Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:12:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2058.56 | 897.37 | 897.37 |
Net Site Energy | 2058.56 | 897.37 | 897.37 |
Total Source Energy | 4672.47 | 2036.83 | 2036.83 |
Net Source Energy | 4672.47 | 2036.83 | 2036.83 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 786.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 86.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 383.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 72.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 433.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 100.69 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1171.86 | 886.70 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 786.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 86.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 383.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 72.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 433.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 100.69 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 198.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 226.96 | 386.53 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 510.84 | 386.53 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 198.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 226.96 | 386.53 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 510.84 | 386.53 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1171.861 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1171.861 | 100.00 |
Total On-Site and Utility Electric Sources | 1171.861 | 100.00 |
Total Electricity End Uses | 1171.861 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2385.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.7888 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 16.5511 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 16.5511 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 12.6567 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 15.0797 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-16:40 | 09-JAN-07:10 | - | - | - | 20-JAN-12:09 |
Heating | 0.00 | 306057.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48983.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28897.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18612.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4589.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 107264.07 | 310646.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 306057.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48983.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28897.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 18612.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4589.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 852.03 | 0.00 | 0.00 | 0.00 |
Cooling | 275.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1213.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 230.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1373.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 109.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3711.29 | 961.18 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 371.42 | 0.00 | 0.00 | 0.00 |
Cooling | 119.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 529.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 598.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.58 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1617.83 | 419.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 371.42 | 0.00 | 0.00 | 0.00 |
Cooling | 119.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 529.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 100.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 598.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.58 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1617.83 | 419.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.78 |
CORE_RETAIL DIRECT AIR | 7.63 |
POINT_OF_SALE DIRECT AIR | 1.15 |
FRONT_RETAIL DIRECT AIR | 0.922732 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 3.89 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 3.89 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 87142.96 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 53706.77 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 286596.46 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 36390.47 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 31449.95 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.78 | 1.78 | 1.78 | 1.78 | 1.80 | 1.80 | 1.00 | 0.986765 | 1.80 |
PSZ-AC:2 | 7.63 | 7.63 | 7.63 | 7.63 | 7.83 | 7.83 | 1.00 | 0.975306 | 7.83 |
PSZ-AC:3 | 1.15 | 1.15 | 1.15 | 1.15 | 1.16 | 1.16 | 1.00 | 0.987550 | 1.16 |
PSZ-AC:4 | 0.922732 | 0.922732 | 0.922732 | 0.922732 | 0.922732 | 0.922732 | 1.00 | 1.000000 | 0.922732 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.80 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.83 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.16 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.922732 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.80 | 1.80 | 1.80 | 1.80 | 32360.88 | 53706.77 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.83 | 7.83 | 7.83 | 7.83 | 161757.43 | 286596.46 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.16 | 1.16 | 1.16 | 1.16 | 21200.64 | 36390.47 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.922732 | 0.922732 | 0.922732 | 0.922732 | 17647.37 | 31449.95 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.80 | 0.899715 | 1.80 | 30077.11 | 32360.88 | 16180.44 | 32360.88 | 0.769413 | 0.769410 | 0.769410 | 0.769410 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.83 | 3.91 | 7.83 | 151994.07 | 161757.43 | 80878.71 | 161757.43 | 0.725509 | 0.725510 | 0.725510 | 0.725510 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.16 | 0.580510 | 1.16 | 19708.31 | 21200.64 | 10600.32 | 21200.64 | 0.764290 | 0.764290 | 0.764290 | 0.764290 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.922730 | 0.461365 | 0.922730 | 16474.16 | 17647.37 | 8823.68 | 17647.37 | 0.749219 | 0.749220 | 0.749220 | 0.749220 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.80 | 1925.48 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.83 | 14380.33 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.16 | 1285.43 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.922732 | 1021.61 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.789 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.859 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 38.071 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 16.551 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 19.781 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 12.657 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.657 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2958.869 | 7.789 | 48.236 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2958.869 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 26489.747 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 26489.747 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2496.071 | 16.551 | 102.501 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2496.071 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 151.881 | 12.657 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 151.881 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.3653 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1269 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.2543E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1462 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1462 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.2394 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.570 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.805 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 39.25 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.764 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.764 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.101 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 9 | 0.44388403E-14 | -0.19833209E-15 | -0.17571945E-09 | -0.67828729E-16 |
25 | 8 | 0.25519067E-07 | 0.50126459E-13 | 0.41507681E-03 | -0.29016055E-09 |
26 | 7 | -0.13350764E-01 | 0.25167361E-08 | -0.24681868E-01 | 0.15180307E-03 |
27 | 6 | 0.43548508 | 0.86427767E-06 | 0.49767502 | -0.51029800E-02 |
28 | 5 | -5.4845859 | 0.31913020E-04 | -4.6373968 | 0.66829645E-01 |
29 | 4 | 34.303045 | 0.25842844E-03 | 22.206171 | -0.43938634 |
30 | 3 | -113.99154 | 0.55814228E-03 | -57.137689 | 1.5551483 |
31 | 2 | 199.87078 | 0.31141811E-03 | 79.264502 | -2.9442243 |
32 | 1 | -172.17605 | 0.32996591E-04 | -55.661443 | 2.7633157 |
33 | 0 | 57.057407 | 0.18609994E-06 | 15.493641 | |
34 | 7 | -0.33516880E-08 | -0.26917848E-14 | 0.21730031E-14 | -0.48381574E-16 |
35 | 6 | 0.36965798E-05 | 0.24265975E-08 | 0.31955345E-02 | -0.26806821E-04 |
36 | 5 | -0.25758771E-03 | 0.14341651E-05 | -0.22404650 | 0.19589918E-02 |
37 | 4 | 0.58712639E-02 | 0.65218313E-04 | 4.8349071 | -0.45316519E-01 |
38 | 3 | -0.51388992E-01 | 0.51813976E-03 | -38.051701 | 0.39898850 |
39 | 2 | 0.18223563 | 0.86130223E-03 | 116.54289 | -1.4187277 |
40 | 1 | -0.26287813 | 0.26208477E-03 | -143.94200 | 2.0496102 |
41 | 0 | 0.12812867 | 0.63668310E-05 | 60.838472 | |
42 | 7 | -0.16899007E-07 | 0.12833127E-13 | -0.13150102E-13 | 0.20583092E-15 |
43 | 6 | 0.19364730E-05 | 0.54235158E-09 | 0.32034335E-02 | -0.26873085E-04 |
44 | 5 | -0.79812125E-04 | 0.30470087E-06 | -0.22449475 | 0.19629486E-02 |
45 | 4 | 0.14364157E-02 | 0.13490553E-04 | 4.8423596 | -0.45388170E-01 |
46 | 3 | -0.11321972E-01 | 0.10487769E-03 | -38.093732 | 0.39945320 |
47 | 2 | 0.38353828E-01 | 0.17071033E-03 | 116.62460 | -1.4198209 |
48 | 1 | -0.54148476E-01 | 0.50633929E-04 | -143.99007 | 2.0504003 |
49 | 0 | 0.26099293E-01 | 0.11774431E-05 | 60.838472 | |
50 | 7 | -0.29032744E-08 | -0.17639877E-14 | 0.20832037E-14 | -0.49045170E-16 |
51 | 6 | 0.41946269E-05 | 0.27953210E-08 | 0.31940319E-02 | -0.26794216E-04 |
52 | 5 | -0.29554009E-03 | 0.16532769E-05 | -0.22396112 | 0.19582382E-02 |
53 | 4 | 0.67585570E-02 | 0.75205421E-04 | 4.8334853 | -0.45302851E-01 |
54 | 3 | -0.59226730E-01 | 0.59766051E-03 | -38.043670 | 0.39889973 |
55 | 2 | 0.21013145 | 0.99372709E-03 | 116.52726 | -1.4185186 |
56 | 1 | -0.30318440 | 0.30250693E-03 | -143.93280 | 2.0494590 |
57 | 0 | 0.14779056 | 0.73395870E-05 | 60.838472 | |
58 | 7 | -0.29032744E-08 | -0.17639877E-14 | 0.20832037E-14 | -0.49045170E-16 |
59 | 6 | 0.41946269E-05 | 0.27953210E-08 | 0.31940319E-02 | -0.26794216E-04 |
60 | 5 | -0.29554009E-03 | 0.16532769E-05 | -0.22396112 | 0.19582382E-02 |
61 | 4 | 0.67585570E-02 | 0.75205421E-04 | 4.8334853 | -0.45302851E-01 |
62 | 3 | -0.59226730E-01 | 0.59766051E-03 | -38.043670 | 0.39889973 |
63 | 2 | 0.21013145 | 0.99372709E-03 | 116.52726 | -1.4185186 |
64 | 1 | -0.30318440 | 0.30250693E-03 | -143.93280 | 2.0494590 |
65 | 0 | 0.14779056 | 0.73395870E-05 | 60.838472 | |
66 | 7 | -0.17562435E-08 | -0.39729445E-15 | 0.58168389E-14 | -0.79484401E-16 |
67 | 6 | 0.66980234E-05 | 0.45884094E-08 | 0.31867327E-02 | -0.26732985E-04 |
68 | 5 | -0.48215914E-03 | 0.27191141E-05 | -0.22354626 | 0.19545764E-02 |
69 | 4 | 0.11093948E-01 | 0.12377744E-03 | 4.8265758 | -0.45236432E-01 |
70 | 3 | -0.97430383E-01 | 0.98443929E-03 | -38.004639 | 0.39846831 |
71 | 2 | 0.34596841 | 0.16377189E-02 | 116.45130 | -1.4175025 |
72 | 1 | -0.49936185 | 0.49916259E-03 | -143.88809 | 2.0487240 |
73 | 0 | 0.24346518 | 0.12028251E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 30 | 1 | VerySmooth | 1.647 | 0.445 | 0.367 | 0.451 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 31 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 20121.36248 | 24145.63497 | 1.47968 | 1.77562 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 25207.33713 | 30248.80455 | 1.10942 | 1.33131 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 86471.67121 | 103766.00546 | 6.36195 | 7.63434 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 63928.51837 | 76714.22205 | 2.78351 | 3.34021 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12816.44908 | 15379.73890 | 0.95547 | 1.14656 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 12524.78897 | 15029.74676 | 0.55351 | 0.66421 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 10041.43754 | 12049.72505 | 0.76894 | 0.92273 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 12525.44692 | 15030.53630 | 0.55354 | 0.66425 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 72535.83974 | 87043.00769 | 3.24365 | 3.89238 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -32.70000 | 1.83376E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 22543.87 | 1.79943 | 1.79943 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 43869.53 | 1.33131 | 1.33131 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 103283.33 | 7.82764 | 7.82764 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 191464.29 | 3.34021 | 3.34021 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 16139.07 | 1.16102 | 1.16102 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 25743.81 | 0.66421 | 0.66421 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 13087.53 | 0.92273 | 0.92273 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 25744.59 | 0.66425 | 0.66425 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.77562 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.63434 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14656 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92273 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.89238 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.89238 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 87142.96305 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.77562 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.77562 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.77562 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.77562 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.79943 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.79943 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.98676 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.63434 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.63434 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.63434 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.63434 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.82764 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.82764 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97531 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14656 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14656 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14656 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14656 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.16102 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.16102 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 0.98755 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.92273 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.92273 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.92273 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.92273 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.92273 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.92273 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.79943 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.82764 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.16102 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.92273 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.79943 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.79943 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.79943 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.79943 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.79943 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.79943 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.89972 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.79943 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30077.11355 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 32360.88000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16180.44000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 32360.88000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76941 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76941 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76941 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76941 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32360.88000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53706.77328 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.79943 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1925.47820 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 53706.77328 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.82764 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.82764 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.82764 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.82764 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 7.82764 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.82764 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.91382 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 7.82764 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 151994.07089 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 161757.43000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 80878.71500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 161757.43000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72551 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72551 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72551 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72551 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 161757.43000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 286596.46130 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.82764 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14380.32933 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 286596.46130 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.16102 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.16102 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.16102 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.16102 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.16102 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.16102 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.58051 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.16102 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19708.31102 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 21200.64000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10600.32000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 21200.64000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76429 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76429 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76429 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76429 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21200.64000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36390.46974 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.16102 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1285.43061 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 36390.46974 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.92273 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.92273 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.92273 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.92273 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.92273 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.92273 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46137 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.92273 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16474.16413 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17647.37000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8823.68500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 17647.37000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74922 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74922 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74922 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74922 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17647.37000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31449.95488 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.92273 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1021.61026 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31449.95488 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30949.0 | 10.89 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 155602.6 | 12.12 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20289.5 | 111.31 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16922.7 | 149.10 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.127 | 0.123 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 2.543E-002 | 2.527E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.146 | 0.141 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.146 | 0.141 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.365 | 0.346 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.239 | 0.226 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 11 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.2134383835 | 0.4159624304 | Pass | Pass | 0.2682921437 | 0.4856769641 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 8.0611467870E-002 | 0.2706486704 | Pass | Pass | 7.3089750031E-002 | 0.2147359650 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.1538147207 | 0.3650269206 | Pass | Pass | 0.3115784444 | 0.6533124436 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1777247240 | 0.3811693395 | Pass | Pass | 0.2955368391 | 0.4587171804 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.2138264790 | 0.4432673466 | Pass | Pass | 0.1044939284 | 0.5660815660 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.346 | 0.365 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.127 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.025 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.146 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.146 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.239 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.647 | 0.445 | 0.451 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.647 | 0.445 | 0.451 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.45 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 1.647 | 0.445 | 0.451 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.224 | 0.480 | 0.484 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.224 | 0.480 | 0.484 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.7888 | 379.89 | 2958.87 | LightsWired | BLDG_LIGHT_BACK_SCH | 63.14 | 168.00 | 62.27 | 0.0000 | Y | 34.59 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 16.5511 | 1600.48 | 26489.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 56.86 | 0.0000 | Y | 282.75 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 16.5511 | 150.81 | 2496.07 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 31.98 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 12.6567 | 12.00 | 151.88 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.95 |
Interior Lighting Total | 15.0797 | 2293.99 | 34592.64 | 383.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 26489.75 | 6622.44 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 4644.36 | AstronomicalClock | - | 83.52 | 83.52 | 72.81 | |
Exterior Lighting Total | 4644.36 | 72.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 32360.88 | 24898.78 | 7462.10 | 0.77 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 161757.43 | 117356.63 | 44400.80 | 0.73 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 21200.64 | 16203.44 | 4997.20 | 0.76 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17647.37 | 13221.76 | 4425.61 | 0.75 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30949.0 | 10.89 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 155602.6 | 12.12 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20289.5 | 111.31 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16922.7 | 149.10 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 87142.96 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 53706.77 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 286596.46 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 36390.47 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31449.95 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.60 | 1110.54 | 3.89 | 7252.16 | 1863.17 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.80 | 1925.48 | 1070.05 | 1.00 | 1.33 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1110.54 | 7.83 | 14380.33 | 1837.12 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.16 | 1285.43 | 1107.16 | 1.00 | 1.37 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.92 | 1021.61 | 1107.16 | 1.00 | 1.42 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20121.36 | 24145.63 | 63.56 | 1.480 | 1.776 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01011 | 20.92 | 0.01270 | 0.232 | 0.00 |
CORE_RETAIL | 86471.67 | 103766.01 | 64.83 | 6.362 | 7.634 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00976 | 20.92 | 0.01270 | 1.890 | 0.00 |
POINT_OF_SALE | 12816.45 | 15379.74 | 101.98 | 0.955 | 1.147 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00902 | 20.92 | 0.01270 | 0.178 | 0.00 |
FRONT_RETAIL | 10041.44 | 12049.73 | 79.90 | 0.769 | 0.923 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00908 | 29.79 | 0.01270 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.07 | 100.00 | 0.00001 | 30.10 | 0.01270 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 25207.34 | 30248.80 | 79.63 | 1.109 | 1.331 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00779 | -32.70 | 0.00018 | 0.232 | 0.00 |
CORE_RETAIL | 63928.52 | 76714.22 | 47.93 | 2.784 | 3.340 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00778 | -32.70 | 0.00018 | 1.890 | 0.00 |
POINT_OF_SALE | 12524.79 | 15029.75 | 99.66 | 0.554 | 0.664 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00787 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_RETAIL | 12525.45 | 15030.54 | 99.67 | 0.554 | 0.664 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00787 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_ENTRY | 72535.84 | 87043.01 | 7253.58 | 3.244 | 3.892 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 20.97 | 0.00596 | -32.70 | 0.00018 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.80 | 1.80 | 1.33 | 1.33 | 1.7994 | 1.7756 | 1.7994 | 0.9868 | 1.0000 |
PSZ-AC:2 | 7.83 | 7.83 | 3.34 | 3.34 | 7.8276 | 7.6343 | 7.8276 | 0.9753 | 1.0000 |
PSZ-AC:3 | 1.16 | 1.16 | 0.66 | 0.66 | 1.1610 | 1.1466 | 1.1610 | 0.9876 | 1.0000 |
PSZ-AC:4 | 0.92 | 0.92 | 0.66 | 0.66 | 0.9227 | 0.9227 | 0.9227 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 87142.963 | 87142.963 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87142.96 | 87142.96 | 3.892384 | 20.78 | 12.40 | 0.00594070 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 20.97 | 0.00596174 | 37.1132 | 87043.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 32360.880 | 0.000 | 1.799430 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 32360.88 | 24541.88 | 1.799430 | 23.60 | 17.15 | 0.01011625 | 12.80 | 11.72 | 0.00850000 | 21.71 | 0.01270324 | 18.57 | 12.8689 | 23.88 | 0.01010516 | 52.3585 | 20121.36 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 53706.773 | 53706.773 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53706.77 | 53706.77 | 1.799433 | 11.58 | 9.09 | 0.00646856 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 12.8689 | 21.11 | 0.00779200 | 47.9641 | 25207.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 161757.430 | 0.000 | 7.827640 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 161757.43 | 125392.79 | 7.827640 | 25.57 | 17.86 | 0.01019752 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 24.1479 | 23.89 | 0.00975515 | 50.5698 | 75896.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 286596.461 | 286596.461 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 286596.46 | 286596.46 | 7.827642 | -9.43 | -9.43 | 0.00348206 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 24.1479 | 21.11 | 0.00778219 | 47.9035 | 63928.52 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 21200.640 | 0.000 | 1.161020 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21200.64 | 17868.03 | 1.161020 | 24.79 | 17.07 | 0.00953423 | 12.80 | 11.72 | 0.00850000 | 29.79 | 0.01270324 | 21.01 | 15.3409 | 23.89 | 0.00901889 | 46.8008 | 12628.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 36390.470 | 36390.470 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36390.47 | 36390.47 | 1.161017 | 6.57 | 5.99 | 0.00581203 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 15.3409 | 21.11 | 0.00787439 | 48.4642 | 12524.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 17647.370 | 0.000 | 0.922730 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 17647.37 | 14389.03 | 0.922730 | 25.05 | 17.35 | 0.00977856 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01270324 | 21.04 | 19.3026 | 23.89 | 0.00907742 | 47.0989 | 10027.79 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 31449.955 | 31449.955 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31449.95 | 31449.95 | 0.922732 | 6.57 | 5.99 | 0.00581215 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.3025 | 21.11 | 0.00787441 | 48.4643 | 12525.45 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 87142.963 | 87142.963 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 3.892384 | 4.49151874 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87142.96 | 87142.96 | 1.0000 | 4.49151874 | 3.892384 | 20.78 | 12.40 | 0.00594070 | 35965.3 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87142.96 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00596174 | 20.97 | 0.00596174 | 37.1132 | 87043.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32360.880 | 0.000 | 1.799430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6456 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 32360.88 | 24541.88 | 1.0000 | 2.07640700 | 1.799430 | 23.60 | 17.15 | 0.01011625 | 49462.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32360.88 | 21.71 | 0.01270324 | 18.57 | 0.23156651 | 12.8689 | 23.88 | 0.00973416 | 23.88 | 0.01010516 | 52.3585 | 20121.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53706.773 | 53706.773 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.799433 | 2.07641028 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53706.77 | 53706.77 | 1.0000 | 2.07641028 | 1.799433 | 11.58 | 9.09 | 0.00646856 | 27954.3 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53706.77 | -32.70 | 0.00018338 | -32.70 | 0.23156651 | 12.8689 | 20.91 | 0.00779200 | 21.11 | 0.00779200 | 47.9641 | 25207.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 161757.430 | 0.000 | 7.827640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7967 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 161757.43 | 125392.79 | 1.0000 | 9.03250836 | 7.827640 | 25.57 | 17.86 | 0.01019752 | 51683.4 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 161757.43 | 30.10 | 0.01270324 | 21.10 | 1.89021192 | 24.1479 | 23.89 | 0.00926594 | 23.89 | 0.00975515 | 50.5698 | 75896.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 286596.461 | 286596.461 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.827642 | 9.03251018 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 286596.46 | 286596.46 | 1.0000 | 9.03251018 | 7.827642 | -9.43 | -9.43 | 0.00348206 | -832.9 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 286596.46 | -32.70 | 0.00018338 | -32.70 | 1.89021192 | 24.1479 | 20.89 | 0.00778219 | 21.11 | 0.00778219 | 47.9035 | 63928.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21200.640 | 0.000 | 1.161020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5637 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21200.64 | 17868.03 | 1.0000 | 1.33972984 | 1.161020 | 24.79 | 17.07 | 0.00953423 | 49197.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21200.64 | 29.79 | 0.01270324 | 21.01 | 0.17811053 | 15.3409 | 23.89 | 0.00895967 | 23.89 | 0.00901889 | 46.8008 | 12628.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36390.470 | 36390.470 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.161017 | 1.33972689 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36390.47 | 36390.47 | 1.0000 | 1.33972689 | 1.161017 | 6.57 | 5.99 | 0.00581203 | 21212.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36390.47 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 15.3409 | 20.96 | 0.00787439 | 21.11 | 0.00787439 | 48.4642 | 12524.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17647.370 | 0.000 | 0.922730 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0179 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 17647.37 | 14389.03 | 1.0000 | 1.06476108 | 0.922730 | 25.05 | 17.35 | 0.00977856 | 50080.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17647.37 | 29.89 | 0.01270324 | 21.04 | 0.17811053 | 19.3026 | 23.89 | 0.00907781 | 23.89 | 0.00907742 | 47.0989 | 10027.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31449.955 | 31449.955 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.922732 | 1.06476283 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31449.95 | 31449.95 | 1.0000 | 1.06476283 | 0.922732 | 6.57 | 5.99 | 0.00581215 | 21213.5 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31449.95 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 19.3025 | 20.96 | 0.00787441 | 21.11 | 0.00787441 | 48.4643 | 12525.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.80 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.83 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.16 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 0.92 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2966.33 | 3727.00 | 2368.67 |
CORE_RETAIL | 2805.00 | 3189.67 | 1698.50 |
POINT_OF_SALE | 2812.50 | 2930.67 | 1434.33 |
FRONT_RETAIL | 2896.00 | 3270.67 | 1775.83 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3679.50 | 3738.50 | 2385.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 12.50 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 8.67 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 17.50 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1.33 | 0.00 | 0.00 | 0.00 |
Facility | 29.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.37 | 61.34 | 2317.33 | 0.684 | 0.030 | 0.000 | 0.000 |
CORE_RETAIL | 127.94 | 258.43 | 9762.95 | 1.024 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.06 | 24.35 | 919.94 | 1.384 | 0.033 | 0.000 | 0.000 |
FRONT_RETAIL | 12.06 | 24.35 | 919.94 | 1.113 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.37 | 61.34 | 2317.33 | 0.351 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.94 | 258.43 | 9762.95 | 0.681 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.06 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.06 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1171.86 | 3193.68 | 11-JUN-07:00 | 107264.07 | 29-JUN-16:40 |
Electricity:Building | 578.40 | 3083.31 | 16-APR-07:50 | 41654.89 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 84.58 | 607.80 | 01-JAN-00:10 | 5172.60 | 02-JAN-09:10 |
InteriorLights:Electricity | 383.24 | 1288.14 | 16-APR-07:50 | 30883.85 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 34.59 | 147.94 | 01-JAN-00:10 | 2413.46 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 383.24 | 1288.14 | 16-APR-07:50 | 30883.85 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 367.04 | 1658.43 | 16-APR-07:50 | 28493.38 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 282.75 | 882.99 | 16-APR-07:50 | 23840.77 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 84.90 | 611.62 | 01-JAN-00:10 | 5167.35 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 39.92 | 197.87 | 01-JAN-00:10 | 2684.87 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 31.98 | 124.80 | 01-JAN-00:10 | 2246.46 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.95 | 7.59 | 01-JAN-00:10 | 136.69 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1171.86 | 3193.68 | 11-JUN-07:00 | 107264.07 | 29-JUN-16:40 |
ElectricityPurchased:Plant | 1171.86 | 3193.68 | 11-JUN-07:00 | 107264.07 | 29-JUN-16:40 |
Cogeneration:ElectricityPurchased | 1171.86 | 3193.68 | 11-JUN-07:00 | 107264.07 | 29-JUN-16:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1171.86 | 3193.68 | 11-JUN-07:00 | 107264.07 | 29-JUN-16:40 |
ElectricityNet:Plant | 1171.86 | 3193.68 | 11-JUN-07:00 | 107264.07 | 29-JUN-16:40 |
Cogeneration:ElectricityNet | 1171.86 | 3193.68 | 11-JUN-07:00 | 107264.07 | 29-JUN-16:40 |
Electricity:HVAC | 520.65 | 0.00 | 01-JAN-20:10 | 70489.14 | 29-JUN-16:00 |
Fans:Electricity | 433.76 | 0.00 | 01-JAN-20:10 | 25865.01 | 01-JAN-08:10 |
General:Fans:Electricity | 433.76 | 0.00 | 01-JAN-20:10 | 25865.01 | 01-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 86.89 | 0.00 | 01-JAN-00:10 | 51876.29 | 29-JUN-16:00 |
ExteriorLights:Electricity | 72.81 | 0.00 | 01-JAN-08:20 | 4644.36 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 72.81 | 0.00 | 01-JAN-08:20 | 4644.36 | 01-JAN-00:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 886.70 | 1862.00 | 28-MAY-07:10 | 310646.45 | 09-JAN-07:10 |
Gas:Plant | 100.69 | 1862.00 | 01-JAN-07:20 | 6348.41 | 27-FEB-12:10 |
WaterSystems:Gas | 100.69 | 1862.00 | 01-JAN-07:20 | 6348.41 | 27-FEB-12:10 |
Water Heater:WaterSystems:Gas | 100.69 | 1862.00 | 01-JAN-07:20 | 6348.41 | 27-FEB-12:10 |
Gas:HVAC | 786.01 | 0.00 | 01-JAN-19:20 | 306057.42 | 09-JAN-07:10 |
Heating:Gas | 786.01 | 0.00 | 01-JAN-19:20 | 306057.42 | 09-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 20-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1672.00 | 0.00 | 01-JAN-20:10 | 369808.94 | 01-JAN-09:10 |
EnergyTransfer:Building | 734.96 | 0.00 | 01-JAN-20:10 | 142909.93 | 01-JAN-08:10 |
EnergyTransfer:Zone:BACK_SPACE | 88.27 | 0.00 | 01-JAN-00:40 | 27734.46 | 04-JAN-06:10 |
Heating:EnergyTransfer | 275.38 | 0.00 | 01-JAN-20:10 | 142909.93 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 44.86 | 0.00 | 01-JAN-00:40 | 27734.46 | 04-JAN-06:10 |
Cooling:EnergyTransfer | 459.58 | 0.00 | 01-JAN-00:10 | 85872.69 | 06-SEP-06:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 43.42 | 0.00 | 01-JAN-00:10 | 11188.58 | 30-JUN-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 358.48 | 0.00 | 01-JAN-00:10 | 85095.87 | 01-JAN-09:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 41.41 | 0.00 | 01-JAN-00:10 | 82148.93 | 06-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 317.07 | 0.00 | 01-JAN-00:10 | 69789.68 | 06-SEP-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 70.39 | 0.00 | 01-JAN-00:10 | 12408.27 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 8.24 | 0.00 | 01-JAN-00:10 | 12408.27 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 62.15 | 0.00 | 01-JAN-00:10 | 11572.09 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 51.57 | 0.00 | 01-JAN-00:10 | 13098.60 | 25-DEC-08:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 14.63 | 0.00 | 01-JAN-00:10 | 13098.60 | 25-DEC-08:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 36.94 | 0.00 | 01-JAN-00:10 | 9324.33 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 166.25 | 0.00 | 01-JAN-00:20 | 65832.78 | 05-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 166.25 | 0.00 | 01-JAN-00:20 | 65832.78 | 05-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 937.04 | 0.00 | 01-JAN-19:20 | 244845.94 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 628.80 | 0.00 | 01-JAN-19:20 | 244845.94 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 308.24 | 0.00 | 01-JAN-00:10 | 177599.62 | 30-JUN-15:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 44.856 | -43.418 | 0.000 | 0.000 | 39.918 | 34.587 | 49.992 | 0.000 | 0.000 | 0.091 | 0.000 | 0.000 | 0.000 | 0.000 | -24.394 | -101.633 |
CORE_RETAIL | 0.000 | 0.000 | 41.408 | -317.068 | 0.000 | 0.000 | 167.801 | 282.746 | 84.299 | 42.385 | 0.000 | 0.074 | 0.017 | 0.000 | -39.502 | 0.000 | -21.161 | -240.981 |
POINT_OF_SALE | 0.000 | 0.000 | 8.243 | -62.148 | 0.000 | 0.000 | 15.573 | 31.980 | 52.922 | 39.592 | 0.000 | 0.038 | 0.001 | 0.000 | -22.412 | 0.000 | -11.011 | -52.777 |
FRONT_RETAIL | 0.000 | 0.000 | 14.626 | -36.942 | 0.000 | 0.000 | 15.827 | 31.980 | 7.943 | 39.553 | 0.000 | 0.039 | 0.001 | 0.000 | -21.998 | 0.000 | -10.693 | -40.336 |
FRONT_ENTRY | 166.245 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.946 | 0.000 | 7.977 | 0.000 | 0.035 | 0.000 | 0.000 | -4.567 | 0.000 | -168.335 | -3.301 |
Total Facility | 166.245 | 0.000 | 109.133 | -459.575 | 0.000 | 0.000 | 239.119 | 383.240 | 195.156 | 129.506 | 0.000 | 0.277 | 0.019 | 0.000 | -88.480 | 0.000 | -235.593 | -439.028 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -38380.87 | 0.00 | 0.00 | 389.93 | 536.32 | 1226.28 | 0.00 | 0.00 | 0.00 | 36228.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 06-SEP-06:02 | 0.00 | 0.00 | 0.00 | -236081.01 | 0.00 | 0.00 | 1598.69 | 5297.95 | 2067.82 | 0.00 | 0.00 | 0.00 | 228971.07 | 0.00 | -1690.91 | 0.00 | -163.62 | 0.00 |
POINT_OF_SALE | 15-SEP-06:02 | 0.00 | 0.00 | 0.00 | -27486.19 | 0.00 | 0.00 | 150.37 | 499.21 | 1298.17 | 0.00 | 0.00 | 0.00 | 26554.20 | 0.00 | -926.21 | 0.00 | -89.56 | 0.00 |
FRONT_RETAIL | 10-SEP-08:62 | 0.00 | 0.00 | 0.00 | -21466.81 | 0.00 | 0.00 | 156.38 | 249.61 | 146.13 | 1280.40 | 0.00 | 0.00 | 19701.96 | 0.00 | -0.00 | 0.00 | -67.68 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-SEP-06:02 | 0.00 | 0.00 | 0.00 | -280075.15 | 0.00 | 0.00 | 2337.82 | 6863.08 | 4787.13 | 0.00 | 0.00 | 0.00 | 270574.43 | 0.00 | -3945.15 | 0.00 | -542.15 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 07-JAN-05:32 | 0.00 | 0.00 | 55508.28 | 0.00 | 0.00 | 0.00 | 0.00 | 147.94 | 459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5151.47 | -50964.61 |
CORE_RETAIL | 01-JAN-08:61 | 0.00 | 0.00 | 293996.60 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.49 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3804.58 | 0.00 | -856.24 | -291435.70 |
POINT_OF_SALE | 13-FEB-05:52 | 0.00 | 0.00 | 36601.79 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 649.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2212.50 | 0.00 | -2363.53 | -32799.66 |
FRONT_RETAIL | 24-DEC-07:52 | 0.00 | 0.00 | 32105.43 | 0.00 | 0.00 | 0.00 | 0.00 | 124.80 | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2553.78 | 0.00 | -2269.85 | -27479.67 |
FRONT_ENTRY | 05-JAN-18:00 | 65832.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 152.32 | 0.00 | -549.85 | 0.00 | -65571.91 | 0.00 |
Total Facility | 01-JAN-08:61 | 10248.59 | 0.00 | 416589.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1729.63 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9073.81 | 0.00 | -10659.56 | -410629.29 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7756 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7994 | 0.1287 | 1.0000 | 0.2316 | 0.1287 | ||
PSZ-AC:2 | 7.6343 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.8276 | 0.2415 | 1.0000 | 1.8902 | 0.2415 | ||
PSZ-AC:3 | 1.1466 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1610 | 0.1534 | 1.0000 | 0.1781 | 0.1534 | ||
PSZ-AC:4 | 0.9227 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.9227 | 0.1930 | 1.0000 | 0.1781 | 0.1930 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7756 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7756 | 1.0000 | 1.0000 | 0.2316 | 0.1304 | ||
PSZ-AC:2 | 7.6343 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.6343 | 1.0000 | 1.0000 | 1.8902 | 0.2476 | ||
PSZ-AC:3 | 1.1466 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1466 | 1.0000 | 1.0000 | 0.1781 | 0.1553 | ||
PSZ-AC:4 | 0.9227 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.9227 | 1.0000 | 1.0000 | 0.1781 | 0.1930 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7756 | 1.7756 | 1.7756 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.6343 | 7.6343 | 7.6343 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1466 | 1.1466 | 1.1466 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9227 | 0.9227 | 0.9227 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7756 | 1.7994 | 1.7756 | 1.7756 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6343 | 7.8276 | 7.6343 | 7.6343 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1466 | 1.1610 | 1.1466 | 1.1466 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9227 | 0.9227 | 0.9227 | 0.9227 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7756 | 1.7756 | 1.7756 | 0.2316 | 0.1739 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.6343 | 7.6343 | 7.6343 | 1.8902 | 0.5659 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1466 | 1.1466 | 1.1466 | 0.1781 | 0.2682 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9227 | 0.9227 | 0.9227 | 0.1781 | 0.2681 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7756 | 1.7756 | 1.7756 | 1.7756 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.6343 | 7.6343 | 7.6343 | 7.6343 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1466 | 1.1466 | 1.1466 | 1.1466 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9227 | 0.9227 | 0.9227 | 0.9227 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 786.01 | 306057.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 86.89 | 51876.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 383.24 | 30883.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 72.81 | 4644.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 433.76 | 25865.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 100.69 | 6348.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1171.86 |
Natural Gas | 0.00 | 886.70 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 2058.56 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 167.06 |
Space Heating | 0.00 |
Space Cooling | 37.88 |
Fans (All) | 189.09 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 510.84 |
Subtotal | 510.84 |
Natural Gas [MJ/m2] | |
Space Heating | 342.64 |
Service Water Heating | 43.89 |
Miscellaneous (All) | 386.53 |
Subtotal | 386.53 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.62 |
Space Heating | 38.18 |
Space Cooling | 4.22 |
Fans (All) | 21.07 |
Service Water Heating | 4.89 |
Receptacle Equipment | 9.48 |
Miscellaneous | 3.54 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3292. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220236E+12 |
February | 0.000 | 0.142155E+12 |
March | 0.000 | 0.106655E+12 |
April | 0.000 | 0.271265E+11 |
May | 0.000 | 0.145958E+10 |
June | 0.000 | 0.434133E+08 |
July | 0.000 | 7159490.161 |
August | 0.000 | 0.807204E+08 |
September | 0.000 | 0.833525E+09 |
October | 0.000 | 0.146335E+11 |
November | 0.000 | 0.728776E+11 |
December | 0.000 | 0.199898E+12 |
Annual Sum or Average | 0.786006E+12 | |
Minimum of Months | 0.000 | 7159490.161 |
Maximum of Months | 0.000 | 0.220236E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9208933.94 | 6314.16 | 22-JAN-09:05 | -11.9 | -12.5 | 0.165178E+10 | 1854.44 | 21-JAN-12:39 | -8.1 | -9.3 |
February | 74097274.11 | 6004.41 | 07-FEB-07:05 | -7.2 | -7.5 | 0.150828E+10 | 1854.44 | 11-FEB-12:09 | -7.6 | -9.1 |
March | 0.481314E+09 | 7182.41 | 10-MAR-07:05 | -11.8 | -12.2 | 0.172835E+10 | 2005.08 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.162752E+10 | 7638.84 | 05-APR-06:05 | -13.5 | -14.0 | 0.180232E+10 | 2451.25 | 13-APR-14:20 | 19.27 | 7.63 |
May | 0.487410E+10 | 37348.67 | 19-MAY-06:02 | 14.47 | 10.08 | 0.218368E+10 | 2451.29 | 27-MAY-15:00 | 21.70 | 14.15 |
June | 0.746623E+10 | 33532.00 | 21-JUN-06:02 | 14.27 | 12.49 | 0.220054E+10 | 2451.33 | 07-JUN-14:09 | 22.20 | 14.32 |
July | 0.960695E+10 | 36515.32 | 08-JUL-06:02 | 11.97 | 10.77 | 0.218789E+10 | 2451.41 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.900092E+10 | 38396.04 | 25-AUG-06:02 | 9.05 | 8.95 | 0.228126E+10 | 2451.29 | 10-AUG-14:39 | 17.60 | 15.80 |
September | 0.581708E+10 | 35856.50 | 02-SEP-06:02 | 13.22 | 10.59 | 0.214321E+10 | 2451.34 | 07-SEP-14:00 | 23.90 | 14.99 |
October | 0.330670E+10 | 4994.84 | 25-OCT-06:02 | -4.2 | -4.4 | 0.193135E+10 | 2451.24 | 21-OCT-12:39 | 18.87 | 11.19 |
November | 0.112425E+10 | 6840.61 | 23-NOV-09:05 | -10.0 | -10.5 | 0.162661E+10 | 2449.60 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 29585689.49 | 8962.61 | 08-DEC-07:04 | -20.4 | -20.7 | 0.165429E+10 | 1854.44 | 23-DEC-15:30 | -15.7 | -16.3 |
Annual Sum or Average | 0.434180E+11 | 0.228996E+11 | ||||||||
Minimum of Months | 9208933.94 | 4994.84 | -20.4 | -20.7 | 0.150828E+10 | 1854.44 | -15.7 | -16.3 | ||
Maximum of Months | 0.960695E+10 | 38396.04 | 14.47 | 12.49 | 0.228126E+10 | 2451.41 | 23.90 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625948E+10 | 64109.37 | 31-JAN-07:03 | -14.2 | -14.6 | 0.695925E+10 | 7812.80 | 14-JAN-11:09 | -17.5 | -17.8 |
February | 0.968056E+10 | 81623.19 | 24-FEB-07:03 | -23.9 | -24.2 | 0.636004E+10 | 8207.95 | 04-FEB-16:10 | 7.70 | 2.50 |
March | 0.170165E+11 | 77527.54 | 16-MAR-06:04 | -22.9 | -23.2 | 0.731136E+10 | 9223.61 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.247661E+11 | 98252.41 | 24-APR-06:03 | 4.40 | 3.41 | 0.784000E+10 | 10327.12 | 13-APR-14:20 | 19.27 | 7.63 |
May | 0.350021E+11 | 221413.89 | 20-MAY-06:02 | 5.68 | 3.23 | 0.927009E+10 | 10327.32 | 27-MAY-12:39 | 21.83 | 13.58 |
June | 0.421710E+11 | 213090.48 | 03-JUN-06:02 | 8.07 | 5.86 | 0.927679E+10 | 10327.44 | 10-JUN-11:50 | 18.12 | 17.35 |
July | 0.473900E+11 | 170967.45 | 08-JUL-06:02 | 11.97 | 10.77 | 0.921834E+10 | 10327.81 | 27-JUL-14:20 | 17.23 | 16.05 |
August | 0.450696E+11 | 201571.37 | 19-AUG-06:02 | 6.23 | 5.90 | 0.961196E+10 | 10327.22 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.355608E+11 | 236139.67 | 06-SEP-06:02 | 2.38 | 2.13 | 0.902399E+10 | 10327.55 | 02-SEP-14:50 | 17.23 | 14.50 |
October | 0.288121E+11 | 204834.44 | 23-OCT-06:02 | 5.60 | 4.30 | 0.810519E+10 | 10327.14 | 07-OCT-11:20 | 12.77 | 12.01 |
November | 0.175477E+11 | 75107.03 | 25-NOV-07:03 | -19.2 | -19.5 | 0.690314E+10 | 10327.00 | 01-NOV-14:20 | 17.97 | 13.31 |
December | 0.779303E+10 | 62934.11 | 02-DEC-07:05 | -27.1 | -27.3 | 0.697004E+10 | 7812.78 | 16-DEC-12:20 | -9.5 | -9.8 |
Annual Sum or Average | 0.317069E+12 | 0.968502E+11 | ||||||||
Minimum of Months | 0.625948E+10 | 62934.11 | -27.1 | -27.3 | 0.636004E+10 | 7812.78 | -17.5 | -17.8 | ||
Maximum of Months | 0.473900E+11 | 236139.67 | 11.97 | 10.77 | 0.961196E+10 | 10327.81 | 21.83 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185605E+10 | 8331.79 | 04-JAN-17:22 | -28.1 | -28.3 | 0.656208E+09 | 784.15 | 27-JAN-15:20 | -14.4 | -15.5 |
February | 0.259902E+10 | 7789.01 | 24-FEB-07:03 | -23.9 | -24.2 | 0.629454E+09 | 973.09 | 04-FEB-16:00 | 7.20 | 2.18 |
March | 0.332615E+10 | 7135.80 | 07-MAR-07:03 | -20.8 | -21.1 | 0.734817E+09 | 973.09 | 20-MAR-14:09 | 0.50 | -0.5 |
April | 0.431537E+10 | 7973.61 | 22-APR-13:30 | 16.95 | 7.06 | 0.782360E+09 | 973.10 | 13-APR-14:20 | 19.27 | 7.63 |
May | 0.650445E+10 | 26614.40 | 17-MAY-06:02 | 11.65 | 8.32 | 0.880305E+09 | 973.18 | 24-MAY-14:09 | 27.22 | 17.66 |
June | 0.754386E+10 | 26135.30 | 17-JUN-06:02 | 9.13 | 8.08 | 0.874145E+09 | 973.20 | 20-JUN-14:50 | 21.70 | 14.56 |
July | 0.894769E+10 | 23840.00 | 08-JUL-06:02 | 11.97 | 10.77 | 0.868659E+09 | 973.25 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.921199E+10 | 24922.82 | 25-AUG-06:02 | 9.05 | 8.95 | 0.905788E+09 | 973.20 | 19-AUG-15:39 | 22.60 | 15.08 |
September | 0.767763E+10 | 27494.40 | 15-SEP-06:02 | 5.87 | 5.35 | 0.854236E+09 | 973.26 | 02-SEP-13:00 | 14.40 | 13.10 |
October | 0.539940E+10 | 27275.39 | 20-OCT-06:02 | 5.92 | 5.92 | 0.817075E+09 | 973.11 | 07-OCT-10:09 | 11.78 | 11.14 |
November | 0.310027E+10 | 6993.29 | 29-NOV-07:03 | -18.4 | -18.6 | 0.704098E+09 | 973.09 | 14-NOV-15:09 | 10.73 | 6.42 |
December | 0.166651E+10 | 7436.31 | 08-DEC-07:03 | -20.4 | -20.7 | 0.657558E+09 | 790.11 | 28-DEC-15:09 | -1.8 | -3.6 |
Annual Sum or Average | 0.621484E+11 | 0.936470E+10 | ||||||||
Minimum of Months | 0.166651E+10 | 6993.29 | -28.1 | -28.3 | 0.629454E+09 | 784.15 | -14.4 | -15.5 | ||
Maximum of Months | 0.921199E+10 | 27494.40 | 16.95 | 10.77 | 0.905788E+09 | 973.26 | 27.22 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601070E+09 | 7595.32 | 09-JAN-10:52 | -22.8 | -23.0 | 0.655730E+09 | 736.18 | 28-JAN-12:30 | -11.4 | -12.5 |
February | 0.114529E+10 | 6380.60 | 28-FEB-07:03 | -14.9 | -15.3 | 0.608466E+09 | 970.24 | 28-FEB-15:50 | 6.10 | 1.53 |
March | 0.157288E+10 | 5814.48 | 20-MAR-06:03 | -10.7 | -10.9 | 0.701092E+09 | 973.07 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.243981E+10 | 5503.60 | 22-APR-13:30 | 16.95 | 7.06 | 0.730111E+09 | 973.10 | 13-APR-14:20 | 19.27 | 7.63 |
May | 0.384905E+10 | 19988.17 | 19-MAY-06:02 | 14.47 | 10.08 | 0.860460E+09 | 973.16 | 19-MAY-14:00 | 17.80 | 14.99 |
June | 0.469278E+10 | 17869.13 | 18-JUN-08:62 | 19.78 | 12.82 | 0.872072E+09 | 973.15 | 07-JUN-14:20 | 22.20 | 14.26 |
July | 0.603848E+10 | 19237.14 | 08-JUL-06:02 | 11.97 | 10.77 | 0.868376E+09 | 973.19 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.620530E+10 | 20252.57 | 25-AUG-06:02 | 9.05 | 8.95 | 0.905105E+09 | 973.14 | 05-AUG-10:09 | 18.98 | 13.63 |
September | 0.502429E+10 | 21471.49 | 10-SEP-08:62 | 10.55 | 8.80 | 0.841096E+09 | 973.20 | 02-SEP-13:50 | 15.33 | 13.44 |
October | 0.340459E+10 | 16041.00 | 22-OCT-08:62 | 11.97 | 10.31 | 0.755639E+09 | 973.10 | 21-OCT-12:39 | 18.87 | 11.19 |
November | 0.150814E+10 | 5409.47 | 10-NOV-07:03 | -8.4 | -9.4 | 0.655175E+09 | 973.10 | 01-NOV-14:20 | 17.97 | 13.31 |
December | 0.460323E+09 | 7840.80 | 19-DEC-11:02 | -24.1 | -24.5 | 0.656726E+09 | 736.18 | 23-DEC-12:30 | -15.5 | -16.1 |
Annual Sum or Average | 0.369420E+11 | 0.911005E+10 | ||||||||
Minimum of Months | 0.460323E+09 | 5409.47 | -24.1 | -24.5 | 0.608466E+09 | 736.18 | -15.5 | -16.1 | ||
Maximum of Months | 0.620530E+10 | 21471.49 | 19.78 | 12.82 | 0.905105E+09 | 973.20 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129922E+11 | 55508.21 | 07-JAN-05:32 | -22.4 |
February | 0.867638E+10 | 55317.98 | 13-FEB-05:42 | -23.8 |
March | 0.604379E+10 | 54917.15 | 14-MAR-04:41 | -13.2 |
April | 0.161053E+10 | 54160.48 | 06-APR-05:01 | -6.0 |
May | 0.250281E+09 | 53089.76 | 01-MAY-05:02 | -3.4 |
June | 0.180534E+09 | 2658.78 | 30-JUN-06:08 | 26.60 |
July | 0.186004E+09 | 2415.84 | 30-JUL-08:08 | 24.60 |
August | 0.191401E+09 | 1885.03 | 27-AUG-07:12 | 12.97 |
September | 0.186687E+09 | 1930.29 | 17-SEP-07:33 | 13.70 |
October | 0.431103E+09 | 48209.30 | 14-OCT-06:01 | -1.1 |
November | 0.323148E+10 | 54181.58 | 25-NOV-05:01 | -19.0 |
December | 0.108751E+11 | 55244.45 | 16-DEC-05:42 | -15.7 |
Annual Sum or Average | 0.448554E+11 | |||
Minimum of Months | 0.180534E+09 | 1885.03 | -23.8 | |
Maximum of Months | 0.129922E+11 | 55508.21 | 26.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112859E+11 | 293996.59 | 01-JAN-08:61 | -26.7 |
February | 0.628842E+10 | 292834.63 | 14-FEB-06:01 | -32.0 |
March | 0.407300E+10 | 291821.70 | 05-MAR-08:61 | -25.9 |
April | 0.173566E+10 | 160085.56 | 04-APR-05:01 | -9.0 |
May | 0.123326E+10 | 28059.75 | 01-MAY-06:05 | -3.5 |
June | 0.886736E+09 | 15768.35 | 30-JUN-05:05 | 26.20 |
July | 0.518955E+09 | 16992.08 | 30-JUL-08:08 | 24.60 |
August | 0.651045E+09 | 14077.21 | 27-AUG-07:12 | 12.97 |
September | 0.119699E+10 | 14398.53 | 17-SEP-07:33 | 13.70 |
October | 0.150933E+10 | 38703.29 | 30-OCT-06:04 | -9.4 |
November | 0.287019E+10 | 291799.33 | 13-NOV-06:01 | -8.4 |
December | 0.915861E+10 | 293070.51 | 26-DEC-06:01 | -26.7 |
Annual Sum or Average | 0.414081E+11 | |||
Minimum of Months | 0.518955E+09 | 14077.21 | -32.0 | |
Maximum of Months | 0.112859E+11 | 293996.59 | 26.20 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.246025E+10 | 36598.01 | 25-JAN-05:32 | -24.2 |
February | 0.130976E+10 | 36601.28 | 13-FEB-05:52 | -23.9 |
March | 0.882539E+09 | 36045.16 | 05-MAR-08:61 | -25.9 |
April | 0.273814E+09 | 36080.91 | 06-APR-05:01 | -6.0 |
May | 0.107383E+09 | 4954.07 | 01-MAY-06:50 | -1.7 |
June | 85780684.89 | 1612.31 | 25-JUN-08:06 | 24.08 |
July | 40533059.95 | 1546.97 | 21-JUL-05:04 | 17.98 |
August | 43120275.42 | 1599.78 | 09-AUG-05:05 | 18.40 |
September | 0.100585E+09 | 1488.56 | 02-SEP-05:03 | 13.80 |
October | 0.142143E+09 | 20471.94 | 30-OCT-06:01 | -9.4 |
November | 0.595767E+09 | 36111.41 | 25-NOV-05:01 | -19.0 |
December | 0.220175E+10 | 36563.54 | 26-DEC-05:52 | -26.7 |
Annual Sum or Average | 0.824343E+10 | |||
Minimum of Months | 40533059.95 | 1488.56 | -26.7 | |
Maximum of Months | 0.246025E+10 | 36601.28 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420215E+10 | 31949.24 | 25-JAN-05:42 | -24.3 |
February | 0.229321E+10 | 31957.78 | 13-FEB-05:42 | -23.8 |
March | 0.168349E+10 | 31640.58 | 06-MAR-05:11 | -18.5 |
April | 0.554941E+09 | 31373.26 | 06-APR-05:01 | -6.0 |
May | 0.115219E+09 | 21916.05 | 01-MAY-06:02 | -3.5 |
June | 87616740.11 | 1312.86 | 25-JUN-08:06 | 24.08 |
July | 77227902.43 | 1096.99 | 30-JUL-08:20 | 24.80 |
August | 83629072.12 | 997.29 | 27-AUG-07:12 | 12.97 |
September | 94444133.09 | 1019.53 | 10-SEP-07:52 | 10.00 |
October | 0.225301E+09 | 30595.74 | 30-OCT-05:02 | -9.9 |
November | 0.123173E+10 | 31393.28 | 25-NOV-05:01 | -19.0 |
December | 0.397747E+10 | 32105.34 | 24-DEC-07:52 | -31.1 |
Annual Sum or Average | 0.146264E+11 | |||
Minimum of Months | 77227902.43 | 997.29 | -31.1 | |
Maximum of Months | 0.420215E+10 | 32105.34 | 24.80 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345232E+11 | 65832.78 | 05-JAN-18:00 | -28.3 |
February | 0.241886E+11 | 57411.82 | 01-FEB-18:00 | -23.3 |
March | 0.220014E+11 | 46936.81 | 15-MAR-11:05 | -15.3 |
April | 0.115276E+11 | 33839.92 | 04-APR-11:03 | -4.9 |
May | 0.391917E+10 | 18798.96 | 01-MAY-11:10 | 6.72 |
June | 0.144704E+10 | 10848.07 | 09-JUN-11:02 | 12.38 |
July | 0.619588E+09 | 9557.12 | 08-JUL-11:10 | 13.30 |
August | 0.101682E+10 | 11346.00 | 17-AUG-12:00 | 10.60 |
September | 0.443379E+10 | 16734.01 | 27-SEP-11:05 | 7.38 |
October | 0.110033E+11 | 26822.54 | 29-OCT-11:10 | 0.68 |
November | 0.184182E+11 | 46090.03 | 25-NOV-12:03 | -14.8 |
December | 0.331463E+11 | 63270.17 | 24-DEC-12:10 | -26.9 |
Annual Sum or Average | 0.166245E+12 | |||
Minimum of Months | 0.619588E+09 | 9557.12 | -28.3 | |
Maximum of Months | 0.345232E+11 | 65832.78 | 13.30 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.290080E+10 | 2413.46 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.263912E+10 | 2413.46 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.300979E+10 | 2413.46 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.284005E+10 | 2413.46 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.295530E+10 | 2413.46 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.290440E+10 | 2413.46 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.289095E+10 | 2413.46 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.300979E+10 | 2413.46 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.284005E+10 | 2413.46 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.290080E+10 | 2413.46 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.280526E+10 | 2413.46 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.289095E+10 | 2413.46 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.345872E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.263912E+10 | 2413.46 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.300979E+10 | 2413.46 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.269874E+11 | 23840.77 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.232137E+11 | 23840.77 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.255088E+11 | 23840.77 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.222451E+11 | 23840.77 | 01-APR-16:40 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.206267E+11 | 23840.77 | 01-MAY-16:00 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.205227E+11 | 23840.77 | 09-JUN-16:30 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.203537E+11 | 23840.77 | 11-JUL-16:30 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.221223E+11 | 23840.77 | 03-AUG-08:09 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.227918E+11 | 23840.77 | 01-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.252591E+11 | 23840.77 | 02-OCT-08:09 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.260185E+11 | 23840.77 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.270962E+11 | 23840.77 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.282746E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.203537E+11 | 23840.77 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.270962E+11 | 23840.77 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.268183E+10 | 2246.46 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.244011E+10 | 2246.46 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.278337E+10 | 2246.46 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.262612E+10 | 2246.46 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.273260E+10 | 2246.46 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.268587E+10 | 2246.46 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.267284E+10 | 2246.46 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.278337E+10 | 2246.46 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.262612E+10 | 2246.46 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.268183E+10 | 2246.46 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.259332E+10 | 2246.46 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.267284E+10 | 2246.46 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.319802E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.244011E+10 | 2246.46 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.278337E+10 | 2246.46 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.163184E+09 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.148475E+09 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.169362E+09 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.159794E+09 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.166273E+09 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.163430E+09 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.162637E+09 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.169362E+09 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.159794E+09 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.163184E+09 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.157798E+09 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.162637E+09 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194593E+10 | ||||
Minimum of Months | 0.148475E+09 | 136.69 | 0.00 | 0.00 | |
Maximum of Months | 0.169362E+09 | 136.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403256E+10 |
February | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348260E+10 |
March | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248543E+10 |
April | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1853105.61 | 0.206783E+10 |
May | 0.536353E+10 | 0.295530E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8311721.00 | 0.105843E+10 |
June | 0.528933E+10 | 0.290440E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32955408.09 | 0.602236E+09 |
July | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34425184.08 | 0.406109E+09 |
August | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13302498.88 | 0.627820E+09 |
September | 0.518069E+10 | 0.284005E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433329.15 | 0.110444E+10 |
October | 0.524694E+10 | 0.290080E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155991E+10 |
November | 0.504819E+10 | 0.280526E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279024E+10 |
December | 0.525489E+10 | 0.289095E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417599E+10 |
Annual Sum or Average | 0.628175E+11 | 0.345872E+11 | 0.499918E+11 | 91281246.81 | 0.243936E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.263912E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406109E+09 |
Maximum of Months | 0.548013E+10 | 0.300979E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34425184.08 | 0.417599E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.269874E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343651E+10 |
February | 0.201852E+11 | 0.232137E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300515E+10 |
March | 0.230879E+11 | 0.255088E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215637E+10 |
April | 0.218263E+11 | 0.222451E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1287223.41 | 0.184632E+10 |
May | 0.225967E+11 | 0.206267E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6799900.19 | 0.947969E+09 |
June | 0.222841E+11 | 0.205227E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26136386.29 | 0.540082E+09 |
July | 0.221389E+11 | 0.203537E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28091886.73 | 0.357713E+09 |
August | 0.230879E+11 | 0.221223E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10884898.62 | 0.550084E+09 |
September | 0.218263E+11 | 0.227918E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354756.71 | 0.959550E+09 |
October | 0.221054E+11 | 0.252591E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135388E+10 |
November | 0.212681E+11 | 0.260185E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243212E+10 |
December | 0.221389E+11 | 0.270962E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357512E+10 |
Annual Sum or Average | 0.264651E+12 | 0.282746E+12 | 0.842987E+11 | 73555051.96 | 0.211609E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.203537E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357713E+09 |
Maximum of Months | 0.230879E+11 | 0.270962E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28091886.73 | 0.357512E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176322E+10 |
February | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155285E+10 |
March | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112940E+10 |
April | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 636919.30 | 0.966026E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3596839.82 | 0.493427E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13255954.32 | 0.284371E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14727150.75 | 0.194933E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5758698.72 | 0.300173E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187682.92 | 0.510768E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727698E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126159E+10 |
December | 0.208610E+10 | 0.267284E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182619E+10 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.529224E+11 | 38163245.82 | 0.110106E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194933E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14727150.75 | 0.182619E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174825E+10 |
February | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152843E+10 |
March | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110080E+10 |
April | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650243.77 | 0.922196E+09 |
May | 0.212923E+10 | 0.273260E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3598377.80 | 0.465222E+09 |
June | 0.209978E+10 | 0.268587E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13615085.73 | 0.264997E+09 |
July | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14792596.05 | 0.181360E+09 |
August | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5759995.15 | 0.282730E+09 |
September | 0.205665E+10 | 0.262612E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187740.57 | 0.486714E+09 |
October | 0.208295E+10 | 0.268183E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687295E+09 |
November | 0.200405E+10 | 0.259332E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121773E+10 |
December | 0.208610E+10 | 0.267284E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180710E+10 |
Annual Sum or Average | 0.249375E+11 | 0.319802E+11 | 0.794328E+10 | 38604039.07 | 0.106928E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.244011E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181360E+09 |
Maximum of Months | 0.217552E+10 | 0.278337E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14792596.05 | 0.180710E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339106E+11 |
February | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239874E+11 |
March | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218206E+11 |
April | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117918E+11 |
May | 0.00 | 0.166273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1220653.91 | 0.444333E+10 |
June | 0.00 | 0.163430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24077553.95 | 0.191358E+10 |
July | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9000140.32 | 0.111501E+10 |
August | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 763067.74 | 0.175265E+10 |
September | 0.00 | 0.159794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529950E+10 |
October | 0.00 | 0.163184E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115162E+11 |
November | 0.00 | 0.157798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183174E+11 |
December | 0.00 | 0.162637E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324670E+11 |
Annual Sum or Average | 0.00 | 0.194593E+10 | 35061415.91 | 0.168335E+12 | |||||
Minimum of Months | 0.00 | 0.148475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111501E+10 |
Maximum of Months | 0.00 | 0.169362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24077553.95 | 0.339106E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2413.46 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7975.30 | 04-JAN-05:56 |
February | 5888.82 | 01-FEB-15:09 | 2413.46 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9445.09 | 12-FEB-22:58 |
March | 5888.82 | 01-MAR-15:09 | 2413.46 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4804.85 | 15-MAR-04:53 |
April | 5888.82 | 01-APR-10:09 | 2413.46 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 280.53 | 23-APR-18:10 | 3974.99 | 01-APR-21:03 |
May | 5888.82 | 01-MAY-14:09 | 2413.46 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.16 | 24-MAY-15:00 | 2020.46 | 20-MAY-05:00 |
June | 5888.82 | 01-JUN-14:09 | 2413.46 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 422.64 | 29-JUN-20:03 | 1399.36 | 09-JUN-20:10 |
July | 5888.82 | 01-JUL-10:09 | 2413.46 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 456.59 | 23-JUL-18:03 | 1304.05 | 06-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 2413.46 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 230.45 | 08-AUG-16:00 | 1855.27 | 27-AUG-06:00 |
September | 5888.82 | 01-SEP-14:09 | 2413.46 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 01-SEP-15:00 | 2527.71 | 20-SEP-01:00 |
October | 5888.82 | 02-OCT-14:09 | 2413.46 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3275.32 | 31-OCT-20:03 |
November | 5888.82 | 01-NOV-14:09 | 2413.46 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5342.11 | 22-NOV-02:00 |
December | 5888.82 | 01-DEC-15:09 | 2413.46 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7712.68 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.05 | |||||
Maximum of Months | 5888.82 | 2413.46 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 456.59 | 9445.09 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 23840.77 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6540.11 | 04-JAN-05:52 |
February | 24809.68 | 01-FEB-15:09 | 23840.77 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8406.85 | 12-FEB-22:52 |
March | 24809.68 | 01-MAR-15:09 | 23840.77 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3983.41 | 15-MAR-04:53 |
April | 24809.68 | 01-APR-10:09 | 23840.77 | 01-APR-16:40 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 193.71 | 23-APR-18:05 | 3411.42 | 02-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 23840.77 | 01-MAY-16:00 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.90 | 24-MAY-15:00 | 1834.25 | 20-MAY-05:00 |
June | 24809.68 | 01-JUN-14:09 | 23840.77 | 09-JUN-16:30 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 344.22 | 29-JUN-20:03 | 1266.18 | 10-JUN-22:00 |
July | 24809.68 | 01-JUL-10:09 | 23840.77 | 11-JUL-16:30 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 372.39 | 23-JUL-18:03 | 1214.34 | 06-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 23840.77 | 03-AUG-08:09 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 | 08-AUG-16:00 | 1668.77 | 27-AUG-06:00 |
September | 24809.68 | 01-SEP-14:09 | 23840.77 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 | 01-SEP-15:00 | 2259.01 | 20-SEP-01:00 |
October | 24809.68 | 02-OCT-14:09 | 23840.77 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2768.67 | 31-OCT-21:00 |
November | 24809.68 | 01-NOV-14:09 | 23840.77 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4971.24 | 22-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 23840.77 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6344.00 | 16-DEC-05:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1214.34 | |||||
Maximum of Months | 24809.68 | 23840.77 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 372.39 | 8406.85 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3443.59 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4059.33 | 12-FEB-22:52 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2082.06 | 15-MAR-04:53 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 23-APR-18:05 | 1734.08 | 01-APR-21:03 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 | 24-MAY-15:00 | 910.54 | 20-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 174.97 | 29-JUN-20:03 | 623.27 | 10-JUN-22:00 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.54 | 23-JUL-18:03 | 659.00 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.87 | 08-AUG-16:00 | 882.54 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 01-SEP-15:00 | 1130.62 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1423.09 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2410.01 | 22-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3342.28 | 16-DEC-05:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.27 | |||||
Maximum of Months | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 188.54 | 4059.33 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2246.46 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3443.59 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2246.46 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4080.28 | 12-FEB-22:52 |
March | 2337.76 | 01-MAR-15:09 | 2246.46 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2082.07 | 15-MAR-04:53 |
April | 2337.76 | 01-APR-10:09 | 2246.46 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.76 | 23-APR-18:05 | 1725.06 | 01-APR-21:03 |
May | 2337.76 | 01-MAY-14:09 | 2246.46 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 24-MAY-15:00 | 876.66 | 20-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 2246.46 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 178.51 | 29-JUN-20:03 | 605.85 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2246.46 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 | 23-JUL-18:03 | 600.89 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2246.46 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.87 | 08-AUG-16:00 | 840.89 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2246.46 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 01-SEP-15:00 | 1080.44 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2246.46 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1418.16 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2246.46 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2277.88 | 22-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2246.46 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3342.13 | 16-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.89 | |||||
Maximum of Months | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 | 4080.28 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 136.69 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 65571.91 | 05-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 136.69 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 57298.57 | 01-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 136.69 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 47385.09 | 15-MAR-11:05 |
April | 0.00 | 01-APR-00:10 | 136.69 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 36082.98 | 04-APR-11:01 |
May | 0.00 | 01-MAY-00:10 | 136.69 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.34 | 25-MAY-17:00 | 19067.20 | 01-MAY-11:10 |
June | 0.00 | 01-JUN-00:10 | 136.69 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.05 | 29-JUN-16:00 | 12057.13 | 09-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 136.69 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.25 | 15-JUL-13:55 | 9938.93 | 08-JUL-11:10 |
August | 0.00 | 01-AUG-00:10 | 136.69 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.09 | 08-AUG-16:00 | 11933.85 | 17-AUG-12:00 |
September | 0.00 | 01-SEP-00:10 | 136.69 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 17210.26 | 27-SEP-11:05 |
October | 0.00 | 01-OCT-00:10 | 136.69 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26761.51 | 29-OCT-11:10 |
November | 0.00 | 01-NOV-00:10 | 136.69 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 46364.69 | 25-NOV-12:03 |
December | 0.00 | 01-DEC-00:10 | 136.69 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 63752.65 | 24-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9938.93 | ||||
Maximum of Months | 0.00 | 136.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.05 | 65571.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6314.16 | 22-JAN-09:05 | 2944.41 | 1072.65 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.49 |
February | 6004.41 | 07-FEB-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524.53 |
March | 7182.41 | 10-MAR-07:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.16 |
April | 7638.84 | 05-APR-06:05 | 2944.41 | 2145.30 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37348.67 | 19-MAY-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 |
June | 33532.00 | 21-JUN-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.38 |
July | 36515.32 | 08-JUL-06:02 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.72 |
August | 38396.04 | 25-AUG-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35856.50 | 02-SEP-06:02 | 3680.51 | 1340.81 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.07 |
October | 4994.84 | 25-OCT-06:02 | 3680.51 | 2681.62 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6840.61 | 23-NOV-09:05 | 2944.41 | 1072.65 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.92 |
December | 8962.61 | 08-DEC-07:04 | 5152.71 | 3754.27 | 8583.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4994.84 | 2944.41 | 1072.65 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38396.04 | 5152.71 | 3754.27 | 8583.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 64109.37 | 31-JAN-07:03 | 18607.26 | 31787.70 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.11 |
February | 81623.19 | 24-FEB-07:03 | 21708.47 | 37085.65 | 14474.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.95 |
March | 77527.54 | 16-MAR-06:04 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.32 |
April | 98252.41 | 24-APR-06:03 | 9303.63 | 15893.85 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.56 |
May | 221413.89 | 20-MAY-06:02 | 15506.05 | 12141.13 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.38 |
June | 213090.48 | 03-JUN-06:02 | 15506.05 | 13244.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.96 |
July | 170967.45 | 08-JUL-06:02 | 15506.05 | 13244.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.68 |
August | 201571.37 | 19-AUG-06:02 | 15506.05 | 13244.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.88 |
September | 236139.67 | 06-SEP-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.62 |
October | 204834.44 | 23-OCT-06:02 | 15506.05 | 26489.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.39 |
November | 75107.03 | 25-NOV-07:03 | 18607.26 | 15893.85 | 9305.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.70 |
December | 62934.11 | 02-DEC-07:05 | 12404.84 | 10595.90 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 62934.11 | 9303.63 | 10595.90 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.39 | |
Maximum of Months | 236139.67 | 21708.47 | 37085.65 | 14474.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8331.79 | 04-JAN-17:22 | 8766.61 | 13478.78 | 17525.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.88 |
February | 7789.01 | 24-FEB-07:03 | 2045.54 | 3494.50 | 9087.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.63 |
March | 7135.80 | 07-MAR-07:03 | 1753.32 | 2995.29 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.59 |
April | 7973.61 | 22-APR-13:30 | 2337.76 | 2246.46 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.57 |
May | 26614.40 | 17-MAY-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 |
June | 26135.30 | 17-JUN-06:02 | 1461.10 | 1248.04 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.22 |
July | 23840.00 | 08-JUL-06:02 | 1461.10 | 1248.04 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.47 |
August | 24922.82 | 25-AUG-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27494.40 | 15-SEP-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.56 |
October | 27275.39 | 20-OCT-06:02 | 1461.10 | 2496.07 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.88 |
November | 6993.29 | 29-NOV-07:03 | 1753.32 | 2995.29 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.96 |
December | 7436.31 | 08-DEC-07:03 | 2045.54 | 3494.50 | 9087.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6993.29 | 1461.10 | 1248.04 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27494.40 | 8766.61 | 13478.78 | 17525.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7595.32 | 09-JAN-10:52 | 7305.51 | 11232.32 | 2192.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.18 |
February | 6380.60 | 28-FEB-07:03 | 1753.32 | 2995.29 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.47 |
March | 5814.48 | 20-MAR-06:03 | 2045.54 | 3494.50 | 1363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.84 |
April | 5503.60 | 22-APR-13:30 | 2337.76 | 2246.46 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.58 |
May | 19988.17 | 19-MAY-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 |
June | 17869.13 | 18-JUN-08:62 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 |
July | 19237.14 | 08-JUL-06:02 | 1461.10 | 1248.04 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.20 |
August | 20252.57 | 25-AUG-06:02 | 1461.10 | 2496.07 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21471.49 | 10-SEP-08:62 | 1753.32 | 1497.64 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 |
October | 16041.00 | 22-OCT-08:62 | 1753.32 | 1497.64 | 876.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.20 |
November | 5409.47 | 10-NOV-07:03 | 2045.54 | 3494.50 | 1363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.37 |
December | 7840.80 | 19-DEC-11:02 | 10227.71 | 11232.32 | 2192.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.38 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5409.47 | 1461.10 | 1248.04 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21471.49 | 10227.71 | 11232.32 | 2192.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 15.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.38 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.95 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.44 |
April | 0.00 | 01-APR-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.37 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.16 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 | |
Maximum of Months | 0.00 | 0.00 | 15.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.95 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.100928E+12 | 72164.25 | 02-JAN-16:30 | 0.229056E+12 | 310646.45 | 09-JAN-07:10 |
February | 0.890232E+11 | 72164.25 | 01-FEB-17:10 | 0.150213E+12 | 286983.95 | 14-FEB-07:10 |
March | 0.978750E+11 | 72164.25 | 01-MAR-17:00 | 0.115641E+12 | 239905.78 | 06-MAR-07:10 |
April | 0.894100E+11 | 70203.23 | 22-APR-15:00 | 0.356507E+11 | 156356.11 | 05-APR-06:10 |
May | 0.938649E+11 | 92801.98 | 25-MAY-16:10 | 0.100748E+11 | 74891.51 | 01-MAY-06:10 |
June | 0.101146E+12 | 107264.07 | 29-JUN-16:40 | 0.823037E+10 | 7643.21 | 02-JUN-11:00 |
July | 0.110356E+12 | 99956.73 | 15-JUL-15:20 | 0.822182E+10 | 5933.90 | 08-JUL-11:00 |
August | 0.106071E+12 | 99069.35 | 08-AUG-14:00 | 0.830331E+10 | 9771.95 | 17-AUG-13:00 |
September | 0.912718E+11 | 91247.38 | 01-SEP-15:30 | 0.876345E+10 | 14351.30 | 27-SEP-11:09 |
October | 0.952327E+11 | 74835.13 | 19-OCT-14:00 | 0.229169E+11 | 104776.93 | 30-OCT-06:30 |
November | 0.955534E+11 | 72164.26 | 01-NOV-16:00 | 0.810633E+11 | 214679.50 | 25-NOV-07:10 |
December | 0.101129E+12 | 72164.25 | 01-DEC-16:19 | 0.208566E+12 | 288786.78 | 24-DEC-09:09 |
Annual Sum or Average | 0.117186E+13 | 0.886700E+12 | ||||
Minimum of Months | 0.890232E+11 | 70203.23 | 0.822182E+10 | 5933.90 | ||
Maximum of Months | 0.110356E+12 | 107264.07 | 0.229056E+12 | 310646.45 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.354150E+11 | 0.798922E+10 | 0.164409E+11 | 0.00 | 0.410831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308815E+11 | 0.656248E+10 | 0.149157E+11 | 0.00 | 0.366635E+11 | 0.00 | 0.00 | 2345.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342547E+11 | 0.637856E+10 | 0.168545E+11 | 0.00 | 0.403871E+11 | 0.00 | 0.00 | 38473.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304972E+11 | 0.528064E+10 | 0.160165E+11 | 0.00 | 0.371111E+11 | 0.00 | 0.00 | 0.504567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.292135E+11 | 0.465365E+10 | 0.166477E+11 | 0.00 | 0.343228E+11 | 0.00 | 0.00 | 0.902733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.289622E+11 | 0.406846E+10 | 0.162772E+11 | 0.00 | 0.310924E+11 | 0.00 | 0.00 | 0.207459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287530E+11 | 0.440842E+10 | 0.163871E+11 | 0.00 | 0.306945E+11 | 0.00 | 0.00 | 0.301128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.308681E+11 | 0.509672E+10 | 0.168545E+11 | 0.00 | 0.316672E+11 | 0.00 | 0.00 | 0.215843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.310439E+11 | 0.578223E+10 | 0.160165E+11 | 0.00 | 0.340462E+11 | 0.00 | 0.00 | 0.438291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336867E+11 | 0.689966E+10 | 0.164409E+11 | 0.00 | 0.376699E+11 | 0.00 | 0.00 | 0.535420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341682E+11 | 0.748763E+10 | 0.159174E+11 | 0.00 | 0.379798E+11 | 0.00 | 0.00 | 278926.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354955E+11 | 0.820379E+10 | 0.163871E+11 | 0.00 | 0.410429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.383240E+12 | 0.728115E+11 | 0.195156E+12 | 0.433761E+12 | 0.00 | 0.868936E+11 | |||||||
Minimum of Months | 0.287530E+11 | 0.406846E+10 | 0.149157E+11 | 0.00 | 0.306945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354955E+11 | 0.820379E+10 | 0.168545E+11 | 0.00 | 0.410831E+11 | 0.00 | 0.00 | 0.301128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.220236E+12 | 0.00 | 0.881973E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.142155E+12 | 0.00 | 0.805733E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.106655E+12 | 0.00 | 0.898671E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.271265E+11 | 0.00 | 0.852414E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.145958E+10 | 0.00 | 0.861521E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 43413309.78 | 0.00 | 0.818696E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 7159490.16 | 0.00 | 0.821466E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 80720365.08 | 0.00 | 0.822259E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.833525E+09 | 0.00 | 0.792993E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.146335E+11 | 0.00 | 0.828340E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.728776E+11 | 0.00 | 0.818570E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.199898E+12 | 0.00 | 0.866776E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.786006E+12 | 0.100694E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 7159490.16 | 0.00 | 0.792993E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.220236E+12 | 0.00 | 0.898671E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 30883.85 | 02-JAN-09:09 | 4644.36 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 25865.01 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 30883.85 | 01-FEB-09:09 | 4644.36 | 01-FEB-00:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 25865.01 | 02-FEB-13:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 30883.85 | 01-MAR-09:09 | 4644.36 | 01-MAR-00:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 25865.01 | 01-MAR-08:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 30883.85 | 01-APR-16:40 | 4644.36 | 01-APR-00:10 | 10771.04 | 01-APR-09:09 | 0.00 | 25865.01 | 01-APR-07:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 30883.85 | 01-MAY-16:00 | 4644.36 | 01-MAY-00:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 25865.01 | 01-MAY-07:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 30883.85 | 09-JUN-16:30 | 4644.36 | 01-JUN-00:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 25865.01 | 03-JUN-12:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 30883.85 | 11-JUL-16:30 | 4644.36 | 01-JUL-00:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 25865.01 | 01-JUL-12:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 30883.85 | 03-AUG-08:09 | 4644.36 | 01-AUG-00:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 25865.01 | 03-AUG-11:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 30883.85 | 01-SEP-08:09 | 4644.36 | 01-SEP-00:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 25865.01 | 02-SEP-13:20 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 30883.85 | 02-OCT-08:09 | 4644.36 | 01-OCT-00:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 25865.01 | 01-OCT-12:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 30883.85 | 01-NOV-08:09 | 4644.36 | 01-NOV-00:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 25865.01 | 01-NOV-14:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 30883.85 | 01-DEC-09:09 | 4644.36 | 01-DEC-00:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 25865.01 | 01-DEC-09:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 30883.85 | 4644.36 | 10771.04 | 0.00 | 25865.01 | 0.00 | 0.00 | |||||
Maximum of Months | 30883.85 | 4644.36 | 10771.04 | 0.00 | 25865.01 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.74 | 04-FEB-16:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19.89 | 18-MAR-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20775.06 | 23-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36001.67 | 25-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 51876.29 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47678.78 | 15-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44761.81 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34211.33 | 01-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14567.39 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 230.27 | 21-NOV-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51876.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72164.25 | 02-JAN-16:30 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 25865.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72164.25 | 01-FEB-17:10 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 25865.01 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72164.25 | 01-MAR-17:00 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 25865.01 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 70203.23 | 22-APR-15:00 | 28897.12 | 10771.04 | 0.00 | 0.00 | 25865.01 | 0.00 | 0.00 | 4670.07 | 0.00 |
May | 92801.98 | 25-MAY-16:10 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18612.85 | 0.00 | 0.00 | 34520.98 | 0.00 |
June | 107264.07 | 29-JUN-16:40 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18612.85 | 0.00 | 0.00 | 48983.06 | 0.00 |
July | 99956.73 | 15-JUL-15:20 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18612.85 | 0.00 | 0.00 | 45649.18 | 0.00 |
August | 99069.35 | 08-AUG-14:00 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18612.85 | 0.00 | 0.00 | 44761.81 | 0.00 |
September | 91247.38 | 01-SEP-15:30 | 28897.12 | 10771.04 | 0.00 | 0.00 | 18612.85 | 0.00 | 0.00 | 32966.38 | 0.00 |
October | 74835.13 | 19-OCT-14:00 | 30883.85 | 10771.04 | 0.00 | 0.00 | 18612.85 | 0.00 | 0.00 | 14567.39 | 0.00 |
November | 72164.26 | 01-NOV-16:00 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 25865.01 | 0.00 | 0.00 | 0.01 | 0.00 |
December | 72164.25 | 01-DEC-16:19 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 25865.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 70203.23 | 24923.66 | 10771.04 | 0.00 | 0.00 | 18612.85 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107264.07 | 30883.85 | 10771.04 | 4644.36 | 0.00 | 25865.01 | 0.00 | 0.00 | 48983.06 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 306057.42 | 09-JAN-07:10 | 0.00 | 6232.95 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 285121.95 | 14-FEB-07:10 | 0.00 | 6348.41 | 27-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 235311.31 | 06-MAR-07:10 | 0.00 | 6344.86 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 154494.11 | 05-APR-06:10 | 0.00 | 6130.14 | 05-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 73029.51 | 01-MAY-06:10 | 0.00 | 5749.89 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 2496.05 | 02-JUN-11:00 | 0.00 | 5150.36 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 886.39 | 08-JUL-11:00 | 0.00 | 5095.05 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 4862.40 | 17-AUG-13:00 | 0.00 | 5061.71 | 01-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 9285.21 | 27-SEP-11:09 | 0.00 | 5067.93 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 100208.66 | 30-OCT-06:30 | 0.00 | 5116.19 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 212817.50 | 25-NOV-07:10 | 0.00 | 5317.56 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 286924.78 | 24-DEC-09:09 | 0.00 | 5820.13 | 26-DEC-12:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 886.39 | 0.00 | 5061.71 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 306057.42 | 0.00 | 6348.41 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 16.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 16.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.17 | 17.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.00 | 16.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.50 | 16.66 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 17.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 16.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 16.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 17.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.33 | 16.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.67 | 16.62 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 16.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.50 | 16.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.33 | 16.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.50 | 16.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.50 | 16.33 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.48 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.12 | 404.17 | 21.11 | 404.17 | 21.11 |
April | 405.00 | 21.89 | 185.17 | 21.12 | 185.17 | 21.12 |
May | 300.33 | 23.40 | 41.83 | 23.36 | 8.17 | 21.16 |
June | 173.83 | 23.84 | 156.33 | 23.89 | 68.17 | 23.89 |
July | 78.00 | 23.89 | 293.83 | 23.89 | 70.33 | 23.89 |
August | 77.50 | 23.87 | 271.67 | 23.89 | 66.67 | 23.89 |
September | 255.17 | 23.68 | 63.83 | 23.89 | 16.50 | 23.89 |
October | 411.17 | 22.39 | 47.50 | 21.11 | 47.50 | 21.11 |
November | 399.00 | 21.26 | 297.00 | 21.11 | 297.00 | 21.11 |
December | 415.00 | 21.11 | 415.00 | 21.11 | 415.00 | 21.11 |
Annual Sum or Average | 3727.00 | 21.96 | 2966.33 | 21.88 | 2368.67 | 21.37 |
Minimum of Months | 77.50 | 21.11 | 41.83 | 21.11 | 8.17 | 21.11 |
Maximum of Months | 422.00 | 23.89 | 415.00 | 23.89 | 415.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 402.17 | 21.11 | 402.17 | 21.11 |
February | 376.00 | 21.11 | 309.67 | 21.11 | 309.67 | 21.11 |
March | 422.00 | 21.15 | 224.83 | 21.11 | 224.83 | 21.11 |
April | 392.33 | 22.13 | 38.33 | 21.11 | 38.33 | 21.11 |
May | 161.67 | 23.30 | 99.17 | 23.86 | 1.17 | 21.11 |
June | 70.17 | 23.86 | 278.50 | 23.89 | 56.83 | 23.89 |
July | 62.17 | 23.89 | 399.17 | 23.89 | 62.17 | 23.89 |
August | 43.00 | 23.86 | 389.33 | 23.89 | 41.00 | 23.89 |
September | 86.17 | 23.28 | 114.50 | 23.88 | 13.17 | 23.89 |
October | 348.17 | 22.10 | 3.33 | 21.21 | 3.17 | 21.11 |
November | 399.00 | 21.31 | 161.50 | 21.11 | 161.50 | 21.11 |
December | 415.00 | 21.11 | 384.50 | 21.11 | 384.50 | 21.11 |
Annual Sum or Average | 3189.67 | 21.70 | 2805.00 | 22.38 | 1698.50 | 21.39 |
Minimum of Months | 43.00 | 21.11 | 3.33 | 21.11 | 1.17 | 21.11 |
Maximum of Months | 422.00 | 23.89 | 402.17 | 23.89 | 402.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 348.83 | 21.11 | 348.83 | 21.11 |
February | 372.50 | 21.42 | 217.83 | 21.11 | 217.83 | 21.11 |
March | 414.50 | 21.60 | 181.50 | 21.11 | 181.50 | 21.11 |
April | 328.83 | 22.40 | 60.83 | 21.59 | 50.33 | 21.11 |
May | 130.83 | 23.41 | 122.83 | 23.84 | 2.17 | 21.10 |
June | 74.83 | 23.86 | 292.00 | 23.89 | 54.00 | 23.89 |
July | 47.67 | 23.90 | 401.50 | 23.89 | 47.50 | 23.90 |
August | 26.67 | 23.84 | 397.50 | 23.89 | 23.67 | 23.89 |
September | 57.67 | 23.46 | 230.67 | 23.89 | 9.83 | 23.89 |
October | 263.00 | 22.55 | 67.50 | 23.59 | 7.17 | 21.11 |
November | 385.17 | 21.80 | 133.17 | 21.11 | 133.17 | 21.11 |
December | 415.00 | 21.12 | 358.33 | 21.11 | 358.33 | 21.11 |
Annual Sum or Average | 2930.67 | 21.87 | 2812.50 | 22.60 | 1434.33 | 21.37 |
Minimum of Months | 26.67 | 21.11 | 60.83 | 21.11 | 2.17 | 21.10 |
Maximum of Months | 415.00 | 23.90 | 401.50 | 23.89 | 358.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 380.50 | 21.11 | 380.50 | 21.11 |
February | 376.00 | 21.21 | 261.67 | 21.11 | 261.67 | 21.11 |
March | 422.00 | 21.28 | 245.00 | 21.11 | 245.00 | 21.11 |
April | 365.00 | 21.86 | 101.17 | 21.26 | 95.67 | 21.11 |
May | 201.67 | 22.94 | 97.17 | 23.72 | 5.83 | 21.11 |
June | 119.33 | 23.67 | 243.67 | 23.89 | 60.50 | 23.89 |
July | 64.00 | 23.85 | 385.50 | 23.89 | 56.83 | 23.89 |
August | 48.67 | 23.75 | 367.33 | 23.89 | 40.50 | 23.89 |
September | 126.33 | 22.96 | 165.50 | 23.89 | 14.00 | 23.89 |
October | 321.50 | 21.81 | 65.50 | 22.52 | 32.33 | 21.11 |
November | 397.17 | 21.34 | 192.50 | 21.11 | 192.50 | 21.11 |
December | 415.00 | 21.11 | 390.50 | 21.11 | 390.50 | 21.11 |
Annual Sum or Average | 3270.67 | 21.69 | 2896.00 | 22.35 | 1775.83 | 21.38 |
Minimum of Months | 48.67 | 21.11 | 65.50 | 21.11 | 5.83 | 21.11 |
Maximum of Months | 422.00 | 23.85 | 390.50 | 23.89 | 390.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09502 | 14.32759 | -0.7966 | 18.54216 |
February | 376.00000 | 21.09520 | 16.13168 | -0.7548 | 17.17070 |
March | 422.00000 | 21.10890 | 20.39356 | -0.6901 | 15.23644 |
April | 405.00000 | 21.87814 | 24.35773 | -0.4105 | 10.08967 |
May | 418.00000 | 23.53270 | 34.61453 | -0.8406 | 21.71282 |
June | 408.00000 | 23.87665 | 48.09347 | -0.5528 | 11.83703 |
July | 415.00000 | 23.90579 | 54.16042 | -0.4448 | 9.27096 |
August | 422.00000 | 23.89857 | 53.59389 | -0.4701 | 9.77553 |
September | 405.00000 | 23.75957 | 41.30154 | -0.6746 | 15.15222 |
October | 414.00000 | 22.39643 | 33.67116 | -0.1781 | 7.49725 |
November | 399.00000 | 21.25129 | 23.99994 | -0.5884 | 12.94129 |
December | 415.00000 | 21.09532 | 15.70664 | -0.7686 | 17.63080 |
Annual Sum or Average | 4913.00000 | 22.41945 | 31.83666 | -0.5967 | 13.89127 |
Minimum of Months | 376.00000 | 21.09502 | 14.32759 | -0.8406 | 7.49725 |
Maximum of Months | 422.00000 | 23.90579 | 54.16042 | -0.1781 | 21.71282 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09713 | 11.11509 | -0.6914 | 15.20584 |
February | 376.00000 | 21.10418 | 13.24866 | -0.6336 | 13.59832 |
March | 422.00000 | 21.15029 | 17.27081 | -0.5489 | 11.59015 |
April | 405.00000 | 22.19521 | 21.17402 | -0.2114 | 7.71820 |
May | 418.00000 | 23.67442 | 32.74822 | -0.6424 | 14.98724 |
June | 408.00000 | 23.90344 | 46.81572 | -0.4154 | 8.91532 |
July | 415.00000 | 23.91090 | 52.95666 | -0.3392 | 7.53116 |
August | 422.00000 | 23.90557 | 52.40616 | -0.3683 | 7.96935 |
September | 405.00000 | 23.77075 | 40.03632 | -0.5527 | 11.95202 |
October | 414.00000 | 22.40033 | 30.89709 | -0.0830 | 6.96062 |
November | 399.00000 | 21.31220 | 21.14896 | -0.4734 | 10.43559 |
December | 415.00000 | 21.09894 | 12.65067 | -0.6648 | 14.45090 |
Annual Sum or Average | 4913.00000 | 22.47182 | 29.51831 | -0.4679 | 10.92996 |
Minimum of Months | 376.00000 | 21.09713 | 11.11509 | -0.6914 | 6.96062 |
Maximum of Months | 422.00000 | 23.91090 | 52.95666 | -0.0830 | 15.20584 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10004 | 10.67178 | -0.6763 | 15.00115 |
February | 376.00000 | 21.42956 | 12.43773 | -0.5210 | 12.15444 |
March | 422.00000 | 21.62583 | 16.28003 | -0.4302 | 10.75909 |
April | 405.00000 | 22.67107 | 19.53404 | -0.1032 | 7.73896 |
May | 418.00000 | 23.74523 | 31.49392 | -0.5913 | 13.79941 |
June | 408.00000 | 23.89976 | 45.63401 | -0.3899 | 8.62592 |
July | 415.00000 | 23.91088 | 51.23969 | -0.2880 | 6.92324 |
August | 422.00000 | 23.90625 | 50.63419 | -0.2933 | 7.07321 |
September | 405.00000 | 23.84061 | 38.43933 | -0.4520 | 10.03077 |
October | 414.00000 | 23.04159 | 28.62231 | 0.07900 | 7.38761 |
November | 399.00000 | 21.86835 | 20.00533 | -0.3482 | 9.64188 |
December | 415.00000 | 21.10327 | 12.16114 | -0.6729 | 14.85737 |
Annual Sum or Average | 4913.00000 | 22.68815 | 28.23895 | -0.3903 | 10.32660 |
Minimum of Months | 376.00000 | 21.10004 | 10.67178 | -0.6763 | 6.92324 |
Maximum of Months | 422.00000 | 23.91088 | 51.23969 | 0.07900 | 15.00115 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09533 | 10.77013 | -0.7187 | 16.21384 |
February | 376.00000 | 21.19509 | 12.70844 | -0.6110 | 13.63571 |
March | 422.00000 | 21.26681 | 16.71156 | -0.5477 | 12.23143 |
April | 405.00000 | 22.05534 | 20.58241 | -0.2666 | 8.94807 |
May | 418.00000 | 23.43009 | 32.75407 | -0.7400 | 19.02908 |
June | 408.00000 | 23.83371 | 46.94817 | -0.4638 | 10.19912 |
July | 415.00000 | 23.89945 | 52.56986 | -0.3411 | 7.66362 |
August | 422.00000 | 23.88755 | 51.74854 | -0.3516 | 7.93938 |
September | 405.00000 | 23.60311 | 39.84507 | -0.5737 | 13.53251 |
October | 414.00000 | 22.27689 | 30.33302 | -0.1131 | 7.98968 |
November | 399.00000 | 21.33510 | 20.76794 | -0.4991 | 11.35236 |
December | 415.00000 | 21.09551 | 12.25951 | -0.7166 | 16.09481 |
Annual Sum or Average | 4913.00000 | 22.42536 | 29.14615 | -0.4947 | 12.06366 |
Minimum of Months | 376.00000 | 21.09533 | 10.77013 | -0.7400 | 7.66362 |
Maximum of Months | 422.00000 | 23.89945 | 52.56986 | -0.1131 | 19.02908 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 69350517.66 | 20210441.20 | 26.48 | 61002988.95 | 8347528.71 | 0.00 | 0.21 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 5378.47 | 23-APR-16:00 | 4712.51 | 23-APR-16:00 | 665.96 | 23-APR-16:00 | 1575.51 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.300285E+10 | 0.824905E+09 | 210.51 | 0.256180E+10 | 0.441055E+09 | 0.00 | 1.00 | 19-MAY-06:02 | 0.00 | 01-MAY-00:10 | 32821.44 | 26-MAY-06:02 | 25618.13 | 19-MAY-06:02 | 9869.82 | 27-MAY-06:02 | 6979.26 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.794097E+10 | 0.212806E+10 | 302.69 | 0.600370E+10 | 0.193727E+10 | 0.00 | 1.00 | 07-JUN-06:02 | 0.00 | 01-JUN-00:10 | 35767.82 | 30-JUN-06:02 | 29647.10 | 18-JUN-08:62 | 17100.18 | 23-JUN-06:02 | 7753.24 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.126009E+11 | 0.331553E+10 | 355.14 | 0.898264E+10 | 0.361824E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 35951.97 | 30-JUL-08:62 | 22330.17 | 06-JUL-06:02 | 18502.42 | 05-JUL-06:04 | 7597.72 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.865283E+10 | 0.226445E+10 | 325.50 | 0.613677E+10 | 0.251606E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 34216.96 | 30-AUG-06:02 | 23354.36 | 20-AUG-08:62 | 17558.54 | 30-AUG-06:04 | 7203.77 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.108081E+10 | 0.288419E+09 | 192.39 | 0.873023E+09 | 0.207784E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 33397.10 | 01-SEP-06:02 | 21706.25 | 02-SEP-06:02 | 16794.94 | 01-SEP-06:04 | 7080.73 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 30742989.49 | 8608423.31 | 43.67 | 29660601.00 | 1082388.49 | 0.00 | 0.13 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3126.14 | 19-OCT-15:00 | 3028.80 | 19-OCT-15:00 | 136.70 | 19-OCT-14:10 | 873.47 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.333784E+11 | 0.885019E+10 | 1456.38 | 0.246486E+11 | 0.872984E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.126009E+11 | 0.331553E+10 | 355.14 | 0.898264E+10 | 0.361824E+10 | 0.00 | 1.00 | 0.00 | 35951.97 | 29647.10 | 18502.42 | 7753.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.108861E+10 | 0.337853E+09 | 52.72 | 0.974299E+09 | 0.114313E+09 | 0.00 | 0.37 | 23-APR-08:63 | 0.00 | 01-APR-00:10 | 48934.40 | 23-APR-16:00 | 44861.50 | 23-APR-08:63 | 6045.46 | 23-APR-15:50 | 15356.23 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.221935E+11 | 0.666948E+10 | 247.06 | 0.190085E+11 | 0.318507E+10 | 0.00 | 1.00 | 16-MAY-06:02 | 0.00 | 01-MAY-00:10 | 164544.23 | 26-MAY-06:02 | 136844.63 | 21-MAY-08:62 | 50168.41 | 26-MAY-06:02 | 39086.70 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.522785E+11 | 0.153267E+11 | 336.11 | 0.388765E+11 | 0.134020E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 178183.83 | 25-JUN-08:62 | 142657.49 | 18-JUN-08:62 | 82842.03 | 23-JUN-06:04 | 43120.52 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.755388E+11 | 0.218677E+11 | 380.79 | 0.525954E+11 | 0.229434E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 181336.84 | 30-JUL-08:62 | 111356.41 | 06-JUL-06:02 | 91517.81 | 30-JUL-08:04 | 42474.73 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.532214E+11 | 0.154018E+11 | 357.03 | 0.369892E+11 | 0.162321E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 171640.49 | 30-AUG-06:02 | 116656.25 | 20-AUG-08:62 | 86271.47 | 30-AUG-06:04 | 40329.66 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.101284E+11 | 0.298614E+10 | 209.25 | 0.811621E+10 | 0.201223E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 167087.08 | 01-SEP-06:02 | 144851.94 | 09-SEP-06:02 | 80491.50 | 01-SEP-06:02 | 39581.11 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.916504E+09 | 0.274994E+09 | 53.24 | 0.843141E+09 | 73363136.77 | 0.00 | 1.00 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 | 152227.18 | 02-OCT-06:02 | 115606.14 | 22-OCT-08:62 | 40712.82 | 02-OCT-06:02 | 36016.75 | 02-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 835549.55 | 263988.41 | 2.92 | 563678.44 | 271871.11 | 0.00 | 0.01 | 21-NOV-13:20 | 0.00 | 01-NOV-00:10 | 728.99 | 21-NOV-13:20 | 490.34 | 21-NOV-13:20 | 238.65 | 21-NOV-13:20 | 230.23 | 21-NOV-13:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.215367E+12 | 0.628649E+11 | 1639.11 | 0.157404E+12 | 0.579628E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.755388E+11 | 0.218677E+11 | 380.79 | 0.525954E+11 | 0.229434E+11 | 0.00 | 1.00 | 0.00 | 181336.84 | 144851.94 | 91517.81 | 43120.52 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 8312.16 | 2345.91 | 2.33 | 8312.16 | 0.00 | 0.00 | 0.00 | 04-FEB-16:50 | 0.00 | 01-FEB-00:10 | 13.24 | 04-FEB-16:50 | 13.24 | 04-FEB-16:50 | 0.00 | 08-FEB-14:10 | 3.74 | 04-FEB-16:50 | 0.00 | 01-FEB-00:10 |
March | 136226.70 | 38423.54 | 14.46 | 136226.70 | 0.00 | 0.00 | 0.00 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 | 70.55 | 18-MAR-13:40 | 70.55 | 18-MAR-13:40 | 0.00 | 19-MAR-15:40 | 19.89 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 |
April | 0.357761E+09 | 96192140.10 | 96.05 | 0.339807E+09 | 17953497.04 | 0.00 | 0.51 | 23-APR-13:40 | 0.00 | 01-APR-00:10 | 9223.35 | 23-APR-13:40 | 8276.41 | 23-APR-14:00 | 1036.55 | 23-APR-13:40 | 2388.26 | 23-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 0.355651E+10 | 0.941345E+09 | 264.55 | 0.316109E+10 | 0.395413E+09 | 0.00 | 1.00 | 17-MAY-06:02 | 0.00 | 01-MAY-00:10 | 21511.34 | 26-MAY-06:02 | 17037.04 | 19-MAY-06:02 | 6439.16 | 26-MAY-06:02 | 4574.01 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.755241E+10 | 0.196768E+10 | 330.47 | 0.590938E+10 | 0.164304E+10 | 0.00 | 1.00 | 07-JUN-06:02 | 0.00 | 01-JUN-00:10 | 23875.66 | 30-JUN-05:03 | 19474.25 | 18-JUN-08:62 | 11037.50 | 30-JUN-05:03 | 5071.89 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.112530E+11 | 0.288519E+10 | 380.15 | 0.832502E+10 | 0.292799E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 23739.77 | 30-JUL-08:62 | 14703.48 | 06-JUL-06:02 | 12204.52 | 30-JUL-08:04 | 4981.10 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.917666E+10 | 0.231483E+10 | 354.81 | 0.673216E+10 | 0.244450E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 22415.20 | 30-AUG-06:02 | 15416.42 | 20-AUG-08:62 | 11392.93 | 30-AUG-06:02 | 4719.23 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.262759E+10 | 0.673570E+09 | 244.17 | 0.225144E+10 | 0.376157E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 21818.41 | 01-SEP-06:02 | 17454.44 | 09-SEP-06:02 | 10690.37 | 01-SEP-06:02 | 4628.58 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.592641E+09 | 0.152138E+09 | 111.22 | 0.556429E+09 | 36212165.74 | 0.00 | 1.00 | 22-OCT-08:62 | 0.00 | 01-OCT-00:10 | 19951.55 | 22-OCT-08:62 | 15171.19 | 22-OCT-08:62 | 5119.40 | 20-OCT-06:02 | 4224.03 | 22-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 51495.66 | 14547.63 | 16.29 | 48837.44 | 2658.23 | 0.00 | 0.00 | 14-NOV-16:20 | 0.00 | 01-NOV-00:10 | 41.87 | 14-NOV-16:20 | 41.87 | 14-NOV-16:20 | 0.96 | 01-NOV-18:35 | 11.81 | 14-NOV-16:20 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.351168E+11 | 0.903100E+10 | 1814.51 | 0.272755E+11 | 0.784127E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.112530E+11 | 0.288519E+10 | 380.15 | 0.832502E+10 | 0.292799E+10 | 0.00 | 1.00 | 0.00 | 23875.66 | 19474.25 | 12204.52 | 5071.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 181.13 | 49.66 | 0.83 | 181.13 | 0.00 | 0.00 | 0.00 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.10 | 31-MAR-14:10 | 0.10 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.03 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.189910E+09 | 50310755.10 | 51.41 | 0.175494E+09 | 14415441.21 | 0.00 | 0.45 | 23-APR-14:00 | 0.00 | 01-APR-00:10 | 6635.72 | 23-APR-14:00 | 5853.07 | 23-APR-14:00 | 865.59 | 23-APR-13:40 | 1708.32 | 23-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.226639E+10 | 0.591600E+09 | 211.92 | 0.196868E+10 | 0.297720E+09 | 0.00 | 1.00 | 18-MAY-06:02 | 0.00 | 01-MAY-00:10 | 17901.40 | 26-MAY-06:02 | 13873.21 | 19-MAY-06:02 | 5532.72 | 26-MAY-06:02 | 3696.83 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.517332E+10 | 0.132348E+10 | 297.03 | 0.393998E+10 | 0.123334E+10 | 0.00 | 1.00 | 07-JUN-06:02 | 0.00 | 01-JUN-00:10 | 19436.59 | 30-JUN-06:02 | 15885.73 | 18-JUN-08:62 | 9358.71 | 23-JUN-06:02 | 4105.01 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.813466E+10 | 0.204442E+10 | 360.60 | 0.583203E+10 | 0.230263E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 19715.58 | 30-JUL-08:62 | 12023.28 | 06-JUL-06:02 | 10108.35 | 05-JUL-06:02 | 4026.11 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.648161E+10 | 0.160321E+10 | 333.22 | 0.467448E+10 | 0.180713E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 18655.08 | 30-AUG-06:02 | 12622.19 | 20-AUG-08:62 | 9540.42 | 30-AUG-06:02 | 3814.63 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.173486E+10 | 0.434780E+09 | 191.58 | 0.147868E+10 | 0.256177E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 18197.94 | 01-SEP-06:02 | 13661.53 | 09-SEP-06:02 | 9120.81 | 01-SEP-06:02 | 3747.70 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.397059E+09 | 99680350.57 | 56.16 | 0.369970E+09 | 27088620.59 | 0.00 | 0.73 | 22-OCT-08:62 | 0.00 | 01-OCT-00:10 | 11186.48 | 22-OCT-08:62 | 8314.87 | 22-OCT-08:62 | 2871.61 | 22-OCT-08:62 | 2504.46 | 22-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 1425.65 | 390.92 | 3.19 | 1414.92 | 10.74 | 0.00 | 0.00 | 17-NOV-13:30 | 0.00 | 01-NOV-00:10 | 0.25 | 17-NOV-13:30 | 0.25 | 17-NOV-13:30 | 0.02 | 01-NOV-16:40 | 0.07 | 17-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.243778E+11 | 0.614748E+10 | 1505.95 | 0.184393E+11 | 0.593849E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.813466E+10 | 0.204442E+10 | 360.60 | 0.583203E+10 | 0.230263E+10 | 0.00 | 1.00 | 0.00 | 19715.58 | 15885.73 | 10108.35 | 4105.01 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.86 | 10.66 | 20.20 | 3.10 | 156.78 | 0.00 | 0.00 | 744.00 |
February | 54.88 | 25.16 | 29.72 | 27.39 | 125.05 | 0.00 | 0.00 | 672.00 |
March | 78.32 | 43.87 | 34.45 | 57.31 | 97.61 | 0.00 | 0.00 | 744.00 |
April | 115.86 | 73.05 | 42.80 | 112.23 | 65.51 | 0.00 | 0.00 | 720.00 |
May | 142.35 | 80.18 | 62.17 | 159.31 | 40.46 | 0.00 | 0.00 | 744.00 |
June | 149.78 | 86.34 | 63.44 | 176.61 | 30.28 | 1.17 | 0.00 | 720.00 |
July | 153.75 | 91.94 | 61.81 | 185.78 | 28.61 | 0.17 | 0.00 | 744.00 |
August | 121.07 | 67.95 | 53.13 | 141.45 | 31.57 | 0.00 | 0.00 | 744.00 |
September | 87.65 | 44.94 | 42.71 | 90.57 | 46.76 | 0.00 | 0.00 | 720.00 |
October | 52.00 | 20.55 | 31.44 | 39.43 | 68.07 | 0.00 | 0.00 | 744.00 |
November | 30.04 | 8.97 | 21.07 | 10.40 | 97.87 | 0.00 | 0.00 | 720.00 |
December | 24.12 | 6.14 | 17.98 | 0.71 | 153.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.88 | 46.75 | 40.14 | 84.00 | 78.29 | 1.33 | 0.00 | 8760.00 |
Minimum of Months | 24.12 | 6.14 | 17.98 | 0.71 | 28.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 153.75 | 91.94 | 63.44 | 185.78 | 156.78 | 1.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1552.49 | 1078.30 | 474.20 | 1300.03 | 1340.56 | 0.00 | 0.00 | 744.00 |
February | 1969.50 | 1329.11 | 640.39 | 1783.89 | 1138.39 | 0.00 | 0.00 | 672.00 |
March | 1741.14 | 1102.86 | 638.28 | 1496.10 | 953.57 | 0.00 | 0.00 | 744.00 |
April | 1580.59 | 860.44 | 720.15 | 1330.97 | 640.35 | 0.00 | 0.00 | 720.00 |
May | 1329.23 | 457.74 | 871.48 | 1112.24 | 377.35 | 0.00 | 0.00 | 744.00 |
June | 1192.76 | 321.29 | 871.47 | 1041.20 | 263.36 | 0.00 | 0.00 | 720.00 |
July | 1304.40 | 416.88 | 887.52 | 1194.36 | 247.72 | 0.00 | 0.00 | 744.00 |
August | 1392.11 | 585.10 | 807.01 | 1337.13 | 293.34 | 0.00 | 0.00 | 744.00 |
September | 1489.37 | 794.77 | 694.61 | 1436.97 | 458.72 | 0.00 | 0.00 | 720.00 |
October | 1268.94 | 746.32 | 522.62 | 1162.62 | 658.66 | 0.00 | 0.00 | 744.00 |
November | 1126.99 | 706.05 | 420.95 | 982.83 | 884.40 | 0.00 | 0.00 | 720.00 |
December | 1198.51 | 784.29 | 414.22 | 930.66 | 1294.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1425.28 | 761.66 | 663.62 | 1255.44 | 710.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1126.99 | 321.29 | 414.22 | 930.66 | 247.72 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1969.50 | 1329.11 | 887.52 | 1783.89 | 1340.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1552.49 | 1078.30 | 474.20 | 1295.87 | 1336.54 | 0.00 | 0.00 | 744.00 |
February | 1969.50 | 1329.11 | 640.39 | 1782.73 | 1127.34 | 0.00 | 0.00 | 672.00 |
March | 1741.14 | 1102.86 | 638.28 | 1497.26 | 938.17 | 0.00 | 0.00 | 744.00 |
April | 1580.59 | 860.44 | 720.15 | 1335.28 | 619.65 | 0.00 | 0.00 | 720.00 |
May | 1329.23 | 457.74 | 871.48 | 1112.55 | 362.07 | 0.00 | 0.00 | 744.00 |
June | 1192.76 | 321.29 | 871.47 | 1036.85 | 252.86 | 0.00 | 0.00 | 720.00 |
July | 1304.40 | 416.88 | 887.52 | 1188.01 | 238.38 | 0.00 | 0.00 | 744.00 |
August | 1392.11 | 585.10 | 807.01 | 1330.64 | 284.09 | 0.00 | 0.00 | 744.00 |
September | 1489.37 | 794.77 | 694.61 | 1434.46 | 445.50 | 0.00 | 0.00 | 720.00 |
October | 1268.94 | 746.32 | 522.62 | 1167.97 | 633.50 | 0.00 | 0.00 | 744.00 |
November | 1126.99 | 706.05 | 420.95 | 985.42 | 864.51 | 0.00 | 0.00 | 720.00 |
December | 1198.51 | 784.29 | 414.22 | 927.43 | 1290.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1425.28 | 761.66 | 663.62 | 1254.22 | 697.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1126.99 | 321.29 | 414.22 | 927.43 | 238.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1969.50 | 1329.11 | 887.52 | 1782.73 | 1336.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 319.45 | 221.88 | 97.57 | 259.10 | 279.47 | 0.00 | 0.00 | 744.00 |
February | 405.25 | 273.48 | 131.77 | 357.44 | 235.17 | 0.00 | 0.00 | 672.00 |
March | 358.26 | 226.93 | 131.33 | 300.84 | 197.35 | 0.00 | 0.00 | 744.00 |
April | 325.23 | 177.05 | 148.18 | 269.68 | 127.84 | 0.00 | 0.00 | 720.00 |
May | 273.51 | 94.19 | 179.32 | 226.51 | 72.88 | 0.00 | 0.00 | 744.00 |
June | 245.43 | 66.11 | 179.32 | 209.56 | 51.01 | 0.00 | 0.00 | 720.00 |
July | 268.40 | 85.78 | 182.62 | 238.43 | 49.73 | 0.00 | 0.00 | 744.00 |
August | 286.45 | 120.39 | 166.05 | 270.76 | 57.93 | 0.00 | 0.00 | 744.00 |
September | 306.46 | 163.54 | 142.93 | 293.80 | 88.89 | 0.00 | 0.00 | 720.00 |
October | 261.10 | 153.57 | 107.54 | 236.81 | 129.22 | 0.00 | 0.00 | 744.00 |
November | 231.90 | 145.28 | 86.62 | 196.42 | 181.31 | 0.00 | 0.00 | 720.00 |
December | 246.61 | 161.38 | 85.23 | 184.69 | 271.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 293.27 | 156.72 | 136.55 | 252.94 | 144.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 231.90 | 66.11 | 85.23 | 184.69 | 49.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 405.25 | 273.48 | 182.62 | 357.44 | 279.47 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82667107.30 | 28551890.81 | 54115216.49 | 8307144.91 | 0.419929E+09 |
February | 0.132754E+09 | 60858984.07 | 71894981.23 | 66268176.24 | 0.302531E+09 |
March | 0.209768E+09 | 0.117496E+09 | 92271339.99 | 0.153502E+09 | 0.261445E+09 |
April | 0.300303E+09 | 0.189355E+09 | 0.110948E+09 | 0.290903E+09 | 0.169798E+09 |
May | 0.381273E+09 | 0.214752E+09 | 0.166522E+09 | 0.426688E+09 | 0.108361E+09 |
June | 0.388230E+09 | 0.223786E+09 | 0.164443E+09 | 0.457768E+09 | 78480124.72 |
July | 0.411799E+09 | 0.246244E+09 | 0.165555E+09 | 0.497585E+09 | 76635407.55 |
August | 0.324278E+09 | 0.181986E+09 | 0.142292E+09 | 0.378868E+09 | 84562549.14 |
September | 0.227194E+09 | 0.116494E+09 | 0.110700E+09 | 0.234748E+09 | 0.121192E+09 |
October | 0.139274E+09 | 55053857.97 | 84219733.44 | 0.105605E+09 | 0.182322E+09 |
November | 77867792.52 | 23246241.70 | 54621550.82 | 26946857.18 | 0.253685E+09 |
December | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 0.409956E+09 |
Annual Sum or Average | 0.274000E+10 | 0.147426E+10 | 0.126574E+10 | 0.264908E+10 | 0.246890E+10 |
Minimum of Months | 64590652.68 | 16433343.23 | 48157309.46 | 1890144.27 | 76635407.55 |
Maximum of Months | 0.411799E+09 | 0.246244E+09 | 0.166522E+09 | 0.497585E+09 | 0.419929E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.348200E+10 | 0.359057E+10 |
February | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.431559E+10 | 0.275399E+10 |
March | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.400714E+10 | 0.255404E+10 |
April | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.344986E+10 | 0.165979E+10 |
May | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.297903E+10 | 0.101069E+10 |
June | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.269878E+10 | 0.682636E+09 |
July | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.319898E+10 | 0.663483E+09 |
August | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.358137E+10 | 0.785690E+09 |
September | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.372462E+10 | 0.118900E+10 |
October | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.311397E+10 | 0.176417E+10 |
November | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.254750E+10 | 0.229236E+10 |
December | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.249267E+10 | 0.346602E+10 |
Annual Sum or Average | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.395915E+11 | 0.224124E+11 |
Minimum of Months | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.249267E+10 | 0.663483E+09 |
Maximum of Months | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.431559E+10 | 0.359057E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.347085E+10 | 0.357980E+10 |
February | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.431279E+10 | 0.272726E+10 |
March | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.401027E+10 | 0.251279E+10 |
April | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.346104E+10 | 0.160612E+10 |
May | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.297986E+10 | 0.969773E+09 |
June | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.268752E+10 | 0.655401E+09 |
July | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.318196E+10 | 0.638486E+09 |
August | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.356398E+10 | 0.760908E+09 |
September | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.371812E+10 | 0.115473E+10 |
October | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.312829E+10 | 0.169675E+10 |
November | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.255422E+10 | 0.224082E+10 |
December | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.248402E+10 | 0.345554E+10 |
Annual Sum or Average | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.395529E+11 | 0.219984E+11 |
Minimum of Months | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.248402E+10 | 0.638486E+09 |
Maximum of Months | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.431279E+10 | 0.357980E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.855610E+09 | 0.594270E+09 | 0.261340E+09 | 0.693975E+09 | 0.748527E+09 |
February | 0.980387E+09 | 0.661611E+09 | 0.318776E+09 | 0.864716E+09 | 0.568918E+09 |
March | 0.959574E+09 | 0.607808E+09 | 0.351766E+09 | 0.805778E+09 | 0.528582E+09 |
April | 0.842995E+09 | 0.458909E+09 | 0.384086E+09 | 0.699001E+09 | 0.331355E+09 |
May | 0.732563E+09 | 0.252272E+09 | 0.480291E+09 | 0.606694E+09 | 0.195189E+09 |
June | 0.636148E+09 | 0.171356E+09 | 0.464792E+09 | 0.543181E+09 | 0.132223E+09 |
July | 0.718880E+09 | 0.229749E+09 | 0.489130E+09 | 0.638598E+09 | 0.133189E+09 |
August | 0.767221E+09 | 0.322460E+09 | 0.444761E+09 | 0.725206E+09 | 0.155158E+09 |
September | 0.794346E+09 | 0.423884E+09 | 0.370462E+09 | 0.761531E+09 | 0.230392E+09 |
October | 0.699338E+09 | 0.411311E+09 | 0.288027E+09 | 0.634260E+09 | 0.346091E+09 |
November | 0.601072E+09 | 0.376564E+09 | 0.224508E+09 | 0.509122E+09 | 0.469959E+09 |
December | 0.660521E+09 | 0.432235E+09 | 0.228286E+09 | 0.494672E+09 | 0.727028E+09 |
Annual Sum or Average | 0.924866E+10 | 0.494243E+10 | 0.430623E+10 | 0.797674E+10 | 0.456661E+10 |
Minimum of Months | 0.601072E+09 | 0.171356E+09 | 0.224508E+09 | 0.494672E+09 | 0.132223E+09 |
Maximum of Months | 0.980387E+09 | 0.661611E+09 | 0.489130E+09 | 0.864716E+09 | 0.748527E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.62 | 2508.54 | 493.83 | 170.56 | 323.27 | 0.00 | 0.00 |
February | 438.28 | 2000.87 | 878.00 | 402.51 | 475.50 | 0.00 | 0.00 |
March | 916.98 | 1561.80 | 1253.09 | 701.89 | 551.20 | 0.00 | 0.00 |
April | 1795.70 | 1048.13 | 1853.72 | 1168.86 | 684.86 | 0.00 | 0.00 |
May | 2548.91 | 647.32 | 2277.62 | 1282.86 | 994.75 | 0.00 | 0.00 |
June | 2825.73 | 484.45 | 2396.48 | 1381.40 | 1015.08 | 0.00 | 0.00 |
July | 2972.43 | 457.80 | 2459.97 | 1470.99 | 988.98 | 0.00 | 0.00 |
August | 2263.25 | 505.15 | 1937.14 | 1087.13 | 850.01 | 0.00 | 0.00 |
September | 1449.06 | 748.10 | 1402.43 | 719.10 | 683.33 | 0.00 | 0.00 |
October | 630.85 | 1089.14 | 831.98 | 328.88 | 503.10 | 0.00 | 0.00 |
November | 166.34 | 1565.96 | 480.67 | 143.50 | 337.17 | 0.00 | 0.00 |
December | 11.29 | 2448.96 | 385.85 | 98.17 | 287.68 | 0.00 | 0.00 |
Annual Sum or Average | 1344.03 | 1252.61 | 1390.16 | 747.97 | 642.18 | 0.00 | 0.00 |
Minimum of Months | 11.29 | 457.80 | 385.85 | 98.17 | 287.68 | 0.00 | 0.00 |
Maximum of Months | 2972.43 | 2508.54 | 2459.97 | 1470.99 | 1015.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1300.03 | 1340.56 | 1552.49 | 1078.30 | 474.20 | 0.00 | 0.00 |
February | 1783.89 | 1138.39 | 1969.50 | 1329.11 | 640.39 | 0.00 | 0.00 |
March | 1496.10 | 953.57 | 1741.14 | 1102.86 | 638.28 | 0.00 | 0.00 |
April | 1330.97 | 640.35 | 1580.59 | 860.44 | 720.15 | 0.00 | 0.00 |
May | 1112.24 | 377.35 | 1329.23 | 457.74 | 871.48 | 0.00 | 0.00 |
June | 1041.20 | 263.36 | 1192.76 | 321.29 | 871.47 | 0.00 | 0.00 |
July | 1194.36 | 247.72 | 1304.40 | 416.88 | 887.52 | 0.00 | 0.00 |
August | 1337.13 | 293.34 | 1392.11 | 585.10 | 807.01 | 0.00 | 0.00 |
September | 1436.97 | 458.72 | 1489.37 | 794.77 | 694.61 | 0.00 | 0.00 |
October | 1162.62 | 658.66 | 1268.94 | 746.32 | 522.62 | 0.00 | 0.00 |
November | 982.83 | 884.40 | 1126.99 | 706.05 | 420.95 | 0.00 | 0.00 |
December | 930.66 | 1294.06 | 1198.51 | 784.29 | 414.22 | 0.00 | 0.00 |
Annual Sum or Average | 1255.44 | 710.69 | 1425.28 | 761.66 | 663.62 | 0.00 | 0.00 |
Minimum of Months | 930.66 | 247.72 | 1126.99 | 321.29 | 414.22 | 0.00 | 0.00 |
Maximum of Months | 1783.89 | 1340.56 | 1969.50 | 1329.11 | 887.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1295.87 | 1336.54 | 1552.49 | 1078.30 | 474.20 | 0.00 | 0.00 |
February | 1782.73 | 1127.34 | 1969.50 | 1329.11 | 640.39 | 0.00 | 0.00 |
March | 1497.26 | 938.17 | 1741.14 | 1102.86 | 638.28 | 0.00 | 0.00 |
April | 1335.28 | 619.65 | 1580.59 | 860.44 | 720.15 | 0.00 | 0.00 |
May | 1112.55 | 362.07 | 1329.23 | 457.74 | 871.48 | 0.00 | 0.00 |
June | 1036.85 | 252.86 | 1192.76 | 321.29 | 871.47 | 0.00 | 0.00 |
July | 1188.01 | 238.38 | 1304.40 | 416.88 | 887.52 | 0.00 | 0.00 |
August | 1330.64 | 284.09 | 1392.11 | 585.10 | 807.01 | 0.00 | 0.00 |
September | 1434.46 | 445.50 | 1489.37 | 794.77 | 694.61 | 0.00 | 0.00 |
October | 1167.97 | 633.50 | 1268.94 | 746.32 | 522.62 | 0.00 | 0.00 |
November | 985.42 | 864.51 | 1126.99 | 706.05 | 420.95 | 0.00 | 0.00 |
December | 927.43 | 1290.15 | 1198.51 | 784.29 | 414.22 | 0.00 | 0.00 |
Annual Sum or Average | 1254.22 | 697.56 | 1425.28 | 761.66 | 663.62 | 0.00 | 0.00 |
Minimum of Months | 927.43 | 238.38 | 1126.99 | 321.29 | 414.22 | 0.00 | 0.00 |
Maximum of Months | 1782.73 | 1336.54 | 1969.50 | 1329.11 | 887.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 259.10 | 279.47 | 319.45 | 221.88 | 97.57 | 0.00 | 0.00 |
February | 357.44 | 235.17 | 405.25 | 273.48 | 131.77 | 0.00 | 0.00 |
March | 300.84 | 197.35 | 358.26 | 226.93 | 131.33 | 0.00 | 0.00 |
April | 269.68 | 127.84 | 325.23 | 177.05 | 148.18 | 0.00 | 0.00 |
May | 226.51 | 72.88 | 273.51 | 94.19 | 179.32 | 0.00 | 0.00 |
June | 209.56 | 51.01 | 245.43 | 66.11 | 179.32 | 0.00 | 0.00 |
July | 238.43 | 49.73 | 268.40 | 85.78 | 182.62 | 0.00 | 0.00 |
August | 270.76 | 57.93 | 286.45 | 120.39 | 166.05 | 0.00 | 0.00 |
September | 293.80 | 88.89 | 306.46 | 163.54 | 142.93 | 0.00 | 0.00 |
October | 236.81 | 129.22 | 261.10 | 153.57 | 107.54 | 0.00 | 0.00 |
November | 196.42 | 181.31 | 231.90 | 145.28 | 86.62 | 0.00 | 0.00 |
December | 184.69 | 271.44 | 246.61 | 161.38 | 85.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.94 | 144.81 | 293.27 | 156.72 | 136.55 | 0.00 | 0.00 |
Minimum of Months | 184.69 | 49.73 | 231.90 | 66.11 | 85.23 | 0.00 | 0.00 |
Maximum of Months | 357.44 | 279.47 | 405.25 | 273.48 | 182.62 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132914E+09 | 0.671887E+10 | 0.132267E+10 | 0.456830E+09 | 0.865843E+09 | 0.00 | 0.00 |
February | 0.106029E+10 | 0.484050E+10 | 0.212406E+10 | 0.973744E+09 | 0.115032E+10 | 0.00 | 0.00 |
March | 0.245603E+10 | 0.418311E+10 | 0.335628E+10 | 0.187994E+10 | 0.147634E+10 | 0.00 | 0.00 |
April | 0.465445E+10 | 0.271676E+10 | 0.480484E+10 | 0.302967E+10 | 0.177517E+10 | 0.00 | 0.00 |
May | 0.682700E+10 | 0.173377E+10 | 0.610038E+10 | 0.343602E+10 | 0.266435E+10 | 0.00 | 0.00 |
June | 0.732429E+10 | 0.125568E+10 | 0.621168E+10 | 0.358058E+10 | 0.263109E+10 | 0.00 | 0.00 |
July | 0.796135E+10 | 0.122617E+10 | 0.658878E+10 | 0.393990E+10 | 0.264888E+10 | 0.00 | 0.00 |
August | 0.606189E+10 | 0.135300E+10 | 0.518844E+10 | 0.291177E+10 | 0.227667E+10 | 0.00 | 0.00 |
September | 0.375598E+10 | 0.193907E+10 | 0.363510E+10 | 0.186390E+10 | 0.177119E+10 | 0.00 | 0.00 |
October | 0.168968E+10 | 0.291716E+10 | 0.222838E+10 | 0.880862E+09 | 0.134752E+10 | 0.00 | 0.00 |
November | 0.431150E+09 | 0.405896E+10 | 0.124588E+10 | 0.371940E+09 | 0.873945E+09 | 0.00 | 0.00 |
December | 30242308.26 | 0.655930E+10 | 0.103345E+10 | 0.262933E+09 | 0.770517E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423853E+11 | 0.395023E+11 | 0.438400E+11 | 0.235881E+11 | 0.202518E+11 | 0.00 | 0.00 |
Minimum of Months | 30242308.26 | 0.122617E+10 | 0.103345E+10 | 0.262933E+09 | 0.770517E+09 | 0.00 | 0.00 |
Maximum of Months | 0.796135E+10 | 0.671887E+10 | 0.658878E+10 | 0.393990E+10 | 0.266435E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.348200E+10 | 0.359057E+10 | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.00 | 0.00 |
February | 0.431559E+10 | 0.275399E+10 | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.00 | 0.00 |
March | 0.400714E+10 | 0.255404E+10 | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.00 | 0.00 |
April | 0.344986E+10 | 0.165979E+10 | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.00 | 0.00 |
May | 0.297903E+10 | 0.101069E+10 | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.00 | 0.00 |
June | 0.269878E+10 | 0.682636E+09 | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.00 | 0.00 |
July | 0.319898E+10 | 0.663483E+09 | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.00 | 0.00 |
August | 0.358137E+10 | 0.785690E+09 | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.00 | 0.00 |
September | 0.372462E+10 | 0.118900E+10 | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.00 | 0.00 |
October | 0.311397E+10 | 0.176417E+10 | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.00 | 0.00 |
November | 0.254750E+10 | 0.229236E+10 | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.00 | 0.00 |
December | 0.249267E+10 | 0.346602E+10 | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.395915E+11 | 0.224124E+11 | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249267E+10 | 0.663483E+09 | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.431559E+10 | 0.359057E+10 | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.347085E+10 | 0.357980E+10 | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.00 | 0.00 |
February | 0.431279E+10 | 0.272726E+10 | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.00 | 0.00 |
March | 0.401027E+10 | 0.251279E+10 | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.00 | 0.00 |
April | 0.346104E+10 | 0.160612E+10 | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.00 | 0.00 |
May | 0.297986E+10 | 0.969773E+09 | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.00 | 0.00 |
June | 0.268752E+10 | 0.655401E+09 | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.00 | 0.00 |
July | 0.318196E+10 | 0.638486E+09 | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.00 | 0.00 |
August | 0.356398E+10 | 0.760908E+09 | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.00 | 0.00 |
September | 0.371812E+10 | 0.115473E+10 | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.00 | 0.00 |
October | 0.312829E+10 | 0.169675E+10 | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.00 | 0.00 |
November | 0.255422E+10 | 0.224082E+10 | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.00 | 0.00 |
December | 0.248402E+10 | 0.345554E+10 | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.395529E+11 | 0.219984E+11 | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248402E+10 | 0.638486E+09 | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.431279E+10 | 0.357980E+10 | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.693975E+09 | 0.748527E+09 | 0.855610E+09 | 0.594270E+09 | 0.261340E+09 | 0.00 | 0.00 |
February | 0.864716E+09 | 0.568918E+09 | 0.980387E+09 | 0.661611E+09 | 0.318776E+09 | 0.00 | 0.00 |
March | 0.805778E+09 | 0.528582E+09 | 0.959574E+09 | 0.607808E+09 | 0.351766E+09 | 0.00 | 0.00 |
April | 0.699001E+09 | 0.331355E+09 | 0.842995E+09 | 0.458909E+09 | 0.384086E+09 | 0.00 | 0.00 |
May | 0.606694E+09 | 0.195189E+09 | 0.732563E+09 | 0.252272E+09 | 0.480291E+09 | 0.00 | 0.00 |
June | 0.543181E+09 | 0.132223E+09 | 0.636148E+09 | 0.171356E+09 | 0.464792E+09 | 0.00 | 0.00 |
July | 0.638598E+09 | 0.133189E+09 | 0.718880E+09 | 0.229749E+09 | 0.489130E+09 | 0.00 | 0.00 |
August | 0.725206E+09 | 0.155158E+09 | 0.767221E+09 | 0.322460E+09 | 0.444761E+09 | 0.00 | 0.00 |
September | 0.761531E+09 | 0.230392E+09 | 0.794346E+09 | 0.423884E+09 | 0.370462E+09 | 0.00 | 0.00 |
October | 0.634260E+09 | 0.346091E+09 | 0.699338E+09 | 0.411311E+09 | 0.288027E+09 | 0.00 | 0.00 |
November | 0.509122E+09 | 0.469959E+09 | 0.601072E+09 | 0.376564E+09 | 0.224508E+09 | 0.00 | 0.00 |
December | 0.494672E+09 | 0.727028E+09 | 0.660521E+09 | 0.432235E+09 | 0.228286E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.797674E+10 | 0.456661E+10 | 0.924866E+10 | 0.494243E+10 | 0.430623E+10 | 0.00 | 0.00 |
Minimum of Months | 0.494672E+09 | 0.132223E+09 | 0.601072E+09 | 0.171356E+09 | 0.224508E+09 | 0.00 | 0.00 |
Maximum of Months | 0.864716E+09 | 0.748527E+09 | 0.980387E+09 | 0.661611E+09 | 0.489130E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.314251E+10 | -.270575E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -436762533.4 | 58.99 | 0.00 | 0.00 |
February | 0.291348E+10 | -.252023E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -393253682.9 | 59.00 | 0.00 | 0.00 |
March | 0.327958E+10 | -.284828E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -431298225.3 | 58.99 | 0.00 | 0.00 |
April | 0.303111E+10 | -.262638E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -404732105.1 | 58.99 | 0.00 | 0.00 |
May | 0.297485E+10 | -.258139E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -393461553.9 | 58.99 | 0.00 | 0.00 |
June | 0.275538E+10 | -.238190E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373476667.7 | 58.99 | 0.00 | 0.00 |
July | 0.264639E+10 | -.226380E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382582163.5 | 58.99 | 0.00 | 0.00 |
August | 0.265219E+10 | -.226850E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -383691805.9 | 58.99 | 0.00 | 0.00 |
September | 0.254509E+10 | -.216891E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -376178177.3 | 58.99 | 0.00 | 0.00 |
October | 0.270194E+10 | -.229376E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -408182192.1 | 59.00 | 0.00 | 0.00 |
November | 0.275426E+10 | -.234051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -413744862.9 | 58.99 | 0.00 | 0.00 |
December | 0.301748E+10 | -.258158E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -435903457.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.344143E+11 | -.295810E+11 | 8760.00 | -.483327E+10 | 58.99 | |||||
Minimum of Months | 0.254509E+10 | -.284828E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -436762533.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.327958E+10 | -.216891E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -373476667.7 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.92 | 0.67 | 24-JAN-12:09 | 185.92 | 5.85 | 0.00 | 0.00 | 150.41 | 4.45 | 0.00 | 0.00 |
February | 265.33 | 0.87 | 0.50 | 26-FEB-12:30 | 243.84 | 7.05 | 0.00 | 4.83 | 198.44 | 5.61 | 0.00 | 0.17 |
March | 254.17 | 0.85 | 0.50 | 02-MAR-11:30 | 272.95 | 6.99 | 0.00 | 16.67 | 225.33 | 5.51 | 0.00 | 5.17 |
April | 296.33 | 0.79 | 0.50 | 01-APR-10:00 | 310.46 | 7.59 | 0.00 | 43.33 | 997.96 | 6.06 | 0.00 | 64.83 |
May | 437.50 | 0.75 | 0.50 | 01-MAY-11:09 | 3099.06 | 10.08 | 0.00 | 170.83 | 1833.69 | 8.40 | 0.00 | 105.67 |
June | 401.83 | 0.75 | 0.50 | 01-JUN-10:39 | 2069.53 | 10.85 | 0.00 | 135.50 | 1990.20 | 9.12 | 0.00 | 92.67 |
July | 409.17 | 0.74 | 0.50 | 01-JUL-09:09 | 1914.85 | 10.70 | 0.00 | 137.17 | 2055.47 | 8.96 | 0.00 | 93.50 |
August | 352.83 | 0.74 | 0.50 | 01-AUG-08:30 | 404.73 | 10.03 | 0.00 | 99.67 | 1215.64 | 8.32 | 0.00 | 87.83 |
September | 344.17 | 0.81 | 0.50 | 02-SEP-11:09 | 315.34 | 8.38 | 0.00 | 41.33 | 257.91 | 6.81 | 0.00 | 12.17 |
October | 299.00 | 0.87 | 0.50 | 07-OCT-11:30 | 251.97 | 7.40 | 0.00 | 2.00 | 203.97 | 5.90 | 0.00 | 0.17 |
November | 255.50 | 0.92 | 0.75 | 01-NOV-12:09 | 187.39 | 6.04 | 0.00 | 0.00 | 151.78 | 4.65 | 0.00 | 0.00 |
December | 226.33 | 0.93 | 0.75 | 04-DEC-11:39 | 173.50 | 5.75 | 0.00 | 0.00 | 140.16 | 4.34 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.81 | 965.81 | 8.44 | 0.00 | 651.33 | 933.67 | 6.86 | 0.00 | 462.17 | ||
Minimum of Months | 226.33 | 0.74 | 0.50 | 173.50 | 5.75 | 0.00 | 0.00 | 140.16 | 4.34 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.93 | 0.75 | 3099.06 | 10.85 | 0.00 | 170.83 | 2055.47 | 9.12 | 0.00 | 105.67 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247496E+11 | 53706.77 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169761E+11 | 53706.77 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128495E+11 | 53706.77 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340193E+10 | 53706.77 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115702E+09 | 53706.77 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902438E+09 | 53706.77 | 14-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.763201E+10 | 53706.77 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.217746E+11 | 53706.77 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884019E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247496E+11 | 53706.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103470E+12 | 286596.46 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.669989E+11 | 286596.46 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.487902E+11 | 286596.46 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102956E+11 | 150845.51 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309794E+09 | 67592.69 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.467689E+10 | 91288.70 | 30-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327641E+11 | 286596.46 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.928594E+11 | 286596.46 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360165E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103470E+12 | 286596.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.998928E+10 | 36390.47 | 01-JAN-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.560021E+10 | 36390.47 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.378787E+10 | 36390.47 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.792819E+09 | 36390.47 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24661788.97 | 8544.19 | 01-MAY-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228198E+09 | 26419.88 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247647E+10 | 36390.47 | 05-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.926895E+10 | 36390.47 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321685E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.998928E+10 | 36390.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133984E+11 | 31449.95 | 01-JAN-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.828731E+10 | 31449.95 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.651367E+10 | 31449.95 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205621E+10 | 31449.95 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95088331.35 | 26842.16 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2229679.84 | 904.45 | 23-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108329E+10 | 31449.95 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.472780E+10 | 31449.95 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126635E+11 | 31449.95 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.488274E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133984E+11 | 31449.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.245816E+11 | 58580.62 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158617E+11 | 50159.66 | 01-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133824E+11 | 37370.13 | 15-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.515462E+10 | 22949.41 | 04-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.622420E+09 | 9008.84 | 08-MAY-11:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34730647.82 | 1996.84 | 02-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5727592.13 | 709.11 | 08-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 64576292.06 | 3889.92 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664591E+09 | 7614.20 | 27-SEP-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481601E+10 | 19205.22 | 29-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107016E+11 | 38548.47 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233523E+11 | 56073.45 | 24-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.992423E+11 | |||||||
Minimum of Months | 5727592.13 | 709.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245816E+11 | 58580.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 69350517.66 | 61002988.95 | 5378.47 | 23-APR-16:00 | 4712.51 | 0.00 |
May | 0.00 | 0.00 | 0.300285E+10 | 0.256180E+10 | 32821.44 | 26-MAY-06:02 | 22957.15 | 0.00 |
June | 0.00 | 0.00 | 0.794097E+10 | 0.600370E+10 | 35767.82 | 30-JUN-06:02 | 20285.21 | 0.00 |
July | 0.00 | 0.00 | 0.126009E+11 | 0.898264E+10 | 35951.97 | 30-JUL-08:62 | 18571.95 | 0.00 |
August | 0.00 | 0.00 | 0.865283E+10 | 0.613677E+10 | 34216.96 | 30-AUG-06:02 | 16742.79 | 0.00 |
September | 0.00 | 0.00 | 0.108081E+10 | 0.873023E+09 | 33397.10 | 01-SEP-06:02 | 16650.61 | 0.00 |
October | 0.00 | 0.00 | 30742989.49 | 29660601.00 | 3126.14 | 19-OCT-15:00 | 3028.80 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.333784E+11 | 0.246486E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126009E+11 | 0.898264E+10 | 35951.97 | 22957.15 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.108861E+10 | 0.974299E+09 | 48934.40 | 23-APR-16:00 | 42889.55 | 0.00 |
May | 0.00 | 0.00 | 0.221935E+11 | 0.190085E+11 | 164544.23 | 26-MAY-06:02 | 114375.82 | 0.00 |
June | 0.00 | 0.00 | 0.522785E+11 | 0.388765E+11 | 178183.83 | 25-JUN-08:62 | 97089.17 | 0.00 |
July | 0.00 | 0.00 | 0.755388E+11 | 0.525954E+11 | 181336.84 | 30-JUL-08:62 | 89919.92 | 0.00 |
August | 0.00 | 0.00 | 0.532214E+11 | 0.369892E+11 | 171640.49 | 30-AUG-06:02 | 85673.88 | 0.00 |
September | 0.00 | 0.00 | 0.101284E+11 | 0.811621E+10 | 167087.08 | 01-SEP-06:02 | 86595.58 | 0.00 |
October | 0.00 | 0.00 | 0.916504E+09 | 0.843141E+09 | 152227.18 | 02-OCT-06:02 | 111514.36 | 0.00 |
November | 0.00 | 0.00 | 835549.55 | 563678.44 | 728.99 | 21-NOV-13:20 | 490.34 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.215367E+12 | 0.157404E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.755388E+11 | 0.525954E+11 | 181336.84 | 114375.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 8312.16 | 8312.16 | 13.24 | 04-FEB-16:50 | 13.24 | 0.00 |
March | 0.00 | 0.00 | 136226.70 | 136226.70 | 70.55 | 18-MAR-13:40 | 70.55 | 0.00 |
April | 0.00 | 0.00 | 0.357761E+09 | 0.339807E+09 | 9223.35 | 23-APR-13:40 | 8186.81 | 0.00 |
May | 0.00 | 0.00 | 0.355651E+10 | 0.316109E+10 | 21511.34 | 26-MAY-06:02 | 15072.18 | 0.00 |
June | 0.00 | 0.00 | 0.755241E+10 | 0.590938E+10 | 23875.66 | 30-JUN-05:03 | 12838.16 | 0.00 |
July | 0.00 | 0.00 | 0.112530E+11 | 0.832502E+10 | 23739.77 | 30-JUL-08:62 | 11551.36 | 0.00 |
August | 0.00 | 0.00 | 0.917666E+10 | 0.673216E+10 | 22415.20 | 30-AUG-06:02 | 11022.27 | 0.00 |
September | 0.00 | 0.00 | 0.262759E+10 | 0.225144E+10 | 21818.41 | 01-SEP-06:02 | 11128.04 | 0.00 |
October | 0.00 | 0.00 | 0.592641E+09 | 0.556429E+09 | 19951.55 | 22-OCT-08:62 | 15171.19 | 0.00 |
November | 0.00 | 0.00 | 51495.66 | 48837.44 | 41.87 | 14-NOV-16:20 | 41.87 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.351168E+11 | 0.272755E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112530E+11 | 0.832502E+10 | 23875.66 | 15171.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 181.13 | 181.13 | 0.10 | 31-MAR-14:10 | 0.10 | 0.00 |
April | 0.00 | 0.00 | 0.189910E+09 | 0.175494E+09 | 6635.72 | 23-APR-14:00 | 5853.07 | 0.00 |
May | 0.00 | 0.00 | 0.226639E+10 | 0.196868E+10 | 17901.40 | 26-MAY-06:02 | 12368.68 | 0.00 |
June | 0.00 | 0.00 | 0.517332E+10 | 0.393998E+10 | 19436.59 | 30-JUN-06:02 | 11131.76 | 0.00 |
July | 0.00 | 0.00 | 0.813466E+10 | 0.583203E+10 | 19715.58 | 30-JUL-08:62 | 9638.65 | 0.00 |
August | 0.00 | 0.00 | 0.648161E+10 | 0.467448E+10 | 18655.08 | 30-AUG-06:02 | 9114.66 | 0.00 |
September | 0.00 | 0.00 | 0.173486E+10 | 0.147868E+10 | 18197.94 | 01-SEP-06:02 | 9077.13 | 0.00 |
October | 0.00 | 0.00 | 0.397059E+09 | 0.369970E+09 | 11186.48 | 22-OCT-08:62 | 8314.87 | 0.00 |
November | 0.00 | 0.00 | 1425.65 | 1414.92 | 0.25 | 17-NOV-13:30 | 0.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.243778E+11 | 0.184393E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.813466E+10 | 0.583203E+10 | 19715.58 | 12368.68 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111479E+11 | 0.92 | 7252.16 | 01-JAN-00:10 | 1.61 |
February | 0.954447E+10 | 0.87 | 7252.16 | 01-FEB-00:16 | 1.61 |
March | 0.100124E+11 | 0.83 | 7252.16 | 01-MAR-06:01 | 1.60 |
April | 0.796176E+10 | 0.68 | 7252.16 | 01-APR-05:02 | 1.60 |
May | 0.423697E+10 | 0.35 | 7252.16 | 01-MAY-05:02 | 1.60 |
June | 0.174363E+10 | 0.15 | 7252.16 | 01-JUN-07:06 | 1.59 |
July | 0.809719E+09 | 0.07 | 7252.16 | 01-JUL-07:10 | 1.58 |
August | 0.131340E+10 | 0.11 | 7252.16 | 01-AUG-11:05 | 1.58 |
September | 0.489847E+10 | 0.41 | 7252.16 | 01-SEP-07:10 | 1.57 |
October | 0.785215E+10 | 0.64 | 7252.16 | 01-OCT-07:02 | 1.59 |
November | 0.922620E+10 | 0.78 | 7252.16 | 01-NOV-05:02 | 1.59 |
December | 0.110719E+11 | 0.91 | 7252.16 | 01-DEC-04:56 | 1.60 |
Annual Sum or Average | 0.798189E+11 | 0.56 | |||
Minimum of Months | 0.809719E+09 | 0.07 | 7252.16 | 1.57 | |
Maximum of Months | 0.111479E+11 | 0.92 | 7252.16 | 1.61 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.314362E+10 | 0.61 | 1925.48 | 04-JAN-19:20 | 0.92 |
February | 0.283081E+10 | 0.58 | 1925.48 | 27-FEB-09:40 | 0.92 |
March | 0.315376E+10 | 0.57 | 1925.48 | 16-MAR-06:04 | 0.92 |
April | 0.301651E+10 | 0.55 | 1925.48 | 06-APR-15:10 | 0.92 |
May | 0.311234E+10 | 0.55 | 1925.48 | 11-MAY-19:17 | 0.91 |
June | 0.303609E+10 | 0.55 | 1925.48 | 02-JUN-17:47 | 0.91 |
July | 0.309155E+10 | 0.54 | 1925.48 | 02-JUL-14:10 | 0.91 |
August | 0.314007E+10 | 0.55 | 1925.48 | 03-AUG-19:50 | 0.90 |
September | 0.301530E+10 | 0.55 | 1925.48 | 11-SEP-16:23 | 0.91 |
October | 0.308462E+10 | 0.55 | 1925.48 | 13-OCT-09:07 | 0.92 |
November | 0.297818E+10 | 0.55 | 1925.48 | 03-NOV-17:33 | 0.92 |
December | 0.313434E+10 | 0.59 | 1925.48 | 14-DEC-10:50 | 0.92 |
Annual Sum or Average | 0.367372E+11 | 0.56 | |||
Minimum of Months | 0.283081E+10 | 0.54 | 1925.48 | 0.90 | |
Maximum of Months | 0.315376E+10 | 0.61 | 1925.48 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.230550E+11 | 0.95 | 14380.33 | 02-JAN-06:14 | 1.58 |
February | 0.209148E+11 | 0.95 | 14380.33 | 03-FEB-16:30 | 1.58 |
March | 0.234514E+11 | 0.96 | 14380.33 | 01-MAR-08:00 | 1.58 |
April | 0.225196E+11 | 0.95 | 14380.33 | 01-APR-19:53 | 1.57 |
May | 0.232444E+11 | 0.95 | 14380.33 | 01-MAY-08:00 | 1.58 |
June | 0.226749E+11 | 0.95 | 14380.33 | 02-JUN-18:52 | 1.57 |
July | 0.230891E+11 | 0.93 | 14380.33 | 06-JUL-08:40 | 1.56 |
August | 0.234514E+11 | 0.95 | 14380.33 | 04-AUG-05:40 | 1.55 |
September | 0.225196E+11 | 0.94 | 14380.33 | 01-SEP-19:02 | 1.55 |
October | 0.230373E+11 | 0.94 | 14380.33 | 01-OCT-16:50 | 1.57 |
November | 0.222090E+11 | 0.94 | 14380.33 | 01-NOV-14:10 | 1.56 |
December | 0.230980E+11 | 0.95 | 14380.33 | 04-DEC-06:03 | 1.58 |
Annual Sum or Average | 0.273264E+12 | 0.95 | |||
Minimum of Months | 0.209148E+11 | 0.93 | 14380.33 | 1.55 | |
Maximum of Months | 0.234514E+11 | 0.96 | 14380.33 | 1.58 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207640E+10 | 0.61 | 1285.43 | 06-JAN-11:50 | 0.95 |
February | 0.187687E+10 | 0.59 | 1285.43 | 01-FEB-13:30 | 0.95 |
March | 0.209874E+10 | 0.59 | 1285.43 | 01-MAR-12:08 | 0.95 |
April | 0.201298E+10 | 0.57 | 1285.43 | 02-APR-07:40 | 0.95 |
May | 0.207777E+10 | 0.57 | 1285.43 | 05-MAY-09:25 | 0.95 |
June | 0.202687E+10 | 0.57 | 1285.43 | 02-JUN-08:48 | 0.95 |
July | 0.206389E+10 | 0.56 | 1285.43 | 05-JUL-08:00 | 0.93 |
August | 0.209628E+10 | 0.57 | 1285.43 | 02-AUG-10:00 | 0.94 |
September | 0.201298E+10 | 0.57 | 1285.43 | 01-SEP-19:02 | 0.94 |
October | 0.205926E+10 | 0.57 | 1285.43 | 02-OCT-16:20 | 0.94 |
November | 0.198662E+10 | 0.57 | 1285.43 | 03-NOV-07:23 | 0.95 |
December | 0.207825E+10 | 0.61 | 1285.43 | 01-DEC-06:25 | 0.95 |
Annual Sum or Average | 0.244669E+11 | 0.58 | |||
Minimum of Months | 0.187687E+10 | 0.56 | 1285.43 | 0.93 | |
Maximum of Months | 0.209874E+10 | 0.61 | 1285.43 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166025E+10 | 0.64 | 1021.61 | 18-JAN-18:17 | 0.95 |
February | 0.149662E+10 | 0.60 | 1021.61 | 02-FEB-07:22 | 0.95 |
March | 0.167078E+10 | 0.59 | 1021.61 | 03-MAR-20:08 | 0.95 |
April | 0.160025E+10 | 0.57 | 1021.61 | 01-APR-09:42 | 0.95 |
May | 0.165133E+10 | 0.57 | 1021.61 | 02-MAY-08:20 | 0.95 |
June | 0.161088E+10 | 0.57 | 1021.61 | 01-JUN-18:30 | 0.95 |
July | 0.164030E+10 | 0.56 | 1021.61 | 07-JUL-07:14 | 0.94 |
August | 0.166604E+10 | 0.57 | 1021.61 | 01-AUG-10:30 | 0.94 |
September | 0.159984E+10 | 0.57 | 1021.61 | 04-SEP-09:00 | 0.94 |
October | 0.163662E+10 | 0.57 | 1021.61 | 01-OCT-12:10 | 0.95 |
November | 0.157986E+10 | 0.57 | 1021.61 | 02-NOV-10:50 | 0.95 |
December | 0.166041E+10 | 0.63 | 1021.61 | 02-DEC-06:10 | 0.95 |
Annual Sum or Average | 0.194732E+11 | 0.58 | |||
Minimum of Months | 0.149662E+10 | 0.56 | 1021.61 | 0.94 | |
Maximum of Months | 0.167078E+10 | 0.64 | 1021.61 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.87 | 0.00 |
February | 2.54 | 0.00 |
March | 2.06 | 0.00 |
April | 0.37 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.06 | 0.00 |
November | 0.87 | 0.00 |
December | 2.85 | 0.00 |
Annual Sum or Average | 11.63 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.87 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 1.05 | 25.84 |
May | 0.78 | 25.84 |
June | 0.42 | 20.67 |
July | 0.87 | 24.61 |
August | 1.04 | 24.81 |
September | 0.33 | 25.84 |
October | 0.96 | 25.84 |
November | 0.18 | 25.84 |
December | 0.03 | 0.00 |
Annual Sum or Average | 5.67 | 24.93 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.05 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.50 | 0.00 |
February | 0.37 | 0.00 |
March | 0.26 | 0.00 |
April | 0.70 | 2.44 |
May | 0.88 | 2.05 |
June | 0.89 | 0.00 |
July | 0.99 | 0.00 |
August | 0.57 | 0.00 |
September | 0.21 | 0.00 |
October | 0.32 | 2.01 |
November | 0.42 | 0.90 |
December | 1.41 | 0.00 |
Annual Sum or Average | 8.50 | 0.53 |
Minimum of Months | 0.21 | 0.00 |
Maximum of Months | 1.50 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.65 | 0.00 |
February | 1.09 | 0.00 |
March | 1.25 | 0.00 |
April | 0.74 | 1.37 |
May | 0.58 | 2.44 |
June | 0.42 | 0.97 |
July | 0.29 | 1.39 |
August | 0.58 | 1.91 |
September | 0.54 | 1.87 |
October | 0.52 | 1.91 |
November | 0.89 | 0.00 |
December | 3.08 | 0.00 |
Annual Sum or Average | 12.64 | 0.50 |
Minimum of Months | 0.29 | 0.00 |
Maximum of Months | 3.08 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 33.60 | 0.00 |
February | 34.41 | 0.00 |
March | 37.41 | 0.00 |
April | 66.97 | 0.00 |
May | 68.32 | 0.00 |
June | 20.83 | 0.00 |
July | 16.60 | 0.00 |
August | 23.77 | 0.00 |
September | 79.55 | 0.00 |
October | 84.29 | 0.00 |
November | 48.22 | 0.00 |
December | 32.87 | 0.00 |
Annual Sum or Average | 546.84 | 0.00 |
Minimum of Months | 16.60 | 0.00 |
Maximum of Months | 84.29 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.314362E+10 | 0.309370E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.283081E+10 | 0.212201E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.315376E+10 | 0.160619E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.303672E+10 | 0.425242E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.393725E+10 | 0.144627E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.516415E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.640708E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.540452E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.330372E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.309322E+10 | 0.112805E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.297818E+10 | 0.954002E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.313434E+10 | 0.272182E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.455874E+11 | 0.110502E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.283081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.640708E+10 | 0.309370E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.230550E+11 | 0.129337E+12 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.209148E+11 | 0.837486E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.234514E+11 | 0.609878E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.228574E+11 | 0.128695E+11 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.299138E+11 | 0.387243E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.380016E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.449567E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.388532E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.255057E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.233123E+11 | 0.584612E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.222092E+11 | 0.409552E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.230980E+11 | 0.116074E+12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.336129E+12 | 0.450206E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.209148E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.449567E+11 | 0.129337E+12 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.207640E+10 | 0.124866E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.187687E+10 | 0.700026E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.209878E+10 | 0.473484E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.210918E+10 | 0.991023E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.301912E+10 | 30827236.21 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.399454E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.494908E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.441111E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.268655E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.221140E+10 | 0.285248E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.198663E+10 | 0.309559E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.207825E+10 | 0.115862E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.334979E+11 | 0.402106E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.187687E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.494908E+10 | 0.124866E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.166025E+10 | 0.167480E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149662E+10 | 0.103591E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167078E+10 | 0.814208E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.165056E+10 | 0.257026E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.224293E+10 | 0.118860E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.293435E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.368471E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.326926E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.203462E+10 | 2787099.80 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.173630E+10 | 0.135411E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.157986E+10 | 0.590976E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166041E+10 | 0.158293E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.256207E+11 | 0.610343E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149662E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.368471E+10 | 0.167480E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.314362E+10 | 0.00 | 0.247496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283081E+10 | 0.00 | 0.169761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315376E+10 | 0.00 | 0.128495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301651E+10 | 69350517.66 | 0.340193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.311234E+10 | 0.300285E+10 | 0.115702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303609E+10 | 0.794097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.309155E+10 | 0.126009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314007E+10 | 0.865283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301530E+10 | 0.108081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.308462E+10 | 30742989.49 | 0.902438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297818E+10 | 0.00 | 0.763201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313434E+10 | 0.00 | 0.217746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367372E+11 | 0.333784E+11 | 0.884019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315376E+10 | 0.126009E+11 | 0.247496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.230550E+11 | 0.00 | 0.103470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209148E+11 | 0.00 | 0.669989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234514E+11 | 0.00 | 0.487902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225196E+11 | 0.108861E+10 | 0.102956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232444E+11 | 0.221935E+11 | 0.309794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.226749E+11 | 0.522785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.230891E+11 | 0.755388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.234514E+11 | 0.532214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.225196E+11 | 0.101284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230373E+11 | 0.916504E+09 | 0.467689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222090E+11 | 835549.55 | 0.327641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230980E+11 | 0.00 | 0.928594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273264E+12 | 0.215367E+12 | 0.360165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.209148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234514E+11 | 0.755388E+11 | 0.103470E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.207640E+10 | 0.00 | 0.998928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187687E+10 | 8312.16 | 0.560021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209874E+10 | 136226.70 | 0.378787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201298E+10 | 0.357761E+09 | 0.792819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207777E+10 | 0.355651E+10 | 24661788.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202687E+10 | 0.755241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206389E+10 | 0.112530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209628E+10 | 0.917666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.201298E+10 | 0.262759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205926E+10 | 0.592641E+09 | 0.228198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198662E+10 | 51495.66 | 0.247647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207825E+10 | 0.00 | 0.926895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244669E+11 | 0.351168E+11 | 0.321685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209874E+10 | 0.112530E+11 | 0.998928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166025E+10 | 0.00 | 0.133984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149662E+10 | 0.00 | 0.828731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167078E+10 | 181.13 | 0.651367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160025E+10 | 0.189910E+09 | 0.205621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165133E+10 | 0.226639E+10 | 95088331.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161088E+10 | 0.517332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164030E+10 | 0.813466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166604E+10 | 0.648161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159984E+10 | 0.173486E+10 | 2229679.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163662E+10 | 0.397059E+09 | 0.108329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157986E+10 | 1425.65 | 0.472780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166041E+10 | 0.00 | 0.126635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194732E+11 | 0.243778E+11 | 0.488274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167078E+10 | 0.813466E+10 | 0.133984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.314362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301651E+10 | 0.00 | 0.00 | 0.00 | 20210441.20 | 0.00 | 0.425242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.311234E+10 | 0.00 | 0.00 | 0.00 | 0.824905E+09 | 0.00 | 0.144627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.303609E+10 | 0.00 | 0.00 | 0.00 | 0.212806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.309155E+10 | 0.00 | 0.00 | 0.00 | 0.331553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314007E+10 | 0.00 | 0.00 | 0.00 | 0.226445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.301530E+10 | 0.00 | 0.00 | 0.00 | 0.288419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.308462E+10 | 0.00 | 0.00 | 0.00 | 8608423.31 | 0.00 | 0.112805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.297818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367372E+11 | 0.00 | 0.00 | 0.00 | 0.885019E+10 | 0.00 | 0.110502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.283081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315376E+10 | 0.00 | 0.00 | 0.00 | 0.331553E+10 | 0.00 | 0.309370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.230550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.209148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225196E+11 | 0.00 | 0.00 | 0.00 | 0.337853E+09 | 0.00 | 0.128695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232444E+11 | 0.00 | 0.00 | 0.00 | 0.666948E+10 | 0.00 | 0.387243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.226749E+11 | 0.00 | 0.00 | 0.00 | 0.153267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.230891E+11 | 0.00 | 0.00 | 0.00 | 0.218677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.234514E+11 | 0.00 | 0.00 | 0.00 | 0.154018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.225196E+11 | 0.00 | 0.00 | 0.00 | 0.298614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230373E+11 | 0.00 | 0.00 | 0.00 | 0.274994E+09 | 0.00 | 0.584612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222090E+11 | 0.00 | 0.00 | 0.00 | 263988.41 | 0.00 | 0.409552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273264E+12 | 0.00 | 0.00 | 0.00 | 0.628649E+11 | 0.00 | 0.450206E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.209148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.234514E+11 | 0.00 | 0.00 | 0.00 | 0.218677E+11 | 0.00 | 0.129337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.207640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187687E+10 | 0.00 | 0.00 | 0.00 | 2345.91 | 0.00 | 0.700026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209874E+10 | 0.00 | 0.00 | 0.00 | 38423.54 | 0.00 | 0.473484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201298E+10 | 0.00 | 0.00 | 0.00 | 96192140.10 | 0.00 | 0.991023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207777E+10 | 0.00 | 0.00 | 0.00 | 0.941345E+09 | 0.00 | 30827236.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202687E+10 | 0.00 | 0.00 | 0.00 | 0.196768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.206389E+10 | 0.00 | 0.00 | 0.00 | 0.288519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209628E+10 | 0.00 | 0.00 | 0.00 | 0.231483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.201298E+10 | 0.00 | 0.00 | 0.00 | 0.673570E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205926E+10 | 0.00 | 0.00 | 0.00 | 0.152138E+09 | 0.00 | 0.285248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198662E+10 | 0.00 | 0.00 | 0.00 | 14547.63 | 0.00 | 0.309559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244669E+11 | 0.00 | 0.00 | 0.00 | 0.903100E+10 | 0.00 | 0.402106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.187687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.209874E+10 | 0.00 | 0.00 | 0.00 | 0.288519E+10 | 0.00 | 0.124866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.166025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167078E+10 | 0.00 | 0.00 | 0.00 | 49.66 | 0.00 | 0.814208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160025E+10 | 0.00 | 0.00 | 0.00 | 50310755.10 | 0.00 | 0.257026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165133E+10 | 0.00 | 0.00 | 0.00 | 0.591600E+09 | 0.00 | 0.118860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161088E+10 | 0.00 | 0.00 | 0.00 | 0.132348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164030E+10 | 0.00 | 0.00 | 0.00 | 0.204442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166604E+10 | 0.00 | 0.00 | 0.00 | 0.160321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159984E+10 | 0.00 | 0.00 | 0.00 | 0.434780E+09 | 0.00 | 2787099.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163662E+10 | 0.00 | 0.00 | 0.00 | 99680350.57 | 0.00 | 0.135411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157986E+10 | 0.00 | 0.00 | 0.00 | 390.92 | 0.00 | 0.590976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194732E+11 | 0.00 | 0.00 | 0.00 | 0.614748E+10 | 0.00 | 0.610343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.149662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167078E+10 | 0.00 | 0.00 | 0.00 | 0.204442E+10 | 0.00 | 0.167480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161001E+11 | 0.00 | 0.00 | 0.20 |
February | 0.685773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116551E+11 | 0.00 | 0.00 | 0.20 |
March | 0.252329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926991E+10 | 0.00 | 0.00 | 0.21 |
April | 0.466808E+10 | 10183141.93 | 0.00 | 450613.67 | 4531645.64 | 0.241773E+10 | 0.657164E+09 | 0.00 | 0.22 |
May | 0.167023E+10 | 97412435.74 | 0.00 | 8623510.45 | 0.00 | 84388381.11 | 0.502002E+10 | 0.00 | 0.47 |
June | 0.290362E+09 | 0.118648E+10 | 0.00 | 12005573.40 | 4761775.06 | 0.00 | 0.539480E+10 | 0.00 | 0.66 |
July | 58660337.82 | 0.194539E+10 | 0.00 | 13220803.97 | 7569293.30 | 0.00 | 0.405630E+10 | 0.00 | 0.65 |
August | 0.116379E+09 | 0.885176E+09 | 0.00 | 17975634.58 | 40171.23 | 0.00 | 0.617977E+10 | 0.00 | 0.77 |
September | 0.115188E+10 | 26440584.54 | 0.00 | 16369438.07 | 0.00 | 0.00 | 0.830254E+10 | 0.00 | 0.55 |
October | 0.569548E+10 | 0.00 | 0.00 | 2413821.55 | 0.00 | 0.547486E+09 | 0.219045E+10 | 0.00 | 0.25 |
November | 0.422185E+10 | 0.00 | 0.00 | 326.49 | 0.00 | 0.548781E+10 | 8339648.75 | 0.00 | 0.20 |
December | 0.459722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148861E+11 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.216591E+11 | 0.415108E+10 | 0.00 | 71059722.19 | 16902885.23 | 0.604485E+11 | 0.318094E+11 | 0.00 | 0.38 |
Minimum of Months | 58660337.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.569548E+10 | 0.194539E+10 | 0.00 | 17975634.58 | 7569293.30 | 0.161001E+11 | 0.830254E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.697779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583347E+11 | 0.00 | 0.00 | 0.39 |
February | 0.662672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310048E+11 | 0.00 | 0.00 | 0.39 |
March | 0.762975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158976E+11 | 0.00 | 0.00 | 0.40 |
April | 0.465744E+11 | 92643801.52 | 0.00 | 15413473.60 | 0.00 | 0.276215E+10 | 0.129667E+11 | 0.00 | 0.46 |
May | 0.112882E+11 | 0.129299E+10 | 0.00 | 70454108.76 | 0.00 | 47098066.28 | 0.338333E+11 | 0.00 | 0.71 |
June | 0.162566E+10 | 0.962746E+10 | 0.00 | 80134570.52 | 54814589.91 | 0.00 | 0.288706E+11 | 0.00 | 0.85 |
July | 0.103857E+10 | 0.155209E+11 | 0.00 | 66782200.85 | 49517574.44 | 0.00 | 0.182612E+11 | 0.00 | 0.82 |
August | 0.161903E+10 | 0.713749E+10 | 0.00 | 92720543.18 | 3501566.48 | 0.00 | 0.295010E+11 | 0.00 | 0.92 |
September | 0.923387E+10 | 0.271986E+09 | 0.00 | 0.100934E+09 | 0.00 | 0.00 | 0.464919E+11 | 0.00 | 0.74 |
October | 0.463652E+11 | 0.00 | 0.00 | 19696746.27 | 0.00 | 0.337507E+09 | 0.155166E+11 | 0.00 | 0.46 |
November | 0.646507E+11 | 0.00 | 0.00 | 575879.97 | 0.00 | 0.105668E+11 | 0.959526E+09 | 0.00 | 0.40 |
December | 0.721333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490744E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.466872E+12 | 0.339435E+11 | 0.00 | 0.446712E+09 | 0.107834E+09 | 0.168025E+12 | 0.186401E+12 | 0.00 | 0.58 |
Minimum of Months | 0.103857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.762975E+11 | 0.155209E+11 | 0.00 | 0.100934E+09 | 54814589.91 | 0.583347E+11 | 0.464919E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.740019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461831E+10 | 0.00 | 0.00 | 0.39 |
February | 0.638926E+10 | 0.00 | 0.00 | 478595.73 | 0.00 | 0.237137E+10 | 0.520299E+09 | 0.00 | 0.40 |
March | 0.631158E+10 | 0.00 | 0.00 | 1100087.51 | 0.00 | 0.157726E+10 | 0.106108E+10 | 0.00 | 0.41 |
April | 0.324292E+10 | 11291533.20 | 0.00 | 6764485.95 | 0.00 | 0.356415E+09 | 0.355939E+10 | 0.00 | 0.63 |
May | 0.620084E+09 | 0.161361E+09 | 0.00 | 14312743.51 | 0.00 | 17412681.61 | 0.523827E+10 | 0.00 | 1.05 |
June | 0.101061E+09 | 0.113367E+10 | 0.00 | 12853610.53 | 403542.56 | 0.00 | 0.383450E+10 | 0.00 | 1.24 |
July | 58393676.14 | 0.188662E+10 | 0.00 | 11199883.70 | 146517.45 | 0.00 | 0.249117E+10 | 0.00 | 1.17 |
August | 99313244.41 | 0.108070E+10 | 0.00 | 16399702.90 | 0.00 | 0.00 | 0.394475E+10 | 0.00 | 1.40 |
September | 0.396562E+09 | 51007273.86 | 0.00 | 23985887.03 | 0.00 | 0.00 | 0.737992E+10 | 0.00 | 1.20 |
October | 0.287106E+10 | 0.00 | 0.00 | 11422860.66 | 0.00 | 67399203.50 | 0.474400E+10 | 0.00 | 0.66 |
November | 0.522434E+10 | 0.00 | 0.00 | 1598164.98 | 0.00 | 0.109915E+10 | 0.124000E+10 | 0.00 | 0.42 |
December | 0.691371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445006E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.396285E+11 | 0.432465E+10 | 0.00 | 0.100116E+09 | 550060.01 | 0.145574E+11 | 0.340134E+11 | 0.00 | 0.78 |
Minimum of Months | 58393676.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.740019E+10 | 0.188662E+10 | 0.00 | 23985887.03 | 403542.56 | 0.461831E+10 | 0.737992E+10 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879074E+10 | 0.00 | 0.00 | 0.39 |
February | 0.401105E+10 | 0.00 | 0.00 | 22827.43 | 0.00 | 0.509796E+10 | 35438428.57 | 0.00 | 0.39 |
March | 0.469387E+10 | 0.00 | 0.00 | 39740.46 | 0.00 | 0.393595E+10 | 49787281.16 | 0.00 | 0.40 |
April | 0.340812E+10 | 10372567.45 | 0.00 | 2276405.75 | 0.00 | 0.111899E+10 | 0.145193E+10 | 0.00 | 0.50 |
May | 0.135482E+10 | 0.135327E+09 | 0.00 | 5611690.34 | 0.00 | 51339054.20 | 0.268915E+10 | 0.00 | 0.75 |
June | 0.324021E+09 | 0.955700E+09 | 0.00 | 6496743.55 | 2271679.57 | 0.00 | 0.252088E+10 | 0.00 | 0.92 |
July | 95760397.53 | 0.159002E+10 | 0.00 | 7197332.10 | 2533632.96 | 0.00 | 0.186989E+10 | 0.00 | 0.92 |
August | 0.130642E+09 | 0.854113E+09 | 0.00 | 10371329.06 | 7903.96 | 0.00 | 0.288312E+10 | 0.00 | 1.05 |
September | 0.113401E+10 | 42705792.29 | 0.00 | 12374928.70 | 0.00 | 0.00 | 0.445496E+10 | 0.00 | 0.86 |
October | 0.385172E+10 | 0.00 | 0.00 | 4642015.00 | 0.00 | 0.439587E+09 | 0.189376E+10 | 0.00 | 0.52 |
November | 0.409601E+10 | 0.00 | 0.00 | 125441.10 | 0.00 | 0.288779E+10 | 0.158361E+09 | 0.00 | 0.39 |
December | 0.269086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.868160E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.290291E+11 | 0.358824E+10 | 0.00 | 49158453.48 | 4813216.49 | 0.310039E+11 | 0.180073E+11 | 0.00 | 0.63 |
Minimum of Months | 95760397.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.469387E+10 | 0.159002E+10 | 0.00 | 12374928.70 | 2533632.96 | 0.879074E+10 | 0.445496E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |