Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:13:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1333.25 | 581.19 | 581.19 |
Net Site Energy | 1333.25 | 581.19 | 581.19 |
Total Source Energy | 3687.84 | 1607.61 | 1607.61 |
Net Source Energy | 3687.84 | 1607.61 | 1607.61 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 161.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 58.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 382.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 367.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 95.11 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1076.62 | 256.63 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 161.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 58.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 382.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 367.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 95.11 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 198.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 185.68 | 111.87 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 469.32 | 111.87 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 198.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 185.68 | 111.87 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 469.32 | 111.87 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1076.618 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1076.618 | 100.00 |
Total On-Site and Utility Electric Sources | 1076.618 | 100.00 |
Total Electricity End Uses | 1076.618 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 660.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.7888 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 16.5511 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 12.6567 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-16:40 | 16-JAN-09:09 | - | - | - | 13-SEP-11:09 |
Heating | 0.00 | 137685.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36643.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18206.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 96505.67 | 139547.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 137685.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36643.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18206.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 175.09 | 0.00 | 0.00 | 0.00 |
Cooling | 183.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1211.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1165.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 103.10 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3409.65 | 278.19 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 76.32 | 0.00 | 0.00 | 0.00 |
Cooling | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 528.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 507.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1486.34 | 121.27 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 76.32 | 0.00 | 0.00 | 0.00 |
Cooling | 80.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 528.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 507.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1486.34 | 121.27 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.68 |
CORE_RETAIL DIRECT AIR | 7.37 |
POINT_OF_SALE DIRECT AIR | 1.26 |
FRONT_RETAIL DIRECT AIR | 1.03 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.66 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.66 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 38039.93 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 45298.51 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 225142.91 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 33977.10 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 28738.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.68 | 1.68 | 1.68 | 1.68 | 1.72 | 1.72 | 1.00 | 0.977403 | 1.72 |
PSZ-AC:2 | 7.37 | 7.37 | 7.37 | 7.37 | 7.53 | 7.53 | 1.00 | 0.978764 | 7.53 |
PSZ-AC:3 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
PSZ-AC:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.72 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.53 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.26 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.03 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.72 | 1.72 | 1.72 | 1.72 | 29479.45 | 45298.51 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.53 | 7.53 | 7.53 | 7.53 | 135474.29 | 225142.91 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 1.26 | 20971.77 | 33977.10 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 17490.38 | 28738.65 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.72 | 0.860515 | 1.72 | 28489.16 | 29479.45 | 14739.73 | 29479.45 | 0.786305 | 0.786300 | 0.786300 | 0.786300 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.53 | 3.76 | 7.53 | 125805.61 | 135474.29 | 67737.15 | 135474.29 | 0.769257 | 0.769260 | 0.769260 | 0.769260 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.26 | 0.629405 | 1.26 | 20837.78 | 20971.77 | 10485.89 | 20971.77 | 0.796306 | 0.796310 | 0.796310 | 0.796310 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.03 | 0.514280 | 1.03 | 17026.32 | 17490.38 | 8745.19 | 17490.38 | 0.788901 | 0.788900 | 0.788900 | 0.788900 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.72 | 1841.58 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.53 | 13832.79 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.26 | 1393.70 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1138.78 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.789 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.859 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 38.071 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 12.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.657 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2958.869 | 7.789 | 48.236 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2958.869 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 26489.747 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26489.747 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 151.881 | 12.657 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 151.881 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4744 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1725 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3437E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3274 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.941 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.721 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 29.02 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.978 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | 0.31219756E-14 | -0.25237900E-15 | -0.17078023E-09 | -0.40080417E-16 |
25 | 8 | 0.24827770E-07 | 0.64895754E-13 | 0.40814970E-03 | -0.28230026E-09 |
26 | 7 | -0.13145170E-01 | 0.32788080E-08 | -0.24386180E-01 | 0.14946539E-03 |
27 | 6 | 0.42990022 | 0.11289000E-05 | 0.49294528 | -0.50371474E-02 |
28 | 5 | -5.4301032 | 0.41776872E-04 | -4.6011904 | 0.66154067E-01 |
29 | 4 | 34.062169 | 0.33899226E-03 | 22.064921 | -0.43618800 |
30 | 3 | -113.47938 | 0.73347792E-03 | -56.858567 | 1.5477483 |
31 | 2 | 199.36357 | 0.40991987E-03 | 79.008039 | -2.9361691 |
32 | 1 | -171.98885 | 0.43498902E-04 | -55.585984 | 2.7600347 |
33 | 0 | 57.057407 | 0.24596459E-06 | 15.505383 | |
34 | 7 | -0.24541788E-08 | -0.10674912E-14 | 0.56595312E-14 | -0.88347803E-16 |
35 | 6 | 0.48874313E-05 | 0.32994277E-08 | 0.31919810E-02 | -0.26777012E-04 |
36 | 5 | -0.34768456E-03 | 0.19525666E-05 | -0.22384457 | 0.19572094E-02 |
37 | 4 | 0.79733842E-02 | 0.88847046E-04 | 4.8315443 | -0.45284193E-01 |
38 | 3 | -0.69943606E-01 | 0.70626596E-03 | -38.032707 | 0.39877855 |
39 | 2 | 0.24825401 | 0.11745943E-02 | 116.50592 | -1.4182332 |
40 | 1 | -0.35825340 | 0.35768630E-03 | -143.92024 | 2.0492525 |
41 | 0 | 0.17465044 | 0.86763216E-05 | 60.838472 | |
42 | 7 | -0.12489162E-07 | 0.28466235E-14 | -0.17145271E-13 | 0.26119495E-15 |
43 | 6 | 0.18517441E-05 | 0.69460444E-09 | 0.32027219E-02 | -0.26867115E-04 |
44 | 5 | -0.89695516E-04 | 0.39969105E-06 | -0.22445454 | 0.19625936E-02 |
45 | 4 | 0.17714562E-02 | 0.17921615E-04 | 4.8416944 | -0.45381772E-01 |
46 | 3 | -0.14613545E-01 | 0.14074818E-03 | -38.089997 | 0.39941188 |
47 | 2 | 0.50542763E-01 | 0.23137019E-03 | 116.61736 | -1.4197240 |
48 | 1 | -0.72070041E-01 | 0.69440628E-04 | -143.98582 | 2.0503304 |
49 | 0 | 0.34918756E-01 | 0.16519960E-05 | 60.838472 | |
50 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
51 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
52 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
53 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
54 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
55 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
56 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
57 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
58 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
59 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
60 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
61 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
62 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
63 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
64 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
65 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
66 | 7 | -0.12723796E-08 | -0.15085021E-15 | 0.80954726E-14 | -0.10933793E-15 |
67 | 6 | 0.91456241E-05 | 0.63025983E-08 | 0.31797574E-02 | -0.26674470E-04 |
68 | 5 | -0.66211654E-03 | 0.37378006E-05 | -0.22314974 | 0.19510765E-02 |
69 | 4 | 0.15256371E-01 | 0.17022008E-03 | 4.8199703 | -0.45172938E-01 |
70 | 3 | -0.13404479 | 0.13543778E-02 | -37.967318 | 0.39805580 |
71 | 2 | 0.47605416 | 0.22539081E-02 | 116.37865 | -1.4165309 |
72 | 1 | -0.68716389 | 0.68732095E-03 | -143.84532 | 2.0480210 |
73 | 0 | 0.33503722 | 0.16534103E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 30 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 31 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 19650.24152 | 23580.28982 | 1.40178 | 1.68214 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 20924.44834 | 25109.33801 | 0.89252 | 1.07103 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 85975.04507 | 103170.05408 | 6.14142 | 7.36970 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 57273.75162 | 68728.50194 | 2.41352 | 2.89622 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 14091.63053 | 16909.95664 | 1.04901 | 1.25881 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10091.07610 | 12109.29132 | 0.43222 | 0.51866 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 11514.08964 | 13816.90757 | 0.85713 | 1.02856 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10086.39224 | 12103.67069 | 0.43201 | 0.51841 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 31674.67514 | 38009.61017 | 1.38104 | 1.65725 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 22334.62 | 1.72103 | 1.72103 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 31357.89 | 1.07103 | 1.07103 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 106243.43 | 7.52960 | 7.52960 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 122691.32 | 2.89622 | 2.89622 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 17754.31 | 1.25881 | 1.25881 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 17137.83 | 0.51866 | 0.51866 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 14717.09 | 1.02856 | 1.02856 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 17132.24 | 0.51841 | 0.51841 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.68214 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.36970 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25881 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02856 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.65725 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.65725 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 38039.92579 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.68214 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.68214 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.68214 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.68214 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.72103 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.72103 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.97740 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.36970 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.36970 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.36970 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.36970 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.52960 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.52960 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97876 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25881 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25881 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25881 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25881 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25881 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25881 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02856 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02856 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02856 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02856 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02856 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02856 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.72103 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.52960 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.25881 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.02856 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.72103 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.72103 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.72103 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.72103 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.72103 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.72103 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.86052 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.72103 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28489.15742 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29479.45000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14739.72500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29479.45000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78630 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78630 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78630 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78630 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29479.45000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 45298.50531 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.72103 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1841.58422 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 45298.50531 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.52960 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.52960 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.52960 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.52960 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.52960 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.52960 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.76480 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.52960 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 125805.61004 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 135474.29000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 67737.14500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 135474.29000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76926 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76926 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76926 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76926 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 135474.29000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 225142.90719 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.52960 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13832.79046 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 225142.90719 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25881 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25881 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25881 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25881 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.25881 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25881 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62941 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.25881 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20837.77520 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20971.77000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10485.88500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20971.77000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79631 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79631 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79631 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79631 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20971.77000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33977.09667 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25881 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1393.70266 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33977.09667 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02856 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02856 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02856 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02856 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02856 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02856 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51428 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02856 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17026.32015 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17490.38000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8745.19000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17490.38000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78890 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78890 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78890 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78890 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17490.38000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28738.64785 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02856 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1138.78043 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28738.64785 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28130.0 | 10.80 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 129566.5 | 12.06 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 19985.1 | 95.58 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16684.0 | 128.79 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.172 | 0.166 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.437E-002 | 3.409E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.327 | 0.303 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.4893713851E-002 | 0.2297164242 | Pass | Pass | 7.1828765232E-002 | 0.2800731283 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.5154750402E-002 | 0.1381086269 | Pass | Pass | 0.3490098400 | 2.3814375324 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 5.7582436469E-002 | 0.2138344426 | Pass | Pass | 0.1537941760 | 0.6922367561 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 7.0969449532E-002 | 0.2446445318 | Pass | Pass | 4.6702560764E-002 | 0.1386246037 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 9.3030598064E-002 | 0.4013800418 | Pass | Pass | 7.4260807746E-002 | 0.5023402517 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.172 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.034 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.327 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.159 | 0.394 | 0.401 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.623 | 0.440 | 0.445 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.623 | 0.440 | 0.445 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.7888 | 379.89 | 2958.87 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 34.59 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 16.5511 | 1600.48 | 26489.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 56.75 | 0.0000 | Y | 282.18 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 12.6567 | 12.00 | 151.88 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.95 |
Interior Lighting Total | 15.0797 | 2293.99 | 34592.64 | 382.67 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4644.36 | AstronomicalClock | - | 83.55 | 83.55 | 72.84 | |
Exterior Lighting Total | 4644.36 | 72.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29479.45 | 23179.69 | 6299.76 | 0.79 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 135474.29 | 104214.95 | 31259.34 | 0.77 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20971.77 | 16700.03 | 4271.74 | 0.80 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17490.38 | 13798.16 | 3692.22 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28130.0 | 10.80 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 129566.5 | 12.06 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 19985.1 | 95.58 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16684.0 | 128.79 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 38039.93 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 45298.51 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 225142.91 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33977.10 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28738.65 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 1.66 | 1773.33 | 1070.05 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.72 | 1841.58 | 1070.05 | 1.00 | 1.34 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1110.54 | 7.53 | 13832.79 | 1837.12 | 1.00 | 1.15 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1393.70 | 1107.16 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1138.78 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 19650.24 | 23580.29 | 62.07 | 1.402 | 1.682 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.88 | 0.01008 | 21.70 | 0.00879 | 0.232 | 0.00 |
CORE_RETAIL | 85975.05 | 103170.05 | 64.46 | 6.141 | 7.370 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00980 | 21.70 | 0.00879 | 1.890 | 0.00 |
POINT_OF_SALE | 14091.63 | 16909.96 | 112.13 | 1.049 | 1.259 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00888 | 29.05 | 0.00879 | 0.178 | 0.00 |
FRONT_RETAIL | 11514.09 | 13816.91 | 91.62 | 0.857 | 1.029 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00897 | 29.05 | 0.00879 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.62 | 100.00 | 0.00001 | 29.40 | 0.00879 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20924.45 | 25109.34 | 66.10 | 0.893 | 1.071 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00714 | -4.20 | 0.00269 | 0.232 | 0.00 |
CORE_RETAIL | 57273.75 | 68728.50 | 42.94 | 2.414 | 2.896 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 1.890 | 0.00 |
POINT_OF_SALE | 10091.08 | 12109.29 | 80.30 | 0.432 | 0.519 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00750 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_RETAIL | 10086.39 | 12103.67 | 80.26 | 0.432 | 0.518 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00750 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_ENTRY | 31674.68 | 38009.61 | 3167.47 | 1.381 | 1.657 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.04 | 0.00575 | -4.20 | 0.00269 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.72 | 1.72 | 1.07 | 1.07 | 1.7210 | 1.6821 | 1.7210 | 0.9774 | 1.0000 |
PSZ-AC:2 | 7.53 | 7.53 | 2.90 | 2.90 | 7.5296 | 7.3697 | 7.5296 | 0.9788 | 1.0000 |
PSZ-AC:3 | 1.26 | 1.26 | 0.52 | 0.52 | 1.2588 | 1.2588 | 1.2588 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.03 | 1.03 | 0.52 | 0.52 | 1.0286 | 1.0286 | 1.0286 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 38039.926 | 38039.926 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 38039.93 | 38039.93 | 1.657248 | 20.82 | 12.46 | 0.00571931 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.04 | 0.00574544 | 36.6626 | 38009.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 29479.450 | 0.000 | 1.721030 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 29479.45 | 24108.51 | 1.721030 | 23.68 | 17.04 | 0.00959884 | 12.80 | 11.97 | 0.00850000 | 22.36 | 0.00879438 | 15.90 | 13.4551 | 23.88 | 0.01007780 | 53.7142 | 19650.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 45298.505 | 45298.505 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 45298.51 | 45298.51 | 1.721031 | 15.45 | 10.70 | 0.00617544 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 13.4551 | 21.11 | 0.00713682 | 45.2414 | 20924.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 135474.290 | 0.000 | 7.529600 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 135474.29 | 122203.58 | 7.529600 | 25.33 | 17.20 | 0.00910677 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 25.1037 | 23.89 | 0.00979833 | 52.2456 | 79573.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 225142.907 | 225142.907 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 225142.91 | 225142.91 | 7.529600 | 4.48 | 3.28 | 0.00436762 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 25.1037 | 21.11 | 0.00751915 | 47.6314 | 57273.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 20971.770 | 0.000 | 1.258810 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 20971.77 | 19603.72 | 1.258810 | 24.63 | 16.76 | 0.00887058 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 14.1491 | 23.89 | 0.00888288 | 47.4242 | 14083.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 33977.097 | 33977.097 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 33977.10 | 33977.10 | 1.258810 | 12.30 | 8.96 | 0.00585151 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 14.1491 | 21.11 | 0.00750485 | 47.5446 | 10091.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 17490.380 | 0.000 | 1.028560 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 17490.38 | 16172.52 | 1.028560 | 24.80 | 16.88 | 0.00893808 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 17.3165 | 23.89 | 0.00896833 | 47.8740 | 11512.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 28738.648 | 28738.648 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28738.65 | 28738.65 | 1.028561 | 12.29 | 8.95 | 0.00585015 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 17.3165 | 21.11 | 0.00750396 | 47.5391 | 10086.39 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 38039.926 | 38039.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.657248 | 1.96713786 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 38039.93 | 38039.93 | 1.0000 | 1.96713786 | 1.657248 | 20.82 | 12.46 | 0.00571931 | 35446.1 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38039.93 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.05 | 0.00574544 | 21.04 | 0.00574544 | 36.6626 | 38009.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29479.450 | 0.000 | 1.721030 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.6838 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 29479.45 | 24108.51 | 1.0000 | 2.04284675 | 1.721030 | 23.68 | 17.04 | 0.00959884 | 48223.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29479.45 | 22.36 | 0.00879438 | 15.90 | 0.23156651 | 13.4551 | 23.89 | 0.00972390 | 23.88 | 0.01007780 | 53.7142 | 19650.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 45298.505 | 45298.505 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.721031 | 2.04284760 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 45298.51 | 45298.51 | 1.0000 | 2.04284760 | 1.721031 | 15.45 | 10.70 | 0.00617544 | 31149.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45298.51 | -4.20 | 0.00269032 | -4.20 | 0.23156651 | 13.4551 | 20.87 | 0.00713682 | 21.11 | 0.00713682 | 45.2414 | 20924.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 135474.290 | 0.000 | 7.529600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7690 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 135474.29 | 122203.58 | 1.0000 | 8.93756580 | 7.529600 | 25.33 | 17.20 | 0.00910677 | 48657.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 135474.29 | 29.31 | 0.00879438 | 18.27 | 1.89021192 | 25.1037 | 23.89 | 0.00921993 | 23.89 | 0.00979833 | 52.2456 | 79573.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 225142.907 | 225142.907 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.529600 | 8.93756564 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 225142.91 | 225142.91 | 1.0000 | 8.93756564 | 7.529600 | 4.48 | 3.28 | 0.00436762 | 15464.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 225142.91 | -4.20 | 0.00269032 | -4.20 | 1.89021192 | 25.1037 | 20.80 | 0.00751915 | 21.11 | 0.00751915 | 47.6314 | 57273.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20971.770 | 0.000 | 1.258810 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3300 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 20971.77 | 19603.72 | 1.0000 | 1.49419587 | 1.258810 | 24.63 | 16.76 | 0.00887058 | 47341.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20971.77 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 14.1491 | 23.89 | 0.00888314 | 23.89 | 0.00888288 | 47.4242 | 14083.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33977.097 | 33977.097 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.258810 | 1.49419605 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 33977.10 | 33977.10 | 1.0000 | 1.49419605 | 1.258810 | 12.30 | 8.96 | 0.00585151 | 27124.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33977.10 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 14.1491 | 20.93 | 0.00750485 | 21.11 | 0.00750485 | 47.5446 | 10091.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17490.380 | 0.000 | 1.028560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4555 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 17490.38 | 16172.52 | 1.0000 | 1.22089124 | 1.028560 | 24.80 | 16.88 | 0.00893808 | 47683.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17490.38 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 17.3165 | 23.89 | 0.00896819 | 23.89 | 0.00896833 | 47.8740 | 11512.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28738.648 | 28738.648 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.028561 | 1.22089257 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28738.65 | 28738.65 | 1.0000 | 1.22089257 | 1.028561 | 12.29 | 8.95 | 0.00585015 | 27117.3 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28738.65 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 17.3165 | 20.93 | 0.00750396 | 21.11 | 0.00750396 | 47.5391 | 10086.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.72 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.53 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.26 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.03 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 1049.83 | 3463.33 | 627.83 |
CORE_RETAIL | 1318.83 | 2483.00 | 128.67 |
POINT_OF_SALE | 1624.83 | 2223.50 | 203.50 |
FRONT_RETAIL | 1461.67 | 2813.17 | 432.83 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 2122.33 | 3469.67 | 660.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1.50 | 0.00 | 0.00 | 0.00 |
Facility | 1.50 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.37 | 61.34 | 2317.33 | 0.727 | 0.027 | 0.000 | 0.000 |
CORE_RETAIL | 127.94 | 258.43 | 9762.95 | 1.080 | 0.005 | 0.000 | 0.000 |
POINT_OF_SALE | 12.06 | 24.35 | 919.94 | 1.630 | 0.029 | 0.000 | 0.000 |
FRONT_RETAIL | 12.06 | 24.35 | 919.94 | 1.227 | 0.029 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.37 | 61.34 | 2317.33 | 0.354 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.94 | 258.43 | 9762.95 | 0.686 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.06 | 24.35 | 919.94 | 0.686 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.06 | 24.35 | 919.94 | 0.686 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1076.62 | 3304.06 | 07-MAY-06:40 | 96505.67 | 10-AUG-16:40 |
Electricity:Building | 577.83 | 3083.31 | 07-MAY-07:20 | 41654.89 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 84.58 | 607.80 | 01-JAN-00:10 | 5172.60 | 02-JAN-09:10 |
InteriorLights:Electricity | 382.67 | 1288.14 | 07-MAY-07:20 | 30883.85 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 34.59 | 147.94 | 01-JAN-00:10 | 2413.46 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 382.67 | 1288.14 | 07-MAY-07:20 | 30883.85 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 366.48 | 1658.43 | 07-MAY-07:20 | 28493.38 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 282.18 | 882.99 | 07-MAY-07:20 | 23840.77 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 84.90 | 611.62 | 01-JAN-00:10 | 5167.35 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 39.92 | 197.87 | 01-JAN-00:10 | 2684.87 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1076.62 | 3304.06 | 07-MAY-06:40 | 96505.67 | 10-AUG-16:40 |
ElectricityPurchased:Plant | 1076.62 | 3304.06 | 07-MAY-06:40 | 96505.67 | 10-AUG-16:40 |
Cogeneration:ElectricityPurchased | 1076.62 | 3304.06 | 07-MAY-06:40 | 96505.67 | 10-AUG-16:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1076.62 | 3304.06 | 07-MAY-06:40 | 96505.67 | 10-AUG-16:40 |
ElectricityNet:Plant | 1076.62 | 3304.06 | 07-MAY-06:40 | 96505.67 | 10-AUG-16:40 |
Cogeneration:ElectricityNet | 1076.62 | 3304.06 | 07-MAY-06:40 | 96505.67 | 10-AUG-16:40 |
Electricity:HVAC | 425.95 | 0.00 | 01-JAN-00:10 | 56085.13 | 10-AUG-15:00 |
Fans:Electricity | 367.89 | 0.00 | 01-JAN-00:10 | 19980.19 | 01-JAN-08:20 |
General:Fans:Electricity | 367.89 | 0.00 | 01-JAN-00:10 | 19980.19 | 01-JAN-08:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 58.07 | 0.00 | 01-JAN-00:10 | 37878.27 | 10-AUG-15:00 |
ExteriorLights:Electricity | 72.84 | 0.00 | 01-JAN-08:10 | 4644.36 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 72.84 | 0.00 | 01-JAN-08:10 | 4644.36 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 256.63 | 1862.00 | 27-APR-05:10 | 139547.67 | 16-JAN-09:10 |
Gas:Plant | 95.11 | 1862.00 | 27-APR-05:10 | 5085.07 | 13-FEB-12:10 |
WaterSystems:Gas | 95.11 | 1862.00 | 27-APR-05:10 | 5085.07 | 13-FEB-12:10 |
Water Heater:WaterSystems:Gas | 95.11 | 1862.00 | 27-APR-05:10 | 5085.07 | 13-FEB-12:10 |
Gas:HVAC | 161.52 | 0.00 | 01-JAN-00:10 | 137685.67 | 16-JAN-09:10 |
Heating:Gas | 161.52 | 0.00 | 01-JAN-00:10 | 137685.67 | 16-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 968.82 | 0.00 | 01-JAN-00:10 | 211640.44 | 10-AUG-14:10 |
EnergyTransfer:Building | 634.36 | 0.00 | 01-JAN-00:10 | 84870.71 | 16-JAN-09:10 |
EnergyTransfer:Zone:BACK_SPACE | 60.86 | 0.00 | 01-JAN-00:10 | 19239.73 | 16-JAN-08:10 |
Heating:EnergyTransfer | 109.40 | 0.00 | 01-JAN-00:10 | 79244.03 | 16-JAN-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 8.30 | 0.00 | 01-JAN-00:10 | 19239.73 | 16-JAN-08:10 |
Cooling:EnergyTransfer | 524.95 | 0.00 | 01-JAN-00:10 | 80157.85 | 10-AUG-14:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 52.56 | 0.00 | 01-JAN-00:10 | 11229.49 | 10-AUG-06:10 |
EnergyTransfer:Zone:CORE_RETAIL | 386.19 | 0.00 | 01-JAN-00:10 | 59382.09 | 12-MAY-06:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 16.85 | 0.00 | 01-JAN-00:10 | 43905.59 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 369.34 | 0.00 | 01-JAN-00:10 | 59382.09 | 12-MAY-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 66.77 | 0.00 | 01-JAN-00:10 | 11179.98 | 04-OCT-14:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 2.17 | 0.00 | 01-JAN-00:10 | 7887.96 | 16-JAN-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 64.61 | 0.00 | 01-JAN-00:10 | 11179.98 | 04-OCT-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 42.42 | 0.00 | 01-JAN-00:10 | 8922.30 | 04-OCT-14:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 3.97 | 0.00 | 01-JAN-00:10 | 8133.20 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 38.45 | 0.00 | 01-JAN-00:10 | 8922.30 | 04-OCT-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 78.11 | 0.00 | 01-JAN-00:10 | 26102.82 | 18-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 78.11 | 0.00 | 01-JAN-00:10 | 26102.82 | 18-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 334.46 | 0.00 | 01-JAN-00:10 | 131482.59 | 10-AUG-14:10 |
HeatingCoils:EnergyTransfer | 129.22 | 0.00 | 01-JAN-00:10 | 110148.54 | 16-JAN-09:10 |
CoolingCoils:EnergyTransfer | 205.25 | 0.00 | 01-JAN-00:10 | 131482.59 | 10-AUG-14:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 8.304 | -52.557 | 0.000 | 0.000 | 38.804 | 34.587 | 49.992 | 0.000 | 0.000 | 0.040 | 0.001 | 0.000 | 0.000 | 0.000 | -15.196 | -63.975 |
CORE_RETAIL | 0.000 | 0.000 | 16.852 | -369.339 | 0.000 | 0.000 | 162.555 | 282.178 | 84.299 | 45.541 | 0.000 | 0.033 | 0.007 | 0.000 | -24.709 | 0.000 | -13.543 | -183.866 |
POINT_OF_SALE | 0.000 | 0.000 | 2.166 | -64.606 | 0.000 | 0.000 | 14.977 | 31.980 | 52.922 | 29.855 | 0.000 | 0.017 | 0.001 | 0.000 | -18.592 | 0.000 | -7.080 | -41.640 |
FRONT_RETAIL | 0.000 | 0.000 | 3.973 | -38.449 | 0.000 | 0.000 | 15.428 | 31.980 | 7.943 | 29.985 | 0.000 | 0.017 | 0.002 | 0.000 | -17.725 | 0.000 | -6.636 | -26.516 |
FRONT_ENTRY | 78.109 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.946 | 0.000 | 6.151 | 0.000 | 0.008 | 1.353 | 0.000 | -3.557 | 0.000 | -84.009 | -0.000 |
Total Facility | 78.109 | 0.000 | 31.295 | -524.951 | 0.000 | 0.000 | 231.763 | 382.671 | 195.156 | 111.532 | 0.000 | 0.116 | 1.365 | 0.000 | -64.583 | 0.000 | -126.465 | -315.997 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 19-JUL-06:02 | 0.00 | 0.00 | 0.00 | -34943.80 | 0.00 | 0.00 | 402.02 | 536.32 | 1226.28 | 0.00 | 0.00 | 0.00 | 32895.79 | 0.00 | -0.00 | 0.00 | -116.62 | 0.00 |
CORE_RETAIL | 05-OCT-06:02 | 0.00 | 0.00 | 0.00 | -199240.29 | 0.00 | 0.00 | 1606.67 | 5297.95 | 2067.82 | 0.00 | 0.00 | 0.00 | 192219.35 | 0.00 | -1797.60 | 0.00 | -153.90 | 0.00 |
POINT_OF_SALE | 05-OCT-06:02 | 0.00 | 0.00 | 0.00 | -27498.78 | 0.00 | 0.00 | 150.36 | 499.21 | 1298.17 | 0.00 | 0.00 | 0.00 | 26916.62 | 0.00 | -1285.89 | 0.00 | -79.70 | 0.00 |
FRONT_RETAIL | 11-SEP-06:02 | 0.00 | 0.00 | 0.00 | -20892.18 | 0.00 | 0.00 | 152.29 | 499.21 | 194.85 | 0.00 | 0.00 | 0.00 | 20962.41 | 0.00 | -856.68 | 0.00 | -59.90 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-OCT-06:02 | 0.00 | 0.00 | 0.00 | -248336.00 | 0.00 | 0.00 | 2349.33 | 6863.08 | 4787.13 | 0.00 | 0.00 | 0.00 | 239432.95 | 0.00 | -4594.71 | 0.00 | -501.77 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 16-JAN-08:61 | 0.00 | 0.00 | 45820.21 | 0.00 | 0.00 | 0.00 | 0.00 | 147.94 | 459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -351.99 | -46076.02 |
CORE_RETAIL | 16-JAN-08:61 | 0.00 | 0.00 | 231962.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.49 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1506.86 | 0.00 | -314.49 | -232240.58 |
POINT_OF_SALE | 16-JAN-08:61 | 0.00 | 0.00 | 33590.66 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 486.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -991.88 | 0.00 | -156.91 | -33053.49 |
FRONT_RETAIL | 16-JAN-08:61 | 0.00 | 0.00 | 28688.43 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -991.62 | 0.00 | -158.82 | -27735.85 |
FRONT_ENTRY | 18-FEB-18:00 | 26101.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 67.72 | 0.00 | -305.85 | 0.00 | -26000.22 | 0.00 |
Total Facility | 16-JAN-08:61 | 5757.60 | 0.00 | 340061.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1729.63 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3696.09 | 0.00 | -4259.19 | -341388.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6821 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7210 | 0.1346 | 1.0000 | 0.2316 | 0.1346 | ||
PSZ-AC:2 | 7.3697 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.5296 | 0.2510 | 1.0000 | 1.8902 | 0.2510 | ||
PSZ-AC:3 | 1.2588 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2588 | 0.1415 | 1.0000 | 0.1781 | 0.1415 | ||
PSZ-AC:4 | 1.0286 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0286 | 0.1732 | 1.0000 | 0.1781 | 0.1732 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6821 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6821 | 1.0000 | 1.0000 | 0.2316 | 0.1377 | ||
PSZ-AC:2 | 7.3697 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.3697 | 1.0000 | 1.0000 | 1.8902 | 0.2565 | ||
PSZ-AC:3 | 1.2588 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2588 | 1.0000 | 1.0000 | 0.1781 | 0.1415 | ||
PSZ-AC:4 | 1.0286 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0286 | 1.0000 | 1.0000 | 0.1781 | 0.1732 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6821 | 1.6821 | 1.6821 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.3697 | 7.3697 | 7.3697 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2588 | 1.2588 | 1.2588 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0286 | 1.0286 | 1.0286 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6821 | 1.7210 | 1.6821 | 1.6821 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.3697 | 7.5296 | 7.3697 | 7.3697 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2588 | 1.2588 | 1.2588 | 1.2588 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0286 | 1.0286 | 1.0286 | 1.0286 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6821 | 1.6821 | 1.6821 | 0.2316 | 0.2162 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.3697 | 7.3697 | 7.3697 | 1.8902 | 0.6526 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2588 | 1.2588 | 1.2588 | 0.1781 | 0.3434 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0286 | 1.0286 | 1.0286 | 0.1781 | 0.3436 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6821 | 1.6821 | 1.6821 | 1.6821 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.3697 | 7.3697 | 7.3697 | 7.3697 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2588 | 1.2588 | 1.2588 | 1.2588 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0286 | 1.0286 | 1.0286 | 1.0286 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:20
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 161.52 | 137685.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 58.07 | 37878.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 382.67 | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.84 | 4644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 367.89 | 19980.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 95.11 | 5085.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1076.62 |
Natural Gas | 0.00 | 256.63 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1333.25 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 166.81 |
Space Heating | 0.00 |
Space Cooling | 25.31 |
Fans (All) | 160.37 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 469.32 |
Subtotal | 469.32 |
Natural Gas [MJ/m2] | |
Space Heating | 70.41 |
Service Water Heating | 41.46 |
Miscellaneous (All) | 111.87 |
Subtotal | 111.87 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 28.70 |
Space Heating | 12.11 |
Space Cooling | 4.36 |
Fans (All) | 27.59 |
Service Water Heating | 7.13 |
Receptacle Equipment | 14.64 |
Miscellaneous | 5.46 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.479797E+11 |
February | 0.000 | 0.307457E+11 |
March | 0.000 | 0.114132E+11 |
April | 0.000 | 0.547740E+10 |
May | 0.000 | 0.314624E+10 |
June | 0.000 | 0.120456E+10 |
July | 0.000 | 0.298999E+09 |
August | 0.000 | 0.149403E+09 |
September | 0.000 | 0.172293E+10 |
October | 0.000 | 0.480290E+10 |
November | 0.000 | 0.181065E+11 |
December | 0.000 | 0.364723E+11 |
Annual Sum or Average | 0.161520E+12 | |
Minimum of Months | 0.000 | 0.149403E+09 |
Maximum of Months | 0.000 | 0.479797E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126579E+10 | 5150.13 | 06-JAN-07:05 | -2.3 | -2.5 | 0.167201E+10 | 2188.75 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.134186E+10 | 5029.53 | 18-FEB-07:05 | -2.1 | -2.8 | 0.160957E+10 | 2451.24 | 25-FEB-14:39 | 13.33 | 11.80 |
March | 0.234824E+10 | 3915.44 | 24-MAR-06:05 | 1.78 | -1.5 | 0.202146E+10 | 2451.23 | 09-MAR-15:09 | 14.13 | 11.88 |
April | 0.319511E+10 | 7108.16 | 27-APR-15:00 | 27.20 | 17.27 | 0.205685E+10 | 2451.27 | 29-APR-15:00 | 20.00 | 14.41 |
May | 0.533344E+10 | 27667.24 | 07-MAY-08:62 | 17.52 | 14.34 | 0.221022E+10 | 2451.30 | 04-MAY-14:20 | 24.07 | 15.16 |
June | 0.708239E+10 | 33758.76 | 29-JUN-06:02 | 12.70 | 11.22 | 0.219861E+10 | 2451.31 | 26-JUN-14:00 | 20.60 | 14.39 |
July | 0.880541E+10 | 34945.26 | 19-JUL-06:02 | 14.08 | 10.93 | 0.218754E+10 | 2451.36 | 22-JUL-14:30 | 25.00 | 16.77 |
August | 0.922076E+10 | 33928.45 | 01-AUG-06:02 | 11.32 | 11.32 | 0.228122E+10 | 2451.33 | 09-AUG-14:09 | 28.42 | 18.30 |
September | 0.636134E+10 | 33223.01 | 15-SEP-06:02 | 11.47 | 11.32 | 0.215167E+10 | 2451.31 | 09-SEP-13:20 | 20.77 | 14.60 |
October | 0.359050E+10 | 6137.12 | 04-OCT-15:00 | 21.70 | 11.47 | 0.211931E+10 | 2451.24 | 21-OCT-11:20 | 12.57 | 9.57 |
November | 0.242825E+10 | 5218.97 | 04-NOV-14:10 | 21.10 | 15.93 | 0.180950E+10 | 2451.24 | 04-NOV-12:50 | 20.32 | 15.90 |
December | 0.158335E+10 | 4758.31 | 06-DEC-07:05 | 0.18 | -0.1 | 0.169558E+10 | 2147.94 | 30-DEC-16:10 | 8.35 | 6.85 |
Annual Sum or Average | 0.525564E+11 | 0.240135E+11 | ||||||||
Minimum of Months | 0.126579E+10 | 3915.44 | -2.3 | -2.8 | 0.160957E+10 | 2147.94 | 8.35 | 6.85 | ||
Maximum of Months | 0.922076E+10 | 34945.26 | 27.20 | 17.27 | 0.228122E+10 | 2451.36 | 28.42 | 18.30 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177812E+11 | 35989.31 | 16-JAN-09:05 | -0.5 | -2.1 | 0.711179E+10 | 10310.51 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.178827E+11 | 35011.28 | 09-FEB-07:03 | -0.7 | -1.1 | 0.694957E+10 | 10327.14 | 25-FEB-11:00 | 15.00 | 12.12 |
March | 0.255010E+11 | 70896.24 | 11-MAR-07:03 | 10.00 | 9.66 | 0.877638E+10 | 10327.01 | 11-MAR-12:20 | 11.30 | 9.96 |
April | 0.278030E+11 | 170971.87 | 27-APR-06:02 | 11.88 | 9.03 | 0.878358E+10 | 10327.49 | 27-APR-14:09 | 26.28 | 16.89 |
May | 0.363741E+11 | 184157.12 | 21-MAY-08:62 | 9.08 | 7.54 | 0.934066E+10 | 10327.19 | 08-MAY-14:00 | 17.80 | 14.19 |
June | 0.416192E+11 | 171265.07 | 02-JUN-06:02 | 11.20 | 9.31 | 0.927198E+10 | 10327.54 | 26-JUN-14:50 | 20.60 | 14.29 |
July | 0.468316E+11 | 174604.64 | 03-JUL-06:02 | 11.88 | 8.45 | 0.921803E+10 | 10327.66 | 22-JUL-14:20 | 24.80 | 16.69 |
August | 0.472822E+11 | 154866.65 | 19-AUG-06:02 | 12.35 | 11.10 | 0.961255E+10 | 10327.56 | 09-AUG-14:39 | 28.17 | 18.40 |
September | 0.372716E+11 | 171138.78 | 29-SEP-06:02 | 10.68 | 8.60 | 0.907126E+10 | 10327.55 | 09-SEP-11:09 | 19.08 | 13.66 |
October | 0.283126E+11 | 199260.24 | 05-OCT-06:02 | 8.48 | 5.35 | 0.900174E+10 | 10327.14 | 14-OCT-10:09 | 11.70 | 9.24 |
November | 0.229997E+11 | 141229.07 | 05-NOV-08:62 | 12.88 | 12.18 | 0.768950E+10 | 10327.22 | 04-NOV-11:50 | 18.72 | 15.12 |
December | 0.196814E+11 | 37240.42 | 26-DEC-07:05 | -1.6 | -1.6 | 0.726899E+10 | 9978.98 | 02-DEC-14:39 | 11.87 | 5.60 |
Annual Sum or Average | 0.369340E+12 | 0.102096E+12 | ||||||||
Minimum of Months | 0.177812E+11 | 35011.28 | -1.6 | -2.1 | 0.694957E+10 | 9978.98 | 11.30 | 5.60 | ||
Maximum of Months | 0.472822E+11 | 199260.24 | 12.88 | 12.18 | 0.961255E+10 | 10327.66 | 28.17 | 18.40 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245676E+10 | 4500.78 | 20-JAN-13:30 | 6.70 | 4.71 | 0.733844E+09 | 973.09 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.296692E+10 | 7080.12 | 27-FEB-15:10 | 19.90 | 12.20 | 0.717160E+09 | 973.10 | 25-FEB-11:00 | 15.00 | 12.12 |
March | 0.432398E+10 | 7689.53 | 18-MAR-13:50 | 19.53 | 10.60 | 0.875179E+09 | 973.10 | 18-MAR-12:09 | 16.78 | 11.23 |
April | 0.512225E+10 | 26157.60 | 27-APR-06:02 | 11.88 | 9.03 | 0.842313E+09 | 973.16 | 29-APR-15:20 | 21.47 | 14.97 |
May | 0.615782E+10 | 25729.19 | 16-MAY-06:02 | 11.70 | 10.49 | 0.882631E+09 | 973.18 | 05-MAY-14:50 | 24.40 | 16.94 |
June | 0.681690E+10 | 25148.16 | 22-JUN-06:02 | 11.70 | 10.71 | 0.873821E+09 | 973.17 | 26-JUN-14:00 | 20.60 | 14.39 |
July | 0.801271E+10 | 26531.12 | 06-JUL-06:02 | 12.80 | 9.82 | 0.868652E+09 | 973.20 | 01-JUL-14:09 | 20.00 | 14.38 |
August | 0.894572E+10 | 24239.53 | 01-AUG-06:02 | 11.32 | 11.32 | 0.905870E+09 | 973.19 | 25-AUG-14:00 | 26.40 | 18.81 |
September | 0.778270E+10 | 25326.09 | 21-SEP-06:02 | 12.20 | 10.58 | 0.855782E+09 | 973.21 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.590639E+10 | 27502.52 | 05-OCT-06:02 | 8.48 | 5.35 | 0.860406E+09 | 973.12 | 07-OCT-15:50 | 16.97 | 12.09 |
November | 0.336611E+10 | 19287.70 | 05-NOV-08:62 | 12.88 | 12.18 | 0.784068E+09 | 973.15 | 04-NOV-10:00 | 17.80 | 14.79 |
December | 0.274814E+10 | 6085.73 | 05-DEC-12:30 | 10.30 | 6.12 | 0.761206E+09 | 973.10 | 02-DEC-11:30 | 11.65 | 5.96 |
Annual Sum or Average | 0.646064E+11 | 0.996093E+10 | ||||||||
Minimum of Months | 0.245676E+10 | 4500.78 | 6.70 | 4.71 | 0.717160E+09 | 973.09 | 11.65 | 5.96 | ||
Maximum of Months | 0.894572E+10 | 27502.52 | 19.90 | 12.20 | 0.905870E+09 | 973.21 | 26.40 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104291E+10 | 4029.61 | 07-JAN-07:05 | -2.5 | -2.6 | 0.666129E+09 | 915.85 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.152742E+10 | 4551.78 | 27-FEB-15:10 | 19.90 | 12.20 | 0.653462E+09 | 973.09 | 27-FEB-15:00 | 19.40 | 12.41 |
March | 0.244642E+10 | 5202.84 | 01-MAR-14:30 | 12.50 | 6.84 | 0.807482E+09 | 973.09 | 18-MAR-11:20 | 13.70 | 9.30 |
April | 0.291863E+10 | 18106.22 | 28-APR-06:02 | 11.10 | 10.22 | 0.806301E+09 | 973.15 | 29-APR-15:20 | 21.47 | 14.97 |
May | 0.355695E+10 | 18494.88 | 05-MAY-06:02 | 13.90 | 11.48 | 0.866190E+09 | 973.11 | 04-MAY-14:20 | 24.07 | 15.16 |
June | 0.405755E+10 | 19921.07 | 29-JUN-06:02 | 12.70 | 11.22 | 0.869360E+09 | 973.15 | 26-JUN-14:00 | 20.60 | 14.39 |
July | 0.512426E+10 | 20180.04 | 08-JUL-06:02 | 13.27 | 11.34 | 0.867716E+09 | 973.17 | 01-JUL-14:09 | 20.00 | 14.38 |
August | 0.599236E+10 | 20162.50 | 01-AUG-06:02 | 11.32 | 11.32 | 0.904739E+09 | 973.15 | 29-AUG-14:09 | 29.90 | 19.92 |
September | 0.504442E+10 | 20895.81 | 11-SEP-06:02 | 12.07 | 10.69 | 0.850172E+09 | 973.20 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.358419E+10 | 19367.36 | 05-OCT-06:02 | 8.48 | 5.35 | 0.829396E+09 | 973.11 | 07-OCT-15:50 | 16.97 | 12.09 |
November | 0.184854E+10 | 7603.71 | 05-NOV-08:62 | 12.88 | 12.18 | 0.701522E+09 | 973.12 | 04-NOV-11:30 | 18.35 | 14.99 |
December | 0.130536E+10 | 3510.86 | 25-DEC-09:05 | -0.1 | -0.6 | 0.687494E+09 | 973.10 | 02-DEC-12:09 | 12.20 | 6.08 |
Annual Sum or Average | 0.384490E+11 | 0.950996E+10 | ||||||||
Minimum of Months | 0.104291E+10 | 3510.86 | -2.5 | -2.6 | 0.653462E+09 | 915.85 | 12.20 | 6.08 | ||
Maximum of Months | 0.599236E+10 | 20895.81 | 19.90 | 12.20 | 0.904739E+09 | 973.20 | 29.90 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258324E+10 | 45820.21 | 16-JAN-08:61 | -1.0 |
February | 0.171893E+10 | 45760.84 | 13-FEB-06:01 | 2.30 |
March | 0.419161E+09 | 45045.39 | 06-MAR-06:02 | 6.70 |
April | 0.203465E+09 | 9686.93 | 19-APR-06:03 | 2.48 |
May | 0.181998E+09 | 1826.76 | 14-MAY-07:43 | 14.03 |
June | 0.174940E+09 | 1784.95 | 11-JUN-07:01 | 12.98 |
July | 0.182684E+09 | 1857.76 | 16-JUL-07:45 | 14.22 |
August | 0.183463E+09 | 1829.42 | 06-AUG-07:53 | 14.20 |
September | 0.180487E+09 | 1797.81 | 03-SEP-07:01 | 13.40 |
October | 0.184328E+09 | 1810.03 | 01-OCT-07:53 | 15.60 |
November | 0.607555E+09 | 45081.20 | 24-NOV-06:02 | 2.02 |
December | 0.168419E+10 | 45817.80 | 25-DEC-08:61 | -0.9 |
Annual Sum or Average | 0.830444E+10 | |||
Minimum of Months | 0.174940E+09 | 1784.95 | -1.0 | |
Maximum of Months | 0.258324E+10 | 45820.21 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252984E+10 | 231962.00 | 16-JAN-08:61 | -1.0 |
February | 0.176497E+10 | 230856.09 | 20-FEB-08:61 | 0.18 |
March | 0.141006E+10 | 13935.19 | 14-MAR-05:45 | 4.40 |
April | 0.132748E+10 | 13793.51 | 18-APR-05:43 | 3.30 |
May | 0.131101E+10 | 13644.27 | 14-MAY-07:43 | 14.03 |
June | 0.105928E+10 | 13474.38 | 11-JUN-07:01 | 12.98 |
July | 0.835662E+09 | 13435.06 | 16-JUL-07:01 | 13.48 |
August | 0.767064E+09 | 13475.53 | 27-AUG-07:12 | 15.77 |
September | 0.116880E+10 | 13487.62 | 03-SEP-07:01 | 13.40 |
October | 0.138726E+10 | 13620.74 | 01-OCT-07:53 | 15.60 |
November | 0.141078E+10 | 15187.03 | 15-NOV-07:13 | 5.53 |
December | 0.187970E+10 | 222855.35 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.168519E+11 | |||
Minimum of Months | 0.767064E+09 | 13435.06 | -1.0 | |
Maximum of Months | 0.252984E+10 | 231962.00 | 15.77 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500607E+09 | 33590.66 | 16-JAN-08:61 | -1.0 |
February | 0.264705E+09 | 33328.10 | 21-FEB-06:01 | 1.70 |
March | 0.141246E+09 | 11938.61 | 06-MAR-06:02 | 6.70 |
April | 0.126910E+09 | 1382.51 | 19-APR-05:53 | 2.20 |
May | 0.128638E+09 | 1360.18 | 14-MAY-07:43 | 14.03 |
June | 0.118596E+09 | 1322.61 | 11-JUN-07:01 | 12.98 |
July | 96833585.77 | 1320.04 | 19-JUL-05:01 | 11.57 |
August | 69147682.85 | 1584.12 | 10-AUG-05:04 | 17.33 |
September | 99106880.21 | 1565.75 | 14-SEP-05:02 | 12.62 |
October | 0.132042E+09 | 1352.86 | 01-OCT-07:53 | 15.60 |
November | 0.151500E+09 | 12050.40 | 24-NOV-06:02 | 2.02 |
December | 0.336906E+09 | 33586.99 | 25-DEC-08:61 | -0.9 |
Annual Sum or Average | 0.216624E+10 | |||
Minimum of Months | 69147682.85 | 1320.04 | -1.0 | |
Maximum of Months | 0.500607E+09 | 33590.66 | 17.33 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118326E+10 | 28688.43 | 16-JAN-08:61 | -1.0 |
February | 0.592408E+09 | 28590.27 | 13-FEB-06:01 | 2.30 |
March | 0.213878E+09 | 27847.10 | 06-MAR-06:02 | 6.70 |
April | 0.131667E+09 | 8047.73 | 11-APR-05:02 | 5.60 |
May | 0.109596E+09 | 1115.63 | 14-MAY-07:43 | 14.03 |
June | 0.105301E+09 | 1089.91 | 11-JUN-07:01 | 12.98 |
July | 0.108317E+09 | 1137.43 | 16-JUL-07:45 | 14.22 |
August | 94542619.96 | 1125.01 | 06-AUG-07:53 | 14.20 |
September | 0.106820E+09 | 1098.45 | 03-SEP-07:01 | 13.40 |
October | 0.112389E+09 | 1299.94 | 16-OCT-06:10 | 6.60 |
November | 0.325081E+09 | 27981.76 | 24-NOV-06:02 | 2.02 |
December | 0.889415E+09 | 28639.43 | 25-DEC-08:61 | -0.9 |
Annual Sum or Average | 0.397268E+10 | |||
Minimum of Months | 94542619.96 | 1089.91 | -1.0 | |
Maximum of Months | 0.118326E+10 | 28688.43 | 14.22 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138758E+11 | 25661.45 | 07-JAN-12:10 | -0.4 |
February | 0.105448E+11 | 26102.82 | 18-FEB-18:00 | -0.6 |
March | 0.875443E+10 | 18922.48 | 05-MAR-12:10 | 5.10 |
April | 0.582182E+10 | 16058.83 | 18-APR-17:00 | 7.20 |
May | 0.411468E+10 | 14437.84 | 23-MAY-17:00 | 8.30 |
June | 0.203159E+10 | 11546.45 | 13-JUN-11:05 | 11.28 |
July | 0.834553E+09 | 7907.79 | 12-JUL-11:10 | 13.98 |
August | 0.607236E+09 | 8226.60 | 01-AUG-11:10 | 13.62 |
September | 0.257581E+10 | 11331.82 | 16-SEP-11:04 | 11.78 |
October | 0.581818E+10 | 13335.52 | 31-OCT-17:00 | 9.40 |
November | 0.102226E+11 | 21424.92 | 12-NOV-18:00 | 3.30 |
December | 0.129071E+11 | 25637.46 | 26-DEC-12:10 | 0.27 |
Annual Sum or Average | 0.781086E+11 | |||
Minimum of Months | 0.607236E+09 | 7907.79 | -0.6 | |
Maximum of Months | 0.138758E+11 | 26102.82 | 13.98 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.290080E+10 | 2413.46 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.263912E+10 | 2413.46 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.300979E+10 | 2413.46 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.284005E+10 | 2413.46 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.295530E+10 | 2413.46 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.290440E+10 | 2413.46 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.289095E+10 | 2413.46 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.300979E+10 | 2413.46 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.284005E+10 | 2413.46 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.290080E+10 | 2413.46 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.280526E+10 | 2413.46 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.289095E+10 | 2413.46 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.345872E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.263912E+10 | 2413.46 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.300979E+10 | 2413.46 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.271899E+11 | 23840.77 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.236584E+11 | 23840.77 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.249976E+11 | 23840.77 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.206289E+11 | 23840.77 | 01-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.204196E+11 | 23840.77 | 01-MAY-16:00 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.202939E+11 | 21854.04 | 01-JUN-16:19 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.207216E+11 | 23840.77 | 12-JUL-08:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.222815E+11 | 23840.77 | 08-AUG-16:00 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.228514E+11 | 23840.77 | 07-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.254317E+11 | 23840.77 | 02-OCT-15:39 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.260728E+11 | 23840.77 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.276305E+11 | 23840.77 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.282178E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.202939E+11 | 21854.04 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.276305E+11 | 23840.77 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.163184E+09 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.148475E+09 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.169362E+09 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.159794E+09 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.166273E+09 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.163430E+09 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.162637E+09 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.169362E+09 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.159794E+09 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.163184E+09 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.157798E+09 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.162637E+09 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194593E+10 | ||||
Minimum of Months | 0.148475E+09 | 136.69 | 0.00 | 0.00 | |
Maximum of Months | 0.169362E+09 | 136.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178987E+10 |
February | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152984E+10 |
March | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158659E+10 |
April | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2197050.89 | 0.151729E+10 |
May | 0.536353E+10 | 0.295530E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142601.28 | 0.124910E+10 |
June | 0.528933E+10 | 0.290440E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1225401.96 | 0.102870E+10 |
July | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12630746.78 | 0.823061E+09 |
August | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24089946.05 | 0.729675E+09 |
September | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135442.51 | 0.586148E+09 |
October | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134951E+10 |
November | 0.504819E+10 | 0.280526E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150412E+10 |
December | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150242E+10 |
Annual Sum or Average | 0.628175E+11 | 0.345872E+11 | 0.499918E+11 | 40421189.47 | 0.151963E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586148E+09 |
Maximum of Months | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24089946.05 | 0.178987E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.271899E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158672E+10 |
February | 0.201852E+11 | 0.236584E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136065E+10 |
March | 0.230879E+11 | 0.249976E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143565E+10 |
April | 0.218263E+11 | 0.206289E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1798492.63 | 0.136687E+10 |
May | 0.225967E+11 | 0.204196E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116822.88 | 0.110912E+10 |
June | 0.222841E+11 | 0.202939E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1003299.21 | 0.914127E+09 |
July | 0.221389E+11 | 0.207216E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10244047.15 | 0.729848E+09 |
August | 0.230879E+11 | 0.222815E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19674197.79 | 0.647743E+09 |
September | 0.218263E+11 | 0.228514E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110909.85 | 0.515743E+09 |
October | 0.221054E+11 | 0.254317E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119977E+10 |
November | 0.212681E+11 | 0.260728E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134210E+10 |
December | 0.221389E+11 | 0.276305E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133491E+10 |
Annual Sum or Average | 0.264651E+12 | 0.282178E+12 | 0.842987E+11 | 32947769.51 | 0.135432E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.202939E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515743E+09 |
Maximum of Months | 0.230879E+11 | 0.276305E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19674197.79 | 0.158672E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816755E+09 |
February | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717905E+09 |
March | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756220E+09 |
April | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 952111.87 | 0.707820E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61810.08 | 0.570341E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531072.71 | 0.470401E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5351044.16 | 0.383959E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10367687.65 | 0.349863E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58569.92 | 0.276294E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633050E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701749E+09 |
December | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695666E+09 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.529224E+11 | 17322296.39 | 0.708002E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276294E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10367687.65 | 0.816755E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770972E+09 |
February | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672729E+09 |
March | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704323E+09 |
April | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 952073.74 | 0.663670E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61822.48 | 0.539455E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 531026.13 | 0.444948E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5384042.16 | 0.360681E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10380558.09 | 0.327263E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58583.45 | 0.261422E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593932E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644854E+09 |
December | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651707E+09 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.794328E+10 | 17368106.05 | 0.663596E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261422E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10380558.09 | 0.770972E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137971E+11 |
February | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107518E+11 |
March | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925246E+10 |
April | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417703.88 | 0.640786E+10 |
May | 0.00 | 0.166273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478616E+10 |
June | 0.00 | 0.163430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272377E+10 |
July | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1572749.41 | 0.153068E+10 |
August | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5661911.40 | 0.125879E+10 |
September | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345542E+10 |
October | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660586E+10 |
November | 0.00 | 0.157798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104914E+11 |
December | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129477E+11 |
Annual Sum or Average | 0.00 | 0.194593E+10 | 7652364.69 | 0.840089E+11 | |||||
Minimum of Months | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125879E+10 |
Maximum of Months | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5661911.40 | 0.137971E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2413.46 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3091.80 | 12-JAN-24:00 |
February | 5888.82 | 01-FEB-15:09 | 2413.46 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2934.67 | 16-FEB-21:03 |
March | 5888.82 | 01-MAR-15:09 | 2413.46 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2625.12 | 28-MAR-24:00 |
April | 5888.82 | 01-APR-10:09 | 2413.46 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.84 | 01-APR-16:00 | 2955.08 | 07-APR-24:00 |
May | 5888.82 | 01-MAY-14:09 | 2413.46 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 05-MAY-16:00 | 2809.80 | 17-MAY-20:05 |
June | 5888.82 | 01-JUN-14:09 | 2413.46 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.23 | 28-JUN-16:00 | 2898.85 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 2413.46 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 237.28 | 30-JUL-18:03 | 1526.99 | 02-JUL-04:00 |
August | 5888.82 | 01-AUG-14:09 | 2413.46 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 217.36 | 13-AUG-18:03 | 2124.82 | 11-AUG-04:00 |
September | 5888.82 | 01-SEP-14:09 | 2413.46 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 14-SEP-17:00 | 1467.50 | 18-SEP-23:00 |
October | 5888.82 | 02-OCT-14:09 | 2413.46 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2998.67 | 31-OCT-20:05 |
November | 5888.82 | 01-NOV-14:09 | 2413.46 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3482.52 | 29-NOV-21:03 |
December | 5888.82 | 01-DEC-15:09 | 2413.46 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2946.20 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1467.50 | |||||
Maximum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 237.28 | 3482.52 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 23840.77 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2907.11 | 12-JAN-24:00 |
February | 24809.68 | 01-FEB-15:09 | 23840.77 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2624.51 | 16-FEB-04:00 |
March | 24809.68 | 01-MAR-15:09 | 23840.77 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2544.20 | 28-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 23840.77 | 01-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.66 | 01-APR-16:00 | 2778.13 | 07-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 23840.77 | 01-MAY-16:00 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 | 05-MAY-16:00 | 2360.88 | 17-MAY-20:10 |
June | 24809.68 | 01-JUN-14:09 | 21854.04 | 01-JUN-16:19 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.12 | 28-JUN-15:00 | 2724.73 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 23840.77 | 12-JUL-08:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.64 | 30-JUL-18:03 | 1394.50 | 02-JUL-04:00 |
August | 24809.68 | 01-AUG-14:09 | 23840.77 | 08-AUG-16:00 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 174.71 | 13-AUG-18:03 | 1917.06 | 11-AUG-04:00 |
September | 24809.68 | 01-SEP-14:09 | 23840.77 | 07-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | 14-SEP-17:00 | 1327.58 | 18-SEP-23:00 |
October | 24809.68 | 02-OCT-14:09 | 23840.77 | 02-OCT-15:39 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2574.01 | 31-OCT-20:30 |
November | 24809.68 | 01-NOV-14:09 | 23840.77 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2897.58 | 29-NOV-21:10 |
December | 24809.68 | 01-DEC-15:09 | 23840.77 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2433.61 | 22-DEC-21:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 21854.04 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327.58 | |||||
Maximum of Months | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 190.64 | 2907.11 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1430.73 | 12-JAN-24:00 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1274.41 | 16-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1324.34 | 28-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-APR-16:00 | 1376.38 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 05-MAY-16:00 | 1250.35 | 17-MAY-20:05 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 28-JUN-16:00 | 1304.29 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 | 30-JUL-18:03 | 689.18 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.09 | 08-AUG-17:00 | 1015.18 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 14-SEP-17:00 | 670.35 | 18-SEP-23:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1382.35 | 31-OCT-20:05 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1516.95 | 29-NOV-21:03 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1281.57 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.35 | |||||
Maximum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 | 1516.95 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1315.60 | 12-JAN-24:00 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1269.71 | 16-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1239.29 | 28-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-APR-16:00 | 1299.55 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 05-MAY-16:00 | 1144.22 | 17-MAY-20:10 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 28-JUN-16:00 | 1231.12 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 96.84 | 30-JUL-18:03 | 651.98 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.79 | 13-AUG-18:03 | 960.99 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 14-SEP-17:00 | 620.73 | 18-SEP-23:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1225.44 | 31-OCT-20:05 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.71 | 29-NOV-21:03 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1275.77 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.73 | |||||
Maximum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 96.84 | 1505.71 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 26182.29 | 07-JAN-12:10 |
February | 0.00 | 01-FEB-00:10 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 26000.22 | 18-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 18834.56 | 05-MAR-12:10 |
April | 0.00 | 01-APR-00:10 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.57 | 01-APR-16:00 | 16383.30 | 18-APR-17:00 |
May | 0.00 | 01-MAY-00:10 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 14910.84 | 23-MAY-17:00 |
June | 0.00 | 01-JUN-00:10 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 12375.70 | 13-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.72 | 24-JUL-15:00 | 8559.64 | 12-JUL-11:10 |
August | 0.00 | 01-AUG-00:10 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.43 | 10-AUG-17:00 | 8879.80 | 01-AUG-11:10 |
September | 0.00 | 01-SEP-00:10 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 12280.81 | 16-SEP-11:02 |
October | 0.00 | 01-OCT-00:10 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 13850.62 | 29-OCT-11:03 |
November | 0.00 | 01-NOV-00:10 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21402.62 | 12-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 25326.05 | 26-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8559.64 | ||||
Maximum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.43 | 26182.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5150.13 | 06-JAN-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.28 |
February | 5029.53 | 18-FEB-07:05 | 2944.41 | 1072.65 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.96 |
March | 3915.44 | 24-MAR-06:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.04 |
April | 7108.16 | 27-APR-15:00 | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 66.60 | 0.00 |
May | 27667.24 | 07-MAY-08:62 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.78 |
June | 33758.76 | 29-JUN-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.32 |
July | 34945.26 | 19-JUL-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.62 |
August | 33928.45 | 01-AUG-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.31 |
September | 33223.01 | 15-SEP-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.22 |
October | 6137.12 | 04-OCT-15:00 | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.18 |
November | 5218.97 | 04-NOV-14:10 | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 |
December | 4758.31 | 06-DEC-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3915.44 | 2944.41 | 1072.65 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34945.26 | 5888.82 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 66.60 | 653.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35989.31 | 16-JAN-09:05 | 12404.84 | 10595.90 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.71 |
February | 35011.28 | 09-FEB-07:03 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.36 |
March | 70896.24 | 11-MAR-07:03 | 9303.63 | 7946.92 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.49 |
April | 170971.87 | 27-APR-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.72 |
May | 184157.12 | 21-MAY-08:62 | 15506.05 | 8829.92 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.43 |
June | 171265.07 | 02-JUN-06:02 | 15506.05 | 24282.27 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.03 |
July | 174604.64 | 03-JUL-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.63 |
August | 154866.65 | 19-AUG-06:02 | 15506.05 | 13244.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.83 |
September | 171138.78 | 29-SEP-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.95 |
October | 199260.24 | 05-OCT-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.90 |
November | 141229.07 | 05-NOV-08:62 | 12404.84 | 10595.90 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.98 |
December | 37240.42 | 26-DEC-07:05 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35011.28 | 9303.63 | 7946.92 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.95 | |
Maximum of Months | 199260.24 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4500.78 | 20-JAN-13:30 | 2045.54 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.93 |
February | 7080.12 | 27-FEB-15:10 | 4675.52 | 4492.93 | 5841.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 |
March | 7689.53 | 18-MAR-13:50 | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.72 |
April | 26157.60 | 27-APR-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.95 |
May | 25729.19 | 16-MAY-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.69 |
June | 25148.16 | 22-JUN-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.65 |
July | 26531.12 | 06-JUL-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.77 |
August | 24239.53 | 01-AUG-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.50 |
September | 25326.09 | 21-SEP-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.23 |
October | 27502.52 | 05-OCT-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.70 |
November | 19287.70 | 05-NOV-08:62 | 1168.88 | 998.43 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.73 |
December | 6085.73 | 05-DEC-12:30 | 2045.54 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4500.78 | 1168.88 | 998.43 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 | |
Maximum of Months | 27502.52 | 4675.52 | 4492.93 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4029.61 | 07-JAN-07:05 | 1168.88 | 998.43 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.55 |
February | 4551.78 | 27-FEB-15:10 | 4675.52 | 4492.93 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 |
March | 5202.84 | 01-MAR-14:30 | 2045.54 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.64 |
April | 18106.22 | 28-APR-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.36 |
May | 18494.88 | 05-MAY-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
June | 19921.07 | 29-JUN-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.39 |
July | 20180.04 | 08-JUL-06:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 |
August | 20162.50 | 01-AUG-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.83 |
September | 20895.81 | 11-SEP-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.90 |
October | 19367.36 | 05-OCT-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.42 |
November | 7603.71 | 05-NOV-08:62 | 1168.88 | 998.43 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.27 |
December | 3510.86 | 25-DEC-09:05 | 1168.88 | 998.43 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3510.86 | 1168.88 | 998.43 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | |
Maximum of Months | 20895.81 | 4675.52 | 4492.93 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.81 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.35 |
April | 0.00 | 01-APR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.06 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.10 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.06 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.44 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | |
Maximum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.81 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.917960E+11 | 66279.47 | 11-JAN-17:30 | 0.562337E+11 | 139547.67 | 16-JAN-09:09 |
February | 0.815843E+11 | 66298.04 | 28-FEB-17:49 | 0.382324E+11 | 128004.97 | 19-FEB-09:09 |
March | 0.891365E+11 | 66288.05 | 02-MAR-17:00 | 0.197257E+11 | 58845.01 | 05-MAR-09:30 |
April | 0.827036E+11 | 82689.00 | 27-APR-14:00 | 0.133882E+11 | 40965.18 | 18-APR-06:49 |
May | 0.856926E+11 | 81510.46 | 04-MAY-15:50 | 0.112133E+11 | 19490.13 | 23-MAY-16:40 |
June | 0.868668E+11 | 85185.53 | 28-JUN-16:00 | 0.894521E+10 | 16275.38 | 13-JUN-13:00 |
July | 0.959768E+11 | 93385.03 | 31-JUL-16:19 | 0.815048E+10 | 12030.54 | 12-JUL-11:20 |
August | 0.103453E+12 | 96505.67 | 10-AUG-16:40 | 0.805588E+10 | 12573.95 | 01-AUG-11:09 |
September | 0.896814E+11 | 86235.58 | 14-SEP-15:30 | 0.936904E+10 | 15752.44 | 26-SEP-13:00 |
October | 0.890863E+11 | 76252.37 | 04-OCT-14:00 | 0.127563E+11 | 19294.20 | 31-OCT-16:40 |
November | 0.882780E+11 | 75616.14 | 04-NOV-13:00 | 0.259054E+11 | 70707.42 | 24-NOV-07:19 |
December | 0.923628E+11 | 66279.48 | 02-DEC-17:00 | 0.446591E+11 | 134688.68 | 26-DEC-07:10 |
Annual Sum or Average | 0.107662E+13 | 0.256635E+12 | ||||
Minimum of Months | 0.815843E+11 | 66279.47 | 0.805588E+10 | 12030.54 | ||
Maximum of Months | 0.103453E+12 | 96505.67 | 0.562337E+11 | 139547.67 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.356175E+11 | 0.791956E+10 | 0.164409E+11 | 0.00 | 0.318180E+11 | 0.00 | 0.00 | 59806.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313262E+11 | 0.652904E+10 | 0.149157E+11 | 0.00 | 0.287862E+11 | 0.00 | 0.00 | 27177338.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337435E+11 | 0.637299E+10 | 0.168545E+11 | 0.00 | 0.320922E+11 | 0.00 | 0.00 | 73325243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288810E+11 | 0.530850E+10 | 0.160165E+11 | 0.00 | 0.305271E+11 | 0.00 | 0.00 | 0.197054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.290064E+11 | 0.471495E+10 | 0.166477E+11 | 0.00 | 0.311573E+11 | 0.00 | 0.00 | 0.416620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.287334E+11 | 0.414927E+10 | 0.162772E+11 | 0.00 | 0.299110E+11 | 0.00 | 0.00 | 0.779590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.291209E+11 | 0.447809E+10 | 0.163871E+11 | 0.00 | 0.299355E+11 | 0.00 | 0.00 | 0.160553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.310274E+11 | 0.514130E+10 | 0.168545E+11 | 0.00 | 0.302567E+11 | 0.00 | 0.00 | 0.201734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.311035E+11 | 0.579337E+10 | 0.160165E+11 | 0.00 | 0.298304E+11 | 0.00 | 0.00 | 0.693749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.338593E+11 | 0.687458E+10 | 0.164409E+11 | 0.00 | 0.313012E+11 | 0.00 | 0.00 | 0.610251E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.342225E+11 | 0.743190E+10 | 0.159174E+11 | 0.00 | 0.304495E+11 | 0.00 | 0.00 | 0.256632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360298E+11 | 0.812298E+10 | 0.163871E+11 | 0.00 | 0.318229E+11 | 0.00 | 0.00 | 3832.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382671E+12 | 0.728365E+11 | 0.195156E+12 | 0.367888E+12 | 0.00 | 0.580663E+11 | |||||||
Minimum of Months | 0.287334E+11 | 0.414927E+10 | 0.149157E+11 | 0.00 | 0.287862E+11 | 0.00 | 0.00 | 3832.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.360298E+11 | 0.812298E+10 | 0.168545E+11 | 0.00 | 0.320922E+11 | 0.00 | 0.00 | 0.201734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.479797E+11 | 0.00 | 0.825391E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.307457E+11 | 0.00 | 0.748673E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.114132E+11 | 0.00 | 0.831252E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.547740E+10 | 0.00 | 0.791076E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.314624E+10 | 0.00 | 0.806711E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.120456E+10 | 0.00 | 0.774065E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.298999E+09 | 0.00 | 0.785148E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.149403E+09 | 0.00 | 0.790647E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.172293E+10 | 0.00 | 0.764611E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.480290E+10 | 0.00 | 0.795341E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181065E+11 | 0.00 | 0.779888E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.364723E+11 | 0.00 | 0.818680E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.161520E+12 | 0.951148E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.149403E+09 | 0.00 | 0.748673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.479797E+11 | 0.00 | 0.831252E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30883.85 | 02-JAN-09:09 | 4644.36 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 19980.19 | 01-JAN-08:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30883.85 | 01-FEB-09:09 | 4644.36 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 19980.19 | 01-FEB-08:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30883.85 | 01-MAR-09:09 | 4644.36 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 19980.19 | 01-MAR-12:39 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30883.85 | 01-APR-16:00 | 4644.36 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 19980.19 | 01-APR-11:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30883.85 | 01-MAY-16:00 | 4644.36 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 19980.19 | 01-MAY-11:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28897.12 | 01-JUN-16:19 | 4644.36 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 19980.19 | 01-JUN-07:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30883.85 | 12-JUL-08:09 | 4644.36 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 19980.19 | 01-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30883.85 | 08-AUG-16:00 | 4644.36 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 19980.19 | 01-AUG-11:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30883.85 | 07-SEP-08:09 | 4644.36 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 19980.19 | 01-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30883.85 | 02-OCT-15:39 | 4644.36 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 19980.19 | 01-OCT-13:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30883.85 | 01-NOV-08:09 | 4644.36 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 19980.19 | 01-NOV-14:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30883.85 | 01-DEC-09:09 | 4644.36 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 19980.19 | 01-DEC-12:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 28897.12 | 4644.36 | 10771.04 | 0.00 | 19980.19 | 0.00 | 0.00 | |||||
Maximum of Months | 30883.85 | 4644.36 | 10771.04 | 0.00 | 19980.19 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 99.52 | 11-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4173.69 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6897.04 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28787.44 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26026.58 | 06-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28258.03 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35892.01 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37878.27 | 10-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29804.10 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16390.62 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15754.39 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.29 | 05-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37878.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 66279.47 | 11-JAN-17:30 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 19980.19 | 0.00 | 0.00 | 0.03 | 0.00 |
February | 66298.04 | 28-FEB-17:49 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 19980.19 | 0.00 | 0.00 | 18.60 | 0.00 |
March | 66288.05 | 02-MAR-17:00 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 19980.19 | 0.00 | 0.00 | 8.61 | 0.00 |
April | 82689.00 | 27-APR-14:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 28787.44 | 0.00 |
May | 81510.46 | 04-MAY-15:50 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 23635.45 | 0.00 |
June | 85185.53 | 28-JUN-16:00 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 27310.51 | 0.00 |
July | 93385.03 | 31-JUL-16:19 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 33523.28 | 0.00 |
August | 96505.67 | 10-AUG-16:40 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 36643.92 | 0.00 |
September | 86235.58 | 14-SEP-15:30 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 28360.57 | 0.00 |
October | 76252.37 | 04-OCT-14:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 16390.62 | 0.00 |
November | 75616.14 | 04-NOV-13:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 15754.39 | 0.00 |
December | 66279.48 | 02-DEC-17:00 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 19980.19 | 0.00 | 0.00 | 0.04 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 66279.47 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18206.86 | 0.00 | 0.00 | 0.03 | 0.00 | |
Maximum of Months | 96505.67 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 19980.19 | 0.00 | 0.00 | 36643.92 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 137685.67 | 16-JAN-09:09 | 0.00 | 5082.80 | 26-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 126142.97 | 19-FEB-09:09 | 0.00 | 5085.07 | 13-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 56983.01 | 05-MAR-09:30 | 0.00 | 5079.95 | 03-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 36407.49 | 18-APR-06:49 | 0.00 | 5060.50 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 15830.64 | 23-MAY-16:00 | 0.00 | 5035.06 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 11410.21 | 13-JUN-13:00 | 0.00 | 5004.69 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 7174.81 | 09-JUL-12:00 | 0.00 | 4979.85 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 7606.63 | 01-AUG-11:09 | 0.00 | 4970.16 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 10910.62 | 26-SEP-14:30 | 0.00 | 4984.71 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 14452.73 | 31-OCT-16:00 | 0.00 | 5012.57 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 68132.76 | 24-NOV-07:10 | 0.00 | 5044.17 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 132826.68 | 26-DEC-07:10 | 0.00 | 5067.90 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 7174.81 | 0.00 | 4970.16 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 137685.67 | 0.00 | 5085.07 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 19.86 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.19 | 228.00 | 21.11 | 228.00 | 21.11 |
February | 376.00 | 21.59 | 166.83 | 21.11 | 166.83 | 21.11 |
March | 422.00 | 22.38 | 35.17 | 21.12 | 35.17 | 21.12 |
April | 374.50 | 23.11 | 1.33 | 21.11 | 1.33 | 21.11 |
May | 308.50 | 23.60 | 13.33 | 23.89 | 0.00 | 0.00 |
June | 147.17 | 23.78 | 18.00 | 23.89 | 0.00 | 0.00 |
July | 59.00 | 23.87 | 145.00 | 23.89 | 0.00 | 0.00 |
August | 26.50 | 23.82 | 194.00 | 23.89 | 0.00 | 0.00 |
September | 130.83 | 23.72 | 51.67 | 23.89 | 0.00 | 0.00 |
October | 398.17 | 23.36 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 391.67 | 22.13 | 45.00 | 21.12 | 45.00 | 21.12 |
December | 415.00 | 21.27 | 151.50 | 21.12 | 151.50 | 21.12 |
Annual Sum or Average | 3463.33 | 22.44 | 1049.83 | 22.23 | 627.83 | 21.11 |
Minimum of Months | 26.50 | 21.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.87 | 228.00 | 23.89 | 228.00 | 21.12 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.25 | 68.17 | 21.11 | 68.17 | 21.11 |
February | 366.17 | 21.73 | 38.33 | 21.11 | 38.33 | 21.11 |
March | 388.50 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 251.67 | 23.06 | 34.33 | 23.89 | 0.00 | 0.00 |
May | 85.83 | 23.19 | 87.00 | 23.89 | 0.00 | 0.00 |
June | 17.33 | 23.51 | 174.00 | 23.89 | 0.00 | 0.00 |
July | 3.67 | 23.82 | 304.50 | 23.89 | 0.00 | 0.00 |
August | 1.33 | 23.73 | 353.67 | 23.89 | 0.00 | 0.00 |
September | 24.33 | 23.35 | 217.50 | 23.89 | 0.00 | 0.00 |
October | 190.00 | 23.07 | 8.33 | 23.88 | 0.00 | 0.00 |
November | 325.17 | 21.89 | 10.83 | 23.87 | 0.00 | 0.00 |
December | 415.00 | 21.38 | 22.17 | 21.11 | 22.17 | 21.11 |
Annual Sum or Average | 2483.00 | 22.07 | 1318.83 | 23.62 | 128.67 | 21.11 |
Minimum of Months | 1.33 | 21.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.82 | 353.67 | 23.89 | 68.17 | 21.11 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.67 | 21.89 | 95.83 | 21.11 | 95.83 | 21.11 |
February | 323.00 | 22.35 | 42.17 | 21.45 | 37.00 | 21.11 |
March | 307.67 | 23.03 | 13.00 | 23.32 | 2.67 | 21.10 |
April | 183.00 | 23.17 | 52.50 | 23.89 | 0.00 | 0.00 |
May | 92.17 | 23.41 | 111.00 | 23.89 | 0.00 | 0.00 |
June | 30.00 | 23.69 | 184.33 | 23.89 | 0.00 | 0.00 |
July | 9.17 | 23.87 | 305.83 | 23.89 | 0.00 | 0.00 |
August | 5.17 | 23.83 | 365.17 | 23.89 | 0.00 | 0.00 |
September | 25.17 | 23.62 | 272.50 | 23.89 | 0.00 | 0.00 |
October | 132.67 | 23.33 | 91.83 | 23.89 | 0.00 | 0.00 |
November | 307.67 | 22.69 | 31.17 | 23.13 | 8.50 | 21.11 |
December | 395.17 | 22.11 | 59.50 | 21.11 | 59.50 | 21.11 |
Annual Sum or Average | 2223.50 | 22.58 | 1624.83 | 23.54 | 203.50 | 21.11 |
Minimum of Months | 5.17 | 21.89 | 13.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 412.67 | 23.87 | 365.17 | 23.89 | 95.83 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.21 | 166.00 | 21.11 | 166.00 | 21.11 |
February | 358.33 | 21.63 | 88.67 | 21.11 | 88.67 | 21.11 |
March | 373.83 | 22.21 | 21.33 | 21.11 | 21.33 | 21.11 |
April | 282.50 | 22.64 | 35.67 | 23.60 | 3.67 | 21.11 |
May | 171.00 | 22.89 | 60.83 | 23.89 | 0.00 | 0.00 |
June | 80.83 | 23.29 | 98.50 | 23.89 | 0.00 | 0.00 |
July | 34.33 | 23.60 | 249.83 | 23.89 | 0.00 | 0.00 |
August | 23.50 | 23.38 | 311.17 | 23.89 | 0.00 | 0.00 |
September | 66.83 | 23.09 | 208.33 | 23.89 | 0.00 | 0.00 |
October | 232.00 | 22.67 | 56.00 | 23.89 | 0.00 | 0.00 |
November | 365.33 | 21.76 | 45.50 | 21.85 | 33.33 | 21.11 |
December | 410.67 | 21.38 | 119.83 | 21.11 | 119.83 | 21.11 |
Annual Sum or Average | 2813.17 | 22.01 | 1461.67 | 23.07 | 432.83 | 21.11 |
Minimum of Months | 23.50 | 21.21 | 21.33 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 414.00 | 23.60 | 311.17 | 23.89 | 166.00 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.17742 | 36.03550 | -0.5344 | 11.25352 |
February | 376.00000 | 21.57733 | 36.97627 | -0.4174 | 9.95406 |
March | 422.00000 | 22.36800 | 37.12613 | -0.1911 | 6.98079 |
April | 405.00000 | 23.15705 | 38.69508 | 0.03906 | 6.15663 |
May | 418.00000 | 23.67060 | 40.62539 | -0.7344 | 17.11592 |
June | 408.00000 | 23.85327 | 41.24860 | -0.6104 | 13.03616 |
July | 415.00000 | 23.89633 | 45.33889 | -0.5253 | 10.93863 |
August | 422.00000 | 23.89648 | 48.68214 | -0.4998 | 10.36482 |
September | 405.00000 | 23.83759 | 47.43967 | -0.5967 | 12.75951 |
October | 414.00000 | 23.37287 | 41.70657 | 0.12055 | 5.97349 |
November | 399.00000 | 22.15126 | 42.56326 | -0.2053 | 7.81039 |
December | 415.00000 | 21.25400 | 38.19080 | -0.4867 | 10.22848 |
Annual Sum or Average | 4913.00000 | 22.86088 | 41.24616 | -0.3875 | 10.22379 |
Minimum of Months | 376.00000 | 21.17742 | 36.03550 | -0.7344 | 5.97349 |
Maximum of Months | 422.00000 | 23.89648 | 48.68214 | 0.12055 | 17.11592 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.25605 | 33.12551 | -0.4202 | 9.04094 |
February | 376.00000 | 21.79305 | 33.67754 | -0.2695 | 7.95911 |
March | 422.00000 | 22.70084 | 33.29441 | -0.0173 | 6.10939 |
April | 405.00000 | 23.38755 | 35.89732 | 0.19232 | 6.57053 |
May | 418.00000 | 23.75729 | 39.17713 | -0.5613 | 12.14137 |
June | 408.00000 | 23.89066 | 40.45959 | -0.4661 | 9.70897 |
July | 415.00000 | 23.90901 | 44.70456 | -0.4000 | 8.52172 |
August | 422.00000 | 23.90746 | 48.04273 | -0.3840 | 8.23568 |
September | 405.00000 | 23.86792 | 46.23441 | -0.4672 | 9.83622 |
October | 414.00000 | 23.52523 | 39.21636 | 0.24417 | 6.72838 |
November | 399.00000 | 22.26804 | 39.64799 | -0.0880 | 7.08717 |
December | 415.00000 | 21.38835 | 34.99319 | -0.3626 | 8.12319 |
Annual Sum or Average | 4913.00000 | 22.98027 | 39.07543 | -0.2506 | 8.34342 |
Minimum of Months | 376.00000 | 21.25605 | 33.12551 | -0.5613 | 6.10939 |
Maximum of Months | 422.00000 | 23.90901 | 48.04273 | 0.24417 | 12.14137 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.88747 | 31.60403 | -0.3165 | 8.40783 |
February | 376.00000 | 22.56068 | 31.43440 | -0.1082 | 7.60100 |
March | 422.00000 | 23.25376 | 30.77363 | 0.09946 | 6.64318 |
April | 405.00000 | 23.56500 | 33.92624 | 0.23887 | 7.22835 |
May | 418.00000 | 23.78982 | 37.87236 | -0.5499 | 12.09605 |
June | 408.00000 | 23.88672 | 39.59753 | -0.4669 | 9.82599 |
July | 415.00000 | 23.90709 | 43.90244 | -0.3801 | 8.29269 |
August | 422.00000 | 23.90732 | 46.94268 | -0.3303 | 7.59984 |
September | 405.00000 | 23.88657 | 44.86089 | -0.3928 | 8.81408 |
October | 414.00000 | 23.71568 | 37.13543 | 0.31565 | 7.67608 |
November | 399.00000 | 22.96532 | 37.32857 | 0.03971 | 6.95231 |
December | 415.00000 | 22.19101 | 32.99721 | -0.2183 | 7.70772 |
Annual Sum or Average | 4913.00000 | 23.29863 | 37.40615 | -0.1737 | 8.24420 |
Minimum of Months | 376.00000 | 21.88747 | 30.77363 | -0.5499 | 6.64318 |
Maximum of Months | 422.00000 | 23.90732 | 46.94268 | 0.31565 | 12.09605 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.19553 | 32.73625 | -0.4946 | 10.56257 |
February | 376.00000 | 21.72456 | 33.45469 | -0.3124 | 8.85093 |
March | 422.00000 | 22.39768 | 33.28702 | -0.1049 | 6.99761 |
April | 405.00000 | 23.01000 | 36.05708 | 0.09252 | 6.90280 |
May | 418.00000 | 23.47670 | 39.50214 | -0.6933 | 16.79490 |
June | 408.00000 | 23.77438 | 40.51714 | -0.5554 | 12.03991 |
July | 415.00000 | 23.87412 | 44.57696 | -0.4463 | 9.52330 |
August | 422.00000 | 23.87383 | 47.66208 | -0.3941 | 8.68407 |
September | 405.00000 | 23.76029 | 46.03566 | -0.4834 | 10.93903 |
October | 414.00000 | 23.20604 | 39.31137 | 0.18013 | 6.96781 |
November | 399.00000 | 21.93481 | 39.84927 | -0.2018 | 7.85250 |
December | 415.00000 | 21.39888 | 34.50163 | -0.4157 | 9.59193 |
Annual Sum or Average | 4913.00000 | 22.81146 | 38.99351 | -0.3198 | 9.65350 |
Minimum of Months | 376.00000 | 21.19553 | 32.73625 | -0.6933 | 6.90280 |
Maximum of Months | 422.00000 | 23.87412 | 47.66208 | 0.18013 | 16.79490 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 168471.50 | 47673.76 | 6.97 | 129866.28 | 38605.23 | 0.00 | 0.00 | 25-FEB-15:30 | 0.00 | 01-FEB-00:10 | 104.28 | 25-FEB-15:30 | 75.85 | 25-FEB-15:30 | 28.43 | 25-FEB-15:30 | 29.46 | 25-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 371392.32 | 105254.15 | 16.67 | 314081.70 | 57310.62 | 0.00 | 0.01 | 11-MAR-15:20 | 0.00 | 01-MAR-00:10 | 125.19 | 11-MAR-15:20 | 98.53 | 11-MAR-15:20 | 26.65 | 11-MAR-15:20 | 35.46 | 11-MAR-15:20 | 0.00 | 01-MAR-00:10 |
April | 0.561156E+09 | 0.156061E+09 | 99.25 | 0.524284E+09 | 36871866.32 | 0.00 | 0.45 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 11128.64 | 27-APR-15:00 | 9919.61 | 27-APR-15:00 | 1212.88 | 27-APR-15:30 | 3073.75 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.130587E+10 | 0.350085E+09 | 187.96 | 0.115032E+10 | 0.155549E+09 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 29351.86 | 07-MAY-08:62 | 20677.36 | 07-MAY-08:62 | 8674.50 | 07-MAY-08:62 | 6250.11 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.268889E+10 | 0.719897E+09 | 250.57 | 0.249167E+10 | 0.197223E+09 | 0.00 | 1.00 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 | 28912.58 | 12-JUN-06:02 | 21865.18 | 28-JUN-06:02 | 10357.01 | 12-JUN-06:02 | 6155.79 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.641038E+10 | 0.170239E+10 | 308.64 | 0.543381E+10 | 0.976567E+09 | 0.00 | 1.00 | 08-JUL-06:02 | 0.00 | 01-JUL-00:10 | 29551.93 | 31-JUL-06:02 | 23259.28 | 23-JUL-08:62 | 10852.37 | 25-JUL-06:02 | 6290.78 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.826524E+10 | 0.221129E+10 | 320.66 | 0.694508E+10 | 0.132016E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 29863.18 | 25-AUG-06:02 | 23499.81 | 13-AUG-08:62 | 11751.51 | 26-AUG-06:02 | 6351.11 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.223608E+10 | 0.589248E+09 | 216.27 | 0.181128E+10 | 0.424801E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 28997.74 | 01-SEP-06:02 | 18868.48 | 01-SEP-06:02 | 10916.96 | 15-SEP-06:02 | 6174.60 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 63103705.53 | 17183078.93 | 108.29 | 63052921.10 | 50784.43 | 0.00 | 0.22 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4801.09 | 04-OCT-15:00 | 4801.09 | 04-OCT-15:00 | 20.50 | 17-OCT-16:00 | 1295.35 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 40930225.44 | 11188870.02 | 21.87 | 30546668.87 | 10383556.57 | 0.00 | 0.17 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 | 3969.68 | 04-NOV-14:10 | 3014.33 | 04-NOV-14:10 | 959.00 | 04-NOV-14:00 | 1077.57 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.215722E+11 | 0.575750E+10 | 1537.14 | 0.184505E+11 | 0.312170E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.826524E+10 | 0.221129E+10 | 320.66 | 0.694508E+10 | 0.132016E+10 | 0.00 | 1.00 | 0.00 | 29863.18 | 23499.81 | 11751.51 | 6351.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 188351.36 | 59709.00 | 0.17 | 170783.34 | 17568.02 | 0.00 | 0.00 | 11-JAN-16:00 | 0.00 | 01-JAN-00:10 | 313.92 | 11-JAN-16:00 | 284.64 | 11-JAN-16:00 | 29.28 | 11-JAN-16:00 | 99.52 | 11-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 40224704.51 | 12543540.11 | 16.94 | 39627600.22 | 597104.29 | 0.00 | 0.08 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 7974.07 | 27-FEB-15:10 | 7974.07 | 27-FEB-15:10 | 161.37 | 27-FEB-16:00 | 2471.40 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.162733E+09 | 49698707.84 | 48.07 | 0.162353E+09 | 379087.13 | 0.00 | 0.17 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 17181.97 | 18-MAR-16:00 | 17181.97 | 18-MAR-16:00 | 136.03 | 10-MAR-18:50 | 5187.52 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.471694E+10 | 0.141540E+10 | 133.35 | 0.444421E+10 | 0.272730E+09 | 0.00 | 1.00 | 27-APR-06:02 | 0.00 | 01-APR-00:10 | 130600.20 | 30-APR-08:62 | 107652.43 | 27-APR-06:02 | 45030.00 | 30-APR-08:62 | 31029.63 | 30-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.108343E+11 | 0.315844E+10 | 215.55 | 0.953530E+10 | 0.129901E+10 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 135824.15 | 07-MAY-08:62 | 116184.40 | 14-MAY-08:62 | 43591.94 | 08-MAY-06:02 | 32311.30 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.202502E+11 | 0.593789E+10 | 287.79 | 0.187374E+11 | 0.151276E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 133525.36 | 12-JUN-06:02 | 112656.65 | 25-JUN-08:62 | 44892.35 | 06-JUN-06:02 | 31775.52 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.407197E+11 | 0.118388E+11 | 343.19 | 0.348449E+11 | 0.587480E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 136365.80 | 31-JUL-06:02 | 113677.14 | 02-JUL-08:62 | 47513.87 | 16-JUL-08:62 | 32430.75 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.494938E+11 | 0.144901E+11 | 349.46 | 0.419915E+11 | 0.750234E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 137700.31 | 30-AUG-06:02 | 108920.98 | 13-AUG-08:62 | 51537.96 | 26-AUG-06:02 | 32713.55 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.167118E+11 | 0.482607E+10 | 249.34 | 0.135691E+11 | 0.314272E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 134367.23 | 25-SEP-06:02 | 104146.59 | 04-SEP-08:62 | 55191.99 | 25-SEP-06:02 | 31977.06 | 25-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.129357E+10 | 0.376562E+09 | 136.14 | 0.121243E+10 | 81139398.82 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 134670.32 | 01-OCT-08:62 | 115338.74 | 05-OCT-06:02 | 43571.10 | 01-OCT-08:62 | 32048.13 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.602178E+09 | 0.175687E+09 | 28.23 | 0.447863E+09 | 0.154315E+09 | 0.00 | 1.00 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 | 131735.73 | 05-NOV-08:62 | 85656.49 | 04-NOV-06:03 | 46354.96 | 05-NOV-08:62 | 31327.38 | 05-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.144826E+12 | 0.422812E+11 | 1808.22 | 0.124985E+12 | 0.198408E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.494938E+11 | 0.144901E+11 | 349.46 | 0.419915E+11 | 0.750234E+10 | 0.00 | 1.00 | 0.00 | 137700.31 | 116184.40 | 55191.99 | 32713.55 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 342.00 | 97.03 | 2.00 | 328.11 | 13.89 | 0.00 | 0.00 | 11-JAN-17:30 | 0.00 | 01-JAN-00:10 | 0.10 | 11-JAN-17:30 | 0.09 | 11-JAN-17:30 | 0.00 | 11-JAN-17:30 | 0.03 | 11-JAN-17:30 | 0.00 | 01-JAN-00:10 |
February | 41069893.99 | 11062888.55 | 55.41 | 40859389.18 | 210504.81 | 0.00 | 0.27 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 4256.34 | 27-FEB-15:00 | 4256.34 | 27-FEB-15:00 | 38.21 | 27-FEB-16:20 | 1123.14 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 61528001.87 | 16332800.28 | 120.89 | 61330698.15 | 197303.72 | 0.00 | 0.31 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4929.64 | 18-MAR-14:00 | 4929.64 | 18-MAR-14:00 | 55.14 | 18-MAR-12:40 | 1284.61 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.930100E+09 | 0.245772E+09 | 174.89 | 0.887217E+09 | 42882306.94 | 0.00 | 1.00 | 28-APR-06:02 | 0.00 | 01-APR-00:10 | 20147.17 | 30-APR-08:62 | 15375.42 | 27-APR-06:02 | 7195.59 | 30-APR-08:62 | 4281.43 | 30-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.158173E+10 | 0.413201E+09 | 215.57 | 0.141723E+10 | 0.164504E+09 | 0.00 | 1.00 | 05-MAY-06:02 | 0.00 | 01-MAY-00:10 | 20915.56 | 07-MAY-08:62 | 15612.88 | 05-MAY-06:02 | 5760.12 | 07-MAY-08:62 | 4453.47 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.271976E+10 | 0.716922E+09 | 275.58 | 0.256692E+10 | 0.152838E+09 | 0.00 | 1.00 | 10-JUN-06:02 | 0.00 | 01-JUN-00:10 | 20619.89 | 12-JUN-06:02 | 17482.16 | 25-JUN-08:62 | 7091.98 | 12-JUN-06:02 | 4390.61 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.581847E+10 | 0.152141E+10 | 327.88 | 0.507278E+10 | 0.745686E+09 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 21048.54 | 31-JUL-06:02 | 16841.01 | 23-JUL-08:62 | 7524.46 | 25-JUL-06:02 | 4480.30 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.785181E+10 | 0.204890E+10 | 342.99 | 0.683751E+10 | 0.101430E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 21253.22 | 25-AUG-06:02 | 16883.47 | 13-AUG-08:62 | 8222.50 | 26-AUG-06:02 | 4519.79 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.360663E+10 | 0.907737E+09 | 264.40 | 0.298260E+10 | 0.624035E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 20671.14 | 01-SEP-06:02 | 16298.39 | 04-SEP-08:62 | 8628.74 | 25-SEP-06:02 | 4401.81 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.528581E+09 | 0.137086E+09 | 189.13 | 0.502926E+09 | 25655241.24 | 0.00 | 0.96 | 06-OCT-06:02 | 0.00 | 01-OCT-00:10 | 18570.58 | 06-OCT-06:02 | 15336.09 | 04-OCT-06:02 | 5718.88 | 06-OCT-06:02 | 3990.58 | 06-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.170849E+09 | 43016781.65 | 65.10 | 0.129499E+09 | 41349282.09 | 0.00 | 0.78 | 05-NOV-08:62 | 0.00 | 01-NOV-00:10 | 14683.86 | 05-NOV-08:62 | 9500.23 | 05-NOV-08:62 | 5183.63 | 05-NOV-08:62 | 3354.29 | 05-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 10607.40 | 2995.37 | 19.62 | 10585.07 | 22.34 | 0.00 | 0.00 | 02-DEC-12:30 | 0.00 | 01-DEC-00:10 | 0.52 | 02-DEC-12:30 | 0.52 | 02-DEC-12:30 | 0.01 | 10-DEC-14:00 | 0.15 | 02-DEC-12:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.233105E+11 | 0.606145E+10 | 2053.47 | 0.204989E+11 | 0.281166E+10 | 0.00 | ||||||||||||||
Minimum of Months | 342.00 | 97.03 | 2.00 | 328.11 | 13.89 | 0.00 | 0.00 | 0.00 | 0.10 | 0.09 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.785181E+10 | 0.204890E+10 | 342.99 | 0.683751E+10 | 0.101430E+10 | 0.00 | 1.00 | 0.00 | 21253.22 | 17482.16 | 8628.74 | 4519.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 13254565.53 | 3523235.73 | 13.65 | 13198648.54 | 55916.98 | 0.00 | 0.17 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 2225.67 | 27-FEB-15:10 | 2225.67 | 27-FEB-15:10 | 25.41 | 27-FEB-16:00 | 584.98 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 27393294.19 | 7188480.95 | 44.85 | 27388644.64 | 4649.56 | 0.00 | 0.22 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2829.71 | 18-MAR-14:00 | 2829.71 | 18-MAR-14:00 | 5.87 | 18-MAR-13:10 | 733.72 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.588852E+09 | 0.153304E+09 | 113.04 | 0.558977E+09 | 29874531.04 | 0.00 | 0.79 | 28-APR-06:02 | 0.00 | 01-APR-00:10 | 12095.82 | 28-APR-06:02 | 8851.81 | 27-APR-13:30 | 3683.16 | 30-APR-08:62 | 2663.60 | 28-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.949384E+09 | 0.244472E+09 | 171.18 | 0.849477E+09 | 99906347.08 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 17431.23 | 07-MAY-08:62 | 12439.88 | 07-MAY-08:62 | 4991.35 | 07-MAY-08:62 | 3604.68 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.162106E+10 | 0.421195E+09 | 240.38 | 0.152464E+10 | 96420780.51 | 0.00 | 1.00 | 21-JUN-06:02 | 0.00 | 01-JUN-00:10 | 16786.17 | 21-JUN-06:02 | 11660.26 | 29-JUN-06:02 | 5785.67 | 12-JUN-06:02 | 3463.90 | 21-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.385587E+10 | 0.992707E+09 | 298.82 | 0.333596E+10 | 0.519916E+09 | 0.00 | 1.00 | 08-JUL-06:02 | 0.00 | 01-JUL-00:10 | 17550.64 | 31-JUL-06:02 | 13924.72 | 23-JUL-08:62 | 6364.50 | 15-JUL-06:02 | 3628.13 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.555996E+10 | 0.142312E+10 | 318.59 | 0.481102E+10 | 0.748942E+09 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 17724.23 | 25-AUG-06:02 | 14025.02 | 13-AUG-08:62 | 6906.54 | 26-AUG-06:02 | 3660.69 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.250105E+10 | 0.614440E+09 | 224.75 | 0.205373E+10 | 0.447317E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 17221.94 | 24-SEP-08:62 | 12004.66 | 10-SEP-08:62 | 7218.31 | 24-SEP-08:62 | 3561.54 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.314641E+09 | 79419717.35 | 118.06 | 0.303091E+09 | 11550398.00 | 0.00 | 0.58 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 | 8340.39 | 05-OCT-06:02 | 7790.13 | 04-OCT-14:30 | 837.96 | 04-OCT-06:02 | 1956.12 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.107615E+09 | 26739236.99 | 16.75 | 81124691.35 | 26490647.53 | 0.00 | 0.48 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 7237.75 | 04-NOV-14:00 | 5632.45 | 04-NOV-14:00 | 1675.11 | 04-NOV-13:30 | 1754.34 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 3051.92 | 836.68 | 4.60 | 3051.92 | 0.00 | 0.00 | 0.00 | 05-DEC-15:50 | 0.00 | 01-DEC-00:10 | 1.06 | 05-DEC-15:50 | 1.06 | 05-DEC-15:50 | 0.00 | 01-DEC-00:10 | 0.29 | 05-DEC-15:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.155391E+11 | 0.396611E+10 | 1564.68 | 0.135586E+11 | 0.198048E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.555996E+10 | 0.142312E+10 | 318.59 | 0.481102E+10 | 0.748942E+09 | 0.00 | 1.00 | 0.00 | 17724.23 | 14025.02 | 7218.31 | 3660.69 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.81 | 69.62 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 30.68 | 62.96 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 62.10 | 54.66 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 116.50 | 45.04 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 160.25 | 38.49 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 178.73 | 31.53 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.54 | 29.61 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.32 | 30.38 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.47 | 40.69 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 48.43 | 53.32 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.12 | 59.46 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.01 | 72.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.26 | 48.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.01 | 29.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.54 | 72.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 594.01 | 824.86 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 1008.96 | 759.30 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1066.69 | 686.58 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1065.65 | 569.63 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 884.33 | 478.38 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 775.49 | 380.57 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 938.70 | 347.59 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1160.21 | 344.45 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1333.95 | 477.12 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1211.25 | 632.56 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 628.16 | 728.87 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 699.52 | 854.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 946.70 | 589.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 594.01 | 344.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1333.95 | 854.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 600.22 | 792.49 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 1018.49 | 721.24 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1076.25 | 647.33 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1073.44 | 541.20 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 888.60 | 457.99 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 775.10 | 365.21 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 936.26 | 333.11 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1156.63 | 331.01 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1332.49 | 460.92 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1215.69 | 604.51 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 637.89 | 683.13 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 705.71 | 815.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 950.81 | 562.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 600.22 | 331.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1332.49 | 815.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.22 | 86.81 | 59.41 | 120.45 | 163.57 | 0.00 | 0.00 | 744.00 |
February | 224.95 | 139.25 | 85.70 | 206.20 | 146.85 | 0.00 | 0.00 | 672.00 |
March | 242.06 | 129.14 | 112.93 | 220.18 | 129.57 | 0.00 | 0.00 | 744.00 |
April | 255.49 | 110.95 | 144.55 | 220.92 | 107.44 | 0.00 | 0.00 | 720.00 |
May | 233.56 | 69.56 | 164.01 | 184.98 | 89.42 | 0.00 | 0.00 | 744.00 |
June | 213.69 | 57.35 | 156.34 | 163.02 | 70.90 | 0.00 | 0.00 | 720.00 |
July | 233.03 | 85.32 | 147.71 | 193.78 | 65.85 | 0.00 | 0.00 | 744.00 |
August | 250.38 | 116.75 | 133.64 | 234.69 | 67.47 | 0.00 | 0.00 | 744.00 |
September | 277.52 | 153.30 | 124.23 | 275.32 | 90.27 | 0.00 | 0.00 | 720.00 |
October | 251.38 | 155.23 | 96.14 | 250.20 | 118.12 | 0.00 | 0.00 | 744.00 |
November | 148.55 | 85.12 | 63.43 | 129.36 | 138.35 | 0.00 | 0.00 | 720.00 |
December | 155.41 | 100.55 | 54.86 | 142.81 | 167.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 219.26 | 107.24 | 112.01 | 195.05 | 112.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 146.22 | 57.35 | 54.86 | 120.45 | 65.85 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 277.52 | 155.23 | 164.01 | 275.32 | 167.60 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23600353.21 | 0.186460E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 74212212.66 | 0.152323E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.166326E+09 | 0.146407E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.301966E+09 | 0.116739E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.429215E+09 | 0.103082E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.463271E+09 | 81719049.62 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521056E+09 | 79294765.56 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416004E+09 | 81379562.82 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.262998E+09 | 0.105470E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.129705E+09 | 0.142817E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 39201959.25 | 0.154111E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 0.194520E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.284633E+10 | 0.154432E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 18774401.16 | 79294765.56 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521056E+09 | 0.194520E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.159100E+10 | 0.220931E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.244087E+10 | 0.183689E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.285703E+10 | 0.183892E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.276217E+10 | 0.147648E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.236859E+10 | 0.128129E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.201008E+10 | 0.986439E+09 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.251421E+10 | 0.930976E+09 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.310750E+10 | 0.922588E+09 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.345759E+10 | 0.123670E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.324422E+10 | 0.169425E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.162819E+10 | 0.188923E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.187361E+10 | 0.228867E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.298551E+11 | 0.185917E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.159100E+10 | 0.922588E+09 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.345759E+10 | 0.228867E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.160763E+10 | 0.212260E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.246393E+10 | 0.174483E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.288261E+10 | 0.173381E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.278235E+10 | 0.140280E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.238001E+10 | 0.122669E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.200906E+10 | 0.946630E+09 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.250769E+10 | 0.892208E+09 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.309791E+10 | 0.886573E+09 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.345382E+10 | 0.119470E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.325609E+10 | 0.161912E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.165341E+10 | 0.177069E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.189017E+10 | 0.218445E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.299847E+11 | 0.177251E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.160763E+10 | 0.886573E+09 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.345382E+10 | 0.218445E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.322623E+09 | 0.438093E+09 |
February | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.498847E+09 | 0.355263E+09 |
March | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.589719E+09 | 0.347033E+09 |
April | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.572620E+09 | 0.278472E+09 |
May | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.495438E+09 | 0.239514E+09 |
June | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.422545E+09 | 0.183779E+09 |
July | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.519008E+09 | 0.176382E+09 |
August | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.628605E+09 | 0.180722E+09 |
September | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.713623E+09 | 0.233975E+09 |
October | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.670124E+09 | 0.316385E+09 |
November | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.335300E+09 | 0.358616E+09 |
December | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.382507E+09 | 0.448910E+09 |
Annual Sum or Average | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.615096E+10 | 0.355714E+10 |
Minimum of Months | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.322623E+09 | 0.176382E+09 |
Maximum of Months | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.713623E+09 | 0.448910E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 140.98 | 1113.86 | 373.27 | 86.35 | 286.92 | 0.00 | 0.00 |
February | 490.82 | 1007.43 | 685.68 | 259.72 | 425.95 | 0.00 | 0.00 |
March | 993.59 | 874.59 | 1108.16 | 470.70 | 637.46 | 0.00 | 0.00 |
April | 1863.98 | 720.61 | 1776.99 | 904.23 | 872.76 | 0.00 | 0.00 |
May | 2564.01 | 615.78 | 2295.61 | 1177.15 | 1118.46 | 0.00 | 0.00 |
June | 2859.70 | 504.44 | 2500.32 | 1454.40 | 1045.92 | 0.00 | 0.00 |
July | 3112.64 | 473.68 | 2612.91 | 1715.65 | 897.26 | 0.00 | 0.00 |
August | 2485.09 | 486.14 | 2091.89 | 1321.60 | 770.29 | 0.00 | 0.00 |
September | 1623.44 | 651.05 | 1485.92 | 823.94 | 661.98 | 0.00 | 0.00 |
October | 774.82 | 853.15 | 866.06 | 397.52 | 468.54 | 0.00 | 0.00 |
November | 241.99 | 951.30 | 438.01 | 114.54 | 323.47 | 0.00 | 0.00 |
December | 112.15 | 1162.01 | 315.18 | 81.42 | 233.76 | 0.00 | 0.00 |
Annual Sum or Average | 1444.10 | 783.52 | 1382.99 | 736.84 | 646.15 | 0.00 | 0.00 |
Minimum of Months | 112.15 | 473.68 | 315.18 | 81.42 | 233.76 | 0.00 | 0.00 |
Maximum of Months | 3112.64 | 1162.01 | 2612.91 | 1715.65 | 1118.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 594.01 | 824.86 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 1008.96 | 759.30 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1066.69 | 686.58 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1065.65 | 569.63 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 884.33 | 478.38 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 775.49 | 380.57 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 938.70 | 347.59 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1160.21 | 344.45 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1333.95 | 477.12 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1211.25 | 632.56 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 628.16 | 728.87 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 699.52 | 854.49 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 946.70 | 589.54 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 594.01 | 344.45 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1333.95 | 854.49 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 600.22 | 792.49 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 1018.49 | 721.24 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1076.25 | 647.33 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1073.44 | 541.20 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 888.60 | 457.99 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 775.10 | 365.21 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 936.26 | 333.11 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1156.63 | 331.01 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1332.49 | 460.92 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1215.69 | 604.51 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 637.89 | 683.13 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 705.71 | 815.58 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 950.81 | 562.06 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 600.22 | 331.01 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1332.49 | 815.58 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 120.45 | 163.57 | 146.22 | 86.81 | 59.41 | 0.00 | 0.00 |
February | 206.20 | 146.85 | 224.95 | 139.25 | 85.70 | 0.00 | 0.00 |
March | 220.18 | 129.57 | 242.06 | 129.14 | 112.93 | 0.00 | 0.00 |
April | 220.92 | 107.44 | 255.49 | 110.95 | 144.55 | 0.00 | 0.00 |
May | 184.98 | 89.42 | 233.56 | 69.56 | 164.01 | 0.00 | 0.00 |
June | 163.02 | 70.90 | 213.69 | 57.35 | 156.34 | 0.00 | 0.00 |
July | 193.78 | 65.85 | 233.03 | 85.32 | 147.71 | 0.00 | 0.00 |
August | 234.69 | 67.47 | 250.38 | 116.75 | 133.64 | 0.00 | 0.00 |
September | 275.32 | 90.27 | 277.52 | 153.30 | 124.23 | 0.00 | 0.00 |
October | 250.20 | 118.12 | 251.38 | 155.23 | 96.14 | 0.00 | 0.00 |
November | 129.36 | 138.35 | 148.55 | 85.12 | 63.43 | 0.00 | 0.00 |
December | 142.81 | 167.60 | 155.41 | 100.55 | 54.86 | 0.00 | 0.00 |
Annual Sum or Average | 195.05 | 112.80 | 219.26 | 107.24 | 112.01 | 0.00 | 0.00 |
Minimum of Months | 120.45 | 65.85 | 146.22 | 57.35 | 54.86 | 0.00 | 0.00 |
Maximum of Months | 275.32 | 167.60 | 277.52 | 155.23 | 164.01 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.377606E+09 | 0.298337E+10 | 0.999755E+09 | 0.231279E+09 | 0.768477E+09 | 0.00 | 0.00 |
February | 0.118740E+10 | 0.243717E+10 | 0.165879E+10 | 0.628323E+09 | 0.103046E+10 | 0.00 | 0.00 |
March | 0.266122E+10 | 0.234250E+10 | 0.296808E+10 | 0.126071E+10 | 0.170737E+10 | 0.00 | 0.00 |
April | 0.483145E+10 | 0.186782E+10 | 0.460597E+10 | 0.234377E+10 | 0.226220E+10 | 0.00 | 0.00 |
May | 0.686744E+10 | 0.164932E+10 | 0.614856E+10 | 0.315289E+10 | 0.299567E+10 | 0.00 | 0.00 |
June | 0.741234E+10 | 0.130750E+10 | 0.648083E+10 | 0.376980E+10 | 0.271104E+10 | 0.00 | 0.00 |
July | 0.833690E+10 | 0.126872E+10 | 0.699841E+10 | 0.459520E+10 | 0.240321E+10 | 0.00 | 0.00 |
August | 0.665606E+10 | 0.130207E+10 | 0.560292E+10 | 0.353978E+10 | 0.206315E+10 | 0.00 | 0.00 |
September | 0.420797E+10 | 0.168753E+10 | 0.385150E+10 | 0.213565E+10 | 0.171585E+10 | 0.00 | 0.00 |
October | 0.207528E+10 | 0.228507E+10 | 0.231966E+10 | 0.106472E+10 | 0.125494E+10 | 0.00 | 0.00 |
November | 0.627231E+09 | 0.246577E+10 | 0.113532E+10 | 0.296899E+09 | 0.838424E+09 | 0.00 | 0.00 |
December | 0.300390E+09 | 0.311232E+10 | 0.844175E+09 | 0.218065E+09 | 0.626110E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.455413E+11 | 0.247092E+11 | 0.436140E+11 | 0.232371E+11 | 0.203769E+11 | 0.00 | 0.00 |
Minimum of Months | 0.300390E+09 | 0.126872E+10 | 0.844175E+09 | 0.218065E+09 | 0.626110E+09 | 0.00 | 0.00 |
Maximum of Months | 0.833690E+10 | 0.311232E+10 | 0.699841E+10 | 0.459520E+10 | 0.299567E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159100E+10 | 0.220931E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.244087E+10 | 0.183689E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.285703E+10 | 0.183892E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.276217E+10 | 0.147648E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.236859E+10 | 0.128129E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.201008E+10 | 0.986439E+09 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.251421E+10 | 0.930976E+09 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.310750E+10 | 0.922588E+09 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.345759E+10 | 0.123670E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.324422E+10 | 0.169425E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.162819E+10 | 0.188923E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.187361E+10 | 0.228867E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.298551E+11 | 0.185917E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.159100E+10 | 0.922588E+09 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.345759E+10 | 0.228867E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160763E+10 | 0.212260E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.246393E+10 | 0.174483E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.288261E+10 | 0.173381E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.278235E+10 | 0.140280E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.238001E+10 | 0.122669E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.200906E+10 | 0.946630E+09 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.250769E+10 | 0.892208E+09 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.309791E+10 | 0.886573E+09 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.345382E+10 | 0.119470E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.325609E+10 | 0.161912E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.165341E+10 | 0.177069E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.189017E+10 | 0.218445E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299847E+11 | 0.177251E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160763E+10 | 0.886573E+09 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.345382E+10 | 0.218445E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.322623E+09 | 0.438093E+09 | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.00 | 0.00 |
February | 0.498847E+09 | 0.355263E+09 | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.00 | 0.00 |
March | 0.589719E+09 | 0.347033E+09 | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.00 | 0.00 |
April | 0.572620E+09 | 0.278472E+09 | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.00 | 0.00 |
May | 0.495438E+09 | 0.239514E+09 | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.00 | 0.00 |
June | 0.422545E+09 | 0.183779E+09 | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.00 | 0.00 |
July | 0.519008E+09 | 0.176382E+09 | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.00 | 0.00 |
August | 0.628605E+09 | 0.180722E+09 | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.00 | 0.00 |
September | 0.713623E+09 | 0.233975E+09 | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.00 | 0.00 |
October | 0.670124E+09 | 0.316385E+09 | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.00 | 0.00 |
November | 0.335300E+09 | 0.358616E+09 | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.00 | 0.00 |
December | 0.382507E+09 | 0.448910E+09 | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.615096E+10 | 0.355714E+10 | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.00 | 0.00 |
Minimum of Months | 0.322623E+09 | 0.176382E+09 | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.00 | 0.00 |
Maximum of Months | 0.713623E+09 | 0.448910E+09 | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.267848E+10 | -.225145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -427027441.2 | 59.00 | 0.00 | 0.00 |
February | 0.244556E+10 | -.206447E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -381090977.6 | 59.00 | 0.00 | 0.00 |
March | 0.272661E+10 | -.231597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -410646613.6 | 58.99 | 0.00 | 0.00 |
April | 0.252908E+10 | -.214140E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -387674918.6 | 58.99 | 0.00 | 0.00 |
May | 0.252540E+10 | -.213336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -392038322.9 | 58.99 | 0.00 | 0.00 |
June | 0.238849E+10 | -.201359E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -374899235.3 | 58.99 | 0.00 | 0.00 |
July | 0.234869E+10 | -.196381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -384872579.8 | 58.99 | 0.00 | 0.00 |
August | 0.239359E+10 | -.200938E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -384209677.8 | 58.99 | 0.00 | 0.00 |
September | 0.231196E+10 | -.193719E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -374773410.6 | 58.99 | 0.00 | 0.00 |
October | 0.243133E+10 | -.203471E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -396618397.4 | 59.00 | 0.00 | 0.00 |
November | 0.243824E+10 | -.203898E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -399254278.2 | 59.00 | 0.00 | 0.00 |
December | 0.262211E+10 | -.219754E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -424574274.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298395E+11 | -.251018E+11 | 8760.00 | -.473768E+10 | 58.99 | |||||
Minimum of Months | 0.231196E+10 | -.231597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -427027441.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.272661E+10 | -.193719E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374773410.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.93 | 0.75 | 17-JAN-12:30 | 171.70 | 5.76 | 0.00 | 0.00 | 139.87 | 4.38 | 0.00 | 0.00 |
February | 259.50 | 0.89 | 0.67 | 15-FEB-11:20 | 224.47 | 6.82 | 0.00 | 0.00 | 182.93 | 5.38 | 0.00 | 0.00 |
March | 247.00 | 0.81 | 0.50 | 06-MAR-11:39 | 317.60 | 8.26 | 0.00 | 32.33 | 258.90 | 6.72 | 0.00 | 10.17 |
April | 379.50 | 0.75 | 0.50 | 01-APR-11:30 | 839.74 | 9.46 | 0.00 | 147.17 | 310.50 | 7.87 | 0.00 | 58.50 |
May | 427.83 | 0.73 | 0.50 | 01-MAY-09:50 | 1676.03 | 10.72 | 0.00 | 176.00 | 1864.34 | 8.99 | 0.00 | 111.33 |
June | 375.17 | 0.75 | 0.50 | 01-JUN-10:30 | 445.47 | 10.42 | 0.00 | 135.83 | 2457.64 | 8.75 | 0.00 | 88.33 |
July | 471.00 | 0.78 | 0.50 | 01-JUL-11:20 | 2254.77 | 8.81 | 0.00 | 142.83 | 2281.88 | 7.12 | 0.00 | 101.17 |
August | 366.67 | 0.78 | 0.50 | 01-AUG-08:09 | 1953.89 | 8.38 | 0.00 | 104.50 | 1375.72 | 6.74 | 0.00 | 80.33 |
September | 301.17 | 0.80 | 0.50 | 01-SEP-12:09 | 334.90 | 8.70 | 0.00 | 35.67 | 266.89 | 7.06 | 0.00 | 10.00 |
October | 245.33 | 0.87 | 0.50 | 02-OCT-09:30 | 245.31 | 6.82 | 0.00 | 5.17 | 198.74 | 5.34 | 0.00 | 0.83 |
November | 242.67 | 0.92 | 0.75 | 01-NOV-12:20 | 187.78 | 6.26 | 0.00 | 0.00 | 153.04 | 4.83 | 0.00 | 0.00 |
December | 160.33 | 0.95 | 0.75 | 10-DEC-12:20 | 150.94 | 4.82 | 0.00 | 0.00 | 122.53 | 3.55 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.81 | 912.66 | 8.37 | 0.00 | 779.50 | 1008.96 | 6.79 | 0.00 | 460.67 | ||
Minimum of Months | 160.33 | 0.73 | 0.50 | 150.94 | 4.82 | 0.00 | 0.00 | 122.53 | 3.55 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.95 | 0.75 | 2254.77 | 10.72 | 0.00 | 176.00 | 2457.64 | 8.99 | 0.00 | 111.33 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.504910E+10 | 45298.51 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332407E+10 | 45298.51 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696758E+09 | 45298.51 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112973E+09 | 13548.41 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11087505.34 | 2424.55 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114085E+10 | 45298.51 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344742E+10 | 45298.51 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137823E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504910E+10 | 45298.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172684E+11 | 225142.91 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104605E+11 | 225142.91 | 20-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128604E+10 | 35489.63 | 24-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144421E+09 | 23050.29 | 19-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54818.45 | 274.09 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.408145E+10 | 44023.15 | 24-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117570E+11 | 216728.64 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.449978E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172684E+11 | 225142.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123961E+10 | 33977.10 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.605996E+09 | 33977.10 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103276E+09 | 11575.00 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20456759.16 | 2789.08 | 19-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83818.59 | 391.05 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189450E+09 | 13210.41 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.840279E+09 | 33977.10 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299915E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123961E+10 | 33977.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345704E+10 | 28738.65 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184988E+10 | 28738.65 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.602855E+09 | 28632.94 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195752E+09 | 9354.53 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9273768.42 | 2081.68 | 18-MAY-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42944434.07 | 3243.63 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108088E+10 | 28738.65 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.268992E+10 | 28738.65 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.992855E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345704E+10 | 28738.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113697E+11 | 23886.92 | 07-JAN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835611E+10 | 24329.48 | 18-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.644164E+10 | 17151.44 | 05-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390831E+10 | 14285.49 | 18-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250772E+10 | 12664.51 | 23-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.963647E+09 | 9128.17 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.239199E+09 | 5739.84 | 09-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119522E+09 | 6085.31 | 01-AUG-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137834E+10 | 8728.50 | 26-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378815E+10 | 11562.18 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799256E+10 | 19651.59 | 12-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104432E+11 | 23862.90 | 26-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.575081E+11 | |||||||
Minimum of Months | 0.119522E+09 | 5739.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113697E+11 | 24329.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 168471.50 | 129866.28 | 104.28 | 25-FEB-15:30 | 75.85 | 0.00 |
March | 0.00 | 0.00 | 371392.32 | 314081.70 | 125.19 | 11-MAR-15:20 | 98.53 | 0.00 |
April | 0.00 | 0.00 | 0.561156E+09 | 0.524284E+09 | 11128.64 | 27-APR-15:00 | 9919.61 | 0.00 |
May | 0.00 | 0.00 | 0.130587E+10 | 0.115032E+10 | 29351.86 | 07-MAY-08:62 | 20677.36 | 0.00 |
June | 0.00 | 0.00 | 0.268889E+10 | 0.249167E+10 | 28912.58 | 12-JUN-06:02 | 18555.57 | 0.00 |
July | 0.00 | 0.00 | 0.641038E+10 | 0.543381E+10 | 29551.93 | 31-JUL-06:02 | 20962.00 | 0.00 |
August | 0.00 | 0.00 | 0.826524E+10 | 0.694508E+10 | 29863.18 | 25-AUG-06:02 | 20401.97 | 0.00 |
September | 0.00 | 0.00 | 0.223608E+10 | 0.181128E+10 | 28997.74 | 01-SEP-06:02 | 18868.48 | 0.00 |
October | 0.00 | 0.00 | 63103705.53 | 63052921.10 | 4801.09 | 04-OCT-15:00 | 4801.09 | 0.00 |
November | 0.00 | 0.00 | 40930225.44 | 30546668.87 | 3969.68 | 04-NOV-14:10 | 3014.33 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.215722E+11 | 0.184505E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.826524E+10 | 0.694508E+10 | 29863.18 | 20962.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 188351.36 | 170783.34 | 313.92 | 11-JAN-16:00 | 284.64 | 0.00 |
February | 0.00 | 0.00 | 40224704.51 | 39627600.22 | 7974.07 | 27-FEB-15:10 | 7974.07 | 0.00 |
March | 0.00 | 0.00 | 0.162733E+09 | 0.162353E+09 | 17181.97 | 18-MAR-16:00 | 17181.97 | 0.00 |
April | 0.00 | 0.00 | 0.471694E+10 | 0.444421E+10 | 130600.20 | 30-APR-08:62 | 85570.21 | 0.00 |
May | 0.00 | 0.00 | 0.108343E+11 | 0.953530E+10 | 135824.15 | 07-MAY-08:62 | 97918.16 | 0.00 |
June | 0.00 | 0.00 | 0.202502E+11 | 0.187374E+11 | 133525.36 | 12-JUN-06:02 | 89418.50 | 0.00 |
July | 0.00 | 0.00 | 0.407197E+11 | 0.348449E+11 | 136365.80 | 31-JUL-06:02 | 99019.30 | 0.00 |
August | 0.00 | 0.00 | 0.494938E+11 | 0.419915E+11 | 137700.31 | 30-AUG-06:02 | 88948.33 | 0.00 |
September | 0.00 | 0.00 | 0.167118E+11 | 0.135691E+11 | 134367.23 | 25-SEP-06:02 | 79175.24 | 0.00 |
October | 0.00 | 0.00 | 0.129357E+10 | 0.121243E+10 | 134670.32 | 01-OCT-08:62 | 91099.22 | 0.00 |
November | 0.00 | 0.00 | 0.602178E+09 | 0.447863E+09 | 131735.73 | 05-NOV-08:62 | 85380.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.144826E+12 | 0.124985E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.494938E+11 | 0.419915E+11 | 137700.31 | 99019.30 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 342.00 | 328.11 | 0.10 | 11-JAN-17:30 | 0.09 | 0.00 |
February | 0.00 | 0.00 | 41069893.99 | 40859389.18 | 4256.34 | 27-FEB-15:00 | 4256.34 | 0.00 |
March | 0.00 | 0.00 | 61528001.87 | 61330698.15 | 4929.64 | 18-MAR-14:00 | 4929.64 | 0.00 |
April | 0.00 | 0.00 | 0.930100E+09 | 0.887217E+09 | 20147.17 | 30-APR-08:62 | 12951.58 | 0.00 |
May | 0.00 | 0.00 | 0.158173E+10 | 0.141723E+10 | 20915.56 | 07-MAY-08:62 | 15155.44 | 0.00 |
June | 0.00 | 0.00 | 0.271976E+10 | 0.256692E+10 | 20619.89 | 12-JUN-06:02 | 13527.91 | 0.00 |
July | 0.00 | 0.00 | 0.581847E+10 | 0.507278E+10 | 21048.54 | 31-JUL-06:02 | 15166.12 | 0.00 |
August | 0.00 | 0.00 | 0.785181E+10 | 0.683751E+10 | 21253.22 | 25-AUG-06:02 | 14678.35 | 0.00 |
September | 0.00 | 0.00 | 0.360663E+10 | 0.298260E+10 | 20671.14 | 01-SEP-06:02 | 13728.07 | 0.00 |
October | 0.00 | 0.00 | 0.528581E+09 | 0.502926E+09 | 18570.58 | 06-OCT-06:02 | 12851.70 | 0.00 |
November | 0.00 | 0.00 | 0.170849E+09 | 0.129499E+09 | 14683.86 | 05-NOV-08:62 | 9500.23 | 0.00 |
December | 0.00 | 0.00 | 10607.40 | 10585.07 | 0.52 | 02-DEC-12:30 | 0.52 | 0.00 |
Annual Sum or Average | 0.233105E+11 | 0.204989E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 342.00 | 328.11 | 0.10 | 0.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.785181E+10 | 0.683751E+10 | 21253.22 | 15166.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 13254565.53 | 13198648.54 | 2225.67 | 27-FEB-15:10 | 2225.67 | 0.00 |
March | 0.00 | 0.00 | 27393294.19 | 27388644.64 | 2829.71 | 18-MAR-14:00 | 2829.71 | 0.00 |
April | 0.00 | 0.00 | 0.588852E+09 | 0.558977E+09 | 12095.82 | 28-APR-06:02 | 8502.99 | 0.00 |
May | 0.00 | 0.00 | 0.949384E+09 | 0.849477E+09 | 17431.23 | 07-MAY-08:62 | 12439.88 | 0.00 |
June | 0.00 | 0.00 | 0.162106E+10 | 0.152464E+10 | 16786.17 | 21-JUN-06:02 | 11419.86 | 0.00 |
July | 0.00 | 0.00 | 0.385587E+10 | 0.333596E+10 | 17550.64 | 31-JUL-06:02 | 12574.15 | 0.00 |
August | 0.00 | 0.00 | 0.555996E+10 | 0.481102E+10 | 17724.23 | 25-AUG-06:02 | 12162.34 | 0.00 |
September | 0.00 | 0.00 | 0.250105E+10 | 0.205373E+10 | 17221.94 | 24-SEP-08:62 | 10003.63 | 0.00 |
October | 0.00 | 0.00 | 0.314641E+09 | 0.303091E+09 | 8340.39 | 05-OCT-06:02 | 7516.82 | 0.00 |
November | 0.00 | 0.00 | 0.107615E+09 | 81124691.35 | 7237.75 | 04-NOV-14:00 | 5632.45 | 0.00 |
December | 0.00 | 0.00 | 3051.92 | 3051.92 | 1.06 | 05-DEC-15:50 | 1.06 | 0.00 |
Annual Sum or Average | 0.155391E+11 | 0.135586E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.555996E+10 | 0.481102E+10 | 17724.23 | 12574.15 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.264894E+10 | 0.50 | 1773.33 | 01-JAN-07:03 | 0.89 |
February | 0.230421E+10 | 0.48 | 1773.33 | 01-FEB-06:03 | 0.89 |
March | 0.240042E+10 | 0.45 | 1773.33 | 01-MAR-06:01 | 0.89 |
April | 0.201511E+10 | 0.39 | 1773.33 | 01-APR-05:02 | 0.89 |
May | 0.172775E+10 | 0.32 | 1773.33 | 01-MAY-07:10 | 0.89 |
June | 0.120244E+10 | 0.23 | 1773.33 | 01-JUN-07:10 | 0.88 |
July | 0.702542E+09 | 0.13 | 1773.33 | 01-JUL-07:10 | 0.88 |
August | 0.564975E+09 | 0.11 | 1773.33 | 01-AUG-07:05 | 0.88 |
September | 0.131850E+10 | 0.25 | 1773.33 | 01-SEP-07:06 | 0.88 |
October | 0.213382E+10 | 0.40 | 1773.33 | 01-OCT-07:09 | 0.88 |
November | 0.233086E+10 | 0.45 | 1773.33 | 01-NOV-06:03 | 0.89 |
December | 0.258990E+10 | 0.48 | 1773.33 | 01-DEC-06:02 | 0.89 |
Annual Sum or Average | 0.219395E+11 | 0.35 | |||
Minimum of Months | 0.564975E+09 | 0.11 | 1773.33 | 0.88 | |
Maximum of Months | 0.264894E+10 | 0.50 | 1773.33 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.295085E+10 | 0.53 | 1841.58 | 01-JAN-12:10 | 0.89 |
February | 0.267969E+10 | 0.54 | 1841.58 | 01-FEB-08:50 | 0.89 |
March | 0.300326E+10 | 0.54 | 1841.58 | 02-MAR-08:50 | 0.89 |
April | 0.288392E+10 | 0.54 | 1841.58 | 01-APR-14:35 | 0.89 |
May | 0.297674E+10 | 0.53 | 1841.58 | 01-MAY-13:40 | 0.88 |
June | 0.290381E+10 | 0.54 | 1841.58 | 01-JUN-14:40 | 0.89 |
July | 0.295685E+10 | 0.53 | 1841.58 | 01-JUL-07:19 | 0.88 |
August | 0.300326E+10 | 0.54 | 1841.58 | 01-AUG-07:45 | 0.88 |
September | 0.288392E+10 | 0.53 | 1841.58 | 01-SEP-09:17 | 0.88 |
October | 0.295022E+10 | 0.53 | 1841.58 | 01-OCT-14:00 | 0.88 |
November | 0.284414E+10 | 0.53 | 1841.58 | 04-NOV-12:00 | 0.88 |
December | 0.295685E+10 | 0.53 | 1841.58 | 01-DEC-07:45 | 0.89 |
Annual Sum or Average | 0.349935E+11 | 0.53 | |||
Minimum of Months | 0.267969E+10 | 0.53 | 1841.58 | 0.88 | |
Maximum of Months | 0.300326E+10 | 0.54 | 1841.58 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.221601E+11 | 0.91 | 13832.79 | 03-JAN-08:30 | 1.52 |
February | 0.201184E+11 | 0.92 | 13832.79 | 06-FEB-20:20 | 1.53 |
March | 0.225585E+11 | 0.93 | 13832.79 | 01-MAR-07:55 | 1.53 |
April | 0.216621E+11 | 0.92 | 13832.79 | 06-APR-11:20 | 1.52 |
May | 0.223593E+11 | 0.92 | 13832.79 | 02-MAY-14:30 | 1.52 |
June | 0.218115E+11 | 0.92 | 13832.79 | 01-JUN-11:20 | 1.52 |
July | 0.222099E+11 | 0.91 | 13832.79 | 01-JUL-17:40 | 1.52 |
August | 0.225585E+11 | 0.92 | 13832.79 | 02-AUG-14:00 | 1.52 |
September | 0.216621E+11 | 0.92 | 13832.79 | 01-SEP-12:10 | 1.51 |
October | 0.221601E+11 | 0.91 | 13832.79 | 01-OCT-17:55 | 1.52 |
November | 0.213634E+11 | 0.91 | 13832.79 | 02-NOV-13:40 | 1.52 |
December | 0.222099E+11 | 0.91 | 13832.79 | 08-DEC-20:00 | 1.53 |
Annual Sum or Average | 0.262834E+12 | 0.92 | |||
Minimum of Months | 0.201184E+11 | 0.91 | 13832.79 | 1.51 | |
Maximum of Months | 0.225585E+11 | 0.93 | 13832.79 | 1.53 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.223281E+10 | 0.55 | 1393.70 | 01-JAN-11:10 | 0.92 |
February | 0.202717E+10 | 0.55 | 1393.70 | 01-FEB-16:20 | 0.92 |
March | 0.227285E+10 | 0.56 | 1393.70 | 01-MAR-18:40 | 0.92 |
April | 0.218254E+10 | 0.55 | 1393.70 | 04-APR-17:05 | 0.92 |
May | 0.225278E+10 | 0.55 | 1393.70 | 01-MAY-15:40 | 0.92 |
June | 0.219759E+10 | 0.56 | 1393.70 | 01-JUN-07:20 | 0.92 |
July | 0.223773E+10 | 0.55 | 1393.70 | 02-JUL-13:50 | 0.92 |
August | 0.227285E+10 | 0.56 | 1393.70 | 01-AUG-11:50 | 0.91 |
September | 0.218254E+10 | 0.55 | 1393.70 | 01-SEP-07:53 | 0.91 |
October | 0.223271E+10 | 0.55 | 1393.70 | 03-OCT-09:05 | 0.92 |
November | 0.215243E+10 | 0.55 | 1393.70 | 02-NOV-10:57 | 0.92 |
December | 0.223773E+10 | 0.55 | 1393.70 | 01-DEC-07:13 | 0.92 |
Annual Sum or Average | 0.264817E+11 | 0.55 | |||
Minimum of Months | 0.202717E+10 | 0.55 | 1393.70 | 0.91 | |
Maximum of Months | 0.227285E+10 | 0.56 | 1393.70 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182523E+10 | 0.55 | 1138.78 | 01-JAN-16:30 | 0.92 |
February | 0.165668E+10 | 0.55 | 1138.78 | 01-FEB-10:10 | 0.92 |
March | 0.185712E+10 | 0.56 | 1138.78 | 01-MAR-07:17 | 0.92 |
April | 0.178333E+10 | 0.55 | 1138.78 | 01-APR-10:40 | 0.92 |
May | 0.184072E+10 | 0.55 | 1138.78 | 01-MAY-13:00 | 0.91 |
June | 0.179563E+10 | 0.56 | 1138.78 | 01-JUN-11:10 | 0.92 |
July | 0.182843E+10 | 0.55 | 1138.78 | 01-JUL-11:40 | 0.91 |
August | 0.185712E+10 | 0.56 | 1138.78 | 01-AUG-06:13 | 0.91 |
September | 0.178333E+10 | 0.55 | 1138.78 | 01-SEP-08:13 | 0.91 |
October | 0.182433E+10 | 0.55 | 1138.78 | 01-OCT-10:25 | 0.91 |
November | 0.175873E+10 | 0.55 | 1138.78 | 01-NOV-06:35 | 0.92 |
December | 0.182853E+10 | 0.55 | 1138.78 | 01-DEC-06:18 | 0.92 |
Annual Sum or Average | 0.216392E+11 | 0.55 | |||
Minimum of Months | 0.165668E+10 | 0.55 | 1138.78 | 0.91 | |
Maximum of Months | 0.185712E+10 | 0.56 | 1138.78 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.00 |
February | 0.15 | 0.00 |
March | 0.08 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.04 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.45 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.32 | 12.36 |
February | 0.31 | 25.84 |
March | 1.78 | 25.84 |
April | 2.11 | 25.84 |
May | 0.40 | 25.84 |
June | 0.17 | 25.84 |
July | 0.67 | 25.84 |
August | 0.83 | 25.84 |
September | 0.21 | 25.84 |
October | 1.58 | 25.84 |
November | 0.62 | 25.84 |
December | 0.28 | 25.84 |
Annual Sum or Average | 9.28 | 25.38 |
Minimum of Months | 0.17 | 12.36 |
Maximum of Months | 2.11 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.56 | 0.97 |
March | 0.74 | 2.44 |
April | 0.69 | 2.44 |
May | 0.21 | 2.44 |
June | 0.14 | 0.00 |
July | 0.58 | 0.00 |
August | 0.42 | 0.00 |
September | 0.29 | 0.35 |
October | 0.33 | 1.83 |
November | 0.46 | 1.99 |
December | 0.06 | 2.44 |
Annual Sum or Average | 4.47 | 1.41 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.74 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.33 | 0.00 |
February | 0.04 | 0.00 |
March | 0.62 | 1.14 |
April | 0.46 | 2.44 |
May | 0.29 | 2.44 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.10 | 2.44 |
October | 0.69 | 2.44 |
November | 0.17 | 0.61 |
December | 0.17 | 0.00 |
Annual Sum or Average | 2.87 | 1.59 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.69 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 30.92 | 0.00 |
February | 18.91 | 0.00 |
March | 7.64 | 0.00 |
April | 10.03 | 0.00 |
May | 17.62 | 0.00 |
June | 27.76 | 0.00 |
July | 27.75 | 0.00 |
August | 20.20 | 0.00 |
September | 25.22 | 0.00 |
October | 13.97 | 0.00 |
November | 14.29 | 0.00 |
December | 26.07 | 0.00 |
Annual Sum or Average | 240.40 | 0.00 |
Minimum of Months | 7.64 | 0.00 |
Maximum of Months | 30.92 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.295085E+10 | 0.631138E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.267974E+10 | 0.415509E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.300336E+10 | 0.870947E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.303998E+10 | 0.141216E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.332682E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.362371E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.465924E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.521455E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.347317E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.296740E+10 | 13859381.68 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.285533E+10 | 0.142606E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.295685E+10 | 0.430928E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.407510E+11 | 0.172278E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.267974E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.521455E+10 | 0.631138E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.221602E+11 | 0.215854E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.201310E+11 | 0.130756E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.226082E+11 | 0.160755E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.230776E+11 | 0.180527E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.255178E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.277494E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.340487E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.370486E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.264882E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.225367E+11 | 68523.07 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.215390E+11 | 0.510182E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.222099E+11 | 0.146963E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.305115E+12 | 0.562473E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.201310E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.370486E+11 | 0.215854E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.223281E+10 | 0.154951E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.203823E+10 | 0.757495E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.228918E+10 | 0.129095E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.242831E+10 | 25570948.95 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.266598E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.291451E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.375914E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.432175E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.309028E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.236980E+10 | 104773.24 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.219545E+10 | 0.236812E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.223773E+10 | 0.105035E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.325432E+11 | 0.374893E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203823E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.432175E+10 | 0.154951E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182523E+10 | 0.432130E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166020E+10 | 0.231235E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.186431E+10 | 0.753569E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.193663E+10 | 0.244691E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.208520E+10 | 11592210.52 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.221682E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.282113E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.328024E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.239777E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.190375E+10 | 53680542.59 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.178547E+10 | 0.135110E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.182853E+10 | 0.336240E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.256053E+11 | 0.124107E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.166020E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.328024E+10 | 0.432130E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.295085E+10 | 0.00 | 0.504910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267969E+10 | 168471.50 | 0.332407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300326E+10 | 371392.32 | 0.696758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288392E+10 | 0.561156E+09 | 0.112973E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.297674E+10 | 0.130587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.290381E+10 | 0.268889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.295685E+10 | 0.641038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.300326E+10 | 0.826524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288392E+10 | 0.223608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295022E+10 | 63103705.53 | 11087505.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.284414E+10 | 40930225.44 | 0.114085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295685E+10 | 0.00 | 0.344742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349935E+11 | 0.215722E+11 | 0.137823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.300326E+10 | 0.826524E+10 | 0.504910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.221601E+11 | 188351.36 | 0.172684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201184E+11 | 40224704.51 | 0.104605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225585E+11 | 0.162733E+09 | 0.128604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216621E+11 | 0.471694E+10 | 0.144421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223593E+11 | 0.108343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218115E+11 | 0.202502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222099E+11 | 0.407197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.225585E+11 | 0.494938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216621E+11 | 0.167118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221601E+11 | 0.129357E+10 | 54818.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213634E+11 | 0.602178E+09 | 0.408145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222099E+11 | 0.00 | 0.117570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262834E+12 | 0.144826E+12 | 0.449978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.201184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225585E+11 | 0.494938E+11 | 0.172684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.223281E+10 | 342.00 | 0.123961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202717E+10 | 41069893.99 | 0.605996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227285E+10 | 61528001.87 | 0.103276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218254E+10 | 0.930100E+09 | 20456759.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225278E+10 | 0.158173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219759E+10 | 0.271976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223773E+10 | 0.581847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227285E+10 | 0.785181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218254E+10 | 0.360663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223271E+10 | 0.528581E+09 | 83818.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215243E+10 | 0.170849E+09 | 0.189450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223773E+10 | 10607.40 | 0.840279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264817E+11 | 0.233105E+11 | 0.299915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.202717E+10 | 342.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227285E+10 | 0.785181E+10 | 0.123961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182523E+10 | 0.00 | 0.345704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165668E+10 | 13254565.53 | 0.184988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185712E+10 | 27393294.19 | 0.602855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178333E+10 | 0.588852E+09 | 0.195752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184072E+10 | 0.949384E+09 | 9273768.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179563E+10 | 0.162106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182843E+10 | 0.385587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185712E+10 | 0.555996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178333E+10 | 0.250105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182433E+10 | 0.314641E+09 | 42944434.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175873E+10 | 0.107615E+09 | 0.108088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182853E+10 | 3051.92 | 0.268992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216392E+11 | 0.155391E+11 | 0.992855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.165668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.185712E+10 | 0.555996E+10 | 0.345704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.295085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267969E+10 | 0.00 | 0.00 | 0.00 | 47673.76 | 0.00 | 0.415509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300326E+10 | 0.00 | 0.00 | 0.00 | 105254.15 | 0.00 | 0.870947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288392E+10 | 0.00 | 0.00 | 0.00 | 0.156061E+09 | 0.00 | 0.141216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.297674E+10 | 0.00 | 0.00 | 0.00 | 0.350085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.290381E+10 | 0.00 | 0.00 | 0.00 | 0.719897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.295685E+10 | 0.00 | 0.00 | 0.00 | 0.170239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.300326E+10 | 0.00 | 0.00 | 0.00 | 0.221129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.288392E+10 | 0.00 | 0.00 | 0.00 | 0.589248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295022E+10 | 0.00 | 0.00 | 0.00 | 17183078.93 | 0.00 | 13859381.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.284414E+10 | 0.00 | 0.00 | 0.00 | 11188870.02 | 0.00 | 0.142606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349935E+11 | 0.00 | 0.00 | 0.00 | 0.575750E+10 | 0.00 | 0.172278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.267969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.300326E+10 | 0.00 | 0.00 | 0.00 | 0.221129E+10 | 0.00 | 0.631138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.221601E+11 | 0.00 | 0.00 | 0.00 | 59709.00 | 0.00 | 0.215854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201184E+11 | 0.00 | 0.00 | 0.00 | 12543540.11 | 0.00 | 0.130756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225585E+11 | 0.00 | 0.00 | 0.00 | 49698707.84 | 0.00 | 0.160755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.216621E+11 | 0.00 | 0.00 | 0.00 | 0.141540E+10 | 0.00 | 0.180527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223593E+11 | 0.00 | 0.00 | 0.00 | 0.315844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.218115E+11 | 0.00 | 0.00 | 0.00 | 0.593789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.222099E+11 | 0.00 | 0.00 | 0.00 | 0.118388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.225585E+11 | 0.00 | 0.00 | 0.00 | 0.144901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.216621E+11 | 0.00 | 0.00 | 0.00 | 0.482607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221601E+11 | 0.00 | 0.00 | 0.00 | 0.376562E+09 | 0.00 | 68523.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.213634E+11 | 0.00 | 0.00 | 0.00 | 0.175687E+09 | 0.00 | 0.510182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.222099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262834E+12 | 0.00 | 0.00 | 0.00 | 0.422812E+11 | 0.00 | 0.562473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.201184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.225585E+11 | 0.00 | 0.00 | 0.00 | 0.144901E+11 | 0.00 | 0.215854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.223281E+10 | 0.00 | 0.00 | 0.00 | 97.03 | 0.00 | 0.154951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202717E+10 | 0.00 | 0.00 | 0.00 | 11062888.55 | 0.00 | 0.757495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227285E+10 | 0.00 | 0.00 | 0.00 | 16332800.28 | 0.00 | 0.129095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.218254E+10 | 0.00 | 0.00 | 0.00 | 0.245772E+09 | 0.00 | 25570948.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225278E+10 | 0.00 | 0.00 | 0.00 | 0.413201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.219759E+10 | 0.00 | 0.00 | 0.00 | 0.716922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223773E+10 | 0.00 | 0.00 | 0.00 | 0.152141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227285E+10 | 0.00 | 0.00 | 0.00 | 0.204890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.218254E+10 | 0.00 | 0.00 | 0.00 | 0.907737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223271E+10 | 0.00 | 0.00 | 0.00 | 0.137086E+09 | 0.00 | 104773.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215243E+10 | 0.00 | 0.00 | 0.00 | 43016781.65 | 0.00 | 0.236812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223773E+10 | 0.00 | 0.00 | 0.00 | 2995.37 | 0.00 | 0.105035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264817E+11 | 0.00 | 0.00 | 0.00 | 0.606145E+10 | 0.00 | 0.374893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.202717E+10 | 0.00 | 0.00 | 0.00 | 97.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227285E+10 | 0.00 | 0.00 | 0.00 | 0.204890E+10 | 0.00 | 0.154951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.182523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165668E+10 | 0.00 | 0.00 | 0.00 | 3523235.73 | 0.00 | 0.231235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185712E+10 | 0.00 | 0.00 | 0.00 | 7188480.95 | 0.00 | 0.753569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178333E+10 | 0.00 | 0.00 | 0.00 | 0.153304E+09 | 0.00 | 0.244691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184072E+10 | 0.00 | 0.00 | 0.00 | 0.244472E+09 | 0.00 | 11592210.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179563E+10 | 0.00 | 0.00 | 0.00 | 0.421195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182843E+10 | 0.00 | 0.00 | 0.00 | 0.992707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.185712E+10 | 0.00 | 0.00 | 0.00 | 0.142312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178333E+10 | 0.00 | 0.00 | 0.00 | 0.614440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182433E+10 | 0.00 | 0.00 | 0.00 | 79419717.35 | 0.00 | 53680542.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175873E+10 | 0.00 | 0.00 | 0.00 | 26739236.99 | 0.00 | 0.135110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182853E+10 | 0.00 | 0.00 | 0.00 | 836.68 | 0.00 | 0.336240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216392E+11 | 0.00 | 0.00 | 0.00 | 0.396611E+10 | 0.00 | 0.124107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.165668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.185712E+10 | 0.00 | 0.00 | 0.00 | 0.142312E+10 | 0.00 | 0.432130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.453795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341467E+10 | 0.00 | 0.00 | 0.20 |
February | 0.441113E+10 | 0.00 | 0.00 | 163886.11 | 0.00 | 0.213411E+10 | 0.315105E+09 | 0.00 | 0.21 |
March | 0.574143E+10 | 0.00 | 0.00 | 490292.35 | 0.00 | 0.547732E+09 | 0.949273E+09 | 0.00 | 0.22 |
April | 0.336037E+10 | 5322227.46 | 0.00 | 3413390.12 | 0.00 | 91882579.96 | 0.362391E+10 | 0.00 | 0.30 |
May | 0.126905E+10 | 3125446.44 | 0.00 | 9674071.76 | 0.00 | 0.00 | 0.744663E+10 | 0.00 | 0.49 |
June | 0.393444E+09 | 4192558.23 | 0.00 | 14480257.79 | 0.00 | 0.00 | 0.873738E+10 | 0.00 | 0.69 |
July | 98834812.37 | 0.160806E+09 | 0.00 | 16483264.15 | 0.00 | 0.00 | 0.724781E+10 | 0.00 | 0.73 |
August | 0.112928E+09 | 0.357739E+09 | 0.00 | 14391096.07 | 0.00 | 0.00 | 0.622382E+10 | 0.00 | 0.67 |
September | 0.572601E+09 | 4250889.38 | 0.00 | 13180646.52 | 0.00 | 0.00 | 0.823983E+10 | 0.00 | 0.62 |
October | 0.283996E+10 | 0.00 | 0.00 | 4636077.22 | 0.00 | 1994580.69 | 0.522439E+10 | 0.00 | 0.32 |
November | 0.504374E+10 | 0.00 | 0.00 | 1140938.34 | 0.00 | 0.715299E+09 | 0.138867E+10 | 0.00 | 0.23 |
December | 0.521064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241938E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.335921E+11 | 0.535435E+09 | 0.00 | 78053920.43 | 0.00 | 0.932507E+10 | 0.493968E+11 | 0.00 | 0.41 |
Minimum of Months | 98834812.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.574143E+10 | 0.357739E+09 | 0.00 | 16483264.15 | 0.00 | 0.341467E+10 | 0.873738E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.538124E+11 | 0.00 | 0.00 | 48384.76 | 0.00 | 0.746441E+10 | 0.177009E+09 | 0.00 | 0.39 |
February | 0.457575E+11 | 0.00 | 0.00 | 2834164.41 | 0.00 | 0.351134E+10 | 0.399382E+10 | 0.00 | 0.41 |
March | 0.401562E+11 | 0.00 | 0.00 | 11028968.45 | 0.00 | 76410807.52 | 0.160178E+11 | 0.00 | 0.43 |
April | 0.198250E+11 | 69060464.93 | 0.00 | 34198091.84 | 0.00 | 0.00 | 0.321328E+11 | 0.00 | 0.53 |
May | 0.804730E+10 | 57046195.12 | 0.00 | 70616250.43 | 0.00 | 0.00 | 0.475163E+11 | 0.00 | 0.71 |
June | 0.197983E+10 | 59668318.31 | 0.00 | 93725033.92 | 0.00 | 0.00 | 0.490961E+11 | 0.00 | 0.88 |
July | 0.108058E+10 | 0.146390E+10 | 0.00 | 93334386.93 | 0.00 | 0.00 | 0.367990E+11 | 0.00 | 0.89 |
August | 0.103155E+10 | 0.315310E+10 | 0.00 | 77952358.05 | 0.00 | 0.00 | 0.312078E+11 | 0.00 | 0.84 |
September | 0.291583E+10 | 81983857.55 | 0.00 | 83479340.65 | 0.00 | 0.00 | 0.469768E+11 | 0.00 | 0.81 |
October | 0.171623E+11 | 0.00 | 0.00 | 40139278.60 | 0.00 | 0.00 | 0.393356E+11 | 0.00 | 0.55 |
November | 0.408582E+11 | 0.00 | 0.00 | 11018737.11 | 0.00 | 0.525008E+09 | 0.124547E+11 | 0.00 | 0.42 |
December | 0.550821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364582E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.287709E+12 | 0.488476E+10 | 0.00 | 0.518375E+09 | 0.00 | 0.152230E+11 | 0.315708E+12 | 0.00 | 0.61 |
Minimum of Months | 0.103155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.550821E+11 | 0.315310E+10 | 0.00 | 93725033.92 | 0.00 | 0.746441E+10 | 0.490961E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.460566E+10 | 0.00 | 0.00 | 443341.35 | 0.00 | 0.738132E+09 | 0.693581E+09 | 0.00 | 0.40 |
February | 0.300214E+10 | 0.00 | 0.00 | 2601443.86 | 0.00 | 0.306017E+09 | 0.257690E+10 | 0.00 | 0.49 |
March | 0.186504E+10 | 0.00 | 0.00 | 5883510.68 | 0.00 | 18117775.48 | 0.536630E+10 | 0.00 | 0.63 |
April | 0.100130E+10 | 9431486.17 | 0.00 | 8677273.55 | 0.00 | 1256143.20 | 0.600119E+10 | 0.00 | 0.84 |
May | 0.520587E+09 | 15253864.01 | 0.00 | 12001291.52 | 0.00 | 0.00 | 0.697727E+10 | 0.00 | 1.13 |
June | 0.132012E+09 | 9945490.11 | 0.00 | 14297679.03 | 0.00 | 0.00 | 0.686026E+10 | 0.00 | 1.42 |
July | 73868558.35 | 0.190968E+09 | 0.00 | 14413488.26 | 0.00 | 0.00 | 0.526250E+10 | 0.00 | 1.45 |
August | 52419597.53 | 0.414725E+09 | 0.00 | 12555469.52 | 0.00 | 0.00 | 0.456386E+10 | 0.00 | 1.35 |
September | 0.150625E+09 | 61002777.01 | 0.00 | 15772156.08 | 0.00 | 0.00 | 0.696923E+10 | 0.00 | 1.38 |
October | 0.728659E+09 | 0.00 | 0.00 | 10921271.16 | 0.00 | 0.00 | 0.752048E+10 | 0.00 | 0.94 |
November | 0.250535E+10 | 0.00 | 0.00 | 3760688.25 | 0.00 | 96979619.02 | 0.342573E+10 | 0.00 | 0.52 |
December | 0.401511E+10 | 0.00 | 0.00 | 1472641.03 | 0.00 | 0.552385E+09 | 0.156035E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.186528E+11 | 0.701326E+09 | 0.00 | 0.102800E+09 | 0.00 | 0.171289E+10 | 0.577776E+11 | 0.00 | 0.92 |
Minimum of Months | 52419597.53 | 0.00 | 0.00 | 443341.35 | 0.00 | 0.00 | 0.693581E+09 | 0.00 | 0.40 |
Maximum of Months | 0.460566E+10 | 0.414725E+09 | 0.00 | 15772156.08 | 0.00 | 0.738132E+09 | 0.752048E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.342622E+10 | 0.00 | 0.00 | 2199.29 | 0.00 | 0.226315E+10 | 14310834.82 | 0.00 | 0.39 |
February | 0.323431E+10 | 0.00 | 0.00 | 498644.20 | 0.00 | 0.116140E+10 | 0.583245E+09 | 0.00 | 0.42 |
March | 0.327978E+10 | 0.00 | 0.00 | 1616504.38 | 0.00 | 0.388309E+09 | 0.170255E+10 | 0.00 | 0.46 |
April | 0.210782E+10 | 8662441.09 | 0.00 | 3425523.32 | 0.00 | 0.130119E+09 | 0.263899E+10 | 0.00 | 0.58 |
May | 0.120582E+10 | 8569380.91 | 0.00 | 5661935.31 | 0.00 | 0.00 | 0.390049E+10 | 0.00 | 0.78 |
June | 0.507125E+09 | 7885809.61 | 0.00 | 7565620.99 | 0.00 | 0.00 | 0.441917E+10 | 0.00 | 1.02 |
July | 0.211637E+09 | 0.156223E+09 | 0.00 | 8542533.12 | 0.00 | 0.00 | 0.372981E+10 | 0.00 | 1.09 |
August | 0.198511E+09 | 0.363315E+09 | 0.00 | 7686381.08 | 0.00 | 0.00 | 0.324600E+10 | 0.00 | 1.03 |
September | 0.579247E+09 | 39704870.33 | 0.00 | 9297484.86 | 0.00 | 0.00 | 0.446375E+10 | 0.00 | 1.00 |
October | 0.202138E+10 | 0.00 | 0.00 | 5076385.96 | 0.00 | 9425473.07 | 0.372633E+10 | 0.00 | 0.65 |
November | 0.354330E+10 | 0.00 | 0.00 | 788621.18 | 0.00 | 0.595212E+09 | 0.701849E+09 | 0.00 | 0.43 |
December | 0.338211E+10 | 0.00 | 0.00 | 264933.74 | 0.00 | 0.183735E+10 | 0.302082E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.236973E+11 | 0.584361E+09 | 0.00 | 50426767.42 | 0.00 | 0.638496E+10 | 0.294286E+11 | 0.00 | 0.69 |
Minimum of Months | 0.198511E+09 | 0.00 | 0.00 | 2199.29 | 0.00 | 0.00 | 14310834.82 | 0.00 | 0.39 |
Maximum of Months | 0.354330E+10 | 0.363315E+09 | 0.00 | 9297484.86 | 0.00 | 0.226315E+10 | 0.446375E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |