Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:12:52
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1158.17 | 504.87 | 504.87 |
Net Site Energy | 1158.17 | 504.87 | 504.87 |
Total Source Energy | 2967.24 | 1293.48 | 1293.48 |
Net Source Energy | 2967.24 | 1293.48 | 1293.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 241.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 352.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 165.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 95.16 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 821.79 | 336.39 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 241.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 48.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 352.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 59.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 165.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 95.16 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 179.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 93.37 | 146.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 358.23 | 146.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 179.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 93.37 | 146.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 358.23 | 146.64 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 821.788 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 821.788 | 100.00 |
Total On-Site and Utility Electric Sources | 821.788 | 100.00 |
Total Electricity End Uses | 821.788 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 821.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 6.8133 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 15.4032 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.4032 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.4032 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 8.7188 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 13.9457 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 13.9457 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:50 | 16-JAN-09:09 | - | - | - | 13-SEP-11:09 |
Heating | 0.00 | 155549.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30182.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26644.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8655.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4116.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 76253.67 | 159666.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 155549.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 30182.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26644.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 8655.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4116.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 261.48 | 0.00 | 0.00 | 0.00 |
Cooling | 154.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1116.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 189.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 523.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 103.16 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2602.60 | 364.64 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 113.99 | 0.00 | 0.00 | 0.00 |
Cooling | 67.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 486.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 82.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 228.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.97 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1134.53 | 158.95 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 113.99 | 0.00 | 0.00 | 0.00 |
Cooling | 67.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 486.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 82.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 228.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 44.97 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1134.53 | 158.95 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.62 |
CORE_RETAIL DIRECT AIR | 7.17 |
POINT_OF_SALE DIRECT AIR | 1.23 |
FRONT_RETAIL DIRECT AIR | 1.00 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.66 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.66 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 38048.71 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 43950.57 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 220954.39 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 33352.61 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 28143.94 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.62 | 1.62 | 1.62 | 1.62 | 1.67 | 1.67 | 1.00 | 0.974248 | 1.67 |
PSZ-AC:2 | 7.17 | 7.17 | 7.17 | 7.17 | 7.34 | 7.34 | 1.00 | 0.977118 | 7.34 |
PSZ-AC:3 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
PSZ-AC:4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.000000 | 1.00 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.67 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.34 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.23 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.00 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.67 | 1.67 | 1.67 | 1.10 | 28803.25 | 43950.57 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.34 | 7.34 | 7.34 | 4.85 | 132850.27 | 220954.39 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 0.812698 | 20557.59 | 33352.61 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 17093.79 | 28143.94 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.67 | 0.832975 | 1.11 | 27577.39 | 28803.25 | 14401.62 | 14401.62 | 0.783008 | 0.783010 | 0.783010 | 0.783010 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.34 | 3.67 | 4.89 | 123436.61 | 132850.27 | 66425.13 | 66425.13 | 0.767302 | 0.767300 | 0.767300 | 0.767300 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.23 | 0.615680 | 0.820907 | 20383.38 | 20557.59 | 10278.80 | 10278.80 | 0.795540 | 0.795540 | 0.795540 | 0.795540 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.00 | 0.501210 | 0.668280 | 16593.61 | 17093.79 | 8546.90 | 8546.90 | 0.787897 | 0.787900 | 0.787900 | 0.787900 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.67 | 1782.64 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.34 | 12367.62 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1363.31 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1109.84 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 6.813 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.883 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 36.923 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 15.403 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.633 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 8.719 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.719 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2588.290 | 6.813 | 42.195 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2588.290 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 24652.487 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24652.487 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2322.950 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.950 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2322.950 | 15.403 | 95.392 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2322.950 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 104.625 | 8.719 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 104.625 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.195 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.1725 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3437E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.1989 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.3274 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8365 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.721 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 29.02 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.950 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.978 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1954460 | 1.1954460 | 1.1954460 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
25 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
26 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
27 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
28 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
29 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
30 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
31 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
32 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
33 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
34 | 7 | -0.24541788E-08 | -0.10674912E-14 | 0.56595312E-14 | -0.88347803E-16 |
35 | 6 | 0.48874313E-05 | 0.32994277E-08 | 0.31919810E-02 | -0.26777012E-04 |
36 | 5 | -0.34768456E-03 | 0.19525666E-05 | -0.22384457 | 0.19572094E-02 |
37 | 4 | 0.79733842E-02 | 0.88847046E-04 | 4.8315443 | -0.45284193E-01 |
38 | 3 | -0.69943606E-01 | 0.70626596E-03 | -38.032707 | 0.39877855 |
39 | 2 | 0.24825401 | 0.11745943E-02 | 116.50592 | -1.4182332 |
40 | 1 | -0.35825340 | 0.35768630E-03 | -143.92024 | 2.0492525 |
41 | 0 | 0.17465044 | 0.86763216E-05 | 60.838472 | |
42 | 7 | -0.12489162E-07 | 0.28466235E-14 | -0.17145271E-13 | 0.26119495E-15 |
43 | 6 | 0.18517441E-05 | 0.69460444E-09 | 0.32027219E-02 | -0.26867115E-04 |
44 | 5 | -0.89695516E-04 | 0.39969105E-06 | -0.22445454 | 0.19625936E-02 |
45 | 4 | 0.17714562E-02 | 0.17921615E-04 | 4.8416944 | -0.45381772E-01 |
46 | 3 | -0.14613545E-01 | 0.14074818E-03 | -38.089997 | 0.39941188 |
47 | 2 | 0.50542763E-01 | 0.23137019E-03 | 116.61736 | -1.4197240 |
48 | 1 | -0.72070041E-01 | 0.69440628E-04 | -143.98582 | 2.0503304 |
49 | 0 | 0.34918756E-01 | 0.16519960E-05 | 60.838472 | |
50 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
51 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
52 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
53 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
54 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
55 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
56 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
57 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
58 | 7 | -0.21220229E-08 | -0.69274912E-15 | 0.44419095E-14 | -0.59983029E-16 |
59 | 6 | 0.55968656E-05 | 0.38086687E-08 | 0.31899104E-02 | -0.26759642E-04 |
60 | 5 | -0.40060043E-03 | 0.22548894E-05 | -0.22372688 | 0.19561706E-02 |
61 | 4 | 0.92029272E-02 | 0.10262663E-03 | 4.8295842 | -0.45265352E-01 |
62 | 3 | -0.80779323E-01 | 0.81597308E-03 | -38.021635 | 0.39865617 |
63 | 2 | 0.28678301 | 0.13572938E-02 | 116.48438 | -1.4179450 |
64 | 1 | -0.41389855 | 0.41342724E-03 | -143.90756 | 2.0490440 |
65 | 0 | 0.20178854 | 0.10024527E-04 | 60.838472 | |
66 | 7 | -0.12723796E-08 | -0.15085021E-15 | 0.80954726E-14 | -0.10933793E-15 |
67 | 6 | 0.91456241E-05 | 0.63025983E-08 | 0.31797574E-02 | -0.26674470E-04 |
68 | 5 | -0.66211654E-03 | 0.37378006E-05 | -0.22314974 | 0.19510765E-02 |
69 | 4 | 0.15256371E-01 | 0.17022008E-03 | 4.8199703 | -0.45172938E-01 |
70 | 3 | -0.13404479 | 0.13543778E-02 | -37.967318 | 0.39805580 |
71 | 2 | 0.47605416 | 0.22539081E-02 | 116.37865 | -1.4165309 |
72 | 1 | -0.68716389 | 0.68732095E-03 | -143.84532 | 2.0480210 |
73 | 0 | 0.33503722 | 0.16534103E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.38_SHGC_0.4 | 30 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 31 | 1 | VerySmooth | 4.262 | 0.604 | 0.475 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47441 | 0.15233 | 0.15233 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1913 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 18988.26929 | 22785.92314 | 1.35254 | 1.62304 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 20971.06117 | 25165.27341 | 0.89456 | 1.07347 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 83765.37894 | 100518.45473 | 5.97758 | 7.17310 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 54825.42079 | 65790.50494 | 2.30682 | 2.76818 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13784.33163 | 16541.19796 | 1.02613 | 1.23136 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10104.47283 | 12125.36740 | 0.43280 | 0.51936 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 11221.44973 | 13465.73968 | 0.83535 | 1.00242 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10099.79783 | 12119.75740 | 0.43260 | 0.51912 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40000 | 8.79438E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 31681.98241 | 38018.37889 | 1.38136 | 1.65763 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 21606.24 | 1.66595 | 1.66595 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 31413.62 | 1.07347 | 1.07347 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 102412.92 | 7.34108 | 7.34108 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 119811.16 | 2.76818 | 2.76818 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 17392.52 | 1.23136 | 1.23136 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 17153.83 | 0.51936 | 0.51936 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 14372.77 | 1.00242 | 1.00242 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 17148.25 | 0.51912 | 0.51912 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.62304 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.17310 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23136 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00242 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.65763 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.65763 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 38048.70912 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.62304 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.62304 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.62304 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.62304 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.66595 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.66595 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.97425 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.17310 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.17310 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.17310 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.17310 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.34108 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.34108 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97712 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23136 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23136 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23136 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23136 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23136 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23136 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00242 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00242 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00242 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00242 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00242 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00242 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.66595 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.34108 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.23136 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.00242 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.66595 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.66595 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.66595 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.66595 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09952 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.66595 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.83298 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.11063 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 27577.38785 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 28803.25000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14401.62500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14401.62500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78301 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78301 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78301 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78301 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28803.25000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 43950.56643 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.66595 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1782.64134 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 43950.56643 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.34108 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.34108 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.34108 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.34108 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.84511 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.34108 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.67054 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.89405 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 123436.60747 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 132850.27000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 66425.13500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 66425.13500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.76730 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.76730 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.76730 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.76730 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 132850.27000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 220954.38896 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.34108 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12367.61888 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 220954.38896 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23136 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23136 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23136 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23136 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.81270 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23136 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61568 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.82091 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 20383.38024 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20557.59000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10278.79500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10278.79500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.79554 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.79554 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.79554 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.79554 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20557.59000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33352.60726 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23136 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1363.31153 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33352.60726 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00242 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00242 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00242 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00242 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00242 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00242 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50121 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.66828 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 16593.61033 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 17093.79000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 8546.89500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 8546.89500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.78790 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.78790 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.78790 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.78790 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17093.79000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28143.93968 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00242 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1109.83875 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 28143.93968 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 27496.9 | 11.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 127089.9 | 12.56 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 19592.5 | 98.91 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16307.9 | 139.15 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.195 | 1.195 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.172 | 0.166 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 3.437E-002 | 3.409E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.199 | 0.190 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.327 | 0.303 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 13 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 5.4930046739E-002 | 0.2203509494 | Pass | Pass | 0.1971426843 | 1.5211100188 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.3644433138E-002 | 0.1446152354 | Pass | Pass | 0.2782329936 | 2.1089439585 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 5.8463819096E-002 | 0.2297086424 | Pass | Pass | 0.3796057210 | 3.0544397268 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 7.2111581414E-002 | 0.2461320041 | Pass | Pass | 6.5574211678E-002 | 0.2516430168 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 9.1982151242E-002 | 0.4061425727 | Pass | Pass | 7.7040494529E-002 | 0.5038204765 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.172 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.034 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.199 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.327 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.604 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.159 | 0.394 | 0.401 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.38_SHGC_0.4 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.159 | 0.394 | 0.401 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 2.623 | 0.440 | 0.445 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 2.623 | 0.440 | 0.445 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.014 | 1.195 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 6.8133 | 379.89 | 2588.29 | LightsWired | BLDG_LIGHT_BACK_SCH | 60.89 | 168.00 | 60.06 | 0.0000 | Y | 29.18 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 15.4032 | 1600.48 | 24652.49 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 56.75 | 0.0000 | Y | 262.61 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 15.4032 | 150.81 | 2322.95 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 15.4032 | 150.81 | 2322.95 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.76 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 8.7188 | 12.00 | 104.63 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.34 |
Interior Lighting Total | 13.9457 | 2293.99 | 31991.30 | 352.65 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.49 | 6163.12 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24652.49 | 6163.12 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 238.00 | AstronomicalClock | - | 42.59 | 42.59 | 1.90 | |
EXTERIOR_LIGHTS_B | 4328.05 | AstronomicalClock | - | 83.55 | 71.26 | 57.89 | |
Exterior Lighting Total | 4566.05 | 59.80 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 28803.25 | 22553.23 | 6250.02 | 0.78 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 132850.27 | 101936.01 | 30914.26 | 0.77 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20557.59 | 16354.39 | 4203.20 | 0.80 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 17093.79 | 13468.20 | 3625.59 | 0.79 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 27496.9 | 11.21 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 127089.9 | 12.56 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 19592.5 | 98.91 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 16307.9 | 139.15 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 38048.71 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 43950.57 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 220954.39 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33352.61 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 28143.94 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.58 | 622.50 | 1.66 | 1773.74 | 1070.05 | 1.00 | 1.33 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.67 | 1782.64 | 1070.05 | 1.00 | 1.34 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.34 | 12367.62 | 1684.71 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1363.31 | 1107.16 | 1.00 | 1.35 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1109.84 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 18988.27 | 22785.92 | 59.98 | 1.353 | 1.623 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.88 | 0.01018 | 21.70 | 0.00879 | 0.232 | 0.00 |
CORE_RETAIL | 83765.38 | 100518.45 | 62.81 | 5.978 | 7.173 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 23.89 | 23.88 | 0.00989 | 21.70 | 0.00879 | 1.890 | 0.00 |
POINT_OF_SALE | 13784.33 | 16541.20 | 109.68 | 1.026 | 1.231 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00889 | 29.05 | 0.00879 | 0.178 | 0.00 |
FRONT_RETAIL | 11221.45 | 13465.74 | 89.29 | 0.835 | 1.002 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00898 | 29.05 | 0.00879 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.58 | 100.00 | 0.00001 | 29.40 | 0.00879 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20971.06 | 25165.27 | 66.24 | 0.895 | 1.073 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00714 | -4.20 | 0.00269 | 0.232 | 0.00 |
CORE_RETAIL | 54825.42 | 65790.50 | 41.11 | 2.307 | 2.768 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 1.890 | 0.00 |
POINT_OF_SALE | 10104.47 | 12125.37 | 80.40 | 0.433 | 0.519 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_RETAIL | 10099.80 | 12119.76 | 80.36 | 0.433 | 0.519 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00751 | -4.20 | 0.00269 | 0.178 | 0.00 |
FRONT_ENTRY | 31681.98 | 38018.38 | 3168.20 | 1.381 | 1.658 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.04 | 0.00575 | -4.20 | 0.00269 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.67 | 1.67 | 1.07 | 1.07 | 1.6659 | 1.6230 | 1.6659 | 0.9742 | 1.0000 |
PSZ-AC:2 | 7.34 | 7.34 | 2.77 | 2.77 | 7.3411 | 7.1731 | 7.3411 | 0.9771 | 1.0000 |
PSZ-AC:3 | 1.23 | 1.23 | 0.52 | 0.52 | 1.2314 | 1.2314 | 1.2314 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.00 | 1.00 | 0.52 | 0.52 | 1.0024 | 1.0024 | 1.0024 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 38048.709 | 38048.709 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 38048.71 | 38048.71 | 1.657632 | 20.82 | 12.46 | 0.00571962 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.04 | 0.00574574 | 36.6645 | 38018.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 14401.625 | 0.000 | 1.665950 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 14401.62 | 11651.47 | 1.665950 | 23.67 | 17.09 | 0.00966357 | 12.80 | 11.97 | 0.00850000 | 22.36 | 0.00879438 | 15.90 | 13.9000 | 23.88 | 0.01018143 | 54.2581 | 18988.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 43950.566 | 43950.566 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43950.57 | 43950.57 | 1.665946 | 15.47 | 10.71 | 0.00618272 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 13.9000 | 21.11 | 0.00714331 | 45.2820 | 20971.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 66425.135 | 0.000 | 7.341080 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 66425.13 | 59778.99 | 7.341080 | 25.39 | 17.23 | 0.00912391 | 12.80 | 11.97 | 0.00850000 | 29.31 | 0.00879438 | 18.27 | 25.7484 | 23.88 | 0.00988894 | 52.7219 | 76331.11 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 220954.389 | 220954.389 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 220954.39 | 220954.39 | 7.341076 | 3.71 | 2.66 | 0.00421415 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 25.7484 | 21.11 | 0.00749486 | 47.4794 | 54825.42 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 10278.795 | 0.000 | 1.231360 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 10278.80 | 9597.31 | 1.231360 | 24.65 | 16.77 | 0.00887753 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 14.4645 | 23.89 | 0.00889138 | 47.4690 | 13777.04 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 33352.607 | 33352.607 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 33352.61 | 33352.61 | 1.231360 | 12.31 | 8.97 | 0.00585508 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 14.4645 | 21.11 | 0.00750687 | 47.5573 | 10104.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 8546.895 | 0.000 | 1.002420 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 8546.90 | 7891.49 | 1.002420 | 24.82 | 16.89 | 0.00894728 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00879438 | 18.22 | 17.7681 | 23.89 | 0.00898056 | 47.9384 | 11221.06 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 28143.940 | 28143.940 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28143.94 | 28143.94 | 1.002421 | 12.30 | 8.96 | 0.00585372 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 17.7680 | 21.11 | 0.00750599 | 47.5517 | 10099.80 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 38048.709 | 38048.709 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.657632 | 1.96759365 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 38048.71 | 38048.71 | 1.0000 | 1.96759365 | 1.657632 | 20.82 | 12.46 | 0.00571962 | 35446.9 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38048.71 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.05 | 0.00574574 | 21.04 | 0.00574574 | 36.6645 | 38018.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14401.625 | 0.000 | 1.665950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8041 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 14401.62 | 11651.47 | 1.0000 | 1.97746730 | 1.665950 | 23.67 | 17.09 | 0.00966357 | 48381.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14401.62 | 22.36 | 0.00879438 | 15.90 | 0.23156651 | 13.9000 | 23.89 | 0.00980389 | 23.88 | 0.01018143 | 54.2581 | 18988.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 43950.566 | 43950.566 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.665946 | 1.97746296 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 43950.57 | 43950.57 | 1.0000 | 1.97746296 | 1.665946 | 15.47 | 10.71 | 0.00618272 | 31180.7 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 43950.57 | -4.20 | 0.00269032 | -4.20 | 0.23156651 | 13.9000 | 20.87 | 0.00714331 | 21.11 | 0.00714331 | 45.2820 | 20971.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 66425.135 | 0.000 | 7.341080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8009 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 66425.13 | 59778.99 | 1.0000 | 8.71379430 | 7.341080 | 25.39 | 17.23 | 0.00912391 | 48763.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66425.13 | 29.31 | 0.00879438 | 18.27 | 1.89021192 | 25.7484 | 23.89 | 0.00925029 | 23.88 | 0.00988894 | 52.7219 | 76331.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 220954.389 | 220954.389 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.341076 | 8.71379002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 220954.39 | 220954.39 | 1.0000 | 8.71379002 | 7.341076 | 3.71 | 2.66 | 0.00421415 | 14299.4 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 220954.39 | -4.20 | 0.00269032 | -4.20 | 1.89021192 | 25.7484 | 20.75 | 0.00749486 | 21.11 | 0.00749486 | 47.4794 | 54825.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10278.795 | 0.000 | 1.231360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3429 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 10278.80 | 9597.31 | 1.0000 | 1.46161297 | 1.231360 | 24.65 | 16.77 | 0.00887753 | 47376.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10278.80 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 14.4645 | 23.89 | 0.00889160 | 23.89 | 0.00889138 | 47.4690 | 13777.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33352.607 | 33352.607 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.231360 | 1.46161355 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 33352.61 | 33352.61 | 1.0000 | 1.46161355 | 1.231360 | 12.31 | 8.97 | 0.00585508 | 27145.7 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33352.61 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 14.4645 | 20.93 | 0.00750687 | 21.11 | 0.00750687 | 47.5573 | 10104.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 8546.895 | 0.000 | 1.002420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4725 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 8546.90 | 7891.49 | 1.0000 | 1.18986330 | 1.002420 | 24.82 | 16.89 | 0.00894728 | 47730.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8546.90 | 29.14 | 0.00879438 | 18.22 | 0.17811053 | 17.7681 | 23.89 | 0.00898032 | 23.89 | 0.00898056 | 47.9384 | 11221.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28143.940 | 28143.940 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.002421 | 1.18986404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 28143.94 | 28143.94 | 1.0000 | 1.18986404 | 1.002421 | 12.30 | 8.96 | 0.00585372 | 27138.2 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28143.94 | -4.20 | 0.00269032 | -4.20 | 0.17811053 | 17.7680 | 20.93 | 0.00750599 | 21.11 | 0.00750599 | 47.5517 | 10099.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialDryBulb | 0.23 | 1.67 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialDryBulb | 1.89 | 7.34 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.23 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialDryBulb | 0.18 | 1.00 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 1145.50 | 3635.50 | 795.83 |
CORE_RETAIL | 1226.50 | 2989.67 | 158.33 |
POINT_OF_SALE | 1579.50 | 2491.33 | 266.83 |
FRONT_RETAIL | 1466.67 | 2981.00 | 503.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 2159.33 | 3638.17 | 821.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 0.83 | 0.00 | 0.00 | 0.00 |
Facility | 0.83 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.32 | 61.34 | 2317.33 | 0.554 | 0.027 | 0.000 | 0.000 |
CORE_RETAIL | 127.72 | 258.43 | 9762.95 | 0.853 | 0.005 | 0.000 | 0.000 |
POINT_OF_SALE | 12.04 | 24.35 | 919.94 | 1.232 | 0.029 | 0.000 | 0.000 |
FRONT_RETAIL | 12.04 | 24.35 | 919.94 | 1.185 | 0.029 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.32 | 61.34 | 2317.33 | 0.354 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 127.72 | 258.43 | 9762.95 | 0.686 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.04 | 24.35 | 919.94 | 0.686 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.04 | 24.35 | 919.94 | 0.686 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 821.79 | 3189.30 | 07-MAY-06:40 | 76253.67 | 10-AUG-15:50 |
Electricity:Building | 547.81 | 2983.86 | 07-MAY-07:20 | 39264.11 | 02-JAN-09:10 |
Electricity:Zone:BACK_SPACE | 79.17 | 589.27 | 01-JAN-00:10 | 4789.50 | 02-JAN-09:10 |
InteriorLights:Electricity | 352.65 | 1188.69 | 07-MAY-07:20 | 28493.07 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 29.18 | 129.41 | 01-JAN-00:10 | 2030.36 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 352.65 | 1188.69 | 07-MAY-07:20 | 28493.07 | 02-JAN-09:10 |
Electricity:Zone:CORE_RETAIL | 346.91 | 1597.18 | 07-MAY-07:20 | 26839.84 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 262.61 | 821.75 | 07-MAY-07:20 | 22187.24 | 02-JAN-09:10 |
Electricity:Zone:POINT_OF_SALE | 82.68 | 602.96 | 01-JAN-00:10 | 5011.54 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 37.71 | 189.21 | 01-JAN-00:10 | 2529.06 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.76 | 116.15 | 01-JAN-00:10 | 2090.65 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.34 | 5.23 | 01-JAN-00:10 | 94.16 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.34 | 5.23 | 01-JAN-00:10 | 94.16 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 821.79 | 3189.30 | 07-MAY-06:40 | 76253.67 | 10-AUG-15:50 |
ElectricityPurchased:Plant | 821.79 | 3189.30 | 07-MAY-06:40 | 76253.67 | 10-AUG-15:50 |
Cogeneration:ElectricityPurchased | 821.79 | 3189.30 | 07-MAY-06:40 | 76253.67 | 10-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 821.79 | 3189.30 | 07-MAY-06:40 | 76253.67 | 10-AUG-15:50 |
ElectricityNet:Plant | 821.79 | 3189.30 | 07-MAY-06:40 | 76253.67 | 10-AUG-15:50 |
Cogeneration:ElectricityNet | 821.79 | 3189.30 | 07-MAY-06:40 | 76253.67 | 10-AUG-15:50 |
Electricity:HVAC | 214.18 | 0.00 | 01-JAN-00:10 | 39365.03 | 10-AUG-15:00 |
Fans:Electricity | 165.38 | 0.00 | 01-JAN-00:10 | 12562.12 | 26-DEC-07:10 |
General:Fans:Electricity | 165.38 | 0.00 | 01-JAN-00:10 | 12562.12 | 26-DEC-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 48.80 | 0.00 | 01-JAN-00:10 | 30513.33 | 10-AUG-15:00 |
ExteriorLights:Electricity | 59.80 | 0.00 | 01-JAN-08:10 | 4566.05 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 59.80 | 0.00 | 01-JAN-08:10 | 4566.05 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 336.39 | 1862.00 | 02-APR-10:10 | 159666.06 | 16-JAN-09:10 |
Gas:Plant | 95.16 | 1862.00 | 02-APR-10:10 | 5085.05 | 14-FEB-13:00 |
WaterSystems:Gas | 95.16 | 1862.00 | 02-APR-10:10 | 5085.05 | 14-FEB-13:00 |
Water Heater:WaterSystems:Gas | 95.16 | 1862.00 | 02-APR-10:10 | 5085.05 | 14-FEB-13:00 |
Gas:HVAC | 241.22 | 0.00 | 01-JAN-00:10 | 155549.09 | 16-JAN-09:10 |
Heating:Gas | 241.22 | 0.00 | 01-JAN-00:10 | 155549.09 | 16-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 13-SEP-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 996.75 | 0.00 | 01-JAN-00:10 | 224174.55 | 16-JAN-09:10 |
EnergyTransfer:Building | 616.97 | 0.00 | 01-JAN-00:10 | 99735.28 | 16-JAN-09:10 |
EnergyTransfer:Zone:BACK_SPACE | 58.68 | 0.00 | 01-JAN-00:10 | 18586.73 | 16-JAN-08:10 |
Heating:EnergyTransfer | 103.39 | 0.00 | 01-JAN-00:10 | 84642.19 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 9.28 | 0.00 | 01-JAN-00:10 | 18586.73 | 16-JAN-08:10 |
Cooling:EnergyTransfer | 513.58 | 0.00 | 01-JAN-00:10 | 76694.40 | 01-AUG-06:10 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 49.40 | 0.00 | 01-JAN-00:10 | 10400.18 | 10-AUG-15:00 |
EnergyTransfer:Zone:CORE_RETAIL | 375.06 | 0.00 | 01-JAN-00:10 | 65702.46 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 9.06 | 0.00 | 01-JAN-00:10 | 51336.77 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 366.00 | 0.00 | 01-JAN-00:10 | 58405.52 | 29-JUN-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 64.51 | 0.00 | 01-JAN-00:10 | 10915.70 | 04-OCT-14:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 1.73 | 0.00 | 01-JAN-00:10 | 7653.70 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 62.77 | 0.00 | 01-JAN-00:10 | 10915.70 | 04-OCT-14:10 |
EnergyTransfer:Zone:FRONT_RETAIL | 39.82 | 0.00 | 01-JAN-00:10 | 8696.43 | 04-OCT-14:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 4.42 | 0.00 | 01-JAN-00:10 | 8240.09 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 35.40 | 0.00 | 01-JAN-00:10 | 8696.43 | 04-OCT-14:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 78.90 | 0.00 | 01-JAN-00:10 | 26136.23 | 18-FEB-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 78.90 | 0.00 | 01-JAN-00:10 | 26136.23 | 18-FEB-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 379.78 | 0.00 | 01-JAN-00:10 | 124439.27 | 16-JAN-09:10 |
HeatingCoils:EnergyTransfer | 192.98 | 0.00 | 01-JAN-00:10 | 124439.27 | 16-JAN-09:10 |
CoolingCoils:EnergyTransfer | 186.81 | 0.00 | 01-JAN-00:10 | 117450.49 | 10-AUG-14:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 9.278 | -49.404 | 0.000 | 0.000 | 39.506 | 29.179 | 49.992 | 0.000 | 0.000 | 0.040 | 0.006 | 0.000 | 0.000 | 0.000 | -14.776 | -63.817 |
CORE_RETAIL | 0.000 | 0.000 | 9.065 | -366.000 | 0.000 | 0.000 | 166.305 | 262.607 | 84.299 | 45.854 | 0.000 | 0.033 | 0.010 | 0.000 | -24.143 | 0.000 | -13.165 | -164.856 |
POINT_OF_SALE | 0.000 | 0.000 | 1.733 | -62.772 | 0.000 | 0.000 | 15.217 | 29.762 | 52.922 | 30.025 | 0.000 | 0.017 | 0.002 | 0.000 | -18.177 | 0.000 | -6.928 | -41.801 |
FRONT_RETAIL | 0.000 | 0.000 | 4.417 | -35.401 | 0.000 | 0.000 | 15.517 | 29.762 | 7.943 | 30.095 | 0.000 | 0.017 | 0.000 | 0.000 | -17.489 | 0.000 | -6.547 | -28.316 |
FRONT_ENTRY | 78.900 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.340 | 0.000 | 6.167 | 0.000 | 0.010 | 0.994 | 0.000 | -3.507 | 0.000 | -83.904 | -0.000 |
Total Facility | 78.900 | 0.000 | 24.493 | -513.577 | 0.000 | 0.000 | 236.546 | 352.651 | 195.156 | 112.141 | 0.000 | 0.118 | 1.012 | 0.000 | -63.315 | 0.000 | -125.319 | -298.789 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-AUG-06:02 | 0.00 | 0.00 | 0.00 | -32424.80 | 0.00 | 0.00 | 402.42 | 451.19 | 1226.28 | 0.00 | 0.00 | 0.00 | 30562.57 | 0.00 | -0.00 | 0.00 | -217.66 | 0.00 |
CORE_RETAIL | 04-JUL-08:62 | 0.00 | 0.00 | 0.00 | -158387.81 | 0.00 | 0.00 | 1665.83 | 2054.37 | 1550.87 | 1580.57 | 0.00 | 0.00 | 151665.21 | 0.00 | -0.00 | 0.00 | -129.04 | 0.00 |
POINT_OF_SALE | 05-OCT-06:02 | 0.00 | 0.00 | 0.00 | -26381.07 | 0.00 | 0.00 | 151.45 | 464.59 | 1298.17 | 0.00 | 0.00 | 0.00 | 25829.78 | 0.00 | -1283.35 | 0.00 | -79.57 | 0.00 |
FRONT_RETAIL | 11-SEP-06:02 | 0.00 | 0.00 | 0.00 | -20468.31 | 0.00 | 0.00 | 151.57 | 464.59 | 194.85 | 0.00 | 0.00 | 0.00 | 20579.08 | 0.00 | -861.48 | 0.00 | -60.30 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUN-06:02 | 0.00 | 0.00 | 0.00 | -227323.76 | 0.00 | 0.00 | 2312.16 | 6331.79 | 4787.13 | 0.00 | 0.00 | 0.00 | 215992.54 | 0.00 | -1597.88 | 0.00 | -501.98 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 16-JAN-08:61 | 0.00 | 0.00 | 44535.63 | 0.00 | 0.00 | 0.00 | 0.00 | 129.41 | 459.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -354.06 | -44770.84 |
CORE_RETAIL | 16-JAN-08:61 | 0.00 | 0.00 | 226627.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.62 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1509.27 | 0.00 | -314.62 | -226811.73 |
POINT_OF_SALE | 16-JAN-08:61 | 0.00 | 0.00 | 33022.92 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 486.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1003.37 | 0.00 | -160.29 | -32462.23 |
FRONT_RETAIL | 17-JAN-06:01 | 0.00 | 0.00 | 28155.15 | 0.00 | 0.00 | 0.00 | 0.00 | 116.15 | 97.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1146.52 | 0.00 | -100.63 | -27121.58 |
FRONT_ENTRY | 18-FEB-18:00 | 26135.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 76.04 | 0.00 | -305.04 | 0.00 | -26000.22 | 0.00 |
Total Facility | 16-JAN-08:61 | 5451.56 | 0.00 | 332306.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1599.57 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3709.29 | 0.00 | -4291.63 | -333152.34 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6230 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6659 | 0.1390 | 1.0000 | 0.2316 | 0.1390 | ||
PSZ-AC:2 | 7.1731 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.3411 | 0.2575 | 1.0000 | 1.8902 | 0.2575 | ||
PSZ-AC:3 | 1.2314 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2314 | 0.1446 | 1.0000 | 0.1781 | 0.1446 | ||
PSZ-AC:4 | 1.0024 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0024 | 0.1777 | 1.0000 | 0.1781 | 0.1777 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.6230 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.6230 | 1.0000 | 1.0000 | 0.2316 | 0.1427 | ||
PSZ-AC:2 | 7.1731 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.1731 | 1.0000 | 1.0000 | 1.8902 | 0.2635 | ||
PSZ-AC:3 | 1.2314 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2314 | 1.0000 | 1.0000 | 0.1781 | 0.1446 | ||
PSZ-AC:4 | 1.0024 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0024 | 1.0000 | 1.0000 | 0.1781 | 0.1777 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6230 | 1.6230 | 1.6230 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.1731 | 7.1731 | 7.1731 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2314 | 1.2314 | 1.2314 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0024 | 1.0024 | 1.0024 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6230 | 1.6659 | 1.6230 | 1.6230 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.1731 | 7.3411 | 7.1731 | 7.1731 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2314 | 1.2314 | 1.2314 | 1.2314 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0024 | 1.0024 | 1.0024 | 1.0024 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.6230 | 1.6230 | 1.6230 | 0.2316 | 0.2157 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.1731 | 7.1731 | 7.1731 | 1.8902 | 0.6828 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.2314 | 1.2314 | 1.2314 | 0.1781 | 0.3429 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0024 | 1.0024 | 1.0024 | 0.1781 | 0.3431 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.6230 | 1.6230 | 1.6230 | 1.6230 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.1731 | 7.1731 | 7.1731 | 7.1731 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.2314 | 1.2314 | 1.2314 | 1.2314 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0024 | 1.0024 | 1.0024 | 1.0024 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:52
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 241.22 | 155549.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 48.80 | 30513.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 352.65 | 28493.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 59.80 | 4566.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 165.38 | 12562.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 95.16 | 5085.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 821.79 |
Natural Gas | 0.00 | 336.39 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1158.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 153.73 |
Space Heating | 0.00 |
Space Cooling | 21.27 |
Fans (All) | 72.09 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 358.23 |
Subtotal | 358.23 |
Natural Gas [MJ/m2] | |
Space Heating | 105.15 |
Service Water Heating | 41.48 |
Miscellaneous (All) | 146.64 |
Subtotal | 146.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 30.45 |
Space Heating | 20.83 |
Space Cooling | 4.21 |
Fans (All) | 14.28 |
Service Water Heating | 8.22 |
Receptacle Equipment | 16.85 |
Miscellaneous | 5.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3175. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.676504E+11 |
February | 0.000 | 0.446663E+11 |
March | 0.000 | 0.211272E+11 |
April | 0.000 | 0.892564E+10 |
May | 0.000 | 0.322472E+10 |
June | 0.000 | 0.122256E+10 |
July | 0.000 | 0.305356E+09 |
August | 0.000 | 0.153824E+09 |
September | 0.000 | 0.174459E+10 |
October | 0.000 | 0.631373E+10 |
November | 0.000 | 0.305660E+11 |
December | 0.000 | 0.553218E+11 |
Annual Sum or Average | 0.241222E+12 | |
Minimum of Months | 0.000 | 0.153824E+09 |
Maximum of Months | 0.000 | 0.676504E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106325E+10 | 6006.40 | 06-JAN-07:05 | -2.3 | -2.5 | 0.165456E+10 | 2037.06 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.134327E+10 | 5626.60 | 09-FEB-07:05 | -0.7 | -1.1 | 0.155237E+10 | 2411.93 | 27-FEB-15:00 | 19.40 | 12.41 |
March | 0.270754E+10 | 5428.97 | 02-MAR-07:05 | 0.78 | -0.0 | 0.185267E+10 | 2451.22 | 18-MAR-15:39 | 20.40 | 10.37 |
April | 0.312974E+10 | 5902.44 | 29-APR-15:00 | 22.20 | 15.22 | 0.192357E+10 | 2451.26 | 27-APR-14:09 | 26.28 | 16.89 |
May | 0.484291E+10 | 10276.70 | 07-MAY-08:62 | 17.52 | 14.34 | 0.217189E+10 | 2451.25 | 06-MAY-12:00 | 23.90 | 17.57 |
June | 0.638117E+10 | 32339.27 | 29-JUN-06:02 | 12.70 | 11.22 | 0.218956E+10 | 2451.28 | 10-JUN-10:09 | 19.60 | 14.75 |
July | 0.808261E+10 | 31553.96 | 20-JUL-06:02 | 14.45 | 12.11 | 0.218543E+10 | 2451.29 | 28-JUL-14:09 | 20.00 | 15.21 |
August | 0.853476E+10 | 32431.74 | 01-AUG-06:02 | 11.32 | 11.32 | 0.227892E+10 | 2451.24 | 26-AUG-10:09 | 18.45 | 15.91 |
September | 0.582311E+10 | 27592.96 | 14-SEP-06:02 | 12.07 | 11.66 | 0.213878E+10 | 2451.25 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.361343E+10 | 5323.53 | 04-OCT-15:00 | 21.70 | 11.47 | 0.200208E+10 | 2451.20 | 21-OCT-15:50 | 14.08 | 9.81 |
November | 0.244374E+10 | 5448.87 | 11-NOV-09:05 | 0.78 | 0.55 | 0.170058E+10 | 2451.24 | 04-NOV-11:20 | 18.17 | 14.92 |
December | 0.143786E+10 | 5482.63 | 06-DEC-07:05 | 0.18 | -0.1 | 0.166059E+10 | 1973.84 | 02-DEC-15:09 | 11.52 | 5.35 |
Annual Sum or Average | 0.494034E+11 | 0.233110E+11 | ||||||||
Minimum of Months | 0.106325E+10 | 5323.53 | -2.3 | -2.5 | 0.155237E+10 | 1973.84 | 11.52 | 5.35 | ||
Maximum of Months | 0.853476E+10 | 32431.74 | 22.20 | 15.22 | 0.227892E+10 | 2451.29 | 26.28 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176440E+11 | 49447.80 | 15-JAN-09:05 | -2.5 | -3.8 | 0.697966E+10 | 9174.64 | 11-JAN-15:00 | 14.40 | 10.48 |
February | 0.187950E+11 | 50914.52 | 19-FEB-09:05 | -3.1 | -4.2 | 0.657234E+10 | 10326.99 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.274874E+11 | 44094.57 | 01-MAR-07:03 | -0.1 | -1.6 | 0.791529E+10 | 10326.69 | 10-MAR-15:09 | 16.02 | 11.50 |
April | 0.283736E+11 | 151504.03 | 28-APR-06:03 | 11.10 | 10.22 | 0.815413E+10 | 10327.04 | 29-APR-10:09 | 14.18 | 12.20 |
May | 0.350914E+11 | 155187.13 | 16-MAY-06:03 | 11.70 | 10.49 | 0.914836E+10 | 10327.10 | 20-MAY-10:50 | 14.82 | 10.06 |
June | 0.393630E+11 | 154708.52 | 03-JUN-06:03 | 11.97 | 9.99 | 0.922656E+10 | 10327.33 | 10-JUN-10:09 | 19.60 | 14.75 |
July | 0.446717E+11 | 158413.31 | 04-JUL-08:62 | 12.98 | 9.42 | 0.920776E+10 | 10327.31 | 28-JUL-14:09 | 20.00 | 15.21 |
August | 0.453258E+11 | 148410.19 | 01-AUG-06:02 | 11.32 | 11.32 | 0.959940E+10 | 10327.22 | 19-AUG-12:09 | 19.18 | 14.29 |
September | 0.360764E+11 | 152221.42 | 11-SEP-06:02 | 12.07 | 10.69 | 0.899008E+10 | 10327.28 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.300131E+11 | 135560.83 | 05-OCT-06:02 | 8.48 | 5.35 | 0.841362E+10 | 10326.75 | 24-OCT-14:09 | 16.78 | 11.76 |
November | 0.233930E+11 | 40604.05 | 11-NOV-09:02 | 0.78 | 0.55 | 0.712647E+10 | 10327.06 | 04-NOV-11:20 | 18.17 | 14.92 |
December | 0.197651E+11 | 47835.09 | 26-DEC-07:05 | -1.6 | -1.6 | 0.701227E+10 | 8848.23 | 02-DEC-14:30 | 11.95 | 5.64 |
Annual Sum or Average | 0.366000E+12 | 0.983459E+11 | ||||||||
Minimum of Months | 0.176440E+11 | 40604.05 | -3.1 | -4.2 | 0.657234E+10 | 8848.23 | 11.95 | 5.64 | ||
Maximum of Months | 0.453258E+11 | 158413.31 | 12.98 | 11.32 | 0.959940E+10 | 10327.33 | 20.00 | 15.21 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271594E+10 | 4626.42 | 15-JAN-09:05 | -2.5 | -3.8 | 0.690373E+09 | 973.08 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.304980E+10 | 6312.26 | 27-FEB-15:10 | 19.90 | 12.20 | 0.684124E+09 | 973.10 | 25-FEB-12:09 | 15.00 | 12.12 |
March | 0.408448E+10 | 6914.10 | 01-MAR-14:30 | 12.50 | 6.84 | 0.842350E+09 | 973.09 | 18-MAR-12:09 | 16.78 | 11.23 |
April | 0.470024E+10 | 19136.91 | 28-APR-06:03 | 11.10 | 10.22 | 0.824658E+09 | 973.12 | 27-APR-14:20 | 26.47 | 16.96 |
May | 0.581959E+10 | 23868.49 | 05-MAY-06:02 | 13.90 | 11.48 | 0.875917E+09 | 973.14 | 06-MAY-10:09 | 20.68 | 16.06 |
June | 0.648418E+10 | 24167.43 | 29-JUN-06:02 | 12.70 | 11.22 | 0.872140E+09 | 973.13 | 10-JUN-10:09 | 19.60 | 14.75 |
July | 0.773606E+10 | 24594.06 | 19-JUL-06:02 | 14.08 | 10.93 | 0.868349E+09 | 973.17 | 24-JUL-14:50 | 30.40 | 18.65 |
August | 0.870929E+10 | 23805.76 | 01-AUG-06:02 | 11.32 | 11.32 | 0.905457E+09 | 973.17 | 16-AUG-14:00 | 19.40 | 16.00 |
September | 0.753674E+10 | 24780.27 | 11-SEP-06:02 | 12.07 | 10.69 | 0.853837E+09 | 973.16 | 15-SEP-14:30 | 22.25 | 16.62 |
October | 0.556094E+10 | 26384.73 | 05-OCT-06:02 | 8.48 | 5.35 | 0.846969E+09 | 973.10 | 14-OCT-10:00 | 11.70 | 8.99 |
November | 0.339974E+10 | 8593.09 | 04-NOV-14:00 | 21.10 | 15.93 | 0.738159E+09 | 973.12 | 04-NOV-15:00 | 20.00 | 15.90 |
December | 0.297546E+10 | 5501.36 | 05-DEC-12:30 | 10.30 | 6.12 | 0.717672E+09 | 973.10 | 02-DEC-11:39 | 11.83 | 6.01 |
Annual Sum or Average | 0.627725E+11 | 0.972001E+10 | ||||||||
Minimum of Months | 0.271594E+10 | 4626.42 | -2.5 | -3.8 | 0.684124E+09 | 973.08 | 11.70 | 6.01 | ||
Maximum of Months | 0.870929E+10 | 26384.73 | 21.10 | 15.93 | 0.905457E+09 | 973.17 | 30.40 | 18.65 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.921836E+09 | 4047.59 | 07-JAN-07:05 | -2.5 | -2.6 | 0.663858E+09 | 892.57 | 11-JAN-15:09 | 14.40 | 10.48 |
February | 0.137449E+10 | 4174.19 | 19-FEB-09:05 | -3.1 | -4.2 | 0.644565E+09 | 973.09 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.209039E+10 | 4545.28 | 01-MAR-15:10 | 13.12 | 7.27 | 0.787812E+09 | 973.09 | 10-MAR-15:00 | 15.60 | 11.53 |
April | 0.250726E+10 | 13526.62 | 28-APR-06:03 | 11.10 | 10.22 | 0.791433E+09 | 973.10 | 29-APR-10:09 | 14.18 | 12.20 |
May | 0.323516E+10 | 17810.02 | 05-MAY-06:02 | 13.90 | 11.48 | 0.860866E+09 | 973.13 | 06-MAY-10:09 | 20.68 | 16.06 |
June | 0.378003E+10 | 19671.42 | 29-JUN-06:02 | 12.70 | 11.22 | 0.867963E+09 | 973.11 | 03-JUN-15:00 | 20.60 | 13.78 |
July | 0.488289E+10 | 19717.03 | 08-JUL-06:02 | 13.27 | 11.34 | 0.867513E+09 | 973.14 | 28-JUL-14:09 | 20.00 | 15.21 |
August | 0.578399E+10 | 19694.59 | 01-AUG-06:02 | 11.32 | 11.32 | 0.904487E+09 | 973.15 | 16-AUG-14:00 | 19.40 | 16.00 |
September | 0.482992E+10 | 20471.82 | 11-SEP-06:02 | 12.07 | 10.69 | 0.848481E+09 | 973.13 | 29-SEP-14:00 | 20.00 | 14.17 |
October | 0.324074E+10 | 19727.46 | 05-OCT-06:02 | 8.48 | 5.35 | 0.815245E+09 | 973.10 | 14-OCT-10:00 | 11.70 | 8.99 |
November | 0.158873E+10 | 6067.62 | 04-NOV-14:20 | 21.10 | 15.93 | 0.685047E+09 | 973.14 | 04-NOV-15:00 | 20.00 | 15.90 |
December | 0.116563E+10 | 3530.96 | 25-DEC-09:05 | -0.1 | -0.6 | 0.683066E+09 | 973.09 | 02-DEC-15:50 | 10.78 | 4.71 |
Annual Sum or Average | 0.354011E+11 | 0.942034E+10 | ||||||||
Minimum of Months | 0.921836E+09 | 3530.96 | -3.1 | -4.2 | 0.644565E+09 | 892.57 | 10.78 | 4.71 | ||
Maximum of Months | 0.578399E+10 | 20471.82 | 21.10 | 15.93 | 0.904487E+09 | 973.15 | 20.68 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.40 | 3.48 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.00 | 0.00 | 17.17 | 13.74 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292760E+10 | 44535.61 | 16-JAN-08:61 | -1.0 |
February | 0.203577E+10 | 44436.00 | 13-FEB-06:01 | 2.30 |
March | 0.755136E+09 | 44066.16 | 06-MAR-06:02 | 6.70 |
April | 0.237732E+09 | 38475.20 | 19-APR-06:03 | 2.48 |
May | 71356620.38 | 706.86 | 14-MAY-07:43 | 14.03 |
June | 68122954.03 | 708.71 | 25-JUN-07:53 | 15.60 |
July | 70890024.47 | 720.31 | 16-JUL-07:45 | 14.22 |
August | 71281114.67 | 709.72 | 06-AUG-07:53 | 14.20 |
September | 71580542.71 | 702.19 | 03-SEP-07:01 | 13.40 |
October | 0.104268E+09 | 22570.82 | 30-OCT-06:03 | 7.20 |
November | 0.833528E+09 | 44093.87 | 24-NOV-06:02 | 2.02 |
December | 0.203119E+10 | 44491.82 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.927846E+10 | |||
Minimum of Months | 68122954.03 | 702.19 | -1.0 | |
Maximum of Months | 0.292760E+10 | 44535.61 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201597E+10 | 226627.55 | 16-JAN-08:61 | -1.0 |
February | 0.120727E+10 | 225579.17 | 20-FEB-08:61 | 0.18 |
March | 0.579562E+09 | 35817.42 | 06-MAR-07:03 | 6.70 |
April | 0.507392E+09 | 14981.34 | 12-APR-06:08 | 3.58 |
May | 0.504445E+09 | 4918.14 | 14-MAY-07:43 | 14.03 |
June | 0.480720E+09 | 4917.79 | 25-JUN-07:53 | 15.60 |
July | 0.462269E+09 | 4978.54 | 16-JUL-07:45 | 14.22 |
August | 0.410744E+09 | 4921.11 | 06-AUG-07:53 | 14.20 |
September | 0.494164E+09 | 4866.33 | 03-SEP-07:01 | 13.40 |
October | 0.513125E+09 | 5007.45 | 16-OCT-05:45 | 6.78 |
November | 0.651834E+09 | 86961.56 | 24-NOV-07:03 | 1.20 |
December | 0.123717E+10 | 226607.21 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.906466E+10 | |||
Minimum of Months | 0.410744E+09 | 4866.33 | -1.0 | |
Maximum of Months | 0.201597E+10 | 226627.55 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.554155E+09 | 33022.92 | 16-JAN-08:61 | -1.0 |
February | 0.262515E+09 | 32804.24 | 19-FEB-08:61 | -4.7 |
March | 84188022.29 | 21990.16 | 06-MAR-06:02 | 6.70 |
April | 57536315.75 | 7386.65 | 18-APR-06:03 | 3.40 |
May | 52237629.79 | 533.69 | 14-MAY-07:43 | 14.03 |
June | 49685687.53 | 535.32 | 25-JUN-07:53 | 15.60 |
July | 45810844.40 | 546.40 | 16-JUL-07:45 | 14.22 |
August | 31540074.44 | 733.83 | 10-AUG-05:05 | 17.33 |
September | 46237087.62 | 723.38 | 14-SEP-05:03 | 12.62 |
October | 53837316.94 | 557.20 | 16-OCT-05:45 | 6.78 |
November | 0.124583E+09 | 23388.01 | 24-NOV-06:02 | 2.02 |
December | 0.370336E+09 | 33006.09 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.173266E+10 | |||
Minimum of Months | 31540074.44 | 533.69 | -4.7 | |
Maximum of Months | 0.554155E+09 | 33022.92 | 17.33 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128096E+10 | 28155.15 | 17-JAN-06:01 | 1.20 |
February | 0.661907E+09 | 28022.09 | 13-FEB-06:01 | 2.30 |
March | 0.292443E+09 | 27683.57 | 06-MAR-06:02 | 6.70 |
April | 0.164183E+09 | 13982.33 | 18-APR-06:03 | 3.40 |
May | 0.107195E+09 | 1089.16 | 14-MAY-07:43 | 14.03 |
June | 0.102537E+09 | 1091.26 | 25-JUN-07:53 | 15.60 |
July | 0.105230E+09 | 1110.35 | 16-JUL-07:45 | 14.22 |
August | 90198983.40 | 1098.43 | 06-AUG-07:53 | 14.20 |
September | 0.102630E+09 | 1071.59 | 03-SEP-07:01 | 13.40 |
October | 0.117280E+09 | 1124.76 | 16-OCT-05:45 | 6.78 |
November | 0.403993E+09 | 27712.65 | 24-NOV-06:02 | 2.02 |
December | 0.988598E+09 | 28066.66 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.441715E+10 | |||
Minimum of Months | 90198983.40 | 1071.59 | -0.8 | |
Maximum of Months | 0.128096E+10 | 28155.15 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139377E+11 | 25707.60 | 07-JAN-12:10 | -0.4 |
February | 0.106162E+11 | 26136.23 | 18-FEB-18:00 | -0.6 |
March | 0.887795E+10 | 18969.66 | 05-MAR-12:10 | 5.10 |
April | 0.592537E+10 | 16167.52 | 18-APR-17:00 | 7.20 |
May | 0.417312E+10 | 14488.58 | 23-MAY-17:00 | 8.30 |
June | 0.207164E+10 | 11543.34 | 13-JUN-11:07 | 11.28 |
July | 0.854389E+09 | 7931.25 | 12-JUL-11:05 | 13.98 |
August | 0.625532E+09 | 8670.29 | 01-AUG-11:05 | 13.62 |
September | 0.261241E+10 | 11337.32 | 16-SEP-11:04 | 11.78 |
October | 0.590706E+10 | 13446.37 | 31-OCT-17:00 | 9.40 |
November | 0.103219E+11 | 21461.52 | 12-NOV-18:00 | 3.30 |
December | 0.129770E+11 | 25671.22 | 26-DEC-12:10 | 0.27 |
Annual Sum or Average | 0.789003E+11 | |||
Minimum of Months | 0.625532E+09 | 7931.25 | -0.6 | |
Maximum of Months | 0.139377E+11 | 26136.23 | 13.98 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.244735E+10 | 2030.36 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.222649E+10 | 2030.36 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.253900E+10 | 2030.36 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.239592E+10 | 2030.36 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.249318E+10 | 2030.36 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.245011E+10 | 2030.36 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.243899E+10 | 2030.36 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.253900E+10 | 2030.36 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.239592E+10 | 2030.36 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.244735E+10 | 2030.36 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.236682E+10 | 2030.36 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.243899E+10 | 2030.36 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.291791E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.222649E+10 | 2030.36 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.253900E+10 | 2030.36 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.253041E+11 | 22187.24 | 02-JAN-09:09 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.220175E+11 | 22187.24 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.232639E+11 | 22187.24 | 01-MAR-09:09 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.191981E+11 | 22187.24 | 01-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.190034E+11 | 22187.24 | 01-MAY-16:00 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.188863E+11 | 20338.30 | 01-JUN-16:19 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.192844E+11 | 22187.24 | 12-JUL-08:09 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.207361E+11 | 22187.24 | 08-AUG-16:00 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.212665E+11 | 22187.24 | 07-SEP-08:09 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.236678E+11 | 22187.24 | 02-OCT-15:39 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.242645E+11 | 22187.24 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.257141E+11 | 22187.24 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.262607E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.188863E+11 | 20338.30 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.257141E+11 | 22187.24 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.244398E+10 | 2090.65 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.249959E+10 | 2090.65 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.244398E+10 | 2090.65 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.249582E+10 | 2090.65 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.227087E+10 | 2090.65 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.259032E+10 | 2090.65 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.244398E+10 | 2090.65 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.254307E+10 | 2090.65 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.249959E+10 | 2090.65 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.248746E+10 | 2090.65 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.259032E+10 | 2090.65 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.244398E+10 | 2090.65 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.249582E+10 | 2090.65 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.241345E+10 | 2090.65 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.248746E+10 | 2090.65 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.297621E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.227087E+10 | 2090.65 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.259032E+10 | 2090.65 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.112411E+09 | 94.16 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.102280E+09 | 94.16 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.116668E+09 | 94.16 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.110076E+09 | 94.16 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.114539E+09 | 94.16 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.112581E+09 | 94.16 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.112035E+09 | 94.16 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.116668E+09 | 94.16 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.110076E+09 | 94.16 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.112411E+09 | 94.16 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.108701E+09 | 94.16 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.112035E+09 | 94.16 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134048E+10 | ||||
Minimum of Months | 0.102280E+09 | 94.16 | 0.00 | 0.00 | |
Maximum of Months | 0.116668E+09 | 94.16 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.244735E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177526E+10 |
February | 0.479114E+10 | 0.222649E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150217E+10 |
March | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150368E+10 |
April | 0.518069E+10 | 0.239592E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2202245.00 | 0.143373E+10 |
May | 0.536353E+10 | 0.249318E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142580.55 | 0.121942E+10 |
June | 0.528933E+10 | 0.245011E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1225963.03 | 0.101682E+10 |
July | 0.525489E+10 | 0.243899E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12656570.47 | 0.818889E+09 |
August | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24100546.27 | 0.725427E+09 |
September | 0.518069E+10 | 0.239592E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135375.26 | 0.578660E+09 |
October | 0.524694E+10 | 0.244735E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127791E+10 |
November | 0.504819E+10 | 0.236682E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144025E+10 |
December | 0.525489E+10 | 0.243899E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148388E+10 |
Annual Sum or Average | 0.628175E+11 | 0.291791E+11 | 0.499918E+11 | 40463280.58 | 0.147761E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.222649E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578660E+09 |
Maximum of Months | 0.548013E+10 | 0.253900E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24100546.27 | 0.177526E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.253041E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157553E+10 |
February | 0.201852E+11 | 0.220175E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133329E+10 |
March | 0.230879E+11 | 0.232639E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135672E+10 |
April | 0.218263E+11 | 0.191981E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1798659.79 | 0.129003E+10 |
May | 0.225967E+11 | 0.190034E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116858.75 | 0.108409E+10 |
June | 0.222841E+11 | 0.188863E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1003869.19 | 0.905449E+09 |
July | 0.221389E+11 | 0.192844E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10260032.76 | 0.727737E+09 |
August | 0.230879E+11 | 0.207361E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19682014.34 | 0.645420E+09 |
September | 0.218263E+11 | 0.212665E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110899.33 | 0.510213E+09 |
October | 0.221054E+11 | 0.236678E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113458E+10 |
November | 0.212681E+11 | 0.242645E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128359E+10 |
December | 0.221389E+11 | 0.257141E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131785E+10 |
Annual Sum or Average | 0.264651E+12 | 0.262607E+12 | 0.842987E+11 | 32972334.15 | 0.131645E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.188863E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510213E+09 |
Maximum of Months | 0.230879E+11 | 0.257141E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19682014.34 | 0.157553E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800091E+09 |
February | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700513E+09 |
March | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730976E+09 |
April | 0.205665E+10 | 0.244398E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 952254.34 | 0.686888E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61900.44 | 0.563152E+09 |
June | 0.209978E+10 | 0.249959E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531376.46 | 0.467598E+09 |
July | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5354060.09 | 0.383671E+09 |
August | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10370107.71 | 0.349739E+09 |
September | 0.205665E+10 | 0.244398E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58731.72 | 0.275206E+09 |
October | 0.208295E+10 | 0.249582E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616587E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674484E+09 |
December | 0.208610E+10 | 0.248746E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678605E+09 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.529224E+11 | 17328430.75 | 0.692751E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275206E+09 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10370107.71 | 0.800091E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767148E+09 |
February | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666043E+09 |
March | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686430E+09 |
April | 0.205665E+10 | 0.244398E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 952133.98 | 0.646384E+09 |
May | 0.212923E+10 | 0.254307E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61785.31 | 0.533657E+09 |
June | 0.209978E+10 | 0.249959E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 531209.25 | 0.442737E+09 |
July | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5387188.29 | 0.360375E+09 |
August | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10382428.65 | 0.327253E+09 |
September | 0.205665E+10 | 0.244398E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58717.30 | 0.260561E+09 |
October | 0.208295E+10 | 0.249582E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579446E+09 |
November | 0.200405E+10 | 0.241345E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629447E+09 |
December | 0.208610E+10 | 0.248746E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647221E+09 |
Annual Sum or Average | 0.249375E+11 | 0.297621E+11 | 0.794328E+10 | 17373462.77 | 0.654670E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.227087E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260561E+09 |
Maximum of Months | 0.217552E+10 | 0.259032E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10382428.65 | 0.767148E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.112411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137965E+11 |
February | 0.00 | 0.102280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107477E+11 |
March | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924567E+10 |
April | 0.00 | 0.110076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877199.26 | 0.639639E+10 |
May | 0.00 | 0.114539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477511E+10 |
June | 0.00 | 0.112581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271234E+10 |
July | 0.00 | 0.112035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2331985.76 | 0.151323E+10 |
August | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7056629.25 | 0.124372E+10 |
September | 0.00 | 0.110076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344852E+10 |
October | 0.00 | 0.112411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659494E+10 |
November | 0.00 | 0.108701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104840E+11 |
December | 0.00 | 0.112035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129462E+11 |
Annual Sum or Average | 0.00 | 0.134048E+10 | 10265814.27 | 0.839043E+11 | |||||
Minimum of Months | 0.00 | 0.102280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124372E+10 |
Maximum of Months | 0.00 | 0.116668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7056629.25 | 0.137965E+11 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2030.36 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3022.31 | 12-JAN-24:00 |
February | 5888.82 | 01-FEB-15:09 | 2030.36 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2933.27 | 16-FEB-21:03 |
March | 5888.82 | 01-MAR-15:09 | 2030.36 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2611.55 | 04-MAR-22:03 |
April | 5888.82 | 01-APR-10:09 | 2030.36 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.84 | 01-APR-16:00 | 2817.49 | 07-APR-24:00 |
May | 5888.82 | 01-MAY-14:09 | 2030.36 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 | 05-MAY-16:00 | 2690.91 | 17-MAY-20:05 |
June | 5888.82 | 01-JUN-14:09 | 2030.36 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 | 28-JUN-16:00 | 2883.24 | 13-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 2030.36 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 238.40 | 30-JUL-18:03 | 1519.78 | 02-JUL-04:00 |
August | 5888.82 | 01-AUG-14:09 | 2030.36 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.34 | 13-AUG-18:03 | 2125.02 | 11-AUG-04:00 |
September | 5888.82 | 01-SEP-14:09 | 2030.36 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 14-SEP-17:00 | 1436.28 | 18-SEP-23:00 |
October | 5888.82 | 02-OCT-14:09 | 2030.36 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2810.52 | 31-OCT-20:03 |
November | 5888.82 | 01-NOV-14:09 | 2030.36 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3487.82 | 29-NOV-21:03 |
December | 5888.82 | 01-DEC-15:09 | 2030.36 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2944.71 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1436.28 | |||||
Maximum of Months | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 238.40 | 3487.82 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 22187.24 | 02-JAN-09:09 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2843.73 | 12-JAN-24:00 |
February | 24809.68 | 01-FEB-15:09 | 22187.24 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2598.59 | 16-FEB-04:00 |
March | 24809.68 | 01-MAR-15:09 | 22187.24 | 01-MAR-09:09 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2415.96 | 28-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 22187.24 | 01-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.66 | 01-APR-16:00 | 2651.95 | 07-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 22187.24 | 01-MAY-16:00 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 | 05-MAY-16:00 | 2245.46 | 17-MAY-20:10 |
June | 24809.68 | 01-JUN-14:09 | 20338.30 | 01-JUN-16:19 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.13 | 28-JUN-15:00 | 2722.04 | 13-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 22187.24 | 12-JUL-08:09 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.38 | 30-JUL-18:03 | 1392.76 | 02-JUL-04:00 |
August | 24809.68 | 01-AUG-14:09 | 22187.24 | 08-AUG-16:00 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 175.39 | 13-AUG-18:03 | 1920.61 | 11-AUG-04:00 |
September | 24809.68 | 01-SEP-14:09 | 22187.24 | 07-SEP-08:09 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | 14-SEP-17:00 | 1301.82 | 18-SEP-23:00 |
October | 24809.68 | 02-OCT-14:09 | 22187.24 | 02-OCT-15:39 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2370.36 | 31-OCT-20:10 |
November | 24809.68 | 01-NOV-14:09 | 22187.24 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2888.39 | 29-NOV-21:10 |
December | 24809.68 | 01-DEC-15:09 | 22187.24 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2431.84 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 20338.30 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.82 | |||||
Maximum of Months | 24809.68 | 22187.24 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 191.38 | 2888.39 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1384.67 | 12-JAN-24:00 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1273.55 | 16-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1287.32 | 28-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-APR-16:00 | 1340.94 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 05-MAY-16:00 | 1200.07 | 17-MAY-20:10 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 28-JUN-16:00 | 1299.54 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.19 | 30-JUL-18:03 | 687.73 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.08 | 08-AUG-17:00 | 1019.87 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 14-SEP-17:00 | 660.89 | 18-SEP-23:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1278.04 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1515.54 | 29-NOV-21:03 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1280.05 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.89 | |||||
Maximum of Months | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 94.19 | 1515.54 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2090.65 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1296.33 | 12-JAN-24:00 |
February | 2337.76 | 01-FEB-15:09 | 2090.65 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1269.15 | 16-FEB-21:03 |
March | 2337.76 | 01-MAR-15:09 | 2090.65 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1205.31 | 28-MAR-24:00 |
April | 2337.76 | 01-APR-10:09 | 2090.65 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 | 01-APR-16:00 | 1264.86 | 07-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2090.65 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 05-MAY-16:00 | 1124.02 | 17-MAY-20:10 |
June | 2337.76 | 01-JUN-14:09 | 2090.65 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 28-JUN-16:00 | 1227.61 | 13-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 2090.65 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.01 | 30-JUL-18:03 | 650.45 | 02-JUL-04:00 |
August | 2337.76 | 01-AUG-14:09 | 2090.65 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.85 | 13-AUG-18:03 | 965.40 | 11-AUG-04:00 |
September | 2337.76 | 01-SEP-14:09 | 2090.65 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 14-SEP-17:00 | 613.07 | 30-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 2090.65 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1218.80 | 31-OCT-20:03 |
November | 2337.76 | 01-NOV-14:09 | 2090.65 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1509.12 | 29-NOV-21:03 |
December | 2337.76 | 01-DEC-15:09 | 2090.65 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1275.23 | 22-DEC-21:03 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.07 | |||||
Maximum of Months | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 97.01 | 1509.12 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 94.16 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 26182.33 | 07-JAN-12:10 |
February | 0.00 | 01-FEB-00:10 | 94.16 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 26000.22 | 18-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 94.16 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 18835.12 | 05-MAR-12:10 |
April | 0.00 | 01-APR-00:10 | 94.16 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.47 | 01-APR-16:00 | 16383.30 | 18-APR-17:00 |
May | 0.00 | 01-MAY-00:10 | 94.16 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 14910.84 | 23-MAY-17:00 |
June | 0.00 | 01-JUN-00:10 | 94.16 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 12365.40 | 13-JUN-11:03 |
July | 0.00 | 01-JUL-00:10 | 94.16 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.35 | 24-JUL-15:00 | 8629.31 | 12-JUL-11:05 |
August | 0.00 | 01-AUG-00:10 | 94.16 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.42 | 10-AUG-17:00 | 9041.59 | 01-AUG-11:05 |
September | 0.00 | 01-SEP-00:10 | 94.16 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 12245.60 | 16-SEP-11:02 |
October | 0.00 | 01-OCT-00:10 | 94.16 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 13702.23 | 29-OCT-11:03 |
November | 0.00 | 01-NOV-00:10 | 94.16 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21402.62 | 12-NOV-17:00 |
December | 0.00 | 01-DEC-00:10 | 94.16 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 25325.44 | 26-DEC-12:10 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8629.31 | ||||
Maximum of Months | 0.00 | 94.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.42 | 26182.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6006.40 | 06-JAN-07:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.35 |
February | 5626.60 | 09-FEB-07:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.41 |
March | 5428.97 | 02-MAR-07:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.72 |
April | 5902.44 | 29-APR-15:00 | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 |
May | 10276.70 | 07-MAY-08:62 | 3680.51 | 1127.98 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.14 |
June | 32339.27 | 29-JUN-06:02 | 4416.61 | 2707.14 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.30 |
July | 31553.96 | 20-JUL-06:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.43 |
August | 32431.74 | 01-AUG-06:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.66 |
September | 27592.96 | 14-SEP-06:02 | 3680.51 | 2255.95 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5323.53 | 04-OCT-15:00 | 5888.82 | 2030.36 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 |
November | 5448.87 | 11-NOV-09:05 | 2944.41 | 902.38 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.61 |
December | 5482.63 | 06-DEC-07:05 | 2944.41 | 1804.76 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5323.53 | 2944.41 | 902.38 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32431.74 | 5888.82 | 2707.14 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49447.80 | 15-JAN-09:05 | 12404.84 | 9860.99 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.02 |
February | 50914.52 | 19-FEB-09:05 | 12404.84 | 9860.99 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.43 |
March | 44094.57 | 01-MAR-07:03 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.81 |
April | 151504.03 | 28-APR-06:03 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.33 |
May | 155187.13 | 16-MAY-06:03 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.68 |
June | 154708.52 | 03-JUN-06:03 | 12404.84 | 9860.99 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.75 |
July | 158413.31 | 04-JUL-08:62 | 12404.84 | 8217.50 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.04 |
August | 148410.19 | 01-AUG-06:02 | 15506.05 | 22598.11 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.03 |
September | 152221.42 | 11-SEP-06:02 | 15506.05 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.57 |
October | 135560.83 | 05-OCT-06:02 | 15506.05 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.51 |
November | 40604.05 | 11-NOV-09:02 | 12404.84 | 9860.99 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.26 |
December | 47835.09 | 26-DEC-07:05 | 12404.84 | 19721.99 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 40604.05 | 12404.84 | 8217.50 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.75 | |
Maximum of Months | 158413.31 | 15506.05 | 24652.49 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4626.42 | 15-JAN-09:05 | 1168.88 | 929.18 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.19 |
February | 6312.26 | 27-FEB-15:10 | 4675.52 | 4181.31 | 5841.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 |
March | 6914.10 | 01-MAR-14:30 | 2045.54 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 |
April | 19136.91 | 28-APR-06:03 | 1168.88 | 1858.36 | 5192.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.63 |
May | 23868.49 | 05-MAY-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 |
June | 24167.43 | 29-JUN-06:02 | 1753.32 | 2787.54 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.95 |
July | 24594.06 | 19-JUL-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.64 |
August | 23805.76 | 01-AUG-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.73 |
September | 24780.27 | 11-SEP-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.84 |
October | 26384.73 | 05-OCT-06:02 | 1461.10 | 2322.95 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.57 |
November | 8593.09 | 04-NOV-14:00 | 2337.76 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5501.36 | 05-DEC-12:30 | 2045.54 | 2090.65 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4626.42 | 1168.88 | 929.18 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26384.73 | 4675.52 | 4181.31 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4047.59 | 07-JAN-07:05 | 1168.88 | 929.18 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 |
February | 4174.19 | 19-FEB-09:05 | 1168.88 | 929.18 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.75 |
March | 4545.28 | 01-MAR-15:10 | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.10 |
April | 13526.62 | 28-APR-06:03 | 1168.88 | 1858.36 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.43 |
May | 17810.02 | 05-MAY-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 |
June | 19671.42 | 29-JUN-06:02 | 1753.32 | 2787.54 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 |
July | 19717.03 | 08-JUL-06:02 | 1461.10 | 1161.47 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 |
August | 19694.59 | 01-AUG-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.04 |
September | 20471.82 | 11-SEP-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 |
October | 19727.46 | 05-OCT-06:02 | 1461.10 | 2322.95 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.41 |
November | 6067.62 | 04-NOV-14:20 | 2337.76 | 2090.65 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 |
December | 3530.96 | 25-DEC-09:05 | 1168.88 | 929.18 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3530.96 | 1168.88 | 929.18 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | |
Maximum of Months | 20471.82 | 2337.76 | 2787.54 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.41 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.62 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.23 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.87 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.63 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.94 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.78 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | |
Maximum of Months | 0.00 | 0.00 | 5.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.41 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.716674E+11 | 53873.96 | 17-JAN-17:00 | 0.759049E+11 | 159666.06 | 16-JAN-09:09 |
February | 0.630707E+11 | 53986.49 | 18-FEB-17:00 | 0.521564E+11 | 153231.93 | 19-FEB-09:09 |
March | 0.679128E+11 | 52933.29 | 06-MAR-17:00 | 0.294505E+11 | 79840.48 | 06-MAR-07:10 |
April | 0.618589E+11 | 62845.99 | 27-APR-16:00 | 0.168452E+11 | 63084.25 | 19-APR-06:10 |
May | 0.639742E+11 | 62252.20 | 04-MAY-15:50 | 0.112955E+11 | 19551.80 | 23-MAY-16:40 |
June | 0.655630E+11 | 65690.64 | 28-JUN-16:00 | 0.896446E+10 | 16337.83 | 13-JUN-13:00 |
July | 0.727180E+11 | 73011.69 | 31-JUL-15:00 | 0.815632E+10 | 12094.67 | 12-JUL-11:20 |
August | 0.787484E+11 | 76253.67 | 10-AUG-15:50 | 0.806161E+10 | 11881.44 | 01-AUG-11:30 |
September | 0.683444E+11 | 66739.67 | 14-SEP-15:30 | 0.939227E+10 | 15809.14 | 26-SEP-13:00 |
October | 0.679252E+11 | 59410.60 | 04-OCT-14:00 | 0.142757E+11 | 40911.48 | 29-OCT-08:30 |
November | 0.680921E+11 | 56904.04 | 04-NOV-14:30 | 0.383719E+11 | 116335.34 | 24-NOV-07:10 |
December | 0.719132E+11 | 53732.66 | 26-DEC-16:19 | 0.635102E+11 | 155222.40 | 26-DEC-07:10 |
Annual Sum or Average | 0.821788E+12 | 0.336385E+12 | ||||
Minimum of Months | 0.618589E+11 | 52933.29 | 0.806161E+10 | 11881.44 | ||
Maximum of Months | 0.787484E+11 | 76253.67 | 0.759049E+11 | 159666.06 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.328555E+11 | 0.675724E+10 | 0.164409E+11 | 0.00 | 0.156138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288880E+11 | 0.548972E+10 | 0.149157E+11 | 0.00 | 0.137605E+11 | 0.00 | 0.00 | 16726283.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311002E+11 | 0.523675E+10 | 0.168545E+11 | 0.00 | 0.146735E+11 | 0.00 | 0.00 | 47860510.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265921E+11 | 0.422339E+10 | 0.160165E+11 | 0.00 | 0.136042E+11 | 0.00 | 0.00 | 0.142271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266972E+11 | 0.368226E+10 | 0.166477E+11 | 0.00 | 0.135862E+11 | 0.00 | 0.00 | 0.336075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264482E+11 | 0.321553E+10 | 0.162772E+11 | 0.00 | 0.127860E+11 | 0.00 | 0.00 | 0.683607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268104E+11 | 0.346137E+10 | 0.163871E+11 | 0.00 | 0.125186E+11 | 0.00 | 0.00 | 0.135406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.285724E+11 | 0.403228E+10 | 0.168545E+11 | 0.00 | 0.126220E+11 | 0.00 | 0.00 | 0.166672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.286605E+11 | 0.470009E+10 | 0.160165E+11 | 0.00 | 0.128240E+11 | 0.00 | 0.00 | 0.614328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.312192E+11 | 0.572988E+10 | 0.164409E+11 | 0.00 | 0.139213E+11 | 0.00 | 0.00 | 0.613882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.315669E+11 | 0.631099E+10 | 0.159174E+11 | 0.00 | 0.141440E+11 | 0.00 | 0.00 | 0.152716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332401E+11 | 0.695723E+10 | 0.163871E+11 | 0.00 | 0.153288E+11 | 0.00 | 0.00 | 2093.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352651E+12 | 0.597967E+11 | 0.195156E+12 | 0.165383E+12 | 0.00 | 0.488018E+11 | |||||||
Minimum of Months | 0.264482E+11 | 0.321553E+10 | 0.149157E+11 | 0.00 | 0.125186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.332401E+11 | 0.695723E+10 | 0.168545E+11 | 0.00 | 0.156138E+11 | 0.00 | 0.00 | 0.166672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.676504E+11 | 0.00 | 0.825443E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.446663E+11 | 0.00 | 0.749016E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.211272E+11 | 0.00 | 0.832331E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.892564E+10 | 0.00 | 0.791955E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.322472E+10 | 0.00 | 0.807080E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.122256E+10 | 0.00 | 0.774190E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.305356E+09 | 0.00 | 0.785096E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.153824E+09 | 0.00 | 0.790779E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.174459E+10 | 0.00 | 0.764768E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.631373E+10 | 0.00 | 0.796201E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.305660E+11 | 0.00 | 0.780593E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.553218E+11 | 0.00 | 0.818835E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241222E+12 | 0.951629E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.153824E+09 | 0.00 | 0.749016E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.676504E+11 | 0.00 | 0.832331E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28493.07 | 02-JAN-09:09 | 4566.05 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 12527.60 | 16-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28493.07 | 01-FEB-09:09 | 4566.05 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 12472.32 | 19-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28493.07 | 01-MAR-09:09 | 4566.05 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 10507.39 | 05-MAR-09:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28493.07 | 01-APR-16:00 | 4566.05 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 10961.77 | 30-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28493.07 | 01-MAY-16:00 | 4566.05 | 01-MAY-19:19 | 10771.04 | 01-MAY-08:09 | 0.00 | 9732.28 | 07-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 26644.13 | 01-JUN-16:19 | 4566.05 | 01-JUN-19:00 | 10771.04 | 01-JUN-08:09 | 0.00 | 10944.15 | 04-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28493.07 | 12-JUL-08:09 | 4566.05 | 01-JUL-20:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 10944.15 | 04-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28493.07 | 08-AUG-16:00 | 4566.05 | 01-AUG-19:40 | 10771.04 | 01-AUG-08:09 | 0.00 | 10638.00 | 30-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28493.07 | 07-SEP-08:09 | 4566.05 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 10605.59 | 03-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28493.07 | 02-OCT-15:39 | 4566.05 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 10054.88 | 29-OCT-08:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28493.07 | 01-NOV-08:09 | 4566.05 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 11131.00 | 24-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28493.07 | 01-DEC-09:09 | 4566.05 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 12562.12 | 26-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 26644.13 | 4566.05 | 10771.04 | 0.00 | 9732.28 | 0.00 | 0.00 | |||||
Maximum of Months | 28493.07 | 4566.05 | 10771.04 | 0.00 | 12562.12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2261.60 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4274.22 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21276.45 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19714.50 | 06-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21578.09 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28219.73 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30513.33 | 10-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23184.04 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12831.22 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10324.66 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 02-DEC-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30513.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 53873.96 | 17-JAN-17:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 10043.81 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53986.49 | 18-FEB-17:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 10156.33 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52933.29 | 06-MAR-17:00 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 9103.13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 62845.99 | 27-APR-16:00 | 26644.13 | 10771.04 | 0.00 | 0.00 | 7315.27 | 0.00 | 0.00 | 18115.55 | 0.00 |
May | 62252.20 | 04-MAY-15:50 | 26644.13 | 10771.04 | 0.00 | 0.00 | 7315.27 | 0.00 | 0.00 | 17521.77 | 0.00 |
June | 65690.64 | 28-JUN-16:00 | 26644.13 | 10771.04 | 0.00 | 0.00 | 7315.27 | 0.00 | 0.00 | 20960.20 | 0.00 |
July | 73011.69 | 31-JUL-15:00 | 26644.13 | 10771.04 | 0.00 | 0.00 | 8064.96 | 0.00 | 0.00 | 27531.56 | 0.00 |
August | 76253.67 | 10-AUG-15:50 | 26644.13 | 10771.04 | 0.00 | 0.00 | 8655.60 | 0.00 | 0.00 | 30182.90 | 0.00 |
September | 66739.67 | 14-SEP-15:30 | 26644.13 | 10771.04 | 0.00 | 0.00 | 7411.64 | 0.00 | 0.00 | 21912.86 | 0.00 |
October | 59410.60 | 04-OCT-14:00 | 28493.07 | 10771.04 | 0.00 | 0.00 | 7315.27 | 0.00 | 0.00 | 12831.22 | 0.00 |
November | 56904.04 | 04-NOV-14:30 | 28493.07 | 10771.04 | 0.00 | 0.00 | 7315.27 | 0.00 | 0.00 | 10324.66 | 0.00 |
December | 53732.66 | 26-DEC-16:19 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 9902.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 52933.29 | 26644.13 | 10771.04 | 0.00 | 0.00 | 7315.27 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76253.67 | 28493.07 | 10771.04 | 4566.05 | 0.00 | 10156.33 | 0.00 | 0.00 | 30182.90 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 155549.09 | 16-JAN-09:09 | 0.00 | 5083.85 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 151146.69 | 19-FEB-09:09 | 0.00 | 5085.05 | 14-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 77978.48 | 06-MAR-07:10 | 0.00 | 5080.82 | 03-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 61222.25 | 19-APR-06:10 | 0.00 | 5061.82 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 15893.55 | 23-MAY-16:00 | 0.00 | 5034.98 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 11471.94 | 13-JUN-13:00 | 0.00 | 5004.21 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 7212.49 | 09-JUL-12:00 | 0.00 | 4980.11 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 7489.73 | 01-AUG-11:09 | 0.00 | 4970.29 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 10967.37 | 26-SEP-14:30 | 0.00 | 4984.72 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 39049.48 | 29-OCT-08:30 | 0.00 | 5014.44 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 111779.63 | 24-NOV-07:10 | 0.00 | 5043.60 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 153360.40 | 26-DEC-07:10 | 0.00 | 5068.78 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 7212.49 | 0.00 | 4970.29 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 155549.09 | 0.00 | 5085.05 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 19.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.02 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.12 | 250.33 | 21.11 | 250.33 | 21.11 |
February | 376.00 | 21.31 | 191.67 | 21.11 | 191.67 | 21.11 |
March | 422.00 | 21.63 | 82.33 | 21.12 | 82.33 | 21.12 |
April | 385.17 | 22.40 | 14.17 | 21.12 | 14.17 | 21.12 |
May | 336.17 | 23.28 | 5.33 | 23.89 | 0.00 | 0.00 |
June | 196.83 | 23.63 | 11.33 | 23.89 | 0.00 | 0.00 |
July | 77.17 | 23.74 | 117.33 | 23.89 | 0.00 | 0.00 |
August | 37.17 | 23.58 | 171.67 | 23.89 | 0.00 | 0.00 |
September | 166.67 | 23.48 | 44.00 | 23.89 | 0.00 | 0.00 |
October | 410.33 | 22.73 | 1.17 | 21.14 | 1.17 | 21.14 |
November | 399.00 | 21.63 | 68.00 | 21.12 | 68.00 | 21.12 |
December | 415.00 | 21.13 | 188.17 | 21.11 | 188.17 | 21.11 |
Annual Sum or Average | 3635.50 | 22.10 | 1145.50 | 21.96 | 795.83 | 21.11 |
Minimum of Months | 37.17 | 21.12 | 1.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.74 | 250.33 | 23.89 | 250.33 | 21.14 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.13 | 74.00 | 21.11 | 74.00 | 21.11 |
February | 376.00 | 21.34 | 46.83 | 21.11 | 46.83 | 21.11 |
March | 422.00 | 21.73 | 2.50 | 21.11 | 2.50 | 21.11 |
April | 346.00 | 22.33 | 19.50 | 23.88 | 0.00 | 0.00 |
May | 160.50 | 22.73 | 74.83 | 23.88 | 0.00 | 0.00 |
June | 48.67 | 23.08 | 148.17 | 23.89 | 0.00 | 0.00 |
July | 12.33 | 23.39 | 289.33 | 23.89 | 0.00 | 0.00 |
August | 14.50 | 23.23 | 339.83 | 23.89 | 0.00 | 0.00 |
September | 73.83 | 22.95 | 189.00 | 23.88 | 0.00 | 0.00 |
October | 317.33 | 22.38 | 3.83 | 23.89 | 0.00 | 0.00 |
November | 389.50 | 21.54 | 8.67 | 22.29 | 5.00 | 21.11 |
December | 415.00 | 21.14 | 30.00 | 21.11 | 30.00 | 21.11 |
Annual Sum or Average | 2989.67 | 21.75 | 1226.50 | 23.53 | 158.33 | 21.11 |
Minimum of Months | 12.33 | 21.13 | 2.50 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 422.00 | 23.39 | 339.83 | 23.89 | 74.00 | 21.11 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.67 | 21.44 | 109.50 | 21.11 | 109.50 | 21.11 |
February | 341.83 | 21.94 | 49.67 | 21.11 | 49.67 | 21.11 |
March | 352.83 | 22.59 | 14.17 | 21.57 | 11.83 | 21.11 |
April | 237.83 | 22.81 | 48.00 | 23.79 | 1.67 | 21.10 |
May | 116.17 | 22.96 | 92.33 | 23.89 | 0.00 | 0.00 |
June | 45.33 | 23.34 | 164.33 | 23.89 | 0.00 | 0.00 |
July | 13.83 | 23.69 | 297.83 | 23.89 | 0.00 | 0.00 |
August | 12.83 | 23.53 | 358.33 | 23.89 | 0.00 | 0.00 |
September | 40.83 | 23.22 | 258.33 | 23.89 | 0.00 | 0.00 |
October | 182.33 | 22.87 | 78.50 | 23.89 | 0.00 | 0.00 |
November | 331.50 | 22.05 | 32.00 | 22.36 | 17.67 | 21.11 |
December | 402.33 | 21.65 | 76.50 | 21.11 | 76.50 | 21.11 |
Annual Sum or Average | 2491.33 | 22.18 | 1579.50 | 23.42 | 266.83 | 21.11 |
Minimum of Months | 12.83 | 21.44 | 14.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 413.67 | 23.69 | 358.33 | 23.89 | 109.50 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.19 | 177.50 | 21.11 | 177.50 | 21.11 |
February | 363.83 | 21.55 | 98.33 | 21.11 | 98.33 | 21.11 |
March | 392.83 | 22.05 | 38.50 | 21.11 | 38.50 | 21.11 |
April | 311.00 | 22.49 | 38.17 | 23.21 | 9.33 | 21.11 |
May | 201.17 | 22.86 | 56.00 | 23.89 | 0.00 | 0.00 |
June | 92.83 | 23.25 | 84.50 | 23.89 | 0.00 | 0.00 |
July | 39.17 | 23.58 | 239.83 | 23.89 | 0.00 | 0.00 |
August | 27.00 | 23.36 | 304.00 | 23.89 | 0.00 | 0.00 |
September | 80.17 | 23.07 | 195.00 | 23.89 | 0.00 | 0.00 |
October | 269.17 | 22.54 | 45.17 | 23.89 | 0.00 | 0.00 |
November | 377.50 | 21.62 | 53.33 | 21.61 | 43.67 | 21.11 |
December | 412.33 | 21.35 | 136.33 | 21.11 | 136.33 | 21.11 |
Annual Sum or Average | 2981.00 | 21.96 | 1466.67 | 22.93 | 503.67 | 21.11 |
Minimum of Months | 27.00 | 21.19 | 38.17 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 414.00 | 23.58 | 304.00 | 23.89 | 177.50 | 21.11 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.10722 | 36.45112 | -0.5566 | 11.66669 |
February | 376.00000 | 21.29701 | 37.91943 | -0.4853 | 10.67831 |
March | 422.00000 | 21.61796 | 38.83357 | -0.3633 | 8.52164 |
April | 405.00000 | 22.46578 | 41.32398 | -0.1171 | 6.69717 |
May | 418.00000 | 23.38975 | 42.70607 | -0.8306 | 20.90863 |
June | 408.00000 | 23.76131 | 42.43573 | -0.6510 | 14.31870 |
July | 415.00000 | 23.86610 | 45.85798 | -0.5474 | 11.48173 |
August | 422.00000 | 23.86710 | 49.14763 | -0.5208 | 10.85999 |
September | 405.00000 | 23.71913 | 48.75255 | -0.6425 | 14.20921 |
October | 414.00000 | 22.73041 | 44.51991 | -0.0202 | 6.11024 |
November | 399.00000 | 21.61473 | 44.18972 | -0.3315 | 8.56177 |
December | 415.00000 | 21.11855 | 38.64848 | -0.5241 | 10.88572 |
Annual Sum or Average | 4913.00000 | 22.55658 | 42.59222 | -0.4665 | 11.25612 |
Minimum of Months | 376.00000 | 21.10722 | 36.45112 | -0.8306 | 6.11024 |
Maximum of Months | 422.00000 | 23.86710 | 49.14763 | -0.0202 | 20.90863 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.12132 | 33.45968 | -0.4504 | 9.41628 |
February | 376.00000 | 21.33860 | 34.76004 | -0.3656 | 8.51315 |
March | 422.00000 | 21.74136 | 35.19225 | -0.2251 | 6.86057 |
April | 405.00000 | 22.56080 | 38.21574 | 0.00908 | 6.29891 |
May | 418.00000 | 23.43925 | 40.88597 | -0.6651 | 15.50104 |
June | 408.00000 | 23.78862 | 41.39332 | -0.5069 | 10.72531 |
July | 415.00000 | 23.87796 | 44.98579 | -0.4214 | 8.92964 |
August | 422.00000 | 23.87272 | 48.27650 | -0.4053 | 8.63842 |
September | 405.00000 | 23.70533 | 47.27614 | -0.5209 | 11.26083 |
October | 414.00000 | 22.74143 | 41.79044 | 0.07804 | 6.17863 |
November | 399.00000 | 21.59594 | 41.34765 | -0.2380 | 7.33495 |
December | 415.00000 | 21.14040 | 35.46470 | -0.4162 | 8.74661 |
Annual Sum or Average | 4913.00000 | 22.58746 | 40.28798 | -0.3445 | 9.04278 |
Minimum of Months | 376.00000 | 21.12132 | 33.45968 | -0.6651 | 6.17863 |
Maximum of Months | 422.00000 | 23.87796 | 48.27650 | 0.07804 | 15.50104 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.43090 | 32.45738 | -0.4096 | 9.32628 |
February | 376.00000 | 22.10317 | 32.66102 | -0.2067 | 8.06159 |
March | 422.00000 | 22.79118 | 32.31999 | -0.0106 | 6.76752 |
April | 405.00000 | 23.24534 | 35.22232 | 0.15556 | 7.08592 |
May | 418.00000 | 23.63130 | 38.61433 | -0.6117 | 14.17314 |
June | 408.00000 | 23.83304 | 39.99247 | -0.4956 | 10.55425 |
July | 415.00000 | 23.89462 | 43.70591 | -0.3970 | 8.57475 |
August | 422.00000 | 23.89211 | 46.59623 | -0.3470 | 7.86239 |
September | 405.00000 | 23.83010 | 44.81847 | -0.4215 | 9.48467 |
October | 414.00000 | 23.43980 | 38.36820 | 0.24588 | 7.37360 |
November | 399.00000 | 22.35638 | 38.91009 | -0.0949 | 7.25208 |
December | 415.00000 | 21.70891 | 34.01136 | -0.3185 | 8.49672 |
Annual Sum or Average | 4913.00000 | 23.02068 | 38.17566 | -0.2436 | 8.76014 |
Minimum of Months | 376.00000 | 21.43090 | 32.31999 | -0.6117 | 6.76752 |
Maximum of Months | 422.00000 | 23.89462 | 46.59623 | 0.24588 | 14.17314 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.17340 | 32.78064 | -0.5084 | 10.79849 |
February | 376.00000 | 21.61308 | 33.71015 | -0.3485 | 9.09948 |
March | 422.00000 | 22.17200 | 33.82283 | -0.1743 | 7.31842 |
April | 405.00000 | 22.80995 | 36.70028 | 0.02932 | 6.93939 |
May | 418.00000 | 23.39096 | 39.91726 | -0.7366 | 18.33533 |
June | 408.00000 | 23.74777 | 40.75412 | -0.5766 | 12.62641 |
July | 415.00000 | 23.86894 | 44.87379 | -0.4572 | 9.74219 |
August | 422.00000 | 23.86843 | 48.08487 | -0.4022 | 8.84228 |
September | 405.00000 | 23.73124 | 46.30966 | -0.5016 | 11.44098 |
October | 414.00000 | 23.01309 | 39.92747 | 0.12314 | 6.89645 |
November | 399.00000 | 21.73634 | 40.33614 | -0.2624 | 8.14593 |
December | 415.00000 | 21.35354 | 34.59243 | -0.4356 | 9.84353 |
Annual Sum or Average | 4913.00000 | 22.71618 | 39.35395 | -0.3549 | 10.01527 |
Minimum of Months | 376.00000 | 21.17340 | 32.78064 | -0.7366 | 6.89645 |
Maximum of Months | 422.00000 | 23.86894 | 48.08487 | 0.12314 | 18.33533 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 1703.83 | 483.55 | 1.25 | 1701.07 | 2.76 | 0.00 | 0.00 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 | 0.81 | 18-MAR-15:20 | 0.81 | 18-MAR-15:20 | 0.00 | 18-MAR-15:10 | 0.23 | 18-MAR-15:20 | 0.00 | 01-MAR-00:10 |
April | 0.386232E+09 | 0.103094E+09 | 41.20 | 0.347391E+09 | 38840414.04 | 0.00 | 0.67 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 8689.45 | 27-APR-15:00 | 7556.77 | 27-APR-15:00 | 1132.68 | 27-APR-15:00 | 2251.08 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.110540E+10 | 0.283177E+09 | 155.95 | 0.946337E+09 | 0.159060E+09 | 0.00 | 0.73 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 | 9942.64 | 06-MAY-13:50 | 7857.61 | 06-MAY-14:10 | 2411.80 | 07-MAY-08:62 | 2384.70 | 06-MAY-13:50 | 0.00 | 01-MAY-00:10 |
June | 0.253211E+10 | 0.644594E+09 | 246.67 | 0.228465E+10 | 0.247461E+09 | 0.00 | 1.00 | 29-JUN-06:02 | 0.00 | 01-JUN-00:10 | 27259.27 | 29-JUN-06:02 | 18791.38 | 29-JUN-06:02 | 8467.89 | 29-JUN-06:02 | 5781.04 | 29-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.601453E+10 | 0.148906E+10 | 312.95 | 0.496010E+10 | 0.105443E+10 | 0.00 | 1.00 | 20-JUL-06:02 | 0.00 | 01-JUL-00:10 | 28853.21 | 31-JUL-06:02 | 22499.48 | 23-JUL-08:62 | 10742.53 | 25-JUL-06:02 | 6142.31 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.758883E+10 | 0.187725E+10 | 326.35 | 0.619729E+10 | 0.139153E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 29152.67 | 25-AUG-06:02 | 22723.84 | 13-AUG-08:62 | 11606.45 | 26-AUG-06:02 | 6200.63 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.214254E+10 | 0.533609E+09 | 206.59 | 0.168124E+10 | 0.461305E+09 | 0.00 | 0.83 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 | 23654.95 | 14-SEP-06:02 | 14423.15 | 14-SEP-06:02 | 9231.80 | 14-SEP-06:02 | 5027.91 | 14-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 58288504.09 | 15485066.21 | 54.77 | 58218475.97 | 70028.11 | 0.00 | 0.36 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4002.76 | 04-OCT-15:00 | 4002.76 | 04-OCT-15:00 | 55.96 | 07-OCT-15:00 | 1040.99 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 21939383.74 | 5960761.41 | 5.72 | 15817190.97 | 6122192.77 | 0.00 | 0.20 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 | 2362.97 | 04-NOV-14:50 | 1736.61 | 04-NOV-15:00 | 627.47 | 04-NOV-14:40 | 636.39 | 04-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.198499E+11 | 0.495223E+10 | 1351.45 | 0.164910E+11 | 0.335883E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.758883E+10 | 0.187725E+10 | 326.35 | 0.619729E+10 | 0.139153E+10 | 0.00 | 1.00 | 0.00 | 29152.67 | 22723.84 | 11606.45 | 6200.63 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 7848983.87 | 2459551.09 | 2.67 | 7508264.20 | 340719.68 | 0.00 | 0.06 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 2730.75 | 27-FEB-15:10 | 2641.23 | 27-FEB-15:10 | 99.65 | 27-FEB-15:30 | 852.23 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 74793850.18 | 22819532.12 | 8.25 | 74789684.67 | 4165.51 | 0.00 | 0.19 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 9555.01 | 18-MAR-16:00 | 9555.01 | 18-MAR-16:00 | 0.87 | 10-MAR-13:20 | 2871.71 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.341707E+10 | 0.977274E+09 | 60.42 | 0.312200E+10 | 0.295073E+09 | 0.00 | 1.00 | 28-APR-06:03 | 0.00 | 01-APR-00:10 | 127835.14 | 30-APR-08:62 | 87125.81 | 28-APR-06:03 | 45606.05 | 30-APR-08:62 | 30365.61 | 30-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.891941E+10 | 0.248190E+10 | 170.22 | 0.764331E+10 | 0.127610E+10 | 0.00 | 1.00 | 05-MAY-06:02 | 0.00 | 01-MAY-00:10 | 133119.71 | 07-MAY-08:62 | 97365.92 | 05-MAY-06:02 | 38364.09 | 07-MAY-08:62 | 31669.02 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.185062E+11 | 0.513834E+10 | 271.63 | 0.165144E+11 | 0.199182E+10 | 0.00 | 1.00 | 03-JUN-06:03 | 0.00 | 01-JUN-00:10 | 130658.21 | 12-JUN-06:02 | 109538.88 | 25-JUN-08:62 | 43712.63 | 12-JUN-06:02 | 31091.47 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.365221E+11 | 0.985858E+10 | 335.03 | 0.302342E+11 | 0.628792E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 133553.25 | 31-JUL-06:02 | 109644.29 | 02-JUL-08:62 | 47525.60 | 16-JUL-08:62 | 31765.11 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.436380E+11 | 0.118107E+11 | 347.36 | 0.358302E+11 | 0.780785E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 134816.33 | 30-AUG-06:02 | 106402.96 | 13-AUG-08:62 | 50720.33 | 26-AUG-06:02 | 32035.09 | 30-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.154103E+11 | 0.419077E+10 | 221.48 | 0.120361E+11 | 0.337423E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 131322.02 | 24-SEP-08:62 | 100332.33 | 04-SEP-08:62 | 54480.16 | 24-SEP-08:62 | 31252.46 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.113606E+10 | 0.330749E+09 | 64.64 | 0.107439E+10 | 61673471.63 | 0.00 | 0.88 | 06-OCT-06:03 | 0.00 | 01-OCT-00:10 | 81261.32 | 05-OCT-06:02 | 71464.83 | 05-OCT-06:02 | 17846.93 | 06-OCT-06:03 | 19240.20 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.305828E+09 | 88951759.33 | 5.89 | 0.220206E+09 | 85621869.80 | 0.00 | 0.40 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 22506.00 | 04-NOV-14:30 | 16644.46 | 04-NOV-14:40 | 5889.93 | 04-NOV-14:00 | 6423.43 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.127938E+12 | 0.349026E+11 | 1487.59 | 0.106757E+12 | 0.211806E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.436380E+11 | 0.118107E+11 | 347.36 | 0.358302E+11 | 0.780785E+10 | 0.00 | 1.00 | 0.00 | 134816.33 | 109644.29 | 54480.16 | 32035.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 48063753.52 | 12357228.06 | 36.10 | 47069835.29 | 993918.23 | 0.00 | 0.50 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 4118.17 | 27-FEB-15:10 | 4118.17 | 27-FEB-15:10 | 107.11 | 27-FEB-16:00 | 1020.93 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 80267633.51 | 20470769.90 | 81.16 | 78687221.28 | 1580412.22 | 0.00 | 0.56 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 4735.73 | 18-MAR-14:00 | 4735.73 | 18-MAR-14:00 | 143.99 | 18-MAR-12:40 | 1150.49 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.928357E+09 | 0.227523E+09 | 151.74 | 0.869106E+09 | 59250845.44 | 0.00 | 1.00 | 27-APR-15:20 | 0.00 | 01-APR-00:10 | 13827.25 | 28-APR-06:03 | 10178.46 | 27-APR-13:30 | 4092.39 | 28-APR-06:03 | 2928.99 | 28-APR-06:03 | 0.00 | 01-APR-00:10 |
May | 0.166908E+10 | 0.407801E+09 | 218.37 | 0.146769E+10 | 0.201388E+09 | 0.00 | 1.00 | 05-MAY-06:02 | 0.00 | 01-MAY-00:10 | 20492.99 | 07-MAY-08:62 | 15273.66 | 05-MAY-06:02 | 5723.68 | 07-MAY-08:62 | 4363.56 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.293957E+10 | 0.726473E+09 | 285.90 | 0.270488E+10 | 0.234682E+09 | 0.00 | 1.00 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 | 20189.88 | 12-JUN-06:02 | 15541.58 | 28-JUN-06:02 | 6995.18 | 12-JUN-06:02 | 4298.88 | 12-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.590390E+10 | 0.141745E+10 | 340.25 | 0.503205E+10 | 0.871854E+09 | 0.00 | 1.00 | 08-JUL-06:02 | 0.00 | 01-JUL-00:10 | 20628.20 | 31-JUL-06:02 | 16496.01 | 23-JUL-08:62 | 7351.29 | 25-JUL-06:02 | 4390.89 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.781566E+10 | 0.186041E+10 | 354.45 | 0.664369E+10 | 0.117197E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 20821.66 | 25-AUG-06:02 | 16598.52 | 13-AUG-08:62 | 8005.95 | 26-AUG-06:02 | 4428.31 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.406874E+10 | 0.937190E+09 | 273.09 | 0.329568E+10 | 0.773057E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 20250.81 | 01-SEP-06:02 | 14204.63 | 10-SEP-08:62 | 8352.64 | 24-SEP-08:62 | 4312.25 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 |
October | 0.842300E+09 | 0.204875E+09 | 163.21 | 0.778988E+09 | 63311836.05 | 0.00 | 1.00 | 04-OCT-14:20 | 0.00 | 01-OCT-00:10 | 15528.70 | 05-OCT-06:02 | 14060.34 | 05-OCT-06:02 | 1874.55 | 04-OCT-06:03 | 3288.73 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.174170E+09 | 39952496.80 | 31.82 | 0.129624E+09 | 44546240.24 | 0.00 | 0.93 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 9369.93 | 04-NOV-14:00 | 7273.55 | 04-NOV-14:00 | 2265.42 | 04-NOV-13:00 | 2044.61 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 5994.90 | 1694.55 | 9.14 | 5981.31 | 13.59 | 0.00 | 0.00 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 | 0.43 | 02-DEC-13:00 | 0.43 | 02-DEC-13:00 | 0.01 | 12-DEC-14:20 | 0.12 | 02-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.244701E+11 | 0.585451E+10 | 1945.23 | 0.210475E+11 | 0.342263E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.781566E+10 | 0.186041E+10 | 354.45 | 0.664369E+10 | 0.117197E+10 | 0.00 | 1.00 | 0.00 | 20821.66 | 16598.52 | 8352.64 | 4428.31 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 8103081.60 | 1909504.66 | 10.44 | 8102562.43 | 519.17 | 0.00 | 0.24 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 1673.08 | 27-FEB-15:10 | 1673.08 | 27-FEB-15:10 | 0.27 | 27-FEB-16:10 | 388.59 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 19772216.52 | 4569724.98 | 32.89 | 19771707.10 | 509.42 | 0.00 | 0.31 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 2207.09 | 18-MAR-14:00 | 2207.09 | 18-MAR-14:00 | 0.10 | 10-MAR-13:00 | 501.89 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.526731E+09 | 0.114820E+09 | 96.87 | 0.505011E+09 | 21719751.32 | 0.00 | 0.96 | 27-APR-14:10 | 0.00 | 01-APR-00:10 | 8855.42 | 27-APR-14:10 | 8419.50 | 27-APR-14:10 | 1661.18 | 28-APR-06:03 | 1804.77 | 27-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 0.861968E+09 | 0.187868E+09 | 162.55 | 0.781940E+09 | 80027672.18 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 17036.39 | 07-MAY-08:62 | 12148.80 | 07-MAY-08:62 | 4887.59 | 07-MAY-08:62 | 3347.12 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.148151E+10 | 0.326663E+09 | 235.83 | 0.141693E+10 | 64578569.59 | 0.00 | 1.00 | 21-JUN-06:02 | 0.00 | 01-JUN-00:10 | 16406.10 | 21-JUN-06:02 | 11550.44 | 23-JUN-06:02 | 5648.76 | 12-JUN-06:02 | 3216.46 | 21-JUN-06:02 | 0.00 | 01-JUN-00:10 |
July | 0.360746E+10 | 0.775489E+09 | 297.42 | 0.317667E+10 | 0.430797E+09 | 0.00 | 1.00 | 08-JUL-06:02 | 0.00 | 01-JUL-00:10 | 17156.93 | 31-JUL-06:02 | 13591.50 | 23-JUL-08:62 | 6233.91 | 15-JUL-06:02 | 3369.60 | 31-JUL-06:02 | 0.00 | 01-JUL-00:10 |
August | 0.529677E+10 | 0.111883E+10 | 316.44 | 0.465394E+10 | 0.642823E+09 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 17325.72 | 25-AUG-06:02 | 13693.85 | 13-AUG-08:62 | 6767.82 | 26-AUG-06:02 | 3399.64 | 25-AUG-06:02 | 0.00 | 01-AUG-00:10 |
September | 0.236776E+10 | 0.481711E+09 | 221.22 | 0.198101E+10 | 0.386744E+09 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 16831.43 | 24-SEP-08:62 | 11725.15 | 10-SEP-08:62 | 7059.51 | 24-SEP-08:62 | 3306.99 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.294801E+09 | 62772948.65 | 104.93 | 0.286340E+09 | 8461773.62 | 0.00 | 0.89 | 04-OCT-14:30 | 0.00 | 01-OCT-00:10 | 8920.97 | 05-OCT-06:02 | 8183.45 | 05-OCT-06:02 | 737.53 | 05-OCT-06:02 | 1652.37 | 05-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 84518360.34 | 17851006.26 | 11.69 | 65046380.90 | 19471979.44 | 0.00 | 0.71 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 6106.71 | 04-NOV-14:00 | 4843.43 | 04-NOV-14:20 | 1317.80 | 04-NOV-13:30 | 1243.92 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 1619.34 | 399.10 | 3.60 | 1619.34 | 0.00 | 0.00 | 0.00 | 05-DEC-11:53 | 0.00 | 01-DEC-00:10 | 0.53 | 05-DEC-11:53 | 0.53 | 05-DEC-11:53 | 0.00 | 01-DEC-00:10 | 0.13 | 05-DEC-11:53 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.145494E+11 | 0.309248E+10 | 1493.88 | 0.128948E+11 | 0.165463E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.529677E+10 | 0.111883E+10 | 316.44 | 0.465394E+10 | 0.642823E+09 | 0.00 | 1.00 | 0.00 | 17325.72 | 13693.85 | 7059.51 | 3399.64 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 5.40 | 17.93 | 8.91 | 69.20 | 0.00 | 0.00 | 744.00 |
February | 42.85 | 16.23 | 26.62 | 31.19 | 61.80 | 0.00 | 0.00 | 672.00 |
March | 69.26 | 29.42 | 39.84 | 63.46 | 51.91 | 0.00 | 0.00 | 744.00 |
April | 111.06 | 56.51 | 54.55 | 118.08 | 42.87 | 0.00 | 0.00 | 720.00 |
May | 143.48 | 73.57 | 69.90 | 161.06 | 37.76 | 0.00 | 0.00 | 744.00 |
June | 156.27 | 90.90 | 65.37 | 179.13 | 31.29 | 0.00 | 0.00 | 720.00 |
July | 163.31 | 107.23 | 56.08 | 194.75 | 29.53 | 0.00 | 0.00 | 744.00 |
August | 130.74 | 82.60 | 48.14 | 155.51 | 30.30 | 0.00 | 0.00 | 744.00 |
September | 92.87 | 51.50 | 41.37 | 101.82 | 40.33 | 0.00 | 0.00 | 720.00 |
October | 54.13 | 24.84 | 29.28 | 49.44 | 50.93 | 0.00 | 0.00 | 744.00 |
November | 27.38 | 7.16 | 20.22 | 15.86 | 57.14 | 0.00 | 0.00 | 720.00 |
December | 19.70 | 5.09 | 14.61 | 7.18 | 71.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 86.44 | 46.05 | 40.38 | 90.88 | 47.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.70 | 5.09 | 14.61 | 7.18 | 29.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 163.31 | 107.23 | 69.90 | 194.75 | 71.83 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 598.70 | 809.25 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 1016.37 | 740.61 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1076.30 | 660.22 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1076.11 | 550.99 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 890.49 | 471.56 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 778.66 | 378.06 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 940.21 | 347.12 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1161.32 | 344.22 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1335.73 | 474.82 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1217.54 | 615.22 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 636.60 | 699.23 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 703.86 | 834.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 952.09 | 576.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 598.70 | 344.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1335.73 | 834.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 710.63 | 421.88 | 288.74 | 601.07 | 789.02 | 0.00 | 0.00 | 744.00 |
February | 1093.22 | 676.73 | 416.49 | 1021.85 | 713.19 | 0.00 | 0.00 | 672.00 |
March | 1176.41 | 627.59 | 548.83 | 1083.14 | 628.73 | 0.00 | 0.00 | 744.00 |
April | 1241.68 | 539.19 | 702.49 | 1081.76 | 525.93 | 0.00 | 0.00 | 720.00 |
May | 1135.10 | 338.05 | 797.06 | 893.32 | 452.66 | 0.00 | 0.00 | 744.00 |
June | 1038.50 | 278.71 | 759.79 | 777.57 | 363.42 | 0.00 | 0.00 | 720.00 |
July | 1132.50 | 414.66 | 717.84 | 937.59 | 332.93 | 0.00 | 0.00 | 744.00 |
August | 1216.85 | 567.39 | 649.46 | 1157.53 | 331.13 | 0.00 | 0.00 | 744.00 |
September | 1348.75 | 745.01 | 603.73 | 1333.93 | 459.47 | 0.00 | 0.00 | 720.00 |
October | 1221.68 | 754.42 | 467.26 | 1221.01 | 589.78 | 0.00 | 0.00 | 744.00 |
November | 721.96 | 413.68 | 308.28 | 642.88 | 666.92 | 0.00 | 0.00 | 720.00 |
December | 755.27 | 488.68 | 266.60 | 707.04 | 810.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1065.58 | 521.20 | 544.38 | 954.29 | 554.56 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 710.63 | 278.71 | 266.60 | 601.07 | 331.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1348.75 | 754.42 | 797.06 | 1333.93 | 810.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.22 | 86.81 | 59.41 | 120.60 | 162.51 | 0.00 | 0.00 | 744.00 |
February | 224.95 | 139.25 | 85.70 | 206.65 | 145.12 | 0.00 | 0.00 | 672.00 |
March | 242.06 | 129.14 | 112.93 | 221.07 | 126.10 | 0.00 | 0.00 | 744.00 |
April | 255.49 | 110.95 | 144.55 | 222.06 | 104.53 | 0.00 | 0.00 | 720.00 |
May | 233.56 | 69.56 | 164.01 | 185.69 | 88.27 | 0.00 | 0.00 | 744.00 |
June | 213.69 | 57.35 | 156.34 | 163.37 | 70.37 | 0.00 | 0.00 | 720.00 |
July | 233.03 | 85.32 | 147.71 | 194.04 | 65.63 | 0.00 | 0.00 | 744.00 |
August | 250.38 | 116.75 | 133.64 | 234.89 | 67.28 | 0.00 | 0.00 | 744.00 |
September | 277.52 | 153.30 | 124.23 | 275.51 | 89.81 | 0.00 | 0.00 | 720.00 |
October | 251.38 | 155.23 | 96.14 | 250.93 | 115.41 | 0.00 | 0.00 | 744.00 |
November | 148.55 | 85.12 | 63.43 | 130.07 | 135.23 | 0.00 | 0.00 | 720.00 |
December | 155.41 | 100.55 | 54.86 | 143.00 | 166.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 219.26 | 107.24 | 112.01 | 195.54 | 111.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 146.22 | 57.35 | 54.86 | 120.60 | 65.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 277.52 | 155.23 | 164.01 | 275.51 | 166.20 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62484716.65 | 14454928.95 | 48029787.70 | 23872623.19 | 0.185357E+09 |
February | 0.103674E+09 | 39270200.80 | 64404057.82 | 75456076.04 | 0.149497E+09 |
March | 0.185505E+09 | 78794595.25 | 0.106711E+09 | 0.169978E+09 | 0.139039E+09 |
April | 0.287873E+09 | 0.146485E+09 | 0.141388E+09 | 0.306060E+09 | 0.111126E+09 |
May | 0.384285E+09 | 0.197056E+09 | 0.187230E+09 | 0.431390E+09 | 0.101124E+09 |
June | 0.405052E+09 | 0.235612E+09 | 0.169440E+09 | 0.464310E+09 | 81110408.80 |
July | 0.437401E+09 | 0.287200E+09 | 0.150200E+09 | 0.521628E+09 | 79093520.48 |
August | 0.350183E+09 | 0.221236E+09 | 0.128947E+09 | 0.416524E+09 | 81164773.80 |
September | 0.240718E+09 | 0.133478E+09 | 0.107240E+09 | 0.263909E+09 | 0.104534E+09 |
October | 0.144979E+09 | 66544707.34 | 78433807.62 | 0.132425E+09 | 0.136401E+09 |
November | 70957682.91 | 18556211.43 | 52401471.49 | 41115403.14 | 0.148103E+09 |
December | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 0.192384E+09 |
Annual Sum or Average | 0.272587E+10 | 0.145232E+10 | 0.127356E+10 | 0.286591E+10 | 0.150893E+10 |
Minimum of Months | 52760926.74 | 13629041.93 | 39131884.81 | 19236312.73 | 79093520.48 |
Maximum of Months | 0.437401E+09 | 0.287200E+09 | 0.187230E+09 | 0.521628E+09 | 0.192384E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.160356E+10 | 0.216750E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.245881E+10 | 0.179168E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.288276E+10 | 0.176834E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.278928E+10 | 0.142817E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.238510E+10 | 0.126304E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.201829E+10 | 0.979930E+09 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.251826E+10 | 0.929714E+09 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.311048E+10 | 0.921968E+09 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.346221E+10 | 0.123073E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.326107E+10 | 0.164779E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.165007E+10 | 0.181242E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.188521E+10 | 0.223527E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.300251E+11 | 0.181765E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.160356E+10 | 0.921968E+09 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.346221E+10 | 0.223527E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.160990E+10 | 0.211331E+10 |
February | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.247206E+10 | 0.172535E+10 |
March | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.290109E+10 | 0.168398E+10 |
April | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.280392E+10 | 0.136321E+10 |
May | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.239267E+10 | 0.121240E+10 |
June | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.201547E+10 | 0.941991E+09 |
July | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.251123E+10 | 0.891712E+09 |
August | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.310032E+10 | 0.886909E+09 |
September | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.345754E+10 | 0.119095E+10 |
October | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.327035E+10 | 0.157967E+10 |
November | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.166634E+10 | 0.172865E+10 |
December | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.189374E+10 | 0.217040E+10 |
Annual Sum or Average | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.300946E+11 | 0.174885E+11 |
Minimum of Months | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.160990E+10 | 0.886909E+09 |
Maximum of Months | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.345754E+10 | 0.217040E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.323006E+09 | 0.435262E+09 |
February | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.499940E+09 | 0.351085E+09 |
March | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.592120E+09 | 0.337751E+09 |
April | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.575572E+09 | 0.270948E+09 |
May | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.497340E+09 | 0.236432E+09 |
June | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.423446E+09 | 0.182409E+09 |
July | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.519705E+09 | 0.175796E+09 |
August | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.629133E+09 | 0.180206E+09 |
September | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.714130E+09 | 0.232782E+09 |
October | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.672088E+09 | 0.309118E+09 |
November | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.337129E+09 | 0.350516E+09 |
December | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.383021E+09 | 0.445152E+09 |
Annual Sum or Average | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.616663E+10 | 0.350746E+10 |
Minimum of Months | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.323006E+09 | 0.175796E+09 |
Maximum of Months | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.714130E+09 | 0.445152E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 142.61 | 1107.27 | 373.27 | 86.35 | 286.92 | 0.00 | 0.00 |
February | 499.05 | 988.73 | 685.68 | 259.72 | 425.95 | 0.00 | 0.00 |
March | 1015.40 | 830.58 | 1108.16 | 470.70 | 637.46 | 0.00 | 0.00 |
April | 1889.26 | 685.97 | 1776.99 | 904.23 | 872.76 | 0.00 | 0.00 |
May | 2577.00 | 604.08 | 2295.61 | 1177.15 | 1118.46 | 0.00 | 0.00 |
June | 2866.11 | 500.68 | 2500.32 | 1454.40 | 1045.92 | 0.00 | 0.00 |
July | 3116.06 | 472.48 | 2612.91 | 1715.65 | 897.26 | 0.00 | 0.00 |
August | 2488.19 | 484.86 | 2091.89 | 1321.60 | 770.29 | 0.00 | 0.00 |
September | 1629.07 | 645.27 | 1485.92 | 823.94 | 661.98 | 0.00 | 0.00 |
October | 791.07 | 814.82 | 866.06 | 397.52 | 468.54 | 0.00 | 0.00 |
November | 253.80 | 914.21 | 438.01 | 114.54 | 323.47 | 0.00 | 0.00 |
December | 114.91 | 1149.25 | 315.18 | 81.42 | 233.76 | 0.00 | 0.00 |
Annual Sum or Average | 1454.04 | 765.57 | 1382.99 | 736.84 | 646.15 | 0.00 | 0.00 |
Minimum of Months | 114.91 | 472.48 | 315.18 | 81.42 | 233.76 | 0.00 | 0.00 |
Maximum of Months | 3116.06 | 1149.25 | 2612.91 | 1715.65 | 1118.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 598.70 | 809.25 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 1016.37 | 740.61 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1076.30 | 660.22 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1076.11 | 550.99 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 890.49 | 471.56 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 778.66 | 378.06 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 940.21 | 347.12 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1161.32 | 344.22 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1335.73 | 474.82 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1217.54 | 615.22 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 636.60 | 699.23 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 703.86 | 834.55 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 952.09 | 576.37 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 598.70 | 344.22 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1335.73 | 834.55 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 601.07 | 789.02 | 710.63 | 421.88 | 288.74 | 0.00 | 0.00 |
February | 1021.85 | 713.19 | 1093.22 | 676.73 | 416.49 | 0.00 | 0.00 |
March | 1083.14 | 628.73 | 1176.41 | 627.59 | 548.83 | 0.00 | 0.00 |
April | 1081.76 | 525.93 | 1241.68 | 539.19 | 702.49 | 0.00 | 0.00 |
May | 893.32 | 452.66 | 1135.10 | 338.05 | 797.06 | 0.00 | 0.00 |
June | 777.57 | 363.42 | 1038.50 | 278.71 | 759.79 | 0.00 | 0.00 |
July | 937.59 | 332.93 | 1132.50 | 414.66 | 717.84 | 0.00 | 0.00 |
August | 1157.53 | 331.13 | 1216.85 | 567.39 | 649.46 | 0.00 | 0.00 |
September | 1333.93 | 459.47 | 1348.75 | 745.01 | 603.73 | 0.00 | 0.00 |
October | 1221.01 | 589.78 | 1221.68 | 754.42 | 467.26 | 0.00 | 0.00 |
November | 642.88 | 666.92 | 721.96 | 413.68 | 308.28 | 0.00 | 0.00 |
December | 707.04 | 810.34 | 755.27 | 488.68 | 266.60 | 0.00 | 0.00 |
Annual Sum or Average | 954.29 | 554.56 | 1065.58 | 521.20 | 544.38 | 0.00 | 0.00 |
Minimum of Months | 601.07 | 331.13 | 710.63 | 278.71 | 266.60 | 0.00 | 0.00 |
Maximum of Months | 1333.93 | 810.34 | 1348.75 | 754.42 | 797.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 120.60 | 162.51 | 146.22 | 86.81 | 59.41 | 0.00 | 0.00 |
February | 206.65 | 145.12 | 224.95 | 139.25 | 85.70 | 0.00 | 0.00 |
March | 221.07 | 126.10 | 242.06 | 129.14 | 112.93 | 0.00 | 0.00 |
April | 222.06 | 104.53 | 255.49 | 110.95 | 144.55 | 0.00 | 0.00 |
May | 185.69 | 88.27 | 233.56 | 69.56 | 164.01 | 0.00 | 0.00 |
June | 163.37 | 70.37 | 213.69 | 57.35 | 156.34 | 0.00 | 0.00 |
July | 194.04 | 65.63 | 233.03 | 85.32 | 147.71 | 0.00 | 0.00 |
August | 234.89 | 67.28 | 250.38 | 116.75 | 133.64 | 0.00 | 0.00 |
September | 275.51 | 89.81 | 277.52 | 153.30 | 124.23 | 0.00 | 0.00 |
October | 250.93 | 115.41 | 251.38 | 155.23 | 96.14 | 0.00 | 0.00 |
November | 130.07 | 135.23 | 148.55 | 85.12 | 63.43 | 0.00 | 0.00 |
December | 143.00 | 166.20 | 155.41 | 100.55 | 54.86 | 0.00 | 0.00 |
Annual Sum or Average | 195.54 | 111.22 | 219.26 | 107.24 | 112.01 | 0.00 | 0.00 |
Minimum of Months | 120.60 | 65.63 | 146.22 | 57.35 | 54.86 | 0.00 | 0.00 |
Maximum of Months | 275.51 | 166.20 | 277.52 | 155.23 | 164.01 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.381962E+09 | 0.296571E+10 | 0.999755E+09 | 0.231279E+09 | 0.768477E+09 | 0.00 | 0.00 |
February | 0.120730E+10 | 0.239195E+10 | 0.165879E+10 | 0.628323E+09 | 0.103046E+10 | 0.00 | 0.00 |
March | 0.271965E+10 | 0.222462E+10 | 0.296808E+10 | 0.126071E+10 | 0.170737E+10 | 0.00 | 0.00 |
April | 0.489697E+10 | 0.177802E+10 | 0.460597E+10 | 0.234377E+10 | 0.226220E+10 | 0.00 | 0.00 |
May | 0.690224E+10 | 0.161798E+10 | 0.614856E+10 | 0.315289E+10 | 0.299567E+10 | 0.00 | 0.00 |
June | 0.742896E+10 | 0.129777E+10 | 0.648083E+10 | 0.376980E+10 | 0.271104E+10 | 0.00 | 0.00 |
July | 0.834605E+10 | 0.126550E+10 | 0.699841E+10 | 0.459520E+10 | 0.240321E+10 | 0.00 | 0.00 |
August | 0.666438E+10 | 0.129864E+10 | 0.560292E+10 | 0.353978E+10 | 0.206315E+10 | 0.00 | 0.00 |
September | 0.422254E+10 | 0.167255E+10 | 0.385150E+10 | 0.213565E+10 | 0.171585E+10 | 0.00 | 0.00 |
October | 0.211881E+10 | 0.218241E+10 | 0.231966E+10 | 0.106472E+10 | 0.125494E+10 | 0.00 | 0.00 |
November | 0.657846E+09 | 0.236964E+10 | 0.113532E+10 | 0.296899E+09 | 0.838424E+09 | 0.00 | 0.00 |
December | 0.307781E+09 | 0.307814E+10 | 0.844175E+09 | 0.218065E+09 | 0.626110E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.458545E+11 | 0.241429E+11 | 0.436140E+11 | 0.232371E+11 | 0.203769E+11 | 0.00 | 0.00 |
Minimum of Months | 0.307781E+09 | 0.126550E+10 | 0.844175E+09 | 0.218065E+09 | 0.626110E+09 | 0.00 | 0.00 |
Maximum of Months | 0.834605E+10 | 0.307814E+10 | 0.699841E+10 | 0.459520E+10 | 0.299567E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160356E+10 | 0.216750E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.245881E+10 | 0.179168E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.288276E+10 | 0.176834E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.278928E+10 | 0.142817E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.238510E+10 | 0.126304E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.201829E+10 | 0.979930E+09 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.251826E+10 | 0.929714E+09 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.311048E+10 | 0.921968E+09 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.346221E+10 | 0.123073E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.326107E+10 | 0.164779E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.165007E+10 | 0.181242E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.188521E+10 | 0.223527E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.300251E+11 | 0.181765E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160356E+10 | 0.921968E+09 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.346221E+10 | 0.223527E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160990E+10 | 0.211331E+10 | 0.190334E+10 | 0.112997E+10 | 0.773374E+09 | 0.00 | 0.00 |
February | 0.247206E+10 | 0.172535E+10 | 0.264471E+10 | 0.163715E+10 | 0.100757E+10 | 0.00 | 0.00 |
March | 0.290109E+10 | 0.168398E+10 | 0.315091E+10 | 0.168093E+10 | 0.146998E+10 | 0.00 | 0.00 |
April | 0.280392E+10 | 0.136321E+10 | 0.321843E+10 | 0.139757E+10 | 0.182086E+10 | 0.00 | 0.00 |
May | 0.239267E+10 | 0.121240E+10 | 0.304026E+10 | 0.905428E+09 | 0.213483E+10 | 0.00 | 0.00 |
June | 0.201547E+10 | 0.941991E+09 | 0.269180E+10 | 0.722426E+09 | 0.196937E+10 | 0.00 | 0.00 |
July | 0.251123E+10 | 0.891712E+09 | 0.303329E+10 | 0.111062E+10 | 0.192267E+10 | 0.00 | 0.00 |
August | 0.310032E+10 | 0.886909E+09 | 0.325920E+10 | 0.151969E+10 | 0.173952E+10 | 0.00 | 0.00 |
September | 0.345754E+10 | 0.119095E+10 | 0.349596E+10 | 0.193108E+10 | 0.156488E+10 | 0.00 | 0.00 |
October | 0.327035E+10 | 0.157967E+10 | 0.327213E+10 | 0.202063E+10 | 0.125150E+10 | 0.00 | 0.00 |
November | 0.166634E+10 | 0.172865E+10 | 0.187131E+10 | 0.107226E+10 | 0.799054E+09 | 0.00 | 0.00 |
December | 0.189374E+10 | 0.217040E+10 | 0.202293E+10 | 0.130888E+10 | 0.714049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.300946E+11 | 0.174885E+11 | 0.336043E+11 | 0.164366E+11 | 0.171676E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160990E+10 | 0.886909E+09 | 0.187131E+10 | 0.722426E+09 | 0.714049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.345754E+10 | 0.217040E+10 | 0.349596E+10 | 0.202063E+10 | 0.213483E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323006E+09 | 0.435262E+09 | 0.391640E+09 | 0.232507E+09 | 0.159133E+09 | 0.00 | 0.00 |
February | 0.499940E+09 | 0.351085E+09 | 0.544188E+09 | 0.336867E+09 | 0.207321E+09 | 0.00 | 0.00 |
March | 0.592120E+09 | 0.337751E+09 | 0.648345E+09 | 0.345876E+09 | 0.302469E+09 | 0.00 | 0.00 |
April | 0.575572E+09 | 0.270948E+09 | 0.662239E+09 | 0.287571E+09 | 0.374668E+09 | 0.00 | 0.00 |
May | 0.497340E+09 | 0.236432E+09 | 0.625578E+09 | 0.186305E+09 | 0.439273E+09 | 0.00 | 0.00 |
June | 0.423446E+09 | 0.182409E+09 | 0.553877E+09 | 0.148650E+09 | 0.405227E+09 | 0.00 | 0.00 |
July | 0.519705E+09 | 0.175796E+09 | 0.624144E+09 | 0.228526E+09 | 0.395618E+09 | 0.00 | 0.00 |
August | 0.629133E+09 | 0.180206E+09 | 0.670629E+09 | 0.312698E+09 | 0.357931E+09 | 0.00 | 0.00 |
September | 0.714130E+09 | 0.232782E+09 | 0.719344E+09 | 0.397348E+09 | 0.321996E+09 | 0.00 | 0.00 |
October | 0.672088E+09 | 0.309118E+09 | 0.673289E+09 | 0.415775E+09 | 0.257514E+09 | 0.00 | 0.00 |
November | 0.337129E+09 | 0.350516E+09 | 0.385050E+09 | 0.220633E+09 | 0.164417E+09 | 0.00 | 0.00 |
December | 0.383021E+09 | 0.445152E+09 | 0.416246E+09 | 0.269321E+09 | 0.146926E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.616663E+10 | 0.350746E+10 | 0.691457E+10 | 0.338208E+10 | 0.353249E+10 | 0.00 | 0.00 |
Minimum of Months | 0.323006E+09 | 0.175796E+09 | 0.385050E+09 | 0.148650E+09 | 0.146926E+09 | 0.00 | 0.00 |
Maximum of Months | 0.714130E+09 | 0.445152E+09 | 0.719344E+09 | 0.415775E+09 | 0.439273E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.267943E+10 | -.225146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -427972890.6 | 58.99 | 0.00 | 0.00 |
February | 0.244827E+10 | -.206449E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -383782125.7 | 58.99 | 0.00 | 0.00 |
March | 0.273455E+10 | -.231592E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -418632766.5 | 59.00 | 0.00 | 0.00 |
April | 0.253633E+10 | -.214134E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -394983439.1 | 59.00 | 0.00 | 0.00 |
May | 0.252857E+10 | -.213334E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -395234043.3 | 59.00 | 0.00 | 0.00 |
June | 0.238962E+10 | -.201360E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -376022043.3 | 58.99 | 0.00 | 0.00 |
July | 0.234912E+10 | -.196381E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385313458.0 | 58.99 | 0.00 | 0.00 |
August | 0.239403E+10 | -.200938E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -384651275.3 | 58.99 | 0.00 | 0.00 |
September | 0.231330E+10 | -.193719E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -376102730.1 | 58.99 | 0.00 | 0.00 |
October | 0.243811E+10 | -.203476E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -403342733.6 | 58.99 | 0.00 | 0.00 |
November | 0.244391E+10 | -.203903E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -404876654.0 | 58.99 | 0.00 | 0.00 |
December | 0.262371E+10 | -.219755E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -426158381.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298789E+11 | -.251019E+11 | 8760.00 | -.477707E+10 | 58.99 | |||||
Minimum of Months | 0.231330E+10 | -.231592E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -427972890.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.273455E+10 | -.193719E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376022043.3 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.93 | 0.75 | 17-JAN-12:30 | 171.70 | 5.76 | 0.00 | 0.00 | 139.87 | 4.38 | 0.00 | 0.00 |
February | 259.50 | 0.89 | 0.67 | 15-FEB-11:20 | 224.47 | 6.82 | 0.00 | 0.00 | 182.93 | 5.38 | 0.00 | 0.00 |
March | 247.00 | 0.81 | 0.50 | 06-MAR-11:39 | 317.60 | 8.26 | 0.00 | 32.33 | 258.90 | 6.72 | 0.00 | 10.17 |
April | 379.50 | 0.75 | 0.50 | 01-APR-11:30 | 839.74 | 9.46 | 0.00 | 147.17 | 310.50 | 7.87 | 0.00 | 58.50 |
May | 427.83 | 0.73 | 0.50 | 01-MAY-09:50 | 1676.03 | 10.72 | 0.00 | 176.00 | 1864.34 | 8.99 | 0.00 | 111.33 |
June | 375.17 | 0.75 | 0.50 | 01-JUN-10:30 | 445.47 | 10.42 | 0.00 | 135.83 | 2457.64 | 8.75 | 0.00 | 88.33 |
July | 471.00 | 0.78 | 0.50 | 01-JUL-11:20 | 2254.77 | 8.81 | 0.00 | 142.83 | 2281.88 | 7.12 | 0.00 | 101.17 |
August | 366.67 | 0.78 | 0.50 | 01-AUG-08:09 | 1953.89 | 8.38 | 0.00 | 104.50 | 1375.72 | 6.74 | 0.00 | 80.33 |
September | 301.17 | 0.80 | 0.50 | 01-SEP-12:09 | 334.90 | 8.70 | 0.00 | 35.67 | 266.89 | 7.06 | 0.00 | 10.00 |
October | 245.33 | 0.87 | 0.50 | 02-OCT-09:30 | 245.31 | 6.82 | 0.00 | 5.17 | 198.74 | 5.34 | 0.00 | 0.83 |
November | 242.67 | 0.92 | 0.75 | 01-NOV-12:20 | 187.78 | 6.26 | 0.00 | 0.00 | 153.04 | 4.83 | 0.00 | 0.00 |
December | 160.33 | 0.95 | 0.75 | 10-DEC-12:20 | 150.94 | 4.82 | 0.00 | 0.00 | 122.53 | 3.55 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.81 | 912.66 | 8.37 | 0.00 | 779.50 | 1008.96 | 6.79 | 0.00 | 460.67 | ||
Minimum of Months | 160.33 | 0.73 | 0.50 | 150.94 | 4.82 | 0.00 | 0.00 | 122.53 | 3.55 | 0.00 | 0.00 | |
Maximum of Months | 471.00 | 0.95 | 0.75 | 2254.77 | 10.72 | 0.00 | 176.00 | 2457.64 | 8.99 | 0.00 | 111.33 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.719808E+10 | 43950.57 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498610E+10 | 43950.57 | 05-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197036E+10 | 43950.57 | 05-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.610787E+09 | 43670.26 | 19-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5275834.00 | 1605.19 | 29-MAY-08:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226559E+09 | 26276.02 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250488E+10 | 43950.57 | 11-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.555860E+10 | 43950.57 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230607E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.719808E+10 | 43950.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.296545E+11 | 220954.39 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191562E+11 | 220954.39 | 20-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.716657E+10 | 62578.99 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210329E+10 | 48047.16 | 12-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11725136.41 | 6729.39 | 18-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.838962E+09 | 29022.20 | 16-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119713E+11 | 125803.65 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236510E+11 | 220954.39 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.945536E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.296545E+11 | 220954.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213865E+10 | 33352.61 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113974E+10 | 33352.61 | 16-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388189E+09 | 22266.70 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129473E+09 | 10837.89 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2738790.82 | 997.88 | 18-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26369656.25 | 2140.36 | 16-OCT-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.581090E+09 | 23711.36 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160487E+10 | 33352.61 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.601113E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213865E+10 | 33352.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.371403E+10 | 28143.94 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204181E+10 | 28143.94 | 12-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.844752E+09 | 28143.94 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322964E+09 | 17554.00 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19794204.46 | 2953.61 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60652.99 | 101.09 | 28-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110514E+09 | 3063.85 | 16-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133264E+10 | 28143.94 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294557E+10 | 28143.94 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113321E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.371403E+10 | 28143.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114151E+11 | 23932.60 | 07-JAN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.840914E+10 | 24362.48 | 18-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.653191E+10 | 17197.49 | 05-MAR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397400E+10 | 14393.78 | 18-APR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254024E+10 | 12714.84 | 23-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.978048E+09 | 9177.55 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.244285E+09 | 5769.99 | 09-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123059E+09 | 6198.88 | 01-AUG-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139561E+10 | 8773.90 | 26-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384858E+10 | 11672.63 | 31-OCT-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.806285E+10 | 19687.78 | 12-NOV-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104974E+11 | 23897.08 | 26-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580202E+11 | |||||||
Minimum of Months | 0.123059E+09 | 5769.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114151E+11 | 24362.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1703.83 | 1701.07 | 0.81 | 18-MAR-15:20 | 0.81 | 0.00 |
April | 0.00 | 0.00 | 0.386232E+09 | 0.347391E+09 | 8689.45 | 27-APR-15:00 | 7556.77 | 0.00 |
May | 0.00 | 0.00 | 0.110540E+10 | 0.946337E+09 | 9942.64 | 06-MAY-13:50 | 7844.63 | 0.00 |
June | 0.00 | 0.00 | 0.253211E+10 | 0.228465E+10 | 27259.27 | 29-JUN-06:02 | 18791.38 | 0.00 |
July | 0.00 | 0.00 | 0.601453E+10 | 0.496010E+10 | 28853.21 | 31-JUL-06:02 | 20288.12 | 0.00 |
August | 0.00 | 0.00 | 0.758883E+10 | 0.619729E+10 | 29152.67 | 25-AUG-06:02 | 19749.33 | 0.00 |
September | 0.00 | 0.00 | 0.214254E+10 | 0.168124E+10 | 23654.95 | 14-SEP-06:02 | 14423.15 | 0.00 |
October | 0.00 | 0.00 | 58288504.09 | 58218475.97 | 4002.76 | 04-OCT-15:00 | 4002.76 | 0.00 |
November | 0.00 | 0.00 | 21939383.74 | 15817190.97 | 2362.97 | 04-NOV-14:50 | 1735.57 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.198499E+11 | 0.164910E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.758883E+10 | 0.619729E+10 | 29152.67 | 20288.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7848983.87 | 7508264.20 | 2730.75 | 27-FEB-15:10 | 2641.23 | 0.00 |
March | 0.00 | 0.00 | 74793850.18 | 74789684.67 | 9555.01 | 18-MAR-16:00 | 9555.01 | 0.00 |
April | 0.00 | 0.00 | 0.341707E+10 | 0.312200E+10 | 127835.14 | 30-APR-08:62 | 82229.09 | 0.00 |
May | 0.00 | 0.00 | 0.891941E+10 | 0.764331E+10 | 133119.71 | 07-MAY-08:62 | 94755.62 | 0.00 |
June | 0.00 | 0.00 | 0.185062E+11 | 0.165144E+11 | 130658.21 | 12-JUN-06:02 | 86945.57 | 0.00 |
July | 0.00 | 0.00 | 0.365221E+11 | 0.302342E+11 | 133553.25 | 31-JUL-06:02 | 96523.99 | 0.00 |
August | 0.00 | 0.00 | 0.436380E+11 | 0.358302E+11 | 134816.33 | 30-AUG-06:02 | 86850.75 | 0.00 |
September | 0.00 | 0.00 | 0.154103E+11 | 0.120361E+11 | 131322.02 | 24-SEP-08:62 | 76841.86 | 0.00 |
October | 0.00 | 0.00 | 0.113606E+10 | 0.107439E+10 | 81261.32 | 05-OCT-06:02 | 71464.83 | 0.00 |
November | 0.00 | 0.00 | 0.305828E+09 | 0.220206E+09 | 22506.00 | 04-NOV-14:30 | 16631.91 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127938E+12 | 0.106757E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.436380E+11 | 0.358302E+11 | 134816.33 | 96523.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 48063753.52 | 47069835.29 | 4118.17 | 27-FEB-15:10 | 4118.17 | 0.00 |
March | 0.00 | 0.00 | 80267633.51 | 78687221.28 | 4735.73 | 18-MAR-14:00 | 4735.73 | 0.00 |
April | 0.00 | 0.00 | 0.928357E+09 | 0.869106E+09 | 13827.25 | 28-APR-06:03 | 9734.86 | 0.00 |
May | 0.00 | 0.00 | 0.166908E+10 | 0.146769E+10 | 20492.99 | 07-MAY-08:62 | 14769.30 | 0.00 |
June | 0.00 | 0.00 | 0.293957E+10 | 0.270488E+10 | 20189.88 | 12-JUN-06:02 | 13194.70 | 0.00 |
July | 0.00 | 0.00 | 0.590390E+10 | 0.503205E+10 | 20628.20 | 31-JUL-06:02 | 14873.96 | 0.00 |
August | 0.00 | 0.00 | 0.781566E+10 | 0.664369E+10 | 20821.66 | 25-AUG-06:02 | 14422.66 | 0.00 |
September | 0.00 | 0.00 | 0.406874E+10 | 0.329568E+10 | 20250.81 | 01-SEP-06:02 | 13438.49 | 0.00 |
October | 0.00 | 0.00 | 0.842300E+09 | 0.778988E+09 | 15528.70 | 05-OCT-06:02 | 14060.34 | 0.00 |
November | 0.00 | 0.00 | 0.174170E+09 | 0.129624E+09 | 9369.93 | 04-NOV-14:00 | 7273.55 | 0.00 |
December | 0.00 | 0.00 | 5994.90 | 5981.31 | 0.43 | 02-DEC-13:00 | 0.43 | 0.00 |
Annual Sum or Average | 0.244701E+11 | 0.210475E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.781566E+10 | 0.664369E+10 | 20821.66 | 14873.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 8103081.60 | 8102562.43 | 1673.08 | 27-FEB-15:10 | 1673.08 | 0.00 |
March | 0.00 | 0.00 | 19772216.52 | 19771707.10 | 2207.09 | 18-MAR-14:00 | 2207.09 | 0.00 |
April | 0.00 | 0.00 | 0.526731E+09 | 0.505011E+09 | 8855.42 | 27-APR-14:10 | 8419.50 | 0.00 |
May | 0.00 | 0.00 | 0.861968E+09 | 0.781940E+09 | 17036.39 | 07-MAY-08:62 | 12148.80 | 0.00 |
June | 0.00 | 0.00 | 0.148151E+10 | 0.141693E+10 | 16406.10 | 21-JUN-06:02 | 11146.23 | 0.00 |
July | 0.00 | 0.00 | 0.360746E+10 | 0.317667E+10 | 17156.93 | 31-JUL-06:02 | 12263.51 | 0.00 |
August | 0.00 | 0.00 | 0.529677E+10 | 0.465394E+10 | 17325.72 | 25-AUG-06:02 | 11864.49 | 0.00 |
September | 0.00 | 0.00 | 0.236776E+10 | 0.198101E+10 | 16831.43 | 24-SEP-08:62 | 9771.93 | 0.00 |
October | 0.00 | 0.00 | 0.294801E+09 | 0.286340E+09 | 8920.97 | 05-OCT-06:02 | 8183.45 | 0.00 |
November | 0.00 | 0.00 | 84518360.34 | 65046380.90 | 6106.71 | 04-NOV-14:00 | 4837.50 | 0.00 |
December | 0.00 | 0.00 | 1619.34 | 1619.34 | 0.53 | 05-DEC-11:53 | 0.53 | 0.00 |
Annual Sum or Average | 0.145494E+11 | 0.128948E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.529677E+10 | 0.465394E+10 | 17325.72 | 12263.51 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.266971E+10 | 0.50 | 1773.74 | 01-JAN-07:03 | 0.89 |
February | 0.232751E+10 | 0.48 | 1773.74 | 01-FEB-06:03 | 0.89 |
March | 0.244556E+10 | 0.46 | 1773.74 | 01-MAR-06:02 | 0.89 |
April | 0.205711E+10 | 0.40 | 1773.74 | 01-APR-05:03 | 0.89 |
May | 0.175569E+10 | 0.33 | 1773.74 | 01-MAY-07:10 | 0.89 |
June | 0.123124E+10 | 0.24 | 1773.74 | 01-JUN-07:10 | 0.88 |
July | 0.724749E+09 | 0.13 | 1773.74 | 01-JUL-07:10 | 0.88 |
August | 0.583304E+09 | 0.11 | 1773.74 | 01-AUG-07:05 | 0.88 |
September | 0.133735E+10 | 0.26 | 1773.74 | 01-SEP-07:06 | 0.88 |
October | 0.216755E+10 | 0.40 | 1773.74 | 01-OCT-07:08 | 0.88 |
November | 0.236909E+10 | 0.46 | 1773.74 | 01-NOV-05:03 | 0.89 |
December | 0.261430E+10 | 0.49 | 1773.74 | 01-DEC-05:27 | 0.89 |
Annual Sum or Average | 0.222832E+11 | 0.35 | |||
Minimum of Months | 0.583304E+09 | 0.11 | 1773.74 | 0.88 | |
Maximum of Months | 0.266971E+10 | 0.50 | 1773.74 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131790E+10 | 0.35 | 1782.64 | 01-JAN-08:61 | 0.89 |
February | 0.115894E+10 | 0.35 | 1782.64 | 05-FEB-09:02 | 0.89 |
March | 0.121080E+10 | 0.34 | 1782.64 | 05-MAR-08:62 | 0.89 |
April | 0.113151E+10 | 0.33 | 1775.82 | 19-APR-06:03 | 0.89 |
May | 0.115271E+10 | 0.32 | 752.12 | 29-MAY-08:35 | 0.56 |
June | 0.112454E+10 | 0.33 | 1777.15 | 29-JUN-06:02 | 0.88 |
July | 0.114637E+10 | 0.32 | 1782.64 | 20-JUL-06:02 | 0.88 |
August | 0.116529E+10 | 0.33 | 1782.64 | 01-AUG-06:02 | 0.88 |
September | 0.111686E+10 | 0.32 | 1473.09 | 14-SEP-06:02 | 0.81 |
October | 0.114783E+10 | 0.32 | 1352.51 | 30-OCT-06:03 | 0.78 |
November | 0.116220E+10 | 0.33 | 1782.64 | 11-NOV-09:02 | 0.89 |
December | 0.128016E+10 | 0.35 | 1782.64 | 01-DEC-06:02 | 0.89 |
Annual Sum or Average | 0.141151E+11 | 0.33 | |||
Minimum of Months | 0.111686E+10 | 0.32 | 752.12 | 0.56 | |
Maximum of Months | 0.131790E+10 | 0.35 | 1782.64 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.892109E+10 | 0.55 | 12367.62 | 01-JAN-08:61 | 1.40 |
February | 0.783833E+10 | 0.54 | 12367.62 | 20-FEB-08:61 | 1.41 |
March | 0.830833E+10 | 0.53 | 7048.71 | 06-MAR-07:03 | 1.05 |
April | 0.781994E+10 | 0.51 | 12367.62 | 28-APR-06:03 | 1.39 |
May | 0.800212E+10 | 0.51 | 12367.62 | 05-MAY-06:02 | 1.39 |
June | 0.781960E+10 | 0.51 | 12367.62 | 03-JUN-06:03 | 1.39 |
July | 0.798442E+10 | 0.51 | 12367.62 | 01-JUL-06:02 | 1.39 |
August | 0.814737E+10 | 0.52 | 12367.62 | 01-AUG-06:02 | 1.39 |
September | 0.776437E+10 | 0.51 | 12367.62 | 01-SEP-06:02 | 1.39 |
October | 0.795361E+10 | 0.51 | 7183.49 | 05-OCT-06:02 | 1.07 |
November | 0.804227E+10 | 0.52 | 9172.06 | 24-NOV-07:03 | 1.22 |
December | 0.873728E+10 | 0.54 | 12367.62 | 26-DEC-06:01 | 1.40 |
Annual Sum or Average | 0.973387E+11 | 0.52 | |||
Minimum of Months | 0.776437E+10 | 0.51 | 7048.71 | 1.05 | |
Maximum of Months | 0.892109E+10 | 0.55 | 12367.62 | 1.41 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.926132E+09 | 0.35 | 1363.31 | 01-JAN-08:61 | 0.92 |
February | 0.821150E+09 | 0.34 | 1363.31 | 16-FEB-06:01 | 0.92 |
March | 0.898836E+09 | 0.34 | 1091.42 | 06-MAR-06:02 | 0.83 |
April | 0.857579E+09 | 0.34 | 897.56 | 28-APR-06:03 | 0.75 |
May | 0.881767E+09 | 0.34 | 1363.31 | 05-MAY-06:02 | 0.92 |
June | 0.860620E+09 | 0.34 | 1363.31 | 12-JUN-06:02 | 0.91 |
July | 0.881110E+09 | 0.33 | 1363.31 | 08-JUL-06:02 | 0.92 |
August | 0.916092E+09 | 0.34 | 1363.31 | 01-AUG-06:02 | 0.91 |
September | 0.867414E+09 | 0.34 | 1363.31 | 01-SEP-06:02 | 0.91 |
October | 0.874324E+09 | 0.33 | 1041.14 | 05-OCT-06:02 | 0.81 |
November | 0.856451E+09 | 0.33 | 1126.86 | 24-NOV-06:02 | 0.84 |
December | 0.914933E+09 | 0.34 | 1363.31 | 18-DEC-06:01 | 0.92 |
Annual Sum or Average | 0.105564E+11 | 0.34 | |||
Minimum of Months | 0.821150E+09 | 0.33 | 897.56 | 0.75 | |
Maximum of Months | 0.926132E+09 | 0.35 | 1363.31 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177892E+10 | 0.55 | 1109.84 | 01-JAN-08:10 | 0.92 |
February | 0.161459E+10 | 0.55 | 1109.84 | 01-FEB-07:10 | 0.92 |
March | 0.180993E+10 | 0.56 | 1109.84 | 01-MAR-07:33 | 0.92 |
April | 0.173801E+10 | 0.55 | 1109.84 | 01-APR-06:27 | 0.92 |
May | 0.179394E+10 | 0.55 | 1109.84 | 01-MAY-12:10 | 0.91 |
June | 0.174999E+10 | 0.56 | 1109.84 | 01-JUN-09:55 | 0.92 |
July | 0.178196E+10 | 0.55 | 1109.84 | 01-JUL-06:02 | 0.92 |
August | 0.180993E+10 | 0.56 | 1109.84 | 01-AUG-06:30 | 0.91 |
September | 0.173801E+10 | 0.55 | 1109.84 | 01-SEP-08:43 | 0.91 |
October | 0.177796E+10 | 0.55 | 1109.84 | 01-OCT-10:53 | 0.91 |
November | 0.171403E+10 | 0.55 | 1109.84 | 01-NOV-06:05 | 0.92 |
December | 0.178211E+10 | 0.55 | 1109.84 | 01-DEC-06:55 | 0.92 |
Annual Sum or Average | 0.210894E+11 | 0.55 | |||
Minimum of Months | 0.161459E+10 | 0.55 | 1109.84 | 0.91 | |
Maximum of Months | 0.180993E+10 | 0.56 | 1109.84 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.30 | 0.00 |
February | 0.22 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.51 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.30 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.08 | 25.84 |
March | 0.44 | 25.84 |
April | 1.15 | 25.84 |
May | 1.65 | 25.84 |
June | 0.42 | 25.84 |
July | 0.17 | 25.84 |
August | 0.17 | 25.84 |
September | 0.53 | 25.84 |
October | 1.58 | 25.84 |
November | 0.33 | 25.84 |
December | 0.00 | 0.00 |
Annual Sum or Average | 6.53 | 25.84 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.65 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.03 | 0.00 |
February | 0.00 | 0.00 |
March | 0.42 | 2.44 |
April | 0.04 | 2.44 |
May | 0.12 | 2.44 |
June | 0.28 | 0.00 |
July | 0.58 | 0.00 |
August | 0.47 | 0.00 |
September | 0.31 | 0.44 |
October | 0.33 | 2.44 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.59 | 0.91 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.58 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.59 | 0.00 |
February | 0.11 | 0.00 |
March | 0.17 | 2.44 |
April | 0.12 | 2.44 |
May | 0.29 | 2.44 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.06 | 2.44 |
September | 0.00 | 0.00 |
October | 0.42 | 2.44 |
November | 0.17 | 0.00 |
December | 0.08 | 0.00 |
Annual Sum or Average | 2.00 | 1.28 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.59 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 31.57 | 0.00 |
February | 22.96 | 0.00 |
March | 13.40 | 0.00 |
April | 11.28 | 0.00 |
May | 17.76 | 0.00 |
June | 27.59 | 0.00 |
July | 28.87 | 0.00 |
August | 20.43 | 0.00 |
September | 24.52 | 0.00 |
October | 13.83 | 0.00 |
November | 16.14 | 0.00 |
December | 28.56 | 0.00 |
Annual Sum or Average | 256.92 | 0.00 |
Minimum of Months | 11.28 | 0.00 |
Maximum of Months | 31.57 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131790E+10 | 0.899760E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115894E+10 | 0.623263E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121080E+10 | 0.246295E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.123460E+10 | 0.763484E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143589E+10 | 6594792.50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176913E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.263543E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.304254E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.165047E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116332E+10 | 0.283199E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.116816E+10 | 0.313110E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.128016E+10 | 0.694826E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.190673E+11 | 0.288258E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115894E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.304254E+10 | 0.899760E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.892109E+10 | 0.370681E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.784079E+10 | 0.239453E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.833115E+10 | 0.895821E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.879721E+10 | 0.262911E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.104840E+11 | 14656420.51 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.129579E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.178430E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.199581E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.119551E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.828436E+10 | 0.104870E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.813122E+10 | 0.149642E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.873728E+10 | 0.295638E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132241E+12 | 0.118192E+12 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.784079E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.199581E+11 | 0.370681E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.926132E+09 | 0.267332E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.833507E+09 | 0.142468E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.919307E+09 | 0.485236E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.108510E+10 | 0.161842E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.128957E+10 | 3423488.52 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.158709E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.229856E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.277650E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.180460E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.107920E+10 | 32962070.32 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.896403E+09 | 0.726362E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.914935E+09 | 0.200609E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.164109E+11 | 0.751391E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.833507E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.277650E+10 | 0.267332E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177892E+10 | 0.464254E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161650E+10 | 0.255226E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.181449E+10 | 0.105594E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.185283E+10 | 0.403705E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.198181E+10 | 24742755.57 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.207666E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.255745E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.292875E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.221972E+10 | 75816.23 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.184073E+10 | 0.138142E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.173189E+10 | 0.166580E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.178211E+10 | 0.368196E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241819E+11 | 0.141652E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.161650E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.292875E+10 | 0.464254E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131790E+10 | 0.00 | 0.719808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115894E+10 | 0.00 | 0.498610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121080E+10 | 1703.83 | 0.197036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113151E+10 | 0.386232E+09 | 0.610787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115271E+10 | 0.110540E+10 | 5275834.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112454E+10 | 0.253211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114637E+10 | 0.601453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116529E+10 | 0.758883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111686E+10 | 0.214254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114783E+10 | 58288504.09 | 0.226559E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116220E+10 | 21939383.74 | 0.250488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128016E+10 | 0.00 | 0.555860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141151E+11 | 0.198499E+11 | 0.230607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131790E+10 | 0.758883E+10 | 0.719808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.892109E+10 | 0.00 | 0.296545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.783833E+10 | 7848983.87 | 0.191562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.830833E+10 | 74793850.18 | 0.716657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.781994E+10 | 0.341707E+10 | 0.210329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.800212E+10 | 0.891941E+10 | 11725136.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.781960E+10 | 0.185062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.798442E+10 | 0.365221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.814737E+10 | 0.436380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.776437E+10 | 0.154103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.795361E+10 | 0.113606E+10 | 0.838962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804227E+10 | 0.305828E+09 | 0.119713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.873728E+10 | 0.00 | 0.236510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.973387E+11 | 0.127938E+12 | 0.945536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.776437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.892109E+10 | 0.436380E+11 | 0.296545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.926132E+09 | 0.00 | 0.213865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821150E+09 | 48063753.52 | 0.113974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898836E+09 | 80267633.51 | 0.388189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.857579E+09 | 0.928357E+09 | 0.129473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.881767E+09 | 0.166908E+10 | 2738790.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.860620E+09 | 0.293957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.881110E+09 | 0.590390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.916092E+09 | 0.781566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.867414E+09 | 0.406874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.874324E+09 | 0.842300E+09 | 26369656.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.856451E+09 | 0.174170E+09 | 0.581090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.914933E+09 | 5994.90 | 0.160487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105564E+11 | 0.244701E+11 | 0.601113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.821150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.926132E+09 | 0.781566E+10 | 0.213865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177892E+10 | 0.00 | 0.371403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161459E+10 | 8103081.60 | 0.204181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180993E+10 | 19772216.52 | 0.844752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173801E+10 | 0.526731E+09 | 0.322964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179394E+10 | 0.861968E+09 | 19794204.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174999E+10 | 0.148151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178196E+10 | 0.360746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180993E+10 | 0.529677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173801E+10 | 0.236776E+10 | 60652.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177796E+10 | 0.294801E+09 | 0.110514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171403E+10 | 84518360.34 | 0.133264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178211E+10 | 1619.34 | 0.294557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210894E+11 | 0.145494E+11 | 0.113321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180993E+10 | 0.529677E+10 | 0.371403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121080E+10 | 0.00 | 0.00 | 0.00 | 483.55 | 0.00 | 0.246295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113151E+10 | 0.00 | 0.00 | 0.00 | 0.103094E+09 | 0.00 | 0.763484E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.115271E+10 | 0.00 | 0.00 | 0.00 | 0.283177E+09 | 0.00 | 6594792.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112454E+10 | 0.00 | 0.00 | 0.00 | 0.644594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114637E+10 | 0.00 | 0.00 | 0.00 | 0.148906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116529E+10 | 0.00 | 0.00 | 0.00 | 0.187725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111686E+10 | 0.00 | 0.00 | 0.00 | 0.533609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114783E+10 | 0.00 | 0.00 | 0.00 | 15485066.21 | 0.00 | 0.283199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116220E+10 | 0.00 | 0.00 | 0.00 | 5960761.41 | 0.00 | 0.313110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141151E+11 | 0.00 | 0.00 | 0.00 | 0.495223E+10 | 0.00 | 0.288258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.111686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131790E+10 | 0.00 | 0.00 | 0.00 | 0.187725E+10 | 0.00 | 0.899760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.892109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.783833E+10 | 0.00 | 0.00 | 0.00 | 2459551.09 | 0.00 | 0.239453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.830833E+10 | 0.00 | 0.00 | 0.00 | 22819532.12 | 0.00 | 0.895821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.781994E+10 | 0.00 | 0.00 | 0.00 | 0.977274E+09 | 0.00 | 0.262911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.800212E+10 | 0.00 | 0.00 | 0.00 | 0.248190E+10 | 0.00 | 14656420.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.781960E+10 | 0.00 | 0.00 | 0.00 | 0.513834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.798442E+10 | 0.00 | 0.00 | 0.00 | 0.985858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.814737E+10 | 0.00 | 0.00 | 0.00 | 0.118107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.776437E+10 | 0.00 | 0.00 | 0.00 | 0.419077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.795361E+10 | 0.00 | 0.00 | 0.00 | 0.330749E+09 | 0.00 | 0.104870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804227E+10 | 0.00 | 0.00 | 0.00 | 88951759.33 | 0.00 | 0.149642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.873728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.973387E+11 | 0.00 | 0.00 | 0.00 | 0.349026E+11 | 0.00 | 0.118192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.776437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.892109E+10 | 0.00 | 0.00 | 0.00 | 0.118107E+11 | 0.00 | 0.370681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.926132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821150E+09 | 0.00 | 0.00 | 0.00 | 12357228.06 | 0.00 | 0.142468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898836E+09 | 0.00 | 0.00 | 0.00 | 20470769.90 | 0.00 | 0.485236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.857579E+09 | 0.00 | 0.00 | 0.00 | 0.227523E+09 | 0.00 | 0.161842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.881767E+09 | 0.00 | 0.00 | 0.00 | 0.407801E+09 | 0.00 | 3423488.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.860620E+09 | 0.00 | 0.00 | 0.00 | 0.726473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.881110E+09 | 0.00 | 0.00 | 0.00 | 0.141745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.916092E+09 | 0.00 | 0.00 | 0.00 | 0.186041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.867414E+09 | 0.00 | 0.00 | 0.00 | 0.937190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.874324E+09 | 0.00 | 0.00 | 0.00 | 0.204875E+09 | 0.00 | 32962070.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.856451E+09 | 0.00 | 0.00 | 0.00 | 39952496.80 | 0.00 | 0.726362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.914933E+09 | 0.00 | 0.00 | 0.00 | 1694.55 | 0.00 | 0.200609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105564E+11 | 0.00 | 0.00 | 0.00 | 0.585451E+10 | 0.00 | 0.751391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.821150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.926132E+09 | 0.00 | 0.00 | 0.00 | 0.186041E+10 | 0.00 | 0.267332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.177892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161459E+10 | 0.00 | 0.00 | 0.00 | 1909504.66 | 0.00 | 0.255226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180993E+10 | 0.00 | 0.00 | 0.00 | 4569724.98 | 0.00 | 0.105594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173801E+10 | 0.00 | 0.00 | 0.00 | 0.114820E+09 | 0.00 | 0.403705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179394E+10 | 0.00 | 0.00 | 0.00 | 0.187868E+09 | 0.00 | 24742755.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174999E+10 | 0.00 | 0.00 | 0.00 | 0.326663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178196E+10 | 0.00 | 0.00 | 0.00 | 0.775489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180993E+10 | 0.00 | 0.00 | 0.00 | 0.111883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.173801E+10 | 0.00 | 0.00 | 0.00 | 0.481711E+09 | 0.00 | 75816.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177796E+10 | 0.00 | 0.00 | 0.00 | 62772948.65 | 0.00 | 0.138142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171403E+10 | 0.00 | 0.00 | 0.00 | 17851006.26 | 0.00 | 0.166580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178211E+10 | 0.00 | 0.00 | 0.00 | 399.10 | 0.00 | 0.368196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210894E+11 | 0.00 | 0.00 | 0.00 | 0.309248E+10 | 0.00 | 0.141652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.161459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180993E+10 | 0.00 | 0.00 | 0.00 | 0.111883E+10 | 0.00 | 0.464254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.391799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404213E+10 | 0.00 | 0.00 | 0.20 |
February | 0.388886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279192E+10 | 0.00 | 0.00 | 0.20 |
March | 0.561783E+10 | 0.00 | 0.00 | 7615.36 | 0.00 | 0.100815E+10 | 32532065.82 | 0.00 | 0.21 |
April | 0.454575E+10 | 2891334.39 | 0.00 | 1272052.82 | 0.00 | 0.286239E+09 | 0.951874E+09 | 0.00 | 0.23 |
May | 0.210731E+10 | 957292.57 | 0.00 | 6508430.04 | 0.00 | 0.00 | 0.454623E+10 | 0.00 | 0.34 |
June | 0.745428E+09 | 2243192.64 | 0.00 | 11655239.86 | 0.00 | 0.00 | 0.612695E+10 | 0.00 | 0.47 |
July | 0.319059E+09 | 0.149973E+09 | 0.00 | 13919847.50 | 0.00 | 0.00 | 0.498443E+10 | 0.00 | 0.50 |
August | 0.260632E+09 | 0.335099E+09 | 0.00 | 12507126.86 | 0.00 | 0.00 | 0.430358E+10 | 0.00 | 0.47 |
September | 0.104056E+10 | 1877024.18 | 0.00 | 10504843.19 | 0.00 | 0.00 | 0.563898E+10 | 0.00 | 0.43 |
October | 0.434850E+10 | 0.00 | 0.00 | 2101748.24 | 0.00 | 83253989.04 | 0.204666E+10 | 0.00 | 0.25 |
November | 0.530621E+10 | 0.00 | 0.00 | 137029.41 | 0.00 | 0.115469E+10 | 0.129107E+09 | 0.00 | 0.21 |
December | 0.431525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327460E+10 | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.364134E+11 | 0.493041E+09 | 0.00 | 58613933.28 | 0.00 | 0.126410E+11 | 0.287603E+11 | 0.00 | 0.31 |
Minimum of Months | 0.260632E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.561783E+10 | 0.335099E+09 | 0.00 | 13919847.50 | 0.00 | 0.404213E+10 | 0.612695E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.530425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798396E+10 | 0.00 | 0.00 | 0.39 |
February | 0.457948E+11 | 0.00 | 0.00 | 459220.59 | 0.00 | 0.447295E+10 | 0.675205E+09 | 0.00 | 0.40 |
March | 0.480168E+11 | 0.00 | 0.00 | 1297617.65 | 0.00 | 0.356543E+09 | 0.174585E+10 | 0.00 | 0.40 |
April | 0.332529E+11 | 59037160.60 | 0.00 | 12373552.28 | 0.00 | 68113665.80 | 0.893019E+10 | 0.00 | 0.43 |
May | 0.151600E+11 | 42604186.94 | 0.00 | 45208709.06 | 0.00 | 0.00 | 0.273932E+11 | 0.00 | 0.51 |
June | 0.486435E+10 | 51879690.89 | 0.00 | 74317750.08 | 0.00 | 0.00 | 0.322318E+11 | 0.00 | 0.61 |
July | 0.193769E+10 | 0.144135E+10 | 0.00 | 81186183.78 | 0.00 | 0.00 | 0.240880E+11 | 0.00 | 0.61 |
August | 0.191421E+10 | 0.305749E+10 | 0.00 | 68682676.66 | 0.00 | 0.00 | 0.200312E+11 | 0.00 | 0.59 |
September | 0.812388E+10 | 75945602.40 | 0.00 | 61400381.12 | 0.00 | 0.00 | 0.285949E+11 | 0.00 | 0.57 |
October | 0.310204E+11 | 0.00 | 0.00 | 16176831.59 | 0.00 | 57761148.45 | 0.143050E+11 | 0.00 | 0.44 |
November | 0.471069E+11 | 0.00 | 0.00 | 1067305.10 | 0.00 | 0.153490E+10 | 0.766738E+09 | 0.00 | 0.40 |
December | 0.527442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501431E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.342979E+12 | 0.472830E+10 | 0.00 | 0.362170E+09 | 0.00 | 0.194885E+11 | 0.158762E+12 | 0.00 | 0.48 |
Minimum of Months | 0.191421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.530425E+11 | 0.305749E+10 | 0.00 | 81186183.78 | 0.00 | 0.798396E+10 | 0.322318E+11 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478975E+10 | 0.00 | 0.00 | 148945.89 | 0.00 | 0.839887E+09 | 0.192079E+09 | 0.00 | 0.39 |
February | 0.355216E+10 | 0.00 | 0.00 | 1620847.04 | 0.00 | 0.360461E+09 | 0.137489E+10 | 0.00 | 0.44 |
March | 0.266937E+10 | 0.00 | 0.00 | 3864783.81 | 0.00 | 0.104643E+09 | 0.318412E+10 | 0.00 | 0.51 |
April | 0.147437E+10 | 9678570.46 | 0.00 | 6611199.41 | 0.00 | 32239115.35 | 0.392554E+10 | 0.00 | 0.63 |
May | 0.745332E+09 | 15621617.22 | 0.00 | 10239685.61 | 0.00 | 0.00 | 0.503838E+10 | 0.00 | 0.83 |
June | 0.273715E+09 | 9263956.87 | 0.00 | 12973528.33 | 0.00 | 0.00 | 0.489860E+10 | 0.00 | 1.00 |
July | 67674269.15 | 0.203617E+09 | 0.00 | 13331366.49 | 0.00 | 0.00 | 0.362500E+10 | 0.00 | 1.01 |
August | 76883911.79 | 0.430397E+09 | 0.00 | 11728436.12 | 0.00 | 0.00 | 0.303974E+10 | 0.00 | 0.95 |
September | 0.299953E+09 | 88190732.45 | 0.00 | 13947417.80 | 0.00 | 0.00 | 0.488168E+10 | 0.00 | 0.99 |
October | 0.123335E+10 | 0.00 | 0.00 | 8996958.63 | 0.00 | 0.00 | 0.509381E+10 | 0.00 | 0.70 |
November | 0.355481E+10 | 0.00 | 0.00 | 2099116.13 | 0.00 | 0.168786E+09 | 0.144635E+10 | 0.00 | 0.44 |
December | 0.433472E+10 | 0.00 | 0.00 | 885444.11 | 0.00 | 0.621363E+09 | 0.794348E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.230721E+11 | 0.756770E+09 | 0.00 | 86447729.38 | 0.00 | 0.212738E+10 | 0.374945E+11 | 0.00 | 0.69 |
Minimum of Months | 67674269.15 | 0.00 | 0.00 | 148945.89 | 0.00 | 0.00 | 0.192079E+09 | 0.00 | 0.39 |
Maximum of Months | 0.478975E+10 | 0.430397E+09 | 0.00 | 13947417.80 | 0.00 | 0.839887E+09 | 0.509381E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245905E+10 | 0.00 | 0.00 | 0.39 |
February | 0.322407E+10 | 0.00 | 0.00 | 325717.32 | 0.00 | 0.129604E+10 | 0.386739E+09 | 0.00 | 0.41 |
March | 0.340307E+10 | 0.00 | 0.00 | 1088194.23 | 0.00 | 0.551348E+09 | 0.117292E+10 | 0.00 | 0.45 |
April | 0.234106E+10 | 6558161.58 | 0.00 | 2576425.65 | 0.00 | 0.180133E+09 | 0.203978E+10 | 0.00 | 0.55 |
May | 0.140655E+10 | 4769126.85 | 0.00 | 4837802.87 | 0.00 | 687403.64 | 0.342404E+10 | 0.00 | 0.74 |
June | 0.586583E+09 | 4938637.46 | 0.00 | 6884156.78 | 0.00 | 0.00 | 0.415149E+10 | 0.00 | 0.97 |
July | 0.231725E+09 | 0.130149E+09 | 0.00 | 8186125.53 | 0.00 | 0.00 | 0.364284E+10 | 0.00 | 1.06 |
August | 0.218651E+09 | 0.317060E+09 | 0.00 | 7653009.85 | 0.00 | 0.00 | 0.318802E+10 | 0.00 | 1.00 |
September | 0.640308E+09 | 26019496.08 | 0.00 | 8832487.58 | 0.00 | 0.00 | 0.426596E+10 | 0.00 | 0.96 |
October | 0.218154E+10 | 0.00 | 0.00 | 4347774.33 | 0.00 | 58989123.81 | 0.319567E+10 | 0.00 | 0.62 |
November | 0.355602E+10 | 0.00 | 0.00 | 483556.50 | 0.00 | 0.785856E+09 | 0.378346E+09 | 0.00 | 0.42 |
December | 0.322425E+10 | 0.00 | 0.00 | 184145.64 | 0.00 | 0.204086E+10 | 0.224551E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.242510E+11 | 0.489495E+09 | 0.00 | 45399396.27 | 0.00 | 0.737297E+10 | 0.260704E+11 | 0.00 | 0.66 |
Minimum of Months | 0.218651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.355602E+10 | 0.317060E+09 | 0.00 | 8832487.58 | 0.00 | 0.245905E+10 | 0.426596E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:52
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |