Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2020-06-03 19:12:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1441.46 | 628.36 | 628.36 |
Net Site Energy | 1441.46 | 628.36 | 628.36 |
Total Source Energy | 3097.40 | 1350.22 | 1350.22 |
Net Source Energy | 3097.40 | 1350.22 | 1350.22 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 608.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 264.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 96.35 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 736.85 | 704.60 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 608.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 82.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 264.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 151.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 96.35 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 133.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 102.28 | 307.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.21 | 307.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 133.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 102.28 | 307.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 321.21 | 307.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 736.853 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 736.853 | 100.00 |
Total On-Site and Utility Electric Sources | 736.853 | 100.00 |
Total Electricity End Uses | 736.853 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2098.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 5.1793 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.8188 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-13:00 | 07-FEB-07:10 | - | - | - | 11-JAN-12:09 |
Heating | 0.00 | 251165.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 37824.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 17624.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9078.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 75297.99 | 253027.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 251165.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 37824.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 17624.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9078.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 659.35 | 0.00 | 0.00 | 0.00 |
Cooling | 262.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 837.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 135.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 480.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 104.44 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2333.61 | 763.79 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 287.42 | 0.00 | 0.00 | 0.00 |
Cooling | 114.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 364.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 58.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 209.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.53 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1017.27 | 332.95 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 287.42 | 0.00 | 0.00 | 0.00 |
Cooling | 114.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 364.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 58.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 209.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.53 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1017.27 | 332.95 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.62 |
CORE_RETAIL DIRECT AIR | 6.70 |
POINT_OF_SALE DIRECT AIR | 1.01 |
FRONT_RETAIL DIRECT AIR | 0.734132 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.71 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.71 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 49493.37 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 46562.38 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 234238.08 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 30567.73 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 24313.71 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.62 | 1.62 | 1.62 | 1.62 | 1.66 | 1.66 | 1.00 | 0.972153 | 1.66 |
PSZ-AC:2 | 6.70 | 6.70 | 6.70 | 6.70 | 6.98 | 6.98 | 1.00 | 0.959132 | 6.98 |
PSZ-AC:3 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
PSZ-AC:4 | 0.734132 | 0.734132 | 0.734132 | 0.734132 | 0.746197 | 0.746197 | 1.00 | 0.983831 | 0.746197 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.66 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 6.98 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.01 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.746197 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.66 | 1.66 | 1.66 | 1.10 | 32263.19 | 46562.38 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 6.98 | 6.98 | 6.98 | 4.61 | 152870.39 | 234238.08 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 0.668355 | 19797.12 | 30567.73 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.746197 | 0.746197 | 0.746197 | 0.746197 | 15535.23 | 24313.71 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.66 | 0.831185 | 1.11 | 30187.19 | 32263.19 | 16131.59 | 16131.59 | 0.744583 | 0.744580 | 0.744580 | 0.744580 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 6.98 | 3.49 | 4.66 | 144294.34 | 152870.39 | 76435.20 | 76435.20 | 0.709053 | 0.709050 | 0.709050 | 0.709050 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.01 | 0.506330 | 0.675107 | 18515.92 | 19797.12 | 9898.56 | 9898.56 | 0.742310 | 0.742310 | 0.742310 | 0.742310 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.746200 | 0.373100 | 0.497467 | 14606.52 | 15535.23 | 7767.61 | 7767.61 | 0.723327 | 0.723330 | 0.723330 | 0.723330 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.66 | 1778.82 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 6.98 | 11766.47 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1121.17 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.746197 | 826.16 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 5.179 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.249 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 33.339 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 1967.547 | 5.179 | 32.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1967.547 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 18915.745 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18915.745 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1725 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3437E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3274 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.721 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 29.02 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.978 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
25 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
26 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
27 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
28 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
29 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
30 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
31 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
32 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
33 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
34 | 7 | -0.24541788E-08 | -0.10674912E-14 | 0.56595312E-14 | -0.88347803E-16 |
35 | 6 | 0.48874313E-05 | 0.32994277E-08 | 0.31919810E-02 | -0.26777012E-04 |
36 | 5 | -0.34768456E-03 | 0.19525666E-05 | -0.22384457 | 0.19572094E-02 |
37 | 4 | 0.79733842E-02 | 0.88847046E-04 | 4.8315443 | -0.45284193E-01 |
38 | 3 | -0.69943606E-01 | 0.70626596E-03 | -38.032707 | 0.39877855 |
39 | 2 | 0.24825401 | 0.11745943E-02 | 116.50592 | -1.4182332 |
40 | 1 | -0.35825340 | 0.35768630E-03 | -143.92024 | 2.0492525 |
41 | 0 | 0.17465044 | 0.86763216E-05 | 60.838472 | |
42 | 7 | -0.12489162E-07 | 0.28466235E-14 | -0.17145271E-13 | 0.26119495E-15 |
43 | 6 | 0.18517441E-05 | 0.69460444E-09 | 0.32027219E-02 | -0.26867115E-04 |
44 | 5 | -0.89695516E-04 | 0.39969105E-06 | -0.22445454 | 0.19625936E-02 |
45 | 4 | 0.17714562E-02 | 0.17921615E-04 | 4.8416944 | -0.45381772E-01 |
46 | 3 | -0.14613545E-01 | 0.14074818E-03 | -38.089997 | 0.39941188 |
47 | 2 | 0.50542763E-01 | 0.23137019E-03 | 116.61736 | -1.4197240 |
48 | 1 | -0.72070041E-01 | 0.69440628E-04 | -143.98582 | 2.0503304 |
49 | 0 | 0.34918756E-01 | 0.16519960E-05 | 60.838472 | |
50 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
51 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
52 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
53 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
54 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
55 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
56 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
57 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
58 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
59 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
60 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
61 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
62 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
63 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
64 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
65 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
66 | 7 | -0.12723796E-08 | -0.15085021E-15 | 0.80954726E-14 | -0.10933793E-15 |
67 | 6 | 0.91456241E-05 | 0.63025983E-08 | 0.31797574E-02 | -0.26674470E-04 |
68 | 5 | -0.66211654E-03 | 0.37378006E-05 | -0.22314974 | 0.19510765E-02 |
69 | 4 | 0.15256371E-01 | 0.17022008E-03 | 4.8199703 | -0.45172938E-01 |
70 | 3 | -0.13404479 | 0.13543778E-02 | -37.967318 | 0.39805580 |
71 | 2 | 0.47605416 | 0.22539081E-02 | 116.37865 | -1.4165309 |
72 | 1 | -0.68716389 | 0.68732095E-03 | -143.84532 | 2.0480210 |
73 | 0 | 0.33503722 | 0.16534103E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.38 | 30 | 1 | VerySmooth | 2.159 | 0.374 | 0.294 | 0.381 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 31 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1928 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 18700.93683 | 22441.12420 | 1.34673 | 1.61608 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 23726.60615 | 28471.92738 | 1.02485 | 1.22982 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 77574.65717 | 93089.58860 | 5.58235 | 6.69882 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 58120.09975 | 69744.11970 | 2.47564 | 2.97076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 11548.24846 | 13857.89816 | 0.84388 | 1.01266 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 11770.39740 | 14124.47688 | 0.51056 | 0.61267 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 8451.09591 | 10141.31510 | 0.61178 | 0.73413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 11772.28063 | 14126.73675 | 0.51064 | 0.61277 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30000 | 1.33455E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 41239.07953 | 49486.89544 | 1.42759 | 1.71311 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30000 | 9.24091E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 21769.67 | 1.66237 | 1.66237 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 37862.64 | 1.22982 | 1.22982 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 98131.07 | 6.98425 | 6.98425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 149961.78 | 2.97076 | 2.97076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 14127.14 | 1.01266 | 1.01266 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 21586.36 | 0.61267 | 0.61267 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 11095.49 | 0.74620 | 0.74620 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 21588.60 | 0.61277 | 0.61277 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.61608 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.69882 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01266 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.73413 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.71311 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.71311 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 49493.37278 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.61608 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.61608 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.61608 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.61608 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.66237 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.66237 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.97215 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.69882 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.69882 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.69882 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.69882 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.98425 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 6.98425 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.95913 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01266 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01266 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01266 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01266 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01266 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01266 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.73413 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.73413 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.73413 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.73413 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.74620 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.74620 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.98383 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.66237 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 6.98425 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.01266 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.74620 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.66237 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.66237 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.66237 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.66237 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09717 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.66237 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83119 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10825 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30187.18761 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32263.19000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16131.59500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16131.59500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74458 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74458 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74458 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74458 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32263.19000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 46562.37628 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.66237 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1778.81815 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 46562.37628 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.98425 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.98425 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.98425 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.98425 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.60960 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.98425 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.49213 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.65617 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 144294.34332 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 152870.39000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 76435.19500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 76435.19500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70905 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70905 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70905 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70905 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 152870.39000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 234238.07991 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.98425 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11766.46564 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 234238.07991 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01266 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01266 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01266 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01266 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.66836 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01266 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50633 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.67511 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18515.91696 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19797.12000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9898.56000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9898.56000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74231 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74231 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74231 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74231 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19797.12000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30567.72857 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01266 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1121.17485 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 30567.72857 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.74620 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.74620 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.74620 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.74620 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.74620 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.74620 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.37310 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.49747 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 14606.52271 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 15535.23000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 7767.61500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 7767.61500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72333 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72333 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72333 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72333 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15535.23000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24313.71487 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.74620 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 826.15869 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 24313.71487 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30957.4 | 11.47 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 147373.4 | 12.90 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 19001.6 | 119.24 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14948.4 | 176.24 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.172 | 0.166 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.437E-002 | 3.409E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.38 | N/A | 2.159 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.327 | 0.303 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 7 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 7.7262470247E-002 | 0.2476515859 | Pass | Pass | 5.9392225945E-002 | 0.2260973424 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.6136801382E-002 | 0.2084428924 | Pass | Pass | 0.1639094054 | 1.1271284093 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 8.1729406681E-002 | 0.2673960886 | Pass | Pass | 6.3735080065E-002 | 0.1696924683 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 9.2077338411E-002 | 0.2922396711 | Pass | Pass | 4.5316604339E-002 | 0.1449470780 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1519516251 | 0.2206943329 | Pass | Pass | 0.1101522891 | 0.6099922673 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.172 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.034 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.327 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.374 | 0.381 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.374 | 0.381 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.38 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.159 | 0.374 | 0.381 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.623 | 0.425 | 0.429 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.623 | 0.425 | 0.429 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 5.1793 | 379.89 | 1967.55 | LightsWired | BLDG_LIGHT_BACK_SCH | 60.89 | 168.00 | 60.06 | 0.0000 | Y | 22.18 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 11.8188 | 1600.48 | 18915.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 54.92 | 0.0000 | Y | 195.02 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.49 |
Interior Lighting Total | 10.7081 | 2293.99 | 24564.32 | 264.36 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 238.00 | AstronomicalClock | - | 42.04 | 42.04 | 1.88 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.67 | 71.18 | 40.82 | |
Exterior Lighting Total | 3292.90 | 42.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32263.19 | 24022.53 | 8240.66 | 0.74 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 152870.39 | 108392.75 | 44477.64 | 0.71 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19797.12 | 14695.60 | 5101.52 | 0.74 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 15535.23 | 11237.10 | 4298.13 | 0.72 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30957.4 | 11.47 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 147373.4 | 12.90 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 19001.6 | 119.24 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 14948.4 | 176.24 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 49493.37 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 46562.38 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 234238.08 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 30567.73 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 24313.71 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 1.71 | 1833.11 | 1070.05 | 1.00 | 1.33 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.66 | 1778.82 | 1070.05 | 1.00 | 1.34 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 6.98 | 11766.47 | 1684.71 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1121.17 | 1107.16 | 1.00 | 1.40 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.75 | 826.16 | 1107.16 | 1.00 | 1.49 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 18700.94 | 22441.12 | 59.07 | 1.347 | 1.616 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01039 | 23.42 | 0.01335 | 0.232 | 0.00 |
CORE_RETAIL | 77574.66 | 93089.59 | 58.16 | 5.582 | 6.699 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01032 | 23.42 | 0.01335 | 1.890 | 0.00 |
POINT_OF_SALE | 11548.25 | 13857.90 | 91.89 | 0.844 | 1.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00914 | 23.42 | 0.01335 | 0.178 | 0.00 |
FRONT_RETAIL | 8451.10 | 10141.32 | 67.25 | 0.612 | 0.734 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01000 | 23.42 | 0.01335 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.13 | 100.00 | 0.00001 | 30.30 | 0.01335 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 23726.61 | 28471.93 | 74.95 | 1.025 | 1.230 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00750 | -16.30 | 0.00092 | 0.232 | 0.00 |
CORE_RETAIL | 58120.10 | 69744.12 | 43.58 | 2.476 | 2.971 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00739 | -16.30 | 0.00092 | 1.890 | 0.00 |
POINT_OF_SALE | 11770.40 | 14124.48 | 93.66 | 0.511 | 0.613 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00767 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_RETAIL | 11772.28 | 14126.74 | 93.67 | 0.511 | 0.613 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00767 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_ENTRY | 41239.08 | 49486.90 | 4123.91 | 1.428 | 1.713 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 16.00 | 15.87 | 0.00497 | -16.30 | 0.00092 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.66 | 1.66 | 1.23 | 1.23 | 1.6624 | 1.6161 | 1.6624 | 0.9722 | 1.0000 |
PSZ-AC:2 | 6.98 | 6.98 | 2.97 | 2.97 | 6.9842 | 6.6988 | 6.9842 | 0.9591 | 1.0000 |
PSZ-AC:3 | 1.01 | 1.01 | 0.61 | 0.61 | 1.0127 | 1.0127 | 1.0127 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.75 | 0.75 | 0.61 | 0.61 | 0.7462 | 0.7341 | 0.7462 | 0.9838 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 49493.373 | 49493.373 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 49493.37 | 49493.37 | 1.713108 | 15.60 | 9.34 | 0.00493558 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 15.87 | 0.00496904 | 43.4215 | 49486.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 16131.595 | 0.000 | 1.662370 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 16131.59 | 11678.32 | 1.662370 | 23.90 | 17.69 | 0.01043988 | 12.80 | 11.87 | 0.00850000 | 24.01 | 0.01334551 | 19.95 | 13.9299 | 23.88 | 0.01039290 | 54.7594 | 18700.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 46562.376 | 46562.376 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46562.38 | 46562.38 | 1.662373 | 13.90 | 10.02 | 0.00625905 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 13.9299 | 21.11 | 0.00749661 | 46.9704 | 23726.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 76435.195 | 0.000 | 6.984250 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 76435.20 | 56855.27 | 6.984250 | 25.78 | 18.36 | 0.01050843 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 27.0639 | 23.88 | 0.01032200 | 54.3921 | 77299.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 234238.080 | 234238.080 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 234238.08 | 234238.08 | 6.984248 | -2.79 | -2.79 | 0.00327733 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 27.0639 | 21.11 | 0.00739386 | 46.3327 | 58120.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 9898.560 | 0.000 | 1.012660 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 9898.56 | 7978.56 | 1.012660 | 25.06 | 17.58 | 0.00983455 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 17.5884 | 23.89 | 0.00914086 | 48.2478 | 10817.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 30567.729 | 30567.729 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30567.73 | 30567.73 | 1.012660 | 10.13 | 7.71 | 0.00571228 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.5884 | 21.11 | 0.00767480 | 48.0721 | 11770.40 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 7767.615 | 0.000 | 0.746200 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 7767.61 | 5975.14 | 0.746200 | 25.42 | 18.00 | 0.01020690 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 23.8690 | 23.88 | 0.00999953 | 52.7172 | 8251.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 24313.715 | 24313.715 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24313.71 | 24313.71 | 0.746197 | 10.13 | 7.71 | 0.00571270 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 23.8691 | 21.11 | 0.00767494 | 48.0729 | 11772.28 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 49493.373 | 49493.373 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.713108 | 2.01106026 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 49493.37 | 49493.37 | 1.0000 | 2.01106026 | 1.713108 | 15.60 | 9.34 | 0.00493558 | 28161.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49493.37 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 15.87 | 0.00496904 | 15.87 | 0.00496904 | 43.4215 | 49486.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16131.595 | 0.000 | 1.662370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2472 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 16131.59 | 11678.32 | 1.0000 | 1.95149822 | 1.662370 | 23.90 | 17.69 | 0.01043988 | 50590.5 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16131.59 | 24.01 | 0.01334551 | 19.95 | 0.23156651 | 13.9299 | 23.88 | 0.00996962 | 23.88 | 0.01039290 | 54.7594 | 18700.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 46562.376 | 46562.376 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.662373 | 1.95150225 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46562.38 | 46562.38 | 1.0000 | 1.95150225 | 1.662373 | 13.90 | 10.02 | 0.00625905 | 29783.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 46562.38 | -16.30 | 0.00092409 | -16.30 | 0.23156651 | 13.9299 | 20.91 | 0.00749661 | 21.11 | 0.00749661 | 46.9704 | 23726.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 76435.195 | 0.000 | 6.984250 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3746 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 76435.20 | 56855.27 | 1.0000 | 8.19898787 | 6.984250 | 25.78 | 18.36 | 0.01050843 | 52688.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76435.20 | 30.30 | 0.01334551 | 21.80 | 1.89021192 | 27.0639 | 23.89 | 0.00932181 | 23.88 | 0.01032200 | 54.3921 | 77299.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 234238.080 | 234238.080 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 6.984248 | 8.19898607 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 234238.08 | 234238.08 | 1.0000 | 8.19898607 | 6.984248 | -2.79 | -2.79 | 0.00327733 | 5373.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 234238.08 | -16.30 | 0.00092409 | -16.30 | 1.89021192 | 27.0639 | 20.84 | 0.00739386 | 21.11 | 0.00739386 | 46.3327 | 58120.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9898.560 | 0.000 | 1.012660 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1219 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 9898.56 | 7978.56 | 1.0000 | 1.18878721 | 1.012660 | 25.06 | 17.58 | 0.00983455 | 50231.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9898.56 | 30.30 | 0.01334551 | 21.80 | 0.17811053 | 17.5884 | 23.89 | 0.00905188 | 23.89 | 0.00914086 | 48.2478 | 10817.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30567.729 | 30567.729 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.012660 | 1.18878666 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30567.73 | 30567.73 | 1.0000 | 1.18878666 | 1.012660 | 10.13 | 7.71 | 0.00571228 | 24574.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30567.73 | -16.30 | 0.00092409 | -16.30 | 0.17811053 | 17.5884 | 20.97 | 0.00767480 | 21.11 | 0.00767480 | 48.0721 | 11770.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 7767.615 | 0.000 | 0.746200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8141 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 7767.61 | 5975.14 | 1.0000 | 0.87598307 | 0.746200 | 25.42 | 18.00 | 0.01020690 | 51552.4 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7767.61 | 30.30 | 0.01334551 | 21.80 | 0.17811053 | 23.8690 | 23.89 | 0.00922131 | 23.88 | 0.00999953 | 52.7172 | 8251.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24313.715 | 24313.715 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.746197 | 0.87597972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24313.71 | 24313.71 | 1.0000 | 0.87597972 | 0.746197 | 10.13 | 7.71 | 0.00571270 | 24577.3 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24313.71 | -16.30 | 0.00092409 | -16.30 | 0.17811053 | 23.8691 | 20.97 | 0.00767494 | 21.11 | 0.00767494 | 48.0729 | 11772.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.66 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 6.98 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.01 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2735.50 | 3748.17 | 2071.67 |
CORE_RETAIL | 2493.17 | 3288.33 | 1410.00 |
POINT_OF_SALE | 2670.00 | 3062.17 | 1392.33 |
FRONT_RETAIL | 2755.50 | 3331.33 | 1677.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3275.83 | 3779.50 | 2098.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 8.67 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8.17 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 16.33 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 457.33 | 0.00 | 0.00 | 0.00 |
Facility | 479.83 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.529 | 0.040 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.818 | 0.008 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 1.021 | 0.043 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.707 | 0.043 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.47 | 61.34 | 2317.33 | 0.350 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.37 | 258.43 | 9762.95 | 0.678 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.10 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.10 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 736.85 | 2865.76 | 30-APR-07:00 | 75297.99 | 15-JUL-14:00 |
Electricity:Building | 459.52 | 2708.13 | 21-MAY-08:00 | 32651.56 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 72.17 | 558.23 | 01-JAN-00:10 | 4302.56 | 02-JAN-09:10 |
InteriorLights:Electricity | 264.36 | 912.95 | 21-MAY-08:00 | 21880.52 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 22.18 | 98.38 | 01-JAN-00:10 | 1543.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 264.36 | 912.95 | 21-MAY-08:00 | 21880.52 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 279.32 | 1405.96 | 21-MAY-08:00 | 21676.77 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 195.02 | 630.52 | 21-MAY-08:00 | 17024.17 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 75.76 | 575.93 | 01-JAN-00:10 | 4525.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 30.78 | 162.19 | 01-JAN-00:10 | 2042.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 736.85 | 2865.76 | 30-APR-07:00 | 75297.99 | 15-JUL-14:00 |
ElectricityPurchased:Plant | 736.85 | 2865.76 | 30-APR-07:00 | 75297.99 | 15-JUL-14:00 |
Cogeneration:ElectricityPurchased | 736.85 | 2865.76 | 30-APR-07:00 | 75297.99 | 15-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 736.85 | 2865.76 | 30-APR-07:00 | 75297.99 | 15-JUL-14:00 |
ElectricityNet:Plant | 736.85 | 2865.76 | 30-APR-07:00 | 75297.99 | 15-JUL-14:00 |
Cogeneration:ElectricityNet | 736.85 | 2865.76 | 30-APR-07:00 | 75297.99 | 15-JUL-14:00 |
Electricity:HVAC | 234.64 | 0.00 | 01-JAN-00:10 | 47021.31 | 21-JUL-06:10 |
Fans:Electricity | 151.87 | 0.00 | 01-JAN-00:10 | 12824.95 | 10-DEC-09:10 |
General:Fans:Electricity | 151.87 | 0.00 | 01-JAN-00:10 | 12824.95 | 10-DEC-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 82.77 | 0.00 | 01-JAN-00:10 | 37824.08 | 15-JUL-14:00 |
ExteriorLights:Electricity | 42.70 | 0.00 | 01-JAN-08:00 | 3292.90 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.70 | 0.00 | 01-JAN-08:00 | 3292.90 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 704.60 | 1862.00 | 22-JUN-07:10 | 253027.16 | 07-FEB-07:10 |
Gas:Plant | 96.35 | 1862.00 | 08-JAN-07:10 | 5227.47 | 14-FEB-13:00 |
WaterSystems:Gas | 96.35 | 1862.00 | 08-JAN-07:10 | 5227.47 | 14-FEB-13:00 |
Water Heater:WaterSystems:Gas | 96.35 | 1862.00 | 08-JAN-07:10 | 5227.47 | 14-FEB-13:00 |
Gas:HVAC | 608.25 | 0.00 | 01-JAN-00:10 | 251165.16 | 07-FEB-07:10 |
Heating:Gas | 608.25 | 0.00 | 01-JAN-00:10 | 251165.16 | 07-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 11-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1378.36 | 0.00 | 01-JAN-00:10 | 308821.82 | 07-FEB-07:10 |
EnergyTransfer:Building | 569.55 | 0.00 | 01-JAN-00:10 | 126895.00 | 06-FEB-06:10 |
EnergyTransfer:Zone:BACK_SPACE | 80.55 | 0.00 | 01-JAN-00:10 | 27321.19 | 06-FEB-06:10 |
Heating:EnergyTransfer | 156.51 | 0.00 | 01-JAN-00:10 | 126895.00 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 37.65 | 0.00 | 01-JAN-00:10 | 27321.19 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 413.03 | 0.00 | 01-JAN-00:10 | 71101.04 | 21-JUL-14:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 42.91 | 0.00 | 01-JAN-00:10 | 11209.10 | 21-JUL-14:10 |
EnergyTransfer:Zone:CORE_RETAIL | 322.47 | 0.00 | 01-JAN-00:10 | 76851.20 | 09-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 29.93 | 0.00 | 01-JAN-00:10 | 75057.09 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 292.53 | 0.00 | 01-JAN-00:10 | 57027.89 | 03-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 58.36 | 0.00 | 01-JAN-00:10 | 12088.55 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 7.83 | 0.00 | 01-JAN-00:10 | 12088.55 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 50.52 | 0.00 | 01-JAN-00:10 | 9190.34 | 21-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 42.26 | 0.00 | 01-JAN-00:10 | 12513.49 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 15.19 | 0.00 | 01-JAN-00:10 | 12513.49 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 27.07 | 0.00 | 01-JAN-00:10 | 6880.05 | 21-SEP-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 65.91 | 0.00 | 01-JAN-00:10 | 38647.82 | 06-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 65.91 | 0.00 | 01-JAN-00:10 | 38647.82 | 06-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 808.81 | 0.00 | 01-JAN-00:10 | 200932.13 | 07-FEB-07:10 |
HeatingCoils:EnergyTransfer | 486.60 | 0.00 | 01-JAN-00:10 | 200932.13 | 07-FEB-07:10 |
CoolingCoils:EnergyTransfer | 322.21 | 0.00 | 01-JAN-00:10 | 152825.05 | 21-JUL-06:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 37.647 | -42.907 | 0.000 | 0.000 | 40.073 | 22.181 | 49.992 | 0.000 | 0.000 | 0.147 | 0.002 | 0.000 | 0.000 | 0.000 | -24.101 | -83.032 |
CORE_RETAIL | 0.000 | 0.000 | 29.933 | -292.533 | 0.000 | 0.000 | 168.626 | 195.020 | 84.299 | 50.512 | 0.000 | 0.120 | 0.017 | 0.000 | -26.965 | 0.000 | -21.279 | -187.733 |
POINT_OF_SALE | 0.000 | 0.000 | 7.833 | -50.523 | 0.000 | 0.000 | 15.667 | 22.836 | 52.922 | 26.186 | 0.000 | 0.061 | 0.001 | 0.000 | -20.187 | 0.000 | -10.913 | -43.884 |
FRONT_RETAIL | 0.000 | 0.000 | 15.190 | -27.065 | 0.000 | 0.000 | 15.876 | 22.836 | 7.943 | 26.246 | 0.000 | 0.063 | 0.001 | 0.000 | -19.606 | 0.000 | -10.493 | -30.991 |
FRONT_ENTRY | 65.912 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.489 | 0.000 | 5.608 | 0.000 | 0.049 | 6.113 | 0.000 | -3.628 | 0.000 | -75.543 | 0.000 |
Total Facility | 65.912 | 0.000 | 90.603 | -413.028 | 0.000 | 0.000 | 240.243 | 264.364 | 195.156 | 108.552 | 0.000 | 0.440 | 6.133 | 0.000 | -70.385 | 0.000 | -142.328 | -345.640 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-AUG-06:02 | 0.00 | 0.00 | 0.00 | -33302.50 | 0.00 | 0.00 | 401.65 | 342.98 | 1226.28 | 0.00 | 0.00 | 0.00 | 31347.76 | 0.00 | -0.00 | 0.00 | -16.17 | 0.00 |
CORE_RETAIL | 13-JUN-06:02 | 0.00 | 0.00 | 0.00 | -167362.56 | 0.00 | 0.00 | 1633.00 | 3783.15 | 2067.82 | 0.00 | 0.00 | 0.00 | 160972.57 | 0.00 | -654.84 | 0.00 | -439.14 | 0.00 |
POINT_OF_SALE | 02-AUG-06:02 | 0.00 | 0.00 | 0.00 | -21662.19 | 0.00 | 0.00 | 151.75 | 356.48 | 1298.17 | 0.00 | 0.00 | 0.00 | 20538.53 | 0.00 | -682.74 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 13-AUG-08:62 | 0.00 | 0.00 | 0.00 | -12210.15 | 0.00 | 0.00 | 163.50 | 178.24 | 146.13 | 1027.14 | 0.00 | 0.00 | 10717.72 | 0.00 | -0.00 | 0.00 | -22.59 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-AUG-06:02 | 0.00 | 0.00 | 0.00 | -212084.97 | 0.00 | 0.00 | 2362.13 | 4862.34 | 4787.13 | 0.00 | 0.00 | 0.00 | 202255.76 | 0.00 | -2182.39 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 06-FEB-06:01 | 0.00 | 0.00 | 47459.79 | 0.00 | 0.00 | 0.00 | 0.00 | 98.38 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1425.80 | -46745.52 |
CORE_RETAIL | 07-FEB-06:01 | 0.00 | 0.00 | 240610.63 | 0.00 | 0.00 | 0.00 | 0.00 | 945.79 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2942.73 | 0.00 | -1139.04 | -238508.56 |
POINT_OF_SALE | 26-DEC-06:01 | 0.00 | 0.00 | 30766.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2047.93 | 0.00 | -694.48 | -28761.83 |
FRONT_RETAIL | 01-DEC-06:02 | 0.00 | 0.00 | 22465.82 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -602.47 | 0.00 | -107.00 | -21942.89 |
FRONT_ENTRY | 06-FEB-18:00 | 38647.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 412.09 | 0.00 | -462.74 | 0.00 | -38701.27 | 0.00 |
Total Facility | 10-DEC-08:61 | 4975.22 | 0.00 | 336233.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1228.22 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3299.32 | 0.00 | -6942.35 | -333990.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6161 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6624 | 0.1393 | 1.0000 | 0.2316 | 0.1393 | ||
PSZ-AC:2 | 6.6988 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.9842 | 0.2706 | 1.0000 | 1.8902 | 0.2706 | ||
PSZ-AC:3 | 1.0127 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0127 | 0.1759 | 1.0000 | 0.1781 | 0.1759 | ||
PSZ-AC:4 | 0.7341 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7462 | 0.2387 | 1.0000 | 0.1781 | 0.2387 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6161 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6161 | 1.0000 | 1.0000 | 0.2316 | 0.1433 | ||
PSZ-AC:2 | 6.6988 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.6988 | 1.0000 | 1.0000 | 1.8902 | 0.2822 | ||
PSZ-AC:3 | 1.0127 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0127 | 1.0000 | 1.0000 | 0.1781 | 0.1759 | ||
PSZ-AC:4 | 0.7341 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.7341 | 1.0000 | 1.0000 | 0.1781 | 0.2426 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6161 | 1.6161 | 1.6161 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.6988 | 6.6988 | 6.6988 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0127 | 1.0127 | 1.0127 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7341 | 0.7341 | 0.7341 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6161 | 1.6624 | 1.6161 | 1.6161 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.6988 | 6.9842 | 6.6988 | 6.6988 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0127 | 1.0127 | 1.0127 | 1.0127 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7341 | 0.7462 | 0.7341 | 0.7341 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6161 | 1.6161 | 1.6161 | 0.2316 | 0.1883 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.6988 | 6.6988 | 6.6988 | 1.8902 | 0.6363 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0127 | 1.0127 | 1.0127 | 0.1781 | 0.2907 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.7341 | 0.7341 | 0.7341 | 0.1781 | 0.2907 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6161 | 1.6161 | 1.6161 | 1.6161 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.6988 | 6.6988 | 6.6988 | 6.6988 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0127 | 1.0127 | 1.0127 | 1.0127 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.7341 | 0.7341 | 0.7341 | 0.7341 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:35
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 608.25 | 251165.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 82.77 | 37824.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 264.36 | 21880.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.70 | 3292.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 151.87 | 12824.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 96.35 | 5227.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 736.85 |
Natural Gas | 0.00 | 704.60 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1441.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 115.24 |
Space Heating | 0.00 |
Space Cooling | 36.08 |
Fans (All) | 66.20 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 321.21 |
Subtotal | 321.21 |
Natural Gas [MJ/m2] | |
Space Heating | 265.15 |
Service Water Heating | 42.00 |
Miscellaneous (All) | 307.15 |
Subtotal | 307.15 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.34 |
Space Heating | 42.20 |
Space Cooling | 5.74 |
Fans (All) | 10.54 |
Service Water Heating | 6.68 |
Receptacle Equipment | 13.54 |
Miscellaneous | 2.96 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3175. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.152753E+12 |
February | 0.000 | 0.144441E+12 |
March | 0.000 | 0.820863E+11 |
April | 0.000 | 0.296917E+11 |
May | 0.000 | 0.138500E+10 |
June | 0.000 | 5717028.397 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.455463E+08 |
October | 0.000 | 0.130409E+11 |
November | 0.000 | 0.460637E+11 |
December | 0.000 | 0.138739E+12 |
Annual Sum or Average | 0.608252E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.152753E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7471535.24 | 5051.76 | 15-JAN-09:05 | 0.87 | 0.15 | 0.165179E+10 | 1854.44 | 28-JAN-16:00 | -6.7 | -8.2 |
February | 10282602.16 | 4690.26 | 19-FEB-09:05 | 2.07 | -1.2 | 0.150831E+10 | 1854.44 | 08-FEB-15:00 | -7.8 | -9.1 |
March | 0.698666E+09 | 5075.71 | 19-MAR-08:05 | 1.47 | 0.11 | 0.178050E+10 | 2451.25 | 14-MAR-14:00 | 24.40 | 16.50 |
April | 0.169950E+10 | 6086.26 | 03-APR-06:05 | -2.8 | -3.4 | 0.172386E+10 | 2451.23 | 08-APR-13:50 | 20.68 | 13.71 |
May | 0.318473E+10 | 5438.02 | 27-MAY-16:00 | 21.70 | 11.99 | 0.211030E+10 | 2451.24 | 20-MAY-11:20 | 16.47 | 9.78 |
June | 0.723915E+10 | 27174.08 | 28-JUN-06:02 | 17.30 | 15.23 | 0.219547E+10 | 2451.29 | 16-JUN-14:30 | 24.15 | 15.91 |
July | 0.993636E+10 | 32705.34 | 12-JUL-06:02 | 14.37 | 11.81 | 0.218774E+10 | 2451.52 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.957421E+10 | 33315.16 | 01-AUG-06:02 | 11.57 | 10.94 | 0.228104E+10 | 2451.30 | 07-AUG-14:09 | 22.15 | 20.23 |
September | 0.603847E+10 | 23828.89 | 15-SEP-06:02 | 18.30 | 16.87 | 0.213946E+10 | 2451.25 | 18-SEP-14:00 | 17.80 | 13.19 |
October | 0.300336E+10 | 6232.32 | 17-OCT-06:05 | -2.8 | -3.3 | 0.189216E+10 | 2451.26 | 11-OCT-14:00 | 22.20 | 14.59 |
November | 0.139913E+10 | 5641.05 | 15-NOV-07:05 | -0.6 | -1.0 | 0.161892E+10 | 2282.86 | 04-NOV-15:00 | 18.30 | 13.47 |
December | 0.116470E+09 | 5560.92 | 16-DEC-07:05 | -0.8 | -1.5 | 0.165448E+10 | 1854.44 | 09-DEC-16:00 | -7.2 | -7.2 |
Annual Sum or Average | 0.429078E+11 | 0.227440E+11 | ||||||||
Minimum of Months | 7471535.24 | 4690.26 | -2.8 | -3.4 | 0.150831E+10 | 1854.44 | -7.8 | -9.1 | ||
Maximum of Months | 0.993636E+10 | 33315.16 | 21.70 | 16.87 | 0.228104E+10 | 2451.52 | 24.40 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.672786E+10 | 61907.12 | 12-JAN-07:05 | -8.5 | -10.0 | 0.695901E+10 | 7812.78 | 17-JAN-15:39 | 7.43 | 6.34 |
February | 0.625742E+10 | 62536.09 | 25-FEB-07:05 | -8.8 | -9.6 | 0.635450E+10 | 7812.77 | 06-FEB-15:09 | -13.3 | -13.6 |
March | 0.160762E+11 | 66022.63 | 04-MAR-07:05 | -10.4 | -11.2 | 0.751958E+10 | 10327.28 | 16-MAR-14:39 | 19.23 | 15.62 |
April | 0.210578E+11 | 52913.43 | 17-APR-06:05 | -4.2 | -5.2 | 0.741497E+10 | 10327.11 | 08-APR-14:20 | 20.20 | 13.54 |
May | 0.279869E+11 | 141787.86 | 28-MAY-08:62 | 18.22 | 13.21 | 0.900264E+10 | 10327.15 | 25-MAY-14:50 | 17.48 | 13.51 |
June | 0.403013E+11 | 167439.96 | 13-JUN-06:02 | 8.80 | 7.95 | 0.925044E+10 | 10327.45 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.461600E+11 | 150387.40 | 06-JUL-06:02 | 13.07 | 10.51 | 0.921740E+10 | 10327.47 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.444438E+11 | 162967.82 | 03-AUG-06:02 | 11.57 | 9.85 | 0.960843E+10 | 10327.16 | 19-AUG-15:00 | 22.80 | 16.32 |
September | 0.335233E+11 | 153109.02 | 23-SEP-06:02 | 12.88 | 11.58 | 0.899725E+10 | 10327.36 | 18-SEP-14:50 | 17.80 | 13.11 |
October | 0.248874E+11 | 44020.97 | 30-OCT-06:05 | -0.4 | -1.0 | 0.787398E+10 | 10327.09 | 12-OCT-14:09 | 18.30 | 14.92 |
November | 0.167975E+11 | 50757.12 | 24-NOV-07:05 | -3.2 | -3.9 | 0.685376E+10 | 10326.76 | 04-NOV-15:00 | 18.30 | 13.47 |
December | 0.831522E+10 | 63486.00 | 08-DEC-07:05 | -10.4 | -10.8 | 0.697349E+10 | 7812.77 | 30-DEC-11:09 | 0.00 | -1.7 |
Annual Sum or Average | 0.292535E+12 | 0.960255E+11 | ||||||||
Minimum of Months | 0.625742E+10 | 44020.97 | -10.4 | -11.2 | 0.635450E+10 | 7812.77 | -13.3 | -13.6 | ||
Maximum of Months | 0.461600E+11 | 167439.96 | 18.22 | 13.21 | 0.960843E+10 | 10327.47 | 22.80 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113989E+10 | 5347.21 | 12-JAN-20:33 | -7.8 | -9.4 | 0.656032E+09 | 755.53 | 11-JAN-15:00 | 11.70 | 10.13 |
February | 0.109277E+10 | 5846.21 | 21-FEB-11:23 | -10.3 | -11.5 | 0.600921E+09 | 837.05 | 22-FEB-15:50 | 10.60 | 4.98 |
March | 0.285857E+10 | 6134.68 | 15-MAR-13:40 | 25.73 | 15.89 | 0.732682E+09 | 973.09 | 16-MAR-14:09 | 18.98 | 15.27 |
April | 0.287781E+10 | 4678.81 | 03-APR-06:05 | -2.8 | -3.4 | 0.744603E+09 | 973.12 | 08-APR-14:09 | 20.40 | 13.65 |
May | 0.406213E+10 | 12816.73 | 24-MAY-06:03 | 18.03 | 15.61 | 0.866110E+09 | 973.14 | 25-MAY-14:50 | 17.48 | 13.51 |
June | 0.648602E+10 | 19190.42 | 20-JUN-06:02 | 13.77 | 12.90 | 0.872586E+09 | 973.15 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.812680E+10 | 20326.88 | 12-JUL-06:02 | 14.37 | 11.81 | 0.868601E+09 | 973.24 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.850078E+10 | 21667.30 | 02-AUG-06:02 | 11.85 | 10.71 | 0.905721E+09 | 973.18 | 15-AUG-14:00 | 23.30 | 20.62 |
September | 0.695091E+10 | 21025.04 | 23-SEP-06:02 | 12.88 | 11.58 | 0.853309E+09 | 973.15 | 06-SEP-14:09 | 16.70 | 13.17 |
October | 0.438224E+10 | 10090.18 | 12-OCT-06:03 | 13.90 | 11.92 | 0.813500E+09 | 973.14 | 12-OCT-14:00 | 18.30 | 15.22 |
November | 0.284298E+10 | 4688.61 | 01-NOV-12:00 | 11.10 | 6.26 | 0.695942E+09 | 973.10 | 04-NOV-11:20 | 15.37 | 12.57 |
December | 0.120217E+10 | 6186.83 | 10-DEC-16:52 | -11.7 | -12.5 | 0.660383E+09 | 895.88 | 16-DEC-13:00 | 5.60 | 2.83 |
Annual Sum or Average | 0.505231E+11 | 0.927039E+10 | ||||||||
Minimum of Months | 0.109277E+10 | 4678.81 | -11.7 | -12.5 | 0.600921E+09 | 755.53 | 5.60 | 2.83 | ||
Maximum of Months | 0.850078E+10 | 21667.30 | 25.73 | 15.89 | 0.905721E+09 | 973.24 | 23.30 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167961E+09 | 4956.83 | 12-JAN-06:04 | -7.4 | -8.9 | 0.655718E+09 | 736.18 | 03-JAN-15:20 | -6.1 | -7.4 |
February | 0.206506E+09 | 5153.03 | 08-FEB-06:04 | -8.6 | -9.3 | 0.598778E+09 | 741.30 | 22-FEB-15:39 | 10.60 | 4.97 |
March | 0.105338E+10 | 4621.68 | 24-MAR-05:05 | -5.5 | -6.6 | 0.710236E+09 | 973.10 | 16-MAR-14:09 | 18.98 | 15.27 |
April | 0.118360E+10 | 4062.07 | 03-APR-06:05 | -2.8 | -3.4 | 0.700787E+09 | 973.12 | 08-APR-14:09 | 20.40 | 13.65 |
May | 0.190590E+10 | 3350.91 | 01-MAY-06:05 | 2.35 | 1.70 | 0.827864E+09 | 973.11 | 31-MAY-14:09 | 21.70 | 14.16 |
June | 0.375829E+10 | 10200.25 | 26-JUN-06:02 | 20.50 | 17.41 | 0.867287E+09 | 973.13 | 02-JUN-14:09 | 24.40 | 18.95 |
July | 0.526139E+10 | 10713.33 | 05-JUL-06:02 | 18.98 | 16.76 | 0.868015E+09 | 973.14 | 15-JUL-11:09 | 22.20 | 21.05 |
August | 0.553381E+10 | 12211.22 | 13-AUG-08:62 | 20.97 | 16.04 | 0.904590E+09 | 973.12 | 12-AUG-10:09 | 21.70 | 16.15 |
September | 0.431796E+10 | 9424.45 | 17-SEP-08:62 | 21.70 | 19.44 | 0.844798E+09 | 973.14 | 06-SEP-14:00 | 16.70 | 13.65 |
October | 0.243129E+10 | 5627.06 | 11-OCT-14:30 | 22.20 | 14.36 | 0.761623E+09 | 973.11 | 10-OCT-14:09 | 17.30 | 13.64 |
November | 0.104846E+10 | 3894.89 | 25-NOV-07:05 | -1.5 | -2.5 | 0.664228E+09 | 973.10 | 16-NOV-15:00 | 17.20 | 13.62 |
December | 0.197115E+09 | 4556.84 | 10-DEC-08:06 | -13.0 | -13.3 | 0.657153E+09 | 787.30 | 16-DEC-13:00 | 5.60 | 2.83 |
Annual Sum or Average | 0.270657E+11 | 0.906108E+10 | ||||||||
Minimum of Months | 0.167961E+09 | 3350.91 | -13.0 | -13.3 | 0.598778E+09 | 736.18 | -6.1 | -7.4 | ||
Maximum of Months | 0.553381E+10 | 12211.22 | 22.20 | 19.44 | 0.904590E+09 | 973.14 | 24.40 | 21.05 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 | -4.6 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.8 | 0.00 | 0.00 | -4.9 | -6.8 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.998895E+10 | 47327.33 | 24-JAN-06:01 | -12.1 |
February | 0.985440E+10 | 47459.78 | 06-FEB-06:01 | -13.9 |
March | 0.515385E+10 | 47329.24 | 06-MAR-05:01 | -11.1 |
April | 0.166558E+10 | 47044.33 | 17-APR-05:01 | -4.0 |
May | 0.125220E+09 | 37729.49 | 01-MAY-06:03 | 2.35 |
June | 67536540.57 | 1042.15 | 18-JUN-08:20 | 24.60 |
July | 64607323.89 | 1209.04 | 16-JUL-08:20 | 24.97 |
August | 70684311.93 | 694.78 | 20-AUG-07:12 | 15.97 |
September | 70025496.86 | 705.55 | 19-SEP-06:00 | 10.60 |
October | 0.450263E+09 | 46822.62 | 30-OCT-05:01 | -0.1 |
November | 0.182476E+10 | 47020.62 | 25-NOV-06:01 | -1.7 |
December | 0.831080E+10 | 47416.94 | 27-DEC-05:42 | -11.2 |
Annual Sum or Average | 0.376467E+11 | |||
Minimum of Months | 64607323.89 | 694.78 | -13.9 | |
Maximum of Months | 0.998895E+10 | 47459.78 | 24.97 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.791872E+10 | 239997.67 | 09-JAN-06:01 | -9.4 |
February | 0.753936E+10 | 240610.61 | 07-FEB-06:01 | -16.2 |
March | 0.313124E+10 | 239289.11 | 28-MAR-05:01 | -2.7 |
April | 0.100172E+10 | 239293.42 | 17-APR-05:01 | -4.0 |
May | 0.485138E+09 | 10510.51 | 01-MAY-06:05 | 2.35 |
June | 0.431189E+09 | 7061.16 | 18-JUN-08:20 | 24.60 |
July | 0.311423E+09 | 9414.84 | 21-JUL-06:08 | 25.68 |
August | 0.369659E+09 | 4616.86 | 20-AUG-07:12 | 15.97 |
September | 0.458762E+09 | 4639.37 | 03-SEP-07:12 | 9.80 |
October | 0.610590E+09 | 109010.06 | 30-OCT-06:03 | -0.4 |
November | 0.131351E+10 | 239229.10 | 24-NOV-06:01 | -3.8 |
December | 0.636187E+10 | 239997.62 | 10-DEC-08:61 | -13.0 |
Annual Sum or Average | 0.299332E+11 | |||
Minimum of Months | 0.311423E+09 | 4616.86 | -16.2 | |
Maximum of Months | 0.791872E+10 | 240610.61 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209854E+10 | 30613.92 | 09-JAN-06:01 | -9.4 |
February | 0.225717E+10 | 30654.67 | 13-FEB-06:01 | -9.4 |
March | 0.809623E+09 | 30557.83 | 06-MAR-05:01 | -11.1 |
April | 0.325648E+09 | 30403.31 | 17-APR-05:01 | -4.0 |
May | 46784305.64 | 9795.99 | 01-MAY-06:03 | 2.35 |
June | 36109454.86 | 445.19 | 12-JUN-06:06 | 22.98 |
July | 24741503.14 | 755.95 | 20-JUL-05:07 | 23.90 |
August | 27360061.20 | 696.68 | 15-AUG-05:07 | 22.70 |
September | 38512203.80 | 531.17 | 17-SEP-07:05 | 22.12 |
October | 83623250.22 | 30205.23 | 30-OCT-05:01 | -0.1 |
November | 0.309656E+09 | 30384.50 | 24-NOV-06:01 | -3.8 |
December | 0.177527E+10 | 30766.00 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.783304E+10 | |||
Minimum of Months | 24741503.14 | 445.19 | -12.2 | |
Maximum of Months | 0.225717E+10 | 30766.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403185E+10 | 22219.36 | 17-JAN-06:01 | 7.20 |
February | 0.401597E+10 | 22181.37 | 01-FEB-06:01 | 7.02 |
March | 0.162368E+10 | 21992.07 | 13-MAR-05:02 | 8.80 |
April | 0.777849E+09 | 22131.06 | 30-APR-07:01 | 7.70 |
May | 77527241.20 | 15921.47 | 01-MAY-06:03 | 2.35 |
June | 6077906.65 | 5122.44 | 14-JUN-06:03 | 7.67 |
July | 5253319.11 | 1090.52 | 16-JUL-08:08 | 24.68 |
August | 1301705.24 | 721.48 | 14-AUG-06:08 | 22.88 |
September | 4354430.50 | 13836.36 | 30-SEP-06:03 | 7.30 |
October | 0.216928E+09 | 20658.64 | 30-OCT-05:01 | -0.1 |
November | 0.789390E+09 | 22410.68 | 14-NOV-06:01 | 8.90 |
December | 0.363979E+10 | 22465.38 | 01-DEC-06:02 | 10.10 |
Annual Sum or Average | 0.151900E+11 | |||
Minimum of Months | 1301705.24 | 721.48 | -0.1 | |
Maximum of Months | 0.403185E+10 | 22465.38 | 24.68 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161831E+11 | 35297.92 | 31-JAN-18:00 | -12.2 |
February | 0.153733E+11 | 38647.82 | 06-FEB-18:00 | -14.4 |
March | 0.913043E+10 | 30129.26 | 06-MAR-18:00 | -8.3 |
April | 0.281645E+10 | 22729.36 | 16-APR-11:10 | -3.1 |
May | 9148786.16 | 1979.39 | 08-MAY-07:10 | 5.87 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.154798E+10 | 20468.06 | 29-OCT-16:21 | 6.95 |
November | 0.533248E+10 | 20377.75 | 19-NOV-15:51 | 7.20 |
December | 0.155189E+11 | 36284.42 | 10-DEC-18:00 | -12.8 |
Annual Sum or Average | 0.659119E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.4 | |
Maximum of Months | 0.161831E+11 | 38647.82 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.186041E+10 | 1543.42 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.169252E+10 | 1543.42 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.193008E+10 | 1543.42 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.182131E+10 | 1543.42 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.189524E+10 | 1543.42 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.186250E+10 | 1543.42 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.185405E+10 | 1543.42 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.193008E+10 | 1543.42 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.182131E+10 | 1543.42 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.186041E+10 | 1543.42 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.179919E+10 | 1543.42 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.185405E+10 | 1543.42 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.221812E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.169252E+10 | 1543.42 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.193008E+10 | 1543.42 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.187732E+11 | 17024.17 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.155013E+11 | 17024.17 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.172508E+11 | 17024.17 | 01-MAR-15:00 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.147422E+11 | 17024.17 | 07-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.152380E+11 | 17024.17 | 11-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.145374E+11 | 15605.49 | 01-JUN-16:40 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.144398E+11 | 15605.49 | 03-JUL-16:40 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.151575E+11 | 17024.17 | 28-AUG-16:10 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.156098E+11 | 17024.17 | 01-SEP-16:00 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.173796E+11 | 17024.17 | 02-OCT-16:40 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.176186E+11 | 17024.17 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.187722E+11 | 17024.17 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.195020E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.144398E+11 | 15605.49 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.187732E+11 | 17024.17 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.124902E+09 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.113644E+09 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.129631E+09 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.122307E+09 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.127266E+09 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.125090E+09 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.124483E+09 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.129631E+09 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.122307E+09 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.124902E+09 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.120779E+09 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.124483E+09 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148942E+10 | ||||
Minimum of Months | 0.113644E+09 | 104.63 | 0.00 | 0.00 | |
Maximum of Months | 0.129631E+09 | 104.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395350E+10 |
February | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419126E+10 |
March | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1222147.29 | 0.252168E+10 |
April | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194809E+10 |
May | 0.536353E+10 | 0.189524E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1151323.85 | 0.112559E+10 |
June | 0.528933E+10 | 0.186250E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30272360.36 | 0.750246E+09 |
July | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65054848.55 | 0.401888E+09 |
August | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45963215.72 | 0.500450E+09 |
September | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3783175.63 | 0.758265E+09 |
October | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159001E+10 |
November | 0.504819E+10 | 0.179919E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221527E+10 |
December | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414508E+10 |
Annual Sum or Average | 0.628175E+11 | 0.221812E+11 | 0.499918E+11 | 0.147447E+09 | 0.241013E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401888E+09 |
Maximum of Months | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65054848.55 | 0.419126E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.187732E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345892E+10 |
February | 0.201852E+11 | 0.155013E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365502E+10 |
March | 0.230879E+11 | 0.172508E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 923976.39 | 0.222643E+10 |
April | 0.218263E+11 | 0.147422E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176242E+10 |
May | 0.225967E+11 | 0.152380E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942629.96 | 0.103601E+10 |
June | 0.222841E+11 | 0.145374E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24661230.83 | 0.675805E+09 |
July | 0.221389E+11 | 0.144398E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52789854.15 | 0.362520E+09 |
August | 0.230879E+11 | 0.151575E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37383142.03 | 0.442166E+09 |
September | 0.218263E+11 | 0.156098E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3096723.59 | 0.667576E+09 |
October | 0.221054E+11 | 0.173796E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139998E+10 |
November | 0.212681E+11 | 0.176186E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196350E+10 |
December | 0.221389E+11 | 0.187722E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362834E+10 |
Annual Sum or Average | 0.264651E+12 | 0.195020E+12 | 0.842987E+11 | 0.119798E+09 | 0.212787E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.144398E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362520E+09 |
Maximum of Months | 0.230879E+11 | 0.187732E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52789854.15 | 0.365502E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173524E+10 |
February | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183490E+10 |
March | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489286.43 | 0.114404E+10 |
April | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903630E+09 |
May | 0.212923E+10 | 0.195129E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499037.61 | 0.530151E+09 |
June | 0.209978E+10 | 0.191792E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12994095.02 | 0.351989E+09 |
July | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26295095.23 | 0.200142E+09 |
August | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19353005.85 | 0.246959E+09 |
September | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1639669.28 | 0.360263E+09 |
October | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763745E+09 |
November | 0.200405E+10 | 0.185183E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102509E+10 |
December | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181667E+10 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.529224E+11 | 61270189.41 | 0.109128E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200142E+09 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26295095.23 | 0.183490E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170754E+10 |
February | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181216E+10 |
March | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 489094.01 | 0.110695E+10 |
April | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855507E+09 |
May | 0.212923E+10 | 0.195129E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 498946.62 | 0.485269E+09 |
June | 0.209978E+10 | 0.191792E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13047055.62 | 0.321736E+09 |
July | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27424342.18 | 0.176568E+09 |
August | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19536807.63 | 0.223427E+09 |
September | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1639535.07 | 0.334247E+09 |
October | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711321E+09 |
November | 0.200405E+10 | 0.185183E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974190E+09 |
December | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178390E+10 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.794328E+10 | 62635781.13 | 0.104928E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176568E+09 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27424342.18 | 0.181216E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166505E+11 |
February | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157587E+11 |
March | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52092.80 | 0.100890E+11 |
April | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398059E+10 |
May | 0.00 | 0.127266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1161135.96 | 0.106984E+10 |
June | 0.00 | 0.125090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12033575.44 | 0.634000E+09 |
July | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24781322.39 | 0.333487E+09 |
August | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11200720.36 | 0.493163E+09 |
September | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102166E+10 |
October | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306565E+10 |
November | 0.00 | 0.120779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644196E+10 |
December | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160042E+11 |
Annual Sum or Average | 0.00 | 0.148942E+10 | 49228846.96 | 0.755427E+11 | |||||
Minimum of Months | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333487E+09 |
Maximum of Months | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24781322.39 | 0.166505E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 1543.42 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7921.72 | 12-JAN-06:00 |
February | 5888.82 | 01-FEB-15:09 | 1543.42 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 8287.45 | 13-FEB-05:52 |
March | 5888.82 | 01-MAR-15:09 | 1543.42 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.30 | 15-MAR-14:00 | 4416.58 | 02-MAR-05:04 |
April | 5888.82 | 01-APR-10:09 | 1543.42 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4383.13 | 16-APR-07:00 |
May | 5888.82 | 01-MAY-14:09 | 1543.42 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 | 14-MAY-15:00 | 2033.45 | 05-MAY-21:00 |
June | 5888.82 | 01-JUN-14:09 | 1543.42 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 314.14 | 12-JUN-13:00 | 2336.85 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 1543.42 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 487.41 | 21-JUL-03:00 | 1655.79 | 06-JUL-02:00 |
August | 5888.82 | 01-AUG-14:09 | 1543.42 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 391.94 | 13-AUG-18:03 | 1235.75 | 30-AUG-20:10 |
September | 5888.82 | 01-SEP-14:09 | 1543.42 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 16-SEP-13:00 | 1975.44 | 29-SEP-04:00 |
October | 5888.82 | 02-OCT-14:09 | 1543.42 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2263.71 | 07-OCT-02:00 |
November | 5888.82 | 01-NOV-14:09 | 1543.42 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4003.32 | 17-NOV-02:00 |
December | 5888.82 | 01-DEC-15:09 | 1543.42 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6535.66 | 28-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1235.75 | |||||
Maximum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 487.41 | 8287.45 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 17024.17 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6631.88 | 12-JAN-01:55 |
February | 24809.68 | 01-FEB-15:09 | 17024.17 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 6719.26 | 13-FEB-05:52 |
March | 24809.68 | 01-MAR-15:09 | 17024.17 | 01-MAR-15:00 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.18 | 15-MAR-14:00 | 4126.00 | 02-MAR-01:00 |
April | 24809.68 | 01-APR-10:09 | 17024.17 | 07-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3947.33 | 16-APR-02:00 |
May | 24809.68 | 01-MAY-14:09 | 17024.17 | 11-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.02 | 14-MAY-15:00 | 1889.56 | 05-MAY-21:00 |
June | 24809.68 | 01-JUN-14:09 | 15605.49 | 01-JUN-16:40 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 257.15 | 12-JUN-13:00 | 2124.28 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 15605.49 | 03-JUL-16:40 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 401.33 | 21-JUL-03:00 | 1527.63 | 06-JUL-02:00 |
August | 24809.68 | 01-AUG-14:09 | 17024.17 | 28-AUG-16:10 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.08 | 13-AUG-18:03 | 1056.10 | 30-AUG-20:40 |
September | 24809.68 | 01-SEP-14:09 | 17024.17 | 01-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.39 | 16-SEP-13:00 | 1841.74 | 29-SEP-04:00 |
October | 24809.68 | 02-OCT-14:09 | 17024.17 | 02-OCT-16:40 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2059.35 | 07-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 17024.17 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3836.90 | 17-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 17024.17 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5389.83 | 28-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 15605.49 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.10 | |||||
Maximum of Months | 24809.68 | 17024.17 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 401.33 | 6719.26 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3412.29 | 12-JAN-05:43 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3591.20 | 13-FEB-05:52 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 15-MAR-14:00 | 2082.83 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1899.34 | 16-APR-07:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 14-MAY-15:00 | 971.33 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.12 | 12-JUN-13:00 | 1066.56 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 | 15-JUL-15:00 | 770.93 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.94 | 13-AUG-18:03 | 555.04 | 30-AUG-20:30 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 | 16-SEP-13:00 | 893.17 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1029.29 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1932.56 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2834.28 | 28-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.04 | |||||
Maximum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 | 3591.20 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3432.72 | 12-JAN-05:53 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3540.09 | 13-FEB-05:52 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 15-MAR-14:00 | 1992.73 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1899.34 | 16-APR-07:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 14-MAY-15:00 | 897.05 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 | 12-JUN-13:00 | 1013.51 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.85 | 15-JUL-15:00 | 710.63 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.67 | 13-AUG-18:03 | 529.68 | 30-AUG-20:10 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 | 16-SEP-13:00 | 825.11 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 962.50 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1803.16 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2829.44 | 28-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.68 | |||||
Maximum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 185.85 | 3540.09 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 35429.18 | 31-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 38701.27 | 06-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.93 | 12-MAR-12:53 | 30620.64 | 06-MAR-18:00 |
April | 0.00 | 01-APR-00:10 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 23115.29 | 16-APR-11:10 |
May | 0.00 | 01-MAY-00:10 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.89 | 10-MAY-12:55 | 5000.17 | 24-MAY-11:01 |
June | 0.00 | 01-JUN-00:10 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.71 | 12-JUN-11:03 | 6750.30 | 13-JUN-11:01 |
July | 0.00 | 01-JUL-00:10 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.99 | 15-JUL-13:55 | 2908.78 | 02-JUL-11:01 |
August | 0.00 | 01-AUG-00:10 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.05 | 13-AUG-11:03 | 4061.49 | 31-AUG-11:01 |
September | 0.00 | 01-SEP-00:10 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 4569.31 | 10-SEP-11:01 |
October | 0.00 | 01-OCT-00:10 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14756.04 | 24-OCT-11:02 |
November | 0.00 | 01-NOV-00:10 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 18517.22 | 22-NOV-18:00 |
December | 0.00 | 01-DEC-00:10 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 36492.55 | 10-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.78 | ||||
Maximum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.99 | 38701.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5051.76 | 15-JAN-09:05 | 2944.41 | 685.97 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.38 |
February | 4690.26 | 19-FEB-09:05 | 2944.41 | 685.97 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.88 |
March | 5075.71 | 19-MAR-08:05 | 2944.41 | 685.97 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.39 |
April | 6086.26 | 03-APR-06:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.59 |
May | 5438.02 | 27-MAY-16:00 | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 |
June | 27174.08 | 28-JUN-06:02 | 4416.61 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.49 |
July | 32705.34 | 12-JUL-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 |
August | 33315.16 | 01-AUG-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 |
September | 23828.89 | 15-SEP-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 |
October | 6232.32 | 17-OCT-06:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.68 |
November | 5641.05 | 15-NOV-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.14 |
December | 5560.92 | 16-DEC-07:05 | 2944.41 | 685.97 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4690.26 | 2944.41 | 685.97 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | |
Maximum of Months | 33315.16 | 5888.82 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 61907.12 | 12-JAN-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.26 |
February | 62536.09 | 25-FEB-07:05 | 12404.84 | 7566.30 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.67 |
March | 66022.63 | 04-MAR-07:05 | 12404.84 | 7566.30 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.69 |
April | 52913.43 | 17-APR-06:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.83 |
May | 141787.86 | 28-MAY-08:62 | 12404.84 | 6305.25 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.96 |
June | 167439.96 | 13-JUN-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.14 |
July | 150387.40 | 06-JUL-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.06 |
August | 162967.82 | 03-AUG-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.28 |
September | 153109.02 | 23-SEP-06:02 | 15506.05 | 9457.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.15 |
October | 44020.97 | 30-OCT-06:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.72 |
November | 50757.12 | 24-NOV-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.30 |
December | 63486.00 | 08-DEC-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 44020.97 | 12404.84 | 6305.25 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.15 | |
Maximum of Months | 167439.96 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1498.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5347.21 | 12-JAN-20:33 | 3506.64 | 3564.78 | 9087.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.45 |
February | 5846.21 | 21-FEB-11:23 | 8182.17 | 6416.60 | 11683.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.50 |
March | 6134.68 | 15-MAR-13:40 | 2045.54 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 0.00 |
April | 4678.81 | 03-APR-06:05 | 1168.88 | 1425.91 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.71 |
May | 12816.73 | 24-MAY-06:03 | 1168.88 | 1425.91 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.83 |
June | 19190.42 | 20-JUN-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.08 |
July | 20326.88 | 12-JUL-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 |
August | 21667.30 | 02-AUG-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21025.04 | 23-SEP-06:02 | 1461.10 | 891.19 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 |
October | 10090.18 | 12-OCT-06:03 | 876.66 | 1069.43 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.65 |
November | 4688.61 | 01-NOV-12:00 | 2045.54 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.74 |
December | 6186.83 | 10-DEC-16:52 | 5844.40 | 5347.17 | 12981.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4678.81 | 876.66 | 891.19 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21667.30 | 8182.17 | 6416.60 | 12981.72 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 539.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4956.83 | 12-JAN-06:04 | 0.00 | 802.08 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.72 |
February | 5153.03 | 08-FEB-06:04 | 0.00 | 802.08 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.50 |
March | 4621.68 | 24-MAR-05:05 | 0.00 | 712.96 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.07 |
April | 4062.07 | 03-APR-06:05 | 1168.88 | 1425.91 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.55 |
May | 3350.91 | 01-MAY-06:05 | 1168.88 | 1425.91 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10200.25 | 26-JUN-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 |
July | 10713.33 | 05-JUL-06:02 | 1753.32 | 2138.87 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.24 |
August | 12211.22 | 13-AUG-08:62 | 1753.32 | 1069.43 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 |
September | 9424.45 | 17-SEP-08:62 | 1461.10 | 891.19 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 |
October | 5627.06 | 11-OCT-14:30 | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 |
November | 3894.89 | 25-NOV-07:05 | 1168.88 | 712.96 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.09 |
December | 4556.84 | 10-DEC-08:06 | 0.00 | 802.08 | 657.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3350.91 | 0.00 | 712.96 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12211.22 | 2337.76 | 2138.87 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.58 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.54 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.05 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.87 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | |
Maximum of Months | 0.00 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.54 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.620675E+11 | 46942.73 | 31-JAN-17:00 | 0.161218E+12 | 223958.55 | 24-JAN-07:10 |
February | 0.546227E+11 | 47295.62 | 06-FEB-17:00 | 0.152149E+12 | 253027.16 | 07-FEB-07:10 |
March | 0.587539E+11 | 49235.57 | 15-MAR-16:30 | 0.906433E+11 | 218678.28 | 06-MAR-07:10 |
April | 0.515234E+11 | 41834.19 | 15-APR-16:00 | 0.377990E+11 | 169436.51 | 17-APR-06:10 |
May | 0.539414E+11 | 51697.20 | 10-MAY-15:20 | 0.957654E+10 | 75347.28 | 01-MAY-06:10 |
June | 0.658762E+11 | 68205.80 | 27-JUN-12:00 | 0.778787E+10 | 5695.89 | 14-JUN-06:30 |
July | 0.793752E+11 | 75297.99 | 15-JUL-13:00 | 0.783659E+10 | 4988.26 | 03-JUL-11:09 |
August | 0.757044E+11 | 66670.64 | 10-AUG-14:50 | 0.786634E+10 | 4965.57 | 01-AUG-11:20 |
September | 0.613132E+11 | 64138.58 | 16-SEP-15:50 | 0.766601E+10 | 22954.22 | 30-SEP-06:49 |
October | 0.557425E+11 | 48939.26 | 11-OCT-15:20 | 0.210249E+11 | 126395.79 | 30-OCT-06:10 |
November | 0.561315E+11 | 45516.29 | 24-NOV-17:00 | 0.539544E+11 | 166774.37 | 24-NOV-07:10 |
December | 0.618013E+11 | 46942.38 | 11-DEC-17:00 | 0.147081E+12 | 246729.33 | 11-DEC-07:10 |
Annual Sum or Average | 0.736853E+12 | 0.704603E+12 | ||||
Minimum of Months | 0.515234E+11 | 41834.19 | 0.766601E+10 | 4965.57 | ||
Maximum of Months | 0.793752E+11 | 75297.99 | 0.161218E+12 | 253027.16 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.245886E+11 | 0.465828E+10 | 0.164409E+11 | 0.00 | 0.163798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207923E+11 | 0.383412E+10 | 0.149157E+11 | 0.00 | 0.150805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232856E+11 | 0.372968E+10 | 0.168545E+11 | 0.00 | 0.143496E+11 | 0.00 | 0.00 | 0.534508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204363E+11 | 0.308879E+10 | 0.160165E+11 | 0.00 | 0.119242E+11 | 0.00 | 0.00 | 57552234.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211630E+11 | 0.275261E+10 | 0.166477E+11 | 0.00 | 0.108522E+11 | 0.00 | 0.00 | 0.252583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.203609E+11 | 0.246650E+10 | 0.162772E+11 | 0.00 | 0.106140E+11 | 0.00 | 0.00 | 0.161576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202356E+11 | 0.261441E+10 | 0.163871E+11 | 0.00 | 0.109715E+11 | 0.00 | 0.00 | 0.291666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.211923E+11 | 0.298680E+10 | 0.168545E+11 | 0.00 | 0.110028E+11 | 0.00 | 0.00 | 0.236680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.213039E+11 | 0.338515E+10 | 0.160165E+11 | 0.00 | 0.105116E+11 | 0.00 | 0.00 | 0.100960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231949E+11 | 0.403197E+10 | 0.164409E+11 | 0.00 | 0.115169E+11 | 0.00 | 0.00 | 0.557740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232422E+11 | 0.436512E+10 | 0.159174E+11 | 0.00 | 0.126025E+11 | 0.00 | 0.00 | 4217106.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245679E+11 | 0.478275E+10 | 0.163871E+11 | 0.00 | 0.160636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264364E+12 | 0.426962E+11 | 0.195156E+12 | 0.151869E+12 | 0.00 | 0.827682E+11 | |||||||
Minimum of Months | 0.202356E+11 | 0.246650E+10 | 0.149157E+11 | 0.00 | 0.105116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.245886E+11 | 0.478275E+10 | 0.168545E+11 | 0.00 | 0.163798E+11 | 0.00 | 0.00 | 0.291666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.152753E+12 | 0.00 | 0.846489E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.144441E+12 | 0.00 | 0.770789E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.820863E+11 | 0.00 | 0.855695E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.296917E+11 | 0.00 | 0.810727E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.138500E+10 | 0.00 | 0.819154E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5717028.40 | 0.00 | 0.778215E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.783659E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.786634E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 45546289.29 | 0.00 | 0.762046E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.130409E+11 | 0.00 | 0.798399E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.460637E+11 | 0.00 | 0.789072E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.138739E+12 | 0.00 | 0.834216E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.608252E+12 | 0.963509E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.762046E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.152753E+12 | 0.00 | 0.855695E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21880.52 | 02-JAN-09:09 | 3292.90 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 12490.71 | 29-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 21880.52 | 01-FEB-09:09 | 3292.90 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 12807.63 | 05-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 21880.52 | 01-MAR-15:00 | 3292.90 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 12288.40 | 05-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 21880.52 | 07-APR-16:00 | 3292.90 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 11539.65 | 16-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 21880.52 | 11-MAY-16:49 | 3292.90 | 01-MAY-05:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 9370.33 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 20461.84 | 01-JUN-16:40 | 3292.90 | 01-JUN-19:49 | 10771.04 | 01-JUN-08:09 | 0.00 | 11457.18 | 18-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 20461.84 | 03-JUL-16:40 | 3292.90 | 01-JUL-19:00 | 10771.04 | 01-JUL-09:09 | 0.00 | 11887.43 | 20-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 21880.52 | 28-AUG-16:10 | 3292.90 | 01-AUG-19:40 | 10771.04 | 01-AUG-08:09 | 0.00 | 11434.83 | 14-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 21880.52 | 01-SEP-16:00 | 3292.90 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 10199.73 | 17-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21880.52 | 02-OCT-16:40 | 3292.90 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 10270.95 | 17-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 21880.52 | 01-NOV-08:09 | 3292.90 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 11145.27 | 23-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 21880.52 | 01-DEC-09:09 | 3292.90 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 12824.95 | 10-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 20461.84 | 3292.90 | 10771.04 | 0.00 | 9370.33 | 0.00 | 0.00 | |||||
Maximum of Months | 21880.52 | 3292.90 | 10771.04 | 0.00 | 12824.95 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14081.17 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4355.61 | 08-APR-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17814.39 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35665.16 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37824.08 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32602.94 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27448.96 | 16-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10387.82 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 451.19 | 16-NOV-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37824.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 46942.73 | 31-JAN-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 10998.28 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 47295.62 | 06-FEB-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 11351.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49235.57 | 15-MAR-16:30 | 20461.84 | 10771.04 | 0.00 | 0.00 | 6692.74 | 0.00 | 0.00 | 11309.96 | 0.00 |
April | 41834.19 | 15-APR-16:00 | 21880.52 | 10771.04 | 0.00 | 0.00 | 9182.63 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51697.20 | 10-MAY-15:20 | 17624.48 | 10771.04 | 0.00 | 0.00 | 6692.74 | 0.00 | 0.00 | 16608.94 | 0.00 |
June | 68205.80 | 27-JUN-12:00 | 13368.43 | 10771.04 | 0.00 | 0.00 | 8401.17 | 0.00 | 0.00 | 35665.16 | 0.00 |
July | 75297.99 | 15-JUL-13:00 | 17624.48 | 10771.04 | 0.00 | 0.00 | 9078.40 | 0.00 | 0.00 | 37824.08 | 0.00 |
August | 66670.64 | 10-AUG-14:50 | 17624.48 | 10771.04 | 0.00 | 0.00 | 7164.50 | 0.00 | 0.00 | 31110.62 | 0.00 |
September | 64138.58 | 16-SEP-15:50 | 20461.84 | 10771.04 | 0.00 | 0.00 | 6784.85 | 0.00 | 0.00 | 26120.86 | 0.00 |
October | 48939.26 | 11-OCT-15:20 | 21880.52 | 10771.04 | 0.00 | 0.00 | 6692.74 | 0.00 | 0.00 | 9594.96 | 0.00 |
November | 45516.29 | 24-NOV-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 9571.84 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 46942.38 | 11-DEC-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 10997.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 41834.19 | 13368.43 | 10771.04 | 0.00 | 0.00 | 6692.74 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75297.99 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 11351.17 | 0.00 | 0.00 | 37824.08 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 219385.53 | 24-JAN-07:10 | 0.00 | 5164.90 | 26-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 251165.16 | 07-FEB-07:10 | 0.00 | 5227.47 | 14-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 215778.02 | 07-MAR-07:10 | 0.00 | 5195.48 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 167574.51 | 17-APR-06:10 | 0.00 | 5129.09 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 73485.28 | 01-MAY-06:10 | 0.00 | 5086.97 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 3153.82 | 14-JUN-06:10 | 0.00 | 5032.37 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4988.26 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4965.57 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 18367.99 | 30-SEP-06:49 | 0.00 | 4988.18 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 124533.79 | 30-OCT-06:10 | 0.00 | 5033.20 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 162215.12 | 24-NOV-07:10 | 0.00 | 5084.58 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 243561.69 | 11-DEC-07:10 | 0.00 | 5127.66 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4965.57 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 251165.16 | 0.00 | 5227.47 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 17.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.33 | 16.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.83 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 16.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.67 | 16.94 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 16.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.50 | 16.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 16.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.17 | 16.58 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 16.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7.33 | 16.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 17.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.67 | 16.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.33 | 16.57 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.33 | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.50 | 12.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.67 | 12.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47.00 | 12.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 119.00 | 13.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58.50 | 14.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6.83 | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9.17 | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 111.67 | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80.17 | 12.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 12.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 457.33 | 12.83 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.00 | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 407.83 | 21.11 | 407.83 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.34 | 300.00 | 21.13 | 300.00 | 21.13 |
April | 405.00 | 21.52 | 135.17 | 21.11 | 135.17 | 21.11 |
May | 404.67 | 23.06 | 14.17 | 22.10 | 14.17 | 22.10 |
June | 160.17 | 23.72 | 157.33 | 23.89 | 43.17 | 23.89 |
July | 87.00 | 23.89 | 341.83 | 23.89 | 83.00 | 23.90 |
August | 57.17 | 23.85 | 259.33 | 23.89 | 44.33 | 23.89 |
September | 199.33 | 23.57 | 109.67 | 23.89 | 33.83 | 23.89 |
October | 408.83 | 22.18 | 38.17 | 21.12 | 38.17 | 21.12 |
November | 399.00 | 21.25 | 199.00 | 21.11 | 199.00 | 21.11 |
December | 415.00 | 21.11 | 397.00 | 21.11 | 397.00 | 21.11 |
Annual Sum or Average | 3748.17 | 21.87 | 2735.50 | 22.00 | 2071.67 | 21.39 |
Minimum of Months | 57.17 | 21.11 | 14.17 | 21.11 | 14.17 | 21.11 |
Maximum of Months | 422.00 | 23.89 | 407.83 | 23.89 | 407.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 367.67 | 21.11 | 367.67 | 21.11 |
February | 376.00 | 21.11 | 337.33 | 21.11 | 337.33 | 21.11 |
March | 413.50 | 21.31 | 165.00 | 21.12 | 164.50 | 21.11 |
April | 405.00 | 21.68 | 23.67 | 21.11 | 23.67 | 21.11 |
May | 240.67 | 22.82 | 35.17 | 23.88 | 3.33 | 23.89 |
June | 60.17 | 23.52 | 253.00 | 23.89 | 27.17 | 23.89 |
July | 61.83 | 23.90 | 398.67 | 23.89 | 61.83 | 23.90 |
August | 37.33 | 23.82 | 352.67 | 23.89 | 33.17 | 23.89 |
September | 91.33 | 23.14 | 185.33 | 23.88 | 20.83 | 23.88 |
October | 374.50 | 21.92 | 10.50 | 22.21 | 6.33 | 21.11 |
November | 399.00 | 21.28 | 62.50 | 21.11 | 62.50 | 21.11 |
December | 415.00 | 21.11 | 301.67 | 21.11 | 301.67 | 21.11 |
Annual Sum or Average | 3288.33 | 21.63 | 2493.17 | 22.48 | 1410.00 | 21.40 |
Minimum of Months | 37.33 | 21.11 | 10.50 | 21.11 | 3.33 | 21.11 |
Maximum of Months | 415.00 | 23.90 | 398.67 | 23.89 | 367.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 363.67 | 21.11 | 363.67 | 21.11 |
February | 376.00 | 21.13 | 322.67 | 21.11 | 322.67 | 21.11 |
March | 393.83 | 21.45 | 164.50 | 21.28 | 154.17 | 21.11 |
April | 388.00 | 22.14 | 58.17 | 21.11 | 58.17 | 21.11 |
May | 246.17 | 23.18 | 29.83 | 23.73 | 1.67 | 21.11 |
June | 65.00 | 23.58 | 231.67 | 23.89 | 18.33 | 23.89 |
July | 29.33 | 23.90 | 392.83 | 23.89 | 28.50 | 23.90 |
August | 18.50 | 23.82 | 382.17 | 23.89 | 15.50 | 23.90 |
September | 52.83 | 23.30 | 258.83 | 23.89 | 7.33 | 23.90 |
October | 280.17 | 22.49 | 54.17 | 23.33 | 10.83 | 21.11 |
November | 383.33 | 21.76 | 75.50 | 21.11 | 75.50 | 21.11 |
December | 415.00 | 21.14 | 336.00 | 21.11 | 336.00 | 21.11 |
Annual Sum or Average | 3062.17 | 21.80 | 2670.00 | 22.51 | 1392.33 | 21.25 |
Minimum of Months | 18.50 | 21.11 | 29.83 | 21.11 | 1.67 | 21.11 |
Maximum of Months | 415.00 | 23.90 | 392.83 | 23.89 | 363.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 391.83 | 21.11 | 391.83 | 21.11 |
February | 376.00 | 21.11 | 357.33 | 21.11 | 357.33 | 21.11 |
March | 403.83 | 21.26 | 215.17 | 21.13 | 213.67 | 21.11 |
April | 402.50 | 21.70 | 97.67 | 21.11 | 97.67 | 21.11 |
May | 326.33 | 22.69 | 18.67 | 22.09 | 12.17 | 21.13 |
June | 101.67 | 23.24 | 195.50 | 23.88 | 16.33 | 23.83 |
July | 33.00 | 23.69 | 371.33 | 23.89 | 21.83 | 23.91 |
August | 35.67 | 23.53 | 335.67 | 23.89 | 15.00 | 23.90 |
September | 92.17 | 22.82 | 207.17 | 23.89 | 4.67 | 23.81 |
October | 332.17 | 21.93 | 42.17 | 22.30 | 24.17 | 21.12 |
November | 399.00 | 21.48 | 144.17 | 21.11 | 144.17 | 21.11 |
December | 415.00 | 21.11 | 378.83 | 21.11 | 378.83 | 21.11 |
Annual Sum or Average | 3331.33 | 21.64 | 2755.50 | 22.26 | 1677.67 | 21.21 |
Minimum of Months | 33.00 | 21.11 | 18.67 | 21.11 | 4.67 | 21.11 |
Maximum of Months | 415.00 | 23.69 | 391.83 | 23.89 | 391.83 | 23.91 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09513 | 21.91231 | -0.7289 | 16.36255 |
February | 376.00000 | 21.09517 | 21.86744 | -0.7317 | 16.43578 |
March | 422.00000 | 21.32819 | 31.13101 | -0.5572 | 13.01050 |
April | 405.00000 | 21.51102 | 36.69353 | -0.4274 | 9.63528 |
May | 418.00000 | 23.07611 | 40.76246 | -1.0085 | 28.21238 |
June | 408.00000 | 23.82342 | 47.94186 | -0.5698 | 12.34244 |
July | 415.00000 | 23.90301 | 55.39151 | -0.4262 | 8.91200 |
August | 422.00000 | 23.89503 | 51.58375 | -0.4694 | 9.74109 |
September | 405.00000 | 23.73149 | 48.78754 | -0.6260 | 14.00489 |
October | 414.00000 | 22.18737 | 41.66831 | -0.1860 | 7.51559 |
November | 399.00000 | 21.23443 | 35.04346 | -0.5077 | 10.85313 |
December | 415.00000 | 21.09626 | 25.66724 | -0.6844 | 15.08265 |
Annual Sum or Average | 4913.00000 | 22.34300 | 38.32499 | -0.5763 | 13.50652 |
Minimum of Months | 376.00000 | 21.09513 | 21.86744 | -1.0085 | 7.51559 |
Maximum of Months | 422.00000 | 23.90301 | 55.39151 | -0.1860 | 28.21238 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09611 | 19.37308 | -0.6325 | 13.54902 |
February | 376.00000 | 21.09617 | 19.28848 | -0.6316 | 13.51282 |
March | 422.00000 | 21.35368 | 28.18097 | -0.4378 | 10.32023 |
April | 405.00000 | 21.68531 | 33.78505 | -0.2762 | 7.57393 |
May | 418.00000 | 23.27288 | 37.81871 | -0.7918 | 19.97726 |
June | 408.00000 | 23.84305 | 46.20898 | -0.4461 | 9.57472 |
July | 415.00000 | 23.90834 | 54.10325 | -0.3355 | 7.45994 |
August | 422.00000 | 23.89632 | 50.23537 | -0.3857 | 8.25359 |
September | 405.00000 | 23.71912 | 47.49018 | -0.5272 | 11.53731 |
October | 414.00000 | 22.11019 | 39.11519 | -0.1195 | 6.93098 |
November | 399.00000 | 21.28077 | 32.60475 | -0.4115 | 9.06004 |
December | 415.00000 | 21.10044 | 23.10827 | -0.5921 | 12.55584 |
Annual Sum or Average | 4913.00000 | 22.37524 | 36.06520 | -0.4649 | 10.85207 |
Minimum of Months | 376.00000 | 21.09611 | 19.28848 | -0.7918 | 6.93098 |
Maximum of Months | 422.00000 | 23.90834 | 54.10325 | -0.1195 | 19.97726 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09981 | 18.69741 | -0.6592 | 14.41437 |
February | 376.00000 | 21.11825 | 18.64189 | -0.6549 | 14.36360 |
March | 422.00000 | 21.59977 | 27.00136 | -0.3908 | 10.23607 |
April | 405.00000 | 22.20084 | 31.85007 | -0.2032 | 7.85406 |
May | 418.00000 | 23.46080 | 36.10045 | -0.7808 | 19.65897 |
June | 408.00000 | 23.84975 | 44.57278 | -0.4565 | 9.93785 |
July | 415.00000 | 23.90863 | 51.83908 | -0.3164 | 7.24218 |
August | 422.00000 | 23.90461 | 47.96071 | -0.3384 | 7.58191 |
September | 405.00000 | 23.81951 | 44.64434 | -0.4450 | 9.87047 |
October | 414.00000 | 22.93759 | 36.03676 | 0.07066 | 7.19499 |
November | 399.00000 | 21.83884 | 30.81272 | -0.2947 | 8.66056 |
December | 415.00000 | 21.12773 | 22.47485 | -0.6199 | 13.45016 |
Annual Sum or Average | 4913.00000 | 22.58378 | 34.33620 | -0.4231 | 10.86090 |
Minimum of Months | 376.00000 | 21.09981 | 18.64189 | -0.7808 | 7.19499 |
Maximum of Months | 422.00000 | 23.90863 | 51.83908 | 0.07066 | 19.65897 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09511 | 18.57050 | -0.7018 | 15.61092 |
February | 376.00000 | 21.09532 | 18.57921 | -0.6998 | 15.57626 |
March | 422.00000 | 21.35865 | 27.39804 | -0.4844 | 11.50234 |
April | 405.00000 | 21.69598 | 33.01871 | -0.3460 | 9.07530 |
May | 418.00000 | 22.92449 | 38.70211 | -0.9882 | 28.05313 |
June | 408.00000 | 23.71549 | 46.81955 | -0.5459 | 12.37111 |
July | 415.00000 | 23.87759 | 53.57519 | -0.3724 | 8.13997 |
August | 422.00000 | 23.85886 | 49.34308 | -0.4032 | 8.71881 |
September | 405.00000 | 23.63198 | 46.27814 | -0.5514 | 12.81915 |
October | 414.00000 | 22.30151 | 37.80263 | -0.0958 | 7.57296 |
November | 399.00000 | 21.46856 | 31.58625 | -0.4151 | 9.85600 |
December | 415.00000 | 21.09914 | 22.43009 | -0.6678 | 14.64808 |
Annual Sum or Average | 4913.00000 | 22.35443 | 35.46697 | -0.5220 | 12.82690 |
Minimum of Months | 376.00000 | 21.09511 | 18.57050 | -0.9882 | 7.57296 |
Maximum of Months | 422.00000 | 23.87759 | 53.57519 | -0.0958 | 28.05313 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.102200E+09 | 28538891.19 | 11.53 | 81093757.33 | 21106048.46 | 0.00 | 0.37 | 15-MAR-14:50 | 0.00 | 01-MAR-00:10 | 5018.90 | 15-MAR-15:00 | 4052.35 | 15-MAR-14:30 | 982.53 | 15-MAR-15:00 | 1379.69 | 15-MAR-14:40 | 0.00 | 01-MAR-00:10 |
April | 180.48 | 51.31 | 0.50 | 149.90 | 30.58 | 0.00 | 0.00 | 08-APR-13:20 | 0.00 | 01-APR-00:10 | 0.19 | 08-APR-13:20 | 0.16 | 08-APR-13:20 | 0.03 | 08-APR-13:20 | 0.06 | 08-APR-13:20 | 0.00 | 01-APR-00:10 |
May | 0.580878E+09 | 0.156591E+09 | 106.67 | 0.512292E+09 | 68585522.81 | 0.00 | 0.49 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 | 6999.55 | 10-MAY-15:00 | 5402.06 | 23-MAY-15:00 | 1872.01 | 10-MAY-15:00 | 1856.45 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.705763E+10 | 0.174350E+10 | 323.12 | 0.505886E+10 | 0.199877E+10 | 0.00 | 1.00 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 | 35873.93 | 18-JUN-08:62 | 22391.27 | 12-JUN-06:02 | 17919.09 | 18-JUN-08:04 | 7568.19 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.152412E+11 | 0.363685E+10 | 394.42 | 0.101773E+11 | 0.506389E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 36255.32 | 21-JUL-06:02 | 22707.12 | 15-JUL-06:02 | 19979.44 | 29-JUL-06:04 | 7663.61 | 21-JUL-06:15 | 0.00 | 01-JUL-00:10 |
August | 0.119266E+11 | 0.291453E+10 | 377.66 | 0.876491E+10 | 0.316168E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 35988.10 | 14-AUG-06:02 | 25075.00 | 06-AUG-08:62 | 20052.35 | 14-AUG-06:06 | 7460.75 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.411591E+10 | 0.101686E+10 | 249.57 | 0.281141E+10 | 0.130450E+10 | 0.00 | 1.00 | 14-SEP-06:02 | 0.00 | 01-SEP-00:10 | 34812.41 | 16-SEP-06:02 | 18900.92 | 17-SEP-08:62 | 17597.66 | 14-SEP-06:02 | 7304.46 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 30188515.90 | 8395638.37 | 27.36 | 26104486.73 | 4084029.18 | 0.00 | 0.20 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2554.92 | 11-OCT-15:00 | 2196.19 | 11-OCT-15:00 | 358.73 | 11-OCT-15:00 | 700.75 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.390546E+11 | 0.950527E+10 | 1490.83 | 0.274320E+11 | 0.116226E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.152412E+11 | 0.363685E+10 | 394.42 | 0.101773E+11 | 0.506389E+10 | 0.00 | 1.00 | 0.00 | 36255.32 | 25075.00 | 20052.35 | 7663.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.120442E+10 | 0.365273E+09 | 19.25 | 0.950241E+09 | 0.254174E+09 | 0.00 | 0.50 | 15-MAR-14:30 | 0.00 | 01-MAR-00:10 | 32293.79 | 15-MAR-14:30 | 27403.34 | 15-MAR-14:30 | 7067.04 | 14-MAR-13:20 | 9655.07 | 15-MAR-14:30 | 0.00 | 01-MAR-00:10 |
April | 76618314.47 | 23519304.61 | 8.71 | 63412839.19 | 13205475.28 | 0.00 | 0.16 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 9522.25 | 08-APR-13:30 | 7953.51 | 08-APR-13:30 | 1695.98 | 08-APR-14:00 | 2899.79 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.647202E+10 | 0.187831E+10 | 137.17 | 0.553697E+10 | 0.935050E+09 | 0.00 | 1.00 | 24-MAY-06:03 | 0.00 | 01-MAY-00:10 | 153148.61 | 24-MAY-06:03 | 123032.76 | 28-MAY-08:62 | 48755.89 | 24-MAY-06:03 | 36434.32 | 24-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.434596E+11 | 0.117852E+11 | 343.77 | 0.306423E+11 | 0.128173E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 170199.20 | 18-JUN-08:62 | 131453.33 | 11-JUN-08:62 | 84689.86 | 08-JUN-06:03 | 40080.61 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.791941E+11 | 0.208452E+11 | 400.04 | 0.515597E+11 | 0.276344E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 172721.01 | 21-JUL-05:03 | 107228.83 | 15-JUL-06:02 | 90821.28 | 29-JUL-06:04 | 40524.37 | 21-JUL-05:03 | 0.00 | 01-JUL-00:10 |
August | 0.613843E+11 | 0.166135E+11 | 384.38 | 0.441621E+11 | 0.172223E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 170108.58 | 14-AUG-06:02 | 117257.63 | 13-AUG-08:62 | 90673.88 | 14-AUG-06:04 | 39488.93 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.246305E+11 | 0.676949E+10 | 272.85 | 0.167502E+11 | 0.788033E+10 | 0.00 | 1.00 | 08-SEP-06:03 | 0.00 | 01-SEP-00:10 | 165097.98 | 16-SEP-06:02 | 109845.36 | 08-SEP-06:03 | 80685.94 | 14-SEP-06:04 | 38694.43 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.642981E+09 | 0.194974E+09 | 34.16 | 0.520602E+09 | 0.122379E+09 | 0.00 | 0.36 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 22011.75 | 11-OCT-15:00 | 18303.86 | 11-OCT-15:00 | 3707.89 | 11-OCT-15:00 | 6476.61 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 3052.36 | 969.44 | 0.50 | 2163.18 | 889.19 | 0.00 | 0.00 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 | 2.62 | 04-NOV-15:40 | 1.86 | 04-NOV-15:40 | 0.77 | 04-NOV-15:40 | 0.83 | 04-NOV-15:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.217065E+12 | 0.584755E+11 | 1600.82 | 0.150186E+12 | 0.668791E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.791941E+11 | 0.208452E+11 | 400.04 | 0.515597E+11 | 0.276344E+11 | 0.00 | 1.00 | 0.00 | 172721.01 | 131453.33 | 90821.28 | 40524.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.353000E+09 | 88613560.85 | 30.62 | 0.290850E+09 | 62150011.22 | 0.00 | 0.84 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 7739.01 | 15-MAR-13:40 | 7009.52 | 15-MAR-13:50 | 1637.27 | 14-MAR-12:00 | 1876.13 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 60539773.27 | 15937746.35 | 41.87 | 54243698.81 | 6296074.46 | 0.00 | 0.43 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 3477.37 | 08-APR-13:40 | 3044.47 | 08-APR-13:30 | 493.85 | 08-APR-14:00 | 881.12 | 08-APR-13:40 | 0.00 | 01-APR-00:10 |
May | 0.110381E+10 | 0.281168E+09 | 204.73 | 0.974181E+09 | 0.129625E+09 | 0.00 | 0.81 | 28-MAY-08:62 | 0.00 | 01-MAY-00:10 | 14888.31 | 24-MAY-06:03 | 9821.06 | 24-MAY-06:03 | 5067.25 | 24-MAY-06:03 | 3170.47 | 24-MAY-06:03 | 0.00 | 01-MAY-00:10 |
June | 0.651569E+10 | 0.155067E+10 | 353.07 | 0.481766E+10 | 0.169804E+10 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 22059.61 | 18-JUN-08:62 | 17202.25 | 11-JUN-08:62 | 11011.65 | 18-JUN-08:04 | 4645.04 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.120990E+11 | 0.279737E+10 | 401.94 | 0.836336E+10 | 0.373562E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 22627.25 | 21-JUL-05:03 | 13848.02 | 15-JUL-06:02 | 12140.94 | 29-JUL-06:04 | 4698.78 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.104668E+11 | 0.244555E+10 | 396.10 | 0.793839E+10 | 0.252840E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 22103.13 | 14-AUG-06:02 | 15434.26 | 06-AUG-08:62 | 12307.24 | 14-AUG-06:04 | 4578.71 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.569729E+10 | 0.132491E+10 | 318.67 | 0.417996E+10 | 0.151733E+10 | 0.00 | 1.00 | 09-SEP-06:02 | 0.00 | 01-SEP-00:10 | 21350.10 | 16-SEP-06:02 | 13914.84 | 08-SEP-06:03 | 10658.46 | 14-SEP-06:02 | 4481.00 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.749692E+09 | 0.185736E+09 | 111.50 | 0.612581E+09 | 0.137111E+09 | 0.00 | 0.91 | 11-OCT-14:40 | 0.00 | 01-OCT-00:10 | 8500.74 | 11-OCT-14:40 | 7562.79 | 11-OCT-14:30 | 2189.28 | 12-OCT-06:03 | 1899.45 | 11-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 5729346.84 | 1593039.76 | 20.33 | 4553844.15 | 1175502.69 | 0.00 | 0.13 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 | 935.66 | 16-NOV-12:40 | 790.87 | 16-NOV-12:40 | 146.12 | 16-NOV-13:00 | 256.77 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.370515E+11 | 0.869156E+10 | 1878.83 | 0.272358E+11 | 0.981574E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.120990E+11 | 0.279737E+10 | 401.94 | 0.836336E+10 | 0.373562E+10 | 0.00 | 1.00 | 0.00 | 22627.25 | 17202.25 | 12307.24 | 4698.78 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
March | 0.229710E+09 | 52082388.68 | 22.25 | 0.189216E+09 | 40494229.25 | 0.00 | 0.73 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 5630.35 | 15-MAR-13:50 | 5065.97 | 15-MAR-13:50 | 1137.98 | 14-MAR-13:00 | 1228.63 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 77057889.12 | 18095132.58 | 25.83 | 72218401.00 | 4839488.13 | 0.00 | 0.37 | 08-APR-13:40 | 0.00 | 01-APR-00:10 | 2558.93 | 08-APR-13:50 | 2251.76 | 08-APR-13:40 | 318.33 | 08-APR-14:00 | 576.00 | 08-APR-13:50 | 0.00 | 01-APR-00:10 |
May | 0.917914E+09 | 0.209757E+09 | 145.10 | 0.814326E+09 | 0.103589E+09 | 0.00 | 0.65 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5075.34 | 10-MAY-15:00 | 3982.38 | 10-MAY-15:00 | 1092.96 | 10-MAY-15:00 | 1123.75 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.506414E+10 | 0.107824E+10 | 345.68 | 0.387052E+10 | 0.119362E+10 | 0.00 | 1.00 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 | 17291.34 | 18-JUN-08:62 | 11246.38 | 12-JUN-06:02 | 8340.29 | 18-JUN-08:04 | 3362.86 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.912198E+10 | 0.188719E+10 | 402.90 | 0.653936E+10 | 0.258262E+10 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 | 17738.10 | 21-JUL-05:03 | 11411.33 | 15-JUL-06:02 | 9500.68 | 21-JUL-05:03 | 3404.87 | 21-JUL-06:15 | 0.00 | 01-JUL-00:10 |
August | 0.812597E+10 | 0.169446E+10 | 396.37 | 0.637302E+10 | 0.175295E+10 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17409.37 | 14-AUG-06:02 | 12856.68 | 13-AUG-08:62 | 8999.96 | 14-AUG-06:04 | 3317.02 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.472525E+10 | 0.984775E+09 | 311.74 | 0.375683E+10 | 0.968416E+09 | 0.00 | 1.00 | 14-SEP-06:02 | 0.00 | 01-SEP-00:10 | 16830.55 | 16-SEP-06:02 | 10089.80 | 17-SEP-08:62 | 7362.31 | 14-SEP-06:02 | 3251.26 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.768519E+09 | 0.168634E+09 | 92.90 | 0.664198E+09 | 0.104321E+09 | 0.00 | 0.84 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 | 6723.56 | 11-OCT-14:30 | 6111.12 | 11-OCT-14:30 | 1269.33 | 12-OCT-14:10 | 1336.26 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 10822823.34 | 2623097.15 | 9.32 | 8983480.68 | 1839342.67 | 0.00 | 0.14 | 16-NOV-12:30 | 0.00 | 01-NOV-00:10 | 896.80 | 16-NOV-12:30 | 833.58 | 16-NOV-12:30 | 189.63 | 04-NOV-14:50 | 214.41 | 16-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.290414E+11 | 0.609586E+10 | 1752.09 | 0.222887E+11 | 0.675269E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.912198E+10 | 0.188719E+10 | 402.90 | 0.653936E+10 | 0.258262E+10 | 0.00 | 1.00 | 0.00 | 17738.10 | 12856.68 | 9500.68 | 3404.87 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.23 | 93.65 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.49 | 88.61 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 78.27 | 65.46 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 120.98 | 48.01 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 167.93 | 36.09 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 207.18 | 26.69 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.82 | 19.90 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.67 | 24.57 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 115.42 | 36.86 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 59.10 | 50.94 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 24.33 | 62.34 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.60 | 90.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 100.11 | 53.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.60 | 19.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 207.18 | 93.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 905.16 | 528.30 | 376.86 | 691.27 | 1103.78 | 0.00 | 0.00 | 744.00 |
February | 1033.90 | 498.66 | 535.24 | 729.78 | 1074.51 | 0.00 | 0.00 | 672.00 |
March | 1262.16 | 709.42 | 552.74 | 1047.64 | 803.68 | 0.00 | 0.00 | 744.00 |
April | 1044.75 | 417.43 | 627.32 | 764.24 | 612.84 | 0.00 | 0.00 | 720.00 |
May | 914.18 | 265.41 | 648.77 | 643.99 | 432.56 | 0.00 | 0.00 | 744.00 |
June | 888.26 | 188.09 | 700.17 | 732.26 | 295.99 | 0.00 | 0.00 | 720.00 |
July | 906.79 | 219.90 | 686.89 | 861.32 | 209.45 | 0.00 | 0.00 | 744.00 |
August | 1018.03 | 329.96 | 688.07 | 983.12 | 276.47 | 0.00 | 0.00 | 744.00 |
September | 1184.03 | 576.80 | 607.23 | 1163.84 | 430.49 | 0.00 | 0.00 | 720.00 |
October | 1133.19 | 647.48 | 485.71 | 1077.62 | 626.26 | 0.00 | 0.00 | 744.00 |
November | 811.29 | 458.00 | 353.28 | 715.08 | 762.04 | 0.00 | 0.00 | 720.00 |
December | 756.82 | 391.59 | 365.23 | 546.01 | 1080.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 987.91 | 435.69 | 552.22 | 830.35 | 640.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 756.82 | 188.09 | 353.28 | 546.01 | 209.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1262.16 | 709.42 | 700.17 | 1163.84 | 1103.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 905.16 | 528.30 | 376.86 | 689.68 | 1095.06 | 0.00 | 0.00 | 744.00 |
February | 1033.90 | 498.66 | 535.24 | 727.76 | 1066.11 | 0.00 | 0.00 | 672.00 |
March | 1262.16 | 709.42 | 552.74 | 1050.21 | 784.93 | 0.00 | 0.00 | 744.00 |
April | 1044.75 | 417.43 | 627.32 | 771.71 | 586.58 | 0.00 | 0.00 | 720.00 |
May | 914.18 | 265.41 | 648.77 | 653.41 | 403.71 | 0.00 | 0.00 | 744.00 |
June | 888.26 | 188.09 | 700.17 | 733.30 | 278.98 | 0.00 | 0.00 | 720.00 |
July | 906.79 | 219.90 | 686.89 | 858.77 | 196.02 | 0.00 | 0.00 | 744.00 |
August | 1018.03 | 329.96 | 688.07 | 980.19 | 261.79 | 0.00 | 0.00 | 744.00 |
September | 1184.03 | 576.80 | 607.23 | 1163.81 | 411.60 | 0.00 | 0.00 | 720.00 |
October | 1133.19 | 647.48 | 485.71 | 1085.64 | 595.23 | 0.00 | 0.00 | 744.00 |
November | 811.29 | 458.00 | 353.28 | 719.49 | 737.15 | 0.00 | 0.00 | 720.00 |
December | 756.82 | 391.59 | 365.23 | 545.04 | 1070.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 987.91 | 435.69 | 552.22 | 832.27 | 621.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 756.82 | 188.09 | 353.28 | 545.04 | 196.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1262.16 | 709.42 | 700.17 | 1163.81 | 1095.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.25 | 108.70 | 77.54 | 147.44 | 204.44 | 0.00 | 0.00 | 744.00 |
February | 212.74 | 102.61 | 110.13 | 157.01 | 201.54 | 0.00 | 0.00 | 672.00 |
March | 259.71 | 145.97 | 113.73 | 226.37 | 144.29 | 0.00 | 0.00 | 744.00 |
April | 214.97 | 85.89 | 129.08 | 175.41 | 104.07 | 0.00 | 0.00 | 720.00 |
May | 188.11 | 54.61 | 133.49 | 148.78 | 72.30 | 0.00 | 0.00 | 744.00 |
June | 182.77 | 38.70 | 144.07 | 154.50 | 54.05 | 0.00 | 0.00 | 720.00 |
July | 186.59 | 45.25 | 141.34 | 170.05 | 41.27 | 0.00 | 0.00 | 744.00 |
August | 209.47 | 67.89 | 141.58 | 196.73 | 54.30 | 0.00 | 0.00 | 744.00 |
September | 243.63 | 118.68 | 124.95 | 244.87 | 77.49 | 0.00 | 0.00 | 720.00 |
October | 233.17 | 133.23 | 99.94 | 237.38 | 104.55 | 0.00 | 0.00 | 744.00 |
November | 166.93 | 94.24 | 72.69 | 157.02 | 128.85 | 0.00 | 0.00 | 720.00 |
December | 155.73 | 80.57 | 75.15 | 116.89 | 198.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 203.28 | 89.65 | 113.63 | 177.82 | 115.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 155.73 | 38.70 | 72.69 | 116.89 | 41.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 259.71 | 145.97 | 144.07 | 244.87 | 204.44 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35442056.25 | 0.250835E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 81012221.37 | 0.214356E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.209628E+09 | 0.175322E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.313568E+09 | 0.124433E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.449797E+09 | 96672056.45 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.537017E+09 | 69176907.30 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.535191E+09 | 53310144.65 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.446420E+09 | 65797048.39 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.299170E+09 | 95550373.12 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.158295E+09 | 0.136428E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 63066458.42 | 0.161578E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 28403013.61 | 0.241838E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.315701E+10 | 0.168530E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 28403013.61 | 53310144.65 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.537017E+09 | 0.250835E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.185150E+10 | 0.295637E+10 |
February | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.176549E+10 | 0.259945E+10 |
March | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.280601E+10 | 0.215257E+10 |
April | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.198090E+10 | 0.158848E+10 |
May | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.172487E+10 | 0.115857E+10 |
June | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.189801E+10 | 0.767209E+09 |
July | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.230696E+10 | 0.560988E+09 |
August | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.263320E+10 | 0.740488E+09 |
September | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.301666E+10 | 0.111583E+10 |
October | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.288631E+10 | 0.167737E+10 |
November | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.185348E+10 | 0.197520E+10 |
December | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.146244E+10 | 0.289446E+10 |
Annual Sum or Average | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.261858E+11 | 0.201870E+11 |
Minimum of Months | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.146244E+10 | 0.560988E+09 |
Maximum of Months | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.301666E+10 | 0.295637E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.184723E+10 | 0.293302E+10 |
February | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.176060E+10 | 0.257913E+10 |
March | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.281288E+10 | 0.210236E+10 |
April | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.200028E+10 | 0.152042E+10 |
May | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.175009E+10 | 0.108129E+10 |
June | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.190071E+10 | 0.723115E+09 |
July | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.230012E+10 | 0.525011E+09 |
August | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.262534E+10 | 0.701177E+09 |
September | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.301659E+10 | 0.106685E+10 |
October | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.290778E+10 | 0.159427E+10 |
November | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.186492E+10 | 0.191069E+10 |
December | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.145984E+10 | 0.286816E+10 |
Annual Sum or Average | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.262464E+11 | 0.196055E+11 |
Minimum of Months | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.145984E+10 | 0.525011E+09 |
Maximum of Months | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.301659E+10 | 0.293302E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498851E+09 | 0.291155E+09 | 0.207696E+09 | 0.394912E+09 | 0.547584E+09 |
February | 0.514661E+09 | 0.248228E+09 | 0.266433E+09 | 0.379838E+09 | 0.487564E+09 |
March | 0.695600E+09 | 0.390976E+09 | 0.304623E+09 | 0.606317E+09 | 0.386475E+09 |
April | 0.557207E+09 | 0.222631E+09 | 0.334576E+09 | 0.454657E+09 | 0.269754E+09 |
May | 0.503822E+09 | 0.146272E+09 | 0.357550E+09 | 0.398505E+09 | 0.193659E+09 |
June | 0.473748E+09 | 0.100318E+09 | 0.373430E+09 | 0.400461E+09 | 0.140086E+09 |
July | 0.499753E+09 | 0.121193E+09 | 0.378560E+09 | 0.455473E+09 | 0.110534E+09 |
August | 0.561058E+09 | 0.181848E+09 | 0.379210E+09 | 0.526920E+09 | 0.145437E+09 |
September | 0.631493E+09 | 0.307630E+09 | 0.323862E+09 | 0.634715E+09 | 0.200864E+09 |
October | 0.624524E+09 | 0.356837E+09 | 0.267686E+09 | 0.635802E+09 | 0.280028E+09 |
November | 0.432692E+09 | 0.244272E+09 | 0.188420E+09 | 0.406992E+09 | 0.333984E+09 |
December | 0.417099E+09 | 0.215812E+09 | 0.201288E+09 | 0.313080E+09 | 0.532209E+09 |
Annual Sum or Average | 0.641051E+10 | 0.282717E+10 | 0.358333E+10 | 0.560767E+10 | 0.362818E+10 |
Minimum of Months | 0.417099E+09 | 0.100318E+09 | 0.188420E+09 | 0.313080E+09 | 0.110534E+09 |
Maximum of Months | 0.695600E+09 | 0.390976E+09 | 0.379210E+09 | 0.635802E+09 | 0.547584E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 211.72 | 1498.42 | 568.74 | 168.49 | 400.25 | 0.00 | 0.00 |
February | 535.80 | 1417.70 | 903.33 | 264.22 | 639.11 | 0.00 | 0.00 |
March | 1252.26 | 1047.32 | 1393.34 | 714.93 | 678.41 | 0.00 | 0.00 |
April | 1935.61 | 768.10 | 1866.83 | 998.08 | 868.75 | 0.00 | 0.00 |
May | 2686.96 | 577.49 | 2375.69 | 1463.72 | 911.97 | 0.00 | 0.00 |
June | 3314.92 | 427.02 | 2751.47 | 1726.09 | 1025.38 | 0.00 | 0.00 |
July | 3197.08 | 318.46 | 2550.38 | 1548.76 | 1001.62 | 0.00 | 0.00 |
August | 2666.79 | 393.05 | 2164.50 | 1199.29 | 965.22 | 0.00 | 0.00 |
September | 1846.73 | 589.82 | 1621.64 | 885.70 | 735.94 | 0.00 | 0.00 |
October | 945.61 | 814.98 | 1007.71 | 436.82 | 570.89 | 0.00 | 0.00 |
November | 389.30 | 997.40 | 581.87 | 181.28 | 400.59 | 0.00 | 0.00 |
December | 169.67 | 1444.67 | 502.11 | 107.94 | 394.17 | 0.00 | 0.00 |
Annual Sum or Average | 1601.73 | 855.05 | 1527.08 | 810.88 | 716.20 | 0.00 | 0.00 |
Minimum of Months | 169.67 | 318.46 | 502.11 | 107.94 | 394.17 | 0.00 | 0.00 |
Maximum of Months | 3314.92 | 1498.42 | 2751.47 | 1726.09 | 1025.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 691.27 | 1103.78 | 905.16 | 528.30 | 376.86 | 0.00 | 0.00 |
February | 729.78 | 1074.51 | 1033.90 | 498.66 | 535.24 | 0.00 | 0.00 |
March | 1047.64 | 803.68 | 1262.16 | 709.42 | 552.74 | 0.00 | 0.00 |
April | 764.24 | 612.84 | 1044.75 | 417.43 | 627.32 | 0.00 | 0.00 |
May | 643.99 | 432.56 | 914.18 | 265.41 | 648.77 | 0.00 | 0.00 |
June | 732.26 | 295.99 | 888.26 | 188.09 | 700.17 | 0.00 | 0.00 |
July | 861.32 | 209.45 | 906.79 | 219.90 | 686.89 | 0.00 | 0.00 |
August | 983.12 | 276.47 | 1018.03 | 329.96 | 688.07 | 0.00 | 0.00 |
September | 1163.84 | 430.49 | 1184.03 | 576.80 | 607.23 | 0.00 | 0.00 |
October | 1077.62 | 626.26 | 1133.19 | 647.48 | 485.71 | 0.00 | 0.00 |
November | 715.08 | 762.04 | 811.29 | 458.00 | 353.28 | 0.00 | 0.00 |
December | 546.01 | 1080.67 | 756.82 | 391.59 | 365.23 | 0.00 | 0.00 |
Annual Sum or Average | 830.35 | 640.13 | 987.91 | 435.69 | 552.22 | 0.00 | 0.00 |
Minimum of Months | 546.01 | 209.45 | 756.82 | 188.09 | 353.28 | 0.00 | 0.00 |
Maximum of Months | 1163.84 | 1103.78 | 1262.16 | 709.42 | 700.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 689.68 | 1095.06 | 905.16 | 528.30 | 376.86 | 0.00 | 0.00 |
February | 727.76 | 1066.11 | 1033.90 | 498.66 | 535.24 | 0.00 | 0.00 |
March | 1050.21 | 784.93 | 1262.16 | 709.42 | 552.74 | 0.00 | 0.00 |
April | 771.71 | 586.58 | 1044.75 | 417.43 | 627.32 | 0.00 | 0.00 |
May | 653.41 | 403.71 | 914.18 | 265.41 | 648.77 | 0.00 | 0.00 |
June | 733.30 | 278.98 | 888.26 | 188.09 | 700.17 | 0.00 | 0.00 |
July | 858.77 | 196.02 | 906.79 | 219.90 | 686.89 | 0.00 | 0.00 |
August | 980.19 | 261.79 | 1018.03 | 329.96 | 688.07 | 0.00 | 0.00 |
September | 1163.81 | 411.60 | 1184.03 | 576.80 | 607.23 | 0.00 | 0.00 |
October | 1085.64 | 595.23 | 1133.19 | 647.48 | 485.71 | 0.00 | 0.00 |
November | 719.49 | 737.15 | 811.29 | 458.00 | 353.28 | 0.00 | 0.00 |
December | 545.04 | 1070.85 | 756.82 | 391.59 | 365.23 | 0.00 | 0.00 |
Annual Sum or Average | 832.27 | 621.69 | 987.91 | 435.69 | 552.22 | 0.00 | 0.00 |
Minimum of Months | 545.04 | 196.02 | 756.82 | 188.09 | 353.28 | 0.00 | 0.00 |
Maximum of Months | 1163.81 | 1095.06 | 1262.16 | 709.42 | 700.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 147.44 | 204.44 | 186.25 | 108.70 | 77.54 | 0.00 | 0.00 |
February | 157.01 | 201.54 | 212.74 | 102.61 | 110.13 | 0.00 | 0.00 |
March | 226.37 | 144.29 | 259.71 | 145.97 | 113.73 | 0.00 | 0.00 |
April | 175.41 | 104.07 | 214.97 | 85.89 | 129.08 | 0.00 | 0.00 |
May | 148.78 | 72.30 | 188.11 | 54.61 | 133.49 | 0.00 | 0.00 |
June | 154.50 | 54.05 | 182.77 | 38.70 | 144.07 | 0.00 | 0.00 |
July | 170.05 | 41.27 | 186.59 | 45.25 | 141.34 | 0.00 | 0.00 |
August | 196.73 | 54.30 | 209.47 | 67.89 | 141.58 | 0.00 | 0.00 |
September | 244.87 | 77.49 | 243.63 | 118.68 | 124.95 | 0.00 | 0.00 |
October | 237.38 | 104.55 | 233.17 | 133.23 | 99.94 | 0.00 | 0.00 |
November | 157.02 | 128.85 | 166.93 | 94.24 | 72.69 | 0.00 | 0.00 |
December | 116.89 | 198.70 | 155.73 | 80.57 | 75.15 | 0.00 | 0.00 |
Annual Sum or Average | 177.82 | 115.05 | 203.28 | 89.65 | 113.63 | 0.00 | 0.00 |
Minimum of Months | 116.89 | 41.27 | 155.73 | 38.70 | 72.69 | 0.00 | 0.00 |
Maximum of Months | 244.87 | 204.44 | 259.71 | 145.97 | 144.07 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.567073E+09 | 0.401336E+10 | 0.152331E+10 | 0.451281E+09 | 0.107203E+10 | 0.00 | 0.00 |
February | 0.129620E+10 | 0.342970E+10 | 0.218533E+10 | 0.639208E+09 | 0.154613E+10 | 0.00 | 0.00 |
March | 0.335405E+10 | 0.280515E+10 | 0.373192E+10 | 0.191488E+10 | 0.181705E+10 | 0.00 | 0.00 |
April | 0.501709E+10 | 0.199093E+10 | 0.483882E+10 | 0.258703E+10 | 0.225179E+10 | 0.00 | 0.00 |
May | 0.719675E+10 | 0.154675E+10 | 0.636305E+10 | 0.392043E+10 | 0.244262E+10 | 0.00 | 0.00 |
June | 0.859228E+10 | 0.110683E+10 | 0.713182E+10 | 0.447402E+10 | 0.265780E+10 | 0.00 | 0.00 |
July | 0.856305E+10 | 0.852962E+09 | 0.683093E+10 | 0.414819E+10 | 0.268274E+10 | 0.00 | 0.00 |
August | 0.714272E+10 | 0.105275E+10 | 0.579741E+10 | 0.321218E+10 | 0.258523E+10 | 0.00 | 0.00 |
September | 0.478672E+10 | 0.152881E+10 | 0.420329E+10 | 0.229574E+10 | 0.190755E+10 | 0.00 | 0.00 |
October | 0.253272E+10 | 0.218285E+10 | 0.269904E+10 | 0.116998E+10 | 0.152907E+10 | 0.00 | 0.00 |
November | 0.100906E+10 | 0.258525E+10 | 0.150820E+10 | 0.469876E+09 | 0.103833E+10 | 0.00 | 0.00 |
December | 0.454448E+09 | 0.386940E+10 | 0.134484E+10 | 0.289095E+09 | 0.105575E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.505122E+11 | 0.269647E+11 | 0.481580E+11 | 0.255719E+11 | 0.225861E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454448E+09 | 0.852962E+09 | 0.134484E+10 | 0.289095E+09 | 0.103833E+10 | 0.00 | 0.00 |
Maximum of Months | 0.859228E+10 | 0.401336E+10 | 0.713182E+10 | 0.447402E+10 | 0.268274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.185150E+10 | 0.295637E+10 | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.00 | 0.00 |
February | 0.176549E+10 | 0.259945E+10 | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.00 | 0.00 |
March | 0.280601E+10 | 0.215257E+10 | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.00 | 0.00 |
April | 0.198090E+10 | 0.158848E+10 | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.00 | 0.00 |
May | 0.172487E+10 | 0.115857E+10 | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.00 | 0.00 |
June | 0.189801E+10 | 0.767209E+09 | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.00 | 0.00 |
July | 0.230696E+10 | 0.560988E+09 | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.00 | 0.00 |
August | 0.263320E+10 | 0.740488E+09 | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.00 | 0.00 |
September | 0.301666E+10 | 0.111583E+10 | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.00 | 0.00 |
October | 0.288631E+10 | 0.167737E+10 | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.00 | 0.00 |
November | 0.185348E+10 | 0.197520E+10 | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.00 | 0.00 |
December | 0.146244E+10 | 0.289446E+10 | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.261858E+11 | 0.201870E+11 | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.146244E+10 | 0.560988E+09 | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.00 | 0.00 |
Maximum of Months | 0.301666E+10 | 0.295637E+10 | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184723E+10 | 0.293302E+10 | 0.242438E+10 | 0.141499E+10 | 0.100938E+10 | 0.00 | 0.00 |
February | 0.176060E+10 | 0.257913E+10 | 0.250121E+10 | 0.120637E+10 | 0.129484E+10 | 0.00 | 0.00 |
March | 0.281288E+10 | 0.210236E+10 | 0.338056E+10 | 0.190011E+10 | 0.148045E+10 | 0.00 | 0.00 |
April | 0.200028E+10 | 0.152042E+10 | 0.270798E+10 | 0.108197E+10 | 0.162601E+10 | 0.00 | 0.00 |
May | 0.175009E+10 | 0.108129E+10 | 0.244853E+10 | 0.710869E+09 | 0.173767E+10 | 0.00 | 0.00 |
June | 0.190071E+10 | 0.723115E+09 | 0.230238E+10 | 0.487537E+09 | 0.181484E+10 | 0.00 | 0.00 |
July | 0.230012E+10 | 0.525011E+09 | 0.242876E+10 | 0.588989E+09 | 0.183977E+10 | 0.00 | 0.00 |
August | 0.262534E+10 | 0.701177E+09 | 0.272670E+10 | 0.883766E+09 | 0.184293E+10 | 0.00 | 0.00 |
September | 0.301659E+10 | 0.106685E+10 | 0.306901E+10 | 0.149506E+10 | 0.157395E+10 | 0.00 | 0.00 |
October | 0.290778E+10 | 0.159427E+10 | 0.303514E+10 | 0.173420E+10 | 0.130094E+10 | 0.00 | 0.00 |
November | 0.186492E+10 | 0.191069E+10 | 0.210285E+10 | 0.118714E+10 | 0.915707E+09 | 0.00 | 0.00 |
December | 0.145984E+10 | 0.286816E+10 | 0.202707E+10 | 0.104883E+10 | 0.978244E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262464E+11 | 0.196055E+11 | 0.311546E+11 | 0.137398E+11 | 0.174147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.145984E+10 | 0.525011E+09 | 0.202707E+10 | 0.487537E+09 | 0.915707E+09 | 0.00 | 0.00 |
Maximum of Months | 0.301659E+10 | 0.293302E+10 | 0.338056E+10 | 0.190011E+10 | 0.184293E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.394912E+09 | 0.547584E+09 | 0.498851E+09 | 0.291155E+09 | 0.207696E+09 | 0.00 | 0.00 |
February | 0.379838E+09 | 0.487564E+09 | 0.514661E+09 | 0.248228E+09 | 0.266433E+09 | 0.00 | 0.00 |
March | 0.606317E+09 | 0.386475E+09 | 0.695600E+09 | 0.390976E+09 | 0.304623E+09 | 0.00 | 0.00 |
April | 0.454657E+09 | 0.269754E+09 | 0.557207E+09 | 0.222631E+09 | 0.334576E+09 | 0.00 | 0.00 |
May | 0.398505E+09 | 0.193659E+09 | 0.503822E+09 | 0.146272E+09 | 0.357550E+09 | 0.00 | 0.00 |
June | 0.400461E+09 | 0.140086E+09 | 0.473748E+09 | 0.100318E+09 | 0.373430E+09 | 0.00 | 0.00 |
July | 0.455473E+09 | 0.110534E+09 | 0.499753E+09 | 0.121193E+09 | 0.378560E+09 | 0.00 | 0.00 |
August | 0.526920E+09 | 0.145437E+09 | 0.561058E+09 | 0.181848E+09 | 0.379210E+09 | 0.00 | 0.00 |
September | 0.634715E+09 | 0.200864E+09 | 0.631493E+09 | 0.307630E+09 | 0.323862E+09 | 0.00 | 0.00 |
October | 0.635802E+09 | 0.280028E+09 | 0.624524E+09 | 0.356837E+09 | 0.267686E+09 | 0.00 | 0.00 |
November | 0.406992E+09 | 0.333984E+09 | 0.432692E+09 | 0.244272E+09 | 0.188420E+09 | 0.00 | 0.00 |
December | 0.313080E+09 | 0.532209E+09 | 0.417099E+09 | 0.215812E+09 | 0.201288E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.560767E+10 | 0.362818E+10 | 0.641051E+10 | 0.282717E+10 | 0.358333E+10 | 0.00 | 0.00 |
Minimum of Months | 0.313080E+09 | 0.110534E+09 | 0.417099E+09 | 0.100318E+09 | 0.188420E+09 | 0.00 | 0.00 |
Maximum of Months | 0.635802E+09 | 0.547584E+09 | 0.695600E+09 | 0.390976E+09 | 0.379210E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.3 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.73 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.65 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.46 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.38 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.38 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.41 | 11.22 | 4.10 | 7.07 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.35 | 4.97 | 4.79 | 0.12 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.71 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.35 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.3 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.38 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.13 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.16 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.04 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.42 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.82 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.22 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.71 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.23 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.51 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.12 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.84 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.40 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.16 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.71 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.2 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.3 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.4 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.82 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.76 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.17 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.74 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.41 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.22 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.95 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.40 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.96 | 4.80 | 10.49 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.96 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.285164E+10 | -.244830E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -403341875.6 | 58.99 | 0.00 | 0.00 |
February | 0.262631E+10 | -.226167E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -364636431.3 | 58.99 | 0.00 | 0.00 |
March | 0.292748E+10 | -.253116E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -396316642.4 | 58.99 | 0.00 | 0.00 |
April | 0.269027E+10 | -.231155E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -378718337.7 | 58.99 | 0.00 | 0.00 |
May | 0.262738E+10 | -.225596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -371413877.2 | 58.99 | 0.00 | 0.00 |
June | 0.242310E+10 | -.207663E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -346466647.9 | 58.99 | 0.00 | 0.00 |
July | 0.233564E+10 | -.198185E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -353790482.4 | 58.99 | 0.00 | 0.00 |
August | 0.236081E+10 | -.200620E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -354617530.0 | 58.99 | 0.00 | 0.00 |
September | 0.229098E+10 | -.194288E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -348105287.0 | 58.99 | 0.00 | 0.00 |
October | 0.245750E+10 | -.207665E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -380847341.1 | 58.99 | 0.00 | 0.00 |
November | 0.251181E+10 | -.213045E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -381363886.8 | 59.00 | 0.00 | 0.00 |
December | 0.275093E+10 | -.234895E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -401980335.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.308538E+11 | -.263722E+11 | 8760.00 | -.448160E+10 | 58.99 | |||||
Minimum of Months | 0.229098E+10 | -.253116E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -403341875.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.292748E+10 | -.194288E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -346466647.9 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.89 | 0.67 | 22-JAN-11:30 | 239.98 | 7.03 | 0.00 | 1.67 | 183.82 | 5.52 | 0.00 | 0.00 |
February | 262.50 | 0.80 | 0.50 | 10-FEB-12:20 | 765.03 | 8.72 | 0.00 | 51.83 | 255.84 | 7.18 | 0.00 | 2.50 |
March | 339.33 | 0.81 | 0.50 | 10-MAR-11:50 | 381.18 | 8.54 | 0.00 | 46.83 | 267.80 | 6.98 | 0.00 | 19.17 |
April | 371.17 | 0.75 | 0.50 | 01-APR-11:09 | 972.88 | 9.47 | 0.00 | 138.33 | 316.56 | 7.90 | 0.00 | 66.00 |
May | 332.17 | 0.74 | 0.50 | 01-MAY-10:39 | 2561.06 | 10.05 | 0.00 | 125.00 | 2688.92 | 8.33 | 0.00 | 83.00 |
June | 430.67 | 0.75 | 0.50 | 01-JUN-09:50 | 411.26 | 10.85 | 0.00 | 135.33 | 343.85 | 9.04 | 0.00 | 90.67 |
July | 439.00 | 0.75 | 0.50 | 01-JUL-10:20 | 498.21 | 10.69 | 0.00 | 141.83 | 466.34 | 8.95 | 0.00 | 87.83 |
August | 406.00 | 0.74 | 0.50 | 01-AUG-08:50 | 1891.16 | 10.27 | 0.00 | 155.33 | 1894.21 | 8.59 | 0.00 | 101.83 |
September | 289.17 | 0.77 | 0.50 | 01-SEP-09:50 | 374.86 | 8.82 | 0.00 | 72.50 | 311.91 | 7.25 | 0.00 | 43.17 |
October | 314.33 | 0.83 | 0.50 | 02-OCT-12:30 | 430.40 | 7.96 | 0.00 | 13.00 | 393.94 | 6.43 | 0.00 | 6.00 |
November | 258.33 | 0.86 | 0.50 | 01-NOV-11:09 | 663.70 | 6.91 | 0.00 | 29.83 | 666.72 | 5.46 | 0.00 | 28.17 |
December | 230.67 | 0.89 | 0.67 | 09-DEC-10:50 | 228.70 | 7.25 | 0.00 | 0.00 | 185.49 | 5.76 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.79 | 823.40 | 9.13 | 0.00 | 911.50 | 704.21 | 7.52 | 0.00 | 528.33 | ||
Minimum of Months | 230.67 | 0.74 | 0.50 | 228.70 | 6.91 | 0.00 | 0.00 | 183.82 | 5.46 | 0.00 | 0.00 | |
Maximum of Months | 439.00 | 0.89 | 0.67 | 2561.06 | 10.85 | 0.00 | 155.33 | 2688.92 | 9.04 | 0.00 | 101.83 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182829E+11 | 46562.38 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175848E+11 | 46562.38 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104906E+11 | 46562.38 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.381846E+10 | 46562.38 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198882E+09 | 42890.16 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1870801.47 | 1582.41 | 30-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119122E+10 | 46562.38 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.492270E+10 | 46562.38 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160755E+11 | 46562.38 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.725669E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182829E+11 | 46562.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.718690E+11 | 234238.08 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672505E+11 | 234238.08 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.390892E+11 | 234238.08 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140542E+11 | 234238.08 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.539847E+09 | 46504.99 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13183411.78 | 10079.64 | 30-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683016E+10 | 151393.81 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231886E+11 | 234238.08 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.650903E+11 | 234238.08 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287925E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.718690E+11 | 234238.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.765401E+10 | 30567.73 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741264E+10 | 30567.73 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.325030E+10 | 30567.73 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125240E+10 | 30567.73 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66359594.93 | 13535.52 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1534590.91 | 1047.44 | 30-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.341270E+09 | 30567.73 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151284E+10 | 30567.73 | 11-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.693026E+10 | 30567.73 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284216E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.765401E+10 | 30567.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108015E+11 | 24313.71 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103644E+11 | 24313.71 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.555171E+10 | 24313.71 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.266922E+10 | 24313.71 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.302910E+09 | 19747.87 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4573622.72 | 7569.16 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19848227.28 | 16635.20 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103707E+10 | 24313.71 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327181E+10 | 24313.71 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.996346E+10 | 24313.71 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.439866E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108015E+11 | 24313.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135951E+11 | 33464.82 | 31-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129405E+11 | 36814.72 | 06-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728724E+10 | 28425.97 | 11-MAR-15:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195907E+10 | 28058.14 | 02-APR-16:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103299E+10 | 28172.67 | 29-OCT-16:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.395506E+10 | 28253.10 | 19-NOV-15:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129317E+11 | 34451.31 | 10-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.537016E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135951E+11 | 36814.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.102200E+09 | 81093757.33 | 5018.90 | 15-MAR-15:00 | 4036.37 | 0.00 |
April | 0.00 | 0.00 | 180.48 | 149.90 | 0.19 | 08-APR-13:20 | 0.16 | 0.00 |
May | 0.00 | 0.00 | 0.580878E+09 | 0.512292E+09 | 6999.55 | 10-MAY-15:00 | 5127.54 | 0.00 |
June | 0.00 | 0.00 | 0.705763E+10 | 0.505886E+10 | 35873.93 | 18-JUN-08:62 | 17986.58 | 0.00 |
July | 0.00 | 0.00 | 0.152412E+11 | 0.101773E+11 | 36255.32 | 21-JUL-06:02 | 18273.72 | 0.00 |
August | 0.00 | 0.00 | 0.119266E+11 | 0.876491E+10 | 35988.10 | 14-AUG-06:02 | 16000.22 | 0.00 |
September | 0.00 | 0.00 | 0.411591E+10 | 0.281141E+10 | 34812.41 | 16-SEP-06:02 | 18217.88 | 0.00 |
October | 0.00 | 0.00 | 30188515.90 | 26104486.73 | 2554.92 | 11-OCT-15:00 | 2196.19 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.390546E+11 | 0.274320E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.152412E+11 | 0.101773E+11 | 36255.32 | 18273.72 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.120442E+10 | 0.950241E+09 | 32293.79 | 15-MAR-14:30 | 27403.34 | 0.00 |
April | 0.00 | 0.00 | 76618314.47 | 63412839.19 | 9522.25 | 08-APR-13:30 | 7953.51 | 0.00 |
May | 0.00 | 0.00 | 0.647202E+10 | 0.553697E+10 | 153148.61 | 24-MAY-06:03 | 104392.72 | 0.00 |
June | 0.00 | 0.00 | 0.434596E+11 | 0.306423E+11 | 170199.20 | 18-JUN-08:62 | 87141.18 | 0.00 |
July | 0.00 | 0.00 | 0.791941E+11 | 0.515597E+11 | 172721.01 | 21-JUL-05:03 | 86307.03 | 0.00 |
August | 0.00 | 0.00 | 0.613843E+11 | 0.441621E+11 | 170108.58 | 14-AUG-06:02 | 79613.15 | 0.00 |
September | 0.00 | 0.00 | 0.246305E+11 | 0.167502E+11 | 165097.98 | 16-SEP-06:02 | 88864.48 | 0.00 |
October | 0.00 | 0.00 | 0.642981E+09 | 0.520602E+09 | 22011.75 | 11-OCT-15:00 | 18303.86 | 0.00 |
November | 0.00 | 0.00 | 3052.36 | 2163.18 | 2.62 | 04-NOV-15:40 | 1.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.217065E+12 | 0.150186E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.791941E+11 | 0.515597E+11 | 172721.01 | 104392.72 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.353000E+09 | 0.290850E+09 | 7739.01 | 15-MAR-13:40 | 6995.60 | 0.00 |
April | 0.00 | 0.00 | 60539773.27 | 54243698.81 | 3477.37 | 08-APR-13:40 | 3021.92 | 0.00 |
May | 0.00 | 0.00 | 0.110381E+10 | 0.974181E+09 | 14888.31 | 24-MAY-06:03 | 9821.06 | 0.00 |
June | 0.00 | 0.00 | 0.651569E+10 | 0.481766E+10 | 22059.61 | 18-JUN-08:62 | 11067.03 | 0.00 |
July | 0.00 | 0.00 | 0.120990E+11 | 0.836336E+10 | 22627.25 | 21-JUL-05:03 | 10512.84 | 0.00 |
August | 0.00 | 0.00 | 0.104668E+11 | 0.793839E+10 | 22103.13 | 14-AUG-06:02 | 9803.13 | 0.00 |
September | 0.00 | 0.00 | 0.569729E+10 | 0.417996E+10 | 21350.10 | 16-SEP-06:02 | 11431.81 | 0.00 |
October | 0.00 | 0.00 | 0.749692E+09 | 0.612581E+09 | 8500.74 | 11-OCT-14:40 | 7530.05 | 0.00 |
November | 0.00 | 0.00 | 5729346.84 | 4553844.15 | 935.66 | 16-NOV-12:40 | 790.87 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.370515E+11 | 0.272358E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120990E+11 | 0.836336E+10 | 22627.25 | 11431.81 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.229710E+09 | 0.189216E+09 | 5630.35 | 15-MAR-13:50 | 5065.97 | 0.00 |
April | 0.00 | 0.00 | 77057889.12 | 72218401.00 | 2558.93 | 08-APR-13:50 | 2244.14 | 0.00 |
May | 0.00 | 0.00 | 0.917914E+09 | 0.814326E+09 | 5075.34 | 10-MAY-15:00 | 3982.38 | 0.00 |
June | 0.00 | 0.00 | 0.506414E+10 | 0.387052E+10 | 17291.34 | 18-JUN-08:62 | 8985.86 | 0.00 |
July | 0.00 | 0.00 | 0.912198E+10 | 0.653936E+10 | 17738.10 | 21-JUL-05:03 | 8237.42 | 0.00 |
August | 0.00 | 0.00 | 0.812597E+10 | 0.637302E+10 | 17409.37 | 14-AUG-06:02 | 8429.03 | 0.00 |
September | 0.00 | 0.00 | 0.472525E+10 | 0.375683E+10 | 16830.55 | 16-SEP-06:02 | 9645.97 | 0.00 |
October | 0.00 | 0.00 | 0.768519E+09 | 0.664198E+09 | 6723.56 | 11-OCT-14:30 | 6111.12 | 0.00 |
November | 0.00 | 0.00 | 10822823.34 | 8983480.68 | 896.80 | 16-NOV-12:30 | 833.58 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290414E+11 | 0.222887E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.912198E+10 | 0.653936E+10 | 17738.10 | 9645.97 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.286823E+10 | 0.53 | 1833.11 | 01-JAN-00:15 | 0.90 |
February | 0.270118E+10 | 0.55 | 1833.11 | 01-FEB-00:05 | 0.91 |
March | 0.193424E+10 | 0.36 | 1833.11 | 01-MAR-03:40 | 0.90 |
April | 0.903107E+09 | 0.17 | 1833.11 | 01-APR-07:10 | 0.90 |
May | 9238854.28 | 0.00 | 1833.11 | 01-MAY-07:10 | 0.90 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.554465E+09 | 0.10 | 1833.11 | 03-OCT-07:10 | 0.90 |
November | 0.142075E+10 | 0.27 | 1833.11 | 01-NOV-07:05 | 0.90 |
December | 0.280494E+10 | 0.52 | 1833.11 | 01-DEC-14:51 | 0.90 |
Annual Sum or Average | 0.131962E+11 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.286823E+10 | 0.55 | 1833.11 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157143E+10 | 0.42 | 1778.82 | 01-JAN-07:01 | 0.90 |
February | 0.145539E+10 | 0.44 | 1778.82 | 01-FEB-05:02 | 0.90 |
March | 0.140563E+10 | 0.38 | 1778.82 | 01-MAR-05:02 | 0.90 |
April | 0.120222E+10 | 0.35 | 1778.82 | 01-APR-05:01 | 0.90 |
May | 0.115467E+10 | 0.33 | 1694.64 | 01-MAY-06:03 | 0.88 |
June | 0.112380E+10 | 0.33 | 1778.82 | 12-JUN-06:02 | 0.89 |
July | 0.115792E+10 | 0.33 | 1778.82 | 01-JUL-06:02 | 0.89 |
August | 0.116536E+10 | 0.33 | 1778.82 | 01-AUG-06:02 | 0.89 |
September | 0.111512E+10 | 0.33 | 1778.82 | 14-SEP-06:02 | 0.88 |
October | 0.116717E+10 | 0.33 | 1778.82 | 17-OCT-05:02 | 0.90 |
November | 0.121187E+10 | 0.35 | 1778.82 | 03-NOV-05:02 | 0.90 |
December | 0.152080E+10 | 0.41 | 1778.82 | 01-DEC-06:02 | 0.90 |
Annual Sum or Average | 0.152514E+11 | 0.36 | |||
Minimum of Months | 0.111512E+10 | 0.33 | 1694.64 | 0.88 | |
Maximum of Months | 0.157143E+10 | 0.44 | 1778.82 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.970607E+10 | 0.60 | 11766.47 | 01-JAN-08:61 | 1.42 |
February | 0.887351E+10 | 0.61 | 11766.47 | 01-FEB-06:01 | 1.42 |
March | 0.885364E+10 | 0.57 | 11766.47 | 01-MAR-06:01 | 1.42 |
April | 0.779411E+10 | 0.54 | 11766.47 | 17-APR-05:01 | 1.42 |
May | 0.762645E+10 | 0.52 | 11766.47 | 24-MAY-06:03 | 1.40 |
June | 0.747126E+10 | 0.52 | 11766.47 | 01-JUN-06:03 | 1.40 |
July | 0.772001E+10 | 0.51 | 11766.47 | 01-JUL-06:02 | 1.41 |
August | 0.772854E+10 | 0.52 | 11766.47 | 01-AUG-06:02 | 1.41 |
September | 0.739062E+10 | 0.52 | 11766.47 | 08-SEP-06:03 | 1.41 |
October | 0.774581E+10 | 0.52 | 9269.56 | 30-OCT-06:03 | 1.27 |
November | 0.796775E+10 | 0.54 | 11766.47 | 24-NOV-06:01 | 1.42 |
December | 0.951934E+10 | 0.60 | 11766.47 | 04-DEC-06:01 | 1.42 |
Annual Sum or Average | 0.983971E+11 | 0.55 | |||
Minimum of Months | 0.739062E+10 | 0.51 | 9269.56 | 1.27 | |
Maximum of Months | 0.970607E+10 | 0.61 | 11766.47 | 1.42 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.891134E+09 | 0.41 | 1121.17 | 01-JAN-07:01 | 0.93 |
February | 0.821569E+09 | 0.43 | 1121.17 | 01-FEB-06:01 | 0.93 |
March | 0.803713E+09 | 0.37 | 1121.17 | 01-MAR-06:01 | 0.93 |
April | 0.730004E+09 | 0.35 | 1121.17 | 01-APR-05:01 | 0.93 |
May | 0.726418E+09 | 0.34 | 784.52 | 24-MAY-06:03 | 0.78 |
June | 0.716304E+09 | 0.34 | 1121.17 | 02-JUN-06:02 | 0.92 |
July | 0.767090E+09 | 0.35 | 1121.17 | 01-JUL-06:02 | 0.92 |
August | 0.761588E+09 | 0.35 | 1121.17 | 01-AUG-06:02 | 0.92 |
September | 0.712086E+09 | 0.34 | 1121.17 | 09-SEP-06:02 | 0.92 |
October | 0.725959E+09 | 0.34 | 1121.17 | 30-OCT-05:01 | 0.93 |
November | 0.725940E+09 | 0.35 | 1121.17 | 11-NOV-08:61 | 0.93 |
December | 0.876015E+09 | 0.40 | 1121.17 | 02-DEC-06:01 | 0.93 |
Annual Sum or Average | 0.925782E+10 | 0.36 | |||
Minimum of Months | 0.712086E+09 | 0.34 | 784.52 | 0.78 | |
Maximum of Months | 0.891134E+09 | 0.43 | 1121.17 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134290E+10 | 0.59 | 826.16 | 01-JAN-08:15 | 0.93 |
February | 0.122882E+10 | 0.62 | 826.16 | 01-FEB-07:10 | 0.93 |
March | 0.135235E+10 | 0.58 | 826.16 | 01-MAR-06:50 | 0.94 |
April | 0.129474E+10 | 0.56 | 826.16 | 01-APR-06:08 | 0.93 |
May | 0.133540E+10 | 0.56 | 826.16 | 01-MAY-05:50 | 0.93 |
June | 0.130269E+10 | 0.56 | 826.16 | 01-JUN-09:50 | 0.92 |
July | 0.132648E+10 | 0.55 | 826.16 | 01-JUL-08:20 | 0.92 |
August | 0.134730E+10 | 0.56 | 826.16 | 01-AUG-13:30 | 0.92 |
September | 0.129376E+10 | 0.56 | 826.16 | 01-SEP-09:50 | 0.92 |
October | 0.132351E+10 | 0.55 | 826.16 | 02-OCT-06:13 | 0.93 |
November | 0.127619E+10 | 0.55 | 826.16 | 01-NOV-06:13 | 0.93 |
December | 0.134248E+10 | 0.59 | 826.16 | 01-DEC-06:07 | 0.93 |
Annual Sum or Average | 0.157666E+11 | 0.57 | |||
Minimum of Months | 0.122882E+10 | 0.55 | 826.16 | 0.92 | |
Maximum of Months | 0.135235E+10 | 0.62 | 826.16 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.19 | 0.00 |
February | 3.17 | 0.00 |
March | 1.32 | 0.00 |
April | 0.21 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.17 | 0.00 |
December | 3.12 | 0.00 |
Annual Sum or Average | 10.18 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.17 | 25.84 |
April | 0.53 | 25.84 |
May | 2.53 | 25.84 |
June | 1.06 | 25.84 |
July | 0.33 | 25.84 |
August | 0.67 | 25.84 |
September | 0.94 | 25.84 |
October | 0.81 | 25.84 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.03 | 25.84 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.53 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.94 | 0.00 |
February | 2.12 | 0.00 |
March | 0.33 | 0.00 |
April | 0.26 | 1.28 |
May | 0.22 | 2.44 |
June | 0.50 | 0.41 |
July | 0.58 | 0.00 |
August | 0.81 | 0.00 |
September | 0.69 | 1.46 |
October | 0.25 | 2.44 |
November | 0.00 | 0.00 |
December | 2.01 | 0.00 |
Annual Sum or Average | 9.73 | 0.28 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.12 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.74 | 0.00 |
February | 3.37 | 0.00 |
March | 0.98 | 0.00 |
April | 0.12 | 0.00 |
May | 0.08 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.56 | 0.73 |
December | 3.43 | 0.00 |
Annual Sum or Average | 11.28 | 0.04 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.43 | 0.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 38.82 | 0.00 |
February | 55.13 | 0.00 |
March | 10.04 | 0.00 |
April | 6.04 | 0.00 |
May | 3.59 | 0.00 |
June | 3.02 | 0.00 |
July | 2.57 | 0.00 |
August | 3.06 | 0.00 |
September | 4.56 | 0.00 |
October | 8.58 | 0.00 |
November | 5.52 | 0.00 |
December | 31.92 | 0.00 |
Annual Sum or Average | 172.83 | 0.00 |
Minimum of Months | 2.57 | 0.00 |
Maximum of Months | 55.13 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.157143E+10 | 0.228537E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.145539E+10 | 0.219811E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143417E+10 | 0.131132E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120222E+10 | 0.477307E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.131126E+10 | 0.248602E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.286730E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.479477E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.407989E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.213197E+10 | 2338501.84 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117557E+10 | 0.148902E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.121187E+10 | 0.615338E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.152080E+10 | 0.200943E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.247566E+11 | 0.907087E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.117557E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.479477E+10 | 0.228537E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.970607E+10 | 0.898363E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.887351E+10 | 0.840631E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.921891E+10 | 0.488616E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.781762E+10 | 0.175678E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.950476E+10 | 0.674809E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.192565E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.285652E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.243420E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.141601E+11 | 16479264.72 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.794078E+10 | 0.853770E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.796775E+10 | 0.289857E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.951934E+10 | 0.813629E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.156873E+12 | 0.359906E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.781762E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.285652E+11 | 0.898363E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.891134E+09 | 0.956751E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.821569E+09 | 0.926580E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.892326E+09 | 0.406288E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.745942E+09 | 0.156550E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.100759E+10 | 82949493.66 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226698E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.356446E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320714E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.203700E+10 | 1918238.63 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.911695E+09 | 0.426588E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.727533E+09 | 0.189106E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.876015E+09 | 0.866282E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.179494E+11 | 0.355270E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.727533E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.356446E+10 | 0.956751E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.134290E+10 | 0.135019E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.122882E+10 | 0.129556E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.140443E+10 | 0.693964E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.131283E+10 | 0.333653E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.154516E+10 | 0.378637E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.238093E+10 | 5717028.40 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.321367E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.304175E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.227854E+10 | 24810284.10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149214E+10 | 0.129634E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.127881E+10 | 0.408976E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.134248E+10 | 0.124543E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.218625E+11 | 0.549832E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.122882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.321367E+10 | 0.135019E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157143E+10 | 0.00 | 0.182829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145539E+10 | 0.00 | 0.175848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140563E+10 | 0.102200E+09 | 0.104906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120222E+10 | 180.48 | 0.381846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115467E+10 | 0.580878E+09 | 0.198882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112380E+10 | 0.705763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115792E+10 | 0.152412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116536E+10 | 0.119266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111512E+10 | 0.411591E+10 | 1870801.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116717E+10 | 30188515.90 | 0.119122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121187E+10 | 0.00 | 0.492270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152080E+10 | 0.00 | 0.160755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152514E+11 | 0.390546E+11 | 0.725669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157143E+10 | 0.152412E+11 | 0.182829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.970607E+10 | 0.00 | 0.718690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.887351E+10 | 0.00 | 0.672505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.885364E+10 | 0.120442E+10 | 0.390892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.779411E+10 | 76618314.47 | 0.140542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762645E+10 | 0.647202E+10 | 0.539847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.747126E+10 | 0.434596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.772001E+10 | 0.791941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.772854E+10 | 0.613843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739062E+10 | 0.246305E+11 | 13183411.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.774581E+10 | 0.642981E+09 | 0.683016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.796775E+10 | 3052.36 | 0.231886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.951934E+10 | 0.00 | 0.650903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983971E+11 | 0.217065E+12 | 0.287925E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.739062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.970607E+10 | 0.791941E+11 | 0.718690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.891134E+09 | 0.00 | 0.765401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821569E+09 | 0.00 | 0.741264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.803713E+09 | 0.353000E+09 | 0.325030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.730004E+09 | 60539773.27 | 0.125240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.726418E+09 | 0.110381E+10 | 66359594.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.716304E+09 | 0.651569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.767090E+09 | 0.120990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.761588E+09 | 0.104668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.712086E+09 | 0.569729E+10 | 1534590.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.725959E+09 | 0.749692E+09 | 0.341270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725940E+09 | 5729346.84 | 0.151284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.876015E+09 | 0.00 | 0.693026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.925782E+10 | 0.370515E+11 | 0.284216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.712086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.891134E+09 | 0.120990E+11 | 0.765401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134290E+10 | 0.00 | 0.108015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122882E+10 | 0.00 | 0.103644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135235E+10 | 0.229710E+09 | 0.555171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129474E+10 | 77057889.12 | 0.266922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133540E+10 | 0.917914E+09 | 0.302910E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130269E+10 | 0.506414E+10 | 4573622.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132648E+10 | 0.912198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134730E+10 | 0.812597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129376E+10 | 0.472525E+10 | 19848227.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132351E+10 | 0.768519E+09 | 0.103707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127619E+10 | 10822823.34 | 0.327181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134248E+10 | 0.00 | 0.996346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157666E+11 | 0.290414E+11 | 0.439866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135235E+10 | 0.912198E+10 | 0.108015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.157143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140563E+10 | 0.00 | 0.00 | 0.00 | 28538891.19 | 0.00 | 0.131132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120222E+10 | 0.00 | 0.00 | 0.00 | 51.31 | 0.00 | 0.477307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115467E+10 | 0.00 | 0.00 | 0.00 | 0.156591E+09 | 0.00 | 0.248602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112380E+10 | 0.00 | 0.00 | 0.00 | 0.174350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115792E+10 | 0.00 | 0.00 | 0.00 | 0.363685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116536E+10 | 0.00 | 0.00 | 0.00 | 0.291453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111512E+10 | 0.00 | 0.00 | 0.00 | 0.101686E+10 | 0.00 | 2338501.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116717E+10 | 0.00 | 0.00 | 0.00 | 8395638.37 | 0.00 | 0.148902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152514E+11 | 0.00 | 0.00 | 0.00 | 0.950527E+10 | 0.00 | 0.907087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.111512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157143E+10 | 0.00 | 0.00 | 0.00 | 0.363685E+10 | 0.00 | 0.228537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.970607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.887351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.885364E+10 | 0.00 | 0.00 | 0.00 | 0.365273E+09 | 0.00 | 0.488616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.779411E+10 | 0.00 | 0.00 | 0.00 | 23519304.61 | 0.00 | 0.175678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.762645E+10 | 0.00 | 0.00 | 0.00 | 0.187831E+10 | 0.00 | 0.674809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.747126E+10 | 0.00 | 0.00 | 0.00 | 0.117852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.772001E+10 | 0.00 | 0.00 | 0.00 | 0.208452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.772854E+10 | 0.00 | 0.00 | 0.00 | 0.166135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739062E+10 | 0.00 | 0.00 | 0.00 | 0.676949E+10 | 0.00 | 16479264.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.774581E+10 | 0.00 | 0.00 | 0.00 | 0.194974E+09 | 0.00 | 0.853770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.796775E+10 | 0.00 | 0.00 | 0.00 | 969.44 | 0.00 | 0.289857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.951934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.983971E+11 | 0.00 | 0.00 | 0.00 | 0.584755E+11 | 0.00 | 0.359906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.739062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.970607E+10 | 0.00 | 0.00 | 0.00 | 0.208452E+11 | 0.00 | 0.898363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.891134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.803713E+09 | 0.00 | 0.00 | 0.00 | 88613560.85 | 0.00 | 0.406288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.730004E+09 | 0.00 | 0.00 | 0.00 | 15937746.35 | 0.00 | 0.156550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.726418E+09 | 0.00 | 0.00 | 0.00 | 0.281168E+09 | 0.00 | 82949493.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.716304E+09 | 0.00 | 0.00 | 0.00 | 0.155067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.767090E+09 | 0.00 | 0.00 | 0.00 | 0.279737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.761588E+09 | 0.00 | 0.00 | 0.00 | 0.244555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.712086E+09 | 0.00 | 0.00 | 0.00 | 0.132491E+10 | 0.00 | 1918238.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.725959E+09 | 0.00 | 0.00 | 0.00 | 0.185736E+09 | 0.00 | 0.426588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725940E+09 | 0.00 | 0.00 | 0.00 | 1593039.76 | 0.00 | 0.189106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.876015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.925782E+10 | 0.00 | 0.00 | 0.00 | 0.869156E+10 | 0.00 | 0.355270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.712086E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.891134E+09 | 0.00 | 0.00 | 0.00 | 0.279737E+10 | 0.00 | 0.956751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.134290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135235E+10 | 0.00 | 0.00 | 0.00 | 52082388.68 | 0.00 | 0.693964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129474E+10 | 0.00 | 0.00 | 0.00 | 18095132.58 | 0.00 | 0.333653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133540E+10 | 0.00 | 0.00 | 0.00 | 0.209757E+09 | 0.00 | 0.378637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130269E+10 | 0.00 | 0.00 | 0.00 | 0.107824E+10 | 0.00 | 5717028.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132648E+10 | 0.00 | 0.00 | 0.00 | 0.188719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134730E+10 | 0.00 | 0.00 | 0.00 | 0.169446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129376E+10 | 0.00 | 0.00 | 0.00 | 0.984775E+09 | 0.00 | 24810284.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132351E+10 | 0.00 | 0.00 | 0.00 | 0.168634E+09 | 0.00 | 0.129634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127619E+10 | 0.00 | 0.00 | 0.00 | 2623097.15 | 0.00 | 0.408976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157666E+11 | 0.00 | 0.00 | 0.00 | 0.609586E+10 | 0.00 | 0.549832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.122882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135235E+10 | 0.00 | 0.00 | 0.00 | 0.188719E+10 | 0.00 | 0.135019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 45735348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110452E+11 | 0.00 | 0.00 | 0.20 |
February | 0.102443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101914E+11 | 0.00 | 0.00 | 0.20 |
March | 0.205760E+10 | 0.00 | 0.00 | 184527.51 | 0.00 | 0.651773E+10 | 0.108874E+09 | 0.00 | 0.21 |
April | 0.417955E+10 | 0.00 | 0.00 | 18642.97 | 0.00 | 0.210170E+10 | 42165326.47 | 0.00 | 0.21 |
May | 0.287021E+10 | 7601053.18 | 0.00 | 3104213.53 | 158101.49 | 0.110535E+09 | 0.265011E+10 | 0.00 | 0.30 |
June | 0.413338E+09 | 0.888530E+09 | 0.00 | 8562126.92 | 2170653.88 | 0.00 | 0.396193E+10 | 0.00 | 0.46 |
July | 31962297.09 | 0.269025E+10 | 0.00 | 5564270.55 | 6915296.36 | 0.00 | 0.104203E+10 | 0.00 | 0.43 |
August | 94739755.27 | 0.139536E+10 | 0.00 | 10652392.63 | 1360636.87 | 0.00 | 0.252211E+10 | 0.00 | 0.45 |
September | 0.877352E+09 | 0.346647E+09 | 0.00 | 8719019.84 | 311499.15 | 0.00 | 0.446155E+10 | 0.00 | 0.47 |
October | 0.473320E+10 | 0.00 | 0.00 | 1117190.84 | 0.00 | 0.516064E+09 | 0.113322E+10 | 0.00 | 0.23 |
November | 0.433745E+10 | 0.00 | 7990.83 | 0.00 | 0.00 | 0.253746E+10 | 0.00 | 22162.21 | 0.20 |
December | 0.740167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988553E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.204837E+11 | 0.532838E+10 | 7990.83 | 37922384.78 | 10916187.74 | 0.429057E+11 | 0.159220E+11 | 22162.21 | 0.30 |
Minimum of Months | 31962297.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.473320E+10 | 0.269025E+10 | 7990.83 | 10652392.63 | 6915296.36 | 0.110452E+11 | 0.446155E+10 | 22162.21 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.516461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354975E+11 | 0.00 | 0.00 | 0.39 |
February | 0.481361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327648E+11 | 0.00 | 0.00 | 0.39 |
March | 0.554242E+11 | 2720570.37 | 0.00 | 1497633.95 | 0.00 | 0.107539E+11 | 0.654138E+09 | 0.00 | 0.40 |
April | 0.437870E+11 | 0.00 | 0.00 | 1527889.98 | 0.00 | 0.295588E+10 | 0.210167E+10 | 0.00 | 0.40 |
May | 0.181243E+11 | 0.168652E+09 | 0.00 | 28414015.93 | 5391235.38 | 50349894.45 | 0.199897E+11 | 0.00 | 0.49 |
June | 0.298410E+10 | 0.758524E+10 | 0.00 | 49696390.13 | 56356243.86 | 0.00 | 0.178876E+11 | 0.00 | 0.57 |
July | 0.272456E+09 | 0.202158E+11 | 0.00 | 22976905.46 | 0.124433E+09 | 0.00 | 0.376835E+10 | 0.00 | 0.54 |
August | 0.820294E+09 | 0.105823E+11 | 0.00 | 48410680.15 | 50668077.65 | 0.00 | 0.100502E+11 | 0.00 | 0.56 |
September | 0.687026E+10 | 0.259881E+10 | 0.00 | 47217240.18 | 12535632.84 | 0.00 | 0.205194E+11 | 0.00 | 0.57 |
October | 0.385251E+11 | 0.00 | 0.00 | 6275575.52 | 1038226.95 | 0.109674E+10 | 0.624192E+10 | 0.00 | 0.42 |
November | 0.486832E+11 | 0.00 | 0.00 | 63819.74 | 1120104.40 | 0.436463E+10 | 0.171150E+09 | 0.00 | 0.39 |
December | 0.552255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280876E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.370499E+12 | 0.411535E+11 | 0.00 | 0.206080E+09 | 0.251542E+09 | 0.115572E+12 | 0.813842E+11 | 0.00 | 0.46 |
Minimum of Months | 0.272456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.554242E+11 | 0.202158E+11 | 0.00 | 49696390.13 | 0.124433E+09 | 0.354975E+11 | 0.205194E+11 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.466896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346071E+10 | 0.00 | 0.00 | 0.39 |
February | 0.403413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352632E+10 | 0.00 | 0.00 | 0.39 |
March | 0.484318E+10 | 8671248.62 | 0.00 | 779008.37 | 0.00 | 0.119805E+10 | 0.336624E+09 | 0.00 | 0.42 |
April | 0.333098E+10 | 0.00 | 0.00 | 1756254.60 | 0.00 | 0.491758E+09 | 0.126320E+10 | 0.00 | 0.47 |
May | 0.100097E+10 | 26700772.72 | 0.00 | 6416521.48 | 23434.99 | 17628319.33 | 0.350691E+10 | 0.00 | 0.67 |
June | 0.213045E+09 | 0.949187E+09 | 0.00 | 7298688.33 | 1453078.90 | 0.00 | 0.234170E+10 | 0.00 | 0.80 |
July | 18484621.31 | 0.263877E+10 | 0.00 | 3518183.76 | 1811851.06 | 0.00 | 0.504139E+09 | 0.00 | 0.72 |
August | 45730645.55 | 0.149454E+10 | 0.00 | 7568113.74 | 241983.25 | 0.00 | 0.127874E+10 | 0.00 | 0.77 |
September | 0.312571E+09 | 0.585241E+09 | 0.00 | 10456565.74 | 163097.88 | 0.00 | 0.306855E+10 | 0.00 | 0.87 |
October | 0.242033E+10 | 0.00 | 0.00 | 5555451.15 | 0.00 | 93501384.55 | 0.282251E+10 | 0.00 | 0.56 |
November | 0.408806E+10 | 0.00 | 0.00 | 1049747.42 | 0.00 | 0.431298E+09 | 0.823655E+09 | 0.00 | 0.43 |
December | 0.478722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299987E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.297637E+11 | 0.570311E+10 | 0.00 | 44398534.59 | 3693446.07 | 0.122191E+11 | 0.159460E+11 | 0.00 | 0.57 |
Minimum of Months | 18484621.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.484318E+10 | 0.263877E+10 | 0.00 | 10456565.74 | 1811851.06 | 0.352632E+10 | 0.350691E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774894E+10 | 0.00 | 0.00 | 0.42 |
February | 0.109873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717202E+10 | 0.00 | 0.00 | 0.43 |
March | 0.319612E+10 | 1502543.91 | 0.00 | 200788.75 | 0.00 | 0.345326E+10 | 53328512.59 | 0.00 | 0.43 |
April | 0.284472E+10 | 0.00 | 0.00 | 265589.72 | 0.00 | 0.171309E+10 | 0.306667E+09 | 0.00 | 0.43 |
May | 0.210759E+10 | 14212046.28 | 0.00 | 1630687.86 | 142799.97 | 0.193227E+09 | 0.996489E+09 | 0.00 | 0.43 |
June | 0.597010E+09 | 0.649632E+09 | 0.00 | 3335609.55 | 1457353.51 | 1100137.35 | 0.982222E+09 | 0.00 | 0.43 |
July | 0.182472E+09 | 0.178023E+10 | 0.00 | 1661442.57 | 6687715.95 | 0.00 | 0.175277E+09 | 0.00 | 0.43 |
August | 0.328222E+09 | 0.100842E+10 | 0.00 | 4077418.60 | 611471.59 | 0.00 | 0.503150E+09 | 0.00 | 0.43 |
September | 0.875706E+09 | 0.293875E+09 | 0.00 | 5473018.74 | 215456.42 | 4597034.26 | 0.117592E+10 | 0.00 | 0.43 |
October | 0.325666E+10 | 0.00 | 0.00 | 1826156.04 | 0.00 | 0.529328E+09 | 0.687782E+09 | 0.00 | 0.42 |
November | 0.315327E+10 | 0.00 | 0.00 | 88901.35 | 74984.99 | 0.205085E+10 | 0.134981E+09 | 0.00 | 0.42 |
December | 0.928779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748565E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.196445E+11 | 0.374787E+10 | 0.00 | 18559613.19 | 9189782.44 | 0.303521E+11 | 0.501582E+10 | 0.00 | 0.43 |
Minimum of Months | 0.182472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.325666E+10 | 0.178023E+10 | 0.00 | 5473018.74 | 6687715.95 | 0.774894E+10 | 0.117592E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:35
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |