Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2020-06-03 19:11:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1704.84 | 743.18 | 743.18 |
Net Site Energy | 1704.84 | 743.18 | 743.18 |
Total Source Energy | 4208.39 | 1834.53 | 1834.53 |
Net Source Energy | 4208.39 | 1834.53 | 1834.53 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 474.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 109.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 373.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 381.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 96.73 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1133.14 | 571.70 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 474.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 109.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 373.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 381.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 96.73 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 194.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.23 | 249.22 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 493.96 | 249.22 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 194.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.23 | 249.22 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 493.96 | 249.22 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1133.145 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1133.145 | 100.00 |
Total On-Site and Utility Electric Sources | 1133.145 | 100.00 |
Total Electricity End Uses | 1133.145 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1903.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.7888 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 16.5511 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 12.6567 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-13:00 | 07-FEB-07:10 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 241600.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47543.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24923.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18373.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 3873.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 101611.38 | 245473.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 241600.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 47543.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24923.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18373.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 3873.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 514.86 | 0.00 | 0.00 | 0.00 |
Cooling | 347.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1183.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 231.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1208.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 104.86 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3588.67 | 619.72 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 224.44 | 0.00 | 0.00 | 0.00 |
Cooling | 151.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 515.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 526.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.71 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1564.38 | 270.15 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 224.44 | 0.00 | 0.00 | 0.00 |
Cooling | 151.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 515.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 526.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 45.71 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1564.38 | 270.15 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.78 |
CORE_RETAIL DIRECT AIR | 7.54 |
POINT_OF_SALE DIRECT AIR | 1.10 |
FRONT_RETAIL DIRECT AIR | 0.841601 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 2.55 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 2.55 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 58083.45 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 50360.95 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 253022.17 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 32630.82 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 26726.69 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.78 | 1.78 | 1.78 | 1.78 | 1.81 | 1.81 | 1.00 | 0.984766 | 1.81 |
PSZ-AC:2 | 7.54 | 7.54 | 7.54 | 7.54 | 7.77 | 7.77 | 1.00 | 0.970903 | 7.77 |
PSZ-AC:3 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-AC:4 | 0.841601 | 0.841601 | 0.841601 | 0.841601 | 0.844259 | 0.844259 | 1.00 | 0.996852 | 0.844259 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.81 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.77 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.10 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.844259 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.81 | 1.81 | 1.81 | 1.81 | 33980.86 | 50360.95 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.77 | 7.77 | 7.77 | 7.77 | 165100.69 | 253022.17 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 21157.32 | 32630.82 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.844259 | 0.844259 | 0.844259 | 0.844259 | 17063.10 | 26726.69 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.81 | 0.906195 | 1.81 | 31701.10 | 33980.86 | 16990.43 | 33980.86 | 0.755601 | 0.755600 | 0.755600 | 0.755600 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.77 | 3.89 | 7.77 | 155481.23 | 165100.69 | 82550.35 | 165100.69 | 0.717453 | 0.717450 | 0.717450 | 0.717450 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.10 | 0.552275 | 1.10 | 19753.14 | 21157.32 | 10578.66 | 21157.32 | 0.748729 | 0.748730 | 0.748730 | 0.748730 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.844260 | 0.422130 | 0.844260 | 16004.07 | 17063.10 | 8531.55 | 17063.10 | 0.732127 | 0.732130 | 0.732130 | 0.732130 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.81 | 1939.34 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.77 | 14276.03 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1222.91 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.844259 | 934.73 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.789 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.859 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 38.071 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 12.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.657 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2958.869 | 7.789 | 48.236 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2958.869 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 26489.747 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26489.747 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 151.881 | 12.657 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 151.881 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4744 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1725 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3437E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3274 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.941 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.721 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 29.02 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.978 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | 0.31219756E-14 | -0.25237900E-15 | -0.17078023E-09 | -0.40080417E-16 |
25 | 8 | 0.24827770E-07 | 0.64895754E-13 | 0.40814970E-03 | -0.28230026E-09 |
26 | 7 | -0.13145170E-01 | 0.32788080E-08 | -0.24386180E-01 | 0.14946539E-03 |
27 | 6 | 0.42990022 | 0.11289000E-05 | 0.49294528 | -0.50371474E-02 |
28 | 5 | -5.4301032 | 0.41776872E-04 | -4.6011904 | 0.66154067E-01 |
29 | 4 | 34.062169 | 0.33899226E-03 | 22.064921 | -0.43618800 |
30 | 3 | -113.47938 | 0.73347792E-03 | -56.858567 | 1.5477483 |
31 | 2 | 199.36357 | 0.40991987E-03 | 79.008039 | -2.9361691 |
32 | 1 | -171.98885 | 0.43498902E-04 | -55.585984 | 2.7600347 |
33 | 0 | 57.057407 | 0.24596459E-06 | 15.505383 | |
34 | 7 | -0.24541788E-08 | -0.10674912E-14 | 0.56595312E-14 | -0.88347803E-16 |
35 | 6 | 0.48874313E-05 | 0.32994277E-08 | 0.31919810E-02 | -0.26777012E-04 |
36 | 5 | -0.34768456E-03 | 0.19525666E-05 | -0.22384457 | 0.19572094E-02 |
37 | 4 | 0.79733842E-02 | 0.88847046E-04 | 4.8315443 | -0.45284193E-01 |
38 | 3 | -0.69943606E-01 | 0.70626596E-03 | -38.032707 | 0.39877855 |
39 | 2 | 0.24825401 | 0.11745943E-02 | 116.50592 | -1.4182332 |
40 | 1 | -0.35825340 | 0.35768630E-03 | -143.92024 | 2.0492525 |
41 | 0 | 0.17465044 | 0.86763216E-05 | 60.838472 | |
42 | 7 | -0.12489162E-07 | 0.28466235E-14 | -0.17145271E-13 | 0.26119495E-15 |
43 | 6 | 0.18517441E-05 | 0.69460444E-09 | 0.32027219E-02 | -0.26867115E-04 |
44 | 5 | -0.89695516E-04 | 0.39969105E-06 | -0.22445454 | 0.19625936E-02 |
45 | 4 | 0.17714562E-02 | 0.17921615E-04 | 4.8416944 | -0.45381772E-01 |
46 | 3 | -0.14613545E-01 | 0.14074818E-03 | -38.089997 | 0.39941188 |
47 | 2 | 0.50542763E-01 | 0.23137019E-03 | 116.61736 | -1.4197240 |
48 | 1 | -0.72070041E-01 | 0.69440628E-04 | -143.98582 | 2.0503304 |
49 | 0 | 0.34918756E-01 | 0.16519960E-05 | 60.838472 | |
50 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
51 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
52 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
53 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
54 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
55 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
56 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
57 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
58 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
59 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
60 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
61 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
62 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
63 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
64 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
65 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
66 | 7 | -0.12723796E-08 | -0.15085021E-15 | 0.80954726E-14 | -0.10933793E-15 |
67 | 6 | 0.91456241E-05 | 0.63025983E-08 | 0.31797574E-02 | -0.26674470E-04 |
68 | 5 | -0.66211654E-03 | 0.37378006E-05 | -0.22314974 | 0.19510765E-02 |
69 | 4 | 0.15256371E-01 | 0.17022008E-03 | 4.8199703 | -0.45172938E-01 |
70 | 3 | -0.13404479 | 0.13543778E-02 | -37.967318 | 0.39805580 |
71 | 2 | 0.47605416 | 0.22539081E-02 | 116.37865 | -1.4165309 |
72 | 1 | -0.68716389 | 0.68732095E-03 | -143.84532 | 2.0480210 |
73 | 0 | 0.33503722 | 0.16534103E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 30 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 31 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 20572.51261 | 24687.01514 | 1.48732 | 1.78478 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 23154.34606 | 27785.21527 | 0.99962 | 1.19954 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 86973.10805 | 104367.72967 | 6.28730 | 7.54476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 60147.45943 | 72176.95131 | 2.56434 | 3.07721 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12570.42073 | 15084.50487 | 0.92046 | 1.10455 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 11647.71391 | 13977.25670 | 0.50513 | 0.60616 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 9650.34604 | 11580.41525 | 0.70133 | 0.84160 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33455E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 11650.42312 | 13980.50775 | 0.50525 | 0.60630 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30000 | 1.33455E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 48363.20631 | 58035.84758 | 2.12773 | 2.55328 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -16.30000 | 9.24091E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 23731.88 | 1.81239 | 1.81239 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 37180.02 | 1.19954 | 1.19954 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 107989.34 | 7.77087 | 7.77087 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 152296.88 | 3.07721 | 3.07721 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 15344.91 | 1.10455 | 1.10455 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 21440.11 | 0.60616 | 0.60616 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 12367.00 | 0.84426 | 0.84426 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 21443.34 | 0.60630 | 0.60630 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.78478 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.54476 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10455 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.84160 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.55328 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 2.55328 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 58083.44869 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.78478 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.78478 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.78478 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.78478 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.81239 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.81239 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.98477 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.54476 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.54476 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.54476 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.54476 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.77087 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.77087 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97090 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10455 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10455 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10455 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10455 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10455 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10455 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.84160 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.84160 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.84160 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.84160 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.84426 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.84426 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.99685 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.81239 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.77087 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.10455 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.84426 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.81239 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.81239 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.81239 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.81239 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.81239 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.81239 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90620 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.81239 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 31701.09692 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33980.86000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16990.43000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 33980.86000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.75560 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.75560 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.75560 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.75560 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33980.86000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50360.95189 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.81239 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1939.34229 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 50360.95189 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.77087 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.77087 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.77087 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.77087 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.77087 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.77087 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.88544 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.77087 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 155481.22593 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 165100.69000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 82550.34500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 165100.69000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71745 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71745 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71745 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71745 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 165100.69000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 253022.16561 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.77087 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14276.02633 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 253022.16561 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10455 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10455 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10455 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10455 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10455 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10455 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55228 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10455 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19753.13625 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21157.32000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10578.66000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21157.32000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74873 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74873 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74873 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74873 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21157.32000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32630.82253 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10455 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1222.91041 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 32630.82253 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.84426 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.84426 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.84426 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.84426 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.84426 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.84426 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.42213 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84426 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16004.07465 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17063.10000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8531.55000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17063.10000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.73213 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.73213 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.73213 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.73213 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17063.10000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26726.68829 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.84426 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 934.72879 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 26726.68829 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32558.0 | 10.97 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 158987.7 | 12.22 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20289.9 | 114.87 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16399.5 | 158.28 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.172 | 0.166 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.437E-002 | 3.409E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.474 | 0.443 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.327 | 0.303 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 7.3311151648E-002 | 0.2395385446 | Pass | Pass | 4.4618104323E-002 | 0.1211078145 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 4.6501533256E-002 | 0.2117701648 | Pass | Pass | 0.3618855679 | 3.1417746181 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 8.1193320129E-002 | 0.2675107210 | Pass | Pass | 7.7156440677E-002 | 0.1919065555 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 8.8757557497E-002 | 0.2933949308 | Pass | Pass | 4.0164743255E-002 | 0.1059607944 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1508185580 | 0.4027389545 | Pass | Pass | 9.2565056147E-002 | 0.5137148202 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.443 | 0.474 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.172 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.034 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.327 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.159 | 0.394 | 0.401 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.623 | 0.440 | 0.445 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.623 | 0.440 | 0.445 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.7888 | 379.89 | 2958.87 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 34.59 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 16.5511 | 1600.48 | 26489.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 54.92 | 0.0000 | Y | 273.11 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 12.6567 | 12.00 | 151.88 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.95 |
Interior Lighting Total | 15.0797 | 2293.99 | 34592.64 | 373.60 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4644.36 | AstronomicalClock | - | 83.67 | 83.67 | 72.94 | |
Exterior Lighting Total | 4644.36 | 72.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 33980.86 | 25675.94 | 8304.92 | 0.76 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 165100.69 | 118451.49 | 46649.20 | 0.72 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21157.32 | 15841.12 | 5316.20 | 0.75 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17063.10 | 12492.41 | 4570.69 | 0.73 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 32558.0 | 10.97 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 158987.7 | 12.22 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20289.9 | 114.87 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16399.5 | 158.28 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 58083.45 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 50360.95 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 253022.17 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 32630.82 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 26726.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.55 | 2732.13 | 1070.05 | 1.00 | 1.27 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.81 | 1939.34 | 1070.05 | 1.00 | 1.33 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1110.54 | 7.77 | 14276.03 | 1837.12 | 1.00 | 1.15 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1222.91 | 1107.16 | 1.00 | 1.38 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.84 | 934.73 | 1107.16 | 1.00 | 1.45 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20572.51 | 24687.02 | 64.98 | 1.487 | 1.785 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01005 | 23.42 | 0.01335 | 0.232 | 0.00 |
CORE_RETAIL | 86973.11 | 104367.73 | 65.21 | 6.287 | 7.545 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00976 | 23.42 | 0.01335 | 1.890 | 0.00 |
POINT_OF_SALE | 12570.42 | 15084.50 | 100.02 | 0.920 | 1.105 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00905 | 23.42 | 0.01335 | 0.178 | 0.00 |
FRONT_RETAIL | 9650.35 | 11580.42 | 76.79 | 0.701 | 0.842 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00960 | 23.42 | 0.01335 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.19 | 100.00 | 0.00001 | 30.30 | 0.01335 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 23154.35 | 27785.22 | 73.14 | 1.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00746 | -16.30 | 0.00092 | 0.232 | 0.00 |
CORE_RETAIL | 60147.46 | 72176.95 | 45.10 | 2.564 | 3.077 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00744 | -16.30 | 0.00092 | 1.890 | 0.00 |
POINT_OF_SALE | 11647.71 | 13977.26 | 92.68 | 0.505 | 0.606 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00767 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_RETAIL | 11650.42 | 13980.51 | 92.70 | 0.505 | 0.606 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00767 | -16.30 | 0.00092 | 0.178 | 0.00 |
FRONT_ENTRY | 48363.21 | 58035.85 | 4836.32 | 2.128 | 2.553 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 21.00 | 0.00563 | -16.30 | 0.00092 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.81 | 1.81 | 1.20 | 1.20 | 1.8124 | 1.7848 | 1.8124 | 0.9848 | 1.0000 |
PSZ-AC:2 | 7.77 | 7.77 | 3.08 | 3.08 | 7.7709 | 7.5448 | 7.7709 | 0.9709 | 1.0000 |
PSZ-AC:3 | 1.10 | 1.10 | 0.61 | 0.61 | 1.1045 | 1.1045 | 1.1045 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.84 | 0.84 | 0.61 | 0.61 | 0.8443 | 0.8416 | 0.8443 | 0.9969 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 58083.449 | 58083.449 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 58083.45 | 58083.45 | 2.553277 | 20.79 | 12.23 | 0.00560564 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00563177 | 35.6351 | 58035.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 33980.860 | 0.000 | 1.812390 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 33980.86 | 25557.01 | 1.812390 | 23.90 | 17.48 | 0.01017664 | 12.80 | 11.87 | 0.00850000 | 24.01 | 0.01334551 | 19.95 | 12.7769 | 23.88 | 0.01004656 | 52.9614 | 20572.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 50360.952 | 50360.952 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50360.95 | 50360.95 | 1.812389 | 13.72 | 9.88 | 0.00620072 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 12.7769 | 21.11 | 0.00746304 | 46.7628 | 23154.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 165100.690 | 0.000 | 7.770870 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 165100.69 | 125418.95 | 7.770870 | 25.58 | 18.15 | 0.01032026 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 24.3243 | 23.89 | 0.00976453 | 51.4950 | 86014.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 253022.166 | 253022.166 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 253022.17 | 253022.17 | 7.770866 | -1.96 | -1.96 | 0.00343609 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.3243 | 21.11 | 0.00743628 | 46.5953 | 60147.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 21157.320 | 0.000 | 1.104550 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21157.32 | 17301.80 | 1.104550 | 24.94 | 17.46 | 0.00972558 | 12.80 | 11.87 | 0.00850000 | 30.22 | 0.01334551 | 21.78 | 16.1252 | 23.89 | 0.00905423 | 47.7963 | 11861.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 32630.823 | 32630.823 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32630.82 | 32630.82 | 1.104548 | 10.02 | 7.63 | 0.00568661 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 16.1252 | 21.11 | 0.00766829 | 48.0319 | 11647.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 17063.100 | 0.000 | 0.844260 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 17063.10 | 13415.20 | 0.844260 | 25.24 | 17.80 | 0.01002815 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01334551 | 21.80 | 21.0966 | 23.89 | 0.00959722 | 50.6253 | 9327.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 26726.688 | 26726.688 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26726.69 | 26726.69 | 0.844259 | 10.02 | 7.63 | 0.00568722 | 40.00 | 20.85 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.0967 | 21.11 | 0.00766849 | 48.0331 | 11650.42 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 58083.449 | 58083.449 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 2.553277 | 2.99735619 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 58083.45 | 58083.45 | 1.0000 | 2.99735619 | 2.553277 | 20.79 | 12.23 | 0.00560564 | 35126.0 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58083.45 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.01 | 0.00563177 | 21.00 | 0.00563177 | 35.6351 | 58035.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 33980.860 | 0.000 | 1.812390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7579 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 33980.86 | 25557.01 | 1.0000 | 2.12761050 | 1.812390 | 23.90 | 17.48 | 0.01017664 | 49919.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33980.86 | 24.01 | 0.01334551 | 19.95 | 0.23156651 | 12.7769 | 23.88 | 0.00971245 | 23.88 | 0.01004656 | 52.9614 | 20572.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50360.952 | 50360.952 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.812389 | 2.12760975 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50360.95 | 50360.95 | 1.0000 | 2.12760975 | 1.812389 | 13.72 | 9.88 | 0.00620072 | 29456.9 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50360.95 | -16.30 | 0.00092409 | -16.30 | 0.23156651 | 12.7769 | 20.91 | 0.00746304 | 21.11 | 0.00746304 | 46.7628 | 23154.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 165100.690 | 0.000 | 7.770870 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0248 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 165100.69 | 125418.95 | 1.0000 | 9.12242100 | 7.770870 | 25.58 | 18.15 | 0.01032026 | 52004.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 165100.69 | 30.30 | 0.01334551 | 21.80 | 1.89021192 | 24.3243 | 23.89 | 0.00923580 | 23.89 | 0.00976453 | 51.4950 | 86014.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 253022.166 | 253022.166 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.770866 | 9.12241672 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 253022.17 | 253022.17 | 1.0000 | 9.12241672 | 7.770866 | -1.96 | -1.96 | 0.00343609 | 6616.0 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 253022.17 | -16.30 | 0.00092409 | -16.30 | 1.89021192 | 24.3243 | 20.89 | 0.00743628 | 21.11 | 0.00743628 | 46.5953 | 60147.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21157.320 | 0.000 | 1.104550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9194 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21157.32 | 17301.80 | 1.0000 | 1.29665921 | 1.104550 | 24.94 | 17.46 | 0.00972558 | 49835.7 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21157.32 | 30.22 | 0.01334551 | 21.78 | 0.17811053 | 16.1252 | 23.89 | 0.00900384 | 23.89 | 0.00905423 | 47.7963 | 11861.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32630.823 | 32630.823 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.104548 | 1.29665733 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32630.82 | 32630.82 | 1.0000 | 1.29665733 | 1.104548 | 10.02 | 7.63 | 0.00568661 | 24391.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32630.82 | -16.30 | 0.00092409 | -16.30 | 0.17811053 | 16.1252 | 20.97 | 0.00766829 | 21.11 | 0.00766829 | 48.0319 | 11647.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17063.100 | 0.000 | 0.844260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4818 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 17063.10 | 13415.20 | 1.0000 | 0.99109819 | 0.844260 | 25.24 | 17.80 | 0.01002815 | 50916.0 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17063.10 | 30.30 | 0.01334551 | 21.80 | 0.17811053 | 21.0966 | 23.89 | 0.00913885 | 23.89 | 0.00959722 | 50.6253 | 9327.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26726.688 | 26726.688 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.844259 | 0.99109708 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26726.69 | 26726.69 | 1.0000 | 0.99109708 | 0.844259 | 10.02 | 7.63 | 0.00568722 | 24395.9 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26726.69 | -16.30 | 0.00092409 | -16.30 | 0.17811053 | 21.0967 | 20.97 | 0.00766849 | 21.11 | 0.00766849 | 48.0331 | 11650.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.81 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.77 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.10 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 0.84 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2616.33 | 3599.33 | 1883.50 |
CORE_RETAIL | 2422.67 | 2967.83 | 1199.50 |
POINT_OF_SALE | 2576.00 | 2806.83 | 1192.33 |
FRONT_RETAIL | 2663.17 | 3212.83 | 1550.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3244.17 | 3615.00 | 1903.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 5.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 5.67 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 12.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 2.17 | 0.00 | 0.00 | 0.00 |
Facility | 19.33 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.715 | 0.040 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 1.055 | 0.008 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 1.383 | 0.043 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 1.077 | 0.043 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.350 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.678 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.678 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1133.14 | 3304.06 | 30-APR-07:00 | 101611.38 | 15-JUL-14:00 |
Electricity:Building | 568.76 | 3083.31 | 21-MAY-08:00 | 41654.89 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 84.58 | 607.80 | 01-JAN-00:10 | 5172.60 | 02-JAN-09:10 |
InteriorLights:Electricity | 373.60 | 1288.14 | 21-MAY-08:00 | 30883.85 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 34.59 | 147.94 | 01-JAN-00:10 | 2413.46 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 373.60 | 1288.14 | 21-MAY-08:00 | 30883.85 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 357.41 | 1658.43 | 21-MAY-08:00 | 28493.38 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 273.11 | 882.99 | 21-MAY-08:00 | 23840.77 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 84.90 | 611.62 | 01-JAN-00:10 | 5167.35 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 39.92 | 197.87 | 01-JAN-00:10 | 2684.87 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1133.14 | 3304.06 | 30-APR-07:00 | 101611.38 | 15-JUL-14:00 |
ElectricityPurchased:Plant | 1133.14 | 3304.06 | 30-APR-07:00 | 101611.38 | 15-JUL-14:00 |
Cogeneration:ElectricityPurchased | 1133.14 | 3304.06 | 30-APR-07:00 | 101611.38 | 15-JUL-14:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1133.14 | 3304.06 | 30-APR-07:00 | 101611.38 | 15-JUL-14:00 |
ElectricityNet:Plant | 1133.14 | 3304.06 | 30-APR-07:00 | 101611.38 | 15-JUL-14:00 |
Cogeneration:ElectricityNet | 1133.14 | 3304.06 | 30-APR-07:00 | 101611.38 | 15-JUL-14:00 |
Electricity:HVAC | 491.44 | 0.00 | 01-JAN-00:10 | 65916.68 | 15-JUL-14:00 |
Fans:Electricity | 381.57 | 0.00 | 01-JAN-00:10 | 21105.13 | 02-JAN-06:40 |
General:Fans:Electricity | 381.57 | 0.00 | 01-JAN-00:10 | 21105.13 | 02-JAN-06:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 109.88 | 0.00 | 01-JAN-00:10 | 47543.67 | 15-JUL-14:00 |
ExteriorLights:Electricity | 72.94 | 0.00 | 01-JAN-08:00 | 4644.36 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 72.94 | 0.00 | 01-JAN-08:00 | 4644.36 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 571.70 | 1862.00 | 12-MAR-18:10 | 245473.86 | 07-FEB-07:10 |
Gas:Plant | 96.73 | 1862.00 | 24-JAN-05:20 | 5273.21 | 10-FEB-12:10 |
WaterSystems:Gas | 96.73 | 1862.00 | 24-JAN-05:20 | 5273.21 | 10-FEB-12:10 |
Water Heater:WaterSystems:Gas | 96.73 | 1862.00 | 24-JAN-05:20 | 5273.21 | 10-FEB-12:10 |
Gas:HVAC | 474.96 | 0.00 | 01-JAN-00:10 | 241600.17 | 07-FEB-07:10 |
Heating:Gas | 474.96 | 0.00 | 01-JAN-00:10 | 241600.17 | 07-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1453.09 | 0.00 | 01-JAN-00:10 | 315395.46 | 07-FEB-07:10 |
EnergyTransfer:Building | 681.88 | 0.00 | 01-JAN-00:10 | 125797.82 | 06-FEB-07:10 |
EnergyTransfer:Zone:BACK_SPACE | 80.47 | 0.00 | 01-JAN-00:10 | 25396.41 | 06-FEB-06:10 |
Heating:EnergyTransfer | 191.81 | 0.00 | 01-JAN-00:10 | 125351.87 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 29.92 | 0.00 | 01-JAN-00:10 | 25396.41 | 06-FEB-06:10 |
Cooling:EnergyTransfer | 490.07 | 0.00 | 01-JAN-00:10 | 78820.02 | 21-JUL-14:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 50.56 | 0.00 | 01-JAN-00:10 | 12151.22 | 21-JUL-14:10 |
EnergyTransfer:Zone:CORE_RETAIL | 375.81 | 0.00 | 01-JAN-00:10 | 81046.81 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 30.21 | 0.00 | 01-JAN-00:10 | 76820.70 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 345.60 | 0.00 | 01-JAN-00:10 | 62354.73 | 06-SEP-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 65.87 | 0.00 | 01-JAN-00:10 | 11611.62 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 6.55 | 0.00 | 01-JAN-00:10 | 11611.62 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 59.32 | 0.00 | 01-JAN-00:10 | 10255.20 | 21-SEP-13:20 |
EnergyTransfer:Zone:FRONT_RETAIL | 46.64 | 0.00 | 01-JAN-00:10 | 11941.07 | 07-FEB-06:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 12.05 | 0.00 | 01-JAN-00:10 | 11941.07 | 07-FEB-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 34.59 | 0.00 | 01-JAN-00:10 | 8013.23 | 21-SEP-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 113.09 | 0.00 | 01-JAN-00:10 | 45644.50 | 06-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 113.09 | 0.00 | 01-JAN-00:10 | 45644.50 | 06-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 771.21 | 0.00 | 01-JAN-00:10 | 193280.14 | 07-FEB-07:10 |
HeatingCoils:EnergyTransfer | 379.97 | 0.00 | 01-JAN-00:10 | 193280.14 | 07-FEB-07:10 |
CoolingCoils:EnergyTransfer | 391.24 | 0.00 | 01-JAN-00:10 | 189891.16 | 21-JUL-06:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 29.916 | -50.558 | 0.000 | 0.000 | 39.509 | 34.587 | 49.992 | 0.000 | 0.000 | 0.146 | 0.000 | 0.000 | 0.000 | 0.000 | -24.723 | -78.868 |
CORE_RETAIL | 0.000 | 0.000 | 30.208 | -345.598 | 0.000 | 0.000 | 165.838 | 273.108 | 84.299 | 50.128 | 0.000 | 0.119 | 0.006 | 0.000 | -27.656 | 0.000 | -21.853 | -208.592 |
POINT_OF_SALE | 0.000 | 0.000 | 6.545 | -59.320 | 0.000 | 0.000 | 15.441 | 31.980 | 52.922 | 27.991 | 0.000 | 0.061 | 0.000 | 0.000 | -20.658 | 0.000 | -11.206 | -43.757 |
FRONT_RETAIL | 0.000 | 0.000 | 12.053 | -34.589 | 0.000 | 0.000 | 15.728 | 31.980 | 7.943 | 28.068 | 0.000 | 0.062 | 0.000 | 0.000 | -20.014 | 0.000 | -10.743 | -30.488 |
FRONT_ENTRY | 113.088 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.946 | 0.000 | 5.676 | 0.000 | 0.030 | 0.000 | 0.000 | -4.092 | 0.000 | -115.879 | -0.768 |
Total Facility | 113.088 | 0.000 | 78.721 | -490.065 | 0.000 | 0.000 | 236.515 | 373.601 | 195.156 | 111.863 | 0.000 | 0.418 | 0.007 | 0.000 | -72.419 | 0.000 | -184.405 | -362.474 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 03-AUG-06:02 | 0.00 | 0.00 | 0.00 | -39303.45 | 0.00 | 0.00 | 400.08 | 536.32 | 1226.28 | 0.00 | 0.00 | 0.00 | 37341.15 | 0.00 | -0.00 | 0.00 | -200.40 | 0.00 |
CORE_RETAIL | 14-JUN-06:02 | 0.00 | 0.00 | 0.00 | -215041.26 | 0.00 | 0.00 | 1626.35 | 5297.95 | 2067.82 | 13.43 | 0.00 | 0.00 | 206434.33 | 0.00 | -0.00 | 0.00 | -398.62 | 0.00 |
POINT_OF_SALE | 12-SEP-06:02 | 0.00 | 0.00 | 0.00 | -25498.88 | 0.00 | 0.00 | 151.93 | 499.21 | 1298.17 | 0.00 | 0.00 | 0.00 | 24625.45 | 0.00 | -968.99 | 0.00 | -106.89 | 0.00 |
FRONT_RETAIL | 02-AUG-06:02 | 0.00 | 0.00 | 0.00 | -18238.56 | 0.00 | 0.00 | 155.04 | 499.21 | 194.85 | 0.00 | 0.00 | 0.00 | 18043.27 | 0.00 | -653.82 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-AUG-06:02 | 0.00 | 0.00 | 0.00 | -259210.76 | 0.00 | 0.00 | 2305.20 | 6863.08 | 4787.13 | 0.00 | 0.00 | 0.00 | 247937.34 | 0.00 | -2123.50 | 0.00 | -558.48 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 06-FEB-05:32 | 0.00 | 0.00 | 51962.68 | 0.00 | 0.00 | 0.00 | 0.00 | 147.94 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5461.53 | -47262.23 |
CORE_RETAIL | 06-FEB-06:01 | 0.00 | 0.00 | 260291.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.49 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2809.64 | 0.00 | -1170.42 | -258669.66 |
POINT_OF_SALE | 26-DEC-06:01 | 0.00 | 0.00 | 32631.39 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2060.39 | 0.00 | -694.04 | -30650.85 |
FRONT_RETAIL | 21-FEB-05:11 | 0.00 | 0.00 | 27239.80 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1998.81 | 0.00 | -2341.85 | -23121.36 |
FRONT_ENTRY | 06-FEB-18:00 | 45643.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -516.08 | 0.00 | -45204.49 | -59.94 |
Total Facility | 10-DEC-08:61 | 7227.00 | 0.00 | 367821.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1729.63 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3162.81 | 0.00 | -7493.19 | -367917.72 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7848 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.8124 | 0.1278 | 1.0000 | 0.2316 | 0.1278 | ||
PSZ-AC:2 | 7.5448 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.7709 | 0.2432 | 1.0000 | 1.8902 | 0.2432 | ||
PSZ-AC:3 | 1.1045 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1045 | 0.1613 | 1.0000 | 0.1781 | 0.1613 | ||
PSZ-AC:4 | 0.8416 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8443 | 0.2110 | 1.0000 | 0.1781 | 0.2110 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7848 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7848 | 1.0000 | 1.0000 | 0.2316 | 0.1297 | ||
PSZ-AC:2 | 7.5448 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.5448 | 1.0000 | 1.0000 | 1.8902 | 0.2505 | ||
PSZ-AC:3 | 1.1045 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1045 | 1.0000 | 1.0000 | 0.1781 | 0.1613 | ||
PSZ-AC:4 | 0.8416 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8416 | 1.0000 | 1.0000 | 0.1781 | 0.2116 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7848 | 1.7848 | 1.7848 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.5448 | 7.5448 | 7.5448 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1045 | 1.1045 | 1.1045 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8416 | 0.8416 | 0.8416 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7848 | 1.8124 | 1.7848 | 1.7848 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.5448 | 7.7709 | 7.5448 | 7.5448 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1045 | 1.1045 | 1.1045 | 1.1045 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8416 | 0.8443 | 0.8416 | 0.8416 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7848 | 1.7848 | 1.7848 | 0.2316 | 0.1930 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.5448 | 7.5448 | 7.5448 | 1.8902 | 0.6143 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1045 | 1.1045 | 1.1045 | 0.1781 | 0.2938 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8416 | 0.8416 | 0.8416 | 0.1781 | 0.2938 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7848 | 1.7848 | 1.7848 | 1.7848 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.5448 | 7.5448 | 7.5448 | 7.5448 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1045 | 1.1045 | 1.1045 | 1.1045 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8416 | 0.8416 | 0.8416 | 0.8416 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 474.96 | 241600.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 109.88 | 47543.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 373.60 | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.94 | 4644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 381.57 | 21105.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 96.73 | 5273.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1133.14 |
Natural Gas | 0.00 | 571.70 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1704.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 162.86 |
Space Heating | 0.00 |
Space Cooling | 47.90 |
Fans (All) | 166.33 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 493.96 |
Subtotal | 493.96 |
Natural Gas [MJ/m2] | |
Space Heating | 207.05 |
Service Water Heating | 42.17 |
Miscellaneous (All) | 249.22 |
Subtotal | 249.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.91 |
Space Heating | 27.86 |
Space Cooling | 6.45 |
Fans (All) | 22.38 |
Service Water Heating | 5.67 |
Receptacle Equipment | 11.45 |
Miscellaneous | 4.28 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.126839E+12 |
February | 0.000 | 0.121041E+12 |
March | 0.000 | 0.601959E+11 |
April | 0.000 | 0.174769E+11 |
May | 0.000 | 0.221601E+10 |
June | 0.000 | 0.329940E+09 |
July | 0.000 | 0.000 |
August | 0.000 | 0.712770E+08 |
September | 0.000 | 0.495728E+09 |
October | 0.000 | 0.777427E+10 |
November | 0.000 | 0.261978E+11 |
December | 0.000 | 0.112327E+12 |
Annual Sum or Average | 0.474964E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.126839E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73739622.96 | 5313.51 | 03-JAN-07:05 | -4.4 | -5.6 | 0.165179E+10 | 1861.40 | 11-JAN-15:00 | 11.70 | 10.13 |
February | 55135129.17 | 5547.56 | 16-FEB-07:05 | -5.1 | -6.1 | 0.150827E+10 | 1854.44 | 02-FEB-15:09 | -3.3 | -4.2 |
March | 0.110196E+10 | 5744.87 | 24-MAR-06:05 | -5.1 | -6.2 | 0.181420E+10 | 2451.23 | 14-MAR-14:09 | 24.90 | 17.32 |
April | 0.184373E+10 | 5334.11 | 17-APR-06:05 | -4.2 | -5.2 | 0.187035E+10 | 2451.24 | 07-APR-14:09 | 19.72 | 10.07 |
May | 0.411256E+10 | 17226.50 | 24-MAY-06:02 | 18.03 | 15.61 | 0.220206E+10 | 2451.27 | 13-MAY-12:39 | 21.33 | 14.36 |
June | 0.850936E+10 | 35394.66 | 23-JUN-06:02 | 13.90 | 11.85 | 0.220085E+10 | 2451.36 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.111501E+11 | 36951.07 | 06-JUL-06:02 | 13.07 | 10.51 | 0.218803E+10 | 2451.62 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.108487E+11 | 39310.42 | 03-AUG-06:02 | 11.57 | 9.85 | 0.228175E+10 | 2451.41 | 15-AUG-14:00 | 23.30 | 20.62 |
September | 0.725478E+10 | 37448.14 | 18-SEP-06:02 | 10.28 | 9.20 | 0.215293E+10 | 2451.36 | 22-SEP-14:30 | 23.90 | 15.37 |
October | 0.338884E+10 | 6666.88 | 13-OCT-06:02 | 10.00 | 9.62 | 0.206235E+10 | 2451.30 | 11-OCT-14:39 | 22.20 | 14.43 |
November | 0.188468E+10 | 5221.88 | 24-NOV-07:05 | -3.2 | -3.9 | 0.171804E+10 | 2451.24 | 16-NOV-15:20 | 17.20 | 13.38 |
December | 0.335478E+09 | 5540.95 | 06-DEC-07:05 | -5.0 | -5.2 | 0.165824E+10 | 1979.72 | 01-DEC-15:00 | 7.20 | 5.38 |
Annual Sum or Average | 0.505591E+11 | 0.233089E+11 | ||||||||
Minimum of Months | 55135129.17 | 5221.88 | -5.1 | -6.2 | 0.150827E+10 | 1854.44 | -3.3 | -4.2 | ||
Maximum of Months | 0.111501E+11 | 39310.42 | 18.03 | 15.61 | 0.228175E+10 | 2451.62 | 24.90 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.992991E+10 | 62145.60 | 04-JAN-07:05 | -12.9 | -13.6 | 0.697010E+10 | 8714.46 | 11-JAN-15:00 | 11.70 | 10.13 |
February | 0.898665E+10 | 60182.21 | 28-FEB-07:05 | -11.9 | -12.4 | 0.636436E+10 | 8520.79 | 22-FEB-15:00 | 10.60 | 5.00 |
March | 0.199997E+11 | 168653.13 | 16-MAR-06:03 | 11.93 | 10.48 | 0.774555E+10 | 10327.11 | 16-MAR-14:09 | 18.98 | 15.27 |
April | 0.234337E+11 | 69935.71 | 09-APR-08:63 | 12.48 | 10.46 | 0.814032E+10 | 10327.20 | 08-APR-12:30 | 20.25 | 13.12 |
May | 0.340676E+11 | 203200.28 | 18-MAY-06:02 | 9.32 | 5.95 | 0.934970E+10 | 10327.49 | 25-MAY-14:39 | 17.77 | 13.50 |
June | 0.466493E+11 | 215070.57 | 14-JUN-06:02 | 7.67 | 5.66 | 0.927626E+10 | 10328.11 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.523908E+11 | 166363.46 | 06-JUL-06:02 | 13.07 | 10.51 | 0.921854E+10 | 10328.58 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.504478E+11 | 179723.38 | 03-AUG-06:02 | 11.57 | 9.85 | 0.961336E+10 | 10327.54 | 15-AUG-14:00 | 23.30 | 20.62 |
September | 0.390698E+11 | 189647.83 | 06-SEP-06:03 | 6.28 | 5.42 | 0.907587E+10 | 10327.73 | 19-SEP-14:00 | 21.10 | 13.28 |
October | 0.277173E+11 | 191260.70 | 05-OCT-06:02 | 8.40 | 7.78 | 0.871029E+10 | 10327.34 | 05-OCT-14:00 | 18.90 | 12.66 |
November | 0.210468E+11 | 33112.52 | 15-NOV-07:03 | -0.6 | -1.0 | 0.734365E+10 | 10327.12 | 04-NOV-11:20 | 15.37 | 12.57 |
December | 0.118618E+11 | 60601.54 | 28-DEC-07:05 | -12.2 | -12.5 | 0.700550E+10 | 8661.98 | 01-DEC-15:09 | 7.20 | 5.58 |
Annual Sum or Average | 0.345601E+12 | 0.988135E+11 | ||||||||
Minimum of Months | 0.898665E+10 | 33112.52 | -12.9 | -13.6 | 0.636436E+10 | 8520.79 | 7.20 | 5.00 | ||
Maximum of Months | 0.523908E+11 | 215070.57 | 13.07 | 10.51 | 0.961336E+10 | 10328.58 | 23.30 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169195E+10 | 4637.53 | 12-JAN-13:30 | -6.7 | -9.0 | 0.660836E+09 | 859.62 | 11-JAN-15:00 | 11.70 | 10.13 |
February | 0.154954E+10 | 4450.07 | 05-FEB-15:33 | -8.3 | -9.2 | 0.608149E+09 | 958.34 | 22-FEB-15:00 | 10.60 | 5.00 |
March | 0.331444E+10 | 16505.54 | 16-MAR-06:03 | 11.93 | 10.48 | 0.778629E+09 | 973.16 | 15-MAR-14:00 | 25.60 | 16.22 |
April | 0.349413E+10 | 5929.38 | 22-APR-13:40 | 15.20 | 6.91 | 0.797475E+09 | 973.19 | 08-APR-14:09 | 20.40 | 13.65 |
May | 0.513567E+10 | 21257.07 | 17-MAY-06:02 | 18.40 | 12.90 | 0.880699E+09 | 973.15 | 25-MAY-14:30 | 18.05 | 13.48 |
June | 0.739872E+10 | 25340.48 | 03-JUN-06:02 | 11.20 | 8.19 | 0.873927E+09 | 973.21 | 23-JUN-14:00 | 18.90 | 13.36 |
July | 0.897519E+10 | 22969.70 | 06-JUL-06:02 | 13.07 | 10.51 | 0.868662E+09 | 973.38 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.937595E+10 | 24351.50 | 03-AUG-06:02 | 11.57 | 9.85 | 0.905882E+09 | 973.25 | 15-AUG-14:00 | 23.30 | 20.62 |
September | 0.792191E+10 | 25505.20 | 12-SEP-06:02 | 9.60 | 8.75 | 0.855609E+09 | 973.22 | 18-SEP-14:39 | 17.80 | 13.02 |
October | 0.540845E+10 | 23940.99 | 13-OCT-06:02 | 10.00 | 9.62 | 0.849329E+09 | 973.18 | 11-OCT-14:00 | 22.20 | 14.59 |
November | 0.330207E+10 | 6506.78 | 01-NOV-12:00 | 11.10 | 6.26 | 0.747432E+09 | 973.10 | 04-NOV-10:20 | 14.27 | 11.95 |
December | 0.175197E+10 | 4100.91 | 29-DEC-09:23 | -6.4 | -7.8 | 0.669987E+09 | 973.08 | 16-DEC-15:30 | 4.70 | 2.48 |
Annual Sum or Average | 0.593200E+11 | 0.949662E+10 | ||||||||
Minimum of Months | 0.154954E+10 | 4100.91 | -8.3 | -9.2 | 0.608149E+09 | 859.62 | 4.70 | 2.48 | ||
Maximum of Months | 0.937595E+10 | 25505.20 | 18.40 | 12.90 | 0.905882E+09 | 973.38 | 25.60 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375712E+09 | 3967.49 | 06-JAN-18:33 | -3.9 | -5.6 | 0.655779E+09 | 736.18 | 02-JAN-15:09 | 0.00 | -0.6 |
February | 0.401481E+09 | 3995.42 | 24-FEB-11:43 | -4.0 | -5.0 | 0.599569E+09 | 799.00 | 22-FEB-15:50 | 10.60 | 4.98 |
March | 0.165723E+10 | 5008.20 | 15-MAR-13:40 | 25.73 | 15.89 | 0.723002E+09 | 973.13 | 16-MAR-14:00 | 19.40 | 15.85 |
April | 0.185996E+10 | 4200.61 | 03-APR-06:05 | -2.8 | -3.4 | 0.731781E+09 | 973.12 | 08-APR-13:20 | 20.93 | 13.54 |
May | 0.264820E+10 | 12077.35 | 24-MAY-06:02 | 18.03 | 15.61 | 0.857696E+09 | 973.12 | 26-MAY-14:20 | 21.70 | 13.60 |
June | 0.459373E+10 | 14918.18 | 11-JUN-08:62 | 21.97 | 14.78 | 0.871157E+09 | 973.18 | 10-JUN-13:09 | 21.10 | 13.36 |
July | 0.610417E+10 | 17089.55 | 12-JUL-06:02 | 14.37 | 11.81 | 0.868511E+09 | 973.26 | 15-JUL-10:00 | 22.20 | 20.99 |
August | 0.640112E+10 | 18242.57 | 02-AUG-06:02 | 11.85 | 10.71 | 0.905549E+09 | 973.18 | 15-AUG-14:00 | 23.30 | 20.62 |
September | 0.517289E+10 | 17857.61 | 23-SEP-06:02 | 12.88 | 11.58 | 0.851082E+09 | 973.19 | 18-SEP-14:09 | 17.80 | 12.77 |
October | 0.330430E+10 | 15851.62 | 12-OCT-06:02 | 13.90 | 11.92 | 0.801748E+09 | 973.18 | 11-OCT-14:00 | 22.20 | 14.59 |
November | 0.168228E+10 | 3923.22 | 25-NOV-07:05 | -1.5 | -2.5 | 0.685153E+09 | 973.09 | 16-NOV-15:09 | 17.20 | 13.32 |
December | 0.387950E+09 | 5250.14 | 10-DEC-15:23 | -10.0 | -10.8 | 0.658537E+09 | 849.33 | 16-DEC-14:09 | 5.50 | 2.81 |
Annual Sum or Average | 0.345890E+11 | 0.920956E+10 | ||||||||
Minimum of Months | 0.375712E+09 | 3923.22 | -10.0 | -10.8 | 0.599569E+09 | 736.18 | 0.00 | -0.6 | ||
Maximum of Months | 0.640112E+10 | 18242.57 | 25.73 | 15.89 | 0.905549E+09 | 973.26 | 23.30 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.71 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.49 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.06 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -4.9 | -6.8 | 0.00 | 0.00 | -4.9 | -6.8 | ||
Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.808021E+10 | 50843.63 | 11-JAN-06:01 | 5.68 |
February | 0.806970E+10 | 51962.59 | 06-FEB-05:32 | -14.3 |
March | 0.389442E+10 | 50856.90 | 26-MAR-07:01 | 1.70 |
April | 0.101938E+10 | 50767.88 | 17-APR-05:01 | -4.0 |
May | 0.196685E+09 | 1913.69 | 21-MAY-07:45 | 14.53 |
June | 0.190052E+09 | 2419.00 | 18-JUN-08:20 | 24.60 |
July | 0.158594E+09 | 2371.44 | 16-JUL-08:20 | 24.97 |
August | 0.176503E+09 | 2175.43 | 06-AUG-08:06 | 22.07 |
September | 0.187699E+09 | 1922.33 | 24-SEP-07:43 | 15.50 |
October | 0.262640E+09 | 32833.64 | 30-OCT-05:02 | -0.1 |
November | 0.108967E+10 | 50532.31 | 24-NOV-06:01 | -3.8 |
December | 0.659008E+10 | 51124.21 | 26-DEC-05:23 | -12.2 |
Annual Sum or Average | 0.299156E+11 | |||
Minimum of Months | 0.158594E+09 | 1913.69 | -14.3 | |
Maximum of Months | 0.808021E+10 | 51962.59 | 24.97 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662524E+10 | 259217.80 | 30-JAN-06:01 | -10.1 |
February | 0.643541E+10 | 260291.23 | 06-FEB-06:01 | -13.9 |
March | 0.303743E+10 | 258329.30 | 07-MAR-06:01 | -13.3 |
April | 0.155300E+10 | 193204.26 | 17-APR-05:01 | -4.0 |
May | 0.138799E+10 | 14093.03 | 21-MAY-07:45 | 14.53 |
June | 0.778916E+09 | 16467.27 | 18-JUN-08:08 | 24.50 |
July | 0.425033E+09 | 16961.18 | 16-JUL-08:08 | 24.68 |
August | 0.467258E+09 | 14817.02 | 11-AUG-05:04 | 17.80 |
September | 0.106062E+10 | 14161.41 | 03-SEP-07:53 | 10.60 |
October | 0.144023E+10 | 14319.55 | 17-OCT-05:33 | -2.8 |
November | 0.170555E+10 | 211771.89 | 24-NOV-06:01 | -3.8 |
December | 0.529135E+10 | 259896.52 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.302080E+11 | |||
Minimum of Months | 0.425033E+09 | 14093.03 | -13.9 | |
Maximum of Months | 0.662524E+10 | 260291.23 | 24.68 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171282E+10 | 32597.50 | 30-JAN-06:01 | -10.1 |
February | 0.185069E+10 | 32630.41 | 06-FEB-05:01 | -14.8 |
March | 0.618769E+09 | 32388.55 | 06-MAR-05:01 | -11.1 |
April | 0.235079E+09 | 32358.23 | 17-APR-05:01 | -4.0 |
May | 0.117335E+09 | 1187.72 | 21-MAY-07:45 | 14.53 |
June | 78489072.90 | 1238.51 | 12-JUN-06:06 | 22.98 |
July | 41392912.02 | 1699.09 | 20-JUL-05:07 | 23.90 |
August | 36208722.56 | 1635.61 | 11-AUG-05:04 | 17.80 |
September | 86992939.11 | 1371.03 | 17-SEP-07:05 | 22.12 |
October | 0.124150E+09 | 7782.73 | 30-OCT-05:02 | -0.1 |
November | 0.226976E+09 | 32142.00 | 24-NOV-06:01 | -3.8 |
December | 0.141615E+10 | 32631.36 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.654506E+10 | |||
Minimum of Months | 36208722.56 | 1187.72 | -14.8 | |
Maximum of Months | 0.185069E+10 | 32631.36 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.321515E+10 | 26843.74 | 30-JAN-06:01 | -10.1 |
February | 0.325846E+10 | 27239.60 | 21-FEB-05:11 | -12.2 |
March | 0.121998E+10 | 26766.65 | 25-MAR-05:01 | -5.1 |
April | 0.494852E+09 | 26765.27 | 17-APR-05:01 | -4.0 |
May | 96619255.82 | 5321.57 | 01-MAY-06:03 | 2.35 |
June | 87876959.91 | 939.59 | 12-JUN-06:06 | 22.98 |
July | 67838670.37 | 1244.56 | 15-JUL-06:06 | 23.72 |
August | 72381498.83 | 904.23 | 20-AUG-07:12 | 15.97 |
September | 86213940.84 | 925.15 | 03-SEP-07:53 | 10.60 |
October | 0.146666E+09 | 26190.47 | 30-OCT-05:02 | -0.1 |
November | 0.502962E+09 | 26636.25 | 24-NOV-06:01 | -3.8 |
December | 0.280364E+10 | 26931.89 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.120526E+11 | |||
Minimum of Months | 67838670.37 | 904.23 | -12.2 | |
Maximum of Months | 0.325846E+10 | 27239.60 | 23.72 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218981E+11 | 42213.69 | 31-JAN-18:00 | -12.2 |
February | 0.204408E+11 | 45644.50 | 06-FEB-18:00 | -14.4 |
March | 0.149691E+11 | 37111.74 | 06-MAR-18:00 | -8.3 |
April | 0.906609E+10 | 29433.78 | 16-APR-11:10 | -3.1 |
May | 0.374176E+10 | 13680.68 | 11-MAY-17:00 | 8.90 |
June | 0.105627E+10 | 14489.94 | 13-JUN-11:03 | 10.00 |
July | 27295121.14 | 3322.17 | 02-JUL-11:10 | 18.48 |
August | 0.248708E+09 | 7455.71 | 31-AUG-11:10 | 14.60 |
September | 0.154380E+10 | 11545.89 | 28-SEP-17:00 | 10.60 |
October | 0.755952E+10 | 19709.44 | 24-OCT-11:10 | 4.50 |
November | 0.115367E+11 | 24795.02 | 23-NOV-18:00 | 0.60 |
December | 0.210000E+11 | 43269.81 | 10-DEC-18:00 | -12.8 |
Annual Sum or Average | 0.113088E+12 | |||
Minimum of Months | 27295121.14 | 3322.17 | -14.4 | |
Maximum of Months | 0.218981E+11 | 45644.50 | 18.48 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.290080E+10 | 2413.46 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.263912E+10 | 2413.46 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.300979E+10 | 2413.46 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.284005E+10 | 2413.46 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.295530E+10 | 2413.46 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.290440E+10 | 2413.46 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.289095E+10 | 2413.46 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.300979E+10 | 2413.46 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.284005E+10 | 2413.46 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.290080E+10 | 2413.46 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.280526E+10 | 2413.46 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.289095E+10 | 2413.46 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.345872E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.263912E+10 | 2413.46 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.300979E+10 | 2413.46 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.262901E+11 | 23840.77 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.217081E+11 | 23840.77 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.241582E+11 | 23840.77 | 01-MAR-15:00 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.206451E+11 | 23840.77 | 07-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.213393E+11 | 23840.77 | 11-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.203583E+11 | 21854.04 | 01-JUN-16:40 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.202216E+11 | 21854.04 | 03-JUL-16:40 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.212266E+11 | 23840.77 | 28-AUG-16:10 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.218601E+11 | 23840.77 | 01-SEP-16:00 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.243384E+11 | 23840.77 | 02-OCT-16:40 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.246732E+11 | 23840.77 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.262887E+11 | 23840.77 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.273108E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.202216E+11 | 21854.04 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.262901E+11 | 23840.77 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.163184E+09 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.148475E+09 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.169362E+09 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.159794E+09 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.166273E+09 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.163430E+09 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.162637E+09 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.169362E+09 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.159794E+09 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.163184E+09 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.157798E+09 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.162637E+09 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194593E+10 | ||||
Minimum of Months | 0.148475E+09 | 136.69 | 0.00 | 0.00 | |
Maximum of Months | 0.169362E+09 | 136.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398297E+10 |
February | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421363E+10 |
March | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128551.76 | 0.256800E+10 |
April | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205584E+10 |
May | 0.536353E+10 | 0.295530E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1151331.81 | 0.120351E+10 |
June | 0.528933E+10 | 0.290440E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30205269.31 | 0.769162E+09 |
July | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64367093.23 | 0.411494E+09 |
August | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45785877.79 | 0.511234E+09 |
September | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3783171.36 | 0.782803E+09 |
October | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172022E+10 |
November | 0.504819E+10 | 0.280526E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232096E+10 |
December | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418340E+10 |
Annual Sum or Average | 0.628175E+11 | 0.345872E+11 | 0.499918E+11 | 0.146421E+09 | 0.247232E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411494E+09 |
Maximum of Months | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64367093.23 | 0.421363E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.262901E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348460E+10 |
February | 0.201852E+11 | 0.217081E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367607E+10 |
March | 0.230879E+11 | 0.241582E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 923953.45 | 0.227436E+10 |
April | 0.218263E+11 | 0.206451E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186657E+10 |
May | 0.225967E+11 | 0.213393E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 942563.81 | 0.109814E+10 |
June | 0.222841E+11 | 0.203583E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24593726.50 | 0.692150E+09 |
July | 0.221389E+11 | 0.202216E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51858740.46 | 0.372859E+09 |
August | 0.230879E+11 | 0.212266E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37200973.42 | 0.452745E+09 |
September | 0.218263E+11 | 0.218601E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3096693.52 | 0.689588E+09 |
October | 0.221054E+11 | 0.243384E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151898E+10 |
November | 0.212681E+11 | 0.246732E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206359E+10 |
December | 0.221389E+11 | 0.262887E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366351E+10 |
Annual Sum or Average | 0.264651E+12 | 0.273108E+12 | 0.842987E+11 | 0.118617E+09 | 0.218532E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.202216E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372859E+09 |
Maximum of Months | 0.230879E+11 | 0.262901E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51858740.46 | 0.367607E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175391E+10 |
February | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185124E+10 |
March | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489148.94 | 0.118026E+10 |
April | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954128E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499047.85 | 0.553868E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12961308.47 | 0.359460E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26053212.93 | 0.204687E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19330923.52 | 0.251446E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1639471.66 | 0.368602E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806507E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108103E+10 |
December | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184125E+10 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.529224E+11 | 60973113.37 | 0.112064E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204687E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26053212.93 | 0.185124E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172148E+10 |
February | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182352E+10 |
March | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 489238.10 | 0.112943E+10 |
April | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.893376E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 498985.75 | 0.516749E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13011398.63 | 0.332425E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27067184.17 | 0.182334E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19478204.67 | 0.229596E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1639519.30 | 0.346032E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.755420E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101197E+10 |
December | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180098E+10 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.794328E+10 | 62184530.62 | 0.107433E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182334E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27067184.17 | 0.182352E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214980E+11 |
February | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200634E+11 |
March | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150346E+11 |
April | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931650E+10 |
May | 0.00 | 0.166273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43764.01 | 0.426809E+10 |
June | 0.00 | 0.163430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8290830.31 | 0.157017E+10 |
July | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16559426.02 | 0.398664E+09 |
August | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5180820.72 | 0.745952E+09 |
September | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236874E+10 |
October | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821383E+10 |
November | 0.00 | 0.157798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117400E+11 |
December | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206613E+11 |
Annual Sum or Average | 0.00 | 0.194593E+10 | 30074841.07 | 0.115879E+12 | |||||
Minimum of Months | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398664E+09 |
Maximum of Months | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16559426.02 | 0.214980E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2413.46 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7921.73 | 12-JAN-05:55 |
February | 5888.82 | 01-FEB-15:09 | 2413.46 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8287.36 | 13-FEB-05:53 |
March | 5888.82 | 01-MAR-15:09 | 2413.46 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.30 | 15-MAR-14:00 | 4416.02 | 02-MAR-05:05 |
April | 5888.82 | 01-APR-10:09 | 2413.46 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4409.04 | 16-APR-06:55 |
May | 5888.82 | 01-MAY-14:09 | 2413.46 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 | 14-MAY-15:00 | 2182.57 | 05-MAY-21:00 |
June | 5888.82 | 01-JUN-14:09 | 2413.46 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 314.14 | 12-JUN-13:00 | 2365.56 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 2413.46 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 464.68 | 21-JUL-03:00 | 1684.51 | 06-JUL-02:00 |
August | 5888.82 | 01-AUG-14:09 | 2413.46 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 389.62 | 13-AUG-18:03 | 1248.80 | 30-AUG-20:20 |
September | 5888.82 | 01-SEP-14:09 | 2413.46 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 | 16-SEP-13:00 | 2059.90 | 29-SEP-04:00 |
October | 5888.82 | 02-OCT-14:09 | 2413.46 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2380.85 | 07-OCT-02:00 |
November | 5888.82 | 01-NOV-14:09 | 2413.46 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4262.40 | 17-NOV-02:00 |
December | 5888.82 | 01-DEC-15:09 | 2413.46 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6563.06 | 28-DEC-21:01 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.80 | |||||
Maximum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 464.68 | 8287.36 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 23840.77 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6753.46 | 12-JAN-01:53 |
February | 24809.68 | 01-FEB-15:09 | 23840.77 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6830.55 | 13-FEB-05:55 |
March | 24809.68 | 01-MAR-15:09 | 23840.77 | 01-MAR-15:00 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.18 | 15-MAR-14:00 | 4191.87 | 02-MAR-01:00 |
April | 24809.68 | 01-APR-10:09 | 23840.77 | 07-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4049.71 | 16-APR-02:00 |
May | 24809.68 | 01-MAY-14:09 | 23840.77 | 11-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 90.02 | 14-MAY-15:00 | 2034.63 | 05-MAY-21:00 |
June | 24809.68 | 01-JUN-14:09 | 21854.04 | 01-JUN-16:40 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 257.14 | 12-JUN-13:00 | 2149.35 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 21854.04 | 03-JUL-16:40 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 366.64 | 21-JUL-03:00 | 1555.07 | 06-JUL-02:00 |
August | 24809.68 | 01-AUG-14:09 | 23840.77 | 28-AUG-16:10 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 316.52 | 13-AUG-18:03 | 1081.71 | 30-AUG-20:40 |
September | 24809.68 | 01-SEP-14:09 | 23840.77 | 01-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.40 | 16-SEP-13:00 | 1915.79 | 29-SEP-04:00 |
October | 24809.68 | 02-OCT-14:09 | 23840.77 | 02-OCT-16:40 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2172.42 | 07-OCT-02:00 |
November | 24809.68 | 01-NOV-14:09 | 23840.77 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4081.40 | 17-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 23840.77 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5396.93 | 28-DEC-21:01 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 21854.04 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.71 | |||||
Maximum of Months | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 366.64 | 6830.55 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3432.72 | 12-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3608.95 | 13-FEB-05:55 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 | 15-MAR-14:00 | 2155.41 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1898.16 | 16-APR-07:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 14-MAY-15:00 | 1021.49 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 | 12-JUN-13:00 | 1077.51 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.86 | 15-JUL-15:00 | 783.91 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.36 | 13-AUG-18:03 | 567.08 | 30-AUG-20:30 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 | 16-SEP-13:00 | 926.27 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1069.43 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2038.78 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2845.83 | 28-DEC-21:01 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.08 | |||||
Maximum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 185.86 | 3608.95 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3432.72 | 12-JAN-05:55 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3610.04 | 13-FEB-05:55 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 15-MAR-14:00 | 2042.69 | 02-MAR-01:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1899.37 | 16-APR-06:55 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 14-MAY-15:00 | 957.32 | 05-MAY-21:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.13 | 12-JUN-13:00 | 1025.77 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 185.86 | 15-JUL-15:00 | 725.04 | 06-JUL-02:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 160.95 | 13-AUG-18:03 | 541.91 | 30-AUG-20:20 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.63 | 16-SEP-13:00 | 866.63 | 29-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1017.52 | 07-OCT-02:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1903.86 | 17-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2842.61 | 28-DEC-21:01 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.91 | |||||
Maximum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 185.86 | 3610.04 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41846.85 | 31-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 45204.49 | 06-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 37057.13 | 06-MAR-18:00 |
April | 0.00 | 01-APR-00:10 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 29282.33 | 16-APR-11:10 |
May | 0.00 | 01-MAY-00:10 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.75 | 10-MAY-14:00 | 14291.04 | 18-MAY-11:02 |
June | 0.00 | 01-JUN-00:10 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.07 | 12-JUN-11:03 | 15785.35 | 13-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.79 | 15-JUL-13:55 | 3990.32 | 02-JUL-11:10 |
August | 0.00 | 01-AUG-00:10 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.47 | 13-AUG-11:05 | 7859.98 | 31-AUG-11:10 |
September | 0.00 | 01-SEP-00:10 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 11937.29 | 28-SEP-17:00 |
October | 0.00 | 01-OCT-00:10 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 20095.59 | 24-OCT-11:10 |
November | 0.00 | 01-NOV-00:10 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 24657.55 | 22-NOV-18:00 |
December | 0.00 | 01-DEC-00:10 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 42965.18 | 10-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3990.32 | ||||
Maximum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 622.79 | 45204.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5313.51 | 03-JAN-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 714.26 |
February | 5547.56 | 16-FEB-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1065.71 |
March | 5744.87 | 24-MAR-06:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.41 |
April | 5334.11 | 17-APR-06:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.48 |
May | 17226.50 | 24-MAY-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.13 |
June | 35394.66 | 23-JUN-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.67 |
July | 36951.07 | 06-JUL-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.20 |
August | 39310.42 | 03-AUG-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.40 |
September | 37448.14 | 18-SEP-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6666.88 | 13-OCT-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.68 |
November | 5221.88 | 24-NOV-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.28 |
December | 5540.95 | 06-DEC-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5221.88 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39310.42 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1065.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 62145.60 | 04-JAN-07:05 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.13 |
February | 60182.21 | 28-FEB-07:05 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.67 |
March | 168653.13 | 16-MAR-06:03 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.23 |
April | 69935.71 | 09-APR-08:63 | 9303.63 | 6622.44 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.19 |
May | 203200.28 | 18-MAY-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.58 |
June | 215070.57 | 14-JUN-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.62 |
July | 166363.46 | 06-JUL-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.31 |
August | 179723.38 | 03-AUG-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.22 |
September | 189647.83 | 06-SEP-06:03 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.10 |
October | 191260.70 | 05-OCT-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.05 |
November | 33112.52 | 15-NOV-07:03 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.25 |
December | 60601.54 | 28-DEC-07:05 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 33112.52 | 9303.63 | 6622.44 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.22 | |
Maximum of Months | 215070.57 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4637.53 | 12-JAN-13:30 | 2045.54 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.66 |
February | 4450.07 | 05-FEB-15:33 | 3506.64 | 4492.93 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.73 |
March | 16505.54 | 16-MAR-06:03 | 1168.88 | 1996.86 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.79 |
April | 5929.38 | 22-APR-13:40 | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.38 |
May | 21257.07 | 17-MAY-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.84 |
June | 25340.48 | 03-JUN-06:02 | 1461.10 | 1248.04 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 |
July | 22969.70 | 06-JUL-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.12 |
August | 24351.50 | 03-AUG-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.38 |
September | 25505.20 | 12-SEP-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.89 |
October | 23940.99 | 13-OCT-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.58 |
November | 6506.78 | 01-NOV-12:00 | 2045.54 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.74 |
December | 4100.91 | 29-DEC-09:23 | 4383.30 | 6739.39 | 8762.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4100.91 | 1168.88 | 1248.04 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.84 | |
Maximum of Months | 25505.20 | 4383.30 | 6739.39 | 8762.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 808.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3967.49 | 06-JAN-18:33 | 4383.30 | 3744.11 | 1315.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.00 |
February | 3995.42 | 24-FEB-11:43 | 6136.63 | 6739.39 | 1315.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.03 |
March | 5008.20 | 15-MAR-13:40 | 2045.54 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 0.00 |
April | 4200.61 | 03-APR-06:05 | 1168.88 | 1996.86 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 |
May | 12077.35 | 24-MAY-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 |
June | 14918.18 | 11-JUN-08:62 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 |
July | 17089.55 | 12-JUL-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.30 |
August | 18242.57 | 02-AUG-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17857.61 | 23-SEP-06:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.70 |
October | 15851.62 | 12-OCT-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.39 |
November | 3923.22 | 25-NOV-07:05 | 1168.88 | 998.43 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.32 |
December | 5250.14 | 10-DEC-15:23 | 4675.52 | 5990.57 | 1558.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3923.22 | 1168.88 | 998.43 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18242.57 | 6136.63 | 6739.39 | 1558.77 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 503.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.46 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.79 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.15 |
April | 0.00 | 01-APR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.19 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.31 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.27 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | |
Maximum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.79 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.927758E+11 | 67404.38 | 02-JAN-16:49 | 0.135341E+12 | 211312.33 | 30-JAN-07:10 |
February | 0.816336E+11 | 67404.38 | 01-FEB-17:30 | 0.128782E+12 | 245473.86 | 07-FEB-07:10 |
March | 0.909553E+11 | 77219.79 | 15-MAR-16:30 | 0.687895E+11 | 205725.79 | 07-MAR-07:10 |
April | 0.827715E+11 | 62760.27 | 25-APR-16:00 | 0.256113E+11 | 137855.24 | 17-APR-06:10 |
May | 0.875057E+11 | 80062.28 | 10-MAY-15:20 | 0.104354E+11 | 18571.91 | 11-MAY-16:00 |
June | 0.100472E+12 | 94714.42 | 17-JUN-16:49 | 0.814421E+10 | 16448.51 | 13-JUN-11:00 |
July | 0.118238E+12 | 101611.38 | 15-JUL-13:00 | 0.786903E+10 | 4991.92 | 03-JUL-11:30 |
August | 0.113522E+12 | 95712.00 | 10-AUG-16:10 | 0.797058E+10 | 10092.37 | 31-AUG-11:09 |
September | 0.950220E+11 | 93248.09 | 16-SEP-15:50 | 0.814773E+10 | 15849.62 | 28-SEP-16:00 |
October | 0.894717E+11 | 76452.84 | 11-OCT-15:20 | 0.157837E+11 | 70427.46 | 17-OCT-06:40 |
November | 0.879483E+11 | 67419.84 | 16-NOV-17:00 | 0.341181E+11 | 134586.46 | 24-NOV-07:10 |
December | 0.928277E+11 | 67404.38 | 01-DEC-16:40 | 0.120706E+12 | 238907.68 | 11-DEC-07:10 |
Annual Sum or Average | 0.113314E+13 | 0.571699E+12 | ||||
Minimum of Months | 0.816336E+11 | 62760.27 | 0.786903E+10 | 4991.92 | ||
Maximum of Months | 0.118238E+12 | 101611.38 | 0.135341E+12 | 245473.86 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.347178E+11 | 0.766040E+10 | 0.164409E+11 | 0.00 | 0.339567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293760E+11 | 0.639249E+10 | 0.149157E+11 | 0.00 | 0.309494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329041E+11 | 0.635070E+10 | 0.168545E+11 | 0.00 | 0.338196E+11 | 0.00 | 0.00 | 0.102643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288972E+11 | 0.541161E+10 | 0.160165E+11 | 0.00 | 0.323423E+11 | 0.00 | 0.00 | 0.103906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299261E+11 | 0.494624E+10 | 0.166477E+11 | 0.00 | 0.321793E+11 | 0.00 | 0.00 | 0.380633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.287979E+11 | 0.447530E+10 | 0.162772E+11 | 0.00 | 0.299179E+11 | 0.00 | 0.00 | 0.210042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.286209E+11 | 0.474839E+10 | 0.163871E+11 | 0.00 | 0.295379E+11 | 0.00 | 0.00 | 0.389441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.299725E+11 | 0.530293E+10 | 0.168545E+11 | 0.00 | 0.302190E+11 | 0.00 | 0.00 | 0.311731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301121E+11 | 0.582960E+10 | 0.160165E+11 | 0.00 | 0.301383E+11 | 0.00 | 0.00 | 0.129254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.327661E+11 | 0.677705E+10 | 0.164409E+11 | 0.00 | 0.325950E+11 | 0.00 | 0.00 | 0.892657E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328229E+11 | 0.721176E+10 | 0.159174E+11 | 0.00 | 0.319930E+11 | 0.00 | 0.00 | 3155416.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.346880E+11 | 0.783596E+10 | 0.163871E+11 | 0.00 | 0.339167E+11 | 0.00 | 0.00 | 67.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373601E+12 | 0.729424E+11 | 0.195156E+12 | 0.381565E+12 | 0.00 | 0.109879E+12 | |||||||
Minimum of Months | 0.286209E+11 | 0.447530E+10 | 0.149157E+11 | 0.00 | 0.295379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.347178E+11 | 0.783596E+10 | 0.168545E+11 | 0.00 | 0.339567E+11 | 0.00 | 0.00 | 0.389441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.126839E+12 | 0.00 | 0.850223E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.121041E+12 | 0.00 | 0.774133E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.601959E+11 | 0.00 | 0.859363E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.174769E+11 | 0.00 | 0.813438E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.221601E+10 | 0.00 | 0.821940E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.329940E+09 | 0.00 | 0.781427E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.786903E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 71277021.69 | 0.00 | 0.789930E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.495728E+09 | 0.00 | 0.765200E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.777427E+10 | 0.00 | 0.800948E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.261978E+11 | 0.00 | 0.792031E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.112327E+12 | 0.00 | 0.837915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.474964E+12 | 0.967345E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.765200E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.126839E+12 | 0.00 | 0.859363E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30883.85 | 02-JAN-09:09 | 4644.36 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 21105.13 | 02-JAN-06:40 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30883.85 | 01-FEB-09:09 | 4644.36 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 21105.13 | 01-FEB-09:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30883.85 | 01-MAR-15:00 | 4644.36 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 21105.13 | 01-MAR-09:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30883.85 | 07-APR-16:00 | 4644.36 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 21105.13 | 01-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30883.85 | 11-MAY-16:49 | 4644.36 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 21105.13 | 06-MAY-14:39 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28897.12 | 01-JUN-16:40 | 4644.36 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 21105.13 | 04-JUN-13:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28897.12 | 03-JUL-16:40 | 4644.36 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 21105.13 | 02-JUL-11:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30883.85 | 28-AUG-16:10 | 4644.36 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 21105.13 | 30-AUG-11:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30883.85 | 01-SEP-16:00 | 4644.36 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 21105.13 | 01-SEP-11:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30883.85 | 02-OCT-16:40 | 4644.36 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 21105.13 | 01-OCT-16:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30883.85 | 01-NOV-08:09 | 4644.36 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 21105.13 | 06-NOV-12:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30883.85 | 01-DEC-09:09 | 4644.36 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 21105.13 | 01-DEC-19:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 28897.12 | 4644.36 | 10771.04 | 0.00 | 21105.13 | 0.00 | 0.00 | |||||
Maximum of Months | 30883.85 | 4644.36 | 10771.04 | 0.00 | 21105.13 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22364.05 | 15-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8074.94 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27342.21 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 45116.69 | 27-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47543.67 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42123.39 | 10-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36646.11 | 16-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17419.41 | 11-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 704.99 | 05-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.07 | 01-DEC-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47543.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 67404.38 | 02-JAN-16:49 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21105.13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67404.38 | 01-FEB-17:30 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21105.13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77219.79 | 15-MAR-16:30 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 19178.62 | 0.00 |
April | 62760.27 | 25-APR-16:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 21105.13 | 0.00 | 0.00 | 0.25 | 0.00 |
May | 80062.28 | 10-MAY-15:20 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 25994.57 | 0.00 |
June | 94714.42 | 17-JUN-16:49 | 26910.39 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 38659.98 | 0.00 |
July | 101611.38 | 15-JUL-13:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 47543.67 | 0.00 |
August | 95712.00 | 10-AUG-16:10 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 37670.83 | 0.00 |
September | 93248.09 | 16-SEP-15:50 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 35206.93 | 0.00 |
October | 76452.84 | 11-OCT-15:20 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 16424.94 | 0.00 |
November | 67419.84 | 16-NOV-17:00 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21105.13 | 0.00 | 0.00 | 15.45 | 0.00 |
December | 67404.38 | 01-DEC-16:40 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21105.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 62760.27 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18373.01 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 101611.38 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21105.13 | 0.00 | 0.00 | 47543.67 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 207684.85 | 10-JAN-07:10 | 0.00 | 5198.04 | 25-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 241600.17 | 07-FEB-07:10 | 0.00 | 5273.21 | 10-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 203863.79 | 07-MAR-07:10 | 0.00 | 5190.17 | 09-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 135993.24 | 17-APR-06:10 | 0.00 | 5132.19 | 04-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 13685.69 | 11-MAY-16:00 | 0.00 | 5088.44 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 11432.24 | 13-JUN-11:00 | 0.00 | 5036.34 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4991.92 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 5124.69 | 31-AUG-11:09 | 0.00 | 4969.31 | 01-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 11017.20 | 28-SEP-16:00 | 0.00 | 4990.86 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 65875.65 | 17-OCT-06:40 | 0.00 | 5034.80 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 132724.46 | 24-NOV-07:10 | 0.00 | 5087.48 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 234340.54 | 11-DEC-07:10 | 0.00 | 5131.26 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4969.31 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 241600.17 | 0.00 | 5273.21 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.00 | 16.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 16.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.33 | 16.89 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 16.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 16.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.67 | 16.62 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 16.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.00 | 16.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 17.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 16.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.00 | 16.44 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 17.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.33 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.17 | 19.85 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 399.83 | 21.11 | 399.83 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 418.00 | 21.48 | 269.67 | 21.11 | 269.67 | 21.11 |
April | 405.00 | 22.22 | 77.50 | 21.12 | 77.50 | 21.12 |
May | 360.33 | 23.57 | 5.83 | 23.89 | 3.33 | 23.89 |
June | 129.00 | 23.84 | 176.67 | 23.89 | 47.33 | 23.89 |
July | 96.00 | 23.90 | 365.17 | 23.89 | 94.50 | 23.90 |
August | 63.67 | 23.89 | 296.17 | 23.89 | 57.83 | 23.89 |
September | 147.33 | 23.78 | 132.50 | 23.89 | 40.50 | 23.89 |
October | 376.00 | 22.97 | 12.17 | 21.11 | 12.17 | 21.11 |
November | 399.00 | 21.70 | 128.67 | 21.11 | 128.67 | 21.11 |
December | 415.00 | 21.13 | 376.17 | 21.11 | 376.17 | 21.11 |
Annual Sum or Average | 3599.33 | 22.12 | 2616.33 | 22.15 | 1883.50 | 21.47 |
Minimum of Months | 63.67 | 21.11 | 5.83 | 21.11 | 3.33 | 21.11 |
Maximum of Months | 418.00 | 23.90 | 399.83 | 23.89 | 399.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.12 | 335.33 | 21.11 | 335.33 | 21.11 |
February | 376.00 | 21.12 | 290.50 | 21.11 | 290.50 | 21.11 |
March | 386.50 | 21.41 | 115.33 | 21.21 | 111.17 | 21.11 |
April | 362.83 | 22.39 | 9.67 | 21.11 | 9.67 | 21.11 |
May | 133.17 | 23.49 | 81.83 | 23.89 | 2.00 | 23.89 |
June | 40.50 | 23.84 | 289.33 | 23.89 | 31.17 | 23.89 |
July | 83.83 | 23.90 | 406.00 | 23.89 | 83.83 | 23.90 |
August | 47.83 | 23.89 | 387.17 | 23.89 | 47.83 | 23.89 |
September | 47.33 | 23.64 | 229.50 | 23.89 | 28.33 | 23.89 |
October | 268.00 | 22.69 | 18.33 | 23.88 | 0.00 | 0.00 |
November | 392.83 | 21.81 | 20.50 | 21.11 | 20.50 | 21.11 |
December | 415.00 | 21.14 | 239.17 | 21.11 | 239.17 | 21.11 |
Annual Sum or Average | 2967.83 | 21.86 | 2422.67 | 22.74 | 1199.50 | 21.56 |
Minimum of Months | 40.50 | 21.12 | 9.67 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.90 | 406.00 | 23.89 | 335.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.17 | 310.33 | 21.11 | 310.33 | 21.11 |
February | 376.00 | 21.21 | 277.83 | 21.11 | 277.83 | 21.11 |
March | 381.17 | 21.91 | 120.50 | 21.58 | 100.00 | 21.11 |
April | 323.50 | 22.62 | 31.50 | 21.20 | 30.50 | 21.11 |
May | 163.33 | 23.48 | 64.00 | 23.89 | 0.00 | 0.00 |
June | 50.50 | 23.79 | 270.50 | 23.89 | 28.17 | 23.89 |
July | 75.50 | 23.90 | 402.33 | 23.89 | 75.50 | 23.90 |
August | 37.00 | 23.90 | 398.17 | 23.89 | 36.67 | 23.90 |
September | 38.83 | 23.67 | 299.50 | 23.89 | 17.50 | 23.90 |
October | 188.00 | 22.97 | 87.00 | 23.78 | 3.33 | 21.10 |
November | 344.00 | 22.27 | 37.67 | 21.24 | 35.83 | 21.11 |
December | 415.00 | 21.23 | 276.67 | 21.11 | 276.67 | 21.11 |
Annual Sum or Average | 2806.83 | 22.03 | 2576.00 | 22.77 | 1192.33 | 21.48 |
Minimum of Months | 37.00 | 21.17 | 31.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.90 | 402.33 | 23.89 | 310.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 368.00 | 21.11 | 368.00 | 21.11 |
February | 376.00 | 21.12 | 325.33 | 21.11 | 325.33 | 21.11 |
March | 396.00 | 21.35 | 171.50 | 21.29 | 160.50 | 21.11 |
April | 378.33 | 21.95 | 59.50 | 21.11 | 59.50 | 21.11 |
May | 257.50 | 23.03 | 28.33 | 23.81 | 3.33 | 23.19 |
June | 96.17 | 23.57 | 223.50 | 23.89 | 39.00 | 23.89 |
July | 92.17 | 23.88 | 385.33 | 23.89 | 87.67 | 23.89 |
August | 53.00 | 23.84 | 369.67 | 23.89 | 45.83 | 23.89 |
September | 83.17 | 23.33 | 249.00 | 23.89 | 25.67 | 23.89 |
October | 275.83 | 22.28 | 56.83 | 23.42 | 9.67 | 21.11 |
November | 375.67 | 21.59 | 81.33 | 21.11 | 81.33 | 21.11 |
December | 415.00 | 21.12 | 344.83 | 21.11 | 344.83 | 21.11 |
Annual Sum or Average | 3212.83 | 21.81 | 2663.17 | 22.48 | 1550.67 | 21.47 |
Minimum of Months | 53.00 | 21.11 | 28.33 | 21.11 | 3.33 | 21.11 |
Maximum of Months | 415.00 | 23.88 | 385.33 | 23.89 | 368.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09572 | 21.61196 | -0.7080 | 15.73223 |
February | 376.00000 | 21.09562 | 21.63308 | -0.7108 | 15.80284 |
March | 422.00000 | 21.48650 | 30.23631 | -0.5009 | 12.16973 |
April | 405.00000 | 22.20464 | 35.01945 | -0.2551 | 7.99329 |
May | 418.00000 | 23.60583 | 37.63760 | -0.8169 | 20.12663 |
June | 408.00000 | 23.88364 | 47.16786 | -0.5239 | 11.11643 |
July | 415.00000 | 23.91006 | 55.87096 | -0.3958 | 8.40301 |
August | 422.00000 | 23.90725 | 51.63444 | -0.4389 | 9.16286 |
September | 405.00000 | 23.85398 | 47.58497 | -0.5616 | 12.04781 |
October | 414.00000 | 23.05085 | 38.85902 | 0.02110 | 6.49580 |
November | 399.00000 | 21.69328 | 34.00379 | -0.3811 | 9.16747 |
December | 415.00000 | 21.11125 | 25.36206 | -0.6589 | 14.40543 |
Annual Sum or Average | 4913.00000 | 22.58696 | 37.33553 | -0.4934 | 11.87361 |
Minimum of Months | 376.00000 | 21.09562 | 21.61196 | -0.8169 | 6.49580 |
Maximum of Months | 422.00000 | 23.91006 | 55.87096 | 0.02110 | 20.12663 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10981 | 19.21978 | -0.6033 | 12.83135 |
February | 376.00000 | 21.11110 | 19.13756 | -0.6036 | 12.81506 |
March | 422.00000 | 21.61378 | 27.43026 | -0.3518 | 9.46505 |
April | 405.00000 | 22.55585 | 31.87777 | -0.0632 | 6.71091 |
May | 418.00000 | 23.77229 | 35.45770 | -0.5967 | 13.15259 |
June | 408.00000 | 23.90233 | 45.78066 | -0.3910 | 8.46504 |
July | 415.00000 | 23.91218 | 54.64010 | -0.2948 | 6.93377 |
August | 422.00000 | 23.91026 | 50.31192 | -0.3457 | 7.62823 |
September | 405.00000 | 23.87629 | 46.43332 | -0.4477 | 9.52734 |
October | 414.00000 | 23.12609 | 36.45404 | 0.12462 | 6.63494 |
November | 399.00000 | 21.85374 | 31.47679 | -0.2551 | 7.60019 |
December | 415.00000 | 21.13622 | 22.91989 | -0.5552 | 11.77182 |
Annual Sum or Average | 4913.00000 | 22.66869 | 35.21562 | -0.3643 | 9.44722 |
Minimum of Months | 376.00000 | 21.10981 | 19.13756 | -0.6036 | 6.63494 |
Maximum of Months | 422.00000 | 23.91218 | 54.64010 | 0.12462 | 13.15259 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.15290 | 18.49477 | -0.6136 | 13.34145 |
February | 376.00000 | 21.19521 | 18.48830 | -0.6041 | 13.26372 |
March | 422.00000 | 22.09182 | 26.05920 | -0.2535 | 9.00867 |
April | 405.00000 | 22.86425 | 30.16393 | -0.0215 | 7.09898 |
May | 418.00000 | 23.73201 | 34.68712 | -0.6414 | 14.67974 |
June | 408.00000 | 23.89289 | 44.83087 | -0.4004 | 8.79329 |
July | 415.00000 | 23.91212 | 53.06233 | -0.2727 | 6.71805 |
August | 422.00000 | 23.91045 | 48.95244 | -0.2950 | 7.01649 |
September | 405.00000 | 23.88232 | 45.03628 | -0.3804 | 8.54758 |
October | 414.00000 | 23.47556 | 34.39348 | 0.22660 | 7.45357 |
November | 399.00000 | 22.49121 | 29.42784 | -0.1210 | 7.46955 |
December | 415.00000 | 21.21991 | 22.25202 | -0.5651 | 12.37032 |
Annual Sum or Average | 4913.00000 | 22.82983 | 33.93969 | -0.3275 | 9.63191 |
Minimum of Months | 376.00000 | 21.15290 | 18.48830 | -0.6414 | 6.71805 |
Maximum of Months | 422.00000 | 23.91212 | 53.06233 | 0.22660 | 14.67974 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09636 | 18.64625 | -0.6675 | 14.64916 |
February | 376.00000 | 21.10353 | 18.62001 | -0.6635 | 14.58289 |
March | 422.00000 | 21.49861 | 27.19375 | -0.4111 | 10.46645 |
April | 405.00000 | 22.06343 | 32.13603 | -0.2175 | 7.98052 |
May | 418.00000 | 23.35067 | 36.64455 | -0.8052 | 20.58794 |
June | 408.00000 | 23.81991 | 46.24347 | -0.4735 | 10.42251 |
July | 415.00000 | 23.90481 | 54.47148 | -0.3217 | 7.35387 |
August | 422.00000 | 23.89950 | 49.92813 | -0.3494 | 7.79080 |
September | 405.00000 | 23.77814 | 46.17765 | -0.4623 | 10.39120 |
October | 414.00000 | 22.81281 | 36.45828 | 0.06029 | 7.23639 |
November | 399.00000 | 21.72103 | 31.01249 | -0.3141 | 8.84126 |
December | 415.00000 | 21.11106 | 22.45019 | -0.6308 | 13.69747 |
Annual Sum or Average | 4913.00000 | 22.52484 | 35.12276 | -0.4371 | 11.15632 |
Minimum of Months | 376.00000 | 21.09636 | 18.62001 | -0.8052 | 7.23639 |
Maximum of Months | 422.00000 | 23.90481 | 54.47148 | 0.06029 | 20.58794 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.272420E+09 | 76827515.74 | 22.95 | 0.222848E+09 | 49572492.55 | 0.00 | 0.29 | 15-MAR-14:20 | 0.00 | 01-MAR-00:10 | 7982.05 | 15-MAR-14:20 | 6888.96 | 15-MAR-14:10 | 1598.78 | 14-MAR-14:10 | 2258.15 | 15-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 1411191.89 | 398941.23 | 17.63 | 1276264.64 | 134927.25 | 0.00 | 0.02 | 08-APR-13:00 | 0.00 | 01-APR-00:10 | 494.85 | 08-APR-13:00 | 453.95 | 08-APR-13:00 | 40.90 | 08-APR-13:00 | 139.69 | 08-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.948651E+09 | 0.260625E+09 | 196.76 | 0.849723E+09 | 98928542.81 | 0.00 | 0.54 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 | 15948.10 | 24-MAY-06:02 | 10669.10 | 24-MAY-06:02 | 5279.00 | 24-MAY-06:02 | 3915.65 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.830331E+10 | 0.220022E+10 | 324.37 | 0.621529E+10 | 0.208802E+10 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 37831.76 | 18-JUN-08:62 | 29994.26 | 11-JUN-08:62 | 18884.35 | 08-JUN-06:02 | 7972.27 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.177174E+11 | 0.461555E+10 | 391.80 | 0.122800E+11 | 0.543740E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 38767.38 | 21-JUL-05:03 | 24268.20 | 15-JUL-06:02 | 20924.62 | 29-JUL-06:04 | 8068.20 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.137874E+11 | 0.365084E+10 | 374.57 | 0.105199E+11 | 0.326749E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 37942.24 | 14-AUG-06:02 | 26807.89 | 06-AUG-08:62 | 21119.68 | 14-AUG-06:06 | 7859.25 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.485613E+10 | 0.127038E+10 | 267.87 | 0.342593E+10 | 0.143020E+10 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 36745.15 | 16-SEP-06:02 | 24392.87 | 08-SEP-06:02 | 18302.09 | 14-SEP-06:04 | 7701.03 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 95434827.63 | 26556383.31 | 85.86 | 85916242.23 | 9518585.40 | 0.00 | 0.19 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4889.71 | 11-OCT-15:00 | 4375.50 | 11-OCT-15:00 | 514.21 | 11-OCT-15:00 | 1345.74 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 3370.69 | 955.77 | 4.11 | 2583.90 | 786.79 | 0.00 | 0.00 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 | 0.45 | 04-NOV-16:00 | 0.34 | 04-NOV-16:00 | 0.11 | 04-NOV-16:00 | 0.13 | 04-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.459821E+11 | 0.121014E+11 | 1685.92 | 0.336008E+11 | 0.123813E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.177174E+11 | 0.461555E+10 | 391.80 | 0.122800E+11 | 0.543740E+10 | 0.00 | 1.00 | 0.00 | 38767.38 | 29994.26 | 21119.68 | 8068.20 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.245086E+10 | 0.750274E+09 | 31.78 | 0.199296E+10 | 0.457898E+09 | 0.00 | 1.00 | 16-MAR-06:03 | 0.00 | 01-MAR-00:10 | 155793.12 | 16-MAR-06:03 | 107928.67 | 16-MAR-06:03 | 47864.46 | 16-MAR-06:03 | 36882.22 | 16-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.250856E+09 | 77306934.67 | 49.02 | 0.220889E+09 | 29966999.66 | 0.00 | 0.16 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 20370.20 | 08-APR-13:30 | 18042.70 | 08-APR-13:00 | 4661.27 | 09-APR-08:63 | 6199.75 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.102029E+11 | 0.303293E+10 | 241.89 | 0.896165E+10 | 0.124127E+10 | 0.00 | 1.00 | 11-MAY-06:02 | 0.00 | 01-MAY-00:10 | 168525.83 | 29-MAY-08:62 | 137487.87 | 17-MAY-06:02 | 68008.92 | 11-MAY-06:02 | 40012.12 | 29-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.539970E+11 | 0.157249E+11 | 362.67 | 0.399893E+11 | 0.140076E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 184338.84 | 18-JUN-08:62 | 143596.61 | 11-JUN-08:62 | 90071.91 | 18-JUN-08:04 | 43299.38 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.988088E+11 | 0.283543E+11 | 407.84 | 0.674929E+11 | 0.313160E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 186656.41 | 21-JUL-05:03 | 115897.94 | 15-JUL-06:02 | 99680.03 | 29-JUL-06:04 | 43809.40 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.766028E+11 | 0.224283E+11 | 392.78 | 0.575523E+11 | 0.190505E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 184658.83 | 14-AUG-06:02 | 127869.36 | 06-AUG-08:62 | 100032.77 | 14-AUG-06:04 | 42684.40 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.316602E+11 | 0.917590E+10 | 307.39 | 0.224058E+11 | 0.925439E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 178750.13 | 16-SEP-06:02 | 121005.55 | 08-SEP-06:02 | 88038.57 | 14-SEP-06:04 | 41837.38 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.186304E+10 | 0.558242E+09 | 97.80 | 0.155434E+10 | 0.308699E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 164608.47 | 01-OCT-08:62 | 113578.42 | 12-OCT-06:02 | 64093.51 | 01-OCT-08:62 | 39169.45 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 3115393.29 | 979005.76 | 11.36 | 2661327.73 | 454065.57 | 0.00 | 0.05 | 05-NOV-08:63 | 0.00 | 01-NOV-00:10 | 6759.53 | 05-NOV-08:63 | 5082.12 | 05-NOV-08:63 | 1677.41 | 05-NOV-08:63 | 2114.97 | 05-NOV-08:63 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.275840E+12 | 0.801031E+11 | 1902.52 | 0.200173E+12 | 0.756667E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.988088E+11 | 0.283543E+11 | 407.84 | 0.674929E+11 | 0.313160E+11 | 0.00 | 1.00 | 0.00 | 186656.41 | 143596.61 | 100032.77 | 43809.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.479338E+09 | 0.127332E+09 | 43.21 | 0.406759E+09 | 72579029.21 | 0.00 | 0.58 | 16-MAR-06:03 | 0.00 | 01-MAR-00:10 | 10205.53 | 16-MAR-06:03 | 9181.37 | 15-MAR-13:50 | 3106.74 | 16-MAR-06:03 | 2622.36 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 75531644.59 | 20446376.11 | 81.93 | 69565385.34 | 5966259.24 | 0.00 | 0.27 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 4399.44 | 08-APR-13:30 | 3985.54 | 08-APR-13:20 | 510.16 | 08-APR-14:00 | 1164.89 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.128169E+10 | 0.341147E+09 | 244.77 | 0.115691E+10 | 0.124780E+09 | 0.00 | 1.00 | 17-MAY-06:02 | 0.00 | 01-MAY-00:10 | 21292.85 | 24-MAY-06:02 | 17764.38 | 17-MAY-06:02 | 6937.44 | 24-MAY-06:02 | 4531.37 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.717843E+10 | 0.186238E+10 | 353.46 | 0.548994E+10 | 0.168849E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 23587.79 | 18-JUN-08:62 | 18660.41 | 11-JUN-08:62 | 11754.82 | 18-JUN-08:04 | 4964.45 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.136679E+11 | 0.348548E+10 | 401.71 | 0.973320E+10 | 0.393469E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 24191.52 | 21-JUL-05:03 | 14838.48 | 15-JUL-06:02 | 13100.60 | 29-JUL-06:02 | 5019.89 | 21-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.115736E+11 | 0.298135E+10 | 392.74 | 0.903712E+10 | 0.253644E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 23643.96 | 14-AUG-06:02 | 16602.89 | 06-AUG-08:62 | 13203.29 | 14-AUG-06:04 | 4894.01 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.590115E+10 | 0.149372E+10 | 322.61 | 0.440652E+10 | 0.149463E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 22846.63 | 16-SEP-06:02 | 15631.81 | 10-SEP-08:62 | 11504.77 | 14-SEP-06:02 | 4791.79 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.764854E+09 | 0.200293E+09 | 177.06 | 0.649155E+09 | 0.115699E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 21097.56 | 01-OCT-08:62 | 14612.24 | 12-OCT-06:02 | 8789.16 | 01-OCT-08:62 | 4492.24 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 7769113.00 | 2173015.59 | 41.63 | 6413402.81 | 1355710.19 | 0.00 | 0.09 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 | 1334.10 | 16-NOV-12:40 | 1157.95 | 16-NOV-12:40 | 185.06 | 16-NOV-13:00 | 369.74 | 16-NOV-12:40 | 0.00 | 01-NOV-00:10 |
December | 237.26 | 67.35 | 0.33 | 185.46 | 51.79 | 0.00 | 0.00 | 01-DEC-13:20 | 0.00 | 01-DEC-00:10 | 0.23 | 01-DEC-13:20 | 0.18 | 01-DEC-13:20 | 0.05 | 01-DEC-13:20 | 0.07 | 01-DEC-13:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.409302E+11 | 0.105143E+11 | 2059.47 | 0.309556E+11 | 0.997463E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.136679E+11 | 0.348548E+10 | 401.71 | 0.973320E+10 | 0.393469E+10 | 0.00 | 1.00 | 0.00 | 24191.52 | 18660.41 | 13203.29 | 5019.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.273167E+09 | 71998911.64 | 24.24 | 0.227264E+09 | 45903564.74 | 0.00 | 0.49 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 7081.26 | 15-MAR-13:40 | 6372.61 | 15-MAR-13:50 | 1481.91 | 14-MAR-12:50 | 1846.82 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 |
April | 21594111.05 | 5753298.52 | 30.67 | 19117459.57 | 2476651.48 | 0.00 | 0.18 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 2336.04 | 08-APR-13:30 | 2057.40 | 08-APR-13:20 | 308.01 | 08-APR-14:00 | 614.78 | 08-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 0.653023E+09 | 0.171633E+09 | 162.44 | 0.582166E+09 | 70857120.46 | 0.00 | 0.85 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 | 13970.31 | 24-MAY-06:02 | 9174.48 | 24-MAY-06:02 | 4795.83 | 24-MAY-06:02 | 3027.69 | 24-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.478698E+10 | 0.121668E+10 | 315.33 | 0.353941E+10 | 0.124757E+10 | 0.00 | 1.00 | 02-JUN-06:02 | 0.00 | 01-JUN-00:10 | 19016.54 | 18-JUN-08:62 | 14630.99 | 11-JUN-08:62 | 9583.74 | 18-JUN-08:04 | 3888.23 | 18-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.997461E+10 | 0.248877E+10 | 390.96 | 0.686889E+10 | 0.310572E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 19495.14 | 21-JUL-05:03 | 11807.36 | 15-JUL-06:02 | 10646.20 | 21-JUL-05:03 | 3935.85 | 21-JUL-06:15 | 0.00 | 01-JUL-00:10 |
August | 0.838006E+10 | 0.211255E+10 | 377.50 | 0.640480E+10 | 0.197526E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 19073.81 | 14-AUG-06:02 | 13132.79 | 13-AUG-08:62 | 10755.37 | 14-AUG-06:04 | 3833.36 | 14-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.397637E+10 | 0.985429E+09 | 278.57 | 0.291423E+10 | 0.106214E+10 | 0.00 | 1.00 | 08-SEP-06:02 | 0.00 | 01-SEP-00:10 | 18439.83 | 16-SEP-06:02 | 12015.63 | 08-SEP-06:02 | 9317.58 | 14-SEP-06:04 | 3754.48 | 16-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.420188E+09 | 0.107565E+09 | 88.46 | 0.353207E+09 | 66980762.82 | 0.00 | 0.90 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 | 14167.88 | 12-OCT-06:02 | 10046.55 | 12-OCT-06:02 | 4121.34 | 12-OCT-06:02 | 3014.49 | 12-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 8864.23 | 2439.77 | 11.02 | 7379.94 | 1484.28 | 0.00 | 0.00 | 01-NOV-16:10 | 0.00 | 01-NOV-00:10 | 3.34 | 01-NOV-16:10 | 3.15 | 01-NOV-16:10 | 0.18 | 01-NOV-16:10 | 0.91 | 01-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.284860E+11 | 0.716039E+10 | 1679.18 | 0.209091E+11 | 0.757690E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.997461E+10 | 0.248877E+10 | 390.96 | 0.686889E+10 | 0.310572E+10 | 0.00 | 1.00 | 0.00 | 19495.14 | 14630.99 | 10755.37 | 3935.85 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.55 | 10.53 | 25.02 | 13.11 | 94.37 | 0.00 | 0.00 | 744.00 |
February | 56.46 | 16.51 | 39.94 | 33.31 | 89.25 | 0.00 | 0.00 | 672.00 |
March | 87.08 | 44.68 | 42.40 | 77.53 | 66.81 | 0.00 | 0.00 | 744.00 |
April | 116.68 | 62.38 | 54.30 | 119.10 | 50.68 | 0.00 | 0.00 | 720.00 |
May | 148.48 | 91.48 | 57.00 | 166.38 | 37.95 | 0.00 | 0.00 | 744.00 |
June | 171.97 | 107.88 | 64.09 | 206.61 | 27.16 | 0.00 | 0.00 | 720.00 |
July | 159.40 | 96.80 | 62.60 | 199.42 | 20.23 | 0.00 | 0.00 | 744.00 |
August | 135.28 | 74.96 | 60.33 | 166.30 | 24.94 | 0.00 | 0.00 | 744.00 |
September | 101.35 | 55.36 | 46.00 | 114.84 | 37.69 | 0.00 | 0.00 | 720.00 |
October | 62.98 | 27.30 | 35.68 | 57.38 | 54.45 | 0.00 | 0.00 | 744.00 |
November | 36.37 | 11.33 | 25.04 | 23.49 | 65.02 | 0.00 | 0.00 | 720.00 |
December | 31.38 | 6.75 | 24.64 | 10.45 | 91.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 95.44 | 50.68 | 44.76 | 99.35 | 54.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 31.38 | 6.75 | 24.64 | 10.45 | 20.23 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.97 | 107.88 | 64.09 | 206.61 | 94.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 968.69 | 565.38 | 403.31 | 743.27 | 1109.12 | 0.00 | 0.00 | 744.00 |
February | 1106.47 | 533.67 | 572.81 | 791.86 | 1079.31 | 0.00 | 0.00 | 672.00 |
March | 1350.75 | 759.22 | 591.53 | 1124.40 | 824.65 | 0.00 | 0.00 | 744.00 |
April | 1118.08 | 446.73 | 671.35 | 816.59 | 645.84 | 0.00 | 0.00 | 720.00 |
May | 978.35 | 284.04 | 694.31 | 686.42 | 451.03 | 0.00 | 0.00 | 744.00 |
June | 950.61 | 201.30 | 749.32 | 781.41 | 300.44 | 0.00 | 0.00 | 720.00 |
July | 970.44 | 235.34 | 735.11 | 915.79 | 212.39 | 0.00 | 0.00 | 744.00 |
August | 1089.49 | 353.12 | 736.37 | 1050.59 | 279.60 | 0.00 | 0.00 | 744.00 |
September | 1267.14 | 617.28 | 649.85 | 1248.56 | 437.49 | 0.00 | 0.00 | 720.00 |
October | 1212.73 | 692.92 | 519.81 | 1142.33 | 660.67 | 0.00 | 0.00 | 744.00 |
November | 868.23 | 490.15 | 378.08 | 755.31 | 798.53 | 0.00 | 0.00 | 720.00 |
December | 809.94 | 419.07 | 390.87 | 586.99 | 1088.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1057.25 | 466.27 | 590.98 | 887.59 | 655.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 809.94 | 201.30 | 378.08 | 586.99 | 212.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1350.75 | 759.22 | 749.32 | 1248.56 | 1109.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 968.69 | 565.38 | 403.31 | 742.44 | 1097.45 | 0.00 | 0.00 | 744.00 |
February | 1106.47 | 533.67 | 572.81 | 791.29 | 1068.25 | 0.00 | 0.00 | 672.00 |
March | 1350.75 | 759.22 | 591.53 | 1132.22 | 797.38 | 0.00 | 0.00 | 744.00 |
April | 1118.08 | 446.73 | 671.35 | 828.47 | 611.70 | 0.00 | 0.00 | 720.00 |
May | 978.35 | 284.04 | 694.31 | 692.32 | 427.56 | 0.00 | 0.00 | 744.00 |
June | 950.61 | 201.30 | 749.32 | 780.22 | 286.01 | 0.00 | 0.00 | 720.00 |
July | 970.44 | 235.34 | 735.11 | 912.19 | 200.27 | 0.00 | 0.00 | 744.00 |
August | 1089.49 | 353.12 | 736.37 | 1046.53 | 267.04 | 0.00 | 0.00 | 744.00 |
September | 1267.14 | 617.28 | 649.85 | 1246.60 | 422.22 | 0.00 | 0.00 | 720.00 |
October | 1212.73 | 692.92 | 519.81 | 1149.81 | 629.08 | 0.00 | 0.00 | 744.00 |
November | 868.23 | 490.15 | 378.08 | 763.16 | 761.19 | 0.00 | 0.00 | 720.00 |
December | 809.94 | 419.07 | 390.87 | 587.34 | 1074.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1057.25 | 466.27 | 590.98 | 890.02 | 634.63 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 809.94 | 201.30 | 378.08 | 587.34 | 200.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1350.75 | 759.22 | 749.32 | 1246.60 | 1097.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.32 | 116.34 | 82.99 | 148.23 | 227.64 | 0.00 | 0.00 | 744.00 |
February | 227.67 | 109.81 | 117.86 | 157.48 | 222.03 | 0.00 | 0.00 | 672.00 |
March | 277.94 | 156.22 | 121.72 | 227.66 | 164.20 | 0.00 | 0.00 | 744.00 |
April | 230.06 | 91.92 | 138.14 | 168.26 | 124.25 | 0.00 | 0.00 | 720.00 |
May | 201.31 | 58.44 | 142.86 | 144.86 | 83.30 | 0.00 | 0.00 | 744.00 |
June | 195.60 | 41.42 | 154.18 | 159.74 | 56.60 | 0.00 | 0.00 | 720.00 |
July | 199.68 | 48.42 | 151.26 | 180.26 | 42.12 | 0.00 | 0.00 | 744.00 |
August | 224.18 | 72.66 | 151.52 | 208.91 | 55.61 | 0.00 | 0.00 | 744.00 |
September | 260.73 | 127.02 | 133.72 | 256.54 | 82.70 | 0.00 | 0.00 | 720.00 |
October | 249.54 | 142.58 | 106.96 | 235.08 | 125.56 | 0.00 | 0.00 | 744.00 |
November | 178.65 | 100.86 | 77.80 | 153.97 | 155.77 | 0.00 | 0.00 | 720.00 |
December | 166.66 | 86.23 | 80.43 | 117.09 | 223.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 217.54 | 95.94 | 121.60 | 179.97 | 129.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 166.66 | 41.42 | 77.80 | 117.09 | 42.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 277.94 | 156.22 | 154.18 | 256.54 | 227.64 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 95207096.91 | 28205060.33 | 67002036.59 | 35104947.56 | 0.252767E+09 |
February | 0.136583E+09 | 39950506.82 | 96632914.22 | 80579574.66 | 0.215925E+09 |
March | 0.233245E+09 | 0.119680E+09 | 0.113565E+09 | 0.207655E+09 | 0.178942E+09 |
April | 0.302426E+09 | 0.161689E+09 | 0.140737E+09 | 0.308713E+09 | 0.131372E+09 |
May | 0.397691E+09 | 0.245027E+09 | 0.152663E+09 | 0.445639E+09 | 0.101653E+09 |
June | 0.445739E+09 | 0.279626E+09 | 0.166112E+09 | 0.535535E+09 | 70395439.86 |
July | 0.426933E+09 | 0.259262E+09 | 0.167671E+09 | 0.534132E+09 | 54191736.58 |
August | 0.362338E+09 | 0.200761E+09 | 0.161577E+09 | 0.445414E+09 | 66802957.03 |
September | 0.262706E+09 | 0.143484E+09 | 0.119222E+09 | 0.297671E+09 | 97705438.10 |
October | 0.168690E+09 | 73123716.24 | 95566567.98 | 0.153684E+09 | 0.145844E+09 |
November | 94262721.42 | 29367220.64 | 64895500.78 | 60885823.13 | 0.168543E+09 |
December | 84052666.02 | 18068445.23 | 65984220.79 | 27997450.26 | 0.244350E+09 |
Annual Sum or Average | 0.300987E+10 | 0.159824E+10 | 0.141163E+10 | 0.313301E+10 | 0.172849E+10 |
Minimum of Months | 84052666.02 | 18068445.23 | 64895500.78 | 27997450.26 | 54191736.58 |
Maximum of Months | 0.445739E+09 | 0.279626E+09 | 0.167671E+09 | 0.535535E+09 | 0.252767E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259455E+10 | 0.151431E+10 | 0.108023E+10 | 0.199078E+10 | 0.297066E+10 |
February | 0.267678E+10 | 0.129105E+10 | 0.138573E+10 | 0.191566E+10 | 0.261106E+10 |
March | 0.361785E+10 | 0.203349E+10 | 0.158436E+10 | 0.301159E+10 | 0.220873E+10 |
April | 0.289806E+10 | 0.115791E+10 | 0.174015E+10 | 0.211660E+10 | 0.167402E+10 |
May | 0.262040E+10 | 0.760766E+09 | 0.185963E+10 | 0.183852E+10 | 0.120805E+10 |
June | 0.246398E+10 | 0.521758E+09 | 0.194223E+10 | 0.202541E+10 | 0.778742E+09 |
July | 0.259924E+10 | 0.630330E+09 | 0.196891E+10 | 0.245286E+10 | 0.568870E+09 |
August | 0.291809E+10 | 0.945798E+09 | 0.197229E+10 | 0.281389E+10 | 0.748878E+09 |
September | 0.328442E+10 | 0.160000E+10 | 0.168442E+10 | 0.323627E+10 | 0.113399E+10 |
October | 0.324818E+10 | 0.185593E+10 | 0.139225E+10 | 0.305962E+10 | 0.176954E+10 |
November | 0.225045E+10 | 0.127047E+10 | 0.979982E+09 | 0.195776E+10 | 0.206978E+10 |
December | 0.216935E+10 | 0.112245E+10 | 0.104691E+10 | 0.157219E+10 | 0.291527E+10 |
Annual Sum or Average | 0.333413E+11 | 0.147043E+11 | 0.186371E+11 | 0.279911E+11 | 0.206576E+11 |
Minimum of Months | 0.216935E+10 | 0.521758E+09 | 0.979982E+09 | 0.157219E+10 | 0.568870E+09 |
Maximum of Months | 0.361785E+10 | 0.203349E+10 | 0.197229E+10 | 0.323627E+10 | 0.297066E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259455E+10 | 0.151431E+10 | 0.108023E+10 | 0.198856E+10 | 0.293940E+10 |
February | 0.267678E+10 | 0.129105E+10 | 0.138573E+10 | 0.191428E+10 | 0.258430E+10 |
March | 0.361785E+10 | 0.203349E+10 | 0.158436E+10 | 0.303255E+10 | 0.213571E+10 |
April | 0.289806E+10 | 0.115791E+10 | 0.174015E+10 | 0.214739E+10 | 0.158553E+10 |
May | 0.262040E+10 | 0.760766E+09 | 0.185963E+10 | 0.185431E+10 | 0.114519E+10 |
June | 0.246398E+10 | 0.521758E+09 | 0.194223E+10 | 0.202233E+10 | 0.741340E+09 |
July | 0.259924E+10 | 0.630330E+09 | 0.196891E+10 | 0.244321E+10 | 0.536393E+09 |
August | 0.291809E+10 | 0.945798E+09 | 0.197229E+10 | 0.280302E+10 | 0.715229E+09 |
September | 0.328442E+10 | 0.160000E+10 | 0.168442E+10 | 0.323120E+10 | 0.109439E+10 |
October | 0.324818E+10 | 0.185593E+10 | 0.139225E+10 | 0.307966E+10 | 0.168492E+10 |
November | 0.225045E+10 | 0.127047E+10 | 0.979982E+09 | 0.197812E+10 | 0.197300E+10 |
December | 0.216935E+10 | 0.112245E+10 | 0.104691E+10 | 0.157313E+10 | 0.287830E+10 |
Annual Sum or Average | 0.333413E+11 | 0.147043E+11 | 0.186371E+11 | 0.280678E+11 | 0.200137E+11 |
Minimum of Months | 0.216935E+10 | 0.521758E+09 | 0.979982E+09 | 0.157313E+10 | 0.536393E+09 |
Maximum of Months | 0.361785E+10 | 0.203349E+10 | 0.197229E+10 | 0.323120E+10 | 0.293940E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.533866E+09 | 0.311592E+09 | 0.222274E+09 | 0.397015E+09 | 0.609714E+09 |
February | 0.550786E+09 | 0.265651E+09 | 0.285134E+09 | 0.380966E+09 | 0.537140E+09 |
March | 0.744424E+09 | 0.418419E+09 | 0.326005E+09 | 0.609754E+09 | 0.439795E+09 |
April | 0.596317E+09 | 0.238257E+09 | 0.358060E+09 | 0.436127E+09 | 0.322062E+09 |
May | 0.539185E+09 | 0.156539E+09 | 0.382647E+09 | 0.387993E+09 | 0.223112E+09 |
June | 0.507001E+09 | 0.107359E+09 | 0.399641E+09 | 0.414050E+09 | 0.146699E+09 |
July | 0.534831E+09 | 0.129700E+09 | 0.405131E+09 | 0.482805E+09 | 0.112822E+09 |
August | 0.600439E+09 | 0.194612E+09 | 0.405827E+09 | 0.559546E+09 | 0.148948E+09 |
September | 0.675818E+09 | 0.329223E+09 | 0.346595E+09 | 0.664952E+09 | 0.214355E+09 |
October | 0.668360E+09 | 0.381884E+09 | 0.286476E+09 | 0.629625E+09 | 0.336294E+09 |
November | 0.463063E+09 | 0.261418E+09 | 0.201645E+09 | 0.399089E+09 | 0.403749E+09 |
December | 0.446376E+09 | 0.230960E+09 | 0.215416E+09 | 0.313622E+09 | 0.597520E+09 |
Annual Sum or Average | 0.686047E+10 | 0.302561E+10 | 0.383485E+10 | 0.567554E+10 | 0.409221E+10 |
Minimum of Months | 0.446376E+09 | 0.107359E+09 | 0.201645E+09 | 0.313622E+09 | 0.112822E+09 |
Maximum of Months | 0.744424E+09 | 0.418419E+09 | 0.405827E+09 | 0.664952E+09 | 0.609714E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 209.71 | 1509.96 | 568.74 | 168.49 | 400.25 | 0.00 | 0.00 |
February | 532.93 | 1428.08 | 903.33 | 264.22 | 639.11 | 0.00 | 0.00 |
March | 1240.47 | 1068.95 | 1393.34 | 714.93 | 678.41 | 0.00 | 0.00 |
April | 1905.63 | 810.94 | 1866.83 | 998.08 | 868.75 | 0.00 | 0.00 |
May | 2662.12 | 607.25 | 2375.69 | 1463.72 | 911.97 | 0.00 | 0.00 |
June | 3305.77 | 434.54 | 2751.47 | 1726.09 | 1025.38 | 0.00 | 0.00 |
July | 3190.76 | 323.73 | 2550.38 | 1548.76 | 1001.62 | 0.00 | 0.00 |
August | 2660.77 | 399.06 | 2164.50 | 1199.29 | 965.22 | 0.00 | 0.00 |
September | 1837.48 | 603.12 | 1621.64 | 885.70 | 735.94 | 0.00 | 0.00 |
October | 918.07 | 871.23 | 1007.71 | 436.82 | 570.89 | 0.00 | 0.00 |
November | 375.84 | 1040.39 | 581.87 | 181.28 | 400.59 | 0.00 | 0.00 |
December | 167.25 | 1459.68 | 502.11 | 107.94 | 394.17 | 0.00 | 0.00 |
Annual Sum or Average | 1589.55 | 876.96 | 1527.08 | 810.88 | 716.20 | 0.00 | 0.00 |
Minimum of Months | 167.25 | 323.73 | 502.11 | 107.94 | 394.17 | 0.00 | 0.00 |
Maximum of Months | 3305.77 | 1509.96 | 2751.47 | 1726.09 | 1025.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 743.27 | 1109.12 | 968.69 | 565.38 | 403.31 | 0.00 | 0.00 |
February | 791.86 | 1079.31 | 1106.47 | 533.67 | 572.81 | 0.00 | 0.00 |
March | 1124.40 | 824.65 | 1350.75 | 759.22 | 591.53 | 0.00 | 0.00 |
April | 816.59 | 645.84 | 1118.08 | 446.73 | 671.35 | 0.00 | 0.00 |
May | 686.42 | 451.03 | 978.35 | 284.04 | 694.31 | 0.00 | 0.00 |
June | 781.41 | 300.44 | 950.61 | 201.30 | 749.32 | 0.00 | 0.00 |
July | 915.79 | 212.39 | 970.44 | 235.34 | 735.11 | 0.00 | 0.00 |
August | 1050.59 | 279.60 | 1089.49 | 353.12 | 736.37 | 0.00 | 0.00 |
September | 1248.56 | 437.49 | 1267.14 | 617.28 | 649.85 | 0.00 | 0.00 |
October | 1142.33 | 660.67 | 1212.73 | 692.92 | 519.81 | 0.00 | 0.00 |
November | 755.31 | 798.53 | 868.23 | 490.15 | 378.08 | 0.00 | 0.00 |
December | 586.99 | 1088.44 | 809.94 | 419.07 | 390.87 | 0.00 | 0.00 |
Annual Sum or Average | 887.59 | 655.05 | 1057.25 | 466.27 | 590.98 | 0.00 | 0.00 |
Minimum of Months | 586.99 | 212.39 | 809.94 | 201.30 | 378.08 | 0.00 | 0.00 |
Maximum of Months | 1248.56 | 1109.12 | 1350.75 | 759.22 | 749.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 742.44 | 1097.45 | 968.69 | 565.38 | 403.31 | 0.00 | 0.00 |
February | 791.29 | 1068.25 | 1106.47 | 533.67 | 572.81 | 0.00 | 0.00 |
March | 1132.22 | 797.38 | 1350.75 | 759.22 | 591.53 | 0.00 | 0.00 |
April | 828.47 | 611.70 | 1118.08 | 446.73 | 671.35 | 0.00 | 0.00 |
May | 692.32 | 427.56 | 978.35 | 284.04 | 694.31 | 0.00 | 0.00 |
June | 780.22 | 286.01 | 950.61 | 201.30 | 749.32 | 0.00 | 0.00 |
July | 912.19 | 200.27 | 970.44 | 235.34 | 735.11 | 0.00 | 0.00 |
August | 1046.53 | 267.04 | 1089.49 | 353.12 | 736.37 | 0.00 | 0.00 |
September | 1246.60 | 422.22 | 1267.14 | 617.28 | 649.85 | 0.00 | 0.00 |
October | 1149.81 | 629.08 | 1212.73 | 692.92 | 519.81 | 0.00 | 0.00 |
November | 763.16 | 761.19 | 868.23 | 490.15 | 378.08 | 0.00 | 0.00 |
December | 587.34 | 1074.64 | 809.94 | 419.07 | 390.87 | 0.00 | 0.00 |
Annual Sum or Average | 890.02 | 634.63 | 1057.25 | 466.27 | 590.98 | 0.00 | 0.00 |
Minimum of Months | 587.34 | 200.27 | 809.94 | 201.30 | 378.08 | 0.00 | 0.00 |
Maximum of Months | 1246.60 | 1097.45 | 1350.75 | 759.22 | 749.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.23 | 227.64 | 199.32 | 116.34 | 82.99 | 0.00 | 0.00 |
February | 157.48 | 222.03 | 227.67 | 109.81 | 117.86 | 0.00 | 0.00 |
March | 227.66 | 164.20 | 277.94 | 156.22 | 121.72 | 0.00 | 0.00 |
April | 168.26 | 124.25 | 230.06 | 91.92 | 138.14 | 0.00 | 0.00 |
May | 144.86 | 83.30 | 201.31 | 58.44 | 142.86 | 0.00 | 0.00 |
June | 159.74 | 56.60 | 195.60 | 41.42 | 154.18 | 0.00 | 0.00 |
July | 180.26 | 42.12 | 199.68 | 48.42 | 151.26 | 0.00 | 0.00 |
August | 208.91 | 55.61 | 224.18 | 72.66 | 151.52 | 0.00 | 0.00 |
September | 256.54 | 82.70 | 260.73 | 127.02 | 133.72 | 0.00 | 0.00 |
October | 235.08 | 125.56 | 249.54 | 142.58 | 106.96 | 0.00 | 0.00 |
November | 153.97 | 155.77 | 178.65 | 100.86 | 77.80 | 0.00 | 0.00 |
December | 117.09 | 223.09 | 166.66 | 86.23 | 80.43 | 0.00 | 0.00 |
Annual Sum or Average | 179.97 | 129.76 | 217.54 | 95.94 | 121.60 | 0.00 | 0.00 |
Minimum of Months | 117.09 | 42.12 | 166.66 | 41.42 | 77.80 | 0.00 | 0.00 |
Maximum of Months | 256.54 | 227.64 | 277.94 | 156.22 | 154.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.561679E+09 | 0.404427E+10 | 0.152331E+10 | 0.451281E+09 | 0.107203E+10 | 0.00 | 0.00 |
February | 0.128927E+10 | 0.345481E+10 | 0.218533E+10 | 0.639208E+09 | 0.154613E+10 | 0.00 | 0.00 |
March | 0.332248E+10 | 0.286307E+10 | 0.373192E+10 | 0.191488E+10 | 0.181705E+10 | 0.00 | 0.00 |
April | 0.493940E+10 | 0.210195E+10 | 0.483882E+10 | 0.258703E+10 | 0.225179E+10 | 0.00 | 0.00 |
May | 0.713023E+10 | 0.162645E+10 | 0.636305E+10 | 0.392043E+10 | 0.244262E+10 | 0.00 | 0.00 |
June | 0.856856E+10 | 0.112633E+10 | 0.713182E+10 | 0.447402E+10 | 0.265780E+10 | 0.00 | 0.00 |
July | 0.854612E+10 | 0.867068E+09 | 0.683093E+10 | 0.414819E+10 | 0.268274E+10 | 0.00 | 0.00 |
August | 0.712662E+10 | 0.106885E+10 | 0.579741E+10 | 0.321218E+10 | 0.258523E+10 | 0.00 | 0.00 |
September | 0.476274E+10 | 0.156329E+10 | 0.420329E+10 | 0.229574E+10 | 0.190755E+10 | 0.00 | 0.00 |
October | 0.245895E+10 | 0.233350E+10 | 0.269904E+10 | 0.116998E+10 | 0.152907E+10 | 0.00 | 0.00 |
November | 0.974173E+09 | 0.269669E+10 | 0.150820E+10 | 0.469876E+09 | 0.103833E+10 | 0.00 | 0.00 |
December | 0.447959E+09 | 0.390960E+10 | 0.134484E+10 | 0.289095E+09 | 0.105575E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.501282E+11 | 0.276559E+11 | 0.481580E+11 | 0.255719E+11 | 0.225861E+11 | 0.00 | 0.00 |
Minimum of Months | 0.447959E+09 | 0.867068E+09 | 0.134484E+10 | 0.289095E+09 | 0.103833E+10 | 0.00 | 0.00 |
Maximum of Months | 0.856856E+10 | 0.404427E+10 | 0.713182E+10 | 0.447402E+10 | 0.268274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199078E+10 | 0.297066E+10 | 0.259455E+10 | 0.151431E+10 | 0.108023E+10 | 0.00 | 0.00 |
February | 0.191566E+10 | 0.261106E+10 | 0.267678E+10 | 0.129105E+10 | 0.138573E+10 | 0.00 | 0.00 |
March | 0.301159E+10 | 0.220873E+10 | 0.361785E+10 | 0.203349E+10 | 0.158436E+10 | 0.00 | 0.00 |
April | 0.211660E+10 | 0.167402E+10 | 0.289806E+10 | 0.115791E+10 | 0.174015E+10 | 0.00 | 0.00 |
May | 0.183852E+10 | 0.120805E+10 | 0.262040E+10 | 0.760766E+09 | 0.185963E+10 | 0.00 | 0.00 |
June | 0.202541E+10 | 0.778742E+09 | 0.246398E+10 | 0.521758E+09 | 0.194223E+10 | 0.00 | 0.00 |
July | 0.245286E+10 | 0.568870E+09 | 0.259924E+10 | 0.630330E+09 | 0.196891E+10 | 0.00 | 0.00 |
August | 0.281389E+10 | 0.748878E+09 | 0.291809E+10 | 0.945798E+09 | 0.197229E+10 | 0.00 | 0.00 |
September | 0.323627E+10 | 0.113399E+10 | 0.328442E+10 | 0.160000E+10 | 0.168442E+10 | 0.00 | 0.00 |
October | 0.305962E+10 | 0.176954E+10 | 0.324818E+10 | 0.185593E+10 | 0.139225E+10 | 0.00 | 0.00 |
November | 0.195776E+10 | 0.206978E+10 | 0.225045E+10 | 0.127047E+10 | 0.979982E+09 | 0.00 | 0.00 |
December | 0.157219E+10 | 0.291527E+10 | 0.216935E+10 | 0.112245E+10 | 0.104691E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.279911E+11 | 0.206576E+11 | 0.333413E+11 | 0.147043E+11 | 0.186371E+11 | 0.00 | 0.00 |
Minimum of Months | 0.157219E+10 | 0.568870E+09 | 0.216935E+10 | 0.521758E+09 | 0.979982E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323627E+10 | 0.297066E+10 | 0.361785E+10 | 0.203349E+10 | 0.197229E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198856E+10 | 0.293940E+10 | 0.259455E+10 | 0.151431E+10 | 0.108023E+10 | 0.00 | 0.00 |
February | 0.191428E+10 | 0.258430E+10 | 0.267678E+10 | 0.129105E+10 | 0.138573E+10 | 0.00 | 0.00 |
March | 0.303255E+10 | 0.213571E+10 | 0.361785E+10 | 0.203349E+10 | 0.158436E+10 | 0.00 | 0.00 |
April | 0.214739E+10 | 0.158553E+10 | 0.289806E+10 | 0.115791E+10 | 0.174015E+10 | 0.00 | 0.00 |
May | 0.185431E+10 | 0.114519E+10 | 0.262040E+10 | 0.760766E+09 | 0.185963E+10 | 0.00 | 0.00 |
June | 0.202233E+10 | 0.741340E+09 | 0.246398E+10 | 0.521758E+09 | 0.194223E+10 | 0.00 | 0.00 |
July | 0.244321E+10 | 0.536393E+09 | 0.259924E+10 | 0.630330E+09 | 0.196891E+10 | 0.00 | 0.00 |
August | 0.280302E+10 | 0.715229E+09 | 0.291809E+10 | 0.945798E+09 | 0.197229E+10 | 0.00 | 0.00 |
September | 0.323120E+10 | 0.109439E+10 | 0.328442E+10 | 0.160000E+10 | 0.168442E+10 | 0.00 | 0.00 |
October | 0.307966E+10 | 0.168492E+10 | 0.324818E+10 | 0.185593E+10 | 0.139225E+10 | 0.00 | 0.00 |
November | 0.197812E+10 | 0.197300E+10 | 0.225045E+10 | 0.127047E+10 | 0.979982E+09 | 0.00 | 0.00 |
December | 0.157313E+10 | 0.287830E+10 | 0.216935E+10 | 0.112245E+10 | 0.104691E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.280678E+11 | 0.200137E+11 | 0.333413E+11 | 0.147043E+11 | 0.186371E+11 | 0.00 | 0.00 |
Minimum of Months | 0.157313E+10 | 0.536393E+09 | 0.216935E+10 | 0.521758E+09 | 0.979982E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323120E+10 | 0.293940E+10 | 0.361785E+10 | 0.203349E+10 | 0.197229E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.397015E+09 | 0.609714E+09 | 0.533866E+09 | 0.311592E+09 | 0.222274E+09 | 0.00 | 0.00 |
February | 0.380966E+09 | 0.537140E+09 | 0.550786E+09 | 0.265651E+09 | 0.285134E+09 | 0.00 | 0.00 |
March | 0.609754E+09 | 0.439795E+09 | 0.744424E+09 | 0.418419E+09 | 0.326005E+09 | 0.00 | 0.00 |
April | 0.436127E+09 | 0.322062E+09 | 0.596317E+09 | 0.238257E+09 | 0.358060E+09 | 0.00 | 0.00 |
May | 0.387993E+09 | 0.223112E+09 | 0.539185E+09 | 0.156539E+09 | 0.382647E+09 | 0.00 | 0.00 |
June | 0.414050E+09 | 0.146699E+09 | 0.507001E+09 | 0.107359E+09 | 0.399641E+09 | 0.00 | 0.00 |
July | 0.482805E+09 | 0.112822E+09 | 0.534831E+09 | 0.129700E+09 | 0.405131E+09 | 0.00 | 0.00 |
August | 0.559546E+09 | 0.148948E+09 | 0.600439E+09 | 0.194612E+09 | 0.405827E+09 | 0.00 | 0.00 |
September | 0.664952E+09 | 0.214355E+09 | 0.675818E+09 | 0.329223E+09 | 0.346595E+09 | 0.00 | 0.00 |
October | 0.629625E+09 | 0.336294E+09 | 0.668360E+09 | 0.381884E+09 | 0.286476E+09 | 0.00 | 0.00 |
November | 0.399089E+09 | 0.403749E+09 | 0.463063E+09 | 0.261418E+09 | 0.201645E+09 | 0.00 | 0.00 |
December | 0.313622E+09 | 0.597520E+09 | 0.446376E+09 | 0.230960E+09 | 0.215416E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.567554E+10 | 0.409221E+10 | 0.686047E+10 | 0.302561E+10 | 0.383485E+10 | 0.00 | 0.00 |
Minimum of Months | 0.313622E+09 | 0.112822E+09 | 0.446376E+09 | 0.107359E+09 | 0.201645E+09 | 0.00 | 0.00 |
Maximum of Months | 0.664952E+09 | 0.609714E+09 | 0.744424E+09 | 0.418419E+09 | 0.405827E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.3 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.73 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.65 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.46 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.38 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.38 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.41 | 11.22 | 4.10 | 7.07 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.35 | 4.97 | 4.79 | 0.12 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.71 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.35 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.3 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.38 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.13 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.16 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.04 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.42 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.82 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.22 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.71 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.23 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.51 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.12 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.84 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.40 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.16 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.71 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.2 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.3 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.4 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.82 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.76 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.17 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.74 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.41 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.22 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.95 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.40 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.96 | 4.80 | 10.49 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.96 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.288260E+10 | -.244827E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -434330372.2 | 59.00 | 0.00 | 0.00 |
February | 0.265443E+10 | -.226168E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -392751993.8 | 58.99 | 0.00 | 0.00 |
March | 0.295626E+10 | -.253114E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -425125113.4 | 59.00 | 0.00 | 0.00 |
April | 0.271257E+10 | -.231155E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -401016070.7 | 58.99 | 0.00 | 0.00 |
May | 0.265014E+10 | -.225591E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -394233701.7 | 59.00 | 0.00 | 0.00 |
June | 0.244922E+10 | -.207665E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -372566362.3 | 58.99 | 0.00 | 0.00 |
July | 0.236305E+10 | -.198183E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -381228297.5 | 58.99 | 0.00 | 0.00 |
August | 0.238813E+10 | -.200620E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -381937870.1 | 58.99 | 0.00 | 0.00 |
September | 0.231655E+10 | -.194285E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373693039.0 | 59.00 | 0.00 | 0.00 |
October | 0.247784E+10 | -.207662E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -401219469.3 | 58.99 | 0.00 | 0.00 |
November | 0.253637E+10 | -.213050E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -405870618.7 | 58.99 | 0.00 | 0.00 |
December | 0.278156E+10 | -.234895E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -432609760.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.311687E+11 | -.263721E+11 | 8760.00 | -.479658E+10 | 58.99 | |||||
Minimum of Months | 0.231655E+10 | -.253114E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -434330372.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.295626E+10 | -.194285E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -372566362.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.89 | 0.67 | 22-JAN-11:30 | 239.98 | 7.03 | 0.00 | 1.67 | 183.82 | 5.52 | 0.00 | 0.00 |
February | 262.50 | 0.80 | 0.50 | 10-FEB-12:20 | 765.03 | 8.72 | 0.00 | 51.83 | 255.84 | 7.18 | 0.00 | 2.50 |
March | 339.33 | 0.81 | 0.50 | 10-MAR-11:50 | 381.18 | 8.54 | 0.00 | 46.83 | 267.80 | 6.98 | 0.00 | 19.17 |
April | 371.17 | 0.75 | 0.50 | 01-APR-11:09 | 972.88 | 9.47 | 0.00 | 138.33 | 316.56 | 7.90 | 0.00 | 66.00 |
May | 332.17 | 0.74 | 0.50 | 01-MAY-10:39 | 2561.06 | 10.05 | 0.00 | 125.00 | 2688.92 | 8.33 | 0.00 | 83.00 |
June | 430.67 | 0.75 | 0.50 | 01-JUN-09:50 | 411.26 | 10.85 | 0.00 | 135.33 | 343.85 | 9.04 | 0.00 | 90.67 |
July | 439.00 | 0.75 | 0.50 | 01-JUL-10:20 | 498.21 | 10.69 | 0.00 | 141.83 | 466.34 | 8.95 | 0.00 | 87.83 |
August | 406.00 | 0.74 | 0.50 | 01-AUG-08:50 | 1891.16 | 10.27 | 0.00 | 155.33 | 1894.21 | 8.59 | 0.00 | 101.83 |
September | 289.17 | 0.77 | 0.50 | 01-SEP-09:50 | 374.86 | 8.82 | 0.00 | 72.50 | 311.91 | 7.25 | 0.00 | 43.17 |
October | 314.33 | 0.83 | 0.50 | 02-OCT-12:30 | 430.40 | 7.96 | 0.00 | 13.00 | 393.94 | 6.43 | 0.00 | 6.00 |
November | 258.33 | 0.86 | 0.50 | 01-NOV-11:09 | 663.70 | 6.91 | 0.00 | 29.83 | 666.72 | 5.46 | 0.00 | 28.17 |
December | 230.67 | 0.89 | 0.67 | 09-DEC-10:50 | 228.70 | 7.25 | 0.00 | 0.00 | 185.49 | 5.76 | 0.00 | 0.00 |
Annual Sum or Average | 3928.50 | 0.79 | 823.40 | 9.13 | 0.00 | 911.50 | 704.21 | 7.52 | 0.00 | 528.33 | ||
Minimum of Months | 230.67 | 0.74 | 0.50 | 228.70 | 6.91 | 0.00 | 0.00 | 183.82 | 5.46 | 0.00 | 0.00 | |
Maximum of Months | 439.00 | 0.89 | 0.67 | 2561.06 | 10.85 | 0.00 | 155.33 | 2688.92 | 9.04 | 0.00 | 101.83 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147480E+11 | 50360.95 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143518E+11 | 50360.95 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.738696E+10 | 50360.95 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173228E+10 | 50360.95 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11008011.54 | 3910.06 | 01-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.233509E+09 | 36587.64 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215712E+10 | 50360.95 | 12-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125283E+11 | 50360.95 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.531490E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147480E+11 | 50360.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542689E+11 | 253022.17 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.515800E+11 | 253022.17 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233897E+11 | 253022.17 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435294E+10 | 184961.80 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4568592.86 | 5299.36 | 01-MAY-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.848277E+09 | 46873.48 | 17-OCT-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.799334E+10 | 205092.71 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.472004E+11 | 253022.17 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189638E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542689E+11 | 253022.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.565770E+10 | 32630.82 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.560380E+10 | 32630.82 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.192373E+10 | 32630.82 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.514692E+09 | 32630.82 | 05-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4225153.13 | 2552.13 | 01-MAY-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73982493.38 | 10113.78 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.576719E+09 | 32630.82 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.496110E+10 | 32630.82 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193159E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565770E+10 | 32630.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.891297E+10 | 26726.69 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.854351E+10 | 26726.69 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401508E+10 | 26726.69 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153598E+10 | 26726.69 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68666626.76 | 8689.99 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1841167.90 | 778.52 | 30-SEP-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.373004E+09 | 26726.69 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203181E+10 | 26726.69 | 12-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813127E+10 | 26726.69 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336141E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.891297E+10 | 26726.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.178832E+11 | 39481.57 | 31-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167533E+11 | 42912.37 | 06-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114412E+11 | 34379.61 | 06-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.584560E+10 | 26713.06 | 16-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168434E+10 | 10948.55 | 11-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.263952E+09 | 9472.06 | 13-JUN-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 57021617.35 | 4099.76 | 31-AUG-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394741E+09 | 8813.76 | 28-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.469064E+10 | 16881.97 | 08-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.819923E+10 | 22062.90 | 23-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170408E+11 | 40537.68 | 10-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.842540E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178832E+11 | 42912.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.272420E+09 | 0.222848E+09 | 7982.05 | 15-MAR-14:20 | 6880.38 | 0.00 |
April | 0.00 | 0.00 | 1411191.89 | 1276264.64 | 494.85 | 08-APR-13:00 | 453.95 | 0.00 |
May | 0.00 | 0.00 | 0.948651E+09 | 0.849723E+09 | 15948.10 | 24-MAY-06:02 | 10669.10 | 0.00 |
June | 0.00 | 0.00 | 0.830331E+10 | 0.621529E+10 | 37831.76 | 18-JUN-08:62 | 19257.86 | 0.00 |
July | 0.00 | 0.00 | 0.177174E+11 | 0.122800E+11 | 38767.38 | 21-JUL-05:03 | 17896.90 | 0.00 |
August | 0.00 | 0.00 | 0.137874E+11 | 0.105199E+11 | 37942.24 | 14-AUG-06:02 | 16890.79 | 0.00 |
September | 0.00 | 0.00 | 0.485613E+10 | 0.342593E+10 | 36745.15 | 16-SEP-06:02 | 19434.64 | 0.00 |
October | 0.00 | 0.00 | 95434827.63 | 85916242.23 | 4889.71 | 11-OCT-15:00 | 4375.50 | 0.00 |
November | 0.00 | 0.00 | 3370.69 | 2583.90 | 0.45 | 04-NOV-16:00 | 0.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.459821E+11 | 0.336008E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.177174E+11 | 0.122800E+11 | 38767.38 | 19434.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.245086E+10 | 0.199296E+10 | 155793.12 | 16-MAR-06:03 | 107928.67 | 0.00 |
April | 0.00 | 0.00 | 0.250856E+09 | 0.220889E+09 | 20370.20 | 08-APR-13:30 | 17825.82 | 0.00 |
May | 0.00 | 0.00 | 0.102029E+11 | 0.896165E+10 | 168525.83 | 29-MAY-08:62 | 115295.31 | 0.00 |
June | 0.00 | 0.00 | 0.539970E+11 | 0.399893E+11 | 184338.84 | 18-JUN-08:62 | 94390.35 | 0.00 |
July | 0.00 | 0.00 | 0.988088E+11 | 0.674929E+11 | 186656.41 | 21-JUL-05:03 | 95301.62 | 0.00 |
August | 0.00 | 0.00 | 0.766028E+11 | 0.575523E+11 | 184658.83 | 14-AUG-06:02 | 84689.80 | 0.00 |
September | 0.00 | 0.00 | 0.316602E+11 | 0.224058E+11 | 178750.13 | 16-SEP-06:02 | 96395.71 | 0.00 |
October | 0.00 | 0.00 | 0.186304E+10 | 0.155434E+10 | 164608.47 | 01-OCT-08:62 | 100514.96 | 0.00 |
November | 0.00 | 0.00 | 3115393.29 | 2661327.73 | 6759.53 | 05-NOV-08:63 | 5082.12 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.275840E+12 | 0.200173E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.988088E+11 | 0.674929E+11 | 186656.41 | 115295.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.479338E+09 | 0.406759E+09 | 10205.53 | 16-MAR-06:03 | 7098.79 | 0.00 |
April | 0.00 | 0.00 | 75531644.59 | 69565385.34 | 4399.44 | 08-APR-13:30 | 3970.37 | 0.00 |
May | 0.00 | 0.00 | 0.128169E+10 | 0.115691E+10 | 21292.85 | 24-MAY-06:02 | 14355.41 | 0.00 |
June | 0.00 | 0.00 | 0.717843E+10 | 0.548994E+10 | 23587.79 | 18-JUN-08:62 | 11853.03 | 0.00 |
July | 0.00 | 0.00 | 0.136679E+11 | 0.973320E+10 | 24191.52 | 21-JUL-05:03 | 11328.54 | 0.00 |
August | 0.00 | 0.00 | 0.115736E+11 | 0.903712E+10 | 23643.96 | 14-AUG-06:02 | 10443.75 | 0.00 |
September | 0.00 | 0.00 | 0.590115E+10 | 0.440652E+10 | 22846.63 | 16-SEP-06:02 | 12182.13 | 0.00 |
October | 0.00 | 0.00 | 0.764854E+09 | 0.649155E+09 | 21097.56 | 01-OCT-08:62 | 12308.39 | 0.00 |
November | 0.00 | 0.00 | 7769113.00 | 6413402.81 | 1334.10 | 16-NOV-12:40 | 1157.95 | 0.00 |
December | 0.00 | 0.00 | 237.26 | 185.46 | 0.23 | 01-DEC-13:20 | 0.18 | 0.00 |
Annual Sum or Average | 0.409302E+11 | 0.309556E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.136679E+11 | 0.973320E+10 | 24191.52 | 14355.41 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.273167E+09 | 0.227264E+09 | 7081.26 | 15-MAR-13:40 | 6358.30 | 0.00 |
April | 0.00 | 0.00 | 21594111.05 | 19117459.57 | 2336.04 | 08-APR-13:30 | 2054.57 | 0.00 |
May | 0.00 | 0.00 | 0.653023E+09 | 0.582166E+09 | 13970.31 | 24-MAY-06:02 | 9174.48 | 0.00 |
June | 0.00 | 0.00 | 0.478698E+10 | 0.353941E+10 | 19016.54 | 18-JUN-08:62 | 9445.85 | 0.00 |
July | 0.00 | 0.00 | 0.997461E+10 | 0.686889E+10 | 19495.14 | 21-JUL-05:03 | 8848.94 | 0.00 |
August | 0.00 | 0.00 | 0.838006E+10 | 0.640480E+10 | 19073.81 | 14-AUG-06:02 | 8325.39 | 0.00 |
September | 0.00 | 0.00 | 0.397637E+10 | 0.291423E+10 | 18439.83 | 16-SEP-06:02 | 9649.60 | 0.00 |
October | 0.00 | 0.00 | 0.420188E+09 | 0.353207E+09 | 14167.88 | 12-OCT-06:02 | 10046.55 | 0.00 |
November | 0.00 | 0.00 | 8864.23 | 7379.94 | 3.34 | 01-NOV-16:10 | 3.15 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.284860E+11 | 0.209091E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.997461E+10 | 0.686889E+10 | 19495.14 | 10046.55 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.447413E+10 | 0.55 | 2732.13 | 01-JAN-00:27 | 0.90 |
February | 0.415247E+10 | 0.57 | 2732.13 | 01-FEB-05:03 | 0.90 |
March | 0.384267E+10 | 0.47 | 2732.13 | 01-MAR-05:02 | 0.90 |
April | 0.356904E+10 | 0.45 | 2732.13 | 01-APR-05:02 | 0.90 |
May | 0.248121E+10 | 0.30 | 2732.13 | 01-MAY-05:03 | 0.90 |
June | 0.947364E+09 | 0.12 | 2732.13 | 01-JUN-07:06 | 0.89 |
July | 38228959.02 | 0.00 | 2732.13 | 02-JUL-11:10 | 0.89 |
August | 0.256273E+09 | 0.03 | 2732.13 | 01-AUG-07:06 | 0.89 |
September | 0.136614E+10 | 0.17 | 2732.13 | 01-SEP-07:10 | 0.89 |
October | 0.316146E+10 | 0.39 | 2732.13 | 01-OCT-07:06 | 0.89 |
November | 0.361756E+10 | 0.46 | 2732.13 | 01-NOV-07:10 | 0.90 |
December | 0.437841E+10 | 0.54 | 2732.13 | 01-DEC-06:02 | 0.90 |
Annual Sum or Average | 0.322850E+11 | 0.34 | |||
Minimum of Months | 38228959.02 | 0.00 | 2732.13 | 0.89 | |
Maximum of Months | 0.447413E+10 | 0.57 | 2732.13 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.313298E+10 | 0.56 | 1939.34 | 01-JAN-15:00 | 0.90 |
February | 0.285839E+10 | 0.58 | 1939.34 | 22-FEB-16:20 | 0.90 |
March | 0.317245E+10 | 0.56 | 1939.34 | 02-MAR-12:40 | 0.90 |
April | 0.303746E+10 | 0.54 | 1939.34 | 01-APR-19:23 | 0.90 |
May | 0.313475E+10 | 0.54 | 1939.34 | 04-MAY-15:30 | 0.90 |
June | 0.305795E+10 | 0.54 | 1939.34 | 01-JUN-10:00 | 0.89 |
July | 0.311381E+10 | 0.53 | 1939.34 | 18-JUL-07:08 | 0.89 |
August | 0.316268E+10 | 0.54 | 1939.34 | 23-AUG-18:00 | 0.89 |
September | 0.303701E+10 | 0.54 | 1939.34 | 01-SEP-11:05 | 0.89 |
October | 0.310683E+10 | 0.54 | 1939.34 | 01-OCT-15:30 | 0.89 |
November | 0.299512E+10 | 0.54 | 1939.34 | 25-NOV-20:17 | 0.90 |
December | 0.313420E+10 | 0.56 | 1939.34 | 02-DEC-06:27 | 0.90 |
Annual Sum or Average | 0.369436E+11 | 0.55 | |||
Minimum of Months | 0.285839E+10 | 0.53 | 1939.34 | 0.89 | |
Maximum of Months | 0.317245E+10 | 0.58 | 1939.34 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.228702E+11 | 0.93 | 14276.03 | 27-JAN-13:30 | 1.55 |
February | 0.207677E+11 | 0.93 | 14276.03 | 01-FEB-09:20 | 1.54 |
March | 0.232813E+11 | 0.94 | 14276.03 | 01-MAR-07:17 | 1.55 |
April | 0.223563E+11 | 0.93 | 14276.03 | 01-APR-08:70 | 1.54 |
May | 0.230758E+11 | 0.93 | 14276.03 | 01-MAY-17:20 | 1.55 |
June | 0.225104E+11 | 0.93 | 14276.03 | 01-JUN-06:04 | 1.53 |
July | 0.229216E+11 | 0.91 | 14276.03 | 01-JUL-11:00 | 1.53 |
August | 0.232813E+11 | 0.93 | 14276.03 | 01-AUG-05:20 | 1.53 |
September | 0.223563E+11 | 0.93 | 14276.03 | 01-SEP-06:50 | 1.53 |
October | 0.228702E+11 | 0.92 | 14276.03 | 01-OCT-10:33 | 1.53 |
November | 0.220479E+11 | 0.92 | 14276.03 | 01-NOV-15:00 | 1.54 |
December | 0.229216E+11 | 0.93 | 14276.03 | 01-DEC-07:27 | 1.54 |
Annual Sum or Average | 0.271261E+12 | 0.93 | |||
Minimum of Months | 0.207677E+11 | 0.91 | 14276.03 | 1.53 | |
Maximum of Months | 0.232813E+11 | 0.94 | 14276.03 | 1.55 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196827E+10 | 0.58 | 1222.91 | 01-JAN-08:10 | 0.93 |
February | 0.179191E+10 | 0.60 | 1222.91 | 01-FEB-06:17 | 0.93 |
March | 0.199555E+10 | 0.57 | 1222.91 | 01-MAR-07:45 | 0.94 |
April | 0.191523E+10 | 0.56 | 1222.91 | 01-APR-07:50 | 0.93 |
May | 0.197671E+10 | 0.56 | 1222.91 | 01-MAY-06:25 | 0.93 |
June | 0.192829E+10 | 0.56 | 1222.91 | 01-JUN-18:50 | 0.92 |
July | 0.196350E+10 | 0.55 | 1222.91 | 01-JUL-08:20 | 0.92 |
August | 0.199432E+10 | 0.56 | 1222.91 | 02-AUG-10:30 | 0.92 |
September | 0.191508E+10 | 0.56 | 1222.91 | 01-SEP-14:30 | 0.93 |
October | 0.195910E+10 | 0.56 | 1222.91 | 01-OCT-15:00 | 0.92 |
November | 0.188866E+10 | 0.55 | 1222.91 | 01-NOV-11:20 | 0.93 |
December | 0.197072E+10 | 0.58 | 1222.91 | 01-DEC-07:47 | 0.93 |
Annual Sum or Average | 0.232673E+11 | 0.57 | |||
Minimum of Months | 0.179191E+10 | 0.55 | 1222.91 | 0.92 | |
Maximum of Months | 0.199555E+10 | 0.60 | 1222.91 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151115E+10 | 0.59 | 934.73 | 02-JAN-06:43 | 0.93 |
February | 0.137895E+10 | 0.61 | 934.73 | 02-FEB-06:17 | 0.93 |
March | 0.152758E+10 | 0.58 | 934.73 | 01-MAR-06:10 | 0.93 |
April | 0.146432E+10 | 0.56 | 934.73 | 01-APR-20:00 | 0.93 |
May | 0.151090E+10 | 0.56 | 934.73 | 01-MAY-06:25 | 0.93 |
June | 0.147388E+10 | 0.56 | 934.73 | 03-JUN-12:10 | 0.93 |
July | 0.150080E+10 | 0.55 | 934.73 | 06-JUL-08:15 | 0.93 |
August | 0.152436E+10 | 0.56 | 934.73 | 01-AUG-19:30 | 0.93 |
September | 0.146379E+10 | 0.56 | 934.73 | 06-SEP-18:50 | 0.92 |
October | 0.149744E+10 | 0.55 | 934.73 | 05-OCT-15:40 | 0.93 |
November | 0.144379E+10 | 0.55 | 934.73 | 04-NOV-13:50 | 0.92 |
December | 0.151176E+10 | 0.58 | 934.73 | 01-DEC-09:35 | 0.93 |
Annual Sum or Average | 0.178087E+11 | 0.57 | |||
Minimum of Months | 0.137895E+10 | 0.55 | 934.73 | 0.92 | |
Maximum of Months | 0.152758E+10 | 0.61 | 934.73 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.67 | 0.00 |
February | 1.96 | 0.00 |
March | 0.57 | 0.00 |
April | 0.08 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.17 | 0.00 |
December | 1.59 | 0.00 |
Annual Sum or Average | 6.04 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.96 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.32 | 25.84 |
April | 1.74 | 25.84 |
May | 0.62 | 25.84 |
June | 0.67 | 25.84 |
July | 0.33 | 25.84 |
August | 0.54 | 23.86 |
September | 0.21 | 25.84 |
October | 1.61 | 25.84 |
November | 0.61 | 25.84 |
December | 0.06 | 25.84 |
Annual Sum or Average | 6.71 | 25.68 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.74 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.09 | 0.00 |
February | 1.24 | 0.00 |
March | 0.15 | 0.00 |
April | 0.57 | 2.44 |
May | 0.38 | 2.44 |
June | 0.60 | 0.17 |
July | 0.72 | 0.00 |
August | 1.18 | 0.00 |
September | 0.18 | 0.56 |
October | 1.01 | 2.10 |
November | 0.17 | 2.44 |
December | 0.81 | 0.00 |
Annual Sum or Average | 8.10 | 0.62 |
Minimum of Months | 0.15 | 0.00 |
Maximum of Months | 1.24 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.79 | 0.00 |
February | 1.95 | 0.00 |
March | 0.24 | 0.00 |
April | 0.12 | 0.81 |
May | 0.24 | 2.44 |
June | 0.33 | 2.44 |
July | 0.00 | 0.00 |
August | 0.79 | 2.05 |
September | 0.12 | 2.44 |
October | 0.46 | 2.44 |
November | 0.46 | 0.44 |
December | 1.76 | 0.00 |
Annual Sum or Average | 8.26 | 0.57 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.95 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 59.05 | 0.00 |
February | 61.03 | 0.00 |
March | 31.69 | 0.00 |
April | 27.56 | 0.00 |
May | 43.47 | 0.00 |
June | 20.79 | 0.00 |
July | 3.74 | 0.00 |
August | 13.61 | 0.00 |
September | 30.32 | 0.00 |
October | 23.06 | 0.00 |
November | 23.03 | 0.00 |
December | 55.91 | 0.00 |
Annual Sum or Average | 393.26 | 0.00 |
Minimum of Months | 3.74 | 0.00 |
Maximum of Months | 61.03 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.313298E+10 | 0.184351E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.285839E+10 | 0.179398E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.324928E+10 | 0.923370E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.303786E+10 | 0.216536E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.339538E+10 | 13760014.43 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.525818E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.772936E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.681352E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.430739E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.313338E+10 | 0.291886E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.299512E+10 | 0.269640E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.313420E+10 | 0.156603E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.490450E+11 | 0.664363E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.285839E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.772936E+10 | 0.184351E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.228702E+11 | 0.678362E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.207677E+11 | 0.644750E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.240316E+11 | 0.292372E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.224336E+11 | 0.544117E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.261087E+11 | 5710741.08 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.382354E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.512758E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.457097E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.315322E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.234284E+11 | 0.106035E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.220489E+11 | 0.999167E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.229216E+11 | 0.590005E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.351364E+12 | 0.237048E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.207677E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.512758E+11 | 0.678362E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.196827E+10 | 0.707212E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.179191E+10 | 0.700476E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.212288E+10 | 0.240466E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.193568E+10 | 0.643365E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.231786E+10 | 5281441.42 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.379066E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.544898E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.497568E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.340880E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.215940E+10 | 92478116.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.189084E+10 | 0.720899E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.197072E+10 | 0.620137E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.337817E+11 | 0.241449E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.179191E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.544898E+10 | 0.707212E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.151115E+10 | 0.111412E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.137895E+10 | 0.106794E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159958E+10 | 0.501885E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147007E+10 | 0.191997E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.168253E+10 | 85833283.45 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.269056E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.398957E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.363691E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.244921E+10 | 2301459.88 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.160500E+10 | 0.466255E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144379E+10 | 0.253976E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.151176E+10 | 0.101641E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.249691E+11 | 0.420177E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.137895E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.398957E+10 | 0.111412E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.313298E+10 | 0.00 | 0.147480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285839E+10 | 0.00 | 0.143518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317245E+10 | 0.272420E+09 | 0.738696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303746E+10 | 1411191.89 | 0.173228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.313475E+10 | 0.948651E+09 | 11008011.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.305795E+10 | 0.830331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311381E+10 | 0.177174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.316268E+10 | 0.137874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303701E+10 | 0.485613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.310683E+10 | 95434827.63 | 0.233509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.299512E+10 | 3370.69 | 0.215712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313420E+10 | 0.00 | 0.125283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369436E+11 | 0.459821E+11 | 0.531490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.317245E+10 | 0.177174E+11 | 0.147480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.228702E+11 | 0.00 | 0.542689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207677E+11 | 0.00 | 0.515800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232813E+11 | 0.245086E+10 | 0.233897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223563E+11 | 0.250856E+09 | 0.435294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230758E+11 | 0.102029E+11 | 4568592.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.225104E+11 | 0.539970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.229216E+11 | 0.988088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.232813E+11 | 0.766028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223563E+11 | 0.316602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228702E+11 | 0.186304E+10 | 0.848277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220479E+11 | 3115393.29 | 0.799334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229216E+11 | 0.00 | 0.472004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271261E+12 | 0.275840E+12 | 0.189638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.207677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.232813E+11 | 0.988088E+11 | 0.542689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.196827E+10 | 0.00 | 0.565770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179191E+10 | 0.00 | 0.560380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199555E+10 | 0.479338E+09 | 0.192373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191523E+10 | 75531644.59 | 0.514692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197671E+10 | 0.128169E+10 | 4225153.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192829E+10 | 0.717843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196350E+10 | 0.136679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199432E+10 | 0.115736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191508E+10 | 0.590115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195910E+10 | 0.764854E+09 | 73982493.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188866E+10 | 7769113.00 | 0.576719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197072E+10 | 237.26 | 0.496110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232673E+11 | 0.409302E+11 | 0.193159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199555E+10 | 0.136679E+11 | 0.565770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151115E+10 | 0.00 | 0.891297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137895E+10 | 0.00 | 0.854351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152758E+10 | 0.273167E+09 | 0.401508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146432E+10 | 21594111.05 | 0.153598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151090E+10 | 0.653023E+09 | 68666626.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147388E+10 | 0.478698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150080E+10 | 0.997461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152436E+10 | 0.838006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146379E+10 | 0.397637E+10 | 1841167.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149744E+10 | 0.420188E+09 | 0.373004E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144379E+10 | 8864.23 | 0.203181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151176E+10 | 0.00 | 0.813127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178087E+11 | 0.284860E+11 | 0.336141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152758E+10 | 0.997461E+10 | 0.891297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.313298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317245E+10 | 0.00 | 0.00 | 0.00 | 76827515.74 | 0.00 | 0.923370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303746E+10 | 0.00 | 0.00 | 0.00 | 398941.23 | 0.00 | 0.216536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.313475E+10 | 0.00 | 0.00 | 0.00 | 0.260625E+09 | 0.00 | 13760014.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.305795E+10 | 0.00 | 0.00 | 0.00 | 0.220022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311381E+10 | 0.00 | 0.00 | 0.00 | 0.461555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.316268E+10 | 0.00 | 0.00 | 0.00 | 0.365084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303701E+10 | 0.00 | 0.00 | 0.00 | 0.127038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.310683E+10 | 0.00 | 0.00 | 0.00 | 26556383.31 | 0.00 | 0.291886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.299512E+10 | 0.00 | 0.00 | 0.00 | 955.77 | 0.00 | 0.269640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369436E+11 | 0.00 | 0.00 | 0.00 | 0.121014E+11 | 0.00 | 0.664363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.285839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.317245E+10 | 0.00 | 0.00 | 0.00 | 0.461555E+10 | 0.00 | 0.184351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.228702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232813E+11 | 0.00 | 0.00 | 0.00 | 0.750274E+09 | 0.00 | 0.292372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223563E+11 | 0.00 | 0.00 | 0.00 | 77306934.67 | 0.00 | 0.544117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230758E+11 | 0.00 | 0.00 | 0.00 | 0.303293E+10 | 0.00 | 5710741.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.225104E+11 | 0.00 | 0.00 | 0.00 | 0.157249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.229216E+11 | 0.00 | 0.00 | 0.00 | 0.283543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.232813E+11 | 0.00 | 0.00 | 0.00 | 0.224283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223563E+11 | 0.00 | 0.00 | 0.00 | 0.917590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228702E+11 | 0.00 | 0.00 | 0.00 | 0.558242E+09 | 0.00 | 0.106035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220479E+11 | 0.00 | 0.00 | 0.00 | 979005.76 | 0.00 | 0.999167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271261E+12 | 0.00 | 0.00 | 0.00 | 0.801031E+11 | 0.00 | 0.237048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.207677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.232813E+11 | 0.00 | 0.00 | 0.00 | 0.283543E+11 | 0.00 | 0.678362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.196827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.199555E+10 | 0.00 | 0.00 | 0.00 | 0.127332E+09 | 0.00 | 0.240466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191523E+10 | 0.00 | 0.00 | 0.00 | 20446376.11 | 0.00 | 0.643365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197671E+10 | 0.00 | 0.00 | 0.00 | 0.341147E+09 | 0.00 | 5281441.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192829E+10 | 0.00 | 0.00 | 0.00 | 0.186238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196350E+10 | 0.00 | 0.00 | 0.00 | 0.348548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199432E+10 | 0.00 | 0.00 | 0.00 | 0.298135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191508E+10 | 0.00 | 0.00 | 0.00 | 0.149372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195910E+10 | 0.00 | 0.00 | 0.00 | 0.200293E+09 | 0.00 | 92478116.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188866E+10 | 0.00 | 0.00 | 0.00 | 2173015.59 | 0.00 | 0.720899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197072E+10 | 0.00 | 0.00 | 0.00 | 67.35 | 0.00 | 0.620137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232673E+11 | 0.00 | 0.00 | 0.00 | 0.105143E+11 | 0.00 | 0.241449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.179191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.199555E+10 | 0.00 | 0.00 | 0.00 | 0.348548E+10 | 0.00 | 0.707212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.151115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152758E+10 | 0.00 | 0.00 | 0.00 | 71998911.64 | 0.00 | 0.501885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146432E+10 | 0.00 | 0.00 | 0.00 | 5753298.52 | 0.00 | 0.191997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151090E+10 | 0.00 | 0.00 | 0.00 | 0.171633E+09 | 0.00 | 85833283.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147388E+10 | 0.00 | 0.00 | 0.00 | 0.121668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150080E+10 | 0.00 | 0.00 | 0.00 | 0.248877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152436E+10 | 0.00 | 0.00 | 0.00 | 0.211255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146379E+10 | 0.00 | 0.00 | 0.00 | 0.985429E+09 | 0.00 | 2301459.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149744E+10 | 0.00 | 0.00 | 0.00 | 0.107565E+09 | 0.00 | 0.466255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144379E+10 | 0.00 | 0.00 | 0.00 | 2439.77 | 0.00 | 0.253976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178087E+11 | 0.00 | 0.00 | 0.00 | 0.716039E+10 | 0.00 | 0.420177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.137895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152758E+10 | 0.00 | 0.00 | 0.00 | 0.248877E+10 | 0.00 | 0.111412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.659771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103815E+11 | 0.00 | 0.00 | 0.20 |
February | 0.448203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981037E+10 | 0.00 | 0.00 | 0.20 |
March | 0.323105E+10 | 0.00 | 0.00 | 528981.17 | 0.00 | 0.513041E+10 | 0.468805E+09 | 0.00 | 0.22 |
April | 0.475411E+10 | 0.00 | 0.00 | 559626.44 | 0.00 | 0.116590E+10 | 0.101359E+10 | 0.00 | 0.23 |
May | 0.142936E+10 | 16416291.15 | 0.00 | 7585765.44 | 26093.21 | 4191847.11 | 0.660873E+10 | 0.00 | 0.48 |
June | 0.210805E+09 | 0.976569E+09 | 0.00 | 12073209.55 | 2353896.13 | 0.00 | 0.610922E+10 | 0.00 | 0.70 |
July | 28881764.24 | 0.278917E+10 | 0.00 | 7513779.24 | 12913999.63 | 0.00 | 0.175421E+10 | 0.00 | 0.64 |
August | 64126241.98 | 0.149020E+10 | 0.00 | 13652933.37 | 1218277.24 | 0.00 | 0.396116E+10 | 0.00 | 0.68 |
September | 0.391173E+09 | 0.374127E+09 | 0.00 | 12751850.78 | 193389.61 | 0.00 | 0.726408E+10 | 0.00 | 0.74 |
October | 0.374869E+10 | 0.00 | 0.00 | 3824721.27 | 0.00 | 0.178132E+09 | 0.407446E+10 | 0.00 | 0.31 |
November | 0.550068E+10 | 0.00 | 0.00 | 64710.13 | 0.00 | 0.143033E+10 | 0.212067E+09 | 0.00 | 0.21 |
December | 0.169309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889542E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.221599E+11 | 0.564648E+10 | 0.00 | 58555577.40 | 16705655.83 | 0.369962E+11 | 0.314663E+11 | 0.00 | 0.40 |
Minimum of Months | 28881764.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.550068E+10 | 0.278917E+10 | 0.00 | 13652933.37 | 12913999.63 | 0.103815E+11 | 0.726408E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.628541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241635E+11 | 0.00 | 0.00 | 0.39 |
February | 0.566766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241017E+11 | 0.00 | 0.00 | 0.39 |
March | 0.562208E+11 | 24645759.72 | 0.00 | 4558165.60 | 0.00 | 0.821390E+10 | 0.398297E+10 | 0.00 | 0.42 |
April | 0.383728E+11 | 0.00 | 0.00 | 13575109.50 | 0.00 | 0.133936E+10 | 0.162483E+11 | 0.00 | 0.46 |
May | 0.668887E+10 | 0.252981E+09 | 0.00 | 72000142.05 | 6340317.50 | 0.00 | 0.481179E+11 | 0.00 | 0.76 |
June | 0.136680E+10 | 0.813889E+10 | 0.00 | 70969097.05 | 73139735.23 | 0.00 | 0.307244E+11 | 0.00 | 0.88 |
July | 0.584906E+09 | 0.216308E+11 | 0.00 | 32016588.87 | 0.224468E+09 | 0.00 | 0.694438E+10 | 0.00 | 0.79 |
August | 0.108726E+10 | 0.115634E+11 | 0.00 | 59475555.73 | 43845641.17 | 0.00 | 0.172027E+11 | 0.00 | 0.83 |
September | 0.249096E+10 | 0.309331E+10 | 0.00 | 73995265.57 | 15984887.35 | 0.00 | 0.382139E+11 | 0.00 | 0.91 |
October | 0.278235E+11 | 0.00 | 0.00 | 29786428.34 | 0.00 | 67214727.10 | 0.285122E+11 | 0.00 | 0.53 |
November | 0.503328E+11 | 0.00 | 0.00 | 2355283.61 | 0.00 | 0.199469E+10 | 0.402176E+10 | 0.00 | 0.41 |
December | 0.629837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203022E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.367483E+12 | 0.447040E+11 | 0.00 | 0.358732E+09 | 0.363779E+09 | 0.801826E+11 | 0.193969E+12 | 0.00 | 0.60 |
Minimum of Months | 0.584906E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.629837E+11 | 0.216308E+11 | 0.00 | 73995265.57 | 0.224468E+09 | 0.241635E+11 | 0.481179E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.551046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262310E+10 | 0.00 | 0.00 | 0.39 |
February | 0.493583E+10 | 0.00 | 0.00 | 7165.35 | 0.00 | 0.260146E+10 | 39700832.74 | 0.00 | 0.39 |
March | 0.461300E+10 | 12527858.42 | 0.00 | 1511887.02 | 0.00 | 0.882904E+09 | 0.128826E+10 | 0.00 | 0.46 |
April | 0.245016E+10 | 0.00 | 0.00 | 4377361.99 | 0.00 | 0.313505E+09 | 0.348266E+10 | 0.00 | 0.60 |
May | 0.559316E+09 | 31666962.78 | 0.00 | 10654342.25 | 0.00 | 0.00 | 0.600138E+10 | 0.00 | 1.04 |
June | 0.116459E+09 | 0.957667E+09 | 0.00 | 10043575.79 | 1228849.12 | 0.00 | 0.385787E+10 | 0.00 | 1.22 |
July | 36459670.03 | 0.266032E+10 | 0.00 | 4770278.58 | 1917581.23 | 0.00 | 0.963070E+09 | 0.00 | 1.06 |
August | 65933344.27 | 0.149918E+10 | 0.00 | 9322906.57 | 132480.19 | 0.00 | 0.224988E+10 | 0.00 | 1.15 |
September | 0.147691E+09 | 0.570039E+09 | 0.00 | 13497554.44 | 28490.44 | 0.00 | 0.511179E+10 | 0.00 | 1.36 |
October | 0.138550E+10 | 0.00 | 0.00 | 9702648.32 | 0.00 | 25076472.27 | 0.587495E+10 | 0.00 | 0.81 |
November | 0.348682E+10 | 0.00 | 0.00 | 2683784.62 | 0.00 | 0.280202E+09 | 0.236177E+10 | 0.00 | 0.50 |
December | 0.547573E+10 | 0.00 | 0.00 | 77548.79 | 0.00 | 0.224301E+10 | 97005582.50 | 0.00 | 0.39 |
Annual Sum or Average | 0.287833E+11 | 0.573141E+10 | 0.00 | 66649053.72 | 3307400.98 | 0.896926E+10 | 0.313283E+11 | 0.00 | 0.78 |
Minimum of Months | 36459670.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.551046E+10 | 0.266032E+10 | 0.00 | 13497554.44 | 1917581.23 | 0.262310E+10 | 0.600138E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592807E+10 | 0.00 | 0.00 | 0.39 |
February | 0.198723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556350E+10 | 0.00 | 0.00 | 0.39 |
March | 0.398886E+10 | 5802817.48 | 0.00 | 309815.31 | 0.00 | 0.209960E+10 | 0.223754E+09 | 0.00 | 0.42 |
April | 0.314983E+10 | 0.00 | 0.00 | 965495.20 | 0.00 | 0.814997E+09 | 0.970336E+09 | 0.00 | 0.45 |
May | 0.140567E+10 | 21650540.70 | 0.00 | 3786976.20 | 27573.93 | 24411430.77 | 0.283887E+10 | 0.00 | 0.66 |
June | 0.329229E+09 | 0.773279E+09 | 0.00 | 5412502.84 | 1454827.55 | 0.00 | 0.254962E+10 | 0.00 | 0.88 |
July | 46461043.34 | 0.211999E+10 | 0.00 | 3136136.97 | 6081732.83 | 0.00 | 0.702363E+09 | 0.00 | 0.83 |
August | 81197955.37 | 0.122243E+10 | 0.00 | 6081632.90 | 1233339.73 | 0.00 | 0.163516E+10 | 0.00 | 0.88 |
September | 0.496303E+09 | 0.392673E+09 | 0.00 | 7708983.17 | 293992.94 | 0.00 | 0.329460E+10 | 0.00 | 0.98 |
October | 0.277920E+10 | 0.00 | 0.00 | 3509416.39 | 0.00 | 0.174815E+09 | 0.234547E+10 | 0.00 | 0.57 |
November | 0.363876E+10 | 0.00 | 0.00 | 478432.28 | 0.00 | 0.104185E+10 | 0.532322E+09 | 0.00 | 0.41 |
December | 0.201746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575623E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.221128E+11 | 0.453583E+10 | 0.00 | 31389391.27 | 9091466.98 | 0.214035E+11 | 0.150925E+11 | 0.00 | 0.61 |
Minimum of Months | 46461043.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.398886E+10 | 0.211999E+10 | 0.00 | 7708983.17 | 6081732.83 | 0.592807E+10 | 0.329460E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |