Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2020-06-03 19:12:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1586.64 | 691.65 | 691.65 |
Net Site Energy | 1586.64 | 691.65 | 691.65 |
Total Source Energy | 3733.87 | 1627.67 | 1627.67 |
Net Source Energy | 3733.87 | 1627.67 | 1627.67 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 519.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 392.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 222.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 17.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 100.71 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 966.86 | 619.78 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 519.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 79.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 392.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 222.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 17.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 100.71 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 197.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 131.60 | 270.18 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 92.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 421.47 | 270.18 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 197.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 131.60 | 270.18 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 92.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 421.47 | 270.18 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 966.855 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 966.855 | 100.00 |
Total On-Site and Utility Electric Sources | 966.855 | 100.00 |
Total Electricity End Uses | 966.855 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 20.08 | 4.08 |
Air to Air Heat Recovery for Heating | 471.83 | 95.92 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 491.91 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2343.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 6.69 |
Skylight-Roof Ratio [%] | 0.29 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 6.8133 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 15.4032 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.4032 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.4032 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 8.7188 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 13.9457 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 13.9457 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-15:00 | 09-JAN-07:10 | - | - | - | 30-MAR-11:09 |
Heating | 0.00 | 312863.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36316.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 27218.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8191.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4589.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 83902.94 | 317452.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 312863.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36316.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 27218.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8191.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4589.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 562.68 | 0.00 | 0.00 | 0.00 |
Cooling | 252.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1242.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 189.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 703.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 55.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 109.17 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3062.03 | 671.84 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 245.28 | 0.00 | 0.00 | 0.00 |
Cooling | 110.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 541.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 82.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 306.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 24.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.59 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1334.80 | 292.87 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 245.28 | 0.00 | 0.00 | 0.00 |
Cooling | 110.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 541.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 82.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 306.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 24.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 47.59 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1334.80 | 292.87 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.72 |
CORE_RETAIL DIRECT AIR | 7.46 |
POINT_OF_SALE DIRECT AIR | 1.12 |
FRONT_RETAIL DIRECT AIR | 0.905679 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 3.89 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 3.89 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 87189.36 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 52371.40 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 282567.26 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 35879.57 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 31074.06 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.72 | 1.72 | 1.72 | 1.72 | 1.75 | 1.75 | 1.00 | 0.982046 | 1.75 |
PSZ-AC:2 | 7.46 | 7.46 | 7.46 | 7.46 | 7.61 | 7.61 | 1.00 | 0.979581 | 7.61 |
PSZ-AC:3 | 1.12 | 1.12 | 1.12 | 1.12 | 1.14 | 1.14 | 1.00 | 0.983034 | 1.14 |
PSZ-AC:4 | 0.905679 | 0.905679 | 0.905679 | 0.905679 | 0.905679 | 0.905679 | 1.00 | 1.00 | 0.905679 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.75 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.61 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.14 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.905679 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.75 | 1.75 | 1.75 | 1.15 | 31813.10 | 52371.40 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.61 | 7.61 | 7.61 | 5.02 | 158521.62 | 282567.26 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.14 | 1.14 | 1.14 | 0.754232 | 20927.23 | 35879.57 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.905679 | 0.905679 | 0.905679 | 0.905679 | 17388.73 | 31074.06 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.75 | 0.873290 | 1.16 | 29601.86 | 31813.10 | 15906.55 | 15906.55 | 0.765129 | 0.765130 | 0.765130 | 0.765130 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.61 | 3.81 | 5.07 | 149047.22 | 158521.62 | 79260.81 | 79260.81 | 0.723232 | 0.723230 | 0.723230 | 0.723230 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.14 | 0.571390 | 0.761853 | 19459.40 | 20927.23 | 10463.61 | 10463.61 | 0.763340 | 0.763340 | 0.763340 | 0.763340 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.905680 | 0.452840 | 0.603787 | 16238.38 | 17388.73 | 8694.36 | 8694.36 | 0.747985 | 0.747980 | 0.747980 | 0.747980 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.75 | 1868.92 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.61 | 12823.62 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.14 | 1265.23 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.905679 | 1002.73 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PSZ-AC:2 OA HEAT RECOVERY | 1.89 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R2C4 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C3 | SKYLIGHTS_R1C3 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C2 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 65 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 6.69 | 10 | 14 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 6.813 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.883 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 36.923 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 8.719 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.719 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2588.290 | 6.813 | 42.195 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2588.290 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 24652.487 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24652.487 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2322.950 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.950 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2322.950 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.950 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 104.625 | 8.719 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 104.625 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4290 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1269 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.2543E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1462 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1462 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.2394 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.163 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.805 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 39.25 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.764 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.764 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.101 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 9 | 0.21485751E-14 | -0.22894401E-15 | -0.17283669E-09 | -0.31350098E-16 |
25 | 8 | 0.25115787E-07 | 0.58773152E-13 | 0.41104347E-03 | -0.28557513E-09 |
26 | 7 | -0.13231082E-01 | 0.29616277E-08 | -0.24509747E-01 | 0.15044224E-03 |
27 | 6 | 0.43223401 | 0.10185882E-05 | 0.49492235 | -0.50646574E-02 |
28 | 5 | -5.4528708 | 0.37659386E-04 | -4.6163278 | 0.66436381E-01 |
29 | 4 | 34.162830 | 0.30532126E-03 | 22.123982 | -0.43752457 |
30 | 3 | -113.69342 | 0.66011806E-03 | -56.975280 | 1.5508408 |
31 | 2 | 199.57555 | 0.36866733E-03 | 79.115267 | -2.9395356 |
32 | 1 | -172.06709 | 0.39096546E-04 | -55.617513 | 2.7614060 |
33 | 0 | 57.057407 | 0.22087022E-06 | 15.500460 | |
34 | 7 | -0.33516880E-08 | -0.26917848E-14 | 0.21730031E-14 | -0.48381574E-16 |
35 | 6 | 0.36965798E-05 | 0.24265975E-08 | 0.31955345E-02 | -0.26806821E-04 |
36 | 5 | -0.25758771E-03 | 0.14341651E-05 | -0.22404650 | 0.19589918E-02 |
37 | 4 | 0.58712639E-02 | 0.65218313E-04 | 4.8349071 | -0.45316519E-01 |
38 | 3 | -0.51388992E-01 | 0.51813976E-03 | -38.051701 | 0.39898850 |
39 | 2 | 0.18223563 | 0.86130223E-03 | 116.54289 | -1.4187277 |
40 | 1 | -0.26287813 | 0.26208477E-03 | -143.94200 | 2.0496102 |
41 | 0 | 0.12812867 | 0.63668310E-05 | 60.838472 | |
42 | 7 | -0.16899007E-07 | 0.12833127E-13 | -0.13150102E-13 | 0.20583092E-15 |
43 | 6 | 0.19364730E-05 | 0.54235158E-09 | 0.32034335E-02 | -0.26873085E-04 |
44 | 5 | -0.79812125E-04 | 0.30470087E-06 | -0.22449475 | 0.19629486E-02 |
45 | 4 | 0.14364157E-02 | 0.13490553E-04 | 4.8423596 | -0.45388170E-01 |
46 | 3 | -0.11321972E-01 | 0.10487769E-03 | -38.093732 | 0.39945320 |
47 | 2 | 0.38353828E-01 | 0.17071033E-03 | 116.62460 | -1.4198209 |
48 | 1 | -0.54148476E-01 | 0.50633929E-04 | -143.99007 | 2.0504003 |
49 | 0 | 0.26099293E-01 | 0.11774431E-05 | 60.838472 | |
50 | 7 | -0.29032744E-08 | -0.17639877E-14 | 0.20832037E-14 | -0.49045170E-16 |
51 | 6 | 0.41946269E-05 | 0.27953210E-08 | 0.31940319E-02 | -0.26794216E-04 |
52 | 5 | -0.29554009E-03 | 0.16532769E-05 | -0.22396112 | 0.19582382E-02 |
53 | 4 | 0.67585570E-02 | 0.75205421E-04 | 4.8334853 | -0.45302851E-01 |
54 | 3 | -0.59226730E-01 | 0.59766051E-03 | -38.043670 | 0.39889973 |
55 | 2 | 0.21013145 | 0.99372709E-03 | 116.52726 | -1.4185186 |
56 | 1 | -0.30318440 | 0.30250693E-03 | -143.93280 | 2.0494590 |
57 | 0 | 0.14779056 | 0.73395870E-05 | 60.838472 | |
58 | 7 | -0.29032744E-08 | -0.17639877E-14 | 0.20832037E-14 | -0.49045170E-16 |
59 | 6 | 0.41946269E-05 | 0.27953210E-08 | 0.31940319E-02 | -0.26794216E-04 |
60 | 5 | -0.29554009E-03 | 0.16532769E-05 | -0.22396112 | 0.19582382E-02 |
61 | 4 | 0.67585570E-02 | 0.75205421E-04 | 4.8334853 | -0.45302851E-01 |
62 | 3 | -0.59226730E-01 | 0.59766051E-03 | -38.043670 | 0.39889973 |
63 | 2 | 0.21013145 | 0.99372709E-03 | 116.52726 | -1.4185186 |
64 | 1 | -0.30318440 | 0.30250693E-03 | -143.93280 | 2.0494590 |
65 | 0 | 0.14779056 | 0.73395870E-05 | 60.838472 | |
66 | 7 | -0.17562435E-08 | -0.39729445E-15 | 0.58168389E-14 | -0.79484401E-16 |
67 | 6 | 0.66980234E-05 | 0.45884094E-08 | 0.31867327E-02 | -0.26732985E-04 |
68 | 5 | -0.48215914E-03 | 0.27191141E-05 | -0.22354626 | 0.19545764E-02 |
69 | 4 | 0.11093948E-01 | 0.12377744E-03 | 4.8265758 | -0.45236432E-01 |
70 | 3 | -0.97430383E-01 | 0.98443929E-03 | -38.004639 | 0.39846831 |
71 | 2 | 0.34596841 | 0.16377189E-02 | 116.45130 | -1.4175025 |
72 | 1 | -0.49936185 | 0.49916259E-03 | -143.88809 | 2.0487240 |
73 | 0 | 0.24346518 | 0.12028251E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.29_SHGC_0.45 | 30 | 1 | VerySmooth | 1.647 | 0.445 | 0.367 | 0.451 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 31 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 8 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
31 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
32 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
33 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
34 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 2 | No | No |
39 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 1.87E-002 | 0 | No | No |
40 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
42 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
43 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
44 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
45 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
46 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
47 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
48 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
49 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
50 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
52 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
54 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
58 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
59 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
60 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
62 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
63 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
64 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
65 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 19461.81358 | 23354.17630 | 1.42935 | 1.71522 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 26177.00127 | 31412.40153 | 1.15284 | 1.38341 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 84523.54355 | 101428.25226 | 6.21360 | 7.45632 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 61362.95381 | 73635.54457 | 2.66977 | 3.20373 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12562.50652 | 15075.00783 | 0.93616 | 1.12339 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 12897.11305 | 15476.53566 | 0.57024 | 0.68429 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 9855.86100 | 11827.03320 | 0.75473 | 0.90568 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27032E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 12896.36971 | 15475.64365 | 0.57021 | 0.68425 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10000 | 1.27032E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 72574.38468 | 87089.26161 | 3.24541 | 3.89449 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -32.70000 | 1.83376E-004 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 21864.30 | 1.74658 | 1.74658 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 45024.51 | 1.38341 | 1.38341 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 100486.13 | 7.61175 | 7.61175 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 188420.44 | 3.20373 | 3.20373 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 15904.67 | 1.14278 | 1.14278 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 26187.36 | 0.68429 | 0.68429 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 12868.87 | 0.90568 | 0.90568 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 26186.47 | 0.68425 | 0.68425 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.71522 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.45632 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.12339 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.90568 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.89449 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 3.89449 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 87189.36320 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.71522 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.71522 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.71522 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.71522 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.74658 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.74658 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.98205 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.45632 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.45632 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.45632 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.45632 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.61175 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.61175 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97958 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.12339 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.12339 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.12339 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.12339 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14278 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14278 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 0.98303 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.90568 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.90568 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.90568 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.90568 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.90568 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.90568 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.74658 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.61175 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.14278 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.90568 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.74658 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.74658 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.74658 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.74658 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.15274 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.74658 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.87329 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.16439 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 29601.86115 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 31813.10000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 15906.55000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 15906.55000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76513 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76513 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76513 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76513 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31813.10000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52371.39520 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.74658 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1868.92436 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 52371.39520 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.61175 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | HeatExchanger:AirToAir:SensibleAndLatent | PSZ-AC:2 OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.89021 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.61175 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.61175 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.61175 |
74 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.02375 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.61175 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.80588 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.07450 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 149047.22290 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 158521.62000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 79260.81000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 79260.81000 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72323 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72323 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72323 |
85 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72323 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 158521.62000 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 282567.26235 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
89 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.61175 |
91 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12823.62452 |
92 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 282567.26235 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14278 |
94 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14278 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14278 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14278 |
98 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.75423 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14278 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57139 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.76185 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19459.39850 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20927.23000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10463.61500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10463.61500 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76334 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76334 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76334 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76334 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20927.23000 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35879.56716 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14278 |
115 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1265.23389 |
116 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 35879.56716 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.90568 |
118 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.90568 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.90568 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.90568 |
122 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.90568 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.90568 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.45284 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.60379 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16238.37976 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17388.73000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8694.36500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8694.36500 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74799 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74798 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74798 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74798 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17388.73000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31074.05513 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.90568 |
139 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1002.72993 |
140 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 31074.05513 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30442.5 | 11.33 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 152535.8 | 12.69 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20030.4 | 114.92 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16677.4 | 160.93 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 25 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.127 | 0.123 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 2.543E-002 | 2.527E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1593.79 | 1600.48 | 1593.79 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
32 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
33 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
34 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 0.84 | 0.84 | 0.84 | 270.00 | 0.00 | 0.91 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
40 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.146 | 0.141 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.146 | 0.141 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
56 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
57 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
58 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.429 | 0.403 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_0.45 | N/A | 1.647 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.239 | 0.226 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.2114058043 | 0.3634485358 | Pass | Pass | 0.6556777906 | 4.2662438366 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 7.7704889272E-002 | 0.2564279668 | Pass | Pass | 7.6107314255E-002 | 0.2397864554 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.1611759498 | 0.3645182310 | Pass | Pass | 0.3756234017 | 0.8613572335 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1873961928 | 0.3787181175 | Pass | Pass | 0.4141088142 | 1.2444456321 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1938353295 | 0.4459028454 | Pass | Pass | 7.9833645264E-002 | 0.5327464459 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 1600.48 | 1593.79 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.403 | 0.429 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.127 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.025 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.146 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.146 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.239 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 0.84 | 0.00 | 0.00 | 0.84 | 0.84 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 270.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.647 | 0.445 | 0.451 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.45 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.647 | 0.445 | 0.451 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.29_SHGC_0.45 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 1.647 | 0.445 | 0.451 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 90.63 | 1.840 | 0.456 | 0.462 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 90.63 | 1.840 | 0.456 | 0.462 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 6.8133 | 379.89 | 2588.29 | LightsWired | BLDG_LIGHT_BACK_SCH | 60.89 | 168.00 | 60.06 | 0.0000 | Y | 29.18 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 15.4032 | 1600.48 | 24652.49 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 65.33 | 0.0000 | Y | 302.33 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 15.4032 | 150.81 | 2322.95 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 15.4032 | 150.81 | 2322.95 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 8.7188 | 12.00 | 104.63 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.34 |
Interior Lighting Total | 13.9457 | 2293.99 | 31991.30 | 392.38 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.17 | 24652.49 | 4250.09 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 238.00 | AstronomicalClock | - | 42.55 | 42.55 | 1.90 | |
EXTERIOR_LIGHTS_B | 4328.05 | AstronomicalClock | - | 83.52 | 71.23 | 57.87 | |
Exterior Lighting Total | 4566.05 | 59.77 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 31813.10 | 24341.16 | 7471.94 | 0.77 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 158521.62 | 114647.59 | 43874.03 | 0.72 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20927.23 | 15974.59 | 4952.64 | 0.76 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17388.73 | 13006.42 | 4382.31 | 0.75 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 30442.5 | 11.33 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 152535.8 | 12.69 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 20030.4 | 114.92 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16677.4 | 160.93 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 87189.36 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 52371.40 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 282567.26 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 35879.57 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 31074.06 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.60 | 1018.41 | 3.89 | 6654.12 | 1708.60 | 1.00 | 1.17 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.75 | 1868.92 | 1070.05 | 1.00 | 1.34 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.61 | 12823.62 | 1684.71 | 1.00 | 1.16 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.14 | 1265.23 | 1107.16 | 1.00 | 1.37 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.91 | 1002.73 | 1107.16 | 1.00 | 1.43 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 19461.81 | 23354.18 | 61.48 | 1.429 | 1.715 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01023 | 20.92 | 0.01270 | 0.232 | 0.00 |
CORE_RETAIL | 84523.54 | 101428.25 | 63.37 | 6.214 | 7.456 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.00984 | 20.92 | 0.01270 | 1.890 | 0.00 |
POINT_OF_SALE | 12562.51 | 15075.01 | 99.96 | 0.936 | 1.123 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00904 | 20.92 | 0.01270 | 0.178 | 0.00 |
FRONT_RETAIL | 9855.86 | 11827.03 | 78.42 | 0.755 | 0.906 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 23.89 | 23.89 | 0.00909 | 29.79 | 0.01270 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.04 | 100.00 | 0.00001 | 30.10 | 0.01270 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 26177.00 | 31412.40 | 82.69 | 1.153 | 1.383 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00781 | -32.70 | 0.00018 | 0.232 | 0.00 |
CORE_RETAIL | 61362.95 | 73635.54 | 46.01 | 2.670 | 3.204 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00776 | -32.70 | 0.00018 | 1.890 | 0.00 |
POINT_OF_SALE | 12897.11 | 15476.54 | 102.62 | 0.570 | 0.684 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00788 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_RETAIL | 12896.37 | 15475.64 | 102.62 | 0.570 | 0.684 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00788 | -32.70 | 0.00018 | 0.178 | 0.00 |
FRONT_ENTRY | 72574.38 | 87089.26 | 7257.44 | 3.245 | 3.894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 21.11 | 20.97 | 0.00596 | -32.70 | 0.00018 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.75 | 1.75 | 1.38 | 1.38 | 1.7466 | 1.7152 | 1.7466 | 0.9820 | 1.0000 |
PSZ-AC:2 | 7.61 | 7.61 | 3.20 | 3.20 | 7.6117 | 7.4563 | 7.6117 | 0.9796 | 1.0000 |
PSZ-AC:3 | 1.14 | 1.14 | 0.68 | 0.68 | 1.1428 | 1.1234 | 1.1428 | 0.9830 | 1.0000 |
PSZ-AC:4 | 0.91 | 0.91 | 0.68 | 0.68 | 0.9057 | 0.9057 | 0.9057 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 87189.363 | 87189.363 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87189.36 | 87189.36 | 3.894489 | 20.78 | 12.40 | 0.00594152 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 20.97 | 0.00596255 | 37.1179 | 87089.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 15906.550 | 0.000 | 1.746580 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 15906.55 | 11890.61 | 1.746580 | 23.60 | 17.22 | 0.01021220 | 12.80 | 11.72 | 0.00850000 | 21.71 | 0.01270324 | 18.57 | 13.2583 | 23.88 | 0.01022709 | 52.9809 | 19461.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 52371.395 | 52371.395 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52371.40 | 52371.40 | 1.746581 | 11.93 | 9.31 | 0.00653676 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 13.2583 | 21.11 | 0.00781404 | 48.0979 | 26177.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 79260.810 | 0.000 | 7.611750 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 79260.81 | 61122.05 | 7.611750 | 25.63 | 17.91 | 0.01024345 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01270324 | 21.10 | 24.8328 | 23.88 | 0.00984076 | 51.0074 | 73529.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 282567.262 | 282567.262 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 282567.26 | 282567.26 | 7.611749 | -10.72 | -10.72 | 0.00328815 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 24.8328 | 21.11 | 0.00775607 | 47.7447 | 61362.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 10463.615 | 0.000 | 1.142780 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 10463.61 | 8799.81 | 1.142780 | 24.81 | 17.09 | 0.00954951 | 12.80 | 11.72 | 0.00850000 | 29.79 | 0.01270324 | 21.01 | 15.5857 | 23.89 | 0.00903578 | 46.8874 | 12430.34 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 35879.567 | 35879.567 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35879.57 | 35879.57 | 1.142776 | 7.00 | 6.28 | 0.00587898 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 15.5858 | 21.11 | 0.00788310 | 48.5171 | 12897.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 8694.365 | 0.000 | 0.905680 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 8694.36 | 7068.91 | 0.905680 | 25.07 | 17.38 | 0.00980031 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01270324 | 21.04 | 19.6659 | 23.89 | 0.00908806 | 47.1533 | 9842.71 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 31074.055 | 31074.055 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31074.06 | 31074.06 | 0.905679 | 7.00 | 6.28 | 0.00587885 | 40.00 | 20.66 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 19.6660 | 21.11 | 0.00788308 | 48.5170 | 12896.37 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 87189.363 | 87189.363 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 3.894489 | 4.49394812 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 87189.36 | 87189.36 | 1.0000 | 4.49394812 | 3.894489 | 20.78 | 12.40 | 0.00594152 | 35967.7 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87189.36 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00596255 | 20.97 | 0.00596255 | 37.1179 | 87089.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15906.550 | 0.000 | 1.746580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8240 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 15906.55 | 11890.61 | 1.0000 | 2.01542208 | 1.746580 | 23.60 | 17.22 | 0.01021220 | 49698.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15906.55 | 21.71 | 0.01270324 | 18.57 | 0.23156651 | 13.2583 | 23.88 | 0.00983145 | 23.88 | 0.01022709 | 52.9809 | 19461.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52371.395 | 52371.395 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.746581 | 2.01542337 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52371.40 | 52371.40 | 1.0000 | 2.01542337 | 1.746581 | 11.93 | 9.31 | 0.00653676 | 28482.6 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52371.40 | -32.70 | 0.00018338 | -32.70 | 0.23156651 | 13.2583 | 20.90 | 0.00781404 | 21.11 | 0.00781404 | 48.0979 | 26177.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 79260.810 | 0.000 | 7.611750 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8821 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 79260.81 | 61122.05 | 1.0000 | 8.78338753 | 7.611750 | 25.63 | 17.91 | 0.01024345 | 51855.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79260.81 | 30.10 | 0.01270324 | 21.10 | 1.89021192 | 24.8328 | 23.89 | 0.00928806 | 23.88 | 0.00984076 | 51.0074 | 73529.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 282567.262 | 282567.262 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.611749 | 8.78338606 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 282567.26 | 282567.26 | 1.0000 | 8.78338606 | 7.611749 | -10.72 | -10.72 | 0.00328815 | -2615.2 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 282567.26 | -32.70 | 0.00018338 | -32.70 | 1.89021192 | 24.8328 | 20.91 | 0.00775607 | 21.11 | 0.00775607 | 47.7447 | 61362.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10463.615 | 0.000 | 1.142780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5921 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 10463.61 | 8799.81 | 1.0000 | 1.31868225 | 1.142780 | 24.81 | 17.09 | 0.00954951 | 49251.5 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10463.61 | 29.79 | 0.01270324 | 21.01 | 0.17811053 | 15.5857 | 23.89 | 0.00896691 | 23.89 | 0.00903578 | 46.8874 | 12430.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35879.567 | 35879.567 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.142776 | 1.31867706 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35879.57 | 35879.57 | 1.0000 | 1.31867706 | 1.142776 | 7.00 | 6.28 | 0.00587898 | 21809.2 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35879.57 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 15.5858 | 20.96 | 0.00788310 | 21.11 | 0.00788310 | 48.5171 | 12897.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8694.365 | 0.000 | 0.905680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0583 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 8694.36 | 7068.91 | 1.0000 | 1.04508666 | 0.905680 | 25.07 | 17.38 | 0.00980031 | 50158.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8694.36 | 29.89 | 0.01270324 | 21.04 | 0.17811053 | 19.6659 | 23.89 | 0.00908848 | 23.89 | 0.00908806 | 47.1533 | 9842.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31074.055 | 31074.055 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.905679 | 1.04508501 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31074.06 | 31074.06 | 1.0000 | 1.04508501 | 0.905679 | 7.00 | 6.28 | 0.00587885 | 21808.0 | 40.00 | 20.66 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31074.06 | -32.70 | 0.00018338 | -32.70 | 0.17811053 | 19.6660 | 20.96 | 0.00788308 | 21.11 | 0.00788308 | 48.5170 | 12896.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.75 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.61 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.14 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 0.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2912.17 | 3764.50 | 2325.00 |
CORE_RETAIL | 2463.17 | 2920.33 | 1287.33 |
POINT_OF_SALE | 2818.17 | 2905.67 | 1400.50 |
FRONT_RETAIL | 2865.17 | 3291.00 | 1777.17 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3645.17 | 3781.17 | 2343.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 17.83 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 11.83 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 20.83 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 1.50 | 0.00 | 0.00 | 0.00 |
Facility | 38.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.540 | 0.030 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.854 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 1.102 | 0.033 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 1.099 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.351 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.682 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.682 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 11 | 11 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 966.86 | 3323.90 | 30-APR-06:30 | 83902.94 | 29-JUN-16:00 |
Electricity:Building | 587.53 | 3253.07 | 11-JUN-07:30 | 39264.11 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 79.17 | 589.27 | 01-JAN-00:10 | 4789.50 | 02-JAN-09:10 |
InteriorLights:Electricity | 392.38 | 1457.90 | 11-JUN-07:30 | 28493.07 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 29.18 | 129.41 | 01-JAN-00:10 | 2030.36 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 392.38 | 1457.90 | 11-JUN-07:30 | 28493.07 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 386.63 | 1866.39 | 11-JUN-07:30 | 26839.84 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 302.33 | 1090.95 | 11-JUN-07:30 | 22187.24 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 82.68 | 602.96 | 01-JAN-00:10 | 5011.54 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 37.71 | 189.21 | 01-JAN-00:10 | 2529.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.34 | 5.23 | 01-JAN-00:10 | 94.16 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.34 | 5.23 | 01-JAN-00:10 | 94.16 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 966.86 | 3323.90 | 30-APR-06:30 | 83902.94 | 29-JUN-16:00 |
ElectricityPurchased:Plant | 966.86 | 3323.90 | 30-APR-06:30 | 83902.94 | 29-JUN-16:00 |
Cogeneration:ElectricityPurchased | 966.86 | 3323.90 | 30-APR-06:30 | 83902.94 | 29-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 966.86 | 3323.90 | 30-APR-06:30 | 83902.94 | 29-JUN-16:00 |
ElectricityNet:Plant | 966.86 | 3323.90 | 30-APR-06:30 | 83902.94 | 29-JUN-16:00 |
Cogeneration:ElectricityNet | 966.86 | 3323.90 | 30-APR-06:30 | 83902.94 | 29-JUN-16:00 |
Electricity:HVAC | 319.55 | 0.00 | 01-JAN-20:10 | 46075.57 | 30-JUN-15:00 |
Fans:Electricity | 222.06 | 0.00 | 01-JAN-20:10 | 19600.14 | 01-JAN-09:10 |
General:Fans:Electricity | 222.06 | 0.00 | 01-JAN-20:10 | 19600.14 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 79.82 | 0.00 | 01-JAN-00:10 | 36316.51 | 29-JUN-16:00 |
ExteriorLights:Electricity | 59.77 | 0.00 | 01-JAN-08:20 | 4566.05 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 59.77 | 0.00 | 01-JAN-08:20 | 4566.05 | 01-JAN-06:10 |
HeatRecovery:Electricity | 17.66 | 0.00 | 01-JAN-00:10 | 1406.23 | 02-JAN-07:20 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 619.78 | 1862.00 | 28-MAY-07:10 | 317452.71 | 09-JAN-07:10 |
Gas:Plant | 100.71 | 1862.00 | 01-JAN-07:10 | 6349.28 | 24-FEB-12:40 |
WaterSystems:Gas | 100.71 | 1862.00 | 01-JAN-07:10 | 6349.28 | 24-FEB-12:40 |
Water Heater:WaterSystems:Gas | 100.71 | 1862.00 | 01-JAN-07:10 | 6349.28 | 24-FEB-12:40 |
Gas:HVAC | 519.07 | 0.00 | 01-JAN-00:10 | 312863.61 | 09-JAN-07:10 |
Heating:Gas | 519.07 | 0.00 | 01-JAN-00:10 | 312863.61 | 09-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 30-MAR-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1911.49 | 0.00 | 01-JAN-20:10 | 373208.93 | 09-JAN-07:10 |
EnergyTransfer:Building | 702.82 | 0.00 | 01-JAN-20:10 | 141333.70 | 01-JAN-08:10 |
EnergyTransfer:Zone:BACK_SPACE | 93.02 | 0.00 | 01-JAN-00:10 | 29778.82 | 01-JAN-08:10 |
Heating:EnergyTransfer | 271.32 | 0.00 | 01-JAN-20:10 | 141333.70 | 01-JAN-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 49.55 | 0.00 | 01-JAN-00:10 | 29778.82 | 01-JAN-08:10 |
Cooling:EnergyTransfer | 431.50 | 0.00 | 01-JAN-00:10 | 75709.13 | 30-JUN-14:30 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 43.47 | 0.00 | 01-JAN-00:10 | 11099.66 | 30-JUN-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 320.95 | 0.00 | 01-JAN-00:10 | 82356.71 | 26-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 31.36 | 0.00 | 01-JAN-00:10 | 77451.78 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 289.60 | 0.00 | 01-JAN-00:10 | 47894.90 | 30-JUN-14:30 |
EnergyTransfer:Zone:POINT_OF_SALE | 70.72 | 0.00 | 01-JAN-00:10 | 12839.93 | 25-DEC-08:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 8.70 | 0.00 | 01-JAN-00:10 | 12839.93 | 25-DEC-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 62.02 | 0.00 | 01-JAN-00:10 | 11412.70 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 52.22 | 0.00 | 01-JAN-00:10 | 13165.21 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 15.80 | 0.00 | 01-JAN-00:10 | 13165.21 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 36.42 | 0.00 | 01-JAN-00:10 | 9181.84 | 01-SEP-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 165.92 | 0.00 | 01-JAN-20:10 | 65885.06 | 05-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 165.92 | 0.00 | 01-JAN-20:10 | 65885.06 | 05-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1208.67 | 0.00 | 01-JAN-00:10 | 250290.89 | 09-JAN-07:10 |
HeatingCoils:EnergyTransfer | 415.26 | 0.00 | 01-JAN-00:10 | 250290.89 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 301.51 | 0.00 | 01-JAN-00:10 | 142268.79 | 05-JUL-10:40 |
HeatRecoveryForHeating:EnergyTransfer | 471.83 | 0.00 | 01-JAN-00:10 | 77079.74 | 31-JAN-18:50 |
HeatRecoveryForCooling:EnergyTransfer | 20.08 | 0.00 | 01-JAN-00:10 | 41090.95 | 15-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 49.551 | -43.469 | 0.000 | 0.000 | 40.110 | 29.179 | 49.992 | 0.000 | 0.000 | 0.091 | 0.001 | 0.000 | 0.000 | 0.000 | -24.288 | -101.166 |
CORE_RETAIL | 0.000 | 0.000 | 31.355 | -289.597 | 0.000 | 0.000 | 163.752 | 302.334 | 84.299 | 11.886 | 0.000 | 0.074 | 0.001 | 0.000 | -11.263 | 0.000 | -21.540 | -271.299 |
POINT_OF_SALE | 0.000 | 0.000 | 8.700 | -62.015 | 0.000 | 0.000 | 15.647 | 29.762 | 52.922 | 39.615 | 0.000 | 0.038 | 0.004 | 0.000 | -22.362 | 0.000 | -10.978 | -51.329 |
FRONT_RETAIL | 0.000 | 0.000 | 15.800 | -36.417 | 0.000 | 0.000 | 15.819 | 29.762 | 7.943 | 39.534 | 0.000 | 0.039 | 0.005 | 0.000 | -22.016 | 0.000 | -10.699 | -39.766 |
FRONT_ENTRY | 165.918 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.340 | 0.000 | 7.976 | 0.000 | 0.041 | 0.000 | 0.000 | -4.563 | 0.000 | -167.821 | -2.892 |
Total Facility | 165.918 | 0.000 | 105.406 | -431.498 | 0.000 | 0.000 | 235.328 | 392.378 | 195.156 | 99.012 | 0.000 | 0.282 | 0.011 | 0.000 | -60.205 | 0.000 | -235.326 | -466.452 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -35172.64 | 0.00 | 0.00 | 404.71 | 451.19 | 1226.28 | 0.00 | 0.00 | 0.00 | 33090.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 09-SEP-06:02 | 0.00 | 0.00 | 0.00 | -198994.98 | 0.00 | 0.00 | 1634.46 | 2465.25 | 1550.87 | 0.00 | 0.00 | 0.00 | 194050.68 | 0.00 | -378.35 | 0.00 | -327.92 | 0.00 |
POINT_OF_SALE | 09-SEP-06:02 | 0.00 | 0.00 | 0.00 | -25078.72 | 0.00 | 0.00 | 151.78 | 232.29 | 973.63 | 0.00 | 0.00 | 0.00 | 24539.04 | 0.00 | -646.68 | 0.00 | -171.35 | 0.00 |
FRONT_RETAIL | 09-SEP-06:02 | 0.00 | 0.00 | 0.00 | -20205.73 | 0.00 | 0.00 | 155.24 | 232.29 | 146.13 | 0.00 | 0.00 | 0.00 | 20479.67 | 0.00 | -636.70 | 0.00 | -170.91 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-AUG-06:02 | 0.00 | 0.00 | 0.00 | -253731.49 | 0.00 | 0.00 | 2301.14 | 6331.79 | 4787.13 | 0.00 | 0.00 | 0.00 | 241813.35 | 0.00 | -1501.92 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 25-DEC-07:42 | 0.00 | 0.00 | 53974.29 | 0.00 | 0.00 | 0.00 | 0.00 | 129.41 | 459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3796.61 | -50766.95 |
CORE_RETAIL | 24-DEC-08:61 | 0.00 | 0.00 | 288371.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.62 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1186.58 | 0.00 | -1130.29 | -288062.23 |
POINT_OF_SALE | 25-DEC-07:11 | 0.00 | 0.00 | 36354.39 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 486.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2381.86 | 0.00 | -1619.89 | -32955.61 |
FRONT_RETAIL | 25-DEC-07:42 | 0.00 | 0.00 | 31462.46 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2405.72 | 0.00 | -1655.65 | -27590.30 |
FRONT_ENTRY | 05-JAN-18:00 | 65885.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 142.12 | 0.00 | -549.39 | 0.00 | -65571.91 | 0.00 |
Total Facility | 24-DEC-08:61 | 11297.94 | 0.00 | 408826.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.57 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6870.99 | 0.00 | -12673.65 | -403974.80 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7152 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7466 | 0.1326 | 1.0000 | 0.2316 | 0.1326 | ||
PSZ-AC:2 | 7.4563 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.6117 | 0.2483 | 1.0000 | 1.8902 | 0.2483 | ||
PSZ-AC:3 | 1.1234 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1428 | 0.1559 | 1.0000 | 0.1781 | 0.1559 | ||
PSZ-AC:4 | 0.9057 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.9057 | 0.1967 | 1.0000 | 0.1781 | 0.1967 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.7152 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.7152 | 1.0000 | 1.0000 | 0.2316 | 0.1350 | ||
PSZ-AC:2 | 7.4563 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.4563 | 1.0000 | 1.0000 | 1.8902 | 0.2535 | ||
PSZ-AC:3 | 1.1234 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1234 | 1.0000 | 1.0000 | 0.1781 | 0.1585 | ||
PSZ-AC:4 | 0.9057 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.9057 | 1.0000 | 1.0000 | 0.1781 | 0.1967 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7152 | 1.7152 | 1.7152 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.4563 | 7.4563 | 7.4563 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1234 | 1.1234 | 1.1234 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9057 | 0.9057 | 0.9057 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7152 | 1.7466 | 1.7152 | 1.7152 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.4563 | 7.6117 | 7.4563 | 7.4563 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1234 | 1.1428 | 1.1234 | 1.1234 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9057 | 0.9057 | 0.9057 | 0.9057 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.7152 | 1.7152 | 1.7152 | 0.2316 | 0.1674 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.4563 | 7.4563 | 7.4563 | 1.8902 | 0.5900 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1234 | 1.1234 | 1.1234 | 0.1781 | 0.2603 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.9057 | 0.9057 | 0.9057 | 0.1781 | 0.2603 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.7152 | 1.7152 | 1.7152 | 1.7152 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.4563 | 7.4563 | 7.4563 | 7.4563 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1234 | 1.1234 | 1.1234 | 1.1234 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.9057 | 0.9057 | 0.9057 | 0.9057 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 519.07 | 312863.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 79.82 | 36316.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 392.38 | 28493.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 59.77 | 4566.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 222.06 | 19600.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 17.66 | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 100.71 | 6349.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 966.86 |
Natural Gas | 0.00 | 619.78 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1586.64 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 171.05 |
Space Heating | 0.00 |
Space Cooling | 34.80 |
Fans (All) | 96.80 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 421.47 |
Subtotal | 421.47 |
Natural Gas [MJ/m2] | |
Space Heating | 226.28 |
Service Water Heating | 43.90 |
Miscellaneous (All) | 270.18 |
Subtotal | 270.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.73 |
Space Heating | 32.72 |
Space Cooling | 5.03 |
Fans (All) | 14.00 |
Service Water Heating | 6.35 |
Receptacle Equipment | 12.30 |
Miscellaneous | 4.88 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3175. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.159931E+12 |
February | 0.000 | 0.910107E+11 |
March | 0.000 | 0.609836E+11 |
April | 0.000 | 0.162161E+11 |
May | 0.000 | 0.127680E+10 |
June | 0.000 | 0.914005E+08 |
July | 0.000 | 0.256759E+08 |
August | 0.000 | 0.100384E+09 |
September | 0.000 | 0.100153E+10 |
October | 0.000 | 0.962887E+10 |
November | 0.000 | 0.401579E+11 |
December | 0.000 | 0.138650E+12 |
Annual Sum or Average | 0.519074E+12 | |
Minimum of Months | 0.000 | 0.256759E+08 |
Maximum of Months | 0.000 | 0.159931E+12 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2588664.64 | 7057.23 | 20-JAN-07:05 | -7.3 | -7.9 | 0.165178E+10 | 1854.45 | 31-JAN-15:09 | -19.4 | -20.0 |
February | 39091115.19 | 7427.40 | 22-FEB-07:05 | -8.6 | -9.0 | 0.150831E+10 | 1854.45 | 01-FEB-15:00 | -20.0 | -20.9 |
March | 0.534117E+09 | 7412.15 | 23-MAR-06:05 | -18.8 | -19.1 | 0.172623E+10 | 1948.80 | 31-MAR-14:00 | 8.30 | 2.61 |
April | 0.215697E+10 | 8666.39 | 05-APR-06:05 | -13.5 | -14.0 | 0.175362E+10 | 2451.25 | 13-APR-14:20 | 19.27 | 7.63 |
May | 0.496200E+10 | 26719.28 | 26-MAY-06:02 | 19.50 | 15.69 | 0.215207E+10 | 2451.25 | 22-MAY-14:30 | 20.20 | 14.04 |
June | 0.708528E+10 | 28702.05 | 22-JUN-06:02 | 15.97 | 14.47 | 0.219500E+10 | 2451.27 | 10-JUN-10:20 | 17.60 | 16.62 |
July | 0.919529E+10 | 34230.69 | 01-JUL-06:02 | 12.25 | 11.44 | 0.218696E+10 | 2451.36 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.847174E+10 | 35185.23 | 25-AUG-06:02 | 9.05 | 8.95 | 0.227979E+10 | 2451.29 | 01-AUG-14:00 | 20.60 | 15.16 |
September | 0.557568E+10 | 34265.37 | 02-SEP-06:02 | 13.22 | 10.59 | 0.212018E+10 | 2451.29 | 02-SEP-13:50 | 15.33 | 13.44 |
October | 0.408005E+10 | 7832.47 | 30-OCT-06:05 | -9.4 | -9.8 | 0.186980E+10 | 2451.24 | 21-OCT-12:50 | 19.13 | 11.25 |
November | 0.135728E+10 | 7851.75 | 23-NOV-09:05 | -10.0 | -10.5 | 0.160910E+10 | 2362.16 | 01-NOV-14:00 | 18.30 | 13.43 |
December | 8991525.14 | 6348.98 | 30-DEC-07:05 | -4.8 | -5.4 | 0.165429E+10 | 1854.45 | 09-DEC-16:00 | -19.1 | -19.9 |
Annual Sum or Average | 0.434691E+11 | 0.227071E+11 | ||||||||
Minimum of Months | 2588664.64 | 6348.98 | -18.8 | -19.1 | 0.150831E+10 | 1854.45 | -20.0 | -20.9 | ||
Maximum of Months | 0.919529E+10 | 35185.23 | 19.50 | 15.69 | 0.227979E+10 | 2451.36 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.647079E+10 | 59658.45 | 25-JAN-07:05 | -25.6 | -25.8 | 0.698990E+10 | 8568.81 | 19-JAN-15:00 | -2.8 | -3.5 |
February | 0.878392E+10 | 70315.53 | 24-FEB-07:05 | -23.9 | -24.2 | 0.658423E+10 | 10033.61 | 08-FEB-15:00 | 4.40 | -0.7 |
March | 0.129159E+11 | 26512.56 | 16-MAR-06:03 | -22.9 | -23.2 | 0.804861E+10 | 10327.01 | 28-MAR-14:09 | 6.20 | 2.92 |
April | 0.187248E+11 | 67187.51 | 23-APR-08:62 | 13.68 | 8.64 | 0.877718E+10 | 10327.25 | 15-APR-12:09 | 5.50 | 5.17 |
May | 0.340168E+11 | 179759.70 | 17-MAY-06:03 | 11.65 | 8.32 | 0.939282E+10 | 10327.13 | 08-MAY-14:09 | 7.03 | 5.20 |
June | 0.411312E+11 | 188842.03 | 17-JUN-06:02 | 9.13 | 8.08 | 0.927789E+10 | 10327.30 | 07-JUN-14:09 | 22.20 | 14.32 |
July | 0.461888E+11 | 167807.69 | 08-JUL-06:02 | 11.97 | 10.77 | 0.921827E+10 | 10328.11 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.447379E+11 | 174032.35 | 25-AUG-06:02 | 9.05 | 8.95 | 0.961311E+10 | 10327.17 | 19-AUG-15:00 | 22.80 | 15.34 |
September | 0.342771E+11 | 199011.97 | 09-SEP-06:02 | 12.20 | 6.68 | 0.908504E+10 | 10327.65 | 02-SEP-13:00 | 14.40 | 13.10 |
October | 0.215821E+11 | 121039.53 | 20-OCT-06:02 | 5.92 | 5.92 | 0.907776E+10 | 10327.31 | 10-OCT-14:00 | 7.20 | 6.66 |
November | 0.127828E+11 | 24235.45 | 25-NOV-07:03 | -19.2 | -19.5 | 0.781848E+10 | 10327.23 | 20-NOV-15:30 | 8.60 | 6.93 |
December | 0.798582E+10 | 66177.41 | 02-DEC-07:05 | -27.1 | -27.3 | 0.701590E+10 | 8621.60 | 05-DEC-15:00 | -0.4 | -0.4 |
Annual Sum or Average | 0.289598E+12 | 0.100899E+12 | ||||||||
Minimum of Months | 0.647079E+10 | 24235.45 | -27.1 | -27.3 | 0.658423E+10 | 8568.81 | -2.8 | -3.5 | ||
Maximum of Months | 0.461888E+11 | 199011.97 | 13.68 | 10.77 | 0.961311E+10 | 10328.11 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160887E+10 | 9387.14 | 05-JAN-18:01 | -28.4 | -28.6 | 0.655723E+09 | 736.18 | 14-JAN-12:50 | -15.2 | -15.6 |
February | 0.251786E+10 | 7259.04 | 11-FEB-07:03 | -16.0 | -16.4 | 0.619411E+09 | 973.05 | 28-FEB-15:09 | 6.10 | 1.53 |
March | 0.341676E+10 | 6957.53 | 16-MAR-06:03 | -22.9 | -23.2 | 0.724177E+09 | 973.06 | 29-MAR-14:09 | 3.98 | 0.93 |
April | 0.468056E+10 | 7801.33 | 22-APR-13:30 | 16.95 | 7.06 | 0.768573E+09 | 973.10 | 22-APR-10:09 | 13.58 | 4.69 |
May | 0.646154E+10 | 24074.55 | 19-MAY-06:02 | 14.47 | 10.08 | 0.876334E+09 | 973.17 | 19-MAY-14:09 | 17.63 | 14.64 |
June | 0.733225E+10 | 22277.77 | 09-JUN-06:02 | 12.12 | 11.47 | 0.873455E+09 | 973.14 | 10-JUN-11:50 | 18.12 | 17.35 |
July | 0.877496E+10 | 23450.34 | 08-JUL-06:02 | 11.97 | 10.77 | 0.868573E+09 | 973.20 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.903461E+10 | 24694.17 | 25-AUG-06:02 | 9.05 | 8.95 | 0.905528E+09 | 973.15 | 10-AUG-14:09 | 18.95 | 16.67 |
September | 0.753113E+10 | 25080.18 | 09-SEP-06:02 | 12.20 | 6.68 | 0.851318E+09 | 973.21 | 02-SEP-13:00 | 14.40 | 13.10 |
October | 0.582120E+10 | 24504.04 | 20-OCT-06:02 | 5.92 | 5.92 | 0.804177E+09 | 973.10 | 07-OCT-10:20 | 11.87 | 11.23 |
November | 0.340419E+10 | 6532.62 | 17-NOV-13:30 | 10.30 | 3.30 | 0.686836E+09 | 973.07 | 01-NOV-14:20 | 17.97 | 13.31 |
December | 0.143124E+10 | 6754.83 | 08-DEC-07:03 | -20.4 | -20.7 | 0.656757E+09 | 736.18 | 18-DEC-15:00 | -23.2 | -23.8 |
Annual Sum or Average | 0.620152E+11 | 0.929086E+10 | ||||||||
Minimum of Months | 0.143124E+10 | 6532.62 | -28.4 | -28.6 | 0.619411E+09 | 736.18 | -23.2 | -23.8 | ||
Maximum of Months | 0.903461E+10 | 25080.18 | 16.95 | 11.47 | 0.905528E+09 | 973.21 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.497790E+09 | 6308.37 | 26-JAN-17:52 | -16.1 | -17.1 | 0.655730E+09 | 736.18 | 07-JAN-14:50 | -16.9 | -17.5 |
February | 0.105244E+10 | 6961.40 | 25-FEB-10:32 | -19.4 | -20.1 | 0.607574E+09 | 959.20 | 28-FEB-15:50 | 6.10 | 1.53 |
March | 0.156268E+10 | 6037.16 | 18-MAR-06:04 | -20.2 | -20.4 | 0.702760E+09 | 973.06 | 31-MAR-14:30 | 8.30 | 2.85 |
April | 0.257783E+10 | 5446.18 | 22-APR-13:30 | 16.95 | 7.06 | 0.733488E+09 | 973.10 | 13-APR-14:20 | 19.27 | 7.63 |
May | 0.378462E+10 | 19662.16 | 19-MAY-06:02 | 14.47 | 10.08 | 0.860943E+09 | 973.11 | 19-MAY-14:00 | 17.80 | 14.99 |
June | 0.453109E+10 | 17570.41 | 18-JUN-08:62 | 19.78 | 12.82 | 0.871607E+09 | 973.13 | 06-JUN-14:30 | 20.00 | 14.71 |
July | 0.588826E+10 | 18923.31 | 08-JUL-06:02 | 11.97 | 10.77 | 0.868313E+09 | 973.19 | 25-JUL-14:30 | 23.05 | 20.24 |
August | 0.604633E+10 | 19921.37 | 25-AUG-06:02 | 9.05 | 8.95 | 0.904945E+09 | 973.17 | 10-AUG-14:20 | 18.50 | 16.38 |
September | 0.489530E+10 | 20206.85 | 09-SEP-06:02 | 12.20 | 6.68 | 0.839732E+09 | 973.17 | 02-SEP-13:50 | 15.33 | 13.44 |
October | 0.359605E+10 | 16264.72 | 20-OCT-06:02 | 5.92 | 5.92 | 0.759862E+09 | 973.09 | 21-OCT-10:09 | 12.35 | 8.15 |
November | 0.160629E+10 | 5347.80 | 10-NOV-07:03 | -8.4 | -9.4 | 0.656668E+09 | 973.10 | 01-NOV-14:09 | 17.88 | 13.28 |
December | 0.378552E+09 | 5049.24 | 07-DEC-07:04 | -7.8 | -7.9 | 0.656725E+09 | 736.18 | 09-DEC-12:30 | -14.9 | -15.7 |
Annual Sum or Average | 0.364172E+11 | 0.911835E+10 | ||||||||
Minimum of Months | 0.378552E+09 | 5049.24 | -20.2 | -20.4 | 0.607574E+09 | 736.18 | -16.9 | -17.5 | ||
Maximum of Months | 0.604633E+10 | 20206.85 | 19.78 | 12.82 | 0.904945E+09 | 973.19 | 23.05 | 20.24 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 | -3.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.37 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.56 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.4 | 0.00 | 0.00 | -23.1 | -23.4 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.00 | 0.00 | 19.75 | 18.15 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147595E+11 | 53918.84 | 07-JAN-05:42 | -22.3 |
February | 0.985441E+10 | 53407.22 | 19-FEB-07:32 | -23.7 |
March | 0.675426E+10 | 53310.27 | 13-MAR-04:42 | -13.3 |
April | 0.147727E+10 | 52706.65 | 04-APR-05:01 | -9.0 |
May | 0.120033E+09 | 46420.34 | 01-MAY-06:01 | -3.5 |
June | 70310015.93 | 1491.43 | 30-JUN-06:20 | 26.50 |
July | 75673499.35 | 1132.04 | 30-JUL-08:20 | 24.80 |
August | 75200929.42 | 734.72 | 27-AUG-07:12 | 12.97 |
September | 73550660.19 | 749.73 | 06-SEP-06:00 | 2.20 |
October | 0.277217E+09 | 52477.16 | 30-OCT-05:01 | -9.9 |
November | 0.348407E+10 | 52872.67 | 25-NOV-05:01 | -19.0 |
December | 0.125288E+11 | 53973.98 | 25-DEC-07:42 | -28.0 |
Annual Sum or Average | 0.495502E+11 | |||
Minimum of Months | 70310015.93 | 734.72 | -28.0 | |
Maximum of Months | 0.147595E+11 | 53973.98 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102869E+11 | 288156.82 | 04-JAN-06:01 | -29.0 |
February | 0.525022E+10 | 287574.62 | 27-FEB-06:01 | -18.5 |
March | 0.284013E+10 | 287495.77 | 15-MAR-05:01 | -22.2 |
April | 0.551027E+09 | 35841.52 | 05-APR-06:03 | -13.5 |
May | 0.506031E+09 | 5115.75 | 01-MAY-05:45 | -3.8 |
June | 0.451477E+09 | 6829.22 | 30-JUN-06:20 | 26.50 |
July | 0.344628E+09 | 6533.20 | 30-JUL-08:08 | 24.60 |
August | 0.417537E+09 | 5058.50 | 27-AUG-07:12 | 12.97 |
September | 0.493897E+09 | 5129.31 | 17-SEP-07:42 | 13.80 |
October | 0.538220E+09 | 5145.76 | 09-OCT-07:23 | -3.1 |
November | 0.154057E+10 | 285212.27 | 27-NOV-06:01 | -7.1 |
December | 0.813503E+10 | 288370.88 | 24-DEC-08:61 | -31.1 |
Annual Sum or Average | 0.313556E+11 | |||
Minimum of Months | 0.344628E+09 | 5058.50 | -31.1 | |
Maximum of Months | 0.102869E+11 | 288370.88 | 26.50 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276302E+10 | 36307.86 | 04-JAN-05:22 | -28.6 |
February | 0.145129E+10 | 35809.20 | 19-FEB-08:61 | -23.5 |
March | 0.938775E+09 | 35777.05 | 06-MAR-05:11 | -18.5 |
April | 0.197876E+09 | 35408.38 | 03-APR-05:01 | -4.3 |
May | 45538837.87 | 6737.32 | 01-MAY-06:07 | -3.5 |
June | 39411718.67 | 773.54 | 25-JUN-08:06 | 24.08 |
July | 25915264.46 | 717.58 | 23-JUL-07:05 | 22.38 |
August | 28961518.02 | 737.07 | 09-AUG-05:07 | 18.40 |
September | 44587039.03 | 651.45 | 01-SEP-05:04 | 15.68 |
October | 65321344.70 | 16935.96 | 30-OCT-05:01 | -9.9 |
November | 0.594360E+09 | 35630.76 | 25-NOV-05:01 | -19.0 |
December | 0.250483E+10 | 36354.34 | 25-DEC-07:11 | -28.4 |
Annual Sum or Average | 0.869988E+10 | |||
Minimum of Months | 25915264.46 | 651.45 | -28.6 | |
Maximum of Months | 0.276302E+10 | 36354.34 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.467221E+10 | 31453.38 | 05-JAN-05:52 | -32.8 |
February | 0.252981E+10 | 31372.51 | 16-FEB-05:42 | -14.3 |
March | 0.180001E+10 | 31226.79 | 06-MAR-05:32 | -18.7 |
April | 0.473266E+09 | 30947.67 | 04-APR-05:01 | -9.0 |
May | 0.106891E+09 | 17592.20 | 01-MAY-06:01 | -3.5 |
June | 85603789.76 | 1244.37 | 25-JUN-08:06 | 24.08 |
July | 76749700.80 | 1002.60 | 09-JUL-07:32 | 13.30 |
August | 83327377.04 | 979.78 | 27-AUG-07:12 | 12.97 |
September | 92981724.67 | 999.39 | 17-SEP-07:42 | 13.80 |
October | 0.175049E+09 | 30744.05 | 30-OCT-05:01 | -9.9 |
November | 0.124705E+10 | 31034.64 | 25-NOV-05:01 | -19.0 |
December | 0.445727E+10 | 31462.37 | 25-DEC-07:42 | -28.0 |
Annual Sum or Average | 0.158002E+11 | |||
Minimum of Months | 76749700.80 | 979.78 | -32.8 | |
Maximum of Months | 0.467221E+10 | 31462.37 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345100E+11 | 65885.06 | 05-JAN-18:00 | -28.3 |
February | 0.241965E+11 | 57455.36 | 01-FEB-18:00 | -23.3 |
March | 0.220179E+11 | 46150.78 | 15-MAR-11:10 | -15.3 |
April | 0.114636E+11 | 33333.25 | 04-APR-11:03 | -4.9 |
May | 0.383283E+10 | 17287.74 | 01-MAY-11:05 | 6.72 |
June | 0.139976E+10 | 10525.35 | 09-JUN-11:05 | 12.38 |
July | 0.597506E+09 | 8918.40 | 08-JUL-11:10 | 13.30 |
August | 0.999699E+09 | 11255.75 | 17-AUG-12:00 | 10.60 |
September | 0.443768E+10 | 16113.20 | 27-SEP-11:05 | 7.38 |
October | 0.109505E+11 | 26431.05 | 29-OCT-17:00 | -1.1 |
November | 0.183713E+11 | 45848.95 | 25-NOV-17:00 | -15.6 |
December | 0.331405E+11 | 63313.25 | 24-DEC-12:10 | -26.9 |
Annual Sum or Average | 0.165918E+12 | |||
Minimum of Months | 0.597506E+09 | 8918.40 | -28.3 | |
Maximum of Months | 0.345100E+11 | 65885.06 | 13.30 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.244735E+10 | 2030.36 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.222649E+10 | 2030.36 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.253900E+10 | 2030.36 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.239592E+10 | 2030.36 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.249318E+10 | 2030.36 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.245011E+10 | 2030.36 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.243899E+10 | 2030.36 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.253900E+10 | 2030.36 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.239592E+10 | 2030.36 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.244735E+10 | 2030.36 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.236682E+10 | 2030.36 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.243899E+10 | 2030.36 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.291791E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.222649E+10 | 2030.36 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.253900E+10 | 2030.36 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.261826E+11 | 22187.24 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.236788E+11 | 22187.24 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.267472E+11 | 22187.24 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.248331E+11 | 22187.24 | 01-APR-16:19 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.246318E+11 | 22187.24 | 01-MAY-15:30 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.243248E+11 | 22187.24 | 08-JUN-16:10 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.240545E+11 | 22187.24 | 06-JUL-16:00 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.257276E+11 | 22187.24 | 02-AUG-15:50 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.248710E+11 | 22187.24 | 01-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.258488E+11 | 22187.24 | 02-OCT-08:09 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.252823E+11 | 22187.24 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.261518E+11 | 22187.24 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.302334E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.236788E+11 | 22187.24 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.267472E+11 | 22187.24 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.244398E+10 | 2090.65 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.249959E+10 | 2090.65 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.244398E+10 | 2090.65 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.244398E+10 | 2090.65 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.249959E+10 | 2090.65 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.244398E+10 | 2090.65 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112411E+09 | 94.16 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102280E+09 | 94.16 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.116668E+09 | 94.16 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.110076E+09 | 94.16 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.114539E+09 | 94.16 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.112581E+09 | 94.16 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112035E+09 | 94.16 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.116668E+09 | 94.16 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.110076E+09 | 94.16 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112411E+09 | 94.16 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108701E+09 | 94.16 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112035E+09 | 94.16 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134048E+10 | ||||
Minimum of Months | 0.102280E+09 | 94.16 | 0.00 | 0.00 | |
Maximum of Months | 0.116668E+09 | 94.16 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.244735E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402224E+10 |
February | 0.479114E+10 | 0.222649E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347284E+10 |
March | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248219E+10 |
April | 0.518069E+10 | 0.239592E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945827.00 | 0.205828E+10 |
May | 0.536353E+10 | 0.249318E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8311914.05 | 0.104264E+10 |
June | 0.528933E+10 | 0.245011E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32947319.13 | 0.594854E+09 |
July | 0.525489E+10 | 0.243899E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34436656.37 | 0.403471E+09 |
August | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13302936.95 | 0.622904E+09 |
September | 0.518069E+10 | 0.239592E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433280.81 | 0.108756E+10 |
October | 0.524694E+10 | 0.244735E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154973E+10 |
November | 0.504819E+10 | 0.236682E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278886E+10 |
December | 0.525489E+10 | 0.243899E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416238E+10 |
Annual Sum or Average | 0.628175E+11 | 0.291791E+11 | 0.499918E+11 | 91377934.31 | 0.242880E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.222649E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403471E+09 |
Maximum of Months | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34436656.37 | 0.416238E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.261826E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344505E+10 |
February | 0.201852E+11 | 0.236788E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302568E+10 |
March | 0.230879E+11 | 0.267472E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220421E+10 |
April | 0.218263E+11 | 0.248331E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1285588.21 | 0.194399E+10 |
May | 0.225967E+11 | 0.246318E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6799939.38 | 0.960143E+09 |
June | 0.222841E+11 | 0.243248E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26191170.78 | 0.540663E+09 |
July | 0.221389E+11 | 0.240545E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28116790.39 | 0.357933E+09 |
August | 0.230879E+11 | 0.257276E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10885612.16 | 0.551305E+09 |
September | 0.218263E+11 | 0.248710E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354674.52 | 0.967089E+09 |
October | 0.221054E+11 | 0.258488E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143841E+10 |
November | 0.212681E+11 | 0.252823E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252088E+10 |
December | 0.221389E+11 | 0.261518E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358468E+10 |
Annual Sum or Average | 0.264651E+12 | 0.302334E+12 | 0.842987E+11 | 73633775.43 | 0.215400E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.236788E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357933E+09 |
Maximum of Months | 0.230879E+11 | 0.267472E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28116790.39 | 0.358468E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175835E+10 |
February | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154588E+10 |
March | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112646E+10 |
April | 0.205665E+10 | 0.244398E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 637456.89 | 0.966108E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3597642.07 | 0.490813E+09 |
June | 0.209978E+10 | 0.249959E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13255949.36 | 0.282659E+09 |
July | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14727907.14 | 0.194434E+09 |
August | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5759292.16 | 0.299215E+09 |
September | 0.205665E+10 | 0.244398E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187904.16 | 0.507841E+09 |
October | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727816E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125893E+10 |
December | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181977E+10 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.529224E+11 | 38166151.78 | 0.109783E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194434E+09 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14727907.14 | 0.181977E+10 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174499E+10 |
February | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152531E+10 |
March | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110220E+10 |
April | 0.205665E+10 | 0.244398E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650371.90 | 0.929796E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3598472.00 | 0.464987E+09 |
June | 0.209978E+10 | 0.249959E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13605755.30 | 0.263669E+09 |
July | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14793402.16 | 0.180874E+09 |
August | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5759698.24 | 0.281868E+09 |
September | 0.205665E+10 | 0.244398E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187882.65 | 0.485115E+09 |
October | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694522E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122289E+10 |
December | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180255E+10 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.794328E+10 | 38595582.25 | 0.106988E+11 | ||||
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180874E+09 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14793402.16 | 0.180255E+10 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338478E+11 |
February | 0.00 | 0.102280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239547E+11 |
March | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218110E+11 |
April | 0.00 | 0.110076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117482E+11 |
May | 0.00 | 0.114539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1506657.52 | 0.434948E+10 |
June | 0.00 | 0.112581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26713916.47 | 0.184893E+10 |
July | 0.00 | 0.112035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11394694.03 | 0.107739E+10 |
August | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006182.19 | 0.171209E+10 |
September | 0.00 | 0.110076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527733E+10 |
October | 0.00 | 0.112411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114918E+11 |
November | 0.00 | 0.108701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182862E+11 |
December | 0.00 | 0.112035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324160E+11 |
Annual Sum or Average | 0.00 | 0.134048E+10 | 40621450.21 | 0.167821E+12 | |||||
Minimum of Months | 0.00 | 0.102280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107739E+10 |
Maximum of Months | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26713916.47 | 0.338478E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2030.36 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7946.81 | 04-JAN-06:00 |
February | 5888.82 | 01-FEB-15:09 | 2030.36 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9445.09 | 12-FEB-22:53 |
March | 5888.82 | 01-MAR-15:09 | 2030.36 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4781.69 | 15-MAR-04:52 |
April | 5888.82 | 01-APR-10:09 | 2030.36 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 296.21 | 23-APR-18:10 | 3988.33 | 01-APR-21:03 |
May | 5888.82 | 01-MAY-14:09 | 2030.36 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.15 | 24-MAY-15:00 | 2011.09 | 20-MAY-05:00 |
June | 5888.82 | 01-JUN-14:09 | 2030.36 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 422.83 | 29-JUN-20:03 | 1395.43 | 09-JUN-20:10 |
July | 5888.82 | 01-JUL-10:09 | 2030.36 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 456.82 | 23-JUL-18:03 | 1296.44 | 06-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 2030.36 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 230.45 | 08-AUG-16:00 | 1847.99 | 27-AUG-06:00 |
September | 5888.82 | 01-SEP-14:09 | 2030.36 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 01-SEP-15:00 | 2507.71 | 20-SEP-01:00 |
October | 5888.82 | 02-OCT-14:09 | 2030.36 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3263.34 | 31-OCT-20:05 |
November | 5888.82 | 01-NOV-14:09 | 2030.36 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5358.22 | 22-NOV-02:00 |
December | 5888.82 | 01-DEC-15:09 | 2030.36 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7660.45 | 16-DEC-05:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1296.44 | |||||
Maximum of Months | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 456.82 | 9445.09 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 22187.24 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6456.76 | 04-JAN-05:52 |
February | 24809.68 | 01-FEB-15:09 | 22187.24 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8458.11 | 12-FEB-22:53 |
March | 24809.68 | 01-MAR-15:09 | 22187.24 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4002.18 | 15-MAR-04:52 |
April | 24809.68 | 01-APR-10:09 | 22187.24 | 01-APR-16:19 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 193.36 | 23-APR-18:05 | 3615.95 | 02-APR-01:00 |
May | 24809.68 | 01-MAY-14:09 | 22187.24 | 01-MAY-15:30 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.89 | 24-MAY-15:00 | 1842.59 | 20-MAY-05:00 |
June | 24809.68 | 01-JUN-14:09 | 22187.24 | 08-JUN-16:10 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 344.71 | 29-JUN-20:03 | 1268.59 | 10-JUN-22:00 |
July | 24809.68 | 01-JUL-10:09 | 22187.24 | 06-JUL-16:00 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 373.34 | 23-JUL-18:03 | 1212.35 | 06-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 22187.24 | 02-AUG-15:50 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 | 08-AUG-16:00 | 1678.96 | 27-AUG-06:00 |
September | 24809.68 | 01-SEP-14:09 | 22187.24 | 01-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 | 01-SEP-15:00 | 2265.74 | 20-SEP-01:00 |
October | 24809.68 | 02-OCT-14:09 | 22187.24 | 02-OCT-08:09 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2941.37 | 31-OCT-21:00 |
November | 24809.68 | 01-NOV-14:09 | 22187.24 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5195.50 | 22-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 22187.24 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6375.03 | 16-DEC-05:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 22187.24 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1212.35 | |||||
Maximum of Months | 24809.68 | 22187.24 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 373.34 | 8458.11 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3416.29 | 04-JAN-05:52 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4091.39 | 12-FEB-23:00 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2082.05 | 15-MAR-04:52 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.89 | 23-APR-18:05 | 1737.63 | 01-APR-21:03 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.01 | 24-MAY-15:00 | 908.33 | 20-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 175.01 | 29-JUN-20:03 | 619.09 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 | 23-JUL-18:03 | 657.54 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.87 | 08-AUG-16:00 | 882.36 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 01-SEP-15:00 | 1124.93 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1422.48 | 31-OCT-20:13 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2418.46 | 22-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3342.13 | 16-DEC-05:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.09 | |||||
Maximum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 | 4091.39 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3443.59 | 04-JAN-06:00 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4098.86 | 12-FEB-22:55 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2082.06 | 15-MAR-04:52 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.84 | 23-APR-18:05 | 1731.54 | 01-APR-21:03 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 24-MAY-15:00 | 874.61 | 20-MAY-05:00 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 178.54 | 29-JUN-20:03 | 599.64 | 09-JUN-20:10 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 | 23-JUL-18:03 | 598.84 | 06-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.86 | 08-AUG-16:00 | 840.65 | 27-AUG-06:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 | 01-SEP-15:00 | 1074.52 | 20-SEP-01:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1413.35 | 31-OCT-20:05 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2306.38 | 22-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3314.38 | 16-DEC-05:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.84 | |||||
Maximum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 | 4098.86 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 94.16 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 65571.91 | 05-JAN-18:00 |
February | 0.00 | 01-FEB-00:10 | 94.16 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 57298.56 | 01-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 94.16 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 46466.14 | 15-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 94.16 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 35161.70 | 04-APR-11:02 |
May | 0.00 | 01-MAY-00:10 | 94.16 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.20 | 25-MAY-17:00 | 17630.88 | 01-MAY-11:05 |
June | 0.00 | 01-JUN-00:10 | 94.16 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 30-JUN-11:02 | 11486.27 | 09-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 94.16 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.70 | 15-JUL-13:55 | 9366.46 | 08-JUL-11:10 |
August | 0.00 | 01-AUG-00:10 | 94.16 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.86 | 08-AUG-16:00 | 11817.37 | 17-AUG-12:00 |
September | 0.00 | 01-SEP-00:10 | 94.16 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 16610.99 | 27-SEP-11:05 |
October | 0.00 | 01-OCT-00:10 | 94.16 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 26406.16 | 29-OCT-17:00 |
November | 0.00 | 01-NOV-00:10 | 94.16 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45558.46 | 25-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 94.16 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 63753.51 | 24-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9366.46 | ||||
Maximum of Months | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 65571.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7057.23 | 20-JAN-07:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.41 |
February | 7427.40 | 22-FEB-07:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7412.15 | 23-MAR-06:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8666.39 | 05-APR-06:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26719.28 | 26-MAY-06:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.63 |
June | 28702.05 | 22-JUN-06:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.89 |
July | 34230.69 | 01-JUL-06:02 | 3680.51 | 1127.98 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.95 |
August | 35185.23 | 25-AUG-06:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34265.37 | 02-SEP-06:02 | 3680.51 | 1127.98 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.16 |
October | 7832.47 | 30-OCT-06:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.59 |
November | 7851.75 | 23-NOV-09:05 | 2944.41 | 902.38 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.58 |
December | 6348.98 | 30-DEC-07:05 | 2944.41 | 902.38 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6348.98 | 2944.41 | 902.38 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35185.23 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 59658.45 | 25-JAN-07:05 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.34 |
February | 70315.53 | 24-FEB-07:05 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.93 |
March | 26512.56 | 16-MAR-06:03 | 18607.26 | 29582.98 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.38 |
April | 67187.51 | 23-APR-08:62 | 18607.26 | 14791.49 | 9305.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.02 |
May | 179759.70 | 17-MAY-06:03 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.75 |
June | 188842.03 | 17-JUN-06:02 | 15506.05 | 12326.24 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 |
July | 167807.69 | 08-JUL-06:02 | 15506.05 | 12326.24 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.92 |
August | 174032.35 | 25-AUG-06:02 | 15506.05 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 199011.97 | 09-SEP-06:02 | 15506.05 | 12326.24 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.92 |
October | 121039.53 | 20-OCT-06:02 | 15506.05 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.58 |
November | 24235.45 | 25-NOV-07:03 | 18607.26 | 14791.49 | 9305.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.10 |
December | 66177.41 | 02-DEC-07:05 | 12404.84 | 9860.99 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24235.45 | 12404.84 | 9860.99 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 199011.97 | 18607.26 | 29582.98 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1106.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9387.14 | 05-JAN-18:01 | 10227.71 | 8130.32 | 20446.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.12 |
February | 7259.04 | 11-FEB-07:03 | 1753.32 | 1393.77 | 5841.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6957.53 | 16-MAR-06:03 | 1753.32 | 2787.54 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.22 |
April | 7801.33 | 22-APR-13:30 | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.57 |
May | 24074.55 | 19-MAY-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
June | 22277.77 | 09-JUN-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.39 |
July | 23450.34 | 08-JUL-06:02 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.70 |
August | 24694.17 | 25-AUG-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25080.18 | 09-SEP-06:02 | 1461.10 | 1161.47 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.35 |
October | 24504.04 | 20-OCT-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 |
November | 6532.62 | 17-NOV-13:30 | 2045.54 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.24 |
December | 6754.83 | 08-DEC-07:03 | 1753.32 | 2787.54 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6532.62 | 1461.10 | 1161.47 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25080.18 | 10227.71 | 8130.32 | 20446.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6308.37 | 26-JAN-17:52 | 7305.51 | 10453.27 | 2192.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.85 |
February | 6961.40 | 25-FEB-10:32 | 8766.61 | 10453.27 | 2192.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.35 |
March | 6037.16 | 18-MAR-06:04 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5446.18 | 22-APR-13:30 | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.58 |
May | 19662.16 | 19-MAY-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 |
June | 17570.41 | 18-JUN-08:62 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.56 |
July | 18923.31 | 08-JUL-06:02 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.26 |
August | 19921.37 | 25-AUG-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20206.85 | 09-SEP-06:02 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.91 |
October | 16264.72 | 20-OCT-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 |
November | 5347.80 | 10-NOV-07:03 | 2045.54 | 3252.13 | 1363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.07 |
December | 5049.24 | 07-DEC-07:04 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5049.24 | 1461.10 | 1161.47 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20206.85 | 8766.61 | 10453.27 | 2192.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 10.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.86 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.40 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.83 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.06 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.96 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.68 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.81 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.10 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | |
Maximum of Months | 0.00 | 0.00 | 10.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.40 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.836231E+11 | 62619.94 | 04-JAN-17:00 | 0.168751E+12 | 317452.71 | 09-JAN-07:10 |
February | 0.737973E+11 | 60495.55 | 01-FEB-17:00 | 0.990698E+11 | 294207.68 | 14-FEB-07:10 |
March | 0.810669E+11 | 59809.52 | 06-MAR-17:00 | 0.699702E+11 | 202905.77 | 15-MAR-06:00 |
April | 0.752695E+11 | 60890.84 | 19-APR-14:00 | 0.247420E+11 | 91737.56 | 05-APR-06:10 |
May | 0.783569E+11 | 73017.56 | 25-MAY-14:00 | 0.989383E+10 | 37215.08 | 01-MAY-06:10 |
June | 0.822031E+11 | 83902.94 | 29-JUN-15:00 | 0.827973E+10 | 8492.35 | 02-JUN-11:00 |
July | 0.886148E+11 | 78962.60 | 15-JUL-14:00 | 0.824133E+10 | 6802.55 | 08-JUL-11:00 |
August | 0.868887E+11 | 79099.06 | 08-AUG-14:00 | 0.832229E+10 | 10567.53 | 17-AUG-13:00 |
September | 0.764344E+11 | 74158.24 | 01-SEP-13:50 | 0.893524E+10 | 15457.68 | 27-SEP-11:20 |
October | 0.797062E+11 | 63944.41 | 28-OCT-16:00 | 0.179149E+11 | 48549.14 | 30-OCT-06:10 |
November | 0.776063E+11 | 61719.24 | 17-NOV-16:30 | 0.483439E+11 | 150172.47 | 29-NOV-07:10 |
December | 0.832880E+11 | 62251.27 | 19-DEC-17:00 | 0.147318E+12 | 296237.19 | 24-DEC-09:09 |
Annual Sum or Average | 0.966855E+12 | 0.619782E+12 | ||||
Minimum of Months | 0.737973E+11 | 59809.52 | 0.824133E+10 | 6802.55 | ||
Maximum of Months | 0.886148E+11 | 83902.94 | 0.168751E+12 | 317452.71 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.337340E+11 | 0.682573E+10 | 0.164409E+11 | 0.00 | 0.245267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209584E+10 | 0.00 | 0.00 |
February | 0.305493E+11 | 0.552260E+10 | 0.149157E+11 | 0.00 | 0.209061E+11 | 0.00 | 0.00 | 41.34 | 0.00 | 0.00 | 0.190347E+10 | 0.00 | 0.00 |
March | 0.345835E+11 | 0.524222E+10 | 0.168545E+11 | 0.00 | 0.220949E+11 | 0.00 | 0.00 | 0.155367E+09 | 0.00 | 0.00 | 0.213634E+10 | 0.00 | 0.00 |
April | 0.322271E+11 | 0.419600E+10 | 0.160165E+11 | 0.00 | 0.191160E+11 | 0.00 | 0.00 | 0.197591E+10 | 0.00 | 0.00 | 0.173795E+10 | 0.00 | 0.00 |
May | 0.323257E+11 | 0.361922E+10 | 0.166477E+11 | 0.00 | 0.159460E+11 | 0.00 | 0.00 | 0.885730E+10 | 0.00 | 0.00 | 0.961015E+09 | 0.00 | 0.00 |
June | 0.318867E+11 | 0.313793E+10 | 0.162772E+11 | 0.00 | 0.133837E+11 | 0.00 | 0.00 | 0.168092E+11 | 0.00 | 0.00 | 0.708428E+09 | 0.00 | 0.00 |
July | 0.315804E+11 | 0.339196E+10 | 0.163871E+11 | 0.00 | 0.127347E+11 | 0.00 | 0.00 | 0.235990E+11 | 0.00 | 0.00 | 0.921612E+09 | 0.00 | 0.00 |
August | 0.335639E+11 | 0.398753E+10 | 0.168545E+11 | 0.00 | 0.133955E+11 | 0.00 | 0.00 | 0.185435E+11 | 0.00 | 0.00 | 0.543802E+09 | 0.00 | 0.00 |
September | 0.322649E+11 | 0.468913E+10 | 0.160165E+11 | 0.00 | 0.162551E+11 | 0.00 | 0.00 | 0.642762E+10 | 0.00 | 0.00 | 0.781088E+09 | 0.00 | 0.00 |
October | 0.334002E+11 | 0.575453E+10 | 0.164409E+11 | 0.00 | 0.192221E+11 | 0.00 | 0.00 | 0.310208E+10 | 0.00 | 0.00 | 0.178637E+10 | 0.00 | 0.00 |
November | 0.325847E+11 | 0.636578E+10 | 0.159174E+11 | 0.00 | 0.203970E+11 | 0.00 | 0.00 | 0.353476E+09 | 0.00 | 0.00 | 0.198784E+10 | 0.00 | 0.00 |
December | 0.336777E+11 | 0.703668E+10 | 0.163871E+11 | 0.00 | 0.240856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210090E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.392378E+12 | 0.597693E+11 | 0.195156E+12 | 0.222063E+12 | 0.00 | 0.798235E+11 | 0.176647E+11 | ||||||
Minimum of Months | 0.305493E+11 | 0.313793E+10 | 0.149157E+11 | 0.00 | 0.127347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543802E+09 | 0.00 | 0.00 |
Maximum of Months | 0.345835E+11 | 0.703668E+10 | 0.168545E+11 | 0.00 | 0.245267E+11 | 0.00 | 0.00 | 0.235990E+11 | 0.00 | 0.00 | 0.213634E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.159931E+12 | 0.00 | 0.881998E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.910107E+11 | 0.00 | 0.805907E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.609836E+11 | 0.00 | 0.898663E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.162161E+11 | 0.00 | 0.852586E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.127680E+10 | 0.00 | 0.861704E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 91400481.72 | 0.00 | 0.818833E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 25675858.14 | 0.00 | 0.821565E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.100384E+09 | 0.00 | 0.822191E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.100153E+10 | 0.00 | 0.793371E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.962887E+10 | 0.00 | 0.828599E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.401579E+11 | 0.00 | 0.818599E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.138650E+12 | 0.00 | 0.866793E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.519074E+12 | 0.100708E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 25675858.14 | 0.00 | 0.793371E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.159931E+12 | 0.00 | 0.898663E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28493.07 | 02-JAN-09:09 | 4566.05 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 19600.14 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28493.07 | 01-FEB-09:09 | 4566.05 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 18416.39 | 17-FEB-07:40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28493.07 | 01-MAR-09:09 | 4566.05 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 17187.92 | 15-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28493.07 | 01-APR-16:19 | 4566.05 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 14888.41 | 05-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28493.07 | 01-MAY-15:30 | 4566.05 | 01-MAY-19:30 | 10771.04 | 01-MAY-08:09 | 0.00 | 14259.74 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28493.07 | 08-JUN-16:10 | 4566.05 | 01-JUN-19:00 | 10771.04 | 01-JUN-08:09 | 0.00 | 14039.96 | 02-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28493.07 | 06-JUL-16:00 | 4566.05 | 01-JUL-20:19 | 10771.04 | 01-JUL-09:09 | 0.00 | 14039.96 | 01-JUL-12:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28493.07 | 02-AUG-15:50 | 4566.05 | 01-AUG-19:49 | 10771.04 | 01-AUG-08:09 | 0.00 | 14039.96 | 03-AUG-12:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28493.07 | 01-SEP-08:09 | 4566.05 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 14039.96 | 25-SEP-13:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28493.07 | 02-OCT-08:09 | 4566.05 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 14523.92 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28493.07 | 01-NOV-08:09 | 4566.05 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 16181.54 | 26-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28493.07 | 01-DEC-09:09 | 4566.05 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 19503.12 | 24-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 28493.07 | 4566.05 | 10771.04 | 0.00 | 14039.96 | 0.00 | 0.00 | |||||
Maximum of Months | 28493.07 | 4566.05 | 10771.04 | 0.00 | 19600.14 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 1406.23 | 02-JAN-07:19 | 0.00 | 0.00 |
February | 0.04 | 08-FEB-13:50 | 0.00 | 0.00 | 1406.23 | 01-FEB-07:30 | 0.00 | 0.00 |
March | 3812.89 | 31-MAR-14:00 | 0.00 | 0.00 | 1406.23 | 01-MAR-07:19 | 0.00 | 0.00 |
April | 14206.58 | 23-APR-15:00 | 0.00 | 0.00 | 1406.23 | 01-APR-06:30 | 0.00 | 0.00 |
May | 26160.98 | 25-MAY-14:00 | 0.00 | 0.00 | 1406.23 | 01-MAY-06:30 | 0.00 | 0.00 |
June | 36316.51 | 29-JUN-15:00 | 0.00 | 0.00 | 1406.23 | 01-JUN-07:19 | 0.00 | 0.00 |
July | 33368.17 | 15-JUL-14:09 | 0.00 | 0.00 | 1406.23 | 08-JUL-07:30 | 0.00 | 0.00 |
August | 31879.91 | 08-AUG-14:00 | 0.00 | 0.00 | 1406.23 | 02-AUG-07:30 | 0.00 | 0.00 |
September | 26243.25 | 01-SEP-11:50 | 0.00 | 0.00 | 1406.23 | 01-SEP-17:10 | 0.00 | 0.00 |
October | 13092.59 | 19-OCT-14:00 | 0.00 | 0.00 | 1406.23 | 01-OCT-08:20 | 0.00 | 0.00 |
November | 4966.95 | 21-NOV-13:00 | 0.00 | 0.00 | 1406.23 | 01-NOV-06:49 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 1406.23 | 01-DEC-07:49 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 1406.23 | 0.00 | 0.00 | ||
Maximum of Months | 36316.51 | 0.00 | 0.00 | 1406.23 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 62619.94 | 04-JAN-17:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 17383.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60495.55 | 01-FEB-17:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 15259.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59809.52 | 06-MAR-17:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 14573.14 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60890.84 | 19-APR-14:00 | 28493.07 | 10771.04 | 0.00 | 0.00 | 14039.96 | 0.00 | 0.00 | 6180.55 | 0.00 |
May | 73017.56 | 25-MAY-14:00 | 27218.04 | 10771.04 | 0.00 | 0.00 | 7461.27 | 0.00 | 0.00 | 26160.98 | 0.00 |
June | 83902.94 | 29-JUN-15:00 | 27218.04 | 10771.04 | 0.00 | 0.00 | 8191.12 | 0.00 | 0.00 | 36316.51 | 0.00 |
July | 78962.60 | 15-JUL-14:00 | 25943.02 | 10771.04 | 0.00 | 0.00 | 7905.21 | 0.00 | 0.00 | 32937.11 | 0.00 |
August | 79099.06 | 08-AUG-14:00 | 27218.04 | 10771.04 | 0.00 | 0.00 | 7823.84 | 0.00 | 0.00 | 31879.91 | 0.00 |
September | 74158.24 | 01-SEP-13:50 | 28493.07 | 10771.04 | 0.00 | 0.00 | 7685.52 | 0.00 | 0.00 | 25802.39 | 0.00 |
October | 63944.41 | 28-OCT-16:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 14039.96 | 0.00 | 0.00 | 4668.07 | 0.00 |
November | 61719.24 | 17-NOV-16:30 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 14039.96 | 0.00 | 0.00 | 2442.90 | 0.00 |
December | 62251.27 | 19-DEC-17:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 17014.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 59809.52 | 25943.02 | 10771.04 | 0.00 | 0.00 | 7461.27 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83902.94 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 17383.56 | 0.00 | 0.00 | 36316.51 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 312863.61 | 09-JAN-07:10 | 0.00 | 6247.18 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 292345.68 | 14-FEB-07:10 | 0.00 | 6349.28 | 24-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 198311.64 | 15-MAR-06:00 | 0.00 | 6346.44 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 89875.56 | 05-APR-06:10 | 0.00 | 6125.91 | 05-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 32630.13 | 01-MAY-06:10 | 0.00 | 5651.16 | 05-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 3343.98 | 02-JUN-11:00 | 0.00 | 5148.45 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 1754.55 | 08-JUL-11:00 | 0.00 | 5095.15 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 5659.47 | 17-AUG-13:00 | 0.00 | 5061.72 | 01-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 10392.33 | 27-SEP-11:20 | 0.00 | 5069.05 | 29-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 46687.14 | 30-OCT-06:10 | 0.00 | 5115.75 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 147937.83 | 25-NOV-07:10 | 0.00 | 5314.97 | 29-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 294375.19 | 24-DEC-09:09 | 0.00 | 5842.51 | 27-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 1754.55 | 0.00 | 5061.72 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 312863.61 | 0.00 | 6349.28 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 16.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.83 | 16.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.50 | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5.17 | 16.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.83 | 16.39 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 17.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 16.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.00 | 16.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 16.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.33 | 16.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11.83 | 16.44 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 16.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.83 | 16.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.17 | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7.00 | 16.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.83 | 16.28 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 17.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 20.47 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 414.00 | 21.11 | 414.00 | 21.11 |
February | 376.00 | 21.11 | 376.00 | 21.11 | 376.00 | 21.11 |
March | 422.00 | 21.11 | 394.83 | 21.11 | 394.83 | 21.11 |
April | 405.00 | 21.66 | 189.00 | 21.11 | 189.00 | 21.11 |
May | 307.17 | 23.14 | 37.67 | 23.28 | 8.33 | 21.13 |
June | 185.50 | 23.71 | 150.17 | 23.89 | 64.50 | 23.88 |
July | 75.00 | 23.84 | 280.67 | 23.89 | 62.17 | 23.89 |
August | 67.00 | 23.78 | 262.83 | 23.89 | 45.67 | 23.89 |
September | 284.83 | 23.46 | 54.17 | 23.89 | 17.67 | 23.89 |
October | 414.00 | 22.09 | 40.67 | 21.12 | 40.67 | 21.12 |
November | 399.00 | 21.19 | 297.17 | 21.11 | 297.17 | 21.11 |
December | 415.00 | 21.11 | 415.00 | 21.11 | 415.00 | 21.11 |
Annual Sum or Average | 3764.50 | 21.86 | 2912.17 | 21.85 | 2325.00 | 21.34 |
Minimum of Months | 67.00 | 21.11 | 37.67 | 21.11 | 8.33 | 21.11 |
Maximum of Months | 422.00 | 23.84 | 415.00 | 23.89 | 415.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.14 | 372.33 | 21.11 | 372.33 | 21.11 |
February | 376.00 | 21.35 | 254.00 | 21.11 | 254.00 | 21.11 |
March | 422.00 | 21.89 | 140.33 | 21.11 | 140.33 | 21.11 |
April | 365.50 | 23.27 | 6.17 | 21.11 | 6.17 | 21.11 |
May | 121.50 | 23.76 | 102.17 | 23.89 | 0.00 | 0.00 |
June | 55.33 | 23.89 | 270.00 | 23.89 | 41.83 | 23.89 |
July | 34.83 | 23.89 | 395.17 | 23.89 | 34.83 | 23.89 |
August | 18.33 | 23.88 | 383.50 | 23.89 | 17.50 | 23.89 |
September | 51.17 | 23.84 | 123.50 | 23.89 | 10.50 | 23.89 |
October | 258.00 | 23.47 | 6.17 | 23.89 | 0.00 | 0.00 |
November | 388.67 | 22.28 | 71.83 | 21.11 | 71.83 | 21.11 |
December | 415.00 | 21.15 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2920.33 | 22.16 | 2463.17 | 22.56 | 1287.33 | 21.34 |
Minimum of Months | 18.33 | 21.14 | 6.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.89 | 395.17 | 23.89 | 372.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 358.83 | 21.11 | 358.83 | 21.11 |
February | 374.67 | 21.32 | 229.33 | 21.11 | 229.33 | 21.11 |
March | 412.67 | 21.47 | 190.00 | 21.11 | 190.00 | 21.11 |
April | 329.50 | 22.19 | 56.33 | 21.63 | 45.83 | 21.11 |
May | 138.33 | 23.17 | 118.67 | 23.84 | 2.00 | 21.11 |
June | 60.33 | 23.71 | 285.17 | 23.89 | 30.00 | 23.89 |
July | 29.17 | 23.87 | 398.33 | 23.89 | 27.00 | 23.90 |
August | 11.50 | 23.56 | 393.33 | 23.89 | 6.67 | 23.89 |
September | 69.17 | 23.14 | 223.83 | 23.89 | 6.33 | 23.89 |
October | 265.50 | 22.28 | 64.50 | 23.69 | 4.67 | 21.11 |
November | 385.83 | 21.60 | 130.00 | 21.11 | 130.00 | 21.11 |
December | 415.00 | 21.11 | 369.83 | 21.11 | 369.83 | 21.11 |
Annual Sum or Average | 2905.67 | 21.72 | 2818.17 | 22.58 | 1400.50 | 21.25 |
Minimum of Months | 11.50 | 21.11 | 56.33 | 21.11 | 2.00 | 21.11 |
Maximum of Months | 415.00 | 23.87 | 398.33 | 23.89 | 369.83 | 23.90 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.11 | 389.00 | 21.11 | 389.00 | 21.11 |
February | 376.00 | 21.20 | 270.50 | 21.11 | 270.50 | 21.11 |
March | 421.17 | 21.29 | 251.33 | 21.11 | 251.33 | 21.11 |
April | 363.83 | 21.90 | 86.17 | 21.29 | 80.67 | 21.11 |
May | 205.17 | 22.96 | 94.67 | 23.75 | 4.83 | 21.10 |
June | 126.50 | 23.65 | 237.50 | 23.89 | 63.50 | 23.89 |
July | 69.67 | 23.84 | 383.83 | 23.89 | 61.00 | 23.89 |
August | 51.67 | 23.73 | 361.50 | 23.89 | 42.00 | 23.89 |
September | 133.33 | 22.95 | 156.17 | 23.89 | 14.17 | 23.89 |
October | 318.50 | 21.85 | 56.50 | 22.80 | 22.17 | 21.11 |
November | 396.17 | 21.34 | 183.00 | 21.11 | 183.00 | 21.11 |
December | 415.00 | 21.11 | 395.00 | 21.11 | 395.00 | 21.11 |
Annual Sum or Average | 3291.00 | 21.72 | 2865.17 | 22.34 | 1777.17 | 21.39 |
Minimum of Months | 51.67 | 21.11 | 56.50 | 21.11 | 4.83 | 21.10 |
Maximum of Months | 421.17 | 23.84 | 395.00 | 23.89 | 395.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09493 | 14.57410 | -0.8117 | 19.05607 |
February | 376.00000 | 21.09539 | 16.42792 | -0.7667 | 17.56303 |
March | 422.00000 | 21.09965 | 20.69305 | -0.6960 | 15.42793 |
April | 405.00000 | 21.64977 | 25.07971 | -0.4476 | 10.37842 |
May | 418.00000 | 23.33339 | 35.81705 | -0.8950 | 24.04469 |
June | 408.00000 | 23.80879 | 48.72574 | -0.5796 | 12.66231 |
July | 415.00000 | 23.89018 | 53.95642 | -0.4590 | 9.55360 |
August | 422.00000 | 23.87770 | 53.51517 | -0.4882 | 10.16862 |
September | 405.00000 | 23.58183 | 42.79249 | -0.7315 | 17.23686 |
October | 414.00000 | 22.08304 | 34.73022 | -0.2293 | 7.62292 |
November | 399.00000 | 21.17869 | 24.24854 | -0.6012 | 13.14799 |
December | 415.00000 | 21.09526 | 15.99474 | -0.7829 | 18.10627 |
Annual Sum or Average | 4913.00000 | 22.32717 | 32.35284 | -0.6233 | 14.56880 |
Minimum of Months | 376.00000 | 21.09493 | 14.57410 | -0.8950 | 7.62292 |
Maximum of Months | 422.00000 | 23.89018 | 53.95642 | -0.2293 | 24.04469 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.12448 | 17.11993 | -0.6505 | 14.11394 |
February | 376.00000 | 21.33668 | 20.02621 | -0.5471 | 11.83972 |
March | 422.00000 | 21.88080 | 24.82396 | -0.3586 | 9.14590 |
April | 405.00000 | 23.32268 | 26.35520 | 0.05823 | 6.11845 |
May | 418.00000 | 23.86147 | 34.02539 | -0.5789 | 12.54434 |
June | 408.00000 | 23.90501 | 45.93832 | -0.4297 | 9.09480 |
July | 415.00000 | 23.91027 | 50.91214 | -0.3638 | 7.86323 |
August | 422.00000 | 23.90867 | 51.06280 | -0.3809 | 8.13842 |
September | 405.00000 | 23.89315 | 40.75528 | -0.5150 | 10.74671 |
October | 414.00000 | 23.63052 | 34.48876 | 0.20184 | 6.37929 |
November | 399.00000 | 22.31578 | 27.62491 | -0.2233 | 7.91971 |
December | 415.00000 | 21.13901 | 19.14373 | -0.6182 | 13.28005 |
Annual Sum or Average | 4913.00000 | 22.86251 | 32.80293 | -0.3669 | 9.75961 |
Minimum of Months | 376.00000 | 21.12448 | 17.11993 | -0.6505 | 6.11845 |
Maximum of Months | 422.00000 | 23.91027 | 51.06280 | 0.20184 | 14.11394 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09555 | 10.80845 | -0.6929 | 15.46805 |
February | 376.00000 | 21.31360 | 12.70812 | -0.5539 | 12.64464 |
March | 422.00000 | 21.51212 | 16.54722 | -0.4544 | 11.06774 |
April | 405.00000 | 22.49642 | 19.97093 | -0.1247 | 7.79874 |
May | 418.00000 | 23.65389 | 31.76120 | -0.6189 | 14.79960 |
June | 408.00000 | 23.87297 | 45.23082 | -0.4097 | 9.02829 |
July | 415.00000 | 23.90672 | 50.10639 | -0.3039 | 7.12337 |
August | 422.00000 | 23.89733 | 49.24919 | -0.3125 | 7.33608 |
September | 405.00000 | 23.76721 | 38.61149 | -0.4801 | 10.83603 |
October | 414.00000 | 22.85706 | 29.12893 | 0.05602 | 7.40827 |
November | 399.00000 | 21.66920 | 20.33761 | -0.3811 | 9.93860 |
December | 415.00000 | 21.09599 | 12.32136 | -0.6897 | 15.32400 |
Annual Sum or Average | 4913.00000 | 22.60523 | 28.20209 | -0.4133 | 10.72453 |
Minimum of Months | 376.00000 | 21.09555 | 10.80845 | -0.6929 | 7.12337 |
Maximum of Months | 422.00000 | 23.90672 | 50.10639 | 0.05602 | 15.46805 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.09539 | 10.78449 | -0.7335 | 16.65953 |
February | 376.00000 | 21.18560 | 12.75643 | -0.6235 | 13.94648 |
March | 422.00000 | 21.28602 | 16.72813 | -0.5461 | 12.32186 |
April | 405.00000 | 22.09307 | 20.59572 | -0.2483 | 8.66869 |
May | 418.00000 | 23.43185 | 32.97908 | -0.7403 | 18.96238 |
June | 408.00000 | 23.82105 | 47.31586 | -0.4732 | 10.45261 |
July | 415.00000 | 23.89716 | 53.10185 | -0.3444 | 7.73001 |
August | 422.00000 | 23.88325 | 52.10594 | -0.3571 | 8.05187 |
September | 405.00000 | 23.58066 | 40.07958 | -0.5857 | 13.88954 |
October | 414.00000 | 22.32547 | 30.27718 | -0.0920 | 7.75086 |
November | 399.00000 | 21.35121 | 20.74042 | -0.4908 | 11.25316 |
December | 415.00000 | 21.09557 | 12.29748 | -0.7308 | 16.52666 |
Annual Sum or Average | 4913.00000 | 22.43149 | 29.29446 | -0.4966 | 12.17811 |
Minimum of Months | 376.00000 | 21.09539 | 10.78449 | -0.7403 | 7.73001 |
Maximum of Months | 422.00000 | 23.89716 | 53.10185 | -0.0920 | 18.96238 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 27552830.39 | 8058055.55 | 11.67 | 23895252.43 | 3657577.96 | 0.00 | 0.25 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 3152.08 | 23-APR-16:00 | 2714.72 | 23-APR-16:00 | 437.37 | 23-APR-16:00 | 915.55 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.263934E+10 | 0.682629E+09 | 186.47 | 0.218930E+10 | 0.450036E+09 | 0.00 | 1.00 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 | 32243.04 | 26-MAY-06:02 | 22307.39 | 26-MAY-06:02 | 9935.65 | 26-MAY-06:02 | 6856.85 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.726995E+10 | 0.180361E+10 | 298.77 | 0.533848E+10 | 0.193147E+10 | 0.00 | 1.00 | 22-JUN-06:02 | 0.00 | 01-JUN-00:10 | 35288.91 | 30-JUN-06:02 | 20223.70 | 29-JUN-06:02 | 16062.32 | 30-JUN-06:15 | 7623.61 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.117236E+11 | 0.283277E+10 | 362.84 | 0.811687E+10 | 0.360670E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 35224.08 | 30-JUL-08:62 | 21705.94 | 06-JUL-06:02 | 18258.03 | 05-JUL-06:02 | 7465.75 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.827164E+10 | 0.200680E+10 | 335.04 | 0.567302E+10 | 0.259862E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 33580.16 | 30-AUG-06:02 | 19119.36 | 08-AUG-06:02 | 17218.51 | 30-AUG-06:02 | 7074.05 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.116647E+10 | 0.297204E+09 | 171.68 | 0.916032E+09 | 0.250435E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 32767.15 | 01-SEP-06:02 | 21172.63 | 02-SEP-06:02 | 16452.72 | 01-SEP-06:02 | 6950.08 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 35427115.59 | 9754090.45 | 24.60 | 33736118.07 | 1690997.53 | 0.00 | 0.22 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2707.05 | 19-OCT-15:00 | 2541.06 | 19-OCT-15:00 | 184.89 | 19-OCT-14:20 | 739.13 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.311339E+11 | 0.764082E+10 | 1391.07 | 0.222913E+11 | 0.884261E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.117236E+11 | 0.283277E+10 | 362.84 | 0.811687E+10 | 0.360670E+10 | 0.00 | 1.00 | 0.00 | 35288.91 | 22307.39 | 18258.03 | 7623.61 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.506565E+09 | 0.155365E+09 | 27.33 | 0.488897E+09 | 17668028.38 | 0.00 | 0.22 | 31-MAR-15:00 | 0.00 | 01-MAR-00:10 | 12750.05 | 31-MAR-15:00 | 12514.56 | 31-MAR-15:00 | 617.38 | 28-MAR-16:00 | 3812.74 | 31-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 0.599483E+10 | 0.180153E+10 | 207.19 | 0.573750E+10 | 0.257338E+09 | 0.00 | 0.53 | 23-APR-08:62 | 0.00 | 01-APR-00:10 | 34136.03 | 24-APR-06:03 | 31061.79 | 23-APR-08:62 | 5234.38 | 23-APR-16:00 | 10175.84 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.237908E+11 | 0.682895E+10 | 349.04 | 0.201806E+11 | 0.361026E+10 | 0.00 | 1.00 | 18-MAY-06:02 | 0.00 | 01-MAY-00:10 | 160754.78 | 26-MAY-06:02 | 122249.96 | 19-MAY-06:02 | 49330.45 | 27-MAY-06:02 | 38201.91 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.437606E+11 | 0.121735E+11 | 362.76 | 0.322446E+11 | 0.115160E+11 | 0.00 | 1.00 | 07-JUN-06:02 | 0.00 | 01-JUN-00:10 | 173577.92 | 25-JUN-08:62 | 138683.74 | 18-JUN-08:62 | 81402.51 | 23-JUN-06:04 | 42042.83 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.607426E+11 | 0.165852E+11 | 385.84 | 0.420915E+11 | 0.186512E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 176653.18 | 30-JUL-08:62 | 108212.75 | 06-JUL-06:02 | 86915.31 | 30-JUL-08:04 | 41606.31 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.480946E+11 | 0.130950E+11 | 377.49 | 0.327371E+11 | 0.153575E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 167743.42 | 30-AUG-06:02 | 113908.71 | 20-AUG-08:62 | 83856.66 | 30-AUG-06:04 | 39455.06 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.174832E+11 | 0.502148E+10 | 321.37 | 0.140973E+11 | 0.338592E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 163272.78 | 01-SEP-06:02 | 140312.81 | 09-SEP-06:02 | 78125.87 | 01-SEP-06:02 | 38701.56 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.943952E+10 | 0.280918E+10 | 254.83 | 0.844592E+10 | 0.993603E+09 | 0.00 | 0.95 | 22-OCT-08:62 | 0.00 | 01-OCT-00:10 | 77676.32 | 20-OCT-06:02 | 51881.53 | 20-OCT-06:02 | 25794.79 | 20-OCT-06:02 | 18400.79 | 20-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.115608E+10 | 0.353421E+09 | 56.50 | 0.100292E+10 | 0.153156E+09 | 0.00 | 0.26 | 21-NOV-14:00 | 0.00 | 01-NOV-00:10 | 16755.45 | 21-NOV-14:00 | 12225.13 | 01-NOV-10:50 | 4986.05 | 21-NOV-14:00 | 4966.74 | 21-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.210969E+12 | 0.588236E+11 | 2342.35 | 0.157026E+12 | 0.539426E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.607426E+11 | 0.165852E+11 | 385.84 | 0.420915E+11 | 0.186512E+11 | 0.00 | 1.00 | 0.00 | 176653.18 | 140312.81 | 86915.31 | 42042.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 146.25 | 41.34 | 0.33 | 146.25 | 0.00 | 0.00 | 0.00 | 08-FEB-13:50 | 0.00 | 01-FEB-00:10 | 0.12 | 08-FEB-13:50 | 0.12 | 08-FEB-13:50 | 0.00 | 08-FEB-15:10 | 0.04 | 08-FEB-13:50 | 0.00 | 01-FEB-00:10 |
March | 4771.69 | 1348.78 | 8.49 | 4771.69 | 0.00 | 0.00 | 0.00 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.56 | 31-MAR-14:10 | 0.56 | 31-MAR-14:10 | 0.00 | 31-MAR-12:50 | 0.16 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.491006E+09 | 0.123972E+09 | 89.21 | 0.470049E+09 | 20957132.26 | 0.00 | 0.84 | 23-APR-13:40 | 0.00 | 01-APR-00:10 | 8295.61 | 23-APR-13:40 | 7327.85 | 23-APR-14:00 | 1052.83 | 23-APR-13:30 | 1941.06 | 23-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.358625E+10 | 0.872140E+09 | 266.78 | 0.314200E+10 | 0.444245E+09 | 0.00 | 1.00 | 18-MAY-06:02 | 0.00 | 01-MAY-00:10 | 21226.77 | 26-MAY-06:02 | 16782.06 | 19-MAY-06:02 | 6338.40 | 26-MAY-06:02 | 4513.69 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.738843E+10 | 0.176708E+10 | 334.35 | 0.565535E+10 | 0.173308E+10 | 0.00 | 1.00 | 07-JUN-06:02 | 0.00 | 01-JUN-00:10 | 23566.18 | 30-JUN-05:03 | 19241.25 | 18-JUN-08:62 | 10896.11 | 30-JUN-05:03 | 5007.91 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.109529E+11 | 0.255058E+10 | 383.31 | 0.792908E+10 | 0.302378E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 23379.75 | 30-JUL-08:62 | 14514.98 | 06-JUL-06:02 | 11873.62 | 05-JUL-06:02 | 4916.06 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.940162E+10 | 0.215921E+10 | 369.28 | 0.673650E+10 | 0.266512E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 22087.98 | 30-AUG-06:02 | 15233.99 | 20-AUG-08:62 | 11082.59 | 30-AUG-06:02 | 4653.21 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.321165E+10 | 0.758487E+09 | 247.07 | 0.270854E+10 | 0.503104E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 21521.82 | 01-SEP-06:02 | 16657.46 | 09-SEP-06:02 | 10490.93 | 01-SEP-06:02 | 4566.31 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.840528E+09 | 0.197453E+09 | 101.73 | 0.772912E+09 | 67615146.17 | 0.00 | 1.00 | 19-OCT-14:10 | 0.00 | 01-OCT-00:10 | 16060.89 | 20-OCT-06:02 | 11167.81 | 20-OCT-06:02 | 4893.08 | 20-OCT-06:02 | 3401.36 | 20-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 191945.75 | 54286.13 | 11.91 | 147566.26 | 44379.49 | 0.00 | 0.02 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 179.53 | 01-NOV-15:00 | 136.97 | 01-NOV-15:00 | 42.56 | 01-NOV-15:00 | 50.71 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.358725E+11 | 0.842897E+10 | 1812.45 | 0.274146E+11 | 0.845795E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.109529E+11 | 0.255058E+10 | 383.31 | 0.792908E+10 | 0.302378E+10 | 0.00 | 1.00 | 0.00 | 23566.18 | 19241.25 | 11873.62 | 5007.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 485.71 | 119.71 | 1.17 | 485.71 | 0.00 | 0.00 | 0.00 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.18 | 31-MAR-14:10 | 0.18 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 | 0.04 | 31-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.187658E+09 | 42350293.43 | 51.54 | 0.175961E+09 | 11697166.54 | 0.00 | 0.74 | 23-APR-14:00 | 0.00 | 01-APR-00:10 | 6371.70 | 23-APR-14:00 | 5738.30 | 23-APR-14:00 | 692.18 | 23-APR-13:40 | 1356.28 | 23-APR-14:10 | 0.00 | 01-APR-00:10 |
May | 0.218068E+10 | 0.473585E+09 | 209.35 | 0.192312E+10 | 0.257556E+09 | 0.00 | 1.00 | 18-MAY-06:02 | 0.00 | 01-MAY-00:10 | 17644.68 | 26-MAY-06:02 | 13636.62 | 19-MAY-06:02 | 5489.98 | 26-MAY-06:02 | 3461.74 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.498235E+10 | 0.106503E+10 | 294.42 | 0.383331E+10 | 0.114904E+10 | 0.00 | 1.00 | 07-JUN-06:02 | 0.00 | 01-JUN-00:10 | 19167.91 | 30-JUN-06:02 | 15622.85 | 18-JUN-08:62 | 9238.76 | 23-JUN-06:02 | 3843.19 | 30-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.786476E+10 | 0.163044E+10 | 359.76 | 0.570209E+10 | 0.216266E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 19423.83 | 30-JUL-08:62 | 11822.41 | 06-JUL-06:02 | 9985.58 | 05-JUL-06:02 | 3768.98 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.625284E+10 | 0.128253E+10 | 331.79 | 0.457036E+10 | 0.168248E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 18382.13 | 30-AUG-06:02 | 12405.56 | 20-AUG-08:62 | 9407.89 | 30-AUG-06:02 | 3571.11 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.165451E+10 | 0.350448E+09 | 189.45 | 0.143384E+10 | 0.220664E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 17935.12 | 01-SEP-06:02 | 12875.41 | 09-SEP-06:02 | 9008.38 | 01-SEP-06:02 | 3509.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.407282E+09 | 85690813.53 | 55.88 | 0.384586E+09 | 22695721.10 | 0.00 | 0.86 | 19-OCT-14:20 | 0.00 | 01-OCT-00:10 | 7586.17 | 19-OCT-14:20 | 7279.31 | 19-OCT-14:30 | 1835.30 | 20-OCT-06:02 | 1492.35 | 19-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 1689.44 | 416.41 | 3.62 | 1685.76 | 3.68 | 0.00 | 0.00 | 17-NOV-13:00 | 0.00 | 01-NOV-00:10 | 0.29 | 17-NOV-13:00 | 0.29 | 17-NOV-13:00 | 0.00 | 01-NOV-13:00 | 0.07 | 17-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.235301E+11 | 0.493008E+10 | 1496.99 | 0.180233E+11 | 0.550680E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.786476E+10 | 0.163044E+10 | 359.76 | 0.570209E+10 | 0.216266E+10 | 0.00 | 1.00 | 0.00 | 19423.83 | 15622.85 | 9985.58 | 3843.19 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.00 | 11.36 | 1.75 | 88.29 | 0.00 | 0.00 | 744.00 |
February | 30.87 | 14.15 | 16.72 | 15.32 | 70.73 | 0.00 | 0.00 | 672.00 |
March | 44.05 | 24.68 | 19.38 | 31.81 | 55.87 | 0.00 | 0.00 | 744.00 |
April | 65.17 | 41.09 | 24.08 | 62.30 | 38.44 | 0.00 | 0.00 | 720.00 |
May | 80.07 | 45.10 | 34.97 | 89.61 | 22.98 | 0.00 | 0.00 | 744.00 |
June | 84.25 | 48.56 | 35.69 | 99.66 | 17.02 | 0.00 | 0.00 | 720.00 |
July | 86.48 | 51.71 | 34.77 | 104.85 | 16.08 | 0.00 | 0.00 | 744.00 |
August | 68.10 | 38.22 | 29.88 | 79.80 | 17.76 | 0.00 | 0.00 | 744.00 |
September | 49.30 | 25.28 | 24.02 | 50.96 | 26.43 | 0.00 | 0.00 | 720.00 |
October | 29.25 | 11.56 | 17.69 | 21.36 | 40.20 | 0.00 | 0.00 | 744.00 |
November | 16.90 | 5.04 | 11.85 | 5.43 | 56.95 | 0.00 | 0.00 | 720.00 |
December | 13.56 | 3.45 | 10.11 | 0.39 | 86.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 48.87 | 26.30 | 22.58 | 47.11 | 44.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.56 | 3.45 | 10.11 | 0.39 | 16.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 86.48 | 51.71 | 35.69 | 104.85 | 88.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1552.49 | 1078.30 | 474.20 | 1301.14 | 1335.51 | 0.00 | 0.00 | 744.00 |
February | 1969.50 | 1329.11 | 640.39 | 1786.14 | 1133.15 | 0.00 | 0.00 | 672.00 |
March | 1741.14 | 1102.86 | 638.28 | 1497.17 | 951.63 | 0.00 | 0.00 | 744.00 |
April | 1580.59 | 860.44 | 720.15 | 1330.79 | 643.00 | 0.00 | 0.00 | 720.00 |
May | 1329.23 | 457.74 | 871.48 | 1113.42 | 376.46 | 0.00 | 0.00 | 744.00 |
June | 1192.76 | 321.29 | 871.47 | 1042.24 | 261.95 | 0.00 | 0.00 | 720.00 |
July | 1304.40 | 416.88 | 887.52 | 1194.51 | 247.15 | 0.00 | 0.00 | 744.00 |
August | 1392.11 | 585.10 | 807.01 | 1337.22 | 292.48 | 0.00 | 0.00 | 744.00 |
September | 1489.37 | 794.77 | 694.61 | 1437.88 | 456.24 | 0.00 | 0.00 | 720.00 |
October | 1268.94 | 746.32 | 522.62 | 1162.35 | 660.86 | 0.00 | 0.00 | 744.00 |
November | 1126.99 | 706.05 | 420.95 | 983.61 | 884.10 | 0.00 | 0.00 | 720.00 |
December | 1198.51 | 784.29 | 414.22 | 931.61 | 1288.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1425.28 | 761.66 | 663.62 | 1256.19 | 709.11 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1126.99 | 321.29 | 414.22 | 931.61 | 247.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1969.50 | 1329.11 | 887.52 | 1786.14 | 1335.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1552.49 | 1078.30 | 474.20 | 1296.72 | 1332.48 | 0.00 | 0.00 | 744.00 |
February | 1969.50 | 1329.11 | 640.39 | 1783.47 | 1124.53 | 0.00 | 0.00 | 672.00 |
March | 1741.14 | 1102.86 | 638.28 | 1496.38 | 939.52 | 0.00 | 0.00 | 744.00 |
April | 1580.59 | 860.44 | 720.15 | 1331.89 | 626.40 | 0.00 | 0.00 | 720.00 |
May | 1329.23 | 457.74 | 871.48 | 1111.80 | 362.72 | 0.00 | 0.00 | 744.00 |
June | 1192.76 | 321.29 | 871.47 | 1037.36 | 251.76 | 0.00 | 0.00 | 720.00 |
July | 1304.40 | 416.88 | 887.52 | 1188.04 | 237.87 | 0.00 | 0.00 | 744.00 |
August | 1392.11 | 585.10 | 807.01 | 1330.60 | 283.33 | 0.00 | 0.00 | 744.00 |
September | 1489.37 | 794.77 | 694.61 | 1434.57 | 444.19 | 0.00 | 0.00 | 720.00 |
October | 1268.94 | 746.32 | 522.62 | 1164.64 | 641.04 | 0.00 | 0.00 | 744.00 |
November | 1126.99 | 706.05 | 420.95 | 983.92 | 869.57 | 0.00 | 0.00 | 720.00 |
December | 1198.51 | 784.29 | 414.22 | 928.11 | 1285.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1425.28 | 761.66 | 663.62 | 1253.63 | 698.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1126.99 | 321.29 | 414.22 | 928.11 | 237.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1969.50 | 1329.11 | 887.52 | 1783.47 | 1332.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 319.45 | 221.88 | 97.57 | 259.67 | 278.24 | 0.00 | 0.00 | 744.00 |
February | 405.25 | 273.48 | 131.77 | 357.76 | 234.36 | 0.00 | 0.00 | 672.00 |
March | 358.26 | 226.93 | 131.33 | 300.55 | 197.48 | 0.00 | 0.00 | 744.00 |
April | 325.23 | 177.05 | 148.18 | 269.03 | 129.16 | 0.00 | 0.00 | 720.00 |
May | 273.51 | 94.19 | 179.32 | 226.56 | 72.82 | 0.00 | 0.00 | 744.00 |
June | 245.43 | 66.11 | 179.32 | 209.81 | 50.60 | 0.00 | 0.00 | 720.00 |
July | 268.40 | 85.78 | 182.62 | 238.60 | 49.44 | 0.00 | 0.00 | 744.00 |
August | 286.45 | 120.39 | 166.05 | 270.77 | 57.66 | 0.00 | 0.00 | 744.00 |
September | 306.46 | 163.54 | 142.93 | 293.80 | 88.57 | 0.00 | 0.00 | 720.00 |
October | 261.10 | 153.57 | 107.54 | 236.22 | 130.66 | 0.00 | 0.00 | 744.00 |
November | 231.90 | 145.28 | 86.62 | 196.12 | 181.88 | 0.00 | 0.00 | 720.00 |
December | 246.61 | 161.38 | 85.23 | 185.07 | 270.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 293.27 | 156.72 | 136.55 | 252.93 | 144.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 231.90 | 66.11 | 85.23 | 185.07 | 49.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 405.25 | 273.48 | 182.62 | 357.76 | 278.24 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46500247.86 | 16060438.58 | 30439809.28 | 4673842.32 | 0.236485E+09 |
February | 74674105.48 | 34233178.54 | 40440926.94 | 37065271.42 | 0.171101E+09 |
March | 0.117994E+09 | 66091758.40 | 51902628.75 | 85201442.19 | 0.149642E+09 |
April | 0.168920E+09 | 0.106512E+09 | 62408284.55 | 0.161486E+09 | 99649215.79 |
May | 0.214466E+09 | 0.120798E+09 | 93668607.63 | 0.240007E+09 | 61536545.49 |
June | 0.218379E+09 | 0.125880E+09 | 92499424.45 | 0.258331E+09 | 44121950.75 |
July | 0.231637E+09 | 0.138512E+09 | 93124733.09 | 0.280836E+09 | 43062191.54 |
August | 0.182406E+09 | 0.102367E+09 | 80039201.87 | 0.213727E+09 | 47569265.29 |
September | 0.127796E+09 | 65527903.73 | 62268508.58 | 0.132096E+09 | 68512627.08 |
October | 78341395.17 | 30967795.11 | 47373600.06 | 57217594.88 | 0.107675E+09 |
November | 43800633.29 | 13076010.95 | 30724622.34 | 14070596.81 | 0.147625E+09 |
December | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 0.230931E+09 |
Annual Sum or Average | 0.154125E+10 | 0.829270E+09 | 0.711979E+09 | 0.148576E+10 | 0.140791E+10 |
Minimum of Months | 36332242.13 | 9243755.57 | 27088486.57 | 1054358.03 | 43062191.54 |
Maximum of Months | 0.231637E+09 | 0.138512E+09 | 93668607.63 | 0.280836E+09 | 0.236485E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.348497E+10 | 0.357702E+10 |
February | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.432103E+10 | 0.274131E+10 |
March | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.401002E+10 | 0.254884E+10 |
April | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.344942E+10 | 0.166666E+10 |
May | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.298219E+10 | 0.100832E+10 |
June | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.270149E+10 | 0.678986E+09 |
July | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.319938E+10 | 0.661975E+09 |
August | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.358161E+10 | 0.783390E+09 |
September | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.372698E+10 | 0.118258E+10 |
October | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.311323E+10 | 0.177005E+10 |
November | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.254951E+10 | 0.229160E+10 |
December | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.249523E+10 | 0.345162E+10 |
Annual Sum or Average | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.396151E+11 | 0.223624E+11 |
Minimum of Months | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.249523E+10 | 0.661975E+09 |
Maximum of Months | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.432103E+10 | 0.357702E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.347314E+10 | 0.356891E+10 |
February | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.431456E+10 | 0.272046E+10 |
March | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.400790E+10 | 0.251641E+10 |
April | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.345226E+10 | 0.162362E+10 |
May | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.297785E+10 | 0.971522E+09 |
June | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.268883E+10 | 0.652558E+09 |
July | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.318204E+10 | 0.637112E+09 |
August | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.356389E+10 | 0.758862E+09 |
September | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.371842E+10 | 0.115134E+10 |
October | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.311938E+10 | 0.171697E+10 |
November | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.255032E+10 | 0.225392E+10 |
December | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.248585E+10 | 0.344424E+10 |
Annual Sum or Average | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.395344E+11 | 0.220159E+11 |
Minimum of Months | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.248585E+10 | 0.637112E+09 |
Maximum of Months | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.431456E+10 | 0.356891E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.855610E+09 | 0.594270E+09 | 0.261340E+09 | 0.695498E+09 | 0.745244E+09 |
February | 0.980387E+09 | 0.661611E+09 | 0.318776E+09 | 0.865492E+09 | 0.566962E+09 |
March | 0.959574E+09 | 0.607808E+09 | 0.351766E+09 | 0.805001E+09 | 0.528941E+09 |
April | 0.842995E+09 | 0.458909E+09 | 0.384086E+09 | 0.697322E+09 | 0.334782E+09 |
May | 0.732563E+09 | 0.252272E+09 | 0.480291E+09 | 0.606824E+09 | 0.195028E+09 |
June | 0.636148E+09 | 0.171356E+09 | 0.464792E+09 | 0.543816E+09 | 0.131157E+09 |
July | 0.718880E+09 | 0.229749E+09 | 0.489130E+09 | 0.639077E+09 | 0.132431E+09 |
August | 0.767221E+09 | 0.322460E+09 | 0.444761E+09 | 0.725238E+09 | 0.154429E+09 |
September | 0.794346E+09 | 0.423884E+09 | 0.370462E+09 | 0.761522E+09 | 0.229578E+09 |
October | 0.699338E+09 | 0.411311E+09 | 0.288027E+09 | 0.632680E+09 | 0.349947E+09 |
November | 0.601072E+09 | 0.376564E+09 | 0.224508E+09 | 0.508331E+09 | 0.471420E+09 |
December | 0.660521E+09 | 0.432235E+09 | 0.228286E+09 | 0.495694E+09 | 0.723262E+09 |
Annual Sum or Average | 0.924866E+10 | 0.494243E+10 | 0.430623E+10 | 0.797649E+10 | 0.456318E+10 |
Minimum of Months | 0.601072E+09 | 0.171356E+09 | 0.224508E+09 | 0.495694E+09 | 0.131157E+09 |
Maximum of Months | 0.980387E+09 | 0.661611E+09 | 0.489130E+09 | 0.865492E+09 | 0.745244E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.96 | 706.35 | 138.89 | 47.97 | 90.92 | 0.00 | 0.00 |
February | 122.57 | 565.81 | 246.94 | 113.20 | 133.73 | 0.00 | 0.00 |
March | 254.48 | 446.96 | 352.43 | 197.41 | 155.03 | 0.00 | 0.00 |
April | 498.41 | 307.56 | 521.36 | 328.74 | 192.62 | 0.00 | 0.00 |
May | 716.87 | 183.80 | 640.58 | 360.81 | 279.77 | 0.00 | 0.00 |
June | 797.32 | 136.18 | 674.01 | 388.52 | 285.49 | 0.00 | 0.00 |
July | 838.82 | 128.62 | 691.87 | 413.72 | 278.15 | 0.00 | 0.00 |
August | 638.37 | 142.08 | 544.82 | 305.76 | 239.07 | 0.00 | 0.00 |
September | 407.70 | 211.46 | 394.43 | 202.25 | 192.19 | 0.00 | 0.00 |
October | 170.90 | 321.61 | 233.99 | 92.50 | 141.50 | 0.00 | 0.00 |
November | 43.43 | 455.63 | 135.19 | 40.36 | 94.83 | 0.00 | 0.00 |
December | 3.15 | 689.76 | 108.52 | 27.61 | 80.91 | 0.00 | 0.00 |
Annual Sum or Average | 376.91 | 357.16 | 390.98 | 210.37 | 180.61 | 0.00 | 0.00 |
Minimum of Months | 3.15 | 128.62 | 108.52 | 27.61 | 80.91 | 0.00 | 0.00 |
Maximum of Months | 838.82 | 706.35 | 691.87 | 413.72 | 285.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1301.14 | 1335.51 | 1552.49 | 1078.30 | 474.20 | 0.00 | 0.00 |
February | 1786.14 | 1133.15 | 1969.50 | 1329.11 | 640.39 | 0.00 | 0.00 |
March | 1497.17 | 951.63 | 1741.14 | 1102.86 | 638.28 | 0.00 | 0.00 |
April | 1330.79 | 643.00 | 1580.59 | 860.44 | 720.15 | 0.00 | 0.00 |
May | 1113.42 | 376.46 | 1329.23 | 457.74 | 871.48 | 0.00 | 0.00 |
June | 1042.24 | 261.95 | 1192.76 | 321.29 | 871.47 | 0.00 | 0.00 |
July | 1194.51 | 247.15 | 1304.40 | 416.88 | 887.52 | 0.00 | 0.00 |
August | 1337.22 | 292.48 | 1392.11 | 585.10 | 807.01 | 0.00 | 0.00 |
September | 1437.88 | 456.24 | 1489.37 | 794.77 | 694.61 | 0.00 | 0.00 |
October | 1162.35 | 660.86 | 1268.94 | 746.32 | 522.62 | 0.00 | 0.00 |
November | 983.61 | 884.10 | 1126.99 | 706.05 | 420.95 | 0.00 | 0.00 |
December | 931.61 | 1288.69 | 1198.51 | 784.29 | 414.22 | 0.00 | 0.00 |
Annual Sum or Average | 1256.19 | 709.11 | 1425.28 | 761.66 | 663.62 | 0.00 | 0.00 |
Minimum of Months | 931.61 | 247.15 | 1126.99 | 321.29 | 414.22 | 0.00 | 0.00 |
Maximum of Months | 1786.14 | 1335.51 | 1969.50 | 1329.11 | 887.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1296.72 | 1332.48 | 1552.49 | 1078.30 | 474.20 | 0.00 | 0.00 |
February | 1783.47 | 1124.53 | 1969.50 | 1329.11 | 640.39 | 0.00 | 0.00 |
March | 1496.38 | 939.52 | 1741.14 | 1102.86 | 638.28 | 0.00 | 0.00 |
April | 1331.89 | 626.40 | 1580.59 | 860.44 | 720.15 | 0.00 | 0.00 |
May | 1111.80 | 362.72 | 1329.23 | 457.74 | 871.48 | 0.00 | 0.00 |
June | 1037.36 | 251.76 | 1192.76 | 321.29 | 871.47 | 0.00 | 0.00 |
July | 1188.04 | 237.87 | 1304.40 | 416.88 | 887.52 | 0.00 | 0.00 |
August | 1330.60 | 283.33 | 1392.11 | 585.10 | 807.01 | 0.00 | 0.00 |
September | 1434.57 | 444.19 | 1489.37 | 794.77 | 694.61 | 0.00 | 0.00 |
October | 1164.64 | 641.04 | 1268.94 | 746.32 | 522.62 | 0.00 | 0.00 |
November | 983.92 | 869.57 | 1126.99 | 706.05 | 420.95 | 0.00 | 0.00 |
December | 928.11 | 1285.93 | 1198.51 | 784.29 | 414.22 | 0.00 | 0.00 |
Annual Sum or Average | 1253.63 | 698.12 | 1425.28 | 761.66 | 663.62 | 0.00 | 0.00 |
Minimum of Months | 928.11 | 237.87 | 1126.99 | 321.29 | 414.22 | 0.00 | 0.00 |
Maximum of Months | 1783.47 | 1332.48 | 1969.50 | 1329.11 | 887.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 259.67 | 278.24 | 319.45 | 221.88 | 97.57 | 0.00 | 0.00 |
February | 357.76 | 234.36 | 405.25 | 273.48 | 131.77 | 0.00 | 0.00 |
March | 300.55 | 197.48 | 358.26 | 226.93 | 131.33 | 0.00 | 0.00 |
April | 269.03 | 129.16 | 325.23 | 177.05 | 148.18 | 0.00 | 0.00 |
May | 226.56 | 72.82 | 273.51 | 94.19 | 179.32 | 0.00 | 0.00 |
June | 209.81 | 50.60 | 245.43 | 66.11 | 179.32 | 0.00 | 0.00 |
July | 238.60 | 49.44 | 268.40 | 85.78 | 182.62 | 0.00 | 0.00 |
August | 270.77 | 57.66 | 286.45 | 120.39 | 166.05 | 0.00 | 0.00 |
September | 293.80 | 88.57 | 306.46 | 163.54 | 142.93 | 0.00 | 0.00 |
October | 236.22 | 130.66 | 261.10 | 153.57 | 107.54 | 0.00 | 0.00 |
November | 196.12 | 181.88 | 231.90 | 145.28 | 86.62 | 0.00 | 0.00 |
December | 185.07 | 270.04 | 246.61 | 161.38 | 85.23 | 0.00 | 0.00 |
Annual Sum or Average | 252.93 | 144.70 | 293.27 | 156.72 | 136.55 | 0.00 | 0.00 |
Minimum of Months | 185.07 | 49.44 | 231.90 | 66.11 | 85.23 | 0.00 | 0.00 |
Maximum of Months | 357.76 | 278.24 | 405.25 | 273.48 | 182.62 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37390738.57 | 0.189188E+10 | 0.372002E+09 | 0.128484E+09 | 0.243518E+09 | 0.00 | 0.00 |
February | 0.296522E+09 | 0.136881E+10 | 0.597393E+09 | 0.273865E+09 | 0.323527E+09 | 0.00 | 0.00 |
March | 0.681612E+09 | 0.119713E+10 | 0.943955E+09 | 0.528734E+09 | 0.415221E+09 | 0.00 | 0.00 |
April | 0.129189E+10 | 0.797194E+09 | 0.135136E+10 | 0.852096E+09 | 0.499266E+09 | 0.00 | 0.00 |
May | 0.192005E+10 | 0.492292E+09 | 0.171573E+10 | 0.966382E+09 | 0.749349E+09 | 0.00 | 0.00 |
June | 0.206665E+10 | 0.352976E+09 | 0.174703E+10 | 0.100704E+10 | 0.739995E+09 | 0.00 | 0.00 |
July | 0.224669E+10 | 0.344498E+09 | 0.185309E+10 | 0.110810E+10 | 0.744998E+09 | 0.00 | 0.00 |
August | 0.170981E+10 | 0.380554E+09 | 0.145925E+10 | 0.818936E+09 | 0.640314E+09 | 0.00 | 0.00 |
September | 0.105677E+10 | 0.548101E+09 | 0.102237E+10 | 0.524223E+09 | 0.498148E+09 | 0.00 | 0.00 |
October | 0.457741E+09 | 0.861396E+09 | 0.626731E+09 | 0.247742E+09 | 0.378989E+09 | 0.00 | 0.00 |
November | 0.112565E+09 | 0.118100E+10 | 0.350405E+09 | 0.104608E+09 | 0.245797E+09 | 0.00 | 0.00 |
December | 8434864.22 | 0.184744E+10 | 0.290658E+09 | 73950044.53 | 0.216708E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.118861E+11 | 0.112633E+11 | 0.123300E+11 | 0.663416E+10 | 0.569583E+10 | 0.00 | 0.00 |
Minimum of Months | 8434864.22 | 0.344498E+09 | 0.290658E+09 | 73950044.53 | 0.216708E+09 | 0.00 | 0.00 |
Maximum of Months | 0.224669E+10 | 0.189188E+10 | 0.185309E+10 | 0.110810E+10 | 0.749349E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.348497E+10 | 0.357702E+10 | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.00 | 0.00 |
February | 0.432103E+10 | 0.274131E+10 | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.00 | 0.00 |
March | 0.401002E+10 | 0.254884E+10 | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.00 | 0.00 |
April | 0.344942E+10 | 0.166666E+10 | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.00 | 0.00 |
May | 0.298219E+10 | 0.100832E+10 | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.00 | 0.00 |
June | 0.270149E+10 | 0.678986E+09 | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.00 | 0.00 |
July | 0.319938E+10 | 0.661975E+09 | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.00 | 0.00 |
August | 0.358161E+10 | 0.783390E+09 | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.00 | 0.00 |
September | 0.372698E+10 | 0.118258E+10 | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.00 | 0.00 |
October | 0.311323E+10 | 0.177005E+10 | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.00 | 0.00 |
November | 0.254951E+10 | 0.229160E+10 | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.00 | 0.00 |
December | 0.249523E+10 | 0.345162E+10 | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.396151E+11 | 0.223624E+11 | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249523E+10 | 0.661975E+09 | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.432103E+10 | 0.357702E+10 | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.347314E+10 | 0.356891E+10 | 0.415820E+10 | 0.288811E+10 | 0.127009E+10 | 0.00 | 0.00 |
February | 0.431456E+10 | 0.272046E+10 | 0.476461E+10 | 0.321538E+10 | 0.154923E+10 | 0.00 | 0.00 |
March | 0.400790E+10 | 0.251641E+10 | 0.466346E+10 | 0.295390E+10 | 0.170956E+10 | 0.00 | 0.00 |
April | 0.345226E+10 | 0.162362E+10 | 0.409689E+10 | 0.223026E+10 | 0.186663E+10 | 0.00 | 0.00 |
May | 0.297785E+10 | 0.971522E+09 | 0.356020E+10 | 0.122602E+10 | 0.233418E+10 | 0.00 | 0.00 |
June | 0.268883E+10 | 0.652558E+09 | 0.309163E+10 | 0.832777E+09 | 0.225885E+10 | 0.00 | 0.00 |
July | 0.318204E+10 | 0.637112E+09 | 0.349370E+10 | 0.111656E+10 | 0.237714E+10 | 0.00 | 0.00 |
August | 0.356389E+10 | 0.758862E+09 | 0.372863E+10 | 0.156713E+10 | 0.216150E+10 | 0.00 | 0.00 |
September | 0.371842E+10 | 0.115134E+10 | 0.386046E+10 | 0.206004E+10 | 0.180042E+10 | 0.00 | 0.00 |
October | 0.311938E+10 | 0.171697E+10 | 0.339873E+10 | 0.199894E+10 | 0.139979E+10 | 0.00 | 0.00 |
November | 0.255032E+10 | 0.225392E+10 | 0.292116E+10 | 0.183007E+10 | 0.109109E+10 | 0.00 | 0.00 |
December | 0.248585E+10 | 0.344424E+10 | 0.321008E+10 | 0.210063E+10 | 0.110945E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.395344E+11 | 0.220159E+11 | 0.449478E+11 | 0.240198E+11 | 0.209279E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248585E+10 | 0.637112E+09 | 0.292116E+10 | 0.832777E+09 | 0.109109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.431456E+10 | 0.356891E+10 | 0.476461E+10 | 0.321538E+10 | 0.237714E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.695498E+09 | 0.745244E+09 | 0.855610E+09 | 0.594270E+09 | 0.261340E+09 | 0.00 | 0.00 |
February | 0.865492E+09 | 0.566962E+09 | 0.980387E+09 | 0.661611E+09 | 0.318776E+09 | 0.00 | 0.00 |
March | 0.805001E+09 | 0.528941E+09 | 0.959574E+09 | 0.607808E+09 | 0.351766E+09 | 0.00 | 0.00 |
April | 0.697322E+09 | 0.334782E+09 | 0.842995E+09 | 0.458909E+09 | 0.384086E+09 | 0.00 | 0.00 |
May | 0.606824E+09 | 0.195028E+09 | 0.732563E+09 | 0.252272E+09 | 0.480291E+09 | 0.00 | 0.00 |
June | 0.543816E+09 | 0.131157E+09 | 0.636148E+09 | 0.171356E+09 | 0.464792E+09 | 0.00 | 0.00 |
July | 0.639077E+09 | 0.132431E+09 | 0.718880E+09 | 0.229749E+09 | 0.489130E+09 | 0.00 | 0.00 |
August | 0.725238E+09 | 0.154429E+09 | 0.767221E+09 | 0.322460E+09 | 0.444761E+09 | 0.00 | 0.00 |
September | 0.761522E+09 | 0.229578E+09 | 0.794346E+09 | 0.423884E+09 | 0.370462E+09 | 0.00 | 0.00 |
October | 0.632680E+09 | 0.349947E+09 | 0.699338E+09 | 0.411311E+09 | 0.288027E+09 | 0.00 | 0.00 |
November | 0.508331E+09 | 0.471420E+09 | 0.601072E+09 | 0.376564E+09 | 0.224508E+09 | 0.00 | 0.00 |
December | 0.495694E+09 | 0.723262E+09 | 0.660521E+09 | 0.432235E+09 | 0.228286E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.797649E+10 | 0.456318E+10 | 0.924866E+10 | 0.494243E+10 | 0.430623E+10 | 0.00 | 0.00 |
Minimum of Months | 0.495694E+09 | 0.131157E+09 | 0.601072E+09 | 0.171356E+09 | 0.224508E+09 | 0.00 | 0.00 |
Maximum of Months | 0.865492E+09 | 0.745244E+09 | 0.980387E+09 | 0.661611E+09 | 0.489130E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.3 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.6 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.5 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.48 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.18 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.96 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.19 | 13.59 | 3.45 | 8.98 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.33 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.48 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.07 | -2.0 | 3.82 | -8.5 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.3 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.98 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -0.9 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.85 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.46 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.93 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.24 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.70 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.34 | 23.33 | 8.07 | 19.92 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.35 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.80 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.60 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.43 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -0.9 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.34 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.3 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.0 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.61 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.6 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.4 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.33 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.46 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.93 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.90 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.70 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.75 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.35 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.70 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.4 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.75 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.24 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.06 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.90 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.75 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.35 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.22 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.16 | 3.43 | 9.18 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 06-DEC-02:00 | 0.00 | -0.0 | 3.60 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.75 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.314318E+10 | -.270575E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -437429209.1 | 58.99 | 0.00 | 0.00 |
February | 0.291401E+10 | -.252023E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -393789248.8 | 58.99 | 0.00 | 0.00 |
March | 0.327986E+10 | -.284829E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -431566841.8 | 58.99 | 0.00 | 0.00 |
April | 0.303260E+10 | -.262639E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -406210061.6 | 58.99 | 0.00 | 0.00 |
May | 0.297673E+10 | -.258141E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -395317620.0 | 58.99 | 0.00 | 0.00 |
June | 0.275629E+10 | -.238189E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -374400574.3 | 59.00 | 0.00 | 0.00 |
July | 0.264677E+10 | -.226382E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -382950460.2 | 58.99 | 0.00 | 0.00 |
August | 0.265274E+10 | -.226849E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -384249526.7 | 58.99 | 0.00 | 0.00 |
September | 0.254706E+10 | -.216892E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -378144274.7 | 58.99 | 0.00 | 0.00 |
October | 0.270421E+10 | -.229377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -410443132.6 | 58.99 | 0.00 | 0.00 |
November | 0.275463E+10 | -.234050E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -414130704.2 | 59.00 | 0.00 | 0.00 |
December | 0.301815E+10 | -.258156E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -436587577.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.344262E+11 | -.295810E+11 | 8760.00 | -.484522E+10 | 58.99 | |||||
Minimum of Months | 0.254706E+10 | -.284829E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -437429209.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.327986E+10 | -.216892E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374400574.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.98 | 0.94 | 03-JAN-12:09 | 124.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.98 | 0.89 | 12-FEB-12:20 | 156.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.97 | 0.83 | 27-MAR-13:20 | 167.56 | 0.00 | 0.00 | 0.33 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.96 | 0.83 | 01-APR-11:50 | 199.74 | 0.00 | 0.00 | 6.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.92 | 0.83 | 01-MAY-08:09 | 1241.67 | 0.00 | 0.00 | 101.50 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.93 | 0.83 | 01-JUN-11:30 | 368.49 | 0.00 | 0.00 | 72.50 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.92 | 0.83 | 01-JUL-08:09 | 1326.79 | 0.00 | 0.00 | 105.67 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.94 | 0.83 | 01-AUG-09:50 | 284.98 | 0.00 | 0.00 | 25.17 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.96 | 0.83 | 02-SEP-12:30 | 215.14 | 0.00 | 0.00 | 0.17 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.97 | 0.89 | 02-OCT-11:39 | 174.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.98 | 0.94 | 01-NOV-09:09 | 130.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.99 | 0.94 | 01-DEC-11:20 | 120.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.95 | 447.80 | 0.00 | 0.00 | 311.33 | ||||||
Minimum of Months | 226.33 | 0.92 | 0.83 | 120.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.99 | 0.94 | 1326.79 | 0.00 | 0.00 | 105.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278451E+11 | 52371.40 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195014E+11 | 52371.40 | 01-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151066E+11 | 52371.40 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418771E+10 | 52371.40 | 01-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158282E+09 | 52371.40 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130921E+10 | 52371.40 | 13-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.924308E+10 | 52371.40 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248299E+11 | 52371.40 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102181E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.278451E+11 | 52371.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.493266E+11 | 282567.26 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216010E+11 | 282567.26 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.837974E+10 | 282567.26 | 05-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422069E+09 | 53667.39 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26400173.00 | 11404.84 | 30-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397686E+10 | 282567.26 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380542E+11 | 282567.26 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121787E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.493266E+11 | 282567.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115513E+11 | 35879.57 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673856E+10 | 35879.57 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481683E+10 | 35879.57 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105525E+10 | 35879.57 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32995403.41 | 11221.75 | 01-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349745E+09 | 21338.98 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313905E+10 | 35879.57 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108338E+11 | 35879.57 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385176E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115513E+11 | 35879.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140000E+11 | 31074.06 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.864088E+10 | 31074.06 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.668000E+10 | 31074.06 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187604E+10 | 31074.06 | 02-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82915844.36 | 22259.85 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3358080.28 | 1181.94 | 23-SEP-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.897757E+09 | 31074.06 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468344E+10 | 31074.06 | 05-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132536E+11 | 31074.06 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.501179E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140000E+11 | 31074.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252219E+11 | 59230.94 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163268E+11 | 50801.24 | 01-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138037E+11 | 38275.60 | 15-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.543184E+10 | 23537.16 | 04-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.747243E+09 | 9331.08 | 01-MAY-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73120385.38 | 2675.18 | 02-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20540686.51 | 1403.64 | 08-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80307314.77 | 4527.57 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.797866E+09 | 8381.31 | 27-SEP-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.511998E+10 | 19776.90 | 29-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110839E+11 | 39194.68 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239481E+11 | 56713.35 | 24-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102655E+12 | |||||||
Minimum of Months | 20540686.51 | 1403.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.252219E+11 | 59230.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 27552830.39 | 23895252.43 | 3152.08 | 23-APR-16:00 | 2714.72 | 0.00 |
May | 0.00 | 0.00 | 0.263934E+10 | 0.218930E+10 | 32243.04 | 26-MAY-06:02 | 22307.39 | 0.00 |
June | 0.00 | 0.00 | 0.726995E+10 | 0.533848E+10 | 35288.91 | 30-JUN-06:02 | 19473.68 | 0.00 |
July | 0.00 | 0.00 | 0.117236E+11 | 0.811687E+10 | 35224.08 | 30-JUL-08:62 | 18396.96 | 0.00 |
August | 0.00 | 0.00 | 0.827164E+10 | 0.567302E+10 | 33580.16 | 30-AUG-06:02 | 16361.65 | 0.00 |
September | 0.00 | 0.00 | 0.116647E+10 | 0.916032E+09 | 32767.15 | 01-SEP-06:02 | 16314.42 | 0.00 |
October | 0.00 | 0.00 | 35427115.59 | 33736118.07 | 2707.05 | 19-OCT-15:00 | 2541.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.311339E+11 | 0.222913E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.117236E+11 | 0.811687E+10 | 35288.91 | 22307.39 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.506565E+09 | 0.488897E+09 | 12750.05 | 31-MAR-15:00 | 12514.56 | 0.00 |
April | 0.00 | 0.00 | 0.599483E+10 | 0.573750E+10 | 34136.03 | 24-APR-06:03 | 29358.89 | 0.00 |
May | 0.00 | 0.00 | 0.237908E+11 | 0.201806E+11 | 160754.78 | 26-MAY-06:02 | 112234.05 | 0.00 |
June | 0.00 | 0.00 | 0.437606E+11 | 0.322446E+11 | 173577.92 | 25-JUN-08:62 | 96918.26 | 0.00 |
July | 0.00 | 0.00 | 0.607426E+11 | 0.420915E+11 | 176653.18 | 30-JUL-08:62 | 89960.42 | 0.00 |
August | 0.00 | 0.00 | 0.480946E+11 | 0.327371E+11 | 167743.42 | 30-AUG-06:02 | 84234.52 | 0.00 |
September | 0.00 | 0.00 | 0.174832E+11 | 0.140973E+11 | 163272.78 | 01-SEP-06:02 | 85146.91 | 0.00 |
October | 0.00 | 0.00 | 0.943952E+10 | 0.844592E+10 | 77676.32 | 20-OCT-06:02 | 51881.53 | 0.00 |
November | 0.00 | 0.00 | 0.115608E+10 | 0.100292E+10 | 16755.45 | 21-NOV-14:00 | 11769.40 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.210969E+12 | 0.157026E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.607426E+11 | 0.420915E+11 | 176653.18 | 112234.05 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 146.25 | 146.25 | 0.12 | 08-FEB-13:50 | 0.12 | 0.00 |
March | 0.00 | 0.00 | 4771.69 | 4771.69 | 0.56 | 31-MAR-14:10 | 0.56 | 0.00 |
April | 0.00 | 0.00 | 0.491006E+09 | 0.470049E+09 | 8295.61 | 23-APR-13:40 | 7244.14 | 0.00 |
May | 0.00 | 0.00 | 0.358625E+10 | 0.314200E+10 | 21226.77 | 26-MAY-06:02 | 14888.37 | 0.00 |
June | 0.00 | 0.00 | 0.738843E+10 | 0.565535E+10 | 23566.18 | 30-JUN-05:03 | 12670.06 | 0.00 |
July | 0.00 | 0.00 | 0.109529E+11 | 0.792908E+10 | 23379.75 | 30-JUL-08:62 | 11567.84 | 0.00 |
August | 0.00 | 0.00 | 0.940162E+10 | 0.673650E+10 | 22087.98 | 30-AUG-06:02 | 11005.39 | 0.00 |
September | 0.00 | 0.00 | 0.321165E+10 | 0.270854E+10 | 21521.82 | 01-SEP-06:02 | 11030.89 | 0.00 |
October | 0.00 | 0.00 | 0.840528E+09 | 0.772912E+09 | 16060.89 | 20-OCT-06:02 | 11167.81 | 0.00 |
November | 0.00 | 0.00 | 191945.75 | 147566.26 | 179.53 | 01-NOV-15:00 | 136.97 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.358725E+11 | 0.274146E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109529E+11 | 0.792908E+10 | 23566.18 | 14888.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 485.71 | 485.71 | 0.18 | 31-MAR-14:10 | 0.18 | 0.00 |
April | 0.00 | 0.00 | 0.187658E+09 | 0.175961E+09 | 6371.70 | 23-APR-14:00 | 5738.30 | 0.00 |
May | 0.00 | 0.00 | 0.218068E+10 | 0.192312E+10 | 17644.68 | 26-MAY-06:02 | 12154.70 | 0.00 |
June | 0.00 | 0.00 | 0.498235E+10 | 0.383331E+10 | 19167.91 | 30-JUN-06:02 | 10910.77 | 0.00 |
July | 0.00 | 0.00 | 0.786476E+10 | 0.570209E+10 | 19423.83 | 30-JUL-08:62 | 9496.82 | 0.00 |
August | 0.00 | 0.00 | 0.625284E+10 | 0.457036E+10 | 18382.13 | 30-AUG-06:02 | 8974.24 | 0.00 |
September | 0.00 | 0.00 | 0.165451E+10 | 0.143384E+10 | 17935.12 | 01-SEP-06:02 | 8926.74 | 0.00 |
October | 0.00 | 0.00 | 0.407282E+09 | 0.384586E+09 | 7586.17 | 19-OCT-14:20 | 7248.61 | 0.00 |
November | 0.00 | 0.00 | 1689.44 | 1685.76 | 0.29 | 17-NOV-13:00 | 0.29 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.235301E+11 | 0.180233E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.786476E+10 | 0.570209E+10 | 19423.83 | 12154.70 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104449E+11 | 0.86 | 6654.12 | 01-JAN-00:10 | 1.47 |
February | 0.898665E+10 | 0.82 | 6654.12 | 01-FEB-00:20 | 1.47 |
March | 0.938363E+10 | 0.77 | 6654.12 | 01-MAR-06:01 | 1.47 |
April | 0.742583E+10 | 0.63 | 6654.12 | 01-APR-06:02 | 1.47 |
May | 0.399016E+10 | 0.33 | 6654.12 | 01-MAY-05:02 | 1.47 |
June | 0.165592E+10 | 0.14 | 6654.12 | 01-JUN-07:05 | 1.46 |
July | 0.774116E+09 | 0.06 | 6654.12 | 01-JUL-07:09 | 1.45 |
August | 0.127028E+10 | 0.10 | 6654.12 | 01-AUG-11:05 | 1.45 |
September | 0.466689E+10 | 0.39 | 6654.12 | 01-SEP-07:10 | 1.44 |
October | 0.735371E+10 | 0.60 | 6654.12 | 01-OCT-07:02 | 1.45 |
November | 0.861255E+10 | 0.73 | 6654.12 | 01-NOV-05:02 | 1.46 |
December | 0.103776E+11 | 0.86 | 6654.12 | 01-DEC-04:54 | 1.47 |
Annual Sum or Average | 0.749422E+11 | 0.52 | |||
Minimum of Months | 0.774116E+09 | 0.06 | 6654.12 | 1.44 | |
Maximum of Months | 0.104449E+11 | 0.86 | 6654.12 | 1.47 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.182119E+10 | 0.49 | 1868.92 | 01-JAN-07:01 | 0.92 |
February | 0.151866E+10 | 0.44 | 1868.92 | 01-FEB-05:11 | 0.92 |
March | 0.154887E+10 | 0.40 | 1868.92 | 01-MAR-06:01 | 0.92 |
April | 0.126066E+10 | 0.35 | 1868.92 | 01-APR-06:02 | 0.92 |
May | 0.121215E+10 | 0.33 | 1868.92 | 01-MAY-06:01 | 0.92 |
June | 0.119114E+10 | 0.34 | 1868.92 | 22-JUN-06:02 | 0.91 |
July | 0.120896E+10 | 0.33 | 1868.92 | 01-JUL-06:02 | 0.91 |
August | 0.122225E+10 | 0.33 | 1868.92 | 01-AUG-06:02 | 0.90 |
September | 0.117099E+10 | 0.33 | 1868.92 | 01-SEP-06:02 | 0.90 |
October | 0.122564E+10 | 0.34 | 1868.92 | 13-OCT-06:01 | 0.92 |
November | 0.135465E+10 | 0.37 | 1868.92 | 01-NOV-06:01 | 0.92 |
December | 0.175270E+10 | 0.47 | 1868.92 | 01-DEC-05:02 | 0.92 |
Annual Sum or Average | 0.164879E+11 | 0.38 | |||
Minimum of Months | 0.117099E+10 | 0.33 | 1868.92 | 0.90 | |
Maximum of Months | 0.182119E+10 | 0.49 | 1868.92 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.956462E+10 | 0.58 | 12823.62 | 01-JAN-07:01 | 1.45 |
February | 0.804846E+10 | 0.55 | 12823.62 | 01-FEB-06:01 | 1.45 |
March | 0.859328E+10 | 0.54 | 12823.62 | 05-MAR-08:61 | 1.44 |
April | 0.804421E+10 | 0.53 | 6590.79 | 05-APR-06:03 | 1.03 |
May | 0.830160E+10 | 0.53 | 12823.62 | 18-MAY-06:02 | 1.43 |
June | 0.812508E+10 | 0.53 | 12823.62 | 07-JUN-06:02 | 1.43 |
July | 0.828208E+10 | 0.52 | 12823.62 | 01-JUL-06:02 | 1.43 |
August | 0.839945E+10 | 0.53 | 12823.62 | 01-AUG-06:02 | 1.42 |
September | 0.804735E+10 | 0.53 | 12823.62 | 01-SEP-06:02 | 1.42 |
October | 0.821814E+10 | 0.52 | 5462.91 | 20-OCT-06:02 | 0.91 |
November | 0.803021E+10 | 0.52 | 12823.62 | 27-NOV-06:01 | 1.45 |
December | 0.927384E+10 | 0.57 | 12823.62 | 02-DEC-06:01 | 1.45 |
Annual Sum or Average | 0.100928E+12 | 0.54 | |||
Minimum of Months | 0.803021E+10 | 0.52 | 5462.91 | 0.91 | |
Maximum of Months | 0.956462E+10 | 0.58 | 12823.62 | 1.45 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.106294E+10 | 0.45 | 1265.23 | 01-JAN-07:01 | 0.95 |
February | 0.881974E+09 | 0.41 | 1265.23 | 01-FEB-05:01 | 0.95 |
March | 0.928430E+09 | 0.38 | 1265.23 | 02-MAR-06:01 | 0.95 |
April | 0.814870E+09 | 0.35 | 1265.23 | 02-APR-07:01 | 0.95 |
May | 0.821259E+09 | 0.35 | 1265.23 | 18-MAY-06:02 | 0.94 |
June | 0.830470E+09 | 0.35 | 1265.23 | 07-JUN-06:02 | 0.94 |
July | 0.859562E+09 | 0.35 | 1265.23 | 01-JUL-06:02 | 0.94 |
August | 0.868227E+09 | 0.36 | 1265.23 | 01-AUG-06:02 | 0.93 |
September | 0.799624E+09 | 0.35 | 1265.23 | 01-SEP-06:02 | 0.93 |
October | 0.818235E+09 | 0.34 | 985.71 | 20-OCT-06:02 | 0.84 |
November | 0.848670E+09 | 0.37 | 1265.23 | 06-NOV-06:01 | 0.95 |
December | 0.104850E+10 | 0.44 | 1265.23 | 01-DEC-06:01 | 0.95 |
Annual Sum or Average | 0.105828E+11 | 0.38 | |||
Minimum of Months | 0.799624E+09 | 0.34 | 985.71 | 0.84 | |
Maximum of Months | 0.106294E+10 | 0.45 | 1265.23 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163302E+10 | 0.64 | 1002.73 | 13-JAN-06:42 | 0.95 |
February | 0.147040E+10 | 0.61 | 1002.73 | 04-FEB-11:53 | 0.95 |
March | 0.164073E+10 | 0.59 | 1002.73 | 10-MAR-15:30 | 0.95 |
April | 0.157044E+10 | 0.57 | 1002.73 | 01-APR-18:50 | 0.95 |
May | 0.162081E+10 | 0.57 | 1002.73 | 07-MAY-13:40 | 0.95 |
June | 0.158110E+10 | 0.57 | 1002.73 | 01-JUN-08:10 | 0.94 |
July | 0.160998E+10 | 0.56 | 1002.73 | 03-JUL-17:10 | 0.93 |
August | 0.163525E+10 | 0.57 | 1002.73 | 01-AUG-18:20 | 0.94 |
September | 0.157028E+10 | 0.57 | 1002.73 | 02-SEP-07:05 | 0.94 |
October | 0.160637E+10 | 0.57 | 1002.73 | 01-OCT-17:50 | 0.95 |
November | 0.155093E+10 | 0.57 | 1002.73 | 01-NOV-07:00 | 0.95 |
December | 0.163300E+10 | 0.63 | 1002.73 | 06-DEC-06:10 | 0.95 |
Annual Sum or Average | 0.191223E+11 | 0.59 | |||
Minimum of Months | 0.147040E+10 | 0.56 | 1002.73 | 0.93 | |
Maximum of Months | 0.164073E+10 | 0.64 | 1002.73 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.44 | 0.00 |
February | 2.08 | 0.00 |
March | 1.89 | 0.00 |
April | 0.14 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.06 | 6.13 |
October | 0.00 | 0.00 |
November | 1.15 | 0.00 |
December | 2.74 | 0.00 |
Annual Sum or Average | 10.48 | 0.03 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.74 | 6.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.08 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.14 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.35 | 0.00 |
February | 0.45 | 0.00 |
March | 0.44 | 0.00 |
April | 0.53 | 2.44 |
May | 1.54 | 2.44 |
June | 1.33 | 1.07 |
July | 0.82 | 0.50 |
August | 0.69 | 0.58 |
September | 0.99 | 1.58 |
October | 0.90 | 2.29 |
November | 0.43 | 0.00 |
December | 1.66 | 0.00 |
Annual Sum or Average | 11.13 | 0.98 |
Minimum of Months | 0.43 | 0.00 |
Maximum of Months | 1.66 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.37 | 0.00 |
February | 1.10 | 0.00 |
March | 0.88 | 0.00 |
April | 0.35 | 2.05 |
May | 1.00 | 2.44 |
June | 0.75 | 1.62 |
July | 0.38 | 1.62 |
August | 0.75 | 2.44 |
September | 1.19 | 2.06 |
October | 0.57 | 2.20 |
November | 0.91 | 0.00 |
December | 2.55 | 0.00 |
Annual Sum or Average | 12.79 | 0.82 |
Minimum of Months | 0.35 | 0.00 |
Maximum of Months | 2.55 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 41.67 | 0.00 |
February | 35.37 | 0.00 |
March | 30.98 | 0.00 |
April | 55.53 | 0.00 |
May | 63.83 | 0.00 |
June | 25.28 | 0.00 |
July | 15.74 | 0.00 |
August | 25.87 | 0.00 |
September | 77.68 | 0.00 |
October | 68.08 | 0.00 |
November | 38.92 | 0.00 |
December | 39.87 | 0.00 |
Annual Sum or Average | 518.83 | 0.00 |
Minimum of Months | 15.74 | 0.00 |
Maximum of Months | 77.68 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.182119E+10 | 0.348064E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.151866E+10 | 0.243767E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154887E+10 | 0.188832E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.126871E+10 | 0.523463E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.189478E+10 | 0.197853E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.299475E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.404173E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.322906E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.146819E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.123539E+10 | 0.163651E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135465E+10 | 0.115538E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.175270E+10 | 0.310374E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241287E+11 | 0.127727E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.123539E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.404173E+10 | 0.348064E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.956462E+10 | 0.616582E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.804846E+10 | 0.270012E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.874865E+10 | 0.104747E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.984574E+10 | 0.527587E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.151305E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.202986E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.248673E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.214944E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.130688E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.110273E+11 | 33000216.25 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.838363E+10 | 0.497107E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.927384E+10 | 0.475678E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159752E+12 | 0.152234E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.804846E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.248673E+11 | 0.616582E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.106294E+10 | 0.144391E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.881974E+09 | 0.842320E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.928431E+09 | 0.602104E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.938842E+09 | 0.131907E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169340E+10 | 41244254.26 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.259755E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.341014E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.302744E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.155811E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.101569E+10 | 0.437181E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.848724E+09 | 0.392382E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.104850E+10 | 0.135423E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.190117E+11 | 0.481470E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.848724E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.341014E+10 | 0.144391E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163302E+10 | 0.175000E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147040E+10 | 0.108011E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.164073E+10 | 0.835000E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161279E+10 | 0.234504E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.209440E+10 | 0.103645E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.264613E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.324043E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.291779E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.192072E+10 | 4197600.35 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.169206E+10 | 0.112220E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.155093E+10 | 0.585430E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163300E+10 | 0.165669E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.240524E+11 | 0.626474E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.147040E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.324043E+10 | 0.175000E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.182119E+10 | 0.00 | 0.278451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151866E+10 | 0.00 | 0.195014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154887E+10 | 0.00 | 0.151066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126066E+10 | 27552830.39 | 0.418771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121215E+10 | 0.263934E+10 | 0.158282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119114E+10 | 0.726995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120896E+10 | 0.117236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122225E+10 | 0.827164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117099E+10 | 0.116647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122564E+10 | 35427115.59 | 0.130921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135465E+10 | 0.00 | 0.924308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175270E+10 | 0.00 | 0.248299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164879E+11 | 0.311339E+11 | 0.102181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182119E+10 | 0.117236E+11 | 0.278451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.956462E+10 | 0.00 | 0.493266E+11 | 0.744401E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804846E+10 | 0.00 | 0.216010E+11 | 0.673206E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.859328E+10 | 0.506565E+09 | 0.837974E+10 | 0.726650E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804421E+10 | 0.599483E+10 | 0.422069E+09 | 0.447790E+11 | 67119123.32 | 0.00 | 0.00 | 0.00 |
May | 0.830160E+10 | 0.237908E+11 | 0.00 | 0.128919E+11 | 0.893354E+09 | 0.00 | 0.00 | 0.00 |
June | 0.812508E+10 | 0.437606E+11 | 0.00 | 0.254056E+10 | 0.597034E+10 | 0.00 | 0.00 | 0.00 |
July | 0.828208E+10 | 0.607426E+11 | 0.00 | 0.763086E+09 | 0.928038E+10 | 0.00 | 0.00 | 0.00 |
August | 0.839945E+10 | 0.480946E+11 | 0.00 | 0.165532E+10 | 0.372486E+10 | 0.00 | 0.00 | 0.00 |
September | 0.804735E+10 | 0.174832E+11 | 0.00 | 0.133002E+11 | 0.141176E+09 | 0.00 | 0.00 | 0.00 |
October | 0.821814E+10 | 0.943952E+10 | 26400173.00 | 0.443047E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803021E+10 | 0.115608E+10 | 0.397686E+10 | 0.610073E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927384E+10 | 0.00 | 0.380542E+11 | 0.761601E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100928E+12 | 0.210969E+12 | 0.121787E+12 | 0.471828E+12 | 0.200772E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.803021E+10 | 0.00 | 0.00 | 0.763086E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956462E+10 | 0.607426E+11 | 0.493266E+11 | 0.761601E+11 | 0.928038E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.106294E+10 | 0.00 | 0.115513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.881974E+09 | 146.25 | 0.673856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928430E+09 | 4771.69 | 0.481683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.814870E+09 | 0.491006E+09 | 0.105525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.821259E+09 | 0.358625E+10 | 32995403.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.830470E+09 | 0.738843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.859562E+09 | 0.109529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.868227E+09 | 0.940162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.799624E+09 | 0.321165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818235E+09 | 0.840528E+09 | 0.349745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.848670E+09 | 191945.75 | 0.313905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104850E+10 | 0.00 | 0.108338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105828E+11 | 0.358725E+11 | 0.385176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.799624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106294E+10 | 0.109529E+11 | 0.115513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163302E+10 | 0.00 | 0.140000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147040E+10 | 0.00 | 0.864088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164073E+10 | 485.71 | 0.668000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157044E+10 | 0.187658E+09 | 0.187604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162081E+10 | 0.218068E+10 | 82915844.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158110E+10 | 0.498235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160998E+10 | 0.786476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163525E+10 | 0.625284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157028E+10 | 0.165451E+10 | 3358080.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160637E+10 | 0.407282E+09 | 0.897757E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155093E+10 | 1689.44 | 0.468344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163300E+10 | 0.00 | 0.132536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191223E+11 | 0.235301E+11 | 0.501179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164073E+10 | 0.786476E+10 | 0.140000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.182119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126066E+10 | 0.00 | 0.00 | 0.00 | 8058055.55 | 0.00 | 0.523463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121215E+10 | 0.00 | 0.00 | 0.00 | 0.682629E+09 | 0.00 | 0.197853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119114E+10 | 0.00 | 0.00 | 0.00 | 0.180361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120896E+10 | 0.00 | 0.00 | 0.00 | 0.283277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122225E+10 | 0.00 | 0.00 | 0.00 | 0.200680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.117099E+10 | 0.00 | 0.00 | 0.00 | 0.297204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122564E+10 | 0.00 | 0.00 | 0.00 | 9754090.45 | 0.00 | 0.163651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164879E+11 | 0.00 | 0.00 | 0.00 | 0.764082E+10 | 0.00 | 0.127727E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.117099E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182119E+10 | 0.00 | 0.00 | 0.00 | 0.283277E+10 | 0.00 | 0.348064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.859328E+10 | 0.00 | 0.00 | 0.00 | 0.155365E+09 | 0.00 | 0.104747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.804421E+10 | 0.00 | 0.00 | 0.00 | 0.180153E+10 | 0.00 | 0.527587E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.830160E+10 | 0.00 | 0.00 | 0.00 | 0.682895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.812508E+10 | 0.00 | 0.00 | 0.00 | 0.121735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.828208E+10 | 0.00 | 0.00 | 0.00 | 0.165852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.839945E+10 | 0.00 | 0.00 | 0.00 | 0.130950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.804735E+10 | 0.00 | 0.00 | 0.00 | 0.502148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.821814E+10 | 0.00 | 0.00 | 0.00 | 0.280918E+10 | 0.00 | 33000216.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803021E+10 | 0.00 | 0.00 | 0.00 | 0.353421E+09 | 0.00 | 0.497107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.927384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100928E+12 | 0.00 | 0.00 | 0.00 | 0.588236E+11 | 0.00 | 0.152234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.803021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.165852E+11 | 0.00 | 0.616582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.106294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.881974E+09 | 0.00 | 0.00 | 0.00 | 41.34 | 0.00 | 0.842320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928430E+09 | 0.00 | 0.00 | 0.00 | 1348.78 | 0.00 | 0.602104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.814870E+09 | 0.00 | 0.00 | 0.00 | 0.123972E+09 | 0.00 | 0.131907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.821259E+09 | 0.00 | 0.00 | 0.00 | 0.872140E+09 | 0.00 | 41244254.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.830470E+09 | 0.00 | 0.00 | 0.00 | 0.176708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.859562E+09 | 0.00 | 0.00 | 0.00 | 0.255058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.868227E+09 | 0.00 | 0.00 | 0.00 | 0.215921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.799624E+09 | 0.00 | 0.00 | 0.00 | 0.758487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.818235E+09 | 0.00 | 0.00 | 0.00 | 0.197453E+09 | 0.00 | 0.437181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.848670E+09 | 0.00 | 0.00 | 0.00 | 54286.13 | 0.00 | 0.392382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105828E+11 | 0.00 | 0.00 | 0.00 | 0.842897E+10 | 0.00 | 0.481470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.799624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106294E+10 | 0.00 | 0.00 | 0.00 | 0.255058E+10 | 0.00 | 0.144391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.163302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164073E+10 | 0.00 | 0.00 | 0.00 | 119.71 | 0.00 | 0.835000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157044E+10 | 0.00 | 0.00 | 0.00 | 42350293.43 | 0.00 | 0.234504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.162081E+10 | 0.00 | 0.00 | 0.00 | 0.473585E+09 | 0.00 | 0.103645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158110E+10 | 0.00 | 0.00 | 0.00 | 0.106503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160998E+10 | 0.00 | 0.00 | 0.00 | 0.163044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163525E+10 | 0.00 | 0.00 | 0.00 | 0.128253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157028E+10 | 0.00 | 0.00 | 0.00 | 0.350448E+09 | 0.00 | 4197600.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160637E+10 | 0.00 | 0.00 | 0.00 | 85690813.53 | 0.00 | 0.112220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155093E+10 | 0.00 | 0.00 | 0.00 | 416.41 | 0.00 | 0.585430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191223E+11 | 0.00 | 0.00 | 0.00 | 0.493008E+10 | 0.00 | 0.626474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.147040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164073E+10 | 0.00 | 0.00 | 0.00 | 0.163044E+10 | 0.00 | 0.175000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13940420.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162433E+11 | 0.00 | 0.00 | 0.20 |
February | 0.307272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120772E+11 | 0.00 | 0.00 | 0.20 |
March | 0.218477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965124E+10 | 0.00 | 0.00 | 0.21 |
April | 0.485653E+10 | 6730495.72 | 0.00 | 181744.91 | 8866358.58 | 0.238988E+10 | 0.221633E+09 | 0.00 | 0.21 |
May | 0.228453E+10 | 89920315.29 | 0.00 | 6186777.75 | 0.00 | 79223829.49 | 0.310091E+10 | 0.00 | 0.35 |
June | 0.509969E+09 | 0.114181E+10 | 0.00 | 9531136.55 | 1727592.39 | 0.00 | 0.368488E+10 | 0.00 | 0.46 |
July | 0.124502E+09 | 0.188525E+10 | 0.00 | 10783585.29 | 3277402.53 | 0.00 | 0.262821E+10 | 0.00 | 0.46 |
August | 0.217094E+09 | 0.861598E+09 | 0.00 | 14954566.08 | 35081.04 | 0.00 | 0.412766E+10 | 0.00 | 0.53 |
September | 0.189085E+10 | 24510623.80 | 0.00 | 11161307.53 | 0.00 | 0.00 | 0.548730E+10 | 0.00 | 0.39 |
October | 0.642958E+10 | 0.00 | 0.00 | 1215326.19 | 0.00 | 0.478463E+09 | 0.959563E+09 | 0.00 | 0.22 |
November | 0.407067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562955E+10 | 0.00 | 0.00 | 0.20 |
December | 0.124121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152686E+11 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.230138E+11 | 0.400982E+10 | 0.00 | 54014444.31 | 13906434.54 | 0.618175E+11 | 0.202101E+11 | 0.00 | 0.30 |
Minimum of Months | 13940420.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.642958E+10 | 0.188525E+10 | 0.00 | 14954566.08 | 8866358.58 | 0.162433E+11 | 0.548730E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317050E+11 | 0.00 | 0.00 | 0.39 |
February | 0.250638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142872E+11 | 0.00 | 0.00 | 0.39 |
March | 0.271613E+11 | 0.00 | 0.00 | 2739105.77 | 0.00 | 0.454371E+10 | 0.250358E+10 | 0.00 | 0.40 |
April | 0.115417E+11 | 53076921.91 | 0.00 | 36276270.85 | 0.00 | 0.270465E+09 | 0.170031E+11 | 0.00 | 0.43 |
May | 0.139220E+10 | 0.491713E+09 | 0.00 | 84036142.05 | 22607.41 | 0.00 | 0.259803E+11 | 0.00 | 0.54 |
June | 0.168611E+09 | 0.506044E+10 | 0.00 | 73885986.96 | 29806971.18 | 0.00 | 0.191227E+11 | 0.00 | 0.60 |
July | 0.179988E+09 | 0.859534E+10 | 0.00 | 58293811.00 | 34646014.15 | 0.00 | 0.110021E+11 | 0.00 | 0.59 |
August | 0.235552E+09 | 0.454292E+10 | 0.00 | 87988883.89 | 5092562.39 | 0.00 | 0.182352E+11 | 0.00 | 0.64 |
September | 0.708579E+09 | 0.160938E+09 | 0.00 | 0.107807E+09 | 0.00 | 0.00 | 0.326309E+11 | 0.00 | 0.56 |
October | 0.799505E+10 | 0.00 | 0.00 | 52218771.49 | 0.00 | 0.00 | 0.205407E+11 | 0.00 | 0.42 |
November | 0.218087E+11 | 0.00 | 0.00 | 6620791.81 | 0.00 | 0.216334E+10 | 0.535263E+10 | 0.00 | 0.40 |
December | 0.276729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262548E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.154046E+12 | 0.189044E+11 | 0.00 | 0.509866E+09 | 69568155.13 | 0.792245E+11 | 0.152371E+12 | 0.00 | 0.48 |
Minimum of Months | 0.168611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.301177E+11 | 0.859534E+10 | 0.00 | 0.107807E+09 | 34646014.15 | 0.317050E+11 | 0.326309E+11 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.668669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534695E+10 | 0.00 | 0.00 | 0.39 |
February | 0.630805E+10 | 0.00 | 0.00 | 303712.82 | 0.00 | 0.257753E+10 | 0.326845E+09 | 0.00 | 0.39 |
March | 0.639076E+10 | 0.00 | 0.00 | 803388.76 | 0.00 | 0.169856E+10 | 0.767946E+09 | 0.00 | 0.40 |
April | 0.350070E+10 | 12368241.88 | 0.00 | 6050279.73 | 0.00 | 0.337379E+09 | 0.269600E+10 | 0.00 | 0.54 |
May | 0.789431E+09 | 0.171172E+09 | 0.00 | 12459742.77 | 0.00 | 4303414.47 | 0.384113E+10 | 0.00 | 0.78 |
June | 0.173687E+09 | 0.116162E+10 | 0.00 | 10956122.59 | 314544.26 | 0.00 | 0.260471E+10 | 0.00 | 0.88 |
July | 36379736.75 | 0.194646E+10 | 0.00 | 9415198.83 | 466053.27 | 0.00 | 0.151690E+10 | 0.00 | 0.84 |
August | 77077013.72 | 0.118793E+10 | 0.00 | 14213122.46 | 0.00 | 0.00 | 0.248425E+10 | 0.00 | 0.98 |
September | 0.561927E+09 | 57608159.47 | 0.00 | 20439614.86 | 0.00 | 0.00 | 0.535013E+10 | 0.00 | 0.88 |
October | 0.313754E+10 | 0.00 | 0.00 | 9974086.68 | 0.00 | 63528152.10 | 0.361022E+10 | 0.00 | 0.55 |
November | 0.534620E+10 | 0.00 | 0.00 | 1122013.64 | 0.00 | 0.118921E+10 | 0.852610E+09 | 0.00 | 0.41 |
December | 0.625305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512731E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.392615E+11 | 0.453715E+10 | 0.00 | 85737283.15 | 780597.53 | 0.163448E+11 | 0.240508E+11 | 0.00 | 0.62 |
Minimum of Months | 36379736.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.668669E+10 | 0.194646E+10 | 0.00 | 20439614.86 | 466053.27 | 0.534695E+10 | 0.535013E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925831E+10 | 0.00 | 0.00 | 0.39 |
February | 0.371816E+10 | 0.00 | 0.00 | 15056.63 | 0.00 | 0.539464E+10 | 32796716.23 | 0.00 | 0.39 |
March | 0.447161E+10 | 0.00 | 0.00 | 54584.11 | 0.00 | 0.414680E+10 | 76705389.55 | 0.00 | 0.40 |
April | 0.356407E+10 | 8896072.38 | 0.00 | 2316731.79 | 0.00 | 0.980727E+09 | 0.144937E+10 | 0.00 | 0.50 |
May | 0.139819E+10 | 0.115769E+09 | 0.00 | 5368986.87 | 0.00 | 45539947.62 | 0.262334E+10 | 0.00 | 0.74 |
June | 0.351223E+09 | 0.908520E+09 | 0.00 | 6037748.25 | 2307509.35 | 0.00 | 0.244358E+10 | 0.00 | 0.90 |
July | 98806858.57 | 0.150236E+10 | 0.00 | 6762704.63 | 2292336.82 | 0.00 | 0.186153E+10 | 0.00 | 0.90 |
August | 0.143778E+09 | 0.793710E+09 | 0.00 | 10081279.57 | 13418.94 | 0.00 | 0.284187E+10 | 0.00 | 1.03 |
September | 0.120274E+10 | 38808959.46 | 0.00 | 11225261.21 | 0.00 | 0.00 | 0.431674E+10 | 0.00 | 0.84 |
October | 0.394062E+10 | 0.00 | 0.00 | 4571656.56 | 0.00 | 0.336133E+09 | 0.192760E+10 | 0.00 | 0.52 |
November | 0.409745E+10 | 0.00 | 0.00 | 157274.43 | 0.00 | 0.287471E+10 | 0.180444E+09 | 0.00 | 0.39 |
December | 0.230557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.907158E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.280645E+11 | 0.336806E+10 | 0.00 | 46591284.04 | 4613265.10 | 0.321084E+11 | 0.177540E+11 | 0.00 | 0.62 |
Minimum of Months | 98806858.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.447161E+10 | 0.150236E+10 | 0.00 | 11225261.21 | 2307509.35 | 0.925831E+10 | 0.431674E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |