Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:13:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1536.08 | 669.61 | 669.61 |
Net Site Energy | 1536.08 | 669.61 | 669.61 |
Total Source Energy | 4174.87 | 1819.91 | 1819.91 |
Net Source Energy | 4174.87 | 1819.91 | 1819.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 236.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 475.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 399.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 95.17 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1204.87 | 331.21 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 236.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 475.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 399.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 95.17 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 201.24 | 144.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 525.23 | 144.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 238.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 201.24 | 144.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 525.23 | 144.38 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1204.875 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1204.875 | 100.00 |
Total On-Site and Utility Electric Sources | 1204.875 | 100.00 |
Total Electricity End Uses | 1204.875 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 908.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:13 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 6.69 |
Skylight-Roof Ratio [%] | 0.29 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 8.3451 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 17.7333 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 17.7333 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 17.7333 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 13.5608 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.1568 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 16.1568 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-14:00 | 20-FEB-07:10 | - | - | - | 14-SEP-11:09 |
Heating | 0.00 | 176687.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40969.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18974.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4432.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 104100.01 | 181120.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 176687.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40969.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18974.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4432.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 255.87 | 0.00 | 0.00 | 0.00 |
Cooling | 197.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1505.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1264.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 103.17 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3815.84 | 359.03 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 111.54 | 0.00 | 0.00 | 0.00 |
Cooling | 86.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 656.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 551.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.97 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1663.40 | 156.51 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 111.54 | 0.00 | 0.00 | 0.00 |
Cooling | 86.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 656.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 551.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.97 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1663.40 | 156.51 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.62 |
CORE_RETAIL DIRECT AIR | 7.47 |
POINT_OF_SALE DIRECT AIR | 1.29 |
FRONT_RETAIL DIRECT AIR | 1.06 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 2.49 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 2.49 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 57266.94 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 43840.34 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 227472.09 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 34661.83 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 29450.54 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.62 | 1.62 | 1.62 | 1.62 | 1.68 | 1.68 | 1.00 | 0.966009 | 1.68 |
PSZ-AC:2 | 7.47 | 7.47 | 7.47 | 7.47 | 7.70 | 7.70 | 1.00 | 0.969826 | 7.70 |
PSZ-AC:3 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.29 | 1.00 | 1.00 | 1.29 |
PSZ-AC:4 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.00 | 1.06 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.68 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.70 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.29 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.06 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.68 | 1.68 | 1.68 | 1.68 | 29561.76 | 43840.34 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.70 | 7.70 | 7.70 | 7.70 | 138373.22 | 227472.09 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.29 | 1.29 | 1.29 | 1.29 | 21405.98 | 34661.83 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 17947.75 | 29450.54 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.68 | 0.838925 | 1.68 | 27774.38 | 29561.76 | 14780.88 | 29561.76 | 0.776426 | 0.776430 | 0.776430 | 0.776430 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.70 | 3.85 | 7.70 | 128474.44 | 138373.22 | 69186.61 | 138373.22 | 0.769802 | 0.769800 | 0.769800 | 0.769800 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.29 | 0.643865 | 1.29 | 21316.50 | 21405.98 | 10702.99 | 21405.98 | 0.797118 | 0.797120 | 0.797120 | 0.797120 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.06 | 0.529460 | 1.06 | 17528.89 | 17947.75 | 8973.88 | 17947.75 | 0.790075 | 0.790070 | 0.790070 | 0.790070 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.68 | 1836.42 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.70 | 14462.55 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.29 | 1468.15 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1207.28 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 8.345 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.415 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 17.733 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.963 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 17.733 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 39.253 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 17.733 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 20.963 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 13.561 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.561 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 3170.217 | 8.345 | 51.681 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3170.217 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 28381.872 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 28381.872 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2674.362 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2674.362 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2674.362 | 17.733 | 109.822 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2674.362 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 162.729 | 13.561 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 162.729 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8391346 | 2.8391346 | 2.8391346 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
25 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
26 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
27 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
28 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
29 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
30 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
31 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
32 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
33 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.51_SHGC_0.4 | 30 | 1 | VerySmooth | 2.899 | 0.395 | 0.315 | 0.401 |
2 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 31 | 1 | VerySmooth | 3.411 | 0.396 | 0.314 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.82741E-002 | 0.31435 | 0.46434 | 0.46434 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10459 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.31383 | 0.45189 | 0.45189 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 1.61274E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 18965.44645 | 22758.53574 | 1.35068 | 1.62082 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 20200.25009 | 24240.30010 | 0.85938 | 1.03126 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 87109.99689 | 104531.99627 | 6.22555 | 7.47066 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 49720.99141 | 59665.18969 | 2.07810 | 2.49371 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 14415.36792 | 17298.44150 | 1.07311 | 1.28773 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 9937.71679 | 11925.26015 | 0.42486 | 0.50983 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 11853.88110 | 14224.65731 | 0.88243 | 1.05892 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 9933.01869 | 11919.62243 | 0.42466 | 0.50959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 47686.43075 | 57223.71690 | 2.07824 | 2.49389 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 22169.97 | 1.67785 | 1.67785 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 30416.47 | 1.03126 | 1.03126 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 108649.63 | 7.70310 | 7.70310 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 113475.00 | 2.49371 | 2.49371 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 18140.88 | 1.28773 | 1.28773 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 16945.06 | 0.50983 | 0.50983 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 15120.41 | 1.05892 | 1.05892 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 16939.46 | 0.50959 | 0.50959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.62082 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.47066 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28773 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05892 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.49389 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.49389 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 57266.93835 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.62082 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62082 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.62082 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.62082 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.67785 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.67785 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.96601 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.47066 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.47066 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.47066 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.47066 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.70310 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.70310 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96983 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.28773 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28773 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.28773 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28773 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.28773 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.28773 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05892 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05892 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05892 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05892 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05892 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05892 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.67785 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.70310 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.28773 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.05892 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.67785 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.67785 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.67785 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.67785 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.67785 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.67785 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83893 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.67785 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27774.37510 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29561.76000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14780.88000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29561.76000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.77643 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.77643 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.77643 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.77643 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29561.76000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43840.33531 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.67785 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1836.41897 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 43840.33531 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.70310 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.70310 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.70310 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.70310 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.70310 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.70310 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.85155 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.70310 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 128474.44325 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 138373.22000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 69186.61000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 138373.22000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76980 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76980 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76980 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76980 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 138373.22000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 227472.08647 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.70310 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14462.54904 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 227472.08647 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.28773 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.28773 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.28773 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.28773 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.28773 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.28773 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.64387 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.28773 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21316.50389 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21405.98000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10702.99000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21405.98000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79712 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79712 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79712 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79712 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21405.98000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34661.83317 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.28773 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1468.15343 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 34661.83317 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05892 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05892 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05892 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05892 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05892 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05892 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52946 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05892 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17528.88595 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17947.75000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8973.87500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17947.75000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79007 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79007 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79007 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79007 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17947.75000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29450.53953 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05892 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1207.28119 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29450.53953 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28245.7 | 10.13 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 132329.4 | 11.52 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20396.7 | 89.01 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17117.6 | 127.86 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.839 | 2.839 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1593.79 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | N/A | 3.411 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 8.3875660570E-002 | 0.3364853223 | Pass | Pass | 5.0127334719E-002 | 0.1979725425 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.4296344069E-002 | 0.2101918962 | Pass | Pass | 0.1246869897 | 0.4670018039 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 9.1541411617E-002 | 0.3886476352 | Pass | Pass | 0.2327098495 | 0.7415863156 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 9.6287254981E-002 | 0.4186104929 | Pass | Pass | 4.9978159728E-002 | 0.2083684116 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1511526425 | 0.5404444866 | Pass | Pass | 9.2454403477E-002 | 0.4843287959 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 1600.48 | 1593.79 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.6_SHGC_0.4 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 3.411 | 0.396 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.51_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.899 | 0.395 | 0.401 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.51_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.899 | 0.395 | 0.401 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.51_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.899 | 0.395 | 0.401 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 90.63 | 2.937 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 90.63 | 2.937 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.992 | 2.839 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 8.3451 | 379.89 | 3170.22 | LightsWired | BLDG_LIGHT_BACK_SCH | 69.84 | 168.00 | 68.87 | 0.0000 | Y | 40.98 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 17.7333 | 1600.48 | 28381.87 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 363.63 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 17.7333 | 150.81 | 2674.36 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.26 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 17.7333 | 150.81 | 2674.36 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 34.26 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 13.5608 | 12.00 | 162.73 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 2.08 |
Interior Lighting Total | 16.1568 | 2293.99 | 37063.54 | 475.23 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4644.36 | AstronomicalClock | - | 83.55 | 83.55 | 72.84 | |
Exterior Lighting Total | 4644.36 | 72.84 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29561.76 | 22952.64 | 6609.12 | 0.78 | 3.50 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 138373.22 | 106519.70 | 31853.52 | 0.77 | 3.23 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21405.98 | 17063.13 | 4342.85 | 0.80 | 3.50 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17947.75 | 14179.98 | 3767.77 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 28245.7 | 10.13 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 132329.4 | 11.52 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20396.7 | 89.01 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17117.6 | 127.86 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 57266.94 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 43840.34 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 227472.09 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 34661.83 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29450.54 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.57 | 622.50 | 2.49 | 2729.58 | 1094.51 | 1.00 | 1.24 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.57 | 622.50 | 1.68 | 1836.42 | 1094.51 | 1.00 | 1.31 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.59 | 1110.54 | 7.70 | 14462.55 | 1877.50 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.29 | 1468.15 | 1140.11 | 1.00 | 1.31 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.55 | 622.50 | 1.06 | 1207.28 | 1140.11 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 18965.45 | 22758.54 | 59.91 | 1.351 | 1.621 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00994 | 21.70 | 0.00879 | 0.232 | 0.00 |
CORE_RETAIL | 87110.00 | 104532.00 | 65.31 | 6.226 | 7.471 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.89 | 0.00973 | 21.70 | 0.00879 | 1.890 | 0.00 |
POINT_OF_SALE | 14415.37 | 17298.44 | 114.70 | 1.073 | 1.288 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00887 | 29.05 | 0.00879 | 0.178 | 0.00 |
FRONT_RETAIL | 11853.88 | 14224.66 | 94.32 | 0.882 | 1.059 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 23.89 | 23.89 | 0.00895 | 29.14 | 0.00879 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.52 | 100.00 | 0.00001 | 29.40 | 0.00879 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20200.25 | 24240.30 | 63.81 | 0.859 | 1.031 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00728 | -4.20 | 0.00269 | 0.232 | 0.00 |
CORE_RETAIL | 49720.99 | 59665.19 | 37.28 | 2.078 | 2.494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00726 | -4.20 | 0.00269 | 1.890 | 0.00 |
POINT_OF_SALE | 9937.72 | 11925.26 | 79.07 | 0.425 | 0.510 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_RETAIL | 9933.02 | 11919.62 | 79.04 | 0.425 | 0.510 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_ENTRY | 47686.43 | 57223.72 | 4768.64 | 2.078 | 2.494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.03 | 0.00574 | -4.20 | 0.00269 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.68 | 1.68 | 1.03 | 1.03 | 1.6779 | 1.6208 | 1.6779 | 0.9660 | 1.0000 |
PSZ-AC:2 | 7.70 | 7.70 | 2.49 | 2.49 | 7.7031 | 7.4707 | 7.7031 | 0.9698 | 1.0000 |
PSZ-AC:3 | 1.29 | 1.29 | 0.51 | 0.51 | 1.2877 | 1.2877 | 1.2877 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.06 | 1.06 | 0.51 | 0.51 | 1.0589 | 1.0589 | 1.0589 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 57266.938 | 57266.938 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 57266.94 | 57266.94 | 2.493893 | 20.89 | 12.49 | 0.00572039 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.03 | 0.00573771 | 36.6308 | 57223.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 29561.760 | 0.000 | 1.677850 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 29561.76 | 26143.11 | 1.677850 | 24.71 | 17.06 | 0.00919824 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 13.8014 | 23.89 | 0.00994428 | 53.0113 | 18965.45 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 43840.335 | 43840.335 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43840.34 | 43840.34 | 1.677853 | 15.27 | 10.70 | 0.00625187 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 13.8014 | 21.11 | 0.00728318 | 46.1579 | 20200.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 138373.220 | 0.000 | 7.703100 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 138373.22 | 125026.17 | 7.703100 | 25.32 | 17.19 | 0.00909604 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 24.5383 | 23.89 | 0.00973338 | 51.9041 | 81444.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 227472.086 | 227472.086 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 227472.09 | 227472.09 | 7.703097 | 1.85 | 1.03 | 0.00379679 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 24.5383 | 21.11 | 0.00726236 | 46.0248 | 49720.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 21405.980 | 0.000 | 1.287730 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21405.98 | 20034.60 | 1.287730 | 24.61 | 16.75 | 0.00886303 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 13.8314 | 23.89 | 0.00887387 | 47.3768 | 14410.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 34661.833 | 34661.833 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34661.83 | 34661.83 | 1.287730 | 12.13 | 8.86 | 0.00582985 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 13.8314 | 21.11 | 0.00751554 | 47.6117 | 9937.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 17947.750 | 0.000 | 1.058920 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17947.75 | 16624.94 | 1.058920 | 24.77 | 16.86 | 0.00892694 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 16.8200 | 23.89 | 0.00895374 | 47.7972 | 11853.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 29450.540 | 29450.540 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29450.54 | 29450.54 | 1.058917 | 12.13 | 8.86 | 0.00582867 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 16.8201 | 21.11 | 0.00751498 | 47.6082 | 9933.02 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 57266.938 | 57266.938 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 2.493893 | 2.96022851 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 57266.94 | 57266.94 | 1.0000 | 2.96022851 | 2.493893 | 20.89 | 12.49 | 0.00572039 | 35514.7 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 57266.94 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.04 | 0.00573771 | 21.03 | 0.00573771 | 36.6308 | 57223.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29561.760 | 0.000 | 1.677850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.9391 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 29561.76 | 26143.11 | 1.0000 | 1.99159249 | 1.677850 | 24.71 | 17.06 | 0.00919824 | 48251.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29561.76 | 29.40 | 0.00879438 | 18.30 | 0.23156651 | 13.8014 | 23.89 | 0.00926857 | 23.89 | 0.00994428 | 53.0113 | 18965.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43840.335 | 43840.335 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.677853 | 1.99159566 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43840.34 | 43840.34 | 1.0000 | 1.99159566 | 1.677853 | 15.27 | 10.70 | 0.00625187 | 31158.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43840.34 | -4.20 | 0.00269032 | -4.20 | 0.23156651 | 13.8014 | 20.91 | 0.00728318 | 21.11 | 0.00728318 | 46.1579 | 20200.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 138373.220 | 0.000 | 7.703100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7491 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 138373.22 | 125026.17 | 1.0000 | 9.14350870 | 7.703100 | 25.32 | 17.19 | 0.00909604 | 48619.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 138373.22 | 29.40 | 0.00879438 | 18.30 | 1.89021192 | 24.5383 | 23.89 | 0.00920191 | 23.89 | 0.00973338 | 51.9041 | 81444.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 227472.086 | 227472.086 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.703097 | 9.14350559 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 227472.09 | 227472.09 | 1.0000 | 9.14350559 | 7.703097 | 1.85 | 1.03 | 0.00379679 | 11367.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 227472.09 | -4.20 | 0.00269032 | -4.20 | 1.89021192 | 24.5383 | 20.80 | 0.00726236 | 21.11 | 0.00726236 | 46.0248 | 49720.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21405.980 | 0.000 | 1.287730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3159 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21405.98 | 20034.60 | 1.0000 | 1.52852364 | 1.287730 | 24.61 | 16.75 | 0.00886303 | 47305.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21405.98 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 13.8314 | 23.89 | 0.00887405 | 23.89 | 0.00887387 | 47.3768 | 14410.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34661.833 | 34661.833 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.287730 | 1.52852335 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34661.83 | 34661.83 | 1.0000 | 1.52852335 | 1.287730 | 12.13 | 8.86 | 0.00582985 | 26905.2 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34661.83 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 13.8314 | 20.91 | 0.00751554 | 21.11 | 0.00751554 | 47.6117 | 9937.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17947.750 | 0.000 | 1.058920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4347 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 17947.75 | 16624.94 | 1.0000 | 1.25692828 | 1.058920 | 24.77 | 16.86 | 0.00892694 | 47628.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17947.75 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 16.8200 | 23.89 | 0.00895374 | 23.89 | 0.00895374 | 47.7972 | 11853.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29450.540 | 29450.540 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.058917 | 1.25692414 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29450.54 | 29450.54 | 1.0000 | 1.25692414 | 1.058917 | 12.13 | 8.86 | 0.00582867 | 26897.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29450.54 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 16.8201 | 20.91 | 0.00751498 | 21.11 | 0.00751498 | 47.6082 | 9933.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.68 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.70 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.29 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.06 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 1251.50 | 3675.00 | 875.33 |
CORE_RETAIL | 1335.33 | 2561.67 | 158.50 |
POINT_OF_SALE | 1558.33 | 2554.67 | 339.67 |
FRONT_RETAIL | 1540.00 | 3084.67 | 631.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 2231.67 | 3680.50 | 908.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 29.67 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 2.17 | 0.00 | 0.00 |
POINT_OF_SALE | 13.50 | 0.67 | 0.00 | 0.00 |
FRONT_RETAIL | 24.17 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 30.83 | 2.50 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.684 | 0.049 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 1.093 | 0.009 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 1.569 | 0.053 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 1.196 | 0.053 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.355 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.688 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.687 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.687 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1204.87 | 3648.35 | 05-MAR-06:50 | 104100.01 | 10-AUG-15:00 |
Electricity:Building | 670.39 | 3648.35 | 01-JAN-00:10 | 44155.79 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 90.98 | 618.37 | 01-JAN-00:10 | 5639.90 | 02-JAN-09:10 |
InteriorLights:Electricity | 475.23 | 1853.18 | 01-JAN-00:10 | 33384.75 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 40.98 | 158.51 | 01-JAN-00:10 | 2880.76 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 475.23 | 1853.18 | 01-JAN-00:10 | 33384.75 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 447.93 | 2194.53 | 01-JAN-00:10 | 30196.29 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 363.63 | 1419.09 | 01-JAN-00:10 | 25543.68 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 87.19 | 620.53 | 01-JAN-00:10 | 5327.81 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 34.26 | 133.72 | 01-JAN-00:10 | 2406.93 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 42.21 | 206.79 | 01-JAN-00:10 | 2845.33 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 34.26 | 133.72 | 01-JAN-00:10 | 2406.93 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 2.08 | 8.14 | 01-JAN-00:10 | 146.46 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 2.08 | 8.14 | 01-JAN-00:10 | 146.46 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1204.87 | 3648.35 | 09-APR-18:10 | 104100.01 | 10-AUG-15:00 |
ElectricityPurchased:Plant | 1204.87 | 3648.35 | 09-APR-18:10 | 104100.01 | 10-AUG-15:00 |
Cogeneration:ElectricityPurchased | 1204.87 | 3648.35 | 09-APR-18:10 | 104100.01 | 10-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1204.87 | 3648.35 | 09-APR-18:10 | 104100.01 | 10-AUG-15:00 |
ElectricityNet:Plant | 1204.87 | 3648.35 | 09-APR-18:10 | 104100.01 | 10-AUG-15:00 |
Cogeneration:ElectricityNet | 1204.87 | 3648.35 | 09-APR-18:10 | 104100.01 | 10-AUG-15:00 |
Electricity:HVAC | 461.65 | 0.00 | 01-JAN-00:10 | 59944.22 | 10-AUG-15:00 |
Fans:Electricity | 399.20 | 0.00 | 01-JAN-00:10 | 21703.98 | 01-JAN-08:10 |
General:Fans:Electricity | 399.20 | 0.00 | 01-JAN-00:10 | 21703.98 | 01-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 62.45 | 0.00 | 01-JAN-00:10 | 40969.82 | 10-AUG-15:00 |
ExteriorLights:Electricity | 72.84 | 0.00 | 01-JAN-08:10 | 4644.36 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 72.84 | 0.00 | 01-JAN-08:10 | 4644.36 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 331.21 | 1862.00 | 20-JUL-07:10 | 181120.43 | 20-FEB-07:10 |
Gas:Plant | 95.17 | 1862.00 | 12-JAN-05:10 | 5085.06 | 14-FEB-12:40 |
WaterSystems:Gas | 95.17 | 1862.00 | 12-JAN-05:10 | 5085.06 | 14-FEB-12:40 |
Water Heater:WaterSystems:Gas | 95.17 | 1862.00 | 12-JAN-05:10 | 5085.06 | 14-FEB-12:40 |
Gas:HVAC | 236.04 | 0.00 | 01-JAN-00:10 | 176687.71 | 20-FEB-07:10 |
Heating:Gas | 236.04 | 0.00 | 01-JAN-00:10 | 176687.71 | 20-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 14-SEP-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1076.09 | 0.00 | 01-JAN-00:10 | 285942.00 | 19-FEB-07:10 |
EnergyTransfer:Building | 678.46 | 0.00 | 01-JAN-00:10 | 144637.54 | 19-FEB-07:10 |
EnergyTransfer:Zone:BACK_SPACE | 63.62 | 0.00 | 01-JAN-00:10 | 38941.96 | 19-FEB-07:10 |
Heating:EnergyTransfer | 172.75 | 0.00 | 01-JAN-00:10 | 144637.54 | 19-FEB-07:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 18.69 | 0.00 | 01-JAN-00:10 | 38941.96 | 19-FEB-07:10 |
Cooling:EnergyTransfer | 505.72 | 0.00 | 01-JAN-00:10 | 82594.13 | 10-AUG-14:30 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 44.93 | 0.00 | 01-JAN-00:10 | 11846.97 | 10-AUG-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 387.60 | 0.00 | 01-JAN-00:10 | 75188.84 | 20-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 17.12 | 0.00 | 01-JAN-00:10 | 75188.84 | 20-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 370.48 | 0.00 | 01-JAN-00:10 | 68121.60 | 09-AUG-04:50 |
EnergyTransfer:Zone:POINT_OF_SALE | 61.56 | 0.00 | 01-JAN-00:10 | 17342.70 | 19-FEB-07:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 4.44 | 0.00 | 01-JAN-00:10 | 17342.70 | 19-FEB-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 57.12 | 0.00 | 01-JAN-00:10 | 10889.58 | 14-SEP-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 41.44 | 0.00 | 01-JAN-00:10 | 17868.43 | 19-FEB-07:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 8.25 | 0.00 | 01-JAN-00:10 | 17868.43 | 19-FEB-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 33.19 | 0.00 | 01-JAN-00:10 | 8796.98 | 14-SEP-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 124.25 | 0.00 | 01-JAN-00:10 | 39544.96 | 18-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 124.25 | 0.00 | 01-JAN-00:10 | 39544.96 | 18-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 31.35 | 26-DEC-05:10 |
EnergyTransfer:HVAC | 397.63 | 0.00 | 01-JAN-00:10 | 141350.17 | 20-FEB-07:10 |
HeatingCoils:EnergyTransfer | 188.83 | 0.00 | 01-JAN-00:10 | 141350.17 | 20-FEB-07:10 |
CoolingCoils:EnergyTransfer | 208.79 | 0.00 | 01-JAN-00:10 | 135147.78 | 10-AUG-14:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 18.690 | -44.930 | 0.000 | 0.000 | 39.151 | 40.985 | 49.992 | 0.000 | 0.000 | 0.073 | 0.001 | 0.000 | 0.000 | 0.000 | -26.071 | -77.889 |
CORE_RETAIL | 0.000 | 0.000 | 17.121 | -370.482 | 0.000 | 0.000 | 162.552 | 363.635 | 84.299 | 6.701 | 0.000 | 0.059 | 0.004 | 0.000 | -6.172 | 0.000 | -24.064 | -233.649 |
POINT_OF_SALE | 0.000 | 0.000 | 4.442 | -57.116 | 0.000 | 0.000 | 15.090 | 34.265 | 52.922 | 28.669 | 0.000 | 0.031 | 0.002 | 0.000 | -23.252 | 0.000 | -12.103 | -42.948 |
FRONT_RETAIL | 0.000 | 0.000 | 8.250 | -33.185 | 0.000 | 0.000 | 15.533 | 34.265 | 7.943 | 28.908 | 0.000 | 0.031 | 0.000 | 0.000 | -22.174 | 0.000 | -11.410 | -28.162 |
FRONT_ENTRY | 124.245 | -0.001 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.085 | 0.000 | 5.929 | 0.000 | 0.009 | 1.093 | 0.000 | -4.444 | 0.000 | -128.915 | -0.000 |
Total Facility | 124.245 | -0.001 | 48.504 | -505.713 | 0.000 | 0.000 | 232.327 | 475.233 | 195.156 | 70.207 | 0.000 | 0.203 | 1.100 | 0.000 | -56.044 | 0.000 | -202.563 | -382.648 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 10-AUG-04:01 | 0.00 | 0.00 | 0.00 | -27885.00 | 0.00 | 0.00 | 0.00 | 158.51 | 613.14 | 0.00 | 0.00 | 0.00 | 27794.23 | 0.00 | -0.00 | 0.00 | -680.88 | 0.00 |
CORE_RETAIL | 19-JUL-04:03 | 0.00 | 0.00 | 0.00 | -157140.86 | 0.00 | 0.00 | 0.00 | 1419.09 | 1033.91 | 0.00 | 0.00 | 0.00 | 155522.26 | 0.00 | -301.83 | 0.00 | -532.57 | 0.00 |
POINT_OF_SALE | 09-AUG-04:01 | 0.00 | 0.00 | 0.00 | -25014.23 | 0.00 | 0.00 | 0.00 | 133.72 | 649.09 | 0.00 | 0.00 | 0.00 | 25586.70 | 0.00 | -1116.09 | 0.00 | -239.19 | 0.00 |
FRONT_RETAIL | 09-AUG-04:01 | 0.00 | 0.00 | 0.00 | -20139.16 | 0.00 | 0.00 | 0.00 | 133.72 | 97.42 | 0.00 | 0.00 | 0.00 | 21205.56 | 0.00 | -1072.35 | 0.00 | -225.19 | 0.00 |
FRONT_ENTRY | 26-DEC-05:02 | 0.00 | -313.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 589.66 | 0.00 | -284.30 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-04:01 | 0.00 | 0.00 | 0.00 | -201376.07 | 0.00 | 0.00 | 0.00 | 1853.18 | 2393.56 | 0.00 | 0.00 | 0.00 | 201321.15 | 0.00 | -2178.23 | 0.00 | -2013.60 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 19-FEB-07:11 | 0.00 | 0.00 | 45230.60 | 0.00 | 0.00 | 0.00 | 0.00 | 158.51 | 459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4982.67 | -40866.29 |
CORE_RETAIL | 15-JAN-07:01 | 0.00 | 0.00 | 236107.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1419.09 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -513.61 | 0.00 | -1994.92 | -235793.48 |
POINT_OF_SALE | 19-FEB-07:11 | 0.00 | 0.00 | 35039.31 | 0.00 | 0.00 | 0.00 | 0.00 | 133.72 | 486.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1996.76 | 0.00 | -2307.13 | -31355.95 |
FRONT_RETAIL | 20-FEB-07:11 | 0.00 | 0.00 | 29922.80 | 0.00 | 0.00 | 0.00 | 0.00 | 133.72 | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1601.17 | 0.00 | -1197.17 | -27331.23 |
FRONT_ENTRY | 18-FEB-18:00 | 39543.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 58.20 | 0.00 | -383.37 | 0.00 | -39364.46 | 0.00 |
Total Facility | 17-JAN-05:01 | 7944.31 | 0.00 | 345007.88 | 0.00 | 0.00 | 0.00 | 0.00 | 1853.18 | 2393.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3221.27 | 0.00 | -3820.49 | -350157.18 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6208 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6779 | 0.1380 | 1.0000 | 0.2316 | 0.1380 | ||
PSZ-AC:2 | 7.4707 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.7031 | 0.2454 | 1.0000 | 1.8902 | 0.2454 | ||
PSZ-AC:3 | 1.2877 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2877 | 0.1383 | 1.0000 | 0.1781 | 0.1383 | ||
PSZ-AC:4 | 1.0589 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0589 | 0.1682 | 1.0000 | 0.1781 | 0.1682 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6208 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6208 | 1.0000 | 1.0000 | 0.2316 | 0.1429 | ||
PSZ-AC:2 | 7.4707 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.4707 | 1.0000 | 1.0000 | 1.8902 | 0.2530 | ||
PSZ-AC:3 | 1.2877 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2877 | 1.0000 | 1.0000 | 0.1781 | 0.1383 | ||
PSZ-AC:4 | 1.0589 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0589 | 1.0000 | 1.0000 | 0.1781 | 0.1682 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6208 | 1.6208 | 1.6208 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.4707 | 7.4707 | 7.4707 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2877 | 1.2877 | 1.2877 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0589 | 1.0589 | 1.0589 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6208 | 1.6779 | 1.6208 | 1.6208 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.4707 | 7.7031 | 7.4707 | 7.4707 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2877 | 1.2877 | 1.2877 | 1.2877 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0589 | 1.0589 | 1.0589 | 1.0589 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6208 | 1.6208 | 1.6208 | 0.2316 | 0.2245 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.4707 | 7.4707 | 7.4707 | 1.8902 | 0.7580 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2877 | 1.2877 | 1.2877 | 0.1781 | 0.3493 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0589 | 1.0589 | 1.0589 | 0.1781 | 0.3495 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6208 | 1.6208 | 1.6208 | 1.6208 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.4707 | 7.4707 | 7.4707 | 7.4707 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2877 | 1.2877 | 1.2877 | 1.2877 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0589 | 1.0589 | 1.0589 | 1.0589 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:04
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 236.04 | 176687.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 62.45 | 40969.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 475.23 | 33384.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.84 | 4644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 399.20 | 21703.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 95.17 | 5085.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1204.87 |
Natural Gas | 0.00 | 331.21 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1536.08 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 207.16 |
Space Heating | 0.00 |
Space Cooling | 27.22 |
Fans (All) | 174.02 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 525.23 |
Subtotal | 525.23 |
Natural Gas [MJ/m2] | |
Space Heating | 102.89 |
Service Water Heating | 41.49 |
Miscellaneous (All) | 144.38 |
Subtotal | 144.38 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.94 |
Space Heating | 15.37 |
Space Cooling | 4.07 |
Fans (All) | 25.99 |
Service Water Heating | 6.20 |
Receptacle Equipment | 12.70 |
Miscellaneous | 4.74 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3641. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2009
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.647956E+11 |
February | 0.000 | 0.432146E+11 |
March | 0.000 | 0.199305E+11 |
April | 0.000 | 0.977617E+10 |
May | 0.000 | 0.517000E+10 |
June | 0.000 | 0.195816E+10 |
July | 0.000 | 0.520141E+09 |
August | 0.000 | 0.272891E+09 |
September | 0.000 | 0.280685E+10 |
October | 0.000 | 0.814498E+10 |
November | 0.000 | 0.278529E+11 |
December | 0.000 | 0.515968E+11 |
Annual Sum or Average | 0.236040E+12 | |
Minimum of Months | 0.000 | 0.272891E+09 |
Maximum of Months | 0.000 | 0.647956E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643608E+09 | 2890.43 | 05-JAN-11:10 | 2.30 | 2.30 | 0.166002E+10 | 2127.25 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.834169E+09 | 3280.19 | 13-FEB-16:10 | 0.60 | 0.13 | 0.158210E+10 | 2451.24 | 27-FEB-15:09 | 19.90 | 12.20 |
March | 0.179226E+10 | 2783.27 | 22-MAR-10:30 | 4.45 | 3.83 | 0.194226E+10 | 2451.24 | 18-MAR-15:39 | 20.40 | 10.37 |
April | 0.247448E+10 | 6974.23 | 27-APR-15:00 | 27.20 | 17.27 | 0.200190E+10 | 2451.25 | 01-APR-12:30 | 21.95 | 13.07 |
May | 0.450187E+10 | 7967.22 | 15-MAY-15:00 | 23.30 | 12.59 | 0.218664E+10 | 2451.31 | 04-MAY-14:20 | 24.07 | 15.16 |
June | 0.642592E+10 | 9767.44 | 28-JUN-15:00 | 26.10 | 15.52 | 0.219199E+10 | 2451.31 | 26-JUN-14:50 | 20.60 | 14.29 |
July | 0.837251E+10 | 11092.68 | 24-JUL-14:40 | 30.20 | 18.54 | 0.218586E+10 | 2451.36 | 22-JUL-14:20 | 24.80 | 16.69 |
August | 0.881705E+10 | 27887.17 | 10-AUG-04:01 | 17.90 | 14.45 | 0.227920E+10 | 2451.33 | 09-AUG-14:09 | 28.42 | 18.30 |
September | 0.568052E+10 | 9171.71 | 14-SEP-15:00 | 23.90 | 16.94 | 0.214347E+10 | 2451.29 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.273241E+10 | 5672.51 | 04-OCT-15:00 | 21.70 | 11.47 | 0.206398E+10 | 2451.25 | 07-OCT-10:20 | 14.27 | 10.89 |
November | 0.170751E+10 | 4695.37 | 04-NOV-14:20 | 21.10 | 15.93 | 0.175654E+10 | 2451.28 | 04-NOV-15:00 | 20.00 | 15.90 |
December | 0.947303E+09 | 2735.38 | 06-DEC-15:10 | 4.72 | 4.12 | 0.167300E+10 | 2072.43 | 30-DEC-16:10 | 8.35 | 6.85 |
Annual Sum or Average | 0.449296E+11 | 0.236669E+11 | ||||||||
Minimum of Months | 0.643608E+09 | 2735.38 | 0.60 | 0.13 | 0.158210E+10 | 2072.43 | 8.35 | 6.85 | ||
Maximum of Months | 0.881705E+10 | 27887.17 | 30.20 | 18.54 | 0.227920E+10 | 2451.36 | 28.42 | 18.30 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171721E+11 | 27325.74 | 21-JAN-07:03 | -0.6 | -0.6 | 0.712539E+10 | 10326.27 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.171874E+11 | 34091.03 | 09-FEB-07:03 | -0.7 | -1.1 | 0.696238E+10 | 10327.09 | 25-FEB-12:20 | 15.00 | 12.12 |
March | 0.244216E+11 | 35133.35 | 01-MAR-07:03 | -0.1 | -1.6 | 0.880192E+10 | 10327.01 | 18-MAR-15:39 | 20.40 | 10.37 |
April | 0.283707E+11 | 103189.90 | 28-APR-05:01 | 11.10 | 9.92 | 0.880103E+10 | 10327.50 | 27-APR-14:09 | 26.28 | 16.89 |
May | 0.370891E+11 | 151241.32 | 05-MAY-04:03 | 13.22 | 10.57 | 0.933110E+10 | 10327.23 | 08-MAY-14:50 | 17.62 | 14.13 |
June | 0.429198E+11 | 151603.40 | 22-JUN-04:03 | 11.60 | 10.67 | 0.926443E+10 | 10327.54 | 26-JUN-14:50 | 20.60 | 14.29 |
July | 0.486137E+11 | 157156.98 | 19-JUL-04:03 | 13.43 | 10.13 | 0.921411E+10 | 10327.69 | 22-JUL-14:30 | 25.00 | 16.77 |
August | 0.496869E+11 | 152022.87 | 09-AUG-04:01 | 14.93 | 12.08 | 0.960833E+10 | 10327.55 | 09-AUG-14:00 | 28.00 | 18.46 |
September | 0.377526E+11 | 150015.93 | 15-SEP-04:02 | 11.70 | 11.34 | 0.906133E+10 | 10327.67 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.271063E+11 | 36450.06 | 04-OCT-14:30 | 21.40 | 11.43 | 0.897651E+10 | 10327.10 | 07-OCT-10:20 | 14.27 | 10.89 |
November | 0.215371E+11 | 32001.90 | 11-NOV-09:03 | 0.78 | 0.55 | 0.767834E+10 | 10327.21 | 04-NOV-11:50 | 18.72 | 15.12 |
December | 0.186254E+11 | 31948.71 | 06-DEC-07:03 | 0.18 | -0.1 | 0.727379E+10 | 9939.09 | 02-DEC-14:50 | 11.78 | 5.55 |
Annual Sum or Average | 0.370483E+12 | 0.102099E+12 | ||||||||
Minimum of Months | 0.171721E+11 | 27325.74 | -0.7 | -1.6 | 0.696238E+10 | 9939.09 | 11.78 | 5.55 | ||
Maximum of Months | 0.496869E+11 | 157156.98 | 21.40 | 12.08 | 0.960833E+10 | 10327.69 | 28.00 | 18.46 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196800E+10 | 3994.73 | 20-JAN-13:30 | 6.70 | 4.71 | 0.711853E+09 | 973.09 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.236937E+10 | 6559.44 | 27-FEB-15:10 | 19.90 | 12.20 | 0.701103E+09 | 973.10 | 25-FEB-12:20 | 15.00 | 12.12 |
March | 0.349815E+10 | 7065.81 | 18-MAR-13:50 | 19.53 | 10.60 | 0.860685E+09 | 973.09 | 31-MAR-14:09 | 9.32 | 7.67 |
April | 0.434972E+10 | 9382.07 | 27-APR-13:30 | 26.10 | 16.53 | 0.834343E+09 | 973.16 | 29-APR-15:20 | 21.47 | 14.97 |
May | 0.539599E+10 | 8774.75 | 05-MAY-05:01 | 12.98 | 10.75 | 0.878314E+09 | 973.18 | 05-MAY-14:39 | 24.40 | 16.86 |
June | 0.614158E+10 | 7732.19 | 28-JUN-15:00 | 26.10 | 15.52 | 0.872523E+09 | 973.16 | 26-JUN-14:50 | 20.60 | 14.29 |
July | 0.750214E+10 | 22678.26 | 24-JUL-04:01 | 16.52 | 13.36 | 0.868245E+09 | 973.19 | 01-JUL-14:09 | 20.00 | 14.38 |
August | 0.857743E+10 | 25016.36 | 09-AUG-04:01 | 14.93 | 12.08 | 0.905373E+09 | 973.19 | 25-AUG-14:00 | 26.40 | 18.81 |
September | 0.723629E+10 | 24441.19 | 15-SEP-04:02 | 11.70 | 11.34 | 0.854544E+09 | 973.22 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.508810E+10 | 10886.39 | 04-OCT-14:10 | 21.20 | 11.40 | 0.854420E+09 | 973.12 | 07-OCT-15:50 | 16.97 | 12.09 |
November | 0.276662E+10 | 9053.24 | 04-NOV-14:00 | 21.10 | 15.93 | 0.765587E+09 | 973.15 | 04-NOV-11:09 | 17.98 | 14.86 |
December | 0.222321E+10 | 5259.59 | 05-DEC-12:40 | 10.40 | 6.14 | 0.740222E+09 | 973.09 | 30-DEC-13:50 | 9.82 | 7.53 |
Annual Sum or Average | 0.571166E+11 | 0.984721E+10 | ||||||||
Minimum of Months | 0.196800E+10 | 3994.73 | 6.70 | 4.71 | 0.701103E+09 | 973.09 | 9.32 | 7.53 | ||
Maximum of Months | 0.857743E+10 | 25016.36 | 26.10 | 16.53 | 0.905373E+09 | 973.22 | 26.40 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.689141E+09 | 3143.60 | 07-JAN-13:10 | 0.97 | 0.44 | 0.662857E+09 | 890.05 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.114905E+10 | 4198.77 | 27-FEB-15:10 | 19.90 | 12.20 | 0.643478E+09 | 973.09 | 27-FEB-15:00 | 19.40 | 12.41 |
March | 0.192499E+10 | 4591.33 | 01-MAR-15:10 | 13.12 | 7.27 | 0.789010E+09 | 973.09 | 18-MAR-15:39 | 20.40 | 10.37 |
April | 0.241876E+10 | 7073.82 | 27-APR-13:30 | 26.10 | 16.53 | 0.792155E+09 | 973.15 | 29-APR-15:09 | 21.83 | 15.10 |
May | 0.301171E+10 | 5530.54 | 15-MAY-13:20 | 22.97 | 13.69 | 0.855547E+09 | 973.11 | 04-MAY-14:20 | 24.07 | 15.16 |
June | 0.357155E+10 | 5601.36 | 28-JUN-15:00 | 26.10 | 15.52 | 0.864513E+09 | 973.14 | 26-JUN-14:50 | 20.60 | 14.29 |
July | 0.471226E+10 | 7408.76 | 31-JUL-13:20 | 27.57 | 18.45 | 0.865982E+09 | 973.17 | 22-JUL-14:39 | 25.20 | 16.84 |
August | 0.567262E+10 | 20140.70 | 09-AUG-04:01 | 14.93 | 12.08 | 0.903192E+09 | 973.15 | 29-AUG-14:09 | 29.90 | 19.92 |
September | 0.462605E+10 | 19817.76 | 15-SEP-04:02 | 11.70 | 11.34 | 0.845546E+09 | 973.20 | 09-SEP-14:09 | 21.20 | 15.01 |
October | 0.302098E+10 | 8647.39 | 04-OCT-14:10 | 21.20 | 11.40 | 0.813605E+09 | 973.10 | 07-OCT-15:39 | 17.23 | 12.15 |
November | 0.145016E+10 | 6519.66 | 04-NOV-14:00 | 21.10 | 15.93 | 0.686479E+09 | 973.12 | 04-NOV-11:39 | 18.53 | 15.05 |
December | 0.938279E+09 | 2964.95 | 06-DEC-12:00 | 3.30 | 3.23 | 0.681798E+09 | 973.10 | 02-DEC-12:20 | 12.20 | 6.04 |
Annual Sum or Average | 0.331855E+11 | 0.940416E+10 | ||||||||
Minimum of Months | 0.689141E+09 | 2964.95 | 0.97 | 0.44 | 0.643478E+09 | 890.05 | 12.20 | 6.04 | ||
Maximum of Months | 0.567262E+10 | 20140.70 | 27.57 | 18.45 | 0.903192E+09 | 973.20 | 29.90 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 291184.56 | 252.88 | 15-JAN-07:02 | -3.4 | -4.3 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 111386.48 | 233.54 | 21-FEB-05:02 | 1.70 | 0.78 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 18613.17 | 214.25 | 06-MAR-05:02 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 3496.53 | 58.28 | 11-APR-04:02 | 5.10 | 4.28 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 40887.41 | 180.87 | 24-NOV-05:02 | 2.70 | 2.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 207231.32 | 313.49 | 26-DEC-05:02 | -0.6 | -0.6 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 672799.48 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.4 | -4.3 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 291184.56 | 313.49 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536797E+10 | 45210.34 | 08-JAN-07:42 | -3.4 |
February | 0.388882E+10 | 45230.69 | 19-FEB-07:11 | -5.0 |
March | 0.176908E+10 | 44842.47 | 06-MAR-05:42 | 6.70 |
April | 0.740292E+09 | 44651.08 | 11-APR-04:01 | 5.10 |
May | 0.219841E+09 | 35067.53 | 18-MAY-04:02 | 6.52 |
June | 0.159318E+09 | 1803.00 | 15-JUN-05:53 | 9.40 |
July | 0.104369E+09 | 1963.82 | 24-JUL-05:05 | 15.87 |
August | 82280656.98 | 2115.95 | 26-AUG-05:04 | 14.73 |
September | 0.158821E+09 | 1820.28 | 27-SEP-05:43 | 8.12 |
October | 0.336896E+09 | 44028.59 | 30-OCT-04:02 | 7.20 |
November | 0.182157E+10 | 44830.47 | 30-NOV-05:42 | 5.60 |
December | 0.404107E+10 | 44946.55 | 23-DEC-05:42 | 3.80 |
Annual Sum or Average | 0.186903E+11 | |||
Minimum of Months | 82280656.98 | 1803.00 | -5.0 | |
Maximum of Months | 0.536797E+10 | 45230.69 | 15.87 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458103E+10 | 236107.49 | 15-JAN-07:01 | -3.4 |
February | 0.301530E+10 | 236008.30 | 06-FEB-05:01 | 4.32 |
March | 0.149564E+10 | 235972.39 | 06-MAR-05:01 | 6.70 |
April | 0.108180E+10 | 16065.25 | 28-APR-05:03 | 11.10 |
May | 0.392617E+09 | 16031.50 | 05-MAY-05:03 | 12.98 |
June | 97349190.14 | 16541.91 | 29-JUN-05:03 | 12.80 |
July | 0.138758E+09 | 16803.43 | 25-JUL-05:03 | 13.90 |
August | 0.134283E+09 | 16836.43 | 01-AUG-05:03 | 11.30 |
September | 0.148713E+09 | 16607.46 | 16-SEP-05:02 | 11.02 |
October | 0.854456E+09 | 14270.55 | 17-OCT-05:53 | 8.30 |
November | 0.176763E+10 | 236044.07 | 24-NOV-05:01 | 2.70 |
December | 0.341386E+10 | 236052.82 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.171214E+11 | |||
Minimum of Months | 97349190.14 | 14270.55 | -3.4 | |
Maximum of Months | 0.458103E+10 | 236107.49 | 13.90 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132375E+10 | 34645.50 | 15-JAN-07:01 | -3.4 |
February | 0.774339E+09 | 35039.37 | 19-FEB-07:11 | -5.0 |
March | 0.347102E+09 | 34606.13 | 06-MAR-05:01 | 6.70 |
April | 0.195020E+09 | 34600.68 | 11-APR-04:01 | 5.10 |
May | 0.120427E+09 | 9864.03 | 18-MAY-04:02 | 6.52 |
June | 67722511.98 | 1498.97 | 29-JUN-05:03 | 12.80 |
July | 22432695.36 | 1713.58 | 20-JUL-05:03 | 13.40 |
August | 21950344.92 | 1864.92 | 13-AUG-07:02 | 18.17 |
September | 43091169.06 | 1811.67 | 10-SEP-07:03 | 12.57 |
October | 0.124158E+09 | 15959.73 | 28-OCT-04:02 | 7.88 |
November | 0.423822E+09 | 34626.96 | 24-NOV-05:01 | 2.70 |
December | 0.978226E+09 | 34628.32 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.444204E+10 | |||
Minimum of Months | 21950344.92 | 1498.97 | -5.0 | |
Maximum of Months | 0.132375E+10 | 35039.37 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235592E+10 | 29880.25 | 16-JAN-07:12 | -1.5 |
February | 0.140356E+10 | 29922.77 | 20-FEB-07:11 | 0.00 |
March | 0.713633E+09 | 29589.29 | 06-MAR-05:01 | 6.70 |
April | 0.372415E+09 | 29586.60 | 11-APR-04:01 | 5.10 |
May | 0.148542E+09 | 25798.69 | 18-MAY-04:02 | 6.52 |
June | 0.100440E+09 | 6720.37 | 14-JUN-05:02 | 10.00 |
July | 66544351.70 | 1282.56 | 24-JUL-05:05 | 15.87 |
August | 48765114.41 | 1304.47 | 08-AUG-05:04 | 15.38 |
September | 72688230.81 | 1417.34 | 15-SEP-05:03 | 11.60 |
October | 0.197942E+09 | 28945.12 | 28-OCT-04:02 | 7.88 |
November | 0.877311E+09 | 29605.08 | 24-NOV-05:01 | 2.70 |
December | 0.189257E+10 | 29605.89 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.825032E+10 | |||
Minimum of Months | 48765114.41 | 1282.56 | -1.5 | |
Maximum of Months | 0.235592E+10 | 29922.77 | 15.87 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214454E+11 | 39207.78 | 07-JAN-12:10 | -0.4 |
February | 0.164659E+11 | 39544.96 | 18-FEB-18:00 | -0.6 |
March | 0.138677E+11 | 28688.88 | 05-MAR-12:10 | 5.10 |
April | 0.934548E+10 | 24546.85 | 18-APR-17:00 | 7.20 |
May | 0.673911E+10 | 22174.62 | 23-MAY-17:00 | 8.30 |
June | 0.358285E+10 | 17584.12 | 13-JUN-11:05 | 11.28 |
July | 0.170010E+10 | 13470.34 | 12-JUL-11:05 | 13.98 |
August | 0.126303E+10 | 13995.13 | 01-AUG-11:04 | 13.62 |
September | 0.444943E+10 | 17058.70 | 17-SEP-11:05 | 11.88 |
October | 0.942484E+10 | 20370.42 | 31-OCT-17:00 | 9.40 |
November | 0.159521E+11 | 32486.09 | 12-NOV-18:00 | 3.30 |
December | 0.200092E+11 | 38734.93 | 26-DEC-12:10 | 0.27 |
Annual Sum or Average | 0.124245E+12 | |||
Minimum of Months | 0.126303E+10 | 13470.34 | -0.6 | |
Maximum of Months | 0.214454E+11 | 39544.96 | 13.98 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.343688E+10 | 2880.76 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.312713E+10 | 2880.76 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.356711E+10 | 2880.76 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.336554E+10 | 2880.76 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.350199E+10 | 2880.76 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.344215E+10 | 2880.76 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.342538E+10 | 2880.76 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.356711E+10 | 2880.76 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.336554E+10 | 2880.76 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.343688E+10 | 2880.76 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.332343E+10 | 2880.76 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.342538E+10 | 2880.76 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.409845E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.312713E+10 | 2880.76 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.356711E+10 | 2880.76 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.304941E+11 | 25543.68 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.277456E+11 | 25543.68 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.316486E+11 | 25543.68 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.298606E+11 | 25543.68 | 01-APR-09:09 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.310713E+11 | 25543.68 | 01-MAY-08:09 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.305400E+11 | 25543.68 | 01-JUN-08:09 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.303919E+11 | 25543.68 | 01-JUL-09:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.316486E+11 | 25543.68 | 01-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.298606E+11 | 25543.68 | 01-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.304941E+11 | 25543.68 | 02-OCT-08:09 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.294876E+11 | 25543.68 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.303919E+11 | 25543.68 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.363635E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.277456E+11 | 25543.68 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.316486E+11 | 25543.68 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.287339E+10 | 2406.93 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.261440E+10 | 2406.93 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.298218E+10 | 2406.93 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.281370E+10 | 2406.93 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.292778E+10 | 2406.93 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.287772E+10 | 2406.93 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.286376E+10 | 2406.93 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.298218E+10 | 2406.93 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.281370E+10 | 2406.93 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.287339E+10 | 2406.93 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.277855E+10 | 2406.93 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.286376E+10 | 2406.93 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.342645E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.261440E+10 | 2406.93 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.298218E+10 | 2406.93 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.287339E+10 | 2406.93 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.261440E+10 | 2406.93 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.298218E+10 | 2406.93 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.281370E+10 | 2406.93 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.292778E+10 | 2406.93 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.287772E+10 | 2406.93 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.286376E+10 | 2406.93 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.298218E+10 | 2406.93 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.281370E+10 | 2406.93 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.287339E+10 | 2406.93 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.277855E+10 | 2406.93 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.286376E+10 | 2406.93 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.342645E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.261440E+10 | 2406.93 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.298218E+10 | 2406.93 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.174840E+09 | 146.46 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.159081E+09 | 146.46 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.181459E+09 | 146.46 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.171207E+09 | 146.46 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.178149E+09 | 146.46 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.175103E+09 | 146.46 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.174254E+09 | 146.46 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.181459E+09 | 146.46 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.171207E+09 | 146.46 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.174840E+09 | 146.46 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.169069E+09 | 146.46 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.174254E+09 | 146.46 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.208492E+10 | ||||
Minimum of Months | 0.159081E+09 | 146.46 | 0.00 | 0.00 | |
Maximum of Months | 0.181459E+09 | 146.46 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.343688E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313575E+10 |
February | 0.479114E+10 | 0.312713E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266709E+10 |
March | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270146E+10 |
April | 0.518069E+10 | 0.336554E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3954672.26 | 0.256612E+10 |
May | 0.536353E+10 | 0.350199E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256700.37 | 0.211719E+10 |
June | 0.528933E+10 | 0.344215E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2205711.55 | 0.174977E+10 |
July | 0.525489E+10 | 0.342538E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22710261.95 | 0.140681E+10 |
August | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43356480.96 | 0.124596E+10 |
September | 0.518069E+10 | 0.336554E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 243826.29 | 0.100444E+10 |
October | 0.524694E+10 | 0.343688E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227715E+10 |
November | 0.504819E+10 | 0.332343E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257374E+10 |
December | 0.525489E+10 | 0.342538E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262560E+10 |
Annual Sum or Average | 0.628175E+11 | 0.409845E+11 | 0.499918E+11 | 72727653.38 | 0.260711E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.312713E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100444E+10 |
Maximum of Months | 0.548013E+10 | 0.356711E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43356480.96 | 0.313575E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.304941E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283763E+10 |
February | 0.201852E+11 | 0.277456E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243028E+10 |
March | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254703E+10 |
April | 0.218263E+11 | 0.298606E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3237298.67 | 0.243280E+10 |
May | 0.225967E+11 | 0.310713E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210310.54 | 0.197031E+10 |
June | 0.222841E+11 | 0.305400E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1805928.68 | 0.161861E+10 |
July | 0.221389E+11 | 0.303919E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18473275.74 | 0.128848E+10 |
August | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35422772.74 | 0.114178E+10 |
September | 0.218263E+11 | 0.298606E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199642.40 | 0.915674E+09 |
October | 0.221054E+11 | 0.304941E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212363E+10 |
November | 0.212681E+11 | 0.294876E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237685E+10 |
December | 0.221389E+11 | 0.303919E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238067E+10 |
Annual Sum or Average | 0.264651E+12 | 0.363635E+12 | 0.842987E+11 | 59349228.76 | 0.240637E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.277456E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915674E+09 |
Maximum of Months | 0.230879E+11 | 0.316486E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35422772.74 | 0.283763E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.287339E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141221E+10 |
February | 0.190200E+10 | 0.261440E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123635E+10 |
March | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128640E+10 |
April | 0.205665E+10 | 0.281370E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1713777.48 | 0.120155E+10 |
May | 0.212923E+10 | 0.292778E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111259.45 | 0.971331E+09 |
June | 0.209978E+10 | 0.287772E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 955920.10 | 0.800271E+09 |
July | 0.208610E+10 | 0.286376E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9639513.21 | 0.653958E+09 |
August | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18664065.80 | 0.593534E+09 |
September | 0.205665E+10 | 0.281370E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105414.94 | 0.474752E+09 |
October | 0.208295E+10 | 0.287339E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107976E+10 |
November | 0.200405E+10 | 0.277855E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119412E+10 |
December | 0.208610E+10 | 0.286376E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119860E+10 |
Annual Sum or Average | 0.249375E+11 | 0.342645E+11 | 0.529224E+11 | 31189950.97 | 0.121028E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.261440E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474752E+09 |
Maximum of Months | 0.217552E+10 | 0.298218E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18664065.80 | 0.141221E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.287339E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135166E+10 |
February | 0.190200E+10 | 0.261440E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117207E+10 |
March | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120479E+10 |
April | 0.205665E+10 | 0.281370E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1713708.46 | 0.112922E+10 |
May | 0.212923E+10 | 0.292778E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 111268.82 | 0.915432E+09 |
June | 0.209978E+10 | 0.287772E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 955838.74 | 0.754832E+09 |
July | 0.208610E+10 | 0.286376E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9701750.49 | 0.614881E+09 |
August | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18687526.41 | 0.557736E+09 |
September | 0.205665E+10 | 0.281370E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 105440.92 | 0.448678E+09 |
October | 0.208295E+10 | 0.287339E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101057E+10 |
November | 0.200405E+10 | 0.277855E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110930E+10 |
December | 0.208610E+10 | 0.286376E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114037E+10 |
Annual Sum or Average | 0.249375E+11 | 0.342645E+11 | 0.794328E+10 | 31275533.85 | 0.114095E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.261440E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448678E+09 |
Maximum of Months | 0.217552E+10 | 0.298218E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18687526.41 | 0.135166E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.174840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211769E+11 |
February | 0.00 | 0.159081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165086E+11 |
March | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142132E+11 |
April | 0.00 | 0.171207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551035.08 | 0.983676E+10 |
May | 0.00 | 0.178149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734220E+10 |
June | 0.00 | 0.175103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421281E+10 |
July | 0.00 | 0.174254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1962177.91 | 0.235976E+10 |
August | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6393583.75 | 0.190024E+10 |
September | 0.00 | 0.171207E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528747E+10 |
October | 0.00 | 0.174840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101291E+11 |
November | 0.00 | 0.169069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160840E+11 |
December | 0.00 | 0.174254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198642E+11 |
Annual Sum or Average | 0.00 | 0.208492E+10 | 8906796.74 | 0.128915E+12 | |||||
Minimum of Months | 0.00 | 0.159081E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190024E+10 |
Maximum of Months | 0.00 | 0.181459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6393583.75 | 0.211769E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2880.76 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5689.08 | 28-JAN-05:10 |
February | 5888.82 | 01-FEB-15:09 | 2880.76 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5367.01 | 19-FEB-08:00 |
March | 5888.82 | 01-MAR-15:09 | 2880.76 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5233.29 | 29-MAR-04:55 |
April | 5888.82 | 01-APR-10:09 | 2880.76 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.32 | 01-APR-16:00 | 4876.84 | 08-APR-04:05 |
May | 5888.82 | 01-MAY-14:09 | 2880.76 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 05-MAY-16:00 | 4809.15 | 17-MAY-20:05 |
June | 5888.82 | 01-JUN-14:09 | 2880.76 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.41 | 28-JUN-16:00 | 4684.12 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 2880.76 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 425.95 | 30-JUL-18:03 | 2534.49 | 02-JUL-04:00 |
August | 5888.82 | 01-AUG-14:09 | 2880.76 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 390.43 | 13-AUG-18:03 | 3563.78 | 11-AUG-04:00 |
September | 5888.82 | 01-SEP-14:09 | 2880.76 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 14-SEP-17:00 | 2460.56 | 18-SEP-23:00 |
October | 5888.82 | 02-OCT-14:09 | 2880.76 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 5080.35 | 31-OCT-20:03 |
November | 5888.82 | 01-NOV-14:09 | 2880.76 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6258.81 | 29-NOV-21:02 |
December | 5888.82 | 01-DEC-15:09 | 2880.76 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5287.55 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2460.56 | |||||
Maximum of Months | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 425.95 | 6258.81 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 25543.68 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 5104.68 | 12-JAN-24:00 |
February | 24809.68 | 01-FEB-15:09 | 25543.68 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4608.62 | 16-FEB-04:00 |
March | 24809.68 | 01-MAR-15:09 | 25543.68 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4475.25 | 28-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 25543.68 | 01-APR-09:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 172.19 | 01-APR-16:00 | 4912.96 | 07-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 25543.68 | 01-MAY-08:09 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 05-MAY-16:00 | 4227.70 | 17-MAY-20:10 |
June | 24809.68 | 01-JUN-14:09 | 25543.68 | 01-JUN-08:09 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.02 | 28-JUN-15:00 | 4776.87 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 25543.68 | 01-JUL-09:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 344.51 | 30-JUL-18:03 | 2465.34 | 02-JUL-04:00 |
August | 24809.68 | 01-AUG-14:09 | 25543.68 | 01-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 315.43 | 13-AUG-18:03 | 3378.55 | 11-AUG-04:00 |
September | 24809.68 | 01-SEP-14:09 | 25543.68 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 14-SEP-17:00 | 2359.24 | 18-SEP-23:00 |
October | 24809.68 | 02-OCT-14:09 | 25543.68 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4548.11 | 31-OCT-20:10 |
November | 24809.68 | 01-NOV-14:09 | 25543.68 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5183.42 | 29-NOV-21:10 |
December | 24809.68 | 01-DEC-15:09 | 25543.68 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4374.20 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2359.24 | |||||
Maximum of Months | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 344.51 | 5183.42 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2406.93 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2491.00 | 28-JAN-05:04 |
February | 2337.76 | 01-FEB-15:09 | 2406.93 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2355.50 | 19-FEB-07:44 |
March | 2337.76 | 01-MAR-15:09 | 2406.93 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2267.42 | 29-MAR-04:55 |
April | 2337.76 | 01-APR-10:09 | 2406.93 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.15 | 01-APR-16:00 | 2261.95 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2406.93 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 05-MAY-16:00 | 2156.94 | 17-MAY-20:05 |
June | 2337.76 | 01-JUN-14:09 | 2406.93 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 28-JUN-16:00 | 2101.00 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2406.93 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.81 | 30-JUL-18:03 | 1142.43 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2406.93 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.66 | 13-AUG-18:03 | 1696.24 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2406.93 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 14-SEP-17:00 | 1125.56 | 18-SEP-23:00 |
October | 2337.76 | 02-OCT-14:09 | 2406.93 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2363.10 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2406.93 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2716.89 | 29-NOV-21:02 |
December | 2337.76 | 01-DEC-15:09 | 2406.93 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2295.97 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.56 | |||||
Maximum of Months | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 169.81 | 2716.89 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2406.93 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2485.18 | 28-JAN-05:14 |
February | 2337.76 | 01-FEB-15:09 | 2406.93 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2327.26 | 19-FEB-07:06 |
March | 2337.76 | 01-MAR-15:09 | 2406.93 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2267.55 | 29-MAR-04:55 |
April | 2337.76 | 01-APR-10:09 | 2406.93 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.15 | 01-APR-16:00 | 2134.82 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2406.93 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 05-MAY-16:00 | 1945.70 | 17-MAY-20:05 |
June | 2337.76 | 01-JUN-14:09 | 2406.93 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 28-JUN-16:00 | 1984.07 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2406.93 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 174.71 | 30-JUL-18:03 | 1079.58 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2406.93 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.48 | 13-AUG-18:03 | 1609.09 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2406.93 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 14-SEP-17:00 | 1038.47 | 18-SEP-23:00 |
October | 2337.76 | 02-OCT-14:09 | 2406.93 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2185.86 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2406.93 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2707.00 | 29-NOV-21:02 |
December | 2337.76 | 01-DEC-15:09 | 2406.93 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2288.72 | 22-DEC-21:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.47 | |||||
Maximum of Months | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 174.71 | 2707.00 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 146.46 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 39635.12 | 07-JAN-12:10 |
February | 0.00 | 01-FEB-00:10 | 146.46 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 39364.46 | 18-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 146.46 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 28515.93 | 05-MAR-12:10 |
April | 0.00 | 01-APR-00:10 | 146.46 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.91 | 01-APR-16:00 | 24803.80 | 18-APR-17:00 |
May | 0.00 | 01-MAY-00:10 | 146.46 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 22573.37 | 23-MAY-17:00 |
June | 0.00 | 01-JUN-00:10 | 146.46 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 18173.33 | 13-JUN-11:05 |
July | 0.00 | 01-JUL-00:10 | 146.46 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.47 | 24-JUL-15:00 | 14799.55 | 12-JUL-11:02 |
August | 0.00 | 01-AUG-00:10 | 146.46 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.78 | 10-AUG-17:00 | 15634.47 | 01-AUG-11:02 |
September | 0.00 | 01-SEP-00:10 | 146.46 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 18189.19 | 16-SEP-11:03 |
October | 0.00 | 01-OCT-00:10 | 146.46 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 20534.01 | 27-OCT-16:00 |
November | 0.00 | 01-NOV-00:10 | 146.46 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32398.90 | 12-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 146.46 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 38340.90 | 26-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14799.55 | ||||
Maximum of Months | 0.00 | 146.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.78 | 39635.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2890.43 | 05-JAN-11:10 | 5152.71 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.65 |
February | 3280.19 | 13-FEB-16:10 | 5152.71 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.40 |
March | 2783.27 | 22-MAR-10:30 | 5152.71 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.17 |
April | 6974.23 | 27-APR-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 | 0.00 |
May | 7967.22 | 15-MAY-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 |
June | 9767.44 | 28-JUN-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 90.41 | 0.00 |
July | 11092.68 | 24-JUL-14:40 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 199.16 | 0.00 |
August | 27887.17 | 10-AUG-04:01 | 0.00 | 1585.11 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.88 |
September | 9171.71 | 14-SEP-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
October | 5672.51 | 04-OCT-15:00 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.92 |
November | 4695.37 | 04-NOV-14:20 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 |
December | 2735.38 | 06-DEC-15:10 | 5888.82 | 2880.76 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2735.38 | 0.00 | 1585.11 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27887.17 | 5888.82 | 2880.76 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 199.16 | 1026.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27325.74 | 21-JAN-07:03 | 9303.63 | 8514.56 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.58 |
February | 34091.03 | 09-FEB-07:03 | 12404.84 | 22705.50 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.94 |
March | 35133.35 | 01-MAR-07:03 | 9303.63 | 17029.12 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.54 |
April | 103189.90 | 28-APR-05:01 | 0.00 | 9933.66 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.92 |
May | 151241.32 | 05-MAY-04:03 | 0.00 | 4257.28 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.96 |
June | 151603.40 | 22-JUN-04:03 | 0.00 | 4257.28 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.76 |
July | 157156.98 | 19-JUL-04:03 | 0.00 | 4257.28 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.57 |
August | 152022.87 | 09-AUG-04:01 | 0.00 | 14190.94 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.38 |
September | 150015.93 | 15-SEP-04:02 | 0.00 | 7095.47 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36450.06 | 04-OCT-14:30 | 24809.68 | 25543.68 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.69 |
November | 32001.90 | 11-NOV-09:03 | 9303.63 | 8514.56 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.77 |
December | 31948.71 | 06-DEC-07:03 | 9303.63 | 17029.12 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 27325.74 | 0.00 | 4257.28 | 3101.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 157156.98 | 24809.68 | 25543.68 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3994.73 | 20-JAN-13:30 | 2045.54 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 |
February | 6559.44 | 27-FEB-15:10 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
March | 7065.81 | 18-MAR-13:50 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.51 |
April | 9382.07 | 27-APR-13:30 | 2045.54 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 | 0.00 |
May | 8774.75 | 05-MAY-05:01 | 0.00 | 936.03 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7732.19 | 28-JUN-15:00 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 0.00 |
July | 22678.26 | 24-JUL-04:01 | 0.00 | 1337.18 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.18 |
August | 25016.36 | 09-AUG-04:01 | 0.00 | 1337.18 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.19 |
September | 24441.19 | 15-SEP-04:02 | 0.00 | 668.59 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10886.39 | 04-OCT-14:10 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 |
November | 9053.24 | 04-NOV-14:00 | 2337.76 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5259.59 | 05-DEC-12:40 | 2045.54 | 2406.93 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3994.73 | 0.00 | 668.59 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25016.36 | 2337.76 | 2406.93 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 267.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3143.60 | 07-JAN-13:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.03 |
February | 4198.77 | 27-FEB-15:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
March | 4591.33 | 01-MAR-15:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.38 |
April | 7073.82 | 27-APR-13:30 | 2045.54 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 | 0.00 |
May | 5530.54 | 15-MAY-13:20 | 2045.54 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 |
June | 5601.36 | 28-JUN-15:00 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 0.00 |
July | 7408.76 | 31-JUL-13:20 | 2045.54 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 0.00 |
August | 20140.70 | 09-AUG-04:01 | 0.00 | 1337.18 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.19 |
September | 19817.76 | 15-SEP-04:02 | 0.00 | 668.59 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8647.39 | 04-OCT-14:10 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 |
November | 6519.66 | 04-NOV-14:00 | 2337.76 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2964.95 | 06-DEC-12:00 | 2045.54 | 2406.93 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2964.95 | 0.00 | 668.59 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20140.70 | 2337.76 | 2406.93 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 225.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 252.88 | 15-JAN-07:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.25 |
February | 233.54 | 21-FEB-05:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.45 |
March | 214.25 | 06-MAR-05:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.80 |
April | 58.28 | 11-APR-04:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.95 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.61 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.38 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.22 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.46 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 |
November | 180.87 | 24-NOV-05:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.72 |
December | 313.49 | 26-DEC-05:02 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 8.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 313.49 | 0.00 | 81.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.95 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.991172E+11 | 70504.15 | 11-JAN-17:30 | 0.730514E+11 | 172462.67 | 16-JAN-07:10 |
February | 0.892318E+11 | 70709.59 | 25-FEB-17:49 | 0.507048E+11 | 181120.43 | 20-FEB-07:10 |
March | 0.996304E+11 | 72226.24 | 18-MAR-15:20 | 0.282501E+11 | 90543.30 | 06-MAR-05:10 |
April | 0.955785E+11 | 94027.67 | 27-APR-14:00 | 0.176944E+11 | 49367.95 | 11-APR-04:10 |
May | 0.100067E+12 | 92048.27 | 06-MAY-13:30 | 0.132437E+11 | 29154.69 | 23-MAY-16:00 |
June | 0.101071E+12 | 93630.43 | 28-JUN-14:00 | 0.970195E+10 | 22559.86 | 13-JUN-13:00 |
July | 0.110085E+12 | 102368.38 | 24-JUL-14:00 | 0.837602E+10 | 16041.94 | 09-JUL-12:00 |
August | 0.117632E+12 | 104100.01 | 10-AUG-14:00 | 0.818223E+10 | 15479.23 | 01-AUG-11:09 |
September | 0.100378E+12 | 95336.62 | 14-SEP-14:09 | 0.104570E+11 | 21606.42 | 26-SEP-14:09 |
October | 0.976937E+11 | 79994.72 | 04-OCT-14:00 | 0.161050E+11 | 26896.81 | 31-OCT-16:49 |
November | 0.953172E+11 | 79104.99 | 04-NOV-14:09 | 0.356583E+11 | 90207.40 | 13-NOV-05:10 |
December | 0.990729E+11 | 70504.16 | 02-DEC-17:00 | 0.597854E+11 | 147322.06 | 26-DEC-05:10 |
Annual Sum or Average | 0.120487E+13 | 0.331210E+12 | ||||
Minimum of Months | 0.892318E+11 | 70504.15 | 0.818223E+10 | 15479.23 | ||
Maximum of Months | 0.117632E+12 | 104100.01 | 0.730514E+11 | 181120.43 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.398525E+11 | 0.791956E+10 | 0.164409E+11 | 0.00 | 0.349041E+11 | 0.00 | 0.00 | 91866.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362606E+11 | 0.652904E+10 | 0.149157E+11 | 0.00 | 0.315009E+11 | 0.00 | 0.00 | 25596384.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413616E+11 | 0.637299E+10 | 0.168545E+11 | 0.00 | 0.349669E+11 | 0.00 | 0.00 | 74429603.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390247E+11 | 0.530850E+10 | 0.160165E+11 | 0.00 | 0.331244E+11 | 0.00 | 0.00 | 0.210432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406071E+11 | 0.471495E+10 | 0.166477E+11 | 0.00 | 0.336791E+11 | 0.00 | 0.00 | 0.441794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399127E+11 | 0.414927E+10 | 0.162772E+11 | 0.00 | 0.322604E+11 | 0.00 | 0.00 | 0.847104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.397190E+11 | 0.447809E+10 | 0.163871E+11 | 0.00 | 0.321347E+11 | 0.00 | 0.00 | 0.173663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.413616E+11 | 0.514130E+10 | 0.168545E+11 | 0.00 | 0.323935E+11 | 0.00 | 0.00 | 0.218815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.390247E+11 | 0.579337E+10 | 0.160165E+11 | 0.00 | 0.322032E+11 | 0.00 | 0.00 | 0.734008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398525E+11 | 0.687458E+10 | 0.164409E+11 | 0.00 | 0.339932E+11 | 0.00 | 0.00 | 0.532431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385372E+11 | 0.743190E+10 | 0.159174E+11 | 0.00 | 0.331914E+11 | 0.00 | 0.00 | 0.239205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.397190E+11 | 0.812298E+10 | 0.163871E+11 | 0.00 | 0.348438E+11 | 0.00 | 0.00 | 2611.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.475233E+12 | 0.728365E+11 | 0.195156E+12 | 0.399196E+12 | 0.00 | 0.624530E+11 | |||||||
Minimum of Months | 0.362606E+11 | 0.414927E+10 | 0.149157E+11 | 0.00 | 0.315009E+11 | 0.00 | 0.00 | 2611.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.413616E+11 | 0.812298E+10 | 0.168545E+11 | 0.00 | 0.349669E+11 | 0.00 | 0.00 | 0.218815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.647956E+11 | 0.00 | 0.825582E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.432146E+11 | 0.00 | 0.749024E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.199305E+11 | 0.00 | 0.831954E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.977617E+10 | 0.00 | 0.791827E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.517000E+10 | 0.00 | 0.807366E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.195816E+10 | 0.00 | 0.774379E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.520141E+09 | 0.00 | 0.785588E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272891E+09 | 0.00 | 0.790934E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.280685E+10 | 0.00 | 0.765020E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.814498E+10 | 0.00 | 0.796006E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.278529E+11 | 0.00 | 0.780535E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.515968E+11 | 0.00 | 0.818857E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.236040E+12 | 0.951707E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.272891E+09 | 0.00 | 0.749024E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.647956E+11 | 0.00 | 0.831954E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 33384.75 | 02-JAN-09:09 | 4644.36 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 21703.98 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 33384.75 | 01-FEB-09:09 | 4644.36 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 21703.98 | 05-FEB-10:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 33384.75 | 01-MAR-09:09 | 4644.36 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 21703.98 | 05-MAR-11:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 33384.75 | 01-APR-09:09 | 4644.36 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 21703.98 | 02-APR-12:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 33384.75 | 01-MAY-08:09 | 4644.36 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 21703.98 | 01-MAY-11:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 33384.75 | 01-JUN-08:09 | 4644.36 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 21703.98 | 01-JUN-09:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 33384.75 | 01-JUL-09:09 | 4644.36 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 21703.98 | 01-JUL-09:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 33384.75 | 01-AUG-08:09 | 4644.36 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 21703.98 | 01-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 33384.75 | 01-SEP-08:09 | 4644.36 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 21703.98 | 01-SEP-12:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 33384.75 | 02-OCT-08:09 | 4644.36 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 21703.98 | 01-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 33384.75 | 01-NOV-08:09 | 4644.36 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 21703.98 | 01-NOV-15:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 33384.75 | 01-DEC-09:09 | 4644.36 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 21703.98 | 01-DEC-09:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 33384.75 | 4644.36 | 10771.04 | 0.00 | 21703.98 | 0.00 | 0.00 | |||||
Maximum of Months | 33384.75 | 4644.36 | 10771.04 | 0.00 | 21703.98 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 152.96 | 11-JAN-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4198.22 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7077.05 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30897.48 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28918.08 | 06-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30500.23 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39238.19 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40969.82 | 10-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32206.43 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16864.53 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15974.79 | 04-NOV-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.18 | 02-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40969.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 70504.15 | 11-JAN-17:30 | 33384.75 | 10771.04 | 4644.36 | 0.00 | 21703.98 | 0.00 | 0.00 | 0.02 | 0.00 |
February | 70709.59 | 25-FEB-17:49 | 33384.75 | 10771.04 | 4644.36 | 0.00 | 21703.98 | 0.00 | 0.00 | 205.46 | 0.00 |
March | 72226.24 | 18-MAR-15:20 | 33384.75 | 10771.04 | 0.00 | 0.00 | 21703.98 | 0.00 | 0.00 | 6366.47 | 0.00 |
April | 94027.67 | 27-APR-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 30897.48 | 0.00 |
May | 92048.27 | 06-MAY-13:30 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 28918.08 | 0.00 |
June | 93630.43 | 28-JUN-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 30500.23 | 0.00 |
July | 102368.38 | 24-JUL-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 39238.19 | 0.00 |
August | 104100.01 | 10-AUG-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 40969.82 | 0.00 |
September | 95336.62 | 14-SEP-14:09 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 32206.43 | 0.00 |
October | 79994.72 | 04-OCT-14:00 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 16864.53 | 0.00 |
November | 79104.99 | 04-NOV-14:09 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 15974.79 | 0.00 |
December | 70504.16 | 02-DEC-17:00 | 33384.75 | 10771.04 | 4644.36 | 0.00 | 21703.98 | 0.00 | 0.00 | 0.03 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 70504.15 | 33384.75 | 10771.04 | 0.00 | 0.00 | 18974.40 | 0.00 | 0.00 | 0.02 | 0.00 | |
Maximum of Months | 104100.01 | 33384.75 | 10771.04 | 4644.36 | 0.00 | 21703.98 | 0.00 | 0.00 | 40969.82 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 170600.67 | 16-JAN-07:10 | 0.00 | 5083.24 | 30-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 176687.71 | 20-FEB-07:10 | 0.00 | 5085.06 | 14-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 88681.30 | 06-MAR-05:10 | 0.00 | 5080.07 | 06-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 47505.95 | 11-APR-04:10 | 0.00 | 5060.19 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 24306.30 | 23-MAY-16:00 | 0.00 | 5035.05 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 17694.67 | 13-JUN-13:00 | 0.00 | 5005.20 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 11322.04 | 09-JUL-12:00 | 0.00 | 4980.14 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 10953.36 | 01-AUG-11:20 | 0.00 | 4970.10 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 16816.47 | 26-SEP-14:30 | 0.00 | 4985.00 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 22411.84 | 28-OCT-04:10 | 0.00 | 5013.75 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 88345.40 | 13-NOV-05:10 | 0.00 | 5043.28 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 145460.06 | 26-DEC-05:10 | 0.00 | 5068.26 | 28-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 10953.36 | 0.00 | 4970.10 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 176687.71 | 0.00 | 5085.06 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.50 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.50 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.67 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.83 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.50 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.67 | 20.23 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.50 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.51 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.54 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 24.51 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.54 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.83 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.52 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13.50 | 20.24 | 0.00 | 0.67 | 24.49 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.33 | 20.53 | 0.00 | 0.00 | 0.33 | 24.52 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 20.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.17 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.83 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.67 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.83 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.17 | 20.18 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.83 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.14 | 278.50 | 21.11 | 278.50 | 21.11 |
February | 376.00 | 21.45 | 204.33 | 21.11 | 204.33 | 21.11 |
March | 422.00 | 22.01 | 76.67 | 21.12 | 76.67 | 21.12 |
April | 384.83 | 22.80 | 13.50 | 21.11 | 13.50 | 21.11 |
May | 338.50 | 23.38 | 6.50 | 23.89 | 0.00 | 0.00 |
June | 198.33 | 23.66 | 13.67 | 23.89 | 0.00 | 0.00 |
July | 92.33 | 23.79 | 134.67 | 23.89 | 0.00 | 0.00 |
August | 51.00 | 23.69 | 176.67 | 23.89 | 0.00 | 0.00 |
September | 178.33 | 23.57 | 44.67 | 23.89 | 0.00 | 0.00 |
October | 410.50 | 23.03 | 1.00 | 21.11 | 1.00 | 21.11 |
November | 394.17 | 21.86 | 80.33 | 21.11 | 80.33 | 21.11 |
December | 415.00 | 21.18 | 221.00 | 21.11 | 221.00 | 21.11 |
Annual Sum or Average | 3675.00 | 22.30 | 1251.50 | 21.95 | 875.33 | 21.11 |
Minimum of Months | 51.00 | 21.14 | 1.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.79 | 278.50 | 23.89 | 278.50 | 21.12 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.27 | 76.00 | 21.11 | 76.00 | 21.11 |
February | 364.33 | 21.73 | 47.33 | 21.11 | 47.33 | 21.11 |
March | 393.83 | 22.61 | 1.00 | 21.11 | 1.00 | 21.11 |
April | 246.33 | 23.05 | 36.33 | 23.89 | 0.00 | 0.00 |
May | 96.00 | 23.14 | 95.17 | 23.89 | 0.00 | 0.00 |
June | 31.33 | 23.44 | 182.00 | 23.89 | 0.00 | 0.00 |
July | 10.00 | 23.74 | 294.17 | 23.89 | 0.00 | 0.00 |
August | 7.17 | 23.60 | 343.83 | 23.89 | 0.00 | 0.00 |
September | 43.00 | 23.32 | 212.00 | 23.89 | 0.00 | 0.00 |
October | 209.83 | 23.04 | 4.67 | 23.89 | 0.00 | 0.00 |
November | 330.83 | 21.89 | 12.67 | 23.01 | 4.00 | 21.11 |
December | 415.00 | 21.38 | 30.17 | 21.11 | 30.17 | 21.11 |
Annual Sum or Average | 2561.67 | 22.10 | 1335.33 | 23.56 | 158.50 | 21.11 |
Minimum of Months | 7.17 | 21.27 | 1.00 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.74 | 343.83 | 23.89 | 76.00 | 21.11 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.66 | 129.83 | 21.11 | 129.83 | 21.11 |
February | 343.33 | 22.19 | 74.00 | 21.17 | 72.50 | 21.11 |
March | 353.17 | 22.87 | 23.17 | 21.59 | 19.17 | 21.11 |
April | 234.33 | 23.05 | 42.83 | 23.74 | 2.33 | 21.11 |
May | 131.67 | 23.21 | 85.67 | 23.89 | 0.00 | 0.00 |
June | 60.33 | 23.54 | 146.83 | 23.89 | 0.00 | 0.00 |
July | 27.67 | 23.82 | 280.67 | 23.89 | 0.00 | 0.00 |
August | 17.50 | 23.70 | 337.50 | 23.89 | 0.00 | 0.00 |
September | 47.83 | 23.48 | 232.83 | 23.89 | 0.00 | 0.00 |
October | 187.33 | 23.19 | 74.33 | 23.89 | 0.00 | 0.00 |
November | 332.83 | 22.47 | 36.83 | 22.23 | 22.00 | 21.11 |
December | 404.67 | 21.91 | 93.83 | 21.11 | 93.83 | 21.11 |
Annual Sum or Average | 2554.67 | 22.48 | 1558.33 | 23.28 | 339.67 | 21.11 |
Minimum of Months | 17.50 | 21.66 | 23.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 414.00 | 23.82 | 337.50 | 23.89 | 129.83 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.18 | 208.83 | 21.11 | 208.83 | 21.11 |
February | 365.67 | 21.54 | 132.50 | 21.11 | 132.50 | 21.11 |
March | 391.67 | 22.05 | 47.67 | 21.11 | 47.67 | 21.11 |
April | 311.50 | 22.48 | 40.67 | 23.01 | 12.83 | 21.11 |
May | 216.17 | 22.72 | 53.83 | 23.89 | 0.00 | 0.00 |
June | 115.67 | 23.09 | 78.67 | 23.89 | 0.00 | 0.00 |
July | 64.33 | 23.42 | 227.83 | 23.89 | 0.00 | 0.00 |
August | 38.50 | 23.21 | 285.33 | 23.89 | 0.00 | 0.00 |
September | 106.17 | 23.01 | 180.83 | 23.89 | 0.00 | 0.00 |
October | 271.50 | 22.49 | 44.00 | 23.89 | 0.00 | 0.00 |
November | 376.17 | 21.63 | 67.33 | 21.52 | 57.33 | 21.11 |
December | 413.33 | 21.34 | 172.50 | 21.11 | 172.50 | 21.11 |
Annual Sum or Average | 3084.67 | 21.97 | 1540.00 | 22.75 | 631.67 | 21.11 |
Minimum of Months | 38.50 | 21.18 | 40.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 414.00 | 23.42 | 285.33 | 23.89 | 208.83 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.14100 | 35.35563 | -0.5678 | 11.95971 |
February | 376.00000 | 21.44855 | 36.55043 | -0.4694 | 10.72508 |
March | 422.00000 | 22.00729 | 37.07673 | -0.2925 | 7.90069 |
April | 405.00000 | 22.84397 | 39.18832 | -0.0476 | 6.47647 |
May | 418.00000 | 23.46832 | 41.14570 | -0.8222 | 20.68581 |
June | 408.00000 | 23.77292 | 41.51560 | -0.6536 | 14.48582 |
July | 415.00000 | 23.86713 | 45.30086 | -0.5458 | 11.51925 |
August | 422.00000 | 23.86423 | 48.67402 | -0.5201 | 10.90778 |
September | 405.00000 | 23.74700 | 47.75547 | -0.6456 | 14.35726 |
October | 414.00000 | 23.02275 | 42.53246 | 0.02545 | 6.07608 |
November | 399.00000 | 21.88322 | 42.53259 | -0.2865 | 8.42471 |
December | 415.00000 | 21.17597 | 37.54263 | -0.5283 | 11.02287 |
Annual Sum or Average | 4913.00000 | 22.69672 | 41.29361 | -0.4468 | 11.22483 |
Minimum of Months | 376.00000 | 21.14100 | 35.35563 | -0.8222 | 6.07608 |
Maximum of Months | 422.00000 | 23.86713 | 48.67402 | 0.02545 | 20.68581 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.27096 | 32.98409 | -0.4249 | 9.14306 |
February | 376.00000 | 21.80366 | 33.53518 | -0.2754 | 8.08580 |
March | 422.00000 | 22.70314 | 33.15482 | -0.0258 | 6.21278 |
April | 405.00000 | 23.38234 | 35.70519 | 0.19080 | 6.63872 |
May | 418.00000 | 23.71659 | 39.11892 | -0.5716 | 12.54241 |
June | 408.00000 | 23.85417 | 40.47989 | -0.4735 | 9.92611 |
July | 415.00000 | 23.88549 | 44.63851 | -0.4066 | 8.67292 |
August | 422.00000 | 23.88294 | 48.05649 | -0.3876 | 8.32233 |
September | 405.00000 | 23.82460 | 46.22652 | -0.4803 | 10.18786 |
October | 414.00000 | 23.46408 | 39.26616 | 0.22362 | 6.63460 |
November | 399.00000 | 22.24077 | 39.61653 | -0.1055 | 7.14780 |
December | 415.00000 | 21.39264 | 34.89465 | -0.3722 | 8.28293 |
Annual Sum or Average | 4913.00000 | 22.96095 | 39.00979 | -0.2597 | 8.48810 |
Minimum of Months | 376.00000 | 21.27096 | 32.98409 | -0.5716 | 6.21278 |
Maximum of Months | 422.00000 | 23.88549 | 48.05649 | 0.22362 | 12.54241 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.66051 | 31.66054 | -0.3934 | 9.29146 |
February | 376.00000 | 22.33628 | 31.67168 | -0.1876 | 8.14315 |
March | 422.00000 | 23.02676 | 31.20670 | 0.01699 | 6.80799 |
April | 405.00000 | 23.39493 | 34.34790 | 0.17382 | 7.11839 |
May | 418.00000 | 23.67112 | 38.19700 | -0.6208 | 14.45375 |
June | 408.00000 | 23.83695 | 39.81125 | -0.5095 | 10.92441 |
July | 415.00000 | 23.88542 | 44.04851 | -0.4072 | 8.84437 |
August | 422.00000 | 23.88207 | 47.18896 | -0.3560 | 8.08743 |
September | 405.00000 | 23.84050 | 45.09307 | -0.4317 | 9.74429 |
October | 414.00000 | 23.56967 | 37.55706 | 0.25744 | 7.34804 |
November | 399.00000 | 22.70234 | 37.69983 | -0.0459 | 7.18385 |
December | 415.00000 | 21.95547 | 33.14423 | -0.2974 | 8.43595 |
Annual Sum or Average | 4913.00000 | 23.15323 | 37.67713 | -0.2346 | 8.87489 |
Minimum of Months | 376.00000 | 21.66051 | 31.20670 | -0.6208 | 6.80799 |
Maximum of Months | 422.00000 | 23.88542 | 47.18896 | 0.25744 | 14.45375 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.17547 | 32.48084 | -0.5267 | 11.16792 |
February | 376.00000 | 21.60661 | 33.42204 | -0.3655 | 9.41598 |
March | 422.00000 | 22.18068 | 33.49316 | -0.1803 | 7.47934 |
April | 405.00000 | 22.79953 | 36.45586 | 0.02414 | 7.01424 |
May | 418.00000 | 23.27867 | 39.98690 | -0.7829 | 20.30296 |
June | 408.00000 | 23.65818 | 40.88703 | -0.6136 | 13.95666 |
July | 415.00000 | 23.81605 | 44.78595 | -0.4803 | 10.43329 |
August | 422.00000 | 23.82537 | 47.93769 | -0.4225 | 9.40630 |
September | 405.00000 | 23.65426 | 46.39168 | -0.5356 | 12.56326 |
October | 414.00000 | 22.96501 | 39.82028 | 0.10662 | 6.90344 |
November | 399.00000 | 21.75324 | 39.97990 | -0.2658 | 8.27091 |
December | 415.00000 | 21.34902 | 34.30914 | -0.4531 | 10.12969 |
Annual Sum or Average | 4913.00000 | 22.68118 | 39.19994 | -0.3753 | 10.60274 |
Minimum of Months | 376.00000 | 21.17547 | 32.48084 | -0.7829 | 6.90344 |
Maximum of Months | 422.00000 | 23.82537 | 47.93769 | 0.10662 | 20.30296 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 36163.41 | 11140.40 | 4.00 | 33578.38 | 2585.02 | 0.00 | 0.00 | 27-FEB-17:50 | 0.00 | 01-FEB-00:10 | 55.78 | 27-FEB-17:50 | 52.07 | 27-FEB-17:50 | 3.71 | 27-FEB-17:50 | 17.18 | 27-FEB-17:50 | 0.00 | 01-FEB-00:10 |
March | 89556.47 | 27544.25 | 8.71 | 74893.41 | 14663.06 | 0.00 | 0.01 | 10-MAR-17:00 | 0.00 | 01-MAR-00:10 | 125.42 | 10-MAR-17:00 | 102.33 | 10-MAR-17:00 | 23.09 | 10-MAR-17:00 | 38.58 | 10-MAR-17:00 | 0.00 | 01-MAR-00:10 |
April | 0.527274E+09 | 0.159644E+09 | 76.78 | 0.488783E+09 | 38491058.15 | 0.00 | 0.44 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 11061.52 | 27-APR-15:00 | 9782.98 | 27-APR-15:00 | 1278.54 | 27-APR-15:00 | 3320.82 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.127919E+10 | 0.372401E+09 | 168.65 | 0.111878E+10 | 0.160401E+09 | 0.00 | 0.48 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 | 12254.99 | 06-MAY-13:40 | 9877.07 | 06-MAY-13:50 | 2483.74 | 06-MAY-12:50 | 3439.29 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 |
June | 0.267179E+10 | 0.777145E+09 | 238.50 | 0.246262E+10 | 0.209169E+09 | 0.00 | 0.53 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 13335.03 | 28-JUN-15:00 | 12252.85 | 28-JUN-15:00 | 1379.83 | 21-JUN-17:00 | 3852.01 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.649910E+10 | 0.187296E+10 | 293.26 | 0.547924E+10 | 0.101985E+10 | 0.00 | 0.64 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 | 16763.91 | 24-JUL-15:00 | 14870.29 | 24-JUL-15:00 | 3471.46 | 15-JUL-14:40 | 5046.20 | 24-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 0.831110E+10 | 0.241342E+10 | 315.59 | 0.696071E+10 | 0.135039E+10 | 0.00 | 1.00 | 10-AUG-04:01 | 0.00 | 01-AUG-00:10 | 29415.02 | 10-AUG-04:01 | 21068.87 | 10-AUG-04:01 | 8346.15 | 10-AUG-04:01 | 6800.06 | 10-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.218759E+10 | 0.626621E+09 | 204.40 | 0.175960E+10 | 0.427984E+09 | 0.00 | 0.53 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 | 13860.64 | 14-SEP-14:10 | 11097.57 | 14-SEP-15:00 | 3481.12 | 23-SEP-14:00 | 3827.46 | 14-SEP-14:10 | 0.00 | 01-SEP-00:10 |
October | 54111894.79 | 16064387.52 | 76.93 | 53976272.00 | 135622.80 | 0.00 | 0.20 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4411.23 | 04-OCT-15:00 | 4411.23 | 04-OCT-15:00 | 42.37 | 26-OCT-14:40 | 1297.90 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 33837342.25 | 10095288.50 | 11.49 | 25071971.97 | 8765370.28 | 0.00 | 0.15 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 | 3439.28 | 04-NOV-14:10 | 2584.69 | 04-NOV-14:20 | 860.52 | 04-NOV-14:00 | 1019.36 | 04-NOV-14:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.215641E+11 | 0.624839E+10 | 1398.30 | 0.183489E+11 | 0.321521E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.831110E+10 | 0.241342E+10 | 315.59 | 0.696071E+10 | 0.135039E+10 | 0.00 | 1.00 | 0.00 | 29415.02 | 21068.87 | 8346.15 | 6800.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 275420.65 | 91773.87 | 0.17 | 251790.67 | 23629.97 | 0.00 | 0.00 | 11-JAN-15:40 | 0.00 | 01-JAN-00:10 | 459.03 | 11-JAN-15:40 | 419.65 | 11-JAN-15:40 | 39.38 | 11-JAN-15:40 | 152.96 | 11-JAN-15:40 | 0.00 | 01-JAN-00:10 |
February | 42641227.00 | 13989902.14 | 19.65 | 41912648.81 | 728578.19 | 0.00 | 0.08 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 8107.78 | 27-FEB-15:10 | 8107.78 | 27-FEB-15:10 | 162.66 | 27-FEB-16:00 | 2642.55 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.170744E+09 | 54874435.52 | 52.17 | 0.170090E+09 | 653066.59 | 0.00 | 0.17 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 17350.17 | 18-MAR-16:00 | 17350.17 | 18-MAR-16:00 | 242.35 | 09-MAR-18:30 | 5510.84 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.491796E+10 | 0.155373E+10 | 142.23 | 0.464494E+10 | 0.273021E+09 | 0.00 | 0.58 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 70053.31 | 27-APR-15:00 | 64483.59 | 27-APR-15:00 | 14079.62 | 28-APR-05:01 | 21880.11 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.110690E+11 | 0.340729E+10 | 218.78 | 0.978391E+10 | 0.128508E+10 | 0.00 | 1.00 | 05-MAY-04:03 | 0.00 | 01-MAY-00:10 | 132020.59 | 06-MAY-04:03 | 103340.80 | 05-MAY-04:03 | 35703.33 | 06-MAY-04:03 | 32932.91 | 06-MAY-04:03 | 0.00 | 01-MAY-00:10 |
June | 0.213427E+11 | 0.658648E+10 | 296.78 | 0.197990E+11 | 0.154372E+10 | 0.00 | 1.00 | 10-JUN-04:03 | 0.00 | 01-JUN-00:10 | 133281.20 | 23-JUN-04:03 | 106638.91 | 11-JUN-06:03 | 39480.45 | 29-JUN-04:03 | 33293.78 | 23-JUN-04:03 | 0.00 | 01-JUN-00:10 |
July | 0.424721E+11 | 0.129609E+11 | 344.49 | 0.363274E+11 | 0.614475E+10 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 138278.47 | 31-JUL-04:01 | 110542.39 | 19-JUL-04:03 | 52587.43 | 16-JUL-06:03 | 34595.28 | 31-JUL-04:01 | 0.00 | 01-JUL-00:10 |
August | 0.518248E+11 | 0.159169E+11 | 353.31 | 0.439764E+11 | 0.784837E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 140632.66 | 25-AUG-04:01 | 106186.84 | 13-AUG-07:01 | 52982.51 | 26-AUG-04:55 | 35131.15 | 25-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.170768E+11 | 0.519843E+10 | 255.44 | 0.139307E+11 | 0.314610E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 136365.54 | 01-SEP-04:03 | 97957.09 | 01-SEP-04:03 | 51665.97 | 23-SEP-04:03 | 34122.42 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 |
October | 0.103964E+10 | 0.328638E+09 | 136.31 | 0.101313E+10 | 26507740.48 | 0.00 | 0.34 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 36587.82 | 04-OCT-15:00 | 36587.82 | 04-OCT-15:00 | 1729.47 | 08-OCT-14:00 | 11225.89 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.520885E+09 | 0.162635E+09 | 29.44 | 0.392069E+09 | 0.128816E+09 | 0.00 | 0.31 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 34983.96 | 04-NOV-14:30 | 27083.24 | 04-NOV-14:30 | 8017.52 | 04-NOV-13:40 | 10758.07 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.150478E+12 | 0.461840E+11 | 1848.78 | 0.130080E+12 | 0.203978E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.518248E+11 | 0.159169E+11 | 353.31 | 0.439764E+11 | 0.784837E+10 | 0.00 | 1.00 | 0.00 | 140632.66 | 110542.39 | 52982.51 | 35131.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 299.36 | 92.23 | 1.67 | 289.22 | 10.14 | 0.00 | 0.00 | 11-JAN-18:40 | 0.00 | 01-JAN-00:10 | 0.11 | 11-JAN-18:40 | 0.11 | 11-JAN-18:40 | 0.00 | 11-JAN-18:40 | 0.03 | 11-JAN-18:40 | 0.00 | 01-JAN-00:10 |
February | 31004798.93 | 9130846.51 | 44.19 | 30900929.28 | 103869.65 | 0.00 | 0.23 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3707.94 | 27-FEB-15:00 | 3707.94 | 27-FEB-15:00 | 25.77 | 27-FEB-16:10 | 1072.72 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 48593923.10 | 14092566.33 | 99.32 | 48556524.87 | 37398.23 | 0.00 | 0.27 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4289.61 | 18-MAR-14:00 | 4289.61 | 18-MAR-14:00 | 19.32 | 18-MAR-12:50 | 1227.47 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.857099E+09 | 0.247419E+09 | 160.24 | 0.820432E+09 | 36667293.12 | 0.00 | 0.63 | 27-APR-14:10 | 0.00 | 01-APR-00:10 | 11927.74 | 27-APR-14:10 | 11339.86 | 27-APR-13:30 | 1083.73 | 29-APR-13:00 | 3361.26 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.144850E+10 | 0.412803E+09 | 201.54 | 0.130307E+10 | 0.145427E+09 | 0.00 | 0.56 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 10687.42 | 06-MAY-13:30 | 9116.20 | 04-MAY-14:10 | 1970.45 | 06-MAY-12:50 | 2931.33 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.249636E+10 | 0.718696E+09 | 264.85 | 0.237156E+10 | 0.124807E+09 | 0.00 | 0.54 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 | 10013.74 | 28-JUN-16:00 | 9682.99 | 28-JUN-15:00 | 922.69 | 21-JUN-17:00 | 2880.56 | 28-JUN-16:00 | 0.00 | 01-JUN-00:10 |
July | 0.553729E+10 | 0.157985E+10 | 324.56 | 0.484920E+10 | 0.688090E+09 | 0.00 | 1.00 | 24-JUL-04:01 | 0.00 | 01-JUL-00:10 | 21341.04 | 31-JUL-04:01 | 16012.71 | 24-JUL-04:01 | 7487.93 | 25-JUL-04:03 | 4933.26 | 31-JUL-04:01 | 0.00 | 01-JUL-00:10 |
August | 0.759472E+10 | 0.215970E+10 | 336.01 | 0.664851E+10 | 0.946215E+09 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 21723.94 | 25-AUG-04:01 | 16023.33 | 09-AUG-04:01 | 8380.00 | 26-AUG-04:01 | 5014.66 | 25-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.339197E+10 | 0.930701E+09 | 253.58 | 0.281944E+10 | 0.572525E+09 | 0.00 | 1.00 | 12-SEP-04:02 | 0.00 | 01-SEP-00:10 | 20914.64 | 14-SEP-04:02 | 13843.82 | 13-SEP-04:03 | 7409.14 | 15-SEP-04:02 | 4833.30 | 14-SEP-04:02 | 0.00 | 01-SEP-00:10 |
October | 0.433467E+09 | 0.122654E+09 | 171.13 | 0.417309E+09 | 16157648.84 | 0.00 | 0.54 | 04-OCT-14:40 | 0.00 | 01-OCT-00:10 | 9537.99 | 04-OCT-14:40 | 9537.99 | 04-OCT-14:40 | 692.55 | 08-OCT-13:30 | 2544.91 | 04-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 0.154929E+09 | 42699446.09 | 43.29 | 0.117953E+09 | 36975829.07 | 0.00 | 0.51 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 9553.80 | 04-NOV-14:00 | 7536.56 | 04-NOV-14:00 | 2155.93 | 04-NOV-13:10 | 2564.50 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 7220.95 | 2213.67 | 14.83 | 7214.61 | 6.34 | 0.00 | 0.00 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 | 0.46 | 02-DEC-13:00 | 0.46 | 02-DEC-13:00 | 0.00 | 30-DEC-14:00 | 0.14 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.219939E+11 | 0.623774E+10 | 1915.21 | 0.194269E+11 | 0.256701E+10 | 0.00 | ||||||||||||||
Minimum of Months | 299.36 | 92.23 | 1.67 | 289.22 | 6.34 | 0.00 | 0.00 | 0.00 | 0.11 | 0.11 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.759472E+10 | 0.215970E+10 | 336.01 | 0.664851E+10 | 0.946215E+09 | 0.00 | 1.00 | 0.00 | 21723.94 | 16023.33 | 8380.00 | 5014.66 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 9220430.06 | 2464495.47 | 10.19 | 9199074.03 | 21356.04 | 0.00 | 0.14 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 1839.33 | 27-FEB-15:10 | 1839.33 | 27-FEB-15:10 | 14.57 | 27-FEB-16:00 | 487.51 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 20541584.25 | 5435057.71 | 33.71 | 20540790.93 | 793.32 | 0.00 | 0.17 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2306.28 | 18-MAR-14:00 | 2306.28 | 18-MAR-14:00 | 0.14 | 10-MAR-13:00 | 604.74 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.547927E+09 | 0.143524E+09 | 98.61 | 0.522381E+09 | 25546030.19 | 0.00 | 0.59 | 27-APR-14:10 | 0.00 | 01-APR-00:10 | 9346.24 | 27-APR-14:10 | 8778.35 | 27-APR-14:10 | 767.29 | 29-APR-13:17 | 2378.73 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.870960E+09 | 0.225448E+09 | 155.68 | 0.781885E+09 | 89074695.27 | 0.00 | 0.51 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 7993.70 | 06-MAY-13:30 | 6654.69 | 06-MAY-13:40 | 1506.18 | 06-MAY-12:50 | 1990.36 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.148854E+10 | 0.388726E+09 | 228.09 | 0.140782E+10 | 80722375.40 | 0.00 | 0.50 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7577.67 | 28-JUN-16:00 | 7291.27 | 28-JUN-15:00 | 700.61 | 21-JUN-17:00 | 1976.24 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 0.368207E+10 | 0.952579E+09 | 285.11 | 0.320250E+10 | 0.479566E+09 | 0.00 | 0.67 | 31-JUL-14:10 | 0.00 | 01-JUL-00:10 | 10887.00 | 31-JUL-14:10 | 9602.17 | 31-JUL-14:10 | 1744.81 | 31-JUL-10:10 | 2780.26 | 31-JUL-14:10 | 0.00 | 01-JUL-00:10 |
August | 0.541738E+10 | 0.139150E+10 | 312.91 | 0.471436E+10 | 0.703016E+09 | 0.00 | 1.00 | 09-AUG-04:01 | 0.00 | 01-AUG-00:10 | 18190.17 | 25-AUG-04:01 | 13205.95 | 09-AUG-04:01 | 7189.09 | 26-AUG-04:01 | 3756.86 | 25-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.236982E+10 | 0.584326E+09 | 213.27 | 0.195492E+10 | 0.414903E+09 | 0.00 | 1.00 | 12-SEP-04:02 | 0.00 | 01-SEP-00:10 | 17514.59 | 14-SEP-04:02 | 11399.57 | 13-SEP-04:03 | 6402.96 | 14-SEP-04:02 | 3620.55 | 14-SEP-04:02 | 0.00 | 01-SEP-00:10 |
October | 0.257253E+09 | 65074511.56 | 100.83 | 0.250106E+09 | 7147244.57 | 0.00 | 0.51 | 04-OCT-14:30 | 0.00 | 01-OCT-00:10 | 7535.94 | 04-OCT-14:30 | 7535.94 | 04-OCT-14:30 | 461.24 | 08-OCT-13:40 | 1812.18 | 04-OCT-14:40 | 0.00 | 01-OCT-00:10 |
November | 94882798.78 | 23775236.68 | 11.94 | 71765268.29 | 23117530.49 | 0.00 | 0.44 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6762.79 | 04-NOV-14:00 | 5267.33 | 04-NOV-14:00 | 1550.65 | 04-NOV-13:30 | 1656.97 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 1449.31 | 397.33 | 3.89 | 1449.31 | 0.00 | 0.00 | 0.00 | 02-DEC-12:07 | 0.00 | 01-DEC-00:10 | 0.31 | 02-DEC-12:07 | 0.31 | 02-DEC-12:07 | 0.00 | 01-DEC-00:10 | 0.08 | 02-DEC-12:07 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.147586E+11 | 0.378286E+10 | 1454.22 | 0.129355E+11 | 0.182311E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.541738E+10 | 0.139150E+10 | 312.91 | 0.471436E+10 | 0.703016E+09 | 0.00 | 1.00 | 0.00 | 18190.17 | 13205.95 | 7189.09 | 3756.86 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 7.91 | 1.60 | 6.31 | 0.43 | 35.47 | 0.00 | 0.00 | 744.00 |
February | 14.60 | 5.23 | 9.37 | 4.93 | 31.55 | 0.00 | 0.00 | 672.00 |
March | 24.14 | 10.12 | 14.02 | 15.94 | 27.14 | 0.00 | 0.00 | 744.00 |
April | 39.22 | 20.02 | 19.20 | 34.39 | 22.40 | 0.00 | 0.00 | 720.00 |
May | 50.99 | 26.39 | 24.60 | 50.10 | 19.13 | 0.00 | 0.00 | 744.00 |
June | 55.73 | 32.72 | 23.00 | 57.30 | 15.85 | 0.00 | 0.00 | 720.00 |
July | 58.22 | 38.48 | 19.73 | 63.23 | 14.92 | 0.00 | 0.00 | 744.00 |
August | 46.29 | 29.35 | 16.94 | 48.92 | 15.09 | 0.00 | 0.00 | 744.00 |
September | 32.49 | 17.93 | 14.56 | 29.07 | 20.05 | 0.00 | 0.00 | 720.00 |
October | 18.60 | 8.29 | 10.31 | 11.06 | 26.16 | 0.00 | 0.00 | 744.00 |
November | 9.33 | 2.21 | 7.11 | 1.62 | 29.66 | 0.00 | 0.00 | 720.00 |
December | 6.60 | 1.46 | 5.14 | 0.15 | 36.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 30.43 | 16.22 | 14.21 | 26.56 | 24.47 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 6.60 | 1.46 | 5.14 | 0.15 | 14.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 58.22 | 38.48 | 24.60 | 63.23 | 36.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 549.02 | 1039.88 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 953.74 | 946.41 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1021.71 | 857.27 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1023.19 | 708.77 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 840.48 | 596.77 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 731.53 | 477.83 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 914.84 | 434.20 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1149.36 | 428.59 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1308.83 | 595.70 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1172.01 | 791.96 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 588.69 | 909.09 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 660.52 | 1073.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 909.09 | 737.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 549.02 | 428.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1308.83 | 1073.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 555.47 | 1006.47 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 965.14 | 903.43 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1034.87 | 808.20 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1036.05 | 671.65 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 850.77 | 566.52 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 736.82 | 455.76 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 916.57 | 414.92 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1149.62 | 411.39 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1311.34 | 572.07 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1180.44 | 750.06 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 600.40 | 855.05 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 667.86 | 1033.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 916.67 | 703.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 555.47 | 411.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1311.34 | 1033.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.22 | 86.81 | 59.41 | 111.03 | 207.57 | 0.00 | 0.00 | 744.00 |
February | 224.95 | 139.25 | 85.70 | 194.61 | 184.28 | 0.00 | 0.00 | 672.00 |
March | 242.06 | 129.14 | 112.93 | 211.35 | 162.61 | 0.00 | 0.00 | 744.00 |
April | 255.49 | 110.95 | 144.55 | 213.12 | 133.52 | 0.00 | 0.00 | 720.00 |
May | 233.56 | 69.56 | 164.01 | 177.75 | 110.50 | 0.00 | 0.00 | 744.00 |
June | 213.69 | 57.35 | 156.34 | 155.63 | 87.73 | 0.00 | 0.00 | 720.00 |
July | 233.03 | 85.32 | 147.71 | 190.02 | 80.99 | 0.00 | 0.00 | 744.00 |
August | 250.38 | 116.75 | 133.64 | 233.24 | 82.88 | 0.00 | 0.00 | 744.00 |
September | 277.52 | 153.30 | 124.23 | 271.36 | 110.89 | 0.00 | 0.00 | 720.00 |
October | 251.38 | 155.23 | 96.14 | 242.91 | 146.70 | 0.00 | 0.00 | 744.00 |
November | 148.55 | 85.12 | 63.43 | 121.28 | 173.78 | 0.00 | 0.00 | 720.00 |
December | 155.41 | 100.55 | 54.86 | 134.67 | 212.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 219.26 | 107.24 | 112.01 | 188.00 | 140.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 146.22 | 57.35 | 54.86 | 111.03 | 80.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 277.52 | 155.23 | 164.01 | 271.36 | 212.00 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 21181988.70 | 4280045.83 | 16901942.87 | 1149057.33 | 94996039.72 |
February | 35320183.96 | 12656046.60 | 22664137.36 | 11915898.73 | 76330455.92 |
March | 64668192.47 | 27116122.37 | 37552070.11 | 42706668.23 | 72690053.28 |
April | 0.101648E+09 | 51893023.97 | 49755052.65 | 89136897.27 | 58071624.47 |
May | 0.136581E+09 | 70693943.00 | 65887129.99 | 0.134190E+09 | 51224771.22 |
June | 0.144445E+09 | 84818070.53 | 59626802.23 | 0.148527E+09 | 41091376.42 |
July | 0.155932E+09 | 0.103076E+09 | 52856367.13 | 0.169365E+09 | 39968080.20 |
August | 0.123985E+09 | 78607588.34 | 45377003.69 | 0.131017E+09 | 40412915.07 |
September | 84211981.79 | 46473511.98 | 37738469.80 | 75340652.33 | 51976319.72 |
October | 49806730.44 | 22205448.01 | 27601282.43 | 29631224.29 | 70061294.58 |
November | 24179294.14 | 5738932.03 | 18440362.11 | 4211395.66 | 76880216.69 |
December | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 97858471.28 |
Annual Sum or Average | 0.959647E+09 | 0.511476E+09 | 0.448171E+09 | 0.837602E+09 | 0.771562E+09 |
Minimum of Months | 17687718.27 | 3916995.70 | 13770722.57 | 411140.01 | 39968080.20 |
Maximum of Months | 0.155932E+09 | 0.103076E+09 | 65887129.99 | 0.169365E+09 | 97858471.28 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.147050E+10 | 0.278522E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.230729E+10 | 0.228955E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.273656E+10 | 0.229612E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.265210E+10 | 0.183713E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.225114E+10 | 0.159839E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.189612E+10 | 0.123854E+10 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.245030E+10 | 0.116296E+10 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.307844E+10 | 0.114793E+10 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.339250E+10 | 0.154405E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.313911E+10 | 0.212120E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.152588E+10 | 0.235635E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.176913E+10 | 0.287504E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.286691E+11 | 0.232525E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.147050E+10 | 0.114793E+10 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.339250E+10 | 0.287504E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.148777E+10 | 0.269572E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.233486E+10 | 0.218557E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.277180E+10 | 0.216470E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.268544E+10 | 0.174092E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.227871E+10 | 0.151737E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.190983E+10 | 0.118132E+10 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.245495E+10 | 0.111133E+10 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.307915E+10 | 0.110187E+10 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.339900E+10 | 0.148280E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.316168E+10 | 0.200896E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.155625E+10 | 0.221628E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.178880E+10 | 0.276754E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.289082E+11 | 0.221744E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.148777E+10 | 0.110187E+10 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.339900E+10 | 0.276754E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.297371E+09 | 0.555963E+09 |
February | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.470795E+09 | 0.445802E+09 |
March | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.566075E+09 | 0.435532E+09 |
April | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.552413E+09 | 0.346077E+09 |
May | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.476095E+09 | 0.295950E+09 |
June | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.403390E+09 | 0.227398E+09 |
July | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.508940E+09 | 0.216920E+09 |
August | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.624723E+09 | 0.221980E+09 |
September | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.703366E+09 | 0.287416E+09 |
October | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.650623E+09 | 0.392919E+09 |
November | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.314363E+09 | 0.450438E+09 |
December | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.360704E+09 | 0.567827E+09 |
Annual Sum or Average | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.592886E+10 | 0.444422E+10 |
Minimum of Months | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.297371E+09 | 0.216920E+09 |
Maximum of Months | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.703366E+09 | 0.567827E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.43 | 283.74 | 63.27 | 12.78 | 50.48 | 0.00 | 0.00 |
February | 39.40 | 252.42 | 116.80 | 41.85 | 74.95 | 0.00 | 0.00 |
March | 127.56 | 217.11 | 193.15 | 80.99 | 112.16 | 0.00 | 0.00 |
April | 275.11 | 179.23 | 313.73 | 160.16 | 153.56 | 0.00 | 0.00 |
May | 400.81 | 153.00 | 407.95 | 211.15 | 196.80 | 0.00 | 0.00 |
June | 458.42 | 126.83 | 445.82 | 261.78 | 184.03 | 0.00 | 0.00 |
July | 505.87 | 119.38 | 465.75 | 307.87 | 157.87 | 0.00 | 0.00 |
August | 391.33 | 120.71 | 370.32 | 234.79 | 135.53 | 0.00 | 0.00 |
September | 232.53 | 160.42 | 259.91 | 143.44 | 116.48 | 0.00 | 0.00 |
October | 88.50 | 209.26 | 148.77 | 66.32 | 82.44 | 0.00 | 0.00 |
November | 13.00 | 237.28 | 74.63 | 17.71 | 56.91 | 0.00 | 0.00 |
December | 1.23 | 292.29 | 52.83 | 11.70 | 41.13 | 0.00 | 0.00 |
Annual Sum or Average | 212.48 | 195.73 | 243.44 | 129.75 | 113.69 | 0.00 | 0.00 |
Minimum of Months | 1.23 | 119.38 | 52.83 | 11.70 | 41.13 | 0.00 | 0.00 |
Maximum of Months | 505.87 | 292.29 | 465.75 | 307.87 | 196.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 549.02 | 1039.88 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 953.74 | 946.41 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1021.71 | 857.27 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1023.19 | 708.77 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 840.48 | 596.77 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 731.53 | 477.83 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 914.84 | 434.20 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1149.36 | 428.59 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1308.83 | 595.70 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1172.01 | 791.96 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 588.69 | 909.09 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 660.52 | 1073.42 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 909.09 | 737.33 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 549.02 | 428.59 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1308.83 | 1073.42 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 555.47 | 1006.47 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 965.14 | 903.43 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1034.87 | 808.20 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1036.05 | 671.65 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 850.77 | 566.52 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 736.82 | 455.76 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 916.57 | 414.92 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1149.62 | 411.39 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1311.34 | 572.07 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1180.44 | 750.06 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 600.40 | 855.05 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 667.86 | 1033.28 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 916.67 | 703.14 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 555.47 | 411.39 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1311.34 | 1033.28 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 111.03 | 207.57 | 146.22 | 86.81 | 59.41 | 0.00 | 0.00 |
February | 194.61 | 184.28 | 224.95 | 139.25 | 85.70 | 0.00 | 0.00 |
March | 211.35 | 162.61 | 242.06 | 129.14 | 112.93 | 0.00 | 0.00 |
April | 213.12 | 133.52 | 255.49 | 110.95 | 144.55 | 0.00 | 0.00 |
May | 177.75 | 110.50 | 233.56 | 69.56 | 164.01 | 0.00 | 0.00 |
June | 155.63 | 87.73 | 213.69 | 57.35 | 156.34 | 0.00 | 0.00 |
July | 190.02 | 80.99 | 233.03 | 85.32 | 147.71 | 0.00 | 0.00 |
August | 233.24 | 82.88 | 250.38 | 116.75 | 133.64 | 0.00 | 0.00 |
September | 271.36 | 110.89 | 277.52 | 153.30 | 124.23 | 0.00 | 0.00 |
October | 242.91 | 146.70 | 251.38 | 155.23 | 96.14 | 0.00 | 0.00 |
November | 121.28 | 173.78 | 148.55 | 85.12 | 63.43 | 0.00 | 0.00 |
December | 134.67 | 212.00 | 155.41 | 100.55 | 54.86 | 0.00 | 0.00 |
Annual Sum or Average | 188.00 | 140.93 | 219.26 | 107.24 | 112.01 | 0.00 | 0.00 |
Minimum of Months | 111.03 | 80.99 | 146.22 | 57.35 | 54.86 | 0.00 | 0.00 |
Maximum of Months | 271.36 | 212.00 | 277.52 | 155.23 | 164.01 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9192458.62 | 0.759968E+09 | 0.169456E+09 | 34240366.64 | 0.135216E+09 | 0.00 | 0.00 |
February | 95327189.84 | 0.610644E+09 | 0.282561E+09 | 0.101248E+09 | 0.181313E+09 | 0.00 | 0.00 |
March | 0.341653E+09 | 0.581520E+09 | 0.517346E+09 | 0.216929E+09 | 0.300417E+09 | 0.00 | 0.00 |
April | 0.713095E+09 | 0.464573E+09 | 0.813185E+09 | 0.415144E+09 | 0.398040E+09 | 0.00 | 0.00 |
May | 0.107352E+10 | 0.409798E+09 | 0.109265E+10 | 0.565552E+09 | 0.527097E+09 | 0.00 | 0.00 |
June | 0.118822E+10 | 0.328731E+09 | 0.115556E+10 | 0.678545E+09 | 0.477014E+09 | 0.00 | 0.00 |
July | 0.135492E+10 | 0.319745E+09 | 0.124746E+10 | 0.824608E+09 | 0.422851E+09 | 0.00 | 0.00 |
August | 0.104814E+10 | 0.323303E+09 | 0.991877E+09 | 0.628861E+09 | 0.363016E+09 | 0.00 | 0.00 |
September | 0.602725E+09 | 0.415811E+09 | 0.673696E+09 | 0.371788E+09 | 0.301908E+09 | 0.00 | 0.00 |
October | 0.237050E+09 | 0.560490E+09 | 0.398454E+09 | 0.177644E+09 | 0.220810E+09 | 0.00 | 0.00 |
November | 33691165.24 | 0.615042E+09 | 0.193434E+09 | 45911456.24 | 0.147523E+09 | 0.00 | 0.00 |
December | 3289120.07 | 0.782868E+09 | 0.141502E+09 | 31335965.57 | 0.110166E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.670082E+10 | 0.617249E+10 | 0.767718E+10 | 0.409181E+10 | 0.358537E+10 | 0.00 | 0.00 |
Minimum of Months | 3289120.07 | 0.319745E+09 | 0.141502E+09 | 31335965.57 | 0.110166E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135492E+10 | 0.782868E+09 | 0.124746E+10 | 0.824608E+09 | 0.527097E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147050E+10 | 0.278522E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.230729E+10 | 0.228955E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.273656E+10 | 0.229612E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.265210E+10 | 0.183713E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.225114E+10 | 0.159839E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.189612E+10 | 0.123854E+10 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.245030E+10 | 0.116296E+10 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.307844E+10 | 0.114793E+10 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.339250E+10 | 0.154405E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.313911E+10 | 0.212120E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.152588E+10 | 0.235635E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.176913E+10 | 0.287504E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286691E+11 | 0.232525E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147050E+10 | 0.114793E+10 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.339250E+10 | 0.287504E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148777E+10 | 0.269572E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.233486E+10 | 0.218557E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.277180E+10 | 0.216470E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.268544E+10 | 0.174092E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.227871E+10 | 0.151737E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.190983E+10 | 0.118132E+10 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.245495E+10 | 0.111133E+10 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.307915E+10 | 0.110187E+10 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.339900E+10 | 0.148280E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.316168E+10 | 0.200896E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.155625E+10 | 0.221628E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.178880E+10 | 0.276754E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.289082E+11 | 0.221744E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148777E+10 | 0.110187E+10 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.339900E+10 | 0.276754E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297371E+09 | 0.555963E+09 | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.00 | 0.00 |
February | 0.470795E+09 | 0.445802E+09 | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.00 | 0.00 |
March | 0.566075E+09 | 0.435532E+09 | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.00 | 0.00 |
April | 0.552413E+09 | 0.346077E+09 | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.00 | 0.00 |
May | 0.476095E+09 | 0.295950E+09 | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.00 | 0.00 |
June | 0.403390E+09 | 0.227398E+09 | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.00 | 0.00 |
July | 0.508940E+09 | 0.216920E+09 | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.00 | 0.00 |
August | 0.624723E+09 | 0.221980E+09 | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.00 | 0.00 |
September | 0.703366E+09 | 0.287416E+09 | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.00 | 0.00 |
October | 0.650623E+09 | 0.392919E+09 | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.00 | 0.00 |
November | 0.314363E+09 | 0.450438E+09 | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.00 | 0.00 |
December | 0.360704E+09 | 0.567827E+09 | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.592886E+10 | 0.444422E+10 | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.00 | 0.00 |
Minimum of Months | 0.297371E+09 | 0.216920E+09 | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.00 | 0.00 |
Maximum of Months | 0.703366E+09 | 0.567827E+09 | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.268045E+10 | -.225145E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -428999956.2 | 59.00 | 0.00 | 0.00 |
February | 0.244833E+10 | -.206449E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -383842808.2 | 58.99 | 0.00 | 0.00 |
March | 0.273238E+10 | -.231596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -416425296.9 | 58.99 | 0.00 | 0.00 |
April | 0.253482E+10 | -.214136E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -393461514.3 | 58.99 | 0.00 | 0.00 |
May | 0.253059E+10 | -.213336E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -397233078.7 | 58.99 | 0.00 | 0.00 |
June | 0.239194E+10 | -.201360E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -378345881.3 | 58.99 | 0.00 | 0.00 |
July | 0.235134E+10 | -.196383E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -387511583.6 | 58.99 | 0.00 | 0.00 |
August | 0.239605E+10 | -.200938E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -386671156.9 | 58.99 | 0.00 | 0.00 |
September | 0.231500E+10 | -.193719E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -377815537.0 | 58.99 | 0.00 | 0.00 |
October | 0.243761E+10 | -.203472E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -402890733.2 | 59.00 | 0.00 | 0.00 |
November | 0.244285E+10 | -.203902E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -403828202.2 | 58.99 | 0.00 | 0.00 |
December | 0.262431E+10 | -.219752E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -426792220.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298857E+11 | -.251019E+11 | 8760.00 | -.478382E+10 | 58.99 | |||||
Minimum of Months | 0.231500E+10 | -.231596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -428999956.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.273238E+10 | -.193719E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -377815537.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.838329E+10 | 43840.34 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.586923E+10 | 43840.34 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231219E+10 | 43840.34 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.768432E+09 | 43840.34 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46074986.41 | 34850.98 | 18-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227044E+09 | 43840.34 | 16-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274103E+10 | 43840.34 | 01-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.635689E+10 | 43840.34 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267042E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.838329E+10 | 43840.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188202E+11 | 227472.09 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115739E+11 | 227472.09 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177551E+10 | 227472.09 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189320E+09 | 24585.92 | 19-APR-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23400599.97 | 7002.51 | 16-OCT-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480534E+10 | 227472.09 | 13-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132588E+11 | 227472.09 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.504465E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188202E+11 | 227472.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230475E+10 | 34661.83 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130767E+10 | 34661.83 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432309E+09 | 34661.83 | 05-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136375E+09 | 34661.83 | 11-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6004966.64 | 9689.21 | 18-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14897426.24 | 15816.60 | 28-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.567239E+09 | 34661.83 | 11-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167575E+10 | 34661.83 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.644500E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230475E+10 | 34661.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.483683E+10 | 29450.54 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284950E+10 | 29450.54 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129604E+10 | 29450.54 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544519E+09 | 29450.54 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89923130.42 | 26339.87 | 18-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1882614.65 | 6049.06 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5148362.65 | 1065.74 | 27-SEP-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203069E+09 | 29450.54 | 28-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180612E+10 | 29450.54 | 10-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388707E+10 | 29450.54 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155201E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.483683E+10 | 29450.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174914E+11 | 36473.38 | 07-JAN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129714E+11 | 36815.38 | 18-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101284E+11 | 25958.49 | 05-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.618229E+10 | 21817.27 | 18-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399399E+10 | 19445.04 | 23-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156464E+10 | 14155.73 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.416113E+09 | 9057.63 | 09-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.218313E+09 | 9419.71 | 01-AUG-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.224033E+10 | 13453.18 | 26-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.604757E+10 | 17640.84 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123626E+11 | 29756.51 | 12-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160989E+11 | 36002.10 | 26-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897160E+11 | |||||||
Minimum of Months | 0.218313E+09 | 9057.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174914E+11 | 36815.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 36163.41 | 33578.38 | 55.78 | 27-FEB-17:50 | 52.07 | 0.00 |
March | 0.00 | 0.00 | 89556.47 | 74893.41 | 125.42 | 10-MAR-17:00 | 102.33 | 0.00 |
April | 0.00 | 0.00 | 0.527274E+09 | 0.488783E+09 | 11061.52 | 27-APR-15:00 | 9782.98 | 0.00 |
May | 0.00 | 0.00 | 0.127919E+10 | 0.111878E+10 | 12254.99 | 06-MAY-13:40 | 9841.09 | 0.00 |
June | 0.00 | 0.00 | 0.267179E+10 | 0.246262E+10 | 13335.03 | 28-JUN-15:00 | 12252.85 | 0.00 |
July | 0.00 | 0.00 | 0.649910E+10 | 0.547924E+10 | 16763.91 | 24-JUL-15:00 | 14870.29 | 0.00 |
August | 0.00 | 0.00 | 0.831110E+10 | 0.696071E+10 | 29415.02 | 10-AUG-04:01 | 21068.87 | 0.00 |
September | 0.00 | 0.00 | 0.218759E+10 | 0.175960E+10 | 13860.64 | 14-SEP-14:10 | 10989.65 | 0.00 |
October | 0.00 | 0.00 | 54111894.79 | 53976272.00 | 4411.23 | 04-OCT-15:00 | 4411.23 | 0.00 |
November | 0.00 | 0.00 | 33837342.25 | 25071971.97 | 3439.28 | 04-NOV-14:10 | 2582.24 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.215641E+11 | 0.183489E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.831110E+10 | 0.696071E+10 | 29415.02 | 21068.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 275420.65 | 251790.67 | 459.03 | 11-JAN-15:40 | 419.65 | 0.00 |
February | 0.00 | 0.00 | 42641227.00 | 41912648.81 | 8107.78 | 27-FEB-15:10 | 8107.78 | 0.00 |
March | 0.00 | 0.00 | 0.170744E+09 | 0.170090E+09 | 17350.17 | 18-MAR-16:00 | 17350.17 | 0.00 |
April | 0.00 | 0.00 | 0.491796E+10 | 0.464494E+10 | 70053.31 | 27-APR-15:00 | 64483.59 | 0.00 |
May | 0.00 | 0.00 | 0.110690E+11 | 0.978391E+10 | 132020.59 | 06-MAY-04:03 | 96317.26 | 0.00 |
June | 0.00 | 0.00 | 0.213427E+11 | 0.197990E+11 | 133281.20 | 23-JUN-04:03 | 99253.25 | 0.00 |
July | 0.00 | 0.00 | 0.424721E+11 | 0.363274E+11 | 138278.47 | 31-JUL-04:01 | 98250.73 | 0.00 |
August | 0.00 | 0.00 | 0.518248E+11 | 0.439764E+11 | 140632.66 | 25-AUG-04:01 | 96429.27 | 0.00 |
September | 0.00 | 0.00 | 0.170768E+11 | 0.139307E+11 | 136365.54 | 01-SEP-04:03 | 97957.09 | 0.00 |
October | 0.00 | 0.00 | 0.103964E+10 | 0.101313E+10 | 36587.82 | 04-OCT-15:00 | 36587.82 | 0.00 |
November | 0.00 | 0.00 | 0.520885E+09 | 0.392069E+09 | 34983.96 | 04-NOV-14:30 | 27083.24 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150478E+12 | 0.130080E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.518248E+11 | 0.439764E+11 | 140632.66 | 99253.25 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 299.36 | 289.22 | 0.11 | 11-JAN-18:40 | 0.11 | 0.00 |
February | 0.00 | 0.00 | 31004798.93 | 30900929.28 | 3707.94 | 27-FEB-15:00 | 3707.94 | 0.00 |
March | 0.00 | 0.00 | 48593923.10 | 48556524.87 | 4289.61 | 18-MAR-14:00 | 4289.61 | 0.00 |
April | 0.00 | 0.00 | 0.857099E+09 | 0.820432E+09 | 11927.74 | 27-APR-14:10 | 11319.57 | 0.00 |
May | 0.00 | 0.00 | 0.144850E+10 | 0.130307E+10 | 10687.42 | 06-MAY-13:30 | 9090.03 | 0.00 |
June | 0.00 | 0.00 | 0.249636E+10 | 0.237156E+10 | 10013.74 | 28-JUN-16:00 | 9625.33 | 0.00 |
July | 0.00 | 0.00 | 0.553729E+10 | 0.484920E+10 | 21341.04 | 31-JUL-04:01 | 14975.56 | 0.00 |
August | 0.00 | 0.00 | 0.759472E+10 | 0.664851E+10 | 21723.94 | 25-AUG-04:01 | 14698.82 | 0.00 |
September | 0.00 | 0.00 | 0.339197E+10 | 0.281944E+10 | 20914.64 | 14-SEP-04:02 | 13529.06 | 0.00 |
October | 0.00 | 0.00 | 0.433467E+09 | 0.417309E+09 | 9537.99 | 04-OCT-14:40 | 9537.99 | 0.00 |
November | 0.00 | 0.00 | 0.154929E+09 | 0.117953E+09 | 9553.80 | 04-NOV-14:00 | 7536.56 | 0.00 |
December | 0.00 | 0.00 | 7220.95 | 7214.61 | 0.46 | 02-DEC-13:00 | 0.46 | 0.00 |
Annual Sum or Average | 0.219939E+11 | 0.194269E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 299.36 | 289.22 | 0.11 | 0.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.759472E+10 | 0.664851E+10 | 21723.94 | 14975.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9220430.06 | 9199074.03 | 1839.33 | 27-FEB-15:10 | 1839.33 | 0.00 |
March | 0.00 | 0.00 | 20541584.25 | 20540790.93 | 2306.28 | 18-MAR-14:00 | 2306.28 | 0.00 |
April | 0.00 | 0.00 | 0.547927E+09 | 0.522381E+09 | 9346.24 | 27-APR-14:10 | 8778.35 | 0.00 |
May | 0.00 | 0.00 | 0.870960E+09 | 0.781885E+09 | 7993.70 | 06-MAY-13:30 | 6650.36 | 0.00 |
June | 0.00 | 0.00 | 0.148854E+10 | 0.140782E+10 | 7577.67 | 28-JUN-16:00 | 7217.56 | 0.00 |
July | 0.00 | 0.00 | 0.368207E+10 | 0.320250E+10 | 10887.00 | 31-JUL-14:10 | 9602.17 | 0.00 |
August | 0.00 | 0.00 | 0.541738E+10 | 0.471436E+10 | 18190.17 | 25-AUG-04:01 | 12097.90 | 0.00 |
September | 0.00 | 0.00 | 0.236982E+10 | 0.195492E+10 | 17514.59 | 14-SEP-04:02 | 11111.63 | 0.00 |
October | 0.00 | 0.00 | 0.257253E+09 | 0.250106E+09 | 7535.94 | 04-OCT-14:30 | 7535.94 | 0.00 |
November | 0.00 | 0.00 | 94882798.78 | 71765268.29 | 6762.79 | 04-NOV-14:00 | 5267.33 | 0.00 |
December | 0.00 | 0.00 | 1449.31 | 1449.31 | 0.31 | 02-DEC-12:07 | 0.31 | 0.00 |
Annual Sum or Average | 0.147586E+11 | 0.129355E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.541738E+10 | 0.471436E+10 | 18190.17 | 12097.90 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.428035E+10 | 0.53 | 2729.58 | 01-JAN-01:37 | 0.91 |
February | 0.375404E+10 | 0.52 | 2729.58 | 01-FEB-05:01 | 0.91 |
March | 0.397110E+10 | 0.49 | 2729.58 | 01-MAR-05:02 | 0.91 |
April | 0.338627E+10 | 0.43 | 2729.58 | 01-APR-04:01 | 0.91 |
May | 0.299464E+10 | 0.37 | 2729.58 | 01-MAY-04:03 | 0.91 |
June | 0.228782E+10 | 0.29 | 2729.58 | 01-JUN-07:10 | 0.91 |
July | 0.152409E+10 | 0.19 | 2729.58 | 01-JUL-07:10 | 0.91 |
August | 0.122697E+10 | 0.15 | 2729.58 | 01-AUG-07:10 | 0.90 |
September | 0.242198E+10 | 0.31 | 2729.58 | 01-SEP-07:10 | 0.90 |
October | 0.358971E+10 | 0.45 | 2729.58 | 01-OCT-07:03 | 0.90 |
November | 0.381482E+10 | 0.49 | 2729.58 | 01-NOV-04:02 | 0.91 |
December | 0.420386E+10 | 0.52 | 2729.58 | 01-DEC-05:01 | 0.91 |
Annual Sum or Average | 0.374557E+11 | 0.40 | |||
Minimum of Months | 0.122697E+10 | 0.15 | 2729.58 | 0.90 | |
Maximum of Months | 0.428035E+10 | 0.53 | 2729.58 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.300678E+10 | 0.57 | 1836.42 | 01-JAN-09:40 | 0.91 |
February | 0.272118E+10 | 0.57 | 1836.42 | 01-FEB-06:30 | 0.91 |
March | 0.302737E+10 | 0.57 | 1836.42 | 01-MAR-06:57 | 0.91 |
April | 0.289107E+10 | 0.56 | 1836.42 | 01-APR-05:37 | 0.91 |
May | 0.296955E+10 | 0.55 | 1836.42 | 01-MAY-13:20 | 0.90 |
June | 0.289567E+10 | 0.55 | 1836.42 | 01-JUN-11:30 | 0.91 |
July | 0.294855E+10 | 0.54 | 1836.42 | 01-JUL-14:10 | 0.90 |
August | 0.299558E+10 | 0.55 | 1836.42 | 01-AUG-15:30 | 0.90 |
September | 0.287583E+10 | 0.55 | 1836.42 | 03-SEP-10:24 | 0.90 |
October | 0.294604E+10 | 0.55 | 1836.42 | 02-OCT-13:20 | 0.91 |
November | 0.286651E+10 | 0.56 | 1836.42 | 01-NOV-06:45 | 0.91 |
December | 0.300316E+10 | 0.57 | 1836.42 | 02-DEC-06:35 | 0.91 |
Annual Sum or Average | 0.351473E+11 | 0.56 | |||
Minimum of Months | 0.272118E+10 | 0.54 | 1836.42 | 0.90 | |
Maximum of Months | 0.302737E+10 | 0.57 | 1836.42 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.232790E+11 | 0.96 | 14462.55 | 01-JAN-08:70 | 1.56 |
February | 0.210996E+11 | 0.96 | 14462.55 | 01-FEB-07:43 | 1.56 |
March | 0.235872E+11 | 0.95 | 14462.55 | 01-MAR-07:50 | 1.56 |
April | 0.226484E+11 | 0.94 | 14462.55 | 01-APR-13:20 | 1.56 |
May | 0.233891E+11 | 0.94 | 14462.55 | 01-MAY-11:20 | 1.55 |
June | 0.228583E+11 | 0.95 | 14462.55 | 01-JUN-09:30 | 1.55 |
July | 0.233629E+11 | 0.94 | 14462.55 | 01-JUL-06:00 | 1.55 |
August | 0.237865E+11 | 0.96 | 14462.55 | 01-AUG-05:50 | 1.55 |
September | 0.227091E+11 | 0.94 | 14462.55 | 01-SEP-09:47 | 1.55 |
October | 0.231690E+11 | 0.93 | 14462.55 | 01-OCT-09:35 | 1.55 |
November | 0.223561E+11 | 0.94 | 14462.55 | 01-NOV-15:50 | 1.55 |
December | 0.232991E+11 | 0.96 | 14462.55 | 01-DEC-09:50 | 1.56 |
Annual Sum or Average | 0.275544E+12 | 0.95 | |||
Minimum of Months | 0.210996E+11 | 0.93 | 14462.55 | 1.55 | |
Maximum of Months | 0.237865E+11 | 0.96 | 14462.55 | 1.56 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.237533E+10 | 0.59 | 1468.15 | 04-JAN-20:30 | 0.95 |
February | 0.215021E+10 | 0.59 | 1468.15 | 07-FEB-16:40 | 0.95 |
March | 0.240049E+10 | 0.59 | 1468.15 | 04-MAR-16:10 | 0.95 |
April | 0.230154E+10 | 0.58 | 1468.15 | 05-APR-11:10 | 0.94 |
May | 0.237330E+10 | 0.57 | 1468.15 | 03-MAY-18:20 | 0.94 |
June | 0.231498E+10 | 0.57 | 1468.15 | 01-JUN-10:59 | 0.95 |
July | 0.236075E+10 | 0.57 | 1468.15 | 01-JUL-09:55 | 0.94 |
August | 0.241082E+10 | 0.58 | 1468.15 | 02-AUG-15:20 | 0.94 |
September | 0.230427E+10 | 0.57 | 1468.15 | 01-SEP-16:30 | 0.94 |
October | 0.235216E+10 | 0.57 | 1468.15 | 02-OCT-10:40 | 0.94 |
November | 0.227555E+10 | 0.58 | 1468.15 | 08-NOV-16:20 | 0.94 |
December | 0.237545E+10 | 0.59 | 1468.15 | 07-DEC-08:50 | 0.95 |
Annual Sum or Average | 0.279948E+11 | 0.58 | |||
Minimum of Months | 0.215021E+10 | 0.57 | 1468.15 | 0.94 | |
Maximum of Months | 0.241082E+10 | 0.59 | 1468.15 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196260E+10 | 0.59 | 1207.28 | 01-JAN-14:00 | 0.95 |
February | 0.177587E+10 | 0.60 | 1207.28 | 01-FEB-06:13 | 0.94 |
March | 0.198080E+10 | 0.60 | 1207.28 | 01-MAR-06:10 | 0.95 |
April | 0.189717E+10 | 0.59 | 1207.28 | 01-APR-05:10 | 0.95 |
May | 0.195259E+10 | 0.57 | 1207.28 | 01-MAY-13:40 | 0.94 |
June | 0.190364E+10 | 0.57 | 1207.28 | 01-JUN-10:57 | 0.94 |
July | 0.193841E+10 | 0.56 | 1207.28 | 01-JUL-10:25 | 0.94 |
August | 0.197365E+10 | 0.58 | 1207.28 | 01-AUG-11:02 | 0.94 |
September | 0.189208E+10 | 0.57 | 1207.28 | 01-SEP-16:10 | 0.94 |
October | 0.193631E+10 | 0.57 | 1207.28 | 01-OCT-14:10 | 0.94 |
November | 0.187836E+10 | 0.58 | 1207.28 | 01-NOV-06:45 | 0.94 |
December | 0.196225E+10 | 0.59 | 1207.28 | 01-DEC-06:03 | 0.95 |
Annual Sum or Average | 0.230537E+11 | 0.58 | |||
Minimum of Months | 0.177587E+10 | 0.56 | 1207.28 | 0.94 | |
Maximum of Months | 0.198080E+10 | 0.60 | 1207.28 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.40 | 0.00 |
February | 0.50 | 0.00 |
March | 0.22 | 0.00 |
April | 0.06 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.06 | 0.00 |
November | 0.04 | 0.00 |
December | 0.49 | 0.00 |
Annual Sum or Average | 2.76 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.40 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.21 | 19.13 |
March | 0.81 | 25.84 |
April | 1.35 | 25.84 |
May | 0.21 | 25.84 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.33 | 0.00 |
September | 0.00 | 0.00 |
October | 0.60 | 25.84 |
November | 0.49 | 16.98 |
December | 0.33 | 12.92 |
Annual Sum or Average | 4.33 | 21.53 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.35 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.43 | 0.00 |
February | 0.10 | 0.00 |
March | 0.29 | 1.04 |
April | 0.33 | 1.42 |
May | 0.21 | 0.49 |
June | 0.14 | 0.00 |
July | 0.28 | 0.00 |
August | 0.39 | 0.00 |
September | 0.22 | 0.00 |
October | 0.17 | 0.00 |
November | 0.22 | 0.00 |
December | 0.26 | 0.00 |
Annual Sum or Average | 3.04 | 0.29 |
Minimum of Months | 0.10 | 0.00 |
Maximum of Months | 0.43 | 1.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.37 | 0.00 |
February | 0.36 | 0.00 |
March | 0.06 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.22 | 1.83 |
November | 0.00 | 0.00 |
December | 0.35 | 0.00 |
Annual Sum or Average | 2.36 | 0.17 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.37 | 1.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 55.59 | 0.00 |
February | 39.11 | 0.00 |
March | 27.76 | 0.00 |
April | 16.50 | 0.00 |
May | 17.71 | 0.00 |
June | 29.97 | 0.00 |
July | 31.58 | 0.00 |
August | 24.47 | 0.00 |
September | 22.78 | 0.00 |
October | 14.18 | 0.00 |
November | 28.83 | 0.00 |
December | 52.64 | 0.00 |
Annual Sum or Average | 361.11 | 0.00 |
Minimum of Months | 14.18 | 0.00 |
Maximum of Months | 55.59 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.300678E+10 | 0.104791E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.272119E+10 | 0.733654E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.302740E+10 | 0.289024E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.305071E+10 | 0.960540E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.334195E+10 | 57593733.01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.367281E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.482152E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.540900E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.350245E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.296210E+10 | 0.283805E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.287660E+10 | 0.342629E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.300316E+10 | 0.794611E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.413957E+11 | 0.333802E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.272119E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.540900E+10 | 0.104791E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.232791E+11 | 0.235253E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.211136E+11 | 0.144674E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.236421E+11 | 0.221939E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.242021E+11 | 0.236650E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.267963E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.294448E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.363238E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.397034E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.279075E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.234976E+11 | 29250749.97 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.225188E+11 | 0.600668E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.232991E+11 | 0.165735E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.321728E+12 | 0.630581E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.211136E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.397034E+11 | 0.235253E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.237533E+10 | 0.288093E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.215934E+10 | 0.163459E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.241458E+10 | 0.540387E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.254895E+10 | 0.170468E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.278610E+10 | 7506208.30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.303368E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.394060E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.457051E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.323497E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.247481E+10 | 18621782.80 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.231825E+10 | 0.709049E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.237546E+10 | 0.209469E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.342326E+11 | 0.805625E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.215934E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.457051E+10 | 0.288093E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.196260E+10 | 0.604603E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.177834E+10 | 0.356187E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.198624E+10 | 0.162005E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.204069E+10 | 0.680649E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.217804E+10 | 0.112404E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.229237E+10 | 2353268.31 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.289099E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.336516E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.247641E+10 | 6435453.31 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.200139E+10 | 0.253836E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.190214E+10 | 0.225765E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.196225E+10 | 0.485884E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.268366E+11 | 0.194001E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.177834E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.336516E+10 | 0.604603E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.300678E+10 | 0.00 | 0.838329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272118E+10 | 36163.41 | 0.586923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302737E+10 | 89556.47 | 0.231219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289107E+10 | 0.527274E+09 | 0.768432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.296955E+10 | 0.127919E+10 | 46074986.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.289567E+10 | 0.267179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294855E+10 | 0.649910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.299558E+10 | 0.831110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287583E+10 | 0.218759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294604E+10 | 54111894.79 | 0.227044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286651E+10 | 33837342.25 | 0.274103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300316E+10 | 0.00 | 0.635689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351473E+11 | 0.215641E+11 | 0.267042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302737E+10 | 0.831110E+10 | 0.838329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.232790E+11 | 275420.65 | 0.188202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210996E+11 | 42641227.00 | 0.115739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235872E+11 | 0.170744E+09 | 0.177551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226484E+11 | 0.491796E+10 | 0.189320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233891E+11 | 0.110690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228583E+11 | 0.213427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.233629E+11 | 0.424721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.237865E+11 | 0.518248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227091E+11 | 0.170768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231690E+11 | 0.103964E+10 | 23400599.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223561E+11 | 0.520885E+09 | 0.480534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232991E+11 | 0.00 | 0.132588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275544E+12 | 0.150478E+12 | 0.504465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.210996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.237865E+11 | 0.518248E+11 | 0.188202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.237533E+10 | 299.36 | 0.230475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215021E+10 | 31004798.93 | 0.130767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240049E+10 | 48593923.10 | 0.432309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230154E+10 | 0.857099E+09 | 0.136375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237330E+10 | 0.144850E+10 | 6004966.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231498E+10 | 0.249636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.236075E+10 | 0.553729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.241082E+10 | 0.759472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230427E+10 | 0.339197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235216E+10 | 0.433467E+09 | 14897426.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227555E+10 | 0.154929E+09 | 0.567239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237545E+10 | 7220.95 | 0.167575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279948E+11 | 0.219939E+11 | 0.644500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.215021E+10 | 299.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.241082E+10 | 0.759472E+10 | 0.230475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.196260E+10 | 0.00 | 0.483683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177587E+10 | 9220430.06 | 0.284950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198080E+10 | 20541584.25 | 0.129604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189717E+10 | 0.547927E+09 | 0.544519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195259E+10 | 0.870960E+09 | 89923130.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190364E+10 | 0.148854E+10 | 1882614.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193841E+10 | 0.368207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197365E+10 | 0.541738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189208E+10 | 0.236982E+10 | 5148362.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193631E+10 | 0.257253E+09 | 0.203069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187836E+10 | 94882798.78 | 0.180612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196225E+10 | 1449.31 | 0.388707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230537E+11 | 0.147586E+11 | 0.155201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.177587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198080E+10 | 0.541738E+10 | 0.483683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.300678E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272118E+10 | 0.00 | 0.00 | 0.00 | 11140.40 | 0.00 | 0.733654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.302737E+10 | 0.00 | 0.00 | 0.00 | 27544.25 | 0.00 | 0.289024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.289107E+10 | 0.00 | 0.00 | 0.00 | 0.159644E+09 | 0.00 | 0.960540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.296955E+10 | 0.00 | 0.00 | 0.00 | 0.372401E+09 | 0.00 | 57593733.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.289567E+10 | 0.00 | 0.00 | 0.00 | 0.777145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294855E+10 | 0.00 | 0.00 | 0.00 | 0.187296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.299558E+10 | 0.00 | 0.00 | 0.00 | 0.241342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287583E+10 | 0.00 | 0.00 | 0.00 | 0.626621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294604E+10 | 0.00 | 0.00 | 0.00 | 16064387.52 | 0.00 | 0.283805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286651E+10 | 0.00 | 0.00 | 0.00 | 10095288.50 | 0.00 | 0.342629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351473E+11 | 0.00 | 0.00 | 0.00 | 0.624839E+10 | 0.00 | 0.333802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.272118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.302737E+10 | 0.00 | 0.00 | 0.00 | 0.241342E+10 | 0.00 | 0.104791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.232790E+11 | 0.00 | 0.00 | 0.00 | 91773.87 | 0.00 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210996E+11 | 0.00 | 0.00 | 0.00 | 13989902.14 | 0.00 | 0.144674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235872E+11 | 0.00 | 0.00 | 0.00 | 54874435.52 | 0.00 | 0.221939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226484E+11 | 0.00 | 0.00 | 0.00 | 0.155373E+10 | 0.00 | 0.236650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233891E+11 | 0.00 | 0.00 | 0.00 | 0.340729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.228583E+11 | 0.00 | 0.00 | 0.00 | 0.658648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.233629E+11 | 0.00 | 0.00 | 0.00 | 0.129609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.237865E+11 | 0.00 | 0.00 | 0.00 | 0.159169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.227091E+11 | 0.00 | 0.00 | 0.00 | 0.519843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231690E+11 | 0.00 | 0.00 | 0.00 | 0.328638E+09 | 0.00 | 29250749.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223561E+11 | 0.00 | 0.00 | 0.00 | 0.162635E+09 | 0.00 | 0.600668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275544E+12 | 0.00 | 0.00 | 0.00 | 0.461840E+11 | 0.00 | 0.630581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.210996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.237865E+11 | 0.00 | 0.00 | 0.00 | 0.159169E+11 | 0.00 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.237533E+10 | 0.00 | 0.00 | 0.00 | 92.23 | 0.00 | 0.288093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215021E+10 | 0.00 | 0.00 | 0.00 | 9130846.51 | 0.00 | 0.163459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240049E+10 | 0.00 | 0.00 | 0.00 | 14092566.33 | 0.00 | 0.540387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230154E+10 | 0.00 | 0.00 | 0.00 | 0.247419E+09 | 0.00 | 0.170468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.237330E+10 | 0.00 | 0.00 | 0.00 | 0.412803E+09 | 0.00 | 7506208.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.231498E+10 | 0.00 | 0.00 | 0.00 | 0.718696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.236075E+10 | 0.00 | 0.00 | 0.00 | 0.157985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.241082E+10 | 0.00 | 0.00 | 0.00 | 0.215970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230427E+10 | 0.00 | 0.00 | 0.00 | 0.930701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235216E+10 | 0.00 | 0.00 | 0.00 | 0.122654E+09 | 0.00 | 18621782.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227555E+10 | 0.00 | 0.00 | 0.00 | 42699446.09 | 0.00 | 0.709049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237545E+10 | 0.00 | 0.00 | 0.00 | 2213.67 | 0.00 | 0.209469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279948E+11 | 0.00 | 0.00 | 0.00 | 0.623774E+10 | 0.00 | 0.805625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.215021E+10 | 0.00 | 0.00 | 0.00 | 92.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.241082E+10 | 0.00 | 0.00 | 0.00 | 0.215970E+10 | 0.00 | 0.288093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.196260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177587E+10 | 0.00 | 0.00 | 0.00 | 2464495.47 | 0.00 | 0.356187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198080E+10 | 0.00 | 0.00 | 0.00 | 5435057.71 | 0.00 | 0.162005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189717E+10 | 0.00 | 0.00 | 0.00 | 0.143524E+09 | 0.00 | 0.680649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195259E+10 | 0.00 | 0.00 | 0.00 | 0.225448E+09 | 0.00 | 0.112404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.388726E+09 | 0.00 | 2353268.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193841E+10 | 0.00 | 0.00 | 0.00 | 0.952579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197365E+10 | 0.00 | 0.00 | 0.00 | 0.139150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189208E+10 | 0.00 | 0.00 | 0.00 | 0.584326E+09 | 0.00 | 6435453.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193631E+10 | 0.00 | 0.00 | 0.00 | 65074511.56 | 0.00 | 0.253836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187836E+10 | 0.00 | 0.00 | 0.00 | 23775236.68 | 0.00 | 0.225765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196225E+10 | 0.00 | 0.00 | 0.00 | 397.33 | 0.00 | 0.485884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230537E+11 | 0.00 | 0.00 | 0.00 | 0.378286E+10 | 0.00 | 0.194001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.177587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.198080E+10 | 0.00 | 0.00 | 0.00 | 0.139150E+10 | 0.00 | 0.604603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485041E+10 | 0.00 | 0.00 | 0.20 |
February | 0.326600E+10 | 0.00 | 0.00 | 48302.22 | 0.00 | 0.323099E+10 | 0.137222E+09 | 0.00 | 0.21 |
March | 0.536230E+10 | 0.00 | 0.00 | 106573.83 | 0.00 | 0.116965E+10 | 0.254174E+09 | 0.00 | 0.21 |
April | 0.372173E+10 | 5955204.58 | 0.00 | 2104353.62 | 0.00 | 0.331209E+09 | 0.228422E+10 | 0.00 | 0.27 |
May | 0.171562E+10 | 3726845.98 | 0.00 | 7308047.56 | 0.00 | 1279419.16 | 0.604757E+10 | 0.00 | 0.45 |
June | 0.644415E+09 | 5674225.96 | 0.00 | 12949708.70 | 0.00 | 0.00 | 0.779179E+10 | 0.00 | 0.64 |
July | 0.295333E+09 | 0.177275E+09 | 0.00 | 14540517.40 | 0.00 | 0.00 | 0.657698E+10 | 0.00 | 0.70 |
August | 0.246645E+09 | 0.384101E+09 | 0.00 | 12144768.99 | 0.00 | 0.00 | 0.575259E+10 | 0.00 | 0.65 |
September | 0.893294E+09 | 5709532.69 | 0.00 | 11085214.17 | 0.00 | 0.00 | 0.722421E+10 | 0.00 | 0.58 |
October | 0.356846E+10 | 0.00 | 0.00 | 2761913.10 | 0.00 | 95504756.15 | 0.340983E+10 | 0.00 | 0.28 |
November | 0.458765E+10 | 0.00 | 0.00 | 433648.28 | 0.00 | 0.145923E+10 | 0.620038E+09 | 0.00 | 0.22 |
December | 0.367914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377234E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.309332E+11 | 0.582442E+09 | 0.00 | 63483047.87 | 0.00 | 0.149106E+11 | 0.400986E+11 | 0.00 | 0.39 |
Minimum of Months | 0.246645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.536230E+10 | 0.384101E+09 | 0.00 | 14540517.40 | 0.00 | 0.485041E+10 | 0.779179E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.523536E+11 | 0.00 | 0.00 | 58465.19 | 0.00 | 0.878595E+10 | 0.215744E+09 | 0.00 | 0.39 |
February | 0.445104E+11 | 0.00 | 0.00 | 2924948.37 | 0.00 | 0.434433E+10 | 0.445069E+10 | 0.00 | 0.41 |
March | 0.388769E+11 | 0.00 | 0.00 | 11422178.89 | 0.00 | 0.163330E+09 | 0.173811E+11 | 0.00 | 0.44 |
April | 0.185834E+11 | 69466468.67 | 0.00 | 34645176.83 | 0.00 | 0.00 | 0.349285E+11 | 0.00 | 0.56 |
May | 0.881479E+10 | 63627635.65 | 0.00 | 63558240.72 | 0.00 | 0.00 | 0.492072E+11 | 0.00 | 0.75 |
June | 0.255286E+10 | 60583625.75 | 0.00 | 89976802.89 | 0.00 | 0.00 | 0.508499E+11 | 0.00 | 0.92 |
July | 0.386644E+09 | 0.147341E+10 | 0.00 | 92439774.11 | 0.00 | 0.00 | 0.393933E+11 | 0.00 | 0.93 |
August | 0.613223E+09 | 0.318690E+10 | 0.00 | 80352648.61 | 0.00 | 0.00 | 0.336740E+11 | 0.00 | 0.88 |
September | 0.432071E+10 | 90150421.74 | 0.00 | 75755217.63 | 0.00 | 0.00 | 0.477654E+11 | 0.00 | 0.85 |
October | 0.181031E+11 | 0.00 | 0.00 | 35162897.44 | 0.00 | 0.00 | 0.389313E+11 | 0.00 | 0.56 |
November | 0.410501E+11 | 0.00 | 0.00 | 9146280.83 | 0.00 | 0.989948E+09 | 0.116309E+11 | 0.00 | 0.42 |
December | 0.536599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496576E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.283826E+12 | 0.494414E+10 | 0.00 | 0.495443E+09 | 0.00 | 0.192493E+11 | 0.328428E+12 | 0.00 | 0.63 |
Minimum of Months | 0.386644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.536599E+11 | 0.318690E+10 | 0.00 | 92439774.11 | 0.00 | 0.878595E+10 | 0.508499E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.444141E+10 | 0.00 | 0.00 | 210905.74 | 0.00 | 0.113790E+10 | 0.300326E+09 | 0.00 | 0.40 |
February | 0.308211E+10 | 0.00 | 0.00 | 1759525.27 | 0.00 | 0.579739E+09 | 0.190692E+10 | 0.00 | 0.47 |
March | 0.213313E+10 | 0.00 | 0.00 | 4294569.42 | 0.00 | 0.197708E+09 | 0.430400E+10 | 0.00 | 0.58 |
April | 0.117235E+10 | 9222759.10 | 0.00 | 6953371.23 | 0.00 | 50641382.16 | 0.520751E+10 | 0.00 | 0.79 |
May | 0.700015E+09 | 13854657.47 | 0.00 | 9642242.59 | 0.00 | 0.00 | 0.627312E+10 | 0.00 | 1.08 |
June | 0.289324E+09 | 9748313.18 | 0.00 | 12612306.35 | 0.00 | 0.00 | 0.641411E+10 | 0.00 | 1.38 |
July | 65645568.85 | 0.186001E+09 | 0.00 | 13071835.06 | 0.00 | 0.00 | 0.523017E+10 | 0.00 | 1.45 |
August | 86874273.55 | 0.407359E+09 | 0.00 | 11919834.83 | 0.00 | 0.00 | 0.460959E+10 | 0.00 | 1.36 |
September | 0.286303E+09 | 57011542.87 | 0.00 | 13969298.23 | 0.00 | 0.00 | 0.666600E+10 | 0.00 | 1.36 |
October | 0.993384E+09 | 0.00 | 0.00 | 8879820.06 | 0.00 | 0.00 | 0.663287E+10 | 0.00 | 0.88 |
November | 0.289871E+10 | 0.00 | 0.00 | 2502315.88 | 0.00 | 0.255361E+09 | 0.246754E+10 | 0.00 | 0.49 |
December | 0.395505E+10 | 0.00 | 0.00 | 939163.95 | 0.00 | 0.862542E+09 | 0.106897E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.201043E+11 | 0.683197E+09 | 0.00 | 86755188.62 | 0.00 | 0.308389E+10 | 0.510811E+11 | 0.00 | 0.89 |
Minimum of Months | 65645568.85 | 0.00 | 0.00 | 210905.74 | 0.00 | 0.00 | 0.300326E+09 | 0.00 | 0.40 |
Maximum of Months | 0.444141E+10 | 0.407359E+09 | 0.00 | 13969298.23 | 0.00 | 0.113790E+10 | 0.666600E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308658E+10 | 0.00 | 0.00 | 0.39 |
February | 0.287779E+10 | 0.00 | 0.00 | 291498.59 | 0.00 | 0.165537E+10 | 0.341879E+09 | 0.00 | 0.42 |
March | 0.310329E+10 | 0.00 | 0.00 | 1108533.31 | 0.00 | 0.797454E+09 | 0.122657E+10 | 0.00 | 0.45 |
April | 0.220225E+10 | 8459528.15 | 0.00 | 2662030.89 | 0.00 | 0.265540E+09 | 0.213321E+10 | 0.00 | 0.56 |
May | 0.144029E+10 | 7361582.62 | 0.00 | 4420118.41 | 0.00 | 29299422.23 | 0.328205E+10 | 0.00 | 0.75 |
June | 0.708282E+09 | 7737210.53 | 0.00 | 6687685.96 | 0.00 | 0.00 | 0.395763E+10 | 0.00 | 0.99 |
July | 0.380616E+09 | 0.153063E+09 | 0.00 | 7487037.27 | 0.00 | 0.00 | 0.345824E+10 | 0.00 | 1.08 |
August | 0.264253E+09 | 0.358683E+09 | 0.00 | 6895170.03 | 0.00 | 0.00 | 0.316383E+10 | 0.00 | 1.03 |
September | 0.795832E+09 | 36871096.45 | 0.00 | 8145109.44 | 0.00 | 0.00 | 0.408499E+10 | 0.00 | 0.98 |
October | 0.217138E+10 | 0.00 | 0.00 | 4082181.48 | 0.00 | 0.105833E+09 | 0.311418E+10 | 0.00 | 0.62 |
November | 0.319036E+10 | 0.00 | 0.00 | 542917.35 | 0.00 | 0.108613E+10 | 0.425267E+09 | 0.00 | 0.42 |
December | 0.272832E+10 | 0.00 | 0.00 | 143940.94 | 0.00 | 0.253815E+10 | 0.177766E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.224321E+11 | 0.572176E+09 | 0.00 | 42466223.67 | 0.00 | 0.956437E+10 | 0.253656E+11 | 0.00 | 0.67 |
Minimum of Months | 0.264253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.319036E+10 | 0.358683E+09 | 0.00 | 8145109.44 | 0.00 | 0.308658E+10 | 0.408499E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:04
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |