Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2020-06-03 19:12:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1101.29 | 480.08 | 480.08 |
Net Site Energy | 1101.29 | 480.08 | 480.08 |
Total Source Energy | 2965.04 | 1292.52 | 1292.52 |
Net Source Energy | 2965.04 | 1292.52 | 1292.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 160.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 215.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 256.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 42.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.90 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 850.33 | 250.96 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 160.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 215.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 256.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 42.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 195.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 140.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 90.90 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 130.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 155.11 | 109.40 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 370.68 | 109.40 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 130.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 155.11 | 109.40 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 85.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 370.68 | 109.40 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 850.330 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 850.330 | 100.00 |
Total On-Site and Utility Electric Sources | 850.330 | 100.00 |
Total Electricity End Uses | 850.330 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1164.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 5.1793 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 11.8188 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 11.8188 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 10.7081 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-JUL-15:00 | 12-FEB-09:09 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 204918.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49770.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16205.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10324.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4545.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 87071.58 | 209464.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 204918.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49770.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16205.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 10324.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4545.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 173.51 | 0.00 | 0.00 | 0.00 |
Cooling | 681.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 812.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 135.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 618.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 445.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 98.54 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2692.99 | 272.05 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 75.64 | 0.00 | 0.00 | 0.00 |
Cooling | 296.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 354.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 58.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 42.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1173.93 | 118.59 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 75.64 | 0.00 | 0.00 | 0.00 |
Cooling | 296.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 354.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 58.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 269.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 42.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1173.93 | 118.59 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 1.83 |
CORE_RETAIL DIRECT AIR | 6.86 |
POINT_OF_SALE DIRECT AIR | 1.07 |
FRONT_RETAIL DIRECT AIR | 0.804126 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 1.14 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 1.14 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 32555.74 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 48052.38 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 213149.09 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 29399.46 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 23567.36 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 1.83 | 1.83 | 1.83 | 1.83 | 1.85 | 1.85 | 1.00 | 0.987320 | 1.85 |
PSZ-AC:2 | 6.86 | 6.86 | 6.86 | 6.86 | 7.12 | 7.12 | 1.00 | 0.963706 | 7.12 |
PSZ-AC:3 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.07 | 1.00 | 1.00 | 1.07 |
PSZ-AC:4 | 0.804126 | 0.804126 | 0.804126 | 0.804126 | 0.807363 | 0.807363 | 1.00 | 0.995991 | 0.807363 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 1.85 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 7.12 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.07 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 0.807363 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 1.85 | 1.85 | 1.85 | 1.22 | 36287.06 | 48052.38 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 7.12 | 7.12 | 7.12 | 4.70 | 171157.08 | 213149.09 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 0.703498 | 22388.96 | 29399.46 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 0.807363 | 0.807363 | 0.807363 | 0.807363 | 18091.50 | 23567.36 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 1.85 | 0.925475 | 1.23 | 33964.10 | 36287.06 | 18143.53 | 18143.53 | 0.741438 | 0.741440 | 0.741440 | 0.741440 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 7.12 | 3.56 | 4.75 | 162490.70 | 171157.08 | 85578.54 | 85578.54 | 0.684159 | 0.684160 | 0.684160 | 0.684160 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.07 | 0.532955 | 0.710607 | 21035.54 | 22388.96 | 11194.48 | 11194.48 | 0.720747 | 0.720750 | 0.720750 | 0.720750 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 0.807360 | 0.403680 | 0.538240 | 17086.32 | 18091.50 | 9045.75 | 9045.75 | 0.702597 | 0.702600 | 0.702600 | 0.702600 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.85 | 1980.61 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 7.12 | 11994.52 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1180.13 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 0.807363 | 893.88 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 5.179 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.249 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 33.339 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 11.819 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 15.049 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 1967.547 | 5.179 | 32.075 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1967.547 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 18915.745 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18915.745 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 1782.389 | 11.819 | 73.194 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.389 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.760 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.7800 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5681 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7602635 | 1.7602635 | 1.7602635 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | -0.41768822E-14 | 0.27520919E-16 | -0.15672466E-09 | 0.83927561E-16 |
25 | 8 | 0.22856702E-07 | 0.10578700E-12 | 0.38803401E-03 | -0.25988854E-09 |
26 | 7 | -0.12546900E-01 | 0.54357740E-08 | -0.23525379E-01 | 0.14266284E-03 |
27 | 6 | 0.41364683 | 0.18861797E-05 | 0.47915075 | -0.48455579E-02 |
28 | 5 | -5.2715232 | 0.70271773E-04 | -4.4954566 | 0.64187715E-01 |
29 | 4 | 33.360936 | 0.57369956E-03 | 21.652120 | -0.42687724 |
30 | 3 | -111.98802 | 0.12481219E-02 | -56.042688 | 1.5262008 |
31 | 2 | 197.88617 | 0.70096321E-03 | 78.258916 | -2.9127067 |
32 | 1 | -171.44340 | 0.74721452E-04 | -55.366563 | 2.7504751 |
33 | 0 | 57.057407 | 0.42462867E-06 | 15.540328 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.46_SHGC_0.25 | 30 | 1 | VerySmooth | 2.615 | 0.252 | 0.162 | 0.251 |
2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 31 | 1 | VerySmooth | 5.108 | 0.600 | 0.461 | 0.601 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.53892E-002 | 0.16139 | 0.61607 | 0.61607 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.46039 | 0.10300 | 0.10300 | 0.60000 | 0.13030 | 0.15164 | 0.00000 | 0.84000 | 0.84000 | 6.93520E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1928 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.937 | 7.811E-002 | 2.576E-002 | 46.096 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 20815.47359 | 24978.56831 | 1.52290 | 1.82748 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 21695.49719 | 26034.59663 | 0.94596 | 1.13516 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 78500.39469 | 94200.47363 | 5.71768 | 6.86122 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 53976.20756 | 64771.44907 | 2.31978 | 2.78373 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 12006.36455 | 14407.63746 | 0.88825 | 1.06591 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10703.85750 | 12844.62899 | 0.46868 | 0.56242 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 9130.09245 | 10956.11094 | 0.67011 | 0.80413 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44457E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10706.94797 | 12848.33757 | 0.46882 | 0.56258 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40000 | 1.44457E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 27122.39166 | 32546.86999 | 0.95130 | 1.14156 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | -6.30000 | 2.29779E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 25039.44 | 1.85095 | 1.85095 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 32632.82 | 1.13516 | 1.13516 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 108202.15 | 7.11962 | 7.11962 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 122059.51 | 2.78373 | 2.78373 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 15344.10 | 1.06591 | 1.06591 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 18182.41 | 0.56242 | 0.56242 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 12473.61 | 0.80736 | 0.80736 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 18186.09 | 0.56258 | 0.56258 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.82748 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.86122 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06591 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.80413 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.14156 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.14156 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 32555.73726 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.82748 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.82748 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.82748 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.82748 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.85095 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.85095 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 0.98732 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.86122 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.86122 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.86122 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 6.86122 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 7.11962 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 7.11962 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.96371 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06591 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06591 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06591 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06591 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06591 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06591 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.80413 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.80413 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.80413 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.80413 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.80736 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 0.80736 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 0.99599 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 1.85095 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 7.11962 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.06591 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 0.80736 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.85095 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.85095 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.85095 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.85095 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22163 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.85095 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.92548 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23397 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 33964.10319 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 36287.06000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 18143.53000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 18143.53000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.74144 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.74144 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.74144 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.74144 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36287.06000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 48052.37846 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.85095 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1980.60617 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 48052.37846 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 7.11962 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 7.11962 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 7.11962 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 7.11962 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 4.69895 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 7.11962 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.55981 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.74641 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 162490.69719 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 171157.08000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 85578.54000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 85578.54000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.68416 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.68416 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.68416 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.68416 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 171157.08000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 213149.08837 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 7.11962 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 11994.52032 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 213149.08837 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06591 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06591 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06591 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06591 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.70350 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06591 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53296 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.71061 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 21035.53624 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 22388.96000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11194.48000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11194.48000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72075 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72075 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72075 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72075 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22388.96000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29399.45613 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06591 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1180.12639 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 29399.45613 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.80736 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.80736 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.80736 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.80736 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.80736 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.80736 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.40368 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.53824 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 17086.31601 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 18091.50000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 9045.75000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 9045.75000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70260 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70260 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70260 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70260 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18091.50000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23567.35744 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.80736 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 893.87853 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23567.35744 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 34832.9 | 11.49 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 165543.9 | 13.08 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21550.6 | 119.77 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17455.8 | 172.48 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.760 | 1.760 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | N/A | 5.108 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 4.6315234661E-002 | 0.1947711746 | Pass | Pass | 1.1133704101 | 12.4402047921 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.3485685259E-002 | 0.1354811882 | Pass | Pass | 0.1831046419 | 0.7320565096 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 4.6957723089E-002 | 0.1884859709 | Pass | Pass | 0.5303895428 | 3.0644712775 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 5.5181846360E-002 | 0.2375881498 | Pass | Pass | 7.5000616357E-002 | 0.2886968975 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1388033926 | 0.5863039404 | Pass | Pass | 6.1557236785E-002 | 0.6150020739 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.9_SHGC_0.6 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 5.108 | 0.600 | 0.601 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.615 | 0.252 | 0.251 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.615 | 0.252 | 0.251 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.46_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 2.615 | 0.252 | 0.251 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.165 | 0.329 | 0.328 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.165 | 0.329 | 0.328 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 1.393 | 1.760 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 5.1793 | 379.89 | 1967.55 | LightsWired | BLDG_LIGHT_BACK_SCH | 60.89 | 168.00 | 60.06 | 0.0000 | Y | 22.18 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 11.8188 | 1600.48 | 18915.75 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 52.76 | 0.0000 | Y | 187.33 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 11.8188 | 150.81 | 1782.39 | LightsWired | BLDG_LIGHT_FRONT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 22.84 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 1.49 |
Interior Lighting Total | 10.7081 | 2293.99 | 24564.32 | 256.67 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 18915.75 | 4728.94 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 238.00 | AstronomicalClock | - | 41.77 | 41.77 | 1.87 | |
EXTERIOR_LIGHTS_B | 3054.90 | AstronomicalClock | - | 83.77 | 71.17 | 40.81 | |
Exterior Lighting Total | 3292.90 | 42.68 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 36287.06 | 26904.68 | 9382.38 | 0.74 | 3.80 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 171157.08 | 117098.83 | 54058.25 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 22388.96 | 16136.84 | 6252.12 | 0.72 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 18091.50 | 12711.09 | 5380.41 | 0.70 | 4.12 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 34832.9 | 11.49 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 165543.9 | 13.08 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 21550.6 | 119.77 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 17455.8 | 172.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 32555.74 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 48052.38 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 213149.09 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 29399.46 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23567.36 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 1.14 | 1263.89 | 1107.16 | 1.00 | 1.36 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.85 | 1980.61 | 1070.05 | 1.00 | 1.33 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 7.12 | 11994.52 | 1684.71 | 1.00 | 1.16 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1180.13 | 1107.16 | 1.00 | 1.39 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.81 | 893.88 | 1107.16 | 1.00 | 1.46 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 20815.47 | 24978.57 | 65.75 | 1.523 | 1.827 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.00994 | 27.37 | 0.01445 | 0.232 | 0.00 |
CORE_RETAIL | 78500.39 | 94200.47 | 58.86 | 5.718 | 6.861 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.01013 | 27.37 | 0.01445 | 1.890 | 0.00 |
POINT_OF_SALE | 12006.36 | 14407.64 | 95.54 | 0.888 | 1.066 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.89 | 0.00908 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_RETAIL | 9130.09 | 10956.11 | 72.65 | 0.670 | 0.804 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.89 | 23.88 | 0.00973 | 27.37 | 0.01445 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 33.73 | 100.00 | 0.00001 | 34.40 | 0.01445 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 21695.50 | 26034.60 | 68.53 | 0.946 | 1.135 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00744 | -6.30 | 0.00230 | 0.232 | 0.00 |
CORE_RETAIL | 53976.21 | 64771.45 | 40.47 | 2.320 | 2.784 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00746 | -6.30 | 0.00230 | 1.890 | 0.00 |
POINT_OF_SALE | 10703.86 | 12844.63 | 85.17 | 0.469 | 0.562 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00765 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_RETAIL | 10706.95 | 12848.34 | 85.20 | 0.469 | 0.563 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00765 | -6.30 | 0.00230 | 0.178 | 0.00 |
FRONT_ENTRY | 27122.39 | 32546.87 | 2712.24 | 0.951 | 1.142 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 16.00 | 15.91 | 0.00504 | -6.30 | 0.00230 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 1.85 | 1.85 | 1.14 | 1.14 | 1.8510 | 1.8275 | 1.8510 | 0.9873 | 1.0000 |
PSZ-AC:2 | 7.12 | 7.12 | 2.78 | 2.78 | 7.1196 | 6.8612 | 7.1196 | 0.9637 | 1.0000 |
PSZ-AC:3 | 1.07 | 1.07 | 0.56 | 0.56 | 1.0659 | 1.0659 | 1.0659 | 1.0000 | 1.0000 |
PSZ-AC:4 | 0.81 | 0.81 | 0.56 | 0.56 | 0.8074 | 0.8041 | 0.8074 | 0.9960 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 32555.737 | 32555.737 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 32555.74 | 32555.74 | 1.141565 | 15.63 | 9.34 | 0.00500578 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 15.91 | 0.00503982 | 43.4230 | 32546.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 18143.530 | 0.000 | 1.850950 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18143.53 | 13630.46 | 1.850950 | 24.40 | 17.60 | 0.01027155 | 12.80 | 11.77 | 0.00850000 | 27.97 | 0.01444568 | 21.76 | 12.5107 | 23.88 | 0.00994178 | 51.8386 | 20815.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 48052.378 | 48052.378 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48052.38 | 48052.38 | 1.850952 | 15.36 | 10.69 | 0.00639106 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 12.5107 | 21.11 | 0.00744006 | 46.1063 | 21695.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 85578.540 | 0.000 | 7.119620 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 85578.54 | 62914.29 | 7.119620 | 26.91 | 18.81 | 0.01078642 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 26.5493 | 23.88 | 0.01013393 | 52.8257 | 77929.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 213149.088 | 213149.088 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 213149.09 | 213149.09 | 7.119615 | 2.41 | 1.44 | 0.00395366 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 26.5494 | 21.11 | 0.00745660 | 46.2052 | 53976.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 11194.480 | 0.000 | 1.065910 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11194.48 | 8946.24 | 1.065910 | 25.73 | 17.80 | 0.00997739 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 16.7097 | 23.89 | 0.00908159 | 47.4100 | 11138.76 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 29399.456 | 29399.456 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29399.46 | 29399.46 | 1.065905 | 12.29 | 8.88 | 0.00595169 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 16.7098 | 21.11 | 0.00764512 | 47.3603 | 10703.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 9045.750 | 0.000 | 0.807360 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 9045.75 | 6931.09 | 0.807360 | 26.24 | 18.27 | 0.01035565 | 12.80 | 11.77 | 0.00850000 | 34.40 | 0.01444567 | 23.51 | 22.0609 | 23.88 | 0.00972593 | 50.7291 | 8709.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 23567.357 | 23567.357 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23567.36 | 23567.36 | 0.807363 | 12.29 | 8.89 | 0.00595239 | 40.00 | 20.73 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 22.0608 | 21.11 | 0.00764541 | 47.3621 | 10706.95 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 32555.737 | 32555.737 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 1.141565 | 1.32532991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:10:00 | 32555.74 | 32555.74 | 1.0000 | 1.32532991 | 1.141565 | 15.63 | 9.34 | 0.00500578 | 28375.2 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32555.74 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 15.92 | 0.00503982 | 15.91 | 0.00503982 | 43.4230 | 32546.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18143.530 | 0.000 | 1.850950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9343 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 18143.53 | 13630.46 | 1.0000 | 2.14890953 | 1.850950 | 24.40 | 17.60 | 0.01027155 | 50668.2 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18143.53 | 27.97 | 0.01444568 | 21.76 | 0.23156651 | 12.5107 | 23.88 | 0.00967466 | 23.88 | 0.00994178 | 51.8386 | 20815.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 48052.378 | 48052.378 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.850952 | 2.14891189 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48052.38 | 48052.38 | 1.0000 | 2.14891189 | 1.850952 | 15.36 | 10.69 | 0.00639106 | 31598.8 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48052.38 | -6.30 | 0.00229779 | -6.30 | 0.23156651 | 12.5107 | 20.91 | 0.00744006 | 21.11 | 0.00744006 | 46.1063 | 21695.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 85578.540 | 0.000 | 7.119620 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8914 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 85578.54 | 62914.29 | 1.0000 | 8.26571180 | 7.119620 | 26.91 | 18.81 | 0.01078642 | 54557.0 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85578.54 | 34.40 | 0.01444567 | 23.51 | 1.89021192 | 26.5493 | 23.89 | 0.00930931 | 23.88 | 0.01013393 | 52.8257 | 77929.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 213149.088 | 213149.088 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 7.119615 | 8.26570647 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 213149.09 | 213149.09 | 1.0000 | 8.26570647 | 7.119615 | 2.41 | 1.44 | 0.00395366 | 12332.2 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 213149.09 | -6.30 | 0.00229779 | -6.30 | 1.89021192 | 26.5494 | 20.85 | 0.00745660 | 21.11 | 0.00745660 | 46.2052 | 53976.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11194.480 | 0.000 | 1.065910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3875 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 11194.48 | 8946.24 | 1.0000 | 1.23749650 | 1.065910 | 25.73 | 17.80 | 0.00997739 | 51282.9 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11194.48 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 16.7097 | 23.89 | 0.00902909 | 23.89 | 0.00908159 | 47.4100 | 11138.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29399.456 | 29399.456 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.065905 | 1.23749107 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29399.46 | 29399.46 | 1.0000 | 1.23749107 | 1.065905 | 12.29 | 8.88 | 0.00595169 | 27368.5 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29399.46 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 16.7098 | 20.90 | 0.00764512 | 21.11 | 0.00764512 | 47.3603 | 10703.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 9045.750 | 0.000 | 0.807360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0906 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 9045.75 | 6931.09 | 1.0000 | 0.93732602 | 0.807360 | 26.24 | 18.27 | 0.01035565 | 52772.7 | 12.80 | 11.77 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9045.75 | 34.40 | 0.01444567 | 23.51 | 0.17811053 | 22.0609 | 23.89 | 0.00917561 | 23.88 | 0.00972593 | 50.7291 | 8709.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23567.357 | 23567.357 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.807363 | 0.93732901 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23567.36 | 23567.36 | 1.0000 | 0.93732901 | 0.807363 | 12.29 | 8.89 | 0.00595239 | 27372.8 | 40.00 | 20.73 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23567.36 | -6.30 | 0.00229779 | -6.30 | 0.17811053 | 22.0608 | 20.90 | 0.00764541 | 21.11 | 0.00764541 | 47.3621 | 10706.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC:1_OA_CONTROLLER | DifferentialEnthalpy | 0.23 | 1.85 | - | |||
PSZ-AC:2_OA_CONTROLLER | DifferentialEnthalpy | 1.89 | 7.12 | - | |||
PSZ-AC:3_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 1.07 | - | |||
PSZ-AC:4_OA_CONTROLLER | DifferentialEnthalpy | 0.18 | 0.81 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 2802.50 | 2720.17 | 1066.33 |
CORE_RETAIL | 2693.83 | 2291.33 | 571.17 |
POINT_OF_SALE | 2773.33 | 1928.50 | 411.50 |
FRONT_RETAIL | 2749.17 | 2415.17 | 774.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 3311.50 | 2821.50 | 1164.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 1.33 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.83 | 0.00 | 0.00 | 0.00 |
FRONT_RETAIL | 1.83 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | 387.17 | 0.00 | 0.00 | 0.00 |
Facility | 390.50 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.510 | 0.029 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.794 | 0.006 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.970 | 0.032 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.959 | 0.032 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.351 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.681 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.681 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 850.33 | 2865.76 | 14-MAY-07:00 | 87071.58 | 08-JUL-16:00 |
Electricity:Building | 451.83 | 2708.13 | 14-MAY-08:00 | 32651.56 | 02-JAN-15:30 |
Electricity:Zone:BACK_SPACE | 72.17 | 558.23 | 01-JAN-00:10 | 4302.56 | 02-JAN-09:10 |
InteriorLights:Electricity | 256.67 | 912.95 | 14-MAY-08:00 | 21880.52 | 02-JAN-15:30 |
InteriorLights:Electricity:Zone:BACK_SPACE | 22.18 | 98.38 | 01-JAN-00:10 | 1543.42 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 256.67 | 912.95 | 14-MAY-08:00 | 21880.52 | 02-JAN-15:30 |
Electricity:Zone:CORE_RETAIL | 271.63 | 1405.96 | 14-MAY-08:00 | 21676.77 | 02-JAN-15:30 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 187.33 | 630.52 | 14-MAY-08:00 | 17024.17 | 02-JAN-15:30 |
Electricity:Zone:POINT_OF_SALE | 75.76 | 575.93 | 01-JAN-00:10 | 4525.04 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 30.78 | 162.19 | 01-JAN-00:10 | 2042.55 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 22.84 | 89.12 | 01-JAN-00:10 | 1604.15 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.49 | 5.81 | 01-JAN-00:10 | 104.63 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.99 | 459.86 | 01-JAN-00:10 | 2759.14 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 195.16 | 1795.17 | 01-JAN-00:10 | 10771.04 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 84.30 | 775.43 | 01-JAN-00:10 | 4652.60 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.92 | 486.81 | 01-JAN-00:10 | 2920.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.94 | 73.07 | 01-JAN-00:10 | 438.40 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 850.33 | 2865.76 | 14-MAY-07:00 | 87071.58 | 08-JUL-16:00 |
ElectricityPurchased:Plant | 850.33 | 2865.76 | 14-MAY-07:00 | 87071.58 | 08-JUL-16:00 |
Cogeneration:ElectricityPurchased | 850.33 | 2865.76 | 14-MAY-07:00 | 87071.58 | 08-JUL-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 850.33 | 2865.76 | 14-MAY-07:00 | 87071.58 | 08-JUL-16:00 |
ElectricityNet:Plant | 850.33 | 2865.76 | 14-MAY-07:00 | 87071.58 | 08-JUL-16:00 |
Cogeneration:ElectricityNet | 850.33 | 2865.76 | 14-MAY-07:00 | 87071.58 | 08-JUL-16:00 |
Electricity:HVAC | 355.82 | 0.00 | 01-JAN-00:10 | 61229.05 | 08-JUL-14:10 |
Fans:Electricity | 140.78 | 0.00 | 01-JAN-00:10 | 12787.34 | 12-FEB-09:10 |
General:Fans:Electricity | 140.78 | 0.00 | 01-JAN-00:10 | 12787.34 | 12-FEB-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 215.04 | 0.00 | 01-JAN-00:10 | 50612.02 | 08-JUL-14:20 |
ExteriorLights:Electricity | 42.68 | 0.00 | 01-JAN-07:50 | 3292.90 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 42.68 | 0.00 | 01-JAN-07:50 | 3292.90 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 250.96 | 1862.00 | 26-FEB-08:10 | 209464.07 | 12-FEB-09:10 |
Gas:Plant | 90.90 | 1862.00 | 08-JAN-07:10 | 5042.02 | 01-FEB-12:10 |
WaterSystems:Gas | 90.90 | 1862.00 | 08-JAN-07:10 | 5042.02 | 01-FEB-12:10 |
Water Heater:WaterSystems:Gas | 90.90 | 1862.00 | 08-JAN-07:10 | 5042.02 | 01-FEB-12:10 |
Gas:HVAC | 160.06 | 0.00 | 01-JAN-00:10 | 204918.84 | 12-FEB-09:10 |
Heating:Gas | 160.06 | 0.00 | 01-JAN-00:10 | 204918.84 | 12-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 1587.40 | 0.00 | 01-JAN-00:10 | 265673.29 | 12-FEB-09:10 |
EnergyTransfer:Building | 633.65 | 0.00 | 01-JAN-00:10 | 108659.49 | 09-JAN-07:10 |
EnergyTransfer:Zone:BACK_SPACE | 88.68 | 0.00 | 01-JAN-00:10 | 23839.73 | 13-FEB-06:10 |
Heating:EnergyTransfer | 43.13 | 0.00 | 01-JAN-00:10 | 108105.36 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 11.90 | 0.00 | 01-JAN-00:10 | 23839.73 | 13-FEB-06:10 |
Cooling:EnergyTransfer | 590.52 | 0.00 | 01-JAN-00:10 | 81893.53 | 07-JUL-14:50 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 76.78 | 0.00 | 01-JAN-00:10 | 13664.37 | 08-JUL-15:30 |
EnergyTransfer:Zone:CORE_RETAIL | 406.51 | 0.00 | 01-JAN-00:10 | 71105.37 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 11.58 | 0.00 | 01-JAN-00:10 | 65030.49 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 394.93 | 0.00 | 01-JAN-00:10 | 58955.97 | 12-OCT-06:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 75.66 | 0.00 | 01-JAN-00:10 | 10368.89 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 2.01 | 0.00 | 01-JAN-00:10 | 10368.89 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 73.65 | 0.00 | 01-JAN-00:10 | 9740.10 | 19-AUG-14:00 |
EnergyTransfer:Zone:FRONT_RETAIL | 49.44 | 0.00 | 01-JAN-00:10 | 10958.20 | 12-FEB-08:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 4.28 | 0.00 | 01-JAN-00:10 | 10958.20 | 12-FEB-08:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 45.16 | 0.00 | 01-JAN-00:10 | 7648.59 | 19-AUG-14:00 |
EnergyTransfer:Zone:FRONT_ENTRY | 13.36 | 0.00 | 01-JAN-00:10 | 25240.50 | 07-JAN-18:00 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 13.36 | 0.00 | 01-JAN-00:10 | 25240.50 | 07-JAN-18:00 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 953.75 | 0.00 | 01-JAN-00:10 | 177760.44 | 08-JUL-14:00 |
HeatingCoils:EnergyTransfer | 128.05 | 0.00 | 01-JAN-00:10 | 163935.07 | 12-FEB-09:10 |
CoolingCoils:EnergyTransfer | 825.70 | 0.00 | 01-JAN-00:10 | 177760.44 | 08-JUL-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 11.897 | -76.782 | 0.000 | 0.000 | 38.448 | 22.181 | 49.992 | 0.000 | 0.000 | 0.548 | 0.000 | 0.000 | 0.000 | 0.000 | -11.461 | -34.824 |
CORE_RETAIL | 0.000 | 0.000 | 11.585 | -394.923 | 0.000 | 0.000 | 161.593 | 187.331 | 84.299 | 73.927 | 0.000 | 0.452 | 0.000 | 0.000 | -21.802 | 0.000 | -10.192 | -92.269 |
POINT_OF_SALE | 0.000 | 0.000 | 2.005 | -73.649 | 0.000 | 0.000 | 14.972 | 22.836 | 52.922 | 26.986 | 0.000 | 0.228 | 0.000 | 0.000 | -15.790 | 0.000 | -5.423 | -25.088 |
FRONT_RETAIL | 0.000 | 0.000 | 4.280 | -45.158 | 0.000 | 0.000 | 15.161 | 22.836 | 7.943 | 27.047 | 0.000 | 0.234 | 0.000 | 0.000 | -15.105 | 0.000 | -5.088 | -12.151 |
FRONT_ENTRY | 13.362 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.489 | 0.000 | 5.519 | 0.000 | 0.907 | 3.070 | 0.000 | -2.849 | 0.000 | -21.499 | 0.000 |
Total Facility | 13.362 | 0.000 | 29.766 | -590.511 | 0.000 | 0.000 | 230.174 | 256.675 | 195.156 | 133.479 | 0.000 | 2.369 | 3.071 | 0.000 | -55.546 | 0.000 | -53.663 | -164.331 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 07-JUN-06:02 | 0.00 | 0.00 | 0.00 | -36872.94 | 0.00 | 0.00 | 387.73 | 342.98 | 1226.28 | 0.00 | 0.00 | 0.00 | 35187.35 | 0.00 | -0.00 | 0.00 | -271.42 | 0.00 |
CORE_RETAIL | 12-OCT-06:02 | 0.00 | 0.00 | 0.00 | -187765.72 | 0.00 | 0.00 | 1673.55 | 3783.15 | 2067.82 | 0.00 | 0.00 | 0.00 | 182526.22 | 0.00 | -2066.77 | 0.00 | -218.26 | 0.00 |
POINT_OF_SALE | 12-OCT-06:02 | 0.00 | 0.00 | 0.00 | -23786.75 | 0.00 | 0.00 | 153.32 | 356.48 | 1298.17 | 0.00 | 0.00 | 0.00 | 23605.95 | 0.00 | -1511.33 | 0.00 | -115.84 | 0.00 |
FRONT_RETAIL | 14-SEP-06:02 | 0.00 | 0.00 | 0.00 | -17696.69 | 0.00 | 0.00 | 156.41 | 356.48 | 194.85 | 0.00 | 0.00 | 0.00 | 18233.35 | 0.00 | -1160.02 | 0.00 | -84.38 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-SEP-06:02 | 0.00 | 0.00 | 0.00 | -236642.40 | 0.00 | 0.00 | 2342.97 | 4862.34 | 4787.13 | 0.00 | 0.00 | 0.00 | 229458.99 | 0.00 | -4271.04 | 0.00 | -537.98 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 13-FEB-05:11 | 0.00 | 0.00 | 48991.19 | 0.00 | 0.00 | 0.00 | 0.00 | 98.38 | 613.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3351.62 | -46351.09 |
CORE_RETAIL | 12-FEB-08:61 | 0.00 | 0.00 | 219592.85 | 0.00 | 0.00 | 0.00 | 0.00 | 945.79 | 775.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2448.06 | 0.00 | -793.83 | -218072.18 |
POINT_OF_SALE | 08-JAN-07:01 | 0.00 | 0.00 | 29416.86 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 486.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1651.84 | 0.00 | -625.98 | -27714.98 |
FRONT_RETAIL | 12-FEB-07:11 | 0.00 | 0.00 | 24058.75 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2308.67 | 0.00 | -1852.39 | -20059.88 |
FRONT_ENTRY | 07-JAN-18:00 | 25239.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 403.48 | 0.00 | -373.37 | 0.00 | -25374.43 | 0.00 |
Total Facility | 12-FEB-08:61 | 5221.34 | 0.00 | 321802.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1228.22 | 1795.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5132.27 | 0.00 | -7223.32 | -317691.77 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.8275 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.8510 | 0.1251 | 1.0000 | 0.2316 | 0.1251 | ||
PSZ-AC:2 | 6.8612 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.1196 | 0.2655 | 1.0000 | 1.8902 | 0.2655 | ||
PSZ-AC:3 | 1.0659 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0659 | 0.1671 | 1.0000 | 0.1781 | 0.1671 | ||
PSZ-AC:4 | 0.8041 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8074 | 0.2206 | 1.0000 | 0.1781 | 0.2206 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 1.8275 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 1.8275 | 1.0000 | 1.0000 | 0.2316 | 0.1267 | ||
PSZ-AC:2 | 6.8612 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 6.8612 | 1.0000 | 1.0000 | 1.8902 | 0.2755 | ||
PSZ-AC:3 | 1.0659 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0659 | 1.0000 | 1.0000 | 0.1781 | 0.1671 | ||
PSZ-AC:4 | 0.8041 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 0.8041 | 1.0000 | 1.0000 | 0.1781 | 0.2215 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.8275 | 1.8275 | 1.8275 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.8612 | 6.8612 | 6.8612 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0659 | 1.0659 | 1.0659 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8041 | 0.8041 | 0.8041 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.8275 | 1.8510 | 1.8275 | 1.8275 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.8612 | 7.1196 | 6.8612 | 6.8612 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0659 | 1.0659 | 1.0659 | 1.0659 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8041 | 0.8074 | 0.8041 | 0.8041 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 1.8275 | 1.8275 | 1.8275 | 0.2316 | 0.2040 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 6.8612 | 6.8612 | 6.8612 | 1.8902 | 0.6790 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.0659 | 1.0659 | 1.0659 | 0.1781 | 0.3167 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 0.8041 | 0.8041 | 0.8041 | 0.1781 | 0.3166 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 1.8275 | 1.8275 | 1.8275 | 1.8275 | 0.2316 | 1.0000 |
PSZ-AC:2 | 6.8612 | 6.8612 | 6.8612 | 6.8612 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.0659 | 1.0659 | 1.0659 | 1.0659 | 0.1781 | 1.0000 |
PSZ-AC:4 | 0.8041 | 0.8041 | 0.8041 | 0.8041 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:53
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 160.06 | 204918.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 215.04 | 50612.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 256.67 | 21880.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 42.68 | 3292.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 195.16 | 10771.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 140.78 | 12787.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 90.90 | 5042.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 195.16 | 850.33 |
Natural Gas | 0.00 | 250.96 |
Additional | 0.00 | 0.00 |
Total | 195.16 | 1101.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 111.89 |
Space Heating | 0.00 |
Space Cooling | 93.74 |
Fans (All) | 61.37 |
Service Water Heating | 0.00 |
Receptacle Equipment | 85.07 |
Miscellaneous (All) | 370.68 |
Subtotal | 370.68 |
Natural Gas [MJ/m2] | |
Space Heating | 69.77 |
Service Water Heating | 39.63 |
Miscellaneous (All) | 109.40 |
Subtotal | 109.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.31 |
Space Heating | 14.53 |
Space Cooling | 19.53 |
Fans (All) | 12.78 |
Service Water Heating | 8.25 |
Receptacle Equipment | 17.72 |
Miscellaneous | 3.88 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 3175. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3609. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3609. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4572. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.742759E+11 |
February | 0.000 | 0.408585E+11 |
March | 0.000 | 0.477137E+10 |
April | 0.000 | 0.691321E+09 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.534162E+09 |
November | 0.000 | 0.698749E+10 |
December | 0.000 | 0.319437E+11 |
Annual Sum or Average | 0.160062E+12 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.742759E+11 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342259E+09 | 5216.24 | 23-JAN-07:05 | -1.2 | -3.0 | 0.168127E+10 | 2332.66 | 20-JAN-15:00 | 17.20 | 12.76 |
February | 0.810552E+09 | 5528.43 | 02-FEB-07:05 | -0.7 | -1.6 | 0.163918E+10 | 2451.26 | 22-FEB-15:50 | 15.33 | 13.46 |
March | 0.273924E+10 | 9609.62 | 31-MAR-06:02 | 17.30 | 16.12 | 0.208809E+10 | 2451.28 | 11-MAR-12:30 | 22.50 | 14.49 |
April | 0.441517E+10 | 16759.10 | 19-APR-06:02 | 15.68 | 14.03 | 0.211094E+10 | 2451.31 | 28-APR-14:00 | 25.60 | 15.82 |
May | 0.797300E+10 | 34453.38 | 17-MAY-06:02 | 16.78 | 13.16 | 0.222879E+10 | 2451.24 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.122105E+11 | 36884.43 | 07-JUN-06:02 | 13.48 | 11.64 | 0.220232E+10 | 2451.22 | 09-JUN-14:09 | 29.90 | 18.88 |
July | 0.138775E+11 | 29124.88 | 03-JUL-06:02 | 18.68 | 16.73 | 0.218813E+10 | 2451.24 | 29-JUL-10:09 | 18.48 | 18.48 |
August | 0.146880E+11 | 27856.34 | 26-AUG-06:02 | 21.78 | 17.45 | 0.228191E+10 | 2451.25 | 26-AUG-10:09 | 27.48 | 20.44 |
September | 0.101006E+11 | 34373.24 | 15-SEP-06:02 | 14.50 | 12.25 | 0.215678E+10 | 2451.31 | 28-SEP-14:20 | 19.40 | 18.15 |
October | 0.551146E+10 | 27825.79 | 11-OCT-06:02 | 17.70 | 16.28 | 0.213118E+10 | 2451.24 | 14-OCT-11:20 | 19.60 | 12.95 |
November | 0.273177E+10 | 6159.83 | 21-NOV-07:05 | -2.8 | -3.8 | 0.191155E+10 | 2451.24 | 04-NOV-11:20 | 16.87 | 16.52 |
December | 0.138386E+10 | 6379.18 | 01-DEC-07:05 | -3.8 | -4.7 | 0.174947E+10 | 2451.21 | 14-DEC-15:50 | 15.00 | 10.72 |
Annual Sum or Average | 0.767838E+11 | 0.243696E+11 | ||||||||
Minimum of Months | 0.342259E+09 | 5216.24 | -3.8 | -4.7 | 0.163918E+10 | 2332.66 | 15.00 | 10.72 | ||
Maximum of Months | 0.146880E+11 | 36884.43 | 21.78 | 17.45 | 0.228191E+10 | 2451.31 | 29.90 | 20.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119608E+11 | 57133.77 | 27-JAN-07:05 | -6.7 | -7.8 | 0.713379E+10 | 10326.93 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.143841E+11 | 59621.59 | 03-FEB-07:05 | -8.9 | -10.1 | 0.701692E+10 | 10327.30 | 22-FEB-15:39 | 16.27 | 13.43 |
March | 0.254122E+11 | 128257.96 | 31-MAR-06:02 | 17.30 | 16.12 | 0.894857E+10 | 10327.35 | 11-MAR-11:30 | 20.00 | 13.41 |
April | 0.310860E+11 | 158833.94 | 18-APR-06:02 | 13.30 | 12.05 | 0.894132E+10 | 10327.16 | 29-APR-10:50 | 18.53 | 15.23 |
May | 0.408905E+11 | 153067.23 | 17-MAY-06:02 | 16.78 | 13.16 | 0.939234E+10 | 10327.09 | 10-MAY-14:09 | 20.78 | 12.15 |
June | 0.496991E+11 | 185103.49 | 08-JUN-06:02 | 12.07 | 8.46 | 0.927787E+10 | 10327.29 | 17-JUN-15:00 | 25.60 | 22.49 |
July | 0.528526E+11 | 125192.23 | 03-JUL-06:02 | 18.68 | 16.73 | 0.921848E+10 | 10327.13 | 01-JUL-15:39 | 27.60 | 23.23 |
August | 0.546012E+11 | 123445.08 | 26-AUG-06:02 | 21.78 | 17.45 | 0.961355E+10 | 10326.99 | 26-AUG-10:20 | 27.77 | 20.59 |
September | 0.415629E+11 | 163504.73 | 14-SEP-06:02 | 12.30 | 10.99 | 0.908429E+10 | 10327.12 | 15-SEP-14:09 | 28.48 | 18.73 |
October | 0.324020E+11 | 187797.63 | 12-OCT-06:02 | 8.12 | 5.86 | 0.892668E+10 | 10327.13 | 21-OCT-10:00 | 18.90 | 12.93 |
November | 0.226421E+11 | 89256.15 | 04-NOV-06:03 | 16.10 | 15.06 | 0.805037E+10 | 10327.13 | 04-NOV-13:50 | 17.62 | 17.30 |
December | 0.174341E+11 | 54013.65 | 18-DEC-07:05 | -5.1 | -6.8 | 0.745426E+10 | 10327.02 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.394928E+12 | 0.103058E+12 | ||||||||
Minimum of Months | 0.119608E+11 | 54013.65 | -8.9 | -10.1 | 0.701692E+10 | 10326.93 | 16.27 | 12.15 | ||
Maximum of Months | 0.546012E+11 | 187797.63 | 21.78 | 17.45 | 0.961355E+10 | 10327.35 | 28.48 | 23.23 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247171E+10 | 4703.47 | 28-JAN-07:05 | -3.5 | -5.2 | 0.716146E+09 | 973.15 | 31-JAN-15:00 | 20.00 | 13.57 |
February | 0.285670E+10 | 6560.54 | 28-FEB-15:40 | 23.87 | 12.90 | 0.692693E+09 | 973.15 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.454424E+10 | 17733.41 | 31-MAR-06:02 | 17.30 | 16.12 | 0.873104E+09 | 973.13 | 11-MAR-11:20 | 19.43 | 13.14 |
April | 0.506337E+10 | 21862.85 | 18-APR-06:02 | 13.30 | 12.05 | 0.846238E+09 | 973.13 | 07-APR-14:09 | 22.57 | 13.55 |
May | 0.662260E+10 | 20994.83 | 17-MAY-06:02 | 16.78 | 13.16 | 0.885265E+09 | 973.13 | 23-MAY-14:09 | 23.53 | 20.59 |
June | 0.850474E+10 | 21864.07 | 07-JUN-06:02 | 13.48 | 11.64 | 0.874282E+09 | 973.12 | 29-JUN-14:09 | 29.18 | 22.36 |
July | 0.943852E+10 | 17106.27 | 03-JUL-06:02 | 18.68 | 16.73 | 0.868655E+09 | 973.13 | 03-JUL-14:09 | 29.90 | 22.09 |
August | 0.105711E+11 | 16609.48 | 26-AUG-06:02 | 21.78 | 17.45 | 0.905873E+09 | 973.13 | 26-AUG-11:39 | 30.03 | 21.74 |
September | 0.845504E+10 | 22798.94 | 14-SEP-06:02 | 12.30 | 10.99 | 0.856276E+09 | 973.14 | 25-SEP-14:09 | 30.40 | 20.08 |
October | 0.683885E+10 | 23789.96 | 12-OCT-06:02 | 8.12 | 5.86 | 0.856596E+09 | 973.13 | 05-OCT-14:00 | 20.60 | 15.45 |
November | 0.490956E+10 | 10068.76 | 04-NOV-06:03 | 16.10 | 15.06 | 0.805863E+09 | 973.13 | 04-NOV-13:09 | 16.88 | 16.57 |
December | 0.337391E+10 | 7697.68 | 13-DEC-07:03 | 16.70 | 15.65 | 0.784719E+09 | 973.10 | 12-DEC-15:20 | 22.60 | 16.09 |
Annual Sum or Average | 0.736504E+11 | 0.996571E+10 | ||||||||
Minimum of Months | 0.247171E+10 | 4703.47 | -3.5 | -5.2 | 0.692693E+09 | 973.10 | 16.88 | 13.14 | ||
Maximum of Months | 0.105711E+11 | 23789.96 | 23.87 | 17.45 | 0.905873E+09 | 973.15 | 30.40 | 22.36 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.950416E+09 | 4180.32 | 15-JAN-09:05 | -2.9 | -5.0 | 0.685060E+09 | 973.10 | 30-JAN-15:50 | 16.70 | 10.50 |
February | 0.122185E+10 | 4366.53 | 28-FEB-15:40 | 23.87 | 12.90 | 0.665628E+09 | 973.11 | 22-FEB-15:30 | 17.20 | 13.31 |
March | 0.223875E+10 | 13705.80 | 31-MAR-06:02 | 17.30 | 16.12 | 0.843720E+09 | 973.13 | 11-MAR-14:09 | 25.18 | 16.16 |
April | 0.265359E+10 | 14556.59 | 18-APR-06:02 | 13.30 | 12.05 | 0.833742E+09 | 973.13 | 20-APR-14:09 | 23.90 | 16.58 |
May | 0.388419E+10 | 16214.03 | 17-MAY-06:02 | 16.78 | 13.16 | 0.883100E+09 | 973.13 | 12-MAY-14:09 | 23.90 | 15.17 |
June | 0.573845E+10 | 17034.91 | 07-JUN-06:02 | 13.48 | 11.64 | 0.874118E+09 | 973.11 | 17-JUN-15:00 | 25.60 | 22.49 |
July | 0.660309E+10 | 13578.84 | 03-JUL-06:02 | 18.68 | 16.73 | 0.868664E+09 | 973.13 | 29-JUL-10:00 | 19.40 | 19.40 |
August | 0.756878E+10 | 12985.42 | 26-AUG-06:02 | 21.78 | 17.45 | 0.905894E+09 | 973.11 | 26-AUG-10:09 | 27.48 | 20.44 |
September | 0.570081E+10 | 17701.97 | 14-SEP-06:02 | 12.30 | 10.99 | 0.855933E+09 | 973.14 | 16-SEP-15:50 | 24.08 | 23.12 |
October | 0.430949E+10 | 16975.73 | 12-OCT-06:02 | 8.12 | 5.86 | 0.841915E+09 | 973.15 | 05-OCT-14:00 | 20.60 | 15.45 |
November | 0.268938E+10 | 5924.24 | 04-NOV-06:03 | 16.10 | 15.06 | 0.780288E+09 | 973.10 | 04-NOV-11:20 | 16.87 | 16.52 |
December | 0.160057E+10 | 4090.41 | 01-DEC-07:05 | -3.8 | -4.7 | 0.737974E+09 | 973.11 | 11-DEC-15:00 | 21.10 | 15.90 |
Annual Sum or Average | 0.451594E+11 | 0.977604E+10 | ||||||||
Minimum of Months | 0.950416E+09 | 4090.41 | -3.8 | -5.0 | 0.665628E+09 | 973.10 | 16.70 | 10.50 | ||
Maximum of Months | 0.756878E+10 | 17701.97 | 23.87 | 17.45 | 0.905894E+09 | 973.15 | 27.48 | 23.12 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 | 0.00 | 0.00 | 01-JAN-00:10 | 5.70 | 4.97 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 | 7.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 | 8.50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 | 0.00 | 0.00 | 01-APR-00:10 | 12.05 | 7.81 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 | 18.59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 | 21.38 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 21.87 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 | 18.45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 | 15.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 6.59 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 | 1.51 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 1.80 | 1.51 | 0.00 | 0.00 | 1.80 | 1.51 | ||
Maximum of Months | 0.00 | 0.00 | 25.13 | 21.87 | 0.00 | 0.00 | 25.13 | 21.87 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545120E+10 | 48701.50 | 08-JAN-07:01 | -4.9 |
February | 0.316265E+10 | 48991.03 | 13-FEB-05:11 | -5.2 |
March | 0.317270E+09 | 43093.51 | 23-MAR-05:02 | 6.10 |
April | 96135081.13 | 18041.72 | 07-APR-06:03 | 2.80 |
May | 79216970.16 | 767.83 | 12-MAY-05:02 | 11.60 |
June | 49574131.77 | 1082.74 | 26-JUN-05:05 | 23.30 |
July | 34572239.35 | 1307.00 | 17-JUL-05:05 | 21.70 |
August | 28392489.89 | 1204.56 | 10-AUG-05:05 | 24.40 |
September | 67401485.89 | 977.82 | 17-SEP-08:20 | 23.87 |
October | 81097858.96 | 825.99 | 31-OCT-06:10 | 8.22 |
November | 0.387421E+09 | 48272.95 | 22-NOV-06:01 | -3.3 |
December | 0.214177E+10 | 48666.28 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.118967E+11 | |||
Minimum of Months | 28392489.89 | 767.83 | -5.2 | |
Maximum of Months | 0.545120E+10 | 48991.03 | 24.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.434116E+10 | 218833.04 | 09-JAN-06:01 | -2.4 |
February | 0.229632E+10 | 219592.79 | 12-FEB-08:61 | -11.9 |
March | 0.513978E+09 | 17015.65 | 20-MAR-06:08 | 5.00 |
April | 0.479358E+09 | 4728.40 | 02-APR-07:12 | 12.97 |
May | 0.452139E+09 | 4684.59 | 14-MAY-07:01 | 13.68 |
June | 0.199231E+09 | 6216.19 | 25-JUN-08:20 | 24.43 |
July | 0.195496E+09 | 7163.29 | 16-JUL-08:20 | 26.33 |
August | 0.181215E+09 | 7844.38 | 06-AUG-08:20 | 25.17 |
September | 0.310050E+09 | 5642.60 | 17-SEP-08:20 | 23.87 |
October | 0.487942E+09 | 4743.09 | 15-OCT-07:12 | 10.73 |
November | 0.568515E+09 | 81279.26 | 22-NOV-07:03 | -3.2 |
December | 0.155926E+10 | 219553.94 | 03-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.115847E+11 | |||
Minimum of Months | 0.181215E+09 | 4684.59 | -11.9 | |
Maximum of Months | 0.434116E+10 | 219592.79 | 26.33 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.887302E+09 | 29416.86 | 08-JAN-07:01 | -4.9 |
February | 0.519271E+09 | 29415.85 | 12-FEB-07:01 | -12.7 |
March | 61880410.09 | 14684.49 | 23-MAR-06:03 | 6.10 |
April | 48152433.18 | 4663.46 | 06-APR-06:57 | 1.70 |
May | 43116624.27 | 501.34 | 19-MAY-05:05 | 16.60 |
June | 19468390.95 | 842.52 | 26-JUN-05:05 | 23.30 |
July | 16685247.07 | 1047.31 | 16-JUL-08:06 | 25.97 |
August | 15723106.73 | 898.25 | 10-AUG-05:05 | 24.40 |
September | 20418875.41 | 922.11 | 09-SEP-05:05 | 21.78 |
October | 42127215.01 | 525.41 | 11-OCT-05:07 | 18.72 |
November | 65344298.22 | 20765.25 | 22-NOV-06:01 | -3.3 |
December | 0.265581E+09 | 29394.15 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.200507E+10 | |||
Minimum of Months | 15723106.73 | 501.34 | -12.7 | |
Maximum of Months | 0.887302E+09 | 29416.86 | 25.97 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177946E+10 | 23752.51 | 08-JAN-07:01 | -4.9 |
February | 0.105393E+10 | 24058.74 | 12-FEB-07:11 | -12.6 |
March | 0.176848E+09 | 23203.17 | 23-MAR-05:02 | 6.10 |
April | 0.108669E+09 | 11281.40 | 06-APR-06:03 | 1.20 |
May | 88246280.27 | 867.49 | 11-MAY-06:00 | 7.80 |
June | 56296305.74 | 1141.59 | 25-JUN-08:06 | 23.87 |
July | 32603146.21 | 1198.73 | 23-JUL-08:06 | 24.37 |
August | 16768110.67 | 1183.78 | 03-AUG-05:04 | 23.90 |
September | 54793057.12 | 1072.92 | 09-SEP-05:05 | 21.78 |
October | 94202359.19 | 2801.89 | 31-OCT-06:05 | 8.22 |
November | 0.152093E+09 | 23523.05 | 22-NOV-06:01 | -3.3 |
December | 0.665580E+09 | 23736.60 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.427949E+10 | |||
Minimum of Months | 16768110.67 | 867.49 | -12.6 | |
Maximum of Months | 0.177946E+10 | 24058.74 | 24.37 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.649425E+10 | 25240.50 | 07-JAN-18:00 | -5.0 |
February | 0.376151E+10 | 25169.65 | 11-FEB-18:00 | -5.0 |
March | 0.369664E+09 | 12898.03 | 22-MAR-11:10 | 4.40 |
April | 18112820.26 | 2010.88 | 26-APR-07:10 | 4.97 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 7705571.25 | 2598.66 | 26-OCT-07:07 | 2.57 |
November | 0.692881E+09 | 20488.52 | 21-NOV-16:51 | 7.20 |
December | 0.201834E+10 | 17009.70 | 17-DEC-18:00 | 1.10 |
Annual Sum or Average | 0.133625E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.649425E+10 | 25240.50 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.186041E+10 | 1543.42 | 02-JAN-09:09 | 0.421155E+10 | 2759.14 | 02-JAN-09:09 |
February | 0.169252E+10 | 1543.42 | 01-FEB-09:09 | 0.382086E+10 | 2759.14 | 01-FEB-09:09 |
March | 0.193008E+10 | 1543.42 | 01-MAR-09:09 | 0.431750E+10 | 2759.14 | 01-MAR-09:09 |
April | 0.182131E+10 | 1543.42 | 01-APR-09:09 | 0.410284E+10 | 2759.14 | 01-APR-09:09 |
May | 0.189524E+10 | 1543.42 | 01-MAY-08:09 | 0.426453E+10 | 2759.14 | 01-MAY-08:09 |
June | 0.186250E+10 | 1543.42 | 01-JUN-08:09 | 0.416961E+10 | 2759.14 | 01-JUN-08:09 |
July | 0.185405E+10 | 1543.42 | 01-JUL-09:09 | 0.419776E+10 | 2759.14 | 01-JUL-09:09 |
August | 0.193008E+10 | 1543.42 | 01-AUG-08:09 | 0.431750E+10 | 2759.14 | 01-AUG-08:09 |
September | 0.182131E+10 | 1543.42 | 01-SEP-08:09 | 0.410284E+10 | 2759.14 | 01-SEP-08:09 |
October | 0.186041E+10 | 1543.42 | 02-OCT-08:09 | 0.421155E+10 | 2759.14 | 02-OCT-08:09 |
November | 0.179919E+10 | 1543.42 | 01-NOV-08:09 | 0.407746E+10 | 2759.14 | 01-NOV-08:09 |
December | 0.185405E+10 | 1543.42 | 01-DEC-09:09 | 0.419776E+10 | 2759.14 | 01-DEC-09:09 |
Annual Sum or Average | 0.221812E+11 | 0.499918E+11 | ||||
Minimum of Months | 0.169252E+10 | 1543.42 | 0.382086E+10 | 2759.14 | ||
Maximum of Months | 0.193008E+10 | 1543.42 | 0.431750E+10 | 2759.14 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.179003E+11 | 17024.17 | 02-JAN-15:30 | 0.710173E+10 | 4652.60 | 02-JAN-09:09 |
February | 0.159989E+11 | 17024.17 | 01-FEB-09:09 | 0.644293E+10 | 4652.60 | 01-FEB-09:09 |
March | 0.163118E+11 | 17024.17 | 01-MAR-17:30 | 0.728039E+10 | 4652.60 | 01-MAR-09:09 |
April | 0.143206E+11 | 17024.17 | 03-APR-08:09 | 0.691842E+10 | 4652.60 | 01-APR-09:09 |
May | 0.143334E+11 | 15605.49 | 05-MAY-16:49 | 0.719106E+10 | 4652.60 | 01-MAY-08:09 |
June | 0.138673E+11 | 15605.49 | 05-JUN-16:00 | 0.703101E+10 | 4652.60 | 01-JUN-08:09 |
July | 0.137786E+11 | 15605.49 | 11-JUL-16:00 | 0.707847E+10 | 4652.60 | 01-JUL-09:09 |
August | 0.143303E+11 | 15605.49 | 18-AUG-16:49 | 0.728039E+10 | 4652.60 | 01-AUG-08:09 |
September | 0.146197E+11 | 17024.17 | 02-SEP-16:49 | 0.691842E+10 | 4652.60 | 01-SEP-08:09 |
October | 0.171920E+11 | 17024.17 | 03-OCT-16:00 | 0.710173E+10 | 4652.60 | 02-OCT-08:09 |
November | 0.168717E+11 | 17024.17 | 01-NOV-08:09 | 0.687562E+10 | 4652.60 | 01-NOV-08:09 |
December | 0.178069E+11 | 17024.17 | 01-DEC-09:09 | 0.707847E+10 | 4652.60 | 01-DEC-09:09 |
Annual Sum or Average | 0.187331E+12 | 0.842987E+11 | ||||
Minimum of Months | 0.137786E+11 | 15605.49 | 0.644293E+10 | 4652.60 | ||
Maximum of Months | 0.179003E+11 | 17024.17 | 0.728039E+10 | 4652.60 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.445844E+10 | 2920.89 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.404485E+10 | 2920.89 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.457061E+10 | 2920.89 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.434336E+10 | 2920.89 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.451452E+10 | 2920.89 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.441405E+10 | 2920.89 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.444384E+10 | 2920.89 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.457061E+10 | 2920.89 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.434336E+10 | 2920.89 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.445844E+10 | 2920.89 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.431649E+10 | 2920.89 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.444384E+10 | 2920.89 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.529224E+11 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.404485E+10 | 2920.89 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.457061E+10 | 2920.89 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.191503E+10 | 1604.15 | 02-JAN-09:09 | 0.669181E+09 | 438.40 | 02-JAN-09:09 |
February | 0.174243E+10 | 1604.15 | 01-FEB-09:09 | 0.607103E+09 | 438.40 | 01-FEB-09:09 |
March | 0.198754E+10 | 1604.15 | 01-MAR-09:09 | 0.686016E+09 | 438.40 | 01-MAR-09:09 |
April | 0.187525E+10 | 1604.15 | 01-APR-09:09 | 0.651908E+09 | 438.40 | 01-APR-09:09 |
May | 0.195129E+10 | 1604.15 | 01-MAY-08:09 | 0.677598E+09 | 438.40 | 01-MAY-08:09 |
June | 0.191792E+10 | 1604.15 | 01-JUN-08:09 | 0.662517E+09 | 438.40 | 01-JUN-08:09 |
July | 0.190862E+10 | 1604.15 | 01-JUL-09:09 | 0.666989E+09 | 438.40 | 01-JUL-09:09 |
August | 0.198754E+10 | 1604.15 | 01-AUG-08:09 | 0.686016E+09 | 438.40 | 01-AUG-08:09 |
September | 0.187525E+10 | 1604.15 | 01-SEP-08:09 | 0.651908E+09 | 438.40 | 01-SEP-08:09 |
October | 0.191503E+10 | 1604.15 | 02-OCT-08:09 | 0.669181E+09 | 438.40 | 02-OCT-08:09 |
November | 0.185183E+10 | 1604.15 | 01-NOV-08:09 | 0.647874E+09 | 438.40 | 01-NOV-08:09 |
December | 0.190862E+10 | 1604.15 | 01-DEC-09:09 | 0.666989E+09 | 438.40 | 01-DEC-09:09 |
Annual Sum or Average | 0.228364E+11 | 0.794328E+10 | ||||
Minimum of Months | 0.174243E+10 | 1604.15 | 0.607103E+09 | 438.40 | ||
Maximum of Months | 0.198754E+10 | 1604.15 | 0.686016E+09 | 438.40 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.124902E+09 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.113644E+09 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.129631E+09 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.122307E+09 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.127266E+09 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.125090E+09 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.124483E+09 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.129631E+09 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.122307E+09 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.124902E+09 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.120779E+09 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.124483E+09 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148942E+10 | ||||
Minimum of Months | 0.113644E+09 | 104.63 | 0.00 | 0.00 | |
Maximum of Months | 0.129631E+09 | 104.63 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216271E+10 |
February | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 614258.15 | 0.184231E+10 |
March | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4815205.73 | 0.120241E+10 |
April | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12463725.29 | 0.767605E+09 |
May | 0.536353E+10 | 0.189524E+10 | 0.426453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37614943.68 | 0.507890E+09 |
June | 0.528933E+10 | 0.186250E+10 | 0.416961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141599E+09 | 0.267988E+09 |
July | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146286E+09 | 0.175240E+09 |
August | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152088E+09 | 0.122456E+09 |
September | 0.518069E+10 | 0.182131E+10 | 0.410284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44351969.94 | 0.278905E+09 |
October | 0.524694E+10 | 0.186041E+10 | 0.421155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8494744.29 | 0.930787E+09 |
November | 0.504819E+10 | 0.179919E+10 | 0.407746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53355.31 | 0.128458E+10 |
December | 0.525489E+10 | 0.185405E+10 | 0.419776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191777E+10 |
Annual Sum or Average | 0.628175E+11 | 0.221812E+11 | 0.499918E+11 | 0.548381E+09 | 0.114606E+11 | ||||
Minimum of Months | 0.479114E+10 | 0.169252E+10 | 0.382086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122456E+09 |
Maximum of Months | 0.548013E+10 | 0.193008E+10 | 0.431750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152088E+09 | 0.216271E+10 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.179003E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190777E+10 |
February | 0.201852E+11 | 0.159989E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398161.01 | 0.165435E+10 |
March | 0.230879E+11 | 0.163118E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3938178.81 | 0.111251E+10 |
April | 0.218263E+11 | 0.143206E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10171737.17 | 0.701115E+09 |
May | 0.225967E+11 | 0.143334E+11 | 0.719106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30651240.37 | 0.456385E+09 |
June | 0.222841E+11 | 0.138673E+11 | 0.703101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116007E+09 | 0.228278E+09 |
July | 0.221389E+11 | 0.137786E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121096E+09 | 0.145744E+09 |
August | 0.230879E+11 | 0.143303E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125926E+09 | 98822786.56 |
September | 0.218263E+11 | 0.146197E+11 | 0.691842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36340100.05 | 0.238677E+09 |
October | 0.221054E+11 | 0.171920E+11 | 0.710173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6952431.56 | 0.811279E+09 |
November | 0.212681E+11 | 0.168717E+11 | 0.687562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44083.98 | 0.113219E+10 |
December | 0.221389E+11 | 0.178069E+11 | 0.707847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170458E+10 |
Annual Sum or Average | 0.264651E+12 | 0.187331E+12 | 0.842987E+11 | 0.451525E+09 | 0.101917E+11 | ||||
Minimum of Months | 0.201852E+11 | 0.137786E+11 | 0.644293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98822786.56 |
Maximum of Months | 0.230879E+11 | 0.179003E+11 | 0.728039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125926E+09 | 0.190777E+10 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989515E+09 |
February | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210903.48 | 0.856671E+09 |
March | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2082405.83 | 0.588228E+09 |
April | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5378792.09 | 0.359811E+09 |
May | 0.212923E+10 | 0.195129E+10 | 0.451452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16074700.04 | 0.237505E+09 |
June | 0.209978E+10 | 0.191792E+10 | 0.441405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59913146.32 | 0.130273E+09 |
July | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60062658.72 | 87888723.32 |
August | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62091762.46 | 71365620.48 |
September | 0.205665E+10 | 0.187525E+10 | 0.434336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18602451.81 | 0.137891E+09 |
October | 0.208295E+10 | 0.191503E+10 | 0.445844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3680041.26 | 0.443303E+09 |
November | 0.200405E+10 | 0.185183E+10 | 0.431649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23377.68 | 0.619155E+09 |
December | 0.208610E+10 | 0.190862E+10 | 0.444384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901262E+09 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.529224E+11 | 0.228120E+09 | 0.542287E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.404485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71365620.48 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.457061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62091762.46 | 0.989515E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953891E+09 |
February | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 210820.32 | 0.818451E+09 |
March | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2082891.53 | 0.545945E+09 |
April | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5387541.91 | 0.332482E+09 |
May | 0.212923E+10 | 0.195129E+10 | 0.677598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16200962.52 | 0.215877E+09 |
June | 0.209978E+10 | 0.191792E+10 | 0.662517E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60914017.50 | 0.112248E+09 |
July | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62348319.98 | 74160360.38 |
August | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64143155.42 | 56086423.17 |
September | 0.205665E+10 | 0.187525E+10 | 0.651908E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18857292.97 | 0.123631E+09 |
October | 0.208295E+10 | 0.191503E+10 | 0.669181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3679481.26 | 0.415408E+09 |
November | 0.200405E+10 | 0.185183E+10 | 0.647874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23338.83 | 0.584797E+09 |
December | 0.208610E+10 | 0.190862E+10 | 0.666989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855273E+09 |
Annual Sum or Average | 0.249375E+11 | 0.228364E+11 | 0.794328E+10 | 0.233848E+09 | 0.508825E+10 | ||||
Minimum of Months | 0.190200E+10 | 0.174243E+10 | 0.607103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56086423.17 |
Maximum of Months | 0.217552E+10 | 0.198754E+10 | 0.686016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64143155.42 | 0.953891E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757173E+10 |
February | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464147E+10 |
March | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194731.01 | 0.142882E+10 |
April | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12980396.01 | 0.560043E+09 |
May | 0.00 | 0.127266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65820728.60 | 0.289439E+09 |
June | 0.00 | 0.125090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262899E+09 | 0.104238E+09 |
July | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312275E+09 | 0.115795E+09 |
August | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225989E+09 | 90990969.76 |
September | 0.00 | 0.122307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26649072.48 | 0.313966E+09 |
October | 0.00 | 0.124902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57026.94 | 0.102154E+10 |
November | 0.00 | 0.120779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21479.72 | 0.191583E+10 |
December | 0.00 | 0.124483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344556E+10 |
Annual Sum or Average | 0.00 | 0.148942E+10 | 0.906886E+09 | 0.214994E+11 | |||||
Minimum of Months | 0.00 | 0.113644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90990969.76 |
Maximum of Months | 0.00 | 0.129631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312275E+09 | 0.757173E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 1543.42 | 02-JAN-09:09 | 2759.14 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4084.80 | 07-JAN-05:04 |
February | 5888.82 | 01-FEB-15:09 | 1543.42 | 01-FEB-09:09 | 2759.14 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 28-FEB-15:00 | 5480.55 | 12-FEB-01:00 |
March | 5888.82 | 01-MAR-15:09 | 1543.42 | 01-MAR-09:09 | 2759.14 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 135.20 | 30-MAR-16:00 | 3059.39 | 22-MAR-03:00 |
April | 5888.82 | 01-APR-10:09 | 1543.42 | 01-APR-09:09 | 2759.14 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.08 | 04-APR-15:00 | 1745.61 | 05-APR-05:00 |
May | 5888.82 | 01-MAY-14:09 | 1543.42 | 01-MAY-08:09 | 2759.14 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.85 | 29-MAY-18:05 | 1486.35 | 10-MAY-04:00 |
June | 5888.82 | 01-JUN-14:09 | 1543.42 | 01-JUN-08:09 | 2759.14 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 517.47 | 11-JUN-18:03 | 1104.46 | 07-JUN-03:00 |
July | 5888.82 | 01-JUL-10:09 | 1543.42 | 01-JUL-09:09 | 2759.14 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 520.43 | 09-JUL-18:03 | 776.49 | 28-JUL-22:00 |
August | 5888.82 | 01-AUG-14:09 | 1543.42 | 01-AUG-08:09 | 2759.14 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 715.38 | 18-AUG-20:03 | 541.60 | 25-AUG-05:00 |
September | 5888.82 | 01-SEP-14:09 | 1543.42 | 01-SEP-08:09 | 2759.14 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 284.15 | 03-SEP-18:03 | 1060.54 | 29-SEP-05:00 |
October | 5888.82 | 02-OCT-14:09 | 1543.42 | 02-OCT-08:09 | 2759.14 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.94 | 11-OCT-14:00 | 2003.97 | 28-OCT-04:00 |
November | 5888.82 | 01-NOV-14:09 | 1543.42 | 01-NOV-08:09 | 2759.14 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 | 19-NOV-15:00 | 3128.31 | 30-NOV-21:05 |
December | 5888.82 | 01-DEC-15:09 | 1543.42 | 01-DEC-09:09 | 2759.14 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4970.84 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.60 | |||||
Maximum of Months | 5888.82 | 1543.42 | 2759.14 | 0.00 | 0.00 | 0.00 | 0.00 | 715.38 | 5480.55 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 17024.17 | 02-JAN-15:30 | 4652.60 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3493.83 | 26-JAN-02:00 |
February | 24809.68 | 01-FEB-15:09 | 17024.17 | 01-FEB-09:09 | 4652.60 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 28-FEB-15:00 | 4958.92 | 12-FEB-01:00 |
March | 24809.68 | 01-MAR-15:09 | 17024.17 | 01-MAR-17:30 | 4652.60 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.67 | 30-MAR-16:00 | 3009.25 | 22-MAR-03:00 |
April | 24809.68 | 01-APR-10:09 | 17024.17 | 03-APR-08:09 | 4652.60 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.02 | 04-APR-15:00 | 1631.03 | 05-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 15605.49 | 05-MAY-16:49 | 4652.60 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 270.61 | 29-MAY-18:05 | 1338.14 | 10-MAY-04:00 |
June | 24809.68 | 01-JUN-14:09 | 15605.49 | 05-JUN-16:00 | 4652.60 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 423.56 | 11-JUN-18:03 | 958.42 | 07-JUN-03:00 |
July | 24809.68 | 01-JUL-10:09 | 15605.49 | 11-JUL-16:00 | 4652.60 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 427.64 | 09-JUL-18:03 | 688.76 | 28-JUL-22:00 |
August | 24809.68 | 01-AUG-14:09 | 15605.49 | 18-AUG-16:49 | 4652.60 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 588.75 | 18-AUG-20:03 | 454.13 | 25-AUG-05:00 |
September | 24809.68 | 01-SEP-14:09 | 17024.17 | 02-SEP-16:49 | 4652.60 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 234.22 | 03-SEP-18:03 | 928.03 | 29-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 17024.17 | 03-OCT-16:00 | 4652.60 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.52 | 11-OCT-14:00 | 1877.98 | 28-OCT-04:00 |
November | 24809.68 | 01-NOV-14:09 | 17024.17 | 01-NOV-08:09 | 4652.60 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 19-NOV-15:00 | 2768.82 | 07-NOV-02:00 |
December | 24809.68 | 01-DEC-15:09 | 17024.17 | 01-DEC-09:09 | 4652.60 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4656.08 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 15605.49 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.13 | |||||
Maximum of Months | 24809.68 | 17024.17 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 588.75 | 4958.92 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 2920.89 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1762.61 | 07-JAN-05:04 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 2920.89 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 28-FEB-15:00 | 2383.03 | 12-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 2920.89 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.59 | 30-MAR-16:00 | 1438.82 | 22-MAR-03:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 2920.89 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 04-APR-15:00 | 786.98 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 2920.89 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.86 | 29-MAY-18:05 | 657.41 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 2920.89 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.94 | 11-JUN-18:03 | 501.40 | 07-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 2920.89 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.72 | 09-JUL-18:03 | 359.62 | 28-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 2920.89 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 304.00 | 18-AUG-20:03 | 264.52 | 31-AUG-05:00 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 2920.89 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.67 | 03-SEP-18:03 | 466.16 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 2920.89 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 11-OCT-14:00 | 976.10 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 2920.89 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 19-NOV-15:00 | 1448.61 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 2920.89 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2230.67 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.52 | |||||
Maximum of Months | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 304.00 | 2383.03 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 1604.15 | 02-JAN-09:09 | 438.40 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1768.13 | 07-JAN-05:04 |
February | 2337.76 | 01-FEB-15:09 | 1604.15 | 01-FEB-09:09 | 438.40 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 28-FEB-15:00 | 2329.51 | 12-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 1604.15 | 01-MAR-09:09 | 438.40 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.58 | 30-MAR-16:00 | 1326.01 | 22-MAR-03:00 |
April | 2337.76 | 01-APR-10:09 | 1604.15 | 01-APR-09:09 | 438.40 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.53 | 04-APR-15:00 | 730.53 | 05-APR-05:00 |
May | 2337.76 | 01-MAY-14:09 | 1604.15 | 01-MAY-08:09 | 438.40 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.39 | 29-MAY-18:05 | 624.17 | 10-MAY-04:00 |
June | 2337.76 | 01-JUN-14:09 | 1604.15 | 01-JUN-08:09 | 438.40 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.64 | 11-JUN-18:03 | 463.86 | 07-JUN-03:00 |
July | 2337.76 | 01-JUL-10:09 | 1604.15 | 01-JUL-09:09 | 438.40 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.89 | 09-JUL-18:03 | 325.30 | 28-JUL-22:00 |
August | 2337.76 | 01-AUG-14:09 | 1604.15 | 01-AUG-08:09 | 438.40 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 306.76 | 18-AUG-20:03 | 228.71 | 25-AUG-05:00 |
September | 2337.76 | 01-SEP-14:09 | 1604.15 | 01-SEP-08:09 | 438.40 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.12 | 03-SEP-18:03 | 437.62 | 29-SEP-05:00 |
October | 2337.76 | 02-OCT-14:09 | 1604.15 | 02-OCT-08:09 | 438.40 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.34 | 11-OCT-14:00 | 917.83 | 28-OCT-04:00 |
November | 2337.76 | 01-NOV-14:09 | 1604.15 | 01-NOV-08:09 | 438.40 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 19-NOV-15:00 | 1385.70 | 07-NOV-02:00 |
December | 2337.76 | 01-DEC-15:09 | 1604.15 | 01-DEC-09:09 | 438.40 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2134.40 | 17-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.71 | |||||
Maximum of Months | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 306.76 | 2329.51 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 104.63 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 25397.65 | 07-JAN-17:00 |
February | 0.00 | 01-FEB-00:10 | 104.63 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 25582.19 | 11-FEB-18:00 |
March | 0.00 | 01-MAR-00:10 | 104.63 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.18 | 28-MAR-17:00 | 13414.93 | 22-MAR-11:10 |
April | 0.00 | 01-APR-00:10 | 104.63 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.68 | 12-APR-14:00 | 6771.38 | 05-APR-11:01 |
May | 0.00 | 01-MAY-00:10 | 104.63 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 738.97 | 30-MAY-11:03 | 2480.65 | 24-MAY-11:01 |
June | 0.00 | 01-JUN-00:10 | 104.63 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1754.26 | 06-JUN-11:02 | 1439.93 | 07-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 104.63 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2298.60 | 08-JUL-11:01 | 2340.04 | 28-JUL-11:01 |
August | 0.00 | 01-AUG-00:10 | 104.63 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1847.55 | 01-AUG-11:02 | 1230.74 | 08-AUG-16:53 |
September | 0.00 | 01-SEP-00:10 | 104.63 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.42 | 09-SEP-11:03 | 2349.13 | 30-SEP-11:01 |
October | 0.00 | 01-OCT-00:10 | 104.63 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.24 | 10-OCT-16:00 | 6005.18 | 25-OCT-11:01 |
November | 0.00 | 01-NOV-00:10 | 104.63 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 19-NOV-14:55 | 14664.65 | 20-NOV-12:02 |
December | 0.00 | 01-DEC-00:10 | 104.63 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 17693.11 | 17-DEC-18:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1230.74 | ||||
Maximum of Months | 0.00 | 104.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2298.60 | 25582.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5216.24 | 23-JAN-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.89 |
February | 5528.43 | 02-FEB-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.93 |
March | 9609.62 | 31-MAR-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.59 |
April | 16759.10 | 19-APR-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.71 |
May | 34453.38 | 17-MAY-06:02 | 4416.61 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.18 |
June | 36884.43 | 07-JUN-06:02 | 4416.61 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.42 |
July | 29124.88 | 03-JUL-06:02 | 4416.61 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 |
August | 27856.34 | 26-AUG-06:02 | 3680.51 | 857.46 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.78 |
September | 34373.24 | 15-SEP-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27825.79 | 11-OCT-06:02 | 3680.51 | 1714.91 | 6131.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.11 |
November | 6159.83 | 21-NOV-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.06 |
December | 6379.18 | 01-DEC-07:05 | 2944.41 | 1371.93 | 4905.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.63 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5216.24 | 2944.41 | 857.46 | 4598.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36884.43 | 4416.61 | 2057.90 | 7357.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 57133.77 | 27-JAN-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.76 |
February | 59621.59 | 03-FEB-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.10 |
March | 128257.96 | 31-MAR-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.78 |
April | 158833.94 | 18-APR-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.20 |
May | 153067.23 | 17-MAY-06:02 | 18607.26 | 22698.89 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 |
June | 185103.49 | 08-JUN-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.99 |
July | 125192.23 | 03-JUL-06:02 | 18607.26 | 22698.89 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.48 |
August | 123445.08 | 26-AUG-06:02 | 15506.05 | 9457.87 | 7754.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 |
September | 163504.73 | 14-SEP-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.55 |
October | 187797.63 | 12-OCT-06:02 | 15506.05 | 18915.75 | 10339.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.26 |
November | 89256.15 | 04-NOV-06:03 | 9303.63 | 5674.72 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 |
December | 54013.65 | 18-DEC-07:05 | 12404.84 | 15132.60 | 8271.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 54013.65 | 9303.63 | 5674.72 | 4652.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.23 | |
Maximum of Months | 187797.63 | 18607.26 | 22698.89 | 12406.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4703.47 | 28-JAN-07:05 | 1168.88 | 712.96 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.81 |
February | 6560.54 | 28-FEB-15:40 | 2337.76 | 1604.15 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
March | 17733.41 | 31-MAR-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.29 |
April | 21862.85 | 18-APR-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 |
May | 20994.83 | 17-MAY-06:02 | 1753.32 | 2138.87 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 |
June | 21864.07 | 07-JUN-06:02 | 1753.32 | 2138.87 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.01 |
July | 17106.27 | 03-JUL-06:02 | 1753.32 | 2138.87 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 |
August | 16609.48 | 26-AUG-06:02 | 1461.10 | 891.19 | 4868.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.74 |
September | 22798.94 | 14-SEP-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.38 |
October | 23789.96 | 12-OCT-06:02 | 1461.10 | 1782.39 | 6490.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.84 |
November | 10068.76 | 04-NOV-06:03 | 876.66 | 534.72 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 |
December | 7697.68 | 13-DEC-07:03 | 876.66 | 1069.43 | 3894.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4703.47 | 876.66 | 534.72 | 2920.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | |
Maximum of Months | 23789.96 | 2337.76 | 2138.87 | 7789.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4180.32 | 15-JAN-09:05 | 1168.88 | 712.96 | 584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.11 |
February | 4366.53 | 28-FEB-15:40 | 2337.76 | 1604.15 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
March | 13705.80 | 31-MAR-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.27 |
April | 14556.59 | 18-APR-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.02 |
May | 16214.03 | 17-MAY-06:02 | 1753.32 | 2138.87 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.71 |
June | 17034.91 | 07-JUN-06:02 | 1753.32 | 2138.87 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.21 |
July | 13578.84 | 03-JUL-06:02 | 1753.32 | 2138.87 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 |
August | 12985.42 | 26-AUG-06:02 | 1461.10 | 891.19 | 730.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.89 |
September | 17701.97 | 14-SEP-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.38 |
October | 16975.73 | 12-OCT-06:02 | 1461.10 | 1782.39 | 974.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.63 |
November | 5924.24 | 04-NOV-06:03 | 876.66 | 534.72 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 |
December | 4090.41 | 01-DEC-07:05 | 1168.88 | 1425.91 | 779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.05 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4090.41 | 876.66 | 534.72 | 438.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | |
Maximum of Months | 17701.97 | 2337.76 | 2138.87 | 1169.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.61 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.44 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.91 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.75 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.53 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.59 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | |
Maximum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.59 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.584250E+11 | 46069.36 | 07-JAN-17:00 | 0.823633E+11 | 187034.56 | 09-JAN-07:10 |
February | 0.522884E+11 | 49989.79 | 28-FEB-17:10 | 0.481780E+11 | 209464.07 | 12-FEB-09:09 |
March | 0.581269E+11 | 59825.33 | 30-MAR-16:40 | 0.128323E+11 | 67951.40 | 23-MAR-06:10 |
April | 0.614737E+11 | 60958.64 | 17-APR-16:19 | 0.827615E+10 | 58830.79 | 07-APR-06:30 |
May | 0.747341E+11 | 67353.23 | 19-MAY-16:49 | 0.763693E+10 | 4937.37 | 01-MAY-11:09 |
June | 0.887595E+11 | 75425.17 | 27-JUN-15:00 | 0.724143E+10 | 4886.22 | 01-JUN-11:50 |
July | 0.965610E+11 | 87071.58 | 08-JUL-15:00 | 0.731800E+10 | 4848.43 | 03-JUL-11:50 |
August | 0.101551E+12 | 82519.36 | 18-AUG-15:00 | 0.737091E+10 | 4846.52 | 31-AUG-11:09 |
September | 0.803907E+11 | 77371.30 | 07-SEP-15:00 | 0.719417E+10 | 4878.03 | 29-SEP-11:50 |
October | 0.652179E+11 | 68765.05 | 10-OCT-15:50 | 0.811644E+10 | 52772.28 | 26-OCT-06:30 |
November | 0.556861E+11 | 53511.23 | 04-NOV-16:00 | 0.145137E+11 | 129454.90 | 22-NOV-07:10 |
December | 0.571154E+11 | 48190.95 | 12-DEC-15:00 | 0.399234E+11 | 164652.39 | 18-DEC-07:10 |
Annual Sum or Average | 0.850330E+12 | 0.250965E+12 | ||||
Minimum of Months | 0.522884E+11 | 46069.36 | 0.719417E+10 | 4846.52 | ||
Maximum of Months | 0.101551E+12 | 87071.58 | 0.823633E+11 | 209464.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.237156E+11 | 0.435204E+10 | 0.164409E+11 | 0.00 | 0.139082E+11 | 0.00 | 0.00 | 8275783.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212900E+11 | 0.367606E+10 | 0.149157E+11 | 0.00 | 0.116533E+11 | 0.00 | 0.00 | 0.753342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223466E+11 | 0.370004E+10 | 0.168545E+11 | 0.00 | 0.115622E+11 | 0.00 | 0.00 | 0.366356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.200147E+11 | 0.321129E+10 | 0.160165E+11 | 0.00 | 0.109318E+11 | 0.00 | 0.00 | 0.112994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202585E+11 | 0.299668E+10 | 0.166477E+11 | 0.00 | 0.112776E+11 | 0.00 | 0.00 | 0.235536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.196908E+11 | 0.275884E+10 | 0.162772E+11 | 0.00 | 0.113439E+11 | 0.00 | 0.00 | 0.386888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195743E+11 | 0.290382E+10 | 0.163871E+11 | 0.00 | 0.120232E+11 | 0.00 | 0.00 | 0.456726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.203651E+11 | 0.317252E+10 | 0.168545E+11 | 0.00 | 0.123200E+11 | 0.00 | 0.00 | 0.488387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.203138E+11 | 0.342071E+10 | 0.160165E+11 | 0.00 | 0.110522E+11 | 0.00 | 0.00 | 0.295875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230073E+11 | 0.391737E+10 | 0.164409E+11 | 0.00 | 0.111831E+11 | 0.00 | 0.00 | 0.106691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.224953E+11 | 0.412605E+10 | 0.159174E+11 | 0.00 | 0.111004E+11 | 0.00 | 0.00 | 0.204688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236027E+11 | 0.444292E+10 | 0.163871E+11 | 0.00 | 0.124226E+11 | 0.00 | 0.00 | 0.260147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256675E+12 | 0.426784E+11 | 0.195156E+12 | 0.140778E+12 | 0.00 | 0.215042E+12 | |||||||
Minimum of Months | 0.195743E+11 | 0.275884E+10 | 0.149157E+11 | 0.00 | 0.109318E+11 | 0.00 | 0.00 | 8275783.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.237156E+11 | 0.444292E+10 | 0.168545E+11 | 0.00 | 0.139082E+11 | 0.00 | 0.00 | 0.488387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.742759E+11 | 0.00 | 0.808744E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.408585E+11 | 0.00 | 0.731953E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.477137E+10 | 0.00 | 0.806094E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.691321E+09 | 0.00 | 0.758483E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.763693E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.724143E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.731800E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.737091E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.719417E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.534162E+09 | 0.00 | 0.758228E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.698749E+10 | 0.00 | 0.752624E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.319437E+11 | 0.00 | 0.797973E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.160062E+12 | 0.909024E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.719417E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.742759E+11 | 0.00 | 0.808744E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21880.52 | 02-JAN-15:30 | 3292.90 | 01-JAN-06:10 | 10771.04 | 02-JAN-09:09 | 0.00 | 12271.47 | 08-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 21880.52 | 01-FEB-09:09 | 3292.90 | 01-FEB-06:10 | 10771.04 | 01-FEB-09:09 | 0.00 | 12787.34 | 12-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 21880.52 | 01-MAR-17:30 | 3292.90 | 01-MAR-06:10 | 10771.04 | 01-MAR-09:09 | 0.00 | 9450.80 | 19-MAR-08:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 21880.52 | 03-APR-08:09 | 3292.90 | 01-APR-05:10 | 10771.04 | 01-APR-09:09 | 0.00 | 9081.56 | 06-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 20461.84 | 05-MAY-16:49 | 3292.90 | 01-MAY-05:10 | 10771.04 | 01-MAY-08:09 | 0.00 | 10348.93 | 31-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 20461.84 | 05-JUN-16:00 | 3292.90 | 01-JUN-05:10 | 10771.04 | 01-JUN-08:09 | 0.00 | 10580.55 | 26-JUN-06:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 20461.84 | 11-JUL-16:00 | 3292.90 | 01-JUL-05:10 | 10771.04 | 01-JUL-09:09 | 0.00 | 10670.65 | 27-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 20461.84 | 18-AUG-16:49 | 3292.90 | 01-AUG-05:10 | 10771.04 | 01-AUG-08:09 | 0.00 | 11072.93 | 20-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 21880.52 | 02-SEP-16:49 | 3292.90 | 01-SEP-05:10 | 10771.04 | 01-SEP-08:09 | 0.00 | 10627.15 | 17-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 21880.52 | 03-OCT-16:00 | 3292.90 | 01-OCT-05:10 | 10771.04 | 02-OCT-08:09 | 0.00 | 10536.20 | 19-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 21880.52 | 01-NOV-08:09 | 3292.90 | 01-NOV-05:10 | 10771.04 | 01-NOV-08:09 | 0.00 | 10175.78 | 22-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 21880.52 | 01-DEC-09:09 | 3292.90 | 01-DEC-06:10 | 10771.04 | 01-DEC-09:09 | 0.00 | 11466.97 | 03-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 20461.84 | 3292.90 | 10771.04 | 0.00 | 9081.56 | 0.00 | 0.00 | |||||
Maximum of Months | 21880.52 | 3292.90 | 10771.04 | 0.00 | 12787.34 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 951.57 | 31-JAN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13425.17 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24569.33 | 30-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24898.59 | 17-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32675.76 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41229.39 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 50612.02 | 08-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 46223.36 | 19-AUG-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40392.45 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31326.51 | 10-OCT-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16094.96 | 05-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9767.48 | 12-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 951.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50612.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 46069.36 | 07-JAN-17:00 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 10124.90 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49989.79 | 28-FEB-17:10 | 21880.52 | 10771.04 | 0.00 | 0.00 | 6955.98 | 0.00 | 0.00 | 10382.25 | 0.00 |
March | 59825.33 | 30-MAR-16:40 | 20461.84 | 10771.04 | 0.00 | 0.00 | 6955.98 | 0.00 | 0.00 | 21636.47 | 0.00 |
April | 60958.64 | 17-APR-16:19 | 20461.84 | 10771.04 | 0.00 | 0.00 | 6955.98 | 0.00 | 0.00 | 22769.78 | 0.00 |
May | 67353.23 | 19-MAY-16:49 | 20461.84 | 10771.04 | 0.00 | 0.00 | 6955.98 | 0.00 | 0.00 | 29164.38 | 0.00 |
June | 75425.17 | 27-JUN-15:00 | 16205.80 | 10771.04 | 0.00 | 0.00 | 8449.39 | 0.00 | 0.00 | 39998.95 | 0.00 |
July | 87071.58 | 08-JUL-15:00 | 16205.80 | 10771.04 | 0.00 | 0.00 | 10324.05 | 0.00 | 0.00 | 49770.69 | 0.00 |
August | 82519.36 | 18-AUG-15:00 | 17624.48 | 10771.04 | 0.00 | 0.00 | 9330.37 | 0.00 | 0.00 | 44793.48 | 0.00 |
September | 77371.30 | 07-SEP-15:00 | 17624.48 | 10771.04 | 0.00 | 0.00 | 8583.33 | 0.00 | 0.00 | 40392.45 | 0.00 |
October | 68765.05 | 10-OCT-15:50 | 20461.84 | 10771.04 | 0.00 | 0.00 | 7112.21 | 0.00 | 0.00 | 30419.97 | 0.00 |
November | 53511.23 | 04-NOV-16:00 | 21880.52 | 10771.04 | 0.00 | 0.00 | 6955.98 | 0.00 | 0.00 | 13903.70 | 0.00 |
December | 48190.95 | 12-DEC-15:00 | 21880.52 | 10771.04 | 0.00 | 0.00 | 6955.98 | 0.00 | 0.00 | 8583.41 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 46069.36 | 16205.80 | 10771.04 | 0.00 | 0.00 | 6955.98 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87071.58 | 21880.52 | 10771.04 | 3292.90 | 0.00 | 10324.05 | 0.00 | 0.00 | 49770.69 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 182482.03 | 09-JAN-07:10 | 0.00 | 5041.54 | 27-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 204918.84 | 12-FEB-09:09 | 0.00 | 5042.02 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 66089.40 | 23-MAR-06:10 | 0.00 | 5027.56 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 56968.79 | 07-APR-06:30 | 0.00 | 4984.71 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4937.37 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4886.22 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4848.43 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4846.52 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4878.03 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 50910.28 | 26-OCT-06:30 | 0.00 | 4931.15 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 124912.40 | 22-NOV-07:10 | 0.00 | 4983.70 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 162790.39 | 18-DEC-07:10 | 0.00 | 5023.40 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4846.52 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 204918.84 | 0.00 | 5042.02 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 16.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 16.90 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 16.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.01 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 17.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 16.85 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.00 | 12.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42.17 | 13.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52.50 | 13.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13.50 | 13.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34.33 | 14.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39.83 | 13.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 136.83 | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 387.17 | 13.33 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 136.83 | 14.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.24 | 340.17 | 21.14 | 340.17 | 21.14 |
February | 376.00 | 21.78 | 195.50 | 21.21 | 195.50 | 21.21 |
March | 381.17 | 22.65 | 48.67 | 21.86 | 36.50 | 21.19 |
April | 258.17 | 23.34 | 57.67 | 23.64 | 28.67 | 23.39 |
May | 116.00 | 23.74 | 267.17 | 23.88 | 62.83 | 23.85 |
June | 20.83 | 23.91 | 343.50 | 23.89 | 10.83 | 23.94 |
July | 47.33 | 23.90 | 415.00 | 23.89 | 47.33 | 23.90 |
August | 27.67 | 23.94 | 422.00 | 23.89 | 27.67 | 23.94 |
September | 21.50 | 23.86 | 338.00 | 23.89 | 15.83 | 23.91 |
October | 274.17 | 23.33 | 105.83 | 23.87 | 40.17 | 23.85 |
November | 368.33 | 22.59 | 63.67 | 22.23 | 55.50 | 21.99 |
December | 415.00 | 21.51 | 205.33 | 21.26 | 205.33 | 21.26 |
Annual Sum or Average | 2720.17 | 22.37 | 2802.50 | 23.10 | 1066.33 | 21.81 |
Minimum of Months | 20.83 | 21.24 | 48.67 | 21.14 | 10.83 | 21.14 |
Maximum of Months | 415.00 | 23.94 | 422.00 | 23.89 | 340.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.29 | 212.83 | 21.17 | 212.83 | 21.17 |
February | 373.00 | 21.90 | 99.33 | 21.21 | 99.33 | 21.21 |
March | 315.67 | 22.65 | 51.00 | 23.76 | 2.33 | 21.11 |
April | 135.00 | 23.10 | 154.50 | 23.89 | 7.67 | 23.89 |
May | 42.00 | 23.55 | 322.67 | 23.89 | 23.83 | 23.89 |
June | 4.50 | 23.79 | 374.50 | 23.89 | 2.00 | 23.93 |
July | 37.17 | 23.89 | 415.00 | 23.89 | 37.17 | 23.89 |
August | 20.17 | 23.90 | 422.00 | 23.89 | 20.17 | 23.90 |
September | 28.17 | 23.82 | 378.50 | 23.89 | 25.33 | 23.90 |
October | 186.50 | 22.93 | 138.83 | 23.87 | 42.83 | 23.83 |
November | 329.67 | 22.44 | 47.83 | 23.38 | 21.17 | 22.74 |
December | 405.50 | 21.54 | 76.83 | 21.49 | 76.50 | 21.48 |
Annual Sum or Average | 2291.33 | 22.17 | 2693.83 | 23.50 | 571.17 | 22.03 |
Minimum of Months | 4.50 | 21.29 | 47.83 | 21.17 | 2.00 | 21.11 |
Maximum of Months | 414.00 | 23.90 | 422.00 | 23.89 | 212.83 | 23.93 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 407.50 | 21.72 | 157.17 | 21.24 | 157.17 | 21.24 |
February | 321.17 | 22.06 | 94.00 | 21.15 | 93.00 | 21.12 |
March | 261.67 | 22.96 | 79.83 | 23.58 | 8.83 | 21.11 |
April | 142.17 | 23.24 | 161.50 | 23.83 | 9.50 | 22.92 |
May | 42.67 | 23.55 | 314.33 | 23.89 | 16.67 | 23.89 |
June | 13.67 | 23.86 | 366.83 | 23.89 | 7.83 | 23.92 |
July | 21.50 | 23.90 | 415.00 | 23.89 | 21.50 | 23.90 |
August | 9.50 | 23.96 | 422.00 | 23.89 | 9.50 | 23.96 |
September | 7.17 | 23.75 | 388.83 | 23.89 | 5.17 | 23.91 |
October | 111.33 | 23.10 | 219.33 | 23.89 | 22.50 | 23.88 |
November | 216.33 | 22.88 | 80.83 | 23.70 | 8.17 | 22.02 |
December | 373.83 | 22.32 | 73.67 | 22.09 | 51.67 | 21.32 |
Annual Sum or Average | 1928.50 | 22.48 | 2773.33 | 23.58 | 411.50 | 21.81 |
Minimum of Months | 7.17 | 21.72 | 73.67 | 21.15 | 5.17 | 21.11 |
Maximum of Months | 407.50 | 23.96 | 422.00 | 23.89 | 157.17 | 23.96 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 21.42 | 217.00 | 21.16 | 217.00 | 21.16 |
February | 353.00 | 21.86 | 139.17 | 21.15 | 139.17 | 21.15 |
March | 315.67 | 22.64 | 69.50 | 23.06 | 20.83 | 21.11 |
April | 200.33 | 23.04 | 120.17 | 23.75 | 19.83 | 23.05 |
May | 111.00 | 23.59 | 291.00 | 23.88 | 63.83 | 23.87 |
June | 43.83 | 23.83 | 350.83 | 23.89 | 33.33 | 23.90 |
July | 58.33 | 23.90 | 415.00 | 23.89 | 58.33 | 23.90 |
August | 45.33 | 23.92 | 422.00 | 23.89 | 45.33 | 23.92 |
September | 32.00 | 23.77 | 373.67 | 23.89 | 24.17 | 23.90 |
October | 171.00 | 22.87 | 182.50 | 23.88 | 37.67 | 23.84 |
November | 277.67 | 22.59 | 65.33 | 23.48 | 20.17 | 22.58 |
December | 393.00 | 21.85 | 103.00 | 21.58 | 95.00 | 21.38 |
Annual Sum or Average | 2415.17 | 22.37 | 2749.17 | 23.41 | 774.67 | 22.19 |
Minimum of Months | 32.00 | 21.42 | 65.33 | 21.15 | 19.83 | 21.11 |
Maximum of Months | 414.00 | 23.92 | 422.00 | 23.89 | 217.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.22194 | 30.70474 | -0.5983 | 13.32915 |
February | 376.00000 | 21.76076 | 32.94637 | -0.4221 | 10.72089 |
March | 422.00000 | 22.75499 | 38.74659 | -0.0740 | 7.10801 |
April | 405.00000 | 23.52698 | 44.46503 | 0.19757 | 6.90318 |
May | 418.00000 | 23.85077 | 51.85016 | -0.5225 | 11.11027 |
June | 408.00000 | 23.90943 | 51.32395 | -0.4027 | 8.55485 |
July | 415.00000 | 23.91356 | 56.06190 | -0.3382 | 7.43936 |
August | 422.00000 | 23.91436 | 55.79173 | -0.3302 | 7.33385 |
September | 405.00000 | 23.90323 | 53.99308 | -0.4314 | 9.01307 |
October | 414.00000 | 23.51897 | 47.95906 | 0.24341 | 7.18721 |
November | 399.00000 | 22.67542 | 38.63308 | -0.0872 | 7.31952 |
December | 415.00000 | 21.49728 | 35.30010 | -0.4473 | 10.64610 |
Annual Sum or Average | 4913.00000 | 23.04623 | 44.91527 | -0.2675 | 8.87967 |
Minimum of Months | 376.00000 | 21.22194 | 30.70474 | -0.5983 | 6.90318 |
Maximum of Months | 422.00000 | 23.91436 | 56.06190 | 0.24341 | 13.32915 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.27323 | 27.85556 | -0.4917 | 10.89477 |
February | 376.00000 | 21.91331 | 30.30571 | -0.2874 | 8.82643 |
March | 422.00000 | 22.96543 | 35.93828 | 0.07302 | 6.74315 |
April | 405.00000 | 23.62435 | 42.07447 | 0.31551 | 7.83462 |
May | 418.00000 | 23.86482 | 49.51961 | -0.4187 | 8.97001 |
June | 408.00000 | 23.90843 | 50.95801 | -0.3319 | 7.45678 |
July | 415.00000 | 23.91297 | 56.61627 | -0.2775 | 6.66709 |
August | 422.00000 | 23.91337 | 56.95007 | -0.2722 | 6.60604 |
September | 405.00000 | 23.89904 | 54.10462 | -0.3662 | 7.93467 |
October | 414.00000 | 23.46251 | 46.48192 | 0.30361 | 7.87365 |
November | 399.00000 | 22.69317 | 36.58559 | -0.0002 | 6.98903 |
December | 415.00000 | 21.58498 | 32.74252 | -0.3369 | 8.77200 |
Annual Sum or Average | 4913.00000 | 23.09306 | 43.45485 | -0.1742 | 7.95776 |
Minimum of Months | 376.00000 | 21.27323 | 27.85556 | -0.4917 | 6.60604 |
Maximum of Months | 422.00000 | 23.91337 | 56.95007 | 0.31551 | 10.89477 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.73676 | 26.47415 | -0.3855 | 10.01881 |
February | 376.00000 | 22.31311 | 28.41256 | -0.1995 | 8.89863 |
March | 422.00000 | 23.30495 | 33.40639 | 0.14140 | 7.25562 |
April | 405.00000 | 23.65613 | 40.52660 | 0.30280 | 7.89758 |
May | 418.00000 | 23.86457 | 47.74640 | -0.4330 | 9.34158 |
June | 408.00000 | 23.90828 | 48.62231 | -0.3201 | 7.36012 |
July | 415.00000 | 23.91232 | 53.04706 | -0.2551 | 6.44571 |
August | 422.00000 | 23.91275 | 52.32799 | -0.2248 | 6.14329 |
September | 405.00000 | 23.90651 | 49.67532 | -0.3163 | 7.28613 |
October | 414.00000 | 23.68191 | 42.94947 | 0.37984 | 8.88299 |
November | 399.00000 | 23.33492 | 33.14921 | 0.17113 | 7.24502 |
December | 415.00000 | 22.46543 | 30.13607 | -0.1347 | 7.71271 |
Annual Sum or Average | 4913.00000 | 23.33995 | 40.64311 | -0.1065 | 7.86672 |
Minimum of Months | 376.00000 | 21.73676 | 26.47415 | -0.4330 | 6.14329 |
Maximum of Months | 422.00000 | 23.91275 | 53.04706 | 0.37984 | 10.01881 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 21.40992 | 27.08459 | -0.4893 | 11.34778 |
February | 376.00000 | 21.96858 | 29.26070 | -0.3073 | 9.65986 |
March | 422.00000 | 22.94704 | 35.08841 | 0.03291 | 7.24952 |
April | 405.00000 | 23.46414 | 42.62929 | 0.23209 | 7.50762 |
May | 418.00000 | 23.81538 | 51.07897 | -0.4857 | 10.61217 |
June | 408.00000 | 23.90244 | 51.83286 | -0.3539 | 7.89277 |
July | 415.00000 | 23.91276 | 57.36080 | -0.2774 | 6.68188 |
August | 422.00000 | 23.91400 | 56.33962 | -0.2498 | 6.38278 |
September | 405.00000 | 23.89668 | 53.33264 | -0.3493 | 7.80165 |
October | 414.00000 | 23.47350 | 45.39445 | 0.31190 | 8.43280 |
November | 399.00000 | 22.97777 | 34.86017 | 0.06616 | 7.26387 |
December | 415.00000 | 21.94753 | 31.39793 | -0.2743 | 8.75472 |
Annual Sum or Average | 4913.00000 | 23.14382 | 43.08945 | -0.1787 | 8.29126 |
Minimum of Months | 376.00000 | 21.40992 | 27.08459 | -0.4893 | 6.38278 |
Maximum of Months | 422.00000 | 23.91400 | 57.36080 | 0.31190 | 11.34778 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.104319E+09 | 29165216.31 | 18.53 | 0.104319E+09 | 26.38 | 0.00 | 0.36 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 5045.02 | 28-FEB-15:10 | 5045.02 | 28-FEB-15:10 | 0.06 | 22-FEB-15:33 | 1390.40 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.106541E+10 | 0.285363E+09 | 96.01 | 0.823781E+09 | 0.241625E+09 | 0.00 | 0.68 | 30-MAR-14:20 | 0.00 | 01-MAR-00:10 | 11274.14 | 30-MAR-14:10 | 8934.32 | 30-MAR-15:00 | 3042.79 | 31-MAR-06:02 | 2927.26 | 30-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.416619E+10 | 0.110590E+10 | 235.94 | 0.340065E+10 | 0.765536E+09 | 0.00 | 0.90 | 19-APR-06:02 | 0.00 | 01-APR-00:10 | 15528.78 | 19-APR-06:02 | 11234.08 | 18-APR-13:10 | 6017.96 | 19-APR-06:02 | 3422.21 | 19-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.107800E+11 | 0.274276E+10 | 347.65 | 0.796411E+10 | 0.281592E+10 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 38691.72 | 26-MAY-06:02 | 27702.27 | 07-MAY-08:62 | 20787.65 | 26-MAY-06:02 | 8119.18 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.203035E+11 | 0.502595E+10 | 409.55 | 0.148304E+11 | 0.547306E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 39638.07 | 23-JUN-06:02 | 34606.97 | 11-JUN-08:62 | 21498.95 | 27-JUN-06:04 | 8383.27 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.244802E+11 | 0.599511E+10 | 426.81 | 0.169414E+11 | 0.753884E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 40162.58 | 30-JUL-08:62 | 28618.75 | 17-JUL-05:03 | 22496.25 | 31-JUL-06:04 | 8567.59 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.266825E+11 | 0.644179E+10 | 441.20 | 0.181611E+11 | 0.852133E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 40733.21 | 20-AUG-07:03 | 29261.43 | 26-AUG-06:04 | 22018.66 | 23-AUG-06:04 | 8513.28 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.155398E+11 | 0.379223E+10 | 378.84 | 0.108295E+11 | 0.471030E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 40489.52 | 17-SEP-08:62 | 28565.67 | 24-SEP-08:62 | 19913.13 | 17-SEP-08:04 | 8443.27 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.449653E+10 | 0.112602E+10 | 213.92 | 0.313049E+10 | 0.136605E+10 | 0.00 | 1.00 | 11-OCT-06:02 | 0.00 | 01-OCT-00:10 | 39704.05 | 19-OCT-06:02 | 20672.61 | 11-OCT-06:02 | 23439.54 | 19-OCT-06:04 | 8223.29 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.408801E+09 | 0.108641E+09 | 79.22 | 0.282018E+09 | 0.126783E+09 | 0.00 | 0.47 | 05-NOV-15:30 | 0.00 | 01-NOV-00:10 | 7494.46 | 05-NOV-15:00 | 5189.02 | 05-NOV-16:00 | 2989.02 | 04-NOV-15:55 | 1935.33 | 05-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 14226507.96 | 4014965.96 | 7.88 | 10216791.78 | 4009716.18 | 0.00 | 0.13 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 1781.71 | 12-DEC-15:10 | 1322.32 | 12-DEC-15:10 | 459.40 | 12-DEC-15:10 | 500.28 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.108041E+12 | 0.266570E+11 | 2655.55 | 0.764780E+11 | 0.315635E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.266825E+11 | 0.644179E+10 | 441.20 | 0.181611E+11 | 0.852133E+10 | 0.00 | 1.00 | 0.00 | 40733.21 | 34606.97 | 23439.54 | 8567.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 998499.03 | 315908.49 | 1.50 | 821601.71 | 176897.32 | 0.00 | 0.02 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 975.02 | 31-JAN-15:10 | 805.45 | 31-JAN-15:10 | 169.58 | 31-JAN-15:10 | 308.24 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.155849E+10 | 0.476470E+09 | 40.65 | 0.153054E+10 | 27948803.00 | 0.00 | 0.44 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 29971.07 | 28-FEB-15:10 | 29004.31 | 28-FEB-15:10 | 966.77 | 28-FEB-15:10 | 9017.04 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.895129E+10 | 0.261622E+10 | 144.36 | 0.672519E+10 | 0.222609E+10 | 0.00 | 1.00 | 30-MAR-06:03 | 0.00 | 01-MAR-00:10 | 175184.59 | 30-MAR-06:03 | 101448.71 | 31-MAR-06:02 | 73931.92 | 30-MAR-06:03 | 41574.43 | 30-MAR-06:03 | 0.00 | 01-MAR-00:10 |
April | 0.290878E+11 | 0.838281E+10 | 268.46 | 0.227928E+11 | 0.629494E+10 | 0.00 | 1.00 | 16-APR-08:62 | 0.00 | 01-APR-00:10 | 178518.31 | 23-APR-08:62 | 130629.33 | 16-APR-08:62 | 88887.78 | 23-APR-08:62 | 42186.15 | 23-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.623757E+11 | 0.173127E+11 | 371.87 | 0.439565E+11 | 0.184192E+11 | 0.00 | 1.00 | 03-MAY-06:03 | 0.00 | 01-MAY-00:10 | 182316.39 | 31-MAY-06:02 | 124135.93 | 30-MAY-06:02 | 92372.92 | 26-MAY-06:02 | 42772.28 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.102240E+12 | 0.277747E+11 | 416.09 | 0.694702E+11 | 0.327695E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 184742.26 | 18-JUN-08:62 | 155047.89 | 11-JUN-08:62 | 89302.55 | 21-JUN-06:02 | 43999.68 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.121642E+12 | 0.326073E+11 | 430.43 | 0.766490E+11 | 0.449930E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 189949.05 | 30-JUL-08:62 | 126962.57 | 25-JUL-06:02 | 99484.94 | 28-JUL-06:02 | 45235.71 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.130347E+12 | 0.344805E+11 | 441.21 | 0.798936E+11 | 0.504533E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 188290.66 | 20-AUG-08:62 | 133590.21 | 26-AUG-06:02 | 98234.57 | 23-AUG-06:02 | 44820.58 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.772200E+11 | 0.207853E+11 | 386.92 | 0.490256E+11 | 0.281944E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 189772.01 | 17-SEP-08:62 | 125888.05 | 16-SEP-06:02 | 91251.12 | 17-SEP-08:04 | 44461.30 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.265634E+11 | 0.735786E+10 | 227.63 | 0.178081E+11 | 0.875531E+10 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 186467.85 | 19-OCT-06:02 | 113712.36 | 12-OCT-06:02 | 104365.58 | 19-OCT-06:04 | 43268.27 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.429001E+10 | 0.126814E+10 | 104.97 | 0.306617E+10 | 0.122384E+10 | 0.00 | 0.50 | 05-NOV-15:50 | 0.00 | 01-NOV-00:10 | 116156.59 | 04-NOV-06:03 | 62981.33 | 04-NOV-06:03 | 53175.26 | 04-NOV-06:03 | 27622.01 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.447303E+09 | 0.135496E+09 | 14.83 | 0.290966E+09 | 0.156337E+09 | 0.00 | 0.31 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 | 21849.75 | 12-DEC-15:10 | 15456.01 | 12-DEC-15:10 | 7150.85 | 12-DEC-14:00 | 6529.42 | 12-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.564724E+12 | 0.153198E+12 | 2848.92 | 0.371210E+12 | 0.193514E+12 | 0.00 | ||||||||||||||
Minimum of Months | 998499.03 | 315908.49 | 1.50 | 821601.71 | 176897.32 | 0.00 | 0.02 | 0.00 | 975.02 | 805.45 | 169.58 | 308.24 | 0.00 | |||||||
Maximum of Months | 0.130347E+12 | 0.344805E+11 | 441.21 | 0.798936E+11 | 0.504533E+11 | 0.00 | 1.00 | 0.00 | 189949.05 | 155047.89 | 104365.58 | 45235.71 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 29127746.16 | 7860374.92 | 22.91 | 24249909.93 | 4877836.22 | 0.00 | 0.26 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 | 2274.74 | 31-JAN-15:10 | 2014.96 | 31-JAN-15:00 | 311.86 | 31-JAN-16:00 | 602.82 | 31-JAN-15:10 | 0.00 | 01-JAN-00:10 |
February | 0.664271E+09 | 0.168786E+09 | 81.46 | 0.661071E+09 | 3200559.13 | 0.00 | 0.74 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 7271.90 | 28-FEB-15:10 | 7271.90 | 28-FEB-15:10 | 284.28 | 22-FEB-15:10 | 1790.08 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.208564E+10 | 0.522288E+09 | 207.40 | 0.169012E+10 | 0.395518E+09 | 0.00 | 1.00 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 | 22786.94 | 31-MAR-06:02 | 13237.23 | 31-MAR-06:02 | 9549.71 | 31-MAR-06:02 | 4843.26 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.460320E+10 | 0.115899E+10 | 282.58 | 0.381022E+10 | 0.792984E+09 | 0.00 | 1.00 | 18-APR-06:02 | 0.00 | 01-APR-00:10 | 22124.82 | 19-APR-06:02 | 14162.93 | 18-APR-06:02 | 8189.53 | 19-APR-06:02 | 4711.55 | 19-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.879641E+10 | 0.216407E+10 | 368.32 | 0.663950E+10 | 0.215691E+10 | 0.00 | 1.00 | 06-MAY-06:02 | 0.00 | 01-MAY-00:10 | 23868.26 | 31-MAY-06:02 | 16878.63 | 30-MAY-06:02 | 12202.48 | 31-MAY-06:02 | 5008.97 | 31-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.140856E+11 | 0.344089E+10 | 409.94 | 0.103544E+11 | 0.373118E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 24555.08 | 26-JUN-05:03 | 21089.51 | 11-JUN-08:62 | 13394.33 | 27-JUN-06:02 | 5177.51 | 26-JUN-05:03 | 0.00 | 01-JUN-00:10 |
July | 0.169192E+11 | 0.410527E+10 | 429.21 | 0.117409E+11 | 0.517826E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 24879.20 | 30-JUL-08:62 | 17567.85 | 15-JUL-05:03 | 14025.56 | 31-JUL-06:02 | 5282.67 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.190327E+11 | 0.455649E+10 | 443.22 | 0.130987E+11 | 0.593401E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 25284.23 | 20-AUG-07:03 | 18246.45 | 26-AUG-06:02 | 13462.65 | 23-AUG-06:04 | 5248.24 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.125450E+11 | 0.296528E+10 | 393.49 | 0.898517E+10 | 0.355981E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 24881.80 | 17-SEP-08:62 | 17800.43 | 08-SEP-05:03 | 13708.69 | 03-SEP-08:62 | 5206.35 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.579309E+10 | 0.136883E+10 | 276.76 | 0.443872E+10 | 0.135438E+10 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 24504.99 | 19-OCT-06:02 | 14752.76 | 09-OCT-08:62 | 14478.57 | 19-OCT-06:02 | 5074.38 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.196134E+10 | 0.485483E+09 | 184.02 | 0.160660E+10 | 0.354748E+09 | 0.00 | 0.81 | 02-NOV-14:30 | 0.00 | 01-NOV-00:10 | 11399.55 | 04-NOV-06:03 | 6701.59 | 02-NOV-14:30 | 5142.53 | 04-NOV-06:03 | 2428.80 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 |
December | 0.374084E+09 | 92848438.82 | 67.13 | 0.260116E+09 | 0.113968E+09 | 0.00 | 0.80 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 8496.16 | 12-DEC-14:00 | 6467.81 | 12-DEC-14:00 | 3335.10 | 13-DEC-07:03 | 1973.38 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.868896E+11 | 0.210371E+11 | 3166.44 | 0.633098E+11 | 0.235799E+11 | 0.00 | ||||||||||||||
Minimum of Months | 29127746.16 | 7860374.92 | 22.91 | 24249909.93 | 3200559.13 | 0.00 | 0.26 | 0.00 | 2274.74 | 2014.96 | 284.28 | 602.82 | 0.00 | |||||||
Maximum of Months | 0.190327E+11 | 0.455649E+10 | 443.22 | 0.130987E+11 | 0.593401E+10 | 0.00 | 1.00 | 0.00 | 25284.23 | 21089.51 | 14478.57 | 5282.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 404109.17 | 99500.53 | 7.64 | 361275.29 | 42833.88 | 0.00 | 0.03 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 | 188.52 | 31-JAN-15:00 | 170.47 | 31-JAN-15:00 | 18.06 | 31-JAN-15:00 | 46.35 | 31-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.348460E+09 | 78920958.45 | 55.46 | 0.348353E+09 | 107431.41 | 0.00 | 0.66 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 5575.27 | 28-FEB-15:10 | 5575.27 | 28-FEB-15:10 | 19.03 | 28-FEB-11:10 | 1227.64 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 |
March | 0.106985E+10 | 0.239691E+09 | 152.59 | 0.861776E+09 | 0.208069E+09 | 0.00 | 1.00 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 | 18407.45 | 31-MAR-06:02 | 10442.79 | 31-MAR-06:02 | 7964.66 | 31-MAR-06:02 | 3610.10 | 31-MAR-06:02 | 0.00 | 01-MAR-00:10 |
April | 0.288580E+10 | 0.651664E+09 | 238.75 | 0.240788E+10 | 0.477926E+09 | 0.00 | 0.82 | 17-APR-14:20 | 0.00 | 01-APR-00:10 | 15259.68 | 19-APR-06:02 | 9361.25 | 19-APR-06:02 | 5898.42 | 19-APR-06:02 | 2964.97 | 19-APR-06:02 | 0.00 | 01-APR-00:10 |
May | 0.608075E+10 | 0.133407E+10 | 333.50 | 0.456173E+10 | 0.151902E+10 | 0.00 | 1.00 | 06-MAY-06:02 | 0.00 | 01-MAY-00:10 | 19310.16 | 26-MAY-06:02 | 12732.17 | 30-MAY-06:02 | 10516.37 | 26-MAY-06:02 | 3737.21 | 26-MAY-06:02 | 0.00 | 01-MAY-00:10 |
June | 0.113555E+11 | 0.244726E+10 | 403.09 | 0.816462E+10 | 0.319087E+10 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 19821.74 | 23-JUN-06:02 | 16524.89 | 11-JUN-08:62 | 11005.73 | 27-JUN-06:04 | 3861.74 | 25-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.138222E+11 | 0.296488E+10 | 425.28 | 0.936498E+10 | 0.445724E+10 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:10 | 20179.53 | 30-JUL-08:62 | 12605.57 | 15-JUL-06:02 | 11405.55 | 31-JUL-06:04 | 3950.89 | 16-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.158666E+11 | 0.335987E+10 | 445.66 | 0.105977E+11 | 0.526891E+10 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 20187.96 | 20-AUG-08:62 | 12629.93 | 03-AUG-05:02 | 11132.70 | 23-AUG-06:04 | 3917.22 | 20-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.976716E+10 | 0.204463E+10 | 377.55 | 0.686553E+10 | 0.290163E+10 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:10 | 20232.45 | 17-SEP-08:62 | 13271.19 | 16-SEP-06:02 | 11173.14 | 03-SEP-08:62 | 3885.18 | 17-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.389678E+10 | 0.816394E+09 | 232.50 | 0.292405E+10 | 0.972722E+09 | 0.00 | 1.00 | 09-OCT-08:62 | 0.00 | 01-OCT-00:10 | 19819.32 | 19-OCT-06:02 | 11645.31 | 09-OCT-08:62 | 11809.30 | 19-OCT-06:02 | 3784.72 | 19-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.827798E+09 | 0.184610E+09 | 128.78 | 0.674031E+09 | 0.153767E+09 | 0.00 | 0.73 | 05-NOV-13:40 | 0.00 | 01-NOV-00:10 | 6885.23 | 05-NOV-13:30 | 4728.30 | 08-NOV-15:10 | 2349.01 | 05-NOV-13:20 | 1413.44 | 05-NOV-13:40 | 0.00 | 01-NOV-00:10 |
December | 0.124015E+09 | 27786967.33 | 32.49 | 87981263.95 | 36034155.42 | 0.00 | 0.63 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 5711.63 | 12-DEC-14:00 | 4042.93 | 12-DEC-14:00 | 1668.70 | 12-DEC-14:00 | 1213.10 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.660453E+11 | 0.141499E+11 | 2833.27 | 0.468590E+11 | 0.191863E+11 | 0.00 | ||||||||||||||
Minimum of Months | 404109.17 | 99500.53 | 7.64 | 361275.29 | 42833.88 | 0.00 | 0.03 | 0.00 | 188.52 | 170.47 | 18.06 | 46.35 | 0.00 | |||||||
Maximum of Months | 0.158666E+11 | 0.335987E+10 | 445.66 | 0.105977E+11 | 0.526891E+10 | 0.00 | 1.00 | 0.00 | 20232.45 | 16524.89 | 11809.30 | 3950.89 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.45 | 35.62 | 28.83 | 59.00 | 77.24 | 2.17 | 0.00 | 744.00 |
February | 80.55 | 49.88 | 30.67 | 85.10 | 67.07 | 4.67 | 0.00 | 672.00 |
March | 116.88 | 71.36 | 45.52 | 138.03 | 48.51 | 0.00 | 0.00 | 744.00 |
April | 147.03 | 90.61 | 56.42 | 186.13 | 40.80 | 0.00 | 0.00 | 720.00 |
May | 162.85 | 93.43 | 69.42 | 214.44 | 28.79 | 0.00 | 0.00 | 744.00 |
June | 173.77 | 101.69 | 72.07 | 238.57 | 21.90 | 0.00 | 0.00 | 720.00 |
July | 161.80 | 90.85 | 70.95 | 226.08 | 17.01 | 0.00 | 0.00 | 744.00 |
August | 148.91 | 80.81 | 68.11 | 209.57 | 16.30 | 0.00 | 0.00 | 744.00 |
September | 111.46 | 61.91 | 49.54 | 147.11 | 27.50 | 0.00 | 0.00 | 720.00 |
October | 95.58 | 64.22 | 31.36 | 115.99 | 46.83 | 0.00 | 0.00 | 744.00 |
November | 71.19 | 40.30 | 30.89 | 77.89 | 59.37 | 9.67 | 0.00 | 720.00 |
December | 58.27 | 31.76 | 26.51 | 56.35 | 68.76 | 12.67 | 0.00 | 744.00 |
Annual Sum or Average | 116.25 | 67.79 | 48.46 | 146.51 | 43.21 | 29.17 | 0.00 | 8760.00 |
Minimum of Months | 58.27 | 31.76 | 26.51 | 56.35 | 16.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.77 | 101.69 | 72.07 | 238.57 | 77.24 | 12.67 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 979.37 | 930.72 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 964.08 | 808.51 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 870.39 | 578.88 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 662.72 | 476.73 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 577.24 | 321.10 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 673.28 | 218.02 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 716.61 | 161.88 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 847.22 | 146.61 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 798.14 | 291.42 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1070.91 | 567.07 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1083.76 | 707.96 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1028.68 | 819.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 855.71 | 500.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 577.24 | 146.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1083.76 | 930.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 866.15 | 603.94 | 262.21 | 985.71 | 907.01 | 0.00 | 0.00 | 744.00 |
February | 808.40 | 541.95 | 266.45 | 968.87 | 781.33 | 0.00 | 0.00 | 672.00 |
March | 726.74 | 378.67 | 348.06 | 877.49 | 550.35 | 0.00 | 0.00 | 744.00 |
April | 544.19 | 177.02 | 367.17 | 665.90 | 453.46 | 0.00 | 0.00 | 720.00 |
May | 439.66 | 50.95 | 388.71 | 576.74 | 303.08 | 0.00 | 0.00 | 744.00 |
June | 406.50 | 22.47 | 384.04 | 670.21 | 203.49 | 0.00 | 0.00 | 720.00 |
July | 410.98 | 30.50 | 380.48 | 713.70 | 148.33 | 0.00 | 0.00 | 744.00 |
August | 490.71 | 91.54 | 399.17 | 843.61 | 132.77 | 0.00 | 0.00 | 744.00 |
September | 539.68 | 200.64 | 339.04 | 795.60 | 276.33 | 0.00 | 0.00 | 720.00 |
October | 782.65 | 507.02 | 275.63 | 1071.86 | 544.41 | 0.00 | 0.00 | 744.00 |
November | 842.16 | 558.92 | 283.24 | 1089.57 | 680.51 | 0.00 | 0.00 | 720.00 |
December | 853.76 | 600.68 | 253.08 | 1036.74 | 786.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.92 | 312.63 | 329.30 | 857.67 | 478.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.50 | 22.47 | 253.08 | 576.74 | 132.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 866.15 | 603.94 | 399.17 | 1089.57 | 907.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 178.22 | 124.27 | 53.95 | 215.42 | 162.31 | 0.00 | 0.00 | 744.00 |
February | 166.34 | 111.51 | 54.83 | 208.77 | 140.92 | 0.00 | 0.00 | 672.00 |
March | 149.54 | 77.92 | 71.62 | 193.12 | 99.86 | 0.00 | 0.00 | 744.00 |
April | 111.97 | 36.42 | 75.55 | 140.62 | 86.71 | 0.00 | 0.00 | 720.00 |
May | 90.47 | 10.48 | 79.98 | 113.91 | 61.34 | 0.00 | 0.00 | 744.00 |
June | 83.64 | 4.62 | 79.02 | 117.82 | 45.89 | 0.00 | 0.00 | 720.00 |
July | 84.56 | 6.28 | 78.29 | 123.05 | 35.51 | 0.00 | 0.00 | 744.00 |
August | 100.97 | 18.84 | 82.13 | 148.03 | 33.99 | 0.00 | 0.00 | 744.00 |
September | 111.05 | 41.28 | 69.76 | 153.25 | 59.00 | 0.00 | 0.00 | 720.00 |
October | 161.04 | 104.33 | 56.72 | 224.51 | 101.99 | 0.00 | 0.00 | 744.00 |
November | 173.29 | 115.01 | 58.28 | 234.79 | 123.01 | 0.00 | 0.00 | 720.00 |
December | 175.67 | 123.60 | 52.08 | 228.30 | 136.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 132.08 | 64.33 | 67.76 | 175.01 | 90.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 83.64 | 4.62 | 52.08 | 113.91 | 33.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 178.22 | 124.27 | 82.13 | 234.79 | 162.31 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172635E+09 | 95413690.10 | 77221269.73 | 0.158038E+09 | 0.206889E+09 |
February | 0.194858E+09 | 0.120666E+09 | 74192313.62 | 0.205886E+09 | 0.162245E+09 |
March | 0.313045E+09 | 0.191129E+09 | 0.121916E+09 | 0.369693E+09 | 0.129931E+09 |
April | 0.381089E+09 | 0.234852E+09 | 0.146237E+09 | 0.482461E+09 | 0.105743E+09 |
May | 0.436178E+09 | 0.250247E+09 | 0.185931E+09 | 0.574349E+09 | 77105499.10 |
June | 0.450402E+09 | 0.263593E+09 | 0.186809E+09 | 0.618369E+09 | 56760978.97 |
July | 0.433368E+09 | 0.243339E+09 | 0.190029E+09 | 0.605531E+09 | 45559772.10 |
August | 0.398843E+09 | 0.216428E+09 | 0.182415E+09 | 0.561320E+09 | 43661588.03 |
September | 0.288893E+09 | 0.160481E+09 | 0.128412E+09 | 0.381310E+09 | 71279793.10 |
October | 0.255999E+09 | 0.172001E+09 | 83998314.46 | 0.310660E+09 | 0.125436E+09 |
November | 0.184524E+09 | 0.104468E+09 | 80055914.30 | 0.201889E+09 | 0.153883E+09 |
December | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 0.184160E+09 |
Annual Sum or Average | 0.366591E+10 | 0.213768E+10 | 0.152823E+10 | 0.462043E+10 | 0.136266E+10 |
Minimum of Months | 0.156075E+09 | 85062197.81 | 71012508.49 | 0.150921E+09 | 43661588.03 |
Maximum of Months | 0.450402E+09 | 0.263593E+09 | 0.190029E+09 | 0.618369E+09 | 0.206889E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.262315E+10 | 0.249285E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.233230E+10 | 0.195596E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.233125E+10 | 0.155048E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.171778E+10 | 0.123569E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.154607E+10 | 0.860038E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.174514E+10 | 0.565118E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.191938E+10 | 0.433592E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.226920E+10 | 0.392672E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.206878E+10 | 0.755354E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.286833E+10 | 0.151885E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.280912E+10 | 0.183503E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.275523E+10 | 0.219459E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.269857E+11 | 0.157902E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.154607E+10 | 0.392672E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.286833E+10 | 0.249285E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.264013E+10 | 0.242934E+10 |
February | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.234389E+10 | 0.189020E+10 |
March | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.235026E+10 | 0.147406E+10 |
April | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.172602E+10 | 0.117536E+10 |
May | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.154474E+10 | 0.811766E+09 |
June | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.173719E+10 | 0.527437E+09 |
July | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.191157E+10 | 0.397299E+09 |
August | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.225952E+10 | 0.355621E+09 |
September | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.206220E+10 | 0.716252E+09 |
October | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.287087E+10 | 0.145814E+10 |
November | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.282417E+10 | 0.176389E+10 |
December | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.277680E+10 | 0.210532E+10 |
Annual Sum or Average | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.270474E+11 | 0.151047E+11 |
Minimum of Months | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.154474E+10 | 0.355621E+09 |
Maximum of Months | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.287087E+10 | 0.242934E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.576983E+09 | 0.434744E+09 |
February | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.505068E+09 | 0.340923E+09 |
March | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.517254E+09 | 0.267462E+09 |
April | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.364492E+09 | 0.224756E+09 |
May | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.305106E+09 | 0.164298E+09 |
June | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.305398E+09 | 0.118953E+09 |
July | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.329588E+09 | 95103079.27 |
August | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.396478E+09 | 91026747.36 |
September | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.397237E+09 | 0.152938E+09 |
October | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.601317E+09 | 0.273176E+09 |
November | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.608575E+09 | 0.318830E+09 |
December | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.611487E+09 | 0.366480E+09 |
Annual Sum or Average | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.551898E+10 | 0.284869E+10 |
Minimum of Months | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.305106E+09 | 91026747.36 |
Maximum of Months | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.611487E+09 | 0.434744E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 944.07 | 1235.90 | 1031.27 | 569.97 | 461.30 | 0.00 | 0.00 |
February | 1361.68 | 1073.05 | 1288.74 | 798.05 | 490.69 | 0.00 | 0.00 |
March | 2208.44 | 776.17 | 1870.04 | 1141.75 | 728.29 | 0.00 | 0.00 |
April | 2978.16 | 652.74 | 2352.40 | 1449.70 | 902.70 | 0.00 | 0.00 |
May | 3431.00 | 460.61 | 2605.60 | 1494.90 | 1110.70 | 0.00 | 0.00 |
June | 3817.09 | 350.38 | 2780.26 | 1627.12 | 1153.14 | 0.00 | 0.00 |
July | 3617.27 | 272.16 | 2588.82 | 1453.64 | 1135.18 | 0.00 | 0.00 |
August | 3353.16 | 260.82 | 2382.58 | 1292.88 | 1089.69 | 0.00 | 0.00 |
September | 2353.77 | 440.00 | 1783.29 | 990.62 | 792.67 | 0.00 | 0.00 |
October | 1855.80 | 749.32 | 1529.27 | 1027.48 | 501.78 | 0.00 | 0.00 |
November | 1246.23 | 949.90 | 1139.03 | 644.86 | 494.17 | 0.00 | 0.00 |
December | 901.56 | 1100.12 | 932.35 | 508.14 | 424.21 | 0.00 | 0.00 |
Annual Sum or Average | 2344.20 | 691.35 | 1859.92 | 1084.56 | 775.36 | 0.00 | 0.00 |
Minimum of Months | 901.56 | 260.82 | 932.35 | 508.14 | 424.21 | 0.00 | 0.00 |
Maximum of Months | 3817.09 | 1235.90 | 2780.26 | 1627.12 | 1153.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 979.37 | 930.72 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 964.08 | 808.51 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 870.39 | 578.88 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 662.72 | 476.73 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 577.24 | 321.10 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 673.28 | 218.02 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 716.61 | 161.88 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 847.22 | 146.61 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 798.14 | 291.42 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1070.91 | 567.07 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1083.76 | 707.96 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1028.68 | 819.37 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 855.71 | 500.70 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 577.24 | 146.61 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1083.76 | 930.72 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 985.71 | 907.01 | 866.15 | 603.94 | 262.21 | 0.00 | 0.00 |
February | 968.87 | 781.33 | 808.40 | 541.95 | 266.45 | 0.00 | 0.00 |
March | 877.49 | 550.35 | 726.74 | 378.67 | 348.06 | 0.00 | 0.00 |
April | 665.90 | 453.46 | 544.19 | 177.02 | 367.17 | 0.00 | 0.00 |
May | 576.74 | 303.08 | 439.66 | 50.95 | 388.71 | 0.00 | 0.00 |
June | 670.21 | 203.49 | 406.50 | 22.47 | 384.04 | 0.00 | 0.00 |
July | 713.70 | 148.33 | 410.98 | 30.50 | 380.48 | 0.00 | 0.00 |
August | 843.61 | 132.77 | 490.71 | 91.54 | 399.17 | 0.00 | 0.00 |
September | 795.60 | 276.33 | 539.68 | 200.64 | 339.04 | 0.00 | 0.00 |
October | 1071.86 | 544.41 | 782.65 | 507.02 | 275.63 | 0.00 | 0.00 |
November | 1089.57 | 680.51 | 842.16 | 558.92 | 283.24 | 0.00 | 0.00 |
December | 1036.74 | 786.03 | 853.76 | 600.68 | 253.08 | 0.00 | 0.00 |
Annual Sum or Average | 857.67 | 478.97 | 641.92 | 312.63 | 329.30 | 0.00 | 0.00 |
Minimum of Months | 576.74 | 132.77 | 406.50 | 22.47 | 253.08 | 0.00 | 0.00 |
Maximum of Months | 1089.57 | 907.01 | 866.15 | 603.94 | 399.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.42 | 162.31 | 178.22 | 124.27 | 53.95 | 0.00 | 0.00 |
February | 208.77 | 140.92 | 166.34 | 111.51 | 54.83 | 0.00 | 0.00 |
March | 193.12 | 99.86 | 149.54 | 77.92 | 71.62 | 0.00 | 0.00 |
April | 140.62 | 86.71 | 111.97 | 36.42 | 75.55 | 0.00 | 0.00 |
May | 113.91 | 61.34 | 90.47 | 10.48 | 79.98 | 0.00 | 0.00 |
June | 117.82 | 45.89 | 83.64 | 4.62 | 79.02 | 0.00 | 0.00 |
July | 123.05 | 35.51 | 84.56 | 6.28 | 78.29 | 0.00 | 0.00 |
August | 148.03 | 33.99 | 100.97 | 18.84 | 82.13 | 0.00 | 0.00 |
September | 153.25 | 59.00 | 111.05 | 41.28 | 69.76 | 0.00 | 0.00 |
October | 224.51 | 101.99 | 161.04 | 104.33 | 56.72 | 0.00 | 0.00 |
November | 234.79 | 123.01 | 173.29 | 115.01 | 58.28 | 0.00 | 0.00 |
December | 228.30 | 136.83 | 175.67 | 123.60 | 52.08 | 0.00 | 0.00 |
Annual Sum or Average | 175.01 | 90.33 | 132.08 | 64.33 | 67.76 | 0.00 | 0.00 |
Minimum of Months | 113.91 | 33.99 | 83.64 | 4.62 | 52.08 | 0.00 | 0.00 |
Maximum of Months | 234.79 | 162.31 | 178.22 | 124.27 | 82.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252860E+10 | 0.331023E+10 | 0.276216E+10 | 0.152662E+10 | 0.123554E+10 | 0.00 | 0.00 |
February | 0.329417E+10 | 0.259593E+10 | 0.311773E+10 | 0.193065E+10 | 0.118708E+10 | 0.00 | 0.00 |
March | 0.591509E+10 | 0.207889E+10 | 0.500872E+10 | 0.305806E+10 | 0.195066E+10 | 0.00 | 0.00 |
April | 0.771938E+10 | 0.169189E+10 | 0.609743E+10 | 0.375763E+10 | 0.233980E+10 | 0.00 | 0.00 |
May | 0.918958E+10 | 0.123369E+10 | 0.697884E+10 | 0.400395E+10 | 0.297490E+10 | 0.00 | 0.00 |
June | 0.989391E+10 | 0.908176E+09 | 0.720643E+10 | 0.421748E+10 | 0.298895E+10 | 0.00 | 0.00 |
July | 0.968850E+10 | 0.728956E+09 | 0.693388E+10 | 0.389342E+10 | 0.304046E+10 | 0.00 | 0.00 |
August | 0.898112E+10 | 0.698585E+09 | 0.638149E+10 | 0.346285E+10 | 0.291864E+10 | 0.00 | 0.00 |
September | 0.610097E+10 | 0.114048E+10 | 0.462229E+10 | 0.256769E+10 | 0.205460E+10 | 0.00 | 0.00 |
October | 0.497057E+10 | 0.200697E+10 | 0.409599E+10 | 0.275201E+10 | 0.134397E+10 | 0.00 | 0.00 |
November | 0.323022E+10 | 0.246213E+10 | 0.295238E+10 | 0.167148E+10 | 0.128089E+10 | 0.00 | 0.00 |
December | 0.241473E+10 | 0.294656E+10 | 0.249720E+10 | 0.136100E+10 | 0.113620E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.739268E+11 | 0.218025E+11 | 0.586545E+11 | 0.342028E+11 | 0.244517E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241473E+10 | 0.698585E+09 | 0.249720E+10 | 0.136100E+10 | 0.113620E+10 | 0.00 | 0.00 |
Maximum of Months | 0.989391E+10 | 0.331023E+10 | 0.720643E+10 | 0.421748E+10 | 0.304046E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.262315E+10 | 0.249285E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.233230E+10 | 0.195596E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.233125E+10 | 0.155048E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.171778E+10 | 0.123569E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.154607E+10 | 0.860038E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.174514E+10 | 0.565118E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.191938E+10 | 0.433592E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.226920E+10 | 0.392672E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.206878E+10 | 0.755354E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.286833E+10 | 0.151885E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.280912E+10 | 0.183503E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.275523E+10 | 0.219459E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.269857E+11 | 0.157902E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154607E+10 | 0.392672E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.286833E+10 | 0.249285E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264013E+10 | 0.242934E+10 | 0.231990E+10 | 0.161759E+10 | 0.702308E+09 | 0.00 | 0.00 |
February | 0.234389E+10 | 0.189020E+10 | 0.195567E+10 | 0.131108E+10 | 0.644589E+09 | 0.00 | 0.00 |
March | 0.235026E+10 | 0.147406E+10 | 0.194650E+10 | 0.101424E+10 | 0.932255E+09 | 0.00 | 0.00 |
April | 0.172602E+10 | 0.117536E+10 | 0.141053E+10 | 0.458839E+09 | 0.951695E+09 | 0.00 | 0.00 |
May | 0.154474E+10 | 0.811766E+09 | 0.117758E+10 | 0.136466E+09 | 0.104112E+10 | 0.00 | 0.00 |
June | 0.173719E+10 | 0.527437E+09 | 0.105366E+10 | 58231071.12 | 0.995429E+09 | 0.00 | 0.00 |
July | 0.191157E+10 | 0.397299E+09 | 0.110077E+10 | 81695334.73 | 0.101907E+10 | 0.00 | 0.00 |
August | 0.225952E+10 | 0.355621E+09 | 0.131433E+10 | 0.245192E+09 | 0.106914E+10 | 0.00 | 0.00 |
September | 0.206220E+10 | 0.716252E+09 | 0.139885E+10 | 0.520056E+09 | 0.878796E+09 | 0.00 | 0.00 |
October | 0.287087E+10 | 0.145814E+10 | 0.209624E+10 | 0.135799E+10 | 0.738250E+09 | 0.00 | 0.00 |
November | 0.282417E+10 | 0.176389E+10 | 0.218287E+10 | 0.144871E+10 | 0.734162E+09 | 0.00 | 0.00 |
December | 0.277680E+10 | 0.210532E+10 | 0.228670E+10 | 0.160885E+10 | 0.677853E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.270474E+11 | 0.151047E+11 | 0.202436E+11 | 0.985895E+10 | 0.103847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154474E+10 | 0.355621E+09 | 0.105366E+10 | 58231071.12 | 0.644589E+09 | 0.00 | 0.00 |
Maximum of Months | 0.287087E+10 | 0.242934E+10 | 0.231990E+10 | 0.161759E+10 | 0.106914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.576983E+09 | 0.434744E+09 | 0.477354E+09 | 0.332844E+09 | 0.144510E+09 | 0.00 | 0.00 |
February | 0.505068E+09 | 0.340923E+09 | 0.402408E+09 | 0.269774E+09 | 0.132634E+09 | 0.00 | 0.00 |
March | 0.517254E+09 | 0.267462E+09 | 0.400520E+09 | 0.208695E+09 | 0.191825E+09 | 0.00 | 0.00 |
April | 0.364492E+09 | 0.224756E+09 | 0.290238E+09 | 94412838.34 | 0.195825E+09 | 0.00 | 0.00 |
May | 0.305106E+09 | 0.164298E+09 | 0.242305E+09 | 28079908.65 | 0.214225E+09 | 0.00 | 0.00 |
June | 0.305398E+09 | 0.118953E+09 | 0.216806E+09 | 11981890.80 | 0.204824E+09 | 0.00 | 0.00 |
July | 0.329588E+09 | 95103079.27 | 0.226499E+09 | 16810004.70 | 0.209689E+09 | 0.00 | 0.00 |
August | 0.396478E+09 | 91026747.36 | 0.270442E+09 | 50451868.80 | 0.219990E+09 | 0.00 | 0.00 |
September | 0.397237E+09 | 0.152938E+09 | 0.287834E+09 | 0.107009E+09 | 0.180825E+09 | 0.00 | 0.00 |
October | 0.601317E+09 | 0.273176E+09 | 0.431332E+09 | 0.279427E+09 | 0.151906E+09 | 0.00 | 0.00 |
November | 0.608575E+09 | 0.318830E+09 | 0.449158E+09 | 0.298093E+09 | 0.151064E+09 | 0.00 | 0.00 |
December | 0.611487E+09 | 0.366480E+09 | 0.470522E+09 | 0.331044E+09 | 0.139478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.551898E+10 | 0.284869E+10 | 0.416542E+10 | 0.202862E+10 | 0.213680E+10 | 0.00 | 0.00 |
Minimum of Months | 0.305106E+09 | 91026747.36 | 0.216806E+09 | 11981890.80 | 0.132634E+09 | 0.00 | 0.00 |
Maximum of Months | 0.611487E+09 | 0.434744E+09 | 0.477354E+09 | 0.332844E+09 | 0.219990E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.45 | -3.0 | 4.56 | -7.9 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.23 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.96 | 3.80 | 4.89 | 2.24 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.53 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.43 | 13.69 | 3.50 | 11.45 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.34 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.67 | 19.85 | 3.24 | 17.63 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.41 | 20.72 | 3.39 | 18.20 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.43 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.01 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.21 | 4.17 | 4.16 | 0.29 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.67 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.28 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.45 | -3.0 | 3.06 | -7.9 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.41 | 20.72 | 5.19 | 18.20 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.95 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.72 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.85 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.53 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.47 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.37 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.89 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.82 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.04 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.54 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.94 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.76 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.72 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.89 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.7 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.7 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.4 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.0 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.44 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.1 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.7 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.80 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.15 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.00 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.33 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.31 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.05 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.12 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.09 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.19 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.87 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.80 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.12 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.80 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.78 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.09 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.88 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.80 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.254193E+10 | -.214399E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -397944700.5 | 58.99 | 0.00 | 0.00 |
February | 0.230859E+10 | -.195631E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -352282827.0 | 58.99 | 0.00 | 0.00 |
March | 0.251988E+10 | -.214512E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -374760686.1 | 58.99 | 0.00 | 0.00 |
April | 0.226139E+10 | -.190923E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -352159453.8 | 58.99 | 0.00 | 0.00 |
May | 0.217276E+10 | -.181626E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -356496743.0 | 58.99 | 0.00 | 0.00 |
June | 0.198064E+10 | -.164086E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -339778568.1 | 58.99 | 0.00 | 0.00 |
July | 0.191023E+10 | -.156096E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -349277382.2 | 59.00 | 0.00 | 0.00 |
August | 0.195415E+10 | -.160533E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -348814327.5 | 58.99 | 0.00 | 0.00 |
September | 0.194205E+10 | -.160075E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -341303432.4 | 58.99 | 0.00 | 0.00 |
October | 0.212639E+10 | -.176387E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -362514902.1 | 58.99 | 0.00 | 0.00 |
November | 0.221402E+10 | -.185070E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -363323253.3 | 58.99 | 0.00 | 0.00 |
December | 0.245321E+10 | -.206166E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -391546454.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.263852E+11 | -.220550E+11 | 8760.00 | -.433020E+10 | 58.99 | |||||
Minimum of Months | 0.191023E+10 | -.214512E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -397944700.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.254193E+10 | -.156096E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -339778568.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.85 | 0.50 | 08-JAN-11:20 | 264.44 | 7.01 | 0.00 | 15.00 | 218.84 | 5.57 | 0.00 | 4.00 |
February | 263.00 | 0.84 | 0.50 | 09-FEB-13:20 | 285.41 | 6.96 | 0.00 | 35.83 | 233.52 | 5.42 | 0.00 | 13.00 |
March | 351.67 | 0.77 | 0.50 | 01-MAR-13:20 | 382.95 | 8.91 | 0.00 | 97.83 | 316.96 | 7.33 | 0.00 | 60.17 |
April | 369.33 | 0.73 | 0.50 | 01-APR-11:09 | 2610.78 | 10.12 | 0.00 | 145.67 | 2728.39 | 8.44 | 0.00 | 103.83 |
May | 407.00 | 0.71 | 0.50 | 01-MAY-09:20 | 474.26 | 11.91 | 0.00 | 171.00 | 398.86 | 10.19 | 0.00 | 116.33 |
June | 411.67 | 0.71 | 0.50 | 01-JUN-09:39 | 471.33 | 12.34 | 0.00 | 173.50 | 395.39 | 10.61 | 0.00 | 114.33 |
July | 411.00 | 0.71 | 0.50 | 01-JUL-09:20 | 483.09 | 12.27 | 0.00 | 183.50 | 405.55 | 10.60 | 0.00 | 128.17 |
August | 390.50 | 0.69 | 0.50 | 01-AUG-11:39 | 629.31 | 11.88 | 0.00 | 196.17 | 469.25 | 10.14 | 0.00 | 136.67 |
September | 298.50 | 0.72 | 0.50 | 01-SEP-09:00 | 3142.88 | 9.77 | 0.00 | 161.17 | 2200.34 | 8.13 | 0.00 | 80.00 |
October | 293.50 | 0.82 | 0.50 | 01-OCT-11:09 | 305.48 | 6.91 | 0.00 | 39.00 | 268.35 | 5.43 | 0.00 | 21.83 |
November | 299.00 | 0.82 | 0.50 | 02-NOV-10:00 | 311.90 | 7.35 | 0.00 | 14.50 | 626.88 | 5.89 | 0.00 | 35.67 |
December | 285.17 | 0.85 | 0.58 | 11-DEC-13:09 | 1344.06 | 6.94 | 0.00 | 44.00 | 205.12 | 5.47 | 0.00 | 0.00 |
Annual Sum or Average | 4071.00 | 0.76 | 881.00 | 9.70 | 0.00 | 1277.17 | 712.53 | 8.08 | 0.00 | 814.00 | ||
Minimum of Months | 263.00 | 0.69 | 0.50 | 264.44 | 6.91 | 0.00 | 14.50 | 205.12 | 5.42 | 0.00 | 0.00 | |
Maximum of Months | 411.67 | 0.85 | 0.58 | 3142.88 | 12.34 | 0.00 | 196.17 | 2728.39 | 10.61 | 0.00 | 136.67 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100928E+11 | 48052.38 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.573609E+10 | 48052.38 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700895E+09 | 43619.45 | 19-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100076E+09 | 22649.67 | 07-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 42400947.88 | 4308.69 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.830509E+09 | 48052.38 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439573E+10 | 48052.38 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218985E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100928E+11 | 48052.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365907E+11 | 213149.09 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.194825E+11 | 213149.09 | 03-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223067E+10 | 46321.00 | 20-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.287714E+09 | 33918.36 | 06-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.285021E+09 | 36852.59 | 26-OCT-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.375191E+10 | 128618.64 | 22-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168144E+11 | 213149.09 | 03-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794430E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365907E+11 | 213149.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292612E+10 | 29399.46 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169693E+10 | 29399.46 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189728E+09 | 17821.63 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53374114.12 | 8251.09 | 06-APR-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23490051.13 | 3039.44 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145833E+09 | 20784.99 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101902E+10 | 29399.46 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.605449E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292612E+10 | 29399.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447327E+10 | 23567.36 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267181E+10 | 23567.36 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444926E+09 | 23567.36 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111690E+09 | 15086.27 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76054297.44 | 4824.66 | 31-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.367246E+09 | 23567.36 | 21-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185261E+10 | 23567.36 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.999761E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447327E+10 | 23567.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.533788E+10 | 28928.74 | 02-JAN-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309942E+10 | 26559.75 | 08-FEB-17:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250874E+09 | 11630.83 | 22-MAR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 202777.02 | 181.40 | 26-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 362953.83 | 909.77 | 26-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.494498E+09 | 25616.26 | 21-NOV-16:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147316E+10 | 15745.81 | 17-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106564E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.533788E+10 | 28928.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.104319E+09 | 0.104319E+09 | 5045.02 | 28-FEB-15:10 | 5045.02 | 0.00 |
March | 0.00 | 0.00 | 0.106541E+10 | 0.823781E+09 | 11274.14 | 30-MAR-14:10 | 8765.85 | 0.00 |
April | 0.00 | 0.00 | 0.416619E+10 | 0.340065E+10 | 15528.78 | 19-APR-06:02 | 9510.82 | 0.00 |
May | 0.00 | 0.00 | 0.107800E+11 | 0.796411E+10 | 38691.72 | 26-MAY-06:02 | 17904.07 | 0.00 |
June | 0.00 | 0.00 | 0.203035E+11 | 0.148304E+11 | 39638.07 | 23-JUN-06:02 | 23441.46 | 0.00 |
July | 0.00 | 0.00 | 0.244802E+11 | 0.169414E+11 | 40162.58 | 30-JUL-08:62 | 20837.05 | 0.00 |
August | 0.00 | 0.00 | 0.266825E+11 | 0.181611E+11 | 40733.21 | 20-AUG-07:03 | 21814.59 | 0.00 |
September | 0.00 | 0.00 | 0.155398E+11 | 0.108295E+11 | 40489.52 | 17-SEP-08:62 | 20680.75 | 0.00 |
October | 0.00 | 0.00 | 0.449653E+10 | 0.313049E+10 | 39704.05 | 19-OCT-06:02 | 16275.16 | 0.00 |
November | 0.00 | 0.00 | 0.408801E+09 | 0.282018E+09 | 7494.46 | 05-NOV-15:00 | 5008.37 | 0.00 |
December | 0.00 | 0.00 | 14226507.96 | 10216791.78 | 1781.71 | 12-DEC-15:10 | 1322.32 | 0.00 |
Annual Sum or Average | 0.108041E+12 | 0.764780E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.266825E+11 | 0.181611E+11 | 40733.21 | 23441.46 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 998499.03 | 821601.71 | 975.02 | 31-JAN-15:10 | 805.45 | 0.00 |
February | 0.00 | 0.00 | 0.155849E+10 | 0.153054E+10 | 29971.07 | 28-FEB-15:10 | 29004.31 | 0.00 |
March | 0.00 | 0.00 | 0.895129E+10 | 0.672519E+10 | 175184.59 | 30-MAR-06:03 | 101252.67 | 0.00 |
April | 0.00 | 0.00 | 0.290878E+11 | 0.227928E+11 | 178518.31 | 23-APR-08:62 | 89630.54 | 0.00 |
May | 0.00 | 0.00 | 0.623757E+11 | 0.439565E+11 | 182316.39 | 31-MAY-06:02 | 91628.21 | 0.00 |
June | 0.00 | 0.00 | 0.102240E+12 | 0.694702E+11 | 184742.26 | 18-JUN-08:62 | 108620.22 | 0.00 |
July | 0.00 | 0.00 | 0.121642E+12 | 0.766490E+11 | 189949.05 | 30-JUL-08:62 | 96872.80 | 0.00 |
August | 0.00 | 0.00 | 0.130347E+12 | 0.798936E+11 | 188290.66 | 20-AUG-08:62 | 104184.06 | 0.00 |
September | 0.00 | 0.00 | 0.772200E+11 | 0.490256E+11 | 189772.01 | 17-SEP-08:62 | 98959.65 | 0.00 |
October | 0.00 | 0.00 | 0.265634E+11 | 0.178081E+11 | 186467.85 | 19-OCT-06:02 | 82235.13 | 0.00 |
November | 0.00 | 0.00 | 0.429001E+10 | 0.306617E+10 | 116156.59 | 04-NOV-06:03 | 62981.33 | 0.00 |
December | 0.00 | 0.00 | 0.447303E+09 | 0.290966E+09 | 21849.75 | 12-DEC-15:10 | 15456.01 | 0.00 |
Annual Sum or Average | 0.564724E+12 | 0.371210E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 998499.03 | 821601.71 | 975.02 | 805.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130347E+12 | 0.798936E+11 | 189949.05 | 108620.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 29127746.16 | 24249909.93 | 2274.74 | 31-JAN-15:10 | 2008.67 | 0.00 |
February | 0.00 | 0.00 | 0.664271E+09 | 0.661071E+09 | 7271.90 | 28-FEB-15:10 | 7271.90 | 0.00 |
March | 0.00 | 0.00 | 0.208564E+10 | 0.169012E+10 | 22786.94 | 31-MAR-06:02 | 13237.23 | 0.00 |
April | 0.00 | 0.00 | 0.460320E+10 | 0.381022E+10 | 22124.82 | 19-APR-06:02 | 13935.29 | 0.00 |
May | 0.00 | 0.00 | 0.879641E+10 | 0.663950E+10 | 23868.26 | 31-MAY-06:02 | 11665.78 | 0.00 |
June | 0.00 | 0.00 | 0.140856E+11 | 0.103544E+11 | 24555.08 | 26-JUN-05:03 | 15621.76 | 0.00 |
July | 0.00 | 0.00 | 0.169192E+11 | 0.117409E+11 | 24879.20 | 30-JUL-08:62 | 12758.98 | 0.00 |
August | 0.00 | 0.00 | 0.190327E+11 | 0.130987E+11 | 25284.23 | 20-AUG-07:03 | 13568.79 | 0.00 |
September | 0.00 | 0.00 | 0.125450E+11 | 0.898517E+10 | 24881.80 | 17-SEP-08:62 | 12947.69 | 0.00 |
October | 0.00 | 0.00 | 0.579309E+10 | 0.443872E+10 | 24504.99 | 19-OCT-06:02 | 10026.42 | 0.00 |
November | 0.00 | 0.00 | 0.196134E+10 | 0.160660E+10 | 11399.55 | 04-NOV-06:03 | 6257.02 | 0.00 |
December | 0.00 | 0.00 | 0.374084E+09 | 0.260116E+09 | 8496.16 | 12-DEC-14:00 | 6467.81 | 0.00 |
Annual Sum or Average | 0.868896E+11 | 0.633098E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 29127746.16 | 24249909.93 | 2274.74 | 2008.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190327E+11 | 0.130987E+11 | 25284.23 | 15621.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 404109.17 | 361275.29 | 188.52 | 31-JAN-15:00 | 170.47 | 0.00 |
February | 0.00 | 0.00 | 0.348460E+09 | 0.348353E+09 | 5575.27 | 28-FEB-15:10 | 5575.27 | 0.00 |
March | 0.00 | 0.00 | 0.106985E+10 | 0.861776E+09 | 18407.45 | 31-MAR-06:02 | 10442.79 | 0.00 |
April | 0.00 | 0.00 | 0.288580E+10 | 0.240788E+10 | 15259.68 | 19-APR-06:02 | 9361.25 | 0.00 |
May | 0.00 | 0.00 | 0.608075E+10 | 0.456173E+10 | 19310.16 | 26-MAY-06:02 | 8793.80 | 0.00 |
June | 0.00 | 0.00 | 0.113555E+11 | 0.816462E+10 | 19821.74 | 23-JUN-06:02 | 10687.31 | 0.00 |
July | 0.00 | 0.00 | 0.138222E+11 | 0.936498E+10 | 20179.53 | 30-JUL-08:62 | 9577.47 | 0.00 |
August | 0.00 | 0.00 | 0.158666E+11 | 0.105977E+11 | 20187.96 | 20-AUG-08:62 | 10070.22 | 0.00 |
September | 0.00 | 0.00 | 0.976716E+10 | 0.686553E+10 | 20232.45 | 17-SEP-08:62 | 9822.21 | 0.00 |
October | 0.00 | 0.00 | 0.389678E+10 | 0.292405E+10 | 19819.32 | 19-OCT-06:02 | 8010.02 | 0.00 |
November | 0.00 | 0.00 | 0.827798E+09 | 0.674031E+09 | 6885.23 | 05-NOV-13:30 | 4554.69 | 0.00 |
December | 0.00 | 0.00 | 0.124015E+09 | 87981263.95 | 5711.63 | 12-DEC-14:00 | 4042.93 | 0.00 |
Annual Sum or Average | 0.660453E+11 | 0.468590E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 404109.17 | 361275.29 | 188.52 | 170.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.158666E+11 | 0.105977E+11 | 20232.45 | 10687.31 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119981E+10 | 0.33 | 1263.89 | 01-JAN-16:51 | 0.94 |
February | 0.688153E+09 | 0.21 | 1263.89 | 01-FEB-08:63 | 0.94 |
March | 0.119109E+09 | 0.03 | 1263.89 | 06-MAR-08:07 | 0.94 |
April | 16683392.96 | 0.00 | 1263.89 | 06-APR-07:05 | 0.94 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 8164751.40 | 0.00 | 1263.89 | 13-OCT-07:09 | 0.94 |
November | 0.206343E+09 | 0.06 | 1263.89 | 07-NOV-08:08 | 0.94 |
December | 0.552669E+09 | 0.15 | 1263.89 | 01-DEC-08:70 | 0.94 |
Annual Sum or Average | 0.279094E+10 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119981E+10 | 0.33 | 1263.89 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152334E+10 | 0.38 | 1980.61 | 01-JAN-08:61 | 0.91 |
February | 0.129759E+10 | 0.36 | 1980.61 | 02-FEB-06:01 | 0.91 |
March | 0.130932E+10 | 0.34 | 1870.98 | 19-MAR-08:62 | 0.89 |
April | 0.124313E+10 | 0.33 | 1352.38 | 07-APR-06:03 | 0.76 |
May | 0.128273E+10 | 0.33 | 1980.61 | 07-MAY-08:62 | 0.90 |
June | 0.127534E+10 | 0.34 | 1980.61 | 01-JUN-06:02 | 0.90 |
July | 0.135461E+10 | 0.34 | 1980.61 | 01-JUL-06:02 | 0.90 |
August | 0.138818E+10 | 0.35 | 1980.61 | 01-AUG-06:02 | 0.89 |
September | 0.125358E+10 | 0.33 | 1980.61 | 01-SEP-06:02 | 0.90 |
October | 0.127114E+10 | 0.33 | 1980.61 | 11-OCT-06:02 | 0.90 |
November | 0.124408E+10 | 0.33 | 1980.61 | 22-NOV-06:01 | 0.91 |
December | 0.138101E+10 | 0.35 | 1980.61 | 01-DEC-06:01 | 0.91 |
Annual Sum or Average | 0.158240E+11 | 0.34 | |||
Minimum of Months | 0.124313E+10 | 0.33 | 1352.38 | 0.76 | |
Maximum of Months | 0.152334E+10 | 0.38 | 1980.61 | 0.91 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.892153E+10 | 0.57 | 11994.52 | 02-JAN-06:01 | 1.43 |
February | 0.763574E+10 | 0.55 | 11994.52 | 03-FEB-07:03 | 1.44 |
March | 0.790152E+10 | 0.53 | 11994.52 | 30-MAR-06:03 | 1.42 |
April | 0.753149E+10 | 0.52 | 11994.52 | 16-APR-08:62 | 1.42 |
May | 0.778483E+10 | 0.52 | 11994.52 | 03-MAY-06:03 | 1.41 |
June | 0.786527E+10 | 0.53 | 11994.52 | 01-JUN-06:02 | 1.42 |
July | 0.836946E+10 | 0.54 | 11994.52 | 01-JUL-06:02 | 1.41 |
August | 0.854850E+10 | 0.55 | 11994.52 | 01-AUG-06:02 | 1.41 |
September | 0.761806E+10 | 0.52 | 11994.52 | 01-SEP-06:02 | 1.41 |
October | 0.770759E+10 | 0.52 | 11994.52 | 02-OCT-06:03 | 1.41 |
November | 0.753690E+10 | 0.52 | 9140.46 | 22-NOV-07:03 | 1.26 |
December | 0.827108E+10 | 0.54 | 11994.52 | 03-DEC-08:61 | 1.44 |
Annual Sum or Average | 0.956920E+11 | 0.53 | |||
Minimum of Months | 0.753149E+10 | 0.52 | 9140.46 | 1.26 | |
Maximum of Months | 0.892153E+10 | 0.57 | 11994.52 | 1.44 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.827498E+09 | 0.36 | 1180.13 | 01-JAN-08:61 | 0.94 |
February | 0.728127E+09 | 0.36 | 1180.13 | 02-FEB-06:01 | 0.94 |
March | 0.774550E+09 | 0.35 | 1180.13 | 31-MAR-06:02 | 0.93 |
April | 0.740691E+09 | 0.34 | 1180.13 | 18-APR-06:02 | 0.93 |
May | 0.765176E+09 | 0.34 | 1180.13 | 06-MAY-06:02 | 0.93 |
June | 0.793862E+09 | 0.36 | 1180.13 | 01-JUN-06:02 | 0.93 |
July | 0.863900E+09 | 0.36 | 1180.13 | 01-JUL-06:02 | 0.93 |
August | 0.925540E+09 | 0.38 | 1180.13 | 01-AUG-06:02 | 0.93 |
September | 0.780717E+09 | 0.35 | 1180.13 | 01-SEP-06:02 | 0.93 |
October | 0.764246E+09 | 0.34 | 1180.13 | 02-OCT-06:03 | 0.93 |
November | 0.732549E+09 | 0.34 | 972.65 | 22-NOV-06:01 | 0.86 |
December | 0.782467E+09 | 0.35 | 1180.13 | 01-DEC-06:01 | 0.94 |
Annual Sum or Average | 0.947932E+10 | 0.35 | |||
Minimum of Months | 0.728127E+09 | 0.34 | 972.65 | 0.86 | |
Maximum of Months | 0.925540E+09 | 0.38 | 1180.13 | 0.94 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143600E+10 | 0.57 | 893.88 | 01-JAN-09:00 | 0.94 |
February | 0.130367E+10 | 0.58 | 893.88 | 01-FEB-08:40 | 0.94 |
March | 0.145774E+10 | 0.57 | 893.88 | 02-MAR-08:04 | 0.94 |
April | 0.139981E+10 | 0.57 | 893.88 | 04-APR-11:50 | 0.93 |
May | 0.144487E+10 | 0.56 | 893.88 | 11-MAY-13:00 | 0.94 |
June | 0.140947E+10 | 0.57 | 893.88 | 05-JUN-15:50 | 0.93 |
July | 0.143521E+10 | 0.56 | 893.88 | 01-JUL-13:35 | 0.93 |
August | 0.145774E+10 | 0.57 | 893.88 | 01-AUG-17:17 | 0.93 |
September | 0.139981E+10 | 0.56 | 893.88 | 05-SEP-05:30 | 0.93 |
October | 0.143199E+10 | 0.56 | 893.88 | 04-OCT-19:25 | 0.94 |
November | 0.138051E+10 | 0.56 | 893.88 | 01-NOV-19:30 | 0.93 |
December | 0.143541E+10 | 0.56 | 893.88 | 01-DEC-20:25 | 0.94 |
Annual Sum or Average | 0.169922E+11 | 0.56 | |||
Minimum of Months | 0.130367E+10 | 0.56 | 893.88 | 0.93 | |
Maximum of Months | 0.145774E+10 | 0.58 | 893.88 | 0.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.58 | 0.00 |
February | 0.65 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.12 | 0.00 |
July | 0.79 | 0.00 |
August | 0.12 | 0.00 |
September | 0.04 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.31 | 0.00 |
Annual Sum or Average | 3.62 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.58 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.31 | 25.84 |
March | 1.46 | 25.84 |
April | 1.33 | 25.84 |
May | 0.83 | 25.84 |
June | 0.21 | 20.67 |
July | 0.71 | 6.08 |
August | 0.12 | 0.00 |
September | 0.54 | 23.86 |
October | 1.72 | 25.84 |
November | 1.26 | 25.84 |
December | 0.21 | 25.84 |
Annual Sum or Average | 8.71 | 23.62 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.72 | 25.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.00 |
February | 0.27 | 0.00 |
March | 0.12 | 2.44 |
April | 0.04 | 2.44 |
May | 0.42 | 0.00 |
June | 1.10 | 0.00 |
July | 2.90 | 0.00 |
August | 1.12 | 0.00 |
September | 1.32 | 0.00 |
October | 0.69 | 1.17 |
November | 0.38 | 2.44 |
December | 0.38 | 2.44 |
Annual Sum or Average | 8.89 | 0.34 |
Minimum of Months | 0.04 | 0.00 |
Maximum of Months | 2.90 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.91 | 0.00 |
February | 0.65 | 0.31 |
March | 0.12 | 2.44 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.12 | 0.00 |
July | 0.88 | 0.00 |
August | 0.38 | 0.00 |
September | 0.12 | 0.00 |
October | 0.75 | 2.44 |
November | 0.54 | 2.44 |
December | 0.29 | 1.04 |
Annual Sum or Average | 4.77 | 0.83 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.91 | 2.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 9.13 | 0.00 |
February | 11.31 | 0.00 |
March | 5.66 | 0.00 |
April | 2.75 | 0.00 |
May | 3.14 | 0.00 |
June | 4.60 | 0.00 |
July | 4.72 | 0.00 |
August | 2.78 | 0.00 |
September | 2.71 | 0.00 |
October | 5.57 | 0.00 |
November | 6.91 | 0.00 |
December | 7.57 | 0.00 |
Annual Sum or Average | 66.84 | 0.00 |
Minimum of Months | 2.71 | 0.00 |
Maximum of Months | 11.31 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.152334E+10 | 0.126160E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132675E+10 | 0.717011E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159469E+10 | 0.876118E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.234903E+10 | 0.125095E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.402549E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.630129E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.734972E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.782997E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.504581E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.239716E+10 | 53001184.86 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.135272E+10 | 0.103814E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.138503E+10 | 0.549466E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.424810E+11 | 0.273731E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132675E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.782997E+10 | 0.126160E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.892184E+10 | 0.457384E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.811220E+10 | 0.243531E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.105177E+11 | 0.278834E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.159143E+11 | 0.359642E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.250975E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.356400E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.409768E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.430290E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.284034E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150654E+11 | 0.356277E+09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.880504E+10 | 0.468989E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.840658E+10 | 0.210180E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.248890E+12 | 0.993037E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.811220E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.430290E+11 | 0.457384E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.835358E+09 | 0.365765E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.896914E+09 | 0.212116E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.129684E+10 | 0.237160E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.189968E+10 | 66717642.65 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.292924E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.423475E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.496917E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.548203E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.374600E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.213308E+10 | 29362563.91 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.121803E+10 | 0.182291E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.875316E+09 | 0.127378E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.305164E+11 | 0.756812E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.835358E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.548203E+10 | 0.365765E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.143610E+10 | 0.559159E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.138259E+10 | 0.333977E+10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.169743E+10 | 0.556158E+09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.205148E+10 | 0.139613E+09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.277894E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.385673E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.440009E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.481761E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.344444E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.224839E+10 | 95067871.80 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.156512E+10 | 0.459058E+09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.146319E+10 | 0.231576E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.311421E+11 | 0.124970E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.138259E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.481761E+10 | 0.559159E+10 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152334E+10 | 0.00 | 0.100928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129759E+10 | 0.104319E+09 | 0.573609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130932E+10 | 0.106541E+10 | 0.700895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124313E+10 | 0.416619E+10 | 0.100076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128273E+10 | 0.107800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127534E+10 | 0.203035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135461E+10 | 0.244802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138818E+10 | 0.266825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125358E+10 | 0.155398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127114E+10 | 0.449653E+10 | 42400947.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124408E+10 | 0.408801E+09 | 0.830509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138101E+10 | 14226507.96 | 0.439573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158240E+11 | 0.108041E+12 | 0.218985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152334E+10 | 0.266825E+11 | 0.100928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.892153E+10 | 998499.03 | 0.365907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763574E+10 | 0.155849E+10 | 0.194825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790152E+10 | 0.895129E+10 | 0.223067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.753149E+10 | 0.290878E+11 | 0.287714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.778483E+10 | 0.623757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.786527E+10 | 0.102240E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.836946E+10 | 0.121642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.854850E+10 | 0.130347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.761806E+10 | 0.772200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770759E+10 | 0.265634E+11 | 0.285021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753690E+10 | 0.429001E+10 | 0.375191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827108E+10 | 0.447303E+09 | 0.168144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.956920E+11 | 0.564724E+12 | 0.794430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.753149E+10 | 998499.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.892153E+10 | 0.130347E+12 | 0.365907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.827498E+09 | 29127746.16 | 0.292612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728127E+09 | 0.664271E+09 | 0.169693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.774550E+09 | 0.208564E+10 | 0.189728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740691E+09 | 0.460320E+10 | 53374114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765176E+09 | 0.879641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.793862E+09 | 0.140856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.863900E+09 | 0.169192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.925540E+09 | 0.190327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.780717E+09 | 0.125450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764246E+09 | 0.579309E+10 | 23490051.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.732549E+09 | 0.196134E+10 | 0.145833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.782467E+09 | 0.374084E+09 | 0.101902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.947932E+10 | 0.868896E+11 | 0.605449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.728127E+09 | 29127746.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.925540E+09 | 0.190327E+11 | 0.292612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143600E+10 | 404109.17 | 0.447327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130367E+10 | 0.348460E+09 | 0.267181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145774E+10 | 0.106985E+10 | 0.444926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139981E+10 | 0.288580E+10 | 0.111690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144487E+10 | 0.608075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140947E+10 | 0.113555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143521E+10 | 0.138222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145774E+10 | 0.158666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139981E+10 | 0.976716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143199E+10 | 0.389678E+10 | 76054297.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138051E+10 | 0.827798E+09 | 0.367246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143541E+10 | 0.124015E+09 | 0.185261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169922E+11 | 0.660453E+11 | 0.999761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130367E+10 | 404109.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145774E+10 | 0.158666E+11 | 0.447327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.152334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129759E+10 | 0.00 | 0.00 | 0.00 | 29165216.31 | 0.00 | 0.717011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130932E+10 | 0.00 | 0.00 | 0.00 | 0.285363E+09 | 0.00 | 0.876118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124313E+10 | 0.00 | 0.00 | 0.00 | 0.110590E+10 | 0.00 | 0.125095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128273E+10 | 0.00 | 0.00 | 0.00 | 0.274276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.502595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135461E+10 | 0.00 | 0.00 | 0.00 | 0.599511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138818E+10 | 0.00 | 0.00 | 0.00 | 0.644179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125358E+10 | 0.00 | 0.00 | 0.00 | 0.379223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 0.112602E+10 | 0.00 | 53001184.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124408E+10 | 0.00 | 0.00 | 0.00 | 0.108641E+09 | 0.00 | 0.103814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138101E+10 | 0.00 | 0.00 | 0.00 | 4014965.96 | 0.00 | 0.549466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158240E+11 | 0.00 | 0.00 | 0.00 | 0.266570E+11 | 0.00 | 0.273731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152334E+10 | 0.00 | 0.00 | 0.00 | 0.644179E+10 | 0.00 | 0.126160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.892153E+10 | 0.00 | 0.00 | 0.00 | 315908.49 | 0.00 | 0.457384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763574E+10 | 0.00 | 0.00 | 0.00 | 0.476470E+09 | 0.00 | 0.243531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.790152E+10 | 0.00 | 0.00 | 0.00 | 0.261622E+10 | 0.00 | 0.278834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.753149E+10 | 0.00 | 0.00 | 0.00 | 0.838281E+10 | 0.00 | 0.359642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.778483E+10 | 0.00 | 0.00 | 0.00 | 0.173127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.786527E+10 | 0.00 | 0.00 | 0.00 | 0.277747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.836946E+10 | 0.00 | 0.00 | 0.00 | 0.326073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.854850E+10 | 0.00 | 0.00 | 0.00 | 0.344805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.761806E+10 | 0.00 | 0.00 | 0.00 | 0.207853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.770759E+10 | 0.00 | 0.00 | 0.00 | 0.735786E+10 | 0.00 | 0.356277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753690E+10 | 0.00 | 0.00 | 0.00 | 0.126814E+10 | 0.00 | 0.468989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827108E+10 | 0.00 | 0.00 | 0.00 | 0.135496E+09 | 0.00 | 0.210180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.956920E+11 | 0.00 | 0.00 | 0.00 | 0.153198E+12 | 0.00 | 0.993037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.753149E+10 | 0.00 | 0.00 | 0.00 | 315908.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.892153E+10 | 0.00 | 0.00 | 0.00 | 0.344805E+11 | 0.00 | 0.457384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.827498E+09 | 0.00 | 0.00 | 0.00 | 7860374.92 | 0.00 | 0.365765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.728127E+09 | 0.00 | 0.00 | 0.00 | 0.168786E+09 | 0.00 | 0.212116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.774550E+09 | 0.00 | 0.00 | 0.00 | 0.522288E+09 | 0.00 | 0.237160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740691E+09 | 0.00 | 0.00 | 0.00 | 0.115899E+10 | 0.00 | 66717642.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.765176E+09 | 0.00 | 0.00 | 0.00 | 0.216407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.793862E+09 | 0.00 | 0.00 | 0.00 | 0.344089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.863900E+09 | 0.00 | 0.00 | 0.00 | 0.410527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.925540E+09 | 0.00 | 0.00 | 0.00 | 0.455649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.780717E+09 | 0.00 | 0.00 | 0.00 | 0.296528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764246E+09 | 0.00 | 0.00 | 0.00 | 0.136883E+10 | 0.00 | 29362563.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.732549E+09 | 0.00 | 0.00 | 0.00 | 0.485483E+09 | 0.00 | 0.182291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.782467E+09 | 0.00 | 0.00 | 0.00 | 92848438.82 | 0.00 | 0.127378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.947932E+10 | 0.00 | 0.00 | 0.00 | 0.210371E+11 | 0.00 | 0.756812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.728127E+09 | 0.00 | 0.00 | 0.00 | 7860374.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.925540E+09 | 0.00 | 0.00 | 0.00 | 0.455649E+10 | 0.00 | 0.365765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143600E+10 | 0.00 | 0.00 | 0.00 | 99500.53 | 0.00 | 0.559159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130367E+10 | 0.00 | 0.00 | 0.00 | 78920958.45 | 0.00 | 0.333977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145774E+10 | 0.00 | 0.00 | 0.00 | 0.239691E+09 | 0.00 | 0.556158E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139981E+10 | 0.00 | 0.00 | 0.00 | 0.651664E+09 | 0.00 | 0.139613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144487E+10 | 0.00 | 0.00 | 0.00 | 0.133407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140947E+10 | 0.00 | 0.00 | 0.00 | 0.244726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143521E+10 | 0.00 | 0.00 | 0.00 | 0.296488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145774E+10 | 0.00 | 0.00 | 0.00 | 0.335987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139981E+10 | 0.00 | 0.00 | 0.00 | 0.204463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143199E+10 | 0.00 | 0.00 | 0.00 | 0.816394E+09 | 0.00 | 95067871.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138051E+10 | 0.00 | 0.00 | 0.00 | 0.184610E+09 | 0.00 | 0.459058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143541E+10 | 0.00 | 0.00 | 0.00 | 27786967.33 | 0.00 | 0.231576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169922E+11 | 0.00 | 0.00 | 0.00 | 0.141499E+11 | 0.00 | 0.124970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.130367E+10 | 0.00 | 0.00 | 0.00 | 99500.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145774E+10 | 0.00 | 0.00 | 0.00 | 0.335987E+10 | 0.00 | 0.559159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627307E+10 | 0.00 | 0.00 | 0.20 |
February | 0.213282E+10 | 0.00 | 0.00 | 265995.63 | 464892.23 | 0.339255E+10 | 0.275604E+09 | 0.00 | 0.23 |
March | 0.316082E+10 | 30849569.09 | 0.00 | 1956545.26 | 0.00 | 0.356164E+09 | 0.159335E+10 | 0.00 | 0.30 |
April | 0.121892E+10 | 0.107133E+09 | 0.00 | 4251576.48 | 2299142.74 | 57054079.64 | 0.222971E+10 | 0.00 | 0.40 |
May | 0.213905E+09 | 0.123715E+10 | 0.00 | 5341144.78 | 610867.62 | 0.00 | 0.181512E+10 | 0.00 | 0.38 |
June | 18479889.73 | 0.449719E+10 | 0.00 | 3279806.71 | 9371503.89 | 0.00 | 0.486651E+09 | 0.00 | 0.27 |
July | 2210152.86 | 0.642439E+10 | 0.00 | 1648372.89 | 18271774.38 | 0.00 | 0.238248E+09 | 0.00 | 0.23 |
August | 2341587.48 | 0.721551E+10 | 0.00 | 690923.94 | 26108065.75 | 0.00 | 45459072.39 | 0.00 | 0.22 |
September | 48475278.66 | 0.305802E+10 | 0.00 | 4574154.57 | 11697787.16 | 0.00 | 0.129559E+10 | 0.00 | 0.32 |
October | 0.169212E+10 | 0.552624E+09 | 0.00 | 5837345.74 | 910992.80 | 22972191.70 | 0.321422E+10 | 0.00 | 0.37 |
November | 0.316773E+10 | 3224741.41 | 4259598.34 | 2293061.15 | 16376310.59 | 0.387805E+09 | 0.204187E+10 | 3699.68 | 0.30 |
December | 0.342155E+10 | 0.00 | 0.00 | 269408.66 | 0.00 | 0.257028E+10 | 0.303660E+09 | 0.00 | 0.21 |
Annual Sum or Average | 0.165687E+11 | 0.231261E+11 | 4259598.34 | 30408335.80 | 86111337.15 | 0.130599E+11 | 0.135395E+11 | 3699.68 | 0.29 |
Minimum of Months | 2210152.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Maximum of Months | 0.342155E+10 | 0.721551E+10 | 4259598.34 | 5837345.74 | 26108065.75 | 0.627307E+10 | 0.321422E+10 | 3699.68 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.456184E+11 | 0.00 | 0.00 | 179305.86 | 0.00 | 0.138978E+11 | 0.437246E+09 | 0.00 | 0.39 |
February | 0.339487E+11 | 0.00 | 0.00 | 5055054.23 | 0.00 | 0.665941E+10 | 0.382072E+10 | 0.00 | 0.42 |
March | 0.227912E+11 | 0.540777E+09 | 0.00 | 18972320.48 | 146770.56 | 0.137033E+09 | 0.123328E+11 | 0.00 | 0.48 |
April | 0.788005E+10 | 0.223291E+10 | 0.00 | 26569680.51 | 86346.82 | 0.00 | 0.123208E+11 | 0.00 | 0.50 |
May | 0.143084E+10 | 0.124888E+11 | 0.00 | 29229687.09 | 22582876.65 | 0.00 | 0.646877E+10 | 0.00 | 0.48 |
June | 0.189974E+09 | 0.369646E+11 | 0.00 | 11371791.22 | 0.212275E+09 | 0.00 | 0.174642E+10 | 0.00 | 0.43 |
July | 16686048.06 | 0.510698E+11 | 0.00 | 2991947.14 | 0.317904E+09 | 0.00 | 0.449682E+09 | 0.00 | 0.40 |
August | 10797244.90 | 0.568331E+11 | 0.00 | 1766400.63 | 0.330534E+09 | 0.00 | 89519544.84 | 0.00 | 0.41 |
September | 0.598520E+09 | 0.242643E+11 | 0.00 | 18408853.53 | 0.156155E+09 | 0.00 | 0.472715E+10 | 0.00 | 0.46 |
October | 0.127651E+11 | 0.498539E+10 | 0.00 | 31720737.24 | 8908633.44 | 0.00 | 0.147037E+11 | 0.00 | 0.49 |
November | 0.251752E+11 | 63185556.78 | 0.00 | 15749953.78 | 65716018.41 | 0.868745E+09 | 0.108746E+11 | 0.00 | 0.47 |
December | 0.404108E+11 | 0.00 | 0.00 | 2228661.57 | 0.00 | 0.528820E+10 | 0.196489E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.190836E+12 | 0.189443E+12 | 0.00 | 0.164244E+09 | 0.111431E+10 | 0.268512E+11 | 0.699362E+11 | 0.00 | 0.45 |
Minimum of Months | 10797244.90 | 0.00 | 0.00 | 179305.86 | 0.00 | 0.00 | 89519544.84 | 0.00 | 0.39 |
Maximum of Months | 0.456184E+11 | 0.568331E+11 | 0.00 | 31720737.24 | 0.330534E+09 | 0.138978E+11 | 0.147037E+11 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401776E+10 | 0.00 | 0.00 | 703268.74 | 0.00 | 0.128257E+10 | 0.611510E+09 | 0.00 | 0.42 |
February | 0.269895E+10 | 48684.73 | 0.00 | 2989855.20 | 0.00 | 0.670314E+09 | 0.130675E+10 | 0.00 | 0.54 |
March | 0.125420E+10 | 93579220.21 | 0.00 | 6073453.10 | 0.00 | 56257553.64 | 0.295147E+10 | 0.00 | 0.68 |
April | 0.550183E+09 | 0.324246E+09 | 0.00 | 4398364.08 | 0.00 | 14599780.18 | 0.179056E+10 | 0.00 | 0.65 |
May | 0.122511E+09 | 0.143823E+10 | 0.00 | 3742881.71 | 842387.81 | 0.00 | 0.896713E+09 | 0.00 | 0.59 |
June | 17996596.60 | 0.384572E+10 | 0.00 | 1716230.13 | 4155289.39 | 0.00 | 0.235109E+09 | 0.00 | 0.47 |
July | 845413.92 | 0.537665E+10 | 0.00 | 553772.60 | 8427855.88 | 0.00 | 60462200.75 | 0.00 | 0.42 |
August | 213699.70 | 0.610047E+10 | 0.00 | 273625.33 | 8155926.06 | 0.00 | 25150644.01 | 0.00 | 0.41 |
September | 23181672.39 | 0.290467E+10 | 0.00 | 2891649.15 | 4022658.85 | 0.00 | 0.630022E+09 | 0.00 | 0.52 |
October | 0.691777E+09 | 0.739741E+09 | 0.00 | 8786354.24 | 79984.25 | 674665.83 | 0.278457E+10 | 0.00 | 0.70 |
November | 0.141619E+10 | 61256705.57 | 0.00 | 7679602.98 | 2346773.32 | 48509993.09 | 0.309258E+10 | 0.00 | 0.67 |
December | 0.287004E+10 | 2832846.20 | 0.00 | 3016448.97 | 0.00 | 0.428970E+09 | 0.189512E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.136638E+11 | 0.208875E+11 | 0.00 | 42825506.22 | 28030875.54 | 0.250189E+10 | 0.162800E+11 | 0.00 | 0.55 |
Minimum of Months | 213699.70 | 0.00 | 0.00 | 273625.33 | 0.00 | 0.00 | 25150644.01 | 0.00 | 0.41 |
Maximum of Months | 0.401776E+10 | 0.610047E+10 | 0.00 | 8786354.24 | 8427855.88 | 0.128257E+10 | 0.309258E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250543E+10 | 0.00 | 0.00 | 88233.63 | 0.00 | 0.296701E+10 | 0.178132E+09 | 0.00 | 0.40 |
February | 0.196150E+10 | 73872.57 | 0.00 | 1222557.27 | 0.00 | 0.168898E+10 | 0.692539E+09 | 0.00 | 0.51 |
March | 0.169071E+10 | 58437223.41 | 0.00 | 2329740.10 | 0.00 | 0.303768E+09 | 0.170931E+10 | 0.00 | 0.62 |
April | 0.860978E+09 | 0.180217E+09 | 0.00 | 1898523.11 | 303839.20 | 68442940.25 | 0.119013E+10 | 0.00 | 0.65 |
May | 0.217861E+09 | 0.105184E+10 | 0.00 | 2185106.97 | 473080.66 | 0.00 | 0.952137E+09 | 0.00 | 0.63 |
June | 47061884.74 | 0.337227E+10 | 0.00 | 1261417.67 | 7697733.29 | 0.00 | 0.219946E+09 | 0.00 | 0.49 |
July | 3497396.48 | 0.476271E+10 | 0.00 | 680521.33 | 13979230.04 | 0.00 | 0.198866E+09 | 0.00 | 0.44 |
August | 4275920.21 | 0.548028E+10 | 0.00 | 345713.21 | 6676340.09 | 0.00 | 38612669.72 | 0.00 | 0.42 |
September | 75086651.17 | 0.243530E+10 | 0.00 | 1957559.33 | 6955414.59 | 0.00 | 0.672112E+09 | 0.00 | 0.53 |
October | 0.107765E+10 | 0.545806E+09 | 0.00 | 5055747.57 | 113512.54 | 47335428.22 | 0.214108E+10 | 0.00 | 0.70 |
November | 0.195499E+10 | 17693526.67 | 0.00 | 3563651.61 | 3330418.32 | 0.140406E+09 | 0.206909E+10 | 0.00 | 0.65 |
December | 0.276735E+10 | 0.00 | 0.00 | 841798.95 | 0.00 | 0.117791E+10 | 0.760661E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.131664E+11 | 0.179046E+11 | 0.00 | 21430570.75 | 39529568.73 | 0.639386E+10 | 0.108226E+11 | 0.00 | 0.54 |
Minimum of Months | 3497396.48 | 0.00 | 0.00 | 88233.63 | 0.00 | 0.00 | 38612669.72 | 0.00 | 0.40 |
Maximum of Months | 0.276735E+10 | 0.548028E+10 | 0.00 | 5055747.57 | 13979230.04 | 0.296701E+10 | 0.214108E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |