222076E+09 | 0.111162E+10 | 0.800931E+09 | 0.310688E+09 | 0.00 | 0.00 |
August | 0.189042E+10 | 0.272109E+09 | 0.103447E+10 | 0.744301E+09 | 0.290171E+09 | 0.00 | 0.00 |
September | 0.163960E+10 | 0.395259E+09 | 0.923805E+09 | 0.691304E+09 | 0.232502E+09 | 0.00 | 0.00 |
October | 0.113654E+10 | 0.556076E+09 | 0.719784E+09 | 0.523117E+09 | 0.196667E+09 | 0.00 | 0.00 |
November | 0.725058E+09 | 0.789748E+09 | 0.552027E+09 | 0.411771E+09 | 0.140256E+09 | 0.00 | 0.00 |
December | 0.515540E+09 | 0.957520E+09 | 0.460354E+09 | 0.306698E+09 | 0.153656E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167837E+11 | 0.676546E+10 | 0.102843E+11 | 0.751492E+10 | 0.276935E+10 | 0.00 | 0.00 |
Minimum of Months | 0.515540E+09 | 0.222076E+09 | 0.460354E+09 | 0.306698E+09 | 0.140256E+09 | 0.00 | 0.00 |
Maximum of Months | 0.228514E+10 | 0.957520E+09 | 0.124189E+10 | 0.962315E+09 | 0.312839E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.398825E+10 | 0.273288E+10 | 0.303164E+10 | 0.229622E+10 | 0.735426E+09 | 0.00 | 0.00 |
February | 0.329495E+10 | 0.227200E+10 | 0.254216E+10 | 0.179223E+10 | 0.749931E+09 | 0.00 | 0.00 |
March | 0.281639E+10 | 0.228109E+10 | 0.229100E+10 | 0.132257E+10 | 0.968430E+09 | 0.00 | 0.00 |
April | 0.185684E+10 | 0.148685E+10 | 0.150636E+10 | 0.565598E+09 | 0.940767E+09 | 0.00 | 0.00 |
May | 0.152691E+10 | 0.101036E+10 | 0.109893E+10 | 0.156427E+09 | 0.942508E+09 | 0.00 | 0.00 |
June | 0.174943E+10 | 0.612414E+09 | 0.916388E+09 | 59459973.85 | 0.856928E+09 | 0.00 | 0.00 |
July | 0.182014E+10 | 0.548360E+09 | 0.965696E+09 | 91226655.22 | 0.874469E+09 | 0.00 | 0.00 |
August | 0.207126E+10 | 0.716710E+09 | 0.123277E+10 | 0.329391E+09 | 0.903382E+09 | 0.00 | 0.00 |
September | 0.300693E+10 | 0.119009E+10 | 0.186083E+10 | 0.969162E+09 | 0.891669E+09 | 0.00 | 0.00 |
October | 0.385367E+10 | 0.172001E+10 | 0.260724E+10 | 0.176320E+10 | 0.844040E+09 | 0.00 | 0.00 |
November | 0.411331E+10 | 0.240531E+10 | 0.303322E+10 | 0.231217E+10 | 0.721054E+09 | 0.00 | 0.00 |
December | 0.400535E+10 | 0.293409E+10 | 0.310462E+10 | 0.232976E+10 | 0.774869E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341034E+11 | 0.199102E+11 | 0.241909E+11 | 0.139874E+11 | 0.102035E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152691E+10 | 0.548360E+09 | 0.916388E+09 | 59459973.85 | 0.721054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.411331E+10 | 0.293409E+10 | 0.310462E+10 | 0.232976E+10 | 0.968430E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.401102E+10 | 0.263904E+10 | 0.303164E+10 | 0.229622E+10 | 0.735426E+09 | 0.00 | 0.00 |
February | 0.330988E+10 | 0.219234E+10 | 0.254216E+10 | 0.179223E+10 | 0.749931E+09 | 0.00 | 0.00 |
March | 0.283238E+10 | 0.220295E+10 | 0.229100E+10 | 0.132257E+10 | 0.968430E+09 | 0.00 | 0.00 |
April | 0.185323E+10 | 0.142565E+10 | 0.150636E+10 | 0.565598E+09 | 0.940767E+09 | 0.00 | 0.00 |
May | 0.151624E+10 | 0.955227E+09 | 0.109893E+10 | 0.156427E+09 | 0.942508E+09 | 0.00 | 0.00 |
June | 0.173940E+10 | 0.565454E+09 | 0.916388E+09 | 59459973.85 | 0.856928E+09 | 0.00 | 0.00 |
July | 0.181110E+10 | 0.501517E+09 | 0.965696E+09 | 91226655.22 | 0.874469E+09 | 0.00 | 0.00 |
August | 0.206026E+10 | 0.670913E+09 | 0.123277E+10 | 0.329391E+09 | 0.903382E+09 | 0.00 | 0.00 |
September | 0.299560E+10 | 0.113871E+10 | 0.186083E+10 | 0.969162E+09 | 0.891669E+09 | 0.00 | 0.00 |
October | 0.385488E+10 | 0.165311E+10 | 0.260724E+10 | 0.176320E+10 | 0.844040E+09 | 0.00 | 0.00 |
November | 0.412556E+10 | 0.233194E+10 | 0.303322E+10 | 0.231217E+10 | 0.721054E+09 | 0.00 | 0.00 |
December | 0.402898E+10 | 0.283764E+10 | 0.310462E+10 | 0.232976E+10 | 0.774869E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341385E+11 | 0.191145E+11 | 0.241909E+11 | 0.139874E+11 | 0.102035E+11 | 0.00 | 0.00 |
Minimum of Months | 0.151624E+10 | 0.501517E+09 | 0.916388E+09 | 59459973.85 | 0.721054E+09 | 0.00 | 0.00 |
Maximum of Months | 0.412556E+10 | 0.283764E+10 | 0.310462E+10 | 0.232976E+10 | 0.968430E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.811365E+09 | 0.532541E+09 | 0.623804E+09 | 0.472480E+09 | 0.151325E+09 | 0.00 | 0.00 |
February | 0.672260E+09 | 0.438262E+09 | 0.523087E+09 | 0.368778E+09 | 0.154309E+09 | 0.00 | 0.00 |
March | 0.579169E+09 | 0.437677E+09 | 0.471406E+09 | 0.272137E+09 | 0.199269E+09 | 0.00 | 0.00 |
April | 0.366531E+09 | 0.289052E+09 | 0.309956E+09 | 0.116380E+09 | 0.193576E+09 | 0.00 | 0.00 |
May | 0.267663E+09 | 0.205732E+09 | 0.226122E+09 | 32187156.39 | 0.193935E+09 | 0.00 | 0.00 |
June | 0.259657E+09 | 0.140047E+09 | 0.188560E+09 | 12234755.43 | 0.176325E+09 | 0.00 | 0.00 |
July | 0.278553E+09 | 0.127319E+09 | 0.198706E+09 | 18771212.68 | 0.179935E+09 | 0.00 | 0.00 |
August | 0.346447E+09 | 0.166501E+09 | 0.253661E+09 | 67776969.32 | 0.185884E+09 | 0.00 | 0.00 |
September | 0.555618E+09 | 0.263863E+09 | 0.382893E+09 | 0.199419E+09 | 0.183474E+09 | 0.00 | 0.00 |
October | 0.771802E+09 | 0.343718E+09 | 0.536477E+09 | 0.362804E+09 | 0.173673E+09 | 0.00 | 0.00 |
November | 0.841639E+09 | 0.463447E+09 | 0.624130E+09 | 0.475762E+09 | 0.148367E+09 | 0.00 | 0.00 |
December | 0.813069E+09 | 0.573227E+09 | 0.638822E+09 | 0.479381E+09 | 0.159441E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.656377E+10 | 0.398139E+10 | 0.497762E+10 | 0.287811E+10 | 0.209951E+10 | 0.00 | 0.00 |
Minimum of Months | 0.259657E+09 | 0.127319E+09 | 0.188560E+09 | 12234755.43 | 0.148367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.841639E+09 | 0.573227E+09 | 0.638822E+09 | 0.479381E+09 | 0.199269E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.32 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.73 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.69 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.47 | -2.7 | 4.72 | 3.37 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.20 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.01 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.90 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.10 | 12.00 | 3.28 | 15.47 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.80 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.00 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.23 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.89 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.89 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.90 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.36 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.84 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.49 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.18 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.19 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.18 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.16 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.85 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.82 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.87 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.43 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.94 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.94 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.16 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.3 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.4 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.3 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.5 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.97 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.40 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.97 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.88 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -2.9 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.0 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.4 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.97 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.15 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.74 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.71 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.10 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.18 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.87 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.16 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.64 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.62 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.55 | 03-NOV-13:20 | 22.07 | 7.93 | 2.10 | 9.59 | 80.17 | 943.83 |
December | 8.27 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.27 | 12.80 | -0.6 | 1.50 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.87 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 943.83 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.70 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.39 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.10 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.27 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.250783E+10 | -.207672E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -431105974.7 | 59.00 | 0.00 | 0.00 |
February | 0.227195E+10 | -.188937E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -382578307.5 | 58.99 | 0.00 | 0.00 |
March | 0.247704E+10 | -.206526E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -411777890.4 | 58.99 | 0.00 | 0.00 |
April | 0.221068E+10 | -.183295E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -377729447.0 | 58.99 | 0.00 | 0.00 |
May | 0.211989E+10 | -.174088E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -379012341.7 | 58.99 | 0.00 | 0.00 |
June | 0.193315E+10 | -.157320E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -359953804.3 | 58.99 | 0.00 | 0.00 |
July | 0.187230E+10 | -.150062E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -371677205.9 | 58.99 | 0.00 | 0.00 |
August | 0.192453E+10 | -.154987E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374661262.1 | 58.99 | 0.00 | 0.00 |
September | 0.191827E+10 | -.155186E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -366418774.9 | 58.99 | 0.00 | 0.00 |
October | 0.210514E+10 | -.171421E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -390933307.5 | 59.00 | 0.00 | 0.00 |
November | 0.220299E+10 | -.179940E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -403580546.6 | 59.00 | 0.00 | 0.00 |
December | 0.243465E+10 | -.200206E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -432589345.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.259784E+11 | -.212964E+11 | 8760.00 | -.468202E+10 | 58.99 | |||||
Minimum of Months | 0.187230E+10 | -.207672E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -432589345.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.250783E+10 | -.150062E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -359953804.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | ||||||||||
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115477E+11 | 68157.00 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.661480E+10 | 68157.00 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332040E+10 | 68157.00 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181562E+09 | 68157.00 | 11-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1607059.22 | 3564.59 | 14-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20099512.83 | 9881.61 | 25-OCT-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436802E+10 | 68157.00 | 05-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141584E+11 | 68157.00 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402126E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141584E+11 | 68157.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103373E+11 | 278797.90 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.453525E+10 | 278797.90 | 02-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160788E+10 | 278797.90 | 02-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17867006.48 | 53065.97 | 03-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17307483.99 | 30454.44 | 12-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 932640.17 | 3108.80 | 13-JUN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273701E+10 | 278797.90 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155304E+11 | 278797.90 | 03-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347839E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155304E+11 | 278797.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129916E+10 | 39333.82 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.820943E+09 | 39333.82 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435489E+09 | 39333.82 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33980264.84 | 20297.24 | 11-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3777628.63 | 5965.54 | 16-MAY-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3531000.08 | 6521.72 | 11-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2368303.77 | 5793.04 | 26-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43364.76 | 144.55 | 19-OCT-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.417229E+09 | 39333.82 | 26-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175855E+10 | 39333.82 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.477507E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175855E+10 | 39333.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224480E+10 | 35365.97 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135395E+10 | 35365.97 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898640E+09 | 35365.97 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89576046.82 | 28556.02 | 11-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4449318.03 | 6392.31 | 14-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12468.73 | 41.56 | 02-JUN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 149937.54 | 499.79 | 29-SEP-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1235223.18 | 793.35 | 25-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.869514E+09 | 35365.97 | 05-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282101E+10 | 35365.97 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828334E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282101E+10 | 35365.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.638148E+10 | 23923.61 | 26-JAN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348701E+10 | 19343.69 | 02-FEB-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200674E+10 | 20551.62 | 01-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.354072E+09 | 10662.87 | 11-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175754.55 | 292.92 | 23-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340682E+09 | 8880.66 | 24-OCT-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.306211E+10 | 21095.38 | 27-NOV-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747165E+10 | 29451.15 | 26-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231039E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.747165E+10 | 29451.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7386293.81 | 7386293.81 | 1378.33 | 21-FEB-16:00 | 1378.33 | 0.00 |
March | 0.00 | 0.00 | 0.401829E+09 | 0.401829E+09 | 6686.27 | 22-MAR-14:20 | 6686.27 | 0.00 |
April | 0.00 | 0.00 | 0.873269E+10 | 0.866194E+10 | 51358.38 | 29-APR-04:01 | 43219.91 | 0.00 |
May | 0.00 | 0.00 | 0.228408E+11 | 0.219988E+11 | 54693.28 | 28-MAY-06:43 | 35120.43 | 0.00 |
June | 0.00 | 0.00 | 0.363697E+11 | 0.345443E+11 | 55193.65 | 28-JUN-04:01 | 31163.67 | 0.00 |
July | 0.00 | 0.00 | 0.425814E+11 | 0.352484E+11 | 59155.50 | 21-JUL-04:01 | 24807.73 | 0.00 |
August | 0.00 | 0.00 | 0.343077E+11 | 0.297028E+11 | 58300.39 | 02-AUG-04:01 | 30308.15 | 0.00 |
September | 0.00 | 0.00 | 0.249168E+11 | 0.212307E+11 | 57603.11 | 22-SEP-04:01 | 29759.24 | 0.00 |
October | 0.00 | 0.00 | 0.771410E+10 | 0.678218E+10 | 55896.03 | 04-OCT-04:01 | 29863.00 | 0.00 |
November | 0.00 | 0.00 | 0.216044E+09 | 0.214178E+09 | 6968.94 | 09-NOV-15:30 | 6968.94 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.178088E+12 | 0.158792E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.425814E+11 | 0.352484E+11 | 59155.50 | 43219.91 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 38748950.54 | 38748437.42 | 6102.13 | 03-JAN-15:10 | 6102.13 | 0.00 |
February | 0.00 | 0.00 | 0.277621E+10 | 0.277621E+10 | 36254.59 | 21-FEB-15:20 | 36254.59 | 0.00 |
March | 0.00 | 0.00 | 0.105709E+11 | 0.105709E+11 | 55905.51 | 22-MAR-14:10 | 55905.51 | 0.00 |
April | 0.00 | 0.00 | 0.573200E+11 | 0.567658E+11 | 198762.12 | 29-APR-04:01 | 168040.49 | 0.00 |
May | 0.00 | 0.00 | 0.109159E+12 | 0.104965E+12 | 209262.34 | 28-MAY-06:01 | 136130.39 | 0.00 |
June | 0.00 | 0.00 | 0.149641E+12 | 0.141248E+12 | 212649.43 | 04-JUN-06:01 | 143443.86 | 0.00 |
July | 0.00 | 0.00 | 0.176273E+12 | 0.141425E+12 | 227327.56 | 21-JUL-04:01 | 104465.64 | 0.00 |
August | 0.00 | 0.00 | 0.149786E+12 | 0.127557E+12 | 224099.03 | 03-AUG-04:01 | 131701.42 | 0.00 |
September | 0.00 | 0.00 | 0.120819E+12 | 0.101926E+12 | 221223.53 | 22-SEP-04:01 | 121523.57 | 0.00 |
October | 0.00 | 0.00 | 0.514351E+11 | 0.453237E+11 | 215946.66 | 04-OCT-04:01 | 120703.59 | 0.00 |
November | 0.00 | 0.00 | 0.436446E+10 | 0.424744E+10 | 53357.72 | 03-NOV-16:00 | 50916.14 | 0.00 |
December | 0.00 | 0.00 | 119653.43 | 119653.43 | 16.54 | 22-DEC-16:20 | 16.54 | 0.00 |
Annual Sum or Average | 0.832185E+12 | 0.736843E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 119653.43 | 119653.43 | 16.54 | 16.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.176273E+12 | 0.141425E+12 | 227327.56 | 168040.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 99693220.46 | 99614023.33 | 4103.97 | 03-JAN-15:00 | 4103.97 | 0.00 |
February | 0.00 | 0.00 | 0.928046E+09 | 0.928045E+09 | 8883.32 | 21-FEB-16:00 | 8883.32 | 0.00 |
March | 0.00 | 0.00 | 0.179013E+10 | 0.179013E+10 | 9512.78 | 22-MAR-13:40 | 9512.78 | 0.00 |
April | 0.00 | 0.00 | 0.767549E+10 | 0.763452E+10 | 28459.24 | 29-APR-04:01 | 24310.10 | 0.00 |
May | 0.00 | 0.00 | 0.138543E+11 | 0.134273E+11 | 30246.93 | 28-MAY-06:43 | 19407.47 | 0.00 |
June | 0.00 | 0.00 | 0.197304E+11 | 0.188317E+11 | 30541.90 | 28-JUN-04:01 | 17223.96 | 0.00 |
July | 0.00 | 0.00 | 0.236482E+11 | 0.195907E+11 | 32761.67 | 21-JUL-04:01 | 13706.05 | 0.00 |
August | 0.00 | 0.00 | 0.213477E+11 | 0.186983E+11 | 32299.61 | 02-AUG-04:01 | 16893.73 | 0.00 |
September | 0.00 | 0.00 | 0.191853E+11 | 0.167682E+11 | 31945.11 | 22-SEP-04:01 | 16924.05 | 0.00 |
October | 0.00 | 0.00 | 0.101860E+11 | 0.929863E+10 | 30980.72 | 04-OCT-04:01 | 16935.98 | 0.00 |
November | 0.00 | 0.00 | 0.187712E+10 | 0.184394E+10 | 13167.83 | 09-NOV-15:10 | 13167.83 | 0.00 |
December | 0.00 | 0.00 | 109898.16 | 109885.36 | 40.19 | 23-DEC-15:00 | 40.19 | 0.00 |
Annual Sum or Average | 0.120322E+12 | 0.108911E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 109898.16 | 109885.36 | 40.19 | 40.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236482E+11 | 0.195907E+11 | 32761.67 | 24310.10 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 45517076.06 | 45455806.67 | 2473.33 | 03-JAN-15:00 | 2473.33 | 0.00 |
February | 0.00 | 0.00 | 0.597480E+09 | 0.597480E+09 | 7112.47 | 20-FEB-15:30 | 7112.47 | 0.00 |
March | 0.00 | 0.00 | 0.114312E+10 | 0.114312E+10 | 7271.26 | 22-MAR-13:40 | 7271.26 | 0.00 |
April | 0.00 | 0.00 | 0.601029E+10 | 0.597489E+10 | 26022.02 | 29-APR-04:02 | 25001.60 | 0.00 |
May | 0.00 | 0.00 | 0.113551E+11 | 0.109797E+11 | 27038.78 | 28-MAY-06:01 | 16944.19 | 0.00 |
June | 0.00 | 0.00 | 0.168671E+11 | 0.160708E+11 | 27542.80 | 28-JUN-04:01 | 15279.25 | 0.00 |
July | 0.00 | 0.00 | 0.203165E+11 | 0.166716E+11 | 29572.59 | 21-JUL-04:01 | 12102.91 | 0.00 |
August | 0.00 | 0.00 | 0.182248E+11 | 0.158653E+11 | 29138.03 | 02-AUG-04:01 | 14951.43 | 0.00 |
September | 0.00 | 0.00 | 0.163460E+11 | 0.141768E+11 | 28810.00 | 22-SEP-04:01 | 14953.31 | 0.00 |
October | 0.00 | 0.00 | 0.824331E+10 | 0.749814E+10 | 27948.13 | 04-OCT-04:01 | 15050.48 | 0.00 |
November | 0.00 | 0.00 | 0.133262E+10 | 0.130568E+10 | 11357.62 | 09-NOV-15:10 | 11357.62 | 0.00 |
December | 0.00 | 0.00 | 42507.04 | 42496.54 | 0.91 | 16-DEC-12:50 | 0.91 | 0.00 |
Annual Sum or Average | 0.100482E+12 | 0.903291E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 42507.04 | 42496.54 | 0.91 | 0.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203165E+11 | 0.166716E+11 | 29572.59 | 25001.60 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.423993E+10 | 0.56 | 2902.71 | 01-JAN-07:01 | 1.04 |
February | 0.316921E+10 | 0.47 | 2902.71 | 01-FEB-05:01 | 1.04 |
March | 0.291833E+10 | 0.39 | 2902.71 | 01-MAR-05:01 | 1.04 |
April | 0.100724E+10 | 0.14 | 2902.71 | 01-APR-04:03 | 1.04 |
May | 0.123375E+09 | 0.02 | 2902.71 | 01-MAY-07:10 | 1.04 |
June | 3700955.67 | 0.00 | 2902.71 | 29-JUN-07:06 | 1.02 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 6351406.65 | 0.00 | 2902.71 | 14-AUG-07:09 | 1.02 |
September | 48402694.77 | 0.01 | 2902.71 | 23-SEP-16:00 | 1.02 |
October | 0.101043E+10 | 0.13 | 2902.71 | 01-OCT-07:04 | 1.03 |
November | 0.312987E+10 | 0.43 | 2902.71 | 01-NOV-07:10 | 1.03 |
December | 0.435904E+10 | 0.58 | 2902.71 | 01-DEC-05:01 | 1.03 |
Annual Sum or Average | 0.200159E+11 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.435904E+10 | 0.58 | 2902.71 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.540063E+10 | 0.65 | 3305.14 | 05-JAN-14:30 | 1.04 |
February | 0.488005E+10 | 0.65 | 3305.14 | 03-FEB-07:40 | 1.04 |
March | 0.543722E+10 | 0.65 | 3305.14 | 02-MAR-07:25 | 1.04 |
April | 0.518362E+10 | 0.63 | 3305.14 | 02-APR-16:50 | 1.04 |
May | 0.541327E+10 | 0.64 | 3305.14 | 03-MAY-08:65 | 1.04 |
June | 0.532161E+10 | 0.65 | 3305.14 | 06-JUN-06:10 | 1.03 |
July | 0.543446E+10 | 0.64 | 3305.14 | 04-JUL-07:04 | 1.02 |
August | 0.550955E+10 | 0.64 | 3305.14 | 01-AUG-07:08 | 1.02 |
September | 0.527171E+10 | 0.64 | 3305.14 | 01-SEP-19:05 | 1.03 |
October | 0.530849E+10 | 0.62 | 3305.14 | 02-OCT-19:13 | 1.03 |
November | 0.515935E+10 | 0.64 | 3305.14 | 17-NOV-07:43 | 1.04 |
December | 0.542966E+10 | 0.67 | 3305.14 | 02-DEC-07:55 | 1.04 |
Annual Sum or Average | 0.637496E+11 | 0.64 | |||
Minimum of Months | 0.488005E+10 | 0.62 | 3305.14 | 1.02 | |
Maximum of Months | 0.550955E+10 | 0.67 | 3305.14 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.288217E+11 | 0.99 | 17922.77 | 03-JAN-17:40 | 1.61 |
February | 0.261007E+11 | 0.98 | 17922.77 | 01-FEB-07:07 | 1.61 |
March | 0.292367E+11 | 0.98 | 17922.77 | 01-MAR-20:20 | 1.61 |
April | 0.281822E+11 | 0.97 | 17922.77 | 11-APR-18:57 | 1.61 |
May | 0.293007E+11 | 0.98 | 17922.77 | 01-MAY-05:20 | 1.61 |
June | 0.287901E+11 | 1.00 | 17922.77 | 11-JUN-07:10 | 1.61 |
July | 0.293716E+11 | 0.98 | 17922.77 | 01-JUL-04:01 | 1.59 |
August | 0.298265E+11 | 0.99 | 17922.77 | 12-AUG-08:00 | 1.58 |
September | 0.286400E+11 | 0.98 | 17922.77 | 09-SEP-06:40 | 1.58 |
October | 0.288369E+11 | 0.96 | 17922.77 | 06-OCT-06:00 | 1.59 |
November | 0.277002E+11 | 0.96 | 17922.77 | 03-NOV-18:30 | 1.59 |
December | 0.289212E+11 | 1.00 | 17922.77 | 04-DEC-19:50 | 1.60 |
Annual Sum or Average | 0.343728E+12 | 0.98 | |||
Minimum of Months | 0.261007E+11 | 0.96 | 17922.77 | 1.58 | |
Maximum of Months | 0.298265E+11 | 1.00 | 17922.77 | 1.61 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.291950E+10 | 0.64 | 1812.53 | 03-JAN-08:00 | 1.03 |
February | 0.264731E+10 | 0.64 | 1812.53 | 01-FEB-06:10 | 1.04 |
March | 0.296146E+10 | 0.64 | 1812.53 | 01-MAR-06:43 | 1.04 |
April | 0.285217E+10 | 0.63 | 1812.53 | 02-APR-07:01 | 1.03 |
May | 0.297795E+10 | 0.64 | 1812.53 | 03-MAY-07:23 | 1.04 |
June | 0.291612E+10 | 0.65 | 1812.53 | 02-JUN-05:30 | 1.03 |
July | 0.297980E+10 | 0.64 | 1812.53 | 09-JUL-10:30 | 1.02 |
August | 0.303005E+10 | 0.65 | 1812.53 | 01-AUG-06:00 | 1.02 |
September | 0.291452E+10 | 0.64 | 1812.53 | 01-SEP-05:10 | 1.02 |
October | 0.292828E+10 | 0.63 | 1812.53 | 01-OCT-07:15 | 1.03 |
November | 0.280501E+10 | 0.62 | 1812.53 | 02-NOV-19:13 | 1.03 |
December | 0.293096E+10 | 0.65 | 1812.53 | 01-DEC-12:00 | 1.04 |
Annual Sum or Average | 0.348631E+11 | 0.64 | |||
Minimum of Months | 0.264731E+10 | 0.62 | 1812.53 | 1.02 | |
Maximum of Months | 0.303005E+10 | 0.65 | 1812.53 | 1.04 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.257599E+10 | 0.65 | 1594.68 | 01-JAN-14:40 | 1.03 |
February | 0.233411E+10 | 0.65 | 1594.68 | 01-FEB-06:45 | 1.04 |
March | 0.261008E+10 | 0.65 | 1594.68 | 01-MAR-06:03 | 1.04 |
April | 0.250281E+10 | 0.63 | 1594.68 | 01-APR-11:45 | 1.04 |
May | 0.260828E+10 | 0.64 | 1594.68 | 01-MAY-08:23 | 1.04 |
June | 0.256328E+10 | 0.65 | 1594.68 | 01-JUN-05:10 | 1.04 |
July | 0.261176E+10 | 0.64 | 1594.68 | 01-JUL-05:20 | 1.03 |
August | 0.265784E+10 | 0.64 | 1594.68 | 01-AUG-05:05 | 1.02 |
September | 0.255655E+10 | 0.64 | 1594.68 | 01-SEP-05:20 | 1.02 |
October | 0.257165E+10 | 0.62 | 1594.68 | 01-OCT-07:01 | 1.03 |
November | 0.247058E+10 | 0.63 | 1594.68 | 07-NOV-16:50 | 1.03 |
December | 0.258715E+10 | 0.65 | 1594.68 | 01-DEC-07:07 | 1.03 |
Annual Sum or Average | 0.306501E+11 | 0.64 | |||
Minimum of Months | 0.233411E+10 | 0.62 | 1594.68 | 1.02 | |
Maximum of Months | 0.265784E+10 | 0.65 | 1594.68 | 1.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.86 | 0.00 |
February | 1.37 | 0.00 |
March | 0.52 | 0.00 |
April | 0.14 | 0.00 |
May | 1.12 | 0.00 |
June | 1.99 | 0.00 |
July | 2.30 | 0.00 |
August | 2.34 | 0.00 |
September | 0.49 | 0.00 |
October | 0.00 | 0.00 |
November | 0.56 | 0.00 |
December | 2.55 | 0.00 |
Annual Sum or Average | 15.23 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.55 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.18 | 11.93 |
February | 0.68 | 17.93 |
March | 1.85 | 20.23 |
April | 1.39 | 6.45 |
May | 3.18 | 0.00 |
June | 1.35 | 0.00 |
July | 1.88 | 0.00 |
August | 1.82 | 0.00 |
September | 0.97 | 0.00 |
October | 0.67 | 3.22 |
November | 1.45 | 21.14 |
December | 0.36 | 22.86 |
Annual Sum or Average | 15.78 | 6.46 |
Minimum of Months | 0.18 | 0.00 |
Maximum of Months | 3.18 | 22.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.24 | 0.86 |
February | 0.33 | 1.83 |
March | 0.68 | 1.69 |
April | 1.32 | 0.18 |
May | 1.08 | 0.00 |
June | 2.31 | 0.00 |
July | 1.98 | 0.00 |
August | 2.46 | 0.00 |
September | 1.28 | 0.00 |
October | 0.91 | 0.00 |
November | 0.70 | 0.55 |
December | 0.00 | 0.00 |
Annual Sum or Average | 13.29 | 0.19 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.46 | 1.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.18 | 0.00 |
February | 0.04 | 2.44 |
March | 0.17 | 1.22 |
April | 0.47 | 0.00 |
May | 1.50 | 0.00 |
June | 1.68 | 0.00 |
July | 2.39 | 0.00 |
August | 2.90 | 0.00 |
September | 0.61 | 0.00 |
October | 0.77 | 0.27 |
November | 0.44 | 1.79 |
December | 0.08 | 0.00 |
Annual Sum or Average | 11.22 | 0.12 |
Minimum of Months | 0.04 | 0.00 |
Maximum of Months | 2.90 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 52.36 | 0.00 |
February | 47.99 | 0.00 |
March | 47.70 | 0.00 |
April | 23.05 | 0.00 |
May | 10.97 | 0.00 |
June | 5.26 | 0.00 |
July | 3.78 | 0.00 |
August | 3.81 | 0.00 |
September | 3.42 | 0.00 |
October | 21.17 | 0.00 |
November | 37.73 | 0.00 |
December | 49.30 | 0.00 |
Annual Sum or Average | 306.54 | 0.00 |
Minimum of Months | 3.42 | 0.00 |
Maximum of Months | 52.36 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.540063E+10 | 0.145713E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.488251E+10 | 0.834674E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.557009E+10 | 0.418977E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.812360E+10 | 0.229101E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.130305E+11 | 2027834.98 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176956E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.192278E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.167212E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.133543E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.781214E+10 | 25362161.30 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.522997E+10 | 0.551169E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.542966E+10 | 0.178655E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.122478E+12 | 0.507415E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.488251E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.192278E+11 | 0.178655E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.288344E+11 | 0.130439E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.270017E+11 | 0.572272E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.326386E+11 | 0.202887E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.470333E+11 | 22545118.58 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.655223E+11 | 21839096.52 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.802423E+11 | 1176833.03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.866261E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.787911E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.674908E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.452599E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.290992E+11 | 0.345364E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.289212E+11 | 0.195967E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.617461E+12 | 0.438914E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.270017E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.866261E+11 | 0.195967E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.294899E+10 | 0.162395E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.291793E+10 | 0.102618E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.348846E+10 | 0.544361E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.519897E+10 | 42475331.06 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.729671E+10 | 4722035.79 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.927872E+10 | 4413750.10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.101939E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.951359E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.856100E+10 | 2960379.71 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.584384E+10 | 54205.95 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.334249E+10 | 0.521536E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.293099E+10 | 0.219818E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.715156E+11 | 0.596884E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.291793E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.101939E+11 | 0.219818E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.258960E+10 | 0.280600E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.250992E+10 | 0.169244E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.295063E+10 | 0.112330E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.436372E+10 | 0.111970E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.618675E+10 | 5561647.54 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.804665E+10 | 15585.91 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.884996E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.822941E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.740042E+10 | 187421.92 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.494996E+10 | 1544028.97 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.285426E+10 | 0.108689E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.258716E+10 | 0.352626E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.615184E+11 | 0.103542E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.250992E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.884996E+10 | 0.352626E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.540063E+10 | 0.00 | 0.115477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.488005E+10 | 7386293.81 | 0.661480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543722E+10 | 0.401829E+09 | 0.332040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.518362E+10 | 0.873269E+10 | 0.181562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541327E+10 | 0.228408E+11 | 1607059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.532161E+10 | 0.363697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543446E+10 | 0.425814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.550955E+10 | 0.343077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.527171E+10 | 0.249168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.530849E+10 | 0.771410E+10 | 20099512.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.515935E+10 | 0.216044E+09 | 0.436802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.542966E+10 | 0.00 | 0.141584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.637496E+11 | 0.178088E+12 | 0.402126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.488005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.550955E+10 | 0.425814E+11 | 0.141584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.288217E+11 | 38748950.54 | 0.103373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261007E+11 | 0.277621E+10 | 0.453525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292367E+11 | 0.105709E+11 | 0.160788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281822E+11 | 0.573200E+11 | 17867006.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293007E+11 | 0.109159E+12 | 17307483.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.287901E+11 | 0.149641E+12 | 932640.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.293716E+11 | 0.176273E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298265E+11 | 0.149786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286400E+11 | 0.120819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288369E+11 | 0.514351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277002E+11 | 0.436446E+10 | 0.273701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289212E+11 | 119653.43 | 0.155304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343728E+12 | 0.832185E+12 | 0.347839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.261007E+11 | 119653.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298265E+11 | 0.176273E+12 | 0.155304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.291950E+10 | 99693220.46 | 0.129916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264731E+10 | 0.928046E+09 | 0.820943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296146E+10 | 0.179013E+10 | 0.435489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.285217E+10 | 0.767549E+10 | 33980264.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.297795E+10 | 0.138543E+11 | 3777628.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.291612E+10 | 0.197304E+11 | 3531000.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.297980E+10 | 0.236482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.303005E+10 | 0.213477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.291452E+10 | 0.191853E+11 | 2368303.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292828E+10 | 0.101860E+11 | 43364.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280501E+10 | 0.187712E+10 | 0.417229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293096E+10 | 109898.16 | 0.175855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348631E+11 | 0.120322E+12 | 0.477507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.264731E+10 | 109898.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.303005E+10 | 0.236482E+11 | 0.175855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.257599E+10 | 45517076.06 | 0.224480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233411E+10 | 0.597480E+09 | 0.135395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261008E+10 | 0.114312E+10 | 0.898640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250281E+10 | 0.601029E+10 | 89576046.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260828E+10 | 0.113551E+11 | 4449318.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256328E+10 | 0.168671E+11 | 12468.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261176E+10 | 0.203165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.265784E+10 | 0.182248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255655E+10 | 0.163460E+11 | 149937.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257165E+10 | 0.824331E+10 | 1235223.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247058E+10 | 0.133262E+10 | 0.869514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258715E+10 | 42507.04 | 0.282101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306501E+11 | 0.100482E+12 | 0.828334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.233411E+10 | 42507.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.265784E+10 | 0.203165E+11 | 0.282101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.540063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.488005E+10 | 0.00 | 0.00 | 0.00 | 2456726.60 | 0.00 | 0.834674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543722E+10 | 0.00 | 0.00 | 0.00 | 0.132867E+09 | 0.00 | 0.418977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.518362E+10 | 0.00 | 0.00 | 0.00 | 0.293998E+10 | 0.00 | 0.229101E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541327E+10 | 0.00 | 0.00 | 0.00 | 0.761725E+10 | 0.00 | 2027834.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.532161E+10 | 0.00 | 0.00 | 0.00 | 0.123740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543446E+10 | 0.00 | 0.00 | 0.00 | 0.137933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.550955E+10 | 0.00 | 0.00 | 0.00 | 0.112116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.527171E+10 | 0.00 | 0.00 | 0.00 | 0.808262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.530849E+10 | 0.00 | 0.00 | 0.00 | 0.250365E+10 | 0.00 | 25362161.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.515935E+10 | 0.00 | 0.00 | 0.00 | 70614535.29 | 0.00 | 0.551169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.542966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.637496E+11 | 0.00 | 0.00 | 0.00 | 0.587284E+11 | 0.00 | 0.507415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.488005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.550955E+10 | 0.00 | 0.00 | 0.00 | 0.137933E+11 | 0.00 | 0.178655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.288217E+11 | 0.00 | 0.00 | 0.00 | 12765793.19 | 0.00 | 0.130439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261007E+11 | 0.00 | 0.00 | 0.00 | 0.900973E+09 | 0.00 | 0.572272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292367E+11 | 0.00 | 0.00 | 0.00 | 0.340183E+10 | 0.00 | 0.202887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.281822E+11 | 0.00 | 0.00 | 0.00 | 0.188511E+11 | 0.00 | 22545118.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293007E+11 | 0.00 | 0.00 | 0.00 | 0.362216E+11 | 0.00 | 21839096.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.287901E+11 | 0.00 | 0.00 | 0.00 | 0.514521E+11 | 0.00 | 1176833.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.293716E+11 | 0.00 | 0.00 | 0.00 | 0.572544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.298265E+11 | 0.00 | 0.00 | 0.00 | 0.489646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286400E+11 | 0.00 | 0.00 | 0.00 | 0.388508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.288369E+11 | 0.00 | 0.00 | 0.00 | 0.164230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277002E+11 | 0.00 | 0.00 | 0.00 | 0.139902E+10 | 0.00 | 0.345364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289212E+11 | 0.00 | 0.00 | 0.00 | 39690.01 | 0.00 | 0.195967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343728E+12 | 0.00 | 0.00 | 0.00 | 0.273732E+12 | 0.00 | 0.438914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.261007E+11 | 0.00 | 0.00 | 0.00 | 39690.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.298265E+11 | 0.00 | 0.00 | 0.00 | 0.572544E+11 | 0.00 | 0.195967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.291950E+10 | 0.00 | 0.00 | 0.00 | 29488609.77 | 0.00 | 0.162395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264731E+10 | 0.00 | 0.00 | 0.00 | 0.270618E+09 | 0.00 | 0.102618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.296146E+10 | 0.00 | 0.00 | 0.00 | 0.527008E+09 | 0.00 | 0.544361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.285217E+10 | 0.00 | 0.00 | 0.00 | 0.234680E+10 | 0.00 | 42475331.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.297795E+10 | 0.00 | 0.00 | 0.00 | 0.431876E+10 | 0.00 | 4722035.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.291612E+10 | 0.00 | 0.00 | 0.00 | 0.636260E+10 | 0.00 | 4413750.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.297980E+10 | 0.00 | 0.00 | 0.00 | 0.721414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.303005E+10 | 0.00 | 0.00 | 0.00 | 0.648354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.291452E+10 | 0.00 | 0.00 | 0.00 | 0.564648E+10 | 0.00 | 2960379.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.292828E+10 | 0.00 | 0.00 | 0.00 | 0.291557E+10 | 0.00 | 54205.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280501E+10 | 0.00 | 0.00 | 0.00 | 0.537481E+09 | 0.00 | 0.521536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293096E+10 | 0.00 | 0.00 | 0.00 | 33675.68 | 0.00 | 0.219818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348631E+11 | 0.00 | 0.00 | 0.00 | 0.366525E+11 | 0.00 | 0.596884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.264731E+10 | 0.00 | 0.00 | 0.00 | 33675.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.303005E+10 | 0.00 | 0.00 | 0.00 | 0.721414E+10 | 0.00 | 0.219818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.257599E+10 | 0.00 | 0.00 | 0.00 | 13613589.13 | 0.00 | 0.280600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233411E+10 | 0.00 | 0.00 | 0.00 | 0.175810E+09 | 0.00 | 0.169244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261008E+10 | 0.00 | 0.00 | 0.00 | 0.340555E+09 | 0.00 | 0.112330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250281E+10 | 0.00 | 0.00 | 0.00 | 0.186091E+10 | 0.00 | 0.111970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260828E+10 | 0.00 | 0.00 | 0.00 | 0.357847E+10 | 0.00 | 5561647.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256328E+10 | 0.00 | 0.00 | 0.00 | 0.548338E+10 | 0.00 | 15585.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261176E+10 | 0.00 | 0.00 | 0.00 | 0.623820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.265784E+10 | 0.00 | 0.00 | 0.00 | 0.557156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255655E+10 | 0.00 | 0.00 | 0.00 | 0.484387E+10 | 0.00 | 187421.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.257165E+10 | 0.00 | 0.00 | 0.00 | 0.237831E+10 | 0.00 | 1544028.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247058E+10 | 0.00 | 0.00 | 0.00 | 0.383678E+09 | 0.00 | 0.108689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258715E+10 | 0.00 | 0.00 | 0.00 | 13026.63 | 0.00 | 0.352626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306501E+11 | 0.00 | 0.00 | 0.00 | 0.308684E+11 | 0.00 | 0.103542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.233411E+10 | 0.00 | 0.00 | 0.00 | 13026.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.265784E+10 | 0.00 | 0.00 | 0.00 | 0.623820E+10 | 0.00 | 0.352626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.846872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544573E+10 | 0.00 | 0.00 | 0.25 |
February | 0.193678E+10 | 0.00 | 0.00 | 8912.93 | 0.00 | 0.312449E+10 | 92451966.78 | 0.00 | 0.30 |
March | 0.298836E+10 | 0.00 | 0.00 | 742295.45 | 0.00 | 0.158227E+10 | 0.131237E+10 | 0.00 | 0.45 |
April | 0.761372E+09 | 99648439.65 | 0.00 | 10866343.64 | 1462254.46 | 0.125744E+09 | 0.414289E+10 | 0.00 | 0.70 |
May | 0.108380E+09 | 0.101364E+10 | 0.00 | 15082882.85 | 0.00 | 0.00 | 0.285541E+10 | 0.00 | 0.69 |
June | 270748.54 | 0.246382E+10 | 0.00 | 18717966.16 | 233185.55 | 0.00 | 0.102733E+10 | 0.00 | 0.56 |
July | 255273.35 | 0.632547E+10 | 0.00 | 6686722.71 | 1341406.25 | 0.00 | 0.141586E+09 | 0.00 | 0.54 |
August | 18025092.14 | 0.355512E+10 | 0.00 | 10465206.08 | 17634.85 | 0.00 | 0.144013E+10 | 0.00 | 0.69 |
September | 79678829.48 | 0.228581E+10 | 0.00 | 12257269.48 | 0.00 | 0.00 | 0.232644E+10 | 0.00 | 0.72 |
October | 0.934318E+09 | 0.500878E+09 | 0.00 | 8035595.56 | 0.00 | 28815985.24 | 0.518213E+10 | 0.00 | 0.85 |
November | 0.272183E+10 | 0.00 | 0.00 | 686420.65 | 0.00 | 0.204154E+10 | 0.861820E+09 | 0.00 | 0.36 |
December | 0.665217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615226E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.110614E+11 | 0.162444E+11 | 0.00 | 83549615.50 | 3054481.12 | 0.185008E+11 | 0.193825E+11 | 0.00 | 0.53 |
Minimum of Months | 255273.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.298836E+10 | 0.632547E+10 | 0.00 | 18717966.16 | 1462254.46 | 0.615226E+10 | 0.518213E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.384455E+11 | 0.00 | 0.00 | 4289301.76 | 0.00 | 0.775894E+10 | 0.936214E+10 | 0.00 | 0.55 |
February | 0.252505E+11 | 0.00 | 0.00 | 16004667.13 | 0.00 | 0.276159E+10 | 0.208293E+11 | 0.00 | 0.73 |
March | 0.169323E+11 | 0.00 | 0.00 | 46000432.02 | 0.00 | 0.717213E+09 | 0.377638E+11 | 0.00 | 0.96 |
April | 0.328382E+10 | 0.157144E+10 | 0.00 | 77971547.70 | 0.00 | 0.00 | 0.294806E+11 | 0.00 | 0.97 |
May | 0.291195E+09 | 0.100743E+11 | 0.00 | 70941102.87 | 851550.34 | 0.00 | 0.137426E+11 | 0.00 | 0.85 |
June | 0.00 | 0.229954E+11 | 0.00 | 59982643.60 | 101970.59 | 0.00 | 0.343840E+10 | 0.00 | 0.74 |
July | 0.00 | 0.461883E+11 | 0.00 | 5426136.07 | 26650700.62 | 0.00 | 0.281160E+09 | 0.00 | 0.72 |
August | 9330808.02 | 0.280376E+11 | 0.00 | 35030167.29 | 27980074.11 | 0.00 | 0.488298E+10 | 0.00 | 0.84 |
September | 0.173555E+09 | 0.189516E+11 | 0.00 | 48681413.56 | 467964.43 | 0.00 | 0.958208E+10 | 0.00 | 0.88 |
October | 0.412979E+10 | 0.443692E+10 | 0.00 | 79021199.56 | 0.00 | 0.00 | 0.342639E+11 | 0.00 | 1.09 |
November | 0.210431E+11 | 0.00 | 0.00 | 32227829.51 | 0.00 | 0.145048E+10 | 0.318245E+11 | 0.00 | 0.82 |
December | 0.409175E+11 | 0.00 | 0.00 | 2635982.48 | 0.00 | 0.103062E+11 | 0.689649E+10 | 0.00 | 0.52 |
Annual Sum or Average | 0.150477E+12 | 0.132256E+12 | 0.00 | 0.478212E+09 | 56052260.09 | 0.229944E+11 | 0.202348E+12 | 0.00 | 0.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2635982.48 | 0.00 | 0.00 | 0.281160E+09 | 0.00 | 0.52 |
Maximum of Months | 0.409175E+11 | 0.461883E+11 | 0.00 | 79021199.56 | 27980074.11 | 0.103062E+11 | 0.377638E+11 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187811E+10 | 0.00 | 0.00 | 5272889.23 | 0.00 | 0.763155E+09 | 0.469790E+10 | 0.00 | 0.83 |
February | 0.131139E+10 | 0.00 | 0.00 | 6611113.33 | 0.00 | 0.475058E+09 | 0.444731E+10 | 0.00 | 1.13 |
March | 0.116032E+10 | 0.00 | 0.00 | 9135936.56 | 0.00 | 0.251253E+09 | 0.522939E+10 | 0.00 | 1.42 |
April | 0.352626E+09 | 0.169086E+09 | 0.00 | 10186191.99 | 0.00 | 15023136.13 | 0.337428E+10 | 0.00 | 1.29 |
May | 51788568.43 | 0.101721E+10 | 0.00 | 7542247.59 | 97973.53 | 0.00 | 0.163671E+10 | 0.00 | 1.10 |
June | 47763.57 | 0.222651E+10 | 0.00 | 7528366.59 | 462900.99 | 0.00 | 0.547256E+09 | 0.00 | 0.91 |
July | 0.00 | 0.465671E+10 | 0.00 | 3884604.19 | 8097087.10 | 0.00 | 0.104617E+09 | 0.00 | 0.89 |
August | 4732857.71 | 0.289744E+10 | 0.00 | 7290440.07 | 151956.73 | 0.00 | 0.814389E+09 | 0.00 | 1.11 |
September | 10821543.82 | 0.210967E+10 | 0.00 | 10935400.19 | 0.00 | 0.00 | 0.158429E+10 | 0.00 | 1.22 |
October | 0.259956E+09 | 0.573157E+09 | 0.00 | 18474447.31 | 0.00 | 0.00 | 0.505808E+10 | 0.00 | 1.69 |
November | 0.116356E+10 | 0.00 | 0.00 | 13540337.89 | 0.00 | 0.199539E+09 | 0.682159E+10 | 0.00 | 1.46 |
December | 0.206183E+10 | 0.00 | 0.00 | 4171180.96 | 0.00 | 0.973389E+09 | 0.428038E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.825519E+10 | 0.136498E+11 | 0.00 | 0.104573E+09 | 8809918.35 | 0.267742E+10 | 0.385962E+11 | 0.00 | 1.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3884604.19 | 0.00 | 0.00 | 0.104617E+09 | 0.00 | 0.75 |
Maximum of Months | 0.206183E+10 | 0.465671E+10 | 0.00 | 18474447.31 | 8097087.10 | 0.973389E+09 | 0.682159E+10 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215647E+10 | 0.00 | 0.00 | 2352426.24 | 0.00 | 0.128233E+10 | 0.249816E+10 | 0.00 | 0.66 |
February | 0.178762E+10 | 0.00 | 0.00 | 3422969.51 | 0.00 | 0.734425E+09 | 0.253056E+10 | 0.00 | 0.91 |
March | 0.132589E+10 | 0.00 | 0.00 | 4973931.77 | 0.00 | 0.604122E+09 | 0.332086E+10 | 0.00 | 1.12 |
April | 0.490777E+09 | 0.167086E+09 | 0.00 | 6318336.41 | 0.00 | 74066764.68 | 0.228690E+10 | 0.00 | 1.06 |
May | 0.106868E+09 | 0.988297E+09 | 0.00 | 4884447.99 | 74968.54 | 0.00 | 0.117709E+10 | 0.00 | 0.96 |
June | 1803229.11 | 0.218760E+10 | 0.00 | 5511549.45 | 203061.99 | 0.00 | 0.468850E+09 | 0.00 | 0.84 |
July | 0.00 | 0.434770E+10 | 0.00 | 2590255.89 | 6118616.57 | 0.00 | 95831296.32 | 0.00 | 0.83 |
August | 12455669.33 | 0.275023E+10 | 0.00 | 4849058.68 | 256395.03 | 0.00 | 0.674607E+09 | 0.00 | 0.99 |
September | 19903896.98 | 0.198210E+10 | 0.00 | 7944475.85 | 0.00 | 0.00 | 0.127785E+10 | 0.00 | 1.08 |
October | 0.453423E+09 | 0.524180E+09 | 0.00 | 13021890.19 | 0.00 | 0.00 | 0.372455E+10 | 0.00 | 1.39 |
November | 0.118028E+10 | 0.00 | 0.00 | 8959213.87 | 0.00 | 0.568899E+09 | 0.482584E+10 | 0.00 | 1.17 |
December | 0.257921E+10 | 0.00 | 0.00 | 1565541.33 | 0.00 | 0.152522E+10 | 0.192664E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.101147E+11 | 0.129472E+11 | 0.00 | 66394097.18 | 6653042.13 | 0.478906E+10 | 0.248078E+11 | 0.00 | 0.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1565541.33 | 0.00 | 0.00 | 95831296.32 | 0.00 | 0.60 |
Maximum of Months | 0.257921E+10 | 0.434770E+10 | 0.00 | 13021890.19 | 6118616.57 | 0.152522E+10 | 0.482584E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |