Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:12:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1764.70 | 769.27 | 769.27 |
Net Site Energy | 1764.70 | 769.27 | 769.27 |
Total Source Energy | 5400.77 | 2354.31 | 2354.31 |
Net Source Energy | 5400.77 | 2354.31 | 2354.31 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 663.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 353.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 389.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.38 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1674.43 | 90.27 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 4.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 663.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 353.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 73.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 389.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 85.38 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 185.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 458.88 | 39.35 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 729.92 | 39.35 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 185.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 458.88 | 39.35 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 729.92 | 39.35 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1674.430 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1674.430 | 100.00 |
Total On-Site and Utility Electric Sources | 1674.430 | 100.00 |
Total Electricity End Uses | 1674.430 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 572.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.7888 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 16.5511 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 12.6567 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-15:00 | 02-JAN-07:10 | - | - | - | 01-MAY-11:09 |
Heating | 0.00 | 79984.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 82652.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24923.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20308.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4534.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 138655.95 | 84518.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 79984.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 82652.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24923.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 20308.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4534.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 5.30 | 0.00 | 0.00 | 0.00 |
Cooling | 2100.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1119.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 231.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1233.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.56 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5302.92 | 97.85 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.31 | 0.00 | 0.00 | 0.00 |
Cooling | 915.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 488.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 537.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.35 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2311.65 | 42.66 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.31 | 0.00 | 0.00 | 0.00 |
Cooling | 915.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 488.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 537.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.35 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2311.65 | 42.66 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.33 |
CORE_RETAIL DIRECT AIR | 8.18 |
POINT_OF_SALE DIRECT AIR | 1.33 |
FRONT_RETAIL DIRECT AIR | 1.08 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.41 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.41 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 32000.03 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 56538.92 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 218261.49 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 33074.83 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 27513.62 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.33 | 2.33 | 2.33 | 2.33 | 2.33 | 2.33 | 1.00 | 1.00 | 2.33 |
PSZ-AC:2 | 8.18 | 8.18 | 8.18 | 8.18 | 8.30 | 8.30 | 1.00 | 0.985684 | 8.30 |
PSZ-AC:3 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.33 | 1.00 | 1.00 | 1.33 |
PSZ-AC:4 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.08 | 1.00 | 1.000000 | 1.08 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.33 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.30 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.33 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.08 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.33 | 2.33 | 2.33 | 2.33 | 45439.75 | 56538.92 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.30 | 8.30 | 8.30 | 8.30 | 206054.21 | 218261.49 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.33 | 1.33 | 1.33 | 1.33 | 29730.48 | 33074.83 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.08 | 1.08 | 1.08 | 1.08 | 25153.14 | 27513.62 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.33 | 1.16 | 2.33 | 42324.29 | 45439.75 | 22719.88 | 45439.75 | 0.742502 | 0.742500 | 0.742500 | 0.742500 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.30 | 4.15 | 8.30 | 198895.57 | 206054.21 | 103027.10 | 206054.21 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.33 | 0.665350 | 1.33 | 27884.04 | 29730.48 | 14865.24 | 29730.48 | 0.703402 | 0.703400 | 0.703400 | 0.703400 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.08 | 0.542060 | 1.08 | 23672.32 | 25153.14 | 12576.57 | 25153.14 | 0.693311 | 0.693310 | 0.693310 | 0.693310 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.33 | 2488.68 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.30 | 15146.35 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.33 | 1473.30 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.08 | 1200.30 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.789 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.859 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 38.071 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 12.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.657 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2958.869 | 7.789 | 48.236 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2958.869 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 26489.747 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26489.747 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 151.881 | 12.657 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 151.881 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.9170 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9232 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.27584055E-14 | 0.34322882E-16 | -0.15031138E-09 | 0.48455878E-16 |
25 | 8 | 0.21957962E-07 | 0.12358672E-12 | 0.37866961E-03 | -0.24966959E-09 |
26 | 7 | -0.12267734E-01 | 0.64103010E-08 | -0.23123512E-01 | 0.13948861E-03 |
27 | 6 | 0.40606172 | 0.22327916E-05 | 0.47269724 | -0.47561475E-02 |
28 | 5 | -5.1975060 | 0.83457246E-04 | -4.4459193 | 0.63269931E-01 |
29 | 4 | 33.033567 | 0.68336110E-03 | 21.458556 | -0.42253064 |
30 | 3 | -111.29159 | 0.14906214E-02 | -55.660041 | 1.5161389 |
31 | 2 | 197.19602 | 0.83912566E-03 | 77.907859 | -2.9017470 |
32 | 1 | -171.18851 | 0.89643828E-04 | -55.264270 | 2.7460078 |
33 | 0 | 57.057407 | 0.51076119E-06 | 15.557052 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 30 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 31 | 1 | VerySmooth | 5.108 | 0.600 | 0.461 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.448 | 1.180E-003 | 5.356E-004 | 0.697 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.367 | 2.293E-004 | 1.864E-004 | 0.135 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.194 | 1.288E-003 | 5.704E-004 | 0.760 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 2.497E-002 | 2.080E-003 | 6.862E-004 | 1.228 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 26519.55159 | 31823.46191 | 1.93814 | 2.32576 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 16709.91232 | 20051.89479 | 0.71720 | 0.86064 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 93794.78345 | 112553.74014 | 6.81584 | 8.17901 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 48896.09121 | 58675.30945 | 2.07137 | 2.48564 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 15050.07129 | 18060.08555 | 1.10892 | 1.33070 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 8213.51616 | 9856.21939 | 0.35438 | 0.42526 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 12309.08518 | 14770.90222 | 0.90344 | 1.08412 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 8218.12694 | 9861.75233 | 0.35458 | 0.42550 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00000 | 9.11023E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 26661.82902 | 31994.19482 | 1.17799 | 1.41359 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 33515.94 | 2.32576 | 2.32576 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 23423.14 | 0.86064 | 0.86064 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 140183.55 | 8.29780 | 8.29780 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 88685.09 | 2.48564 | 2.48564 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 20494.81 | 1.33070 | 1.33070 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 12653.70 | 0.42526 | 0.42526 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 17612.40 | 1.08412 | 1.08412 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 12659.20 | 0.42550 | 0.42550 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.32576 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.17901 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.33070 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08412 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.41359 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.41359 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 32000.03073 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.32576 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.32576 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.32576 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.32576 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.32576 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.32576 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.17901 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.17901 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.17901 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.17901 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.29780 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.29780 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98568 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.33070 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33070 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.33070 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.33070 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.33070 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.33070 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08412 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08412 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08412 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08412 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.08412 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.08412 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.32576 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.29780 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.33070 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.08412 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.32576 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.32576 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.32576 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.32576 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.32576 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.32576 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.16288 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.32576 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 42324.29103 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 45439.75000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 22719.87500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 45439.75000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74250 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74250 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74250 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74250 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45439.75000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56538.92025 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.32576 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2488.67706 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 56538.92025 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.29780 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.29780 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.29780 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.29780 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 8.29780 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.29780 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.14890 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 8.29780 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 198895.57296 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 206054.21000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 103027.10500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 206054.21000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 206054.21000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 218261.48518 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.29780 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 15146.35460 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 218261.48518 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.33070 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.33070 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.33070 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.33070 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.33070 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.33070 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.66535 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.33070 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27884.04217 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29730.48000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14865.24000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 29730.48000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70340 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70340 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70340 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70340 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29730.48000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33074.82616 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.33070 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1473.30050 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33074.82616 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.08412 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.08412 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.08412 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.08412 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.08412 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.08412 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54206 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.08412 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23672.32450 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25153.14000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12576.57000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 25153.14000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69331 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69331 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69331 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69331 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25153.14000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27513.62296 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.08412 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1200.29818 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27513.62296 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 43612.7 | 10.87 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 199508.0 | 12.59 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 28682.8 | 106.60 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 24299.0 | 137.77 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.917 | 0.806 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.1085495503E-002 | 0.1225401806 | Pass | Pass | 0.2887551374 | 1.5542576169 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 5.5296991971E-002 | 0.1270979844 | Pass | Pass | 0.2214267448 | 0.9873884484 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 6.0437306310E-002 | 0.1157008655 | Pass | Pass | 5.8086068430E-002 | 0.2159159526 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 5.9229240820E-002 | 0.1115049127 | Pass | Pass | 0.1651072315 | 0.7103030101 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 9.0989669648E-002 | 0.3792831668 | Pass | Pass | 6.8858552559E-002 | 0.4954228804 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.806 | 0.917 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.843 | 0.252 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.343 | 0.329 | 0.328 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.343 | 0.329 | 0.328 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.7888 | 379.89 | 2958.87 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 34.59 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 16.5511 | 1600.48 | 26489.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 50.90 | 0.0000 | Y | 253.10 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 12.6567 | 12.00 | 151.88 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.95 |
Interior Lighting Total | 15.0797 | 2293.99 | 34592.64 | 353.59 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4644.36 | AstronomicalClock | - | 83.75 | 83.75 | 73.02 | |
Exterior Lighting Total | 4644.36 | 73.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 45439.75 | 33739.01 | 11700.74 | 0.74 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 206054.21 | 139309.13 | 66745.08 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29730.48 | 20912.42 | 8818.06 | 0.70 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25153.14 | 17438.92 | 7714.22 | 0.69 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 43612.7 | 10.87 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 199508.0 | 12.59 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 28682.8 | 106.60 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 24299.0 | 137.77 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 32000.03 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 56538.92 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 218261.49 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33074.83 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27513.62 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 1.41 | 1565.07 | 1107.16 | 1.00 | 1.31 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.33 | 2488.68 | 1070.05 | 1.00 | 1.29 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.61 | 1110.54 | 8.30 | 15146.35 | 1825.35 | 1.00 | 1.15 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.33 | 1473.30 | 1107.16 | 1.00 | 1.34 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.08 | 1200.30 | 1107.16 | 1.00 | 1.38 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 26519.55 | 31823.46 | 83.77 | 1.938 | 2.326 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00769 | 34.82 | 0.00911 | 0.232 | 0.00 |
CORE_RETAIL | 93794.78 | 112553.74 | 70.32 | 6.816 | 8.179 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00797 | 34.82 | 0.00911 | 1.890 | 0.00 |
POINT_OF_SALE | 15050.07 | 18060.09 | 119.75 | 1.109 | 1.331 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00740 | 34.82 | 0.00911 | 0.178 | 0.00 |
FRONT_RETAIL | 12309.09 | 14770.90 | 97.94 | 0.903 | 1.084 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00754 | 34.82 | 0.00911 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 40.93 | 100.00 | 0.00001 | 42.00 | 0.00911 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 16709.91 | 20051.89 | 52.78 | 0.717 | 0.861 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00785 | 6.30 | 0.00607 | 0.232 | 0.00 |
CORE_RETAIL | 48896.09 | 58675.31 | 36.66 | 2.071 | 2.486 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00795 | 6.30 | 0.00607 | 1.890 | 0.00 |
POINT_OF_SALE | 8213.52 | 9856.22 | 65.36 | 0.354 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00789 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_RETAIL | 8218.13 | 9861.75 | 65.39 | 0.355 | 0.425 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00789 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_ENTRY | 26661.83 | 31994.19 | 2666.18 | 1.178 | 1.414 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.09 | 0.00693 | 6.30 | 0.00607 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.33 | 2.33 | 0.86 | 0.86 | 2.3258 | 2.3258 | 2.3258 | 1.0000 | 1.0000 |
PSZ-AC:2 | 8.30 | 8.30 | 2.49 | 2.49 | 8.2978 | 8.1790 | 8.2978 | 0.9857 | 1.0000 |
PSZ-AC:3 | 1.33 | 1.33 | 0.43 | 0.43 | 1.3307 | 1.3307 | 1.3307 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.08 | 1.08 | 0.43 | 0.43 | 1.0841 | 1.0841 | 1.0841 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 32000.031 | 32000.031 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32000.03 | 32000.03 | 1.413588 | 20.94 | 13.56 | 0.00691982 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.09 | 0.00692840 | 43.5011 | 31994.19 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 45439.750 | 0.000 | 2.325760 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 45439.75 | 40401.96 | 2.325760 | 25.02 | 15.89 | 0.00783014 | 12.80 | 10.33 | 0.00700000 | 34.82 | 0.00911022 | 20.12 | 9.9566 | 23.89 | 0.00768860 | 40.6712 | 26519.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 56538.920 | 56538.920 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56538.92 | 56538.92 | 2.325764 | 16.93 | 12.43 | 0.00737422 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 9.9566 | 21.11 | 0.00785346 | 49.1681 | 16709.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 206054.210 | 0.000 | 8.297800 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 206054.21 | 182373.65 | 8.297800 | 28.35 | 17.22 | 0.00803462 | 12.80 | 10.33 | 0.00700000 | 41.92 | 0.00911022 | 22.18 | 22.7797 | 23.89 | 0.00797070 | 42.1470 | 84396.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 218261.485 | 218261.485 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 218261.49 | 218261.49 | 8.297803 | 9.75 | 8.46 | 0.00652300 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 22.7797 | 21.11 | 0.00795362 | 49.7865 | 48896.09 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 29730.480 | 0.000 | 1.330700 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 29730.48 | 27315.94 | 1.330700 | 26.42 | 16.22 | 0.00763721 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 13.3847 | 23.89 | 0.00740097 | 39.1656 | 14088.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 33074.826 | 33074.826 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33074.83 | 33074.83 | 1.330704 | 14.77 | 11.30 | 0.00712607 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.3847 | 21.11 | 0.00788546 | 49.3660 | 8213.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 25153.140 | 0.000 | 1.084120 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 25153.14 | 22827.76 | 1.084120 | 26.94 | 16.50 | 0.00775551 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 16.4290 | 23.89 | 0.00753968 | 39.8918 | 11655.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 27513.623 | 27513.623 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27513.62 | 27513.62 | 1.084125 | 14.78 | 11.30 | 0.00712657 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 16.4290 | 21.11 | 0.00788558 | 49.3667 | 8218.13 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 32000.031 | 32000.031 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.413588 | 1.65924888 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 32000.03 | 32000.03 | 1.0000 | 1.65924888 | 1.413588 | 20.94 | 13.56 | 0.00691982 | 38615.5 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32000.03 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.09 | 0.00692840 | 21.09 | 0.00692840 | 43.5011 | 31994.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45439.750 | 0.000 | 2.325760 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3958 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 45439.75 | 40401.96 | 1.0000 | 2.72994327 | 2.325760 | 25.02 | 15.89 | 0.00783014 | 45085.7 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45439.75 | 34.82 | 0.00911022 | 20.12 | 0.23156651 | 9.9566 | 23.93 | 0.00768860 | 23.89 | 0.00768860 | 40.6712 | 26519.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56538.920 | 56538.920 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.325764 | 2.72994757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 56538.92 | 56538.92 | 1.0000 | 2.72994757 | 2.325764 | 16.93 | 12.43 | 0.00737422 | 35682.0 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56538.92 | 6.30 | 0.00607234 | 6.30 | 0.23156651 | 9.9566 | 20.84 | 0.00785346 | 21.11 | 0.00785346 | 49.1681 | 16709.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 206054.210 | 0.000 | 8.297800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7760 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 206054.21 | 182373.65 | 1.0000 | 9.73983699 | 8.297800 | 28.35 | 17.22 | 0.00803462 | 49000.7 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 206054.21 | 41.92 | 0.00911022 | 22.18 | 1.89021192 | 22.7797 | 23.89 | 0.00768134 | 23.89 | 0.00797070 | 42.1470 | 84396.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 218261.485 | 218261.485 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.297803 | 9.73984051 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 218261.49 | 218261.49 | 1.0000 | 9.73984051 | 8.297803 | 9.75 | 8.46 | 0.00652300 | 26229.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 218261.49 | 6.30 | 0.00607234 | 6.30 | 1.89021192 | 22.7797 | 20.70 | 0.00795362 | 21.11 | 0.00795362 | 49.7865 | 48896.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29730.480 | 0.000 | 1.330700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0372 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 29730.48 | 27315.94 | 1.0000 | 1.56195631 | 1.330700 | 26.42 | 16.22 | 0.00763721 | 46019.0 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29730.48 | 42.00 | 0.00911023 | 22.20 | 0.17811053 | 13.3847 | 23.89 | 0.00739828 | 23.89 | 0.00740097 | 39.1656 | 14088.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33074.826 | 33074.826 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.330704 | 1.56196095 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33074.83 | 33074.83 | 1.0000 | 1.56196095 | 1.330704 | 14.77 | 11.30 | 0.00712607 | 32861.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33074.83 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 13.3847 | 20.88 | 0.00788546 | 21.11 | 0.00788546 | 49.3660 | 8213.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25153.140 | 0.000 | 1.084120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2571 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 25153.14 | 22827.76 | 1.0000 | 1.27252429 | 1.084120 | 26.94 | 16.50 | 0.00775551 | 46858.5 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25153.14 | 42.00 | 0.00911023 | 22.20 | 0.17811053 | 16.4290 | 23.89 | 0.00748058 | 23.89 | 0.00753968 | 39.8918 | 11655.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27513.623 | 27513.623 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.084125 | 1.27252986 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27513.62 | 27513.62 | 1.0000 | 1.27252986 | 1.084125 | 14.78 | 11.30 | 0.00712657 | 32866.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27513.62 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 16.4290 | 20.88 | 0.00788558 | 21.11 | 0.00788558 | 49.3667 | 8218.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3051.83 | 1056.67 | 122.00 |
CORE_RETAIL | 3427.67 | 978.00 | 564.67 |
POINT_OF_SALE | 4100.33 | 277.00 | 81.00 |
FRONT_RETAIL | 3803.33 | 528.50 | 194.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4113.50 | 1507.17 | 572.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 1.67 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 3.17 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.17 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 4.83 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.372 | 0.023 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.720 | 0.004 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.719 | 0.025 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.719 | 0.025 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.339 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.660 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.660 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.659 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1674.43 | 3304.06 | 05-MAR-08:00 | 138655.95 | 10-JUN-16:00 |
Electricity:Building | 548.75 | 3083.31 | 14-MAY-08:00 | 41654.89 | 02-JAN-16:20 |
Electricity:Zone:BACK_SPACE | 84.58 | 607.80 | 01-JAN-00:10 | 5172.60 | 02-JAN-09:10 |
InteriorLights:Electricity | 353.59 | 1288.14 | 14-MAY-08:00 | 30883.85 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:BACK_SPACE | 34.59 | 147.94 | 01-JAN-00:10 | 2413.46 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 353.59 | 1288.14 | 14-MAY-08:00 | 30883.85 | 02-JAN-16:20 |
Electricity:Zone:CORE_RETAIL | 337.39 | 1658.43 | 14-MAY-08:00 | 28493.38 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 253.10 | 882.99 | 14-MAY-08:00 | 23840.77 | 02-JAN-16:20 |
Electricity:Zone:POINT_OF_SALE | 84.90 | 611.62 | 01-JAN-00:10 | 5167.35 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 39.92 | 197.87 | 01-JAN-00:10 | 2684.87 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1674.43 | 3304.06 | 05-MAR-08:00 | 138655.95 | 10-JUN-16:00 |
ElectricityPurchased:Plant | 1674.43 | 3304.06 | 05-MAR-08:00 | 138655.95 | 10-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1674.43 | 3304.06 | 05-MAR-08:00 | 138655.95 | 10-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1674.43 | 3304.06 | 05-MAR-08:00 | 138655.95 | 10-JUN-16:00 |
ElectricityNet:Plant | 1674.43 | 3304.06 | 05-MAR-08:00 | 138655.95 | 10-JUN-16:00 |
Cogeneration:ElectricityNet | 1674.43 | 3304.06 | 05-MAR-08:00 | 138655.95 | 10-JUN-16:00 |
Electricity:HVAC | 1052.67 | 0.00 | 01-JAN-00:10 | 102961.25 | 10-JUN-16:00 |
Fans:Electricity | 389.49 | 0.00 | 01-JAN-00:10 | 21873.70 | 01-JAN-09:40 |
General:Fans:Electricity | 389.49 | 0.00 | 01-JAN-00:10 | 21873.70 | 01-JAN-09:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 663.18 | 0.00 | 01-JAN-00:10 | 82652.62 | 10-JUN-16:00 |
ExteriorLights:Electricity | 73.02 | 0.00 | 01-JAN-07:20 | 4644.36 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 73.02 | 0.00 | 01-JAN-07:20 | 4644.36 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 90.27 | 1862.00 | 29-JAN-19:10 | 84518.92 | 02-JAN-07:10 |
Gas:Plant | 85.38 | 1862.00 | 29-JAN-19:10 | 4923.05 | 17-JAN-13:00 |
WaterSystems:Gas | 85.38 | 1862.00 | 29-JAN-19:10 | 4923.05 | 17-JAN-13:00 |
Water Heater:WaterSystems:Gas | 85.38 | 1862.00 | 29-JAN-19:10 | 4923.05 | 17-JAN-13:00 |
Gas:HVAC | 4.89 | 0.00 | 01-JAN-00:10 | 79984.74 | 02-JAN-07:10 |
Heating:Gas | 4.89 | 0.00 | 01-JAN-00:10 | 79984.74 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3223.71 | 0.00 | 01-JAN-00:10 | 365969.75 | 08-JUL-06:10 |
EnergyTransfer:Building | 1039.19 | 0.00 | 01-JAN-00:10 | 121018.59 | 12-JUN-06:10 |
EnergyTransfer:Zone:BACK_SPACE | 164.70 | 0.00 | 01-JAN-00:10 | 21314.19 | 05-JUL-06:10 |
Heating:EnergyTransfer | 9.96 | 0.00 | 01-JAN-00:10 | 56467.94 | 01-JAN-09:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.62 | 0.00 | 01-JAN-00:10 | 9503.55 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1029.23 | 0.00 | 01-JAN-00:10 | 115067.63 | 12-JUN-06:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 164.09 | 0.00 | 01-JAN-00:10 | 21314.19 | 05-JUL-06:10 |
EnergyTransfer:Zone:CORE_RETAIL | 636.18 | 0.00 | 01-JAN-00:10 | 80855.60 | 07-JUN-06:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 2.40 | 0.00 | 01-JAN-00:10 | 37836.00 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 633.79 | 0.00 | 01-JAN-00:10 | 73832.40 | 12-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 132.74 | 0.00 | 01-JAN-00:10 | 12941.87 | 02-OCT-14:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.14 | 0.00 | 01-JAN-00:10 | 3323.84 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 132.59 | 0.00 | 01-JAN-00:10 | 12941.87 | 02-OCT-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 98.90 | 0.00 | 01-JAN-00:10 | 10879.73 | 02-OCT-14:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.15 | 0.00 | 01-JAN-00:10 | 4209.01 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 98.76 | 0.00 | 01-JAN-00:10 | 10879.73 | 02-OCT-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 6.66 | 0.00 | 01-JAN-00:10 | 15067.48 | 31-DEC-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 6.66 | 0.00 | 01-JAN-00:10 | 15067.48 | 31-DEC-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 2184.52 | 0.00 | 01-JAN-00:10 | 270348.22 | 18-JUL-06:10 |
HeatingCoils:EnergyTransfer | 3.91 | 0.00 | 01-JAN-00:10 | 63987.79 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 2180.61 | 0.00 | 01-JAN-00:10 | 270348.22 | 18-JUL-06:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.618 | -164.082 | 0.000 | 0.000 | 36.738 | 34.587 | 49.992 | 0.000 | 0.000 | 2.414 | 41.323 | 0.000 | 0.000 | 0.000 | -1.591 | -0.005 |
CORE_RETAIL | 0.000 | 0.000 | 2.396 | -633.780 | 0.000 | 0.000 | 154.734 | 253.096 | 84.299 | 86.145 | 0.000 | 2.055 | 66.665 | 0.000 | -14.222 | 0.000 | -1.389 | -0.010 |
POINT_OF_SALE | 0.000 | 0.000 | 0.141 | -132.592 | 0.000 | 0.000 | 14.564 | 31.980 | 52.922 | 35.800 | 0.000 | 0.979 | 6.368 | 0.000 | -9.372 | 0.000 | -0.790 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.146 | -98.754 | 0.000 | 0.000 | 14.585 | 31.980 | 7.943 | 35.829 | 0.000 | 1.022 | 16.922 | 0.000 | -8.948 | 0.000 | -0.726 | -0.001 |
FRONT_ENTRY | 6.663 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.946 | 0.000 | 6.393 | 0.000 | 4.053 | 0.000 | 0.000 | -1.945 | 0.000 | -10.520 | -6.591 |
Total Facility | 6.663 | 0.000 | 3.301 | -1029.208 | 0.000 | 0.000 | 220.621 | 353.590 | 195.156 | 164.167 | 0.000 | 10.523 | 131.279 | 0.000 | -34.486 | 0.000 | -15.015 | -6.608 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -40617.94 | 0.00 | 0.00 | 0.00 | 147.94 | 613.14 | 0.00 | 0.00 | 0.87 | 39855.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 08-APR-06:02 | 0.00 | 0.00 | 0.00 | -170251.97 | 0.00 | 0.00 | 1595.72 | 2648.97 | 1550.87 | 0.00 | 0.00 | 0.00 | 165020.53 | 0.00 | -545.42 | 0.00 | -18.70 | 0.00 |
POINT_OF_SALE | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -26235.40 | 0.00 | 0.00 | 0.00 | 124.80 | 649.09 | 0.00 | 0.00 | 0.11 | 25785.79 | 0.00 | -324.39 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -22184.25 | 0.00 | 0.00 | 0.00 | 124.80 | 97.42 | 0.00 | 0.00 | 0.27 | 22254.10 | 0.00 | -292.35 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -258632.99 | 0.00 | 0.00 | 0.00 | 1729.63 | 2393.56 | 0.00 | 0.00 | 2.18 | 255990.63 | 0.00 | -1482.91 | 0.00 | -0.11 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 02-JAN-07:03 | 0.00 | 0.00 | 38013.44 | 0.00 | 0.00 | 0.00 | 531.24 | 536.32 | 1226.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -40307.29 |
CORE_RETAIL | 02-JAN-07:03 | 0.00 | 0.00 | 151339.62 | 0.00 | 0.00 | 0.00 | 2238.13 | 5297.95 | 2067.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1686.72 | 0.00 | 0.00 | -159256.81 |
POINT_OF_SALE | 02-JAN-07:03 | 0.00 | 0.00 | 13295.03 | 0.00 | 0.00 | 0.00 | 210.89 | 499.21 | 1298.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1264.70 | 0.00 | 0.00 | -14038.61 |
FRONT_RETAIL | 02-JAN-07:03 | 0.00 | 0.00 | 14710.07 | 0.00 | 0.00 | 0.00 | 210.89 | 499.21 | 194.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1247.44 | 0.00 | 0.00 | -14367.59 |
FRONT_ENTRY | 31-DEC-18:00 | 15069.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.75 | 0.00 | 0.00 | 0.00 | 0.00 | 653.58 | 0.00 | -223.88 | 0.00 | -15559.51 | 0.00 |
Total Facility | 02-JAN-07:03 | 780.33 | 0.00 | 217358.16 | 0.00 | 0.00 | 0.00 | 3191.17 | 6863.08 | 4787.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4454.72 | 0.00 | 0.00 | -228525.14 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.3258 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.3258 | 0.0996 | 1.0000 | 0.2316 | 0.0996 | ||
PSZ-AC:2 | 8.1790 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.2978 | 0.2278 | 1.0000 | 1.8902 | 0.2278 | ||
PSZ-AC:3 | 1.3307 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3307 | 0.1338 | 1.0000 | 0.1781 | 0.1338 | ||
PSZ-AC:4 | 1.0841 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0841 | 0.1643 | 1.0000 | 0.1781 | 0.1643 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.3258 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.3258 | 1.0000 | 1.0000 | 0.2316 | 0.0996 | ||
PSZ-AC:2 | 8.1790 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.1790 | 1.0000 | 1.0000 | 1.8902 | 0.2311 | ||
PSZ-AC:3 | 1.3307 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3307 | 1.0000 | 1.0000 | 0.1781 | 0.1338 | ||
PSZ-AC:4 | 1.0841 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0841 | 1.0000 | 1.0000 | 0.1781 | 0.1643 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.3258 | 2.3258 | 2.3258 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.1790 | 8.1790 | 8.1790 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3307 | 1.3307 | 1.3307 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0841 | 1.0841 | 1.0841 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.3258 | 2.3258 | 2.3258 | 2.3258 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.1790 | 8.2978 | 8.1790 | 8.1790 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3307 | 1.3307 | 1.3307 | 1.3307 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0841 | 1.0841 | 1.0841 | 1.0841 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.3258 | 2.3258 | 2.3258 | 0.2316 | 0.2691 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.1790 | 8.1790 | 8.1790 | 1.8902 | 0.7605 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.3307 | 1.3307 | 1.3307 | 0.1781 | 0.4188 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0841 | 1.0841 | 1.0841 | 0.1781 | 0.4186 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.3258 | 2.3258 | 2.3258 | 2.3258 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.1790 | 8.1790 | 8.1790 | 8.1790 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.3307 | 1.3307 | 1.3307 | 1.3307 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0841 | 1.0841 | 1.0841 | 1.0841 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 4.89 | 79984.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 663.18 | 82652.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 353.59 | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 73.02 | 4644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 389.49 | 21873.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.38 | 4923.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1674.43 |
Natural Gas | 0.00 | 90.27 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1764.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 154.14 |
Space Heating | 0.00 |
Space Cooling | 289.09 |
Fans (All) | 169.79 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 729.92 |
Subtotal | 729.92 |
Natural Gas [MJ/m2] | |
Space Heating | 2.13 |
Service Water Heating | 37.22 |
Miscellaneous (All) | 39.35 |
Subtotal | 39.35 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.04 |
Space Heating | 0.28 |
Space Cooling | 37.58 |
Fans (All) | 22.07 |
Service Water Heating | 4.84 |
Receptacle Equipment | 11.06 |
Miscellaneous | 4.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.293774E+10 |
February | 0.000 | 0.396030E+09 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 2079912.456 |
December | 0.000 | 0.155103E+10 |
Annual Sum or Average | 0.488688E+10 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.293774E+10 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316885E+10 | 5932.47 | 14-JAN-16:10 | 21.20 | 15.00 | 0.213581E+10 | 2451.30 | 24-JAN-15:20 | 20.57 | 11.66 |
February | 0.494685E+10 | 14957.22 | 25-FEB-07:03 | 18.20 | 15.79 | 0.198359E+10 | 2451.33 | 23-FEB-15:50 | 24.97 | 14.29 |
March | 0.991748E+10 | 38611.43 | 27-MAR-06:02 | 20.30 | 13.98 | 0.228125E+10 | 2451.30 | 24-MAR-14:20 | 26.80 | 14.41 |
April | 0.155293E+11 | 40617.49 | 28-APR-05:01 | 27.22 | 17.14 | 0.215733E+10 | 2451.34 | 14-APR-14:09 | 38.82 | 20.97 |
May | 0.209004E+11 | 40338.70 | 06-MAY-05:01 | 29.55 | 17.33 | 0.223346E+10 | 2451.37 | 30-MAY-14:00 | 40.70 | 24.50 |
June | 0.213851E+11 | 38037.98 | 07-JUN-05:01 | 33.20 | 19.47 | 0.220253E+10 | 2451.35 | 10-JUN-14:30 | 42.05 | 25.44 |
July | 0.215547E+11 | 33137.57 | 07-JUL-05:01 | 31.52 | 25.90 | 0.218818E+10 | 2451.35 | 06-JUL-14:39 | 39.77 | 25.32 |
August | 0.209405E+11 | 31631.10 | 15-AUG-05:01 | 26.82 | 25.45 | 0.228194E+10 | 2451.19 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.177415E+11 | 35628.50 | 27-SEP-05:02 | 23.08 | 20.68 | 0.215729E+10 | 2451.17 | 30-SEP-11:20 | 32.67 | 23.64 |
October | 0.146853E+11 | 38430.35 | 02-OCT-05:02 | 21.60 | 17.46 | 0.218486E+10 | 2451.29 | 17-OCT-14:00 | 32.80 | 18.32 |
November | 0.873710E+10 | 37373.17 | 02-NOV-06:02 | 16.88 | 13.39 | 0.210093E+10 | 2451.33 | 01-NOV-14:00 | 28.50 | 15.91 |
December | 0.457831E+10 | 7115.95 | 01-DEC-15:10 | 23.22 | 13.40 | 0.217193E+10 | 2451.32 | 01-DEC-15:09 | 23.22 | 13.40 |
Annual Sum or Average | 0.164085E+12 | 0.260791E+11 | ||||||||
Minimum of Months | 0.316885E+10 | 5932.47 | 16.88 | 13.39 | 0.198359E+10 | 2451.17 | 20.57 | 11.66 | ||
Maximum of Months | 0.215547E+11 | 40617.49 | 33.20 | 25.90 | 0.228194E+10 | 2451.37 | 42.05 | 26.11 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251056E+11 | 31699.27 | 14-JAN-16:40 | 20.90 | 14.82 | 0.903195E+10 | 10327.27 | 11-JAN-15:20 | 21.90 | 11.75 |
February | 0.301996E+11 | 90419.36 | 25-FEB-07:03 | 18.20 | 15.79 | 0.836688E+10 | 10327.09 | 11-FEB-11:20 | 17.80 | 12.65 |
March | 0.470771E+11 | 165559.11 | 27-MAR-06:02 | 20.30 | 13.98 | 0.961140E+10 | 10327.19 | 24-MAR-14:00 | 26.80 | 14.13 |
April | 0.621495E+11 | 170258.55 | 08-APR-06:02 | 23.28 | 14.20 | 0.908863E+10 | 10327.47 | 08-APR-10:30 | 30.50 | 16.31 |
May | 0.748343E+11 | 165227.50 | 06-MAY-05:01 | 29.55 | 17.33 | 0.940951E+10 | 10327.69 | 06-MAY-10:09 | 36.52 | 19.41 |
June | 0.734302E+11 | 150738.78 | 07-JUN-05:01 | 33.20 | 19.47 | 0.927923E+10 | 10327.35 | 05-JUN-14:09 | 42.75 | 22.44 |
July | 0.688962E+11 | 128172.66 | 01-JUL-05:01 | 29.33 | 23.52 | 0.921893E+10 | 10327.02 | 01-JUL-11:20 | 37.50 | 27.65 |
August | 0.667975E+11 | 119005.13 | 03-AUG-05:01 | 28.40 | 23.49 | 0.961395E+10 | 10326.95 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.594564E+11 | 136411.94 | 27-SEP-05:02 | 23.08 | 20.68 | 0.908872E+10 | 10326.81 | 29-SEP-14:50 | 31.93 | 22.64 |
October | 0.551674E+11 | 161278.61 | 23-OCT-06:02 | 19.08 | 14.20 | 0.920453E+10 | 10326.92 | 21-OCT-10:09 | 26.07 | 16.99 |
November | 0.411008E+11 | 153040.44 | 02-NOV-06:02 | 16.88 | 13.39 | 0.885003E+10 | 10327.02 | 25-NOV-12:20 | 22.27 | 12.91 |
December | 0.295746E+11 | 36101.72 | 01-DEC-15:20 | 23.03 | 13.47 | 0.915300E+10 | 10327.30 | 30-DEC-16:00 | 14.00 | 8.19 |
Annual Sum or Average | 0.633789E+12 | 0.109917E+12 | ||||||||
Minimum of Months | 0.251056E+11 | 31699.27 | 16.88 | 13.39 | 0.836688E+10 | 10326.81 | 14.00 | 8.19 | ||
Maximum of Months | 0.748343E+11 | 170258.55 | 33.20 | 23.52 | 0.961395E+10 | 10327.69 | 42.75 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.641263E+10 | 8246.38 | 12-JAN-15:10 | 23.55 | 14.23 | 0.861034E+09 | 973.20 | 12-JAN-15:30 | 23.45 | 14.33 |
February | 0.698109E+10 | 11678.85 | 25-FEB-07:03 | 18.20 | 15.79 | 0.790149E+09 | 973.20 | 21-FEB-15:00 | 26.10 | 15.64 |
March | 0.973609E+10 | 24019.90 | 27-MAR-06:02 | 20.30 | 13.98 | 0.905771E+09 | 973.21 | 09-MAR-15:30 | 30.70 | 17.88 |
April | 0.115809E+11 | 26234.51 | 28-APR-05:01 | 27.22 | 17.14 | 0.856427E+09 | 973.21 | 26-APR-14:30 | 39.05 | 22.00 |
May | 0.135818E+11 | 25800.77 | 06-MAY-05:01 | 29.55 | 17.33 | 0.886644E+09 | 973.19 | 19-MAY-14:50 | 41.02 | 23.17 |
June | 0.135360E+11 | 24091.80 | 13-JUN-04:02 | 32.82 | 22.61 | 0.874366E+09 | 973.18 | 03-JUN-14:20 | 40.47 | 22.53 |
July | 0.135518E+11 | 20701.85 | 07-JUL-04:02 | 31.73 | 26.03 | 0.868661E+09 | 973.09 | 01-JUL-11:20 | 37.50 | 27.65 |
August | 0.134666E+11 | 19746.56 | 15-AUG-05:01 | 26.82 | 25.45 | 0.905883E+09 | 973.08 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.124932E+11 | 23045.39 | 27-SEP-05:02 | 23.08 | 20.68 | 0.856395E+09 | 973.06 | 08-SEP-14:09 | 28.40 | 25.90 |
October | 0.129317E+11 | 25180.51 | 02-OCT-05:02 | 21.60 | 17.46 | 0.867379E+09 | 973.23 | 31-OCT-14:50 | 29.92 | 18.37 |
November | 0.106703E+11 | 24059.41 | 02-NOV-06:02 | 16.88 | 13.39 | 0.834396E+09 | 973.23 | 08-NOV-15:20 | 29.67 | 18.18 |
December | 0.765257E+10 | 9381.45 | 02-DEC-14:00 | 24.10 | 13.12 | 0.866794E+09 | 973.21 | 04-DEC-15:20 | 22.83 | 14.36 |
Annual Sum or Average | 0.132595E+12 | 0.103739E+11 | ||||||||
Minimum of Months | 0.641263E+10 | 8246.38 | 16.88 | 13.12 | 0.790149E+09 | 973.06 | 22.83 | 14.33 | ||
Maximum of Months | 0.135818E+11 | 26234.51 | 32.82 | 26.03 | 0.905883E+09 | 973.23 | 41.02 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388547E+10 | 6038.25 | 12-JAN-15:10 | 23.55 | 14.23 | 0.849470E+09 | 973.14 | 24-JAN-15:39 | 20.43 | 11.61 |
February | 0.455270E+10 | 7188.68 | 22-FEB-14:20 | 27.03 | 16.26 | 0.785810E+09 | 973.16 | 23-FEB-15:00 | 24.80 | 14.33 |
March | 0.683763E+10 | 19942.64 | 27-MAR-06:02 | 20.30 | 13.98 | 0.905456E+09 | 973.16 | 25-MAR-15:09 | 25.75 | 14.44 |
April | 0.875659E+10 | 22183.56 | 28-APR-05:01 | 27.22 | 17.14 | 0.856406E+09 | 973.18 | 28-APR-14:09 | 38.70 | 21.18 |
May | 0.106183E+11 | 21374.02 | 06-MAY-05:01 | 29.55 | 17.33 | 0.886640E+09 | 973.16 | 26-MAY-14:09 | 40.73 | 21.85 |
June | 0.105690E+11 | 19530.09 | 12-JUN-04:02 | 33.75 | 20.80 | 0.874363E+09 | 973.17 | 02-JUN-14:00 | 38.70 | 20.98 |
July | 0.105947E+11 | 16294.46 | 07-JUL-05:01 | 31.52 | 25.90 | 0.868664E+09 | 973.09 | 01-JUL-11:20 | 37.50 | 27.65 |
August | 0.104244E+11 | 15238.23 | 15-AUG-05:01 | 26.82 | 25.45 | 0.905886E+09 | 973.08 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.961148E+10 | 18460.05 | 27-SEP-05:02 | 23.08 | 20.68 | 0.856397E+09 | 973.07 | 08-SEP-14:09 | 28.40 | 25.90 |
October | 0.100186E+11 | 20663.87 | 02-OCT-05:02 | 21.60 | 17.46 | 0.867345E+09 | 973.18 | 23-OCT-14:39 | 31.13 | 18.01 |
November | 0.790975E+10 | 19885.31 | 02-NOV-06:02 | 16.88 | 13.39 | 0.834047E+09 | 973.18 | 04-NOV-15:09 | 30.07 | 17.54 |
December | 0.497785E+10 | 7227.60 | 02-DEC-14:00 | 24.10 | 13.12 | 0.862029E+09 | 973.18 | 01-DEC-15:50 | 22.48 | 13.65 |
Annual Sum or Average | 0.987566E+11 | 0.103525E+11 | ||||||||
Minimum of Months | 0.388547E+10 | 6038.25 | 16.88 | 13.12 | 0.785810E+09 | 973.07 | 20.43 | 11.61 | ||
Maximum of Months | 0.106183E+11 | 22183.56 | 33.75 | 25.90 | 0.905886E+09 | 973.18 | 40.73 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106492E+09 | 38014.21 | 02-JAN-07:03 | 6.78 |
February | 17900114.29 | 1523.91 | 25-FEB-07:07 | 18.20 |
March | 68055534.02 | 3198.11 | 11-MAR-07:06 | 23.87 |
April | 80414243.70 | 4807.06 | 16-APR-08:06 | 30.70 |
May | 57999299.16 | 5208.94 | 01-MAY-06:06 | 32.80 |
June | 43108367.95 | 5185.28 | 04-JUN-08:06 | 31.72 |
July | 36296526.65 | 4334.34 | 08-JUL-05:07 | 31.70 |
August | 36673436.11 | 4031.06 | 06-AUG-07:06 | 29.23 |
September | 49800956.10 | 3690.31 | 22-SEP-05:04 | 27.07 |
October | 54107916.05 | 3572.43 | 04-OCT-06:06 | 25.52 |
November | 25381509.54 | 2550.62 | 12-NOV-09:04 | 20.32 |
December | 41603028.93 | 1340.74 | 25-DEC-11:00 | 20.60 |
Annual Sum or Average | 0.617833E+09 | |||
Minimum of Months | 17900114.29 | 1340.74 | 6.78 | |
Maximum of Months | 0.106492E+09 | 38014.21 | 32.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109976E+09 | 151344.01 | 02-JAN-07:03 | 6.78 |
February | 4136354.78 | 5662.84 | 25-FEB-07:07 | 18.20 |
March | 0.157405E+09 | 17493.21 | 11-MAR-07:06 | 23.87 |
April | 0.369844E+09 | 32024.53 | 16-APR-08:06 | 30.70 |
May | 0.371083E+09 | 35946.55 | 01-MAY-06:06 | 32.80 |
June | 0.286027E+09 | 37446.20 | 07-JUN-06:06 | 33.87 |
July | 0.248619E+09 | 33919.01 | 02-JUL-07:06 | 33.57 |
August | 0.256631E+09 | 26204.30 | 08-AUG-05:06 | 30.10 |
September | 0.296659E+09 | 21248.23 | 02-SEP-05:04 | 27.20 |
October | 0.261438E+09 | 20951.65 | 04-OCT-06:06 | 25.52 |
November | 30729335.45 | 8297.88 | 12-NOV-09:20 | 20.73 |
December | 3241833.31 | 1936.97 | 24-DEC-10:23 | 17.75 |
Annual Sum or Average | 0.239579E+10 | |||
Minimum of Months | 3241833.31 | 1936.97 | 6.78 | |
Maximum of Months | 0.371083E+09 | 151344.01 | 33.87 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5559593.50 | 13295.37 | 02-JAN-07:03 | 6.78 |
February | 450292.87 | 877.15 | 25-FEB-07:07 | 18.20 |
March | 10346211.14 | 1752.75 | 12-MAR-08:04 | 21.93 |
April | 28652752.06 | 3228.24 | 27-APR-05:04 | 30.50 |
May | 20430504.22 | 3719.91 | 01-MAY-05:04 | 32.45 |
June | 15859583.43 | 3655.69 | 12-JUN-05:04 | 34.12 |
July | 10042576.54 | 3146.36 | 07-JUL-05:04 | 31.52 |
August | 12482752.89 | 2577.59 | 28-AUG-05:06 | 29.10 |
September | 21280139.95 | 2484.08 | 02-SEP-05:04 | 27.20 |
October | 14090369.59 | 2180.45 | 04-OCT-05:04 | 25.07 |
November | 1837520.54 | 1358.64 | 12-NOV-09:04 | 20.32 |
December | 107345.21 | 353.36 | 29-DEC-07:07 | 16.73 |
Annual Sum or Average | 0.141140E+09 | |||
Minimum of Months | 107345.21 | 353.36 | 6.78 | |
Maximum of Months | 28652752.06 | 13295.37 | 34.12 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18712417.91 | 14710.51 | 02-JAN-07:03 | 6.78 |
February | 901651.40 | 4323.84 | 11-FEB-07:03 | 9.97 |
March | 6846113.41 | 1266.88 | 11-MAR-07:06 | 23.87 |
April | 24537618.52 | 2557.08 | 27-APR-05:04 | 30.50 |
May | 22027233.43 | 3102.87 | 01-MAY-05:04 | 32.45 |
June | 17368498.03 | 3370.30 | 12-JUN-05:04 | 34.12 |
July | 11938060.69 | 2598.13 | 06-JUL-05:06 | 31.18 |
August | 14179590.65 | 2442.26 | 08-AUG-05:06 | 30.10 |
September | 20636196.41 | 1987.44 | 02-SEP-05:04 | 27.20 |
October | 8815961.79 | 1573.43 | 04-OCT-05:04 | 25.07 |
November | 455021.42 | 578.36 | 19-NOV-09:04 | 18.47 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.146418E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.78 | |
Maximum of Months | 24537618.52 | 14710.51 | 34.12 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328930E+10 | 13729.87 | 01-JAN-18:00 | 13.10 |
February | 0.816129E+09 | 11055.09 | 10-FEB-18:00 | 14.50 |
March | 58762160.10 | 1960.39 | 16-MAR-07:10 | 15.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 304245.96 | 1333.96 | 31-OCT-07:07 | 16.90 |
November | 73925988.52 | 2535.70 | 30-NOV-18:00 | 19.10 |
December | 0.242482E+10 | 15067.48 | 31-DEC-18:00 | 12.10 |
Annual Sum or Average | 0.666324E+10 | |||
Minimum of Months | 0.00 | 0.00 | 12.10 | |
Maximum of Months | 0.328930E+10 | 15067.48 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.290080E+10 | 2413.46 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.263912E+10 | 2413.46 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.300979E+10 | 2413.46 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.284005E+10 | 2413.46 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.295530E+10 | 2413.46 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.290440E+10 | 2413.46 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.289095E+10 | 2413.46 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.300979E+10 | 2413.46 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.284005E+10 | 2413.46 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.290080E+10 | 2413.46 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.280526E+10 | 2413.46 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.289095E+10 | 2413.46 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.345872E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.263912E+10 | 2413.46 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.300979E+10 | 2413.46 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.235969E+11 | 23840.77 | 02-JAN-16:19 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.202557E+11 | 23840.77 | 01-FEB-16:40 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.211709E+11 | 23840.77 | 01-MAR-17:10 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.200304E+11 | 23840.77 | 22-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.207535E+11 | 23840.77 | 31-MAY-16:30 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.199209E+11 | 19867.31 | 01-JUN-16:00 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.190888E+11 | 23840.77 | 18-JUL-08:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.202891E+11 | 23840.77 | 14-AUG-16:40 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.195727E+11 | 23840.77 | 05-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.215418E+11 | 23840.77 | 02-OCT-16:00 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.229763E+11 | 23840.77 | 01-NOV-16:30 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.238989E+11 | 23840.77 | 01-DEC-16:10 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.253096E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.190888E+11 | 19867.31 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.238989E+11 | 23840.77 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.163184E+09 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.148475E+09 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.169362E+09 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.159794E+09 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.166273E+09 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.163430E+09 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.162637E+09 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.169362E+09 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.159794E+09 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.163184E+09 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.157798E+09 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.162637E+09 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194593E+10 | ||||
Minimum of Months | 0.148475E+09 | 136.69 | 0.00 | 0.00 | |
Maximum of Months | 0.169362E+09 | 136.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362628E+09 |
February | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5840965.75 | 0.410133E+09 |
March | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75298300.20 | 0.275573E+09 |
April | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289952E+09 | 23307239.76 |
May | 0.536353E+10 | 0.295530E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561537E+09 | 12843369.04 |
June | 0.528933E+10 | 0.290440E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422843E+09 | 6407408.28 |
July | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491437E+09 | 4776111.26 |
August | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284060E+09 | 7645227.66 |
September | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175038E+09 | 12881263.10 |
October | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87094358.69 | 26961817.09 |
November | 0.504819E+10 | 0.280526E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20671305.93 | 95100675.93 |
December | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 197041.86 | 0.352407E+09 |
Annual Sum or Average | 0.628175E+11 | 0.345872E+11 | 0.499918E+11 | 0.241397E+10 | 0.159066E+10 | ||||
Minimum of Months | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4776111.26 |
Maximum of Months | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561537E+09 | 0.410133E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.235969E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316916E+09 |
February | 0.201852E+11 | 0.202557E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4781645.40 | 0.361639E+09 |
March | 0.230879E+11 | 0.211709E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61379905.74 | 0.250669E+09 |
April | 0.218263E+11 | 0.200304E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237905E+09 | 20275429.86 |
May | 0.225967E+11 | 0.207535E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476499E+09 | 9551346.92 |
June | 0.222841E+11 | 0.199209E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358512E+09 | 4725344.75 |
July | 0.221389E+11 | 0.190888E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430944E+09 | 2620156.56 |
August | 0.230879E+11 | 0.202891E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249346E+09 | 4059455.76 |
September | 0.218263E+11 | 0.195727E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147286E+09 | 7591474.45 |
October | 0.221054E+11 | 0.215418E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71446854.36 | 21694724.63 |
November | 0.212681E+11 | 0.229763E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16921189.64 | 81427576.92 |
December | 0.221389E+11 | 0.238989E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161345.31 | 0.307754E+09 |
Annual Sum or Average | 0.264651E+12 | 0.253096E+12 | 0.842987E+11 | 0.205518E+10 | 0.138892E+10 | ||||
Minimum of Months | 0.201852E+11 | 0.190888E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2620156.56 |
Maximum of Months | 0.230879E+11 | 0.238989E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476499E+09 | 0.361639E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170864E+09 |
February | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2530956.42 | 0.194587E+09 |
March | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31634225.79 | 0.145798E+09 |
April | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120615E+09 | 15716554.69 |
May | 0.212923E+10 | 0.273260E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225846E+09 | 9413270.41 |
June | 0.209978E+10 | 0.268587E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172033E+09 | 3552823.20 |
July | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194643E+09 | 4176429.97 |
August | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112317E+09 | 6143599.31 |
September | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72837250.56 | 11154732.99 |
October | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37112232.69 | 15039434.32 |
November | 0.200405E+10 | 0.259332E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8956042.72 | 46767246.06 |
December | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85377.23 | 0.166650E+09 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.529224E+11 | 0.978610E+09 | 0.789863E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3552823.20 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225846E+09 | 0.194587E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162402E+09 |
February | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2531186.29 | 0.184089E+09 |
March | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31902376.43 | 0.130728E+09 |
April | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122650E+09 | 11771223.63 |
May | 0.212923E+10 | 0.273260E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236796E+09 | 5805093.84 |
June | 0.209978E+10 | 0.268587E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179991E+09 | 2649514.05 |
July | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207624E+09 | 2034109.39 |
August | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119509E+09 | 3507343.05 |
September | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74309323.75 | 6399610.01 |
October | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37273157.85 | 13103418.74 |
November | 0.200405E+10 | 0.259332E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8957235.41 | 44296938.93 |
December | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85376.10 | 0.158959E+09 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.794328E+10 | 0.102163E+10 | 0.725746E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2034109.39 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236796E+09 | 0.184089E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412437E+10 |
February | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148344E+10 |
March | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61784710.95 | 0.391340E+09 |
April | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605230E+09 | 35558504.67 |
May | 0.00 | 0.166273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112142E+10 | 10405203.12 |
June | 0.00 | 0.163430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101187E+10 | 17076680.97 |
July | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577594E+09 | 12812069.42 |
August | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367000E+09 | 26593593.54 |
September | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237665E+09 | 31156243.08 |
October | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70930742.92 | 0.215585E+09 |
November | 0.00 | 0.157798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772390E+09 |
December | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339911E+10 |
Annual Sum or Average | 0.00 | 0.194593E+10 | 0.405350E+10 | 0.105198E+11 | |||||
Minimum of Months | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10405203.12 |
Maximum of Months | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112142E+10 | 0.412437E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2413.46 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1076.99 | 15-JAN-19:01 |
February | 5888.82 | 01-FEB-15:09 | 2413.46 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 19-FEB-15:00 | 1872.04 | 09-FEB-21:10 |
March | 5888.82 | 01-MAR-15:09 | 2413.46 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 608.71 | 26-MAR-18:03 | 2711.06 | 24-MAR-24:00 |
April | 5888.82 | 01-APR-10:09 | 2413.46 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.75 | 02-APR-18:03 | 323.10 | 10-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 2413.46 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2010.46 | 28-MAY-18:02 | 288.19 | 15-MAY-03:00 |
June | 5888.82 | 01-JUN-14:09 | 2413.46 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1662.27 | 17-JUN-21:03 | 297.55 | 18-JUN-04:00 |
July | 5888.82 | 01-JUL-10:09 | 2413.46 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.39 | 20-JUL-20:03 | 249.19 | 19-JUL-03:00 |
August | 5888.82 | 01-AUG-14:09 | 2413.46 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 728.38 | 15-AUG-20:03 | 314.07 | 15-AUG-24:00 |
September | 5888.82 | 01-SEP-14:09 | 2413.46 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.72 | 02-SEP-21:03 | 180.24 | 19-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 2413.46 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.03 | 03-OCT-15:00 | 474.14 | 12-OCT-03:00 |
November | 5888.82 | 01-NOV-14:09 | 2413.46 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.26 | 13-NOV-14:00 | 744.20 | 28-NOV-05:00 |
December | 5888.82 | 01-DEC-15:09 | 2413.46 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 28-DEC-14:00 | 1673.45 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 | |||||
Maximum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 2010.46 | 2711.06 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 23840.77 | 02-JAN-16:19 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 889.56 | 15-JAN-19:10 |
February | 24809.68 | 01-FEB-15:09 | 23840.77 | 01-FEB-16:40 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.02 | 19-FEB-15:00 | 1594.97 | 09-FEB-21:20 |
March | 24809.68 | 01-MAR-15:09 | 23840.77 | 01-MAR-17:10 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 495.94 | 26-MAR-18:03 | 2870.62 | 24-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 23840.77 | 22-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 960.21 | 02-APR-18:03 | 272.24 | 10-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 23840.77 | 31-MAY-16:30 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1653.63 | 28-MAY-18:02 | 214.32 | 15-MAY-03:00 |
June | 24809.68 | 01-JUN-14:09 | 19867.31 | 01-JUN-16:00 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1373.69 | 17-JUN-21:03 | 243.99 | 18-JUN-05:00 |
July | 24809.68 | 01-JUL-10:09 | 23840.77 | 18-JUL-08:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 922.85 | 20-JUL-20:03 | 194.79 | 19-JUL-03:00 |
August | 24809.68 | 01-AUG-14:09 | 23840.77 | 14-AUG-16:40 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 604.65 | 15-AUG-20:03 | 226.75 | 15-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 23840.77 | 05-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 402.17 | 02-SEP-21:03 | 123.73 | 19-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 23840.77 | 02-OCT-16:00 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 376.54 | 03-OCT-15:00 | 396.54 | 12-OCT-03:00 |
November | 24809.68 | 01-NOV-14:09 | 23840.77 | 01-NOV-16:30 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.55 | 13-NOV-14:00 | 667.75 | 28-NOV-05:00 |
December | 24809.68 | 01-DEC-15:09 | 23840.77 | 01-DEC-16:10 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 28-DEC-14:00 | 1557.02 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 19867.31 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.73 | |||||
Maximum of Months | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1653.63 | 2870.62 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 469.33 | 15-JAN-19:01 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 19-FEB-15:00 | 828.60 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 247.17 | 26-MAR-18:03 | 1468.46 | 24-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.92 | 30-APR-18:02 | 156.77 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 863.89 | 28-MAY-18:02 | 166.08 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 713.35 | 17-JUN-21:03 | 143.97 | 18-JUN-04:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 475.10 | 20-JUL-20:03 | 127.23 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 308.24 | 15-AUG-20:03 | 163.58 | 15-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 205.87 | 02-SEP-21:03 | 104.55 | 19-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.35 | 03-OCT-15:00 | 238.34 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.33 | 13-NOV-14:00 | 386.29 | 28-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 28-DEC-14:00 | 784.03 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.55 | |||||
Maximum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 863.89 | 1468.46 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 435.88 | 15-JAN-19:10 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 19-FEB-15:00 | 810.27 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 251.85 | 26-MAR-18:03 | 1320.02 | 24-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.91 | 02-APR-18:03 | 135.49 | 10-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 866.14 | 28-MAY-18:02 | 123.39 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 717.11 | 17-JUN-21:03 | 118.85 | 18-JUN-04:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 479.15 | 20-JUL-20:03 | 100.87 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 311.85 | 15-AUG-20:03 | 139.26 | 15-AUG-24:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 207.80 | 02-SEP-21:03 | 83.59 | 19-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 199.35 | 03-OCT-15:00 | 207.63 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.33 | 13-NOV-14:00 | 359.45 | 28-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 | 28-DEC-14:00 | 730.74 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.59 | |||||
Maximum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 866.14 | 1320.02 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 13889.52 | 01-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 11358.68 | 10-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.43 | 28-MAR-11:02 | 2092.14 | 01-MAR-08:70 |
April | 0.00 | 01-APR-00:10 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3377.58 | 16-APR-11:01 | 1180.67 | 05-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4963.44 | 01-MAY-11:01 | 714.76 | 31-MAY-16:53 |
June | 0.00 | 01-JUN-00:10 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4915.70 | 12-JUN-11:01 | 1267.79 | 27-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3234.24 | 06-JUL-11:01 | 839.86 | 18-JUL-11:03 |
August | 0.00 | 01-AUG-00:10 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.52 | 05-AUG-11:02 | 673.02 | 16-AUG-07:02 |
September | 0.00 | 01-SEP-00:10 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.04 | 11-SEP-11:02 | 670.03 | 19-SEP-07:02 |
October | 0.00 | 01-OCT-00:10 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1226.81 | 02-OCT-11:02 | 1989.23 | 31-OCT-07:01 |
November | 0.00 | 01-NOV-00:10 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3416.11 | 30-NOV-18:00 |
December | 0.00 | 01-DEC-00:10 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 15607.32 | 21-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.03 | ||||
Maximum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4963.44 | 15607.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5932.47 | 14-JAN-16:10 | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.28 |
February | 14957.22 | 25-FEB-07:03 | 2208.31 | 804.49 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.33 |
March | 38611.43 | 27-MAR-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.69 |
April | 40617.49 | 28-APR-05:01 | 0.00 | 1035.60 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
May | 40338.70 | 06-MAY-05:01 | 0.00 | 1035.60 | 3219.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 | 0.00 |
June | 38037.98 | 07-JUN-05:01 | 0.00 | 1183.55 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 98.57 | 0.00 |
July | 33137.57 | 07-JUL-05:01 | 0.00 | 1035.60 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 | 0.00 |
August | 31631.10 | 15-AUG-05:01 | 0.00 | 1035.60 | 4292.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
September | 35628.50 | 27-SEP-05:02 | 0.00 | 887.66 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 |
October | 38430.35 | 02-OCT-05:02 | 0.00 | 887.66 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
November | 37373.17 | 02-NOV-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.59 |
December | 7115.95 | 01-DEC-15:10 | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5932.47 | 0.00 | 804.49 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40617.49 | 5888.82 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 98.57 | 125.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31699.27 | 14-JAN-16:40 | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 |
February | 90419.36 | 25-FEB-07:03 | 9303.63 | 7946.92 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.18 |
March | 165559.11 | 27-MAR-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.75 |
April | 170258.55 | 08-APR-06:02 | 15506.05 | 13244.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 |
May | 165227.50 | 06-MAY-05:01 | 0.00 | 9271.41 | 5428.04 | 0.00 | 0.00 | 0.00 | 0.00 | 29.56 | 0.00 |
June | 150738.78 | 07-JUN-05:01 | 0.00 | 10595.90 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 89.23 | 0.00 |
July | 128172.66 | 01-JUL-05:01 | 0.00 | 9271.41 | 5428.04 | 0.00 | 0.00 | 0.00 | 0.00 | 37.55 | 0.00 |
August | 119005.13 | 03-AUG-05:01 | 0.00 | 9271.41 | 7237.38 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 | 0.00 |
September | 136411.94 | 27-SEP-05:02 | 0.00 | 7946.92 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
October | 161278.61 | 23-OCT-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 |
November | 153040.44 | 02-NOV-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.49 |
December | 36101.72 | 01-DEC-15:20 | 24809.68 | 21854.04 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 31699.27 | 0.00 | 7946.92 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 170258.55 | 24809.68 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 89.23 | 115.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8246.38 | 12-JAN-15:10 | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
February | 11678.85 | 25-FEB-07:03 | 876.66 | 748.82 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.02 |
March | 24019.90 | 27-MAR-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 |
April | 26234.51 | 28-APR-05:01 | 0.00 | 873.62 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 0.00 |
May | 25800.77 | 06-MAY-05:01 | 0.00 | 873.62 | 3407.70 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 0.00 |
June | 24091.80 | 13-JUN-04:02 | 0.00 | 748.82 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20701.85 | 07-JUL-04:02 | 0.00 | 624.02 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19746.56 | 15-AUG-05:01 | 0.00 | 873.62 | 4543.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
September | 23045.39 | 27-SEP-05:02 | 0.00 | 748.82 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
October | 25180.51 | 02-OCT-05:02 | 0.00 | 748.82 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
November | 24059.41 | 02-NOV-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.04 |
December | 9381.45 | 02-DEC-14:00 | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8246.38 | 0.00 | 624.02 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26234.51 | 2337.76 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 56.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6038.25 | 12-JAN-15:10 | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
February | 7188.68 | 22-FEB-14:20 | 2045.54 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 0.00 |
March | 19942.64 | 27-MAR-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.30 |
April | 22183.56 | 28-APR-05:01 | 0.00 | 873.62 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 0.00 |
May | 21374.02 | 06-MAY-05:01 | 0.00 | 873.62 | 511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 |
June | 19530.09 | 12-JUN-04:02 | 0.00 | 748.82 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 102.97 | 0.00 |
July | 16294.46 | 07-JUL-05:01 | 0.00 | 873.62 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 | 0.00 |
August | 15238.23 | 15-AUG-05:01 | 0.00 | 873.62 | 681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
September | 18460.05 | 27-SEP-05:02 | 0.00 | 748.82 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
October | 20663.87 | 02-OCT-05:02 | 0.00 | 748.82 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
November | 19885.31 | 02-NOV-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 |
December | 7227.60 | 02-DEC-14:00 | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6038.25 | 0.00 | 748.82 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22183.56 | 2337.76 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 102.97 | 53.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 0.00 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 10.05 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.101212E+12 | 86679.26 | 14-JAN-17:49 | 0.106082E+11 | 84518.92 | 02-JAN-07:10 |
February | 0.987144E+11 | 90573.52 | 24-FEB-16:40 | 0.729038E+10 | 16411.52 | 10-FEB-17:40 |
March | 0.125348E+12 | 106429.33 | 28-MAR-16:40 | 0.753018E+10 | 4893.78 | 01-MAR-12:39 |
April | 0.142564E+12 | 120179.67 | 26-APR-14:00 | 0.704122E+10 | 4841.15 | 03-APR-11:09 |
May | 0.169598E+12 | 130922.26 | 02-MAY-14:20 | 0.705877E+10 | 4791.13 | 01-MAY-11:20 |
June | 0.172111E+12 | 138655.95 | 10-JUN-15:00 | 0.669027E+10 | 4743.12 | 01-JUN-11:20 |
July | 0.172889E+12 | 132054.34 | 01-JUL-16:40 | 0.680130E+10 | 4715.01 | 03-JUL-11:20 |
August | 0.172723E+12 | 125588.17 | 08-AUG-16:00 | 0.689707E+10 | 4737.40 | 31-AUG-11:09 |
September | 0.155996E+12 | 123450.78 | 14-SEP-16:00 | 0.680027E+10 | 4779.84 | 29-SEP-11:09 |
October | 0.139857E+12 | 115641.26 | 03-OCT-14:39 | 0.721336E+10 | 4836.83 | 31-OCT-11:20 |
November | 0.117720E+12 | 100001.37 | 08-NOV-17:30 | 0.718634E+10 | 5966.17 | 30-NOV-17:00 |
December | 0.105697E+12 | 87532.33 | 16-DEC-17:30 | 0.915373E+10 | 21608.08 | 22-DEC-17:00 |
Annual Sum or Average | 0.167443E+13 | 0.902711E+11 | ||||
Minimum of Months | 0.987144E+11 | 86679.26 | 0.669027E+10 | 4715.01 | ||
Maximum of Months | 0.172889E+12 | 138655.95 | 0.106082E+11 | 84518.92 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.320246E+11 | 0.701670E+10 | 0.164409E+11 | 0.00 | 0.341553E+11 | 0.00 | 0.00 | 0.115741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.279235E+11 | 0.607203E+10 | 0.149157E+11 | 0.00 | 0.300804E+11 | 0.00 | 0.00 | 0.197228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299168E+11 | 0.629218E+10 | 0.168545E+11 | 0.00 | 0.331911E+11 | 0.00 | 0.00 | 0.390932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.282825E+11 | 0.566797E+10 | 0.160165E+11 | 0.00 | 0.318034E+11 | 0.00 | 0.00 | 0.607937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293403E+11 | 0.548684E+10 | 0.166477E+11 | 0.00 | 0.328315E+11 | 0.00 | 0.00 | 0.852917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.283605E+11 | 0.511065E+10 | 0.162772E+11 | 0.00 | 0.320371E+11 | 0.00 | 0.00 | 0.903253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.274880E+11 | 0.538931E+10 | 0.163871E+11 | 0.00 | 0.326228E+11 | 0.00 | 0.00 | 0.910021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.290350E+11 | 0.568748E+10 | 0.168545E+11 | 0.00 | 0.331239E+11 | 0.00 | 0.00 | 0.880224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278248E+11 | 0.590762E+10 | 0.160165E+11 | 0.00 | 0.318041E+11 | 0.00 | 0.00 | 0.744434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.299694E+11 | 0.654297E+10 | 0.164409E+11 | 0.00 | 0.325348E+11 | 0.00 | 0.00 | 0.543686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311260E+11 | 0.669624E+10 | 0.159174E+11 | 0.00 | 0.314513E+11 | 0.00 | 0.00 | 0.325292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322982E+11 | 0.714767E+10 | 0.163871E+11 | 0.00 | 0.338554E+11 | 0.00 | 0.00 | 0.160086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353590E+12 | 0.730177E+11 | 0.195156E+12 | 0.389491E+12 | 0.00 | 0.663175E+12 | |||||||
Minimum of Months | 0.274880E+11 | 0.511065E+10 | 0.149157E+11 | 0.00 | 0.300804E+11 | 0.00 | 0.00 | 0.115741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.322982E+11 | 0.714767E+10 | 0.168545E+11 | 0.00 | 0.341553E+11 | 0.00 | 0.00 | 0.910021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.293774E+10 | 0.00 | 0.767051E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.396030E+09 | 0.00 | 0.689434E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.753018E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.704122E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.705877E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.669027E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.680130E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.689707E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.680027E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.721336E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2079912.46 | 0.00 | 0.718427E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.155103E+10 | 0.00 | 0.760270E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.488688E+10 | 0.853843E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.669027E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.293774E+10 | 0.00 | 0.767051E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30883.85 | 02-JAN-16:19 | 4644.36 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 21873.70 | 01-JAN-09:39 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30883.85 | 01-FEB-16:40 | 4644.36 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 21873.70 | 01-FEB-16:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30883.85 | 01-MAR-17:10 | 4644.36 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 21873.70 | 17-MAR-07:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30883.85 | 22-APR-16:00 | 4644.36 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 20308.63 | 01-APR-05:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30883.85 | 31-MAY-16:30 | 4644.36 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 20308.63 | 01-MAY-05:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26910.39 | 01-JUN-16:00 | 4644.36 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 20308.63 | 01-JUN-06:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30883.85 | 18-JUL-08:09 | 4644.36 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 20308.63 | 01-JUL-05:19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30883.85 | 14-AUG-16:40 | 4644.36 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 20308.63 | 01-AUG-05:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30883.85 | 05-SEP-08:09 | 4644.36 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 20308.63 | 02-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30883.85 | 02-OCT-16:00 | 4644.36 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 20621.64 | 31-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30883.85 | 01-NOV-16:30 | 4644.36 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 21873.70 | 25-NOV-19:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30883.85 | 01-DEC-16:10 | 4644.36 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 21873.70 | 06-DEC-17:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 26910.39 | 4644.36 | 10771.04 | 0.00 | 20308.63 | 0.00 | 0.00 | |||||
Maximum of Months | 30883.85 | 4644.36 | 10771.04 | 0.00 | 21873.70 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 22800.06 | 12-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31958.72 | 24-FEB-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 49370.34 | 28-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 64176.34 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74918.93 | 02-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82652.62 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78295.20 | 01-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72548.99 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66051.18 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 59704.55 | 03-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40035.23 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25815.15 | 28-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 22800.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82652.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 86679.26 | 14-JAN-17:49 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21873.70 | 0.00 | 0.00 | 18506.31 | 0.00 |
February | 90573.52 | 24-FEB-16:40 | 28897.12 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 30596.73 | 0.00 |
March | 106429.33 | 28-MAR-16:40 | 28897.12 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 46452.54 | 0.00 |
April | 120179.67 | 26-APR-14:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 64176.34 | 0.00 |
May | 130922.26 | 02-MAY-14:20 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 74918.93 | 0.00 |
June | 138655.95 | 10-JUN-15:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 82652.62 | 0.00 |
July | 132054.34 | 01-JUL-16:40 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 76051.02 | 0.00 |
August | 125588.17 | 08-AUG-16:00 | 26910.39 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 67598.11 | 0.00 |
September | 123450.78 | 14-SEP-16:00 | 28897.12 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 63473.99 | 0.00 |
October | 115641.26 | 03-OCT-14:39 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 59637.93 | 0.00 |
November | 100001.37 | 08-NOV-17:30 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 20308.63 | 0.00 | 0.00 | 33393.49 | 0.00 |
December | 87532.33 | 16-DEC-17:30 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21873.70 | 0.00 | 0.00 | 19359.39 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 86679.26 | 24923.66 | 10771.04 | 0.00 | 0.00 | 20308.63 | 0.00 | 0.00 | 18506.31 | 0.00 | |
Maximum of Months | 138655.95 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 21873.70 | 0.00 | 0.00 | 82652.62 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 79984.74 | 02-JAN-07:10 | 0.00 | 4923.05 | 17-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 11862.53 | 10-FEB-17:00 | 0.00 | 4919.08 | 01-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4893.78 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4841.15 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4791.13 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4743.12 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4715.01 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4737.40 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4779.84 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4836.83 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 1206.00 | 30-NOV-17:00 | 0.00 | 4885.78 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 16878.01 | 31-DEC-17:00 | 0.00 | 4916.53 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4715.01 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79984.74 | 0.00 | 4923.05 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.21 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.22 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 26.21 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.22 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.43 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.43 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.41 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.41 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.41 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 28.42 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.43 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 360.67 | 23.39 | 0.50 | 21.30 | 0.50 | 21.30 |
February | 196.00 | 23.63 | 10.50 | 23.89 | 0.00 | 0.00 |
March | 38.00 | 23.86 | 157.83 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 346.17 | 23.89 | 0.00 | 0.00 |
May | 4.50 | 24.00 | 418.00 | 23.89 | 4.50 | 24.00 |
June | 15.50 | 23.94 | 408.00 | 23.89 | 15.50 | 23.94 |
July | 37.17 | 23.95 | 415.00 | 23.90 | 37.17 | 23.95 |
August | 31.83 | 23.95 | 422.00 | 23.89 | 31.83 | 23.95 |
September | 31.67 | 23.92 | 405.00 | 23.89 | 31.67 | 23.92 |
October | 0.83 | 23.94 | 375.33 | 23.89 | 0.83 | 23.94 |
November | 44.33 | 23.81 | 93.50 | 23.89 | 0.00 | 0.00 |
December | 296.17 | 23.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1056.67 | 23.60 | 3051.83 | 23.89 | 122.00 | 23.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 360.67 | 24.00 | 422.00 | 23.90 | 37.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 210.00 | 23.12 | 17.17 | 23.84 | 0.33 | 21.33 |
February | 58.67 | 23.17 | 74.17 | 23.89 | 0.00 | 0.00 |
March | 10.17 | 23.84 | 276.67 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 372.17 | 23.89 | 0.00 | 0.00 |
May | 3.67 | 23.93 | 418.00 | 23.89 | 3.67 | 23.93 |
June | 47.83 | 23.91 | 408.00 | 23.89 | 47.83 | 23.91 |
July | 142.67 | 23.90 | 415.00 | 23.89 | 142.67 | 23.90 |
August | 223.83 | 23.90 | 422.00 | 23.89 | 223.83 | 23.90 |
September | 145.33 | 23.90 | 405.00 | 23.89 | 145.33 | 23.90 |
October | 1.00 | 23.93 | 397.83 | 23.89 | 1.00 | 23.93 |
November | 11.83 | 23.48 | 208.33 | 23.89 | 0.00 | 0.00 |
December | 123.00 | 23.31 | 13.33 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 978.00 | 23.61 | 3427.67 | 23.89 | 564.67 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 13.33 | 23.84 | 0.00 | 0.00 |
Maximum of Months | 223.83 | 23.93 | 422.00 | 23.89 | 223.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.50 | 23.02 | 127.33 | 23.89 | 0.17 | 21.26 |
February | 37.50 | 23.25 | 215.50 | 23.89 | 0.00 | 0.00 |
March | 5.17 | 23.89 | 340.50 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 393.50 | 23.89 | 0.00 | 0.00 |
May | 1.67 | 23.99 | 418.00 | 23.89 | 1.67 | 23.99 |
June | 10.00 | 23.94 | 408.00 | 23.89 | 10.00 | 23.94 |
July | 24.33 | 23.95 | 415.00 | 23.89 | 24.33 | 23.95 |
August | 24.00 | 23.94 | 422.00 | 23.89 | 24.00 | 23.94 |
September | 20.33 | 23.92 | 405.00 | 23.89 | 20.33 | 23.92 |
October | 0.50 | 23.95 | 414.00 | 23.89 | 0.50 | 23.95 |
November | 3.17 | 23.80 | 350.83 | 23.89 | 0.00 | 0.00 |
December | 57.83 | 23.47 | 190.67 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 277.00 | 23.44 | 4100.33 | 23.89 | 81.00 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 127.33 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 92.50 | 23.99 | 422.00 | 23.89 | 24.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 152.00 | 22.71 | 54.17 | 23.86 | 0.50 | 21.21 |
February | 64.67 | 22.85 | 154.83 | 23.89 | 0.00 | 0.00 |
March | 18.17 | 23.70 | 300.17 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 373.17 | 23.89 | 0.00 | 0.00 |
May | 5.17 | 23.96 | 418.00 | 23.89 | 5.17 | 23.96 |
June | 23.00 | 23.92 | 408.00 | 23.89 | 23.00 | 23.92 |
July | 48.83 | 23.92 | 415.00 | 23.89 | 48.83 | 23.92 |
August | 54.67 | 23.92 | 422.00 | 23.89 | 54.67 | 23.92 |
September | 60.50 | 23.91 | 405.00 | 23.89 | 60.50 | 23.91 |
October | 2.00 | 23.92 | 407.83 | 23.89 | 2.00 | 23.92 |
November | 8.67 | 23.44 | 322.33 | 23.89 | 0.00 | 0.00 |
December | 90.83 | 23.02 | 122.83 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 528.50 | 23.27 | 3803.33 | 23.89 | 194.67 | 23.91 |
Minimum of Months | 0.00 | 0.00 | 54.17 | 23.86 | 0.00 | 0.00 |
Maximum of Months | 152.00 | 23.96 | 422.00 | 23.89 | 60.50 | 23.96 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.42898 | 44.33253 | 0.13955 | 6.30549 |
February | 376.00000 | 23.73915 | 44.46873 | 0.27102 | 6.89518 |
March | 422.00000 | 23.89434 | 44.33942 | 0.38844 | 8.23778 |
April | 405.00000 | 23.91234 | 44.33762 | 0.48238 | 9.94033 |
May | 418.00000 | 23.91402 | 49.94390 | -0.2626 | 6.52082 |
June | 408.00000 | 23.91475 | 53.51268 | -0.2232 | 6.14290 |
July | 415.00000 | 23.91664 | 57.60254 | -0.2002 | 5.93467 |
August | 422.00000 | 23.91540 | 58.10176 | -0.2117 | 6.00672 |
September | 405.00000 | 23.91476 | 56.57014 | -0.2611 | 6.49186 |
October | 414.00000 | 23.91135 | 47.42535 | 0.48855 | 10.04868 |
November | 399.00000 | 23.88365 | 43.91330 | 0.37267 | 7.97397 |
December | 415.00000 | 23.69296 | 42.25482 | 0.22549 | 6.44689 |
Annual Sum or Average | 4913.00000 | 23.83703 | 48.94723 | 0.09861 | 7.24229 |
Minimum of Months | 376.00000 | 23.42898 | 42.25482 | -0.2626 | 5.93467 |
Maximum of Months | 422.00000 | 23.91664 | 58.10176 | 0.48855 | 10.04868 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.47694 | 40.15851 | 0.22076 | 6.86281 |
February | 376.00000 | 23.76622 | 40.91671 | 0.34583 | 7.78002 |
March | 422.00000 | 23.89735 | 41.16530 | 0.44122 | 9.14971 |
April | 405.00000 | 23.91199 | 41.60204 | 0.52048 | 10.76174 |
May | 418.00000 | 23.91387 | 49.10092 | -0.2165 | 6.07868 |
June | 408.00000 | 23.91450 | 54.49172 | -0.1795 | 5.77658 |
July | 415.00000 | 23.91583 | 60.68321 | -0.1690 | 5.66946 |
August | 422.00000 | 23.91527 | 62.13136 | -0.1771 | 5.71180 |
September | 405.00000 | 23.91485 | 59.57868 | -0.2187 | 6.06168 |
October | 414.00000 | 23.90960 | 46.59428 | 0.51974 | 10.71909 |
November | 399.00000 | 23.87901 | 40.95071 | 0.41725 | 8.71621 |
December | 415.00000 | 23.70380 | 38.47166 | 0.29256 | 7.13818 |
Annual Sum or Average | 4913.00000 | 23.84366 | 48.05926 | 0.14742 | 7.52695 |
Minimum of Months | 376.00000 | 23.47694 | 38.47166 | -0.2187 | 5.66946 |
Maximum of Months | 422.00000 | 23.91583 | 62.13136 | 0.52048 | 10.76174 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.67466 | 37.63658 | 0.32431 | 7.89616 |
February | 376.00000 | 23.82002 | 38.73314 | 0.41240 | 8.88009 |
March | 422.00000 | 23.90283 | 39.40581 | 0.49535 | 10.27706 |
April | 405.00000 | 23.91180 | 40.27563 | 0.56666 | 11.84846 |
May | 418.00000 | 23.91298 | 46.58352 | -0.1555 | 5.62772 |
June | 408.00000 | 23.91322 | 50.63247 | -0.1200 | 5.43843 |
July | 415.00000 | 23.91412 | 55.02879 | -0.0990 | 5.31684 |
August | 422.00000 | 23.91345 | 55.60915 | -0.1056 | 5.32864 |
September | 405.00000 | 23.91324 | 53.25883 | -0.1342 | 5.50666 |
October | 414.00000 | 23.91255 | 42.59927 | 0.61054 | 12.93181 |
November | 399.00000 | 23.90221 | 37.97321 | 0.52668 | 10.95045 |
December | 415.00000 | 23.82254 | 35.91617 | 0.39058 | 8.50198 |
Annual Sum or Average | 4913.00000 | 23.87644 | 44.53134 | 0.22368 | 8.19284 |
Minimum of Months | 376.00000 | 23.67466 | 35.91617 | -0.1555 | 5.31684 |
Maximum of Months | 422.00000 | 23.91412 | 55.60915 | 0.61054 | 12.93181 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.42776 | 39.82312 | 0.24510 | 7.39102 |
February | 376.00000 | 23.69467 | 40.60455 | 0.35868 | 8.27464 |
March | 422.00000 | 23.88723 | 40.62322 | 0.46202 | 9.62675 |
April | 405.00000 | 23.91138 | 40.91305 | 0.53589 | 11.13369 |
May | 418.00000 | 23.91323 | 47.74575 | -0.1953 | 5.91279 |
June | 408.00000 | 23.91369 | 52.32363 | -0.1578 | 5.64937 |
July | 415.00000 | 23.91503 | 57.33816 | -0.1312 | 5.46650 |
August | 422.00000 | 23.91430 | 58.16986 | -0.1369 | 5.48082 |
September | 405.00000 | 23.91381 | 55.77092 | -0.1666 | 5.69656 |
October | 414.00000 | 23.91118 | 43.80544 | 0.58402 | 12.25691 |
November | 399.00000 | 23.88444 | 38.96939 | 0.49223 | 10.23021 |
December | 415.00000 | 23.68261 | 37.43568 | 0.33173 | 7.87670 |
Annual Sum or Average | 4913.00000 | 23.83155 | 46.18826 | 0.18288 | 7.90412 |
Minimum of Months | 376.00000 | 23.42776 | 37.43568 | -0.1953 | 5.46650 |
Maximum of Months | 422.00000 | 23.91503 | 58.16986 | 0.58402 | 12.25691 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.424248E+10 | 0.118096E+10 | 270.58 | 0.362013E+10 | 0.622350E+09 | 0.00 | 0.26 | 14-JAN-15:30 | 0.00 | 01-JAN-00:10 | 9676.48 | 14-JAN-15:30 | 7789.24 | 14-JAN-15:30 | 2126.89 | 17-JAN-16:00 | 2622.73 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.787140E+10 | 0.219794E+10 | 322.19 | 0.671078E+10 | 0.116062E+10 | 0.00 | 0.56 | 25-FEB-07:03 | 0.00 | 01-FEB-00:10 | 22655.38 | 25-FEB-07:03 | 17431.58 | 25-FEB-07:03 | 5223.81 | 25-FEB-07:03 | 5615.34 | 25-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.163742E+11 | 0.473101E+10 | 416.39 | 0.141628E+11 | 0.221147E+10 | 0.00 | 1.00 | 10-MAR-07:02 | 0.00 | 01-MAR-00:10 | 47406.81 | 11-MAR-07:02 | 42362.74 | 27-MAR-06:02 | 10435.62 | 11-MAR-07:02 | 10538.23 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.250535E+11 | 0.781321E+10 | 425.63 | 0.225446E+11 | 0.250895E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 47917.63 | 17-APR-05:02 | 45064.67 | 28-APR-05:01 | 10888.08 | 03-APR-06:02 | 11417.44 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.359076E+11 | 0.113745E+11 | 446.61 | 0.300247E+11 | 0.588285E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 51209.39 | 24-MAY-05:02 | 45192.35 | 06-MAY-05:01 | 23704.85 | 24-MAY-05:02 | 11711.85 | 31-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.393959E+11 | 0.121061E+11 | 439.57 | 0.304616E+11 | 0.893435E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 52282.57 | 26-JUN-05:02 | 43918.62 | 12-JUN-04:02 | 29780.15 | 26-JUN-05:04 | 12011.62 | 14-JUN-04:02 | 0.00 | 01-JUN-00:10 |
July | 0.437032E+11 | 0.124064E+11 | 447.20 | 0.298819E+11 | 0.138214E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 52374.58 | 26-JUL-05:02 | 38478.60 | 07-JUL-05:01 | 30285.05 | 20-JUL-05:05 | 12118.91 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.430787E+11 | 0.119132E+11 | 452.27 | 0.287068E+11 | 0.143719E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 52153.04 | 10-AUG-05:01 | 35872.29 | 15-AUG-05:01 | 26627.12 | 10-AUG-05:06 | 11550.51 | 13-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.353928E+11 | 0.990222E+10 | 432.47 | 0.245980E+11 | 0.107948E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 52347.23 | 03-SEP-07:02 | 39251.04 | 27-SEP-05:02 | 27666.23 | 03-SEP-07:03 | 11269.22 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.244891E+11 | 0.707800E+10 | 430.85 | 0.202541E+11 | 0.423498E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 49503.65 | 12-OCT-06:02 | 41771.86 | 02-OCT-05:02 | 19647.55 | 12-OCT-06:04 | 10782.64 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.138119E+11 | 0.390886E+10 | 386.82 | 0.119519E+11 | 0.186001E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 47050.51 | 09-NOV-07:02 | 40134.08 | 02-NOV-06:02 | 10383.98 | 09-NOV-07:02 | 10145.80 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.636333E+10 | 0.176643E+10 | 329.54 | 0.549719E+10 | 0.866144E+09 | 0.00 | 0.28 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 | 10337.33 | 28-DEC-15:20 | 9443.27 | 01-DEC-15:10 | 1950.27 | 16-DEC-16:10 | 2912.53 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.295684E+12 | 0.863789E+11 | 4800.13 | 0.228414E+12 | 0.672698E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.424248E+10 | 0.118096E+10 | 270.58 | 0.362013E+10 | 0.622350E+09 | 0.00 | 0.26 | 0.00 | 9676.48 | 7789.24 | 1950.27 | 2622.73 | 0.00 | |||||||
Maximum of Months | 0.437032E+11 | 0.124064E+11 | 452.27 | 0.304616E+11 | 0.143719E+11 | 0.00 | 1.00 | 0.00 | 52374.58 | 45192.35 | 30285.05 | 12118.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.252187E+11 | 0.763453E+10 | 287.32 | 0.210332E+11 | 0.418558E+10 | 0.00 | 0.31 | 12-JAN-15:50 | 0.00 | 01-JAN-00:10 | 52630.53 | 14-JAN-15:00 | 44882.84 | 12-JAN-15:10 | 12078.24 | 17-JAN-16:00 | 15584.24 | 12-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 0.450593E+11 | 0.136514E+11 | 331.17 | 0.372782E+11 | 0.778107E+10 | 0.00 | 0.73 | 25-FEB-07:03 | 0.00 | 01-FEB-00:10 | 142825.91 | 25-FEB-07:03 | 99758.18 | 25-FEB-07:03 | 43067.73 | 25-FEB-07:03 | 36866.84 | 25-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.880649E+11 | 0.275173E+11 | 419.09 | 0.735736E+11 | 0.144913E+11 | 0.00 | 1.00 | 10-MAR-07:02 | 0.00 | 01-MAR-00:10 | 213865.11 | 10-MAR-07:02 | 178811.25 | 26-MAR-08:62 | 64350.31 | 10-MAR-07:02 | 52289.53 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.127776E+12 | 0.429729E+11 | 427.15 | 0.111390E+12 | 0.163855E+11 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 218082.72 | 26-APR-06:02 | 193333.67 | 09-APR-08:62 | 69553.94 | 26-APR-06:02 | 57027.38 | 16-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.177180E+12 | 0.601309E+11 | 446.69 | 0.140512E+12 | 0.366684E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 226029.21 | 24-MAY-06:02 | 196789.90 | 01-MAY-05:01 | 98599.80 | 24-MAY-06:04 | 58555.10 | 04-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.195298E+12 | 0.636539E+11 | 437.05 | 0.138629E+12 | 0.566687E+11 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 232017.34 | 26-JUN-06:02 | 186251.26 | 12-JUN-05:01 | 117196.97 | 26-JUN-06:04 | 59793.14 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.211852E+12 | 0.636835E+11 | 445.50 | 0.127384E+12 | 0.844680E+11 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 232793.22 | 18-JUL-06:02 | 160377.27 | 05-JUL-05:01 | 119832.69 | 18-JUL-06:06 | 60382.12 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.211198E+12 | 0.616422E+11 | 452.10 | 0.120690E+12 | 0.905076E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 233891.61 | 12-AUG-06:02 | 145381.27 | 07-AUG-05:01 | 123596.89 | 12-AUG-06:06 | 57473.92 | 08-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.175150E+12 | 0.520578E+11 | 433.19 | 0.106604E+12 | 0.685455E+11 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 233495.82 | 10-SEP-08:62 | 151984.90 | 27-SEP-05:02 | 123361.85 | 10-SEP-08:04 | 56318.23 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.118932E+12 | 0.372820E+11 | 427.14 | 0.921837E+11 | 0.267482E+11 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 224426.81 | 12-OCT-06:02 | 171205.00 | 23-OCT-06:02 | 97096.46 | 12-OCT-06:04 | 54118.14 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.713792E+11 | 0.219555E+11 | 385.63 | 0.594722E+11 | 0.119070E+11 | 0.00 | 1.00 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 | 214357.94 | 09-NOV-07:02 | 162006.11 | 12-NOV-09:02 | 67562.07 | 09-NOV-07:02 | 50691.37 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.350248E+11 | 0.105757E+11 | 336.31 | 0.292946E+11 | 0.573023E+10 | 0.00 | 0.34 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 | 57568.30 | 28-DEC-15:30 | 49983.76 | 02-DEC-14:40 | 11799.87 | 29-DEC-16:00 | 17535.40 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.148213E+13 | 0.462758E+12 | 4828.34 | 0.105804E+13 | 0.424087E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.252187E+11 | 0.763453E+10 | 287.32 | 0.210332E+11 | 0.418558E+10 | 0.00 | 0.31 | 0.00 | 52630.53 | 44882.84 | 11799.87 | 15584.24 | 0.00 | |||||||
Maximum of Months | 0.211852E+12 | 0.636835E+11 | 452.10 | 0.140512E+12 | 0.905076E+11 | 0.00 | 1.00 | 0.00 | 233891.61 | 196789.90 | 123596.89 | 60382.12 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.674451E+10 | 0.178506E+10 | 352.08 | 0.601197E+10 | 0.732537E+09 | 0.00 | 0.43 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 10420.73 | 12-JAN-15:10 | 9670.94 | 12-JAN-15:10 | 1594.29 | 18-JAN-13:40 | 2746.32 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.875984E+10 | 0.233140E+10 | 349.81 | 0.770504E+10 | 0.105480E+10 | 0.00 | 0.65 | 25-FEB-07:03 | 0.00 | 01-FEB-00:10 | 17890.47 | 25-FEB-07:03 | 13491.94 | 25-FEB-07:03 | 4398.53 | 25-FEB-07:03 | 4235.15 | 25-FEB-07:03 | 0.00 | 01-FEB-00:10 |
March | 0.140314E+11 | 0.389902E+10 | 426.81 | 0.123252E+11 | 0.170619E+10 | 0.00 | 1.00 | 10-MAR-07:02 | 0.00 | 01-MAR-00:10 | 30749.06 | 11-MAR-07:02 | 26599.04 | 27-MAR-06:02 | 7137.32 | 11-MAR-07:02 | 6740.13 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.181119E+11 | 0.550689E+10 | 427.82 | 0.163167E+11 | 0.179511E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 31475.87 | 17-APR-05:02 | 29325.94 | 28-APR-05:01 | 8090.69 | 24-APR-06:02 | 7341.39 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.239961E+11 | 0.747509E+10 | 451.15 | 0.198979E+11 | 0.409819E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 33663.68 | 24-MAY-05:02 | 29286.23 | 06-MAY-05:01 | 15974.06 | 24-MAY-05:02 | 7594.85 | 04-MAY-04:02 | 0.00 | 01-MAY-00:10 |
June | 0.260725E+11 | 0.787565E+10 | 442.92 | 0.198163E+11 | 0.625623E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 34207.64 | 26-JUN-05:02 | 28263.68 | 12-JUN-04:02 | 19645.85 | 26-JUN-05:04 | 7719.85 | 14-JUN-04:02 | 0.00 | 01-JUN-00:10 |
July | 0.288158E+11 | 0.804044E+10 | 450.62 | 0.192257E+11 | 0.959016E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 34267.83 | 26-JUL-05:02 | 24645.69 | 07-JUL-04:02 | 19900.32 | 20-JUL-05:05 | 7785.97 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.288337E+11 | 0.781571E+10 | 455.15 | 0.186989E+11 | 0.101348E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 34210.62 | 19-AUG-05:02 | 22922.24 | 09-AUG-04:02 | 17643.69 | 19-AUG-05:03 | 7437.37 | 08-AUG-04:02 | 0.00 | 01-AUG-00:10 |
September | 0.248222E+11 | 0.677817E+10 | 433.87 | 0.170663E+11 | 0.775587E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 34249.94 | 03-SEP-07:02 | 25440.15 | 27-SEP-05:02 | 18531.08 | 03-SEP-07:03 | 7251.07 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.197351E+11 | 0.549580E+10 | 436.90 | 0.165312E+11 | 0.320386E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 32343.13 | 12-OCT-06:02 | 27347.99 | 02-OCT-05:02 | 13458.62 | 12-OCT-06:02 | 6920.91 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.140488E+11 | 0.376583E+10 | 398.99 | 0.124759E+11 | 0.157290E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 30573.59 | 09-NOV-07:02 | 25840.18 | 02-NOV-06:02 | 6877.51 | 09-NOV-07:02 | 6486.90 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.856671E+10 | 0.225653E+10 | 381.53 | 0.766512E+10 | 0.901586E+09 | 0.00 | 0.47 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 11662.95 | 29-DEC-07:03 | 10909.52 | 02-DEC-14:00 | 1785.89 | 29-DEC-07:03 | 3024.55 | 28-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.222538E+12 | 0.630256E+11 | 5007.64 | 0.173736E+12 | 0.488023E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.674451E+10 | 0.178506E+10 | 349.81 | 0.601197E+10 | 0.732537E+09 | 0.00 | 0.43 | 0.00 | 10420.73 | 9670.94 | 1594.29 | 2746.32 | 0.00 | |||||||
Maximum of Months | 0.288337E+11 | 0.804044E+10 | 455.15 | 0.198979E+11 | 0.101348E+11 | 0.00 | 1.00 | 0.00 | 34267.83 | 29325.94 | 19900.32 | 7785.97 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.363575E+10 | 0.973515E+09 | 283.00 | 0.317506E+10 | 0.460687E+09 | 0.00 | 0.39 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 | 7914.32 | 12-JAN-15:10 | 7189.86 | 12-JAN-15:10 | 1375.70 | 13-JAN-14:00 | 2109.01 | 12-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.572066E+10 | 0.154209E+10 | 317.49 | 0.491579E+10 | 0.804868E+09 | 0.00 | 0.49 | 22-FEB-14:20 | 0.00 | 01-FEB-00:10 | 10097.54 | 22-FEB-14:20 | 9090.88 | 22-FEB-14:20 | 2328.11 | 25-FEB-07:03 | 2784.93 | 22-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 0.104864E+11 | 0.294589E+10 | 414.21 | 0.898618E+10 | 0.150020E+10 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 26092.71 | 11-MAR-07:02 | 21674.54 | 27-MAR-06:02 | 6748.24 | 10-MAR-07:02 | 5712.54 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.147481E+11 | 0.450075E+10 | 425.93 | 0.130601E+11 | 0.168798E+10 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 26547.83 | 17-APR-05:02 | 24548.80 | 28-APR-05:01 | 7818.26 | 24-APR-06:02 | 6209.12 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.203464E+11 | 0.631115E+10 | 449.39 | 0.164739E+11 | 0.387252E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 28424.89 | 24-MAY-05:02 | 24114.46 | 01-MAY-05:01 | 14231.08 | 24-MAY-05:02 | 6370.63 | 31-MAY-05:01 | 0.00 | 01-MAY-00:10 |
June | 0.223364E+11 | 0.668959E+10 | 440.55 | 0.163945E+11 | 0.594187E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 28941.00 | 26-JUN-05:02 | 23017.97 | 12-JUN-04:02 | 17235.85 | 26-JUN-05:02 | 6530.40 | 14-JUN-04:02 | 0.00 | 01-JUN-00:10 |
July | 0.249259E+11 | 0.687178E+10 | 448.50 | 0.158004E+11 | 0.912548E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:10 | 28991.93 | 26-JUL-05:02 | 19357.35 | 07-JUL-05:01 | 17362.51 | 20-JUL-05:03 | 6592.50 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.248258E+11 | 0.665125E+10 | 453.01 | 0.151831E+11 | 0.964274E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:10 | 28943.52 | 19-AUG-05:02 | 17971.20 | 09-AUG-05:01 | 15806.56 | 19-AUG-05:03 | 6274.96 | 08-AUG-05:04 | 0.00 | 01-AUG-00:10 |
September | 0.210491E+11 | 0.570520E+10 | 432.99 | 0.137360E+11 | 0.731302E+10 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:10 | 28976.78 | 03-SEP-07:02 | 20124.33 | 27-SEP-05:02 | 16339.22 | 03-SEP-07:03 | 6143.58 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.161727E+11 | 0.451283E+10 | 431.35 | 0.131751E+11 | 0.299760E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 27594.61 | 12-OCT-06:02 | 22051.03 | 02-OCT-05:02 | 12630.97 | 12-OCT-06:02 | 5873.54 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.107213E+11 | 0.289894E+10 | 387.92 | 0.929979E+10 | 0.142156E+10 | 0.00 | 1.00 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 | 25988.68 | 09-NOV-07:02 | 20829.49 | 02-NOV-06:02 | 7050.16 | 09-NOV-07:02 | 5508.61 | 09-NOV-07:02 | 0.00 | 01-NOV-00:10 |
December | 0.528750E+10 | 0.140993E+10 | 340.27 | 0.459705E+10 | 0.690452E+09 | 0.00 | 0.44 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 | 8932.04 | 02-DEC-14:00 | 8483.95 | 02-DEC-14:00 | 1357.79 | 16-DEC-14:20 | 2372.39 | 02-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.180256E+12 | 0.510129E+11 | 4824.60 | 0.134797E+12 | 0.454590E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.363575E+10 | 0.973515E+09 | 283.00 | 0.317506E+10 | 0.460687E+09 | 0.00 | 0.39 | 0.00 | 7914.32 | 7189.86 | 1357.79 | 2109.01 | 0.00 | |||||||
Maximum of Months | 0.249259E+11 | 0.687178E+10 | 453.01 | 0.164739E+11 | 0.964274E+10 | 0.00 | 1.00 | 0.00 | 28991.93 | 24548.80 | 17362.51 | 6592.50 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.02 | 42.55 | 37.47 | 91.20 | 59.44 | 6.00 | 0.00 | 744.00 |
February | 102.03 | 57.10 | 44.92 | 125.28 | 48.62 | 0.00 | 0.00 | 672.00 |
March | 135.00 | 80.16 | 54.84 | 178.61 | 33.99 | 0.00 | 0.00 | 744.00 |
April | 175.52 | 122.75 | 52.77 | 247.52 | 20.34 | 0.00 | 0.00 | 720.00 |
May | 185.22 | 127.65 | 57.58 | 268.79 | 10.30 | 0.00 | 0.00 | 744.00 |
June | 173.59 | 110.15 | 63.44 | 255.58 | 6.25 | 0.00 | 0.00 | 720.00 |
July | 121.69 | 43.38 | 78.31 | 183.04 | 3.80 | 0.00 | 0.00 | 744.00 |
August | 104.93 | 29.53 | 75.40 | 157.10 | 5.85 | 0.00 | 0.00 | 744.00 |
September | 108.96 | 46.46 | 62.49 | 154.51 | 12.36 | 0.00 | 0.00 | 720.00 |
October | 120.78 | 76.35 | 44.43 | 166.14 | 30.76 | 0.00 | 0.00 | 744.00 |
November | 101.42 | 66.79 | 34.63 | 129.81 | 47.47 | 0.00 | 0.00 | 720.00 |
December | 77.91 | 41.88 | 36.04 | 90.12 | 60.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.93 | 70.33 | 53.60 | 170.73 | 28.19 | 6.00 | 0.00 | 8760.00 |
Minimum of Months | 77.91 | 29.53 | 34.63 | 90.12 | 3.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 185.22 | 127.65 | 78.31 | 268.79 | 60.19 | 6.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1201.31 | 714.67 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1210.56 | 575.91 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1128.09 | 362.76 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 970.40 | 150.67 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 948.01 | 41.91 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 966.59 | 24.49 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 901.54 | 13.18 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 840.37 | 33.96 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 953.63 | 92.86 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1479.64 | 315.21 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1690.00 | 544.23 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1340.84 | 711.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1135.20 | 297.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 840.37 | 13.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1690.00 | 714.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1206.70 | 690.59 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1212.13 | 556.13 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1125.82 | 346.20 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 968.40 | 137.26 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 950.15 | 33.75 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 972.31 | 19.37 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 906.65 | 8.99 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 841.07 | 26.14 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 951.44 | 79.47 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1475.89 | 301.30 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1688.12 | 528.37 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1343.44 | 691.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1136.13 | 283.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 841.07 | 8.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1688.12 | 691.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.13 | 113.12 | 73.01 | 250.07 | 133.35 | 0.00 | 0.00 | 744.00 |
February | 176.96 | 98.29 | 78.66 | 247.26 | 109.18 | 0.00 | 0.00 | 672.00 |
March | 151.25 | 66.79 | 84.47 | 216.95 | 74.87 | 0.00 | 0.00 | 744.00 |
April | 106.22 | 29.94 | 76.27 | 156.37 | 37.98 | 0.00 | 0.00 | 720.00 |
May | 76.37 | 5.61 | 70.76 | 128.43 | 15.44 | 0.00 | 0.00 | 744.00 |
June | 69.88 | 1.17 | 68.71 | 130.37 | 9.55 | 0.00 | 0.00 | 720.00 |
July | 72.90 | 0.99 | 71.91 | 130.63 | 5.34 | 3.67 | 0.00 | 744.00 |
August | 77.34 | 4.12 | 73.22 | 128.93 | 11.94 | 0.00 | 0.00 | 744.00 |
September | 103.67 | 26.89 | 76.78 | 159.08 | 26.96 | 7.50 | 0.00 | 720.00 |
October | 178.38 | 99.61 | 78.78 | 275.67 | 73.98 | 0.00 | 0.00 | 744.00 |
November | 222.88 | 147.34 | 75.54 | 334.49 | 110.51 | 0.00 | 0.00 | 720.00 |
December | 198.92 | 124.67 | 74.25 | 277.69 | 133.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 134.83 | 59.66 | 75.18 | 202.72 | 61.66 | 11.17 | 0.00 | 8760.00 |
Minimum of Months | 69.88 | 0.99 | 68.71 | 128.43 | 5.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 222.88 | 147.34 | 84.47 | 334.49 | 133.45 | 7.50 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214320E+09 | 0.113961E+09 | 0.100359E+09 | 0.244273E+09 | 0.159203E+09 |
February | 0.246820E+09 | 0.138147E+09 | 0.108673E+09 | 0.303089E+09 | 0.117632E+09 |
March | 0.361595E+09 | 0.214707E+09 | 0.146888E+09 | 0.478390E+09 | 91028144.38 |
April | 0.454937E+09 | 0.318167E+09 | 0.136771E+09 | 0.641567E+09 | 52723326.90 |
May | 0.496103E+09 | 0.341893E+09 | 0.154210E+09 | 0.719935E+09 | 27585746.50 |
June | 0.449956E+09 | 0.285516E+09 | 0.164441E+09 | 0.662474E+09 | 16197253.93 |
July | 0.325929E+09 | 0.116191E+09 | 0.209738E+09 | 0.490249E+09 | 10175157.76 |
August | 0.281048E+09 | 79099543.10 | 0.201948E+09 | 0.420783E+09 | 15670445.05 |
September | 0.282413E+09 | 0.120436E+09 | 0.161977E+09 | 0.400491E+09 | 32039833.43 |
October | 0.323499E+09 | 0.204504E+09 | 0.118996E+09 | 0.444991E+09 | 82374931.17 |
November | 0.262887E+09 | 0.173114E+09 | 89772742.24 | 0.336456E+09 | 0.123035E+09 |
December | 0.208680E+09 | 0.112160E+09 | 96520417.23 | 0.241388E+09 | 0.161207E+09 |
Annual Sum or Average | 0.390819E+10 | 0.221789E+10 | 0.169029E+10 | 0.538409E+10 | 0.888872E+09 |
Minimum of Months | 0.208680E+09 | 79099543.10 | 89772742.24 | 0.241388E+09 | 10175157.76 |
Maximum of Months | 0.496103E+09 | 0.341893E+09 | 0.209738E+09 | 0.719935E+09 | 0.161207E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.321758E+10 | 0.191416E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.292858E+10 | 0.139325E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.302149E+10 | 0.971603E+09 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.251527E+10 | 0.390542E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.253914E+10 | 0.112241E+09 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.250540E+10 | 63481798.77 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.241468E+10 | 35297605.86 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.225084E+10 | 90963227.37 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.247180E+10 | 0.240682E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.396306E+10 | 0.844258E+09 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.438047E+10 | 0.141065E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.359131E+10 | 0.190472E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.357996E+11 | 0.937186E+10 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.225084E+10 | 35297605.86 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.438047E+10 | 0.191416E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.323203E+10 | 0.184967E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.293239E+10 | 0.134540E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.301540E+10 | 0.927256E+09 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.251008E+10 | 0.355776E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.254488E+10 | 90399562.62 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.252023E+10 | 50203549.08 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.242836E+10 | 24067503.94 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.225273E+10 | 70004329.34 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.246614E+10 | 0.205989E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.395303E+10 | 0.806990E+09 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.437561E+10 | 0.136952E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.359827E+10 | 0.185267E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.358291E+11 | 0.894794E+10 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.225273E+10 | 24067503.94 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.437561E+10 | 0.185267E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.669777E+09 | 0.357159E+09 |
February | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.598173E+09 | 0.264125E+09 |
March | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.581085E+09 | 0.200522E+09 |
April | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.405307E+09 | 98446362.17 |
May | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.343994E+09 | 41356231.93 |
June | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.337917E+09 | 24756359.94 |
July | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.349877E+09 | 14296293.96 |
August | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.345317E+09 | 31976965.88 |
September | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.412328E+09 | 69892477.93 |
October | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.738344E+09 | 0.198158E+09 |
November | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.866992E+09 | 0.286446E+09 |
December | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.743775E+09 | 0.357421E+09 |
Annual Sum or Average | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.639288E+10 | 0.194455E+10 |
Minimum of Months | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.337917E+09 | 14296293.96 |
Maximum of Months | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.866992E+09 | 0.357421E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1459.22 | 951.03 | 1280.29 | 680.77 | 599.52 | 0.00 | 0.00 |
February | 2004.55 | 777.99 | 1632.41 | 913.67 | 718.74 | 0.00 | 0.00 |
March | 2857.77 | 543.78 | 2160.06 | 1282.60 | 877.47 | 0.00 | 0.00 |
April | 3960.29 | 325.45 | 2808.25 | 1963.99 | 844.26 | 0.00 | 0.00 |
May | 4300.69 | 164.79 | 2963.58 | 2042.37 | 921.21 | 0.00 | 0.00 |
June | 4089.35 | 99.98 | 2777.51 | 1762.44 | 1015.07 | 0.00 | 0.00 |
July | 2928.61 | 60.78 | 1947.01 | 694.09 | 1252.92 | 0.00 | 0.00 |
August | 2513.64 | 93.61 | 1678.90 | 472.52 | 1206.38 | 0.00 | 0.00 |
September | 2472.17 | 197.78 | 1743.29 | 743.43 | 999.86 | 0.00 | 0.00 |
October | 2658.25 | 492.08 | 1932.49 | 1221.65 | 710.85 | 0.00 | 0.00 |
November | 2076.89 | 759.48 | 1622.76 | 1068.61 | 554.15 | 0.00 | 0.00 |
December | 1441.98 | 963.00 | 1246.60 | 670.01 | 576.59 | 0.00 | 0.00 |
Annual Sum or Average | 2731.65 | 450.98 | 1982.85 | 1125.26 | 857.58 | 0.00 | 0.00 |
Minimum of Months | 1441.98 | 60.78 | 1246.60 | 472.52 | 554.15 | 0.00 | 0.00 |
Maximum of Months | 4300.69 | 963.00 | 2963.58 | 2042.37 | 1252.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1201.31 | 714.67 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1210.56 | 575.91 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1128.09 | 362.76 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 970.40 | 150.67 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 948.01 | 41.91 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 966.59 | 24.49 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 901.54 | 13.18 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 840.37 | 33.96 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 953.63 | 92.86 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1479.64 | 315.21 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1690.00 | 544.23 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1340.84 | 711.14 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1135.20 | 297.18 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 840.37 | 13.18 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1690.00 | 714.67 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1206.70 | 690.59 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1212.13 | 556.13 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1125.82 | 346.20 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 968.40 | 137.26 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 950.15 | 33.75 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 972.31 | 19.37 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 906.65 | 8.99 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 841.07 | 26.14 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 951.44 | 79.47 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1475.89 | 301.30 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1688.12 | 528.37 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1343.44 | 691.71 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1136.13 | 283.74 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 841.07 | 8.99 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1688.12 | 691.71 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 250.07 | 133.35 | 186.13 | 113.12 | 73.01 | 0.00 | 0.00 |
February | 247.26 | 109.18 | 176.96 | 98.29 | 78.66 | 0.00 | 0.00 |
March | 216.95 | 74.87 | 151.25 | 66.79 | 84.47 | 0.00 | 0.00 |
April | 156.37 | 37.98 | 106.22 | 29.94 | 76.27 | 0.00 | 0.00 |
May | 128.43 | 15.44 | 76.37 | 5.61 | 70.76 | 0.00 | 0.00 |
June | 130.37 | 9.55 | 69.88 | 1.17 | 68.71 | 0.00 | 0.00 |
July | 130.63 | 5.34 | 72.90 | 0.99 | 71.91 | 0.00 | 0.00 |
August | 128.93 | 11.94 | 77.34 | 4.12 | 73.22 | 0.00 | 0.00 |
September | 159.08 | 26.96 | 103.67 | 26.89 | 76.78 | 0.00 | 0.00 |
October | 275.67 | 73.98 | 178.38 | 99.61 | 78.78 | 0.00 | 0.00 |
November | 334.49 | 110.51 | 222.88 | 147.34 | 75.54 | 0.00 | 0.00 |
December | 277.69 | 133.45 | 198.92 | 124.67 | 74.25 | 0.00 | 0.00 |
Annual Sum or Average | 202.72 | 61.66 | 134.83 | 59.66 | 75.18 | 0.00 | 0.00 |
Minimum of Months | 128.43 | 5.34 | 69.88 | 0.99 | 68.71 | 0.00 | 0.00 |
Maximum of Months | 334.49 | 133.45 | 222.88 | 147.34 | 84.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.390836E+10 | 0.254724E+10 | 0.342912E+10 | 0.182338E+10 | 0.160574E+10 | 0.00 | 0.00 |
February | 0.484942E+10 | 0.188211E+10 | 0.394912E+10 | 0.221035E+10 | 0.173877E+10 | 0.00 | 0.00 |
March | 0.765424E+10 | 0.145645E+10 | 0.578551E+10 | 0.343531E+10 | 0.235021E+10 | 0.00 | 0.00 |
April | 0.102651E+11 | 0.843573E+09 | 0.727900E+10 | 0.509067E+10 | 0.218833E+10 | 0.00 | 0.00 |
May | 0.115190E+11 | 0.441372E+09 | 0.793764E+10 | 0.547029E+10 | 0.246736E+10 | 0.00 | 0.00 |
June | 0.105996E+11 | 0.259156E+09 | 0.719930E+10 | 0.456825E+10 | 0.263105E+10 | 0.00 | 0.00 |
July | 0.784399E+10 | 0.162803E+09 | 0.521487E+10 | 0.185906E+10 | 0.335581E+10 | 0.00 | 0.00 |
August | 0.673253E+10 | 0.250727E+09 | 0.449676E+10 | 0.126559E+10 | 0.323117E+10 | 0.00 | 0.00 |
September | 0.640786E+10 | 0.512637E+09 | 0.451861E+10 | 0.192697E+10 | 0.259163E+10 | 0.00 | 0.00 |
October | 0.711986E+10 | 0.131800E+10 | 0.517598E+10 | 0.327206E+10 | 0.190393E+10 | 0.00 | 0.00 |
November | 0.538329E+10 | 0.196856E+10 | 0.420620E+10 | 0.276983E+10 | 0.143636E+10 | 0.00 | 0.00 |
December | 0.386220E+10 | 0.257931E+10 | 0.333889E+10 | 0.179456E+10 | 0.154433E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.861454E+11 | 0.142219E+11 | 0.625310E+11 | 0.354863E+11 | 0.270447E+11 | 0.00 | 0.00 |
Minimum of Months | 0.386220E+10 | 0.162803E+09 | 0.333889E+10 | 0.126559E+10 | 0.143636E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115190E+11 | 0.257931E+10 | 0.793764E+10 | 0.547029E+10 | 0.335581E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.321758E+10 | 0.191416E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.292858E+10 | 0.139325E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.302149E+10 | 0.971603E+09 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.251527E+10 | 0.390542E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.253914E+10 | 0.112241E+09 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.250540E+10 | 63481798.77 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.241468E+10 | 35297605.86 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.225084E+10 | 90963227.37 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.247180E+10 | 0.240682E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.396306E+10 | 0.844258E+09 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.438047E+10 | 0.141065E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.359131E+10 | 0.190472E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357996E+11 | 0.937186E+10 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225084E+10 | 35297605.86 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.438047E+10 | 0.191416E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323203E+10 | 0.184967E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.293239E+10 | 0.134540E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.301540E+10 | 0.927256E+09 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.251008E+10 | 0.355776E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.254488E+10 | 90399562.62 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.252023E+10 | 50203549.08 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.242836E+10 | 24067503.94 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.225273E+10 | 70004329.34 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.246614E+10 | 0.205989E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.395303E+10 | 0.806990E+09 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.437561E+10 | 0.136952E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.359827E+10 | 0.185267E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.358291E+11 | 0.894794E+10 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225273E+10 | 24067503.94 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.437561E+10 | 0.185267E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.669777E+09 | 0.357159E+09 | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.00 | 0.00 |
February | 0.598173E+09 | 0.264125E+09 | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.00 | 0.00 |
March | 0.581085E+09 | 0.200522E+09 | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.00 | 0.00 |
April | 0.405307E+09 | 98446362.17 | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.00 | 0.00 |
May | 0.343994E+09 | 41356231.93 | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.00 | 0.00 |
June | 0.337917E+09 | 24756359.94 | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.00 | 0.00 |
July | 0.349877E+09 | 14296293.96 | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.00 | 0.00 |
August | 0.345317E+09 | 31976965.88 | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.00 | 0.00 |
September | 0.412328E+09 | 69892477.93 | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.00 | 0.00 |
October | 0.738344E+09 | 0.198158E+09 | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.00 | 0.00 |
November | 0.866992E+09 | 0.286446E+09 | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.00 | 0.00 |
December | 0.743775E+09 | 0.357421E+09 | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.639288E+10 | 0.194455E+10 | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.00 | 0.00 |
Minimum of Months | 0.337917E+09 | 14296293.96 | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.00 | 0.00 |
Maximum of Months | 0.866992E+09 | 0.357421E+09 | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.220015E+10 | -.180385E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -396301891.4 | 58.99 | 0.00 | 0.00 |
February | 0.195949E+10 | -.160755E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -351939232.5 | 58.99 | 0.00 | 0.00 |
March | 0.208508E+10 | -.170246E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382623447.8 | 58.99 | 0.00 | 0.00 |
April | 0.181619E+10 | -.145247E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -363723782.8 | 58.99 | 0.00 | 0.00 |
May | 0.169838E+10 | -.132686E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -371527431.5 | 58.99 | 0.00 | 0.00 |
June | 0.152743E+10 | -.116831E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -359117887.7 | 58.99 | 0.00 | 0.00 |
July | 0.148773E+10 | -.111746E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -370264300.4 | 58.99 | 0.00 | 0.00 |
August | 0.156572E+10 | -.119402E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -371695409.5 | 58.99 | 0.00 | 0.00 |
September | 0.161751E+10 | -.125600E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -361513020.1 | 58.99 | 0.00 | 0.00 |
October | 0.182558E+10 | -.144866E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376921004.2 | 58.99 | 0.00 | 0.00 |
November | 0.193313E+10 | -.156205E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -371080960.1 | 58.99 | 0.00 | 0.00 |
December | 0.214451E+10 | -.175319E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -391320020.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.218609E+11 | -.173929E+11 | 8760.00 | -.446803E+10 | 58.99 | |||||
Minimum of Months | 0.148773E+10 | -.180385E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -396301891.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.220015E+10 | -.111746E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -351939232.5 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.80 | 0.50 | 14-JAN-11:39 | 323.38 | 8.09 | 0.00 | 30.00 | 266.49 | 6.65 | 0.00 | 4.67 |
February | 303.83 | 0.76 | 0.50 | 01-FEB-10:00 | 385.45 | 8.99 | 0.00 | 78.83 | 319.10 | 7.43 | 0.00 | 44.33 |
March | 364.50 | 0.71 | 0.50 | 01-MAR-10:00 | 2499.35 | 10.09 | 0.00 | 174.00 | 2685.86 | 8.50 | 0.00 | 103.17 |
April | 379.83 | 0.73 | 0.50 | 01-APR-10:20 | 421.38 | 10.32 | 0.00 | 128.67 | 350.10 | 8.69 | 0.00 | 72.50 |
May | 406.00 | 0.73 | 0.50 | 04-MAY-11:00 | 423.67 | 11.57 | 0.00 | 117.33 | 352.46 | 9.88 | 0.00 | 65.00 |
June | 386.67 | 0.71 | 0.50 | 01-JUN-09:09 | 454.45 | 12.32 | 0.00 | 143.83 | 376.83 | 10.55 | 0.00 | 91.67 |
July | 379.83 | 0.68 | 0.50 | 01-JUL-10:09 | 530.31 | 13.18 | 0.00 | 207.83 | 447.27 | 11.53 | 0.00 | 145.50 |
August | 372.50 | 0.68 | 0.50 | 01-AUG-08:50 | 596.27 | 12.53 | 0.00 | 194.50 | 520.02 | 10.94 | 0.00 | 142.33 |
September | 344.33 | 0.69 | 0.50 | 01-SEP-09:09 | 1385.39 | 11.43 | 0.00 | 173.50 | 1375.41 | 9.80 | 0.00 | 119.17 |
October | 347.33 | 0.74 | 0.50 | 01-OCT-10:00 | 404.52 | 9.13 | 0.00 | 100.83 | 336.04 | 7.64 | 0.00 | 59.67 |
November | 317.83 | 0.81 | 0.58 | 28-NOV-10:50 | 322.92 | 7.92 | 0.00 | 1.33 | 267.36 | 6.43 | 0.00 | 0.00 |
December | 315.50 | 0.81 | 0.58 | 08-DEC-11:39 | 315.35 | 7.96 | 0.00 | 8.33 | 259.31 | 6.48 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.73 | 680.21 | 10.42 | 0.00 | 1359.00 | 638.00 | 8.84 | 0.00 | 848.00 | ||
Minimum of Months | 303.83 | 0.68 | 0.50 | 315.35 | 7.92 | 0.00 | 1.33 | 259.31 | 6.43 | 0.00 | 0.00 | |
Maximum of Months | 406.00 | 0.81 | 0.58 | 2499.35 | 13.18 | 0.00 | 207.83 | 2685.86 | 11.53 | 0.00 | 145.50 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105575E+09 | 42029.77 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105575E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105575E+09 | 42029.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.434961E+09 | 176216.15 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.434961E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.434961E+09 | 176216.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13992611.29 | 16216.32 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 13992611.29 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13992611.29 | 16216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 74993008.38 | 17629.44 | 02-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4009504.36 | 6023.45 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1614630.56 | 1495.34 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80617143.30 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74993008.38 | 17629.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172067E+10 | 12164.80 | 01-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312815E+09 | 9490.02 | 10-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1663929.96 | 964.80 | 30-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123921E+10 | 13502.41 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327436E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172067E+10 | 13502.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.424248E+10 | 0.362013E+10 | 9676.48 | 14-JAN-15:30 | 7789.24 | 0.00 |
February | 0.00 | 0.00 | 0.787140E+10 | 0.671078E+10 | 22655.38 | 25-FEB-07:03 | 17431.58 | 0.00 |
March | 0.00 | 0.00 | 0.163742E+11 | 0.141628E+11 | 47406.81 | 11-MAR-07:02 | 36971.19 | 0.00 |
April | 0.00 | 0.00 | 0.250535E+11 | 0.225446E+11 | 47917.63 | 17-APR-05:02 | 38197.11 | 0.00 |
May | 0.00 | 0.00 | 0.359076E+11 | 0.300247E+11 | 51209.39 | 24-MAY-05:02 | 27504.54 | 0.00 |
June | 0.00 | 0.00 | 0.393959E+11 | 0.304616E+11 | 52282.57 | 26-JUN-05:02 | 22683.51 | 0.00 |
July | 0.00 | 0.00 | 0.437032E+11 | 0.298819E+11 | 52374.58 | 26-JUL-05:02 | 24169.20 | 0.00 |
August | 0.00 | 0.00 | 0.430787E+11 | 0.287068E+11 | 52153.04 | 10-AUG-05:01 | 26340.27 | 0.00 |
September | 0.00 | 0.00 | 0.353928E+11 | 0.245980E+11 | 52347.23 | 03-SEP-07:02 | 24851.86 | 0.00 |
October | 0.00 | 0.00 | 0.244891E+11 | 0.202541E+11 | 49503.65 | 12-OCT-06:02 | 30208.24 | 0.00 |
November | 0.00 | 0.00 | 0.138119E+11 | 0.119519E+11 | 47050.51 | 09-NOV-07:02 | 36666.52 | 0.00 |
December | 0.00 | 0.00 | 0.636333E+10 | 0.549719E+10 | 10337.33 | 28-DEC-15:20 | 8979.34 | 0.00 |
Annual Sum or Average | 0.295684E+12 | 0.228414E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.424248E+10 | 0.362013E+10 | 9676.48 | 7789.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.437032E+11 | 0.304616E+11 | 52374.58 | 38197.11 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.252187E+11 | 0.210332E+11 | 52630.53 | 14-JAN-15:00 | 41264.21 | 0.00 |
February | 0.00 | 0.00 | 0.450593E+11 | 0.372782E+11 | 142825.91 | 25-FEB-07:03 | 99758.18 | 0.00 |
March | 0.00 | 0.00 | 0.880649E+11 | 0.735736E+11 | 213865.11 | 10-MAR-07:02 | 149514.80 | 0.00 |
April | 0.00 | 0.00 | 0.127776E+12 | 0.111390E+12 | 218082.72 | 26-APR-06:02 | 148528.78 | 0.00 |
May | 0.00 | 0.00 | 0.177180E+12 | 0.140512E+12 | 226029.21 | 24-MAY-06:02 | 127995.12 | 0.00 |
June | 0.00 | 0.00 | 0.195298E+12 | 0.138629E+12 | 232017.34 | 26-JUN-06:02 | 115015.01 | 0.00 |
July | 0.00 | 0.00 | 0.211852E+12 | 0.127384E+12 | 232793.22 | 18-JUL-06:02 | 113619.47 | 0.00 |
August | 0.00 | 0.00 | 0.211198E+12 | 0.120690E+12 | 233891.61 | 12-AUG-06:02 | 110884.46 | 0.00 |
September | 0.00 | 0.00 | 0.175150E+12 | 0.106604E+12 | 233495.82 | 10-SEP-08:62 | 110218.78 | 0.00 |
October | 0.00 | 0.00 | 0.118932E+12 | 0.921837E+11 | 224426.81 | 12-OCT-06:02 | 127963.52 | 0.00 |
November | 0.00 | 0.00 | 0.713792E+11 | 0.594722E+11 | 214357.94 | 09-NOV-07:02 | 146795.87 | 0.00 |
December | 0.00 | 0.00 | 0.350248E+11 | 0.292946E+11 | 57568.30 | 28-DEC-15:30 | 48878.97 | 0.00 |
Annual Sum or Average | 0.148213E+13 | 0.105804E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.252187E+11 | 0.210332E+11 | 52630.53 | 41264.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.211852E+12 | 0.140512E+12 | 233891.61 | 149514.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.674451E+10 | 0.601197E+10 | 10420.73 | 12-JAN-15:10 | 9670.94 | 0.00 |
February | 0.00 | 0.00 | 0.875984E+10 | 0.770504E+10 | 17890.47 | 25-FEB-07:03 | 13491.94 | 0.00 |
March | 0.00 | 0.00 | 0.140314E+11 | 0.123252E+11 | 30749.06 | 11-MAR-07:02 | 23611.74 | 0.00 |
April | 0.00 | 0.00 | 0.181119E+11 | 0.163167E+11 | 31475.87 | 17-APR-05:02 | 24527.23 | 0.00 |
May | 0.00 | 0.00 | 0.239961E+11 | 0.198979E+11 | 33663.68 | 24-MAY-05:02 | 17689.62 | 0.00 |
June | 0.00 | 0.00 | 0.260725E+11 | 0.198163E+11 | 34207.64 | 26-JUN-05:02 | 14716.10 | 0.00 |
July | 0.00 | 0.00 | 0.288158E+11 | 0.192257E+11 | 34267.83 | 26-JUL-05:02 | 15633.73 | 0.00 |
August | 0.00 | 0.00 | 0.288337E+11 | 0.186989E+11 | 34210.62 | 19-AUG-05:02 | 16783.74 | 0.00 |
September | 0.00 | 0.00 | 0.248222E+11 | 0.170663E+11 | 34249.94 | 03-SEP-07:02 | 15918.90 | 0.00 |
October | 0.00 | 0.00 | 0.197351E+11 | 0.165312E+11 | 32343.13 | 12-OCT-06:02 | 18884.51 | 0.00 |
November | 0.00 | 0.00 | 0.140488E+11 | 0.124759E+11 | 30573.59 | 09-NOV-07:02 | 23696.08 | 0.00 |
December | 0.00 | 0.00 | 0.856671E+10 | 0.766512E+10 | 11662.95 | 29-DEC-07:03 | 9877.06 | 0.00 |
Annual Sum or Average | 0.222538E+12 | 0.173736E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.674451E+10 | 0.601197E+10 | 10420.73 | 9670.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.288337E+11 | 0.198979E+11 | 34267.83 | 24527.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.363575E+10 | 0.317506E+10 | 7914.32 | 12-JAN-15:10 | 7189.86 | 0.00 |
February | 0.00 | 0.00 | 0.572066E+10 | 0.491579E+10 | 10097.54 | 22-FEB-14:20 | 9090.88 | 0.00 |
March | 0.00 | 0.00 | 0.104864E+11 | 0.898618E+10 | 26092.71 | 11-MAR-07:02 | 19417.70 | 0.00 |
April | 0.00 | 0.00 | 0.147481E+11 | 0.130601E+11 | 26547.83 | 17-APR-05:02 | 19843.86 | 0.00 |
May | 0.00 | 0.00 | 0.203464E+11 | 0.164739E+11 | 28424.89 | 24-MAY-05:02 | 14193.82 | 0.00 |
June | 0.00 | 0.00 | 0.223364E+11 | 0.163945E+11 | 28941.00 | 26-JUN-05:02 | 11705.15 | 0.00 |
July | 0.00 | 0.00 | 0.249259E+11 | 0.158004E+11 | 28991.93 | 26-JUL-05:02 | 12487.86 | 0.00 |
August | 0.00 | 0.00 | 0.248258E+11 | 0.151831E+11 | 28943.52 | 19-AUG-05:02 | 13270.00 | 0.00 |
September | 0.00 | 0.00 | 0.210491E+11 | 0.137360E+11 | 28976.78 | 03-SEP-07:02 | 12736.18 | 0.00 |
October | 0.00 | 0.00 | 0.161727E+11 | 0.131751E+11 | 27594.61 | 12-OCT-06:02 | 14963.64 | 0.00 |
November | 0.00 | 0.00 | 0.107213E+11 | 0.929979E+10 | 25988.68 | 09-NOV-07:02 | 18938.52 | 0.00 |
December | 0.00 | 0.00 | 0.528750E+10 | 0.459705E+10 | 8932.04 | 02-DEC-14:00 | 8483.95 | 0.00 |
Annual Sum or Average | 0.180256E+12 | 0.134797E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.363575E+10 | 0.317506E+10 | 7914.32 | 7189.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.249259E+11 | 0.164739E+11 | 28991.93 | 19843.86 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162086E+10 | 0.36 | 1565.07 | 01-JAN-08:65 | 0.93 |
February | 0.543534E+09 | 0.13 | 1565.07 | 01-FEB-08:70 | 0.93 |
March | 71788094.00 | 0.02 | 1565.07 | 01-MAR-08:70 | 0.92 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 375615.88 | 0.00 | 1565.07 | 28-OCT-07:09 | 0.92 |
November | 86696839.67 | 0.02 | 1565.07 | 01-NOV-07:09 | 0.92 |
December | 0.124789E+10 | 0.28 | 1565.07 | 01-DEC-08:70 | 0.93 |
Annual Sum or Average | 0.357114E+10 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162086E+10 | 0.36 | 1565.07 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.398686E+10 | 0.53 | 2488.68 | 01-JAN-09:40 | 0.89 |
February | 0.361953E+10 | 0.54 | 2488.68 | 01-FEB-10:55 | 0.89 |
March | 0.405853E+10 | 0.54 | 2488.68 | 01-MAR-09:00 | 0.89 |
April | 0.389727E+10 | 0.54 | 2488.68 | 01-APR-06:00 | 0.89 |
May | 0.402270E+10 | 0.54 | 2488.68 | 01-MAY-05:50 | 0.89 |
June | 0.392862E+10 | 0.55 | 2488.68 | 01-JUN-06:20 | 0.89 |
July | 0.400025E+10 | 0.54 | 2488.68 | 01-JUL-05:15 | 0.88 |
August | 0.405853E+10 | 0.54 | 2488.68 | 01-AUG-07:50 | 0.89 |
September | 0.389727E+10 | 0.54 | 2488.68 | 01-SEP-05:04 | 0.88 |
October | 0.398686E+10 | 0.53 | 2488.68 | 01-OCT-07:20 | 0.89 |
November | 0.384351E+10 | 0.53 | 2488.68 | 01-NOV-07:00 | 0.89 |
December | 0.399582E+10 | 0.54 | 2488.68 | 01-DEC-08:30 | 0.90 |
Annual Sum or Average | 0.472958E+11 | 0.54 | |||
Minimum of Months | 0.361953E+10 | 0.53 | 2488.68 | 0.88 | |
Maximum of Months | 0.405853E+10 | 0.55 | 2488.68 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.242645E+11 | 0.91 | 15146.35 | 03-JAN-13:20 | 1.53 |
February | 0.220289E+11 | 0.92 | 15146.35 | 03-FEB-12:00 | 1.53 |
March | 0.247007E+11 | 0.93 | 15146.35 | 02-MAR-10:00 | 1.52 |
April | 0.237192E+11 | 0.92 | 15146.35 | 06-APR-10:40 | 1.53 |
May | 0.244826E+11 | 0.92 | 15146.35 | 03-MAY-07:55 | 1.52 |
June | 0.238828E+11 | 0.92 | 15146.35 | 04-JUN-13:30 | 1.52 |
July | 0.243190E+11 | 0.90 | 15146.35 | 18-JUL-08:30 | 1.51 |
August | 0.247007E+11 | 0.92 | 15146.35 | 16-AUG-05:10 | 1.51 |
September | 0.237192E+11 | 0.91 | 15146.35 | 03-SEP-16:40 | 1.51 |
October | 0.242645E+11 | 0.91 | 15146.35 | 04-OCT-07:00 | 1.52 |
November | 0.233920E+11 | 0.91 | 15146.35 | 01-NOV-14:10 | 1.53 |
December | 0.243190E+11 | 0.92 | 15146.35 | 02-DEC-20:10 | 1.53 |
Annual Sum or Average | 0.287793E+12 | 0.92 | |||
Minimum of Months | 0.220289E+11 | 0.90 | 15146.35 | 1.51 | |
Maximum of Months | 0.247007E+11 | 0.93 | 15146.35 | 1.53 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.236023E+10 | 0.55 | 1473.30 | 01-JAN-09:40 | 0.93 |
February | 0.214277E+10 | 0.56 | 1473.30 | 01-FEB-11:40 | 0.93 |
March | 0.240266E+10 | 0.56 | 1473.30 | 01-MAR-09:33 | 0.93 |
April | 0.230729E+10 | 0.56 | 1473.30 | 01-APR-08:40 | 0.92 |
May | 0.238510E+10 | 0.56 | 1473.30 | 01-MAY-05:40 | 0.93 |
June | 0.233019E+10 | 0.57 | 1473.30 | 01-JUN-06:30 | 0.92 |
July | 0.237323E+10 | 0.56 | 1473.30 | 01-JUL-06:06 | 0.92 |
August | 0.240657E+10 | 0.56 | 1473.30 | 01-AUG-07:10 | 0.92 |
September | 0.230797E+10 | 0.56 | 1473.30 | 01-SEP-06:15 | 0.92 |
October | 0.236023E+10 | 0.55 | 1473.30 | 01-OCT-07:40 | 0.92 |
November | 0.227537E+10 | 0.55 | 1473.30 | 01-NOV-06:30 | 0.93 |
December | 0.236553E+10 | 0.56 | 1473.30 | 01-DEC-07:10 | 0.93 |
Annual Sum or Average | 0.280171E+11 | 0.56 | |||
Minimum of Months | 0.214277E+10 | 0.55 | 1473.30 | 0.92 | |
Maximum of Months | 0.240657E+10 | 0.57 | 1473.30 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192288E+10 | 0.55 | 1200.30 | 01-JAN-09:00 | 0.93 |
February | 0.174571E+10 | 0.56 | 1200.30 | 01-FEB-15:50 | 0.93 |
March | 0.195745E+10 | 0.56 | 1200.30 | 01-MAR-21:00 | 0.93 |
April | 0.187967E+10 | 0.56 | 1200.30 | 03-APR-05:40 | 0.92 |
May | 0.194118E+10 | 0.56 | 1200.30 | 14-MAY-07:15 | 0.92 |
June | 0.189552E+10 | 0.57 | 1200.30 | 03-JUN-06:06 | 0.92 |
July | 0.193037E+10 | 0.55 | 1200.30 | 02-JUL-08:15 | 0.92 |
August | 0.195812E+10 | 0.56 | 1200.30 | 08-AUG-05:20 | 0.91 |
September | 0.187967E+10 | 0.55 | 1200.30 | 07-SEP-05:20 | 0.91 |
October | 0.192288E+10 | 0.55 | 1200.30 | 05-OCT-05:30 | 0.92 |
November | 0.185374E+10 | 0.55 | 1200.30 | 01-NOV-07:01 | 0.93 |
December | 0.192720E+10 | 0.56 | 1200.30 | 01-DEC-18:05 | 0.93 |
Annual Sum or Average | 0.228144E+11 | 0.56 | |||
Minimum of Months | 0.174571E+10 | 0.55 | 1200.30 | 0.91 | |
Maximum of Months | 0.195812E+10 | 0.57 | 1200.30 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 6.13 |
February | 0.00 | 0.00 |
March | 0.08 | 6.13 |
April | 0.27 | 3.72 |
May | 0.21 | 0.00 |
June | 0.77 | 0.00 |
July | 0.94 | 0.00 |
August | 1.16 | 0.00 |
September | 0.80 | 0.00 |
October | 0.27 | 0.00 |
November | 0.17 | 6.13 |
December | 0.00 | 0.00 |
Annual Sum or Average | 4.83 | 0.71 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.16 | 6.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 25.84 |
February | 0.00 | 0.00 |
March | 0.17 | 12.92 |
April | 0.27 | 15.66 |
May | 0.16 | 0.00 |
June | 0.38 | 0.00 |
July | 0.33 | 0.00 |
August | 0.27 | 0.00 |
September | 0.47 | 0.00 |
October | 0.07 | 0.00 |
November | 0.17 | 25.84 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.42 | 5.92 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.47 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.42 | 0.00 |
March | 1.56 | 0.00 |
April | 1.58 | 0.00 |
May | 0.86 | 0.00 |
June | 1.26 | 0.00 |
July | 1.70 | 0.00 |
August | 1.58 | 0.00 |
September | 2.41 | 0.00 |
October | 1.55 | 0.00 |
November | 1.26 | 0.00 |
December | 0.22 | 0.00 |
Annual Sum or Average | 14.41 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.41 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.58 | 1.39 |
April | 0.72 | 0.00 |
May | 0.30 | 0.00 |
June | 0.94 | 0.00 |
July | 1.05 | 0.00 |
August | 1.33 | 0.00 |
September | 2.05 | 0.00 |
October | 0.97 | 0.42 |
November | 0.71 | 1.15 |
December | 0.00 | 0.00 |
Annual Sum or Average | 8.64 | 0.23 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.05 | 1.39 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 13.18 | 0.00 |
February | 12.64 | 0.00 |
March | 4.83 | 0.00 |
April | 3.44 | 0.00 |
May | 3.79 | 0.00 |
June | 3.25 | 0.00 |
July | 1.73 | 0.00 |
August | 1.39 | 0.00 |
September | 1.29 | 0.00 |
October | 1.82 | 0.00 |
November | 7.12 | 0.00 |
December | 20.65 | 0.00 |
Annual Sum or Average | 75.14 | 0.00 |
Minimum of Months | 1.29 | 0.00 |
Maximum of Months | 20.65 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.516782E+10 | 0.131969E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.581747E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.878954E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.117105E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.153972E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.160348E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.164066E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.159717E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.137995E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.110649E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.775238E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.576225E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133675E+12 | 0.131969E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.516782E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.164066E+11 | 0.131969E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.318990E+11 | 0.543701E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.356802E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.522179E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.666921E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.846135E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.875366E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.880025E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.863429E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.757770E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.615464E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.453476E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.348947E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.750551E+12 | 0.543701E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.318990E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.880025E+11 | 0.543701E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.414529E+10 | 17490764.11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.447416E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.630168E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.781418E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.986018E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.102058E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.104137E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.102223E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.908614E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.785603E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.604119E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.462206E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.910427E+11 | 17490764.11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.414529E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.104137E+11 | 17490764.11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.289639E+10 | 93741260.47 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.328780E+10 | 5011880.45 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.490333E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.638041E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.825233E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.858512E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.880215E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.860937E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.758486E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.643571E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.475268E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.333713E+10 | 2018288.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.738273E+11 | 0.100771E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.289639E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.880215E+10 | 93741260.47 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.398686E+10 | 0.424248E+10 | 0.105575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361953E+10 | 0.787140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405853E+10 | 0.163742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389727E+10 | 0.250535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.402270E+10 | 0.359076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392862E+10 | 0.393959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400025E+10 | 0.437032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.405853E+10 | 0.430787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.389727E+10 | 0.353928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398686E+10 | 0.244891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384351E+10 | 0.138119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399582E+10 | 0.636333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472958E+11 | 0.295684E+12 | 0.105575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361953E+10 | 0.424248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.405853E+10 | 0.437032E+11 | 0.105575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.242645E+11 | 0.252187E+11 | 0.434961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220289E+11 | 0.450593E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247007E+11 | 0.880649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237192E+11 | 0.127776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244826E+11 | 0.177180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238828E+11 | 0.195298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243190E+11 | 0.211852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.247007E+11 | 0.211198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237192E+11 | 0.175150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242645E+11 | 0.118932E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233920E+11 | 0.713792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243190E+11 | 0.350248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287793E+12 | 0.148213E+13 | 0.434961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.220289E+11 | 0.252187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.247007E+11 | 0.211852E+12 | 0.434961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.236023E+10 | 0.674451E+10 | 13992611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214277E+10 | 0.875984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240266E+10 | 0.140314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230729E+10 | 0.181119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238510E+10 | 0.239961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233019E+10 | 0.260725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237323E+10 | 0.288158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.240657E+10 | 0.288337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230797E+10 | 0.248222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236023E+10 | 0.197351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227537E+10 | 0.140488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236553E+10 | 0.856671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280171E+11 | 0.222538E+12 | 13992611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.214277E+10 | 0.674451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.240657E+10 | 0.288337E+11 | 13992611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192288E+10 | 0.363575E+10 | 74993008.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174571E+10 | 0.572066E+10 | 4009504.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195745E+10 | 0.104864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187967E+10 | 0.147481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194118E+10 | 0.203464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189552E+10 | 0.223364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193037E+10 | 0.249259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195812E+10 | 0.248258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.187967E+10 | 0.210491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192288E+10 | 0.161727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185374E+10 | 0.107213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192720E+10 | 0.528750E+10 | 1614630.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228144E+11 | 0.180256E+12 | 80617143.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.174571E+10 | 0.363575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195812E+10 | 0.249259E+11 | 74993008.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.398686E+10 | 0.00 | 0.00 | 0.00 | 0.118096E+10 | 0.00 | 0.131969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.361953E+10 | 0.00 | 0.00 | 0.00 | 0.219794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405853E+10 | 0.00 | 0.00 | 0.00 | 0.473101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389727E+10 | 0.00 | 0.00 | 0.00 | 0.781321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.402270E+10 | 0.00 | 0.00 | 0.00 | 0.113745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392862E+10 | 0.00 | 0.00 | 0.00 | 0.121061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.400025E+10 | 0.00 | 0.00 | 0.00 | 0.124064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.405853E+10 | 0.00 | 0.00 | 0.00 | 0.119132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.389727E+10 | 0.00 | 0.00 | 0.00 | 0.990222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398686E+10 | 0.00 | 0.00 | 0.00 | 0.707800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384351E+10 | 0.00 | 0.00 | 0.00 | 0.390886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399582E+10 | 0.00 | 0.00 | 0.00 | 0.176643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472958E+11 | 0.00 | 0.00 | 0.00 | 0.863789E+11 | 0.00 | 0.131969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.361953E+10 | 0.00 | 0.00 | 0.00 | 0.118096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.405853E+10 | 0.00 | 0.00 | 0.00 | 0.124064E+11 | 0.00 | 0.131969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.242645E+11 | 0.00 | 0.00 | 0.00 | 0.763453E+10 | 0.00 | 0.543701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220289E+11 | 0.00 | 0.00 | 0.00 | 0.136514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247007E+11 | 0.00 | 0.00 | 0.00 | 0.275173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237192E+11 | 0.00 | 0.00 | 0.00 | 0.429729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244826E+11 | 0.00 | 0.00 | 0.00 | 0.601309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.238828E+11 | 0.00 | 0.00 | 0.00 | 0.636539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243190E+11 | 0.00 | 0.00 | 0.00 | 0.636835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.247007E+11 | 0.00 | 0.00 | 0.00 | 0.616422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237192E+11 | 0.00 | 0.00 | 0.00 | 0.520578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242645E+11 | 0.00 | 0.00 | 0.00 | 0.372820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233920E+11 | 0.00 | 0.00 | 0.00 | 0.219555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243190E+11 | 0.00 | 0.00 | 0.00 | 0.105757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287793E+12 | 0.00 | 0.00 | 0.00 | 0.462758E+12 | 0.00 | 0.543701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.220289E+11 | 0.00 | 0.00 | 0.00 | 0.763453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.247007E+11 | 0.00 | 0.00 | 0.00 | 0.636835E+11 | 0.00 | 0.543701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.236023E+10 | 0.00 | 0.00 | 0.00 | 0.178506E+10 | 0.00 | 17490764.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214277E+10 | 0.00 | 0.00 | 0.00 | 0.233140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240266E+10 | 0.00 | 0.00 | 0.00 | 0.389902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230729E+10 | 0.00 | 0.00 | 0.00 | 0.550689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238510E+10 | 0.00 | 0.00 | 0.00 | 0.747509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233019E+10 | 0.00 | 0.00 | 0.00 | 0.787565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237323E+10 | 0.00 | 0.00 | 0.00 | 0.804044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.240657E+10 | 0.00 | 0.00 | 0.00 | 0.781571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230797E+10 | 0.00 | 0.00 | 0.00 | 0.677817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.236023E+10 | 0.00 | 0.00 | 0.00 | 0.549580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227537E+10 | 0.00 | 0.00 | 0.00 | 0.376583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236553E+10 | 0.00 | 0.00 | 0.00 | 0.225653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280171E+11 | 0.00 | 0.00 | 0.00 | 0.630256E+11 | 0.00 | 17490764.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.214277E+10 | 0.00 | 0.00 | 0.00 | 0.178506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.240657E+10 | 0.00 | 0.00 | 0.00 | 0.804044E+10 | 0.00 | 17490764.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.192288E+10 | 0.00 | 0.00 | 0.00 | 0.973515E+09 | 0.00 | 93741260.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174571E+10 | 0.00 | 0.00 | 0.00 | 0.154209E+10 | 0.00 | 5011880.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195745E+10 | 0.00 | 0.00 | 0.00 | 0.294589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187967E+10 | 0.00 | 0.00 | 0.00 | 0.450075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.194118E+10 | 0.00 | 0.00 | 0.00 | 0.631115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.189552E+10 | 0.00 | 0.00 | 0.00 | 0.668959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193037E+10 | 0.00 | 0.00 | 0.00 | 0.687178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195812E+10 | 0.00 | 0.00 | 0.00 | 0.665125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.187967E+10 | 0.00 | 0.00 | 0.00 | 0.570520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192288E+10 | 0.00 | 0.00 | 0.00 | 0.451283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185374E+10 | 0.00 | 0.00 | 0.00 | 0.289894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192720E+10 | 0.00 | 0.00 | 0.00 | 0.140993E+10 | 0.00 | 2018288.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228144E+11 | 0.00 | 0.00 | 0.00 | 0.510129E+11 | 0.00 | 0.100771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.174571E+10 | 0.00 | 0.00 | 0.00 | 0.973515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195812E+10 | 0.00 | 0.00 | 0.00 | 0.687178E+10 | 0.00 | 93741260.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222971E+10 | 0.00 | 0.00 | 5244373.61 | 0.00 | 0.127210E+09 | 0.252871E+10 | 0.00 | 0.22 |
February | 0.916750E+09 | 26577035.59 | 0.00 | 8693255.27 | 0.00 | 0.00 | 0.161540E+10 | 0.00 | 0.22 |
March | 0.248079E+09 | 0.106942E+10 | 0.00 | 8324620.33 | 2066865.32 | 0.00 | 0.661125E+09 | 0.00 | 0.23 |
April | 20693687.61 | 0.349781E+10 | 0.00 | 1607397.72 | 40820688.95 | 0.00 | 34213312.01 | 0.00 | 0.22 |
May | 23358.97 | 0.805888E+10 | 0.00 | 201879.53 | 53210737.21 | 0.00 | 86167.38 | 0.00 | 0.23 |
June | 0.00 | 0.108362E+11 | 0.00 | 18901.75 | 70360411.67 | 0.00 | 47373.38 | 0.00 | 0.23 |
July | 0.00 | 0.136103E+11 | 0.00 | 0.00 | 65848108.59 | 0.00 | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.140079E+11 | 0.00 | 0.00 | 78182852.93 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.105427E+11 | 0.00 | 0.00 | 0.103292E+09 | 0.00 | 0.00 | 0.00 | 0.23 |
October | 58597803.67 | 0.365710E+10 | 0.00 | 2170734.64 | 33982251.04 | 0.00 | 55109736.32 | 0.00 | 0.22 |
November | 0.382925E+09 | 0.462019E+09 | 0.00 | 9640727.18 | 0.00 | 0.00 | 0.899175E+09 | 0.00 | 0.22 |
December | 0.154676E+10 | 0.00 | 0.00 | 8435875.72 | 0.00 | 0.00 | 0.261313E+10 | 0.00 | 0.22 |
Annual Sum or Average | 0.540354E+10 | 0.657690E+11 | 0.00 | 44337765.76 | 0.447764E+09 | 0.127210E+09 | 0.840699E+10 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.222971E+10 | 0.140079E+11 | 0.00 | 9640727.18 | 0.103292E+09 | 0.127210E+09 | 0.261313E+10 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147113E+11 | 0.00 | 0.00 | 37208461.05 | 0.00 | 0.196128E+09 | 0.185443E+11 | 0.00 | 0.43 |
February | 0.614312E+10 | 0.752286E+09 | 0.00 | 43980352.99 | 0.00 | 0.00 | 0.999373E+10 | 0.00 | 0.43 |
March | 0.150556E+10 | 0.115146E+11 | 0.00 | 34476570.26 | 22900111.20 | 0.00 | 0.330950E+10 | 0.00 | 0.44 |
April | 92281556.73 | 0.328559E+11 | 0.00 | 4463234.61 | 0.432639E+09 | 0.00 | 0.130613E+09 | 0.00 | 0.44 |
May | 0.00 | 0.675179E+11 | 0.00 | 106961.02 | 0.621861E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.870112E+11 | 0.00 | 0.00 | 0.821345E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.106353E+12 | 0.00 | 0.00 | 0.106579E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.107427E+12 | 0.00 | 0.00 | 0.114394E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.809083E+11 | 0.00 | 0.00 | 0.119676E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.521543E+09 | 0.311173E+11 | 0.00 | 8967594.98 | 0.356369E+09 | 0.00 | 0.426418E+09 | 0.00 | 0.43 |
November | 0.284374E+10 | 0.619521E+10 | 0.00 | 36358562.97 | 0.00 | 0.00 | 0.534616E+10 | 0.00 | 0.43 |
December | 0.106949E+11 | 15401805.94 | 0.00 | 50231367.44 | 0.00 | 0.00 | 0.172297E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.365125E+11 | 0.531668E+12 | 0.00 | 0.215793E+09 | 0.566161E+10 | 0.196128E+09 | 0.549804E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.147113E+11 | 0.107427E+12 | 0.00 | 50231367.44 | 0.119676E+10 | 0.196128E+09 | 0.185443E+11 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.950569E+09 | 303695.72 | 0.00 | 11492492.63 | 0.00 | 5530898.29 | 0.193486E+10 | 0.00 | 0.43 |
February | 0.439208E+09 | 0.150438E+09 | 0.00 | 9725698.23 | 0.00 | 0.00 | 0.882485E+09 | 0.00 | 0.43 |
March | 0.120053E+09 | 0.130719E+10 | 0.00 | 5428231.36 | 1192316.13 | 0.00 | 0.291244E+09 | 0.00 | 0.44 |
April | 7238822.10 | 0.331403E+10 | 0.00 | 673807.52 | 22087431.90 | 0.00 | 15943557.49 | 0.00 | 0.43 |
May | 8100.77 | 0.675050E+10 | 0.00 | 58071.63 | 37063998.24 | 0.00 | 66411.41 | 0.00 | 0.44 |
June | 0.00 | 0.881146E+10 | 0.00 | 11611.95 | 46363591.98 | 0.00 | 65902.89 | 0.00 | 0.44 |
July | 0.00 | 0.109165E+11 | 0.00 | 0.00 | 42630705.82 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.111939E+11 | 0.00 | 0.00 | 60902480.02 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.862768E+10 | 0.00 | 0.00 | 77949819.35 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 11083501.00 | 0.355222E+10 | 0.00 | 1392557.41 | 18949853.43 | 0.00 | 40300901.95 | 0.00 | 0.43 |
November | 0.168666E+09 | 0.855558E+09 | 0.00 | 7358804.44 | 0.00 | 0.00 | 0.436704E+09 | 0.00 | 0.43 |
December | 0.618658E+09 | 12124682.91 | 0.00 | 13594219.71 | 0.00 | 0.00 | 0.168700E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.231548E+10 | 0.554919E+11 | 0.00 | 49735494.89 | 0.307140E+09 | 5530898.29 | 0.528867E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 303695.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.950569E+09 | 0.111939E+11 | 0.00 | 13594219.71 | 77949819.35 | 5530898.29 | 0.193486E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133582E+10 | 0.00 | 0.00 | 6295041.56 | 0.00 | 62628633.98 | 0.165008E+10 | 0.00 | 0.42 |
February | 0.635661E+09 | 0.111225E+09 | 0.00 | 6046262.30 | 0.00 | 538763.17 | 0.821059E+09 | 0.00 | 0.43 |
March | 0.176625E+09 | 0.118971E+10 | 0.00 | 3748098.65 | 1209673.07 | 0.00 | 0.293965E+09 | 0.00 | 0.44 |
April | 11992383.65 | 0.320767E+10 | 0.00 | 457121.38 | 30141535.09 | 0.00 | 12649035.16 | 0.00 | 0.43 |
May | 13766.23 | 0.654739E+10 | 0.00 | 80619.63 | 43039736.84 | 0.00 | 37231.35 | 0.00 | 0.44 |
June | 3811.63 | 0.852341E+10 | 0.00 | 5706.92 | 48192234.18 | 0.00 | 50628.25 | 0.00 | 0.44 |
July | 0.00 | 0.105110E+11 | 0.00 | 0.00 | 46496936.84 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.107470E+11 | 0.00 | 0.00 | 60594821.63 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.821341E+10 | 0.00 | 0.00 | 78932284.40 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 26530253.18 | 0.336712E+10 | 0.00 | 1038316.37 | 19932600.13 | 0.00 | 39832770.58 | 0.00 | 0.43 |
November | 0.235952E+09 | 0.784539E+09 | 0.00 | 5335200.81 | 0.00 | 0.00 | 0.435229E+09 | 0.00 | 0.43 |
December | 0.929814E+09 | 5840549.83 | 0.00 | 8393899.28 | 0.00 | 0.00 | 0.150961E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.335241E+10 | 0.532083E+11 | 0.00 | 31400266.88 | 0.328540E+09 | 63167397.15 | 0.476251E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.133582E+10 | 0.107470E+11 | 0.00 | 8393899.28 | 78932284.40 | 62628633.98 | 0.165008E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |