Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2020-06-03 19:11:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1505.48 | 656.27 | 656.27 |
Net Site Energy | 1505.48 | 656.27 | 656.27 |
Total Source Energy | 4315.14 | 1881.06 | 1881.06 |
Net Source Energy | 4315.14 | 1881.06 | 1881.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 126.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 286.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 362.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 370.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 91.30 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1288.14 | 217.33 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 126.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 286.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 362.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 73.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 370.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 91.30 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 190.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 286.45 | 94.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 561.53 | 94.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 190.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 286.45 | 94.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 561.53 | 94.74 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1288.144 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1288.144 | 100.00 |
Total On-Site and Utility Electric Sources | 1288.144 | 100.00 |
Total Electricity End Uses | 1288.144 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1033.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:11 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.7888 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 16.5511 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 12.6567 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-JUL-15:00 | 12-FEB-09:09 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 201954.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 58398.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24923.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18797.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 112890.40 | 203816.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 201954.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 58398.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24923.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18797.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1862.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 136.62 | 0.00 | 0.00 | 0.00 |
Cooling | 906.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1149.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 231.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1174.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 98.97 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4079.55 | 235.59 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.55 | 0.00 | 0.00 | 0.00 |
Cooling | 395.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 500.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 512.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.14 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1778.36 | 102.70 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.55 | 0.00 | 0.00 | 0.00 |
Cooling | 395.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 500.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 512.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 43.14 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1778.36 | 102.70 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.95 |
CORE_RETAIL DIRECT AIR | 7.66 |
POINT_OF_SALE DIRECT AIR | 1.15 |
FRONT_RETAIL DIRECT AIR | 0.888083 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.82 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.82 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 40807.95 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 50811.10 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 231144.20 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 31123.07 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 25385.70 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.95 | 1.95 | 1.95 | 1.95 | 1.96 | 1.96 | 1.00 | 0.993813 | 1.96 |
PSZ-AC:2 | 7.66 | 7.66 | 7.66 | 7.66 | 7.86 | 7.86 | 1.00 | 0.974546 | 7.86 |
PSZ-AC:3 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC:4 | 0.888083 | 0.888083 | 0.888083 | 0.888083 | 0.888083 | 0.888083 | 1.00 | 1.00 | 0.888083 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.96 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.86 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.15 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.888083 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.96 | 1.96 | 1.96 | 1.96 | 37524.06 | 50811.10 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.86 | 7.86 | 7.86 | 7.86 | 183338.60 | 231144.20 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 23700.38 | 31123.07 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.888083 | 0.888083 | 0.888083 | 0.888083 | 19433.41 | 25385.70 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.96 | 0.981710 | 1.96 | 35045.08 | 37524.06 | 18762.03 | 37524.06 | 0.749446 | 0.749450 | 0.749450 | 0.749450 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.86 | 3.93 | 7.86 | 173673.09 | 183338.60 | 91669.30 | 183338.60 | 0.691992 | 0.691990 | 0.691990 | 0.691990 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.15 | 0.573230 | 1.15 | 22237.60 | 23700.38 | 11850.19 | 23700.38 | 0.725398 | 0.725400 | 0.725400 | 0.725400 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.888080 | 0.444040 | 0.888080 | 18319.54 | 19433.41 | 9716.70 | 19433.41 | 0.709122 | 0.709120 | 0.709120 | 0.709120 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.96 | 2100.95 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.86 | 14444.01 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1269.31 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.888083 | 983.25 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.789 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.859 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 38.071 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 12.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.657 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2958.869 | 7.789 | 48.236 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2958.869 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 26489.747 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26489.747 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 151.881 | 12.657 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 151.881 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.6890 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.284 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.23694873E-14 | 0.24460372E-16 | -0.16093703E-09 | 0.40693747E-16 |
25 | 8 | 0.23448185E-07 | 0.93803824E-13 | 0.39412945E-03 | -0.26661394E-09 |
26 | 7 | -0.12728387E-01 | 0.47911758E-08 | -0.23786565E-01 | 0.14472641E-03 |
27 | 6 | 0.41857762 | 0.16585077E-05 | 0.48334039 | -0.49036802E-02 |
28 | 5 | -5.3196350 | 0.61661373E-04 | -4.5275917 | 0.64784285E-01 |
29 | 4 | 33.573705 | 0.50245725E-03 | 21.777630 | -0.42970229 |
30 | 3 | -112.44059 | 0.10912898E-02 | -56.290775 | 1.5327395 |
31 | 2 | 198.33458 | 0.61196217E-03 | 78.486619 | -2.9198277 |
32 | 1 | -171.60898 | 0.65143140E-04 | -55.433097 | 2.7533770 |
33 | 0 | 57.057407 | 0.36965150E-06 | 15.529602 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.46_SHGC_0.25 | 30 | 1 | VerySmooth | 2.615 | 0.252 | 0.162 | 0.251 |
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 31 | 1 | VerySmooth | 5.108 | 0.600 | 0.461 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.53892E-002 | 0.16139 | 0.61607 | 0.61607 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 22182.30741 | 26618.76889 | 1.62606 | 1.95127 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 22186.00419 | 26623.20502 | 0.96783 | 1.16140 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 87309.29525 | 104771.15430 | 6.38515 | 7.66218 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 57508.76566 | 69010.51879 | 2.47698 | 2.97238 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12893.31476 | 15471.97771 | 0.95538 | 1.14646 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10977.43128 | 13172.91753 | 0.48090 | 0.57708 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 10053.14996 | 12063.77995 | 0.74007 | 0.88808 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10981.16878 | 13177.40253 | 0.48106 | 0.57728 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40000 | 1.44457E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 33975.96933 | 40771.16319 | 1.51415 | 1.81698 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30000 | 2.29779E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 26495.59 | 1.96342 | 1.96342 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 33218.20 | 1.16140 | 1.16140 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 117302.77 | 7.86230 | 7.86230 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 126292.97 | 2.97238 | 2.97238 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 16438.60 | 1.14646 | 1.14646 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 18479.68 | 0.57708 | 0.57708 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 13551.93 | 0.88808 | 0.88808 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 18484.14 | 0.57728 | 0.57728 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.95127 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.66218 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14646 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.88808 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.81698 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.81698 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 40807.94825 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.95127 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.95127 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.95127 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.95127 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.96342 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.96342 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.99381 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.66218 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.66218 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.66218 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.66218 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.86230 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.86230 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97455 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14646 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14646 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14646 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14646 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14646 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14646 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.88808 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.88808 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.88808 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.88808 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.88808 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.88808 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.96342 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.86230 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.14646 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.88808 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.96342 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.96342 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.96342 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.96342 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.96342 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.96342 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98171 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.96342 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 35045.08238 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 37524.06000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18762.03000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 37524.06000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74945 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74945 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74945 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74945 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37524.06000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50811.09738 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.96342 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2100.95006 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 50811.09738 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.86230 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.86230 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.86230 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.86230 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.86230 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.86230 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.93115 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.86230 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 173673.08745 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 183338.60000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 91669.30000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 183338.60000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69199 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69199 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69199 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69199 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 183338.60000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 231144.19873 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.86230 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14444.00869 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 231144.19873 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14646 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14646 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14646 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14646 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14646 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14646 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57323 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14646 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22237.59857 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23700.38000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11850.19000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 23700.38000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72540 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72540 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72540 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72540 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23700.38000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31123.06895 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14646 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1269.31496 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31123.06895 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.88808 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.88808 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.88808 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.88808 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.88808 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.88808 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.44404 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.88808 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 18319.53609 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 19433.41000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9716.70500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 19433.41000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70912 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70912 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70912 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70912 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 19433.41000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25385.70159 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.88808 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 983.24913 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25385.70159 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 35982.2 | 11.00 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 177143.4 | 12.34 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 22798.9 | 115.16 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18734.4 | 152.49 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.689 | 0.625 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 15 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.3234535206E-002 | 0.2130425185 | Pass | Pass | 0.2537994470 | 1.5831862231 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.3945429052E-002 | 0.1030680431 | Pass | Pass | 0.1170141478 | 0.2925910648 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 6.5696336755E-002 | 0.2024548627 | Pass | Pass | 0.2627480908 | 1.1640830596 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 6.0142199207E-002 | 0.2452598219 | Pass | Pass | 0.1050548179 | 0.3396095498 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1152015770 | 0.3954580775 | Pass | Pass | 8.3382116320E-002 | 0.5170588392 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.625 | 0.689 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.615 | 0.252 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.615 | 0.252 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.615 | 0.252 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.165 | 0.329 | 0.328 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.165 | 0.329 | 0.328 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.7888 | 379.89 | 2958.87 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 34.59 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 16.5511 | 1600.48 | 26489.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 52.76 | 0.0000 | Y | 262.34 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 12.6567 | 12.00 | 151.88 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.95 |
Interior Lighting Total | 15.0797 | 2293.99 | 34592.64 | 362.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4644.36 | AstronomicalClock | - | 83.77 | 83.77 | 73.03 | |
Exterior Lighting Total | 4644.36 | 73.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 37524.06 | 28122.41 | 9401.65 | 0.75 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 183338.60 | 126868.48 | 56470.12 | 0.69 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23700.38 | 17192.26 | 6508.12 | 0.73 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 19433.41 | 13780.62 | 5652.79 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 35982.2 | 11.00 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 177143.4 | 12.34 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 22798.9 | 115.16 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 18734.4 | 152.49 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 40807.95 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 50811.10 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 231144.20 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31123.07 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25385.70 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 1.82 | 1944.26 | 1070.05 | 1.00 | 1.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.96 | 2100.95 | 1070.05 | 1.00 | 1.32 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1110.54 | 7.86 | 14444.01 | 1837.12 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1269.31 | 1107.16 | 1.00 | 1.37 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.89 | 983.25 | 1107.16 | 1.00 | 1.43 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 22182.31 | 26618.77 | 70.07 | 1.626 | 1.951 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00968 | 27.37 | 0.01445 | 0.232 | 0.00 |
CORE_RETAIL | 87309.30 | 104771.15 | 65.46 | 6.385 | 7.662 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00969 | 27.37 | 0.01445 | 1.890 | 0.00 |
POINT_OF_SALE | 12893.31 | 15471.98 | 102.59 | 0.955 | 1.146 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00905 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_RETAIL | 10053.15 | 12063.78 | 79.99 | 0.740 | 0.888 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00943 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 33.80 | 100.00 | 0.00001 | 34.40 | 0.01445 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 22186.00 | 26623.21 | 70.08 | 0.968 | 1.161 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00731 | -6.30 | 0.00230 | 0.232 | 0.00 |
CORE_RETAIL | 57508.77 | 69010.52 | 43.12 | 2.477 | 2.972 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00720 | -6.30 | 0.00230 | 1.890 | 0.00 |
POINT_OF_SALE | 10977.43 | 13172.92 | 87.35 | 0.481 | 0.577 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00753 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_RETAIL | 10981.17 | 13177.40 | 87.38 | 0.481 | 0.577 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00753 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_ENTRY | 33975.97 | 40771.16 | 3397.60 | 1.514 | 1.817 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.03 | 0.00569 | -6.30 | 0.00230 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.96 | 1.96 | 1.16 | 1.16 | 1.9634 | 1.9513 | 1.9634 | 0.9938 | 1.0000 |
PSZ-AC:2 | 7.86 | 7.86 | 2.97 | 2.97 | 7.8623 | 7.6622 | 7.8623 | 0.9745 | 1.0000 |
PSZ-AC:3 | 1.15 | 1.15 | 0.58 | 0.58 | 1.1465 | 1.1465 | 1.1465 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.89 | 0.89 | 0.58 | 0.58 | 0.8881 | 0.8881 | 0.8881 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 40807.948 | 40807.948 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40807.95 | 40807.95 | 1.816981 | 20.82 | 12.20 | 0.00566678 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.03 | 0.00569326 | 35.5523 | 40771.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 37524.060 | 0.000 | 1.963420 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 37524.06 | 28941.60 | 1.963420 | 24.37 | 17.44 | 0.01008329 | 12.80 | 11.77 | 0.00850000 | 27.97 | 0.01444568 | 21.76 | 11.7940 | 23.89 | 0.00967680 | 50.4753 | 22182.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 50811.097 | 50811.097 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50811.10 | 50811.10 | 1.963418 | 15.48 | 10.66 | 0.00631357 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 11.7941 | 21.11 | 0.00731366 | 45.3333 | 22186.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 183338.600 | 0.000 | 7.862300 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 183338.60 | 137254.27 | 7.862300 | 26.62 | 18.57 | 0.01059222 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 24.0415 | 23.89 | 0.00969326 | 50.5601 | 79666.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 231144.199 | 231144.199 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 231144.20 | 231144.20 | 7.862304 | 3.58 | 2.26 | 0.00408274 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 24.0414 | 21.11 | 0.00720047 | 44.6380 | 57508.77 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 23700.380 | 0.000 | 1.146460 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23700.38 | 19113.03 | 1.146460 | 25.59 | 17.69 | 0.00989754 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 15.5357 | 23.89 | 0.00905208 | 47.2580 | 12065.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 31123.069 | 31123.069 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31123.07 | 31123.07 | 1.146462 | 12.55 | 8.96 | 0.00591423 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 15.5357 | 21.11 | 0.00752872 | 46.6492 | 10977.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 19433.410 | 0.000 | 0.888080 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19433.41 | 15092.30 | 0.888080 | 26.02 | 18.09 | 0.01022402 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 20.0557 | 23.89 | 0.00942833 | 49.1968 | 9621.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 25385.702 | 25385.702 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25385.70 | 25385.70 | 0.888083 | 12.55 | 8.96 | 0.00591504 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 20.0556 | 21.11 | 0.00752908 | 46.6514 | 10981.17 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 40807.948 | 40807.948 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.816981 | 2.10947277 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 40807.95 | 40807.95 | 1.0000 | 2.10947277 | 1.816981 | 20.82 | 12.20 | 0.00566678 | 35308.0 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40807.95 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 21.05 | 0.00569326 | 21.03 | 0.00569326 | 35.5523 | 40771.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37524.060 | 0.000 | 1.963420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5843 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 37524.06 | 28941.60 | 1.0000 | 2.27948456 | 1.963420 | 24.37 | 17.44 | 0.01008329 | 50159.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37524.06 | 27.97 | 0.01444568 | 21.76 | 0.23156651 | 11.7940 | 23.89 | 0.00950000 | 23.89 | 0.00967680 | 50.4753 | 22182.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50811.097 | 50811.097 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.963418 | 2.27948222 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50811.10 | 50811.10 | 1.0000 | 2.27948222 | 1.963418 | 15.48 | 10.66 | 0.00631357 | 31529.6 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50811.10 | -6.30 | 0.00229779 | -6.30 | 0.23156651 | 11.7941 | 20.91 | 0.00731366 | 21.11 | 0.00731366 | 45.3333 | 22186.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 183338.600 | 0.000 | 7.862300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5304 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 183338.60 | 137254.27 | 1.0000 | 9.12794585 | 7.862300 | 26.62 | 18.57 | 0.01059222 | 53762.1 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 183338.60 | 34.40 | 0.01444567 | 23.51 | 1.89021192 | 24.0415 | 23.89 | 0.00923990 | 23.89 | 0.00969326 | 50.5601 | 79666.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 231144.199 | 231144.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.862304 | 9.12795068 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 231144.20 | 231144.20 | 1.0000 | 9.12795068 | 7.862304 | 3.58 | 2.26 | 0.00408274 | 13834.6 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 231144.20 | -6.30 | 0.00229779 | -6.30 | 1.89021192 | 24.0414 | 20.84 | 0.00720047 | 21.11 | 0.00720047 | 44.6380 | 57508.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23700.380 | 0.000 | 1.146460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2390 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23700.38 | 19113.03 | 1.0000 | 1.33101316 | 1.146460 | 25.59 | 17.69 | 0.00989754 | 50934.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23700.38 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 15.5357 | 23.89 | 0.00902072 | 23.89 | 0.00905208 | 47.2580 | 12065.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31123.069 | 31123.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.146462 | 1.33101501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31123.07 | 31123.07 | 1.0000 | 1.33101501 | 1.146462 | 12.55 | 8.96 | 0.00591423 | 27540.5 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31123.07 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 15.5357 | 20.97 | 0.00752872 | 21.11 | 0.00752872 | 46.6492 | 10977.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 19433.410 | 0.000 | 0.888080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8459 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19433.41 | 15092.30 | 1.0000 | 1.03104005 | 0.888080 | 26.02 | 18.09 | 0.01022402 | 52208.4 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19433.41 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 20.0557 | 23.89 | 0.00915092 | 23.89 | 0.00942833 | 49.1968 | 9621.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25385.702 | 25385.702 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.888083 | 1.03104382 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25385.70 | 25385.70 | 1.0000 | 1.03104382 | 0.888083 | 12.55 | 8.96 | 0.00591504 | 27545.5 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25385.70 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 20.0556 | 20.97 | 0.00752908 | 21.11 | 0.00752908 | 46.6514 | 10981.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.96 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 1.89 | 7.86 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 1.15 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 0.89 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2726.00 | 2663.33 | 989.50 |
CORE_RETAIL | 2760.17 | 1942.67 | 426.33 |
POINT_OF_SALE | 2819.33 | 1805.50 | 434.83 |
FRONT_RETAIL | 2765.33 | 2288.67 | 715.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3310.17 | 2719.67 | 1033.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 2.67 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 1.50 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 3.17 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.67 | 0.00 | 0.00 | 0.00 |
Facility | 5.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.27 | 61.34 | 2317.33 | 0.662 | 0.053 | 0.000 | 0.000 |
CORE_RETAIL | 127.51 | 258.43 | 9762.95 | 0.981 | 0.010 | 0.000 | 0.000 |
POINT_OF_SALE | 12.02 | 24.35 | 919.94 | 1.266 | 0.058 | 0.000 | 0.000 |
FRONT_RETAIL | 12.02 | 24.35 | 919.94 | 1.017 | 0.058 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.27 | 61.34 | 2317.33 | 0.351 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.51 | 258.43 | 9762.95 | 0.681 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.02 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.02 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1288.14 | 3304.06 | 14-MAY-07:00 | 112890.40 | 07-JUL-16:00 |
Electricity:Building | 557.99 | 3083.31 | 14-MAY-08:00 | 41654.89 | 02-JAN-15:30 |
Electricity:Zone:BACK_SPACE | 84.58 | 607.80 | 01-JAN-00:10 | 5172.60 | 02-JAN-09:10 |
InteriorLights:Electricity | 362.83 | 1288.14 | 14-MAY-08:00 | 30883.85 | 02-JAN-15:30 |
InteriorLights:Electricity:Zone:BACK_SPACE | 34.59 | 147.94 | 01-JAN-00:10 | 2413.46 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 362.83 | 1288.14 | 14-MAY-08:00 | 30883.85 | 02-JAN-15:30 |
Electricity:Zone:CORE_RETAIL | 346.64 | 1658.43 | 14-MAY-08:00 | 28493.38 | 02-JAN-15:30 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 262.34 | 882.99 | 14-MAY-08:00 | 23840.77 | 02-JAN-15:30 |
Electricity:Zone:POINT_OF_SALE | 84.90 | 611.62 | 01-JAN-00:10 | 5167.35 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 39.92 | 197.87 | 01-JAN-00:10 | 2684.87 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1288.14 | 3304.06 | 14-MAY-07:00 | 112890.40 | 07-JUL-16:00 |
ElectricityPurchased:Plant | 1288.14 | 3304.06 | 14-MAY-07:00 | 112890.40 | 07-JUL-16:00 |
Cogeneration:ElectricityPurchased | 1288.14 | 3304.06 | 14-MAY-07:00 | 112890.40 | 07-JUL-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1288.14 | 3304.06 | 14-MAY-07:00 | 112890.40 | 07-JUL-16:00 |
ElectricityNet:Plant | 1288.14 | 3304.06 | 14-MAY-07:00 | 112890.40 | 07-JUL-16:00 |
Cogeneration:ElectricityNet | 1288.14 | 3304.06 | 14-MAY-07:00 | 112890.40 | 07-JUL-16:00 |
Electricity:HVAC | 657.12 | 0.00 | 01-JAN-00:10 | 79445.03 | 08-JUL-14:30 |
Fans:Electricity | 370.99 | 0.00 | 01-JAN-00:10 | 20741.78 | 01-JAN-08:20 |
General:Fans:Electricity | 370.99 | 0.00 | 01-JAN-00:10 | 20741.78 | 01-JAN-08:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 286.14 | 0.00 | 01-JAN-00:10 | 60647.51 | 08-JUL-14:30 |
ExteriorLights:Electricity | 73.03 | 0.00 | 01-JAN-07:50 | 4644.36 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 73.03 | 0.00 | 01-JAN-07:50 | 4644.36 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 217.33 | 1862.00 | 10-MAR-10:50 | 203816.07 | 12-FEB-09:10 |
Gas:Plant | 91.30 | 1862.00 | 07-JAN-05:10 | 5045.39 | 01-FEB-12:10 |
WaterSystems:Gas | 91.30 | 1862.00 | 07-JAN-05:10 | 5045.39 | 01-FEB-12:10 |
Water Heater:WaterSystems:Gas | 91.30 | 1862.00 | 07-JAN-05:10 | 5045.39 | 01-FEB-12:10 |
Gas:HVAC | 126.03 | 0.00 | 01-JAN-00:10 | 201954.07 | 12-FEB-09:10 |
Heating:Gas | 126.03 | 0.00 | 01-JAN-00:10 | 201954.07 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1820.90 | 0.00 | 01-JAN-00:10 | 284077.94 | 08-JUL-14:10 |
EnergyTransfer:Building | 728.42 | 0.00 | 01-JAN-00:10 | 128214.73 | 12-FEB-08:10 |
EnergyTransfer:Zone:BACK_SPACE | 95.01 | 0.00 | 01-JAN-00:10 | 24478.88 | 13-FEB-06:10 |
Heating:EnergyTransfer | 77.08 | 0.00 | 01-JAN-00:10 | 128214.73 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 12.44 | 0.00 | 01-JAN-00:10 | 24478.88 | 13-FEB-06:10 |
Cooling:EnergyTransfer | 651.34 | 0.00 | 01-JAN-00:10 | 90025.23 | 07-JUL-14:40 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 82.57 | 0.00 | 01-JAN-00:10 | 14590.56 | 08-JUL-15:20 |
EnergyTransfer:Zone:CORE_RETAIL | 455.99 | 0.00 | 01-JAN-00:10 | 76805.01 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 17.40 | 0.00 | 01-JAN-00:10 | 76805.01 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 438.59 | 0.00 | 01-JAN-00:10 | 63756.34 | 13-OCT-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 81.84 | 0.00 | 01-JAN-00:10 | 10510.82 | 12-FEB-07:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 2.60 | 0.00 | 01-JAN-00:10 | 10510.82 | 12-FEB-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 79.24 | 0.00 | 01-JAN-00:10 | 10421.35 | 19-AUG-14:00 |
EnergyTransfer:Zone:FRONT_RETAIL | 55.27 | 0.00 | 01-JAN-00:10 | 11173.51 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 4.34 | 0.00 | 01-JAN-00:10 | 11173.51 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 50.93 | 0.00 | 01-JAN-00:10 | 8317.57 | 19-AUG-14:00 |
EnergyTransfer:Zone:FRONT_ENTRY | 40.30 | 0.00 | 01-JAN-00:10 | 32006.06 | 11-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 40.30 | 0.00 | 01-JAN-00:10 | 32006.06 | 11-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1092.48 | 0.00 | 01-JAN-00:10 | 195262.44 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 100.82 | 0.00 | 01-JAN-00:10 | 161563.26 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 991.66 | 0.00 | 01-JAN-00:10 | 195262.44 | 08-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 12.438 | -82.569 | 0.000 | 0.000 | 38.043 | 34.587 | 49.992 | 0.000 | 0.000 | 0.981 | 0.003 | 0.000 | 0.000 | 0.000 | -20.749 | -32.723 |
CORE_RETAIL | 0.000 | 0.000 | 17.400 | -438.588 | 0.000 | 0.000 | 159.133 | 262.340 | 84.299 | 73.569 | 0.000 | 0.805 | 0.000 | 0.000 | -22.331 | 0.000 | -18.876 | -117.749 |
POINT_OF_SALE | 0.000 | 0.000 | 2.602 | -79.237 | 0.000 | 0.000 | 14.847 | 31.980 | 52.922 | 26.857 | 0.000 | 0.408 | 0.001 | 0.000 | -15.991 | 0.000 | -9.761 | -24.628 |
FRONT_RETAIL | 0.000 | 0.000 | 4.336 | -50.933 | 0.000 | 0.000 | 15.088 | 31.980 | 7.943 | 26.944 | 0.000 | 0.418 | 0.001 | 0.000 | -15.258 | 0.000 | -9.141 | -11.378 |
FRONT_ENTRY | 40.304 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.946 | 0.000 | 5.263 | 0.000 | 0.805 | 0.000 | 0.000 | -3.126 | 0.000 | -44.217 | -0.974 |
Total Facility | 40.304 | 0.000 | 36.775 | -651.326 | 0.000 | 0.000 | 227.111 | 362.834 | 195.156 | 132.633 | 0.000 | 3.416 | 0.004 | 0.000 | -56.706 | 0.000 | -102.744 | -187.452 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 10-JUN-06:02 | 0.00 | 0.00 | 0.00 | -44187.84 | 0.00 | 0.00 | 395.72 | 268.16 | 919.71 | 0.00 | 0.00 | 0.00 | 42843.73 | 0.00 | -0.00 | 0.00 | -239.49 | 0.00 |
CORE_RETAIL | 10-MAY-06:02 | 0.00 | 0.00 | 0.00 | -235574.51 | 0.00 | 0.00 | 1614.07 | 5297.95 | 2067.82 | 0.00 | 0.00 | 0.00 | 228247.74 | 0.00 | -1076.04 | 0.00 | -577.03 | 0.00 |
POINT_OF_SALE | 12-OCT-06:02 | 0.00 | 0.00 | 0.00 | -26756.32 | 0.00 | 0.00 | 150.53 | 499.21 | 1298.17 | 0.00 | 0.00 | 0.00 | 26528.24 | 0.00 | -1510.84 | 0.00 | -209.01 | 0.00 |
FRONT_RETAIL | 15-SEP-06:02 | 0.00 | 0.00 | 0.00 | -18732.53 | 0.00 | 0.00 | 152.23 | 499.21 | 194.85 | 0.00 | 0.00 | 0.00 | 18891.67 | 0.00 | -1005.43 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-OCT-06:02 | 0.00 | 0.00 | 0.00 | -279670.70 | 0.00 | 0.00 | 2325.38 | 6863.08 | 4787.13 | 0.00 | 0.00 | 0.00 | 272397.68 | 0.00 | -5377.48 | 0.00 | -1325.10 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 13-FEB-06:01 | 0.00 | 0.00 | 51652.28 | 0.00 | 0.00 | 0.00 | 0.00 | 147.94 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1742.89 | -50670.48 |
CORE_RETAIL | 13-FEB-06:01 | 0.00 | 0.00 | 238924.20 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.49 | 1033.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2672.82 | 0.00 | -1411.40 | -237198.39 |
POINT_OF_SALE | 13-FEB-06:01 | 0.00 | 0.00 | 31195.12 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1949.22 | 0.00 | -766.10 | -29253.69 |
FRONT_RETAIL | 09-JAN-06:01 | 0.00 | 0.00 | 25618.29 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1570.38 | 0.00 | -456.27 | -23813.87 |
FRONT_ENTRY | 11-FEB-18:00 | 32003.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 79.04 | 0.00 | -349.62 | 0.00 | -31869.83 | 0.00 |
Total Facility | 12-FEB-08:61 | 7026.56 | 0.00 | 344818.53 | 0.00 | 0.00 | 0.00 | 0.00 | 1729.63 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5191.61 | 0.00 | -9989.47 | -340188.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9513 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9634 | 0.1179 | 1.0000 | 0.2316 | 0.1179 | ||
PSZ-AC:2 | 7.6622 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.8623 | 0.2404 | 1.0000 | 1.8902 | 0.2404 | ||
PSZ-AC:3 | 1.1465 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1465 | 0.1554 | 1.0000 | 0.1781 | 0.1554 | ||
PSZ-AC:4 | 0.8881 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8881 | 0.2006 | 1.0000 | 0.1781 | 0.2006 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9513 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9513 | 1.0000 | 1.0000 | 0.2316 | 0.1187 | ||
PSZ-AC:2 | 7.6622 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.6622 | 1.0000 | 1.0000 | 1.8902 | 0.2467 | ||
PSZ-AC:3 | 1.1465 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1465 | 1.0000 | 1.0000 | 0.1781 | 0.1554 | ||
PSZ-AC:4 | 0.8881 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8881 | 1.0000 | 1.0000 | 0.1781 | 0.2006 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9513 | 1.9513 | 1.9513 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.6622 | 7.6622 | 7.6622 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1465 | 1.1465 | 1.1465 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8881 | 0.8881 | 0.8881 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9513 | 1.9634 | 1.9513 | 1.9513 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6622 | 7.8623 | 7.6622 | 7.6622 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1465 | 1.1465 | 1.1465 | 1.1465 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8881 | 0.8881 | 0.8881 | 0.8881 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9513 | 1.9513 | 1.9513 | 0.2316 | 0.1994 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.6622 | 7.6622 | 7.6622 | 1.8902 | 0.6359 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1465 | 1.1465 | 1.1465 | 0.1781 | 0.3086 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8881 | 0.8881 | 0.8881 | 0.1781 | 0.3085 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9513 | 1.9513 | 1.9513 | 1.9513 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6622 | 7.6622 | 7.6622 | 7.6622 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1465 | 1.1465 | 1.1465 | 1.1465 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8881 | 0.8881 | 0.8881 | 0.8881 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:11:32
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 126.03 | 201954.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 286.14 | 60647.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 362.83 | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 73.03 | 4644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 370.99 | 20741.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 91.30 | 5045.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1288.14 |
Natural Gas | 0.00 | 217.33 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1505.48 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 158.17 |
Space Heating | 0.00 |
Space Cooling | 124.73 |
Fans (All) | 161.72 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 561.53 |
Subtotal | 561.53 |
Natural Gas [MJ/m2] | |
Space Heating | 54.94 |
Service Water Heating | 39.80 |
Miscellaneous (All) | 94.74 |
Subtotal | 94.74 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.10 |
Space Heating | 8.37 |
Space Cooling | 19.01 |
Fans (All) | 24.64 |
Service Water Heating | 6.06 |
Receptacle Equipment | 12.96 |
Miscellaneous | 4.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.602702E+11 |
February | 0.000 | 0.325669E+11 |
March | 0.000 | 0.381187E+10 |
April | 0.000 | 0.960528E+09 |
May | 0.000 | 0.140937E+08 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.366627E+08 |
October | 0.000 | 0.121831E+10 |
November | 0.000 | 0.479764E+10 |
December | 0.000 | 0.223534E+11 |
Annual Sum or Average | 0.126030E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.602702E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334746E+09 | 5327.72 | 26-JAN-07:05 | -5.1 | -7.0 | 0.171129E+10 | 2451.27 | 31-JAN-15:09 | 20.92 | 13.07 |
February | 0.762010E+09 | 5479.03 | 09-FEB-07:05 | -5.6 | -7.4 | 0.169578E+10 | 2451.25 | 22-FEB-15:00 | 14.40 | 13.41 |
March | 0.285520E+10 | 26017.30 | 31-MAR-06:02 | 17.30 | 16.12 | 0.217541E+10 | 2451.28 | 11-MAR-12:09 | 21.97 | 14.28 |
April | 0.498296E+10 | 33936.92 | 19-APR-06:02 | 15.68 | 14.03 | 0.213454E+10 | 2451.34 | 28-APR-14:50 | 25.50 | 15.63 |
May | 0.885141E+10 | 36455.10 | 17-MAY-06:02 | 16.78 | 13.16 | 0.223147E+10 | 2451.25 | 11-MAY-14:30 | 22.80 | 14.23 |
June | 0.131399E+11 | 44194.66 | 10-JUN-06:02 | 12.48 | 9.21 | 0.220241E+10 | 2451.31 | 07-JUN-14:00 | 23.90 | 15.21 |
July | 0.148218E+11 | 29910.33 | 03-JUL-06:02 | 18.68 | 16.73 | 0.218816E+10 | 2451.32 | 29-JUL-10:39 | 19.03 | 19.03 |
August | 0.156936E+11 | 28757.99 | 26-AUG-06:02 | 21.78 | 17.45 | 0.228193E+10 | 2451.19 | 26-AUG-11:20 | 29.47 | 21.46 |
September | 0.109927E+11 | 39932.59 | 14-SEP-06:02 | 12.30 | 10.99 | 0.215714E+10 | 2451.43 | 28-SEP-14:50 | 19.40 | 17.98 |
October | 0.604180E+10 | 29674.52 | 11-OCT-06:02 | 17.70 | 16.28 | 0.216381E+10 | 2451.28 | 14-OCT-15:00 | 22.20 | 13.94 |
November | 0.291068E+10 | 30828.81 | 04-NOV-06:02 | 16.10 | 15.06 | 0.198740E+10 | 2451.27 | 01-NOV-14:00 | 20.60 | 15.19 |
December | 0.118513E+10 | 5388.90 | 01-DEC-07:05 | -3.8 | -4.7 | 0.184502E+10 | 2451.24 | 11-DEC-15:09 | 21.10 | 14.71 |
Annual Sum or Average | 0.825719E+11 | 0.247744E+11 | ||||||||
Minimum of Months | 0.334746E+09 | 5327.72 | -5.6 | -7.4 | 0.169578E+10 | 2451.19 | 14.40 | 13.07 | ||
Maximum of Months | 0.156936E+11 | 44194.66 | 21.78 | 17.45 | 0.228193E+10 | 2451.43 | 29.47 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131964E+11 | 43892.98 | 10-JAN-07:05 | -4.5 | -4.5 | 0.739148E+10 | 10327.12 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.161184E+11 | 68326.06 | 22-FEB-07:03 | 11.02 | 6.31 | 0.732876E+10 | 10327.99 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.283490E+11 | 172645.22 | 14-MAR-06:03 | 13.48 | 11.32 | 0.936149E+10 | 10327.47 | 27-MAR-14:30 | 21.40 | 12.70 |
April | 0.354402E+11 | 202772.57 | 01-APR-06:02 | 12.80 | 8.49 | 0.904367E+10 | 10327.53 | 15-APR-11:09 | 25.78 | 14.57 |
May | 0.461325E+11 | 235588.00 | 10-MAY-06:02 | 9.40 | 4.75 | 0.940634E+10 | 10327.46 | 10-MAY-14:20 | 20.97 | 12.24 |
June | 0.551827E+11 | 201233.09 | 08-JUN-06:02 | 12.07 | 8.46 | 0.927900E+10 | 10327.30 | 08-JUN-14:00 | 25.60 | 14.28 |
July | 0.586812E+11 | 132978.08 | 03-JUL-06:02 | 18.68 | 16.73 | 0.921888E+10 | 10326.97 | 08-JUL-11:20 | 34.07 | 24.36 |
August | 0.605072E+11 | 133524.22 | 26-AUG-06:02 | 21.78 | 17.45 | 0.961389E+10 | 10326.91 | 26-AUG-11:20 | 29.47 | 21.46 |
September | 0.463934E+11 | 177831.94 | 14-SEP-06:02 | 12.30 | 10.99 | 0.908835E+10 | 10327.57 | 28-SEP-14:09 | 19.40 | 18.21 |
October | 0.359391E+11 | 232985.41 | 13-OCT-06:02 | 5.60 | 4.35 | 0.913524E+10 | 10327.28 | 21-OCT-10:00 | 18.90 | 12.93 |
November | 0.245681E+11 | 174468.62 | 10-NOV-07:03 | 11.20 | 9.62 | 0.850053E+10 | 10327.41 | 04-NOV-13:00 | 17.80 | 17.48 |
December | 0.180868E+11 | 138252.56 | 13-DEC-07:03 | 16.70 | 15.65 | 0.815095E+10 | 10327.38 | 13-DEC-15:20 | 17.93 | 16.88 |
Annual Sum or Average | 0.438595E+12 | 0.105519E+12 | ||||||||
Minimum of Months | 0.131964E+11 | 43892.98 | -4.5 | -4.5 | 0.732876E+10 | 10326.91 | 17.20 | 12.24 | ||
Maximum of Months | 0.605072E+11 | 235588.00 | 21.78 | 17.45 | 0.961389E+10 | 10327.99 | 34.07 | 24.36 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245206E+10 | 4287.86 | 26-JAN-07:05 | -5.1 | -7.0 | 0.748267E+09 | 973.19 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.306009E+10 | 7220.40 | 28-FEB-15:30 | 24.15 | 13.10 | 0.713177E+09 | 973.25 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.507021E+10 | 18875.01 | 31-MAR-06:02 | 17.30 | 16.12 | 0.886305E+09 | 973.15 | 11-MAR-11:30 | 20.00 | 13.41 |
April | 0.558882E+10 | 23497.69 | 18-APR-06:02 | 13.30 | 12.05 | 0.851049E+09 | 973.19 | 28-APR-14:00 | 25.60 | 15.82 |
May | 0.724262E+10 | 22157.43 | 16-MAY-06:02 | 15.87 | 13.09 | 0.886072E+09 | 973.11 | 10-MAY-14:09 | 20.78 | 12.15 |
June | 0.917217E+10 | 23850.93 | 10-JUN-06:02 | 12.48 | 9.21 | 0.874325E+09 | 973.10 | 10-JUN-10:30 | 22.80 | 13.48 |
July | 0.101247E+11 | 17809.05 | 03-JUL-06:02 | 18.68 | 16.73 | 0.868662E+09 | 973.15 | 29-JUL-10:09 | 18.48 | 18.48 |
August | 0.112553E+11 | 17136.58 | 26-AUG-06:02 | 21.78 | 17.45 | 0.905876E+09 | 973.19 | 25-AUG-14:39 | 31.10 | 19.03 |
September | 0.901432E+10 | 24255.55 | 14-SEP-06:02 | 12.30 | 10.99 | 0.856373E+09 | 973.18 | 13-SEP-14:39 | 25.07 | 15.82 |
October | 0.734955E+10 | 26759.28 | 12-OCT-06:02 | 8.12 | 5.86 | 0.862839E+09 | 973.19 | 06-OCT-14:39 | 19.80 | 12.78 |
November | 0.534691E+10 | 21960.09 | 03-NOV-06:02 | 13.80 | 12.88 | 0.820151E+09 | 973.17 | 04-NOV-13:00 | 17.80 | 17.48 |
December | 0.356247E+10 | 18742.42 | 13-DEC-07:03 | 16.70 | 15.65 | 0.817030E+09 | 973.17 | 13-DEC-15:39 | 17.57 | 16.89 |
Annual Sum or Average | 0.792392E+11 | 0.100901E+11 | ||||||||
Minimum of Months | 0.245206E+10 | 4287.86 | -5.1 | -7.0 | 0.713177E+09 | 973.10 | 17.20 | 12.15 | ||
Maximum of Months | 0.112553E+11 | 26759.28 | 24.15 | 17.45 | 0.905876E+09 | 973.25 | 31.10 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114308E+10 | 4084.10 | 15-JAN-09:05 | -2.9 | -5.0 | 0.694418E+09 | 973.11 | 31-JAN-15:50 | 20.18 | 13.48 |
February | 0.149063E+10 | 4965.28 | 28-FEB-15:40 | 23.87 | 12.90 | 0.676066E+09 | 973.12 | 22-FEB-15:09 | 19.07 | 12.79 |
March | 0.271432E+10 | 14676.64 | 31-MAR-06:02 | 17.30 | 16.12 | 0.856746E+09 | 973.14 | 27-MAR-14:00 | 21.70 | 13.08 |
April | 0.311842E+10 | 14201.76 | 18-APR-06:02 | 13.30 | 12.05 | 0.838708E+09 | 973.14 | 15-APR-15:00 | 28.30 | 15.97 |
May | 0.445083E+10 | 17380.58 | 17-MAY-06:02 | 16.78 | 13.16 | 0.883710E+09 | 973.13 | 13-MAY-15:00 | 27.20 | 15.42 |
June | 0.638093E+10 | 18160.08 | 07-JUN-06:02 | 13.48 | 11.64 | 0.874128E+09 | 973.11 | 08-JUN-14:00 | 25.60 | 14.28 |
July | 0.726713E+10 | 14450.15 | 03-JUL-06:02 | 18.68 | 16.73 | 0.868652E+09 | 973.13 | 29-JUL-10:39 | 19.03 | 19.03 |
August | 0.823968E+10 | 13958.64 | 26-AUG-06:02 | 21.78 | 17.45 | 0.905876E+09 | 973.07 | 26-AUG-10:09 | 27.48 | 20.44 |
September | 0.623430E+10 | 18735.76 | 15-SEP-06:02 | 14.50 | 12.25 | 0.856052E+09 | 973.17 | 28-SEP-14:09 | 19.40 | 18.21 |
October | 0.477750E+10 | 16386.44 | 10-OCT-06:02 | 15.00 | 14.30 | 0.848099E+09 | 973.18 | 04-OCT-14:09 | 19.68 | 12.49 |
November | 0.316388E+10 | 13370.10 | 04-NOV-06:02 | 16.10 | 15.06 | 0.791201E+09 | 973.12 | 09-NOV-15:00 | 20.00 | 12.39 |
December | 0.195368E+10 | 6103.24 | 13-DEC-07:03 | 16.70 | 15.65 | 0.756215E+09 | 973.11 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.509344E+11 | 0.984987E+10 | ||||||||
Minimum of Months | 0.114308E+10 | 4084.10 | -2.9 | -5.0 | 0.676066E+09 | 973.07 | 19.03 | 12.39 | ||
Maximum of Months | 0.823968E+10 | 18735.76 | 23.87 | 17.45 | 0.905876E+09 | 973.18 | 28.30 | 20.44 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544659E+10 | 51547.17 | 07-JAN-06:01 | -1.3 |
February | 0.326027E+10 | 51652.27 | 13-FEB-06:01 | -5.6 |
March | 0.365383E+09 | 50110.11 | 22-MAR-05:02 | 6.02 |
April | 0.218527E+09 | 2424.99 | 06-APR-06:07 | 1.20 |
May | 0.210909E+09 | 2059.12 | 14-MAY-07:45 | 15.22 |
June | 0.105219E+09 | 2479.11 | 04-JUN-08:06 | 22.57 |
July | 64006121.01 | 2856.98 | 17-JUL-05:05 | 21.70 |
August | 48635271.08 | 2711.58 | 10-AUG-05:05 | 24.40 |
September | 0.137590E+09 | 2469.64 | 16-SEP-06:06 | 22.70 |
October | 0.206558E+09 | 2049.99 | 08-OCT-07:55 | 13.30 |
November | 0.445676E+09 | 50901.24 | 22-NOV-06:01 | -3.3 |
December | 0.192850E+10 | 51313.27 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.124379E+11 | |||
Minimum of Months | 48635271.08 | 2049.99 | -5.6 | |
Maximum of Months | 0.544659E+10 | 51652.27 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456344E+10 | 238802.42 | 07-JAN-06:01 | -1.3 |
February | 0.280498E+10 | 238924.18 | 13-FEB-06:01 | -5.6 |
March | 0.143460E+10 | 14520.91 | 23-MAR-05:23 | 6.10 |
April | 0.130254E+10 | 14459.97 | 07-APR-05:33 | 2.97 |
May | 0.950354E+09 | 14247.71 | 14-MAY-07:45 | 15.22 |
June | 0.371039E+09 | 16647.84 | 25-JUN-08:06 | 23.87 |
July | 0.338119E+09 | 17627.53 | 15-JUL-06:06 | 24.40 |
August | 0.323232E+09 | 17490.54 | 05-AUG-05:05 | 23.22 |
September | 0.573176E+09 | 15571.85 | 04-SEP-08:06 | 23.17 |
October | 0.132225E+10 | 14089.51 | 09-OCT-07:12 | 14.80 |
November | 0.142869E+10 | 19277.78 | 21-NOV-07:20 | -2.8 |
December | 0.198743E+10 | 237060.38 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.173999E+11 | |||
Minimum of Months | 0.323232E+09 | 14089.51 | -5.6 | |
Maximum of Months | 0.456344E+10 | 238924.18 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.960386E+09 | 31132.97 | 07-JAN-06:01 | -1.3 |
February | 0.624448E+09 | 31195.11 | 13-FEB-06:01 | -5.6 |
March | 0.126348E+09 | 8896.20 | 22-MAR-05:02 | 6.02 |
April | 0.117668E+09 | 1270.36 | 07-APR-05:33 | 2.97 |
May | 0.104090E+09 | 1312.52 | 19-MAY-05:04 | 16.60 |
June | 36057984.38 | 1688.58 | 26-JUN-05:07 | 23.30 |
July | 28430776.82 | 1922.03 | 17-JUL-05:05 | 21.70 |
August | 24912416.76 | 1866.14 | 10-AUG-05:05 | 24.40 |
September | 38841779.95 | 1913.11 | 09-SEP-05:05 | 21.78 |
October | 0.106458E+09 | 1226.20 | 29-OCT-08:00 | 12.20 |
November | 0.131906E+09 | 27302.34 | 22-NOV-06:01 | -3.3 |
December | 0.302000E+09 | 30888.93 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.260155E+10 | |||
Minimum of Months | 24912416.76 | 1226.20 | -5.6 | |
Maximum of Months | 0.960386E+09 | 31195.11 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181302E+10 | 25618.29 | 09-JAN-06:01 | -2.4 |
February | 0.109543E+10 | 25567.65 | 12-FEB-07:01 | -12.7 |
March | 0.161980E+09 | 24799.50 | 22-MAR-05:02 | 6.02 |
April | 0.111162E+09 | 12715.55 | 06-APR-05:01 | 0.18 |
May | 96330803.46 | 958.40 | 14-MAY-07:45 | 15.22 |
June | 60835569.19 | 1217.96 | 25-JUN-08:06 | 23.87 |
July | 32943899.15 | 1315.57 | 23-JUL-08:06 | 24.37 |
August | 16920748.48 | 1303.33 | 10-AUG-06:06 | 24.50 |
September | 57825987.24 | 1183.50 | 09-SEP-05:05 | 21.78 |
October | 95723950.75 | 1454.84 | 26-OCT-06:07 | 2.20 |
November | 0.154450E+09 | 25246.38 | 22-NOV-06:01 | -3.3 |
December | 0.638951E+09 | 25408.21 | 18-DEC-06:01 | -5.0 |
Annual Sum or Average | 0.433558E+10 | |||
Minimum of Months | 16920748.48 | 958.40 | -12.7 | |
Maximum of Months | 0.181302E+10 | 25618.29 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128883E+11 | 32004.49 | 07-JAN-18:00 | -5.0 |
February | 0.795592E+10 | 32006.06 | 11-FEB-18:00 | -5.0 |
March | 0.374028E+10 | 19397.53 | 22-MAR-11:10 | 4.40 |
April | 0.125484E+10 | 14989.91 | 05-APR-11:05 | 8.17 |
May | 0.171636E+09 | 4292.08 | 10-MAY-11:10 | 17.30 |
June | 5611764.05 | 1769.15 | 10-JUN-07:04 | 14.27 |
July | 58170287.23 | 2565.73 | 28-JUL-11:10 | 19.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.150441E+09 | 3688.29 | 28-SEP-17:00 | 17.20 |
October | 0.187521E+10 | 13554.48 | 25-OCT-11:05 | 9.18 |
November | 0.382188E+10 | 19582.87 | 20-NOV-12:10 | 3.98 |
December | 0.838143E+10 | 23715.47 | 17-DEC-18:00 | 1.10 |
Annual Sum or Average | 0.403038E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.128883E+11 | 32006.06 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.290080E+10 | 2413.46 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.263912E+10 | 2413.46 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.300979E+10 | 2413.46 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.284005E+10 | 2413.46 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.295530E+10 | 2413.46 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.290440E+10 | 2413.46 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.289095E+10 | 2413.46 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.300979E+10 | 2413.46 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.284005E+10 | 2413.46 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.290080E+10 | 2413.46 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.280526E+10 | 2413.46 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.289095E+10 | 2413.46 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.345872E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.263912E+10 | 2413.46 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.300979E+10 | 2413.46 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.250676E+11 | 23840.77 | 02-JAN-15:30 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.224050E+11 | 23840.77 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.228431E+11 | 23840.77 | 01-MAR-17:30 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.200547E+11 | 23840.77 | 03-APR-08:09 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.200726E+11 | 21854.04 | 05-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.194199E+11 | 21854.04 | 05-JUN-16:00 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.192956E+11 | 21854.04 | 11-JUL-16:00 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.200683E+11 | 21854.04 | 18-AUG-16:49 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.204735E+11 | 23840.77 | 02-SEP-16:49 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.240757E+11 | 23840.77 | 03-OCT-16:00 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.236273E+11 | 23840.77 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.249369E+11 | 23840.77 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.262340E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.192956E+11 | 21854.04 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.250676E+11 | 23840.77 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.163184E+09 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.148475E+09 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.169362E+09 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.159794E+09 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.166273E+09 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.163430E+09 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.162637E+09 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.169362E+09 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.159794E+09 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.163184E+09 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.157798E+09 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.162637E+09 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194593E+10 | ||||
Minimum of Months | 0.148475E+09 | 136.69 | 0.00 | 0.00 | |
Maximum of Months | 0.169362E+09 | 136.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386426E+10 |
February | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 875411.33 | 0.333927E+10 |
March | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8662364.78 | 0.222086E+10 |
April | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22399177.66 | 0.138789E+10 |
May | 0.536353E+10 | 0.295530E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67563546.13 | 0.904195E+09 |
June | 0.528933E+10 | 0.290440E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253863E+09 | 0.475894E+09 |
July | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260688E+09 | 0.312825E+09 |
August | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271742E+09 | 0.219918E+09 |
September | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79335463.28 | 0.499762E+09 |
October | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15288210.94 | 0.168576E+10 |
November | 0.504819E+10 | 0.280526E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96880.28 | 0.235429E+10 |
December | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348361E+10 |
Annual Sum or Average | 0.628175E+11 | 0.345872E+11 | 0.499918E+11 | 0.980514E+09 | 0.207485E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219918E+09 |
Maximum of Months | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271742E+09 | 0.386426E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.250676E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346835E+10 |
February | 0.201852E+11 | 0.224050E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 716794.35 | 0.305408E+10 |
March | 0.230879E+11 | 0.228431E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7085220.16 | 0.209861E+10 |
April | 0.218263E+11 | 0.200547E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18299414.84 | 0.128923E+10 |
May | 0.225967E+11 | 0.200726E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55016084.32 | 0.831202E+09 |
June | 0.222841E+11 | 0.194199E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207393E+09 | 0.418936E+09 |
July | 0.221389E+11 | 0.192956E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214580E+09 | 0.269643E+09 |
August | 0.230879E+11 | 0.200683E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224111E+09 | 0.186082E+09 |
September | 0.218263E+11 | 0.204735E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64865244.35 | 0.437429E+09 |
October | 0.221054E+11 | 0.240757E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12512594.46 | 0.150381E+10 |
November | 0.212681E+11 | 0.236273E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79359.76 | 0.213073E+10 |
December | 0.221389E+11 | 0.249369E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318778E+10 |
Annual Sum or Average | 0.264651E+12 | 0.262340E+12 | 0.842987E+11 | 0.804659E+09 | 0.188759E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.192956E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186082E+09 |
Maximum of Months | 0.230879E+11 | 0.250676E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224111E+09 | 0.346835E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177858E+10 |
February | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379525.46 | 0.154381E+10 |
March | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3748432.16 | 0.106106E+10 |
April | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9677543.22 | 0.644940E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28877780.03 | 0.421909E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107498E+09 | 0.232103E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106981E+09 | 0.157650E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111078E+09 | 0.127907E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33352168.12 | 0.246122E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6624519.20 | 0.793703E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42063.24 | 0.111756E+10 |
December | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163590E+10 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.529224E+11 | 0.408260E+09 | 0.976124E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127907E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111078E+09 | 0.177858E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170435E+10 |
February | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 379498.54 | 0.147122E+10 |
March | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3749459.70 | 0.987521E+09 |
April | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9690070.99 | 0.597731E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29093631.23 | 0.384725E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109074E+09 | 0.200919E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110797E+09 | 0.133537E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114521E+09 | 0.101044E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33762117.14 | 0.221515E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6624399.10 | 0.744935E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42027.64 | 0.105272E+10 |
December | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154085E+10 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.794328E+10 | 0.417733E+09 | 0.914108E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101044E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114521E+09 | 0.170435E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129374E+11 |
February | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815899E+10 |
March | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9934.22 | 0.427059E+10 |
April | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6392274.16 | 0.159636E+10 |
May | 0.00 | 0.166273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52727875.01 | 0.457440E+09 |
June | 0.00 | 0.163430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237541E+09 | 0.126028E+09 |
July | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285274E+09 | 0.180687E+09 |
August | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202269E+09 | 0.105477E+09 |
September | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20267762.23 | 0.467886E+09 |
October | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23621.30 | 0.258722E+10 |
November | 0.00 | 0.157798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453124E+10 |
December | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879781E+10 |
Annual Sum or Average | 0.00 | 0.194593E+10 | 0.804505E+09 | 0.442171E+11 | |||||
Minimum of Months | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105477E+09 |
Maximum of Months | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285274E+09 | 0.129374E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2413.46 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7305.71 | 07-JAN-05:04 |
February | 5888.82 | 01-FEB-15:09 | 2413.46 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.08 | 28-FEB-15:00 | 9480.29 | 12-FEB-00:55 |
March | 5888.82 | 01-MAR-15:09 | 2413.46 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 243.35 | 30-MAR-16:00 | 5440.50 | 22-MAR-03:00 |
April | 5888.82 | 01-APR-10:09 | 2413.46 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.12 | 04-APR-15:00 | 3041.74 | 05-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 2413.46 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 601.35 | 29-MAY-18:03 | 2592.76 | 10-MAY-04:00 |
June | 5888.82 | 01-JUN-14:09 | 2413.46 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 928.49 | 11-JUN-18:03 | 1919.23 | 07-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 2413.46 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 934.96 | 09-JUL-18:03 | 1366.21 | 28-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 2413.46 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1283.28 | 18-AUG-20:03 | 950.80 | 25-AUG-05:00 |
September | 5888.82 | 01-SEP-14:09 | 2413.46 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 508.41 | 03-SEP-18:03 | 1871.77 | 29-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 2413.46 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 192.48 | 11-OCT-14:00 | 3555.60 | 28-OCT-04:00 |
November | 5888.82 | 01-NOV-14:09 | 2413.46 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.88 | 19-NOV-14:55 | 5837.69 | 30-NOV-21:03 |
December | 5888.82 | 01-DEC-15:09 | 2413.46 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8631.09 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.80 | |||||
Maximum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1283.28 | 9480.29 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 23840.77 | 02-JAN-15:30 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6325.07 | 26-JAN-02:00 |
February | 24809.68 | 01-FEB-15:09 | 23840.77 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.21 | 28-FEB-15:00 | 8872.99 | 12-FEB-00:55 |
March | 24809.68 | 01-MAR-15:09 | 23840.77 | 01-MAR-17:30 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.19 | 30-MAR-16:00 | 5648.10 | 22-MAR-03:00 |
April | 24809.68 | 01-APR-10:09 | 23840.77 | 03-APR-08:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.81 | 04-APR-15:00 | 2948.26 | 05-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 21854.04 | 05-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 490.90 | 29-MAY-18:03 | 2392.69 | 10-MAY-04:00 |
June | 24809.68 | 01-JUN-14:09 | 21854.04 | 05-JUN-16:00 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 760.09 | 11-JUN-18:03 | 1726.21 | 07-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 21854.04 | 11-JUL-16:00 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 768.05 | 09-JUL-18:03 | 1254.87 | 28-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 21854.04 | 18-AUG-16:49 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.44 | 18-AUG-20:03 | 825.40 | 25-AUG-05:00 |
September | 24809.68 | 01-SEP-14:09 | 23840.77 | 02-SEP-16:49 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 419.05 | 03-SEP-18:03 | 1671.71 | 29-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 23840.77 | 03-OCT-16:00 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.55 | 11-OCT-14:00 | 3476.68 | 28-OCT-04:00 |
November | 24809.68 | 01-NOV-14:09 | 23840.77 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 19-NOV-15:00 | 4988.04 | 30-NOV-21:50 |
December | 24809.68 | 01-DEC-15:09 | 23840.77 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8532.70 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 21854.04 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.40 | |||||
Maximum of Months | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.44 | 8872.99 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3198.33 | 07-JAN-05:03 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.12 | 28-FEB-15:00 | 4139.63 | 12-FEB-00:55 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.45 | 30-MAR-16:00 | 2522.79 | 22-MAR-03:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 | 04-APR-15:00 | 1369.93 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 253.81 | 29-MAY-18:03 | 1145.03 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 395.92 | 11-JUN-18:03 | 872.77 | 07-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.73 | 09-JUL-18:03 | 634.41 | 28-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 544.76 | 18-AUG-20:03 | 456.51 | 25-AUG-05:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.95 | 03-SEP-18:03 | 821.66 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.42 | 11-OCT-14:00 | 1706.16 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 19-NOV-15:00 | 2580.36 | 30-NOV-21:03 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3863.81 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.51 | |||||
Maximum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 544.76 | 4139.63 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3143.32 | 07-JAN-05:03 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.11 | 28-FEB-15:00 | 4160.52 | 12-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.45 | 30-MAR-16:00 | 2335.99 | 22-MAR-03:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.96 | 04-APR-15:00 | 1276.38 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 257.10 | 29-MAY-18:03 | 1088.49 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.01 | 11-JUN-18:03 | 810.74 | 07-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 401.84 | 09-JUL-18:03 | 577.96 | 28-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 549.69 | 18-AUG-20:03 | 404.78 | 25-AUG-05:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 | 03-SEP-18:03 | 772.54 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.42 | 11-OCT-14:00 | 1610.50 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 19-NOV-15:00 | 2441.75 | 30-NOV-21:03 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3687.17 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.78 | |||||
Maximum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 549.69 | 4160.52 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 31630.47 | 07-JAN-17:00 |
February | 0.00 | 01-FEB-00:10 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31869.83 | 11-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 28-MAR-17:00 | 19346.60 | 22-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.79 | 12-APR-14:00 | 15627.25 | 05-APR-11:05 |
May | 0.00 | 01-MAY-00:10 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 663.09 | 30-MAY-11:03 | 4721.70 | 10-MAY-11:10 |
June | 0.00 | 01-JUN-00:10 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1651.70 | 06-JUN-11:02 | 1525.39 | 07-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.73 | 08-JUL-11:01 | 3172.08 | 28-JUL-11:10 |
August | 0.00 | 01-AUG-00:10 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1737.03 | 01-AUG-11:02 | 1270.67 | 08-AUG-16:53 |
September | 0.00 | 01-SEP-00:10 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.11 | 09-SEP-11:05 | 4363.86 | 28-SEP-17:00 |
October | 0.00 | 01-OCT-00:10 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 10-OCT-16:00 | 14204.18 | 25-OCT-11:05 |
November | 0.00 | 01-NOV-00:10 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19937.23 | 20-NOV-12:10 |
December | 0.00 | 01-DEC-00:10 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 23781.70 | 17-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.67 | ||||
Maximum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2189.73 | 31869.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5327.72 | 26-JAN-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.55 |
February | 5479.03 | 09-FEB-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.27 |
March | 26017.30 | 31-MAR-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.71 |
April | 33936.92 | 19-APR-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 |
May | 36455.10 | 17-MAY-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.04 |
June | 44194.66 | 10-JUN-06:02 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.49 |
July | 29910.33 | 03-JUL-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.80 |
August | 28757.99 | 26-AUG-06:02 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.90 |
September | 39932.59 | 14-SEP-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.26 |
October | 29674.52 | 11-OCT-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.58 |
November | 30828.81 | 04-NOV-06:02 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.03 |
December | 5388.90 | 01-DEC-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5327.72 | 2944.41 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.90 | |
Maximum of Months | 44194.66 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1266.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 43892.98 | 10-JAN-07:05 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.53 |
February | 68326.06 | 22-FEB-07:03 | 9303.63 | 15893.85 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.06 |
March | 172645.22 | 14-MAR-06:03 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.10 |
April | 202772.57 | 01-APR-06:02 | 15506.05 | 13244.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 235588.00 | 10-MAY-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.03 |
June | 201233.09 | 08-JUN-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.68 |
July | 132978.08 | 03-JUL-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.69 |
August | 133524.22 | 26-AUG-06:02 | 15506.05 | 13244.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 |
September | 177831.94 | 14-SEP-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.39 |
October | 232985.41 | 13-OCT-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.70 |
November | 174468.62 | 10-NOV-07:03 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.94 |
December | 138252.56 | 13-DEC-07:03 | 12404.84 | 21191.80 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.67 |
Annual Sum or Average | |||||||||||
Minimum of Months | 43892.98 | 9303.63 | 13244.87 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 235588.00 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4287.86 | 26-JAN-07:05 | 1168.88 | 1996.86 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.57 |
February | 7220.40 | 28-FEB-15:30 | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 0.00 |
March | 18875.01 | 31-MAR-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.11 |
April | 23497.69 | 18-APR-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.11 |
May | 22157.43 | 16-MAY-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.06 |
June | 23850.93 | 10-JUN-06:02 | 1461.10 | 1248.04 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.80 |
July | 17809.05 | 03-JUL-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.39 |
August | 17136.58 | 26-AUG-06:02 | 1461.10 | 1248.04 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 |
September | 24255.55 | 14-SEP-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.77 |
October | 26759.28 | 12-OCT-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.01 |
November | 21960.09 | 03-NOV-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.51 |
December | 18742.42 | 13-DEC-07:03 | 1168.88 | 1996.86 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4287.86 | 1168.88 | 1248.04 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26759.28 | 2337.76 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 547.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4084.10 | 15-JAN-09:05 | 1168.88 | 998.43 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.46 |
February | 4965.28 | 28-FEB-15:40 | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
March | 14676.64 | 31-MAR-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.14 |
April | 14201.76 | 18-APR-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.28 |
May | 17380.58 | 17-MAY-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.11 |
June | 18160.08 | 07-JUN-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.14 |
July | 14450.15 | 03-JUL-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 |
August | 13958.64 | 26-AUG-06:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 |
September | 18735.76 | 15-SEP-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16386.44 | 10-OCT-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.45 |
November | 13370.10 | 04-NOV-06:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.89 |
December | 6103.24 | 13-DEC-07:03 | 1168.88 | 1996.86 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.60 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4084.10 | 1168.88 | 998.43 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18735.76 | 2337.76 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.64 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.50 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.30 |
April | 0.00 | 01-APR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.52 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.19 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.29 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.26 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.98 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.13 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | |
Maximum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.13 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.902918E+11 | 67042.31 | 20-JAN-17:00 | 0.683956E+11 | 182159.73 | 08-JAN-09:09 |
February | 0.820977E+11 | 77191.66 | 28-FEB-17:10 | 0.399189E+11 | 203816.07 | 12-FEB-09:09 |
March | 0.927949E+11 | 88553.54 | 30-MAR-16:40 | 0.119035E+11 | 37881.02 | 18-MAR-06:00 |
April | 0.963496E+11 | 89579.05 | 17-APR-16:19 | 0.857784E+10 | 29854.63 | 06-APR-06:00 |
May | 0.112762E+12 | 97623.68 | 19-MAY-16:49 | 0.768689E+10 | 6830.00 | 10-MAY-11:20 |
June | 0.129723E+12 | 104277.30 | 12-JUN-15:50 | 0.727459E+10 | 4889.62 | 01-JUN-11:09 |
July | 0.138997E+12 | 112890.40 | 07-JUL-15:00 | 0.735098E+10 | 4851.45 | 03-JUL-11:30 |
August | 0.145170E+12 | 110866.49 | 18-AUG-16:49 | 0.740506E+10 | 4849.75 | 31-AUG-11:00 |
September | 0.119444E+12 | 106611.78 | 07-SEP-16:30 | 0.726390E+10 | 6931.12 | 28-SEP-16:00 |
October | 0.101340E+12 | 99006.47 | 10-OCT-15:00 | 0.883285E+10 | 18539.99 | 25-OCT-11:09 |
November | 0.887606E+11 | 80611.19 | 04-NOV-16:00 | 0.123557E+11 | 84878.23 | 22-NOV-07:30 |
December | 0.904137E+11 | 75811.51 | 12-DEC-15:00 | 0.303665E+11 | 140310.10 | 04-DEC-07:10 |
Annual Sum or Average | 0.128814E+13 | 0.217332E+12 | ||||
Minimum of Months | 0.820977E+11 | 67042.31 | 0.726390E+10 | 4849.75 | ||
Maximum of Months | 0.145170E+12 | 112890.40 | 0.683956E+11 | 203816.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.334953E+11 | 0.722848E+10 | 0.164409E+11 | 0.00 | 0.330944E+11 | 0.00 | 0.00 | 32680041.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300728E+11 | 0.616957E+10 | 0.149157E+11 | 0.00 | 0.296248E+11 | 0.00 | 0.00 | 0.131479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315890E+11 | 0.630890E+10 | 0.168545E+11 | 0.00 | 0.324556E+11 | 0.00 | 0.00 | 0.558697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283067E+11 | 0.558438E+10 | 0.160165E+11 | 0.00 | 0.302611E+11 | 0.00 | 0.00 | 0.161809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.286594E+11 | 0.531686E+10 | 0.166477E+11 | 0.00 | 0.305934E+11 | 0.00 | 0.00 | 0.315444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.278595E+11 | 0.494624E+10 | 0.162772E+11 | 0.00 | 0.296504E+11 | 0.00 | 0.00 | 0.509894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.276949E+11 | 0.518589E+10 | 0.163871E+11 | 0.00 | 0.302385E+11 | 0.00 | 0.00 | 0.594910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.288142E+11 | 0.556487E+10 | 0.168545E+11 | 0.00 | 0.306550E+11 | 0.00 | 0.00 | 0.632815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287256E+11 | 0.587976E+10 | 0.160165E+11 | 0.00 | 0.295810E+11 | 0.00 | 0.00 | 0.392411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325034E+11 | 0.661542E+10 | 0.164409E+11 | 0.00 | 0.311949E+11 | 0.00 | 0.00 | 0.145852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317770E+11 | 0.687458E+10 | 0.159174E+11 | 0.00 | 0.308219E+11 | 0.00 | 0.00 | 0.336971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.333362E+11 | 0.735666E+10 | 0.163871E+11 | 0.00 | 0.328162E+11 | 0.00 | 0.00 | 0.517604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362834E+12 | 0.730316E+11 | 0.195156E+12 | 0.370987E+12 | 0.00 | 0.286135E+12 | |||||||
Minimum of Months | 0.276949E+11 | 0.494624E+10 | 0.149157E+11 | 0.00 | 0.295810E+11 | 0.00 | 0.00 | 32680041.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.334953E+11 | 0.735666E+10 | 0.168545E+11 | 0.00 | 0.330944E+11 | 0.00 | 0.00 | 0.632815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.602702E+11 | 0.00 | 0.812540E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.325669E+11 | 0.00 | 0.735207E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.381187E+10 | 0.00 | 0.809166E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.960528E+09 | 0.00 | 0.761731E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 14093745.28 | 0.00 | 0.767280E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.727459E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.735098E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.740506E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 36662726.48 | 0.00 | 0.722724E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.121831E+10 | 0.00 | 0.761453E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.479764E+10 | 0.00 | 0.755809E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223534E+11 | 0.00 | 0.801311E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.126030E+12 | 0.913028E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.722724E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.602702E+11 | 0.00 | 0.812540E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30883.85 | 02-JAN-15:30 | 4644.36 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 20741.78 | 01-JAN-08:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30883.85 | 01-FEB-09:09 | 4644.36 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 20741.78 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30883.85 | 01-MAR-17:30 | 4644.36 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 20741.78 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30883.85 | 03-APR-08:09 | 4644.36 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 20741.78 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28897.12 | 05-MAY-16:49 | 4644.36 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 20741.78 | 01-MAY-07:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28897.12 | 05-JUN-16:00 | 4644.36 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 20741.78 | 07-JUN-07:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28897.12 | 11-JUL-16:00 | 4644.36 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 20741.78 | 28-JUL-11:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28897.12 | 18-AUG-16:49 | 4644.36 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 18797.52 | 01-AUG-19:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30883.85 | 02-SEP-16:49 | 4644.36 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 20741.78 | 14-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30883.85 | 03-OCT-16:00 | 4644.36 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 20741.78 | 01-OCT-11:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30883.85 | 01-NOV-08:09 | 4644.36 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 20741.78 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30883.85 | 01-DEC-09:09 | 4644.36 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 20741.78 | 01-DEC-06:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 28897.12 | 4644.36 | 10771.04 | 0.00 | 18797.52 | 0.00 | 0.00 | |||||
Maximum of Months | 30883.85 | 4644.36 | 10771.04 | 0.00 | 20741.78 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 4279.69 | 31-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21176.37 | 28-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33845.51 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33760.46 | 17-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43221.09 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 52049.12 | 06-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 60647.51 | 08-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 56145.03 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50631.93 | 07-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41267.94 | 10-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24122.53 | 05-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18180.97 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 4279.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60647.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 67042.31 | 20-JAN-17:00 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 20741.78 | 0.00 | 0.00 | 1.28 | 0.00 |
February | 77191.66 | 28-FEB-17:10 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 16739.24 | 0.00 |
March | 88553.54 | 30-MAR-16:40 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 30087.85 | 0.00 |
April | 89579.05 | 17-APR-16:19 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 31113.36 | 0.00 |
May | 97623.68 | 19-MAY-16:49 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 39158.00 | 0.00 |
June | 104277.30 | 12-JUN-15:50 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 49785.08 | 0.00 |
July | 112890.40 | 07-JUL-15:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 58398.18 | 0.00 |
August | 110866.49 | 18-AUG-16:49 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 52400.81 | 0.00 |
September | 106611.78 | 07-SEP-16:30 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 48146.10 | 0.00 |
October | 99006.47 | 10-OCT-15:00 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 40540.79 | 0.00 |
November | 80611.19 | 04-NOV-16:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 20158.78 | 0.00 |
December | 75811.51 | 12-DEC-15:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 15359.10 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 67042.31 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18797.52 | 0.00 | 0.00 | 1.28 | 0.00 | |
Maximum of Months | 112890.40 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 20741.78 | 0.00 | 0.00 | 58398.18 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 179051.84 | 09-JAN-07:10 | 0.00 | 5045.34 | 27-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 201954.07 | 12-FEB-09:09 | 0.00 | 5045.39 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 33287.14 | 18-MAR-06:00 | 0.00 | 5029.69 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 25347.10 | 06-APR-06:49 | 0.00 | 4988.58 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 2083.18 | 10-MAY-11:09 | 0.00 | 4941.09 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4889.62 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4851.45 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4849.75 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 2174.60 | 28-SEP-16:00 | 0.00 | 4881.63 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 13819.60 | 26-OCT-06:00 | 0.00 | 4933.70 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 80334.33 | 22-NOV-07:30 | 0.00 | 4986.53 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 138448.10 | 04-DEC-07:10 | 0.00 | 5026.17 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4849.75 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 201954.07 | 0.00 | 5045.39 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.33 | 16.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 16.78 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 16.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 15.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 16.03 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 16.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 16.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 15.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.17 | 16.36 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 16.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.24 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.37 | 316.17 | 21.17 | 316.17 | 21.17 |
February | 376.00 | 22.10 | 177.00 | 21.29 | 177.00 | 21.29 |
March | 359.50 | 23.09 | 41.17 | 22.53 | 20.33 | 21.13 |
April | 226.50 | 23.54 | 58.67 | 23.69 | 20.83 | 23.33 |
May | 106.17 | 23.82 | 282.67 | 23.89 | 67.33 | 23.88 |
June | 40.67 | 23.91 | 350.00 | 23.89 | 32.17 | 23.92 |
July | 58.50 | 23.91 | 415.00 | 23.89 | 58.50 | 23.91 |
August | 48.33 | 23.93 | 422.00 | 23.89 | 48.33 | 23.93 |
September | 28.50 | 23.91 | 350.50 | 23.89 | 25.33 | 23.92 |
October | 235.17 | 23.59 | 111.17 | 23.89 | 39.33 | 23.89 |
November | 356.00 | 23.01 | 49.67 | 22.76 | 32.17 | 22.14 |
December | 414.00 | 21.93 | 152.00 | 21.32 | 152.00 | 21.32 |
Annual Sum or Average | 2663.33 | 22.66 | 2726.00 | 23.22 | 989.50 | 22.04 |
Minimum of Months | 28.50 | 21.37 | 41.17 | 21.17 | 20.33 | 21.13 |
Maximum of Months | 414.00 | 23.93 | 422.00 | 23.89 | 316.17 | 23.93 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.17 | 21.55 | 170.00 | 21.22 | 170.00 | 21.22 |
February | 337.00 | 22.19 | 85.50 | 21.42 | 76.00 | 21.11 |
March | 245.00 | 23.20 | 69.33 | 23.89 | 0.00 | 0.00 |
April | 79.33 | 23.39 | 187.50 | 23.89 | 6.33 | 23.89 |
May | 53.50 | 23.83 | 356.67 | 23.89 | 43.83 | 23.89 |
June | 0.33 | 23.94 | 383.50 | 23.89 | 0.17 | 24.02 |
July | 28.33 | 23.89 | 415.00 | 23.89 | 28.33 | 23.89 |
August | 14.83 | 23.91 | 422.00 | 23.89 | 14.83 | 23.91 |
September | 12.67 | 23.90 | 390.50 | 23.89 | 12.67 | 23.90 |
October | 96.50 | 23.32 | 163.50 | 23.89 | 22.50 | 23.89 |
November | 276.50 | 23.05 | 69.00 | 23.81 | 11.00 | 23.43 |
December | 385.50 | 22.21 | 47.67 | 21.98 | 40.67 | 21.66 |
Annual Sum or Average | 1942.67 | 22.51 | 2760.17 | 23.61 | 426.33 | 22.11 |
Minimum of Months | 0.33 | 21.55 | 47.67 | 21.22 | 0.00 | 0.00 |
Maximum of Months | 413.17 | 23.94 | 422.00 | 23.89 | 170.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 395.17 | 22.03 | 126.00 | 21.11 | 126.00 | 21.11 |
February | 285.67 | 22.21 | 81.00 | 21.40 | 72.50 | 21.11 |
March | 211.50 | 23.14 | 90.67 | 23.71 | 6.00 | 21.11 |
April | 116.67 | 23.43 | 181.83 | 23.87 | 7.33 | 23.50 |
May | 60.33 | 23.79 | 334.67 | 23.89 | 41.17 | 23.89 |
June | 31.00 | 23.91 | 373.67 | 23.89 | 26.00 | 23.91 |
July | 42.67 | 23.91 | 415.00 | 23.89 | 42.67 | 23.91 |
August | 25.67 | 23.93 | 422.00 | 23.89 | 25.67 | 23.93 |
September | 12.50 | 23.91 | 391.67 | 23.89 | 11.17 | 23.92 |
October | 89.50 | 23.41 | 238.00 | 23.89 | 26.83 | 23.89 |
November | 186.67 | 23.22 | 96.00 | 23.75 | 9.83 | 22.57 |
December | 348.17 | 22.71 | 68.83 | 22.46 | 39.67 | 21.41 |
Annual Sum or Average | 1805.50 | 22.78 | 2819.33 | 23.65 | 434.83 | 22.33 |
Minimum of Months | 12.50 | 22.03 | 68.83 | 21.11 | 6.00 | 21.11 |
Maximum of Months | 395.17 | 23.93 | 422.00 | 23.89 | 126.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.17 | 21.52 | 190.00 | 21.18 | 190.00 | 21.18 |
February | 333.17 | 21.90 | 117.17 | 21.18 | 117.17 | 21.18 |
March | 282.83 | 22.73 | 77.67 | 23.35 | 15.17 | 21.11 |
April | 177.83 | 23.08 | 140.83 | 23.79 | 16.83 | 23.08 |
May | 102.50 | 23.61 | 300.33 | 23.88 | 63.50 | 23.87 |
June | 47.83 | 23.84 | 355.83 | 23.89 | 38.67 | 23.90 |
July | 68.50 | 23.90 | 415.00 | 23.89 | 68.50 | 23.90 |
August | 51.50 | 23.92 | 422.00 | 23.89 | 51.50 | 23.92 |
September | 33.50 | 23.81 | 378.83 | 23.89 | 27.17 | 23.90 |
October | 148.67 | 22.94 | 199.00 | 23.89 | 33.83 | 23.87 |
November | 245.17 | 22.66 | 76.67 | 23.61 | 17.17 | 22.65 |
December | 384.00 | 22.02 | 92.00 | 21.86 | 75.50 | 21.42 |
Annual Sum or Average | 2288.67 | 22.45 | 2765.33 | 23.49 | 715.00 | 22.36 |
Minimum of Months | 33.50 | 21.52 | 76.67 | 21.18 | 15.17 | 21.11 |
Maximum of Months | 413.17 | 23.92 | 422.00 | 23.89 | 190.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.35043 | 29.25988 | -0.5655 | 12.96243 |
February | 376.00000 | 22.08544 | 30.62161 | -0.3484 | 10.28838 |
March | 422.00000 | 23.18855 | 36.11347 | 0.02314 | 6.72431 |
April | 405.00000 | 23.68607 | 42.86773 | 0.23927 | 7.05387 |
May | 418.00000 | 23.88105 | 51.46863 | -0.4951 | 10.44963 |
June | 408.00000 | 23.91138 | 52.02907 | -0.3801 | 8.20287 |
July | 415.00000 | 23.91449 | 57.02294 | -0.3148 | 7.12922 |
August | 422.00000 | 23.91476 | 56.84506 | -0.3059 | 7.02107 |
September | 405.00000 | 23.90949 | 54.15110 | -0.4092 | 8.62513 |
October | 414.00000 | 23.72172 | 46.21396 | 0.29413 | 7.44999 |
November | 399.00000 | 23.09652 | 36.02580 | 0.00778 | 6.83978 |
December | 415.00000 | 21.92321 | 33.45012 | -0.3471 | 9.42643 |
Annual Sum or Average | 4913.00000 | 23.22289 | 43.95347 | -0.2168 | 8.50480 |
Minimum of Months | 376.00000 | 21.35043 | 29.25988 | -0.5655 | 6.72431 |
Maximum of Months | 422.00000 | 23.91476 | 57.02294 | 0.29413 | 12.96243 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.55019 | 26.97325 | -0.4190 | 10.11831 |
February | 376.00000 | 22.36038 | 28.62241 | -0.1756 | 8.45841 |
March | 422.00000 | 23.49374 | 33.74235 | 0.20047 | 6.94104 |
April | 405.00000 | 23.80541 | 40.65035 | 0.36841 | 8.32191 |
May | 418.00000 | 23.90205 | 49.05503 | -0.3793 | 8.22472 |
June | 408.00000 | 23.91161 | 50.40342 | -0.3036 | 7.08536 |
July | 415.00000 | 23.91360 | 55.94693 | -0.2508 | 6.38900 |
August | 422.00000 | 23.91379 | 56.51856 | -0.2442 | 6.31583 |
September | 405.00000 | 23.91099 | 53.20629 | -0.3396 | 7.52508 |
October | 414.00000 | 23.76920 | 44.51888 | 0.38053 | 8.48892 |
November | 399.00000 | 23.31470 | 34.34740 | 0.14505 | 6.85310 |
December | 415.00000 | 22.33476 | 31.15213 | -0.1629 | 7.47146 |
Annual Sum or Average | 4913.00000 | 23.35507 | 42.21089 | -0.0987 | 7.67584 |
Minimum of Months | 376.00000 | 21.55019 | 26.97325 | -0.4190 | 6.31583 |
Maximum of Months | 422.00000 | 23.91379 | 56.51856 | 0.38053 | 10.11831 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.10145 | 25.43185 | -0.2977 | 9.29338 |
February | 376.00000 | 22.59826 | 27.20916 | -0.1228 | 8.53006 |
March | 422.00000 | 23.50961 | 32.48259 | 0.20695 | 7.40133 |
April | 405.00000 | 23.75928 | 40.05151 | 0.34333 | 8.27149 |
May | 418.00000 | 23.89055 | 48.23510 | -0.3951 | 8.62463 |
June | 408.00000 | 23.91068 | 49.45963 | -0.2881 | 6.96864 |
July | 415.00000 | 23.91313 | 54.32255 | -0.2211 | 6.11503 |
August | 422.00000 | 23.91303 | 53.42557 | -0.1935 | 5.88104 |
September | 405.00000 | 23.91065 | 50.58597 | -0.2859 | 6.90962 |
October | 414.00000 | 23.79441 | 42.87168 | 0.42405 | 9.40033 |
November | 399.00000 | 23.57603 | 32.22153 | 0.24166 | 7.45417 |
December | 415.00000 | 22.88928 | 28.72023 | -0.0266 | 7.35282 |
Annual Sum or Average | 4913.00000 | 23.48629 | 40.53138 | -0.0517 | 7.67589 |
Minimum of Months | 376.00000 | 22.10145 | 25.43185 | -0.3951 | 5.88104 |
Maximum of Months | 422.00000 | 23.91313 | 54.32255 | 0.42405 | 9.40033 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.51022 | 26.54534 | -0.4482 | 10.86231 |
February | 376.00000 | 22.10794 | 28.50082 | -0.2549 | 9.36064 |
March | 422.00000 | 23.10067 | 34.23900 | 0.08997 | 7.27930 |
April | 405.00000 | 23.52846 | 41.79619 | 0.26330 | 7.72003 |
May | 418.00000 | 23.82500 | 50.27349 | -0.4602 | 10.08218 |
June | 408.00000 | 23.90211 | 51.23723 | -0.3319 | 7.58539 |
July | 415.00000 | 23.91264 | 56.75192 | -0.2562 | 6.45572 |
August | 422.00000 | 23.91367 | 55.87697 | -0.2288 | 6.18570 |
September | 405.00000 | 23.89918 | 52.70352 | -0.3294 | 7.51925 |
October | 414.00000 | 23.55330 | 44.65049 | 0.34519 | 8.67326 |
November | 399.00000 | 23.12407 | 34.09992 | 0.12012 | 7.32244 |
December | 415.00000 | 22.15029 | 30.64554 | -0.2045 | 8.24986 |
Annual Sum or Average | 4913.00000 | 23.21813 | 42.39520 | -0.1414 | 8.09997 |
Minimum of Months | 376.00000 | 21.51022 | 26.54534 | -0.4602 | 6.18570 |
Maximum of Months | 422.00000 | 23.91367 | 56.75192 | 0.34519 | 10.86231 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 10588.57 | 3000.33 | 4.61 | 7951.16 | 2637.41 | 0.00 | 0.00 | 20-JAN-15:10 | 0.00 | 01-JAN-00:10 | 1.29 | 20-JAN-15:10 | 0.94 | 20-JAN-15:10 | 0.35 | 20-JAN-15:10 | 0.36 | 20-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.250470E+09 | 71061498.16 | 41.81 | 0.250467E+09 | 2785.09 | 0.00 | 0.28 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 | 8080.44 | 28-FEB-15:00 | 8080.44 | 28-FEB-15:00 | 2.69 | 16-FEB-15:50 | 2282.49 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.156587E+10 | 0.433915E+09 | 156.74 | 0.126376E+10 | 0.302108E+09 | 0.00 | 0.86 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 | 31285.26 | 31-MAR-06:02 | 18056.05 | 31-MAR-06:02 | 13229.22 | 31-MAR-06:02 | 6964.48 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.555068E+10 | 0.153965E+10 | 261.84 | 0.466623E+10 | 0.884455E+09 | 0.00 | 1.00 | 19-APR-06:02 | 0.00 | 01-APR-00:10 | 37136.63 | 19-APR-06:02 | 23369.88 | 19-APR-06:02 | 13766.75 | 19-APR-06:02 | 7908.42 | 19-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.129019E+11 | 0.351027E+10 | 343.66 | 0.990572E+10 | 0.299619E+10 | 0.00 | 1.00 | 04-MAY-06:02 | 0.00 | 01-MAY-00:10 | 40115.97 | 31-MAY-06:02 | 27015.00 | 17-MAY-06:02 | 21354.77 | 26-MAY-06:02 | 8408.62 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.231929E+11 | 0.632591E+10 | 402.04 | 0.173918E+11 | 0.580114E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 41522.59 | 29-JUN-06:02 | 35897.57 | 11-JUN-08:62 | 23785.50 | 23-JUN-06:04 | 8698.85 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.275377E+11 | 0.745751E+10 | 422.71 | 0.196127E+11 | 0.792502E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 42098.59 | 27-JUL-06:02 | 27605.38 | 18-JUL-06:02 | 26028.95 | 27-JUL-06:04 | 8885.15 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.301356E+11 | 0.805513E+10 | 440.88 | 0.210962E+11 | 0.903945E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 42333.10 | 12-AUG-06:02 | 27194.23 | 27-AUG-08:62 | 26328.60 | 21-AUG-06:02 | 8809.95 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.179825E+11 | 0.477730E+10 | 378.07 | 0.130258E+11 | 0.495674E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 42230.70 | 17-SEP-08:62 | 29702.34 | 09-SEP-06:02 | 23042.63 | 03-SEP-08:04 | 8738.55 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.540605E+10 | 0.143870E+10 | 238.32 | 0.393129E+10 | 0.147476E+10 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 41169.22 | 19-OCT-06:02 | 21562.47 | 11-OCT-06:02 | 24617.09 | 19-OCT-06:02 | 8512.64 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.706926E+09 | 0.192779E+09 | 111.14 | 0.508683E+09 | 0.198244E+09 | 0.00 | 0.99 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 | 37361.37 | 04-NOV-06:02 | 20932.92 | 04-NOV-06:02 | 16428.45 | 04-NOV-06:02 | 7978.41 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 55969312.38 | 15593376.18 | 14.45 | 41606539.80 | 14362772.58 | 0.00 | 0.16 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 4754.24 | 12-DEC-15:10 | 3696.96 | 12-DEC-15:10 | 1320.61 | 12-DEC-14:00 | 1321.51 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.125287E+12 | 0.338178E+11 | 2816.27 | 0.916942E+11 | 0.335925E+11 | 0.00 | ||||||||||||||
Minimum of Months | 10588.57 | 3000.33 | 4.61 | 7951.16 | 2637.41 | 0.00 | 0.00 | 0.00 | 1.29 | 0.94 | 0.35 | 0.36 | 0.00 | |||||||
Maximum of Months | 0.301356E+11 | 0.805513E+10 | 440.88 | 0.210962E+11 | 0.903945E+10 | 0.00 | 1.00 | 0.00 | 42333.10 | 35897.57 | 26328.60 | 8885.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 74753837.62 | 23360294.24 | 18.36 | 63299913.78 | 11453923.84 | 0.00 | 0.08 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 10750.25 | 31-JAN-15:10 | 9374.33 | 31-JAN-15:10 | 1375.92 | 31-JAN-15:10 | 3340.04 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.302190E+10 | 0.934413E+09 | 78.52 | 0.300537E+10 | 16534419.41 | 0.00 | 0.33 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 | 47397.41 | 28-FEB-15:00 | 47397.41 | 28-FEB-15:00 | 1321.94 | 22-FEB-15:00 | 14740.86 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.138706E+11 | 0.419150E+10 | 215.22 | 0.109107E+11 | 0.295990E+10 | 0.00 | 1.00 | 09-MAR-07:03 | 0.00 | 01-MAR-00:10 | 188070.27 | 30-MAR-06:02 | 122226.47 | 14-MAR-06:03 | 77169.20 | 30-MAR-06:02 | 44614.77 | 30-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.404687E+11 | 0.122426E+11 | 294.55 | 0.329677E+11 | 0.750098E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 191534.12 | 23-APR-08:62 | 146270.60 | 01-APR-06:02 | 93377.48 | 23-APR-08:62 | 45241.05 | 23-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.785757E+11 | 0.234748E+11 | 373.54 | 0.583819E+11 | 0.201938E+11 | 0.00 | 1.00 | 01-MAY-06:02 | 0.00 | 01-MAY-00:10 | 196318.19 | 26-MAY-06:02 | 158791.61 | 10-MAY-06:02 | 101985.50 | 26-MAY-06:04 | 45953.81 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.123247E+12 | 0.370295E+11 | 421.50 | 0.886322E+11 | 0.346148E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 197428.59 | 23-JUN-06:02 | 168317.02 | 11-JUN-08:62 | 97185.20 | 21-JUN-06:04 | 47126.07 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.144573E+12 | 0.430101E+11 | 436.98 | 0.969971E+11 | 0.475755E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 201526.79 | 30-JUL-08:62 | 139643.54 | 25-JUL-06:02 | 107839.06 | 28-JUL-06:04 | 48411.87 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.153506E+12 | 0.451989E+11 | 447.67 | 0.100710E+12 | 0.527957E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 201779.08 | 20-AUG-08:62 | 147185.02 | 26-AUG-06:02 | 106895.76 | 23-AUG-06:04 | 47985.00 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.956236E+11 | 0.280854E+11 | 394.07 | 0.652896E+11 | 0.303340E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 201758.83 | 17-SEP-08:62 | 139314.23 | 16-SEP-06:02 | 90696.17 | 11-SEP-06:02 | 47551.07 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.356059E+11 | 0.104651E+11 | 269.01 | 0.254792E+11 | 0.101268E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 200214.59 | 19-OCT-06:02 | 137444.92 | 12-OCT-06:02 | 112242.80 | 19-OCT-06:04 | 46394.49 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.792088E+10 | 0.237535E+10 | 149.01 | 0.587058E+10 | 0.205030E+10 | 0.00 | 1.00 | 02-NOV-06:03 | 0.00 | 01-NOV-00:10 | 186585.53 | 04-NOV-06:02 | 109728.84 | 10-NOV-07:03 | 81454.23 | 05-NOV-08:62 | 44319.58 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.117061E+10 | 0.354458E+09 | 38.77 | 0.793152E+09 | 0.377461E+09 | 0.00 | 1.00 | 13-DEC-07:03 | 0.00 | 01-DEC-00:10 | 186524.43 | 13-DEC-07:03 | 107889.01 | 13-DEC-07:03 | 78635.43 | 13-DEC-07:03 | 44307.10 | 13-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.697658E+12 | 0.207385E+12 | 3137.19 | 0.489101E+12 | 0.208557E+12 | 0.00 | ||||||||||||||
Minimum of Months | 74753837.62 | 23360294.24 | 18.36 | 63299913.78 | 11453923.84 | 0.00 | 0.08 | 0.00 | 10750.25 | 9374.33 | 1321.94 | 3340.04 | 0.00 | |||||||
Maximum of Months | 0.153506E+12 | 0.451989E+11 | 447.67 | 0.100710E+12 | 0.527957E+11 | 0.00 | 1.00 | 0.00 | 201779.08 | 168317.02 | 112242.80 | 48411.87 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 30381090.18 | 8366693.63 | 38.69 | 26215205.72 | 4165884.45 | 0.00 | 0.16 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 2776.02 | 31-JAN-15:00 | 2552.93 | 31-JAN-15:00 | 307.05 | 31-JAN-13:53 | 755.92 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.725441E+09 | 0.194444E+09 | 91.98 | 0.723859E+09 | 1581753.19 | 0.00 | 0.47 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 | 9086.14 | 28-FEB-15:00 | 9086.14 | 28-FEB-15:00 | 195.93 | 22-FEB-15:10 | 2433.08 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.226639E+10 | 0.604762E+09 | 229.57 | 0.187367E+10 | 0.392713E+09 | 0.00 | 1.00 | 30-MAR-06:02 | 0.00 | 01-MAR-00:10 | 24285.87 | 30-MAR-06:02 | 14076.54 | 30-MAR-06:02 | 10237.11 | 31-MAR-06:02 | 5156.26 | 30-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.542535E+10 | 0.146457E+10 | 289.34 | 0.459506E+10 | 0.830292E+09 | 0.00 | 1.00 | 18-APR-06:02 | 0.00 | 01-APR-00:10 | 24031.94 | 22-APR-06:02 | 18133.89 | 16-APR-08:62 | 11437.36 | 23-APR-08:62 | 5110.38 | 22-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.100295E+11 | 0.268973E+10 | 361.36 | 0.782557E+10 | 0.220396E+10 | 0.00 | 1.00 | 03-MAY-06:02 | 0.00 | 01-MAY-00:10 | 25348.67 | 31-MAY-06:02 | 16842.59 | 17-MAY-06:02 | 13226.03 | 31-MAY-06:02 | 5312.25 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.158291E+11 | 0.428512E+10 | 402.85 | 0.119584E+11 | 0.387066E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 26252.66 | 29-JUN-06:02 | 22465.74 | 11-JUN-08:62 | 15189.32 | 23-JUN-06:02 | 5515.87 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.186896E+11 | 0.502272E+10 | 425.87 | 0.133311E+11 | 0.535853E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 26750.76 | 26-JUL-06:02 | 17675.33 | 15-JUL-05:03 | 16712.99 | 26-JUL-06:02 | 5605.88 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.209859E+11 | 0.554838E+10 | 445.53 | 0.148633E+11 | 0.612269E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 27216.04 | 20-AUG-07:03 | 17691.25 | 10-AUG-05:03 | 15498.34 | 29-AUG-06:02 | 5561.25 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.138576E+11 | 0.361596E+10 | 388.40 | 0.102762E+11 | 0.358135E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 26767.62 | 17-SEP-08:62 | 18688.98 | 09-SEP-06:02 | 15636.37 | 17-SEP-08:62 | 5520.30 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.604195E+10 | 0.156164E+10 | 280.11 | 0.474073E+10 | 0.130122E+10 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 25984.24 | 19-OCT-06:02 | 15694.70 | 09-OCT-08:62 | 15496.52 | 19-OCT-06:02 | 5375.17 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.199947E+10 | 0.524287E+09 | 186.28 | 0.163671E+10 | 0.362753E+09 | 0.00 | 1.00 | 03-NOV-06:02 | 0.00 | 01-NOV-00:10 | 24004.13 | 04-NOV-06:02 | 14065.07 | 03-NOV-06:02 | 10473.75 | 04-NOV-06:02 | 5105.17 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.384075E+09 | 0.100395E+09 | 98.99 | 0.277758E+09 | 0.106317E+09 | 0.00 | 1.00 | 13-DEC-07:03 | 0.00 | 01-DEC-00:10 | 24068.06 | 13-DEC-07:03 | 13761.29 | 13-DEC-07:03 | 10306.77 | 13-DEC-07:03 | 5117.10 | 13-DEC-07:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.962648E+11 | 0.256204E+11 | 3238.97 | 0.721285E+11 | 0.241362E+11 | 0.00 | ||||||||||||||
Minimum of Months | 30381090.18 | 8366693.63 | 38.69 | 26215205.72 | 1581753.19 | 0.00 | 0.16 | 0.00 | 2776.02 | 2552.93 | 195.93 | 755.92 | 0.00 | |||||||
Maximum of Months | 0.209859E+11 | 0.554838E+10 | 445.53 | 0.148633E+11 | 0.612269E+10 | 0.00 | 1.00 | 0.00 | 27216.04 | 22465.74 | 16712.99 | 5605.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 3385194.15 | 950052.87 | 12.92 | 2948505.60 | 436688.55 | 0.00 | 0.05 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 749.83 | 31-JAN-15:00 | 669.50 | 31-JAN-15:00 | 84.91 | 31-JAN-14:50 | 209.72 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.422631E+09 | 0.114874E+09 | 63.35 | 0.422110E+09 | 521049.15 | 0.00 | 0.41 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 6325.29 | 28-FEB-15:10 | 6325.29 | 28-FEB-15:10 | 51.66 | 22-FEB-14:30 | 1719.93 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.131597E+10 | 0.356788E+09 | 174.31 | 0.105473E+10 | 0.261244E+09 | 0.00 | 1.00 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 | 19796.48 | 31-MAR-06:02 | 11184.51 | 31-MAR-06:02 | 8611.97 | 31-MAR-06:02 | 4207.11 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.339901E+10 | 0.934058E+09 | 249.98 | 0.281302E+10 | 0.585996E+09 | 0.00 | 0.81 | 19-APR-06:02 | 0.00 | 01-APR-00:10 | 14677.98 | 19-APR-06:02 | 9000.82 | 19-APR-06:02 | 5677.16 | 19-APR-06:02 | 3322.38 | 19-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.688939E+10 | 0.186957E+10 | 337.01 | 0.516272E+10 | 0.172667E+10 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 20793.14 | 31-MAY-06:02 | 13466.63 | 17-MAY-06:02 | 11247.25 | 26-MAY-06:02 | 4356.80 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.123660E+11 | 0.334896E+10 | 395.15 | 0.888986E+10 | 0.347610E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 21507.22 | 29-JUN-06:02 | 17910.53 | 11-JUN-08:62 | 12456.32 | 23-JUN-06:04 | 4521.45 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.149355E+11 | 0.400070E+10 | 419.05 | 0.101236E+11 | 0.481187E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 21815.21 | 27-JUL-06:02 | 13337.26 | 15-JUL-06:02 | 13581.78 | 27-JUL-06:02 | 4606.81 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.170301E+11 | 0.447917E+10 | 442.06 | 0.113933E+11 | 0.563681E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 21934.96 | 12-AUG-06:02 | 13132.78 | 26-AUG-06:02 | 13756.39 | 21-AUG-06:02 | 4566.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.105647E+11 | 0.276236E+10 | 376.30 | 0.743139E+10 | 0.313336E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 21930.39 | 17-SEP-08:62 | 14394.31 | 09-SEP-06:02 | 12830.04 | 17-SEP-08:62 | 4526.29 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.430700E+10 | 0.111982E+10 | 241.23 | 0.323069E+10 | 0.107631E+10 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 21331.97 | 19-OCT-06:02 | 12562.34 | 09-OCT-08:62 | 12846.10 | 19-OCT-06:02 | 4409.47 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.104089E+10 | 0.277295E+09 | 140.69 | 0.836111E+09 | 0.204774E+09 | 0.00 | 0.87 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 | 16291.55 | 04-NOV-06:02 | 8949.15 | 04-NOV-06:02 | 7342.39 | 04-NOV-06:02 | 3620.44 | 04-NOV-06:02 | 0.00 | 01-NOV-00:10 |
December | 0.177075E+09 | 47157507.17 | 41.80 | 0.123715E+09 | 53359747.18 | 0.00 | 0.45 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7536.71 | 12-DEC-14:00 | 5504.64 | 12-DEC-14:00 | 2072.89 | 12-DEC-13:50 | 1934.89 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.724517E+11 | 0.193117E+11 | 2893.86 | 0.514842E+11 | 0.209675E+11 | 0.00 | ||||||||||||||
Minimum of Months | 3385194.15 | 950052.87 | 12.92 | 2948505.60 | 436688.55 | 0.00 | 0.05 | 0.00 | 749.83 | 669.50 | 51.66 | 209.72 | 0.00 | |||||||
Maximum of Months | 0.170301E+11 | 0.447917E+10 | 442.06 | 0.113933E+11 | 0.563681E+10 | 0.00 | 1.00 | 0.00 | 21934.96 | 17910.53 | 13756.39 | 4606.81 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 58.46 | 78.14 | 0.50 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 84.18 | 68.77 | 0.00 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 136.68 | 50.27 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 185.41 | 41.46 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 213.98 | 29.10 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.17 | 22.16 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 225.69 | 17.31 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.20 | 16.60 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 146.77 | 27.83 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.28 | 48.05 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 76.71 | 61.59 | 4.00 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 55.20 | 71.41 | 6.50 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 145.80 | 44.26 | 11.00 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 55.20 | 16.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.17 | 78.14 | 6.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 971.35 | 938.96 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 957.41 | 819.90 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 862.89 | 589.14 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 658.83 | 480.40 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 575.60 | 322.06 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 672.26 | 219.04 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 715.48 | 163.64 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 846.64 | 148.03 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 797.71 | 292.60 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1068.46 | 572.12 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1077.54 | 719.89 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1019.30 | 839.29 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 851.64 | 507.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 575.60 | 148.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1077.54 | 938.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 981.95 | 909.09 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 964.44 | 789.86 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 870.26 | 560.07 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 661.95 | 456.70 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 574.92 | 304.11 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 669.00 | 204.87 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 712.35 | 150.38 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 842.81 | 134.57 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 795.01 | 277.86 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1069.59 | 548.88 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1084.14 | 689.93 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1030.38 | 799.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 854.40 | 483.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 574.92 | 134.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1084.14 | 909.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 178.22 | 124.27 | 53.95 | 197.03 | 186.28 | 0.00 | 0.00 | 744.00 |
February | 166.34 | 111.51 | 54.83 | 194.78 | 160.64 | 0.00 | 0.00 | 672.00 |
March | 149.54 | 77.92 | 71.62 | 178.64 | 110.61 | 0.00 | 0.00 | 744.00 |
April | 111.97 | 36.42 | 75.55 | 134.05 | 91.05 | 0.00 | 0.00 | 720.00 |
May | 90.47 | 10.48 | 79.98 | 112.08 | 61.95 | 0.00 | 0.00 | 744.00 |
June | 83.64 | 4.62 | 79.02 | 116.99 | 46.22 | 0.00 | 0.00 | 720.00 |
July | 84.56 | 6.28 | 78.29 | 122.07 | 36.02 | 0.00 | 0.00 | 744.00 |
August | 100.97 | 18.84 | 82.13 | 147.31 | 34.41 | 0.00 | 0.00 | 744.00 |
September | 111.05 | 41.28 | 69.76 | 152.24 | 59.78 | 0.00 | 0.00 | 720.00 |
October | 161.04 | 104.33 | 56.72 | 217.73 | 109.47 | 0.00 | 0.00 | 744.00 |
November | 173.29 | 115.01 | 58.28 | 222.49 | 135.81 | 0.00 | 0.00 | 720.00 |
December | 175.67 | 123.60 | 52.08 | 208.60 | 161.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 132.08 | 64.33 | 67.76 | 166.89 | 99.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 83.64 | 4.62 | 52.08 | 112.08 | 34.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 178.22 | 124.27 | 82.13 | 222.49 | 186.28 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.156585E+09 | 0.209279E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.203652E+09 | 0.166358E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.366071E+09 | 0.134637E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.480573E+09 | 0.107468E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.573137E+09 | 77948644.32 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.617347E+09 | 57450383.04 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.604491E+09 | 46355201.75 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.560330E+09 | 44469826.07 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.380419E+09 | 72128506.12 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.308778E+09 | 0.128694E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.198821E+09 | 0.159649E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 0.191262E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.459804E+10 | 0.139570E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.147838E+09 | 44469826.07 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.617347E+09 | 0.209279E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.260166E+10 | 0.251492E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.231617E+10 | 0.198350E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.231115E+10 | 0.157794E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.170769E+10 | 0.124519E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.154167E+10 | 0.862615E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.174250E+10 | 0.567743E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.191633E+10 | 0.438290E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.226764E+10 | 0.396494E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.206766E+10 | 0.758424E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.286177E+10 | 0.153237E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.279297E+10 | 0.186596E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.273008E+10 | 0.224797E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.268573E+11 | 0.159914E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.154167E+10 | 0.396494E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.286177E+10 | 0.251492E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.263005E+10 | 0.243489E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.233318E+10 | 0.191083E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.233089E+10 | 0.150009E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.171577E+10 | 0.118376E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.153988E+10 | 0.814520E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.173405E+10 | 0.531015E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.190795E+10 | 0.402775E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.225739E+10 | 0.360436E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.206066E+10 | 0.720210E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.286480E+10 | 0.147011E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.281009E+10 | 0.178829E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.275977E+10 | 0.214068E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.269445E+11 | 0.152576E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.153988E+10 | 0.360436E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.286480E+10 | 0.243489E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.527738E+09 | 0.498941E+09 |
February | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.471206E+09 | 0.388616E+09 |
March | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.478458E+09 | 0.296261E+09 |
April | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.347455E+09 | 0.235991E+09 |
May | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.300195E+09 | 0.165928E+09 |
June | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.303234E+09 | 0.119799E+09 |
July | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.326963E+09 | 96488262.18 |
August | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.394555E+09 | 92156257.48 |
September | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.394608E+09 | 0.154962E+09 |
October | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.583160E+09 | 0.293207E+09 |
November | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.576702E+09 | 0.352017E+09 |
December | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.558723E+09 | 0.431654E+09 |
Annual Sum or Average | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.526300E+10 | 0.312602E+10 |
Minimum of Months | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.300195E+09 | 92156257.48 |
Maximum of Months | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.583160E+09 | 0.498941E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 935.39 | 1250.17 | 1031.27 | 569.97 | 461.30 | 0.00 | 0.00 |
February | 1346.90 | 1100.25 | 1288.74 | 798.05 | 490.69 | 0.00 | 0.00 |
March | 2186.81 | 804.29 | 1870.04 | 1141.75 | 728.29 | 0.00 | 0.00 |
April | 2966.50 | 663.38 | 2352.40 | 1449.70 | 902.70 | 0.00 | 0.00 |
May | 3423.76 | 465.64 | 2605.60 | 1494.90 | 1110.70 | 0.00 | 0.00 |
June | 3810.78 | 354.63 | 2780.26 | 1627.12 | 1153.14 | 0.00 | 0.00 |
July | 3611.05 | 276.91 | 2588.82 | 1453.64 | 1135.18 | 0.00 | 0.00 |
August | 3347.25 | 265.65 | 2382.58 | 1292.88 | 1089.69 | 0.00 | 0.00 |
September | 2348.27 | 445.24 | 1783.29 | 990.62 | 792.67 | 0.00 | 0.00 |
October | 1844.55 | 768.78 | 1529.27 | 1027.48 | 501.78 | 0.00 | 0.00 |
November | 1227.29 | 985.49 | 1139.03 | 644.86 | 494.17 | 0.00 | 0.00 |
December | 883.14 | 1142.54 | 932.35 | 508.14 | 424.21 | 0.00 | 0.00 |
Annual Sum or Average | 2332.85 | 708.12 | 1859.92 | 1084.56 | 775.36 | 0.00 | 0.00 |
Minimum of Months | 883.14 | 265.65 | 932.35 | 508.14 | 424.21 | 0.00 | 0.00 |
Maximum of Months | 3810.78 | 1250.17 | 2780.26 | 1627.12 | 1153.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 971.35 | 938.96 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 957.41 | 819.90 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 862.89 | 589.14 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 658.83 | 480.40 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 575.60 | 322.06 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 672.26 | 219.04 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 715.48 | 163.64 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 846.64 | 148.03 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 797.71 | 292.60 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1068.46 | 572.12 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1077.54 | 719.89 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1019.30 | 839.29 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 851.64 | 507.08 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 575.60 | 148.03 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1077.54 | 938.96 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 981.95 | 909.09 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 964.44 | 789.86 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 870.26 | 560.07 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 661.95 | 456.70 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 574.92 | 304.11 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 669.00 | 204.87 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 712.35 | 150.38 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 842.81 | 134.57 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 795.01 | 277.86 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1069.59 | 548.88 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1084.14 | 689.93 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1030.38 | 799.24 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 854.40 | 483.82 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 574.92 | 134.57 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1084.14 | 909.09 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 197.03 | 186.28 | 178.22 | 124.27 | 53.95 | 0.00 | 0.00 |
February | 194.78 | 160.64 | 166.34 | 111.51 | 54.83 | 0.00 | 0.00 |
March | 178.64 | 110.61 | 149.54 | 77.92 | 71.62 | 0.00 | 0.00 |
April | 134.05 | 91.05 | 111.97 | 36.42 | 75.55 | 0.00 | 0.00 |
May | 112.08 | 61.95 | 90.47 | 10.48 | 79.98 | 0.00 | 0.00 |
June | 116.99 | 46.22 | 83.64 | 4.62 | 79.02 | 0.00 | 0.00 |
July | 122.07 | 36.02 | 84.56 | 6.28 | 78.29 | 0.00 | 0.00 |
August | 147.31 | 34.41 | 100.97 | 18.84 | 82.13 | 0.00 | 0.00 |
September | 152.24 | 59.78 | 111.05 | 41.28 | 69.76 | 0.00 | 0.00 |
October | 217.73 | 109.47 | 161.04 | 104.33 | 56.72 | 0.00 | 0.00 |
November | 222.49 | 135.81 | 173.29 | 115.01 | 58.28 | 0.00 | 0.00 |
December | 208.60 | 161.16 | 175.67 | 123.60 | 52.08 | 0.00 | 0.00 |
Annual Sum or Average | 166.89 | 99.13 | 132.08 | 64.33 | 67.76 | 0.00 | 0.00 |
Minimum of Months | 112.08 | 34.41 | 83.64 | 4.62 | 52.08 | 0.00 | 0.00 |
Maximum of Months | 222.49 | 186.28 | 178.22 | 124.27 | 82.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250535E+10 | 0.334846E+10 | 0.276216E+10 | 0.152662E+10 | 0.123554E+10 | 0.00 | 0.00 |
February | 0.325843E+10 | 0.266173E+10 | 0.311773E+10 | 0.193065E+10 | 0.118708E+10 | 0.00 | 0.00 |
March | 0.585714E+10 | 0.215420E+10 | 0.500872E+10 | 0.305806E+10 | 0.195066E+10 | 0.00 | 0.00 |
April | 0.768916E+10 | 0.171949E+10 | 0.609743E+10 | 0.375763E+10 | 0.233980E+10 | 0.00 | 0.00 |
May | 0.917019E+10 | 0.124718E+10 | 0.697884E+10 | 0.400395E+10 | 0.297490E+10 | 0.00 | 0.00 |
June | 0.987755E+10 | 0.919206E+09 | 0.720643E+10 | 0.421748E+10 | 0.298895E+10 | 0.00 | 0.00 |
July | 0.967185E+10 | 0.741683E+09 | 0.693388E+10 | 0.389342E+10 | 0.304046E+10 | 0.00 | 0.00 |
August | 0.896528E+10 | 0.711517E+09 | 0.638149E+10 | 0.346285E+10 | 0.291864E+10 | 0.00 | 0.00 |
September | 0.608671E+10 | 0.115406E+10 | 0.462229E+10 | 0.256769E+10 | 0.205460E+10 | 0.00 | 0.00 |
October | 0.494045E+10 | 0.205910E+10 | 0.409599E+10 | 0.275201E+10 | 0.134397E+10 | 0.00 | 0.00 |
November | 0.318114E+10 | 0.255438E+10 | 0.295238E+10 | 0.167148E+10 | 0.128089E+10 | 0.00 | 0.00 |
December | 0.236541E+10 | 0.306018E+10 | 0.249720E+10 | 0.136100E+10 | 0.113620E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.735687E+11 | 0.223312E+11 | 0.586545E+11 | 0.342028E+11 | 0.244517E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236541E+10 | 0.711517E+09 | 0.249720E+10 | 0.136100E+10 | 0.113620E+10 | 0.00 | 0.00 |
Maximum of Months | 0.987755E+10 | 0.334846E+10 | 0.720643E+10 | 0.421748E+10 | 0.304046E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.260166E+10 | 0.251492E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.231617E+10 | 0.198350E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.231115E+10 | 0.157794E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.170769E+10 | 0.124519E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.154167E+10 | 0.862615E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.174250E+10 | 0.567743E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.191633E+10 | 0.438290E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.226764E+10 | 0.396494E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.206766E+10 | 0.758424E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.286177E+10 | 0.153237E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.279297E+10 | 0.186596E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.273008E+10 | 0.224797E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.268573E+11 | 0.159914E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154167E+10 | 0.396494E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.286177E+10 | 0.251492E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.263005E+10 | 0.243489E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.233318E+10 | 0.191083E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.233089E+10 | 0.150009E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.171577E+10 | 0.118376E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.153988E+10 | 0.814520E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.173405E+10 | 0.531015E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.190795E+10 | 0.402775E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.225739E+10 | 0.360436E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.206066E+10 | 0.720210E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.286480E+10 | 0.147011E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.281009E+10 | 0.178829E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.275977E+10 | 0.214068E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.269445E+11 | 0.152576E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.153988E+10 | 0.360436E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.286480E+10 | 0.243489E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.527738E+09 | 0.498941E+09 | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.00 | 0.00 |
February | 0.471206E+09 | 0.388616E+09 | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.00 | 0.00 |
March | 0.478458E+09 | 0.296261E+09 | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.00 | 0.00 |
April | 0.347455E+09 | 0.235991E+09 | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.00 | 0.00 |
May | 0.300195E+09 | 0.165928E+09 | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.00 | 0.00 |
June | 0.303234E+09 | 0.119799E+09 | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.00 | 0.00 |
July | 0.326963E+09 | 96488262.18 | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.00 | 0.00 |
August | 0.394555E+09 | 92156257.48 | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.00 | 0.00 |
September | 0.394608E+09 | 0.154962E+09 | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.00 | 0.00 |
October | 0.583160E+09 | 0.293207E+09 | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.00 | 0.00 |
November | 0.576702E+09 | 0.352017E+09 | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.00 | 0.00 |
December | 0.558723E+09 | 0.431654E+09 | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.526300E+10 | 0.312602E+10 | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.00 | 0.00 |
Minimum of Months | 0.300195E+09 | 92156257.48 | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.00 | 0.00 |
Maximum of Months | 0.583160E+09 | 0.498941E+09 | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.45 | -3.0 | 4.56 | -7.9 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.23 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.96 | 3.80 | 4.89 | 2.24 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.53 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.43 | 13.69 | 3.50 | 11.45 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.34 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.67 | 19.85 | 3.24 | 17.63 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.41 | 20.72 | 3.39 | 18.20 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.43 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.01 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.21 | 4.17 | 4.16 | 0.29 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.67 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.28 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.45 | -3.0 | 3.06 | -7.9 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.41 | 20.72 | 5.19 | 18.20 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.95 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.72 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.85 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.53 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.47 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.37 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.89 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.82 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.04 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.54 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.94 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.76 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.72 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.89 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.7 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.7 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.4 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.0 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.44 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.1 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.7 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.80 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.15 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.00 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.33 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.31 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.05 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.12 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.09 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.19 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.87 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.80 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.12 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.80 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.78 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.09 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.88 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.80 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.257351E+10 | -.214394E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -429564759.5 | 59.00 | 0.00 | 0.00 |
February | 0.233443E+10 | -.195628E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -378150957.8 | 59.00 | 0.00 | 0.00 |
March | 0.254596E+10 | -.214514E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -400819387.5 | 58.99 | 0.00 | 0.00 |
April | 0.228835E+10 | -.190920E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -379150297.8 | 58.99 | 0.00 | 0.00 |
May | 0.220110E+10 | -.181625E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -384847878.3 | 58.99 | 0.00 | 0.00 |
June | 0.200774E+10 | -.164083E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -366911256.3 | 58.99 | 0.00 | 0.00 |
July | 0.193787E+10 | -.156098E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376888613.1 | 58.99 | 0.00 | 0.00 |
August | 0.198173E+10 | -.160534E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376390380.8 | 58.99 | 0.00 | 0.00 |
September | 0.196907E+10 | -.160072E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -368348274.3 | 58.99 | 0.00 | 0.00 |
October | 0.215368E+10 | -.176390E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -389786288.9 | 58.99 | 0.00 | 0.00 |
November | 0.223949E+10 | -.185070E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -388786704.5 | 58.99 | 0.00 | 0.00 |
December | 0.248116E+10 | -.206169E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -419472267.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.267141E+11 | -.220550E+11 | 8760.00 | -.465912E+10 | 58.99 | |||||
Minimum of Months | 0.193787E+10 | -.214514E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -429564759.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.257351E+10 | -.156098E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -366911256.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.85 | 0.50 | 08-JAN-11:20 | 264.44 | 7.01 | 0.00 | 15.00 | 218.84 | 5.57 | 0.00 | 4.00 |
February | 263.00 | 0.84 | 0.50 | 09-FEB-13:20 | 285.41 | 6.96 | 0.00 | 35.83 | 233.52 | 5.42 | 0.00 | 13.00 |
March | 351.67 | 0.77 | 0.50 | 01-MAR-13:20 | 382.95 | 8.91 | 0.00 | 97.83 | 316.96 | 7.33 | 0.00 | 60.17 |
April | 369.33 | 0.73 | 0.50 | 01-APR-11:09 | 2610.78 | 10.12 | 0.00 | 145.67 | 2728.39 | 8.44 | 0.00 | 103.83 |
May | 407.00 | 0.71 | 0.50 | 01-MAY-09:20 | 474.26 | 11.91 | 0.00 | 171.00 | 398.86 | 10.19 | 0.00 | 116.33 |
June | 411.67 | 0.71 | 0.50 | 01-JUN-09:39 | 471.33 | 12.34 | 0.00 | 173.50 | 395.39 | 10.61 | 0.00 | 114.33 |
July | 411.00 | 0.71 | 0.50 | 01-JUL-09:20 | 483.09 | 12.27 | 0.00 | 183.50 | 405.55 | 10.60 | 0.00 | 128.17 |
August | 390.50 | 0.69 | 0.50 | 01-AUG-11:39 | 629.31 | 11.88 | 0.00 | 196.17 | 469.25 | 10.14 | 0.00 | 136.67 |
September | 298.50 | 0.72 | 0.50 | 01-SEP-09:00 | 3142.88 | 9.77 | 0.00 | 161.17 | 2200.34 | 8.13 | 0.00 | 80.00 |
October | 293.50 | 0.82 | 0.50 | 01-OCT-11:09 | 305.48 | 6.91 | 0.00 | 39.00 | 268.35 | 5.43 | 0.00 | 21.83 |
November | 299.00 | 0.82 | 0.50 | 02-NOV-10:00 | 311.90 | 7.35 | 0.00 | 14.50 | 626.88 | 5.89 | 0.00 | 35.67 |
December | 285.17 | 0.85 | 0.58 | 11-DEC-13:09 | 1344.06 | 6.94 | 0.00 | 44.00 | 205.12 | 5.47 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.76 | 881.00 | 9.70 | 0.00 | 1277.17 | 712.53 | 8.08 | 0.00 | 814.00 | ||
Minimum of Months | 263.00 | 0.69 | 0.50 | 264.44 | 6.91 | 0.00 | 14.50 | 205.12 | 5.42 | 0.00 | 0.00 | |
Maximum of Months | 411.67 | 0.85 | 0.58 | 3142.88 | 12.34 | 0.00 | 196.17 | 2728.39 | 10.61 | 0.00 | 136.67 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.833765E+10 | 50811.10 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.475470E+10 | 50811.10 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286954E+09 | 50811.10 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44806464.46 | 5719.87 | 06-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7860450.84 | 2845.34 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394321E+09 | 50811.10 | 21-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.285827E+10 | 50811.10 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166846E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.833765E+10 | 50811.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232225E+11 | 231144.20 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115620E+11 | 231144.20 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232550E+09 | 17965.63 | 23-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28651007.29 | 13653.72 | 07-APR-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11705625.53 | 12197.73 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.897184E+09 | 57557.36 | 21-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688606E+10 | 231144.20 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428407E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232225E+11 | 231144.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223613E+10 | 31123.07 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127711E+10 | 31123.07 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77101452.94 | 8431.87 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 26653511.92 | 3901.81 | 06-APR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2541997.52 | 1575.61 | 26-OCT-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79803407.98 | 27603.09 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.621472E+09 | 31123.07 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432082E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.223613E+10 | 31123.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.424900E+10 | 25385.70 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.255016E+10 | 25385.70 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.351943E+09 | 25361.66 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96801922.86 | 12302.86 | 06-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48368168.93 | 4381.58 | 26-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271902E+09 | 25385.70 | 21-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159800E+10 | 25385.70 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.916618E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.424900E+10 | 25385.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.101709E+11 | 30060.23 | 07-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590948E+10 | 30061.80 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210095E+10 | 17452.16 | 22-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571510E+09 | 12232.35 | 05-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11274996.22 | 1666.55 | 10-MAY-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29330181.19 | 1739.68 | 28-SEP-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.904174E+09 | 11051.72 | 25-OCT-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219490E+10 | 17637.67 | 20-NOV-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.591893E+10 | 21771.21 | 17-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278114E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.101709E+11 | 30061.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10588.57 | 7951.16 | 1.29 | 20-JAN-15:10 | 0.94 | 0.00 |
February | 0.00 | 0.00 | 0.250470E+09 | 0.250467E+09 | 8080.44 | 28-FEB-15:00 | 8080.44 | 0.00 |
March | 0.00 | 0.00 | 0.156587E+10 | 0.126376E+10 | 31285.26 | 31-MAR-06:02 | 18056.05 | 0.00 |
April | 0.00 | 0.00 | 0.555068E+10 | 0.466623E+10 | 37136.63 | 19-APR-06:02 | 23369.88 | 0.00 |
May | 0.00 | 0.00 | 0.129019E+11 | 0.990572E+10 | 40115.97 | 31-MAY-06:02 | 19438.49 | 0.00 |
June | 0.00 | 0.00 | 0.231929E+11 | 0.173918E+11 | 41522.59 | 29-JUN-06:02 | 18986.14 | 0.00 |
July | 0.00 | 0.00 | 0.275377E+11 | 0.196127E+11 | 42098.59 | 27-JUL-06:02 | 16074.27 | 0.00 |
August | 0.00 | 0.00 | 0.301356E+11 | 0.210962E+11 | 42333.10 | 12-AUG-06:02 | 17055.54 | 0.00 |
September | 0.00 | 0.00 | 0.179825E+11 | 0.130258E+11 | 42230.70 | 17-SEP-08:62 | 20748.87 | 0.00 |
October | 0.00 | 0.00 | 0.540605E+10 | 0.393129E+10 | 41169.22 | 19-OCT-06:02 | 16552.13 | 0.00 |
November | 0.00 | 0.00 | 0.706926E+09 | 0.508683E+09 | 37361.37 | 04-NOV-06:02 | 20932.92 | 0.00 |
December | 0.00 | 0.00 | 55969312.38 | 41606539.80 | 4754.24 | 12-DEC-15:10 | 3696.96 | 0.00 |
Annual Sum or Average | 0.125287E+12 | 0.916942E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 10588.57 | 7951.16 | 1.29 | 0.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.301356E+11 | 0.210962E+11 | 42333.10 | 23369.88 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 74753837.62 | 63299913.78 | 10750.25 | 31-JAN-15:10 | 9374.33 | 0.00 |
February | 0.00 | 0.00 | 0.302190E+10 | 0.300537E+10 | 47397.41 | 28-FEB-15:00 | 47397.41 | 0.00 |
March | 0.00 | 0.00 | 0.138706E+11 | 0.109107E+11 | 188070.27 | 30-MAR-06:02 | 110901.07 | 0.00 |
April | 0.00 | 0.00 | 0.404687E+11 | 0.329677E+11 | 191534.12 | 23-APR-08:62 | 98156.65 | 0.00 |
May | 0.00 | 0.00 | 0.785757E+11 | 0.583819E+11 | 196318.19 | 26-MAY-06:02 | 94568.13 | 0.00 |
June | 0.00 | 0.00 | 0.123247E+12 | 0.886322E+11 | 197428.59 | 23-JUN-06:02 | 121731.83 | 0.00 |
July | 0.00 | 0.00 | 0.144573E+12 | 0.969971E+11 | 201526.79 | 30-JUL-08:62 | 111932.65 | 0.00 |
August | 0.00 | 0.00 | 0.153506E+12 | 0.100710E+12 | 201779.08 | 20-AUG-08:62 | 113681.98 | 0.00 |
September | 0.00 | 0.00 | 0.956236E+11 | 0.652896E+11 | 201758.83 | 17-SEP-08:62 | 112588.77 | 0.00 |
October | 0.00 | 0.00 | 0.356059E+11 | 0.254792E+11 | 200214.59 | 19-OCT-06:02 | 88069.33 | 0.00 |
November | 0.00 | 0.00 | 0.792088E+10 | 0.587058E+10 | 186585.53 | 04-NOV-06:02 | 105304.46 | 0.00 |
December | 0.00 | 0.00 | 0.117061E+10 | 0.793152E+09 | 186524.43 | 13-DEC-07:03 | 107889.01 | 0.00 |
Annual Sum or Average | 0.697658E+12 | 0.489101E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 74753837.62 | 63299913.78 | 10750.25 | 9374.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.153506E+12 | 0.100710E+12 | 201779.08 | 121731.83 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 30381090.18 | 26215205.72 | 2776.02 | 31-JAN-15:00 | 2552.93 | 0.00 |
February | 0.00 | 0.00 | 0.725441E+09 | 0.723859E+09 | 9086.14 | 28-FEB-15:00 | 9086.14 | 0.00 |
March | 0.00 | 0.00 | 0.226639E+10 | 0.187367E+10 | 24285.87 | 30-MAR-06:02 | 14076.54 | 0.00 |
April | 0.00 | 0.00 | 0.542535E+10 | 0.459506E+10 | 24031.94 | 22-APR-06:02 | 13797.97 | 0.00 |
May | 0.00 | 0.00 | 0.100295E+11 | 0.782557E+10 | 25348.67 | 31-MAY-06:02 | 12122.64 | 0.00 |
June | 0.00 | 0.00 | 0.158291E+11 | 0.119584E+11 | 26252.66 | 29-JUN-06:02 | 11773.71 | 0.00 |
July | 0.00 | 0.00 | 0.186896E+11 | 0.133311E+11 | 26750.76 | 26-JUL-06:02 | 10037.77 | 0.00 |
August | 0.00 | 0.00 | 0.209859E+11 | 0.148633E+11 | 27216.04 | 20-AUG-07:03 | 12987.12 | 0.00 |
September | 0.00 | 0.00 | 0.138576E+11 | 0.102762E+11 | 26767.62 | 17-SEP-08:62 | 11131.25 | 0.00 |
October | 0.00 | 0.00 | 0.604195E+10 | 0.474073E+10 | 25984.24 | 19-OCT-06:02 | 10487.72 | 0.00 |
November | 0.00 | 0.00 | 0.199947E+10 | 0.163671E+10 | 24004.13 | 04-NOV-06:02 | 13530.39 | 0.00 |
December | 0.00 | 0.00 | 0.384075E+09 | 0.277758E+09 | 24068.06 | 13-DEC-07:03 | 13761.29 | 0.00 |
Annual Sum or Average | 0.962648E+11 | 0.721285E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 30381090.18 | 26215205.72 | 2776.02 | 2552.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209859E+11 | 0.148633E+11 | 27216.04 | 14076.54 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3385194.15 | 2948505.60 | 749.83 | 31-JAN-15:00 | 669.50 | 0.00 |
February | 0.00 | 0.00 | 0.422631E+09 | 0.422110E+09 | 6325.29 | 28-FEB-15:10 | 6325.29 | 0.00 |
March | 0.00 | 0.00 | 0.131597E+10 | 0.105473E+10 | 19796.48 | 31-MAR-06:02 | 11184.51 | 0.00 |
April | 0.00 | 0.00 | 0.339901E+10 | 0.281302E+10 | 14677.98 | 19-APR-06:02 | 9000.82 | 0.00 |
May | 0.00 | 0.00 | 0.688939E+10 | 0.516272E+10 | 20793.14 | 31-MAY-06:02 | 9828.06 | 0.00 |
June | 0.00 | 0.00 | 0.123660E+11 | 0.888986E+10 | 21507.22 | 29-JUN-06:02 | 9618.59 | 0.00 |
July | 0.00 | 0.00 | 0.149355E+11 | 0.101236E+11 | 21815.21 | 27-JUL-06:02 | 8233.43 | 0.00 |
August | 0.00 | 0.00 | 0.170301E+11 | 0.113933E+11 | 21934.96 | 12-AUG-06:02 | 8684.83 | 0.00 |
September | 0.00 | 0.00 | 0.105647E+11 | 0.743139E+10 | 21930.39 | 17-SEP-08:62 | 9100.35 | 0.00 |
October | 0.00 | 0.00 | 0.430700E+10 | 0.323069E+10 | 21331.97 | 19-OCT-06:02 | 8485.87 | 0.00 |
November | 0.00 | 0.00 | 0.104089E+10 | 0.836111E+09 | 16291.55 | 04-NOV-06:02 | 8949.15 | 0.00 |
December | 0.00 | 0.00 | 0.177075E+09 | 0.123715E+09 | 7536.71 | 12-DEC-14:00 | 5504.64 | 0.00 |
Annual Sum or Average | 0.724517E+11 | 0.514842E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 3385194.15 | 2948505.60 | 749.83 | 669.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.170301E+11 | 0.113933E+11 | 21934.96 | 11184.51 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.295190E+10 | 0.52 | 1944.26 | 01-JAN-07:03 | 0.91 |
February | 0.225849E+10 | 0.44 | 1944.26 | 01-FEB-06:03 | 0.91 |
March | 0.180055E+10 | 0.31 | 1944.26 | 01-MAR-08:70 | 0.91 |
April | 0.824148E+09 | 0.15 | 1944.26 | 01-APR-07:10 | 0.91 |
May | 0.209071E+09 | 0.04 | 1944.26 | 01-MAY-07:05 | 0.90 |
June | 10456856.76 | 0.00 | 1944.26 | 07-JUN-07:07 | 0.90 |
July | 57161125.90 | 0.01 | 1944.26 | 28-JUL-11:10 | 0.89 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.144068E+09 | 0.03 | 1944.26 | 14-SEP-07:10 | 0.90 |
October | 0.108129E+10 | 0.19 | 1944.26 | 01-OCT-11:10 | 0.89 |
November | 0.179098E+10 | 0.32 | 1944.26 | 01-NOV-07:10 | 0.91 |
December | 0.263033E+10 | 0.46 | 1944.26 | 01-DEC-05:03 | 0.91 |
Annual Sum or Average | 0.137584E+11 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.295190E+10 | 0.52 | 1944.26 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.338347E+10 | 0.56 | 2100.95 | 01-JAN-15:00 | 0.90 |
February | 0.307172E+10 | 0.56 | 2100.95 | 06-FEB-14:20 | 0.91 |
March | 0.342623E+10 | 0.55 | 2100.95 | 01-MAR-17:40 | 0.90 |
April | 0.329009E+10 | 0.55 | 2100.95 | 02-APR-12:00 | 0.90 |
May | 0.339598E+10 | 0.54 | 2100.95 | 01-MAY-09:23 | 0.90 |
June | 0.331278E+10 | 0.55 | 2100.95 | 03-JUN-14:50 | 0.90 |
July | 0.337329E+10 | 0.54 | 2100.95 | 01-JUL-16:20 | 0.90 |
August | 0.342623E+10 | 0.55 | 2100.95 | 06-AUG-17:00 | 0.90 |
September | 0.329009E+10 | 0.54 | 2100.95 | 05-SEP-11:35 | 0.90 |
October | 0.336572E+10 | 0.54 | 2100.95 | 01-OCT-14:50 | 0.90 |
November | 0.324471E+10 | 0.54 | 2100.95 | 02-NOV-15:30 | 0.90 |
December | 0.337653E+10 | 0.55 | 2100.95 | 02-DEC-12:20 | 0.91 |
Annual Sum or Average | 0.399568E+11 | 0.55 | |||
Minimum of Months | 0.307172E+10 | 0.54 | 2100.95 | 0.90 | |
Maximum of Months | 0.342623E+10 | 0.56 | 2100.95 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.231393E+11 | 0.93 | 14444.01 | 01-JAN-10:30 | 1.55 |
February | 0.210074E+11 | 0.94 | 14444.01 | 01-FEB-08:00 | 1.56 |
March | 0.235553E+11 | 0.95 | 14444.01 | 02-MAR-11:35 | 1.55 |
April | 0.226193E+11 | 0.94 | 14444.01 | 02-APR-10:55 | 1.54 |
May | 0.233473E+11 | 0.93 | 14444.01 | 08-MAY-07:35 | 1.54 |
June | 0.227753E+11 | 0.94 | 14444.01 | 01-JUN-11:10 | 1.54 |
July | 0.231913E+11 | 0.92 | 14444.01 | 01-JUL-06:20 | 1.54 |
August | 0.235553E+11 | 0.94 | 14444.01 | 05-AUG-06:20 | 1.54 |
September | 0.226193E+11 | 0.93 | 14444.01 | 19-SEP-09:00 | 1.55 |
October | 0.231393E+11 | 0.93 | 14444.01 | 01-OCT-10:30 | 1.54 |
November | 0.223073E+11 | 0.93 | 14444.01 | 01-NOV-13:00 | 1.55 |
December | 0.231913E+11 | 0.94 | 14444.01 | 02-DEC-09:50 | 1.57 |
Annual Sum or Average | 0.274448E+12 | 0.93 | |||
Minimum of Months | 0.210074E+11 | 0.92 | 14444.01 | 1.54 | |
Maximum of Months | 0.235553E+11 | 0.95 | 14444.01 | 1.57 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.203718E+10 | 0.57 | 1269.31 | 01-JAN-08:30 | 0.94 |
February | 0.185034E+10 | 0.58 | 1269.31 | 01-FEB-07:55 | 0.94 |
March | 0.207000E+10 | 0.57 | 1269.31 | 02-MAR-14:00 | 0.94 |
April | 0.198775E+10 | 0.57 | 1269.31 | 01-APR-09:10 | 0.94 |
May | 0.205172E+10 | 0.56 | 1269.31 | 01-MAY-08:33 | 0.93 |
June | 0.200146E+10 | 0.57 | 1269.31 | 01-JUN-07:15 | 0.93 |
July | 0.203801E+10 | 0.56 | 1269.31 | 01-JUL-06:08 | 0.92 |
August | 0.207000E+10 | 0.57 | 1269.31 | 01-AUG-15:00 | 0.93 |
September | 0.198775E+10 | 0.56 | 1269.31 | 01-SEP-06:30 | 0.93 |
October | 0.203344E+10 | 0.56 | 1269.31 | 01-OCT-14:00 | 0.93 |
November | 0.196033E+10 | 0.56 | 1269.31 | 01-NOV-12:20 | 0.93 |
December | 0.203819E+10 | 0.56 | 1269.31 | 01-DEC-08:70 | 0.94 |
Annual Sum or Average | 0.241262E+11 | 0.57 | |||
Minimum of Months | 0.185034E+10 | 0.56 | 1269.31 | 0.92 | |
Maximum of Months | 0.207000E+10 | 0.58 | 1269.31 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158257E+10 | 0.58 | 983.25 | 03-JAN-07:55 | 0.94 |
February | 0.143684E+10 | 0.58 | 983.25 | 02-FEB-06:35 | 0.94 |
March | 0.160348E+10 | 0.57 | 983.25 | 11-MAR-14:00 | 0.94 |
April | 0.153977E+10 | 0.57 | 983.25 | 07-APR-17:50 | 0.94 |
May | 0.158932E+10 | 0.56 | 983.25 | 01-MAY-09:13 | 0.93 |
June | 0.155039E+10 | 0.57 | 983.25 | 02-JUN-12:40 | 0.94 |
July | 0.157870E+10 | 0.56 | 983.25 | 01-JUL-17:30 | 0.93 |
August | 0.160348E+10 | 0.57 | 983.25 | 03-AUG-19:50 | 0.93 |
September | 0.153977E+10 | 0.56 | 983.25 | 01-SEP-11:05 | 0.93 |
October | 0.157517E+10 | 0.56 | 983.25 | 01-OCT-11:23 | 0.93 |
November | 0.151853E+10 | 0.56 | 983.25 | 05-NOV-17:05 | 0.93 |
December | 0.157982E+10 | 0.57 | 983.25 | 01-DEC-06:10 | 0.94 |
Annual Sum or Average | 0.186978E+11 | 0.57 | |||
Minimum of Months | 0.143684E+10 | 0.56 | 983.25 | 0.93 | |
Maximum of Months | 0.160348E+10 | 0.58 | 983.25 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.44 | 0.00 |
February | 0.55 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.21 | 0.00 |
July | 0.21 | 0.00 |
August | 0.21 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.06 | 0.00 |
December | 0.51 | 0.00 |
Annual Sum or Average | 3.18 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.44 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 25.84 |
February | 0.50 | 25.84 |
March | 1.12 | 25.84 |
April | 0.44 | 25.84 |
May | 0.67 | 25.84 |
June | 0.54 | 7.95 |
July | 0.38 | 0.00 |
August | 0.38 | 0.00 |
September | 0.38 | 22.97 |
October | 0.68 | 25.84 |
November | 1.71 | 25.84 |
December | 0.79 | 25.84 |
Annual Sum or Average | 7.67 | 21.91 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 1.71 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.26 | 0.00 |
February | 0.50 | 0.67 |
March | 0.31 | 2.44 |
April | 0.26 | 1.15 |
May | 0.28 | 0.00 |
June | 0.71 | 0.00 |
July | 0.88 | 0.00 |
August | 1.18 | 0.00 |
September | 0.82 | 0.00 |
October | 0.24 | 1.00 |
November | 0.86 | 2.44 |
December | 0.35 | 1.85 |
Annual Sum or Average | 6.63 | 0.66 |
Minimum of Months | 0.24 | 0.00 |
Maximum of Months | 1.18 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.79 | 0.00 |
February | 0.33 | 0.00 |
March | 0.22 | 2.44 |
April | 0.06 | 2.44 |
May | 0.00 | 0.00 |
June | 0.38 | 0.00 |
July | 0.38 | 0.00 |
August | 0.62 | 0.00 |
September | 0.12 | 0.00 |
October | 0.46 | 2.44 |
November | 0.57 | 2.20 |
December | 0.53 | 0.83 |
Annual Sum or Average | 4.45 | 0.78 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.79 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 39.47 | 0.00 |
February | 38.65 | 0.00 |
March | 21.35 | 0.00 |
April | 24.35 | 0.00 |
May | 11.54 | 0.00 |
June | 5.38 | 0.00 |
July | 4.42 | 0.00 |
August | 3.11 | 0.00 |
September | 6.30 | 0.00 |
October | 20.72 | 0.00 |
November | 29.07 | 0.00 |
December | 23.58 | 0.00 |
Annual Sum or Average | 227.94 | 0.00 |
Minimum of Months | 3.11 | 0.00 |
Maximum of Months | 39.47 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.338347E+10 | 0.104221E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.314278E+10 | 0.594337E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.386014E+10 | 0.358693E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.482974E+10 | 56008080.57 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.690625E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.963869E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.108308E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114814E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.806739E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.480442E+10 | 9825563.55 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.343749E+10 | 0.492902E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.339212E+10 | 0.357283E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.737746E+11 | 0.208557E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.314278E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114814E+11 | 0.104221E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.231627E+11 | 0.290281E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.219418E+11 | 0.144525E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.277468E+11 | 0.290688E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.348619E+11 | 35813759.12 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.468221E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.598048E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.662014E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.687542E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.507048E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.336044E+11 | 14632031.92 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.246827E+11 | 0.112148E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.235458E+11 | 0.860758E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.481833E+12 | 0.535509E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.219418E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.687542E+11 | 0.290281E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.204555E+10 | 0.279517E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.204478E+10 | 0.159639E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.267476E+10 | 96376816.17 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.345232E+10 | 33316889.90 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.474146E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.628658E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.706073E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.761838E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.560370E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.359508E+10 | 3177496.90 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.248462E+10 | 99754259.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.213859E+10 | 0.776840E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.497465E+11 | 0.540102E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.204478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.761838E+10 | 0.279517E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158352E+10 | 0.531125E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.155171E+10 | 0.318770E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.196027E+10 | 0.439928E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.247383E+10 | 0.121002E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.345890E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.489935E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.557941E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.608265E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.430213E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.269498E+10 | 60460211.16 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.179582E+10 | 0.339877E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.162698E+10 | 0.199750E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.380096E+11 | 0.114577E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.155171E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.608265E+10 | 0.531125E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.338347E+10 | 10588.57 | 0.833765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307172E+10 | 0.250470E+09 | 0.475470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342623E+10 | 0.156587E+10 | 0.286954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.329009E+10 | 0.555068E+10 | 44806464.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.339598E+10 | 0.129019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.331278E+10 | 0.231929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337329E+10 | 0.275377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.342623E+10 | 0.301356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329009E+10 | 0.179825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336572E+10 | 0.540605E+10 | 7860450.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324471E+10 | 0.706926E+09 | 0.394321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337653E+10 | 55969312.38 | 0.285827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399568E+11 | 0.125287E+12 | 0.166846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.307172E+10 | 10588.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.342623E+10 | 0.301356E+11 | 0.833765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.231393E+11 | 74753837.62 | 0.232225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210074E+11 | 0.302190E+10 | 0.115620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235553E+11 | 0.138706E+11 | 0.232550E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226193E+11 | 0.404687E+11 | 28651007.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233473E+11 | 0.785757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227753E+11 | 0.123247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.231913E+11 | 0.144573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.235553E+11 | 0.153506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226193E+11 | 0.956236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231393E+11 | 0.356059E+11 | 11705625.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223073E+11 | 0.792088E+10 | 0.897184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231913E+11 | 0.117061E+10 | 0.688606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274448E+12 | 0.697658E+12 | 0.428407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.210074E+11 | 74753837.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.235553E+11 | 0.153506E+12 | 0.232225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.203718E+10 | 30381090.18 | 0.223613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185034E+10 | 0.725441E+09 | 0.127711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207000E+10 | 0.226639E+10 | 77101452.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198775E+10 | 0.542535E+10 | 26653511.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205172E+10 | 0.100295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.200146E+10 | 0.158291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203801E+10 | 0.186896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207000E+10 | 0.209859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198775E+10 | 0.138576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203344E+10 | 0.604195E+10 | 2541997.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196033E+10 | 0.199947E+10 | 79803407.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203819E+10 | 0.384075E+09 | 0.621472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241262E+11 | 0.962648E+11 | 0.432082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185034E+10 | 30381090.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207000E+10 | 0.209859E+11 | 0.223613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158257E+10 | 3385194.15 | 0.424900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143684E+10 | 0.422631E+09 | 0.255016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160348E+10 | 0.131597E+10 | 0.351943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153977E+10 | 0.339901E+10 | 96801922.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158932E+10 | 0.688939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155039E+10 | 0.123660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157870E+10 | 0.149355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160348E+10 | 0.170301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153977E+10 | 0.105647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157517E+10 | 0.430700E+10 | 48368168.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151853E+10 | 0.104089E+10 | 0.271902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157982E+10 | 0.177075E+09 | 0.159800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186978E+11 | 0.724517E+11 | 0.916618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143684E+10 | 3385194.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160348E+10 | 0.170301E+11 | 0.424900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.338347E+10 | 0.00 | 0.00 | 0.00 | 3000.33 | 0.00 | 0.104221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307172E+10 | 0.00 | 0.00 | 0.00 | 71061498.16 | 0.00 | 0.594337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342623E+10 | 0.00 | 0.00 | 0.00 | 0.433915E+09 | 0.00 | 0.358693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.329009E+10 | 0.00 | 0.00 | 0.00 | 0.153965E+10 | 0.00 | 56008080.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.339598E+10 | 0.00 | 0.00 | 0.00 | 0.351027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.331278E+10 | 0.00 | 0.00 | 0.00 | 0.632591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337329E+10 | 0.00 | 0.00 | 0.00 | 0.745751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.342623E+10 | 0.00 | 0.00 | 0.00 | 0.805513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329009E+10 | 0.00 | 0.00 | 0.00 | 0.477730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336572E+10 | 0.00 | 0.00 | 0.00 | 0.143870E+10 | 0.00 | 9825563.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324471E+10 | 0.00 | 0.00 | 0.00 | 0.192779E+09 | 0.00 | 0.492902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337653E+10 | 0.00 | 0.00 | 0.00 | 15593376.18 | 0.00 | 0.357283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399568E+11 | 0.00 | 0.00 | 0.00 | 0.338178E+11 | 0.00 | 0.208557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.307172E+10 | 0.00 | 0.00 | 0.00 | 3000.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.342623E+10 | 0.00 | 0.00 | 0.00 | 0.805513E+10 | 0.00 | 0.104221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.231393E+11 | 0.00 | 0.00 | 0.00 | 23360294.24 | 0.00 | 0.290281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210074E+11 | 0.00 | 0.00 | 0.00 | 0.934413E+09 | 0.00 | 0.144525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235553E+11 | 0.00 | 0.00 | 0.00 | 0.419150E+10 | 0.00 | 0.290688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226193E+11 | 0.00 | 0.00 | 0.00 | 0.122426E+11 | 0.00 | 35813759.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233473E+11 | 0.00 | 0.00 | 0.00 | 0.234748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.227753E+11 | 0.00 | 0.00 | 0.00 | 0.370295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.231913E+11 | 0.00 | 0.00 | 0.00 | 0.430101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.235553E+11 | 0.00 | 0.00 | 0.00 | 0.451989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.226193E+11 | 0.00 | 0.00 | 0.00 | 0.280854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231393E+11 | 0.00 | 0.00 | 0.00 | 0.104651E+11 | 0.00 | 14632031.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223073E+11 | 0.00 | 0.00 | 0.00 | 0.237535E+10 | 0.00 | 0.112148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231913E+11 | 0.00 | 0.00 | 0.00 | 0.354458E+09 | 0.00 | 0.860758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274448E+12 | 0.00 | 0.00 | 0.00 | 0.207385E+12 | 0.00 | 0.535509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.210074E+11 | 0.00 | 0.00 | 0.00 | 23360294.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.235553E+11 | 0.00 | 0.00 | 0.00 | 0.451989E+11 | 0.00 | 0.290281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.203718E+10 | 0.00 | 0.00 | 0.00 | 8366693.63 | 0.00 | 0.279517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185034E+10 | 0.00 | 0.00 | 0.00 | 0.194444E+09 | 0.00 | 0.159639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207000E+10 | 0.00 | 0.00 | 0.00 | 0.604762E+09 | 0.00 | 96376816.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198775E+10 | 0.00 | 0.00 | 0.00 | 0.146457E+10 | 0.00 | 33316889.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205172E+10 | 0.00 | 0.00 | 0.00 | 0.268973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.200146E+10 | 0.00 | 0.00 | 0.00 | 0.428512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203801E+10 | 0.00 | 0.00 | 0.00 | 0.502272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207000E+10 | 0.00 | 0.00 | 0.00 | 0.554838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198775E+10 | 0.00 | 0.00 | 0.00 | 0.361596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203344E+10 | 0.00 | 0.00 | 0.00 | 0.156164E+10 | 0.00 | 3177496.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.196033E+10 | 0.00 | 0.00 | 0.00 | 0.524287E+09 | 0.00 | 99754259.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203819E+10 | 0.00 | 0.00 | 0.00 | 0.100395E+09 | 0.00 | 0.776840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.241262E+11 | 0.00 | 0.00 | 0.00 | 0.256204E+11 | 0.00 | 0.540102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.185034E+10 | 0.00 | 0.00 | 0.00 | 8366693.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207000E+10 | 0.00 | 0.00 | 0.00 | 0.554838E+10 | 0.00 | 0.279517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.158257E+10 | 0.00 | 0.00 | 0.00 | 950052.87 | 0.00 | 0.531125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143684E+10 | 0.00 | 0.00 | 0.00 | 0.114874E+09 | 0.00 | 0.318770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160348E+10 | 0.00 | 0.00 | 0.00 | 0.356788E+09 | 0.00 | 0.439928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153977E+10 | 0.00 | 0.00 | 0.00 | 0.934058E+09 | 0.00 | 0.121002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158932E+10 | 0.00 | 0.00 | 0.00 | 0.186957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155039E+10 | 0.00 | 0.00 | 0.00 | 0.334896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157870E+10 | 0.00 | 0.00 | 0.00 | 0.400070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160348E+10 | 0.00 | 0.00 | 0.00 | 0.447917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153977E+10 | 0.00 | 0.00 | 0.00 | 0.276236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157517E+10 | 0.00 | 0.00 | 0.00 | 0.111982E+10 | 0.00 | 60460211.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151853E+10 | 0.00 | 0.00 | 0.00 | 0.277295E+09 | 0.00 | 0.339877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157982E+10 | 0.00 | 0.00 | 0.00 | 47157507.17 | 0.00 | 0.199750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186978E+11 | 0.00 | 0.00 | 0.00 | 0.193117E+11 | 0.00 | 0.114577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143684E+10 | 0.00 | 0.00 | 0.00 | 950052.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160348E+10 | 0.00 | 0.00 | 0.00 | 0.447917E+10 | 0.00 | 0.531125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194449E+10 | 0.00 | 0.00 | 33907.08 | 0.00 | 0.561640E+10 | 0.149920E+09 | 0.00 | 0.20 |
February | 0.209557E+10 | 61238.62 | 0.00 | 807362.20 | 0.00 | 0.299103E+10 | 0.108970E+10 | 0.00 | 0.30 |
March | 0.239744E+10 | 45964373.11 | 0.00 | 3516043.18 | 0.00 | 0.244067E+09 | 0.374390E+10 | 0.00 | 0.43 |
April | 0.835044E+09 | 0.156791E+09 | 0.00 | 5620773.88 | 825939.75 | 36843327.86 | 0.372481E+10 | 0.00 | 0.56 |
May | 0.173635E+09 | 0.127702E+10 | 0.00 | 6765919.11 | 800659.93 | 0.00 | 0.278751E+10 | 0.00 | 0.52 |
June | 41851048.52 | 0.435766E+10 | 0.00 | 4705383.06 | 4303856.31 | 0.00 | 0.739965E+09 | 0.00 | 0.33 |
July | 15122475.39 | 0.626597E+10 | 0.00 | 2563082.94 | 12032597.91 | 0.00 | 0.543464E+09 | 0.00 | 0.27 |
August | 13745937.07 | 0.702057E+10 | 0.00 | 1653023.48 | 14179942.07 | 0.00 | 0.142916E+09 | 0.00 | 0.24 |
September | 33914729.06 | 0.301787E+10 | 0.00 | 6299925.49 | 8577573.93 | 0.00 | 0.195121E+10 | 0.00 | 0.42 |
October | 0.111322E+10 | 0.577852E+09 | 0.00 | 8098216.14 | 0.00 | 0.00 | 0.547059E+10 | 0.00 | 0.54 |
November | 0.265778E+10 | 18103395.35 | 0.00 | 4217057.48 | 9288709.78 | 0.224629E+09 | 0.407040E+10 | 0.00 | 0.44 |
December | 0.393752E+10 | 0.00 | 0.00 | 622485.55 | 0.00 | 0.198689E+10 | 0.696731E+09 | 0.00 | 0.24 |
Annual Sum or Average | 0.152593E+11 | 0.227379E+11 | 0.00 | 44903179.59 | 50009279.69 | 0.110999E+11 | 0.251111E+11 | 0.00 | 0.37 |
Minimum of Months | 13745937.07 | 0.00 | 0.00 | 33907.08 | 0.00 | 0.00 | 0.142916E+09 | 0.00 | 0.20 |
Maximum of Months | 0.393752E+10 | 0.702057E+10 | 0.00 | 8098216.14 | 14179942.07 | 0.561640E+10 | 0.547059E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.460295E+11 | 0.00 | 0.00 | 1778379.42 | 0.00 | 0.123474E+11 | 0.327340E+10 | 0.00 | 0.41 |
February | 0.305747E+11 | 721872.43 | 0.00 | 13530323.46 | 0.00 | 0.578260E+10 | 0.132277E+11 | 0.00 | 0.53 |
March | 0.133513E+11 | 0.722689E+09 | 0.00 | 41017712.12 | 0.00 | 0.00 | 0.330208E+11 | 0.00 | 0.69 |
April | 0.402497E+10 | 0.279012E+10 | 0.00 | 46047300.24 | 0.00 | 0.00 | 0.237319E+11 | 0.00 | 0.70 |
May | 0.936276E+09 | 0.131741E+11 | 0.00 | 41256405.64 | 21008770.85 | 0.00 | 0.121843E+11 | 0.00 | 0.65 |
June | 0.344411E+09 | 0.377671E+11 | 0.00 | 12752867.42 | 0.209091E+09 | 0.00 | 0.271175E+10 | 0.00 | 0.48 |
July | 55455470.87 | 0.520824E+11 | 0.00 | 2719919.23 | 0.323691E+09 | 0.00 | 0.579740E+09 | 0.00 | 0.41 |
August | 40445256.84 | 0.575395E+11 | 0.00 | 1884259.11 | 0.343830E+09 | 0.00 | 0.211861E+09 | 0.00 | 0.41 |
September | 0.375376E+09 | 0.255001E+11 | 0.00 | 23301303.96 | 0.187478E+09 | 0.00 | 0.813653E+10 | 0.00 | 0.54 |
October | 0.683605E+10 | 0.564973E+10 | 0.00 | 53610196.43 | 7707918.87 | 0.00 | 0.304621E+11 | 0.00 | 0.70 |
November | 0.191729E+11 | 0.158401E+09 | 0.00 | 34122782.13 | 40473238.25 | 0.171057E+09 | 0.272195E+11 | 0.00 | 0.66 |
December | 0.388609E+11 | 0.00 | 0.00 | 8246002.57 | 0.00 | 0.310800E+10 | 0.104658E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.160602E+12 | 0.195385E+12 | 0.00 | 0.280267E+09 | 0.113328E+10 | 0.214090E+11 | 0.165225E+12 | 0.00 | 0.55 |
Minimum of Months | 40445256.84 | 0.00 | 0.00 | 1778379.42 | 0.00 | 0.00 | 0.211861E+09 | 0.00 | 0.41 |
Maximum of Months | 0.460295E+11 | 0.575395E+11 | 0.00 | 53610196.43 | 0.343830E+09 | 0.123474E+11 | 0.330208E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.359717E+10 | 0.00 | 0.00 | 1540925.65 | 0.00 | 0.118359E+10 | 0.152612E+10 | 0.00 | 0.47 |
February | 0.239573E+10 | 184662.24 | 0.00 | 3903962.17 | 0.00 | 0.628040E+09 | 0.234880E+10 | 0.00 | 0.71 |
March | 0.943662E+09 | 94545745.27 | 0.00 | 7966283.35 | 0.00 | 31513257.57 | 0.473825E+10 | 0.00 | 0.96 |
April | 0.384109E+09 | 0.319896E+09 | 0.00 | 6077609.66 | 0.00 | 2030520.03 | 0.282523E+10 | 0.00 | 0.90 |
May | 0.102178E+09 | 0.139369E+10 | 0.00 | 5047818.05 | 518645.52 | 0.00 | 0.157970E+10 | 0.00 | 0.81 |
June | 26930495.61 | 0.372911E+10 | 0.00 | 2529595.86 | 660952.90 | 0.00 | 0.436365E+09 | 0.00 | 0.58 |
July | 4394881.19 | 0.521856E+10 | 0.00 | 1416449.23 | 4547608.64 | 0.00 | 0.266040E+09 | 0.00 | 0.50 |
August | 2444921.64 | 0.593662E+10 | 0.00 | 669850.70 | 5754540.28 | 0.00 | 83502849.87 | 0.00 | 0.44 |
September | 25444085.54 | 0.279993E+10 | 0.00 | 3784798.55 | 1756098.28 | 0.00 | 0.110481E+10 | 0.00 | 0.66 |
October | 0.446130E+09 | 0.686455E+09 | 0.00 | 10800865.90 | 0.00 | 0.00 | 0.445597E+10 | 0.00 | 1.02 |
November | 0.972482E+09 | 55258081.80 | 0.00 | 9266704.01 | 448683.10 | 47521995.46 | 0.500854E+10 | 0.00 | 0.96 |
December | 0.229428E+10 | 2017473.86 | 0.00 | 4400293.18 | 0.00 | 0.354255E+09 | 0.350657E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.111950E+11 | 0.202363E+11 | 0.00 | 57405156.32 | 13686528.72 | 0.224695E+10 | 0.278799E+11 | 0.00 | 0.72 |
Minimum of Months | 2444921.64 | 0.00 | 0.00 | 669850.70 | 0.00 | 0.00 | 83502849.87 | 0.00 | 0.44 |
Maximum of Months | 0.359717E+10 | 0.593662E+10 | 0.00 | 10800865.90 | 5754540.28 | 0.118359E+10 | 0.500854E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280259E+10 | 0.00 | 0.00 | 216977.35 | 0.00 | 0.259525E+10 | 0.297456E+09 | 0.00 | 0.41 |
February | 0.204937E+10 | 104808.97 | 0.00 | 1523472.15 | 0.00 | 0.151509E+10 | 0.904753E+09 | 0.00 | 0.54 |
March | 0.154517E+10 | 72688951.11 | 0.00 | 3092690.02 | 0.00 | 0.211603E+09 | 0.224667E+10 | 0.00 | 0.68 |
April | 0.734412E+09 | 0.232156E+09 | 0.00 | 2424818.96 | 401403.58 | 65486974.65 | 0.144832E+10 | 0.00 | 0.69 |
May | 0.214268E+09 | 0.116132E+10 | 0.00 | 2512776.44 | 547856.10 | 0.00 | 0.103652E+10 | 0.00 | 0.66 |
June | 56218911.33 | 0.346680E+10 | 0.00 | 1616889.10 | 3143626.69 | 0.00 | 0.246761E+09 | 0.00 | 0.51 |
July | 10922491.15 | 0.486276E+10 | 0.00 | 1048431.81 | 6924075.00 | 0.00 | 0.227056E+09 | 0.00 | 0.46 |
August | 6627029.17 | 0.555810E+10 | 0.00 | 629668.82 | 3920991.68 | 0.00 | 65742840.65 | 0.00 | 0.43 |
September | 70097621.73 | 0.252253E+10 | 0.00 | 2384548.77 | 4465760.79 | 0.00 | 0.751214E+09 | 0.00 | 0.57 |
October | 0.982557E+09 | 0.587886E+09 | 0.00 | 5754202.79 | 0.00 | 21703758.70 | 0.250095E+10 | 0.00 | 0.76 |
November | 0.172176E+10 | 22900578.17 | 0.00 | 4308522.23 | 1471541.93 | 0.112142E+09 | 0.261509E+10 | 0.00 | 0.71 |
December | 0.283814E+10 | 35357.68 | 0.00 | 1305857.06 | 0.00 | 0.968267E+09 | 0.109044E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.130321E+11 | 0.184873E+11 | 0.00 | 26818855.49 | 20875255.79 | 0.548954E+10 | 0.134310E+11 | 0.00 | 0.57 |
Minimum of Months | 6627029.17 | 0.00 | 0.00 | 216977.35 | 0.00 | 0.00 | 65742840.65 | 0.00 | 0.41 |
Maximum of Months | 0.283814E+10 | 0.555810E+10 | 0.00 | 5754202.79 | 6924075.00 | 0.259525E+10 | 0.261509E+10 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:11:32
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |