Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2020-06-03 19:12:13
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1413.12 | 616.01 | 616.01 |
Net Site Energy | 1413.12 | 616.01 | 616.01 |
Total Source Energy | 4302.39 | 1875.50 | 1875.50 |
Net Source Energy | 4302.39 | 1875.50 | 1875.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 703.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 237.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 83.03 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1330.09 | 83.03 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 703.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 237.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 151.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 83.03 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 122.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 372.72 | 36.20 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 579.81 | 36.20 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 122.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 372.72 | 36.20 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 579.81 | 36.20 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1330.086 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1330.086 | 100.00 |
Total On-Site and Utility Electric Sources | 1330.086 | 100.00 |
Total Electricity End Uses | 1330.086 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 4.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1225.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 5.1793 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.8188 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-14:00 | 11-JAN-12:30 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65137.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16205.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13330.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4788.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 105445.31 | 4788.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 65137.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16205.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13330.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4788.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2227.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 751.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 135.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 480.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.01 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4212.38 | 90.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 971.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 209.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.24 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1836.27 | 39.24 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 971.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 209.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.24 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1836.27 | 39.24 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.95 |
CORE_RETAIL DIRECT AIR | 6.96 |
POINT_OF_SALE DIRECT AIR | 1.09 |
FRONT_RETAIL DIRECT AIR | 0.835838 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.014172 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.014172 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 417.46 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 44926.68 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 161224.46 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 25127.24 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 19313.23 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.95 | 1.95 | 1.95 | 1.95 | 1.97 | 1.97 | 1.00 | 0.990419 | 1.97 |
PSZ-AC:2 | 6.96 | 6.96 | 6.96 | 6.96 | 7.22 | 7.22 | 1.00 | 0.963674 | 7.22 |
PSZ-AC:3 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.09 | 1.00 | 1.00 | 1.09 |
PSZ-AC:4 | 0.835838 | 0.835838 | 0.835838 | 0.835838 | 0.840590 | 0.840590 | 1.00 | 0.994346 | 0.840590 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.97 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.22 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.09 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.840590 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.97 | 1.97 | 1.97 | 1.30 | 40550.81 | 44926.68 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.22 | 7.22 | 7.22 | 4.76 | 179241.50 | 161224.46 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.09 | 1.09 | 1.09 | 0.719614 | 25003.01 | 25127.24 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.840590 | 0.840590 | 0.840590 | 0.554790 | 20681.87 | 19313.23 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.97 | 0.986505 | 1.32 | 38097.13 | 40550.81 | 20275.40 | 20275.40 | 0.727116 | 0.727120 | 0.727120 | 0.727120 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.22 | 3.61 | 4.81 | 179241.62 | 179241.50 | 89620.75 | 89620.75 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.09 | 0.545160 | 0.726880 | 23650.79 | 25003.01 | 12501.50 | 12501.50 | 0.696396 | 0.696400 | 0.696400 | 0.696400 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.840590 | 0.420295 | 0.560393 | 19662.93 | 20681.87 | 10340.93 | 10340.93 | 0.678358 | 0.678360 | 0.678360 | 0.678360 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.97 | 2111.22 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.22 | 12160.36 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.09 | 1207.16 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.840590 | 930.67 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 5.179 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.249 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 33.339 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 1967.547 | 5.179 | 32.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1967.547 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 18915.745 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18915.745 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.9837 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8493 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | 0.31844121E-15 | 0.33891907E-16 | -0.14717764E-09 | -0.34085343E-17 |
25 | 8 | 0.21517510E-07 | 0.13210865E-12 | 0.37403321E-03 | -0.24466149E-09 |
26 | 7 | -0.12129356E-01 | 0.68855956E-08 | -0.22924263E-01 | 0.13791520E-03 |
27 | 6 | 0.40230169 | 0.24029480E-05 | 0.46949424 | -0.47118258E-02 |
28 | 5 | -5.1608121 | 0.89965799E-04 | -4.4213154 | 0.62814943E-01 |
29 | 4 | 32.871256 | 0.73775273E-03 | 21.362378 | -0.42037561 |
30 | 3 | -110.94624 | 0.16114037E-02 | -55.469893 | 1.5111496 |
31 | 2 | 196.85374 | 0.90819125E-03 | 77.733479 | -2.8963115 |
32 | 1 | -171.06207 | 0.97128343E-04 | -55.213590 | 2.7437919 |
33 | 0 | 57.057407 | 0.55402955E-06 | 15.565444 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5_SHGC_0.25 | 30 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 31 | 1 | VerySmooth | 5.108 | 0.600 | 0.461 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1928 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 23029.26200 | 27635.11440 | 1.62843 | 1.95411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71339E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 3416.20467 | 4099.44561 | 0.14476 | 0.23157 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 82462.25234 | 98954.70281 | 5.79654 | 6.95585 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71339E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 15409.75720 | 18491.70865 | 0.64779 | 1.89021 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12725.72663 | 15270.87195 | 0.90860 | 1.09032 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71339E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 1872.19881 | 2246.63857 | 7.90448E-002 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 9829.08136 | 11794.89763 | 0.69653 | 0.83584 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71339E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 1872.19881 | 2246.63857 | 7.90448E-002 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20000 | 1.71339E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10000 | 1.47983E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 28009.52 | 1.97301 | 1.97301 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 5573.32 | 0.23157 | 0.23157 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 117900.45 | 7.21806 | 7.21806 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 45493.45 | 1.89021 | 1.89021 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 16219.10 | 1.09032 | 1.09032 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 4286.75 | 0.17811 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 13332.52 | 0.84059 | 0.84059 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 4286.75 | 0.17811 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.95411 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.95585 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09032 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83584 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.41723E-002 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.41723E-002 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 417.45501 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.95411 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.95411 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.95411 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.95411 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.97301 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.97301 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.99042 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.95585 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.95585 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.95585 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.95585 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.21806 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.21806 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96367 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09032 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09032 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09032 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09032 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09032 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.09032 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.83584 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.83584 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.83584 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.83584 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.84059 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.84059 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.99435 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.97301 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.21806 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.09032 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.84059 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.97301 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.97301 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.97301 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.97301 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30219 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.97301 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98651 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31534 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 38097.12513 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 40550.81000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 20275.40500 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 20275.40500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72712 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72712 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72712 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72712 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40550.81000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 44926.67939 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.97301 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2111.21891 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 44926.67939 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.21806 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.21806 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.21806 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.21806 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.76392 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.21806 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.60903 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.81204 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 179241.61907 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 179241.50000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 89620.75000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 89620.75000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 179241.50000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 161224.46210 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.21806 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 12160.36325 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 161224.46210 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09032 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09032 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09032 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09032 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.71961 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09032 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54516 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.72688 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 23650.79016 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 25003.01000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 12501.50500 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 12501.50500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69640 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69640 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69640 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69640 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25003.01000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25127.24373 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09032 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1207.16186 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 25127.24373 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.84059 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.84059 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.84059 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.84059 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.55479 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.84059 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.42030 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.56039 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 19662.93016 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 20681.87000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 10340.93500 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 10340.93500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67836 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67836 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67836 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67836 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20681.87000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 19313.22571 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.84059 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 930.66696 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 19313.22571 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 38999.6 | 11.42 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 173547.1 | 13.30 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 24144.1 | 115.70 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 20018.8 | 153.01 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 3.4182829326E-002 | 0.1429786681 | Pass | Pass | 0.1660870571 | 1.0454221530 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 2.9440339636E-002 | 0.1301508661 | Pass | Pass | 0.1012021087 | 0.6298533201 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 4.2256156721E-002 | 0.1806257478 | Pass | Pass | 4.5606682002E-002 | 0.2085922743 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 3.5109403143E-002 | 0.1468157020 | Pass | Pass | 7.9956533820E-002 | 0.4963872405 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 6.7157717552E-002 | 0.1087166415 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.843 | 0.252 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.5_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.843 | 0.252 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.343 | 0.329 | 0.328 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.343 | 0.329 | 0.328 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 5.1793 | 379.89 | 1967.55 | LightsWired | BLDG_LIGHT_BACK_SCH | 60.89 | 168.00 | 60.06 | 0.0000 | Y | 22.18 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 11.8188 | 1600.48 | 18915.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 47.27 | 0.0000 | Y | 167.83 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.49 |
Interior Lighting Total | 10.7081 | 2293.99 | 24564.32 | 237.18 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 238.00 | AstronomicalClock | - | 41.93 | 41.93 | 1.87 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.83 | 71.26 | 40.86 | |
Exterior Lighting Total | 3292.90 | 42.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 40550.81 | 29485.30 | 11065.51 | 0.73 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 179241.50 | 121181.59 | 58059.91 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 25003.01 | 17412.10 | 7590.91 | 0.70 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 20681.87 | 14029.75 | 6652.12 | 0.68 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 38999.6 | 11.42 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 173547.1 | 13.30 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 24144.1 | 115.70 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 20018.8 | 153.01 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 417.46 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 44926.68 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 161224.46 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 25127.24 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 19313.23 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.01 | 15.87 | 1120.11 | 1.00 | 15.42 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.97 | 2111.22 | 1070.05 | 1.00 | 1.32 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.22 | 12160.36 | 1684.71 | 1.00 | 1.16 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.09 | 1207.16 | 1107.16 | 1.00 | 1.38 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.84 | 930.67 | 1107.16 | 1.00 | 1.45 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 23029.26 | 27635.11 | 72.75 | 1.628 | 1.954 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 23.89 | 23.89 | 0.00967 | 28.91 | 0.01713 | 0.232 | 0.00 |
CORE_RETAIL | 82462.25 | 98954.70 | 61.83 | 5.797 | 6.956 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 23.89 | 23.88 | 0.01001 | 28.91 | 0.01713 | 1.890 | 0.00 |
POINT_OF_SALE | 12725.73 | 15270.87 | 101.26 | 0.909 | 1.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 23.89 | 23.89 | 0.00907 | 28.91 | 0.01713 | 0.178 | 0.00 |
FRONT_RETAIL | 9829.08 | 11794.90 | 78.21 | 0.697 | 0.836 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 23.89 | 23.89 | 0.00960 | 28.91 | 0.01713 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 34.68 | 100.00 | 0.00001 | 35.20 | 0.01713 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 3416.20 | 4099.45 | 10.79 | 0.145 | 0.232 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01064 | 20.10 | 0.01480 | 0.232 | 0.00 |
CORE_RETAIL | 15409.76 | 18491.71 | 11.55 | 0.648 | 1.890 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00868 | 20.10 | 0.01480 | 1.890 | 0.00 |
POINT_OF_SALE | 1872.20 | 2246.64 | 14.90 | 0.079 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01042 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_RETAIL | 1872.20 | 2246.64 | 14.90 | 0.079 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01042 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 0.00 | 16.00 | 0.00800 | 20.10 | 0.01480 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.97 | 1.97 | 0.23 | 0.23 | 1.9730 | 1.9541 | 1.9730 | 0.9904 | 1.0000 |
PSZ-AC:2 | 7.22 | 7.22 | 1.89 | 1.89 | 7.2181 | 6.9558 | 7.2181 | 0.9637 | 1.0000 |
PSZ-AC:3 | 1.09 | 1.09 | 0.18 | 0.18 | 1.0903 | 1.0903 | 1.0903 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.84 | 0.84 | 0.18 | 0.18 | 0.8406 | 0.8358 | 0.8406 | 0.9943 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 417.455 | 417.455 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 417.46 | 417.46 | 0.014172 | 16.00 | 12.90 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 16.00 | 0.00800000 | 70.7169 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 20275.405 | 0.000 | 1.973010 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 20275.40 | 14984.97 | 1.973010 | 24.54 | 18.08 | 0.01033194 | 12.80 | 12.09 | 0.00850000 | 29.45 | 0.01713393 | 24.34 | 11.7367 | 23.89 | 0.00966937 | 52.2890 | 23029.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 44926.679 | 44926.679 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 44926.68 | 44926.68 | 1.973015 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 11.7367 | 21.11 | 0.01064281 | 68.0173 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 89620.750 | 0.000 | 7.218060 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 89620.75 | 60792.56 | 7.218060 | 26.88 | 19.67 | 0.01140073 | 12.80 | 12.09 | 0.00850000 | 34.85 | 0.01713393 | 25.71 | 26.1873 | 23.88 | 0.01001482 | 54.1304 | 78590.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 161224.462 | 161224.462 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 161224.46 | 161224.46 | 7.218055 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 26.1873 | 21.11 | 0.00868090 | 55.6538 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 12501.505 | 0.000 | 1.090320 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 12501.50 | 9338.26 | 1.090320 | 25.85 | 18.59 | 0.01043375 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 16.3356 | 23.89 | 0.00906974 | 49.0872 | 11665.65 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 25127.244 | 25127.244 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | 25127.24 | 25127.24 | 1.090324 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.3356 | 21.11 | 0.01042087 | 66.6212 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 10340.935 | 0.000 | 0.840590 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 10340.93 | 7343.32 | 0.840590 | 26.37 | 19.13 | 0.01091430 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 21.1888 | 23.89 | 0.00959904 | 51.9145 | 9222.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 19313.226 | 19313.226 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 19313.23 | 19313.23 | 0.840590 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 21.1887 | 21.11 | 0.01042087 | 66.6212 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 417.455 | 417.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.014172 | 0.01705772 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 417.46 | 417.46 | 1.0000 | 0.01705772 | 0.014172 | 16.00 | 12.90 | 0.00800000 | 36322.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 417.46 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 16.00 | 0.00800000 | 16.00 | 0.00800000 | 70.7169 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20275.405 | 0.000 | 1.973010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0466 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 20275.40 | 14984.97 | 1.0000 | 2.37470493 | 1.973010 | 24.54 | 18.08 | 0.01033194 | 50967.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20275.40 | 29.45 | 0.01713393 | 24.34 | 0.23156651 | 11.7367 | 23.88 | 0.00942746 | 23.89 | 0.00966937 | 52.2890 | 23029.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44926.679 | 44926.679 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.973015 | 2.37471050 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 44926.68 | 44926.68 | 1.0000 | 2.37471050 | 1.973015 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44926.68 | 20.10 | 0.01479830 | 20.10 | 0.23156651 | 11.7367 | 21.11 | 0.00000000 | 21.11 | 0.01064281 | 68.0173 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 89620.750 | 0.000 | 7.218060 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0334 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 89620.75 | 60792.56 | 1.0000 | 8.68762079 | 7.218060 | 26.88 | 19.67 | 0.01140073 | 56092.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89620.75 | 34.85 | 0.01713393 | 25.71 | 1.89021192 | 26.1873 | 23.89 | 0.00924775 | 23.88 | 0.01001482 | 54.1304 | 78590.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 161224.462 | 161224.462 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.218055 | 8.68761500 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 161224.46 | 161224.46 | 1.0000 | 8.68761500 | 7.218055 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 161224.46 | 20.10 | 0.01479830 | 20.10 | 1.89021192 | 26.1873 | 21.11 | 0.00000000 | 21.11 | 0.00868090 | 55.6538 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 12501.505 | 0.000 | 1.090320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2358 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 12501.50 | 9338.26 | 1.0000 | 1.31230368 | 1.090320 | 25.85 | 18.59 | 0.01043375 | 52569.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12501.50 | 35.20 | 0.01713393 | 25.80 | 0.17811053 | 16.3356 | 23.89 | 0.00902919 | 23.89 | 0.00906974 | 49.0872 | 11665.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25127.244 | 25127.244 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.090324 | 1.31230862 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:20:00 | 25127.24 | 25127.24 | 1.0000 | 1.31230862 | 1.090324 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25127.24 | 20.10 | 0.01479830 | 20.10 | 0.17811053 | 16.3356 | 21.11 | 0.00000000 | 21.11 | 0.01042087 | 66.6212 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 10340.935 | 0.000 | 0.840590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.1291 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 10340.93 | 7343.32 | 1.0000 | 1.01172991 | 0.840590 | 26.37 | 19.13 | 0.01091430 | 54326.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10340.93 | 35.20 | 0.01713393 | 25.80 | 0.17811053 | 21.1888 | 23.89 | 0.00916808 | 23.89 | 0.00959904 | 51.9145 | 9222.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19313.226 | 19313.226 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.840590 | 1.01173034 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 19313.23 | 19313.23 | 1.0000 | 1.01173034 | 0.840590 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19313.23 | 20.10 | 0.01479830 | 20.10 | 0.17811053 | 21.1887 | 21.11 | 0.00000000 | 21.11 | 0.01042087 | 66.6212 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 4913.00 | 335.17 | 335.17 |
CORE_RETAIL | 4913.00 | 1223.17 | 1223.17 |
POINT_OF_SALE | 4913.00 | 244.17 | 244.17 |
FRONT_RETAIL | 4913.00 | 468.17 | 468.17 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4913.00 | 1225.17 | 1225.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 6.83 | 0.00 | 4.83 |
CORE_RETAIL | 0.00 | 1.00 | 0.00 | 1.00 |
POINT_OF_SALE | 0.00 | 0.17 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 0.33 | 0.00 | 0.33 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 6.83 | 0.00 | 4.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.372 | 0.020 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.721 | 0.004 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.720 | 0.021 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.720 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.39 | 61.34 | 2317.33 | 0.364 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.05 | 258.43 | 9762.95 | 0.706 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.07 | 24.35 | 919.94 | 0.705 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.07 | 24.35 | 919.94 | 0.706 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1330.09 | 2708.13 | 05-MAR-08:00 | 105445.31 | 13-JUN-15:00 |
Electricity:Building | 432.33 | 2550.50 | 29-JAN-09:00 | 32651.56 | 02-JAN-16:30 |
Electricity:Zone:BACK_SPACE | 72.17 | 558.23 | 01-JAN-00:10 | 4302.56 | 02-JAN-09:10 |
InteriorLights:Electricity | 237.18 | 755.32 | 29-JAN-09:00 | 21880.52 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BACK_SPACE | 22.18 | 98.38 | 01-JAN-00:10 | 1543.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 237.18 | 755.32 | 29-JAN-09:00 | 21880.52 | 02-JAN-16:30 |
Electricity:Zone:CORE_RETAIL | 252.13 | 1248.33 | 29-JAN-09:00 | 21676.77 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 167.83 | 472.89 | 29-JAN-09:00 | 17024.17 | 02-JAN-16:30 |
Electricity:Zone:POINT_OF_SALE | 75.76 | 575.93 | 01-JAN-00:10 | 4525.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 30.78 | 162.19 | 01-JAN-00:10 | 2042.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1330.09 | 2708.13 | 05-MAR-08:00 | 105445.31 | 13-JUN-15:00 |
ElectricityPurchased:Plant | 1330.09 | 2708.13 | 05-MAR-08:00 | 105445.31 | 13-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1330.09 | 2708.13 | 05-MAR-08:00 | 105445.31 | 13-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1330.09 | 2708.13 | 05-MAR-08:00 | 105445.31 | 13-JUN-15:00 |
ElectricityNet:Plant | 1330.09 | 2708.13 | 05-MAR-08:00 | 105445.31 | 13-JUN-15:00 |
Cogeneration:ElectricityNet | 1330.09 | 2708.13 | 05-MAR-08:00 | 105445.31 | 13-JUN-15:00 |
Electricity:HVAC | 855.01 | 0.00 | 01-JAN-00:10 | 78540.37 | 11-JUN-08:10 |
Fans:Electricity | 151.58 | 0.00 | 01-JAN-00:10 | 14605.03 | 11-JUN-08:10 |
General:Fans:Electricity | 151.58 | 0.00 | 01-JAN-00:10 | 14605.03 | 11-JUN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 703.43 | 0.00 | 01-JAN-00:10 | 65137.54 | 13-JUN-15:00 |
ExteriorLights:Electricity | 42.74 | 0.00 | 01-JAN-06:20 | 3292.90 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.74 | 0.00 | 01-JAN-06:20 | 3292.90 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 83.03 | 1862.00 | 01-JAN-00:10 | 4788.73 | 11-JAN-12:30 |
Gas:Plant | 83.03 | 1862.00 | 01-JAN-00:10 | 4788.73 | 11-JAN-12:30 |
WaterSystems:Gas | 83.03 | 1862.00 | 01-JAN-00:10 | 4788.73 | 11-JAN-12:30 |
Water Heater:WaterSystems:Gas | 83.03 | 1862.00 | 01-JAN-00:10 | 4788.73 | 11-JAN-12:30 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3907.44 | 0.00 | 01-JAN-00:10 | 359134.24 | 11-JUN-08:10 |
EnergyTransfer:Building | 1117.40 | 0.00 | 01-JAN-00:10 | 93763.34 | 23-NOV-09:10 |
EnergyTransfer:Zone:BACK_SPACE | 202.95 | 0.00 | 01-JAN-00:10 | 17909.97 | 07-MAY-08:10 |
Heating:EnergyTransfer | 2.49 | 0.00 | 01-JAN-00:10 | 11275.86 | 26-MAR-07:20 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.26 | 0.00 | 01-JAN-00:10 | 1512.01 | 14-MAY-07:20 |
Cooling:EnergyTransfer | 1114.91 | 0.00 | 01-JAN-00:10 | 92001.76 | 06-MAY-13:40 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 202.69 | 0.00 | 01-JAN-00:10 | 17909.97 | 07-MAY-08:10 |
EnergyTransfer:Zone:CORE_RETAIL | 676.25 | 0.00 | 01-JAN-00:10 | 61193.46 | 23-NOV-09:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 2.03 | 0.00 | 01-JAN-00:10 | 9120.54 | 09-APR-07:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 674.22 | 0.00 | 01-JAN-00:10 | 57985.89 | 23-NOV-09:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 136.42 | 0.00 | 01-JAN-00:10 | 11359.08 | 08-DEC-13:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.11 | 0.00 | 01-JAN-00:10 | 806.84 | 11-APR-05:20 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 136.31 | 0.00 | 01-JAN-00:10 | 11359.08 | 08-DEC-13:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 101.79 | 0.00 | 01-JAN-00:10 | 9242.72 | 08-DEC-13:30 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.09 | 0.00 | 01-JAN-00:10 | 740.21 | 09-APR-07:20 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 101.70 | 0.00 | 01-JAN-00:10 | 9242.72 | 08-DEC-13:30 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 2790.04 | 0.00 | 01-JAN-00:10 | 271353.05 | 11-JUN-08:10 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2790.04 | 0.00 | 01-JAN-00:10 | 271353.05 | 11-JUN-08:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.258 | -202.678 | 0.000 | 0.000 | 36.660 | 22.181 | 49.992 | 0.000 | 0.000 | 1.814 | 92.269 | 0.000 | 0.000 | 0.000 | -0.497 | -0.003 |
CORE_RETAIL | 0.000 | 0.000 | 2.031 | -674.194 | 0.000 | 0.000 | 154.451 | 167.835 | 84.299 | 93.215 | 0.000 | 1.571 | 176.997 | 0.000 | -5.873 | 0.000 | -0.331 | -0.007 |
POINT_OF_SALE | 0.000 | 0.000 | 0.106 | -136.306 | 0.000 | 0.000 | 14.554 | 22.836 | 52.922 | 28.202 | 0.000 | 0.748 | 20.464 | 0.000 | -3.192 | 0.000 | -0.334 | -0.000 |
FRONT_RETAIL | 0.000 | 0.000 | 0.092 | -101.690 | 0.000 | 0.000 | 14.554 | 22.836 | 7.943 | 28.149 | 0.000 | 0.783 | 30.336 | 0.000 | -2.773 | 0.000 | -0.229 | -0.001 |
FRONT_ENTRY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.489 | 0.000 | 4.805 | 0.000 | 2.764 | 0.000 | 0.000 | -0.844 | 0.000 | -0.843 | -7.371 |
Total Facility | 0.000 | 0.000 | 2.486 | -1114.868 | 0.000 | 0.000 | 220.218 | 237.178 | 195.156 | 154.371 | 0.000 | 7.680 | 320.066 | 0.000 | -12.683 | 0.000 | -2.234 | -7.382 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | -30707.96 | 0.00 | 0.00 | 0.00 | 98.38 | 613.14 | 0.00 | 0.00 | 0.00 | 30014.70 | 0.00 | -0.00 | 0.00 | -18.26 | 0.00 |
CORE_RETAIL | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | -119664.98 | 0.00 | 0.00 | 0.00 | 945.79 | 1033.91 | 0.00 | 0.00 | 0.00 | 118498.54 | 0.00 | -799.29 | 0.00 | -13.97 | 0.00 |
POINT_OF_SALE | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | -19274.27 | 0.00 | 0.00 | 0.00 | 89.12 | 649.09 | 0.00 | 0.00 | 0.00 | 19103.87 | 0.00 | -557.60 | 0.00 | -10.20 | 0.00 |
FRONT_RETAIL | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | -14905.27 | 0.00 | 0.00 | 0.00 | 89.12 | 97.42 | 0.00 | 0.00 | 0.00 | 15241.65 | 0.00 | -514.24 | 0.00 | -8.68 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | -184552.48 | 0.00 | 0.00 | 0.00 | 1228.22 | 2393.56 | 0.00 | 0.00 | 0.00 | 182974.18 | 0.00 | -1990.74 | 0.00 | -52.74 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 07-MAY-07:20 | 0.00 | 0.00 | 2262.23 | 0.00 | 0.00 | 0.00 | 0.00 | 98.38 | 459.86 | 0.00 | 0.00 | 43.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2863.48 |
CORE_RETAIL | 28-MAY-07:05 | 0.00 | 0.00 | 21294.96 | 0.00 | 0.00 | 0.00 | 0.00 | 788.16 | 775.43 | 3505.98 | 0.00 | 36.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26400.79 |
POINT_OF_SALE | 28-MAY-07:07 | 0.00 | 0.00 | 2074.22 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 486.81 | 980.77 | 0.00 | 19.01 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3649.94 |
FRONT_RETAIL | 28-MAY-07:07 | 0.00 | 0.00 | 1884.96 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 73.07 | 1016.37 | 0.00 | 18.95 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3082.47 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-MAY-07:05 | -29683.38 | 29683.38 | 21294.96 | -29683.38 | 0.00 | 0.00 | 0.00 | 1070.58 | 1795.17 | 5697.07 | 0.00 | 718.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -892.59 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9541 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9730 | 0.1174 | 1.0000 | 0.2316 | 0.1174 | ||
PSZ-AC:2 | 6.9558 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.2181 | 0.2619 | 1.0000 | 1.8902 | 0.2619 | ||
PSZ-AC:3 | 1.0903 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0903 | 0.1634 | 1.0000 | 0.1781 | 0.1634 | ||
PSZ-AC:4 | 0.8358 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8406 | 0.2119 | 1.0000 | 0.1781 | 0.2119 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.9541 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.9541 | 1.0000 | 1.0000 | 0.2316 | 0.1185 | ||
PSZ-AC:2 | 6.9558 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.9558 | 1.0000 | 1.0000 | 1.8902 | 0.2717 | ||
PSZ-AC:3 | 1.0903 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0903 | 1.0000 | 1.0000 | 0.1781 | 0.1634 | ||
PSZ-AC:4 | 0.8358 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8358 | 1.0000 | 1.0000 | 0.1781 | 0.2131 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9541 | 1.9541 | 1.9541 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.9558 | 6.9558 | 6.9558 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0903 | 1.0903 | 1.0903 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8358 | 0.8358 | 0.8358 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9541 | 1.9730 | 1.9541 | 1.9541 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.9558 | 7.2181 | 6.9558 | 6.9558 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0903 | 1.0903 | 1.0903 | 1.0903 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8358 | 0.8406 | 0.8358 | 0.8358 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.9541 | 1.9541 | 1.9541 | 0.2316 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.9558 | 6.9558 | 6.9558 | 1.8902 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0903 | 1.0903 | 1.0903 | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8358 | 0.8358 | 0.8358 | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.9541 | 1.9541 | 1.9541 | 1.9541 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.9558 | 6.9558 | 6.9558 | 6.9558 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0903 | 1.0903 | 1.0903 | 1.0903 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8358 | 0.8358 | 0.8358 | 0.8358 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:13
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2293.99 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 4.83 |
Number of hours not met | 4.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 703.43 | 65137.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 237.18 | 21880.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.74 | 3292.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 151.58 | 14605.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 83.03 | 4788.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 1330.09 |
Natural Gas | 0.00 | 83.03 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1413.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.39 |
Space Heating | 0.00 |
Space Cooling | 306.64 |
Fans (All) | 66.08 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 579.81 |
Subtotal | 579.81 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 36.20 |
Miscellaneous (All) | 36.20 |
Subtotal | 36.20 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 16.78 |
Space Heating | 0.00 |
Space Cooling | 49.78 |
Fans (All) | 10.73 |
Service Water Heating | 5.88 |
Receptacle Equipment | 13.81 |
Miscellaneous | 3.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3175. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151832E+11 | 27701.67 | 24-JAN-07:02 | 19.50 | 17.56 | 0.218487E+10 | 2451.25 | 30-JAN-15:50 | 30.42 | 24.65 |
February | 0.149195E+11 | 30711.12 | 23-FEB-06:02 | 22.85 | 19.63 | 0.199509E+10 | 2451.28 | 21-FEB-15:39 | 32.60 | 23.32 |
March | 0.177819E+11 | 25339.42 | 03-MAR-07:02 | 23.83 | 20.44 | 0.228192E+10 | 2451.23 | 07-MAR-15:30 | 30.90 | 24.67 |
April | 0.180814E+11 | 24569.72 | 27-APR-05:02 | 26.00 | 23.87 | 0.215723E+10 | 2451.17 | 15-APR-11:20 | 32.67 | 26.00 |
May | 0.192087E+11 | 25415.81 | 11-MAY-05:02 | 24.00 | 24.00 | 0.223336E+10 | 2451.19 | 01-MAY-14:09 | 34.83 | 27.34 |
June | 0.203080E+11 | 26139.76 | 20-JUN-05:02 | 24.00 | 24.00 | 0.220243E+10 | 2451.26 | 30-JUN-14:00 | 29.00 | 27.47 |
July | 0.181344E+11 | 27902.49 | 11-JUL-05:02 | 24.12 | 23.83 | 0.218816E+10 | 2451.24 | 12-JUL-14:00 | 27.00 | 25.53 |
August | 0.175546E+11 | 25650.03 | 16-AUG-05:02 | 24.00 | 24.00 | 0.228190E+10 | 2451.25 | 19-AUG-14:09 | 29.00 | 26.51 |
September | 0.166484E+11 | 25437.07 | 12-SEP-05:02 | 25.00 | 24.24 | 0.215725E+10 | 2451.21 | 16-SEP-13:09 | 24.58 | 24.19 |
October | 0.152710E+11 | 24921.06 | 11-OCT-05:02 | 24.00 | 23.32 | 0.218486E+10 | 2451.24 | 13-OCT-14:09 | 30.33 | 26.58 |
November | 0.148292E+11 | 26019.53 | 25-NOV-07:02 | 21.17 | 18.83 | 0.210214E+10 | 2451.25 | 22-NOV-15:09 | 31.37 | 24.56 |
December | 0.147675E+11 | 26824.69 | 21-DEC-07:02 | 18.83 | 17.79 | 0.218818E+10 | 2451.22 | 09-DEC-14:50 | 27.67 | 24.93 |
Annual Sum or Average | 0.202687E+12 | 0.261574E+11 | ||||||||
Minimum of Months | 0.147675E+11 | 24569.72 | 18.83 | 17.56 | 0.199509E+10 | 2451.17 | 24.58 | 23.32 | ||
Maximum of Months | 0.203080E+11 | 30711.12 | 26.00 | 24.24 | 0.228192E+10 | 2451.28 | 34.83 | 27.47 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.537122E+11 | 111835.37 | 23-JAN-07:02 | 19.82 | 17.48 | 0.920437E+10 | 10327.34 | 14-JAN-16:00 | 28.50 | 23.48 |
February | 0.519865E+11 | 119683.39 | 23-FEB-06:02 | 22.85 | 19.63 | 0.840510E+10 | 10326.95 | 11-FEB-11:09 | 29.17 | 24.63 |
March | 0.618787E+11 | 107120.79 | 14-MAR-05:02 | 25.00 | 22.78 | 0.961374E+10 | 10327.01 | 04-MAR-16:00 | 31.00 | 22.02 |
April | 0.607556E+11 | 102475.59 | 27-APR-05:02 | 26.00 | 23.87 | 0.908850E+10 | 10326.88 | 15-APR-11:20 | 32.67 | 26.00 |
May | 0.601968E+11 | 97301.96 | 31-MAY-05:02 | 24.17 | 24.17 | 0.940929E+10 | 10327.01 | 01-MAY-14:09 | 34.83 | 27.34 |
June | 0.609514E+11 | 98366.96 | 20-JUN-05:02 | 24.00 | 24.00 | 0.927904E+10 | 10326.84 | 24-JUN-15:00 | 29.30 | 26.87 |
July | 0.560495E+11 | 103232.96 | 31-JUL-05:02 | 24.15 | 23.23 | 0.921873E+10 | 10326.79 | 01-JUL-11:20 | 31.57 | 25.04 |
August | 0.570208E+11 | 96806.71 | 24-AUG-05:02 | 24.00 | 24.00 | 0.961371E+10 | 10327.07 | 19-AUG-14:50 | 25.00 | 24.56 |
September | 0.553737E+11 | 97415.84 | 13-SEP-05:02 | 24.17 | 24.04 | 0.908850E+10 | 10327.02 | 16-SEP-12:50 | 25.17 | 24.51 |
October | 0.525583E+11 | 96550.54 | 10-OCT-05:02 | 24.00 | 23.57 | 0.920474E+10 | 10327.10 | 30-OCT-14:09 | 23.92 | 23.86 |
November | 0.513916E+11 | 106495.82 | 25-NOV-07:02 | 21.17 | 18.83 | 0.885613E+10 | 10327.12 | 09-NOV-15:50 | 24.92 | 24.31 |
December | 0.523424E+11 | 104632.95 | 27-DEC-07:02 | 20.50 | 19.41 | 0.921832E+10 | 10327.36 | 27-DEC-15:00 | 31.20 | 22.98 |
Annual Sum or Average | 0.674217E+12 | 0.110200E+12 | ||||||||
Minimum of Months | 0.513916E+11 | 96550.54 | 19.82 | 17.48 | 0.840510E+10 | 10326.79 | 23.92 | 22.02 | ||
Maximum of Months | 0.618787E+11 | 119683.39 | 26.00 | 24.17 | 0.961374E+10 | 10327.36 | 34.83 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123792E+11 | 18125.51 | 18-JAN-06:02 | 19.95 | 19.88 | 0.867345E+09 | 973.16 | 28-JAN-11:09 | 28.33 | 21.84 |
February | 0.112842E+11 | 19276.74 | 23-FEB-06:02 | 22.85 | 19.63 | 0.791994E+09 | 973.14 | 25-FEB-11:00 | 29.00 | 21.35 |
March | 0.119815E+11 | 15788.91 | 03-MAR-06:03 | 22.23 | 20.03 | 0.905869E+09 | 973.14 | 03-MAR-15:00 | 32.80 | 23.89 |
April | 0.111720E+11 | 14606.83 | 27-APR-05:02 | 26.00 | 23.87 | 0.856373E+09 | 973.07 | 15-APR-11:20 | 32.67 | 26.00 |
May | 0.114547E+11 | 14828.80 | 11-MAY-05:02 | 24.00 | 24.00 | 0.886602E+09 | 973.08 | 01-MAY-14:09 | 34.83 | 27.34 |
June | 0.114174E+11 | 14903.24 | 20-JUN-05:02 | 24.00 | 24.00 | 0.874330E+09 | 973.13 | 30-JUN-14:09 | 27.33 | 25.85 |
July | 0.107146E+11 | 16102.30 | 11-JUL-05:02 | 24.12 | 23.83 | 0.868654E+09 | 973.10 | 08-JUL-10:39 | 28.30 | 24.42 |
August | 0.107966E+11 | 14927.78 | 16-AUG-05:02 | 24.00 | 24.00 | 0.905870E+09 | 973.10 | 19-AUG-14:50 | 25.00 | 24.56 |
September | 0.107449E+11 | 15170.59 | 12-SEP-05:02 | 25.00 | 24.24 | 0.856381E+09 | 973.10 | 16-SEP-15:09 | 27.07 | 25.50 |
October | 0.108121E+11 | 15227.11 | 11-OCT-05:02 | 24.00 | 23.32 | 0.867338E+09 | 973.10 | 21-OCT-10:09 | 28.50 | 24.52 |
November | 0.113343E+11 | 15994.14 | 24-NOV-06:02 | 23.05 | 20.95 | 0.834492E+09 | 973.12 | 09-NOV-15:00 | 24.40 | 24.15 |
December | 0.122211E+11 | 16846.68 | 07-DEC-06:02 | 22.17 | 22.05 | 0.868658E+09 | 973.15 | 20-DEC-15:50 | 30.50 | 21.53 |
Annual Sum or Average | 0.136313E+12 | 0.103839E+11 | ||||||||
Minimum of Months | 0.107146E+11 | 14606.83 | 19.95 | 19.63 | 0.791994E+09 | 973.07 | 24.40 | 21.35 | ||
Maximum of Months | 0.123792E+11 | 19276.74 | 26.00 | 24.24 | 0.905870E+09 | 973.16 | 34.83 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.944635E+10 | 13514.59 | 16-JAN-08:61 | 22.05 | 20.00 | 0.867327E+09 | 973.12 | 28-JAN-11:09 | 28.33 | 21.84 |
February | 0.861853E+10 | 14907.51 | 23-FEB-06:02 | 22.85 | 19.63 | 0.791987E+09 | 973.10 | 25-FEB-11:50 | 28.83 | 21.33 |
March | 0.894931E+10 | 11866.18 | 03-MAR-07:02 | 23.83 | 20.44 | 0.905863E+09 | 973.10 | 04-MAR-16:49 | 31.37 | 22.08 |
April | 0.831485E+10 | 11123.48 | 27-APR-05:02 | 26.00 | 23.87 | 0.856380E+09 | 973.07 | 15-APR-11:20 | 32.67 | 26.00 |
May | 0.851465E+10 | 11094.41 | 11-MAY-05:02 | 24.00 | 24.00 | 0.886606E+09 | 973.08 | 01-MAY-14:09 | 34.83 | 27.34 |
June | 0.854420E+10 | 11292.88 | 20-JUN-05:02 | 24.00 | 24.00 | 0.874332E+09 | 973.11 | 30-JUN-14:09 | 27.33 | 25.85 |
July | 0.782400E+10 | 11745.28 | 16-JUL-07:02 | 24.92 | 23.77 | 0.868655E+09 | 973.06 | 03-JUL-14:00 | 25.60 | 23.63 |
August | 0.784097E+10 | 11244.05 | 16-AUG-05:02 | 24.00 | 24.00 | 0.905872E+09 | 973.09 | 04-AUG-14:09 | 24.17 | 24.17 |
September | 0.791908E+10 | 11339.67 | 12-SEP-05:02 | 25.00 | 24.24 | 0.856384E+09 | 973.10 | 16-SEP-12:39 | 25.93 | 24.85 |
October | 0.790420E+10 | 11454.53 | 11-OCT-05:02 | 24.00 | 23.32 | 0.867339E+09 | 973.07 | 13-OCT-14:30 | 29.00 | 25.91 |
November | 0.851589E+10 | 12526.42 | 25-NOV-07:02 | 21.17 | 18.83 | 0.834486E+09 | 973.11 | 09-NOV-15:00 | 24.40 | 24.15 |
December | 0.930330E+10 | 12992.63 | 29-DEC-06:02 | 21.13 | 21.13 | 0.868645E+09 | 973.11 | 20-DEC-15:39 | 30.20 | 21.38 |
Annual Sum or Average | 0.101695E+12 | 0.103839E+11 | ||||||||
Minimum of Months | 0.782400E+10 | 11094.41 | 21.13 | 18.83 | 0.791987E+09 | 973.06 | 24.17 | 21.33 | ||
Maximum of Months | 0.944635E+10 | 14907.51 | 26.00 | 24.24 | 0.905872E+09 | 973.12 | 34.83 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12370501.65 | 1443.82 | 11-JAN-07:08 | 25.55 |
February | 16689377.12 | 1898.10 | 19-FEB-09:08 | 27.32 |
March | 25821272.92 | 2134.53 | 05-MAR-09:08 | 28.25 |
April | 22795856.33 | 1796.43 | 23-APR-08:08 | 26.67 |
May | 21598856.55 | 2262.96 | 07-MAY-07:20 | 29.93 |
June | 14695693.74 | 1971.87 | 25-JUN-08:08 | 27.33 |
July | 25121698.89 | 1896.71 | 30-JUL-08:08 | 27.67 |
August | 26278010.56 | 1814.58 | 20-AUG-08:08 | 26.33 |
September | 26310497.03 | 1803.43 | 17-SEP-08:08 | 26.32 |
October | 29180041.77 | 2181.47 | 08-OCT-08:08 | 28.25 |
November | 24354725.37 | 2186.26 | 11-NOV-09:08 | 28.23 |
December | 12852968.71 | 2205.73 | 10-DEC-09:08 | 28.20 |
Annual Sum or Average | 0.258070E+09 | |||
Minimum of Months | 12370501.65 | 1443.82 | 25.55 | |
Maximum of Months | 29180041.77 | 2262.96 | 29.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80250381.05 | 10625.25 | 11-JAN-07:20 | 26.40 |
February | 0.120102E+09 | 15305.66 | 20-FEB-09:08 | 28.23 |
March | 0.214612E+09 | 16384.55 | 26-MAR-08:08 | 29.33 |
April | 0.226905E+09 | 12682.85 | 07-APR-06:08 | 27.08 |
May | 0.169563E+09 | 21293.76 | 28-MAY-07:05 | 32.25 |
June | 0.131571E+09 | 12484.80 | 11-JUN-07:05 | 28.50 |
July | 0.237272E+09 | 14190.99 | 30-JUL-08:08 | 27.67 |
August | 0.189977E+09 | 11821.08 | 20-AUG-08:20 | 26.67 |
September | 0.194955E+09 | 11520.88 | 17-SEP-08:20 | 26.63 |
October | 0.204581E+09 | 10317.26 | 20-OCT-06:08 | 25.85 |
November | 0.177113E+09 | 16037.81 | 23-NOV-09:08 | 28.57 |
December | 83715618.76 | 15799.24 | 31-DEC-09:08 | 28.47 |
Annual Sum or Average | 0.203062E+10 | |||
Minimum of Months | 80250381.05 | 10317.26 | 25.85 | |
Maximum of Months | 0.237272E+09 | 21293.76 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3648367.68 | 916.54 | 03-JAN-07:06 | 25.27 |
February | 6021980.45 | 917.58 | 20-FEB-08:05 | 26.33 |
March | 10073229.26 | 1099.66 | 26-MAR-07:06 | 27.17 |
April | 11266801.92 | 1195.13 | 09-APR-07:05 | 27.78 |
May | 11052669.94 | 2074.72 | 28-MAY-07:07 | 32.25 |
June | 8916626.59 | 1167.61 | 18-JUN-07:07 | 28.00 |
July | 12504461.20 | 923.76 | 20-JUL-06:06 | 25.23 |
August | 10298742.01 | 1008.69 | 12-AUG-05:06 | 27.00 |
September | 11014203.93 | 890.05 | 30-SEP-05:05 | 26.08 |
October | 9415478.49 | 937.19 | 29-OCT-07:05 | 26.50 |
November | 8361455.05 | 1026.76 | 11-NOV-08:05 | 26.75 |
December | 2952930.68 | 961.19 | 10-DEC-08:05 | 26.33 |
Annual Sum or Average | 0.105527E+09 | |||
Minimum of Months | 2952930.68 | 890.05 | 25.23 | |
Maximum of Months | 12504461.20 | 2074.72 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1522122.53 | 371.72 | 13-JAN-06:04 | 24.48 |
February | 3327303.20 | 723.22 | 20-FEB-08:05 | 26.33 |
March | 9386162.03 | 827.93 | 04-MAR-07:06 | 24.83 |
April | 13082228.68 | 1071.31 | 30-APR-07:05 | 28.10 |
May | 9872573.16 | 1885.20 | 28-MAY-07:07 | 32.25 |
June | 8465230.47 | 1167.51 | 25-JUN-08:08 | 27.33 |
July | 8490476.72 | 774.06 | 09-JUL-07:04 | 26.50 |
August | 11117553.78 | 989.80 | 20-AUG-08:08 | 26.33 |
September | 10270307.04 | 966.01 | 17-SEP-08:08 | 26.32 |
October | 10060809.91 | 835.29 | 20-OCT-06:08 | 25.85 |
November | 4988427.78 | 825.35 | 11-NOV-08:05 | 26.75 |
December | 1362583.10 | 734.12 | 10-DEC-08:05 | 26.33 |
Annual Sum or Average | 91945778.40 | |||
Minimum of Months | 1362583.10 | 371.72 | 24.48 | |
Maximum of Months | 13082228.68 | 1885.20 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.186041E+10 | 1543.42 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.169252E+10 | 1543.42 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.193008E+10 | 1543.42 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.182131E+10 | 1543.42 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.189524E+10 | 1543.42 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.186250E+10 | 1543.42 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.185405E+10 | 1543.42 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.193008E+10 | 1543.42 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.182131E+10 | 1543.42 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.186041E+10 | 1543.42 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.179919E+10 | 1543.42 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.185405E+10 | 1543.42 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.221812E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.169252E+10 | 1543.42 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.193008E+10 | 1543.42 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.147010E+11 | 17024.17 | 02-JAN-16:30 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.130611E+11 | 17024.17 | 01-FEB-16:00 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.145977E+11 | 17024.17 | 01-MAR-16:00 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.135319E+11 | 17024.17 | 19-APR-16:00 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.140240E+11 | 17024.17 | 02-MAY-16:00 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.134318E+11 | 17024.17 | 01-JUN-16:00 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.136014E+11 | 17024.17 | 10-JUL-16:00 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.142029E+11 | 17024.17 | 04-AUG-16:00 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.135847E+11 | 17024.17 | 01-SEP-16:00 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.139698E+11 | 17024.17 | 02-OCT-16:49 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.142439E+11 | 17024.17 | 01-NOV-16:30 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.148845E+11 | 17024.17 | 01-DEC-16:30 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.167835E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.130611E+11 | 17024.17 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.148845E+11 | 17024.17 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.124902E+09 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.113644E+09 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.129631E+09 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.122307E+09 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.127266E+09 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.125090E+09 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.124483E+09 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.129631E+09 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.122307E+09 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.124902E+09 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.120779E+09 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.124483E+09 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148942E+10 | ||||
Minimum of Months | 0.113644E+09 | 104.63 | 0.00 | 0.00 | |
Maximum of Months | 0.129631E+09 | 104.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99968732.86 | 82435373.50 |
February | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131966E+09 | 25801063.15 |
March | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218799E+09 | 48300342.81 |
April | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217046E+09 | 8887221.40 |
May | 0.536353E+10 | 0.189524E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245807E+09 | 27163492.20 |
June | 0.528933E+10 | 0.186250E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212712E+09 | 34216208.51 |
July | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138186E+09 | 28543606.41 |
August | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166667E+09 | 43034493.76 |
September | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123531E+09 | 23928405.10 |
October | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101304E+09 | 35161949.69 |
November | 0.504819E+10 | 0.179919E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80684639.87 | 45150855.01 |
December | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77403532.01 | 94229282.06 |
Annual Sum or Average | 0.628175E+11 | 0.221812E+11 | 0.499918E+11 | 0.181407E+10 | 0.496852E+09 | ||||
Minimum of Months | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77403532.01 | 8887221.40 |
Maximum of Months | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245807E+09 | 94229282.06 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.147010E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83312794.41 | 62957965.50 |
February | 0.201852E+11 | 0.130611E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110565E+09 | 16760336.57 |
March | 0.230879E+11 | 0.145977E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186914E+09 | 31442480.04 |
April | 0.218263E+11 | 0.135319E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192099E+09 | 4533962.28 |
May | 0.225967E+11 | 0.140240E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220846E+09 | 15495827.18 |
June | 0.222841E+11 | 0.134318E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194769E+09 | 15534842.11 |
July | 0.221389E+11 | 0.136014E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118224E+09 | 14269807.08 |
August | 0.230879E+11 | 0.142029E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143230E+09 | 24782047.58 |
September | 0.218263E+11 | 0.135847E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105049E+09 | 14541153.53 |
October | 0.221054E+11 | 0.139698E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84436763.93 | 24315543.49 |
November | 0.212681E+11 | 0.142439E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67231854.48 | 32775852.63 |
December | 0.221389E+11 | 0.148845E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64060404.53 | 73661005.50 |
Annual Sum or Average | 0.264651E+12 | 0.167835E+12 | 0.842987E+11 | 0.157074E+10 | 0.331071E+09 | ||||
Minimum of Months | 0.201852E+11 | 0.130611E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64060404.53 | 4533962.28 |
Maximum of Months | 0.230879E+11 | 0.148845E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220846E+09 | 73661005.50 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41040845.85 | 53848768.98 |
February | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54241687.99 | 22624609.34 |
March | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88556135.44 | 40273013.52 |
April | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85962475.53 | 9713709.90 |
May | 0.212923E+10 | 0.195129E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100070E+09 | 16210153.21 |
June | 0.209978E+10 | 0.191792E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89483700.63 | 17995896.75 |
July | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58547381.90 | 15695214.19 |
August | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70275828.81 | 27280742.10 |
September | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51048029.97 | 16836345.56 |
October | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42239180.09 | 25329430.22 |
November | 0.200405E+10 | 0.185183E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33597829.06 | 31526615.52 |
December | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32465687.02 | 56492965.35 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.529224E+11 | 0.747529E+09 | 0.333827E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32465687.02 | 9713709.90 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100070E+09 | 56492965.35 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41740294.86 | 43422010.13 |
February | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55202238.54 | 15420811.73 |
March | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91964293.98 | 23871290.48 |
April | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94063281.40 | 3109295.48 |
May | 0.212923E+10 | 0.195129E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108589E+09 | 9679912.96 |
June | 0.209978E+10 | 0.191792E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95840494.38 | 10146506.06 |
July | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60395810.97 | 9852951.15 |
August | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72747361.88 | 15512815.62 |
September | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52934482.61 | 10243149.04 |
October | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43143699.30 | 17225899.11 |
November | 0.200405E+10 | 0.185183E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34119262.49 | 23522894.51 |
December | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32721522.68 | 47461082.48 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.794328E+10 | 0.783462E+09 | 0.229469E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32721522.68 | 3109295.48 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108589E+09 | 47461082.48 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73892537.52 | 0.129096E+09 |
February | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170484E+09 | 60981112.30 |
March | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349112E+09 | 31277306.99 |
April | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413721E+09 | 15394631.23 |
May | 0.00 | 0.127266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452219E+09 | 39994317.53 |
June | 0.00 | 0.125090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414827E+09 | 31865054.73 |
July | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214228E+09 | 72529110.35 |
August | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256672E+09 | 67760299.90 |
September | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214707E+09 | 65078308.58 |
October | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108423E+09 | 77636534.94 |
November | 0.00 | 0.120779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57460224.41 | 0.112311E+09 |
December | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38478276.21 | 0.139318E+09 |
Annual Sum or Average | 0.00 | 0.148942E+10 | 0.276422E+10 | 0.843242E+09 | |||||
Minimum of Months | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38478276.21 | 15394631.23 |
Maximum of Months | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452219E+09 | 0.139318E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 1543.42 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 351.88 | 08-JAN-19:03 | 1296.70 | 07-JAN-05:00 |
February | 5888.82 | 01-FEB-15:09 | 1543.42 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.71 | 20-FEB-19:03 | 151.13 | 20-FEB-07:00 |
March | 5888.82 | 01-MAR-15:09 | 1543.42 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 977.37 | 19-MAR-18:03 | 270.82 | 14-MAR-22:00 |
April | 5888.82 | 01-APR-10:09 | 1543.42 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 583.95 | 02-APR-18:03 | 126.06 | 13-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 1543.42 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 775.36 | 07-MAY-18:03 | 538.06 | 08-MAY-22:00 |
June | 5888.82 | 01-JUN-14:09 | 1543.42 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 717.71 | 11-JUN-18:03 | 607.50 | 20-JUN-23:00 |
July | 5888.82 | 01-JUL-10:09 | 1543.42 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 395.96 | 25-JUL-20:03 | 185.17 | 19-JUL-21:10 |
August | 5888.82 | 01-AUG-14:09 | 1543.42 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.61 | 01-AUG-20:03 | 329.53 | 04-AUG-03:00 |
September | 5888.82 | 01-SEP-14:09 | 1543.42 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.07 | 10-SEP-15:00 | 305.89 | 15-SEP-22:00 |
October | 5888.82 | 02-OCT-14:09 | 1543.42 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 492.48 | 08-OCT-18:03 | 175.53 | 23-OCT-05:00 |
November | 5888.82 | 01-NOV-14:09 | 1543.42 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 210.23 | 10-NOV-13:00 | 242.94 | 25-NOV-05:00 |
December | 5888.82 | 01-DEC-15:09 | 1543.42 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.04 | 09-DEC-14:00 | 452.46 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 210.23 | 126.06 | |||||
Maximum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 977.37 | 1296.70 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 17024.17 | 02-JAN-16:30 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.61 | 08-JAN-19:03 | 1112.52 | 07-JAN-05:00 |
February | 24809.68 | 01-FEB-15:09 | 17024.17 | 01-FEB-16:00 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 371.58 | 20-FEB-19:03 | 106.73 | 20-FEB-07:00 |
March | 24809.68 | 01-MAR-15:09 | 17024.17 | 01-MAR-16:00 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 809.28 | 19-MAR-18:03 | 205.01 | 03-MAR-05:30 |
April | 24809.68 | 01-APR-10:09 | 17024.17 | 19-APR-16:00 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 483.70 | 02-APR-18:03 | 88.01 | 22-APR-03:00 |
May | 24809.68 | 01-MAY-14:09 | 17024.17 | 02-MAY-16:00 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 644.76 | 07-MAY-18:03 | 383.24 | 08-MAY-22:00 |
June | 24809.68 | 01-JUN-14:09 | 17024.17 | 01-JUN-16:00 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 597.36 | 11-JUN-18:03 | 406.15 | 20-JUN-23:00 |
July | 24809.68 | 01-JUL-10:09 | 17024.17 | 10-JUL-16:00 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 329.56 | 25-JUL-20:03 | 127.77 | 19-JUL-20:20 |
August | 24809.68 | 01-AUG-14:09 | 17024.17 | 04-AUG-16:00 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 413.62 | 01-AUG-20:03 | 245.88 | 19-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 17024.17 | 01-SEP-16:00 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.08 | 10-SEP-15:00 | 257.39 | 15-SEP-22:00 |
October | 24809.68 | 02-OCT-14:09 | 17024.17 | 02-OCT-16:49 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 408.29 | 08-OCT-18:03 | 143.04 | 23-OCT-05:00 |
November | 24809.68 | 01-NOV-14:09 | 17024.17 | 01-NOV-16:30 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 172.08 | 10-NOV-13:00 | 195.50 | 25-NOV-05:00 |
December | 24809.68 | 01-DEC-15:09 | 17024.17 | 01-DEC-16:30 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.57 | 09-DEC-14:00 | 375.20 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 17024.17 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 172.08 | 88.01 | |||||
Maximum of Months | 24809.68 | 17024.17 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 809.28 | 1112.52 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.43 | 08-JAN-19:03 | 717.02 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.81 | 20-FEB-19:03 | 87.86 | 20-FEB-07:00 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 414.28 | 19-MAR-18:03 | 150.24 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 249.05 | 02-APR-18:03 | 67.01 | 13-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 332.76 | 07-MAY-18:03 | 262.77 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 308.94 | 11-JUN-18:03 | 295.67 | 20-JUN-23:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.01 | 25-JUL-20:03 | 91.49 | 19-JUL-20:20 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.94 | 01-AUG-20:03 | 174.84 | 04-AUG-03:00 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 10-SEP-15:00 | 165.08 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 207.24 | 08-OCT-18:03 | 98.86 | 23-OCT-22:40 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 | 10-NOV-13:00 | 120.49 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.19 | 09-DEC-14:00 | 221.59 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 | 67.01 | |||||
Maximum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 414.28 | 717.02 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 149.08 | 08-JAN-19:03 | 629.03 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.54 | 20-FEB-19:03 | 70.65 | 20-FEB-07:00 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 418.00 | 19-MAR-18:03 | 122.51 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 251.27 | 02-APR-18:03 | 49.54 | 13-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 335.23 | 07-MAY-18:03 | 219.54 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 311.00 | 11-JUN-18:03 | 240.24 | 20-JUN-23:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.32 | 25-JUL-20:03 | 75.62 | 19-JUL-20:20 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 214.74 | 01-AUG-20:03 | 124.42 | 04-AUG-03:00 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 10-SEP-15:00 | 129.52 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 209.62 | 08-OCT-18:03 | 78.78 | 01-OCT-23:00 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 | 10-NOV-13:00 | 109.56 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.19 | 09-DEC-14:00 | 202.33 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 91.10 | 49.54 | |||||
Maximum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 418.00 | 629.03 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.45 | 04-JAN-12:03 | 1531.31 | 24-JAN-08:61 |
February | 0.00 | 01-FEB-00:10 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1175.52 | 26-FEB-12:02 | 1048.32 | 21-FEB-09:53 |
March | 0.00 | 01-MAR-00:10 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2436.42 | 19-MAR-11:02 | 993.34 | 14-MAR-11:03 |
April | 0.00 | 01-APR-00:10 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1859.86 | 09-APR-11:02 | 1192.01 | 14-APR-15:53 |
May | 0.00 | 01-MAY-00:10 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2972.99 | 05-MAY-11:01 | 1872.97 | 21-MAY-12:52 |
June | 0.00 | 01-JUN-00:10 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.35 | 16-JUN-11:02 | 1609.53 | 30-JUN-12:53 |
July | 0.00 | 01-JUL-00:10 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.30 | 01-JUL-11:02 | 1359.14 | 03-JUL-12:53 |
August | 0.00 | 01-AUG-00:10 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.39 | 16-AUG-11:02 | 1834.80 | 20-AUG-11:02 |
September | 0.00 | 01-SEP-00:10 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.39 | 30-SEP-11:02 | 1577.57 | 15-SEP-16:53 |
October | 0.00 | 01-OCT-00:10 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.25 | 27-OCT-11:03 | 840.36 | 11-OCT-12:53 |
November | 0.00 | 01-NOV-00:10 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 812.98 | 18-NOV-12:55 | 1056.81 | 25-NOV-08:61 |
December | 0.00 | 01-DEC-00:10 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.82 | 11-DEC-12:05 | 1180.98 | 21-DEC-08:61 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.82 | 840.36 | ||||
Maximum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2972.99 | 1872.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27701.67 | 24-JAN-07:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.86 |
February | 30711.12 | 23-FEB-06:02 | 0.00 | 590.26 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 |
March | 25339.42 | 03-MAR-07:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 |
April | 24569.72 | 27-APR-05:02 | 0.00 | 590.26 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
May | 25415.81 | 11-MAY-05:02 | 0.00 | 491.89 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.78 |
June | 26139.76 | 20-JUN-05:02 | 0.00 | 590.26 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 |
July | 27902.49 | 11-JUL-05:02 | 0.00 | 491.89 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25650.03 | 16-AUG-05:02 | 0.00 | 491.89 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 |
September | 25437.07 | 12-SEP-05:02 | 0.00 | 590.26 | 3678.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 |
October | 24921.06 | 11-OCT-05:02 | 0.00 | 491.89 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
November | 26019.53 | 25-NOV-07:02 | 3680.51 | 857.46 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.75 |
December | 26824.69 | 21-DEC-07:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24569.72 | 0.00 | 491.89 | 3065.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30711.12 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 111835.37 | 23-JAN-07:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 |
February | 119683.39 | 23-FEB-06:02 | 0.00 | 5674.72 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 |
March | 107120.79 | 14-MAR-05:02 | 0.00 | 5674.72 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
April | 102475.59 | 27-APR-05:02 | 0.00 | 5674.72 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
May | 97301.96 | 31-MAY-05:02 | 0.00 | 5674.72 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
June | 98366.96 | 20-JUN-05:02 | 0.00 | 5674.72 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 |
July | 103232.96 | 31-JUL-05:02 | 0.00 | 5674.72 | 6203.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 |
August | 96806.71 | 24-AUG-05:02 | 0.00 | 4728.94 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97415.84 | 13-SEP-05:02 | 0.00 | 4728.94 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 |
October | 96550.54 | 10-OCT-05:02 | 0.00 | 4728.94 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 |
November | 106495.82 | 25-NOV-07:02 | 15506.05 | 7881.56 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 |
December | 104632.95 | 27-DEC-07:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 96550.54 | 0.00 | 4728.94 | 5169.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 119683.39 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18125.51 | 18-JAN-06:02 | 0.00 | 445.60 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 |
February | 19276.74 | 23-FEB-06:02 | 0.00 | 534.72 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 |
March | 15788.91 | 03-MAR-06:03 | 0.00 | 356.48 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 |
April | 14606.83 | 27-APR-05:02 | 0.00 | 534.72 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 |
May | 14828.80 | 11-MAY-05:02 | 0.00 | 445.60 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 |
June | 14903.24 | 20-JUN-05:02 | 0.00 | 534.72 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
July | 16102.30 | 11-JUL-05:02 | 0.00 | 445.60 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14927.78 | 16-AUG-05:02 | 0.00 | 445.60 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 |
September | 15170.59 | 12-SEP-05:02 | 0.00 | 534.72 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
October | 15227.11 | 11-OCT-05:02 | 0.00 | 445.60 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
November | 15994.14 | 24-NOV-06:02 | 0.00 | 534.72 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 |
December | 16846.68 | 07-DEC-06:02 | 0.00 | 445.60 | 3245.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14606.83 | 0.00 | 356.48 | 2596.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19276.74 | 0.00 | 534.72 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13514.59 | 16-JAN-08:61 | 0.00 | 623.84 | 511.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
February | 14907.51 | 23-FEB-06:02 | 0.00 | 534.72 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 |
March | 11866.18 | 03-MAR-07:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 |
April | 11123.48 | 27-APR-05:02 | 0.00 | 534.72 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
May | 11094.41 | 11-MAY-05:02 | 0.00 | 445.60 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 |
June | 11292.88 | 20-JUN-05:02 | 0.00 | 534.72 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 |
July | 11745.28 | 16-JUL-07:02 | 0.00 | 445.60 | 365.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 11244.05 | 16-AUG-05:02 | 0.00 | 445.60 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
September | 11339.67 | 12-SEP-05:02 | 0.00 | 534.72 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 |
October | 11454.53 | 11-OCT-05:02 | 0.00 | 445.60 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
November | 12526.42 | 25-NOV-07:02 | 1461.10 | 891.19 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 |
December | 12992.63 | 29-DEC-06:02 | 0.00 | 445.60 | 487.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11094.41 | 0.00 | 445.60 | 365.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | |
Maximum of Months | 14907.51 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.71 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 7.71 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.102344E+12 | 84293.35 | 04-JAN-15:00 | 0.710399E+10 | 4788.73 | 11-JAN-12:30 |
February | 0.969126E+11 | 88896.93 | 13-FEB-15:39 | 0.641882E+10 | 4787.79 | 01-FEB-12:09 |
March | 0.113476E+12 | 91579.73 | 28-MAR-14:00 | 0.711987E+10 | 4782.83 | 01-MAR-12:09 |
April | 0.116012E+12 | 96676.53 | 01-APR-15:30 | 0.682596E+10 | 4774.51 | 03-APR-11:00 |
May | 0.124494E+12 | 104681.60 | 06-MAY-15:09 | 0.701955E+10 | 4765.96 | 02-MAY-11:39 |
June | 0.123987E+12 | 105445.31 | 13-JUN-14:00 | 0.678810E+10 | 4758.36 | 01-JUN-11:00 |
July | 0.107657E+12 | 88754.42 | 15-JUL-15:39 | 0.696090E+10 | 4754.62 | 28-JUL-11:09 |
August | 0.118262E+12 | 96140.49 | 11-AUG-14:09 | 0.702532E+10 | 4759.29 | 29-AUG-11:39 |
September | 0.111887E+12 | 96768.47 | 30-SEP-10:00 | 0.679609E+10 | 4766.92 | 28-SEP-11:50 |
October | 0.108860E+12 | 89537.74 | 16-OCT-14:50 | 0.703779E+10 | 4776.58 | 31-OCT-11:20 |
November | 0.103456E+12 | 87447.34 | 14-NOV-16:19 | 0.683694E+10 | 4784.00 | 29-NOV-12:00 |
December | 0.102738E+12 | 85684.33 | 30-DEC-16:10 | 0.709957E+10 | 4788.19 | 28-DEC-12:20 |
Annual Sum or Average | 0.133009E+13 | 0.830329E+11 | ||||
Minimum of Months | 0.969126E+11 | 84293.35 | 0.641882E+10 | 4754.62 | ||
Maximum of Months | 0.124494E+12 | 105445.31 | 0.711987E+10 | 4788.73 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.205164E+11 | 0.384230E+10 | 0.164409E+11 | 0.00 | 0.113470E+11 | 0.00 | 0.00 | 0.501972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183521E+11 | 0.340539E+10 | 0.149157E+11 | 0.00 | 0.107938E+11 | 0.00 | 0.00 | 0.494455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206325E+11 | 0.363089E+10 | 0.168545E+11 | 0.00 | 0.126462E+11 | 0.00 | 0.00 | 0.597119E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192261E+11 | 0.341281E+10 | 0.160165E+11 | 0.00 | 0.133222E+11 | 0.00 | 0.00 | 0.640347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199491E+11 | 0.345307E+10 | 0.166477E+11 | 0.00 | 0.146017E+11 | 0.00 | 0.00 | 0.698429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.192552E+11 | 0.329427E+10 | 0.162772E+11 | 0.00 | 0.148093E+11 | 0.00 | 0.00 | 0.703513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193971E+11 | 0.343727E+10 | 0.163871E+11 | 0.00 | 0.121260E+11 | 0.00 | 0.00 | 0.563095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202377E+11 | 0.349061E+10 | 0.168545E+11 | 0.00 | 0.137901E+11 | 0.00 | 0.00 | 0.638891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192788E+11 | 0.348394E+10 | 0.160165E+11 | 0.00 | 0.129327E+11 | 0.00 | 0.00 | 0.601751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197852E+11 | 0.371387E+10 | 0.164409E+11 | 0.00 | 0.123429E+11 | 0.00 | 0.00 | 0.565768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198676E+11 | 0.370091E+10 | 0.159174E+11 | 0.00 | 0.115018E+11 | 0.00 | 0.00 | 0.524685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206803E+11 | 0.387262E+10 | 0.163871E+11 | 0.00 | 0.113676E+11 | 0.00 | 0.00 | 0.504303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237178E+12 | 0.427380E+11 | 0.195156E+12 | 0.151581E+12 | 0.00 | 0.703433E+12 | |||||||
Minimum of Months | 0.183521E+11 | 0.329427E+10 | 0.149157E+11 | 0.00 | 0.107938E+11 | 0.00 | 0.00 | 0.494455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206803E+11 | 0.387262E+10 | 0.168545E+11 | 0.00 | 0.148093E+11 | 0.00 | 0.00 | 0.703513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.710399E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.641882E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.711987E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.682596E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.701955E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.678810E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.696090E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.702532E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.679609E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.703779E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.683694E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.709957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.830329E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.641882E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.711987E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21880.52 | 02-JAN-16:30 | 3292.90 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 11778.28 | 10-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 21880.52 | 01-FEB-16:00 | 3292.90 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 12292.01 | 16-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 21880.52 | 01-MAR-16:00 | 3292.90 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 12458.13 | 26-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 21880.52 | 19-APR-16:00 | 3292.90 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 13203.76 | 30-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 21880.52 | 02-MAY-16:00 | 3292.90 | 01-MAY-05:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 14455.26 | 28-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 21880.52 | 01-JUN-16:00 | 3292.90 | 01-JUN-05:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 14605.03 | 11-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 21880.52 | 10-JUL-16:00 | 3292.90 | 01-JUL-05:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 12338.26 | 02-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 21880.52 | 04-AUG-16:00 | 3292.90 | 01-AUG-05:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 14428.52 | 13-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 21880.52 | 01-SEP-16:00 | 3292.90 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 13890.41 | 03-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21880.52 | 02-OCT-16:49 | 3292.90 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 12437.90 | 29-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 21880.52 | 01-NOV-16:30 | 3292.90 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 12432.14 | 11-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 21880.52 | 01-DEC-16:30 | 3292.90 | 01-DEC-17:30 | 10771.04 | 01-DEC-09:09 | 0.00 | 12422.55 | 10-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 21880.52 | 3292.90 | 10771.04 | 0.00 | 11778.28 | 0.00 | 0.00 | |||||
Maximum of Months | 21880.52 | 3292.90 | 10771.04 | 0.00 | 14605.03 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 46897.99 | 12-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51169.05 | 15-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54091.36 | 28-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 58638.52 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63896.07 | 06-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65137.54 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 50896.19 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 61305.58 | 13-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59912.26 | 30-SEP-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52743.37 | 29-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 51662.40 | 11-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52242.78 | 10-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 46897.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65137.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 84293.35 | 04-JAN-15:00 | 19043.16 | 10771.04 | 0.00 | 0.00 | 8964.40 | 0.00 | 0.00 | 45514.76 | 0.00 |
February | 88896.93 | 13-FEB-15:39 | 17624.48 | 10771.04 | 0.00 | 0.00 | 9979.86 | 0.00 | 0.00 | 50521.57 | 0.00 |
March | 91579.73 | 28-MAR-14:00 | 16205.80 | 10771.04 | 0.00 | 0.00 | 10667.02 | 0.00 | 0.00 | 53935.88 | 0.00 |
April | 96676.53 | 01-APR-15:30 | 17624.48 | 10771.04 | 0.00 | 0.00 | 11485.57 | 0.00 | 0.00 | 56795.45 | 0.00 |
May | 104681.60 | 06-MAY-15:09 | 17624.48 | 10771.04 | 0.00 | 0.00 | 12770.68 | 0.00 | 0.00 | 63515.40 | 0.00 |
June | 105445.31 | 13-JUN-14:00 | 16205.80 | 10771.04 | 0.00 | 0.00 | 13330.94 | 0.00 | 0.00 | 65137.54 | 0.00 |
July | 88754.42 | 15-JUL-15:39 | 17624.48 | 10771.04 | 0.00 | 0.00 | 10045.17 | 0.00 | 0.00 | 50313.74 | 0.00 |
August | 96140.49 | 11-AUG-14:09 | 14787.11 | 10771.04 | 0.00 | 0.00 | 12221.69 | 0.00 | 0.00 | 58360.65 | 0.00 |
September | 96768.47 | 30-SEP-10:00 | 13368.43 | 10771.04 | 0.00 | 0.00 | 12716.74 | 0.00 | 0.00 | 59912.26 | 0.00 |
October | 89537.74 | 16-OCT-14:50 | 16205.80 | 10771.04 | 0.00 | 0.00 | 10719.14 | 0.00 | 0.00 | 51841.76 | 0.00 |
November | 87447.34 | 14-NOV-16:19 | 21880.52 | 10771.04 | 0.00 | 0.00 | 9301.96 | 0.00 | 0.00 | 45493.82 | 0.00 |
December | 85684.33 | 30-DEC-16:10 | 20461.84 | 10771.04 | 0.00 | 0.00 | 9155.40 | 0.00 | 0.00 | 45296.05 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 84293.35 | 13368.43 | 10771.04 | 0.00 | 0.00 | 8964.40 | 0.00 | 0.00 | 45296.05 | 0.00 | |
Maximum of Months | 105445.31 | 21880.52 | 10771.04 | 0.00 | 0.00 | 13330.94 | 0.00 | 0.00 | 65137.54 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 4788.73 | 11-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 4787.79 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4782.83 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4774.51 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4765.96 | 02-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4758.36 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4754.62 | 28-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4759.29 | 29-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4766.92 | 28-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4776.58 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4784.00 | 29-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 4788.19 | 28-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4754.62 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4788.73 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.78 | 2.50 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.25 | 2.00 | 24.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.49 | 0.33 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 25.01 | 4.83 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 25.25 | 2.50 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 23.98 | 414.00 | 23.89 | 14.67 | 23.98 |
February | 7.67 | 24.01 | 376.00 | 23.89 | 7.67 | 24.01 |
March | 21.50 | 23.98 | 422.00 | 23.89 | 21.50 | 23.98 |
April | 28.67 | 23.98 | 405.00 | 23.90 | 28.67 | 23.98 |
May | 44.83 | 23.96 | 418.00 | 23.90 | 44.83 | 23.96 |
June | 28.17 | 24.00 | 408.00 | 23.90 | 28.17 | 24.00 |
July | 12.33 | 24.03 | 415.00 | 23.89 | 12.33 | 24.03 |
August | 51.50 | 23.94 | 422.00 | 23.90 | 51.50 | 23.94 |
September | 34.00 | 23.96 | 405.00 | 23.89 | 34.00 | 23.96 |
October | 47.17 | 23.93 | 414.00 | 23.89 | 47.17 | 23.93 |
November | 26.00 | 23.96 | 399.00 | 23.89 | 26.00 | 23.96 |
December | 18.67 | 23.97 | 415.00 | 23.89 | 18.67 | 23.97 |
Annual Sum or Average | 335.17 | 23.97 | 4913.00 | 23.89 | 335.17 | 23.97 |
Minimum of Months | 7.67 | 23.93 | 376.00 | 23.89 | 7.67 | 23.93 |
Maximum of Months | 51.50 | 24.03 | 422.00 | 23.90 | 51.50 | 24.03 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.67 | 23.93 | 414.00 | 23.89 | 32.67 | 23.93 |
February | 21.17 | 23.95 | 376.00 | 23.89 | 21.17 | 23.95 |
March | 33.83 | 23.94 | 422.00 | 23.89 | 33.83 | 23.94 |
April | 71.00 | 23.92 | 405.00 | 23.89 | 71.00 | 23.92 |
May | 179.33 | 23.91 | 418.00 | 23.90 | 179.33 | 23.91 |
June | 141.67 | 23.91 | 408.00 | 23.90 | 141.67 | 23.91 |
July | 74.83 | 23.92 | 415.00 | 23.89 | 74.83 | 23.92 |
August | 202.33 | 23.90 | 422.00 | 23.90 | 202.33 | 23.90 |
September | 151.50 | 23.90 | 405.00 | 23.90 | 151.50 | 23.90 |
October | 168.17 | 23.90 | 414.00 | 23.89 | 168.17 | 23.90 |
November | 90.33 | 23.91 | 399.00 | 23.89 | 90.33 | 23.91 |
December | 56.33 | 23.91 | 415.00 | 23.89 | 56.33 | 23.91 |
Annual Sum or Average | 1223.17 | 23.91 | 4913.00 | 23.89 | 1223.17 | 23.91 |
Minimum of Months | 21.17 | 23.90 | 376.00 | 23.89 | 21.17 | 23.90 |
Maximum of Months | 202.33 | 23.95 | 422.00 | 23.90 | 202.33 | 23.95 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 24.00 | 414.00 | 23.89 | 5.67 | 24.00 |
February | 3.50 | 24.01 | 376.00 | 23.89 | 3.50 | 24.01 |
March | 13.50 | 23.99 | 422.00 | 23.89 | 13.50 | 23.99 |
April | 22.50 | 23.96 | 405.00 | 23.89 | 22.50 | 23.96 |
May | 36.83 | 23.94 | 418.00 | 23.89 | 36.83 | 23.94 |
June | 29.33 | 23.96 | 408.00 | 23.89 | 29.33 | 23.96 |
July | 16.67 | 23.97 | 415.00 | 23.89 | 16.67 | 23.97 |
August | 39.17 | 23.94 | 422.00 | 23.89 | 39.17 | 23.94 |
September | 27.67 | 23.95 | 405.00 | 23.89 | 27.67 | 23.95 |
October | 30.17 | 23.94 | 414.00 | 23.89 | 30.17 | 23.94 |
November | 12.33 | 23.99 | 399.00 | 23.89 | 12.33 | 23.99 |
December | 6.83 | 24.01 | 415.00 | 23.89 | 6.83 | 24.01 |
Annual Sum or Average | 244.17 | 23.96 | 4913.00 | 23.89 | 244.17 | 23.96 |
Minimum of Months | 3.50 | 23.94 | 376.00 | 23.89 | 3.50 | 23.94 |
Maximum of Months | 39.17 | 24.01 | 422.00 | 23.89 | 39.17 | 24.01 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 23.98 | 414.00 | 23.89 | 12.67 | 23.98 |
February | 8.50 | 24.02 | 376.00 | 23.89 | 8.50 | 24.02 |
March | 24.50 | 23.96 | 422.00 | 23.89 | 24.50 | 23.96 |
April | 36.17 | 23.94 | 405.00 | 23.89 | 36.17 | 23.94 |
May | 64.83 | 23.93 | 418.00 | 23.90 | 64.83 | 23.93 |
June | 51.83 | 23.94 | 408.00 | 23.90 | 51.83 | 23.94 |
July | 36.67 | 23.94 | 415.00 | 23.89 | 36.67 | 23.94 |
August | 83.83 | 23.92 | 422.00 | 23.89 | 83.83 | 23.92 |
September | 52.00 | 23.93 | 405.00 | 23.89 | 52.00 | 23.93 |
October | 57.50 | 23.92 | 414.00 | 23.89 | 57.50 | 23.92 |
November | 23.83 | 23.96 | 399.00 | 23.89 | 23.83 | 23.96 |
December | 15.83 | 23.98 | 415.00 | 23.89 | 15.83 | 23.98 |
Annual Sum or Average | 468.17 | 23.94 | 4913.00 | 23.89 | 468.17 | 23.94 |
Minimum of Months | 8.50 | 23.92 | 376.00 | 23.89 | 8.50 | 23.92 |
Maximum of Months | 83.83 | 24.02 | 422.00 | 23.90 | 83.83 | 24.02 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.91424 | 54.75812 | 0.54755 | 11.31944 |
February | 376.00000 | 23.91498 | 54.36797 | 0.56064 | 11.62242 |
March | 422.00000 | 23.91527 | 55.16777 | 0.57761 | 12.04544 |
April | 405.00000 | 23.91649 | 56.99488 | 0.60367 | 12.69612 |
May | 418.00000 | 23.91839 | 58.86439 | -0.2278 | 6.18560 |
June | 408.00000 | 23.91800 | 57.77510 | -0.2089 | 6.01297 |
July | 415.00000 | 23.91562 | 55.56597 | -0.2637 | 6.51390 |
August | 422.00000 | 23.91674 | 59.86348 | -0.2527 | 6.43268 |
September | 405.00000 | 23.91603 | 58.94175 | -0.2600 | 6.48772 |
October | 414.00000 | 23.91576 | 59.77740 | 0.58208 | 12.14768 |
November | 399.00000 | 23.91560 | 57.70135 | 0.56999 | 11.85108 |
December | 415.00000 | 23.91427 | 56.09336 | 0.55105 | 11.39913 |
Annual Sum or Average | 4913.00000 | 23.91596 | 57.17415 | 0.22818 | 9.53674 |
Minimum of Months | 376.00000 | 23.91424 | 54.36797 | -0.2637 | 6.01297 |
Maximum of Months | 422.00000 | 23.91839 | 59.86348 | 0.60367 | 12.69612 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.91167 | 57.63460 | 0.59154 | 12.37423 |
February | 376.00000 | 23.91415 | 57.44776 | 0.60543 | 12.72774 |
March | 422.00000 | 23.91488 | 57.88198 | 0.62117 | 13.14127 |
April | 405.00000 | 23.91602 | 61.06400 | 0.64909 | 13.88896 |
May | 418.00000 | 23.91773 | 64.29867 | -0.1880 | 5.81330 |
June | 408.00000 | 23.91734 | 64.02364 | -0.1776 | 5.73480 |
July | 415.00000 | 23.91536 | 61.33573 | -0.2271 | 6.13171 |
August | 422.00000 | 23.91634 | 65.15173 | -0.2035 | 5.94381 |
September | 405.00000 | 23.91619 | 64.23422 | -0.2045 | 5.94242 |
October | 414.00000 | 23.91569 | 64.57103 | 0.63459 | 13.49306 |
November | 399.00000 | 23.91497 | 62.03235 | 0.62018 | 13.10988 |
December | 415.00000 | 23.91180 | 59.49123 | 0.59796 | 12.53685 |
Annual Sum or Average | 4913.00000 | 23.91518 | 61.62265 | 0.27314 | 10.04037 |
Minimum of Months | 376.00000 | 23.91167 | 57.44776 | -0.2271 | 5.73480 |
Maximum of Months | 422.00000 | 23.91773 | 65.15173 | 0.64909 | 13.88896 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.91350 | 49.30547 | 0.64424 | 13.77512 |
February | 376.00000 | 23.91336 | 49.80104 | 0.64866 | 13.89060 |
March | 422.00000 | 23.91362 | 51.68645 | 0.64257 | 13.72649 |
April | 405.00000 | 23.91436 | 54.82582 | 0.65600 | 14.09129 |
May | 418.00000 | 23.91525 | 57.19308 | -0.1561 | 5.61051 |
June | 408.00000 | 23.91489 | 57.05977 | -0.1484 | 5.55953 |
July | 415.00000 | 23.91394 | 54.22951 | -0.1981 | 5.89122 |
August | 422.00000 | 23.91445 | 57.86321 | -0.1802 | 5.78337 |
September | 405.00000 | 23.91439 | 56.43679 | -0.1728 | 5.71949 |
October | 414.00000 | 23.91441 | 55.95019 | 0.64791 | 13.87243 |
November | 399.00000 | 23.91427 | 52.85501 | 0.65189 | 13.98611 |
December | 415.00000 | 23.91353 | 50.40043 | 0.64687 | 13.84947 |
Annual Sum or Average | 4913.00000 | 23.91417 | 53.99756 | 0.30332 | 10.44409 |
Minimum of Months | 376.00000 | 23.91336 | 49.30547 | -0.1981 | 5.55953 |
Maximum of Months | 422.00000 | 23.91525 | 57.86321 | 0.65600 | 14.09129 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.91372 | 51.05347 | 0.62118 | 13.15502 |
February | 376.00000 | 23.91414 | 51.49669 | 0.62552 | 13.26497 |
March | 422.00000 | 23.91431 | 53.82256 | 0.62101 | 13.15035 |
April | 405.00000 | 23.91531 | 57.29842 | 0.63758 | 13.58805 |
May | 418.00000 | 23.91699 | 59.98161 | -0.1863 | 5.82548 |
June | 408.00000 | 23.91650 | 59.69404 | -0.1790 | 5.76798 |
July | 415.00000 | 23.91493 | 57.08327 | -0.2284 | 6.15857 |
August | 422.00000 | 23.91564 | 61.19740 | -0.2075 | 5.99903 |
September | 405.00000 | 23.91537 | 59.39276 | -0.2021 | 5.94308 |
October | 414.00000 | 23.91508 | 59.08363 | 0.63338 | 13.47576 |
November | 399.00000 | 23.91493 | 55.21829 | 0.63291 | 13.46697 |
December | 415.00000 | 23.91404 | 52.33572 | 0.62527 | 13.26529 |
Annual Sum or Average | 4913.00000 | 23.91509 | 56.50851 | 0.27922 | 10.22319 |
Minimum of Months | 376.00000 | 23.91372 | 51.05347 | -0.2284 | 5.76798 |
Maximum of Months | 422.00000 | 23.91699 | 61.19740 | 0.63758 | 13.58805 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.271808E+11 | 0.673830E+10 | 429.84 | 0.187454E+11 | 0.843537E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:10 | 45437.01 | 09-JAN-06:02 | 29914.26 | 24-JAN-07:02 | 21860.03 | 09-JAN-07:04 | 9777.78 | 11-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.267454E+11 | 0.666769E+10 | 394.96 | 0.186113E+11 | 0.813408E+10 | 0.00 | 1.00 | 01-FEB-06:02 | 0.00 | 01-FEB-00:10 | 45319.58 | 20-FEB-08:62 | 33428.58 | 23-FEB-06:02 | 20483.25 | 16-FEB-07:06 | 10069.21 | 20-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.326410E+11 | 0.815943E+10 | 444.58 | 0.224195E+11 | 0.102215E+11 | 0.00 | 1.00 | 01-MAR-06:02 | 0.00 | 01-MAR-00:10 | 46132.13 | 27-MAR-05:02 | 28846.57 | 04-MAR-07:02 | 22553.10 | 27-MAR-05:03 | 10237.53 | 26-MAR-08:15 | 0.00 | 01-MAR-00:10 |
April | 0.353651E+11 | 0.875111E+10 | 430.15 | 0.230207E+11 | 0.123444E+11 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 46611.93 | 03-APR-05:02 | 28049.81 | 28-APR-05:02 | 23851.71 | 03-APR-05:05 | 10224.70 | 30-APR-08:15 | 0.00 | 01-APR-00:10 |
May | 0.396622E+11 | 0.972007E+10 | 443.54 | 0.245115E+11 | 0.151507E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 46748.68 | 20-MAY-05:02 | 28566.36 | 11-MAY-05:02 | 27984.06 | 22-MAY-05:03 | 10501.40 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.409248E+11 | 0.100262E+11 | 433.71 | 0.256034E+11 | 0.153214E+11 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 46739.51 | 12-JUN-05:02 | 28966.32 | 20-JUN-05:02 | 26839.20 | 10-JUN-05:07 | 10325.78 | 18-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.336079E+11 | 0.810499E+10 | 437.69 | 0.220845E+11 | 0.115234E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 45319.21 | 01-JUL-06:02 | 31180.05 | 11-JUL-05:02 | 21815.35 | 01-JUL-06:04 | 9992.19 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.366494E+11 | 0.876472E+10 | 445.48 | 0.219519E+11 | 0.146975E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 46665.03 | 12-AUG-05:02 | 28782.64 | 16-AUG-05:02 | 25408.26 | 13-AUG-07:04 | 10242.55 | 27-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.338902E+11 | 0.813959E+10 | 427.09 | 0.207750E+11 | 0.131153E+11 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 46002.54 | 25-SEP-05:02 | 28685.70 | 12-SEP-05:02 | 23244.33 | 25-SEP-06:06 | 10161.28 | 10-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.314936E+11 | 0.751899E+10 | 435.47 | 0.190243E+11 | 0.124694E+11 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 45904.21 | 30-OCT-05:02 | 28232.47 | 08-OCT-07:02 | 23271.68 | 14-OCT-06:04 | 10119.39 | 29-OCT-08:15 | 0.00 | 01-OCT-00:10 |
November | 0.289252E+11 | 0.697699E+10 | 418.57 | 0.183358E+11 | 0.105894E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 45316.07 | 12-NOV-09:02 | 29024.81 | 07-NOV-06:02 | 21926.11 | 12-NOV-09:06 | 10096.94 | 23-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.273194E+11 | 0.670213E+10 | 429.44 | 0.182248E+11 | 0.909461E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 45371.53 | 11-DEC-06:02 | 28896.43 | 21-DEC-07:02 | 21713.20 | 11-DEC-07:06 | 10085.39 | 31-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.394405E+12 | 0.962702E+11 | 5170.51 | 0.253308E+12 | 0.141097E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.267454E+11 | 0.666769E+10 | 394.96 | 0.182248E+11 | 0.813408E+10 | 0.00 | 1.00 | 0.00 | 45316.07 | 28049.81 | 20483.25 | 9777.78 | 0.00 | |||||||
Maximum of Months | 0.409248E+11 | 0.100262E+11 | 445.48 | 0.256034E+11 | 0.153214E+11 | 0.00 | 1.00 | 0.00 | 46748.68 | 33428.58 | 27984.06 | 10501.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.128968E+12 | 0.341052E+11 | 421.10 | 0.790289E+11 | 0.499389E+11 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:10 | 201908.55 | 10-JAN-07:02 | 123834.09 | 16-JAN-09:02 | 104381.25 | 10-JAN-07:02 | 47496.14 | 11-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.127532E+12 | 0.338885E+11 | 386.62 | 0.787212E+11 | 0.488108E+11 | 0.00 | 1.00 | 01-FEB-06:02 | 0.00 | 01-FEB-00:10 | 202272.77 | 16-FEB-07:02 | 130314.99 | 25-FEB-06:02 | 104391.74 | 16-FEB-07:06 | 48874.57 | 20-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.155801E+12 | 0.415218E+11 | 442.14 | 0.956468E+11 | 0.601540E+11 | 0.00 | 1.00 | 01-MAR-06:02 | 0.00 | 01-MAR-00:10 | 202159.88 | 25-MAR-06:02 | 122293.40 | 14-MAR-05:02 | 104428.17 | 25-MAR-06:06 | 49509.34 | 26-MAR-08:04 | 0.00 | 01-MAR-00:10 |
April | 0.171995E+12 | 0.449743E+11 | 428.16 | 0.969409E+11 | 0.750545E+11 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 202851.23 | 15-APR-06:02 | 119728.38 | 27-APR-05:02 | 105711.47 | 15-APR-06:02 | 49586.21 | 30-APR-08:15 | 0.00 | 01-APR-00:10 |
May | 0.189935E+12 | 0.488556E+11 | 441.67 | 0.985789E+11 | 0.913564E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 206579.57 | 23-MAY-06:02 | 112132.33 | 07-MAY-07:01 | 124040.92 | 22-MAY-06:06 | 51035.11 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.191103E+12 | 0.490916E+11 | 431.10 | 0.988193E+11 | 0.922833E+11 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 206449.28 | 29-JUN-06:02 | 110953.42 | 20-JUN-05:02 | 118208.57 | 29-JUN-06:02 | 50029.27 | 18-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.152222E+12 | 0.390208E+11 | 432.16 | 0.837146E+11 | 0.685077E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 203254.45 | 01-JUL-06:02 | 118090.36 | 03-JUL-05:02 | 107894.28 | 01-JUL-06:02 | 48566.40 | 09-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.178300E+12 | 0.448511E+11 | 442.74 | 0.885277E+11 | 0.897725E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 206329.22 | 12-AUG-06:02 | 110840.76 | 24-AUG-05:02 | 116889.69 | 12-AUG-06:02 | 49530.19 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.166864E+12 | 0.421700E+11 | 425.05 | 0.851491E+11 | 0.817150E+11 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 205780.63 | 25-SEP-06:02 | 112240.14 | 06-SEP-05:02 | 115949.24 | 25-SEP-06:02 | 49257.76 | 10-SEP-08:15 | 0.00 | 01-SEP-00:10 |
October | 0.157075E+12 | 0.394760E+11 | 430.88 | 0.794830E+11 | 0.775924E+11 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 204731.52 | 15-OCT-08:62 | 112666.74 | 09-OCT-07:02 | 113829.77 | 12-OCT-06:02 | 49086.59 | 29-OCT-08:15 | 0.00 | 01-OCT-00:10 |
November | 0.141753E+12 | 0.361385E+11 | 413.16 | 0.764221E+11 | 0.653309E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 204157.28 | 12-NOV-09:02 | 119245.20 | 23-NOV-08:61 | 108667.96 | 14-NOV-07:06 | 49060.95 | 23-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.131802E+12 | 0.343220E+11 | 419.03 | 0.768259E+11 | 0.549765E+11 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 203118.92 | 10-DEC-09:02 | 116601.59 | 03-DEC-09:02 | 106092.28 | 30-DEC-07:06 | 49005.20 | 31-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.189335E+13 | 0.488415E+12 | 5113.81 | 0.103786E+13 | 0.855493E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.127532E+12 | 0.338885E+11 | 386.62 | 0.764221E+11 | 0.488108E+11 | 0.00 | 1.00 | 0.00 | 201908.55 | 110840.76 | 104381.25 | 47496.14 | 0.00 | |||||||
Maximum of Months | 0.191103E+12 | 0.490916E+11 | 442.74 | 0.988193E+11 | 0.922833E+11 | 0.00 | 1.00 | 0.00 | 206579.57 | 130314.99 | 124040.92 | 51035.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.213248E+11 | 0.510832E+10 | 437.10 | 0.149785E+11 | 0.634638E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:10 | 28192.08 | 09-JAN-06:02 | 19316.99 | 18-JAN-06:02 | 13476.98 | 02-JAN-07:04 | 5921.52 | 11-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.199663E+11 | 0.484310E+10 | 397.44 | 0.139830E+11 | 0.598336E+10 | 0.00 | 1.00 | 01-FEB-06:02 | 0.00 | 01-FEB-00:10 | 28135.65 | 20-FEB-08:62 | 20784.07 | 23-FEB-06:02 | 12902.88 | 16-FEB-07:04 | 6095.76 | 20-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.224741E+11 | 0.548693E+10 | 447.38 | 0.153108E+11 | 0.716328E+10 | 0.00 | 1.00 | 01-MAR-06:02 | 0.00 | 01-MAR-00:10 | 28650.41 | 27-MAR-05:02 | 17698.58 | 03-MAR-06:03 | 14324.21 | 27-MAR-05:03 | 6179.77 | 26-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.232312E+11 | 0.561579E+10 | 431.33 | 0.146800E+11 | 0.855121E+10 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 28785.15 | 03-APR-05:02 | 16725.10 | 28-APR-05:02 | 15117.33 | 03-APR-05:03 | 6177.97 | 30-APR-08:04 | 0.00 | 01-APR-00:10 |
May | 0.255946E+11 | 0.611822E+10 | 444.53 | 0.151815E+11 | 0.104131E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 28824.53 | 13-MAY-05:02 | 16757.42 | 11-MAY-05:02 | 17558.36 | 22-MAY-05:03 | 6361.50 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.254955E+11 | 0.608828E+10 | 433.71 | 0.150785E+11 | 0.104170E+11 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 28824.53 | 06-JUN-05:02 | 16771.22 | 30-JUN-05:02 | 17232.29 | 10-JUN-05:05 | 6255.18 | 18-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.213808E+11 | 0.504179E+10 | 437.96 | 0.134430E+11 | 0.793774E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 28163.06 | 02-JUL-07:02 | 18146.02 | 11-JUL-05:02 | 14238.20 | 01-JUL-06:04 | 6058.92 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.240921E+11 | 0.561803E+10 | 447.11 | 0.138699E+11 | 0.102223E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 28824.53 | 02-AUG-05:02 | 16841.69 | 16-AUG-05:02 | 16270.42 | 13-AUG-07:04 | 6200.71 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.229882E+11 | 0.538192E+10 | 429.53 | 0.136661E+11 | 0.932204E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 28595.74 | 25-SEP-05:02 | 17123.40 | 12-SEP-05:02 | 15010.61 | 25-SEP-06:02 | 6155.51 | 10-SEP-08:04 | 0.00 | 01-SEP-00:10 |
October | 0.225868E+11 | 0.524835E+10 | 438.50 | 0.135051E+11 | 0.908175E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 28467.98 | 30-OCT-05:02 | 17193.01 | 11-OCT-05:02 | 14919.48 | 23-OCT-06:02 | 6108.00 | 29-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.217757E+11 | 0.510189E+10 | 421.74 | 0.138868E+11 | 0.788893E+10 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 28099.12 | 12-NOV-08:62 | 17949.68 | 23-NOV-08:61 | 13508.71 | 13-NOV-07:04 | 6107.47 | 23-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.216712E+11 | 0.513257E+10 | 436.51 | 0.147498E+11 | 0.692140E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 28109.87 | 11-DEC-06:02 | 18432.36 | 07-DEC-06:02 | 13120.63 | 11-DEC-07:04 | 6099.64 | 31-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.272581E+12 | 0.647852E+11 | 5202.83 | 0.172333E+12 | 0.100248E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.199663E+11 | 0.484310E+10 | 397.44 | 0.134430E+11 | 0.598336E+10 | 0.00 | 1.00 | 0.00 | 28099.12 | 16725.10 | 12902.88 | 5921.52 | 0.00 | |||||||
Maximum of Months | 0.255946E+11 | 0.611822E+10 | 447.38 | 0.153108E+11 | 0.104170E+11 | 0.00 | 1.00 | 0.00 | 28824.53 | 20784.07 | 17558.36 | 6361.50 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.178448E+11 | 0.424541E+10 | 433.77 | 0.118265E+11 | 0.601830E+10 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:10 | 23292.56 | 09-JAN-06:02 | 14223.58 | 16-JAN-08:61 | 12375.11 | 02-JAN-07:02 | 4903.44 | 11-JAN-07:02 | 0.00 | 01-JAN-00:10 |
February | 0.168170E+11 | 0.404621E+10 | 395.83 | 0.111173E+11 | 0.569972E+10 | 0.00 | 1.00 | 01-FEB-06:02 | 0.00 | 01-FEB-00:10 | 23247.23 | 20-FEB-08:62 | 15822.34 | 23-FEB-06:02 | 11846.37 | 16-FEB-07:02 | 5045.50 | 20-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.187843E+11 | 0.454372E+10 | 444.43 | 0.120448E+11 | 0.673950E+10 | 0.00 | 1.00 | 01-MAR-06:02 | 0.00 | 01-MAR-00:10 | 23673.19 | 27-MAR-05:02 | 13451.63 | 04-MAR-07:02 | 12610.33 | 25-MAR-06:02 | 5111.84 | 26-MAR-08:04 | 0.00 | 01-MAR-00:10 |
April | 0.196826E+11 | 0.469357E+10 | 430.04 | 0.115911E+11 | 0.809152E+10 | 0.00 | 1.00 | 01-APR-05:02 | 0.00 | 01-APR-00:10 | 23810.34 | 03-APR-05:02 | 12718.43 | 27-APR-05:02 | 13187.92 | 03-APR-05:03 | 5122.48 | 30-APR-08:15 | 0.00 | 01-APR-00:10 |
May | 0.218706E+11 | 0.514903E+10 | 442.96 | 0.119962E+11 | 0.987432E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 23842.92 | 13-MAY-05:02 | 12434.35 | 11-MAY-05:02 | 15256.31 | 22-MAY-05:03 | 5262.07 | 28-MAY-07:02 | 0.00 | 01-MAY-00:10 |
June | 0.218831E+11 | 0.514523E+10 | 432.28 | 0.119650E+11 | 0.991810E+10 | 0.00 | 1.00 | 01-JUN-05:02 | 0.00 | 01-JUN-00:10 | 23842.92 | 06-JUN-05:02 | 12543.25 | 30-JUN-05:02 | 14898.86 | 10-JUN-05:05 | 5169.41 | 18-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.177596E+11 | 0.414187E+10 | 436.59 | 0.103286E+11 | 0.743094E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 23510.34 | 01-JUL-06:02 | 13485.84 | 09-JUL-07:02 | 13070.21 | 01-JUL-06:02 | 5014.35 | 30-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.202565E+11 | 0.465526E+10 | 444.13 | 0.106680E+11 | 0.958843E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 23862.34 | 05-AUG-06:02 | 12554.16 | 16-AUG-05:02 | 14475.34 | 05-AUG-06:02 | 5123.04 | 27-AUG-08:15 | 0.00 | 01-AUG-00:10 |
September | 0.194142E+11 | 0.448355E+10 | 427.54 | 0.106124E+11 | 0.880181E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 23698.79 | 17-SEP-08:62 | 12762.47 | 12-SEP-05:02 | 13649.03 | 25-SEP-06:02 | 5091.18 | 10-SEP-08:15 | 0.00 | 01-SEP-00:10 |
October | 0.188823E+11 | 0.433352E+10 | 432.67 | 0.103647E+11 | 0.851762E+10 | 0.00 | 1.00 | 01-OCT-07:02 | 0.00 | 01-OCT-00:10 | 23619.93 | 14-OCT-06:02 | 12888.53 | 08-OCT-07:02 | 13633.13 | 14-OCT-06:02 | 5071.87 | 29-OCT-08:15 | 0.00 | 01-OCT-00:10 |
November | 0.183281E+11 | 0.425111E+10 | 419.99 | 0.108524E+11 | 0.747574E+10 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:10 | 23366.96 | 09-NOV-07:02 | 13738.19 | 23-NOV-08:61 | 12493.22 | 09-NOV-07:02 | 5059.21 | 23-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.181807E+11 | 0.427363E+10 | 432.90 | 0.116118E+11 | 0.656896E+10 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 23238.06 | 11-DEC-06:02 | 13814.66 | 03-DEC-08:62 | 12011.85 | 11-DEC-07:02 | 5054.58 | 10-DEC-09:15 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.229704E+12 | 0.539621E+11 | 5173.12 | 0.134979E+12 | 0.947249E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.168170E+11 | 0.404621E+10 | 395.83 | 0.103286E+11 | 0.569972E+10 | 0.00 | 1.00 | 0.00 | 23238.06 | 12434.35 | 11846.37 | 4903.44 | 0.00 | |||||||
Maximum of Months | 0.218831E+11 | 0.514903E+10 | 444.43 | 0.120448E+11 | 0.991810E+10 | 0.00 | 1.00 | 0.00 | 23862.34 | 15822.34 | 15256.31 | 5262.07 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.47 | 56.03 | 61.44 | 166.64 | 16.29 | 0.00 | 0.00 | 744.00 |
February | 135.80 | 70.36 | 65.43 | 193.59 | 16.77 | 0.00 | 0.00 | 672.00 |
March | 157.23 | 91.96 | 65.27 | 223.73 | 13.72 | 0.00 | 0.00 | 744.00 |
April | 159.28 | 89.05 | 70.23 | 227.53 | 9.43 | 0.00 | 0.00 | 720.00 |
May | 133.32 | 57.76 | 75.56 | 193.14 | 7.79 | 0.00 | 0.00 | 744.00 |
June | 144.05 | 71.04 | 73.00 | 208.05 | 7.60 | 0.00 | 0.00 | 720.00 |
July | 121.34 | 40.05 | 81.29 | 174.67 | 10.25 | 0.00 | 0.00 | 744.00 |
August | 133.94 | 57.29 | 76.65 | 186.73 | 9.68 | 0.00 | 0.00 | 744.00 |
September | 123.75 | 47.83 | 75.91 | 177.64 | 9.18 | 0.00 | 0.00 | 720.00 |
October | 113.12 | 39.88 | 73.24 | 158.36 | 9.89 | 0.00 | 0.00 | 744.00 |
November | 108.20 | 40.94 | 67.27 | 153.65 | 12.39 | 0.00 | 0.00 | 720.00 |
December | 109.11 | 48.86 | 60.25 | 154.91 | 16.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 129.62 | 59.13 | 70.49 | 184.74 | 11.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 108.20 | 39.88 | 60.25 | 153.65 | 7.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 159.28 | 91.96 | 81.29 | 227.53 | 16.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.57 | 317.25 | 443.32 | 1326.43 | 159.10 | 0.00 | 0.00 | 744.00 |
February | 645.80 | 210.46 | 435.34 | 1141.10 | 133.44 | 0.00 | 0.00 | 672.00 |
March | 440.55 | 58.94 | 381.61 | 815.96 | 101.38 | 0.00 | 0.00 | 744.00 |
April | 328.64 | 0.14 | 328.50 | 717.71 | 54.40 | 0.00 | 0.00 | 720.00 |
May | 328.87 | 0.00 | 328.87 | 739.75 | 56.74 | 0.00 | 0.00 | 744.00 |
June | 327.69 | 0.00 | 327.69 | 731.41 | 62.77 | 0.00 | 0.00 | 720.00 |
July | 337.57 | 0.00 | 337.57 | 669.99 | 94.56 | 0.00 | 0.00 | 744.00 |
August | 328.62 | 0.50 | 328.12 | 648.29 | 79.70 | 0.00 | 0.00 | 744.00 |
September | 363.73 | 11.79 | 351.93 | 709.24 | 82.18 | 0.00 | 0.00 | 720.00 |
October | 475.88 | 75.80 | 400.08 | 834.17 | 98.56 | 0.00 | 0.00 | 744.00 |
November | 618.83 | 188.73 | 430.10 | 1086.54 | 118.47 | 0.00 | 0.00 | 720.00 |
December | 760.22 | 323.39 | 436.82 | 1324.08 | 173.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 475.75 | 98.53 | 377.22 | 894.29 | 101.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 327.69 | 0.00 | 327.69 | 648.29 | 54.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 760.57 | 323.39 | 443.32 | 1326.43 | 173.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.57 | 317.25 | 443.32 | 1323.96 | 145.43 | 0.00 | 0.00 | 744.00 |
February | 645.80 | 210.46 | 435.34 | 1138.46 | 119.64 | 0.00 | 0.00 | 672.00 |
March | 440.55 | 58.94 | 381.61 | 813.61 | 86.34 | 0.00 | 0.00 | 744.00 |
April | 328.64 | 0.14 | 328.50 | 716.97 | 41.41 | 0.00 | 0.00 | 720.00 |
May | 328.87 | 0.00 | 328.87 | 740.17 | 45.30 | 0.00 | 0.00 | 744.00 |
June | 327.69 | 0.00 | 327.69 | 730.21 | 50.55 | 0.00 | 0.00 | 720.00 |
July | 337.57 | 0.00 | 337.57 | 667.81 | 81.28 | 0.00 | 0.00 | 744.00 |
August | 328.62 | 0.50 | 328.12 | 646.65 | 66.07 | 0.00 | 0.00 | 744.00 |
September | 363.73 | 11.79 | 351.93 | 707.12 | 69.02 | 0.00 | 0.00 | 720.00 |
October | 475.88 | 75.80 | 400.08 | 832.72 | 84.32 | 0.00 | 0.00 | 744.00 |
November | 618.83 | 188.73 | 430.10 | 1084.70 | 105.68 | 0.00 | 0.00 | 720.00 |
December | 760.22 | 323.39 | 436.82 | 1321.87 | 160.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 475.75 | 98.53 | 377.22 | 892.60 | 87.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 327.69 | 0.00 | 327.69 | 646.65 | 41.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 760.57 | 323.39 | 443.32 | 1323.96 | 160.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.50 | 65.28 | 91.22 | 242.63 | 40.44 | 0.00 | 0.00 | 744.00 |
February | 132.88 | 43.30 | 89.58 | 201.80 | 36.27 | 0.00 | 0.00 | 672.00 |
March | 90.65 | 12.13 | 78.52 | 133.67 | 28.48 | 0.00 | 0.00 | 744.00 |
April | 67.62 | 0.03 | 67.59 | 110.05 | 16.53 | 0.00 | 0.00 | 720.00 |
May | 67.67 | 0.00 | 67.67 | 113.57 | 16.98 | 70.17 | 0.00 | 744.00 |
June | 67.43 | 0.00 | 67.43 | 111.90 | 18.42 | 13.83 | 0.00 | 720.00 |
July | 69.46 | 0.00 | 69.46 | 110.27 | 23.27 | 0.00 | 0.00 | 744.00 |
August | 67.62 | 0.10 | 67.52 | 104.71 | 20.86 | 0.33 | 0.00 | 744.00 |
September | 74.84 | 2.43 | 72.42 | 116.78 | 21.42 | 0.00 | 0.00 | 720.00 |
October | 97.92 | 15.60 | 82.32 | 145.32 | 24.93 | 4.50 | 0.00 | 744.00 |
November | 127.33 | 38.83 | 88.50 | 196.02 | 30.53 | 0.00 | 0.00 | 720.00 |
December | 156.43 | 66.54 | 89.88 | 243.88 | 43.39 | 2.50 | 0.00 | 744.00 |
Annual Sum or Average | 97.89 | 20.27 | 77.62 | 152.35 | 26.77 | 91.33 | 0.00 | 8760.00 |
Minimum of Months | 67.43 | 0.00 | 67.43 | 104.71 | 16.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 156.50 | 66.54 | 91.22 | 243.88 | 43.39 | 70.17 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314634E+09 | 0.150061E+09 | 0.164573E+09 | 0.446329E+09 | 43619953.07 |
February | 0.328515E+09 | 0.170218E+09 | 0.158298E+09 | 0.468322E+09 | 40563139.17 |
March | 0.421135E+09 | 0.246316E+09 | 0.174819E+09 | 0.599244E+09 | 36743099.47 |
April | 0.412844E+09 | 0.230813E+09 | 0.182031E+09 | 0.589760E+09 | 24443268.43 |
May | 0.357097E+09 | 0.154711E+09 | 0.202387E+09 | 0.517305E+09 | 20878086.40 |
June | 0.373368E+09 | 0.184144E+09 | 0.189223E+09 | 0.539264E+09 | 19702686.09 |
July | 0.324984E+09 | 0.107266E+09 | 0.217717E+09 | 0.467844E+09 | 27453853.42 |
August | 0.358738E+09 | 0.153449E+09 | 0.205289E+09 | 0.500131E+09 | 25919350.35 |
September | 0.320752E+09 | 0.123984E+09 | 0.196768E+09 | 0.460445E+09 | 23788030.63 |
October | 0.302973E+09 | 0.106811E+09 | 0.196161E+09 | 0.424150E+09 | 26486982.77 |
November | 0.280463E+09 | 0.106106E+09 | 0.174357E+09 | 0.398260E+09 | 32102800.71 |
December | 0.292233E+09 | 0.130872E+09 | 0.161360E+09 | 0.414913E+09 | 45380414.97 |
Annual Sum or Average | 0.408774E+10 | 0.186475E+10 | 0.222298E+10 | 0.582597E+10 | 0.367082E+09 |
Minimum of Months | 0.280463E+09 | 0.106106E+09 | 0.158298E+09 | 0.398260E+09 | 19702686.09 |
Maximum of Months | 0.421135E+09 | 0.246316E+09 | 0.217717E+09 | 0.599244E+09 | 45380414.97 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.355270E+10 | 0.426141E+09 |
February | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.276054E+10 | 0.322820E+09 |
March | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.218547E+10 | 0.271539E+09 |
April | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.186029E+10 | 0.141010E+09 |
May | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.198135E+10 | 0.151962E+09 |
June | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.189581E+10 | 0.162706E+09 |
July | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.179450E+10 | 0.253272E+09 |
August | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.173637E+10 | 0.213456E+09 |
September | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.183835E+10 | 0.212998E+09 |
October | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.223423E+10 | 0.263985E+09 |
November | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.281632E+10 | 0.307065E+09 |
December | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.354642E+10 | 0.464706E+09 |
Annual Sum or Average | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.282024E+11 | 0.319166E+10 |
Minimum of Months | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.173637E+10 | 0.141010E+09 |
Maximum of Months | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.355270E+10 | 0.464706E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.354609E+10 | 0.389513E+09 |
February | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.275417E+10 | 0.289431E+09 |
March | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.217919E+10 | 0.231256E+09 |
April | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.185838E+10 | 0.107337E+09 |
May | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.198246E+10 | 0.121341E+09 |
June | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.189270E+10 | 0.131036E+09 |
July | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.178867E+10 | 0.217699E+09 |
August | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.173199E+10 | 0.176953E+09 |
September | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.183285E+10 | 0.178910E+09 |
October | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.223037E+10 | 0.225832E+09 |
November | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.281156E+10 | 0.273922E+09 |
December | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.354050E+10 | 0.430179E+09 |
Annual Sum or Average | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.281489E+11 | 0.277341E+10 |
Minimum of Months | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.173199E+10 | 0.107337E+09 |
Maximum of Months | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.354609E+10 | 0.430179E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419164E+09 | 0.174841E+09 | 0.244323E+09 | 0.649847E+09 | 0.108324E+09 |
February | 0.321469E+09 | 0.104763E+09 | 0.216705E+09 | 0.488186E+09 | 87742631.25 |
March | 0.242798E+09 | 32482927.03 | 0.210315E+09 | 0.358026E+09 | 76289120.47 |
April | 0.175280E+09 | 75470.34 | 0.175204E+09 | 0.285256E+09 | 42855842.64 |
May | 0.181249E+09 | 0.00 | 0.181249E+09 | 0.304196E+09 | 45479843.02 |
June | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.290038E+09 | 47750790.59 |
July | 0.186042E+09 | 0.00 | 0.186042E+09 | 0.295360E+09 | 62320425.90 |
August | 0.181109E+09 | 275347.01 | 0.180833E+09 | 0.280454E+09 | 55871300.74 |
September | 0.193990E+09 | 6290561.79 | 0.187700E+09 | 0.302693E+09 | 55513904.65 |
October | 0.262268E+09 | 41773245.91 | 0.220495E+09 | 0.389225E+09 | 66769869.49 |
November | 0.330048E+09 | 0.100659E+09 | 0.229390E+09 | 0.508095E+09 | 79122159.29 |
December | 0.418970E+09 | 0.178229E+09 | 0.240742E+09 | 0.653211E+09 | 0.116219E+09 |
Annual Sum or Average | 0.308716E+10 | 0.639389E+09 | 0.244777E+10 | 0.480459E+10 | 0.844259E+09 |
Minimum of Months | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.280454E+09 | 42855842.64 |
Maximum of Months | 0.419164E+09 | 0.178229E+09 | 0.244323E+09 | 0.653211E+09 | 0.116219E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2666.25 | 260.57 | 1879.53 | 896.42 | 983.11 | 0.00 | 0.00 |
February | 3097.37 | 268.27 | 2172.72 | 1125.78 | 1046.94 | 0.00 | 0.00 |
March | 3579.71 | 219.49 | 2515.74 | 1471.42 | 1044.32 | 0.00 | 0.00 |
April | 3640.49 | 150.88 | 2548.42 | 1424.77 | 1123.65 | 0.00 | 0.00 |
May | 3090.23 | 124.72 | 2133.20 | 924.20 | 1209.00 | 0.00 | 0.00 |
June | 3328.79 | 121.62 | 2304.74 | 1136.69 | 1168.05 | 0.00 | 0.00 |
July | 2794.77 | 164.00 | 1941.36 | 640.78 | 1300.58 | 0.00 | 0.00 |
August | 2987.64 | 154.83 | 2143.00 | 916.66 | 1226.34 | 0.00 | 0.00 |
September | 2842.25 | 146.84 | 1979.95 | 765.33 | 1214.62 | 0.00 | 0.00 |
October | 2533.75 | 158.23 | 1809.87 | 638.06 | 1171.81 | 0.00 | 0.00 |
November | 2458.39 | 198.17 | 1731.25 | 654.97 | 1076.28 | 0.00 | 0.00 |
December | 2478.57 | 271.09 | 1745.72 | 781.80 | 963.92 | 0.00 | 0.00 |
Annual Sum or Average | 2955.84 | 186.24 | 2073.94 | 946.09 | 1127.85 | 0.00 | 0.00 |
Minimum of Months | 2458.39 | 121.62 | 1731.25 | 638.06 | 963.92 | 0.00 | 0.00 |
Maximum of Months | 3640.49 | 271.09 | 2548.42 | 1471.42 | 1300.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1326.43 | 159.10 | 760.57 | 317.25 | 443.32 | 0.00 | 0.00 |
February | 1141.10 | 133.44 | 645.80 | 210.46 | 435.34 | 0.00 | 0.00 |
March | 815.96 | 101.38 | 440.55 | 58.94 | 381.61 | 0.00 | 0.00 |
April | 717.71 | 54.40 | 328.64 | 0.14 | 328.50 | 0.00 | 0.00 |
May | 739.75 | 56.74 | 328.87 | 0.00 | 328.87 | 0.00 | 0.00 |
June | 731.41 | 62.77 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
July | 669.99 | 94.56 | 337.57 | 0.00 | 337.57 | 0.00 | 0.00 |
August | 648.29 | 79.70 | 328.62 | 0.50 | 328.12 | 0.00 | 0.00 |
September | 709.24 | 82.18 | 363.73 | 11.79 | 351.93 | 0.00 | 0.00 |
October | 834.17 | 98.56 | 475.88 | 75.80 | 400.08 | 0.00 | 0.00 |
November | 1086.54 | 118.47 | 618.83 | 188.73 | 430.10 | 0.00 | 0.00 |
December | 1324.08 | 173.50 | 760.22 | 323.39 | 436.82 | 0.00 | 0.00 |
Annual Sum or Average | 894.29 | 101.21 | 475.75 | 98.53 | 377.22 | 0.00 | 0.00 |
Minimum of Months | 648.29 | 54.40 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
Maximum of Months | 1326.43 | 173.50 | 760.57 | 323.39 | 443.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1323.96 | 145.43 | 760.57 | 317.25 | 443.32 | 0.00 | 0.00 |
February | 1138.46 | 119.64 | 645.80 | 210.46 | 435.34 | 0.00 | 0.00 |
March | 813.61 | 86.34 | 440.55 | 58.94 | 381.61 | 0.00 | 0.00 |
April | 716.97 | 41.41 | 328.64 | 0.14 | 328.50 | 0.00 | 0.00 |
May | 740.17 | 45.30 | 328.87 | 0.00 | 328.87 | 0.00 | 0.00 |
June | 730.21 | 50.55 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
July | 667.81 | 81.28 | 337.57 | 0.00 | 337.57 | 0.00 | 0.00 |
August | 646.65 | 66.07 | 328.62 | 0.50 | 328.12 | 0.00 | 0.00 |
September | 707.12 | 69.02 | 363.73 | 11.79 | 351.93 | 0.00 | 0.00 |
October | 832.72 | 84.32 | 475.88 | 75.80 | 400.08 | 0.00 | 0.00 |
November | 1084.70 | 105.68 | 618.83 | 188.73 | 430.10 | 0.00 | 0.00 |
December | 1321.87 | 160.61 | 760.22 | 323.39 | 436.82 | 0.00 | 0.00 |
Annual Sum or Average | 892.60 | 87.94 | 475.75 | 98.53 | 377.22 | 0.00 | 0.00 |
Minimum of Months | 646.65 | 41.41 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
Maximum of Months | 1323.96 | 160.61 | 760.57 | 323.39 | 443.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 242.63 | 40.44 | 156.50 | 65.28 | 91.22 | 0.00 | 0.00 |
February | 201.80 | 36.27 | 132.88 | 43.30 | 89.58 | 0.00 | 0.00 |
March | 133.67 | 28.48 | 90.65 | 12.13 | 78.52 | 0.00 | 0.00 |
April | 110.05 | 16.53 | 67.62 | 0.03 | 67.59 | 0.00 | 0.00 |
May | 113.57 | 16.98 | 67.67 | 0.00 | 67.67 | 0.00 | 0.00 |
June | 111.90 | 18.42 | 67.43 | 0.00 | 67.43 | 0.00 | 0.00 |
July | 110.27 | 23.27 | 69.46 | 0.00 | 69.46 | 0.00 | 0.00 |
August | 104.71 | 20.86 | 67.62 | 0.10 | 67.52 | 0.00 | 0.00 |
September | 116.78 | 21.42 | 74.84 | 2.43 | 72.42 | 0.00 | 0.00 |
October | 145.32 | 24.93 | 97.92 | 15.60 | 82.32 | 0.00 | 0.00 |
November | 196.02 | 30.53 | 127.33 | 38.83 | 88.50 | 0.00 | 0.00 |
December | 243.88 | 43.39 | 156.43 | 66.54 | 89.88 | 0.00 | 0.00 |
Annual Sum or Average | 152.35 | 26.77 | 97.89 | 20.27 | 77.62 | 0.00 | 0.00 |
Minimum of Months | 104.71 | 16.53 | 67.43 | 0.00 | 67.43 | 0.00 | 0.00 |
Maximum of Months | 243.88 | 43.39 | 156.50 | 66.54 | 91.22 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.714127E+10 | 0.697919E+09 | 0.503414E+10 | 0.240097E+10 | 0.263317E+10 | 0.00 | 0.00 |
February | 0.749315E+10 | 0.649010E+09 | 0.525625E+10 | 0.272349E+10 | 0.253276E+10 | 0.00 | 0.00 |
March | 0.958791E+10 | 0.587890E+09 | 0.673815E+10 | 0.394105E+10 | 0.279710E+10 | 0.00 | 0.00 |
April | 0.943616E+10 | 0.391092E+09 | 0.660550E+10 | 0.369301E+10 | 0.291249E+10 | 0.00 | 0.00 |
May | 0.827688E+10 | 0.334049E+09 | 0.571356E+10 | 0.247538E+10 | 0.323818E+10 | 0.00 | 0.00 |
June | 0.862823E+10 | 0.315243E+09 | 0.597388E+10 | 0.294631E+10 | 0.302758E+10 | 0.00 | 0.00 |
July | 0.748550E+10 | 0.439262E+09 | 0.519974E+10 | 0.171626E+10 | 0.348348E+10 | 0.00 | 0.00 |
August | 0.800210E+10 | 0.414710E+09 | 0.573981E+10 | 0.245519E+10 | 0.328462E+10 | 0.00 | 0.00 |
September | 0.736711E+10 | 0.380608E+09 | 0.513204E+10 | 0.198375E+10 | 0.314829E+10 | 0.00 | 0.00 |
October | 0.678640E+10 | 0.423792E+09 | 0.484756E+10 | 0.170898E+10 | 0.313858E+10 | 0.00 | 0.00 |
November | 0.637216E+10 | 0.513645E+09 | 0.448741E+10 | 0.169769E+10 | 0.278971E+10 | 0.00 | 0.00 |
December | 0.663860E+10 | 0.726087E+09 | 0.467573E+10 | 0.209396E+10 | 0.258177E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.932155E+11 | 0.587331E+10 | 0.654038E+11 | 0.298360E+11 | 0.355677E+11 | 0.00 | 0.00 |
Minimum of Months | 0.637216E+10 | 0.315243E+09 | 0.448741E+10 | 0.169769E+10 | 0.253276E+10 | 0.00 | 0.00 |
Maximum of Months | 0.958791E+10 | 0.726087E+09 | 0.673815E+10 | 0.394105E+10 | 0.348348E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.355270E+10 | 0.426141E+09 | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.00 | 0.00 |
February | 0.276054E+10 | 0.322820E+09 | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.00 | 0.00 |
March | 0.218547E+10 | 0.271539E+09 | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.00 | 0.00 |
April | 0.186029E+10 | 0.141010E+09 | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.00 | 0.00 |
May | 0.198135E+10 | 0.151962E+09 | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.00 | 0.00 |
June | 0.189581E+10 | 0.162706E+09 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
July | 0.179450E+10 | 0.253272E+09 | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.00 | 0.00 |
August | 0.173637E+10 | 0.213456E+09 | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.00 | 0.00 |
September | 0.183835E+10 | 0.212998E+09 | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.00 | 0.00 |
October | 0.223423E+10 | 0.263985E+09 | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.00 | 0.00 |
November | 0.281632E+10 | 0.307065E+09 | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.00 | 0.00 |
December | 0.354642E+10 | 0.464706E+09 | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.282024E+11 | 0.319166E+10 | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.00 | 0.00 |
Minimum of Months | 0.173637E+10 | 0.141010E+09 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
Maximum of Months | 0.355270E+10 | 0.464706E+09 | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.354609E+10 | 0.389513E+09 | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.00 | 0.00 |
February | 0.275417E+10 | 0.289431E+09 | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.00 | 0.00 |
March | 0.217919E+10 | 0.231256E+09 | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.00 | 0.00 |
April | 0.185838E+10 | 0.107337E+09 | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.00 | 0.00 |
May | 0.198246E+10 | 0.121341E+09 | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.00 | 0.00 |
June | 0.189270E+10 | 0.131036E+09 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
July | 0.178867E+10 | 0.217699E+09 | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.00 | 0.00 |
August | 0.173199E+10 | 0.176953E+09 | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.00 | 0.00 |
September | 0.183285E+10 | 0.178910E+09 | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.00 | 0.00 |
October | 0.223037E+10 | 0.225832E+09 | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.00 | 0.00 |
November | 0.281156E+10 | 0.273922E+09 | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.00 | 0.00 |
December | 0.354050E+10 | 0.430179E+09 | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.281489E+11 | 0.277341E+10 | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.00 | 0.00 |
Minimum of Months | 0.173199E+10 | 0.107337E+09 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
Maximum of Months | 0.354609E+10 | 0.430179E+09 | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.649847E+09 | 0.108324E+09 | 0.419164E+09 | 0.174841E+09 | 0.244323E+09 | 0.00 | 0.00 |
February | 0.488186E+09 | 87742631.25 | 0.321469E+09 | 0.104763E+09 | 0.216705E+09 | 0.00 | 0.00 |
March | 0.358026E+09 | 76289120.47 | 0.242798E+09 | 32482927.03 | 0.210315E+09 | 0.00 | 0.00 |
April | 0.285256E+09 | 42855842.64 | 0.175280E+09 | 75470.34 | 0.175204E+09 | 0.00 | 0.00 |
May | 0.304196E+09 | 45479843.02 | 0.181249E+09 | 0.00 | 0.181249E+09 | 0.00 | 0.00 |
June | 0.290038E+09 | 47750790.59 | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.00 | 0.00 |
July | 0.295360E+09 | 62320425.90 | 0.186042E+09 | 0.00 | 0.186042E+09 | 0.00 | 0.00 |
August | 0.280454E+09 | 55871300.74 | 0.181109E+09 | 275347.01 | 0.180833E+09 | 0.00 | 0.00 |
September | 0.302693E+09 | 55513904.65 | 0.193990E+09 | 6290561.79 | 0.187700E+09 | 0.00 | 0.00 |
October | 0.389225E+09 | 66769869.49 | 0.262268E+09 | 41773245.91 | 0.220495E+09 | 0.00 | 0.00 |
November | 0.508095E+09 | 79122159.29 | 0.330048E+09 | 0.100659E+09 | 0.229390E+09 | 0.00 | 0.00 |
December | 0.653211E+09 | 0.116219E+09 | 0.418970E+09 | 0.178229E+09 | 0.240742E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.480459E+10 | 0.844259E+09 | 0.308716E+10 | 0.639389E+09 | 0.244777E+10 | 0.00 | 0.00 |
Minimum of Months | 0.280454E+09 | 42855842.64 | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.00 | 0.00 |
Maximum of Months | 0.653211E+09 | 0.116219E+09 | 0.419164E+09 | 0.178229E+09 | 0.244323E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.65 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.90 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.36 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 22.99 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.54 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.00 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.13 | 23.20 | 1.94 | 20.28 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.59 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 22.99 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.66 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.00 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 22.99 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.95 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.41 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.58 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.62 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.85 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.50 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.22 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.33 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.21 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.00 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.85 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.93 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.52 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.16 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.27 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.92 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.69 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.10 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.42 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.05 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.55 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.52 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.86 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.10 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.05 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.03 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.55 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.10 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.173594E+10 | -.138735E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -348584690.5 | 58.99 | 0.00 | 0.00 |
February | 0.156931E+10 | -.125525E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -314061658.6 | 58.99 | 0.00 | 0.00 |
March | 0.174901E+10 | -.140191E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -347105063.8 | 58.99 | 0.00 | 0.00 |
April | 0.163898E+10 | -.130410E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -334881787.7 | 58.99 | 0.00 | 0.00 |
May | 0.166584E+10 | -.132032E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -345520794.3 | 58.99 | 0.00 | 0.00 |
June | 0.160868E+10 | -.127508E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -333604138.9 | 59.00 | 0.00 | 0.00 |
July | 0.161844E+10 | -.127251E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -345935650.5 | 58.99 | 0.00 | 0.00 |
August | 0.166990E+10 | -.132286E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -347042178.5 | 58.99 | 0.00 | 0.00 |
September | 0.161580E+10 | -.128001E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -335789076.4 | 58.99 | 0.00 | 0.00 |
October | 0.168031E+10 | -.133231E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -347999132.6 | 58.99 | 0.00 | 0.00 |
November | 0.164820E+10 | -.131120E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -337006006.1 | 58.99 | 0.00 | 0.00 |
December | 0.173165E+10 | -.138260E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -349048800.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.199321E+11 | -.158455E+11 | 8760.00 | -.408658E+10 | 58.99 | |||||
Minimum of Months | 0.156931E+10 | -.140191E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -349048800.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.174901E+10 | -.125525E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -314061658.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.68 | 0.50 | 01-JAN-10:20 | 678.26 | 10.68 | 0.00 | 188.33 | 570.83 | 9.16 | 0.00 | 137.50 |
February | 321.17 | 0.66 | 0.50 | 01-FEB-09:09 | 3845.24 | 11.24 | 0.00 | 186.67 | 3340.93 | 9.68 | 0.00 | 160.00 |
March | 361.17 | 0.67 | 0.50 | 01-MAR-08:50 | 570.39 | 12.19 | 0.00 | 210.00 | 471.54 | 10.50 | 0.00 | 145.00 |
April | 358.33 | 0.67 | 0.50 | 01-APR-09:09 | 535.41 | 13.73 | 0.00 | 205.83 | 443.61 | 11.97 | 0.00 | 145.50 |
May | 376.33 | 0.67 | 0.50 | 01-MAY-08:30 | 559.29 | 14.64 | 1.83 | 219.83 | 448.54 | 12.84 | 0.00 | 156.17 |
June | 370.50 | 0.65 | 0.50 | 01-JUN-08:00 | 983.17 | 17.92 | 53.17 | 255.83 | 455.41 | 13.43 | 0.00 | 154.67 |
July | 383.17 | 0.67 | 0.50 | 01-JUL-08:30 | 542.79 | 14.63 | 0.00 | 219.67 | 453.85 | 12.93 | 0.00 | 161.67 |
August | 369.33 | 0.66 | 0.50 | 01-AUG-08:50 | 562.11 | 14.33 | 0.00 | 220.33 | 468.99 | 12.63 | 0.00 | 162.33 |
September | 357.83 | 0.67 | 0.50 | 01-SEP-08:30 | 579.83 | 12.89 | 0.00 | 208.67 | 469.87 | 11.30 | 0.00 | 154.67 |
October | 356.83 | 0.66 | 0.50 | 01-OCT-08:50 | 1003.03 | 12.27 | 0.00 | 234.17 | 624.28 | 10.65 | 0.00 | 158.33 |
November | 337.67 | 0.67 | 0.50 | 01-NOV-08:50 | 1355.99 | 11.47 | 0.00 | 190.17 | 1375.90 | 9.84 | 0.00 | 141.67 |
December | 349.33 | 0.69 | 0.50 | 01-DEC-08:39 | 516.04 | 10.56 | 0.00 | 183.83 | 434.21 | 9.03 | 0.00 | 131.50 |
Annual Sum or Average | 4292.33 | 0.67 | 946.93 | 13.11 | 55.00 | 2523.33 | 767.47 | 11.22 | 0.00 | 1809.00 | ||
Minimum of Months | 321.17 | 0.65 | 0.50 | 516.04 | 10.56 | 0.00 | 183.83 | 434.21 | 9.03 | 0.00 | 131.50 | |
Maximum of Months | 383.17 | 0.69 | 0.50 | 3845.24 | 17.92 | 53.17 | 255.83 | 3340.93 | 13.43 | 0.00 | 162.33 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.271808E+11 | 0.187454E+11 | 45437.01 | 09-JAN-06:02 | 24320.40 | 0.00 |
February | 0.00 | 0.00 | 0.267454E+11 | 0.186113E+11 | 45319.58 | 20-FEB-08:62 | 25510.13 | 0.00 |
March | 0.00 | 0.00 | 0.326410E+11 | 0.224195E+11 | 46132.13 | 27-MAR-05:02 | 23695.83 | 0.00 |
April | 0.00 | 0.00 | 0.353651E+11 | 0.230207E+11 | 46611.93 | 03-APR-05:02 | 22949.42 | 0.00 |
May | 0.00 | 0.00 | 0.396622E+11 | 0.245115E+11 | 46748.68 | 20-MAY-05:02 | 20832.60 | 0.00 |
June | 0.00 | 0.00 | 0.409248E+11 | 0.256034E+11 | 46739.51 | 12-JUN-05:02 | 21739.29 | 0.00 |
July | 0.00 | 0.00 | 0.336079E+11 | 0.220845E+11 | 45319.21 | 01-JUL-06:02 | 23599.82 | 0.00 |
August | 0.00 | 0.00 | 0.366494E+11 | 0.219519E+11 | 46665.03 | 12-AUG-05:02 | 22404.90 | 0.00 |
September | 0.00 | 0.00 | 0.338902E+11 | 0.207750E+11 | 46002.54 | 25-SEP-05:02 | 23712.71 | 0.00 |
October | 0.00 | 0.00 | 0.314936E+11 | 0.190243E+11 | 45904.21 | 30-OCT-05:02 | 23307.34 | 0.00 |
November | 0.00 | 0.00 | 0.289252E+11 | 0.183358E+11 | 45316.07 | 12-NOV-09:02 | 23584.23 | 0.00 |
December | 0.00 | 0.00 | 0.273194E+11 | 0.182248E+11 | 45371.53 | 11-DEC-06:02 | 24557.34 | 0.00 |
Annual Sum or Average | 0.394405E+12 | 0.253308E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.267454E+11 | 0.182248E+11 | 45316.07 | 20832.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.409248E+11 | 0.256034E+11 | 46748.68 | 25510.13 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.128968E+12 | 0.790289E+11 | 201908.55 | 10-JAN-07:02 | 97527.30 | 0.00 |
February | 0.00 | 0.00 | 0.127532E+12 | 0.787212E+11 | 202272.77 | 16-FEB-07:02 | 98111.58 | 0.00 |
March | 0.00 | 0.00 | 0.155801E+12 | 0.956468E+11 | 202159.88 | 25-MAR-06:02 | 97899.09 | 0.00 |
April | 0.00 | 0.00 | 0.171995E+12 | 0.969409E+11 | 202851.23 | 15-APR-06:02 | 97139.76 | 0.00 |
May | 0.00 | 0.00 | 0.189935E+12 | 0.985789E+11 | 206579.57 | 23-MAY-06:02 | 87515.62 | 0.00 |
June | 0.00 | 0.00 | 0.191103E+12 | 0.988193E+11 | 206449.28 | 29-JUN-06:02 | 88240.71 | 0.00 |
July | 0.00 | 0.00 | 0.152222E+12 | 0.837146E+11 | 203254.45 | 01-JUL-06:02 | 95360.17 | 0.00 |
August | 0.00 | 0.00 | 0.178300E+12 | 0.885277E+11 | 206329.22 | 12-AUG-06:02 | 89439.53 | 0.00 |
September | 0.00 | 0.00 | 0.166864E+12 | 0.851491E+11 | 205780.63 | 25-SEP-06:02 | 89831.40 | 0.00 |
October | 0.00 | 0.00 | 0.157075E+12 | 0.794830E+11 | 204731.52 | 15-OCT-08:62 | 94387.68 | 0.00 |
November | 0.00 | 0.00 | 0.141753E+12 | 0.764221E+11 | 204157.28 | 12-NOV-09:02 | 95912.33 | 0.00 |
December | 0.00 | 0.00 | 0.131802E+12 | 0.768259E+11 | 203118.92 | 10-DEC-09:02 | 99110.45 | 0.00 |
Annual Sum or Average | 0.189335E+13 | 0.103786E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.127532E+12 | 0.764221E+11 | 201908.55 | 87515.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.191103E+12 | 0.988193E+11 | 206579.57 | 99110.45 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.213248E+11 | 0.149785E+11 | 28192.08 | 09-JAN-06:02 | 15111.66 | 0.00 |
February | 0.00 | 0.00 | 0.199663E+11 | 0.139830E+11 | 28135.65 | 20-FEB-08:62 | 15746.00 | 0.00 |
March | 0.00 | 0.00 | 0.224741E+11 | 0.153108E+11 | 28650.41 | 27-MAR-05:02 | 14407.51 | 0.00 |
April | 0.00 | 0.00 | 0.232312E+11 | 0.146800E+11 | 28785.15 | 03-APR-05:02 | 13809.91 | 0.00 |
May | 0.00 | 0.00 | 0.255946E+11 | 0.151815E+11 | 28824.53 | 13-MAY-05:02 | 12886.25 | 0.00 |
June | 0.00 | 0.00 | 0.254955E+11 | 0.150785E+11 | 28824.53 | 06-JUN-05:02 | 13818.16 | 0.00 |
July | 0.00 | 0.00 | 0.213808E+11 | 0.134430E+11 | 28163.06 | 02-JUL-07:02 | 15147.52 | 0.00 |
August | 0.00 | 0.00 | 0.240921E+11 | 0.138699E+11 | 28824.53 | 02-AUG-05:02 | 13798.79 | 0.00 |
September | 0.00 | 0.00 | 0.229882E+11 | 0.136661E+11 | 28595.74 | 25-SEP-05:02 | 14193.89 | 0.00 |
October | 0.00 | 0.00 | 0.225868E+11 | 0.135051E+11 | 28467.98 | 30-OCT-05:02 | 14466.05 | 0.00 |
November | 0.00 | 0.00 | 0.217757E+11 | 0.138868E+11 | 28099.12 | 12-NOV-08:62 | 15429.18 | 0.00 |
December | 0.00 | 0.00 | 0.216712E+11 | 0.147498E+11 | 28109.87 | 11-DEC-06:02 | 15251.02 | 0.00 |
Annual Sum or Average | 0.272581E+12 | 0.172333E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.199663E+11 | 0.134430E+11 | 28099.12 | 12886.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.255946E+11 | 0.153108E+11 | 28824.53 | 15746.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.178448E+11 | 0.118265E+11 | 23292.56 | 09-JAN-06:02 | 11576.41 | 0.00 |
February | 0.00 | 0.00 | 0.168170E+11 | 0.111173E+11 | 23247.23 | 20-FEB-08:62 | 12244.21 | 0.00 |
March | 0.00 | 0.00 | 0.187843E+11 | 0.120448E+11 | 23673.19 | 27-MAR-05:02 | 11109.65 | 0.00 |
April | 0.00 | 0.00 | 0.196826E+11 | 0.115911E+11 | 23810.34 | 03-APR-05:02 | 10678.89 | 0.00 |
May | 0.00 | 0.00 | 0.218706E+11 | 0.119962E+11 | 23842.92 | 13-MAY-05:02 | 9742.96 | 0.00 |
June | 0.00 | 0.00 | 0.218831E+11 | 0.119650E+11 | 23842.92 | 06-JUN-05:02 | 10406.08 | 0.00 |
July | 0.00 | 0.00 | 0.177596E+11 | 0.103286E+11 | 23510.34 | 01-JUL-06:02 | 10440.13 | 0.00 |
August | 0.00 | 0.00 | 0.202565E+11 | 0.106680E+11 | 23862.34 | 05-AUG-06:02 | 9387.00 | 0.00 |
September | 0.00 | 0.00 | 0.194142E+11 | 0.106124E+11 | 23698.79 | 17-SEP-08:62 | 10089.49 | 0.00 |
October | 0.00 | 0.00 | 0.188823E+11 | 0.103647E+11 | 23619.93 | 14-OCT-06:02 | 9986.80 | 0.00 |
November | 0.00 | 0.00 | 0.183281E+11 | 0.108524E+11 | 23366.96 | 09-NOV-07:02 | 10873.73 | 0.00 |
December | 0.00 | 0.00 | 0.181807E+11 | 0.116118E+11 | 23238.06 | 11-DEC-06:02 | 11635.26 | 0.00 |
Annual Sum or Average | 0.229704E+12 | 0.134979E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.168170E+11 | 0.103286E+11 | 23238.06 | 9387.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218831E+11 | 0.120448E+11 | 23862.34 | 12244.21 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139734E+10 | 0.32 | 2111.22 | 01-JAN-09:02 | 0.86 |
February | 0.131245E+10 | 0.33 | 2111.22 | 01-FEB-06:02 | 0.87 |
March | 0.154789E+10 | 0.34 | 2111.22 | 01-MAR-06:02 | 0.86 |
April | 0.161272E+10 | 0.36 | 2111.22 | 01-APR-05:02 | 0.86 |
May | 0.180000E+10 | 0.37 | 2111.22 | 01-MAY-05:01 | 0.86 |
June | 0.187095E+10 | 0.39 | 2111.22 | 01-JUN-05:02 | 0.86 |
July | 0.154854E+10 | 0.34 | 2111.22 | 01-JUL-06:02 | 0.86 |
August | 0.167717E+10 | 0.36 | 2111.22 | 01-AUG-05:02 | 0.86 |
September | 0.155600E+10 | 0.35 | 2111.22 | 01-SEP-05:02 | 0.86 |
October | 0.147724E+10 | 0.33 | 2111.22 | 01-OCT-07:02 | 0.86 |
November | 0.138773E+10 | 0.32 | 2111.22 | 01-NOV-06:02 | 0.86 |
December | 0.139457E+10 | 0.32 | 2111.22 | 01-DEC-07:02 | 0.86 |
Annual Sum or Average | 0.185826E+11 | 0.34 | |||
Minimum of Months | 0.131245E+10 | 0.32 | 2111.22 | 0.86 | |
Maximum of Months | 0.187095E+10 | 0.39 | 2111.22 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.826902E+10 | 0.51 | 12160.36 | 01-JAN-09:02 | 1.36 |
February | 0.791207E+10 | 0.53 | 12160.36 | 01-FEB-06:02 | 1.36 |
March | 0.936789E+10 | 0.55 | 12160.36 | 01-MAR-06:02 | 1.36 |
April | 0.996105E+10 | 0.58 | 12160.36 | 01-APR-05:02 | 1.36 |
May | 0.108793E+11 | 0.60 | 12160.36 | 01-MAY-05:01 | 1.35 |
June | 0.110120E+11 | 0.62 | 12160.36 | 01-JUN-05:02 | 1.36 |
July | 0.896505E+10 | 0.54 | 12160.36 | 01-JUL-06:02 | 1.35 |
August | 0.103086E+11 | 0.58 | 12160.36 | 01-AUG-05:02 | 1.36 |
September | 0.964964E+10 | 0.57 | 12160.36 | 01-SEP-05:02 | 1.36 |
October | 0.916343E+10 | 0.54 | 12160.36 | 01-OCT-07:02 | 1.36 |
November | 0.845236E+10 | 0.53 | 12160.36 | 01-NOV-06:02 | 1.35 |
December | 0.828080E+10 | 0.51 | 12160.36 | 01-DEC-07:02 | 1.36 |
Annual Sum or Average | 0.112221E+12 | 0.55 | |||
Minimum of Months | 0.791207E+10 | 0.51 | 12160.36 | 1.35 | |
Maximum of Months | 0.110120E+11 | 0.62 | 12160.36 | 1.36 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.943296E+09 | 0.37 | 1207.16 | 01-JAN-08:62 | 0.89 |
February | 0.879167E+09 | 0.37 | 1207.16 | 01-FEB-06:02 | 0.90 |
March | 0.973239E+09 | 0.38 | 1207.16 | 01-MAR-06:02 | 0.89 |
April | 0.979935E+09 | 0.38 | 1207.16 | 01-APR-05:02 | 0.89 |
May | 0.107337E+10 | 0.39 | 1207.16 | 01-MAY-05:01 | 0.89 |
June | 0.107327E+10 | 0.40 | 1207.16 | 01-JUN-05:02 | 0.89 |
July | 0.909964E+09 | 0.36 | 1207.16 | 01-JUL-06:02 | 0.89 |
August | 0.101279E+10 | 0.38 | 1207.16 | 01-AUG-05:02 | 0.89 |
September | 0.967692E+09 | 0.38 | 1207.16 | 01-SEP-05:02 | 0.89 |
October | 0.956556E+09 | 0.37 | 1207.16 | 01-OCT-07:02 | 0.89 |
November | 0.931734E+09 | 0.37 | 1207.16 | 01-NOV-05:03 | 0.89 |
December | 0.948734E+09 | 0.37 | 1207.16 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.116498E+11 | 0.38 | |||
Minimum of Months | 0.879167E+09 | 0.36 | 1207.16 | 0.89 | |
Maximum of Months | 0.107337E+10 | 0.40 | 1207.16 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.737327E+09 | 0.37 | 930.67 | 01-JAN-09:02 | 0.89 |
February | 0.690108E+09 | 0.38 | 930.67 | 01-FEB-06:02 | 0.90 |
March | 0.757152E+09 | 0.38 | 930.67 | 01-MAR-06:02 | 0.89 |
April | 0.768528E+09 | 0.38 | 930.67 | 01-APR-05:02 | 0.89 |
May | 0.849056E+09 | 0.40 | 930.67 | 01-MAY-05:01 | 0.89 |
June | 0.853011E+09 | 0.41 | 930.67 | 01-JUN-05:02 | 0.89 |
July | 0.702427E+09 | 0.36 | 930.67 | 01-JUL-06:02 | 0.89 |
August | 0.791534E+09 | 0.38 | 930.67 | 01-AUG-05:02 | 0.89 |
September | 0.759326E+09 | 0.38 | 930.67 | 01-SEP-05:02 | 0.89 |
October | 0.745714E+09 | 0.37 | 930.67 | 01-OCT-07:02 | 0.89 |
November | 0.729956E+09 | 0.37 | 930.67 | 01-NOV-06:02 | 0.89 |
December | 0.743456E+09 | 0.37 | 930.67 | 01-DEC-07:02 | 0.89 |
Annual Sum or Average | 0.912759E+10 | 0.38 | |||
Minimum of Months | 0.690108E+09 | 0.36 | 930.67 | 0.89 | |
Maximum of Months | 0.853011E+09 | 0.41 | 930.67 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.00 |
February | 0.17 | 0.00 |
March | 0.58 | 0.00 |
April | 0.62 | 0.00 |
May | 0.83 | 2.45 |
June | 0.94 | 2.89 |
July | 1.12 | 0.00 |
August | 0.31 | 1.12 |
September | 0.75 | 0.00 |
October | 1.00 | 0.00 |
November | 0.33 | 0.00 |
December | 0.33 | 0.00 |
Annual Sum or Average | 7.21 | 0.71 |
Minimum of Months | 0.17 | 0.00 |
Maximum of Months | 1.12 | 2.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.08 | 0.00 |
March | 0.25 | 0.00 |
April | 0.29 | 0.00 |
May | 0.33 | 0.00 |
June | 0.17 | 0.00 |
July | 0.38 | 0.00 |
August | 0.08 | 0.00 |
September | 0.33 | 0.00 |
October | 0.33 | 0.00 |
November | 0.21 | 0.00 |
December | 0.04 | 0.00 |
Annual Sum or Average | 2.58 | 0.00 |
Minimum of Months | 0.04 | 0.00 |
Maximum of Months | 0.38 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.08 | 0.00 |
February | 0.83 | 0.00 |
March | 1.25 | 0.00 |
April | 0.79 | 0.00 |
May | 1.00 | 0.00 |
June | 0.75 | 0.00 |
July | 3.12 | 0.00 |
August | 0.67 | 0.00 |
September | 1.67 | 0.00 |
October | 2.31 | 0.00 |
November | 1.92 | 0.00 |
December | 2.25 | 0.00 |
Annual Sum or Average | 17.64 | 0.00 |
Minimum of Months | 0.67 | 0.00 |
Maximum of Months | 3.12 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 0.00 |
February | 0.50 | 0.00 |
March | 0.75 | 0.00 |
April | 0.62 | 0.00 |
May | 0.50 | 0.00 |
June | 0.50 | 0.00 |
July | 1.12 | 0.00 |
August | 0.25 | 0.00 |
September | 0.75 | 0.00 |
October | 1.25 | 0.00 |
November | 1.00 | 0.00 |
December | 1.00 | 0.00 |
Annual Sum or Average | 8.75 | 0.00 |
Minimum of Months | 0.25 | 0.00 |
Maximum of Months | 1.25 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.58 | 0.00 |
February | 2.33 | 0.00 |
March | 0.08 | 0.00 |
April | 0.17 | 0.00 |
May | 1.22 | 0.00 |
June | 0.50 | 0.00 |
July | 1.17 | 0.00 |
August | 0.42 | 0.00 |
September | 0.33 | 0.00 |
October | 0.64 | 0.00 |
November | 1.64 | 0.00 |
December | 2.36 | 0.00 |
Annual Sum or Average | 14.44 | 0.00 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 3.58 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.813564E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.798014E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.970732E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.103638E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.115201E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.118972E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.965353E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.104419E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.969559E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.899623E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.836473E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.809670E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.114853E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.798014E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.118972E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.423742E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.418006E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.508897E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.549353E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.597349E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.601037E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.479859E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.551597E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.518197E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.486394E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.445909E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.426028E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.600637E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.418006E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.601037E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.605161E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.572227E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.646017E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.659573E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.719160E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.716156E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.595176E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.663082E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.634962E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.620490E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.603363E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.608130E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.764350E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.572227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.719160E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.498274E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.473632E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.530087E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.546209E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.599808E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.599824E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.484430E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.544680E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.524288E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.507923E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.498107E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.501708E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.630897E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.473632E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.599824E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139734E+10 | 0.271808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131245E+10 | 0.267454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154789E+10 | 0.326410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161272E+10 | 0.353651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180000E+10 | 0.396622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187095E+10 | 0.409248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154854E+10 | 0.336079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167717E+10 | 0.366494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155600E+10 | 0.338902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147724E+10 | 0.314936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138773E+10 | 0.289252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139457E+10 | 0.273194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185826E+11 | 0.394405E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131245E+10 | 0.267454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187095E+10 | 0.409248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.826902E+10 | 0.128968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.791207E+10 | 0.127532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936789E+10 | 0.155801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.996105E+10 | 0.171995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108793E+11 | 0.189935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110120E+11 | 0.191103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.896505E+10 | 0.152222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103086E+11 | 0.178300E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.964964E+10 | 0.166864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.916343E+10 | 0.157075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.845236E+10 | 0.141753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.828080E+10 | 0.131802E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112221E+12 | 0.189335E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.791207E+10 | 0.127532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110120E+11 | 0.191103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.943296E+09 | 0.213248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.879167E+09 | 0.199663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.973239E+09 | 0.224741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.979935E+09 | 0.232312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107337E+10 | 0.255946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107327E+10 | 0.254955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.909964E+09 | 0.213808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101279E+10 | 0.240921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.967692E+09 | 0.229882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.956556E+09 | 0.225868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.931734E+09 | 0.217757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.948734E+09 | 0.216712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116498E+11 | 0.272581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.879167E+09 | 0.199663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107337E+10 | 0.255946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.737327E+09 | 0.178448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690108E+09 | 0.168170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757152E+09 | 0.187843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.768528E+09 | 0.196826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.849056E+09 | 0.218706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.853011E+09 | 0.218831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702427E+09 | 0.177596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.791534E+09 | 0.202565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.759326E+09 | 0.194142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.745714E+09 | 0.188823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729956E+09 | 0.183281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.743456E+09 | 0.181807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912759E+10 | 0.229704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.690108E+09 | 0.168170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.853011E+09 | 0.218831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.139734E+10 | 0.00 | 0.00 | 0.00 | 0.673830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131245E+10 | 0.00 | 0.00 | 0.00 | 0.666769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154789E+10 | 0.00 | 0.00 | 0.00 | 0.815943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161272E+10 | 0.00 | 0.00 | 0.00 | 0.875111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.180000E+10 | 0.00 | 0.00 | 0.00 | 0.972007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187095E+10 | 0.00 | 0.00 | 0.00 | 0.100262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154854E+10 | 0.00 | 0.00 | 0.00 | 0.810499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167717E+10 | 0.00 | 0.00 | 0.00 | 0.876472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155600E+10 | 0.00 | 0.00 | 0.00 | 0.813959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147724E+10 | 0.00 | 0.00 | 0.00 | 0.751899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138773E+10 | 0.00 | 0.00 | 0.00 | 0.697699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139457E+10 | 0.00 | 0.00 | 0.00 | 0.670213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185826E+11 | 0.00 | 0.00 | 0.00 | 0.962702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.131245E+10 | 0.00 | 0.00 | 0.00 | 0.666769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187095E+10 | 0.00 | 0.00 | 0.00 | 0.100262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.826902E+10 | 0.00 | 0.00 | 0.00 | 0.341052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.791207E+10 | 0.00 | 0.00 | 0.00 | 0.338885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.936789E+10 | 0.00 | 0.00 | 0.00 | 0.415218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.996105E+10 | 0.00 | 0.00 | 0.00 | 0.449743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108793E+11 | 0.00 | 0.00 | 0.00 | 0.488556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110120E+11 | 0.00 | 0.00 | 0.00 | 0.490916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.896505E+10 | 0.00 | 0.00 | 0.00 | 0.390208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103086E+11 | 0.00 | 0.00 | 0.00 | 0.448511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.964964E+10 | 0.00 | 0.00 | 0.00 | 0.421700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.916343E+10 | 0.00 | 0.00 | 0.00 | 0.394760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.845236E+10 | 0.00 | 0.00 | 0.00 | 0.361385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.828080E+10 | 0.00 | 0.00 | 0.00 | 0.343220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112221E+12 | 0.00 | 0.00 | 0.00 | 0.488415E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.791207E+10 | 0.00 | 0.00 | 0.00 | 0.338885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110120E+11 | 0.00 | 0.00 | 0.00 | 0.490916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.943296E+09 | 0.00 | 0.00 | 0.00 | 0.510832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.879167E+09 | 0.00 | 0.00 | 0.00 | 0.484310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.973239E+09 | 0.00 | 0.00 | 0.00 | 0.548693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.979935E+09 | 0.00 | 0.00 | 0.00 | 0.561579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107337E+10 | 0.00 | 0.00 | 0.00 | 0.611822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107327E+10 | 0.00 | 0.00 | 0.00 | 0.608828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.909964E+09 | 0.00 | 0.00 | 0.00 | 0.504179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101279E+10 | 0.00 | 0.00 | 0.00 | 0.561803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.967692E+09 | 0.00 | 0.00 | 0.00 | 0.538192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.956556E+09 | 0.00 | 0.00 | 0.00 | 0.524835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.931734E+09 | 0.00 | 0.00 | 0.00 | 0.510189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.948734E+09 | 0.00 | 0.00 | 0.00 | 0.513257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116498E+11 | 0.00 | 0.00 | 0.00 | 0.647852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.879167E+09 | 0.00 | 0.00 | 0.00 | 0.484310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107337E+10 | 0.00 | 0.00 | 0.00 | 0.611822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.737327E+09 | 0.00 | 0.00 | 0.00 | 0.424541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.690108E+09 | 0.00 | 0.00 | 0.00 | 0.404621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.757152E+09 | 0.00 | 0.00 | 0.00 | 0.454372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.768528E+09 | 0.00 | 0.00 | 0.00 | 0.469357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.849056E+09 | 0.00 | 0.00 | 0.00 | 0.514903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.853011E+09 | 0.00 | 0.00 | 0.00 | 0.514523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702427E+09 | 0.00 | 0.00 | 0.00 | 0.414187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.791534E+09 | 0.00 | 0.00 | 0.00 | 0.465526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.759326E+09 | 0.00 | 0.00 | 0.00 | 0.448355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.745714E+09 | 0.00 | 0.00 | 0.00 | 0.433352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.729956E+09 | 0.00 | 0.00 | 0.00 | 0.425111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.743456E+09 | 0.00 | 0.00 | 0.00 | 0.427363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.912759E+10 | 0.00 | 0.00 | 0.00 | 0.539621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.690108E+09 | 0.00 | 0.00 | 0.00 | 0.404621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.853011E+09 | 0.00 | 0.00 | 0.00 | 0.514903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13622397.98 | 0.752300E+10 | 0.00 | 572242.19 | 85269228.54 | 0.00 | 4471631.76 | 0.00 | 0.22 |
February | 23284.24 | 0.770513E+10 | 0.00 | 395868.10 | 77555410.24 | 0.00 | 3428293.83 | 0.00 | 0.22 |
March | 0.00 | 0.946397E+10 | 0.00 | 0.00 | 78450020.50 | 0.00 | 0.00 | 0.00 | 0.23 |
April | 0.00 | 0.118360E+11 | 0.00 | 0.00 | 82658082.29 | 0.00 | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.141543E+11 | 0.00 | 0.00 | 0.101614E+09 | 0.00 | 0.00 | 0.00 | 0.23 |
June | 0.00 | 0.144053E+11 | 0.00 | 0.00 | 75765666.30 | 0.00 | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.105903E+11 | 0.00 | 0.00 | 0.131285E+09 | 0.00 | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.132040E+11 | 0.00 | 0.00 | 0.133661E+09 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.122109E+11 | 0.00 | 0.00 | 0.140123E+09 | 0.00 | 0.00 | 0.00 | 0.22 |
October | 0.00 | 0.113130E+11 | 0.00 | 0.00 | 0.155319E+09 | 0.00 | 0.00 | 0.00 | 0.22 |
November | 802867.09 | 0.964222E+10 | 0.00 | 120007.94 | 0.127039E+09 | 0.00 | 1303728.12 | 0.00 | 0.22 |
December | 6304624.76 | 0.814925E+10 | 0.00 | 95760.65 | 0.110092E+09 | 0.00 | 385894.71 | 0.00 | 0.22 |
Annual Sum or Average | 20753174.08 | 0.130197E+12 | 0.00 | 1183878.87 | 0.129883E+10 | 0.00 | 9589548.41 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.752300E+10 | 0.00 | 0.00 | 75765666.30 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 13622397.98 | 0.144053E+11 | 0.00 | 572242.19 | 0.155319E+09 | 0.00 | 4471631.76 | 0.00 | 0.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112647E+09 | 0.565005E+11 | 0.00 | 2162573.54 | 0.112967E+10 | 0.00 | 44505541.67 | 0.00 | 0.43 |
February | 5379863.92 | 0.579123E+11 | 0.00 | 1360861.36 | 0.113838E+10 | 0.00 | 22726358.45 | 0.00 | 0.43 |
March | 0.00 | 0.727721E+11 | 0.00 | 0.00 | 0.134153E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.00 | 0.900551E+11 | 0.00 | 0.00 | 0.134566E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
May | 0.00 | 0.106676E+12 | 0.00 | 0.00 | 0.137798E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.107460E+12 | 0.00 | 0.00 | 0.113020E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.759003E+11 | 0.00 | 0.00 | 0.189919E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.987619E+11 | 0.00 | 0.00 | 0.166661E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.907587E+11 | 0.00 | 0.00 | 0.160434E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.839473E+11 | 0.00 | 0.00 | 0.183470E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 11653161.57 | 0.713642E+11 | 0.00 | 356007.54 | 0.150134E+10 | 0.00 | 967216.89 | 0.00 | 0.43 |
December | 27885096.94 | 0.604708E+11 | 0.00 | 256243.62 | 0.136789E+10 | 0.00 | 2968019.22 | 0.00 | 0.43 |
Annual Sum or Average | 0.157565E+09 | 0.972579E+12 | 0.00 | 4135686.05 | 0.173375E+11 | 0.00 | 71167136.23 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.565005E+11 | 0.00 | 0.00 | 0.112967E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.112647E+09 | 0.107460E+12 | 0.00 | 2162573.54 | 0.189919E+10 | 0.00 | 44505541.67 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 876264.52 | 0.666871E+10 | 0.00 | 329521.07 | 40648524.98 | 0.00 | 6908605.46 | 0.00 | 0.43 |
February | 0.00 | 0.659420E+10 | 0.00 | 112130.92 | 46807145.32 | 0.00 | 832022.18 | 0.00 | 0.43 |
March | 0.00 | 0.785271E+10 | 0.00 | 31680.18 | 47430173.58 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.00 | 0.944474E+10 | 0.00 | 0.00 | 53947215.58 | 0.00 | 0.00 | 0.00 | 0.44 |
May | 0.00 | 0.111555E+11 | 0.00 | 0.00 | 68970773.11 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.111743E+11 | 0.00 | 0.00 | 59796223.54 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.834522E+10 | 0.00 | 0.00 | 90537125.06 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.104958E+11 | 0.00 | 0.00 | 73992389.20 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.979554E+10 | 0.00 | 0.00 | 79772954.23 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.934048E+10 | 0.00 | 0.00 | 81524347.22 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 78966.80 | 0.818553E+10 | 0.00 | 48733.64 | 70090001.93 | 0.00 | 623758.43 | 0.00 | 0.43 |
December | 1386883.98 | 0.720234E+10 | 0.00 | 94603.56 | 55762450.24 | 0.00 | 2029900.07 | 0.00 | 0.43 |
Annual Sum or Average | 2342115.29 | 0.106255E+12 | 0.00 | 616669.38 | 0.769279E+09 | 0.00 | 10394286.12 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.659420E+10 | 0.00 | 0.00 | 40648524.98 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 1386883.98 | 0.111743E+11 | 0.00 | 329521.07 | 90537125.06 | 0.00 | 6908605.46 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8180419.51 | 0.637543E+10 | 0.00 | 262330.72 | 42716592.97 | 0.00 | 4046593.83 | 0.00 | 0.43 |
February | 12743.39 | 0.633263E+10 | 0.00 | 149992.03 | 49768670.48 | 0.00 | 2461678.16 | 0.00 | 0.43 |
March | 0.00 | 0.748336E+10 | 0.00 | 11064.11 | 52185963.89 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.00 | 0.902116E+10 | 0.00 | 0.00 | 68617190.95 | 0.00 | 0.00 | 0.00 | 0.44 |
May | 0.00 | 0.106709E+11 | 0.00 | 0.00 | 74033048.41 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.107269E+11 | 0.00 | 0.00 | 65443218.49 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.785576E+10 | 0.00 | 0.00 | 98902056.36 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.989997E+10 | 0.00 | 0.00 | 96275881.71 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.928735E+10 | 0.00 | 0.00 | 0.101380E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.877613E+10 | 0.00 | 0.00 | 0.117876E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 564589.61 | 0.780190E+10 | 0.00 | 51265.00 | 67119806.90 | 0.00 | 1127177.04 | 0.00 | 0.43 |
December | 4266770.20 | 0.687659E+10 | 0.00 | 80686.50 | 52115388.85 | 0.00 | 752521.58 | 0.00 | 0.43 |
Annual Sum or Average | 13024522.70 | 0.101108E+12 | 0.00 | 555338.36 | 0.886433E+09 | 0.00 | 8387970.61 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.633263E+10 | 0.00 | 0.00 | 42716592.97 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 8180419.51 | 0.107269E+11 | 0.00 | 262330.72 | 0.117876E+09 | 0.00 | 4046593.83 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:13
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |